HOTEL KANATA 160 HEARST WAY KANATA, ONTARIO SERVICING REPORT. Prepared for: David Johnston Architect. Prepared By:
|
|
- Berniece Hawkins
- 6 years ago
- Views:
Transcription
1 HOTEL KANATA 160 HEARST WAY KANATA, ONTARIO SERVICING REPORT Prepared for: David Johnston Architect Prepared By: BaseTech Consulting Inc. 309 Roywood Crescent Newmarket, Ontario L3Y 1A6 BCI Project No June, 2015
2 TABLE OF CONTENTS Page No. 1. INTRODUCTION SITE DESCRIPTION WATER DISTRIBUTION AND FIRE PROTECTION SANITARY SERVICING STORMWATER MANAGEMENT MAJOR FLOW ROUTE CONVEYANCE QUALITY CONTROL SEDIMENTATION AND EROSION CONTROL WATER BALANCE SUMMARY... 6 APPENDIX 1 APPENDIX 2 APPENDIX 3 WATER DISTRIBUTION CALCULATIONS SANITARY SEWAGE CALCULATIONS STORMWATER MANAGEMENT CORRESPONDENCE
3 HOTEL KANATA STORMWATER MANAGEMENT REPORT June, INTRODUCTION The site is located at 160 Hearst Way in Kanata as shown on the Site Plan prepared by David Johnston Architect. It is proposed to construct a three storey hotel with associated access and parking on the site with access to Hearst Way. The Report describes how the proposed development will be serviced in compliance with the requirements of the City of Ottawa. The Report has used the following documentation in its preparation: 1. Site Plan prepared by David Johnston Architect. 2. The current City of Ottawa Design Guidelines and Drawings. 3. The current Missippi Valley Conservation Authority Guidelines. 4. Stormwater Management Planning and Design Manual by the Ministry of the Environment, dated March SITE DESCRIPTION The site measures ha. and is vacant at present. Drainage of the site is via overland flow to the north and east. The existing municipal services are available in Hearst Way: 450mm diameter sanitary sewer 1200mm diameter storm sewer 300mm diameter watermain 3. WATER DISTRIBUTION AND FIRE PROTECTION The proposed hotel will require sprinkler protection and so the site will be serviced with a 150mm diameter PVC water service. The service will be split at the lot line to provide a 150mm diameter Fire Main and a 100mm diameter Domestic Service. A private hydrant will not be required as there is an existing hydrant directly across Hearst Way approximately 70m from the building entrance. BaseTech Consulting Inc. Consulting Engineers 1
4 HOTEL KANATA STORMWATER MANAGEMENT REPORT June, 2015 Domestic water demands for the proposed development have been calculated in accordance with Section 3.28 of the City of Ottawa Water Distribution Guidelines and the results are summarised below. Detailed calculations are shown in Appendix 1. Average Day Demand = l/sec. Maximum Daily Demand = 0.234l/sec. Peak Hour Demand = 0.421l/sec. The Fire Flow Demand has been estimated at 234 l/sec. based on the Fire Underwriter s Survey calculation (see Appendix 1). The site has been analyzed using EPANET based on the boundary conditions provided by the City of Ottawa. A summary of the results is shown below and detailed output results are shown in Appendix 1. Table 3.1 Summary of Allowable and Anticipated Water Pressures Condition Allowable per City EPANET model results guidelines Maximum Day + Fire Flow Greater than 20psi psi Peak Hour 40 80psi 86.8psi* Average Day Not greater than 80psi 97.9psi* It is recommended that a pressure reducing valve is installed. 4. SANITARY SERVICING It is proposed to service the proposed development with a 200mm diameter sanitary service connecting to the existing sewer in Hearst Way. The anticipated sanitary flows have been calculated using the City of Ottawa Sewer Design Guidelines 2012 and detailed calculations are shown in Appendix 2. A summary of the anticipated flows are as follows: Average Daily Flow = 0.156l/sec. Peak Daily Flow = 0.234l/sec. Infiltration = 0.17l/sec. Total Peak Design Flow = 0.404l/sec. BaseTech Consulting Inc. Consulting Engineers 2
5 HOTEL KANATA STORMWATER MANAGEMENT REPORT June, 2015 It was not possible to obtain sanitary sewer design sheets for the sewer from the City. However, we did obtain a copy of the Sanitary Drainage drawing for the area and, based on the information on the drawing, calculated that the allowable Average Daily Flow from the site is 0.25l/sec. which is greater than the actual estimated flow. Details of the allowable flow calculations and Sanitary Drainage drawing are shown in Appendix 2. Therefore, the existing sanitary sewer has sufficient capacity to accommodate the proposed development. 5. STORMWATER MANAGEMENT The site is within the Kanata Town Centre, Stage A area which allows for a pre-development runoff coefficient of 0.7 and a time of concentration of 20 minutes. The City of Ottawa requires that post-development run-off shall match the pre-development runoff for the year storm events based on a post-development time of concentration of 10 minutes. Any excess runoff will be retained on site and discharged at pre-development rates so the there is no impact on the existing stormwater management regime. A separate Stormwater Management Report has been prepared for the proposed development with rainfall intensities based on the City of Ottawa Rainfall Intensity-Duration-Frequency Curves as defined by the following equation and values: I = A mm/m (T d +C) B Storm A B C 2 year year year year year year and T d = duration (min.) BaseTech Consulting Inc. Consulting Engineers 3
6 HOTEL KANATA STORMWATER MANAGEMENT REPORT June, 2015 Calculation of the post-development runoff coefficients is based on the following impermeability factors: 2 10 Year 25 Year 50 Year 100 Year Buildings Paving Gravel Grass/Landscape The runoff coefficients for the lower figures have been increased for the 25, 50 and 100 year storms by 10%, 20% and 25% respectively as recommended by MTO Design Chart Discharges are calculated using the formula Q = 2.78C*I*A where Q = discharge (l/sec) A = area (ha) C = impermeability factor I = rainfall intensity (mm/hr) Drainage from the site will be controlled using an orifice tube at the outlet from the site. The discharge through the orifice tube will be controlled to the 2 year pre-development flow. Based on a time of concentration of 20 minutes the 2 year pre-development flow will be; Q Pre2 = 2.78 x x 0.70 x = 61.40l/sec. The 100 year post-development flow, based on a 10 minute time of concentration, will be Q Post100 = 2.78 x x 0.68 x = l/sec. The retention volume will be; V 100 = ( ) x 10 x = 85.98m 3 BaseTech Consulting Inc. Consulting Engineers 4
