Redline. Line protection by means of MCB s. Protection against overloads. Circuit Protection T1.2

Size: px
Start display at page:

Download "Redline. Line protection by means of MCB s. Protection against overloads. Circuit Protection T1.2"

Transcription

1 Redline Circuit Protection Line protection by means of MCB s Protective devices shall be capable of breaking any overcurrent up to and including the prospective shortcircuit current at the point where the device is installed. One of the protective devices complying with those conditions is the MCB. Protection against overloads According to IEC 0 protective devices shall be provided to break any overload current flowing in the circuit conductors before such a current could cause a temperature rise detrimental to insulation, joints or surrounding goods to the conductors. he operating characteristics of a device protecting a cable against overload shall satisfy the two following conditions: l B ln lz l.5 lz Circuit characteristic Protective device characteristic I B = Current for which the circuit is designed. I Z = Continuous current carrying capacity of the cable. In= Nominal current of the protective device. I = Current ensuring effective operation of the protective device. In and I are values provided by the manufacturer of the protective device. Calculation of the cable cross section shall be done following the national wiring regulations as well as the IEC 055 standard. he maximum current admissible by the conductor (Iz) depends of following factors:. Conductor crosssection.. Insulation material.. Composition of the conductor.. Ambient temperature. 5. Emplacement and canalisation. Protection of phase conductor Protection of overcurrent shall be provided for all phase conductors; it shall cause the disconnection of the conductor in which the overcurrent is detected, but not necessarily of other live conductor except in the following cases: In or N systems, for circuits supplied between phases and in which the neutral conductor is not distributed, overcurrent detection need to be provided for one of the phase conductors, provided that the following conditions are simultaneously fulfilled: here is, in the same circuit or on the supply side a differential protection intended to cause disconnection of all the phase conductors; he neutral conductor is not distributed from an artificial neutral point of the circuit situated on the load side of the differential protective device. In I systems it is mandatory to protect all the phase conductors. Protection of neutral conductor I system In I systems it is strongly recommended that the neutral conductor should not be distributed. However, when the neutral conductor is distributed, it is generally necessary to provide overcurrent detection for the neutral conductor of every circuit, which will cause the disconnection of all live conductors of the corresponding circuit, including the neutral conductor. his measure is not necessary if: he particular neutral conductor is effectively protected against shortcircuit by a prospective device placed on the supply side. or if the particular circuit is protected by a RCD with a rated residual current not exceeding 0, times the currentcarrying of the corresponding neutral conductor. his device shall disconnect all the live conductors of the corresponding circuit, including the neutral conductor. & N systems Where the cross sectional area of the neutral conductor is at least equal or equivalent to that of the phase conductors, it is not neccesary to provide overcurrent detection for the neutral conductor or a disconnecting device for that conductor. Where the cross sectional area of the neutral conductor is less than that of the phase conductor, it is neccesary to provide overcurrent detection for the neutral conductor, appropiate to the crosssectional area of that conductor; this connection shall cause the disconnection of the phase conductor, but not neccesarily of the neutral conductor.

2 However, overcurrent detection does not need to be provided for the neutral conductor if the following two conditions are simultaneously fulfilled: he neutral conductor is protected against shortcircuit by the protective device for the phase conductors of the circuit, and he maximum current likely to traverse the neutral conductor is, in normal service, clearly less than the value of the currentcarrying capacity of that conductor. System NC, PEN conductor NS separate PE & N conductors I S N =S F III+N P PN PN+ RCD P PN+ RCD S N <S F III+N P PN PN+ RCD P III P P+ RCD P I+N P PN PN+ RCD P S N = Crosssection of neutral conductor S F = Crosssection of phase conductor P = Protected pole RCD= Residual current device N = Neutral pole II P P+ RCD P Protection against shortcircuit According to IEC 0 protective devices shall be provided to break any shortcircuit current flowing in the circuit conductors before such a current could cause danger due to thermal and mechanical effects produced in conductors and connections. o consider that an installation is well protected against shortcircuits, it is required that the protective device complies with the following conditions: he breaking capacity shall not be less than the prospective shortcircuit current at the place of its installation. Icc: Maximum value of the shortcircuit current in that point. Icu: Shortcircuit capacity of the protective device. Calculation of Icc he value of the shortcircuit current flowing at the end of a cable depends on the shortcircuit current flowing at the begining of the cable (transformer terminals), the cross section as well as its length. echnical Data Icu Icc Letthrough energy I t smaller than admissible energy of the cable. According to IEC 07 there are some cases where the omission of devices for protection against overload is recommended for circuits supplying currentused equipment where unexpected opening of the circuit could cause danger. Examples of such a cases are: Excitation circuit of rotating machines. Supply circuit of lifting magnets. Secondary circuits of current transformers. As in those cases the Iu>Iz, it is necessary to verify the shortcircuit value at the point of the installation to ensure the protection (Icc min) Shortcircuit current at the transformer terminals (Icc 0 ) hree phase oil transformer 0V ransformer power kva Voltage Ucc in % In Arms Icc 0 ka rms

3 . Circuit Protection Calculation of the shortcircuit current in function of: Icc 0, crosssection and length of the conductor. he following table provides information to calculate approximately the shortcircuit current at a relevant point of the installation Values shorter than m or longer than km are not considered. All values are for voltage 0V. Correction coefficient Example Cable with cross section 95 mm Cu, 5 m length, and shortcircuit current at the transformer terminals of ka. Estimated shortcircuit current of ka at the end of the cable. Redline V 0V Line protection Copper conductor mm Length of the line in m Icc o (ka) x95 x x0 x85 x x95 x x0 x85 x Voltage K Icc at the origin of the cable Shortcircuit current at the end of the cable

4 echnical Data Line protection Aluminium conductor mm Length of the line Values shorter than m or longer than km are not considered. All values are for voltage 0V. Correction coefficient Example Cable with cross section 0 mm Al, 5 m length, and shortcircuit current at the transformer terminals of ka. Estimated shortcircuit current of 5.5 ka at the end of the cable x95 x x0 x85 x x95 x x0 x85 x Icc o (ka) Icc at the origin of the cable V 0V 8.5 Voltage K Shortcircuit current at the end of the cable

5 Redline Circuit Protection ransformers in parallel In the case of several transformers in parallel there are some points of the installation where the Icc is the sum of the shortcircuit currents provided by each transformer. he shortcircuit capacity of the protective devices shall be calculated taking into consideration the following criteria: Shortcircuit in A: Icu Icc + Icc Shortcircuit in F: Icu Icc Shortcircuit in D: Icu Icc + Icc + Icc Letthrough energy he standard IEC 0 describes that the current limiting of the conductors (K S ) shall be equal or greater than the letthrought energy (I t) quoted by the protective device. he K coefficient depends on the conductor insulation. S is the cross section of the conductor. Copper conductor Insulation K= Cross section mm PVC I t K S Rubber Polyethylene XLPE Maximum admissible value K S x Aluminium conductor Insulation PVC Rubber Polyethylene XLPE K= Cross section mm Maximum admissible value K S x

6 Maximum protected cable length in the event of shortcircuit (Icc minimum) he following values are applicable in case that the protective device does not exist or is overrated. hey are calculated according to the formula:. U. S Icc=. K. ρ.. L U: Voltage 0V 0,8: Reduction coefficient due to impedances S: Conductor cross section ρ: Cu resistivity: 0.0 Ω mm /m L: Conductor length K: Correction coeffecient Maximum protected cable length in case of shortcircuit For network x0 V without N, ripping characteristic C (Im: x In) It is possible to determinate the maximum cable length protected in the event of shortcircuit current in function of: he nominal current he nominal voltage he conductor characteristic he magnetic tripping characteristic of the protective device he shortcircuit current at any point of the installation shall be high enough to disconnect the protective device. o ensure the MCB disconnection, we needed to take into consideration the following table echnical Data In (A) S mm x95 x x0 x85 x x95 x x0 x85 x 0, Maximum protected length (m) for Cu conductor Example Network x0+n with a copper conductor of 95mm crosssection and using as a protection device a MCB C. Maximum cable length: Lmax= 89x8x=9m Correction coefficients ripping characteristic Voltage Conductor Cross section> mm Number of cables in parallel Curve B Curve D Curve Im K x x x /lm x V x 0V + N V PhaseN x 0V + N/ K x 8 x 8 x 8 x 0.9 Aluminium K x K x 0 x 5 x 0 x 0.75 x K5 x 0 x 0 x x 0 x..7

7 Redline Circuit Protection Characteristics according to EN/IEC 0898 Miniature Circuit Breakers are intended for the protection of wiring installations against both overloads and shortcircuits in domestic or commercial wiring installations where operation is possible by uninstructed people. ripping characteristic curves B, C and D Rated shortcircuit breaking capacity (Icn) Is the value of the shortcircuit that the MCB is capable of withstanding in the following test of sequence of operations: OtCO After the test the MCB is capable, without maintenance to withstand a dielectric strength test at a test voltage of 900V. Moreover the MCB shall be capable of tripping when loaded with.8 In within the time corresponding to 5 In but greater than 0.s. Service shortcircuit breaking capacity (Ics) Is the value of the shortcircuit that the MCB is capable of withstanding in the following test of sequence of operations: OtCOtCO After the test the MCB is capable, without maintenance to withstand a dielectric strength test at a test voltage of 0V. Moreover the MCB shall not trip when a current of In. he MCB shall trip within h when current is. In. Magnetic release An electromagnet with plunger ensures instantaneous tripping in the event of shortcircuit. he standard distinguishes three different types, following the current for instantaneous release: type B,C,D. O Represents an opening operation CO Represents a closing operation followed by an automatic opening. t Represents the time interval between two successive shortcircuit operations: minutes. he relation between the Rated shortcircuit capacity (Icn) and the Rated service shortcircuit breaking capacity (Ics) shall be as follows: lcn (A) Ics (A) lcn (A) B C D est current x ln 5 x ln 5 x ln x ln x ln x ln ** if In A, t < 8s ripping time 0. < t < 5s (In A) 0. < t < 90s (In > A) t < 0.s 0. < t < s (In A) 0. < t < s (In > A) t < 0.s 0. < t < s(**) (In A) 0. < t < 8s (In > A) t < 0.s Applications Only for resistive loads such as: electrical heating water heater stoves Usual loads such as: lighting socket outlets small motors Control and protection of circuits having important transient inrush currents (large motors) 000 > > lcn min lcn min. 70 hermal release he release is initiated by a bimetal strip in the event of overload. he standard defines the range of releases for specific overload values. Reference ambient temperature is C. est current. x ln ripping time t h (ln A) t h (ln > A).5 x ln t < h (ln A) t < h (ln > A) 5 x ln s < t < 0s (ln A) s < t < s (ln > A).8

