Seismic Design of Reinforced Concrete Structures. CASE STUDY #1 Three Storey Office Building Vancouver, B.C. Canada
|
|
- Roger Jordan
- 6 years ago
- Views:
Transcription
1 Seismic Desin of Reinforced Concrete Structures CASE STUDY #1 Three Storey Office Buildin Vancouver, B.C. Canada SOFTEK Services Ltd. # Maycrest Way Richmond, BC, Canada V6V N8 Tel: (604) Web: Copyriht Notice This document is copyriht 007 by Softek Services Ltd. All rihts reserved. No part of this publication may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any human or computer lanuae, in any form or by any means, electronic, mechanical, optical, chemical, manual, or otherise, ithout the prior ritten permission of Softek Services Ltd. Disclaimer Softek Services Ltd. cannot be held responsible for the material presented in this document. This document is intended for the use of professional personnel competent to evaluate the sinificance and limitations of its content and recommendations, and ho ill accept the responsibility for its application. Softek Services Ltd. disclaims any and all responsibility for the application of the contents presented in this document and for the accuracy of any of the material contained in this document includin computer softare referenced herein.
2 CASE STUDY #1 In this project, e ill desin various shear alls in a three storey office buildin located in a hih risk seismic zone usin SOFTEK s products: S-FRAME and S-CONCRETE TM. Key results enerated by S-FRAME and S-CONCRETE TM ill also be verified usin hand calculations. Buildin Description Desin Data (NBCC 005) Location: Loads: Commercial Buildin in Vancouver, BC, Canada (Granville & 41 st Ave), Site Soil Class C Retail on Ground Floor, Live Load 4.8 kpa Offices on Upper Levels, Live Load.4 kpa Partition Alloance 1.0 kpa Front Curtain Wall Weiht 1.0 kpa Ground Sno, S s 1.9 kpa and S r 0. kpa Seismic: S a (0.) 0.95, S a (0.5) 0.65, S a (1.0) 0.4, S a (.0) 0.17, PGA 0.47 Importance Factor I E 1.0 Force Modification Factors R d.0, R (moderately ductile SFRS)
3 Materials: ' ' f 5 MPa, f 400 MPa, E 4500 f,500 MPa c y c c c W 400 k/m.5 kn/m Ec,500 Gc 91 MPa (1 +ν ) (1 + 0.) Sno Load for Roof Level, NBCC 005 Clause S Is Ss( CbCCsCa) + Sr ( ) kpa Buildin Seismic Weiht Estimation Buildin Seismic Weiht Estimation at Roof Level Item Description Weiht (kn) 1 Sno Load 0.5 x 1.8 kn/m x 1m x 4m (no hole) 11 Slab.5 kn/m x 0.m x 1m x 4m (no hole) 154 Front Curtain Wall 1.0 kn/m x 1.5m x 1m 18 4 Columns.5 kn/m x ( x 0.m x 0.m + 0.m x 0.4m) x 1.5m 1 5 Walls.5 kn/m x [1.5mx(0.mx64m + 0.5mx.4mx) x0.mx1.mx0.75m] Buildin Seismic Weiht Estimation at rd Floor 506 Sub-Total W 4,01 Item Description Weiht (kn) Area of Holes 4.8m x.4m +.4m x.4m 17.8 m Net Area 1m x 4m 17.8 m 70.7 m 1 Partition Load 0.5 kn/m x 70.7 m (max 0.5 kpa) 15 Slab.5 kn/m x 0.m x 70.7 m 17 Front Curtain Wall 1.0 kn/m x m x 1m 6 4 Columns.5 kn/m x ( x 0.m x 0.m + 0.m x 0.4m) x m 5 5 Walls.5 kn/m x [mx(0.mx64m + 0.5mx.4mx) - x0.x1.mx1.5m] 101 Buildin Seismic Weiht Estimation at nd Floor Sub-Total W,480 Item Description Weiht (kn) Area of Holes 4.8m x.4m +.4m x.4m 17.8 m Net Area 1m x 4m 17.8 m 70.7 m 1 Partition Load 0.5 kn/m x 70.7 m (max 0.5 kpa) 15 Slab.5 kn/m x 0.m x 70.7 m 17 Front Curtain Wall 1.0 kn/m x.5m x 1m 9 4 Columns.5 kn/m x ( x 0.m x 0.m + 0.m x 0.4m) x.5m 7 5 Walls.5 kn/m x [.5mx(0.mx64m + 0.5mx.4mx) x0.x1.mx1.5m] 1098 Sub-Total W,571 Total Weiht W W x W y W + W + W kn
4 Buildin Period, NBCC 005 Clause () a ( ) ( ) T 0.05 h sec same for each direction n Accordin to Article (), Equivalent Static Force Procedure as described in Article may be used for structures that meet the folloin criteria: reular structures that are less than 60m in heiht and have a fundamental lateral period, T a, less than sec in each of the orthoonal directions. For this buildin, it meets this criteria. Seismic Base Shear Calculation Sa(0.) For 5.6 < 8 and S (.0) a < 1.0, 1.0 Sa(0.) For 5.6 < 8 and Ta < 0.5, J 1.0 Sa (.0) No reduction in overturnin moment T a M v Table Table For Site C Class For Site C Class and and S (0.) 0.95, a S (1.0) 0.4, a F F a v Table B Table C Minimum Lateral Earthquake Force S(Ta )M view V Article R R S(.0)M view V R R d d 0 0 For R d 1.5, V S(0.)I R R S(T 0.s) F a S a (0.) 1.0x S(T 0.5s) F v S a (0.5) or F a S a (0.), hichever is smaller 0.65 S(T.0s) F v S a (.0) 0.17 Usin linear interpolation: S(T 0.7s) 0.88 d 0 E W V V 0.88x1.0x1.0x707 kn kn.0x1.4 x0.95x1.0x707 kn 1600 kn.0x x1.0x1.0x707.0x kn Seismic Base Shear V 1600 kn 4
5 Centre of Mass Calculation Since most of the eiht is distributed uniformly around the buildin, e ill place the axes at the centre of the slab (see fiure belo). The only eihts that ill influence the location of the centre of mass ill be Walls #, #4, #5, #6 and the holes in the slab for the nd and rd floor. We ill assume there are no holes at the roof level. For the roof level: WiUi.5kN / m x1.5mx0.mx.7mx.6m + WiUi 99 U 0.m Wi 01.5kN / m x1.5mx0.5mx.4mx4.8x kNm V WiVi.5kN / m x1.5mx0.mx.7mx(.05)m +.5kN / m x1.5mx0.5mx.4mx( m) kNm WiVi m Wi 01 For practical purposes, the centre of mass equals to the centre of the slab ( U V 0 ). The influence of Wall #, #4, #5, #6 and the holes in the slab is minimal because the eiht of the slab and the other alls (#1, #, and #7) dominate the centre of mass for this buildin. 5
6 Centre of Riidity Calculation This hand calculation is based on the assumption that alls are stron in bendin in one direction and very eak or neliible in bendin in the other direction. Lateral stiffness (k) of each all element must also be estimated assumin some form of flexural behaviour. Special attention is iven to Wall # and Wall #6. The to alls ill likely be reinforced in such a manner that they ill deflect and behave as a sinle unit an L-Shaped all. This ill be reflected in the computations belo. For the purpose of this calculation, the folloin reference axes ill be used. Walls #1 and # (use h m for calculations) A 4m x 0.m 4.8 m I 0.m x (4m) / m 4 If e apply a 100kN force at the top, the lateral deflection ill be approximately: Vh 1.Vh 100,000x000 1.x100,000x mm E I G A 1 6 c c x,500x0.4x10 91x4.8x10 (assumin a pin-fixed end condition) 100 kn k y 1,087 kn/mm and k x 0 (no stiffness in eak direction) mm Walls #4 and #5 (use h m for calculations) A.4m x 0.5m 0.6 m I 0.5m x (.4m) / m 4 If e apply a 100kN force at the top, the lateral deflection ill be approximately: Vh 1.Vh 100,000x000 + E ci Gc A x,500x0.88x10 (assumin a pin-fixed end condition) 100 kn k 490 kn/mm and k y 0.04 mm x 1 1.x100,000x mm 6 91x0.6x10 0 (no stiffness in eak direction) 6
7 Wall # and Wall #6 as an L-Shape (use h m for calculations) S-CONCRETE L-Shape Results If e apply a 100kN force at the top in the X-direction, the lateral deflection ill be approximately: 9 4 I 678.6x10 mm, A 190x10 mm y x x Vh E I c y mm 1.Vh 100,000x000 + G A x,500x678.6x kn k x 110 kn / mm mm c 9 1.x100,000x x1.9x10 If e apply a 100kN force at the top in the Y-direction, the lateral deflection ill be approximately: 9 4 I x10 mm, A 190x10 mm x y y Vh E I c y mm 1.Vh 100,000x000 + G A x,500x1785.9x kn k y 1898 kn / mm mm c 9 1.x100,000x x1.9x10 Wall #7 (use h m for calculations) This as modelled in S-FRAME usin quadrilateral elements and a riid diaphram on the roof (see fiure belo). A force of 100kN as applied at the roof and a lateral deflection of 0.01mm as obtained. F 100 kn k x 4700 kn/mm and k y 0.01 mm 0 (no stiffness in eak direction) 7