7 HOTEL KANATA STORMWATER MANAGEMENT REPORT June, 2015 This was carried out for the other storms and the retention volumes are shown in Table 4.1. TABLE 4.1 STORM PRE-DEVELOPMENT FLOW (l/sec.) RETENTION VOLUME (cu.m.) 2 Year Year Year Year Year Year Copies of correspondence with the City of Ottawa and the Mississippi Valley Conservation Authority are shown in Appendix 3. The Ministry of Environment and Climate Change were contacted but no responses were received. 6. MAJOR FLOW ROUTE The major flow route will continue to be towards the northeast corner of the site. 7. CONVEYANCE The development will be serviced by a catchbasin and storm sewer system connecting to the existing 1200 mm diameter storm sewer in Hearst Way 8. QUALITY CONTROL The Mississippi Valley Conservation Authority requires that all parking and access areas be provided with a facility to prevent fuel spills and sediment from entering the storm system. Therefore, an oil/grit separator will be provided to control any spillages/debris in the run-off. This should be designed to remove at least 70% of suspended solids from the runoff. BaseTech Consulting Inc. Consulting Engineers 5
8
9 APPENDIX 1 WATER DISTRIBUTION CALCULATIONS
10 WATER DISTRIBUTION CALCULATIONS AVERAGE DAILY DEMAND = 225l/bed space./day = 225 x 60/24/60/60 = 0.156l/sec. MAXIMUM DAILY DEMAND PEAKING FACTOR = 1.5 X Average Daily Demand MAXIMUM DAILY DEMAND = X 1.5 = 0.234l/sec. PEAK HOUR DEMAND FACTOR = 1.8 x Maximum Daily Demand PEAK HOUR DEMAND = X 1.8 = 0.421l/sec. FIRE FLOW CALCULATION F = 220C A Construction Coefficient = 1.5 (Wood Frame Construction) Sprinkler Protection = -30% (Full Sprinkler Protection) Combustibility = 0% (Combustible) No. of Storeys = 3 Gross Floor Area = m 2 Fire Flow, F = 220 x = 17,467l/min. Sprinkler Protection = -30% F = 12,227l/min Exposure Distances: N = 50m+ 0% S = 46m 5% E = 34m 5% W = 47m 5% Total % = 15% F = 12,227 x 1.15 = 14,061l/min. TOITAL FIRE FLOW REQUIRED = 14,061l/min. = 234l/sec.
11 Hunt Club Road, #300 Ottawa, Ontario, K1V 0Y3 Tel: (613) Fax: (613) Website: MEMO TO: FROM: Peter Feherty, M.Sc., P.Eng Guy Somers, P.Eng DATE: June 23, 2015 COPIES: SUBJECT: Kanata Hotel 160 Hearst Way Hydraulic Analysis The purpose of this memo is to provide a hydraulic analysis of the proposed water service connection to the subject development in support of a site plan approval as per the City of Ottawa requirements. The below summary shall be included under the watermain design section of the overall site servicing report. The subject site consists of a three storey hotel located in the southwest quadrant of Highway 417 and Eagleson Road, in the City of Ottawa. The services in this area lie within the City of Ottawa s 3W pressure zone. Ground elevations of the site are approximately 94 m. The hydraulic grade lines (HGL) provided by the City vary between 143 m m under normal operating conditions. The proposed development will be serviced by a 150 mm diameter service lateral splitting into a 100mm diameter PVC domestic lateral and a 150mm diameter firemain at the property line, off the existing 300 mm diameter municipal main located on Hearst Way. The proposed building will be fully sprinklered and an existing fire hydrant is located across the street within 50 m of an unobstructed path of travel from the main building entrance. As provided, the domestic and the fire flow demands from the development were determined in accordance with Section 4.28 of the City of Ottawa Water Distribution Guidelines and Fire Underwriter s Survey, respectively, and are summarized below: Average Day Demand L/s Maximum Daily Demand L/s Peak Hour Demand L/s Fire Flow 234 L/s The site has been analyzed to ensure all the City of Ottawa minimum criteria for water pressures are met for the three conditions; maximum day + fire flow, peak hour and average day demand. The analysis was carried out using EPANET hydraulic and water quality analysis based on the boundary conditions provided by the City of Ottawa. The detailed output results are attached as an enclosure to this memo.
12 Case 1: Maximum day plus fire flow According to section of the City of Ottawa Design Guidelines, during periods of the maximum day and fire flow demand, the residual pressure at any point in the distribution system shall not be less than 140 kpa (20 psi). With respect to a maximum daily demand of L/s and fire flow of 234 L/s for the proposed building, the model indicated the residual pressure in the system varied between 52.8 psi and 69 psi. Since the expected pressures under load conditions are greater than 20 psi, this site can be fully serviced by the proposed service connection and the existing municipal watermain along Hearst Way. The pressure drop in the pipe was acceptable and was within the City of Ottawa s minimum pressure requirements. Case 2: Peak hour demand According to section of the City of Ottawa Design Guidelines, the distribution system shall be sized so the under maximum hourly demand conditions the pressure are not less than 276 kpa (40 psi) and the maximum pressure at any point in the system shall not be greater than 80 psi in accordance with section With respect to a peak hour demand of L/s for the proposed building, the model indicated the residual pressure of 86.8 psi at the proposed development. Since the expected pressure was greater than 80 psi at the proposed development, it is recommended that a pressure reducing valve (PRV) to be installed on site. Case 3: Average day demand Maximum HGL According to section of the City of Ottawa Design Guidelines, the maximum pressure at any point in the distribution system in occupied area shall not exceed 552 kpa (80 psi). With respect to an average day demand of L/s for the proposed building, the model indicated the residual pressure of 97.9 psi at the building. However, since the residual pressure is greater than 80 psi, a PRV is recommended to be installed on site. The following options for PRV installation are preferred by the City of Ottawa: as a central unit, to be located in a chamber or facility, or to be installed immediately downstream of the isolation valve in the building, located downstream of the meter so it is owner maintained
13 Therefore, in view of the above, the proposed development is located in an area of the City s water distribution system that has sufficient capacity to provide both the required domestic and fire flows. The water services designed should be adequate enough to meet both the domestic and firefighting demands of the proposed development. Prepared by: Reviewed by: David Grinchpoun, EIT Ishaque Jafferjee, P.Eng. Enclosures (2) Enclosures: EPANET Output Reports Boundary Conditions from the City of Ottawa
