1 Micro-grid to System Synchronization Based on Pre-Insertion Impedance Method (Version 1.0) By Peter Zhou University of Alberta Jan 30 th, 2015
2 Outline 1. What is Synchronization? 2. Synchronization Concerns? 3. How Synchronization is Performed In Reality? 4. Synchronization Challenges 5. Project Proposal 6. Project Solutions I. Theoretical Explanation of Transients II. What is Acceptable Transient Level? III. Practical V and f Range for Open Loop IV. Procedure for Selecting Z V. Impedance Bypass Considerations 7. Other Problems Caused? I. Stability Consideration II. Reactive Power Imbalance III. Bypass transient due to Q Imbalance 8. Advantages of Open Loop 9. Future Work
3 1. What is Synchronization? Synchronization in simple terms is a process of connecting an electrical island to another. The electrical island can be a generator, a micro-grid, or part of a large power grid. There are 3 synchronization scenarios to consider: Generator synchronizes to system Micro-grid synchronizes to system System synchronizes to another system
4 2. Synchronization Concerns? To perform a successful synchronization, these parameters must be matched closely across both sides of the breaker: Voltage Magnitude Phase Angle Frequency V Poor synchronization can: Result in High Synchronizing Transient Current Result in generator out of synchronism with system I peak V Z eq
5 3. How is Synchronization Performed in Reality? In practice, all synchronizations require a way of feedback control Through feedback control, V across synchronizing breaker is minimized Feedback Control Generator to System: System ~ Generator Multi-DG Feedback Controls ~ Micro-grid to System: System Micro-grid ~ ~ System to System: The synchronization process can become complicated. Require sophisticated coordination and tuning of many generators.
6 4. Synchronization Challenges Consider in a rural area, DG is really far away from utility substation, feedback control is not the best option. Disadvantages: Long tuning process Costly to build Low Reliability over long distance due to attenuation/loss 30 miles long, it is a present situation of a real MW-scale Micro-grid located in a rural area of Rio de Janeiro state of Brazil.
7 4. Synchronization Challenges Restoration of islands is required after a blackout or major faults. Effective Coordination and time are crucial factors in play to minimize impacts on utility customers. Feedback control is difficult to implement during system restoration process. Stabilize any surviving islands Recover Generation Restore loads Energize Transmission Synchronize islands to each other An example of IESO s restoration strategy
8 5. Project Proposal The idea is to use an impedance pre-insertion to reduce the transients effects from synchronization. I peak V Z eq V Z insert +X d +X t +X eq Impedance Pre-insertion
9 6. Project Solutions I. Theoretical Explanation of Transients SG Superposition Across Breaker Grid Zstator Z Insertion Zsys Local Load Assumptions: Constant Z type Load Grid as swing bus Zsys is the system short circuit impedance SG Zeq Grid Zs I Transient Zse Zsys X d
10 6. Project Solutions I. Theoretical Explanation of Transients Following analytical equations were derived based on the transient circuit of superposition. Closing transient is primarily a function of V, δ, and Z eq Z eq is equivalent impedance seen at breaker I peak is the max current among three phases VA IsyncA( t) sin( wt A ) sin( A ) e Z eq VB IsyncB ( t) sin( wt B ) sin( B ) e Z eq VC IsyncC ( t) sin( wt C ) sin( C ) e Z eq Rt / L Rt / L Rt / L I peak V Z eq V Z insert +X d +X t +X eq Impedance Pre-insertion
11 Te (pu) I Stator (pu) I sync (pu) 6. Project Solutions II. What is the acceptable transient level? According to IEEE standards C50.12 and C50.13, the synchronization criteria for both cylindrical and salient-pole synchronous generators are: Angle ±10 Voltage 0 to 5 % Slip ±0.067Hz If within IEEE standards, the maximum transients will be in an acceptable level: 1 0 Synchronizing Transients pu 1.91pu I peak =0.932 pu for synchronizing transient T e =0.91pu Reference Torque deviation pu time (s)
12 6. Project Solutions III. Practical V and f Range for Open Loop Busses inside both electrical islands to be synchronized have their voltages and frequencies inside a practical range that was decided by the utility protocol. The boundary conditions for voltage and frequency based on the practical range determine the worst case transients possible for open loop. After knowing the worst transients, the impedance size can be determined either by analytical approach or EMTP simulations. θ = 10 is the IEEE standard value. However, in most cases, faulty synchronization could happen due to higher than expected slip and breaker mechanism delay, a worst case of θ = 30 is assumed. Generator, Microgrid 1 2 Bulk Grid Table 1: Practical V and f Ranges Based on AIES Standard Vmin~Vmax (pu) Fmin~Fmax (Hz) Micro-grid (bus 1) 0.9~ ~60.2 System (bus 2) 0.9~ ~60.05
13 6. Project Solutions IV. Procedure for Selecting Z Start Run Load Flow (breaker Open) Based on AIES standard, worst case open loop synchronization scenario is determined as: V = 0.2pu Adjust Xfmer tap, local loading to match IEEE Synchronization Criteria o (5%,10,0.067 Hz) Adjust Xfmer tap, local loading to match Worst case open loop Synchronization Criteria o (20%,30,0.35 Hz) θ = 30 f = 0.35Hz Run EMTP Simulation with disturbance (Closing breaker) Run EMTP Simulation with disturbance (Closing breaker) Re-run Iopen loop> I? IEEE No Stop Obtain Z Yes Add Impedance at synchronization link (Initial Guess of Z obtained from Analytical solution)
14 6. Project Solutions IV. Procedure for Selecting Z Bottom figure is a comparison between analytical and EMTP simulation results of I peak Vs θ. They come to close agreements. θ is the primary factor that affects I peak when θ > 10. f = 0.35Hz has negligible impact on I peak.
15 6. Project Solutions IV. Procedure for Selecting Z The impedance to be inserted is selected based on the intersection of synchronizing transient curve with the acceptable reference line. As an example, Z=0.556 (pu) or 16.6 ohm is needed to limit the maximum transient level to be within the acceptable level incurred by V = 0.1pu, θ = 30, and f = 0.35Hz
16 6. Project Solutions V. Impedance Bypass Impedance bypass is required to avoid excessive energy dissipation due to the impedance insertion and restores the transmission line capacity back to its original state. After synchronization, the generator starts to have electromechanical oscillations. In order to bypass the impedance, it is desirable to wait for generator electromechanical oscillations to reach a steady state first. This way, a minimum voltage is seen across breaker 2, which guarantees a minimum bypass transient. V Micro-grid Generators BRK1 BRK2 Z Insertion Steady Power Flow Bulk Grid V1 P R 2 2 V1 V2 cos( ) XV2 sin( ) R X V1 Q RV sin( ) X V 1 V2 cos( ) R X
17 Switching Transients (pu) 6. Project Solutions V. Impedance Bypass Steady state P flow is caused by a micro-grid frequency different from the system frequency, which results in DG s change in mechanical power. Steady state Q flow is caused by the unmatched voltage magnitudes across the breaker. 3 Bypassing Under Different Conditions of V, f Frequency 5% droop 2.5 V 10%, 30 o Synchronizing Transient 2 f o Optimal Impedance = 16.6 ohm f s f 1.5 V 10%, f 0.35Hz P 1 V 0, f 0.35Hz 0.5 Bypass Transient V 10%, f 0.25Hz V 0, f 0.25Hz Power Output P o P Inserted Impedance (ohms)
18 7. Other Problems Caused? I. Stability Consideration Impedance insertion leads to further rotor angle advancements. But by how much? θ and f have most impact on transient stability of generator Inclusion of governor model can reduce the effects of f as shown due to changing Pm. Even in the worst case scenario, the generator remains angular stable. The max δ deviation is 5 when maximum impedance per unit is inserted. Micro-grid Frequency (Hz) System Frequency (Hz) f (Hz) 60.2 (max) (min) (min) (max) -0.35
19 7. Other Problems Caused? I. Stability Consideration The Inertia constant H of the generator will have an effect on the rotor angle deviation: Higher the H means higher the initial kinetic energy of rotor Initial kinetic energy can cause further rotor advancement in the transient swing due to f Doubling the H value with f = 0.35Hz in the worst case has negligible impact on the stability of generator. H = 2.52s
20 7. Other Problems Caused? II. Reactive Power Imbalance Reactive power imbalance is a concern after bypassing the impedance. Reactive power will flow from the side of higher voltage magnitude to the lower voltage magnitude bus. A result from high V difference across breaker. Consequences: 1. Sudden over-excitation or under-excitation of the field current. Both situations should be avoided to prevent heating or damage to the field windings and end iron core. Q I f I s P End Region Heating 2. Power quality concern. For example, voltage swells or sags that may affect some sensitive loads in the area.