8 Element Xi (m) Yi (m) Kxi (kn/m) (x 10 ) Kyi (kn/m) (x 10 ) Xi Kyi (kn x 10 ) Yi Kxi (kn x 10 ) , & ,10 1,898 19,60 10, , , N/A ,764 5 N/A ,940 7 N/A 4 4, ,800 Totals 6,800 6,07 164,404 18,480 Xi Kyi 164,404 Distance to Centre of Riidity Xcr 6.0 m Kyi 6,07 Small difference beteen centre of mass and centre of riidity (e x 0.m) Yi Kxi 18,480 Distance to Centre of Riidity Ycr 18.9 m Kxi 6,800 Sinificant difference beteen centre of mass and centre of riidity (e y 6.89m) 8
9 Distribution of Base Shear, NBCC Clause (6) F t 0 because T a < 0.7sec Wxhx Fx (V Ft ) here V 1600 kn n W h 1 i i Level Heiht h x (m) Storey Weiht W x (kn) W x h x (knm) Lateral Force F x (kn) Storey Shear V x (kn) Roof 9.5,01 19, ,480 16, ,571 8, ,07 44, Desin Eccentricities, NBCC Clause (10) T x F x (e x ± 0.10 D nx ) F x (0. ± 0.1 x 1) F x (0. ± 1.) knm T x F x (e y ± 0.10 D ny ) F x (6.9 ± 0.1 x 4) F x (6.9 ±.4) knm Hand Calculations Versus D Modellin in S-FRAME For this project and for one load case, hand calculations ill be used to compute the distribution of lateral forces and torsional moments to all the lateral force resistin elements in this buildin for the upper most level only. A D model usin S-FRAME ill also be created and the results ill be compared to hand computed values. The D model in S-FRAME can also ive us an estimate of the torsional sensitivity, B, for this buildin, NBCC Clause (9). Numerous other load cases and load combinations ill also be enerated usin S-FRAME. D Beam Model in S-FRAME In this D model, the alls are modelled as beam elements ith a computed moment of inertia for stron axis bendin and zero for eak axis bendin. This approach should produce similar results as hand calculations because the same assumption is applied eak or non-existent in one direction and stron in the other direction. Shear areas are also provided to ive more accurate deflections for evaluation purposes. Riid members are provided to model the behavior at the ends of each all. Riid means a relatively hih moment of inertia. Accordin to Clause of NBCC 005, structural modellin shall be representative of the manitude and spatial distribution of the mass of the buildin and of the stiffness of all elements of the SFRS. The model shall account for the effect of cracked sections in reinforced concrete and say effects arisin from the interaction of ravity loads ith the displaced confiuration of the structure (P-Delta). S-FRAME can perform eometric non-linear analysis (P-Delta). Furthermore, accordin to Clause of CSA-A.-04, for the purpose of determinin forces in and deflections of the structure, reduced section properties shall be used. The effective property to be used as a fraction of the ross section property shall be as specified belo: 9
10 Couplin Beams A ve 0.15 A ; I e 0.4 I ithout diaonal reinforcement Ps Column I e α c I ; α c ' f A Ps Wall A xe α A ; I e α I ; α ' f A c c For alls, P s shall be determined at the base of the all. Preliminary calculations indicate an α value in the rane of 0.6 and α c value in the rane of 0.65 hich ill be confirmed later. Element Gross Properties Effective Section Properties Wall #1 & # Walls # & #6 Walls #4 & #5 Column 00x00 00x4, I.04x10 mm 1 A 00x4,000 4,800,000 mm 5 A v x00x4,000 4,000,000 mm 6 I 678.6x10 y x 9 I x10 A 190x10 9 mm 4 mm mm 5 A v x190x x x I.88x10 mm 1 A 50x ,000 mm 4 mm 5 A v x50x ,000 mm I x Iy 6.75x10 mm 1 A 00x00 90,000 mm I e 0.6 x.04 x x mm 4 A e 0.6 x 4,800,000,976,000 mm A ev 0.6 x 4,000,000,480,000 mm I ey 0.6 x x x mm 4 I ex 0.6 x x x mm 4 A e 0.6 x 190 x ,800 mm A ev 0.6 x 1075 x ,500 mm I e 0.6 x.88 x x mm 4 A e 0.6 x 600,000 7,000 mm A ev 0.6 x 500,000 10,000 mm I e 0.65 x 6.75 x x 10 8 mm 4 A e A 90,000 mm Column 00x400 00x400 I x 1.066x mm 400x00 8 I y.67x10 mm 1 A 00x400 80,000 mm 4 4 I ex 0.65 x x x 10 8 mm 4 I ey 0.65 x.67 x x 10 8 mm 4 A e A 80,000 mm 10
11 Wall #7 is modelled as a frame ith riid members that connect the end faces of each pier to the ends of couplin beams. The couplin beams represent the sements at the openins. This is illustrated belo in elevation. Element Gross Properties Effective Section Properties Wall #7a Wall #7b Couplin Beam B1 Couplin Beam B Couplin Beam B 00x I.04x10 mm 1 A 00x ,000 mm 5 A v x00x ,000 mm 6 00x4800 I 1.84x10 1 A 00x ,000 mm 1 4 mm 5 A v x00x ,000 mm 6 00x700 9 I 5.717x10 mm 1 A 00x ,000 mm 00x I 5.65x10 mm 1 A 00x ,000 mm 00x000 I 1.x10 1 A 00x ,000 mm mm 4 4 I e 0.6 x.04 x x mm 4 A e 0.6 x 480,000 97,600 mm A ev 0.6 x 400,000 48,000 mm I e 0.6 x 1.84 x x 10 1 mm 4 A e 0.6 x 960, ,00 mm A ev 0.6 x 800, ,000 mm I e 0.4 x x x 10 9 mm 4 A e 0.15 x 140,000 1,000 mm I e 0.4 x 5.65 x x mm 4 A e 0.15 x 00,000 45,000 mm I e 0.4 x 1. x x mm 4 A e 0.15 x 400,000 60,000 mm 11
12 S-FRAME Model usin Beam Type Members Only and Riid Diaphrams The S-FRAME D model of the office buildin shon here consists only of beam type members ith riid diaphrams specified for each floor level. Only the nd floor diaphram is displayed above. Special attention is iven to Walls # and #6. Walls # and #6 is modelled as one column hich ill be subjected to biaxial bendin. The properties of this column is iven the section properties of the L-Shape (i.e. I x and I y ). Note that to minimize the amount of torsion that ill be attracted to each all, the torsional constants, J, for each all ere assined neliible values. 1
13 S-FRAME Model Center of Riidity Evaluation To assess the accuracy of C of R calculation, e ill apply 1000 kn force at each level in the X-direction at the computed C of R. In theory, loadin the buildin at the C of R ill enerate deflections ithout rotation pure translation. The results are displayed belo (Xdeflections in mm). As you can see above, the buildin is rotatin in a clockise direction. This most likely means that e have underestimated the stiffness of the L-Shape (Walls # & #6). Usin a trial-anderror approach in S-FRAME, e discovered the true center of riidity near e y 5.5m for this buildin (as indicated belo). 1
14 Torsional Sensitivity Evaluation The next step is to use this D model in S-FRAME to ive us an estimate of the torsional sensitivity, B, for this buildin. Here, the primary concern ould be loadin in the X-direction creatin a tist in the buildin. Accordin to NBCC Clause (9), the equivalent static forces, F x, shall be applied at distances of ±0.10D ny ±.4m from the center of mass at each floor level. The critical load case for this evaluation ould be applyin the forces at a distance of +.4m aay from the C of M. This is implemented in S-FRAME by applyin the equivalent static forces, F x, at the center of mass at each level plus a torsional moment of F x x.4m in the appropriate direction. Torsional Sensitivity: B x δ δ max av Level Corner Deflections Total # of δ max (mm) Corners (mm) (mm) B x Roof x.85 + x rd x1.8 + x nd x0.794+x Base on the results above, B 1.5 for this buildin. Accordin to NBCC Clause (10), for a buildin ith B 1.7, torsional effects can be accounted for by applyin equivalent static forces, F x, to the buildin located at ±0.10D nx and ±0.10D ny from the C of M for each principle direction. Technically, e should also evaluate the torsional sensitivity for loadin in the y-direction (N-S direction). Since lare alls (Wall #1 and #) dominate the riidity in the y-direction, it is unlikely that the torsional sensitivity parameter, B, for loadin in this direction ill be reater than that computed above. δ av 14
15 Distribution of Lateral Force to Walls For hand calculations in tabular form, e ill consider only one load case (E-W direction) and applied to the roof only. The results of these hand calculations ill then be compared to the results enerated by S-FRAME for the alls in the top floor. To complete the desin of this buildin, other load cases ill be enerated in S-FRAME includin loadin in the N-S direction, dead loads, and factored load combinations. V x F x 69 kn, V y 0 kn T V x (e y D ny ) 69 x ( x 4) 6445 knm Note: T V x (e y D ny ) 69 x ( x 4) 119 knm done in S-FRAME only 15