14 Page 1 22/06/2015 3:14:36 PM ********************************************************************** * E P A N E T * * Hydraulic and Water Quality * * Analysis for Pipe Networks * * Version 2.0 * ********************************************************************** Input File: 160Hearst Case 1.NET Link - Node Table: Link Start End Length Diameter ID Node Node m mm 2 FH BLDG R R Node Results: Node Demand Head Pressure Quality ID LPS m m BLDG FH R Reservoir R Reservoir Link Results: Link Flow VelocityUnit Headloss Status ID LPS m/s m/km Open Open Open Open Open
15 Page 1 22/06/2015 2:42:11 PM ********************************************************************** * E P A N E T * * Hydraulic and Water Quality * * Analysis for Pipe Networks * * Version 2.0 * ********************************************************************** Input File: 160Hearst Case 2.NET Link - Node Table: Link Start End Length Diameter ID Node Node m mm 2 FH BLDG R R Node Results: Node Demand Head Pressure Quality ID LPS m m BLDG FH R Reservoir R Reservoir Link Results: Link Flow VelocityUnit Headloss Status ID LPS m/s m/km Open Open Open Open Open
16 Page 1 22/06/2015 3:19:57 PM ********************************************************************** * E P A N E T * * Hydraulic and Water Quality * * Analysis for Pipe Networks * * Version 2.0 * ********************************************************************** Input File: 160Hearst Case 3.NET Link - Node Table: Link Start End Length Diameter ID Node Node m mm 2 FH BLDG R R Node Results: Node Demand Head Pressure Quality ID LPS m m BLDG FH R Reservoir R Reservoir Link Results: Link Flow VelocityUnit Headloss Status ID LPS m/s m/km Open Open Open Open Open
17 Information Provided: Date provided: 01 June 2015 Boundary Conditions at 160 Hearst Way Criteria Average Demand Maximum Daily Demand Peak Hourly Demand Fire Flow Demand 234 Maximum Daily + Fire Flow Demand Demand (L/s) Location:
18 Results Connection: Criteria Head (m) Pressure (psi) Max HGL PKHR MXDY + Fire Flow (234 L/s) Considerations 1. According to the City of Ottawa Water Design Guidelines as well as the Ontario Building Code, the maximum pressure at any point within a distribution system shall not exceed 80 psi in occupied areas. Measures should be taken to try to reduce the residual pressure below 80 psi without the use of special pressure control equipment. In circumstances where the residual pressure cannot be reduced below 80 psi without the use of pressure control equipment, a pressure reducing valve (PRV) should be installed at site. Disclaimer The boundary condition information is based on current operation of the city water distribution system. The computer model simulation is based on the best information available at the time. The operation of the water distribution system can change on a regular basis, resulting in a variation in boundary conditions. The physical properties of watermains deteriorate over time, as such must be assumed in the absence of actual field test data. The variation in physical watermain properties can therefore alter the results of the computer model simulation. Fire Flow analysis is a reflection of available flow in the watermain; there may be additional restrictions that occur between the watermain and the hydrant that the model cannot take into account.
19 APPENDIX 2 SANITARY SEWAGE CALCULATIONS
20 SANITARY SEWAGE FLOW CALCULATIONS AVERAGE DAILY FLOW = 225l/bed space./day = 225 x 60/24/60/60 = 0.156l/sec. PEAK DAILY FLOW PEAKING FACTOR = 1.5 X Average Daily Flow PEAK DAILY FLOW = X 1.5 = 0.234l/sec. INFILTRATION FLOW = 0.28 X Lot Area = 0.28 x = 0.17l/sec. TOTAL PEAK DESIGN FLOW = = 0.404l/sec. ALLOWABLE SANITARY FLOW BASED ON KANATA TOWN CENTRE SANITARY DRAINAGE PLAN The Sanitary Drainage Plan for the Campau Corporation, Kanata Town Centre, Stage A shows a proposed population of 800 persons for the section of sewer servicing the site (see attached). The drainage area for this proposed population is approximately 7.8 hectares. This equates to 102 persons/hectare. The area of the site is hectares or a population of b 62 persons. The average daily flow calculations are based on a figure of 350 l/c/day. Therefore the allowable Average Daily Flow from the site will be: ALLOWABLE AVERAGE DAILY FLOW = 350 x 62/24/60/60 = 0.25 l/sec. This is greater than the anticipated Average Daily Flow.
21
22 APPENDIX 3 STORMWATER MANAGEMENT CORRESPONDENCE
23
24
25
26
27
28
SERVICING BRIEF & STORMWATER MANAGEMENT REPORT Colonial Road Sarsfield (Ottawa), Ontario. Report No June 15, 2017
SERVICING BRIEF & STORMWATER MANAGEMENT REPORT 2980 Colonial Road Sarsfield (Ottawa), Ontario Report No. 16033 June 15, 2017 D. B. G R A Y E N G I N E E R I N G I N C. Stormwater Management - Grading &
More informationJp2g Consultants Inc.
Jp2g Consultants Inc. ENGINEERS PLANNERS PROJECT MANAGERS 1150 Morrison Drive, Suite 410 Ottawa, ON K2H 8S9 T 613-828-7800, F 613-828-2600, www.jp2g.com September 20, 2018 City of Ottawa Development Review
More information3301 East 120 th Avenue Assited Living & Memory Care
UTILITY REPORT FOR 3301 East 120 th Avenue Assited Living & Memory Care 1 st Submittal January 23, 2016 2 nd Submittal March 04, 2016 Prepared for: 3301 E. 120 th Ave, LLC. 8200 E. Maplewood Ave., Suite
More informationD. B. G R A Y E N G I N E E R I N G I N C.
STORMWATER MANAGEMENT REPORT 948 Hunt lub Road Ottawa, Ontario Report No. 12020-SWM August 27, 2012 Revised April 21, 2014 Revised December 9, 2014 Revised April 14, 2015 D. B. G R A Y E N G I N E E R
More informationEastlake Assited Living & Memory Care
UTILITY REPORT FOR Eastlake Assited Living & Memory Care 1 st Submittal January 23, 2016 2 nd Submittal March 04, 2016 June 7, 2016 Final Submittal August 08, 2016 Prepared for: 3301 E. 120 th Ave, LLC.
More informationUTILITY REPORT FOR THORNTON SELF STORAGE THORNTON, COLORADO
UTILITY REPORT FOR THORNTON SELF STORAGE THORNTON, COLORADO Prepared by: Bowman Consulting 63 Park Point Dr. Suite 1 Golden, CO 841 (33)-81-29 June 29, 215 Revised August 14, 215 Revised September 3, 215
More informationFUNCTIONAL SERVICING REPORT AND SWM REPORT
FUNCTIONAL SERVICING REPORT AND SWM REPORT 104 WHITE CRESCENT CITY OF BARRIE, COUNTY OF SIMCOE December 2018 18058 TABLE OF CONTENTS 1. INTRODUCTION... 4 2. SUPPORTING DOCUMENTS... 4 3. DESIGN POPULATION...