21 7. Other Problems Caused? II. Reactive Power Imbalance Reactive power will flow from the side of higher voltage magnitude to the lower voltage magnitude bus. Reactive power imbalance not much a concern after synchronization because the inserted impedance is there to limit the amount of Q flow. However, after bypass, the Q flow will be a concern if voltage magnitudes not matched properly. One consequence of Q imbalance can result in a sudden over-excitation or underexcitation of the field voltage. Both situations should be avoided to prevent heating or damage to the field windings and end iron core. Second concern over reactive power imbalance is related to power quality. For example, voltage swells or sags that may affect some sensitive loads in the area. Although it is a secondary concern if no equipment damage occurs. Due to the reactive power imbalance, it is strongly suggested to run load flow after closing the synchronizing breaker to check any nearby generators have reached their reactive capability limit. Relief small island loading and/or restore more loading in the larger island could be a way to mitigate the problem by pre-determine the loading profile of both islands.
22 Peak Current (pu) 7. Other Problems Caused? III. Bypass Transients due to Q Imbalance Bypass transients is over the acceptable level at all impedance values when V = 0.2pu in the worst case. Recommendations: Adjust AVR settings to match the Q of local loads. (Voltage following mode for DGs) Run load flow first to pre-determine a load profile for both micro-grid and system so that generators will not go beyond its Qmax & Qmin Synchronizing Curve V 20%, 30 o Analytical Simulation Reference Line Bypass Curve V 20%, f 0.25Hz Optimal Z = ohm Inserted Impedance (ohm)
23 8. Advantages of Impedance Based Synchronization Idea of impedance insertion can mitigate the synchronizing transients from synchronization. If the busses of islands are inside the practical range of V and f, then open loop synchronization without feedback control can be implemented with impedance preinsertion. This approach eliminates the need for a feedback control of generators. It is beneficial in the following ways: No need to build a communication line when DG is far away from the switchyard. Improves reliability in the case of power outage. No need to spend the time to tune/control the DGs if bus V and f are in the practical range. Faster synchronization process results in faster system restoration.
24 9. Future work: Impedance based synchronization method shall be investigated between system to system. In the system to system synchronization scenario, can one determine the size of impedance still by the analytical approach? If so, is there a way to simplify or reducing the networks in a way to easily find the impedance?
25
26 Open Loop Micro-grid to System Synchronization Based on Pre-Insertion Impedance Method (Final Version) By Peter Zhou University of Alberta Jan 30 th, 2015
27 Outline 1. Synchronization Concerns 2. Current Practice for Performing Synchronization 3. Synchronization Issues 4. New Idea --- Open Loop Synchronization 5. Research Strategy 6. Solutions 7. Conclusions 8. Future Works
28 1. Synchronization Concerns Synchronization in simple terms is a process of connecting an electrical island to another. The electrical island can be a generator, a micro-grid, or part of a large power grid. There are 3 synchronization scenarios to consider: Generator synchronizes to system Micro-grid synchronizes to system System synchronizes to another system
29 1. Synchronization Concerns Synchronization without any control may result in damage of generator and prime mover due to High Synchronizing Transient Current generator out of synchronism with system How to deal with them? Challenge
30 2. Current Practice for Performing Synchronization Adjust the voltage phasor difference across the breaker into an acceptable range during synchronization process through feedback. V ΔV --- difference of voltage magnitude Δθ --- difference of voltage phase angle Δf --- difference of frequency (IEEE criteria) Limit Transient Current Limit Torque deviation I peak V Z eq Ensure stability
31 2. Current Practice for Performing Synchronization Feedback Control Generator to System: System ~ Generator Multi-DG Feedback Controls ~ Micro-grid to System: System Micro-grid ~ ~ System to System: The synchronization process can become complicated. Require sophisticated coordination and tuning of generators on both sides.
32 3. Synchronization Issues Micro-grid Bulk Grid Sync Panel 25 ~ Synchronizing Control Communication Link Issues: A costly communication link must be build when a DG is far away from PCC. Feedback control is not reliable in the extreme case of power outage. Feedback control may need an inacceptable long time to tune the generators, when system restoration at emergency is required.
33 4. New Idea --- Open Loop Synchronization New Idea: Using an impedance pre-insertion to reduce the transients effects from synchronization instead of adjusting V through feedback. I peak V V Z eq Z insert +X d +X t +X eq The impedance is designed to meet the synchronization requirement, based on a pre-defined voltage and frequency range of the islands to be synchronized together, such that the open loop synchronization can be achieved. Z IEEE or utility criteria synchronization requirements Ipeak, ΔTe must remain the same level Circuit Breaker fg ( Hz) 60.2 Generator, Microgrid 1 2 Bulk Grid ( Hz) 0.9 Pre-established Pre-established Vg ( pu) Operating Region Operating Region fs Vs ( pu) 59.7
34 4. New Idea --- Open Loop Synchronization Feedback Control System ~ No Watch V, θ, f Meet Criteria for V, f? Yes Watch θ θ<criteria? Generator Yes Close Synchronizing Breaker No Close Loop Feedback Z Circuit Breaker fg ( Hz) 60.2 Generator, Microgrid Bulk Grid 0.9 Pre-established Pre-established Vg ( pu) Operating Region Operating Region fs ( Hz) Vs ( pu) Each party operates within preestablished operating region (i.e. power quality limits) Verify if V and f are within the region at the breaker location Yes Watch θ θ<criteria? Yes Close Synchronizing Breaker No Open Loop No Bypass Impedance Can t perform Synchronization
35 5. Research Strategies Problems What is the acceptable transient level? Strategies Use IEEE C50.12 criteria for generator synchronization to establish acceptable transients level. How to select the impedance to control switching transient? Use common utility operating limits for voltage and frequency to establish open loop criteria. Is the impedance bypass transient acceptable? Evaluate the bypass transients to establish the number of steps or impedance values for bypassing operation Can the generator reach stable condition? Establish a method or criterion to determine the impact on stability
36 Electromagnetic Torque Te (pu) Stator Current (pu) 6. Solutions Acceptable transient level According to IEEE standards C50.12 and C50.13, the synchronization criteria for both cylindrical and salient-pole synchronous generators are: Angle ±10 ; Voltage 0 to 5 %; Slip ±0.067Hz Current and torque transients experienced by a generator under the above condition is considered acceptable. Therefore, the limits on transients can be established by determining the maximum transient under the above conditions For example, simulation study reveals (Based on C50.12 standards): I peak =0.537 pu for stator current transient T e =Te max Te ss = =0.572pu Time (s) Time (s)
37 6. Solutions Impedance selection Each party is expected to operate within established limits that meet the power quality requirements of respective systems, as illustrated below: V min ~V max (pu) f min ~f max (Hz) Micro-grid (bus 1) 0.9~ ~60.2 System (bus 2) 0.9~ ~60.05 Generator, Microgrid 1 2 Bulk Grid Limit on Δθ: θ is monitored at the synchronization point. The limit on θ is selected to be the same as that use for close-loop synchronization, which is 10 degrees difference. Objective of Impedance Selection: Find minimal Z that leads to acceptable transients levels (inrush current and torque limits) under above synchronizing conditions.
