TeSys circuit-breakers
|
|
- Barrie Hodge
- 5 years ago
- Views:
Transcription
1 Presentation Thermal-magnetic motor circuit-breakers types GV2, GV and GV7 GV2-ME, GV2-P, GV-ME and GV7-R motor circuit-breakers are -pole thermal-magnetic circuit-breakers specifically designed for the control and protection of motors, conforming to standards IEC/EN and IEC/EN Connection These circuit-breakers are designed for connection by screw clamp terminals. Circuit-breaker GV2-ME can be supplied with spring terminal connections. These ensure secure, permanent and durable clamping that is resistant to harsh environments, vibration and impact and is even more effective when conductors without cable ends are used. Each connection can take two independent conductors. GV2-ME with screw clamp connections Operation O I 2 4 O I O 2. GV2-ME with spring terminal connections GV2-P GV2-ME GV-ME GV2-P GV7-R GV2-ME and GV-ME: Pushbutton control. Energisation is controlled manually by operating the Start button I. De-energisation is controlled manually by operating the Stop button O 2, or automatically by the thermal-magnetic protection elements or by a voltage trip attachment. Control is manual and local when the motor circuit-breaker is used on its own. Control is automatic and remote when it is associated with a contactor. Protection of motors and personnel GV2-P: control by rotary knob. GV7-R: control by rocker lever. Energisation is controlled manually by moving the knob or rocker lever to position I. De-energisation is controlled manually by moving the knob or rocker lever to position O 2. De-energisation due to a fault automatically places the knob or rocker lever in the Trip position. Re-energisation is possible only after having returned the knob or rocker switch to position O. Motor protection is provided by the thermal-magnetic protection elements incorporated in the motor circuit-breaker. The magnetic elements (short-circuit protection) have a non-adjustable tripping threshold, which is equal to about times the maximum setting current of the thermal trips. The thermal elements (overload protection) include automatic compensation for ambient temperature variations. The rated operational current of the motor is displayed by means of a graduated knob 4. Personnel protection is also provided. All live parts are protected against direct finger contact. The addition of an undervoltage trip allows the circuit-breaker to be de-energised in the event of an undervoltage condition. The user is therefore protected against sudden starting of the machine when normal voltage is restored, since the Start button I has to be pressed to restart the motor. GV-ME With the addition of a shunt trip, de-energisation of the unit can be remotely controlled. The operators on both open-mounted and enclosed motor circuit-breakers can be locked in the Stop position O by up to padlocks. Because they are suitable for isolation, these circuit-breakers, in the open position, provide an adequate isolation distance and indicate the actual position of the moving contacts by the position of the operators. Special features These motor circuit-breakers are easily installed in any configuration thanks to their universal fixing arrangement: screw fixing or clip-on mounting on symmetrical, asymmetrical or combination rails. GV7-R Characteristics: pages /5 to /7 & /25 to /0 pages /4 to /48 pages /49 to /5 /
2 Definitions, comments Coordination (according to standard IEC/EN ) The standard defines the degree of acceptable damage to the equipment following a short-circuit. Standard IEC/EN (motor-starters) defines 2 types Type Damage to motor-starter components is The fault current has been successfully interrupted. coordination accepted. No damage has been caused to persons or to installations. Type 2 coordination Welding of the contactor or motor-starter contacts is accepted providing they can be easily separated. Coordination table for GV2 + contactors: see pages /40 to /4.. Iq = rated conditional short-circuit current (ka) - that the circuit-breaker can interrupt - that the associated motor-starter components can withstand without damage. Suitability for isolation x According to standard IEC/EN , sub-clause 7--6 (additional safety requirements for equipment suitable for isolation): Equipment suitable for isolation shall provide in the open position and isolating distance in accordance with the requirements necessary to satisfy the isolating function and shall be fitted with an indicating device indicating the position of the moving contacts. This position indicator shall be connected to the moving contacts in a reliable way; the handle may form such an indicator, providing it cannot indicate the open position when released unless all the moving contacts are in the open position. Breaking capacity (according to standard IEC/EN ) Icu: Rated ultimate short-circuit breaking capacity Breaking capacity for which the prescribed conditions according to a specified test sequence do not include the capability of the circuit-breaker to carry its rated current continuously following the sequence of operations )O-t-CO. Ics: Rated service short-circuit breaking capacity Breaking capacity for which the prescribed conditions according to a specified test sequence include the capability of the circuit-breaker to carry its rated current continuously following the sequence of operations O-t-CO-t-CO. It is expressed as a percentage of Icu (25, 50, 75 or 00%). In operational conditions, the short-circuit currents normally encountered rarely exceed 25 to 50% of the prospective short-circuit current at the point of installation of the circuit-breaker. Other definitions Discrimination (selectivity) Discrimination of protective devices requires that protection against a fault arising at any point of the network is effected by the nearest device on the supply side of the fault. Discrimination may be total or partial. In the latter case the overcurrent limit must be defined. See pages /20 to /24. Cascading Where two separate protective devices in series operate at the same time under short circuit fault conditions, the breaking capacity lcu of the downstream device is increased. See page /20. Current limiting By the use of additional poles operating in series with the main poles, the overall breaking capacity lcu of a motor circuitbreaker is substantially increased. A single current limiting block may be used in conjunction with a number of motor circuit-breakers up to the 6 A thermal limit. See page /6. Sensitivity to phase loss (according to standard IEC/EN , sub-clause ) Limits of operation of -pole thermal overload relays energised on two poles: With the overload relay energised on two poles at.0 times the current setting (Ir) and on one pole at 0.9 Ir, tripping shall not occur in less than 2 hours starting from the cold state at 20 o C. When the value Ir flowing in two poles is increased to.5 Ir and the third pole is de-energised, tripping shall occur in less than 2 hours. See curves, pages /8 to /0. /4