8 Information on product according to EN/IEC 0898 Example: P MCB C characteristic A rade mark Approvals on shoulder Rated current proceeded by the symbol of the tripping curve Rated shortcircuit breaking capacity Icn Rated voltage Product name Electric diagram Catalogue number ONOFF indicator echnical Data Approvals on front echnical data according to IEC 097 Use of an MCB Safety terminals to avoid incorrect introduction of wires Contact position indicator Access to the mechanism for extensions oggle Bistable clip Rail for terminal indicator Bifunctional terminal for connectivity through busbars/wires

9 Redline Characteristics according to EN/IEC 097 Miniature Circuit Breakers are intended for the protection of the lines against both overloads and shortcircuits in industrial wiring installations where normally operation is done by instructed people. Circuit Protection ripping characteristic curves B, C, D and Z 0 0 ripping characteristic curve K (Z) (B) 5 8.5(C) (D and M) 8 (K)..5 Magnetic release An electromagnet with plunger ensures instantaneous tripping in the event of shortcircuit. he standard leaves the calibration of magnetic release to the manufacturer s discretion. GE offers instantaneous tripping ranges: Z: ln B: ln C: 8.5 In ( In for A) D and M: ln hermal release he release is initiated by a bimetal strip in the event of overload. he standard defines the range of release for two special overload values. Reference ambient temperature is: C for G0 and G0 (B, C, D) C for G and G (B, C, D) C for EP0 and EP (Z) Magnetic release An electromagnet with plunger ensures instantaneous tripping in the event of shortcircuit. he standard leaves the calibration of magnetic release to the manufacturer s discretion. GE offers instantaneous tripping ranges: K: ln Motors starting I = In, tripping > s. hermal release he release is initiated by a bimetal strip in the event of overload. he standard defines the range of release for two special overload values. Reference ambient temperature is: 5 C for EP0 and EP0 (K) est current. x ln ripping time t h (ln A) t h (ln > A) est current 5 x ln ripping time t h (ln A) t h (ln > A).5 x ln t < h (ln A) t < h (ln > A). x ln t < h (ln A) t < h (ln > A).

10 Shortcircuit test Rated ultimate shortcircuit breaking capacity (Icu) Is the value of the shortcircuit that the MCB is capable of withstanding in the following test of sequence of operations: OtCO After the test the MCB is capable, without maintenance, to withstand a dielectric strength test at a test voltage of 00V. Moreover the MCB shall be capable of tripping when loaded with,5 In within the time corresponding to In but greater than 0.s. Rated service shortcircuit breaking capacity (Ics) Is the value of the shortcircuit that the MCB is capable of withstanding in the following test of sequence of operations: OtCOtCO After the test the MCB is capable, without maintenance, to withstand a dielectric strength test at a test voltage of twice its rated insulation voltage with a minimum of 00V. A verification of the overload releases on In and moreover the MCB shall trip within h when current is.5 In (for In < A) and h (for In > A). ripping characteristic curves and their applications B: Protection of generators, long distance cables, resistive loads, people protection in N systems. C: General purpose, resistive and inductive loads. D: High inductive loads, transformers LV/LV with high peak current. K: Motors, pumps, fans, transformers, lamps groups, avoiding nuisance tripping. Z: Protection of electronic loads (semi conductors etc.) and secundary measurement circuits, long distance cables allowing cost saving with smaller section. Circuits feeding motors Advantages of Kcurve protection Curve K (EN/IEC 097) versus B, C, D (EN/IEC 0898) 0 I =. x In I =.5 x In hermal tripping. In.5 In Curve B,C,D: C Curve K: 5 C echnical Data O Represents an opening operation CO Represents a closing operation followed by an automatic opening. t Represents the time interval between two successive shortcircuit operations: minutes. Category A: Without a shorttime withstand current rating. Seconds Minutes K curve avoids nuisance tripping at the starting of motors (typical peak In) for a minimum of seconds. B,C and D don t garantee nuisance tripping. Magnetic tripping 8 In In Utilization category Application with respect to selectivity B C D 8 K A Circuit breakers not specifically intended for selectivity under shortcircuit conditions with respect to other shortcircuit protective devices in series on the load side, i.e. without an intentional shorttime delay provided for selectivity under shortcircuit conditions, and therefore without a shorttime withstand current rating according to.. B Circuit breakers specifically intended for selectivity under shortcircuit conditions with respect to other shortcircuit protective devices in series on the load side, i.e. without an intentional shorttime delay (which may be adjustable), provided for selectivity under shortcircuit conditions. Such circuitbreakers have a shorttime withstand current rating according to...

11 Redline Information on product according to EN/IEC 097 Example: EP P A 5 to Iu Circuit Protection rademark Rated current ripping curve Service category and calibration temperature Product name Catalogue number Electrical diagram Rated shortcircuit breaking capacity Icu/Ics Rated voltage IEC 097 standard Use of an MCB Contact position indicator Access to the mechanism for extensions oggle Circuit indicator.

12 ACCESS O HE MECHANISM FOR EXENSIONS Connection of the extensions. It is possible to couple any auxiliary contact, shunt trip, undervoltage release or motor driver either on the right or the left hand side, following the stackon configuration of the extensions in page. echnical Data OGGLE o switch the MCB ON or OFF CONAC POSIION INDICAOR Printing on the toggle to provide information of the real contact position. OOFF Contacts in open position. Ensure a distance between contacts > mm. ION Contacts in closed position. Ensure continuity in the main circuit..

13 Redline Definitions related to MCB s MCB= Miniature Circuit Breakers Circuit Protection Shortcircuit (making and breaking) capacity Alternating component of the prospective current, expressed by its r.m.s. value, which the circuitbreaker is designed to make, to carry for its opening time and to break under specified conditions. Ultimate or rated shortcircuit breaking capacity (Icn EN/IEC 0898) A breaking capacity for which the prescribed conditions, according to a specified test sequence do not include the capability of the MCB to carry times its rated current for the conventional time. Ultimate shortcircuit breaking capacity (Icu EN/IEC 097) A breaking capacity for which the prescribed conditions, according to a specified test sequence do not include the capability of the MCB to carry its rated current for the conventional time. Service shortcircuit breaking capacity (Ics EN/IEC 0898) A breaking capacity for which the prescribed conditions according to a specified test sequence include the capability of the MCB to carry times its rated current for the conventional time. Service shortcircuit breaking capacity (Ics EN/IEC 097) A breaking capacity for which the prescribed conditions according to a specified test sequence include the capability of the MCB to carry its rated current for the conventional time. Prospective current he current that would flow in the circuit, if each main current path of the MCB were replaced by a conductor of negligible impedance. Conventional nontripping current (Int) A specified value of current which the circuit breaker is capable of carrying for a specified time without tripping. Conventional tripping current (It) A specified value of current which causes the circuit breaker to trip within a specified time. Open position he position in which the predetermined clearance between open contacts in the main circuit of the MCB is secured. Closed position he position in which the predetermined continuity of the main circuit of the MCB is secured. Maximum prospective peak current (Ip) he prospective peak current when the initiation of the current takes place at the instant which leads to the highest possible value..

14 Notes echnical Data.

15 Redline Circuit Protection Selectivity An installation with some protective devices in series (a protective device must be placed at the point where a reduction of the cross sectional area of the conductors or another change causes modification in the characteristics of the installation) is considered as selective when, in the event of shortcircuit, the installation is interrupted only by the device which is immediately upstream of the fault point. Selectivity is ensured when the characteristic time/current of the upstream MCB (A) is above the characteristic time /current of the downstream MCB (B). he letthrough energy (I t) of the downstream protective device shall be lower than the one of the upstream protective device. Selectivity may be total or partial. otal selectivity Selectivity is total in the event of a shortcircuit fault and only disconnects the protective device B immediately upstream of the fault point. Partial selectivity Selectivity is partial when the no disconnection of the protective device (A) is ensured only up to a certain level of the current. In figure below is shown that selectivity is total up to the point of overlapping curves. From this point total selectivity can not be assured and selectivity curves based on tests by the manufacturer should be consulted. Disconnects B only Both devices could trip Consult selectivity tables by manufacturer.