38 6. Solutions Impedance selection Research Method for Impedance Selection: Step 1. Determine all possible worst case synchronization scenarios based on pre-established power quality limits of the two parties. Step 2. Evaluate the worst case transients (Torque and Current) resulting from synchronization scenarios above. Step 3. Design an impedance value for insertion such that the highest transient is within the acceptable level.
39 6. Solutions Impedance selection Research Method Step 1 (Worst case synchronization scenarios): Ideally, synchronization wants to take place when V1=V2, θ1=θ2, f1=f2, two parties will synchronize with perfect parallelization with no switching transients and no system disturbances at all. Case 1 represents the reference case for acceptable transients. Possible worst case synchronizations will take place in following cases 2-5 shown in Table 1, which the operating points of both parties deviate the most from normal operation (1pu, 60Hz), and synchronize at a maximum allowable voltage and frequency differences. 0.9pu f Hz Hz 3 1.1pu V 1 0.9pu f Hz Hz 1.1pu V 2 Table 1: Synchronization Scenarios V1 (pu) V2 (pu) f1 (Hz) f2 (Hz) θ=θ1-θ2 (deg) case case case case case
40 Torque and Current Deviation (pu) 6. Solutions Impedance selection Research Method Step 2 (Worst case transients evaluation): System under study: SUB V2,f2 CB V1,f1 15 miles 15 miles 25/4.16kV Yg/Yg SG 6.6MVA 25kV 346MVA 2.0MW 0.65MVAr Assumptions: micro-grid is operating at near full load as a worst case. Worst transient case: Highest current and torque transient is located in case MW 0.65MVAr MW 0.65MVAr case1 case2 case3 case4 case5 case Te Ipeak Fig: Torque and current peak deviations when not controlled by impedance insertion.
41 6. Solutions Impedance selection Research Method Step 3 (Impedance Design Procedure to Reduce Worst Case Current Transient): Case Study File (reference case) Case Study File (worst case) Establish V1,V2,f1,f2 and θ across open breaker (Initialize by loadflow) Calculation Acceptable transient level (I & Te) Establish V1,V2,f1,f2 and θ across open breaker (Initialize by loadflow) Calculation Z f ( I, V, V, f, f, ) acceptable Impedance Z is determined by analytical solution. The accuracy of the analytical solution is verified by numerous transient simulations.
42 6. Solutions Impedance selection Analytical method for determination of Impedance Z Superposition Across Breaker Micro-grid Generators Bulk Grid Following analytical equations were derived based on the transient circuit of superposition: For simplicity, assuming f1=f2 (same frequency) VA IsyncA( t) sin( wt A ) sin( A ) e Z eq VB IsyncB ( t) sin( wt B ) sin( B ) e Z eq VC IsyncC ( t) sin( wt C ) sin( C ) e Z Where: eq V V V V V A B c 1 tan ( wl / R) 1 2 A ( V1 V2) Rt/ L Rt/ L Rt/ L V1, f1 V2, f2 Z eq is the total equivalent series impedance seen by the breaker. Z insertion is determined by subtracting all other system equivalent impedances such as transformer, line, and generator sub-transient reactance. Z f ( I, V, V, ) insertion acceptable 1 2
43 Stator Current (pu) Stator Current Deviation (pu) Torque and Current Deviation (pu) 6. Solutions Impedance selection Analytical & Simulation results for determination of Impedance Z Analytical solution results in a Z insertion value of 0.23 pu (21.8 ohm). Analytical current waveform is closely matched to the simulation within the first cycle after breaker is closed. With this designed impedance, both current and torque transient disturbances are within the reference level that comply with IEEE synchronization criteria Z=0.23pu Simulation (case 2) Analytical (case 2) Reference case Z Insertion=0.23pu Impedance Insertion Value (pu) Phase A (simulation) Phase A (Analytical) Time (s) case1 case2 case3 case4 case5 Te Ipeak Fig: Torque and current peak deviations when controlled by a designed impedance insertion. Note: cases 4 and 5 have relatively lower excitation compare to 2 and 3, therefore the P-δ transient curve is lower so the power and torque transient swing is smaller.
44 7. Bypass Transients Impedance bypass is done after the system has reached to a new steady-state. The process of bypass also produces current and torque transients. These transients must not exceed the allowable limits as well. Method adopted to evaluate the bypass transient is shown below. Bypass Transient Evaluation Method: 1. Evaluate the steady state real and reactive power imbalance between the two parties after synchronization, when both parties synchronizes within the operating limits pre-established. 2. Evaluate the worst bypass scenario based on worst resulting voltage phasor difference across the inserted impedance V, since I bypass V. 3. Determine and verify that whether if the worst bypass transient is below the allowable limit.
45 Reactive Power Imbalance (pu) 7. Bypass Transients Evaluation Step 1 (Evaluate Steady state P&Q Imbalance): Real and reactive power imbalance is mainly due to a frequency difference and voltage magnitude difference prior to synchronization. ( f P m, V Q) The real and reactive power imbalance will incur a current flowing through the impedance, and therefore incur a voltage drop across the impedance. Therefore, it is true that higher the power imbalances, the higher the voltage across the impedance and hence, the higher the bypass transient Z=0.23pu Segment 1-3 and 2-4 is obtained by fixing V1 and V2 but vary f1 ( ) and f2 ( ) Segment 1-2 and 3-4 is obtained by fixing f1 and f2 but vary V1 ( ) and V2 ( ) Active Power Imbalance (pu)
46 Reactive Power Imbalance (pu) 7. Bypass Transients Evaluation Step 2 (Evaluate worst bypass scenario): Since the V across the impedance is dependent on S = P 2 + Q 2, worst bypass scenarios can be evaluated by the worst power imbalances shown by 4 cases in the figure. V = Z I = Z (S/V1), with V1 1pu, V is proportional to both the impedance size Z and the power imbalance S. Based on figure below, there are 4 possible cases where the bypass transient are the highest Z=0.23pu Active Power Imbalance (pu)
47 Reactive Power Imbalance (pu) 7. Bypass Transients Evaluation Step 2 (Evaluate worst bypass scenario): Z=0.23pu V1 (pu) V2 (pu) f1 (Hz) f2 (Hz) Case Case Case Case Active Power Imbalance (pu) BRK2 Impedance Switching (BRK1 Closes) Micro-grid Generators V Z Insertion BRK1 1 1 V2 2 Bulk Grid Determine largest voltage difference across impedance ( V) (by power flow) Real Power (pu) Reactive Power (pu) S (pu) V over Z (pu) Case Case Case Case Worst bypass scenario is Case 1
48 Electric Torque Te (pu) Stator Current (pu) 7. Bypass Transients Evaluation Step 3 (Verify worst case bypass transient is within allowable limits): Time (s) Impedance switching Impedance switching Impedance bypass Impedance bypass Time (s) Impedance is bypassed at a worst bypass scenario according to case 1 conditions. Bypass transients (current and torque) is no more severe than the allowable limits in the worst case, in fact, it is quite small due to a small voltage drop across the impedance. After the bypass, the stator current is over 1 per unit, which suggests a machine overloading primarily due to the reactive power imbalance. This is more of a power quality concern and a secondary concern if no sensitive equipment are damaged.