16 Distribution of E-W Lateral Force and Torsional Moment to Walls V x F x 69 kn, V y 0 kn T -V x (e y D ny ) -69 x ( x 4) knm Force and Torsional Moment Applied at Roof Level Wall X i (m) Y i (m) K xi (kn/m) (x 10 ) K yi (kn/m) (x 10 ) K xi K xi (kn) V x y k i J r xi (kn) T V xi (kn) # , #/ ,10 1, K yi K yi (kn) V y x k # , # # # , i J r yi (kn) T V yi (kn) J J J r r r X K + Y yi [ 6. 1, , ,087 + ( ) ] 1.1x10 i 9 i knm K xi x10 knm 16
17 Comparison of Hand Calculations Versus S-FRAME D Results Wall Hand Calculations S-FRAME Comments #1-74 kn -47 kn less stiff in S-FRAME # & #6 6 kn / 164 kn* 8 kn / kn* more stiff in S-FRAME # 8 kn 19 kn less stiff in S-FRAME #4 87 kn 66 kn less stiff in S-FRAME #5 81 kn 68 kn less stiff in S-FRAME #7 61 kn kn less stiff in S-FRAME * Shear in the eak direction (V y kn) for the L-Shape (Walls # & #6) is not displayed in the above plot but can be obtained easily in a plot for y Shear. Overall, hand calculated results ive similar values to S-FRAME. Reasonable numbers ere obtained usin simple assumptions on flexural behaviour hich otherise ould be considered rather complex in the D orld. The key to structural desin is to develop a complete load path, determine the sectional forces from this load path, and reinforce the members appropriately. This has been accomplished usin both hand calculations and in S-FRAME. To complete the desin of this buildin, other load cases and load combinations ill be enerated usin S-FRAME includin earthquake loadin E-W (-0.10D ny ), earthquake loadin N- S (±0.10D nx ), and dead load. 17
18 Dead Load Estimation (at base of the all) Wall #1 Tributary Area 0.75 x 6m x 4m 54.0 m Slab 0.m x 54.0 m x.5 kn/m 5.8 kn at each level Partitions 54.0 m x 1 kn/m 54.0 kn at each level (except roof) Self Weiht 9.5m x 0.m x 4m x.5 kn/m 1,071.6 kn Total at base x x ,941 kn Walls # & #6 Tributary Area 5m x 5m 5 m Slab 0.m x 5 m x.5 kn/m kn at each level Partitions 5 m x 1 kn/m 5 kn at each level (except roof) Self Weiht 9.5m x 0.5m x.4m x.5 kn/m 14 kn Total at base x x kn Wall #7b Tributary Area 0.8 x m x 4.8m 11.5 m Slab 0.m x 11.5 m x.5 kn/m 54.0 kn at each level Partitions 11.5 m x 1 kn/m 11.5 kn at each level (except roof) Self Weiht 9.5m x 0.m x 4.8m x.5 kn/m 14 kn Total at base x x kn Hand calculations for dead load at the base of each all are similar to the results enerated by S- FRAME. Since S-FRAME is relatively more accurate than the hand computed values, e ill use S-FRAME results to evaluate the effective section properties as outlined in Clause of CSA-A
19 Wall #1 Effective Section Properties P s 1919 kn, f c ' 5 MPa, A 00 x 4,000 4,800,000 mm Ps 1,919,000 α ' f A 5x4,800,000 c A xe 0.6 x A,976,000 mm (effective cross-sectional area) A ve 0.6 x 5/6 x A,480,000 mm (effective shear area) I e 0.6 x I 0.6 x.04x x10 14 mm 4 Walls # & #6 Effective Section Properties P s 490 kn, f c ' 5 MPa, A 1,90,000 mm Ps 490,000 α ' f A 5x1,90,000 c A xe 0.6 x A 799,800 mm (effective cross-sectional area) A ve 0.6 x 5/6 x A 666,500 mm (effective shear area) I ey 0.6 x I y 0.6 x x x10 11 mm 4 I ex 0.6 x I x 0.6 x x x10 11 mm 4 Wall #7b Effective Section Properties P s 440 kn, f c ' 5 MPa, A 00 x 4, ,000 mm Ps 440,000 α ' f A 5x960,000 c A xe 0.6 x A 595,00 mm (effective cross-sectional area) A ve 0.6 x 5/6 x A 496,000 mm (effective shear area) I e 0.6 x I 0.6 x 1.84x x10 1 mm 4 For practical purposes, all the alls in this buildin appear to have an effective moment of inertia of 0.6 x I and effective cross-sectional area of 0.6 x A. This as used in the S-FRAME model to compute the factored lateral deflections ( f ) and the factored sectional forces (N f, V f, and M f ) used for analysis and desin of these alls. 19
20 Desin Load Combinations S-FRAME ill be used to enerate the load cases and load combinations for desin purposes. The folloin load combinations ill be created for the desin of Wall #1, # & #6, and #7b hich is based on 1.0 x Earthquake x Dead load factors. Load Combination #1: 1.0 x E-W (+0.10Dny) x D Load Combination #: 1.0 x E-W (-0.10Dny) x D Load Combination #: 1.0 x N-S (+0.10Dnx) x D Load Combination #4: 1.0 x N-S (-0.10Dnx) x D Lateral Load in Opposite Direction (primarily used to desin the L-Shape) Load Combination #5: -1.0 x E-W (+0.10Dny) x D Load Combination #6: -1.0 x E-W (-0.10Dny) x D Load Combination #7: -1.0 x N-S (+0.10Dnx) x D Load Combination #8: -1.0 x N-S (-0.10Dnx) x D Companion loads associated ith Live and Sno Loads may easily be added to the above load combinations but, in this case, they ill not likely overn the desin of this buildin. The primary purpose here is to illustrate the use and application of S-FRAME and S-CONCRETE in the analysis and desin of this office buildin. Desin Sectional Forces at base for Wall #7b (enerated by S-FRAME) Load Combination #1: Load Combination #: Load Combination #5: Load Combination #6: N f -44 kn, V f 41 kn, M f 118 knm, f 1.5 mm N f -47 kn, V f 47 kn, M f 41 knm, f 1.6 mm N f -44 kn, V f 46 kn, M f 478 knm, f 1.8 mm N f -45 kn, V f 5 kn, M f 700 knm, f 1.9 mm Note: The shear forces displayed here must be manified for desin purposes. Accordin to Clause of CSA-A.-04, the desin shear force or resistance must not be less than the smaller of: (1) the shear force correspondin to the development of the nominal moment capacity of the all at its plastic hine location and () shear force at R d R o 1.0. S-CONCRETE can make this estimation. Desin Sectional Forces at base for Walls # & #6 (enerated by S-FRAME) LC #1: N f +477 kn, V fy 411 kn, M fz +114 knm, fy. mm V fz 5 kn, M fy +84 knm, fz 0.1 mm LC #: N f +48 kn, V fy 88 kn, M fz +106 knm, fy.0 mm V fz 0 kn, M fy -65 knm, fz 0.0 mm LC #5: N f kn, V fy 7 kn, M fz -109 knm, fy.6 mm V fz 64 kn, M fy +1 knm, fz 0.1 mm LC #6: N f -195 kn, V fy 50 kn, M fz -117 knm, fy.5 mm V fz 41 kn, M fy +85 knm, fz 0.1 mm Note: This all may experience small tension forces accordin to S-FRAME results. This is reasonable because Wall # ill be carryin a sinificant amount of shear force due to the torsional moment hich, in term, ill tend to lift Walls #6 and #. 0
21 Desin Sectional Forces at base for Wall #1 (enerated by S-FRAME) Load Combination #1: Load Combination #: Load Combination #: Load Combination #4: Load Combination #5: Load Combination #6: Load Combination #7: Load Combination #8: N f kn, V f 676 kn, M f 980 knm, f 0.19 mm N f kn, V f 195 kn, M f 6448 knm, f 0.08 mm N f -188 kn, V f 71 kn, M f 96 knm, f 0.16 mm N f kn, V f 95 kn, M f 549 knm, f 0. mm N f -196 kn, V f 80 kn, M f 8855 knm, f 0. mm N f -57 kn, V f kn, M f 59 knm, f 0.11 mm N f kn, V f 585 kn, M f 4488 knm, f 0.1 mm N f kn, V f 86 kn, M f 595 knm, f 0.19 mm Note: Here, the larest moment is enerated from a load combination ith a sinificant torsional moment (#1) hich is interestin. The larest shear force is enerated from a load combination that applies the lateral loads in the stron direction for this all (#4) hich is as expected. S-FRAME results (i.e. axial force, shear force, and moment diarams) can be directly exported to S-CONCRETE to complete the desin. This is illustrated belo for Wall #7b, Wall # & #6, and Wall #1. Hand calculations ill also be performed to verify the results of S-CONCRETE. 1
22 Wall #7b Desin and Detailin S-FRAME ill export sectional forces and moments evaluated at various stations alon the member. In this case, it has evaluated sectional forces at three stations per member sement per load combination. For this member in the D model, it has been subdivided into to sements on the first floor.