16 Selectivity MCB's / MCB's C or G & RCBO's DM Curve B C5 C0 DM0 DM0 () Curve B G0 G0 G DME0 DME0 MCB s In A A A A A A A MCB s In A A A A A A A A A Curve C A 0.07 Curve C A 0.07 A 0. A 0. A A G0G0G Hti S90 A A A A A A.0.0 0A A 0A G0G0G Hti S90 A A A A A A A A 0A echnical Data MCB s Curve C G0G0G Hti S90 Curve C C5 C0 DM0 DM0 () In A A A A A A A A A A A A A A A A A A A 0A A 0A MCB s Curve C G0G0G Hti S90 Curve C G G5 G0 G0 G DME0 DME0 In A A A A A A A A A A A A A A A A A A A A A A A A A 0A () Icc limited to ka for C0, DM0, DM0 () Icc limited to ka for DM0 = otal : selective untill the Icu of the downstream device Example A combination of an MCB C with an upstream MCB C0 guarantees selectivity up to a shortcircuit level of 5 ka..7

17 Redline.8 Circuit Protection Selectivity Fuses glgg / MCB's G0 Example A combination of an MCB G C with an upstream fuse A guarantees selectivity up to a shortcircuit level of. ka. Fuses Curve B G0 DME0 In A A A A A A A A A A Fuses gggl A A A A A 5A... A A A A A Fuses Curve C G0 DME0 Fuses gggl A A A A A A 5.. A..9. A A A A Fuses Curve D G0 ype D In A A A A A A A A A A A A A Fuses gggl A 0. A A 0. A 0. A. 0. 5A.7 A..8 A.7. A A A In A A A A A A A A A A A A A

18 Selectivity Fuses BS / MCB's G0 Curve B G0 DME0 Curve C G0 DME0 Fuses In A A A A A A A A A Fuses In A A A A A A A A A Fuses BS A.8. Fuses BS A.. A A A A A A A A A 0A echnical Data Curve D G0 Fuses In A A A A A A A A A Fuses BS A.7.. A A A A A Example A combination of an MCB G C with an upstream fuse A guarantees selectivity up to a shortcircuit level of. ka..9

19 0 Circuit Protection Example A combination of an MCB G C with an upstream fuse A guarantees selectivity up to a shortcircuit level of. ka. Selectivity Fuses glgg / MCB's G0 Fuses Curve B G0 DME0 In A A A A A A A A A A Fuses gggl Fuses Curve C G0 DME0 Fuses gggl Fuses Curve D G0 ype D In A A A A A A A A A A A A A Fuses gggl A A A A A A.7... A A A A A A In A A A A A A A A A A A A A A A A A A A 5.. A..9. A A A A A A 0. A A 0. A 0. A A..8.7 A A A A A A 9.5 Redline

20 echnical Data Selectivity Fuses BS / MCB's G0 Fuses Curve B G0 DME0 In A A A A A A A A A Fuses BS A.8. A A A A A Fuses Curve C G0 DME0 In A A A A A A A A A Fuses BS A.. A A , 0A A A 9. Fuses Curve D G0 In A A A A A A A A A Fuses BS A.7.. A A A A A 9.

21 Redline Selectivity MCCB's Record / MCB's ElfaPlus A A DDL D0 D DH 0 DH D0L DL D0 DH0 D0L A A A 0A A A A A 0A A 0A 0A A 0A A A 0A D0S DH0S All D DH DL DH0 All DS D DHS DS D0S All All (A) Circuit Protection Curve B C50 / DM00 () Curve B G0 / DME Curve B G0 / DME0 Curve B G () Icc limited to ka for C0, DM0 Icc limited to ka for DM0 = otal : selective untill the Icu of the downstream device OR the Icu of the upstream device Example A combination of an MCB G C with an upstream D0 0A guarantees selectivity up to a shortcircuit level of ka. MCCB MCB D0 A G C

22 echnical Data Selectivity MCCB's Record / MCB's ElfaPlus Curve C C 50 / DM 00 () Curve C G5 Curve C G0 / DME0 Curve C G0 / DME0 Curve C Hti DDL D0 D DH 0 DH D0L DL D0 DH0 D0L A A A A A A A A A A.0 0A A 0A 0A A A A A 0A All All All All 0 (A) D DH DL DH0 DS DHS D0S D DS D0S DH0S () Icc limited to ka for C0, DM0 Icc limited to ka for DM0 = otal : selective untill the Icu of the downstream device OR the Icu of the upstream device

23 Circuit Protection Redline Redline G0 B/C curve G0 B/C curve G B/C curve Hti B/C curve S90 C curve In (A) Record Plus M type FD0E FD0S FD0N, H & L Selectivity limit in ka * = otal: selective unil the lowest Icu value of the two devices placed in series. Selectivity MCCB s Record Plus / MCB s Redline

24 5 echnical Data Record Plus M type FE0N, H & L ML FE0N, H & L MLD FE0N, H & L SMR FEN, H & L MLD FEN, H & L SMR Selectivity limit in ka * = otal: selective unil the lowest Icu value of the two devices placed in series. Selectivity MCCB s Record Plus / MCB s Redline Redline G0 B/C curve G0 B/C curve G B/C curve Hti B/C curve S90 C curve In (A) & 0

25 Redline Association (backup protection) Circuit Protection Association consist the use of an MCB with lower breaking capacity than the presumed one at the place of its installation. If another protective device installed upstream is coordinated so that the energy letthrough by these two devices does not exceed that which can be withstood without damage by the device placed downstream and the conductor protected by these devices. In the event of shortcircuit, both protective devices will disconnect, therefore the selectivity between them is considered as partial. Association reduces the cost of the installation in case of high shortcircuit currents. o obtain association between a breaker and a protective device, several conditions linked to the components characteristic must be fullfilled. hose have been defined by calculation and testing. SCPD SCPD: ShortCircuit Protective Device : Fuses / : MCB s Redline Icc max 0 ka* * ka, 0V with x 8 cartridge fuses : MCB s ElfaPlus : fuses Series In (A) min. rating (A) ype gg max. rating (A) min. rating (A) ype am max. rating (A) Curve C G0 G0 G Hti 0 8 (*) (*) (*) (*) (*) (*) 0 (*) (*) 0 (*) (*) (*) (*) (*) (*) (*) (*) (*) (*) * In case of MCB with B characteristics

26 Backup MCB's Redline / MCB's Redline Voltage 0/V, Icc max. In ka G5 G0 G0 Icu (ka) In (A) G0 ka... G0 ka... G ka < G ka... G ka... Hti ka... 0 Voltage /V, Icc max. In ka C5 C0 DM0 DM0 G5 G0DME0 G0DME0 Icu (ka) 5 In (A) G0 ka... G0 ka... G ka < G ka... G ka... Hti ka... echnical Data Backup MCCB's Record / MCB's Redline Voltage /V, Icc max. In ka C5 C0 G5 G0DME0 G0DME0 G G G Hti Icu (ka) 5 In (A) < > >... D 0kA 70 DL ka 90 D0 70kA DH0 ka D0L ka D 70kA DH ka DL ka D0 ka DH0 70kA D0L ka D 70kA DH ka DL ka Voltage 0/V, Icc max. In ka G5 G0 G0 G G G Hti Icu (ka) In (A) D ka DL 0kA D0 ka DH0 ka D0L 0kA D 5kA DH ka DL 0kA D0 5kA DH0 ka D0L 0kA D 5kA DH ka DL 0kA D0 ka DH0 70kA 7

27 Redline Backup RecordPlus / Redline Voltage /V, Icc max. In ka Circuit Protection C5 C0 G5 G0 G0 G G G Hti S90 Icu (ka) 5 Voltage 0/V, Icc max. In ka In (A) FD0E ka FD0S ka FD0N 85kA FD0H 0kA FD0L 0kA FEN 85kA FEH 0kA FEL 0kA G5 G0 G0 G G G Hti S90 Icu (ka) 5 In (A) FD0E ka FD0S ka FD0N ka FD0H ka FD0L 0kA FEN ka FEH ka FEL 0kA Selectivity: MCB S90 / Redline Voltage 0/V, Icc max. In ka EP0 EP0 EP EP EP Icu (ka) In (A) S90 ka 0 S90H ka 8

28 Use in DC Selection criteria he selection of an MCB to protect a D.C. installation depends on the following parameters: he nominal current he nominal voltage of the power supply, which determines the number of poles to switch the device he maximum shortcircuit current, to determine the shortcircuit capacity of the MCB ype of power supply In the event of an insulation fault, it is considered as an overload when one pole or an intermediate connection of the power supply is connected to earth, and the conductive parts of the installation are also connected to earth. Insulated generator In insulated generators there is no earth connection, therefore an earth leakage in any pole has no consequence. In the event of fault between the two poles (+ and ) there is a shortcircuit in the installation which value will depend on the impedance of the installation as well as of the voltage Un. Each polarity shall be provided with the appropriate number of poles. Generator with centre point earth connection In the event of shortcircuit between any pole (+ or ) and earth, there is a Isc<Isc max because the voltage is Un/. If the fault occurs between the two poles there is a shortcircuit in the installation which value depends on the impedance of the installation as well as the voltage Un. Each polarity shall be provided with the necessary number of poles to break the maximum shortcircuit at Un/. echnical Data Generator with one earthed pole In the event of a fault occuring in the earthed pole () there is no consequence. In the event of a fault between the two poles (+ and ) or between the pole + and earth, then there is a shortcircuit in the installation which value depends on the impedance of the installation as well as of the voltage Un. he unearthed pole (+) shall be provided with the necessary numbers of poles to break the maximum shortcircuit. 9

29 Redline Circuit Protection Use of standard MCB in DC (acc. to IEC 097) For MCB s designed to be used in alternating current but used in installations in direct current, the following should be taken into consideration: For protection against overloads it is necessary to connect the two poles to the MCB. In these conditions the tripping characteristic of the MCB in direct current is similar in alternating current. For protection against shortcircuits it is necessary to connect the two poles to the MCB. In these Use in DC selection table Series G0 () G0 () G () EP0UC Rated current (A)...A...A...A...A conditions the tripping characteristic of the MCB in direct current is % higher than the one in alternating current. Use of special MCB (UC) in DC (acc. to IEC 0898) (UC= Universal Current) For MCB s designed to work in both alternating and direct current, it is necessary to respect the polarity of the terminals since the device is equipped with a permanent magnet. 0 V pole V poles in series V pole V poles in series Icu (ka) Icu (ka) Icu (ka) Icu (ka) () Nominal voltage for G0/G0/G: 8/VDC Maximum voltage for G0/G0/G: 5/VDC Installation of MCB s series EP0 UC in direct current Example of utilisation for maximum voltage between lines according to the number of poles MCB s EP 0 UC P EP 0 UC P EP 0 UC P * Maximum voltage between lines Maximum voltage between lines and earth Power supply at bottom terminals V V V V V V () V V V (poles inversion) V Power supply at top terminals () Negative pole connected to earth * On request Example of utilisation for different voltages between line and earth than between two lines MCB s EP 0 UC P EP 0 UC P * Maximum voltage between lines Maximum voltage between lines and earth V Multipole breaking V Generator with centre point earth connection V Multipole breaking V Generator without earth connection or with one earthed pole V Multipole breaking V Generator without earth connection or with one earthed pole * On request.

