Transient Stability Assessment of Synchronous Generator in Power System with High-Penetration Photovoltaics (Part 2)
|
|
- Sharyl Jennings
- 5 years ago
- Views:
Transcription
1 Journal of Mechanics Engineering and Automation 5 (2015) doi: / / D DAVID PUBLISHING Transient Stability Assessment of Synchronous Generator in Power System with High-Penetration Photovoltaics (Part 2) Masaki Yagami 1, Seiichiro Ishikawa 1, Yoshihiro Ichinohe 1, Kenji Misawa 1 and Junji Tamura 2 1. Department of Electrical and Electronic Engineering, Hokkaido University of Science, Sapporo , Japan 2. Department of Electrical and Electronic Engineering, Kitami Institute of Technology, Kitami , Japan Abstract: In the previous paper [1], the transient stability of synchronous generator in power system with high-penetration PV (photovoltaic) was assessed by simulation analysis of a single-machine infinite-bus system model. Through the simulation analysis, we have obtained some conclusions in terms of the impact of high-penetration PV on the stability. However, for more accurate assessment of the transient stability, it is necessary to analyze various simulation models considering many other power system conditions. This paper presents the results of the analysis for the transient stability simulation performed for IEEE 9-bus system model, in which the effects of various conditions, such as variety of power sources (inverter or rotational machine), load characteristics, existence of LVRT (low-voltage ride-through) capability and fault locations, on the transient stability are investigated. Key words: High-penetration photovoltaics, LVRT (low-voltage ride-through), synchronous generator, transient stability. 1. Introduction After the Fukushima nuclear power plant accident in Japan, the investment in the field of PV (photovoltaic) power generation has been increasing. During 2013, a total of 6.9 GW of PV was installed in Japan, 400% increase beyond the installation in the previous year (1.7 GW). Cumulative installed capacity of PV systems in 2013 reached 13.6 GW [2]. With the increasing of PV capacity in the power system, the capacity of conventional synchronous generators needs to be reduced relatively. This leads to the lower system inertia, the higher generator reactance and the fewer frequency control generators, and hence the synchronous generator transient stability may negatively be affected. In the previous paper [1], the results of the simulation analysis of the synchronous generator stability for a single-machine infinite-bus system with Corresponding author: Masaki Yagami, Ph.D., associate professor, research fields: power system stability and FACTS (flexible AC transmission system). yagami@hus.ac.jp. PV installed were presented. Through the simulation analysis, we have obtained the fundamental characteristics of the transient stability in the power system with PV installed, and it was concluded that the transient stability becomes better in the cases of the higher penetration PV without LVRT (low-voltage ride-through) capability. However, this conclusion is for a case study using the single-machine infinite-bus system model. For more accurate assessment of the transient stability and the dynamic characteristics of the power system with PV installed, it is necessary to analyze various simulation models considering many other power system conditions. In this work, the transient stability simulation is performed for IEEE 9-bus system model [3], in which the effects of various conditions, such as variety of power sources (inverter or rotational machine), load characteristics (constant impedance or power), fault locations (6 fault points) and existence of LVRT capability, on the stability are investigated. The
2 402 Transient Stability Assessment of Synchronous Generator in Power simulation is performed by using PSCAD/EMTDC software [4]. The paper is organized as follows: Section 2 describes the simulation model; Section 3 presents the simulation results and discussions; Section 4 gives conclusions. 2. Simulation Model 2.1 Power System Model Fig. 1 shows 9-bus power system model used in the simulation analysis. A synchronous generator of 500 MVA (SG1) and a large-scale PV plant of 500 MW (PV) or another synchronous generator of 500 MVA (SG2) are connected to an infinite bus through transformers and double circuit transmission lines. The capacity of PV or SG2 is equivalent to 50% for the power system capacity of 1,000 MVA. In the case with PV connected, the existence of LVRT capability is considered for PV inverter. LVRT characteristic considered in this work is simple. The PV inverter with LVRT capability maintains the connection to the grid even if its terminal voltage is dropped. On the other hand, the PV inverter without LVRT capability is disconnected from the grid when its terminal voltage drops below 70% of the nominal voltage [5], and the disconnection is maintained for remaining period of the simulation. The parameters used for each generator are shown in Table 1. AVR (automatic voltage regulator) and governor control systems which are the same models as those in Ref. [1] have also been included in each generator model. In the power system model, the symmetrical 3LG (three-line-to-ground) fault is assumed as network disturbance. The fault occurs at each fault point (F1-) at 0.1 s, the CBs (circuit breakers) on the faulted lines are opened at 0.17 s, and at 1.17 s, they are reclosed. 2.2 PV System Model The PV system model is shown in Fig. 2. It consists of PV module, inverter and LC (low-pass) filter. The PV module is represented with a voltage source, and hence the PV output is constant under the steady state. This means irradiation and PV cell temperature are constant during the simulation period. In general, transient stability is analyzed in a time window of a P/V = 0.5/ j0.144 (j0.0373) j0.025 F2 SG1 500 MVA CB 20/500 kv 500/20 kv F1 F j0.322 (j0.0765) 3LG fault CB P/Q = 0.5/ j (j0.0523) F j0.34 (j0.0895) P/Q = 0.5/0.0 j MVA SG2 or PV 500 MW P/Q = 0.4/0.3 F5 P/Q = 0.2/ j0.17 (j0.044) j0.184 (j0.0395) V = 1.0 j Hz, 1,000 MVA base Infinite bus Fig. 1 Power system model.