23 Let s assume that minimum distributed reinforcin and zone reinforcin ill be sufficient to meet all the requirements of CSA-A.-04. We ill desin the base of the all (i.e. plastic hine reion). Wall Dimensions: Panel Reinforcin: Zone Reinforcin: L 4800mm, b 00mm, h 9500mm h Squat Wall (technically) L 4800 Hoever, for practical desin purposes, e ill treat it as a normal all. To force S-CONCRETE to not apply the squat all provisions, e assined a value of 9601mm to h. Vertical Bars Each Face ( curtains) Horz Bars 400 Each Face ( curtains) A b x100 ρ v ρh Clause b S 00x M bars at each end of the all (minimum requirement) 10M 95mm (Clause and ) S 6d 6x16 96 mm Governs b 4d 0.5b tie 4x11. 71mm 0.5x mm Axial Load and Moment Capacity: Mf 700 Utilization M 64 r OK S-CONCRETE results and interaction diaram shon belo:
24 Overstrenth Factor: M n 4198 knm (nominal moment capacity from S-CONCRETE) M f 700 knm (from S-FRAME) Mn 4198 γ (same as S-CONCRETE s estimate) M 700 f Dimensional Limitations: Clause , L u mm b 00 mm Lu 00 5 mm Lu mm 0 0 Not Good OK Hoever, accordin to Clause , the L u /14 requirement may be aived if the neutral axis depth does not exceed 4b or 0.L (i.e. C 800 mm) hich is the case here. S-CONCRETE ill compute the neutral axis depths for load combination here flexure is dominant and determine if the all meets these requirements for dimensions and ductility. This is displayed belo in the Results Report indo of S-CONCRETE. 4
25 Ductility Evaluation: Clause 1.7.., R d.0, R Check #1 C 456 mm < 0.15L 0.15x mm OK Alternative Check # C < 0.L 1584 mm and f h mm < 7 mm OK Alternative Check # (Clause 1.6.7) frdr0 f γ 1.9x.0x x1.55 θid θid 0.00 L 4800 h 9500 ε cu L 0.005x4800 θ ic C x456 θ id < θ ic OK All ductility checks indicate that special concrete confinement requirements ill not be required. S-CONCRETE has the capability to evaluate special concrete confinement requirements as outlined in Clause for zone reinforcin. Desin Shear Force: Accordin to Clause of CSA-A.-04, the desin shear force or resistance must not be less than the smaller of: (1) the shear force correspondin to the development of the nominal moment capacity of the all at its plastic hine location and () shear force at R d R o 1.0. V V f f Mn (desin) Vf M f (desin) R R V d 0 (S FRAME) f (S FRAME) γ V f (S FRAME).0 x 1.4 x kn x 5 81 kn S-CONCRETE has the option to perform Shear Force Manification in the manner described above to determine the desin shear forces. Shear Resistance: Shear Desin is based on Clauses to (simplified method) Panel Reinforcin 400 H.E.F. V 81 kn V V f r c V c λβφ o + V c s f V ' c b r max d v 0.15λφ and V ;' c c s f b d v for θ φsa v fyd S tan θ v id θ 45 Clause (c), dv 0.8L 840 mm ' b S If A v 00mm > 0.06 fc 60mm, then β 0.18 Clause (a) f β 0.18 for θid Clause (b) yv ' Vc λβφ c fc b dv 1 x 0.18 x 0.65 x 5 x 00 x840 N 449. kn 5
26 V V φsa v fydv 0.85x00x400x840 N S tan θ o 400x tan 45 V + V kn s r c s Vf Utilization V r S-FRAME Results 0.77 < kn OK 6
27 Walls # & #6 Desin and Detailin Let s assume that minimum distributed reinforcin and zone reinforcin ill be sufficient to meet all the requirements of CSA-A.-04. We ill desin the base of the all (i.e. plastic hine reion). Wall Dimensions: L 700mm, b 50mm, h 9500mm h >.0 Not a Squat Wall L 700 Panel 1 Reinforcin: Vertical Bars - 00 Each Face ( curtains) Horz Bars 00 Each Face ( curtains) A b x100 ρ v ρh Clause b S 50x00 Panel Reinforcin: Vertical Bars Each Face ( curtains) Horz Bars 400 Each Face ( curtains) A b x100 ρ v ρh Clause b S 00x400 7
28 Zone A Reinforcin: 4 10M bars at each end of the all (minimum requirement) 10M 65mm (Clause and ) S 6d b 4d 0.5b 6x mm tie 4x11. 71mm 0.5x mm Governs Zone B Reinforcin: 4 15M bars at each end of the all (minimum requirement) 10M 95mm (Clause and ) S 6d b 4d 0.5b 6x16 96 mm tie 4x11. 71mm 0.5x mm Governs Zone C Reinforcin: 4 10M bars at each end of the all (minimum requirement) 10M 65mm (Clause and ) S 6d b 4d 0.5b 6x mm tie 4x11. 71mm 0.5x mm Governs Note: Emphasis as placed on minimizin the amount of vertical bars in the section includin both zone steel and distributed reinforcin. This ill reduce the axial load and moment capacity hich increases the N vs M utilization. This, in turn, ill reduce the desin or manified shear forces because it ill enerate a smaller overstrenth factor. Axial Load and Moment Interaction Diaram (Biaxial Bendin, Theta 94 ): 8
29 M Utilization M f r Borderline Overstrenth Factor for bendin about z-z axis (Theta 90 ): S-CONCRETE has determined the overnin load combination for pure unixaxial bendin about the z-z axis is LC #1 hich is 1.0xE-W (+0.10D ny ) + 1.0xD. N f +477 kn, M f 114 knm M n 165 knm (nominal moment capacity from S-CONCRETE) Mn 165 γ 1.0 (same as S-CONCRETE s estimate) M 114 f Panel 1 Dimensions: Clause , L u mm Lu 00 b 50 mm 165 mm OK 0 0 L 400mm 0.5h + t 0.5x mm OK Panel Dimensions: Clause , L u mm Lu 00 b 00 mm 165 mm OK 0 0 L 700mm > 0.5h + t 0.5x mm NG Accordin to Clause , the flane idth of Panel is too lon. This means that part of Panel is ineffective in the overall axial load and moment capacity of the section for bendin about the z-z axis. Technically, e should shorten the lenth of the panel hich is unlikely. Evaluatin the nominal moment capacity in this direction usin the full lenth ill ive a conservative estimate on the required desin shear force (i.e. hiher overstrenth factor). The Warnin can be inored in this case. 9
30 Ductility Evaluation: Clause 1.7.., R d.0, R 0 1.4, C 10 mm from S-CONCRETE Check #1 C 10 mm < 0.15L 0.15x mm Not OK Alternative Check # C < 0.L 79 mm and f h mm < 7 mm OK Alternative Check # (Clause 1.6.7) frdr0 f γ.6x.0x1.4.6x1.0 θid θid 0.00 L 400 h 9500 ε cu L 0.005x400 θ ic C x10 θ id < θ ic OK Desin Shear Force: Mn f (desin) Vf (S FRAME) γ Vf (S FRAME 1.0 x 411 M f (desin) R R V.0 x 1.4 x kN V ) V f d 0 f (S FRAME) 494 kn S-CONCRETE has the option to perform Shear Force Manification in the manner described above to determine the desin shear forces. Shear Resistance: S-CONCRETE results For this all, the section may be subjected to tension forces. Here, the General Method of Shear Desin must be used to evaluate the shear resistance. 0
31 Wall #1 Desin and Detailin (Sq uat Wall) Let s assume that minimum distributed reinforcin and zone reinforcin ill be sufficient to meet all the requirements of CSA-A.-04. We ill desin the base of the all. Wall Dimensions: L 4,000mm, b 00mm, h 9500mm h <.0 Squat Wall L 4,000 (Clause 1.7.4) Panel Reinforcin: Zone Reinforcin: Vertical Bars - 00 Each Face ( curtains) Horz Bars 00 Each Face ( curtains) A b x100 ρ v ρh Clause (a) b S 00x00 Maximum Bar Spacin 00mm Clause (a) Accordin to Clause , tied vertical reinforcement shall be provided at each end of the all. The minimum reinforcement ratio of shall be provided over a minimum all lenth of 00mm. A minimum of four bars shall be provided and tied as a column in accordance ith Clause 7.6. The ties shall be detailed as hoops. 6 15M bars at each end of the all (spaced at 150 mm apart) A b x00 ρ Clause (a) b S 00x150 10M 00 mm (Clause ) S 16d 16x16 56 mm 48dtie 48x mm b 00 mm Governs b 1