30 Influence of ambient air temperature on the rated current he thermal callibration of the MCB s was carried out at ambient temperature of C. Ambient temperatures different from C influence the bimetal and this results in earlier or later thermal tripping. 0,5 A A echnical Data A A Influence of air temperature (IEC/EN 0898) : P (Single pole) : mp (Multipole) pole In Calibrated at C n poles In Calibrated at C

31 Redline Circuit Protection ripping current as a function of the frequency All the MCB s are designed to work at frequencies of 0 Hz, therefore to work at different values, consideration must be given to the variation of the tripping characteristics. he thermal tripping does not change with variation of the frequency but the magnetic tripping values can be up to % higher than the ones at 0 Hz. For DC current magnetic tripping is % higher. ripping current variation 0Hz 0Hz. 0Hz 0Hz. 0Hz Limitation curves Letthrough energy I t he limitation capacity of a MCB in shortcircuit conditions, is its capacity to reduce the value of the letthrough energy that the shortcircuit would be generating. Peak current lp It is the value of the maximum peak of the shortcircuit current limited by the MCB. Power losses he power losses are calculated by measuring the voltage drop between the incoming and the outgoing terminals of the device at rated current. Power losses per pole MCB Series G In (A) 8 Voltage drop (V) Energy loss Pw (W) Resistance Z (mohm) Power losses per pole MCB Series Hti A B Icc peak assumed Icc assumed Icc peak limited Icc limited See page. up to. In (A) Voltage drop (V) Energy loss Pw (W) Resistance Z (mohm) Power losses per pole MCB Series C In (A) Voltage drop (V) Energy loss Pw (W) Resistance Z (mohm)

32 C5C0 Curve P+N / module I t Letthrough energy at V Letthrough energy I t (A s) echnical Data.

33 Redline G5 Curve C P, P+N, P, P, P I t Letthrough energy at /0 V G5 Curve C P I t Letthrough energy at V Circuit Protection Letthrough energy I t (A s) Letthrough energy I t (A s) Ip Limited peak current at /0 V Limited peak current I p (ka) 7 5 C C C C C C C C C C C 0.

34 G5 Curve B P, P+N, P, P, P I t Letthrough energy at /0 V G5 Curve B P I t Letthrough energy at V Letthrough energy I t (A s) Letthrough energy I t (A s) echnical Data Ip Limited peak current at /0 V Limited peak current I p (ka) 7 5 B B B B B B B B B 0.5

35 Redline G0 Curve B P, P+N, P, P, P I t Letthrough energy at /0 V G0 Curve B P I t Letthrough energy at V Circuit Protection Letthrough energy I t (A s) Letthrough energy I t (A s) Ip Limited peak current at /0 V Limited peak current I p (ka) 7 5 B B B B B B B B B 0.

36 G0 Curve C P, P+N, P, P, P I t Letthrough energy at /0 V G0 Curve C P I t Letthrough energy at V Letthrough energy I t (A s) Letthrough energy I t (A s) echnical Data Ip Limited peak current at /0 V Limited peak current I p (ka) 7 5 C C C C C C C C C C C 0.7

37 Redline G0 Curve D P, P+N, P, P, P I t Letthrough energy at /0 V G0 Curve D P I t Letthrough energy at V Circuit Protection Letthrough energy I t (A s) Letthrough energy I t (A s) Ip Limited peak current at /0 V Limited peak current I p (ka) 7 5 D D D D D D D D D D D 0.8

38 G0 Curve B P, P+N, P, P, P I t Letthrough energy at /0 V G0 Curve B P I t Letthrough energy at V Letthrough energy I t (A s) 5 Letthrough energy I t (A s) echnical Data 5 0 Ip Limited peak current at /0 V Limited peak current I p (ka) 7 5 B B B B B B B B B 0.9

39 Redline G0 Curve C P, P+N, P, P+N I t Letthrough energy at /0 V G0 Curve C P I t Letthrough energy at V Circuit Protection Letthrough energy I t (A s) 5 Letthrough energy I t (A s) 5 0 Ip Limited peak current at /0 V Limited peak current I p (ka) C C C C C C C C C C C 0.

40 G0 Curve B P, P+N, P, P, P I t Letthrough energy at /0 V G0 Curve B P I t Letthrough energy at V Letthrough energy I t (A s) Letthrough energy I t (A s) echnical Data Ip Limited peak current at /0 V Limited peak current I p (ka) D D D D D D D D D D D 0.

41 Redline G Curve B P, P, P, P I t Letthrough energy at /0 V G Curve B P I t Letthrough energy at V Circuit Protection Letthrough energy I t (A s) Letthrough energy I t (A s) Ip Limited peak current at /0 V Limited peak current I p (ka) B B B B B B B B B 0.

42 G Curve C P, P, P, P I t Letthrough energy at /0 V G Curve C P I t Letthrough energy at V Letthrough energy I t (A s) Letthrough energy I t (A s) echnical Data Ip Limited peak current at /0 V Limited peak current I p (ka) 8 C C C C C C C C C C C 0.

43 Redline G Curve D P, P, P, P I t Letthrough energy at /0 V G Curve D P I t Letthrough energy at V Circuit Protection Letthrough energy I t (A s) Letthrough energy I t (A s) Ip Limited peak current at /0 V Limited peak current I p (ka) D D D D D D D D D D D 0.

44 ripping curves acc. EN/IEC 0898 he following tables show the average tripping curves of the GE MCB s based on the thermal calibration as well as the magnetic characteristic. Curve B Curve D echnical Data x In x In Curve C x In.5

45 Redline Selective circuit breaker S90 Application Fig. No fault main contact: K closes, K opens (KK closed) Parallel current path Circuit Protection he selective circuit breaker ElfaPlus S90 often serves as gang switches in distribution boards with the highest demand on selectivity and operating convenience. he ElfaPlus S90 are used as higher protection element in a installation with different MCB s. he S90 breaker are equipped additional to the main current path with another two circuits: Parallel current path that contains a resistor R for current limitation. Measuring circuit with magnet impulses to close the main contact Function he selective main circuit breaker ElfaPlus S90 is a miniature circuit breaker employed as superordinate protective element in series with traditional MCB s. he unit, in order to switch selectively has in addition to the main current path (fig. ) another paralelle current path with a currentlimiting resistor R and a measuringcircuit with a solnenoid drive to close the main contact. Manual closing (fig. and fig. ) If the selective circuit breaker is manually switchedon, first of all the contact K closes and the operating current flows via the parallel current path. At the same time contact K and hence the measuring circuit are closed (fig. ). Only then is the main contact K closed and the operating current flows via the main current path (fig. ). As the parallel current path owing to resistor R has a higher resistance than the main current path, no mentionable current continues to flow there. On K closing, K in the measuring circuit is reopened. Main current path Measuring circuit Fault closure lockout (fig. ) If the MCB is closed onto an existing fault, the measuring circuit that measures the voltage between line and neutral at the output of the ElfaPlus S90,prevents the main contact K closing. he breaker can not be closed onto the fault and no high current can flow. After a short time contacts K and K are reopened due to the bimetal trip B and the current limited by resistor R in the parallel current path (maximum 5 times rated current) is interrupted. his fault closure lockout thus protects the installation but also the operating personel. Fig. Existing fault: K does not close. B opens K and k after max. s. Parallel current path Main current path Measuring circuit Fig. Manual closing: K and K close Parallel current path Main current path Measuring circuit Selective fault tripping (fig. and fig. ) If the selective circuit is switchedon (K closed) and a fault occurs downstream of an MCB, the fault current is interrupted either by the MCB alone or with the help of the operating main contact K. Contact K remains closed, and current can still flow via parallel current path, even when the arc at the main contact K is quenched (fig. ). If the downstream MCB has isolated the fault from the installation, in the ElfaPlus S90 the main contact is reclosed (fig. ). Loads lying parallel to the faulted circuit are immediatelly supplied with current, at first via the parallel current path and shortly after again via the main current path..

46 Fault upstream of MCB (fig. and fig. ) If the fault occurs between the ElfaPlus S90 and the downstream MCB (or if some reasons a fault behind a miniature circuit breaker is not cleared by it), after quenching of the arc a current limited by resistor R still flows at the contact point K via the parallel current path (fig. ) untill contact K is also opened due to the bimetal B (fig. ) Opening on overload (fig. 5) If an overload current flows fot too long, the bimetal trip B in the main current path operates and opens contact K and K in the main and parallel current paths. Fig. 5 Overload: B opens and K and K Fig. Fault while unit closed: K opens and K closes Parallel current path Main current path Parallel current path Main current path Measuring circuit echnical Data Measuring circuit ripping curve Curve C according to EN/IEC 0898 Manual opening On manual opening the contacts are opened not only in the main current path but also in the parallel current path (K and K) t(s).7