3 Characteristics Thermal-magnetic motor circuit-breakers types GV2-ME and GV2-P (Also applies to GV2-RT. Use GV2-ME table eg: for GV2-RT4 use GV2-ME4 data) Breaking capacity of GV2-ME and GV2-P Circuit-breaker type GV2- GV2- ME0 ME07 ME08 ME0 ME4 ME6 ME20 ME2 ME2 P0 P07 P08 P0 P4 P6 P20 P2 P2 to and to and ME06 ME22 P06 P22 Rating A to and to and Breaking capacity 20/ Icu ka g g g g g g g g g g g g g g g g conforming to 240 V IEC/EN Ics g g g g g g g g g g g g g g g g % () 400/ Icu ka g g g g g g g g g g g V Ics g g g g g g g g g g g % () 440 V Icu ka g g g g g g g g Ics g g g g g g g g % () 500 V Icu ka g g g g g g g Ics g g g g g g g % () 690 V Icu ka g g Ics g g % () Associated fuses (if required) if Isc > breaking capacity Icu conforming to 20/ am A g g g g g g g g g g g g g g g g IEC/EN V gg A g g g g g g g g g g g g g g g g 400/ am A g g g g g g g g g g g V gg A g g g g g g g g g g g V am A g g g g g g g g gg A g g g g g g g g V am A g g g g g g g gg A g g g g g g g V am A g g gg A g g g > 00 ka. () As % of Icu. pages / to /42 pages /4 to /48 pages /49 to /5 /5
4 Characteristics (continued) Thermal-magnetic motor circuit-breakers types GV2-ME and GV2-P (Also applies to GV2-RT. Use GV2-ME table eg: for GV2-RT4 use GV2-ME4 data) Breaking capacity of GV2-ME and GV2-P (used in association with current limiter GV-L) Circuit-breaker type GV2- ME0 ME07 ME08 ME0 ME4 ME6 ME20 ME2 ME22 ME2 to ME06 Rating A Breaking capacity 20/ Icu ka g g g g g g g g g g conforming to 240 V IEC/EN Ics g g g g g g g g g g % () 400/ Icu ka g g g g g V Ics g g g g g % () 440 V Icu ka g g g g g Ics g g g g g % () 500 V Icu ka g g g g Ics g g g g % () Circuit-breaker type GV2- P0 P07 P08 P0 P4 P6 P20 P2 P22 P2 to P06 Rating A Breaking capacity 20/ Icu ka g g g g g g g g g g conforming to 240 V IEC/EN Ics g g g g g g g g g g % () 400/ Icu ka g g g g g g g g g g 45 V Ics g g g g g g g g g g % () 440 V Icu ka g g g g g Ics g g g g g % () 500 V Icu ka g g g g Ics g g g g % () 690 V Icu=Ics ka g () Circuit-breaker type GV2- ME0 ME07 ME08 ME0 ME4 ME6 ME20 ME2 ME22 ME2 to ME06 Rating A Cable protection against thermal stress in the event of short-circuit (PVC insulated copper cables) Minimum mm 2 p p p 0 ka 6 ka (2) (2) (2) (2) (2) c.s.a. protected.5 mm 2 p p p 20 ka 0 ka (2) (2) (2) (2) (2) at 40 C at Isc max. 2.5 mm 2 p p p p p p p p p (2) pages / to / mm 2 p p p p p p p p p p g > 00 ka. p Cable c.s.a. protected. () As % of Icu. (2) Cable c.s.a. not protected. () With limiter LA9-LB920. pages /4 to /48 pages /49 to /5 /6
5 Characteristics Magnetic motor circuit-breakers types GV2-LE and GV2-L Breaking capacity of GV2-LE and GV2-L Type GV2- GV2- LE0 LE07 LE08 LE0 LE4 LE6 LE20 LE22 LE2 L0 L07 L08 L0 L4 L6 L20 L22 L2 to to LE06 L06 Rating A to to.6 Breaking capacity 20/ Icu ka g g g g g g g g g g g g g g to IEC/EN V Ics g g g g g g g g g g g g g g % () 400/ Icu ka g g g g g g g g g g V Ics g g g g g g g g g g % () 440 V Icu ka g g g g g g g Ics g g g g g g g % () 500 V Icu ka g g g g g g g Ics g g g g g g g % () 690 V Icu ka g g Ics g g % () Associated fuses (if required) If Isc > breaking capacity Icu to IEC/EN / am A g g g g g g g g g g g g g g V gg A g g g g g g g g g g g g g g Cable protection against thermal stress in the event of short-circuit (PVC insulated copper cables) 400/ am A g g g g g g g g g g V gg A g g g g g g g g g g V am A g g g g g g g gg A g g g g g g g V am A g g g g g g g gg A g g g g g g g V am A g g gg A g g Minimum c.s.a. mm 2 ka p p p 0 6 (2) (2) (2) (2) p p p 0 6 (2) (2) (2) (2) protected at 40 C and at Isc max.5 mm 2 ka p p p 20 0 (2) (2) (2) (2) p p p 20 0 (2) (2) (2) (2) pages / to / mm 2 p p p p p p p p (2) p p p p p p p p (2) 4 6 mm 2 p p p p p p p p p p p p p p p p p p g > 00 ka () As % of Icu (2) Cable c.s.a. not protected p Cable c.s.a. protected pages /4 to /48 pages /49 to /5 /7
6 Curves Thermal-magnetic motor circuit-breakers types GV2-ME and GV2-P Thermal-magnetic tripping curves for GV2-ME and GV2-P Average operating time at 20 C according to multiples of the setting current Time (s) , 0,0 0,00, x setting current (Ir) poles from cold state 2 2 poles from cold state poles from hot state pages / to /42 pages /4 to /48 pages /49 to /5 /8
7 Curves Thermal-magnetic motor circuit-breakers type GV2-RT Thermal-magnetic tripping curves for GV2-RT Time (s) , 0,0 0, x setting current (Ir) poles from cold state 2 2 poles from cold state poles from hot state pages / to /42 pages /4 to /48 pages /49 to /5 /9
8 Curves (continued) Magnetic motor circuit-breakers types GV2-L and GV2-LE Tripping curves for GV2-L or LE combined with thermal overload relay LRD or LR2-K Average operating time at 20 C according to multiples of the setting current Time (s) , 0,0 0, x setting current (Ir) poles from cold state 2 2 poles from cold state poles from hot state pages / to /42 pages /4 to /48 pages /49 to /5 /0
9 Curves Thermal-magnetic motor circuit-breakers types GV2-ME, GV2-P and GV2-RT Current limitation on short-circuit for GV2-ME, GV2-P and GV2-RT -phase 400/45 V Dynamic stress I peak = f (prospective Isc) at.05 Ue = 45 V Limited peak current (ka) 00 = 0.25 = = 0.7 = = cos = 0.95 = , 0, 0 5 (2) 00 Prospective Isc (ka) Maximum peak current A A A A A A A 5-8 A -.6 A A 2 Limit of rated ultimate breaking capacity on short-circuit of GV2-ME (4, 8, 2 and 25 A ratings) pages / to /42 pages /4 to /48 pages /49 to /5 /
10 Curves (continued) Magnetic motor circuit-breakers types GV2-L and GV2-LE Current limitation on short-circuit For GV2-L and GV2-LE only -phase 400/45 V Dynamic stress I peak = f (prospective Isc) at.05 Ue = 45 V Limited peak current (ka) 00 = = = 0.7 = = 0.9 = cos = , 0, Prospective Isc (ka) Maximum peak current 6 0 A. 2 2 A 7 6. A 25 A 8 4 A 4 8 A A 5 4 A 0.6 A Limit of rated ultimate breaking capacity on short-circuit of GV2-LE (4, 8 and 25 A ratings) pages / to /42 pages /4 to /48 pages /49 to /5 /2
11 Curves Magnetic motor circuit-breakers types GV2-L and GV2-LE Current limitation on short-circuit For GV2-L and GV2-LE + thermal overload relay LRD or LR2-K -phase 400/45 V Dynamic stress I peak = f (prospective Isc) at.05 Ue = 45 V Limited peak current (ka) 00 = 0.25 = = 0.7 = = cos = 0.95 = , 0, Prospective Isc (ka) Maximum peak current 6 0 A 2 2 A 7 6. A 25 A 8 4 A 4 8 A A 5 4 A 0.6 A Limit of rated ultimate breaking capacity on short-circuit of GV2-LE (4, 8 and 25 A ratings) pages / to /42 pages /4 to /48 pages /49 to /5 /