More informationWELCOME Lake Wabukayne OPEN HOUSE
WELCOME Lake Wabukayne Sediment Removal Project OPEN HOUSE We are here to: Update you, the community, on recent developments and activities at Lake Wabukayne Present the preferred alternative and receive
More informationVillages at Riverdale Thornton, CO
FINAL UTILITY REPORT Villages at Riverdale Thornton, CO October 14, 216 Revised: March 29, 217 JN: 1539 Prepared for: PCS Group, Inc. 11 16 th Street #3 B-18 Denver, CO 8265 P: 33.531.495 Prepared by:
More informationReference: Addendum#2 - Proposed Commercial Development, Terry Fox Drive at Fernbank Road, City of Ottawa, Serviceability Study, September 26, 2011
400-1331 Clyde Avenue Ottawa ON K2C 3G4 Tel: (613) 722-4420 Fax: (613) 722-2799 February 14, 2014 File: 160400812 Attention: Patricia McCann-MacMillan Planning and Infrastructure Portfolio Planning & Growth
More informationSTORMWATER REPORT FRITO LAY SUBDIVISION NO. 3
STORMWATER REPORT FRITO LAY SUBDIVISION NO. 3 May 2018 STORMWATER REPORT I. Subdivision Data a. The parcel is adjacent to the existing Frito Lay property in Topeka; and the subject plat application encompasses
More informationSTREUVER FIDELCO CAPPELLI, LLC YONKERS DOWNTOWN DEVELOPMENT PHASE 1. DRAFT ENVIRONMENTAL IMPACT STATEMENT For: PALISADES POINT
STREUVER FIDELCO CAPPELLI, LLC YONKERS DOWNTOWN DEVELOPMENT PHASE 1 DRAFT ENVIRONMENTAL IMPACT STATEMENT For: PALISADES POINT Prepared by: PAULUS, SOKOLOWSKI & SARTOR STORMWATER MANAGEMENT 1. Methodology
More informationCaledon Villas Corporation
Caledon Villas Corporation Functional Servicing Report Caledon Villas Residential Subdivision Town of Caledon Project No. L11-557 April 2014 Caledon Villas Corporation Town of Caledon Caledon Villas Residential
More information: WATER SUPPLY SERVICING
APPENDICES LONGFIELDS BLOCK 13 COMMERCIAL PLAZA SERVICING AND STORMWATER MANAGEMENT REPORT Appendix A : Water Supply Servicing November 20, 2017 : WATER SUPPLY SERVICING A.1 DOMESTIC WATER DEMAND ESTIMATE
More informationSection 4: Model Development and Application
Section 4: Model Development and Application The hydrologic model for the Wissahickon Act 167 study was built using GIS layers of land use, hydrologic soil groups, terrain and orthophotography. Within
More informationStormwater Guidelines and Case Studies. CAHILL ASSOCIATES Environmental Consultants West Chester, PA (610)
Stormwater Guidelines and Case Studies CAHILL ASSOCIATES Environmental Consultants West Chester, PA (610) 696-4150 www.thcahill.com Goals and Challenges for Manual State Stormwater Policy More Widespread
More informationNATHAN HALE HIGH SCHOOL PARKING AND TRAFFIC ANALYSIS. Table of Contents
Parking and Traffic Analysis Seattle, WA Prepared for: URS Corporation 1501 4th Avenue, Suite 1400 Seattle, WA 98101-1616 Prepared by: Mirai Transportation Planning & Engineering 11410 NE 122nd Way, Suite
More informationINFLOW DESIGN FLOOD CONTROL SYSTEM PLAN 40 C.F.R. PART PLANT YATES ASH POND 2 (AP-2) GEORGIA POWER COMPANY
INFLOW DESIGN FLOOD CONTROL SYSTEM PLAN 40 C.F.R. PART 257.82 PLANT YATES ASH POND 2 (AP-2) GEORGIA POWER COMPANY EPA s Disposal of Coal Combustion Residuals from Electric Utilities Final Rule (40 C.F.R.
More informationFINAL UTILITY REPORT Creekside Thornton, CO
FINAL UTILITY REPORT Creekside Thornton, CO March 4, 216 Revised: June 27, 216 JN: 1539 Prepared for: HW Sodbusters, LLC 2733 E. Parleys Way, Suite 3 Salt Lake City, UT 8419 P: 81.485.777 Prepared by:
More informationSnow and Ice Control POLICY NO. P-01/2015. CITY OF AIRDRIE Snow and Ice Control Policy
Page 1 CITY OF AIRDRIE Snow and Ice Control Effective Date: Approved By: Approved On: March 17, 2015 City Council March 16, 2015 Revision Date: Resolution #: ------ PURPOSE: The City of Airdrie is responsible
More informationStorm Sewer Design [2]
Class 5 [1] Storm Sewer Design 9. Check Q < Qf and Vmax > vf > Vmin. Vmin is normally specified to avoid sedimentation. This will normally be 1.0 m/s at pipe full condition. (BS EN 752 suggests that for
More informationTechnical Memorandum. City of Salem, Stormwater Management Design Standards. Project No:
Technical Memorandum 6500 SW Macadam Avenue, Suite 200 Portland, Oregon, 97239 Tel: 503-244-7005 Fax: 503-244-9095 Prepared for: Project Title: City of Salem, Oregon City of Salem, Stormwater Management
More informationBRANDON LAKES AVENUE PRE AND POST CONDITIONS DRAINAGE REPORT
BRANDON LAKES AVENUE PRE AND POST CONDITIONS DRAINAGE REPORT Hillsborough County Public Works County Center, 22nd Floor 601 E. Kennedy Blvd. Tampa, FL 33602 BRANDON LAKES AVENUE DRAINAGE IMPROVEMENTS Capital
More informationWoodford County Erosion Prevention Plan and Permit. Application #
Woodford County Erosion Prevention Plan and Permit Application # Date Instructions: Applicant will complete Parts A and B, and attach a proposed site diagram. This diagram must be completed in accordance
More informationWATER DISTRIBUTION NETWORKS
WATER DISTRIBUTION NETWORKS CE 370 1 Components of Water Supply System 2 1 Water Distribution System Water distribution systems are designed to adequately satisfy the water requirements for a combinations
More informationSite Servicing and Stormwater Management Brief Hampton Inn and Suites, 4401 Fallowfield Road, Ottawa, ON
Site Servicing and Stormwater Management Brief Hampton Inn and Suites, 4401 Fallowfield Road, Ottawa, ON File: 160401378/83 Prepared for: 2441736 Ontario Inc. Prepared by: Stantec Consulting Ltd. October
More informationProject Description. Project Options. End Analysis On... Apr 26, :00:00. Rainfall Details
Project Description File Name... 323 - Att Pond 3 East PIPES ONLY.SPF Project Options Flow Units... Elevation Type... Hydrology Method... EPA SWMM Infiltration Method... Link Routing Method... Enable Overflow
More informationGeoSpatial Water Distribution, Sanitary Sewer and Stormwater Network Modeling
2009 Bentley Systems, Incorporated GeoSpatial Water Distribution, Sanitary Sewer and Stormwater Network Modeling Angela Battisti, Gary Griffiths Bentley Systems Inc Presenter Profile Angela Battisti, CE,