47 Redline Circuit Protection ext for specifiers MCB Series G0/0 According to EN/IEC 0898 standard For DIN rail mounting according to DIN EN/IEC 0; EN/IEC 0; future EN/IEC 07; IEC 07 (top hat rail 5 mm) Grid distance 5 mm Working ambient temperature from C up to + C Approved by CEBEC, VDE, KEMA, IMQ... pole is a module of 8 mm wide Nominal rated currents are: ////////////// A ripping characteristics: B,C,D,K Number of poles: P, P+N, P, P, P+N, P he shortcircuit breaking capacity is: /,5//kA, energy limiting class erminal capacity from up to 5mm rigid wire or,5 up to mm flexible wire. Screw head suitable for flat or Pozidriv screwdriver Can be connected by means of both pin or fork busbars on bottom terminals he toggle can be sealed in ON or OFF position Rapid closing Both incoming and outgoing terminals have a protection degree of IP and they are sealable Isolator function thanks to the printing Red/Green on the toggle. Maximum voltage between two phases; V~ Maximum voltage for utilisation in DC current: 8 V P and V P wo position rail clip Mechanical shock resistance g (direction x, y, z) minimum 8 shocks 5 ms halfsinusoidal acc. to IEC 0087 Vibrations resistance: g (direction x, y, z) minimum min. according to IEC 008 Extensions can be added on both left or right hand side Auxiliary contact Shunt trip Undervoltage release Motor operator Panel board switch MCB s have a circuit indicator for easy circuit identification Addon RCD can be coupled MCB Series G According to EN/IEC 097. standard For DIN rail mounting according to DIN EN/IEC 0; EN/IEC 0; future EN/IEC 07; IEC 07 (top hat rail 5 mm) Working ambient temperature from C up to + C pole is a module of 8 mm wide Nominal rated currents are: 0,5////////////// A ripping characteristics: B,C Number of poles: P, P, P, P he shortcircuit capacity is: /// ka erminal capacity from up to 5mm rigid wire or,5 up to mm flexible wire Screw head suitable for flat or Pozidriv screwdriver Can be connected by means of both pin or fork busbars on bottom terminals he toggle can be sealed in ON or OFF position Rapid closing Both incoming and outgoing terminals have a protection degree of IP and they are sealable Isolator function thanks to the printing Red/Green on the toggle. Maximum voltage between two phases; V~ Maximum voltage for utilisation in DC current: 8 V P and V P wo position rail clip Mechanical shock resistance g (direction x, y, z) minimum 8 shocks 5 ms halfsinusoidal acc. to IEC 0087 Vibrations resistance: g (direction x, y, z) minimum min. according to IEC 008 Extensions can be added on both left or right hand side Auxiliary contact Shunt trip Undervoltage release Motor operator Panel board switch MCB s have a circuit indicator for easy circuit identification Addon RCD can be coupled.8

48 MCB Series EP0 UC According to EN/IEC 0898 standard For DIN rail mounting according to DIN EN/IEC 0; EN/IEC 0; future EN/IEC 07; IEC 07 (top hat rail 5 mm) Grid distance 5 mm Working ambient temperature from C up to + C pole is a module of 8 mm wide Nominal rated currents are: 0,5////////////// A ripping characteristics: B, C Number of poles: P, P he shortcircuit breaking capacity is: ka, energy limiting class erminal capacity from up to 5mm rigid wire or,5 up to mm flexible wire Screw head suitable for flat or Pozidriv screwdriver Can be connected by means of both pin or fork busbars on top or bottom terminals he toggle can be sealed in ON or OFF position Rapid closing Both incoming and outgoing terminals have a protection degree of IP and they are sealable Isolator function thanks to the printing Red/Green on the toggle. Maximum voltage: P V P V. Poles in series wo position rail clip Mechanical shock resistance g (direction x, y, z) minimum 8 shocks 5 ms halfsinusoidal according to IEC 0087 Vibrations resistance: g (direction x, y, z) minimum min. according to IEC 008 Extensions can be added on both left or right hand side Auxiliary contact Shunt trip Undervoltage release Motor operator Panel board switch MCB s have a circuit indicator for easy circuit identification Addon RCD can be coupled MCB Series Hti According to EN/IEC 097. standard For DIN rail mounting according to DIN EN/IEC 0; EN/IEC 0; future EN/IEC 07; IEC 07 (top hat rail 5 mm) Working ambient temperature from C up to + C pole is a module,5 module (7mm) Nominal rated currents are: /0/A ripping characteristics: B, C, D Number of poles: P, P, P, P he shortcircuit capacity is: ka erminal capacity from,5 up to 70mm he toggle can be sealed in ON or OFF position Both incoming and outgoing terminals have a protection degree of IP and they are sealable Isolator function thanks to the printing red/green on the toggle. It can be used as main switch Maximum voltage between two phases: V~ wo position rail clip Mechanical shock resistance g (direction x, y, z) minimum 8 shocks 5 ms halfsinusoidal according to IEC 0087 Extensions can be added Auxiliary contact Shunt trip Endurance: Mechanical: 00 operations Electrical: 00 operations Addon RCD can be coupled echnical Data.9

Sealing possibility Electrical endurance (ops) Mechanical endurance (ops) Overvoltage category Standards

Sealing possibility Electrical endurance (ops) Mechanical endurance (ops) Overvoltage category Standards Miniature circuit breaker ETIMAT 7,7 0.5 Rated voltage Rated current Rated frequency Rated short-circuit capacity Energy limiting class characteristic Build-in width Mounting on the rail 0/00 V AC, max.

More information

Miniatur Circuite Breakers (MCB)

Miniatur Circuite Breakers (MCB) Redline Miniatur Circuite Breakers (MCB) Technical data MCB s Series Standards Tripping characteristics Nominal current Calibration temperature Number of poles (#mod) Neutral pole protected Nominal voltage

More information

TeSys circuit-breakers

TeSys circuit-breakers Presentation Thermal-magnetic motor circuit-breakers types GV2, GV and GV7 GV2-ME, GV2-P, GV-ME and GV7-R motor circuit-breakers are -pole thermal-magnetic circuit-breakers specifically designed for the

More information

Redline Unibis : the solution Circuit protection

Redline Unibis : the solution Circuit protection 2 circuits in 1 mo Redline Unibis : the solution ircuit protection Unibis compact Ms are one of the latest introductions in the Redline range and are developed to reduce the size of the distribution board

More information

90 MCB MODULAR CIRCUIT BREAKERS FOR CIRCUIT PROTECTION

90 MCB MODULAR CIRCUIT BREAKERS FOR CIRCUIT PROTECTION MCB - MTC - MT - MTHP Technical data TYPE MTC MT MTC45 MTC60 MTC100 MT 45 MT 60 Rated current (In) (A) 2-32 6-32 6-32 6-40 1-63 Utilization category A A A A A Rated operational voltage (Ue) (V) 230/400-240/415

More information

90 MCB range Modular circuit breakers for circuit protection

90 MCB range Modular circuit breakers for circuit protection MCB - MTC - MT - MTHP Technical data TYPE MTC MT MTC45 MTC60 MTC100 MT 45 MT 60 Rated current (In) (A) 2-32 6-32 6-32 6-40 1-63 Utilization category A A A A A Rated operational voltage (Ue) (V) 230 / 400

More information

MCB NB1-63H Miniature Circuit Breaker

MCB NB1-63H Miniature Circuit Breaker NB-H Miniature Circuit Breaker. General. Function protection of circuits against short-circuit currents, protection of circuits against overload currents, switch, isolation, NB-H circuit-breakers are used

More information

UL 1077 DIN Rail Supplementary Protectors

UL 1077 DIN Rail Supplementary Protectors UL 0 DIN Rail Supplementary Protectors Product Overview UL 0 DIN Rail Supplementary Protectors PRODUCT OVERVIEW Product Overview Standard Features WMZS breaker terminals provide finger and back-of-hand

More information

Miniature circuit breakers. Residential current circuit breaker. Busbar systems. Comfort functions/energy control. Residential enclosures

Miniature circuit breakers. Residential current circuit breaker. Busbar systems. Comfort functions/energy control. Residential enclosures ...5..8.0....8.0....8.0....5 Five good reasons to appreciate the EG MCB's Benefits of the MCB's Series E90 Selection table Series E90N Miniature circuit breakers k Series E90E Miniature circuit breakers.5k

More information

Miniature circuit breakers. Residual current circuit breakers. Busbar systems. Comfort functions/energy control. Residential enclosures

Miniature circuit breakers. Residual current circuit breakers. Busbar systems. Comfort functions/energy control. Residential enclosures Residual current circuit breakers B...5 Five good reasons to appreciate the EG MCBs Benefits of the MCBs Series E90 Selection table Busbar systems C..8.....8.... Series E90N k Series E90E.5k Series E90

More information

Electrical installation solutions for buildings Technical details RCDs

Electrical installation solutions for buildings Technical details RCDs /1 Electrical installation solutions for buildings Technical details RCDs Index Functions and classification criteria for RCDs / Limitation of specific let-through energy I t /5 Peak current Ip /9 Coordination

More information

Thermal-Magnetic Circuit Breaker 2210-T2...

Thermal-Magnetic Circuit Breaker 2210-T2... Thermal-Magnetic Circuit Breaker 0-T... Description One, two and three pole thermal-magnetic circuit breakers with trip-free mechanism and toggle actuation (S-type TM CBE to EN 6094/IEC 94). Featuring

More information

C120N circuit-breakers B, C and D curves EN 60898/EN 61009: IEC : 10 ka

C120N circuit-breakers B, C and D curves EN 60898/EN 61009: IEC : 10 ka C0N circuit-breakers B, C and D curves EN 09/EN 009: 0000 - IEC 097-: 0 ka function # protection of cables against overloads and short-circuits in final distribution # manual control and isolation # earth

More information

C60N circuit breakers0 B, C and D curves IEC 60898: 6000 A, IEC : 10 ka

C60N circuit breakers0 B, C and D curves IEC 60898: 6000 A, IEC : 10 ka C0N circuit breakers0 B, C and s IEC 0898: 000 A, IEC 097-: 0 ka Function b The circuit-breakers combine the following functions: v protection of circuits against short-circuit currents v protection of

More information

Electrical installation solutions for buildings Technical details Arc Fault Detection Devices

Electrical installation solutions for buildings Technical details Arc Fault Detection Devices /1 Electrical installation solutions for buildings Technical details Arc Fault Detection Devices Index Functions and classification criteria for AFDD /2 Power loss, derating and performance in altitude

More information

5SJ4...-.HG Circuit Breakers to IEC and UL 489

5SJ4...-.HG Circuit Breakers to IEC and UL 489 Siemens AG 009 5SJ...-.HG Circuit Breakers to IEC and UL 89 BETA Low-Voltage Circuit Protection Compliance with industry standards is a must in today's manufacturing environment. Worldwide acceptance is

More information

Siemens AG Miniature Circuit Breakers. Totally Integrated Power SENTRON. Configuration. Edition 10/2014. Manual. siemens.