12 Curves (continued) Thermal-magnetic motor circuit-breakers types GV2-ME and GV2-RT Thermal limit on short-circuit for GV2-ME and GV2-RT Thermal limit in KA 2 s in the magnetic operating zone Sum of I 2 dt = f (prospective Isc) at.05 Ue = 45 V Sum of I 2 dt (ka 2 s) , 0,0 0, 0 00 Prospective Isc (ka) 24-2 A (GV2-ME) A A A 7-2 A A 4-8 A A A A pages / to /42 pages /4 to /48 pages /49 to /5 /4
13 Curves Thermal-magnetic motor circuit-breakers type GV2-P Thermal limit on short-circuit for GV2-P Thermal limit in ka 2 s in the magnetic operating zone Sum of I 2 dt = f (prospective Isc) at.05 Ue = 45 V Sum of I 2 dt (ka 2 s) , 0,0 0, 0 00 Prospective Isc (ka) A A A A -8 A A A A A pages / to /42 pages /4 to /48 pages /49 to /5 /5
14 Curves (continued) Magnetic motor circuit-breakers types GV2-L Thermal limit on short-circuit for GV2-L Thermal limit in ka 2 s in the magnetic operating zone Sum of I 2 dt = f (prospective Isc) at.05 Ue = 45 V Sum of I 2 dt (ka 2 s) , 0,0 0, 0 00 Prospective Isc (ka) 25 A and 2 A 5 6. A 2 8 A 6 4 A 4 A A 4 0 A 8.6 A pages / to /42 pages /4 to /48 pages /49 to /5 /6
15 Curves Magnetic motor circuit-breakers types GV2-LE Thermal limit on short-circuit for GV2-LE Thermal limit in ka 2 s in the magnetic operating zone Sum of I 2 dt = f (prospective Isc) at.05 Ue = 45 V Sum of I 2 dt (ka 2 s) , 0,0 0, 0 00 Prospective Isc (ka) 2 A 6 6. A 2 25 A 7 4 A 8 A A 4 4 A 9.6 A 5 0 A pages / to /42 pages /4 to /48 pages /49 to /5 /7
16 Curves (continued) Magnetic motor circuit-breakers types GV2-L and GV2-LE Thermal limit on short-circuit For GV2-L and GV2-LE + thermal overload relay LRD or LR2-K Thermal limit in ka 2 s in the magnetic operating zone Sum of I 2 dt = f (prospective Isc) at.05 Ue = 45 V Sum of I2dt (ka2 s) , 0 0,0 0, Prospective Isc (ka) 2 A (GV2-LE2) 7 4 A 2 25 A and 2 A (GV2-L2) A 8 A 9.6 A 4 4 A 0 Limit of rated ultimate breaking capacity on short-circuit 5 0 A of GV2-LE (4, 8 and 25 A ratings) 6 6. A pages / to /42 pages /4 to /48 pages /49 to /5 /8
17 Earth loop impedance Maximum Earth Fault Loop Impedance Z S for 0.4s disconnection time with U 0 20V () Thermal Adjustment Magnetic Tripping Tolerance Maximum Loop Reference Range I n Current I m I m +20% Impedance Z s (A) (A) (A) (Ω) GV2-ME GV2-ME GV2-ME GV2-ME GV2-ME GV2-ME GV2-ME GV2-ME GV2-ME GV2-ME GV2-ME GV2-ME GV2-ME GV2-ME GV2-ME GV2-P GV2-P GV2-P GV2-P GV2-P GV2-P GV2-P GV2-P GV2-P GV2-P GV2-P GV2-P GV2-P GV2-P GV2-L GVL-L GV2-L GV2-L GV2-L GV2-L GV2-L GV2-L GV2-L GV2-L GV2-L GV2-LE GVL-LE GV2-LE GV2-LE GV2-LE GV2-LE GV2-LE GV2-LE GV2-LE GV2-LE GV2-LE GV2-LE GV2-RT GV2-RT GV2-RT GV2-RT GV2-RT GV2-RT GV2-RT GV2-RT GV2-RT GV2-RT GV2-RT () Whilst the IEE Regulations provide for a disconnection time of 5s for fixed equipment, the value of impedance obtained will limit the current to a level which may affect the starting characteristics of the motor. Dimensions, mounting: pages / to /42 pages /4 to /48 pages /49 to /5 /9
18 Discrimination Cascading Upstream circuit-breaker NSC00N NS00N NS00H NS00L Breaking capacity ka rms Downstream circuit-breaker Breaking capacity (ka rms) GV2-ME 4 A GV2-L 8 A GV2-P 8 A GV2-L or GV2-LE upstream circuit-breaker. Upstream circuit-breaker L4 L6 L20 L22 trip unit LE4 LE6 LE20 LE22 Rating (A) Downstream Rating Discrimination (A) circuit-breaker (A) GV2-ME0 0.6 GV2-ME GV2-ME0 0.4 GV2-ME GV2-ME GV2-ME GV2-ME GV2-ME GV2-ME0 6. GV2-ME4 0 GV2-ME6 4 GV2-ME20 8 GV2-ME2 2 GV2-ME22 25 GV2-ME2 2 GV2-P0 0.6 GV2-P GV2-P0 0.4 GV2-P GV2-P GV2-P GV2-P GV2-P GV2-P0 6. GV2-P4 0 GV2-P6 4 GV2-P20 8 GV2-P2 2 GV2-P22 25 GV2-L0 0.4 GV2-L GV2-L GV2-L GV2-L GV2-L GV2-L0 6. GV2-L4 0 GV2-L6 4 GV2-L20 8 GV2-L22 25 GV2-LE0 0.4 GV2-LE GV2-LE GV2-LE GV2-LE GV2-LE GV2-LE0 6. GV2-LE4 0 GV2-LE6 4 GV2-LE20 8 GV2-LE22 25 GV2-LE2 2 Total discrimination zone 50 Partial discrimination limited to 50 ka No discrimination Dimensions, mounting: pages / to /42 pages /4 to /48 pages /49 to /5 /20
19 Discrimination Compact NS00 or NS60N/H/L upstream circuit-breaker with TM-D trip unit Upstream circuit-breaker NS00N/H/L NS60N/H/L Trip unit TM-D TM-D Rating (A) Downstream Thermal Rating Discrimination (ka) circuit-breaker overload relay (A) GV2-ME0 Built-in GV2-ME02 Built-in GV2-ME0 Built-in GV2-ME04 Built-in GV2-ME05 Built-in 0.6 GV2-ME06 Built-in.6 GV2-ME07 Built-in GV2-ME08 Built-in GV2-ME0 Built-in GV2-ME4 Built-in 6 0 GV2-ME6 Built-in 9 4 GV2-ME20 Built-in GV2-ME2 Built-in GV2-ME22 Built-in GV2-ME2 Built-in GV2-P0 Built-in GV2-P02 Built-in GV2-P0 Built-in GV2-P04 Built-in GV2-P05 Built-in 0.6 GV2-P06 Built-in.6 GV2-P07 Built-in GV2-P08 Built-in GV2-P0 Built-in GV2-P4 Built-in 6 0 GV2-P6 Built-in 9 4 GV2-P20 Built-in 8 0 GV2-P2 Built-in GV2-P22 Built-in GV2-L0 LR2-D GV2-L04 LR2-D GV2-L05 LR2-D GV2-L06 LR2-D06.6 GV2-L07 LR2-D GV2-L08 LR2-D GV2-L0 LR2-D GV2-L4 LR2-D GV2-L6 LR2-D6 9 GV2-L20 LR2-D GV2-L22 LR2-D GV2-LE0 LR2-K GV2-LE0 LR2-K GV2-LE0 LR2-K GV2-LE04 LR2-K GV2-LE04 LR2-K GV2-LE05 LR2-K GV2-LE05 LR2-K GV2-LE06 LR2-K GV2-LE06 LR2-K GV2-LE07 LR2-K GV2-LE07 LR2-K GV2-LE08 LR2-K GV2-LE08 LR2-K GV2-LE0 LR2-K GV2-LE0 LR2-K GV2-LE4 LR2-K GV2-LE4 LR2-K GV2-LE4 LR2-D4 7 0 GV2-LE6 LR2-D6 9 GV2-LE20 LR2-D GV2-LE22 LR2-D GV2-LE2 LR2-D Total discrimination 6 Partial discrimination limited to 6 ka No discrimination Dimensions, mounting: pages / to /42 pages /4 to /48 pages /49 to /5 /2
20 Discrimination (continued) Compact NS60 or 250N/H/L upstream circuit-breaker with TM-D trip unit Upstream circuit-breaker NS60N/H/L NS250N/H/L Trip unit TM-D TM-D Rating (A) Downstream Thermal Rating Discrimination (ka) circuit-breaker overload relay (A) GV2-ME0 Built-in GV2-ME02 Built-in GV2-ME0 Built-in GV2-ME04 Built-in GV2-ME05 Built-in 0.6 GV2-ME06 Built-in.6 GV2-ME07 Built-in GV2-ME08 Built-in GV2-ME0 Built-in 4 6. GV2-ME4 Built-in 6 0 GV2-ME6 Built-in 9 4 GV2-ME20 Built-in 8 GV2-ME2 Built-in 7 2 GV2-ME22 Built-in GV2-ME2 Built-in 24 2 GV2-P0 Built-in GV2-P02 Built-in GV2-P0 Built-in GV2-P04 Built-in GV2-P05 Built-in 0.6 GV2-P06 Built-in.6 GV2-P07 Built-in GV2-P08 Built-in GV2-P0 Built-in 4 6. GV2-P4 Built-in 6 0 GV2-P6 Built-in 9 4 GV2-P20 Built-in 8 GV2-P2 Built-in 7 2 GV2-P22 Built-in GV2-L0 LR2-D GV2-L04 LR2-D GV2-L05 LR2-D GV2-L06 LR2-D06.6 GV2-L07 LR2-D GV2-L08 LR2-D GV2-L0 LR2-D0 4 6 GV2-L4 LR2-D GV2-L6 LR2-D6 9 GV2-L20 LR2-D2 2 8 GV2-L22 LR2-D GV2-LE0 LR2-K GV2-LE0 LR2-K GV2-LE0 LR2-K GV2-LE04 LR2-K GV2-LE04 LR2-K GV2-LE05 LR2-K GV2-LE05 LR2-K GV2-LE06 LR2-K GV2-LE06 LR2-K GV2-LE07 LR2-K GV2-LE07 LR2-K GV2-LE08 LR2-K GV2-LE08 LR2-K GV2-LE0 LR2-K GV2-LE0 LR2-K GV2-LE4 LR2-K GV2-LE4 LR2-K GV2-LE4 LR2-D4 7 0 GV2-LE6 LR2-D6 9 GV2-LE20 LR2-D2 2 8 GV2-LE22 LR2-D GV2-LE2 LR2-D Total discrimination 6 Partial discrimination limited to 6 ka No discrimination Dimensions, mounting: pages / to /42 pages /4 to /48 pages /49 to /5 /22