More informationspatial water demand (population density) spatial junctions distribution (building density) digital elevation map
SYSTEM ID: WDS-Designer NARRATIVE DESCRIPTION With the WDS Designer a tool for the algorithmic generation of synthetic water distribution systems (swds) based on GIS data was presented (Sitzenfrei et al.,
More informationChapter 7 Mudflow Analysis
Chapter 7 Mudflow Analysis 7.0 Introduction This chapter provides information on the potential and magnitude of mud floods and mudflows that may develop in Aspen due to rainfall events, snowmelt, or rain
More informationHISTORY OF CONSTRUCTION FOR EXISTING CCR SURFACE IMPOUNDMENT PLANT GASTON ASH POND 40 CFR (c)(1)(i) (xii)
HISTORY OF CONSTRUCTION FOR EXISTING CCR SURFACE IMPOUNDMENT PLANT GASTON ASH POND 40 CFR 257.73(c)(1)(i) (xii) (i) Site Name and Ownership Information: Site Name: E.C. Gaston Steam Plant Site Location:
More informationSeptember 6, City of Thornton 9500 Civic Center Drive Thornton, CO (303) RE: Maverik Thornton, CO - Drainage Report
September 6, 2016 City of Thornton 9500 Civic Center Drive Thornton, CO 80229 (303) 538-7295 RE: Maverik Thornton, CO - Drainage Report As per your request, we are submitting to you the drainage report
More informationNoise Feasibility Study Proposed Residential Development (Infill) 747 Liverpool Road Pickering, Ontario
Noise Feasibility Study Proposed Residential Development (Infill) 747 Liverpool Road Pickering, Ontario Prepared for: Madison Liverpool Limited 369 Rimrock Road Toronto, Ontario, M3J 3G2 Prepared by Victor
More information*Corresponding author,
Monitoring the performance of a storm water separating manifold with DTS J.G. Langeveld 1,3*, C. de Haan 1,3, M. Klootwijk 2 and R.P.S. Schilperoort, 1,3 1 Royal Haskoning, Barbarossastraat 35, P.O. Box
More informationAppendix E Guidance for Shallow Flooding Analyses and Mapping
Appendix E Guidance for Shallow Flooding Analyses and Mapping E.1 Introduction Different types of shallow flooding commonly occur throughout the United States. Types of flows that result in shallow flooding
More informationARTICLE 5 (PART 2) DETENTION VOLUME EXAMPLE PROBLEMS
ARTICLE 5 (PART 2) DETENTION VOLUME EXAMPLE PROBLEMS Example 5.7 Simple (Detention Nomograph) Example 5.8 Offsite and Unrestricted Areas (HEC-HMS) Example 5.9 Ponds in Series w/ Tailwater (HEC-HMS) Example
More informationPW 001 SNOW REMOVAL AND SANDING FOR ROADWAYS AND SIDEWALKS October 6, 2014 (#223-14) Original October 19, 2015; October 15, 2018 Public Works
Policy Statement: The Village of Kitscoty will provide snow and ice control on municipal streets and sidewalks according to determined priorities. Purpose: To provide direction and information to employees
More informationWEBER ROAD RESIDENTIAL DEVELOPMENT Single Family Residential Project
WEBER ROAD RESIDENTIAL DEVELOPMENT Single Family Residential Project WEBER ROAD RESIDENTIAL DEVELOPMENT TRAFFIC IMPACT STUDY TABLE OF CONTENTS 1.0 Executive Summary Page 2.0 Introduction 2.1 DEVELOPMENT
More informationLOCATED IN INDIAN RIVER COUNTY PREPARED FOR S.J.R.W.M.D. AND F.W.C.D. DECEMBER, 2003 Updated 2007 Updated May 2014 PREPARED BY
FELLSMERE WATER CONTROL DISTRICT EAST MASTER DRAINAGE PLAN AND STORMWATER HYDROLOGIC ANALYSIS OF THE GRAVITY DRAINAGE SYSTEM LOCATED BETWEEN THE EAST BOUNDARY, LATERAL U, THE MAIN CANAL, AND DITCH 24 LOCATED
More informationWATER MANAGEMENT REPORT FOR PAGE ESTATES
WATER MANAGEMENT REPORT FOR PAGE ESTATES SLB Consulting of SW Florida, LLC PO Box 2826 Bonita Springs, FL. 34133 Phone: 239-948-9566 sandra@slbconsult.com C.O.A. # 25395 September 1, 2014 Sandra L. Bottcher
More informationHydrology Study Report
Hafeez Consulting www.hafeezconsulting.com Civil/ Structural Engineering, Design & Construction 1451 S. Hacienda St. Anaheim CA 92804 (714) 225-4565 Fax (714)917-2977 engineer@hafeezconsulting.com Hydrology
More informationChapter 7 Mudflow Analysis
Chapter 7 Mudflow Analysis 7.0 Introduction This chapter provides information on the potential and magnitude of mud floods and mudflows that may develop in Aspen due to rainfall events, snowmelt, or rain
More informationSediment Capture in Pervious Concrete Pavement tsystems: Effects on Hydrological Performance and Suspended Solids
Concrete Sustainability Conference April 14 th 2010, Tempe, AZ Sediment Capture in Pervious Concrete Pavement tsystems: Effects on Hydrological l Performance and Suspended Solids Discharge Luis A. Mata,
More informationCOUNCIL POLICY MANUAL
COUNCIL POLICY MANUAL SECTION: PUBLIC WORKS SUBJECT: SNOW & ICE CONTROL POLICY 2012/2013 GOAL: Pages: 1 of 10 Approval Date: Dec. 3, 2012 Res. # 1001/2012 To annually identify the winter maintenance costs
More informationLarge-Scale Sediment Retention Device Testing (ASTM D 7351) SedCatch Sediment Basket Inlet Filter Exposed to 6% Sediment Load
Large-Scale Sediment Retention Device Testing (ASTM D 7351) of SedCatch Sediment Basket Inlet Filter Exposed to 6% Sediment Load February 2010 Submitted to: SedCatch Environmental Products 8380 Point O
More informationStatus Report on Polychlorinated Biphenyls in the Western Storm Drain University of California, Richmond Field Station Richmond, California
Status Report on Polychlorinated Biphenyls in the Western Storm Drain University of California, Richmond Field Station Richmond, California Introduction Beginning in 1999, the University of California,
More informationSpecifications Whitcomb Elementary School Demolition January 15, 2016
SECTION 31 2500 - EROSION CONTROL PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The provisions of the Contract Documents apply to the work of this Section. B. The Virginia Erosion and Sediment Control Handbook,
More informationSHADOW STUDY REPORT REGARDING
SHADOW STUDY REPORT REGARDING an APPLICATION TO REDEVELOP Three 6 Storey Condominiums Regional Road 25 (Ontario Street) and Britannia Road Milton, Ontario KNYMH FILE # 17030 Prepared by: Krista Lilley
More informationSewer, pressurization, differential pressure monitoring, fully dynamic hydraulic modeling, air displacement modeling.