Siemens AG Miniature Circuit Breakers. Totally Integrated Power SENTRON. Configuration. Edition 10/2014. Manual. siemens. Siemens AG 05 Totally Integrated Power SENTRON Configuration Manual Edition 0/0 siemens.com/lowvoltage Siemens AG 05 Siemens AG 05 Introduction 5SL miniature circuit breakers 5SY and 5SP miniature circuit

More information

Thermal-Magnetic Circuit Breaker 2210-S2..

Thermal-Magnetic Circuit Breaker 2210-S2.. Thermal-Magnetic Circuit Breaker -S.. Description One, two and three pole thermal-magnetic circuit breakers with trip-free mechanism and toggle actuation (S-type TM CBE to EN 60934/IEC 934). Designed for

More information

5SP and 5SY Supplementary Protection UL 1077

5SP and 5SY Supplementary Protection UL 1077 Product Guide 5SP and 5SY Supplementary Protection UL 077 for North merican and International applications usa.siemens.com/5sy Table of contents Certifications, standards, features and description Characteristic

More information

Thermal-Magnetic Circuit Breaker 2210-S2..

Thermal-Magnetic Circuit Breaker 2210-S2.. Thermal-Magnetic Circuit Breaker -S.. Description One, two and three pole thermal-magnetic circuit breakers with trip free mechanism and toggle actuation (S-type TM CBE to EN 6094/IEC 94). Designed for

More information

Thermal-Magnetic Circuit Breaker 2210-S2...

Thermal-Magnetic Circuit Breaker 2210-S2... Thermal-Magnetic Circuit Breaker 0-S... Description One, two and three pole thermal-magnetic circuit breakers with trip free mechanism and toggle actuation (S-type TM CBE to EN 60934/IEC 934). Designed

More information

Thermal-Magnetic Circuit Breaker 2210-S2...

Thermal-Magnetic Circuit Breaker 2210-S2... Description One, two and three pole thermal-magnetic circuit breakers with trip free mechanism and toggle actuation (S-type TM CBE to EN 6094/IEC 94). Designed for panel or plug-in mounting. Available

More information

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-T...

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-T... Magnetic and Hydraulic-Magnetic Circuit Breaker 830-T... Description ngle, two and three pole magnetic and hydraulic-magnetic circuit breakers with trip-free mechanism and toggle actuation. A choice of

More information

FAZ tripping characteristics at 30 C: B, C, D to IEC/EN FAZ tripping characteristics at 30 C: R to IEC/EN

FAZ tripping characteristics at 30 C: B, C, D to IEC/EN FAZ tripping characteristics at 30 C: R to IEC/EN FAZ, AZ High-Capacity Tripping Characteristics Moeller HPL011-001/00 1/07 FAZ tripping characteristics at 0 C: B, C, D to IEC/EN 0 9 FAZ tripping characteristics at 0 C: R to IEC/EN 0 97 t [s] 700 00 100

More information

Thermal-Magnetic Circuit Breaker 2210-S2..

Thermal-Magnetic Circuit Breaker 2210-S2.. Thermal-Magnetic Circuit Breaker -S.. Description One, two and three pole thermal-magnetic circuit breakers with trip free mechanism and toggle actuation (S-type TM CBE to EN 60934/IEC 934). Designed for

More information

THE DIMENSIONING OF ELECTRICAL CONDUCTORS FOR USE IN "PANEL BOARDS" ADDRESSED TO HAZARDOUS AREAS - PART THREE

THE DIMENSIONING OF ELECTRICAL CONDUCTORS FOR USE IN PANEL BOARDS ADDRESSED TO HAZARDOUS AREAS - PART THREE July 04 THE DIMENSIONING OF ELECTRICAL CONDUCTORS FOR USE IN "PANEL BOARDS" ADDRESSED TO HAZARDOUS AREAS - PART THREE In this third part. we want to speak about how important is the correct sizing of the

More information

08/072 PKZ2 Motor-Protective Circuit-Breakers Tripping Characteristics

08/072 PKZ2 Motor-Protective Circuit-Breakers Tripping Characteristics 0/07 PKZ Tripping Characteristics Moeller HPL0-00/00 S-PKZ high-capacity contact module, SEA-PKZ contact module Normal switching duty AC-/00V kw A Rated output of three-phase motors 0...0 Hz. 7..... 0.7

More information

Varius SUMMARY OF MODELS OF HRC FUSE-LINKS

Varius SUMMARY OF MODELS OF HRC FUSE-LINKS SUMMARY OF MODELS OF HRC FUSE-LINKS Type PNA000 PHNA000 PNA00 PHNA00 Rated current I n up to A up to 0 A up to A up to 0 A Rated voltage U n AC 00 V, 00 V 90 V 00 V 90 V DC 0 V 0 V 0 V 0 V Fuse-link size

More information

Issued August DATA SHEET. 3VT5 MCCB up to 1600 A

Issued August DATA SHEET. 3VT5 MCCB up to 1600 A ssued August 9 DATA SHEET VT5 MCCB up to 0 A Based on Siemens Catalog V 8 Standard circuit breakers Releases Technical specifications Specifications VT5 circuit breakers Switch disconnectors Type Standards

More information

BETA Protecting Miniature Circuit Breakers

BETA Protecting Miniature Circuit Breakers Siemens AG 00 / Product overview / High-capacity range 000 A 0000 A 0000 A, high current 0000 A, universal current 000 A ka /0 Comfort range with plug-in terminal / Compact range +N in MW / Additional

More information

Overload Relays. SIRIUS 3RU1 Thermal Overload Relays. 3RU11 for standard applications. 5/46 Siemens LV 1 AO 2011

Overload Relays. SIRIUS 3RU1 Thermal Overload Relays. 3RU11 for standard applications. 5/46 Siemens LV 1 AO 2011 SIRIUS 3RU1 Thermal Overview 1 2 7 3 4 6 "Increased safety" type of EEx e according to ATEX directive 94/9/EC The 3RU11 thermal overload relays are suitable for the overload of explosion-proof motors with

More information

X T O B P 1 6 B C 1 S

X T O B P 1 6 B C 1 S 9 Overload Relays XTOB, XTOT May 07 Contents Description Page Overload Relays XTOB, XTOT Selection................ 9 Product Selection.......... 95 Accessories............... 9 Technical Data and Specifications............

More information

Issued August DATA SHEET. 3VT3 MCCB up to 630 A

Issued August DATA SHEET. 3VT3 MCCB up to 630 A ssued August 9 DATA SHEET VT MCCB up to 6 A Based on Siemens Catalog V 6 8 Circuit breakers Switch disconnectors Technical specifications Specifications Type VT 76-AA6/6/56-AA, VT 76-AA6/6/56-AA Circuit

More information

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager. Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager. 1 -A - Introduction - Thank for your purchasing MITSUBISHI ELECTRIC MELPRO TM D Series Digital Protection

More information

3VT4 Molded Case Circuit Breakers up to 1000 A

3VT4 Molded Case Circuit Breakers up to 1000 A VT4 Molded Case Circuit Breakers up to 00 A Catalog Technical nformation VT4 Molded Case Circuit Breakers up to 00 A General data / - Overview Circuit breakers Switch disconnectors / - Selection and ordering

More information

BETA Protecting. Low-Voltage Fuse Systems. LV HRC fuse links. 3/36 Siemens ET B1 2008

BETA Protecting. Low-Voltage Fuse Systems. LV HRC fuse links. 3/36 Siemens ET B1 2008 LV HRC fuse links Overview LV HRC fuses are used for installation systems in non-residential, commercial and industrial buildings as well as in switchboards of power supply companies. They therefore protect

More information

F F FAULT CURRENT Prospective. 1. Introduction. 2. Types of fault conditions

F F FAULT CURRENT Prospective. 1. Introduction. 2. Types of fault conditions FAULT CURRENT F F13-13 FAULT CURRENT - Contents 1. Introduction 2. Types of fault conditions 3 fault current must be determined 3.1 Purposes for which of prospective fault current magnitudes are used 3.2

More information

1SDC007004D0201. Discrimination tables

1SDC007004D0201. Discrimination tables 1SDC007004D0201 Discrimination tables tables Introduction Index Introduction... I Back-up...1/1 Discrimination...2/1 tables Introduction Introduction... II Choosing the type of coordination for the protection

More information

VX25 Enclosure System. Technical documentation PE conductor connection, current carrying capacity

VX25 Enclosure System. Technical documentation PE conductor connection, current carrying capacity VX Enclosure System Technical documentation PE conductor connection, current carrying capacity Enclosure system VX Contents Contents. General remarks. Introduction. Notes on the design of the earthing

More information

General characteristics, Products

General characteristics, Products The Feature Packed line of Manual Motor Protectors Eaton s new XT family of Manual Motor Protectors (MMPs) features a pushbutton or rotary ON/OFF manual disconnect, Class adjustable bimetallic overload

More information

Technical catalogue SmiSSline electrical protective devices in a system

Technical catalogue SmiSSline electrical protective devices in a system Technical catalogue SmiSSline electrical protective devices in a system SmiSSline The original Shaping the future SmiSSline protection devices are simply snapped into a plug-in socket system. The arduous

More information

1SDC007004D0205. Coordination tables

1SDC007004D0205. Coordination tables Coordination tables Coordination tables Index Introduction...I Back-up... / Discrimination... / Motor protection... 3/ Switch-disconnectors... 4/ Coordination tables Introduction Discrimination and back-up

More information

Miniature Circuit Breaker

Miniature Circuit Breaker Miniature Circuit Breaker SG-DPN I E C / E N 0 8 9 8-5 0 0 SG-DPN Applications Approval / Marking Function and Feature Integrate with switch phase and neutral in one module Protection against both overload