21 Discrimination Compact NS00N/H/L upstream circuit-breaker with STR22SE trip unit Upstream circuit-breaker NS00N/H/L Trip unit STR22SE Rating (A) Downstream Thermal Rating Discrimination (ka) circuit-breaker overload relay (A) GV2-ME0 Built-in GV2-ME02 Built-in GV2-ME0 Built-in GV2-ME04 Built-in GV2-ME05 Built-in 0.6 GV2-ME06 Built-in.6 GV2-ME07 Built-in GV2-ME08 Built-in GV2-ME0 Built-in GV2-ME4 Built-in GV2-ME6 Built-in GV2-ME20 Built-in 8.2 GV2-ME2 Built-in GV2-ME22 Built-in GV2-ME2 Built-in GV2-P0 Built-in GV2-P02 Built-in GV2-P0 Built-in GV2-P04 Built-in GV2-P05 Built-in 0.6 GV2-P06 Built-in.6 GV2-P07 Built-in GV2-P08 Built-in GV2-P0 Built-in GV2-P4 Built-in GV2-P6 Built-in GV2-P20 Built-in GV2-P2 Built-in GV2-P22 Built-in GV2-L0 LR2-D GV2-L04 LR2-D GV2-L05 LR2-D GV2-L06 LR2-D06.6 GV2-L07 LR2-D GV2-L08 LR2-D GV2-L0 LR2-D GV2-L4 LR2-D GV2-L6 LR2-D GV2-L20 LR2-D GV2-L22 LR2-D GV2-LE0 LR2-K GV2-LE0 LR2-K GV2-LE0 LR2-K GV2-LE04 LR2-K GV2-LE04 LR2-K GV2-LE05 LR2-K GV2-LE05 LR2-K GV2-LE06 LR2-K GV2-LE06 LR2-K GV2-LE07 LR2-K GV2-LE07 LR2-K GV2-LE08 LR2-K GV2-LE08 LR2-K GV2-LE0 LR2-K GV2-LE0 LR2-K GV2-LE4 LR2-K GV2-LE4 LR2-K GV2-LE4 LR2-D GV2-LE6 LR2-D GV2-LE20 LR2-D GV2-LE22 LR2-D GV2-LE2 LR2-D Total discrimination 6 Partial discrimination limited to 6 ka No discrimination Dimensions, mounting: pages / to /42 pages /4 to /48 pages /49 to /5 /2
22 Discrimination (continued) Compact NS60 60N/H/L upstream circuit-breaker with STRlllE trip unit Upstream circuit-breaker NS60N/H/L NS250N/H/L NS400 or 60N/H/L Trip unit STR22SE STR22SE STR2SE/5UE Rating (A) Downstream Thermal Rating Discrimination (ka) circuit-breaker overload relay (A) GV2-ME0 Built-in GV2-ME02 Built-in GV2-ME0 Built-in GV2-ME04 Built-in GV2-ME05 Built-in 0.6 GV2-ME06 Built-in.6 GV2-ME07 Built-in GV2-ME08 Built-in GV2-ME0 Built-in 4 6. GV2-ME4 Built-in 6 0 GV2-ME6 Built-in 9 4 GV2-ME20 Built-in 8 GV2-ME2 Built-in 7 2 GV2-ME22 Built-in GV2-ME2 Built-in 24 2 GV2-P0 Built-in GV2-P02 Built-in GV2-P0 Built-in GV2-P04 Built-in GV2-P05 Built-in 0.6 GV2-P06 Built-in.6 GV2-P07 Built-in GV2-P08 Built-in GV2-P0 Built-in 4 6. GV2-P4 Built-in 6 0 GV2-P6 Built-in 9 4 GV2-P20 Built-in 8 GV2-P2 Built-in 7 2 GV2-P22 Built-in GV2-L0 LR2-D GV2-L04 LR2-D GV2-L05 LR2-D GV2-L06 LR2-D06.6 GV2-L07 LR2-D GV2-L08 LR2-D GV2-L0 LR2-D0 4 6 GV2-L4 LR2-D GV2-L6 LR2-D6 9 GV2-L20 LR2-D2 2 8 GV2-L22 LR2-D GV2-LE0 LR2-K GV2-LE0 LR2-K GV2-LE0 LR2-K GV2-LE04 LR2-K GV2-LE04 LR2-K GV2-LE05 LR2-K GV2-LE05 LR2-K GV2-LE06 LR2-K GV2-LE06 LR2-K GV2-LE07 LR2-K GV2-LE07 LR2-K GV2-LE08 LR2-K GV2-LE08 LR2-K GV2-LE0 LR2-K GV2-LE0 LR2-K GV2-LE4 LR2-K GV2-LE4 LR2-K GV2-LE4 LR2-D4 7 0 GV2-LE6 LR2-D6 9 GV2-LE20 LR2-D2 2 8 GV2-LE22 LR2-D GV2-LE2 LR2-D Total discrimination 6 Partial discrimination limited to 6 ka No discrimination Dimensions, mounting: pages / to /42 pages /4 to /48 pages /49 to /5 /24
23 Characteristics Thermal-magnetic motor circuit-breakers types GV2-ME and GV2-P Circuit-breaker type GV2-ME GV2-P Environment Conforming to standards IEC/EN , , , UL 508, CSA C22-2 N 4, NF C 6-650, NF C6-20, 79-0, VDE 0, Product approvals CSA, CEBEC, GOST, TSE, UL, BV, GL, LROS, DNV, CSA, UL, PTB, EZU, GOST, TSE, DNV, LROS, GL, PTB, EZU, SETI, RINA BV, RINA Protective treatment TH TH Degree of protection Basic unit: IP 20 Basic unit: IP 20 conforming to IEC/EN In enclosure GV2-Mi0: IP 4 In enclosure GV2-Mi02: IP 55 Shock resistance 0 gn - ms 0 gn - ms conforming to IEC/EN Vibration resistance 5 gn (5 to 50 Hz) 5 gn (5 to 50 Hz) conforming to IEC/EN Ambient air temperature - storage C operation C in open air in enclosure In open air Temperature compensation C in free air Flame resistance C conforming to IEC/EN Maximum operating altitude m Operating positions in relation to normal vertical mounting position GV2-ME GV2-MEii Cabling Number of conductors and c.s.a. Maximum Minimum Maximum Minimum Maximum Minimum Solid cable mm 2 2 x 6 2 x 2 x 6 2 x () 2 x 6 2 x Flexible cable without cable end mm 2 2 x 6 2 x.5 2 x 4 2 x.5 () 2 x 6 2 x.5 Flexible cable with cable end mm 2 2 x 4 2 x 2 x 4 2 x Suitable for isolation Yes Yes conforming to IEC/EN Tightening torque N.m.7.7 Resistance to mechanical impact J Enclosed: 6 Sensitivity to phase failure Yes, conforming to IEC/EN () For c.s.a. of to.5 mm 2, use cable end reducer LA9-D99. Dimensions, mounting: pages / to /42 pages /4 to /48 pages /49 to /5 /25
24 Characteristics (continued) Thermal-magnetic motor circuit-breakers types GV2-ME and GV2-P Circuit-breaker type GV2-ME GV2-P Technical characteristics Utilisation category conforming to IEC/EN A A conforming to IEC/EN AC- AC- Rated operational voltage (Ue) conforming to IEC/EN V Rated insulation voltage (Ui) conforming to IEC/EN V conforming to CSA C22-2 n 4, UL 508 V Rated operational frequency conforming to IEC/EN Hz 50/60 50/60 Rated impulse withstand voltage (U imp) kv 6 6 conforming to IEC/EN Total power dissipated per pole W Mechanical durability C.O. 00,000 00,000 (C.O.: Closing, Opening) Electrical durability C.O. 00,000 00,000 for AC- duty 440 V In/2 Duty class C.O./h (maximum operating rate) Rated duty conforming to IEC/EN Uninterrupted duty Uninterrupted duty Maximum conventional rated A thermal current (Ith) conforming to IEC/EN Dimensions, mounting: pages / to /42 pages /4 to /48 pages /49 to /5 /26
25 Characteristics Magnetic motor circuit-breakers types GV2-LE and GV2-L Circuit-breaker type GV2-LE GV2-L Environment Conforming to standards IEC/EN , IEC/EN , NF C 6-650, NF C 6-20, NF C 79-0, VDE 0, VDE 0660 Approvals BV, GL, LROS, DNV, TSE, UL, CSA BV, GL, LROS, DNV, EZU, GOST, TSE, UL, CSA pending Protective treatment TH TH Shock resistance to IEC/EN gn 0 gn Vibration resistance to IEC/EN gn (5 to 50 Hz) 5 gn (5 to 50 Hz) Ambient air temperature - storage C operation C Flame resistance to IEC/EN C Maximum operating altitude m Operating position Cabling Number of conductors and c.s.a. Max Min Max Min Solid cable mm 2 2 x 6 2 x 2 x 6 2 x Flexible cable without cable end mm 2 2 x 6 2 x.5 2 x 6 2 x.5 Flexible cable with cable end mm 2 2 x 4 2 x 2 x 4 2 x Suitability for isolation Yes Yes conforming to IEC/EN Tightening torque N.m.7.7 Resistance to mechanical impact J Utilisation category conforming to IEC/EN A A conforming to IEC/EN AC- AC- Rated operational voltage (Ue) conforming to IEC/EN V Rated insulation voltage (Ui) conforming to IEC/EN V Rated operational frequency conforming to IEC/EN Hz 50/60 50/60 Rated impulse withstand voltage (U imp) to IEC/EN kv 6 6 Total power dissipated per pole W.8.8 Mechanical durability C.O. 00,000 00,000 (C.O.: closing, opening) Electrical durability for AC- duty C.O. 00,000 00,000 Duty class (maximum operating rate) C.O./h Rated duty to IEC/EN Continuous duty Continuous duty pages / to /42 pages /4 to /48 pages /49 to /5 /27