Using Dynamic Hydraulic Modeling to Understand Sewer Headspace Dynamics A Case Study of Metro Vancouver s Highbury Interceptor Yuko Suda, P.Eng. Kerr Wood Leidal Associates Ltd. 200-4185A Still Creek Drive
More informationCity of Thornton Attn: Tim Semones Development Engineeering 9500 Civic Center Dr. Thornton, CO 80229
Development Engineering Land Surveying Construction Administration District Services October 20, 2017 City of Thornton Attn: Tim Semones Development Engineeering 9500 Civic Center Dr. Thornton, CO 80229
More informationWEST NORRITON TOWNSHIP
WEST NORRITON TOWNSHIP SANITARY SEWER SYSTEM INFLOW AND INFILTRATION STUDY November 2013 Rettew Associates, Inc. 3020 Columbia Avenue Lancaster, PA 17603 RECOMMENDATIONS The top four priorities for inflow
More informationWater & Wastewater Facility Plan Update
ater & astewater Facility Plan Update South Kalispell Development Supplement to: ater Facility Plan Update, 2008 astewater Facility Plan Update, 2008 November, 2016 Table of Contents Chapter 1 - Basis
More informationSHADOW IMPACT STUDY REPORT
SHADOW IMPACT STUDY REPORT 175 Zoo Park Road Town of Wasaga Beach Date: September 2017 Prepared for: Simcoe County Housing Corporation Prepared by: MacNaughton Hermsen Britton Clarkson Planning Limited
More informationLarge-Scale Sediment Retention Device Testing (ASTM D 7351) SedCatch Sediment Basket Inlet Filter Exposed to 1.5% Sediment Load
Large-Scale Sediment Retention Device Testing (ASTM D 7351) of SedCatch Sediment Basket Inlet Filter Exposed to 1.5% Sediment Load February 2010 Submitted to: SedCatch Environmental Products 8380 Point
More informationCITY OF NEW LONDON WINTER ROAD & SIDEWALK MAINTENANCE POLICY
CITY OF NEW LONDON WINTER ROAD & SIDEWALK MAINTENANCE POLICY GENERAL The purpose of this policy is to set up acceptable procedures and policies for the winter maintenance of public areas in the City of
More informationStage Discharge Tabulation for Only Orifice Flow
Stage Discharge Tabulation for Only Orifice Flow DEPTH STAGE DISCHARGE (meters) (feet) (meters) (feet) (m 3 /s) (ft 3 /s) 0 0.20 0.40 0.60 0.80 1.00 1.20 1.40 1.60 1.80 2.00 0.7 1.3 2.0 2.6 3.3 3.9 4.6
More informationB805 TEMPORARY EROSION AND SEDIMENT CONTROL MEASURES - OPSS 805
B805 MEASURES - OPSS 805 805.1 GENERAL Construction activities frequently remove protective cover and expose soil to accelerated rates of erosion. Sediments generated thereby can be conveyed via runoff
More informationD.M. Wills Associates Limited PARTNERS IN ENGINEERING. Stormwater Management Report. City of Peterborough
Stormwater Management Report City of Peterborough P-20-12 Parkway Corridor Class Environmental Assessment Jackson Park Parkhill Road West to Chemong Road D.M. Wills Project No. 12-5061 D.M. Wills Associates
More informationTemplate for Sediment and Erosion Control Plan General Instructions. Section Instructions
Template for Sediment and Erosion Control Plan General Instructions Introduction: Soil erosion and sediment deposition from farmlands can contribute to degraded surface water quality. Sediment delivery
More informationFOR PROJECTS INITIATED AFTER NOVEMBER 1, 2008 ITEM 716 EMBANKMENT EARTH OUTLET SEDIMENT TRAP
AFTER NOVEMBER 1, 2008 ITEM 716 EMBANKMENT EARTH OUTLET SEDIMENT TRAP 716.1 Description. This work shall consist of furnishing, installing, maintaining, and removing temporary erosion protection and sediment
More informationOrica Australia Pty Ltd Ammonium Nitrate Facility Upgrade
Orica Australia Pty Ltd Ammonium Nitrate Facility Upgrade January 2010 Revision 0 Contents 1. Introduction 1 1.1 Purpose 1 1.2 Objectives 1 1.3 Relevant Environmental Legislation, Guidelines and Policies
More informationGuide to the use of the Erosion and Sediment Control Evaluation Tool
Guide to the use of the Erosion and Sediment Control Evaluation Tool December 2017 If you require content in an alternate format please contact us at 905-895-1281 or by email at Accessibility@LSRCA.on.ca
More informationCITY OF CAPE CORAL STORMWATER MASTER PLAN PHASE II - PART 1 BASINS 4, 10, & 14 SUB-BASIN DRAINAGE IMPROVEMENTS HYDRAULIC ANALYSIS SUMMARY
CITY OF CAPE CORAL STORMWATER MASTER PLAN PHASE II - PART 1 BASINS 4, 10, & 14 SUB-BASIN DRAINAGE IMPROVEMENTS HYDRAULIC ANALYSIS SUMMARY Cape Coral, FL Prepared for: The City of Cape Coral Public Works
More informationUNIVERSITY OF BOLTON WESTERN INTERNATIONAL COLLEGE, RAS AL KHAIMAH BENG (HONS) CIVIL ENGINEERING SEMESTER TWO EXAMINATION 2014/2015
OCD54 UNIVERSITY OF BOLTON WESTERN INTERNATIONAL COLLEGE, RAS AL KHAIMAH BENG (HONS) CIVIL ENGINEERING SEMESTER TWO EXAMINATION 2014/2015 GROUND AND WATER STUDIES 2 MODULE NO: CIE5005 Date: Thursday 10
More informationWellsgate Terrace SPECIFICATIONS.