More information

Varius SUMMARY OF MODELS OF HRC FUSE-LINKS. Type PVA10 / PV10 PV14 PV22 Rated current I n up to 32 A up to 63 A up to 125 A Rated voltage U n

Varius SUMMARY OF MODELS OF HRC FUSE-LINKS. Type PVA10 / PV10 PV14 PV22 Rated current I n up to 32 A up to 63 A up to 125 A Rated voltage U n Varius SUMMARY OF MODELS OF HRC FUSE-LINKS Type A / Rated current I n up to A up to up to A Rated voltage U n AC V, V V, V, 9 V V, V, 9 V DC V V V Fuse-link size x8 x x8 Utilization category of the fuse-link

More information

Current protection I 2 t long-time protection

Current protection I 2 t long-time protection I 2 t long-time protection The long-time protection function protects cables against overloads. This function is based on true rms measurements. It is possible to select either I 2 t long-time protection

More information

University of Moratuwa, Sri Lanka. EE3231: Design of Electrical Installation

University of Moratuwa, Sri Lanka. EE3231: Design of Electrical Installation University of Moratuwa, Sri Lanka B.Sc. Engineering Level 4 Semester 1 Examination EE3231: Design of Electrical Installation Time allowed: 2 Hours January 2010 Additional Material: Not required INSTRUCTIONS

More information

TEST REPORT IEC :2002 Circuit-Breakers for overcorrect protection for household and similar installation

TEST REPORT IEC :2002 Circuit-Breakers for overcorrect protection for household and similar installation age 1 of 92 R e port ref. No.: C009-CB2012CQC-044407 Test Report issued under the responsibility of: TEST REORT IEC 60 898-1:2002 Circuit-Breakers for overcorrect protection for household and similar installation

More information

Periodic Inspection and Testing of Electrical Installations Sample Test ( ) Version 1.3 July 2018

Periodic Inspection and Testing of Electrical Installations Sample Test ( ) Version 1.3 July 2018 Periodic Inspection and Testing of Electrical Installations Sample Test (2391-051) Version 1.3 July 2018 Sample Questions Version and date Change detail Section 1.3 July 2018 Modified questions/answers

More information

ATyS Automatic and remotely operated transfer switches from 125 to 3200 A

ATyS Automatic and remotely operated transfer switches from 125 to 3200 A atys-p_001_b atys_d_001_a_1_cat ATyS p I-0-II 4P ATyS d I-0-II 4P Function The ATyS are three-phase motorised transfer switches with positive break indication. They enable the on load transfer of two three-phase

More information

Instruction. Vacuum Circuit Breaker Operator Module. Type 3AH 4.16kV to 38kV. Power Transmission & Distribution

Instruction. Vacuum Circuit Breaker Operator Module. Type 3AH 4.16kV to 38kV. Power Transmission & Distribution Instruction 0001-22-2--00 Vacuum Circuit Breaker Operator Module Type 3AH 4.16kV to 38kV Power Transmission & Distribution Hazardous voltages and high-speed moving parts. Will cause death, serious injury

More information

SIRCOVER Manual transfer switches from 125 to 3200 A

SIRCOVER Manual transfer switches from 125 to 3200 A Manual transfer switches svr_149_a 3200 A Function are manual multipolar transfer switches with positive break indication. The family includes two ranges: AC for dead time switching (I-0-II), for overlapping

More information

October Selectivity, back up protection and coordination guide

October Selectivity, back up protection and coordination guide October 2015 Selectivity, back up protection and coordination guide Energising a world that demands more. We deliver: Electrical solutions that use less energy, improve power reliability and make the places

More information

TEST REPORT IEC/EN Circuit-breakers for over current protection for household and similar installations

TEST REPORT IEC/EN Circuit-breakers for over current protection for household and similar installations Test Report issued under the responsibility of: TEST REORT IEC/EN 60898-1 Circuit-breakers for over current protection for household and similar installations Report Reference No.... : 130100913SHA-004

More information

Complementary technical information

Complementary technical information Complementary technical information Catalogue 2018 Low Voltage schneider-electric.com Green Premium TM Endorsing eco-friendly products in the industry Schneider Electric s Green Premium ecolabel is committed

More information

16 Appendix 16 Electrical Research Association Report

16 Appendix 16 Electrical Research Association Report Guide to the Wiring Regulations 16 Appendix 16 Electrical Research Association Report (ERA) report on armoured cables with external CPCs The attached report was commissioned by the ECA and is copyright

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current Transducer LDSR 0.3-TP/SP1 I P R N = 300 ma For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Features Closed

More information

440V 500V V / / /2 12.

440V 500V V / / /2 12. -26 Manual Motor Protectors March 0 B-Frame D-Frame Table -6. XTPR Rotary Manual Motor Protectors with Screw Terminals Global Ratings and North American Ratings Type and Type 2 Coordination Motor Protective

More information

Non-Contact Safety Systems CMS

Non-Contact Safety Systems CMS Selection table for non-contact safety system // Evaluation units Connection Desi Read head contact assembly Assured switch-on distance S ao [mm] Assured switch-on distance S ar [mm] Number of outputs

More information

H i g h A m p e r a g e 2 5 t o A M P. T y p e I & I I I V e h i c l e P r o t e c t i o n. I P 6 7 W a t e r p r o o f

H i g h A m p e r a g e 2 5 t o A M P. T y p e I & I I I V e h i c l e P r o t e c t i o n. I P 6 7 W a t e r p r o o f H i g h A m p e r a g e 2 5 t o 3 0 0 A M P T y p e I & I I I V e h i c l e P r o t e c t i o n I P 6 7 W a t e r p r o o f I g n i t i o n - P r o t e c t e d S A E & A B Y C C o m p l i a n t L E D T

More information

Fault Calculation Methods

Fault Calculation Methods ELEC9713 Industrial and Commercial Power Systems Fault Calculation Methods There are two major problems that can occur in electrical systems: these are open circuits and short circuits. Of the two, the

More information

TeSys contactors. TeSys D contactors. 690 V on a and c

TeSys contactors. TeSys D contactors. 690 V on a and c Selection guide TeSys D contactors Applications All types of control system Rated operational current le max AC- (Ue y 0 V) A A A A A A le AC- (q y 0 C) 0/ A / A /0 A 0 A Rated operational voltage 0 V

More information

ISOCON-6. 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER

ISOCON-6. 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER ISOCON-6 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER Whilst every effort has been taken to ensure the accuracy of this document, we accept no responsibility for damage, injury, loss or expense resulting

More information

Semiconductor (AC) fuses

Semiconductor (AC) fuses PSC gr sizes 7x - 690 VAC Main characteristics 6,9 grb 71 PA 200 6,9 grb 73 TTF 1000 + MS7V1-5 UR Ferraz Shawmut PSC-gRB 690 VAC fuse-links provide maximum flexibility in equipment design and ultimate

More information

Power capacitors in general

Power capacitors in general INDEX Power capacitors in general..low VOLTGE CPCITORS MKP (Box )..PPM / MKP TECHNOLOGY..OPERTING CONDITION.. Voltage..mbient temperature.. Installation.. Discharge the capacitor.. Inrush current limitation..

More information

Interference suppression film capacitors MKP 336 1

Interference suppression film capacitors MKP 336 1 MKP RADIAL POTTED TYPE PITCH /15/22.5/27.5 mm l b h lt P d t CBA196 Fig.1 Simplified outlines. FEATURES to 27.5 mm lead pitch Supplied loose in box and taped on reel Consists of a low-inductive wound cell

More information

1..LOW VOLTAGE POWER CAPACITORS MKP (CYLINDRICAL) 2 2..PPM / MKP TECHNOLOGY 2 3..OPERATING CONDITION Voltage Ambient temperature

1..LOW VOLTAGE POWER CAPACITORS MKP (CYLINDRICAL) 2 2..PPM / MKP TECHNOLOGY 2 3..OPERATING CONDITION Voltage Ambient temperature INDEX..LOW VOLTGE CPCITORS MKP (CYLINDRICL)..PPM / MKP TECHNOLOGY..OPERTING CONDITION.. Voltage..mbient temperature.. Installation.. Discharge the capacitor.. Inrush current limitation.. Harmonics.7.Overpresure

More information

Products for Luminaire Protection and Power Adjustment Products

Products for Luminaire Protection and Power Adjustment Products Products for uminaire Protection and Power Adjustment Products uminaire Protection evice For electronic devices When electronic components form part of lighting systems, it is often necessary to protect

More information

NM1. Moulded Case Circuit Breaker NM1 P-084. Moulded Case Circuit Breakers. 2. Type designation. 1. General. 3. Classification N M 1- /

NM1. Moulded Case Circuit Breaker NM1 P-084. Moulded Case Circuit Breakers. 2. Type designation. 1. General. 3. Classification N M 1- / P0. Type designation N M / Type of Npole for P breaker* pplication: lank: for power distribution; : for motor protection elease type and accessory code (please refer to table on page 9) Number of poles

More information

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager. Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager. 1 -C - Safety section - This Safety section should be read before starting any work on the relay.

More information

Microprocessor Based Characteristics and adjustments

Microprocessor Based Characteristics and adjustments Microprocessor Based Characteristics and adjustments 7- Range Operation Settings Operation and Examples 0 Ground Fault and Pre-rip larm LED ndication and OCR Controller ime/current Curves - OCR Checker

More information

PHOENIX CONTACT - 04/2016. Features

PHOENIX CONTACT - 04/2016. Features Signal conditioner Data sheet 100238_de_06 1 Description PHOENIX CONTACT - 04/2016 Features The MCR-C-UI-UI(-450)-DCI(-NC) 3-way isolation amplifier is used to electrically isolate and convert analog signals.