49 8. Transient Stability Assessment Transient stability is the ability of the power system to maintain in synchronism when subjected to a transient disturbance, in this case, micro-grid to system synchronization. In the proposed open loop synchronization approach, there are 2 expected switching (disturbances) to the power system, one is the first impedance switching, and the second is the impedance bypass switching. Both disturbances must remain in rotor angle stable, therefore, will be assessed individually by examining their maximum rotor angle deviation δ_max. Transient Stability Assessment Impedance Switching Bypass Switching Worst case δ_max deviation based on power quality limits of open loop synchronization scheme? Using Equal Area criterion for transient stability assessment of bypass operation Sensitivity Study to show the impact of different loading levels and machine inertia values on δ_max
50 8. Transient Stability Assessment Method to analyze Micro-grid to System Synchronization phenomenon: For the impedance switching, it is important to realize that there is no power transfer between the micro-grid to system prior to breaker closes. After breaker is closed, although steady state active power transfer is non-zero due to the governor droop setting of the machine, but in the transient time period, Pe steady state can be assumed to be zero. In other words, Pm=Pe ss =0. At the instant when breaker is closed, the transient Pmax is determined by Vth, Vsys, and Zeq seen across breaker (assume loads are modelled as constant impedance). Sudden loading of the micro-grid generator is determined by the instant loading angle, which is the instantaneous angle difference when breaker is closed. The rotor angle and rotor speed behaviors due to the impact of impedance switching can be best explained by the Equation of Motion or the Swing Equation. Micro-grid can be best viewed as an Equivalent Machine through the reduction of Thevenin equivalence. Micro-grid Impedance Switching V Z th th System Equivalent Machine Pe 0 V sys sys
51 Rotor Deviation Power Transfer Pe Rotor Frequency (Hz) 8. Transient Stability Assessment Impedance Switching Impact on Transient Stability (Power Angle Relationship): 2H d 2 δ(t) ω syn dt 2 = P mp.u P ep.u H ω syn dδ dt 2 δmax δ max = (P δ mp.u P ep.u )dδ 0 δ 0 δ max = cos 1 cos(δ o ) H W syn 2π f gen f sys 2 X th + X insert + X sys V th V s max o P max Vth V X eq sys Wr Wsyn Begin Synchronization (Breaker closed) In practice,due to dynamics of field and damping winding, the electromechanical oscillation is damped and stabilized Rotor angle starts increasing due to higher micro-grid frequency than system frequency Time (s) o o max min o Initial Angle difference at across breaker ss Power Angle (deg) max min min Time (s)
52 δ max (deg) 8. Transient Stability Assessment Worst case δ_max due to Impedance Switching (with constant Ef): 4 cases are worth to consider to investigate the worst case δ based on power quality limits. Cases F1 (Micro-grid Frequency) Hz F2 (System Frequency) Hz V1 (pu) V2 (pu) θ=θ 1 θ 2 (Deg) Worst case With Constant Ef case1 case2 case3 case4 Fig: Impedance used equals 0.23pu, with Micro-grid loading level= 85%. Maximum δ occurs in cases 3 and 4 are primarily due to an initial large speed deviation between the Micro-grid to system. Cases 3 and 4 have a larger first swing because f= Hz, which the speed differential represents the initial kinetic energy offset in the rotor.
53 δ max (deg) 8. Transient Stability Assessment Worst case δ_max due to Impedance Switching (with Excitation control AVR): 3 cases are worth to consider to investigate the worst case δ based on power quality limits and AVR control Cases 27.8 F1 (Micro-grid Frequency) Hz F2 (System Frequency) Hz V1 (pu) V2 (pu) θ=θ 1 θ 2 (Deg) case1 case2 case3 δ max (const Ef) δ max (AVR) 36.4 Fig: Impedance used equals 0.23pu, with Micro-grid loading level= 85%. Worst case As can be seen from figure, with the addition of AVR excitation control, during transient, it can either help or aggravate the rotor angle advancement depending on the relative magnitude of system voltage. IEEE type 1 exciter and voltage regulator is implemented. In case 3, rotor advancement increases due to AVR is because although system voltage is on the higher end (1.1pu), but the AVR lowers the field voltage set point automatically due to an injecting Q from the system. Worst case With AVR
54 Max transient Rotor Deviation (deg) Max Transient Rotor Angle Deviation (Deg) 8. Transient Stability Assessment Sensitivity study of Micro-grid Loading level and Machine Inertia effects on δ_max: Z=0.23pu Z=0.3pu Z=0.4pu H=1.26 H=2.52 H= % 20% 30% 40% 50% 60% 70% 80% Percentage Loading of Micro-grid Fig: Loading effects for case3 synchronizing condition with AVR control The mechanical Pm of the machine increases as the loading of the Micro-grid increases. With AVR controlling the Q out of the machine by adjusting the field voltage, in case 3, maximum power transfer capability decreases after impedance switching due to a Q flow from the system side. As a result, the steady state Load angle of the machine increases, which also affects the transient rotor angle deviation due to AVR % 20% 30% 40% 50% 60% 70% 80% Percentage of Micro-grid Loading Level Fig: Sensitivity Study of the effect of Machine Inertia (H) on transient stability, Z=0.23pu, case 3 Effect of H can be explained through the fundamental equation of motion. For a 3-phase to ground terminal fault, H can improve stability by reducing the amount of rotor advancement when rotor is accelerating. However, for synchronization, higher H may aggravate the rotor advancement primarily due to the initial kinetic energy stored within the rotor due to f across breaker. Thus, for small inertia machines within the micro-grid, the machine will most likely to be stable for all loading levels if synchronized within the power quality limits.
55 Rotor Angle (Deg) Power Transfer Pe 8. Transient Stability Assessment Impedance Bypass Impacts on Transient Stability: Micro-grid V Z th th Bypass Switching System Pe ss Pmax increased due to a decreased in Zeq Equivalent Machine Pe ss V sys sys Power Angle (deg) Bypass Impedance can be seen as a way to improve the system stability by increasing maximum power transfer. Bypass operation should be always rotor angle stable since the steady state Pe is close to zero before the bypass. In addition, the δ max for bypass is considered a much smaller disturbance than the first switching due to δ o 10 and f= Impedance Switching Bypass Time (s)
56 9. Conclusion Open loop synchronization is based on pre-defined power quality limits can be implemented with an impedance insertion at the PCC to limit the inrush current within an acceptable level. In practice, voltage levels of either the Micro-grid or the system should meet the voltage and frequency range requirements as defined by the power quality protocol at all times. Synchronization transient current and torque disturbances are quite similar to that of a short circuit/fault problem, which can be analyzed with similar procedure. Transient stability analysis of Micro-grid to system synchronization problem may be analyzed using the Equal Area Criterion and the Equation of Motion by an analogy to single machine to infinite bus case. As a general finding, loading levels of the Micro-grid have negligible effects on the transient current and torque due to synchronization. A properly designed impedance can limit the worst case transient inrush current without incurring a significant impact on the transient stability (rotor deviation).