GRADING NOTES: 1. LOT GRADING SHALL BE COMPLETED TO PROVE SUFFICIENT DIRT ON EACH PAD TO ACHIEVE THE CRITICAL PAD GRADES AND SPOT GRADES ON EACH LOT. AFTER ACHIEVING CRITICAL PAD GRADES INDICATED ON THIS
More informationAssessment of Unaccounted-for Water in Municipal Water Networks Using GIS and Modeling
24 Assessment of Unaccounted-for Water in Municipal Water Networks Using GIS and Modeling Homayoun Motiee, Ali Motiei, Ahmad Hejranfar and M.Reza Delavar This chapter presents a study to calculate Unaccounted-for
More informationHISTORY OF CONSTRUCTION FOR EXISTING CCR SURFACE IMPOUNDMENT PLANT GADSDEN ASH POND 40 CFR (c)(1)(i)-(xii)
HISTORY OF CONSTRUCTION FOR EXISTING CCR SURFACE IMPOUNDMENT PLANT GADSDEN ASH POND 40 CFR 257.73(c)(1)(i)-(xii) (i) Site Name and Ownership Information: Site Name: Site Location: Site Address: Gadsden
More informationSTORMWATER DESIGN CALCULATIONS
STORMWATER DESIGN CALCULATIONS REF : C7011-2390 AT 19a-23 MEMORIAL AVENUE BLACKWALL FOR MR KERR Contents 1.0 Detention System Requirements 1.1 Storage-Area calcs. 1.2 Data Files for Pre & Post Developed
More informationWASTEWATER FLOW COMPONENTS
Chapter 3 WASTEWATER FLOW COMPONENTS 3.1 INTRODUCTION A sanitary sewer collection system receives two flow components: dry weather flow (DWF) and wet weather flow (WWF). The Base Wastewater Flow (BWF)
More informationTown of Georgetown Founded Incorporated 1912
SPECIFICATION FOR SNOW REMOVAL & ICE CONTROL 7.1 Kilometers of Undesignated Streets Season 2017-18 SNOW REMOVAL 1. Snow removal to be carried out before regular business hours to allow normal movement
More informationEstimating Sewage System Flows
9 Estimating Sewage System Flows DWSD Wholesale Sewer Rates 201 In this module, you will learn the sources of dry and wet weather flows and how these flows are estimated. Three different tools are used
More informationMIDDLESEX COUNTY Department of Planning and Community Development P.O. Box 427, Saluda, VA Phone: Fax:
MIDDLESEX COUNTY Department of Planning and Community Development P.O. Box 427, Saluda, VA 23149 Phone: 804-758-3382 Fax: 804-758-0061 LAND DISTURBANCE PERMIT SUBMISSION REQUIREMENTS In order to expedite
More informationStormwater Capacity Analysis for Westover Branch Watershed
Stormwater Capacity Analysis for Westover Branch Watershed Pimmit Run Little Pimmit Run, Mainstem Stohman's Run Gulf Branch Pimmit Run Tributary Little Pimmit Run, W. Branch Little Pimmit Run, E. Branch
More informationUNIVERSITY OF BOLTON WESTERN INTERNATIONAL COLLEGE FZE BENG (HONS) CIVIL ENGINEERING SEMESTER TWO EXAMINATION 2016/2017 GROUND AND WATER STUDIES 2
OCD27 UNIVERSITY OF BOLTON WESTERN INTERNATIONAL COLLEGE FZE BENG (HONS) CIVIL ENGINEERING SEMESTER TWO EXAMINATION 2016/2017 GROUND AND WATER STUDIES 2 MODULE NO: CIE5005 Date: Saturday 27 May 2017 Time:
More informationSTAFF REPORT ACTION REQUIRED
STAFF REPORT ACTION REQUIRED Appeal by Fast Signs of the Decision of the Chief Building Official for One Variance Respecting a Proposed First Party Wall Sign 10-21 Four Seasons Place Date: January 18,
More informationAPPENDIX G APPENDIX G SEDIMENT CONTAINMENT SYSTEM DESIGN RATIONALE
APPENDIX G SEDIMENT CONTAINMENT SYSTEM DESIGN RATIONALE March 18, 2003 This page left blank intentionally. March 18, 2003 G-2 FIGURES Page # Figure G.1 Estimated Runoff from Precipitation Over Different
More informationMEMORANDUM. The study area of the analysis was discussed with City staff and includes the following intersections:
MEMORANDUM DATE: JULY 6, 2012 TO: FROM: RE: CC: MELANIE KNIGHT BRAD BYVELDS/ JENNIFER LUONG 1050 SOMERSET STREET PRELIMINARY TRAFFIC ANALYSIS OUR FILE NO. 111152 NEIL MALHOTRA The purpose of this memo
More informationCORPORATION OF THE CITY OF COURTENAY COUNCIL MEETING AGENDA
CORPORATION OF THE CITY OF COURTENAY COUNCIL MEETING AGENDA DATE: Monday, January 14, 2013 PLACE: City Hall Council Chambers TIME: 4:00 p.m. 1.00 ADOPTION OF MINUTES 1. Adopt January 7, 2013 Regular Council
More informationCITY OF PAPILLION PLANNING COMMISSION STAFF REPORT MAY 27, 2015 AGENDA 2015 ANNEXATION MISC
PLANNING COMMISSION STAFF REPORT MAY 27, 2015 AGENDA 2015 ANNEXATION MISC-15-0005 I. GENERAL INFORMATION A. APPLICANT: City of Papillion 122 East Third St. Papillion, NE 68046 B. LEGAL DESCRIPTION: See
More informationIndependent Environmental Audit Erosion and Sediment Control
Independent Environmental Audit Erosion and Sediment Control Commencement of YOUNG TO BETHUNGRA LOOPING PIPELINE JUNE 2016 suite 1, 39 fitzmaurice st (po box 5464) wagga wagga nsw 2650 australia t (02)
More informationBasic Hydraulics June 2007
Basic Hydraulics www.concrete-pipe.org June 2007 2007 Overview Open Channel Flow Manning Equation Basic Culvert Design Sanitary Sewer Design Flow, Velocity Stormwater Sewer Design Flow, Velocity 2 Open
More informationHydrogeological Assessment for Part of Lots 2 and 3, Concession 5, Township of Thurlow, County of Hastings 1.0 INTRODUCTION. 1.