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current Transducer HO-NP series I P N = 4, 6, 12, 15 A Ref: HO 4-NP, HO 6-NP, HO 12-NP, HO 15-NP For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary

More information

Operating Instructions for Digital Manometer. Model: MAN-SD

Operating Instructions for Digital Manometer. Model: MAN-SD Operating Instructions for Digital Manometer Model: MAN-SD 1. Contents 1. Contents...2 2. Note...3 3. Instrument Inspection...3 4. Regulation Use...4 5. Operating Principle...4 6. Mechanical Connection...5

More information

To order, specify : Types Protection functions Current surge Asymmetry and loss of phase. Operating principle

To order, specify : Types Protection functions Current surge Asymmetry and loss of phase. Operating principle otor protection relays - T - FWIT Since % of -phase motor failures are due to load problems or loss of phase, the CROUZET range of motor protection relays is indispensable! models give motor protection

More information

ISOCON-3 MAINS POWERED ISOLATING SIGNAL CONVERTER

ISOCON-3 MAINS POWERED ISOLATING SIGNAL CONVERTER ISOCON-3 MAINS POWERED ISOLATING SIGNAL CONVERTER CAUTION: This equipment is designed for connection to mains voltages and must be used in accordance with this guide. If it is not, the safety protection

More information

Impedance relay and protection assemblies

Impedance relay and protection assemblies RXZK 21H, 22H, 23H 509 006-BEN Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970175) (SE970184) Features Micro-processor based impedance relay with R and X settings

More information

DATA SHEET POSITIVE TEMPERATURE COEFFICIENT AC/DC POWER SUPPLY SMD0603 series

DATA SHEET POSITIVE TEMPERATURE COEFFICIENT AC/DC POWER SUPPLY SMD0603 series Product specification November 05, 201 V.0 DATA SHEET AC/DC POWER SUPPLY series RoHS compliant & Halogen free 2 Positive Temperature Coefficient (PTC) Data Sheet Description The 0603 series provides miniature

More information

Selecting the current rating for equipment

Selecting the current rating for equipment Selecting the current rating for equipment 1. Rated current: the maximum continuous load current. Short-time withstand current: thermal withstand current term term is given for 1s or 3s short circuit current

More information

EXEMPLAR NATIONAL CERTIFICATE (VOCATIONAL) ELECTRICAL PRINCIPLES AND PRACTICE NQF LEVEL 3 ( ) (X-Paper) 09:00 12:00

EXEMPLAR NATIONAL CERTIFICATE (VOCATIONAL) ELECTRICAL PRINCIPLES AND PRACTICE NQF LEVEL 3 ( ) (X-Paper) 09:00 12:00 NATIONAL CERTIFICATE (VOCATIONAL) ELECTRICAL PRINCIPLES AND PRACTICE NQF LEVEL 3 2008 (12041002) (X-Paper) 09:00 12:00 EXEMPLAR This question paper consists of 7 pages. EXEMPLAR -2- NC(V) TIME: 3 HOURS

More information

FL ballasts Electronic fixed output. PC TC PRO sr 1/2x11 42 W PC PRO compact

FL ballasts Electronic fixed output. PC TC PRO sr 1/2x11 42 W PC PRO compact FL ballasts EL HE PC TC PRO sr 1/2x11 42 W PC PRO compact Product description CELMA Energy Efficiency Index A2 BAT / A2 T Nominal life-time up to 50,000 h (at ta 50 C with a failure rate max. 0.2 % per

More information

Digital Current Transducer HO-SW series I P N = A. Ref: HO 100-SW; HO 150-SW; HO 200-SW; HO 250-SW

Digital Current Transducer HO-SW series I P N = A. Ref: HO 100-SW; HO 150-SW; HO 200-SW; HO 250-SW Digital Current Transducer HO-SW series I P N = 100... 250 A Ref: HO 100-SW; HO 150-SW; HO 200-SW; HO 250-SW Bitstream output from on onboard Sigma Delta modulator. For the electronic measurement of current:

More information

GPS1B. Characteristics. Technical performances

GPS1B. Characteristics. Technical performances Thermal and magnetic protection PS Motor protection devices Standards/pprovals 097, 0972, 097 N V 00T 0//2 UL/S UL/cULus Shipping approvals: RN ureau Lloyd s Register Veritas ermanischer Lloyd haracteristics

More information

Modular contactors for installation into distribution

Modular contactors for installation into distribution Modular contactors for installation into distribution boards Modular contactors for installation into distribution boards Modular contactor for installation into distribution board Description Modular

More information

COPPER FOR BUSBARS CHAPTER 4: SHORT-CIRCUIT EFFECTS

COPPER FOR BUSBARS CHAPTER 4: SHORT-CIRCUIT EFFECTS European Copper Institute COPPER FOR BUSBARS CHAPTER 4: SHORT-CIRCUIT EFFECTS David Chapman August 2011 ECI Available from www.leonardo-energy.org Document Issue Control Sheet Document Title: Publication

More information

TEST CERTIFICATES OR REPORTS ISSUED BY VEIKI-VNL LTD.

TEST CERTIFICATES OR REPORTS ISSUED BY VEIKI-VNL LTD. Page 2 of 29 TEST CERTIFICATES OR REPORTS ISSUED BY LTD. Type Test Certificate of Complete Type Test This certificate provides the verification of all the rated characteristics of the equipment as assigned

More information

Moulded Case Circuit Breakers. Breaking capacity code: S:standard H:Higher type/r:current limiting type

Moulded Case Circuit Breakers. Breaking capacity code: S:standard H:Higher type/r:current limiting type TPact Moulded Case Circuit Breakers TPact Moulded Case Circuit Breaker. General Certificates: KEMA,CB; Electric ratings: AC0/0Hz, AC0V~90V DC0V~00V, A~0A; Standard: IEC/EN 097.. Type Designation TPact...

More information

Ref: HLSR 16-PW; HLSR 32-PW; HLSR 40-PW-000; HLSR 50-PW-000,

Ref: HLSR 16-PW; HLSR 32-PW; HLSR 40-PW-000; HLSR 50-PW-000, Digital Current Transducer HLSR-PW series I P N = 16... 50 A Ref: HLSR 16-PW; HLSR 32-PW; HLSR 40-PW-000; HLSR 50-PW-000, Bitstream output from on onboard Sigma Delta modulator. For the electronic measurement

More information

Magnetic Field Simulation of a Miniature Circuit Breaker s Coil

Magnetic Field Simulation of a Miniature Circuit Breaker s Coil Magnetic Field Simulation of a Miniature Circuit Breaker s Coil Comparison of Simulation and analitical results on the solenoid axis. Conecici-Lucian Madalin, Munteanu Calin, Purcar Ioan Marius Technical

More information

LD-LP-LL-LC Rope Safety Switches with reset for emergency stop

LD-LP-LL-LC Rope Safety Switches with reset for emergency stop TECHNICA DATASHEET D-P--C Rope Safety Switches with reset for emergency stop Metal or polymer housing, from one or three conduit entries Protection degree IP6 In conformity with EN ISO 13850 contact blocks

More information

Test Report issued under the responsibility of: SHA-001 Date of issue... : Total number of pages... : 292. Report Number...

Test Report issued under the responsibility of: SHA-001 Date of issue... : Total number of pages... : 292. Report Number... D Test Report issued under the responsibility of: TEST REORT Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCBs) art 1: General rules

More information

Single Phase Motors Technical Datasheets

Single Phase Motors Technical Datasheets Single Phase Motors Technical Datasheets EN A dynamic, strong and ambitious Group: Orange1 Holding is an international renown Group, one of the most important European manufacturers of single-phase and

More information

MOULDED CASE CIRCUIT BREAKERS BL1000S

MOULDED CASE CIRCUIT BREAKERS BL1000S G MOUDED CASE CRCUT BREAKERS BS G BS COMMERCA NFORMATON P Switching units, withdrawable device, plug-in device...g Overcurrent releases...g Signalling units...g Connecting sets...h Switches...H Shunt trips...h

More information

XD1-L Cable Differential Protection Relay

XD1-L Cable Differential Protection Relay XD1-L Cable Differential Protection Relay Manual XD1-L (Revision B) Woodward Manual XD1-L GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information

More information

Metallized polyester film capacitors MKT 470

Metallized polyester film capacitors MKT 470 MKT RADIAL POTTED TYPE PITCH 5 mm CBA141 Fig.1 Simplified outlines. FEATURES Low-inductive wound cell of metallized (PETP) film Potted with epoxy resin in a flame-retardant case Radial leads of solder-coated

More information

SION Lateral 3AE6 Vacuum Circuit Breaker with Lateral Operating Mechanism

SION Lateral 3AE6 Vacuum Circuit Breaker with Lateral Operating Mechanism Catalog HG.07 Edition 03/ 07 SION Lateral 3AE Vacuum Circuit Breaker with Lateral Operating Mechanism Medium-Voltage Equipment siemens.com/sion R-HG-3.psd Catalog HG.07 03 / 07 SION 3AE Vacuum Circuit

More information

E8EB-N0C2B E8EB-N0B2B

E8EB-N0C2B E8EB-N0B2B Slim Sensor CSM DS_E 1 Ideal for Workpiece Position and Original Checking The to 1 kpa model can be used for workpiece position checking. The to 1MPa model is ideal for original pressure checking. Degree

More information

TeSys enclosed starters 2

TeSys enclosed starters 2 Characteristics, references TeSys enclosed starters D..L. starters for motor control 0. to. kw with -phase thermal overload relay with protected phases Characteristics () Conforming to standards IEC 0--,

More information

T h e rm i s t o r s

T h e rm i s t o r s Data Pack E Issued March 00 - T h e rm i s t o r s NTC thermistors The R S range of NTC thermistors includes standard tolerance negative temperature coefficient thermistors, a range of small close tolerance

More information

MR medium rating busbar

MR medium rating busbar technical information General features MR is fully compliant with S EN 0-, specifically, the rated current of the Zucchini busbar trunking systems is always rated at the average ambient temperature of

More information

Masterpact. Installation recommendations

Masterpact. Installation recommendations 90 Installation recommendations Presentation Functions and characteristics 9 Dimensions and connection 5 Electrical diagrams 8 Operating conditions 92 Installation in switchboard 9 Door interlock catch

More information