Open Loop Synchronization of Micro-grid to System Based on Impedance Pre-insertion
First Version Open Loop Synchronization of Micro-grid to System Based on Impedance Pre-insertion First A. Author, Fellow, IEEE, Second B. Author, and Third C. Author, Jr., Member, IEEE Abstract This paper
More informationGenerators. What its all about
Generators What its all about How do we make a generator? Synchronous Operation Rotor Magnetic Field Stator Magnetic Field Forces and Magnetic Fields Force Between Fields Motoring Generators & motors are
More informationSCHOOL OF ELECTRICAL, MECHANICAL AND MECHATRONIC SYSTEMS. Transient Stability LECTURE NOTES SPRING SEMESTER, 2008
SCHOOL OF ELECTRICAL, MECHANICAL AND MECHATRONIC SYSTEMS LECTURE NOTES Transient Stability SPRING SEMESTER, 008 October 7, 008 Transient Stability Transient stability refers to the ability of a synchronous
More informationChapter 9: Transient Stability
Chapter 9: Transient Stability 9.1 Introduction The first electric power system was a dc system built by Edison in 1882. The subsequent power systems that were constructed in the late 19 th century were
More informationPOWER SYSTEM STABILITY
LESSON SUMMARY-1:- POWER SYSTEM STABILITY 1. Introduction 2. Classification of Power System Stability 3. Dynamic Equation of Synchronous Machine Power system stability involves the study of the dynamics
More informationECE 585 Power System Stability
Homework 1, Due on January 29 ECE 585 Power System Stability Consider the power system below. The network frequency is 60 Hz. At the pre-fault steady state (a) the power generated by the machine is 400
More information7. Transient stability
1 7. Transient stability In AC power system, each generator is to keep phase relationship according to the relevant power flow, i.e. for a certain reactance X, the both terminal voltages V1and V2, and
More informationB.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis
B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester Electrical and Electronics Engineering EE 1352 Power System Analysis (Regulation 2008) Time: Three hours Answer all questions Part A (10
More informationTransient Stability Assessment of Synchronous Generator in Power System with High-Penetration Photovoltaics (Part 2)
Journal of Mechanics Engineering and Automation 5 (2015) 401-406 doi: 10.17265/2159-5275/2015.07.003 D DAVID PUBLISHING Transient Stability Assessment of Synchronous Generator in Power System with High-Penetration
More informationYou know for EE 303 that electrical speed for a generator equals the mechanical speed times the number of poles, per eq. (1).
Stability 1 1. Introduction We now begin Chapter 14.1 in your text. Our previous work in this course has focused on analysis of currents during faulted conditions in order to design protective systems
More informationINSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous)
INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad - 500 043 ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK Course Name : Computer Methods in Power Systems Course Code : A60222
More informationExamples of Applications of Potential Functions in Problem Solving (Web Appendix to the Paper)
Examples of Applications of otential Functions in roblem Solving (Web Appendix to the aper) Ali Mehrizi-Sani and Reza Iravani May 5, 2010 1 Introduction otential functions may be exploited to formulate
More informationPower System Stability GENERATOR CONTROL AND PROTECTION
Power System Stability Outline Basis for Steady-State Stability Transient Stability Effect of Excitation System on Stability Small Signal Stability Power System Stabilizers Speed Based Integral of Accelerating
More informationPower System Stability and Control. Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India
Power System Stability and Control Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India Contents Chapter 1 Introduction to Power System Stability
More informationReliability of Bulk Power Systems (cont d)
Reliability of Bulk Power Systems (cont d) Important requirements of a reliable electric power service Voltage and frequency must be held within close tolerances Synchronous generators must be kept running
More informationLESSON 20 ALTERNATOR OPERATION OF SYNCHRONOUS MACHINES
ET 332b Ac Motors, Generators and Power Systems LESSON 20 ALTERNATOR OPERATION OF SYNCHRONOUS MACHINES 1 LEARNING OBJECTIVES After this presentation you will be able to: Interpret alternator phasor diagrams
More informationDynamic simulation of a five-bus system
ELEC0047 - Power system dynamics, control and stability Dynamic simulation of a five-bus system Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct November 2017 1 / 16 System modelling
More informationChapter 3 AUTOMATIC VOLTAGE CONTROL
Chapter 3 AUTOMATIC VOLTAGE CONTROL . INTRODUCTION TO EXCITATION SYSTEM The basic function of an excitation system is to provide direct current to the field winding of the synchronous generator. The excitation
More informationEE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION
EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION PART: A 1. Define per unit value of an electrical quantity. Write equation for base impedance with respect to 3-phase system. 2. What is bus admittance
More informationQUESTION BANK ENGINEERS ACADEMY. Power Systems Power System Stability 1
ower ystems ower ystem tability QUETION BANK. A cylindrical rotor generator delivers 0.5 pu power in the steady-state to an infinite bus through a transmission line of reactance 0.5 pu. The generator no-load
More informationDynamics of the synchronous machine
ELEC0047 - Power system dynamics, control and stability Dynamics of the synchronous machine Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct October 2018 1 / 38 Time constants and
More informationEE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A
EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A 1. What are the advantages of an inter connected system? The advantages of an inter-connected system are
More informationKINGS COLLEGE OF ENGINEERING Punalkulam
KINGS COLLEGE OF ENGINEERING Punalkulam 613 303 DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING POWER SYSTEM ANALYSIS QUESTION BANK UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A (TWO MARK
More informationA. P. Sakis Meliopoulos and George J. Cokkinides Power System Relaying, Theory and Applications. Chapter 8 2 Generator Protection 2
DRAFT and INCOMPLETE Table of Contents from A. P. Sakis Meliopoulos and George J. Cokkinides Power System Relaying, Theory and Applications Chapter 8 Generator Protection 8. Introduction 8. Generator Protection
More informationDYNAMIC RESPONSE OF A GROUP OF SYNCHRONOUS GENERATORS FOLLOWING DISTURBANCES IN DISTRIBUTION GRID
Engineering Review Vol. 36 Issue 2 8-86 206. 8 DYNAMIC RESPONSE OF A GROUP OF SYNCHRONOUS GENERATORS FOLLOWING DISTURBANCES IN DISTRIBUTION GRID Samir Avdaković * Alija Jusić 2 BiH Electrical Utility Company
More informationEE 451 Power System Stability
EE 451 Power System Stability Power system operates in synchronous mode Power system is subjected to a wide range of disturbances (small and large) - Loads and generation changes - Network changes - Faults
More informationEVALUATION OF THE IMPACT OF POWER SECTOR REFORM ON THE NIGERIA POWER SYSTEM TRANSIENT STABILITY
EVALUATION OF THE IMPACT OF POWER SECTOR REFORM ON THE NIGERIA POWER SYSTEM TRANSIENT STABILITY F. I. Izuegbunam * Department of Electrical & Electronic Engineering, Federal University of Technology, Imo
More informationFinal Exam, Second Semester: 2015/2016 Electrical Engineering Department