February 10,2017 25506400 Ontario Ltd. Foxboro, ON Attention: Brad Newbatt Re: Hydrogeological Assessment for Part of Lots 2 and 3, Concession 5, Township of Thurlow, County of Hastings 1.0 INTRODUCTION
More informationMethod of Measuring Machinery Sound Within an Equipment Space
ANSI/AHRI Standard 575 (Formerly ARI Standard 575) 2008 Standard for Method of Measuring Machinery Sound Within an Equipment Space Price $15.00 (M) $30.00 (NM) Printed in U.S.A. 8Copyright 1994, by Air-Conditioning
More informationPressure Head: Pressure head is the height of a column of water that would exert a unit pressure equal to the pressure of the water.
Design Manual Chapter - Stormwater D - Storm Sewer Design D- Storm Sewer Sizing A. Introduction The purpose of this section is to outline the basic hydraulic principles in order to determine the storm
More informationAppendix K.2: Sediment Management Excerpt from South Orange County Hydromodification Management Plan
Appendix K.2: Sediment Management Excerpt from South Orange County Hydromodification Management Plan 4 Sediment Supply Management Requirements Permit Order R9-2013-0001 as amended by Order No. R9-2015-0001Section
More informationAPPENDIX B DRAINAGE REPORT
APPENDIX B DRAINAGE REPORT B-1 South Lamar Blvd. Transportation Corridor Study Drainage Report Prepared for: City of Austin and HDR, Inc. Prepared by: and Services, Inc. Final 07-09-2015 Michael C. Meriwether,
More informationFlood Scenario Worksheet
Flood Scenario Worksheet Scenario adapted from: http://www.epa.gov/watersecurity/tools/trainingcd/simple/source/scenario-8/ssc8-0.pdf Simple Tabletop Exercise, Interdependency Natural Disaster Scenario,
More informationTransportation Noise Feasibility Assessment & 3930 Riverside Drive Ottawa, Ontario
Transportation Noise Feasibility Assessment 3960 & 3930 Riverside Drive Ottawa, Ontario REPORT: GWE18 039 Transportation Noise Prepared For: Alex Turner 225 Metcalfe Street, Suite 708 Ottawa, Ontario K2P
More informationEstimated Sediment Volume: Bridge Street Dam Impoundment, Royal River, Yarmouth, Maine
University of Southern Maine USM Digital Commons Publications Casco Bay Estuary Partnership (CBEP) 2015 Estimated Sediment Volume: Bridge Street Dam Impoundment, Royal River, Yarmouth, Maine Stantec Follow
More informationFHWA Headloss in InfoWorks ICM. August 2013
FHWA Headloss in InfoWorks ICM August 2013 Innovyze 1 August 2013 Contents FHWA Headloss... 1 Contents... 2 1. Introduction... 3 2. Step 1, Calculation of E ai... 3 3. Step 2, Adjustment of E ai to Provide
More informationSediment Trap. At multiple locations within the project site where sediment control is needed.
Sediment Trap SE-3 Objectives EC Erosion Control SE Sediment Control TR Tracking Control WE Wind Erosion Control Non-Stormwater NS Management Control Waste Management and WM Materials Pollution Control
More informationClimate Adaptation Challenges for Boston s Water and Sewer Systems
National Association of Flood & Stormwater Management Agencies Climate Adaptation Challenges for Boston s Water and Sewer Systems John P Sullivan P.E. October 15,2014 Boston 1630 Boston 1630-2012 Boston
More informationContinuing Education Associated with Maintaining CPESC and CESSWI Certification
Continuing Education Associated with Maintaining CPESC and CESSWI Certification Module 2: Stormwater Management Principles for Earth Disturbing Activities Sponsors: ODOTs Local Technical Assistance Program
More informationHYDROLOGY REPORT Tentative Tract No. 5978
ATTACHMENT 5 October 2016 HYDROLOGY REPORT Tentative Tract No. 5978 City of Simi Valley County of Ventura Prepared For: Landsea Holdings Corporation 7525 Irvine Center Drive Suite 200 Irvine, CA 92618
More informationAdvanced /Surface Hydrology Dr. Jagadish Torlapati Fall 2017 MODULE 2 - ROUTING METHODS
Routing MODULE - ROUTING METHODS Routing is the process of find the distribution of flow rate and depth in space and time along a river or storm sewer. Routing is also called Flow routing or flood routing.
More informationSOUTHEAST PLANT POWER FEED AND PRIMARY SWITCHGEAR UPGRADES CIVIC DESIGN REVIEW - PHASE 1 - NOVEMBER 14, 2016
SOUTHEAST PLANT POWER FEED AND PRIMARY SWITCHGEAR UPGRADES CIVIC DESIGN REVIEW - PHASE 1 - NOVEMBER 14, 2016 CITY & COUNTY OF SAN FRANCISCO PUBLIC UTILITIES COMMISSION PROJECT LOCATION CALTRAIN RAILROAD
More informationRoadway Traffic Noise Assessment. 407 Nelson Street Ottawa, Ontario
407 Nelson Street Ottawa, Ontario REPORT: GWE17-042 Traffic Noise Prepared For: Tony Kazarian AK Global Management Inc. 680 Eagleson Road Ottawa, Ontario K2M 2G9 Canada Prepared By: Omar Daher, B.Eng.,
More informationRock & Aggregate Drop Inlet Protection
Rock & Aggregate Drop Inlet Protection SEDIMENT CONTROL TECHNIQUE Type 1 System Sheet Flow Sandy Soils Type 2 System [1] Concentrated Flow Clayey Soils Type 3 System Supplementary Trap Dispersive Soils
More informationThe University of Akron. William Troyer The Dr. Gary B. and Pamela S. Williams Honors College
The University of Akron IdeaExchange@UAkron Honors Research Projects The Dr. Gary B. and Pamela S. Williams Honors College Spring 2018 Applying Control Logic to the End of the Ohio Canal Interceptor Tunnel
More informationFlow Monitoring in the Collection System September 11, 2014
Flow Monitoring in the Collection System September 11, 2014 FISHBECK, THOMPSON, CARR, & HUBER INC. Lori Lloyd, PE, LEED AP BD+C Definitions Why Flow Monitor? Flow Monitoring Applications Site Selection
More information