32 Axial Load and Moment Capacity: (S-CONCRETE Results) M Utilization M f r < 1.0 OK Accordin to Clause , the vertical tension force required to resist overturnin at the base of the all shall be provided by zone reinforcin and panel reinforcin in addition to the amount required by Clause to resist the shear correspondin to the applied bendin moment. Mf Let ρ m Estimated Vertical Steel Ratio Required for Moment ρv 0.00 x M r
33 Mn Desin Shear Force: γ 10.4 > RdR0.0 x M 979 f γ.8 Overstrenth Factor V f (desin) γ V f (sframe).8 x 95,668 kn (Load Combination #4) Shear Desin: Clause d v 0.8 L 0.8 x 4,000 19,00 mm V f 0.15 λ φ c f c ' b d v 0.15 x 1 x 0.65 x 5 x 00 x 19,00 N 960 kn β 0 V c 0 φsa vfydv φsfydv A v Vs ρhb here ρhb S tanθ tanθ S V f V r V c + V s V s assume θ 45 φsfydv 0.85x400x19,00 Vr Vs ρhb x0.00x00 N 45 kn tanθ o tan Utilization 0.61 < 1 OK 45 Let ρ vs vertical steel ratio required to resist shear A 00 x 4,000 4,800,000 mm For load combination #4, V f 668 kn, P s N f 1851 kn ρ ρ h 0.00 ρ ρ tan hs P Vf tanθ,668,000x tan 45 ρh(req' d) OK φ f d b 0.85x400x19,00x00 s y v ,851,000 o tan x400x4,800,000 hs s vs θ φsfya o
34 For another load combination, V f 668 kn, P s N f 1448 kn ρ ρ h 0.00 ρ ρ tan Total Vertical Steel Ratio Required: hs P Vf tanθ,668,000x tan 45 ρh(req' d) OK φ f d b 0.85x400x19,00x00 s y v ,448,000 o tan x400x4,800,000 hs s vs θ φsfya o ρ v 0.00 ρ v (required) ρm + ρvs OK Accordin to Clause , all vertical reinforcement required at the base of the all shall be extended the full heiht of the all. S-FRAME Results (Panel and Zone Reinforcin): 4
35 Conclusions When desinin alls that intersect ith other alls (Wall #6), e have nelected the influence of Wall # on Wall #6. A portion of Wall # should be included in the calculation for moment capacity hich, in turn, ill likely increase the desin shear force. Overall, nelectin the intersection of Wall #6 ith Wall # ill not chane the reinforcin confiuration very much if at all. Hoever, as alays, careful consideration of all the parameters should be iven nevertheless. Some enineers may have considered a different approach to the desin of Wall #7. In our model, e have assumed a coupled all system hich may be inappropriate for such a short all. In fact, a finite element model of the same buildin appears to contradict the sectional forces produced by this beam model version. For more information on the finite element model, refer to Case Study #. The finite element model suests that beam theory of plane sections remainin plane does not apply to Wall #7 and Wall #1. In Case Study #, you ill find sinificant differences in the sectional forces enerated for each all. This suests that Wall #7 should be desined as a squat all and vie the indo openins as havin little influence on the overall behaviour of the all. Hand calculations may ive you reasonable desin values for the lateral load resistin elements in a iven buildin but D modellin ill ive you a better representation of the overall performance of the buildin provided the model truly represents its behaviour in an earthquake. The key to any desin is to ensure that a load path has been defined and carried throuh to all the lateral load and ravity load resistin elements in the buildin. Minimizin the tist in the buildin and detailin the members carefully ill help ensure that the loads reach the beams, columns and alls as desined. 5
According to the Ratio of Height to Least Lateral Dimension: (ACI Code and ACI Code ) < 22, when member is braced against sideways.
CHAPTER 5 COLUMN 5.1 INTRODUCTION Columns are structural elements used primarily to support compressive loads. All practical columns are members subjected not only to axial load but also to bendin moments,
More informationDesign of Chevron Gusset Plates
017 SEAOC CONENTION PROCEEDINGS Desin of Chevron Gusset Plates Rafael Sali, Director of Seismic Desin Walter P Moore San Francisco, California Leih Arber, Senior Enineer American Institute of Steel Construction
More informationSabah Shawkat Cabinet of Structural Engineering Walls carrying vertical loads should be designed as columns. Basically walls are designed in
Sabah Shawkat Cabinet of Structural Engineering 17 3.6 Shear walls Walls carrying vertical loads should be designed as columns. Basically walls are designed in the same manner as columns, but there are
More informationFOOTING FIXITY EFFECT ON PIER DEFLECTION
Southern Illinois University Carbondale OpenSIUC Publications Department of Civil and Environmental Enineerin Fall 9--04 FOOTING FIXITY EFFECT ON PIER DEFECTION Jen-kan Kent Hsiao Yunyi Jian Southern Illinois
More informationChapter 8. Shear and Diagonal Tension
Chapter 8. and Diagonal Tension 8.1. READING ASSIGNMENT Text Chapter 4; Sections 4.1-4.5 Code Chapter 11; Sections 11.1.1, 11.3, 11.5.1, 11.5.3, 11.5.4, 11.5.5.1, and 11.5.6 8.2. INTRODUCTION OF SHEAR
More informationTABLE OF CONTANINET 1. Design criteria. 2. Lateral loads. 3. 3D finite element model (SAP2000, Ver.16). 4. Design of vertical elements (CSI, Ver.9).
TABLE OF CONTANINET 1. Design criteria. 2. Lateral loads. 2-1. Wind loads calculation 2-2. Seismic loads 3. 3D finite element model (SAP2000, Ver.16). 4. Design of vertical elements (CSI, Ver.9). 4-1.
More informationSlenderness Effects for Concrete Columns in Sway Frame - Moment Magnification Method (CSA A )
Slenderness Effects for Concrete Columns in Sway Frame - Moment Magnification Method (CSA A23.3-94) Slender Concrete Column Design in Sway Frame Buildings Evaluate slenderness effect for columns in a
More informationDesign of a Multi-Storied RC Building
Design of a Multi-Storied RC Building 16 14 14 3 C 1 B 1 C 2 B 2 C 3 B 3 C 4 13 B 15 (S 1 ) B 16 (S 2 ) B 17 (S 3 ) B 18 7 B 4 B 5 B 6 B 7 C 5 C 6 C 7 C 8 C 9 7 B 20 B 22 14 B 19 (S 4 ) C 10 C 11 B 23
More informationCHAPTER 5. T a = 0.03 (180) 0.75 = 1.47 sec 5.12 Steel moment frame. h n = = 260 ft. T a = (260) 0.80 = 2.39 sec. Question No.
CHAPTER 5 Question Brief Explanation No. 5.1 From Fig. IBC 1613.5(3) and (4) enlarged region 1 (ASCE 7 Fig. -3 and -4) S S = 1.5g, and S 1 = 0.6g. The g term is already factored in the equations, thus
More informationCHAPTER 4. Design of R C Beams
CHAPTER 4 Design of R C Beams Learning Objectives Identify the data, formulae and procedures for design of R C beams Design simply-supported and continuous R C beams by integrating the following processes
More informationε t increases from the compressioncontrolled Figure 9.15: Adjusted interaction diagram
CHAPTER NINE COLUMNS 4 b. The modified axial strength in compression is reduced to account for accidental eccentricity. The magnitude of axial force evaluated in step (a) is multiplied by 0.80 in case
More informationLecture-04 Design of RC Members for Shear and Torsion
Lecture-04 Design of RC Members for Shear and Torsion By: Prof. Dr. Qaisar Ali Civil Engineering Department UET Peshawar drqaisarali@uetpeshawar.edu.pk www.drqaisarali.com 1 Topics Addressed Design of
More informationCase Study in Reinforced Concrete adapted from Simplified Design of Concrete Structures, James Ambrose, 7 th ed.