Philadelphia University Faculty of Engineering Student Name Student No: Serial No Final Exam, Second Semester: 2015/2016 Electrical Engineering Department Course Title: Power II Date: 21 st June 2016 Course
More informationECE 325 Electric Energy System Components 7- Synchronous Machines. Instructor: Kai Sun Fall 2015
ECE 325 Electric Energy System Components 7- Synchronous Machines Instructor: Kai Sun Fall 2015 1 Content (Materials are from Chapters 16-17) Synchronous Generators Synchronous Motors 2 Synchronous Generators
More information1 Unified Power Flow Controller (UPFC)
Power flow control with UPFC Rusejla Sadikovic Internal report 1 Unified Power Flow Controller (UPFC) The UPFC can provide simultaneous control of all basic power system parameters ( transmission voltage,
More informationBehaviour of synchronous machine during a short-circuit (a simple example of electromagnetic transients)
ELEC0047 - Power system dynamics, control and stability (a simple example of electromagnetic transients) Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct October 2018 1 / 25 Objectives
More informationCHAPTER 3 MATHEMATICAL MODELING OF HYDEL AND STEAM POWER SYSTEMS CONSIDERING GT DYNAMICS
28 CHAPTER 3 MATHEMATICAL MODELING OF HYDEL AND STEAM POWER SYSTEMS CONSIDERING GT DYNAMICS 3.1 INTRODUCTION This chapter focuses on the mathematical state space modeling of all configurations involved
More informationLesson 17: Synchronous Machines
Lesson 17: Synchronous Machines ET 332b Ac Motors, Generators and Power Systems Lesson 17_et332b.pptx 1 Learning Objectives After this presentation you will be able to: Explain how synchronous machines
More informationSSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL
1 SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL Power Systems: Generation, Transmission and Distribution Power Systems: Generation, Transmission and Distribution Power Systems:
More informationComparative Study of Synchronous Machine, Model 1.0 and Model 1.1 in Transient Stability Studies with and without PSS
Comparative Study of Synchronous Machine, Model 1.0 and Model 1.1 in Transient Stability Studies with and without PSS Abhijit N Morab, Abhishek P Jinde, Jayakrishna Narra, Omkar Kokane Guide: Kiran R Patil
More informationTorques 1.0 Two torques We have written the swing equation where speed is in rad/sec as:
Torques 1.0 Two torques We have written the swing equation where speed is in rad/sec as: 2H Re ( t) T au T mu T eu (1) and when speed is in per-unit as 2H u ( t) Tau Tmu Teu (2) We note that in both cases
More informationAutomatic Generation Control. Meth Bandara and Hassan Oukacha
Automatic Generation Control Meth Bandara and Hassan Oukacha EE194 Advanced Controls Theory February 25, 2013 Outline Introduction System Modeling Single Generator AGC Going Forward Conclusion Introduction
More informationDynamic Modeling of GE 1.5 and 3.6 Wind Turbine-Generators
GE Power Systems Dynamic Modeling of GE.5 and 3.6 Wind Turbine-Generators Prepared by: Nicholas W. Miller William W. Price Juan J. Sanchez-Gasca October 27, 2003 Version 3.0 GE-Power Systems Energy Consulting
More informationPredicting, controlling and damping inter-area mode oscillations in Power Systems including Wind Parks
3rd IASME/WSEAS Int. Conf. on Energy & Environment, University of Cambridge, UK, February 3-5, 008 Predicting, controlling and damping inter-area mode oscillations in Power Systems including Wind Parks
More informationA Computer Application for Power System Control Studies
A Computer Application for Power System Control Studies Dinis C. A. Bucho Student nº55262 of Instituto Superior Técnico Technical University of Lisbon Lisbon, Portugal Abstract - This thesis presents studies
More informationDesign of PSS and SVC Controller Using PSO Algorithm to Enhancing Power System Stability
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 10, Issue 2 Ver. II (Mar Apr. 2015), PP 01-09 www.iosrjournals.org Design of PSS and SVC Controller
More informationThe synchronous machine (detailed model)
ELEC0029 - Electric Power System Analysis The synchronous machine (detailed model) Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct February 2018 1 / 6 Objectives The synchronous
More informationDynamic Voltage Stability Enhancement of a Microgrid with Static and Dynamic Loads Using Microgrid Voltage Stabilizer
Dynamic Voltage Stability Enhancement of a Microgrid with Static and Dynamic Loads Using Microgrid Voltage Stabilizer Kenan Hatipoglu 1, Ismail Fidan 2, Ghadir Radman 3 1 Electrical and Computer Engineering
More informationPARAMETRIC ANALYSIS OF SHAFT TORQUE ESTIMATOR BASED ON OBSERVER
PARAMETRIC ANALYSIS OF SHAFT TORQUE ESTIMATOR BASED ON OBSERVER Tetsuro Kakinoki, Ryuichi Yokoyama Tokyo Metropolitan University t.kakinoki@h4.dion.ne.jp Goro Fujita Shibaura Institute of Technology Kaoru
More informationECE 422/522 Power System Operations & Planning/Power Systems Analysis II : 7 - Transient Stability
ECE 4/5 Power System Operations & Planning/Power Systems Analysis II : 7 - Transient Stability Spring 014 Instructor: Kai Sun 1 Transient Stability The ability of the power system to maintain synchronism
More informationTransient Stability Analysis with PowerWorld Simulator
Transient Stability Analysis with PowerWorld Simulator T1: Transient Stability Overview, Models and Relationships 2001 South First Street Champaign, Illinois 61820 +1 (217) 384.6330 support@powerworld.com
More informationEE 742 Chapter 3: Power System in the Steady State. Y. Baghzouz
EE 742 Chapter 3: Power System in the Steady State Y. Baghzouz Transmission Line Model Distributed Parameter Model: Terminal Voltage/Current Relations: Characteristic impedance: Propagation constant: π
More informationTransient Stability Analysis of Single Machine Infinite Bus System by Numerical Methods
International Journal of Electrical and Electronics Research ISSN 348-6988 (online) Vol., Issue 3, pp: (58-66), Month: July - September 04, Available at: www.researchpublish.com Transient Stability Analysis
More informationECEN 667 Power System Stability Lecture 20: Oscillations, Small Signal Stability Analysis
ECEN 667 Power System Stability Lecture 20: Oscillations, Small Signal Stability Analysis Prof. Tom Overbye Dept. of Electrical and Computer Engineering Texas A&M University, overbye@tamu.edu 1 Announcements
More informationModule 3 : Sequence Components and Fault Analysis
Module 3 : Sequence Components and Fault Analysis Lecture 12 : Sequence Modeling of Power Apparatus Objectives In this lecture we will discuss Per unit calculation and its advantages. Modeling aspects
More informationEE2351 POWER SYSTEM ANALYSIS
EE351 POWER SYSTEM ANALYSIS A.Ahamed Riazudeen EEE DEPARTMENT 1 UNIT I INTRODUCTION Power system network 3 SINGLE LINE DIAGRAM It is a diagrammatic representation of a power system in which the components
More information11.1 Power System Stability Overview
11.1 Power System Stability Overview This introductory section provides a general description of the power system stability phenomena including fundamental concepts, classification, and definition of associated
More informationCahier Technique N 13 Principe de réduction des courants d enclenchement des transformateurs
Cahier Technique N 13 Principe de réduction des courants d enclenchement des transformateurs Numerical transformer inrush current minimizer Principle of the operation Rev 1.0 Document version information
More informationDynamic Behavior of Three phase Inductions Motors as Loads in an Electric Power System with Distributed Generation, a Case of Study.