26 Characteristics Thermal-magnetic motor circuit-breakers types GV2 Electric trips Trip type GV-AU GV-AX () GV-AS Characteristics of electric trips Rated insulation voltage (Ui) conforming to IEC/EN V conforming to CSA C22-2 n 4, V UL 508 Operational voltage conforming to IEC/EN V Un 0.7. Un Drop-out voltage V Un Un. Inrush consumption a VA 2 4 c W Sealed consumption a VA.5 5 c W..6 Operating time From the moment the voltage reaches its operational value until opening of the circuit-breaker. conforming to IEC/EN ms 0 5 On-load factor 00 % Cabling Number of conductors or 2 Solid cable mm Flexible cable without cable end mm Flexible cable with cable end mm Tightening torque N.m.4 max Mechanical durability C.O. 00,000 (C.O.: Closing-Opening) () Wiring scheme of undervoltage trip for dangerous machines (conforming to INRS) on GV2-ME only, see page /49. pages / to /42 pages /4 to /48 pages /49 to /5 /28
27 Characteristics Thermal-magnetic motor circuit-breakers types GV2 Auxiliary contacts Contact type Instantaneous auxiliary Fault signalling Instantaneous auxilairy GV-AN, GV-AD GV-AD, GV-AM () GV-AE Rated insulation voltage (Ui) (associated insulation coordination) V (690 in relation to to IEC/EN main circuit) to CSA C22-2 n 4 and UL 508 V Conventional rated thermal current (Ith) to IEC/EN A to CSA C22-2 n 4 and UL 508 A 5 Mechanical durability C.O. 00, ,000 Operational power and current to IEC/EN , a.c. operation AC-5/00,000 C.O. AC-4/000 C.O. AC-5/00,000 C.O. Rated operational voltage (Ue) V Operational power, normal conditions VA Occasional breaking and making VA ,000 5,000,000 2, capacities, abnormal conditions Rated operational current (Ie) A Operational power and current to IEC/EN , d.c. operation DC-/00,000 C.O. DC-/000 C.O. DC-/00,000 C.O. Rated operational voltage (Ue) V (2) Operational power, normal conditions W Occasional breaking and making W capacities, abnormal conditions Rated operational current (Ie) A Low level switching contact reliability GV-AE: Number of failures for for n million operating cycles (7 V-5 ma): = 0-6 Minimum operational conditions V 7 d.c. operation ma 5 Short-circuit protection By GB2-CBpp circuit-breaker (rating according to operational current GB2-CB06 or for Ue 45 V) or by gg fuse 0 A max gg fuse 0 A max Cabling, screw clamp terminals Number of conductors 2 Solid cable mm Flexible cable without cable end mm Flexible cable with cable end mm Tightening torque N.m.4 max.4 max Cabling, spring terminal connections GV-AN only Flexible cable without cable end mm Contact operation, instantaneous auxiliary contacts Power pole Contact open GV-AN20 N/O Contact closed N/O GV-AN GV-AE GV-AE20 GV-AE GV-ADpp0 N/O N/C N/O N/C N/O N/O N/O N/C N/O Operation of fault signalling contacts GV-AM Change of state following tripping on short-circuit. GV-AD0pp and GV-AD0pp Change of state following tripping on short-circuit, overload or undervoltage. GV-ADpp0 N/C () For application example of fault signalling contact and short-circuit signalling contact, see page /49. (2) Add an RC circuit type LA4-D to the load terminals, see page 2/87. pages / to /42 pages /4 to /48 pages /49 to /5 /29
28 Characteristics Thermal-magnetic motor circuit-breakers types GV2 Auxiliary contacts Characteristics of -pole busbars GV2-Gppp Rated insulation voltage (Ui) To IEC/EN V 690 Conventional rated thermal current To IEC/EN A 6 (Ith) Permissible peak current ka (I peak) Permissible thermal limit ka 2 s 04 (I 2 t) Degree of protection To IEC/EN IP 20 Characteristics of terminal blocks GV2-G05 and GV-G09. Rated insulation voltage (Ui) To IEC/EN V 690 Conventional rated thermal current To IEC/EN A 6 (Ith) Degree of protection To IEC/EN IP 20 Cabling Solid cable mm 2 x.5 to 25 conductor or 2 x.5 to 0 conductors Flexible cable without mm 2 x.5 to 25 conductor or 2 x 2.5 to 0 conductors cable end Flexible cable with mm 2 x.5 to 6 conductor or 2 x.5 to 4 conductors cable end Tightening torque Connector N.m 2.2 Screw clamp N.m.7 Characteristics of current limiters (GV2-ME and GV2-P) Type GV-L LA9-LB920 Rated insulation voltage (Ui) To IEC/EN V Conventional rated thermal current To IEC/EN A 6 6 (Ith) Operating threshold rms current A 500 (non adjustable threshold) 000 (non adjustable threshold) Cabling conductor 2 conductors conductor 2 conductors Solid cable mm Flexible cable without mm cable end Flexible cable with mm cable end Tightening torque N.m 2.2 pages / to /42 pages /4 to /48 pages /49 to /5 /0
08/072 PKZ2 Motor-Protective Circuit-Breakers Tripping Characteristics
0/07 PKZ Tripping Characteristics Moeller HPL0-00/00 S-PKZ high-capacity contact module, SEA-PKZ contact module Normal switching duty AC-/00V kw A Rated output of three-phase motors 0...0 Hz. 7..... 0.7
More informationGeneral characteristics, Products
The Feature Packed line of Manual Motor Protectors Eaton s new XT family of Manual Motor Protectors (MMPs) features a pushbutton or rotary ON/OFF manual disconnect, Class adjustable bimetallic overload
More informationSealing possibility Electrical endurance (ops) Mechanical endurance (ops) Overvoltage category Standards
Miniature circuit breaker ETIMAT 7,7 0.5 Rated voltage Rated current Rated frequency Rated short-circuit capacity Energy limiting class characteristic Build-in width Mounting on the rail 0/00 V AC, max.
More informationC120N circuit-breakers B, C and D curves EN 60898/EN 61009: IEC : 10 ka
C0N circuit-breakers B, C and D curves EN 09/EN 009: 0000 - IEC 097-: 0 ka function # protection of cables against overloads and short-circuits in final distribution # manual control and isolation # earth
More informationMCB NB1-63H Miniature Circuit Breaker
NB-H Miniature Circuit Breaker. General. Function protection of circuits against short-circuit currents, protection of circuits against overload currents, switch, isolation, NB-H circuit-breakers are used
More informationTeSys contactors. TeSys D contactors. 690 V on a and c
Selection guide TeSys D contactors Applications All types of control system Rated operational current le max AC- (Ue y 0 V) A A A A A A le AC- (q y 0 C) 0/ A / A /0 A 0 A Rated operational voltage 0 V
More informationThermal-Magnetic Circuit Breaker 2210-T2...