ARCH 631 Note Set 11 S017abn Case Study in Reinforced Concrete adapted from Simplified Design of Concrete Structures, James Ambrose, 7 th ed. Building description The building is a three-story office building
More informationEarthquake Loads According to IBC IBC Safety Concept
Earthquake Loads According to IBC 2003 The process of determining earthquake loads according to IBC 2003 Spectral Design Method can be broken down into the following basic steps: Determination of the maimum
More informationLecture 4 Dynamic Analysis of Buildings
1 Lecture 4 Dynamic Analysis of Buildings Course Instructor: Dr. Carlos E. Ventura, P.Eng. Department of Civil Engineering The University of British Columbia ventura@civil.ubc.ca Short Course for CSCE
More informationDesign of Reinforced Concrete Beam for Shear
Lecture 06 Design of Reinforced Concrete Beam for Shear By: Civil Engineering Department UET Peshawar drqaisarali@uetpeshawar.edu.pk Topics Addressed Shear Stresses in Rectangular Beams Diagonal Tension
More informationDesign of Reinforced Concrete Beam for Shear
Lecture 06 Design of Reinforced Concrete Beam for Shear By: Prof Dr. Qaisar Ali Civil Engineering Department UET Peshawar drqaisarali@uetpeshawar.edu.pk 1 Topics Addressed Shear Stresses in Rectangular
More informationDESIGN AND DETAILING OF COUNTERFORT RETAINING WALL
DESIGN AND DETAILING OF COUNTERFORT RETAINING WALL When the height of the retaining wall exceeds about 6 m, the thickness of the stem and heel slab works out to be sufficiently large and the design becomes
More informationCivil Engineering Design (1) Design of Reinforced Concrete Columns 2006/7
Civil Engineering Design (1) Design of Reinforced Concrete Columns 2006/7 Dr. Colin Caprani, Chartered Engineer 1 Contents 1. Introduction... 3 1.1 Background... 3 1.2 Failure Modes... 5 1.3 Design Aspects...
More informationLecture-03 Design of Reinforced Concrete Members for Flexure and Axial Loads
Lecture-03 Design of Reinforced Concrete Members for Flexure and Axial Loads By: Prof. Dr. Qaisar Ali Civil Engineering Department UET Peshawar drqaisarali@uetpeshawar.edu.pk www.drqaisarali.com Prof.
More informationChapter. Materials. 1.1 Notations Used in This Chapter
Chapter 1 Materials 1.1 Notations Used in This Chapter A Area of concrete cross-section C s Constant depending on the type of curing C t Creep coefficient (C t = ε sp /ε i ) C u Ultimate creep coefficient
More informationFlexure: Behavior and Nominal Strength of Beam Sections
4 5000 4000 (increased d ) (increased f (increased A s or f y ) c or b) Flexure: Behavior and Nominal Strength of Beam Sections Moment (kip-in.) 3000 2000 1000 0 0 (basic) (A s 0.5A s ) 0.0005 0.001 0.0015
More informationSERVICEABILITY LIMIT STATE DESIGN
CHAPTER 11 SERVICEABILITY LIMIT STATE DESIGN Article 49. Cracking Limit State 49.1 General considerations In the case of verifications relating to Cracking Limit State, the effects of actions comprise
More informationDesign of Reinforced Concrete Structures (II)
Design of Reinforced Concrete Structures (II) Discussion Eng. Mohammed R. Kuheil Review The thickness of one-way ribbed slabs After finding the value of total load (Dead and live loads), the elements are
More informationRoadway Grade = m, amsl HWM = Roadway grade dictates elevation of superstructure and not minimum free board requirement.
Example on Design of Slab Bridge Design Data and Specifications Chapter 5 SUPERSTRUCTURES Superstructure consists of 10m slab, 36m box girder and 10m T-girder all simply supported. Only the design of Slab
More informationJob No. Sheet No. Rev. CONSULTING Engineering Calculation Sheet. Member Design - RC Two Way Spanning Slab XX
CONSULTING Engineering Calculation Sheet E N G I N E E R S Consulting Engineers jxxx 1 Material Properties Characteristic strength of concrete, f cu ( 60N/mm 2 ; HSC N/A) 35 N/mm 2 OK Yield strength of
More informationSupport Idealizations
IVL 3121 nalysis of Statically Determinant Structures 1/12 nalysis of Statically Determinate Structures nalysis of Statically Determinate Structures The most common type of structure an engineer will analyze
More informationRELIABILITY OF EXPOSED COLUMN-BASE PLATE CONNECTION IN SPECIAL MOMENT-RESISTING FRAMES
October 1-17, 008, Beijin, China RELIABILITY OF EXPOSED COLUMN-BASE PLATE CONNECTION IN SPECIAL MOMENT-RESISTING FRAMES A. Aviram 1, B. Stojadinovic, and A. Der Kiurehian 3 1 Ph.D. Candidate, Department
More informationLecture-09 Introduction to Earthquake Resistant Analysis & Design of RC Structures (Part I)
Lecture-09 Introduction to Earthquake Resistant Analysis & Design of RC Structures (Part I) By: Prof Dr. Qaisar Ali Civil Engineering Department UET Peshawar www.drqaisarali.com 1 Topics Introduction Earthquake
More informationAccordingly, the nominal section strength [resistance] for initiation of yielding is calculated by using Equation C-C3.1.
C3 Flexural Members C3.1 Bending The nominal flexural strength [moment resistance], Mn, shall be the smallest of the values calculated for the limit states of yielding, lateral-torsional buckling and distortional
More informationAssociate Professor. Tel:
DEPARTMENT OF CIVIL ENGINEERING IIT DELHI Dr. Suresh Bhalla Associate Professor Tel: 2659-1040 Email: Sbhalla@civil.iitd.ac.in FOUNDATIONS Geotechnical Engineer Structural Engineer Location and depth criteria
More informationThis Technical Note describes how the program checks column capacity or designs reinforced concrete columns when the ACI code is selected.
COMPUTERS AND STRUCTURES, INC., BERKELEY, CALIFORNIA DECEMBER 2001 CONCRETE FRAME DESIGN ACI-318-99 Technical Note This Technical Note describes how the program checks column capacity or designs reinforced
More informationChapter 14 - Fluids. Pressure is defined as the perpendicular force on a surface per unit surface area.
Chapter 4 - Fluids This chapter deals ith fluids, hich means a liquid or a as. It covers both fluid statics (fluids at rest) and fluid dynamics (fluids in motion). Pressure in a fluid Pressure is defined
More informationA Study of Computer Modeling Techniques to Predict the Response of Floor Systems Due to Walking
A Study of Computer Modelin Techniques to Predict the Response of Floor Systems Due to Walkin by Jason Daniel Perry Thesis submitted to the faculty of the Virinia Polytechnic Institute and State University
More informationStructural Steelwork Eurocodes Development of A Trans-national Approach
Structural Steelwork Eurocodes Development of A Trans-national Approach Course: Eurocode Module 7 : Worked Examples Lecture 0 : Simple braced frame Contents: 1. Simple Braced Frame 1.1 Characteristic Loads
More informationCodal Provisions IS 1893 (Part 1) 2002
Abstract Codal Provisions IS 1893 (Part 1) 00 Paresh V. Patel Assistant Professor, Civil Engineering Department, Nirma Institute of Technology, Ahmedabad 38481 In this article codal provisions of IS 1893
More informationDesign of reinforced concrete sections according to EN and EN
Design of reinforced concrete sections according to EN 1992-1-1 and EN 1992-2 Validation Examples Brno, 21.10.2010 IDEA RS s.r.o. South Moravian Innovation Centre, U Vodarny 2a, 616 00 BRNO tel.: +420-511
More informationChapter 6 Seismic Design of Bridges. Kazuhiko Kawashima Tokyo Institute of Technology
Chapter 6 Seismic Design of Bridges Kazuhiko Kawashima okyo Institute of echnology Seismic Design Loading environment (dead, live, wind, earthquake etc) Performance criteria for gravity (deflection, stresses)
More informationLecture-08 Gravity Load Analysis of RC Structures
Lecture-08 Gravity Load Analysis of RC Structures By: Prof Dr. Qaisar Ali Civil Engineering Department UET Peshawar www.drqaisarali.com 1 Contents Analysis Approaches Point of Inflection Method Equivalent
More informationAnnex - R C Design Formulae and Data
The design formulae and data provided in this Annex are for education, training and assessment purposes only. They are based on the Hong Kong Code of Practice for Structural Use of Concrete 2013 (HKCP-2013).