Dynamic Behavior of Three phase Inductions Motors as Loads in an Electric Power System with Distributed Generation, a Case of Study. Marcelo Rodrigo García Saquicela, Ernesto Ruppert Filho, José Luis Azcue
More informationMathematical Modeling and Dynamic Simulation of a Class of Drive Systems with Permanent Magnet Synchronous Motors
Applied and Computational Mechanics 3 (2009) 331 338 Mathematical Modeling and Dynamic Simulation of a Class of Drive Systems with Permanent Magnet Synchronous Motors M. Mikhov a, a Faculty of Automatics,
More informationElectromagnetic Oscillations and Alternating Current. 1. Electromagnetic oscillations and LC circuit 2. Alternating Current 3.
Electromagnetic Oscillations and Alternating Current 1. Electromagnetic oscillations and LC circuit 2. Alternating Current 3. RLC circuit in AC 1 RL and RC circuits RL RC Charging Discharging I = emf R
More informationModule 6 : Preventive, Emergency and Restorative Control. Lecture 27 : Normal and Alert State in a Power System. Objectives
Module 6 : Preventive, Emergency and Restorative Control Lecture 27 : Normal and Alert State in a Power System Objectives In this lecture you will learn the following Different states in a power system
More informationIntroduction to Synchronous. Machines. Kevin Gaughan
Introduction to Synchronous Machines Kevin Gaughan The Synchronous Machine An AC machine (generator or motor) with a stator winding (usually 3 phase) generating a rotating magnetic field and a rotor carrying
More informationFrom now, we ignore the superbar - with variables in per unit. ψ ψ. l ad ad ad ψ. ψ ψ ψ
From now, we ignore the superbar - with variables in per unit. ψ 0 L0 i0 ψ L + L L L i d l ad ad ad d ψ F Lad LF MR if = ψ D Lad MR LD id ψ q Ll + Laq L aq i q ψ Q Laq LQ iq 41 Equivalent Circuits for
More informationANALYSIS OF SUBSYNCHRONOUS RESONANCE EFFECT IN SERIES COMPENSATED LINE WITH BOOSTER TRANSFORMER
ANALYSIS OF SUBSYNCHRONOUS RESONANCE EFFECT IN SERIES COMPENSATED LINE WITH BOOSTER TRANSFORMER G.V.RAJASEKHAR, 2 GVSSNS SARMA,2 Department of Electrical Engineering, Aurora Engineering College, Hyderabad,
More informationSECTION 7: FAULT ANALYSIS. ESE 470 Energy Distribution Systems
SECTION 7: FAULT ANALYSIS ESE 470 Energy Distribution Systems 2 Introduction Power System Faults 3 Faults in three-phase power systems are short circuits Line-to-ground Line-to-line Result in the flow
More informationCHAPTER 5 SIMULATION AND TEST SETUP FOR FAULT ANALYSIS
47 CHAPTER 5 SIMULATION AND TEST SETUP FOR FAULT ANALYSIS 5.1 INTRODUCTION This chapter describes the simulation model and experimental set up used for the fault analysis. For the simulation set up, the
More informationPower System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur
Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur Lecture - 9 Transmission Line Steady State Operation Welcome to lesson 9, in Power
More informationControl of Wind Turbine Generators. James Cale Guest Lecturer EE 566, Fall Semester 2014 Colorado State University
Control of Wind Turbine Generators James Cale Guest Lecturer EE 566, Fall Semester 2014 Colorado State University Review from Day 1 Review Last time, we started with basic concepts from physics such as
More informationFault Calculation Methods
ELEC9713 Industrial and Commercial Power Systems Fault Calculation Methods There are two major problems that can occur in electrical systems: these are open circuits and short circuits. Of the two, the
More informationIEEE PES Task Force on Benchmark Systems for Stability Controls
IEEE PES Task Force on Benchmark Systems for Stability Controls Ian Hiskens November 9, 3 Abstract This report summarizes a study of an IEEE -generator, 39-bus system. Three types of analysis were performed:
More informationQFT Framework for Robust Tuning of Power System Stabilizers
45-E-PSS-75 QFT Framework for Robust Tuning of Power System Stabilizers Seyyed Mohammad Mahdi Alavi, Roozbeh Izadi-Zamanabadi Department of Control Engineering, Aalborg University, Denmark Correspondence
More informationElectrical Machines and Energy Systems: Operating Principles (Part 2) SYED A Rizvi
Electrical Machines and Energy Systems: Operating Principles (Part 2) SYED A Rizvi AC Machines Operating Principles: Synchronous Motor In synchronous motors, the stator of the motor has a rotating magnetic
More informationSelf-Tuning Control for Synchronous Machine Stabilization
http://dx.doi.org/.5755/j.eee.2.4.2773 ELEKTRONIKA IR ELEKTROTECHNIKA, ISSN 392-25, VOL. 2, NO. 4, 25 Self-Tuning Control for Synchronous Machine Stabilization Jozef Ritonja Faculty of Electrical Engineering
More informationCHAPTER 2 MATHEMATICAL MODELLING OF AN ISOLATED HYBRID POWER SYSTEM FOR LFC AND BPC
20 CHAPTER 2 MATHEMATICAL MODELLING OF AN ISOLATED HYBRID POWER SYSTEM FOR LFC AND BPC 2.1 INTRODUCTION The technology of the hybrid power system is at an exciting stage of development. Much research effort
More informationMODELING AND SIMULATION OF ENGINE DRIVEN INDUCTION GENERATOR USING HUNTING NETWORK METHOD
MODELING AND SIMULATION OF ENGINE DRIVEN INDUCTION GENERATOR USING HUNTING NETWORK METHOD K. Ashwini 1, G. N. Sreenivas 1 and T. Giribabu 2 1 Department of Electrical and Electronics Engineering, JNTUH
More informationECEN 667 Power System Stability Lecture 18: Voltage Stability, Load Models
ECEN 667 Power System Stability Lecture 18: Voltage Stability, Load Models Prof. Tom Overbye Dept. of Electrical and Computer Engineering Texas A&M University, overbye@tamu.edu 1 Announcements Read Chapter
More informationMinimax Approximation Synthesis in PSS Design by Embedding
Minimax Approximation Synthesis in PSS Design by Embedding Gravitational Search Algorithm Dr. Akash Saxena Department of Electrical Engineering Swami Keshvanand Institute of Technology Jaipur, India Power
More informationEEE3405 ELECTRICAL ENGINEERING PRINCIPLES 2 - TEST
ATTEMPT ALL QUESTIONS (EACH QUESTION 20 Marks, FULL MAKS = 60) Given v 1 = 100 sin(100πt+π/6) (i) Find the MS, period and the frequency of v 1 (ii) If v 2 =75sin(100πt-π/10) find V 1, V 2, 2V 1 -V 2 (phasor)
More informationIJSER. 1. Introduction
International Journal of Scientific & Engineering Research, Volume 7, Issue 5, May-2016 1543 Transient Stability Analysis of Generation and Transmission system of a thermal power plant of Pakistan. Izhar
More informationEFFECTS OF EHV POWER CIRCUIT BREAKER RECLOSING ON POWER SYSTEM STABILITY
EFFECTS OF EHV POWER CIRCUIT BREAKER RECLOSING ON POWER SYSTEM STABILITY A THESIS Presented to The Faculty of the Division of Graduate Studies By U. C. Roumillat, Jr. In Partial Fulfillment of the Requirements
More informationECEN 667 Power System Stability Lecture 25: FFT, Energy Methods