Thermal-Magnetic Circuit Breaker 0-T... Description One, two and three pole thermal-magnetic circuit breakers with trip-free mechanism and toggle actuation (S-type TM CBE to EN 6094/IEC 94). Featuring
More informationFAZ tripping characteristics at 30 C: B, C, D to IEC/EN FAZ tripping characteristics at 30 C: R to IEC/EN
FAZ, AZ High-Capacity Tripping Characteristics Moeller HPL011-001/00 1/07 FAZ tripping characteristics at 0 C: B, C, D to IEC/EN 0 9 FAZ tripping characteristics at 0 C: R to IEC/EN 0 97 t [s] 700 00 100
More informationOverload Relays. SIRIUS 3RU1 Thermal Overload Relays. 3RU11 for standard applications. 5/46 Siemens LV 1 AO 2011
SIRIUS 3RU1 Thermal Overview 1 2 7 3 4 6 "Increased safety" type of EEx e according to ATEX directive 94/9/EC The 3RU11 thermal overload relays are suitable for the overload of explosion-proof motors with
More information90 MCB MODULAR CIRCUIT BREAKERS FOR CIRCUIT PROTECTION
MCB - MTC - MT - MTHP Technical data TYPE MTC MT MTC45 MTC60 MTC100 MT 45 MT 60 Rated current (In) (A) 2-32 6-32 6-32 6-40 1-63 Utilization category A A A A A Rated operational voltage (Ue) (V) 230/400-240/415
More informationTeSys enclosed starters 2
Characteristics, references TeSys enclosed starters D..L. starters for motor control 0. to. kw with -phase thermal overload relay with protected phases Characteristics () Conforming to standards IEC 0--,
More informationUL 1077 DIN Rail Supplementary Protectors
UL 0 DIN Rail Supplementary Protectors Product Overview UL 0 DIN Rail Supplementary Protectors PRODUCT OVERVIEW Product Overview Standard Features WMZS breaker terminals provide finger and back-of-hand
More informationVarius SUMMARY OF MODELS OF HRC FUSE-LINKS
SUMMARY OF MODELS OF HRC FUSE-LINKS Type PNA000 PHNA000 PNA00 PHNA00 Rated current I n up to A up to 0 A up to A up to 0 A Rated voltage U n AC 00 V, 00 V 90 V 00 V 90 V DC 0 V 0 V 0 V 0 V Fuse-link size
More informationRequest Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.
Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager. 1 -A - Introduction - Thank for your purchasing MITSUBISHI ELECTRIC MELPRO TM D Series Digital Protection
More information5SP and 5SY Supplementary Protection UL 1077
Product Guide 5SP and 5SY Supplementary Protection UL 077 for North merican and International applications usa.siemens.com/5sy Table of contents Certifications, standards, features and description Characteristic
More informationSiemens AG Miniature Circuit Breakers. Totally Integrated Power SENTRON. Configuration. Edition 10/2014. Manual. siemens.
Siemens AG 05 Totally Integrated Power SENTRON Configuration Manual Edition 0/0 siemens.com/lowvoltage Siemens AG 05 Siemens AG 05 Introduction 5SL miniature circuit breakers 5SY and 5SP miniature circuit
More information5SJ4...-.HG Circuit Breakers to IEC and UL 489
Siemens AG 009 5SJ...-.HG Circuit Breakers to IEC and UL 89 BETA Low-Voltage Circuit Protection Compliance with industry standards is a must in today's manufacturing environment. Worldwide acceptance is
More informationX T O B P 1 6 B C 1 S
9 Overload Relays XTOB, XTOT May 07 Contents Description Page Overload Relays XTOB, XTOT Selection................ 9 Product Selection.......... 95 Accessories............... 9 Technical Data and Specifications............
More informationC60N circuit breakers0 B, C and D curves IEC 60898: 6000 A, IEC : 10 ka
C0N circuit breakers0 B, C and s IEC 0898: 000 A, IEC 097-: 0 ka Function b The circuit-breakers combine the following functions: v protection of circuits against short-circuit currents v protection of
More informationTeSys protection components Thermal-magnetic motor circuit-breakers GV2 ME and GV2 P
Dimensions GV ME and GV P Dimensions GV ME GV AX GV AD, AM, AN, AU, AS, AX, X Block GV AD, AM, AN Block GV AU, AS, AX GV AE b, X b GV MEpp GV MEpp () Maximum X Electrical clearance 0 mm for Ue y 0 V,,,
More informationIssued August DATA SHEET. 3VT3 MCCB up to 630 A
ssued August 9 DATA SHEET VT MCCB up to 6 A Based on Siemens Catalog V 6 8 Circuit breakers Switch disconnectors Technical specifications Specifications Type VT 76-AA6/6/56-AA, VT 76-AA6/6/56-AA Circuit
More information90 MCB range Modular circuit breakers for circuit protection
MCB - MTC - MT - MTHP Technical data TYPE MTC MT MTC45 MTC60 MTC100 MT 45 MT 60 Rated current (In) (A) 2-32 6-32 6-32 6-40 1-63 Utilization category A A A A A Rated operational voltage (Ue) (V) 230 / 400
More informationBETA Protecting Miniature Circuit Breakers
Siemens AG 00 / Product overview / High-capacity range 000 A 0000 A 0000 A, high current 0000 A, universal current 000 A ka /0 Comfort range with plug-in terminal / Compact range +N in MW / Additional
More informationF F FAULT CURRENT Prospective. 1. Introduction. 2. Types of fault conditions
FAULT CURRENT F F13-13 FAULT CURRENT - Contents 1. Introduction 2. Types of fault conditions 3 fault current must be determined 3.1 Purposes for which of prospective fault current magnitudes are used 3.2
More informationIssued August DATA SHEET. 3VT5 MCCB up to 1600 A
ssued August 9 DATA SHEET VT5 MCCB up to 0 A Based on Siemens Catalog V 8 Standard circuit breakers Releases Technical specifications Specifications VT5 circuit breakers Switch disconnectors Type Standards
More informationThermal-Magnetic Circuit Breaker 2210-S2...
Thermal-Magnetic Circuit Breaker 0-S... Description One, two and three pole thermal-magnetic circuit breakers with trip free mechanism and toggle actuation (S-type TM CBE to EN 60934/IEC 934). Designed
More informationThermal-Magnetic Circuit Breaker 2210-S2...
Description One, two and three pole thermal-magnetic circuit breakers with trip free mechanism and toggle actuation (S-type TM CBE to EN 6094/IEC 94). Designed for panel or plug-in mounting. Available
More information440V 500V V / / /2 12.
-26 Manual Motor Protectors March 0 B-Frame D-Frame Table -6. XTPR Rotary Manual Motor Protectors with Screw Terminals Global Ratings and North American Ratings Type and Type 2 Coordination Motor Protective
More information3VT4 Molded Case Circuit Breakers up to 1000 A
VT4 Molded Case Circuit Breakers up to 00 A Catalog Technical nformation VT4 Molded Case Circuit Breakers up to 00 A General data / - Overview Circuit breakers Switch disconnectors / - Selection and ordering
More informationATyS Automatic and remotely operated transfer switches from 125 to 3200 A
atys-p_001_b atys_d_001_a_1_cat ATyS p I-0-II 4P ATyS d I-0-II 4P Function The ATyS are three-phase motorised transfer switches with positive break indication. They enable the on load transfer of two three-phase
More informationTo order, specify : Types Protection functions Current surge Asymmetry and loss of phase. Operating principle
otor protection relays - T - FWIT Since % of -phase motor failures are due to load problems or loss of phase, the CROUZET range of motor protection relays is indispensable! models give motor protection
More informationNR2 Thermal Overload Relay
Contactors,, Starters. Type designation N - Current class Design sequence No. N Thermal Overload elay. General. Certificates: CE, KEM, UkrSEPO, GOST, CC, UL;. Electric ratings: C 0/0z, 90V, 0.~30;.3 Tripping
More informationThermal-Magnetic Circuit Breaker 2210-S2..
Thermal-Magnetic Circuit Breaker -S.. Description One, two and three pole thermal-magnetic circuit breakers with trip-free mechanism and toggle actuation (S-type TM CBE to EN 60934/IEC 934). Designed for
More informationVX25 Enclosure System. Technical documentation PE conductor connection, current carrying capacity
VX Enclosure System Technical documentation PE conductor connection, current carrying capacity Enclosure system VX Contents Contents. General remarks. Introduction. Notes on the design of the earthing
More informationMagnetic and Hydraulic-Magnetic Circuit Breaker 8340-T...
Magnetic and Hydraulic-Magnetic Circuit Breaker 830-T... Description ngle, two and three pole magnetic and hydraulic-magnetic circuit breakers with trip-free mechanism and toggle actuation. A choice of
More informationThermal-Magnetic Circuit Breaker 2210-S2..