More informationCOLUMN INTERACTION EFFECT ON PUSH OVER 3D ANALYSIS OF IRREGULAR STRUCTURES
th World Conference on Earthquake Engineering Vancouver, B.C., Canada August -6, Paper No. 6 COLUMN INTERACTION EFFECT ON PUSH OVER D ANALYSIS OF IRREGULAR STRUCTURES Jaime DE-LA-COLINA, MariCarmen HERNANDEZ
More informationDesign of Beams (Unit - 8)
Design of Beams (Unit - 8) Contents Introduction Beam types Lateral stability of beams Factors affecting lateral stability Behaviour of simple and built - up beams in bending (Without vertical stiffeners)
More informationDesign Beam Flexural Reinforcement
COPUTERS AND STRUCTURES, INC., BERKELEY, CALIFORNIA DECEBER 2001 CONCRETE FRAE DESIGN ACI-318-99 Technical Note This Technical Note describes how this program completes beam design when the ACI 318-99
More informationCE5510 Advanced Structural Concrete Design - Design & Detailing of Openings in RC Flexural Members-
CE5510 Advanced Structural Concrete Design - Design & Detailing Openings in RC Flexural Members- Assoc Pr Tan Kiang Hwee Department Civil Engineering National In this lecture DEPARTMENT OF CIVIL ENGINEERING
More informationCHAPTER 4: BENDING OF BEAMS
(74) CHAPTER 4: BENDING OF BEAMS This chapter will be devoted to the analysis of prismatic members subjected to equal and opposite couples M and M' acting in the same longitudinal plane. Such members are
More informationBending and Shear in Beams
Bending and Shear in Beams Lecture 3 5 th October 017 Contents Lecture 3 What reinforcement is needed to resist M Ed? Bending/ Flexure Section analysis, singly and doubly reinforced Tension reinforcement,
More informationEUROCODE EN SEISMIC DESIGN OF BRIDGES
Brussels, 18-20 February 2008 Dissemination of information workshop 1 EUROCODE EN1998-2 SEISMIC DESIGN OF BRIDGES Basil Kolias Basic Requirements Brussels, 18-20 February 2008 Dissemination of information
More informationCHAPTER 4. ANALYSIS AND DESIGN OF COLUMNS
4.1. INTRODUCTION CHAPTER 4. ANALYSIS AND DESIGN OF COLUMNS A column is a vertical structural member transmitting axial compression loads with or without moments. The cross sectional dimensions of a column
More informationGeneral Comparison between AISC LRFD and ASD
General Comparison between AISC LRFD and ASD 1 General Comparison between AISC LRFD and ASD 2 AISC ASD and LRFD AISC ASD = American Institute of Steel Construction = Allowable Stress Design AISC Ninth
More informationExperiment 1: Simple Pendulum
COMSATS Institute of Information Technoloy, Islamabad Campus PHY-108 : Physics Lab 1 (Mechanics of Particles) Experiment 1: Simple Pendulum A simple pendulum consists of a small object (known as the bob)
More informationConsideration of Slenderness Effect in Columns
Conideration of Slenderne Effect in Column Read Ainment Text: Section 9.1; Code and Commentary: 10.10, 10.11 General Short Column - Slender Column - Strenth can be computed by coniderin only the column
More informationBeam Design and Deflections
Beam Design and Deflections tation: a = name for width dimension A = name for area Areq d-adj = area required at allowable stress when shear is adjusted to include self weight Aweb = area of the web of
More informationExam 2A Solution. 1. A baseball is thrown vertically upward and feels no air resistance. As it is rising
Exam 2A Solution 1. A baseball is thrown vertically upward and feels no air resistance. As it is risin Solution: Possible answers: A) both its momentum and its mechanical enery are conserved - incorrect.
More informationCAPACITY DESIGN FOR TALL BUILDINGS WITH MIXED SYSTEM
13 th World Conference on Earthquake Engineering Vancouver, B.C., Canada August 1-6, 24 Paper No. 2367 CAPACITY DESIGN FOR TALL BUILDINGS WITH MIXED SYSTEM M.UMA MAHESHWARI 1 and A.R.SANTHAKUMAR 2 SUMMARY
More informationVTU EDUSAT PROGRAMME Lecture Notes on Design of Columns
VTU EDUSAT PROGRAMME 17 2012 Lecture Notes on Design of Columns DESIGN OF RCC STRUCTURAL ELEMENTS - 10CV52 (PART B, UNIT 6) Dr. M. C. Nataraja Professor, Civil Engineering Department, Sri Jayachamarajendra
More informationspslab v3.11. Licensed to: STRUCTUREPOINT, LLC. License ID: D2DE-2175C File: C:\Data\CSA A Kt Revised.slb
X Z Y spslab v3.11. Licensed to: STRUCTUREPOINT, LLC. License ID: 00000-0000000-4-2D2DE-2175C File: C:\Data\CSA A23.3 - Kt Revised.slb Project: CSA A23.3 - Kt Torsional Stiffness Illustration Frame: Engineer:
More information5.4.3 Centre of stiffness and elastic displacements of the diaphragm
5.4.3 Centre of stiffness and elastic displacements of the diaphragm The current paragraph examines the special case of orthogonal columns in parallel arrangement. The general case is examined in Appendix
More informationEarthquake Simulation Tests on a 1:5 Scale 10 - Story RC Residential Building Model
Earthquake Simulation Tests on a 1:5 Scale 1 - Story RC Residential Building Model H. S. Lee, S. J. Hwang, K. B. Lee, & C. B. Kang Korea University, Seoul, Republic of Korea S. H. Lee & S. H. Oh Pusan
More informationSeismic Pushover Analysis Using AASHTO Guide Specifications for LRFD Seismic Bridge Design
Seismic Pushover Analysis Using AASHTO Guide Specifications for LRFD Seismic Bridge Design Elmer E. Marx, Alaska Department of Transportation and Public Facilities Michael Keever, California Department
More informationΙApostolos Konstantinidis Diaphragmatic behaviour. Volume B
Volume B 3.1.4 Diaphragmatic behaviour In general, when there is eccentric loading at a floor, e.g. imposed by the horizontal seismic action, the in-plane rigidity of the slab forces all the in-plane points
More informationGATE SOLUTIONS E N G I N E E R I N G
GATE SOLUTIONS C I V I L E N G I N E E R I N G From (1987-018) Office : F-16, (Lower Basement), Katwaria Sarai, New Delhi-110016 Phone : 011-65064 Mobile : 81309090, 9711853908 E-mail: info@iesmasterpublications.com,
More informationBehavior and Modeling of Existing Reinforced Concrete Columns
Behavior and Modeling of Existing Reinforced Concrete Columns Kenneth J. Elwood University of British Columbia with contributions from Jose Pincheira, Univ of Wisconsin John Wallace, UCLA Questions? What
More information1. Background. 2. Objectives of Project. Page 1 of 29
1. Background In close collaboration with local partners, Earthquake Damage Analysis Center (EDAC) of Bauhaus Universität Weimar initiated a Turkish German joint research project on Seismic Risk Assessment
More informationSPECIFIC VERIFICATION Chapter 5
As = 736624/(0.5*413.69) = 3562 mm 2 (ADAPT 3569 mm 2, B29, C6) Data Block 27 - Compressive Stresses The initial compressive strength, f ci, is the strength entered in the Material/Concrete input screen.
More informationFinite Element Analysis Prof. Dr. B. N. Rao Department of Civil Engineering Indian Institute of Technology, Madras. Module - 01 Lecture - 13
Finite Element Analysis Prof. Dr. B. N. Rao Department of Civil Engineering Indian Institute of Technology, Madras (Refer Slide Time: 00:25) Module - 01 Lecture - 13 In the last class, we have seen how
More informationENG1001 Engineering Design 1
ENG1001 Engineering Design 1 Structure & Loads Determine forces that act on structures causing it to deform, bend, and stretch Forces push/pull on objects Structures are loaded by: > Dead loads permanent
More informationCONSULTING Engineering Calculation Sheet. Job Title Member Design - Reinforced Concrete Column BS8110
E N G I N E E R S Consulting Engineers jxxx 1 Job Title Member Design - Reinforced Concrete Column Effects From Structural Analysis Axial force, N (tension-ve and comp +ve) (ensure >= 0) 8000kN OK Major
More informationFigure 1: Representative strip. = = 3.70 m. min. per unit length of the selected strip: Own weight of slab = = 0.
Example (8.1): Using the ACI Code approximate structural analysis, design for a warehouse, a continuous one-way solid slab supported on beams 4.0 m apart as shown in Figure 1. Assume that the beam webs
More informationJob No. Sheet No. Rev. CONSULTING Engineering Calculation Sheet
E N G I N E E R S Consulting Engineers jxxx 1 Material Properties Characteristic strength of concrete, f cu ( 60N/mm 2 ; HSC N/A) 35 N/mm 2 OK Yield strength of longitudinal steel, f y 460 N/mm 2 Yield
More informationAppendix J. Example of Proposed Changes
Appendix J Example of Proposed Changes J.1 Introduction The proposed changes are illustrated with reference to a 200-ft, single span, Washington DOT WF bridge girder with debonded strands and no skew.
More informationFinite Element Modelling with Plastic Hinges
01/02/2016 Marco Donà Finite Element Modelling with Plastic Hinges 1 Plastic hinge approach A plastic hinge represents a concentrated post-yield behaviour in one or more degrees of freedom. Hinges only
More informationPROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED
Ministry of Municipal Affairs PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED CHANGE NUMBER: SOURCE: B-04-01-15 Ontario-NBC CODE REFERENCE: Division B / 4.1.8.2. Division B / 4.1.8.4.