ECEN 667 Power System Stability Lecture 5: FFT, Energy Methods Prof. Tom Overbye Dept. of Electrical and Computer Engineering Texas A&M University, overbye@tamu.edu 1 Announcements Read Chapter 9 Final
More informationCHAPTER 2 DYNAMIC STABILITY MODEL OF THE POWER SYSTEM
20 CHAPTER 2 DYNAMIC STABILITY MODEL OF THE POWER SYSTEM 2. GENERAL Dynamic stability of a power system is concerned with the dynamic behavior of the system under small perturbations around an operating
More informationAdaptive under frequency load shedding using synchrophasor measurement
Adaptive under load shedding using synchrophasor measurement Abstract - The imbalance between the generation and the demand is the major factor that causes instability in a power system. Conventional Under
More informationDESIGN OF POWER SYSTEM STABILIZER USING FUZZY BASED SLIDING MODE CONTROL TECHNIQUE
DESIGN OF POWER SYSTEM STABILIZER USING FUZZY BASED SLIDING MODE CONTROL TECHNIQUE LATHA.R Department of Instrumentation and Control Systems Engineering, PSG College of Technology, Coimbatore, 641004,
More informationEE Branch GATE Paper 2010
Q.1 Q.25 carry one mark each 1. The value of the quantity P, where, is equal to 0 1 e 1/e 2. Divergence of the three-dimensional radial vector field is 3 1/r 3. The period of the signal x(t) = 8 is 0.4
More informationEquivalent Circuits with Multiple Damper Windings (e.g. Round rotor Machines)
Equivalent Circuits with Multiple Damper Windings (e.g. Round rotor Machines) d axis: L fd L F - M R fd F L 1d L D - M R 1d D R fd R F e fd e F R 1d R D Subscript Notations: ( ) fd ~ field winding quantities
More informationA New Improved Method to Damp Inter-Area Oscillations in. Power Systems with SSR Mitigation and Zone Protection. Compensation
A New Improved Method to Damp Inter-Area Oscillations in Power Systems with SSR Mitigation and Zone Protection Compensation Thesis submitted for the degree of Doctor of Philosophy at the University of
More informationECE 422/522 Power System Operations & Planning/ Power Systems Analysis II 4 Active Power and Frequency Control
ECE 422/522 Power System Operations & Planning/ Power Systems Analysis II 4 Active Power and Frequency Control Spring 2014 Instructor: Kai Sun 1 References Chapter 12 of Saadat s book Chapter 11.1 of Kundur
More informationDHANALAKSHMI SRINIVASAN COLLEGE OF ENGINEERING AND TECHNOLOGY Mamalapuram Chennai QUESTION BANK V SEMESTER. EE6501-Power system Analysis
DHANALAKSHMI SRINIVASAN COLLEGE OF ENGINEERING AND TECHNOLOGY Mamalapuram Chennai DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK V SEMESTER EE6501-Power system Analysis Regulation 2013
More informationUniversity of Jordan Faculty of Engineering & Technology Electric Power Engineering Department
University of Jordan Faculty of Engineering & Technology Electric Power Engineering Department EE471: Electrical Machines-II Tutorial # 2: 3-ph Induction Motor/Generator Question #1 A 100 hp, 60-Hz, three-phase
More informationControl Strategies for Microgrids
Control Strategies for Microgrids Ali Mehrizi-Sani Assistant Professor School of Electrical Engineering and Computer Science Washington State University Graz University of Technology Thursday, November
More informationPower system modelling under the phasor approximation
ELEC0047 - Power system dynamics, control and stability Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct October 2018 1 / 16 Electromagnetic transient vs. phasor-mode simulations
More informationAPPLICATIONS OF CONTROLLABLE SERIES CAPACITORS FOR DAMPING OF POWER SWINGS *
APPLICATIONS OF CONTROLLABLE SERIES CAPACITORS FOR DAPING OF POWER SWINGS *. Noroozian P. Halvarsson Reactive Power Compensation Division ABB Power Systems S-7 64 Västerås, Sweden Abstract This paper examines
More informationLecture 10: Grid Faults and Disturbances
/ 2 Lecture : Grid Faults and Disturbances ELEC-E842 Control of Electric Drives and Power Converters (5 ECTS) Jarno Kukkola and Marko Hinkkanen Spring 27 2 / 2 Learning Outcomes After this lecture you
More informationSynchronous Machines
Synchronous machine 1. Construction Generator Exciter View of a twopole round rotor generator and exciter. A Stator with laminated iron core C Slots with phase winding B A B Rotor with dc winding B N S
More informationTransient Behavior of
Transient Behavior of Static Fault Current Limiter in Distribution System by Shahram Najafi, Vijay K. Sood University of Ontario Institute of Technology, Oshawa, Ontario Electrical Power and Energy Conference
More informationTHE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session
Name: Student ID: Signature: THE UNIVERSITY OF NEW SOUTH WALES School of Electrical Engineering & Telecommunications FINALEXAMINATION Session 00 ELEC46 Power System Analysis TIME ALLOWED: 3 hours TOTAL
More informationThe Effects of Machine Components on Bifurcation and Chaos as Applied to Multimachine System
1 The Effects of Machine Components on Bifurcation and Chaos as Applied to Multimachine System M. M. Alomari and B. S. Rodanski University of Technology, Sydney (UTS) P.O. Box 123, Broadway NSW 2007, Australia
More informationStepping Motors. Chapter 11 L E L F L D
Chapter 11 Stepping Motors In the synchronous motor, the combination of sinusoidally distributed windings and sinusoidally time varying current produces a smoothly rotating magnetic field. We can eliminate
More informationThe synchronous machine (SM) in the power system (2) (Where does the electricity come from)?
1 The synchronous machine (SM) in the power system (2) (Where does the electricity come from)? 2 Lecture overview Synchronous machines with more than 2 magnetic poles The relation between the number of
More information(Refer Slide Time: 00:55) Friends, today we shall continue to study about the modelling of synchronous machine. (Refer Slide Time: 01:09)
(Refer Slide Time: 00:55) Power System Dynamics Prof. M. L. Kothari Department of Electrical Engineering Indian Institute of Technology, Delhi Lecture - 09 Modelling of Synchronous Machine (Contd ) Friends,
More informationUNIT-I Economic Operation of Power Systems -1
UNIT-I Economic Operation of Power Systems -1 Overview Economic Distribution of Loads between the Units of a Plant Generating Limits Economic Sharing of Loads between Different Plants Automatic Generation
More informationPOWER SYSTEM STABILITY AND CONTROL
POWER SYSTEM STABILITY AND CONTROL P. KUNDUR Vice-President, Power Engineering Powertech Labs Inc., Surrey, British Columbia Formerly Manager Analytical Methods and Specialized Studies Department Power
More informationSynchronous Machines
Synchronous Machines Synchronous Machines n 1 Φ f n 1 Φ f I f I f I f damper (run-up) winding Stator: similar to induction (asynchronous) machine ( 3 phase windings that forms a rotational circular magnetic
More information