Thermal-Magnetic Circuit Breaker -S.. Description One, two and three pole thermal-magnetic circuit breakers with trip free mechanism and toggle actuation (S-type TM CBE to EN 60934/IEC 934). Designed for
More informationTEST REPORT IEC/EN Circuit-breakers for over current protection for household and similar installations
Test Report issued under the responsibility of: TEST REORT IEC/EN 60898-1 Circuit-breakers for over current protection for household and similar installations Report Reference No.... : 130100913SHA-004
More informationInstruction. Vacuum Circuit Breaker Operator Module. Type 3AH 4.16kV to 38kV. Power Transmission & Distribution
Instruction 0001-22-2--00 Vacuum Circuit Breaker Operator Module Type 3AH 4.16kV to 38kV Power Transmission & Distribution Hazardous voltages and high-speed moving parts. Will cause death, serious injury
More informationMiniatur Circuite Breakers (MCB)
Redline Miniatur Circuite Breakers (MCB) Technical data MCB s Series Standards Tripping characteristics Nominal current Calibration temperature Number of poles (#mod) Neutral pole protected Nominal voltage
More informationThermal-Magnetic Circuit Breaker 2210-S2..
Thermal-Magnetic Circuit Breaker -S.. Description One, two and three pole thermal-magnetic circuit breakers with trip free mechanism and toggle actuation (S-type TM CBE to EN 6094/IEC 94). Designed for
More information6 - TeSys protection components: relays and controllers
Contents - : relays and controllers Selection guide............................................. page / Motor and machine protection................................. page / TeSys K, thermal overload relays
More informationRequest Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.
Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager. 1 -C - Safety section - This Safety section should be read before starting any work on the relay.
More informationLD-LP-LL-LC Rope Safety Switches with reset for emergency stop
TECHNICA DATASHEET D-P--C Rope Safety Switches with reset for emergency stop Metal or polymer housing, from one or three conduit entries Protection degree IP6 In conformity with EN ISO 13850 contact blocks
More informationMiniature Circuit Breaker
Miniature Circuit Breaker SG-DPN I E C / E N 0 8 9 8-5 0 0 SG-DPN Applications Approval / Marking Function and Feature Integrate with switch phase and neutral in one module Protection against both overload
More informationSIRCOVER Manual transfer switches from 125 to 3200 A
Manual transfer switches svr_149_a 3200 A Function are manual multipolar transfer switches with positive break indication. The family includes two ranges: AC for dead time switching (I-0-II), for overlapping
More informationBETA Protecting. Low-Voltage Fuse Systems. LV HRC fuse links. 3/36 Siemens ET B1 2008
LV HRC fuse links Overview LV HRC fuses are used for installation systems in non-residential, commercial and industrial buildings as well as in switchboards of power supply companies. They therefore protect
More informationNM1. Moulded Case Circuit Breaker NM1 P-084. Moulded Case Circuit Breakers. 2. Type designation. 1. General. 3. Classification N M 1- /
P0. Type designation N M / Type of Npole for P breaker* pplication: lank: for power distribution; : for motor protection elease type and accessory code (please refer to table on page 9) Number of poles
More informationGPS1B. Characteristics. Technical performances
Thermal and magnetic protection PS Motor protection devices Standards/pprovals 097, 0972, 097 N V 00T 0//2 UL/S UL/cULus Shipping approvals: RN ureau Lloyd s Register Veritas ermanischer Lloyd haracteristics
More informationTEST REPORT IEC :2002 Circuit-Breakers for overcorrect protection for household and similar installation
age 1 of 92 R e port ref. No.: C009-CB2012CQC-044407 Test Report issued under the responsibility of: TEST REORT IEC 60 898-1:2002 Circuit-Breakers for overcorrect protection for household and similar installation
More informationNon-Contact Safety Systems CMS
Selection table for non-contact safety system // Evaluation units Connection Desi Read head contact assembly Assured switch-on distance S ao [mm] Assured switch-on distance S ar [mm] Number of outputs
More informationTime - timing relays 1 Industrial relays, solid state output, width 22.5 mm
haracteristics Zelio ime - timing relays Industrial relays, solid state output, width. mm Presentation 08 he E9 range of relays is designed for simple, repetitive applications with short and intensive
More informationMasterpact. Installation recommendations
90 Installation recommendations Presentation Functions and characteristics 9 Dimensions and connection 5 Electrical diagrams 8 Operating conditions 92 Installation in switchboard 9 Door interlock catch
More informationPeriodic Inspection and Testing of Electrical Installations Sample Test ( ) Version 1.3 July 2018
Periodic Inspection and Testing of Electrical Installations Sample Test (2391-051) Version 1.3 July 2018 Sample Questions Version and date Change detail Section 1.3 July 2018 Modified questions/answers
More informationVarius SUMMARY OF MODELS OF HRC FUSE-LINKS. Type PVA10 / PV10 PV14 PV22 Rated current I n up to 32 A up to 63 A up to 125 A Rated voltage U n
Varius SUMMARY OF MODELS OF HRC FUSE-LINKS Type A / Rated current I n up to A up to up to A Rated voltage U n AC V, V V, V, 9 V V, V, 9 V DC V V V Fuse-link size x8 x x8 Utilization category of the fuse-link
More informationMoulded Case Circuit Breakers. Breaking capacity code: S:standard H:Higher type/r:current limiting type
TPact Moulded Case Circuit Breakers TPact Moulded Case Circuit Breaker. General Certificates: KEMA,CB; Electric ratings: AC0/0Hz, AC0V~90V DC0V~00V, A~0A; Standard: IEC/EN 097.. Type Designation TPact...
More informationFor the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.
Current Transducer LDSR 0.3-TP/SP1 I P R N = 300 ma For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Features Closed
More informationFault Calculation Methods
ELEC9713 Industrial and Commercial Power Systems Fault Calculation Methods There are two major problems that can occur in electrical systems: these are open circuits and short circuits. Of the two, the
More informationRedline Unibis : the solution Circuit protection
2 circuits in 1 mo Redline Unibis : the solution ircuit protection Unibis compact Ms are one of the latest introductions in the Redline range and are developed to reduce the size of the distribution board
More informationRedline. Line protection by means of MCB s. Protection against overloads. Circuit Protection T1.2
Redline Circuit Protection Line protection by means of MCB s Protective devices shall be capable of breaking any overcurrent up to and including the prospective shortcircuit current at the point where
More informationCat. No. 140M-F M-D8E-B
Bulletin 0M Motor Protection Circuit Breakers Product Selection Motor Protection Circuit Breakers Short Circuit Protection Standard Magnetic Trip ( x I e ) Motor Overload Protection Trip Class Rated Operational
More informationImpedance relay and protection assemblies
RXZK 21H, 22H, 23H 509 006-BEN Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970175) (SE970184) Features Micro-processor based impedance relay with R and X settings
More informationSelecting the current rating for equipment
Selecting the current rating for equipment 1. Rated current: the maximum continuous load current. Short-time withstand current: thermal withstand current term term is given for 1s or 3s short circuit current
More informationISOCON-6. 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER
ISOCON-6 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER Whilst every effort has been taken to ensure the accuracy of this document, we accept no responsibility for damage, injury, loss or expense resulting
More informationUniversal limit switches
SWITCHES.CROUZET.COM 1 LIMIT SWITCHES 0/016 Universal limit switches 8384 standard 8384 with positive break operation Conformity to standards IEC / EN 60947--1, including Annex K for version with positive
More informationFor the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.
Current Transducer HO-NP series I P N = 4, 6, 12, 15 A Ref: HO 4-NP, HO 6-NP, HO 12-NP, HO 15-NP For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary
More informationTHE DIMENSIONING OF ELECTRICAL CONDUCTORS FOR USE IN "PANEL BOARDS" ADDRESSED TO HAZARDOUS AREAS - PART THREE
July 04 THE DIMENSIONING OF ELECTRICAL CONDUCTORS FOR USE IN "PANEL BOARDS" ADDRESSED TO HAZARDOUS AREAS - PART THREE In this third part. we want to speak about how important is the correct sizing of the
More informationNR2 Thermal Overload Relay. 4. Technical Data. 1. General. 2. Type Designation. 3. Features. Item Series No. I/In Operating time Tp Test condition
s elays C US N Thermal Overload elay. General. Certificates: CB,CE, UL, PCT, CC, VDE;. Electric ratings: C 0/0z, V, 0.~;.3 Tripping class: 0;. Mounting version: a. Plug-in: vailable for N-.,, 3, 93, 0;
More informationSingle Phase Motors Technical Datasheets
Single Phase Motors Technical Datasheets EN A dynamic, strong and ambitious Group: Orange1 Holding is an international renown Group, one of the most important European manufacturers of single-phase and
More informationPHOENIX CONTACT - 04/2016. Features
Signal conditioner Data sheet 100238_de_06 1 Description PHOENIX CONTACT - 04/2016 Features The MCR-C-UI-UI(-450)-DCI(-NC) 3-way isolation amplifier is used to electrically isolate and convert analog signals.