More information7 STATICALLY DETERMINATE PLANE TRUSSES
7 STATICALLY DETERMINATE PLANE TRUSSES OBJECTIVES: This chapter starts with the definition of a truss and briefly explains various types of plane truss. The determinancy and stability of a truss also will
More informationJob No. Sheet No. Rev. CONSULTING Engineering Calculation Sheet. Member Design - Steel Composite Beam XX 22/09/2016
CONSULTING Engineering Calculation Sheet jxxx 1 Member Design - Steel Composite Beam XX Introduction Chd. 1 Grade 50 more common than Grade 43 because composite beam stiffness often 3 to 4 times non composite
More informationPEER/SSC Tall Building Design. Case study #2
PEER/SSC Tall Building Design Case study #2 Typical Plan View at Ground Floor and Below Typical Plan View at 2 nd Floor and Above Code Design Code Design Shear Wall properties Shear wall thickness and
More informationAPPENDIX 1 MODEL CALCULATION OF VARIOUS CODES
163 APPENDIX 1 MODEL CALCULATION OF VARIOUS CODES A1.1 DESIGN AS PER NORTH AMERICAN SPECIFICATION OF COLD FORMED STEEL (AISI S100: 2007) 1. Based on Initiation of Yielding: Effective yield moment, M n
More informationABS Consulting Project No
SUPPORTING STRUCTURE DESIGN FOR BLAST RESISTANT WINDOWS CHILD DEVELOPMENT CENTER MOODY AFB, GA ABS Consulting Project No. 898 PREPARED FOR: ATLANTIC ENGINEERING SERVICE 6 ARLINGTON EXPRESSWAY BLDG. B,
More informationFailure in Flexure. Introduction to Steel Design, Tensile Steel Members Modes of Failure & Effective Areas
Introduction to Steel Design, Tensile Steel Members Modes of Failure & Effective Areas MORGAN STATE UNIVERSITY SCHOOL OF ARCHITECTURE AND PLANNING LECTURE VIII Dr. Jason E. Charalambides Failure in Flexure!
More informationFRAME ANALYSIS. Dr. Izni Syahrizal bin Ibrahim. Faculty of Civil Engineering Universiti Teknologi Malaysia
FRAME ANALYSIS Dr. Izni Syahrizal bin Ibrahim Faculty of Civil Engineering Universiti Teknologi Malaysia Email: iznisyahrizal@utm.my Introduction 3D Frame: Beam, Column & Slab 2D Frame Analysis Building
More informationPLATE GIRDERS II. Load. Web plate Welds A Longitudinal elevation. Fig. 1 A typical Plate Girder
16 PLATE GIRDERS II 1.0 INTRODUCTION This chapter describes the current practice for the design of plate girders adopting meaningful simplifications of the equations derived in the chapter on Plate Girders
More informationSeismic design of bridges
NATIONAL TECHNICAL UNIVERSITY OF ATHENS LABORATORY FOR EARTHQUAKE ENGINEERING Seismic design of bridges Lecture 3 Ioannis N. Psycharis Capacity design Purpose To design structures of ductile behaviour
More informationReinforced concrete structures II. 4.5 Column Design
4.5 Column Design A non-sway column AB of 300*450 cross-section resists at ultimate limit state, an axial load of 700 KN and end moment of 90 KNM and 0 KNM in the X direction,60 KNM and 27 KNM in the Y
More informationANALYZE In all three cases (a) (c), the reading on the scale is. w = mg = (11.0 kg) (9.8 m/s 2 ) = 108 N.
Chapter 5 1. We are only concerned with horizontal forces in this problem (ravity plays no direct role). We take East as the +x direction and North as +y. This calculation is efficiently implemented on
More informationInternal Internal Forces Forces
Internal Forces ENGR 221 March 19, 2003 Lecture Goals Internal Force in Structures Shear Forces Bending Moment Shear and Bending moment Diagrams Internal Forces and Bending The bending moment, M. Moment
More information8-5 Conjugate-Beam method. 8-5 Conjugate-Beam method. 8-5 Conjugate-Beam method. 8-5 Conjugate-Beam method
The basis for the method comes from the similarity of eqn.1 &. to eqn 8. & 8. To show this similarity, we can write these eqn as shown dv dx w d θ M dx d M w dx d v M dx Here the shear V compares with
More informationDownloaded from Downloaded from / 1
PURWANCHAL UNIVERSITY III SEMESTER FINAL EXAMINATION-2002 LEVEL : B. E. (Civil) SUBJECT: BEG256CI, Strength of Material Full Marks: 80 TIME: 03:00 hrs Pass marks: 32 Candidates are required to give their
More informationAPPENDIX D SUMMARY OF EXISTING SIMPLIFIED METHODS
APPENDIX D SUMMARY OF EXISTING SIMPLIFIED METHODS D-1 An extensive literature search revealed many methods for the calculation of live load distribution factors. This appendix will discuss, in detail,
More informationFATIGUE ASSESSMENT OF SHIP STRUCTURES
CLSSIFICTION NOTES No. 30.7 FTIGUE SSESSMENT OF SHIP STRUCTURES FEBRURY 003 Veritasveien 1, N-13 Høvik, Noray Tel.: +47 67 57 99 00 Fax: +47 67 57 99 11 FOREWORD is an autonomous and independent Foundation
More informationSoil-Structure Interaction in Nonlinear Pushover Analysis of Frame RC Structures: Nonhomogeneous Soil Condition
ABSTRACT: Soil-Structure Interaction in Nonlinear Pushover Analysis of Frame RC Structures: Nonhomogeneous Soil Condition G. Dok ve O. Kırtel Res. Assist., Department of Civil Engineering, Sakarya University,
More informationFLOW CHART FOR DESIGN OF BEAMS
FLOW CHART FOR DESIGN OF BEAMS Write Known Data Estimate self-weight of the member. a. The self-weight may be taken as 10 percent of the applied dead UDL or dead point load distributed over all the length.
More informationSERVICEABILITY OF BEAMS AND ONE-WAY SLABS
CHAPTER REINFORCED CONCRETE Reinforced Concrete Design A Fundamental Approach - Fifth Edition Fifth Edition SERVICEABILITY OF BEAMS AND ONE-WAY SLABS A. J. Clark School of Engineering Department of Civil
More informationSTRUCTURAL ANALYSIS CHAPTER 2. Introduction
CHAPTER 2 STRUCTURAL ANALYSIS Introduction The primary purpose of structural analysis is to establish the distribution of internal forces and moments over the whole part of a structure and to identify
More informationGeneration of Biaxial Interaction Surfaces
COPUTERS AND STRUCTURES, INC., BERKELEY, CALIFORNIA AUGUST 2002 CONCRETE FRAE DESIGN BS 8110-97 Technical Note This Technical Note describes how the program checks column capacity or designs reinforced
More informationCHAPTER 6: ULTIMATE LIMIT STATE
CHAPTER 6: ULTIMATE LIMIT STATE 6.1 GENERAL It shall be in accordance with JSCE Standard Specification (Design), 6.1. The collapse mechanism in statically indeterminate structures shall not be considered.
More informationSub. Code:
Important Instructions to examiners: ) The answers should be examined by key words and not as word-to-word as given in the model answer scheme. ) The model answer and the answer written by candidate may
More informationDesign of AAC wall panel according to EN 12602
Design of wall panel according to EN 160 Example 3: Wall panel with wind load 1.1 Issue Design of a wall panel at an industrial building Materials with a compressive strength 3,5, density class 500, welded
More information- Rectangular Beam Design -
Semester 1 2016/2017 - Rectangular Beam Design - Department of Structures and Material Engineering Faculty of Civil and Environmental Engineering University Tun Hussein Onn Malaysia Introduction The purposes
More informationDetailing. Lecture 9 16 th November Reinforced Concrete Detailing to Eurocode 2
Detailing Lecture 9 16 th November 2017 Reinforced Concrete Detailing to Eurocode 2 EC2 Section 8 - Detailing of Reinforcement - General Rules Bar spacing, Minimum bend diameter Anchorage of reinforcement
More informationA Mathematical Model for the Fire-extinguishing Rocket Flight in a Turbulent Atmosphere
A Mathematical Model for the Fire-extinuishin Rocket Fliht in a Turbulent Atmosphere CRISTINA MIHAILESCU Electromecanica Ploiesti SA Soseaua Ploiesti-Tiroviste, Km 8 ROMANIA crismihailescu@yahoo.com http://www.elmec.ro
More informationQUESTION BANK DEPARTMENT: CIVIL SEMESTER: III SUBJECT CODE: CE2201 SUBJECT NAME: MECHANICS OF SOLIDS UNIT 1- STRESS AND STRAIN PART A
DEPARTMENT: CIVIL SUBJECT CODE: CE2201 QUESTION BANK SEMESTER: III SUBJECT NAME: MECHANICS OF SOLIDS UNIT 1- STRESS AND STRAIN PART A (2 Marks) 1. Define longitudinal strain and lateral strain. 2. State
More information