More informationPerformance. Standards. Technical data
ilos Loadbreak disconnectors for INrail and wall mounting ilos up to ilos 2 up to los up to Order codes pplications pprovals / Marking ddon devices Performance INrail type and wall mounting type Main disconnector,
More informationCurrent protection I 2 t long-time protection
I 2 t long-time protection The long-time protection function protects cables against overloads. This function is based on true rms measurements. It is possible to select either I 2 t long-time protection
More informationXM1 Motor Protection Relay. Manual XM1 (Revision B)
XM1 Motor Protection Relay Manual XM1 (Revision B) Woodward Manual XM1 GB Woodward Kempen GmbH reserves the right to update any portion of this publication at any time. Information provided by Woodward
More informationElectrical installation solutions for buildings Technical details RCDs
/1 Electrical installation solutions for buildings Technical details RCDs Index Functions and classification criteria for RCDs / Limitation of specific let-through energy I t /5 Peak current Ip /9 Coordination
More information2-2. Bulletin 140M Motor Protection Circuit Breakers. Product Overview. Table of Contents. Standards Compliance. Certifications. General Information
Bulletin 0M Motor Protection Circuit Breakers Product Overview Bulletin 0M Motor Protection Circuit Breakers Current Rane 0. 0 A UL Listed for Motor Loads Short Circuit Protection Overload Protection Visible
More informationTest Report issued under the responsibility of: SHA-001 Date of issue... : Total number of pages... : 292. Report Number...
D Test Report issued under the responsibility of: TEST REORT Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCBs) art 1: General rules
More informationComplementary technical information
Complementary technical information Catalogue 2018 Low Voltage schneider-electric.com Green Premium TM Endorsing eco-friendly products in the industry Schneider Electric s Green Premium ecolabel is committed
More informationISOCON-3 MAINS POWERED ISOLATING SIGNAL CONVERTER
ISOCON-3 MAINS POWERED ISOLATING SIGNAL CONVERTER CAUTION: This equipment is designed for connection to mains voltages and must be used in accordance with this guide. If it is not, the safety protection
More informationTYPE. max. working voltage 250 V 350 V 500 V 750 V. max. overload voltage 500 V 700 V 1000 V 1500 V. basic specifications IEC B
FEATURES Non inductive High pulse loading capability. APPLICATIONS Application for overload and high voltage surge hazard circuits. DESCRIPTION A carbon film is deposited on a high grade ceramic body.
More information400 Volts, 50HZ 480 Volts, 60HZ 600 Volts, 60HZ TECHNICAL REFERENCE MANUAL
400 Volts, 50HZ 480 Volts, 60HZ 600 Volts, 60HZ TECHNICAL REFERENCE MANUAL FORM: MAP-TRM-E REL. July 2013 REV. 015 2013 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation Matrix AP Harmonic
More informationTable of Contents Pin-Configuration Selection Guide for HDE, HDS, & EFP
Table of Contents -Configuration Selection Guide for HDE, HDS, & EFP Service Voltage Rating... Electrical Service Ratings... Ampacity Ratings by Contact... Electrical Service Ratings Explained... Operating
More informationDigital Current Transducer HO-SW series I P N = A. Ref: HO 100-SW; HO 150-SW; HO 200-SW; HO 250-SW
Digital Current Transducer HO-SW series I P N = 100... 250 A Ref: HO 100-SW; HO 150-SW; HO 200-SW; HO 250-SW Bitstream output from on onboard Sigma Delta modulator. For the electronic measurement of current:
More informationFilm Capacitors. EMI suppression capacitors. Date: June 2018
Film Capacitors EMI suppression capacitors Date: June 2018 EPCOS AG 2018. Reproduction, publication and dissemination of this publication, enclosures hereto and the information contained therein without
More informationFL ballasts Electronic fixed output. PC TC PRO sr 1/2x11 42 W PC PRO compact
FL ballasts EL HE PC TC PRO sr 1/2x11 42 W PC PRO compact Product description CELMA Energy Efficiency Index A2 BAT / A2 T Nominal life-time up to 50,000 h (at ta 50 C with a failure rate max. 0.2 % per
More informationFEATURES APPLICATIONS DESCRIPTION QUICK REFERENCE DATA. PILKOR components
FEATURES Excellent anti-surge characteristics Stable characteristics to moisture resistance even in high resistance range. Good replacement for ceramic plate resistors. APPLICATIONS Telecommunication Industrial
More informationTeSys DF IEC-Type Fuseholders
TeSys DF IEC-Type 9080CT080 08 Contents... Page Characteristics......3 Accessories... Dimensions...5 Wirg diagrams...5 Fuses...6 7 Characteristics TeSys DF IEC-Type Fuseholder type DF8 DF0 DF DF DFCC Environment
More informationAlternating Current (AC): Alternating Current is electric current that reverses directions at regular intervals.
Glossary Alternating Current (AC): Alternating Current is electric current that reverses directions at regular intervals. American National Standards Institute (ANSI): American National Standards Institute
More informationFor the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.
Current Transducer HO-NSM series I PN = 8, 15, 25 A Ref: HO 8-NSM, HO 15-NSM, HO 25-NSM For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the
More informationPerformance. Standards. Technical data
ilos Loadbreak disconnectors for wall mounting ilos H up to 5 ilos 3 up to ilos 4 up to Order codes pplications pprovals / Marking ilos H34 ilos H ddon devices Performance Wall mounting Main disconnector,
More informationSemiconductor (AC) fuses
PSC gr sizes 7x - 690 VAC Main characteristics 6,9 grb 71 PA 200 6,9 grb 73 TTF 1000 + MS7V1-5 UR Ferraz Shawmut PSC-gRB 690 VAC fuse-links provide maximum flexibility in equipment design and ultimate
More informationCat. No. 140M-F M-D8E-B
Bulletin 0M Motor Protection Circuit Breakers Product Selection Motor Protection Circuit Breakers Short Circuit Protection Standard Magnetic Trip ( x I e ) Motor Overload Protection Trip Class Rated Operational
More informationModular contactors for installation into distribution
Modular contactors for installation into distribution boards Modular contactors for installation into distribution boards Modular contactor for installation into distribution board Description Modular
More informationInstallation Contactors ISU-xxx ISM-xxx
Installation Contactors ISU-xxx ISM-xxx Installation contactors are used in building technology switching cabinets of apartment blocks, office buildings, restaurants and hotels, shopping centres and hospitals
More information1SDC007004D0205. Coordination tables
Coordination tables Coordination tables Index Introduction...I Back-up... / Discrimination... / Motor protection... 3/ Switch-disconnectors... 4/ Coordination tables Introduction Discrimination and back-up
More informationProducts for Luminaire Protection and Power Adjustment Products
Products for uminaire Protection and Power Adjustment Products uminaire Protection evice For electronic devices When electronic components form part of lighting systems, it is often necessary to protect
More informationE8EB-N0C2B E8EB-N0B2B
Slim Sensor CSM DS_E 1 Ideal for Workpiece Position and Original Checking The to 1 kpa model can be used for workpiece position checking. The to 1MPa model is ideal for original pressure checking. Degree
More informationHigh-ohmic/high-voltage resistors
FEATURES These resistors meet the safety requirements of: UL1676 (range 510 kω to 11 MΩ) EN60065 BS60065 (U.K.) NFC 92-130 (France) VDE 0860 (Germany) High pulse loading capability Small size. APPLICATIONS
More informationPressure transmitters for industrial applications MBS 32 and MBS 33
Data sheet Pressure transmitters for industrial applications MBS 32 and MBS 33 The standard pressure transmitters MBS 32 and MBS 33 are designed for use in almost all industrial applications, and offer
More informationSafety Precautions WARNING If critical situations that could lead to user s death or serious injury is assumed by mishandling of the product.
Safety Precautions Observe the following notices to ensure personal safety or to prevent accidents. To ensure that you use this product correctly, read this User s Manual thoroughly before use. Make sure
More informationFor the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.
Current Transducer HO-NP/SP33 series I PN = 8, 15, 25 A Ref: HO 8-NP/SP33, HO 15-NP/SP33, HO 25-NP/SP33 For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the
More information1SDC007004D0201. Discrimination tables
1SDC007004D0201 Discrimination tables tables Introduction Index Introduction... I Back-up...1/1 Discrimination...2/1 tables Introduction Introduction... II Choosing the type of coordination for the protection
More information