3 Transient Stability Assessment of Synchronous Generator in Power 403 Table 1 Synchronous generator parameters. Generator parameters SG1 SG2 SG1 SG2 R a (pu) X q (pu) X l (pu) T d (sec) X d (pu) T d (sec) X q (pu) T q (sec) X d (pu) H (s) X d (pu) LC filter Inverter PV PWM pulse I abc V abc abc/dq carrier Comparator PQ calculation P PV I d I d ref V d ref dq/abc V abc ref Q PV P PV ref Q PV ref I q ref I q V q ref Fig. 2 Control block diagram of PV inverter. few seconds to several tens of seconds. The assumption, therefore, may be valid for the transient stability analyses. The genetic PWM (pulse-width modulation) voltage source converter is used as PV inverter. The inverter controls the active and reactive power injected from the PV module to the system. To maintain the active and reactive power at the reference set points, the currents of the inverter are controlled by using vector control technique. The current limitation for over current is not considered in this model. Currently, most of the PV inverters are designed to operate at unity power factor [5], and therefore, the reference value of the reactive power is set to zero in each case. 2.3 Load Model A static load model can be expressed as algebraic functions of the bus voltage magnitude. The voltage dependency characteristic of load is represented by the exponential model [6]: a V P P0 V (1) 0 b V Q Q0 V (2) 0 where, P and Q are active and reactive components of the load when the bus voltage magnitude is V. The subscript 0 means the values of the respective variables at the initial operating condition. The parameters of this model are the exponents a and b. If these exponents equal to 0, 1, or 2, the model represents constant power, constant current or constant impedance characteristics respectively. In this simulation, two load models, the constant power and the constant impedance expressed by exponents of 0 and 2, are considered.
4 404 Transient Stability Assessment of Synchronous Generator in Power 3. Simulation Results 3.1 Impact of LVRT Capability The phase angle responses of SG1 in the case of fault point F1 are shown in Fig. 3. To compare the effects of the conventional rotating machine and PV system on transient stability, we have considered three simulation conditions in terms of the power sources as follows: (1) connecting SG2 instead of PV, (2) connecting PV with LVRT capability, and (3) connecting PV without LVRT capability. The load models of the constant impedance are used for all of the simulation conditions. As can be seen, the first peak of the phase angle swing is decreased in the case of PV without LVRT. In other words, risk of out-of-step of the synchronous generator becomes low in the power system with PV without LVRT installed. Fig. 4 shows the first peaks of the phase angle swings of SG1 in the case of each fault point. In all of the fault point cases, the first peaks of the phase angle swings in the case of PV without LVRT are restrained more than those in other cases. This is because the kinetic energy stored in the rotor of SG1 can be released quickly compared with other cases. Fig. 5 shows the kinetic energy responses of SG1 in the case of fault point F1. As can be seen, in the case of PV without Phase angle of SG1 (deg) Fig. 3 Phase angle of SG1 for each power source (fault First peak of phase angle swing (deg) 140 F1 F2 F3 F4 F5 Fig. 4 First peak of phase angle swing of SG1 for each power source. Kinetic energy of SG1 (pu) Fig. 5 Kinetic energy of SG1 for each power source (fault LVRT, the kinetic energy stored in the rotor of SG1 can be released quickly compared with other cases. Fig. 6 shows the stability index, W c [1, 7-9], in each fault point case. W c is an integrated variation of the energy exchanged between the generator rotor and the power system; thus, the lower the value of the parameter, the shorter the convergence time of the swing. In this work, the simulation time of t = 30 (s) is used to calculate W c. As can be seen, in most of the fault point cases, W c is decreased in the case of PV without LVRT. Namely, the convergence of the kinetic energy swing becomes fast in this case.
5 Transient Stability Assessment of Synchronous Generator in Power 405 W c (s) Fig. 6 F1 F2 F3 F4 F5 Stability index W c for each fault point. than that in the case of the. As a result, the kinetic energy stored during the period of acceleration is released quickly. The kinetic energy responses of SG1 are shown in Fig. 9. The first peaks of the phase angle swings and the stability index W c of SG1 in the case of the use of each load model are shown in Fig. 10. As a whole, values in the case of the are slightly larger in most cases than those in the case of the. Namely, the generator stability becomes slightly lower in the case of the Phase angle of SG1 (deg) Active power of SG1 (pu) Fig. 7 Phase angle of SG1 for each load model (fault point F1). 3.2 Impact of Load Characteristics Fig. 7 shows the phase angle responses of SG1 in the cases where each load model and PV without LVRT are considered. The load model of the constant impedance or the constant power, represented by Eqs. (1) and (2), is used in the simulation. As can be seen, the first peak of the phase angle swing in the case of the is smaller than that in the case of the. Fig. 8 shows the active power of SG1. After the fault clearing, the active power of SG1 in the case of the becomes slightly larger Fig. 8 Active power of SG1 for each load model (fault Kinetic energy of SG1 (pu) Fig. 9 Kinetic energy of SG1 for each load model (fault
6 406 Transient Stability Assessment of Synchronous Generator in Power First peak of phase angle swing (deg) F1 F2 F3 F4 F5 (a) First peak of phase angle swing of SG1 characteristics, fault locations and existence of LVRT capability, on the stability are investigated. Through the simulation results, it is concluded that the risk of out-of-step of the synchronous generator becomes low in the case of the use of PV without LVRT capability because the disconnection of PV system after the network disturbance increases the power load of the synchronous generator. Acknowledgments This work was supported by research grant from Japan Power Academy and JSPS KAKENHI Grant Number , 15H References W c (s) F1 F2 F3 (b) Stability index W c Fig. 10 Comparison of and constant impedance load. 4. Conclusions With the increasing of PV capacity in the power system, the transient stability of the conventional synchronous generator may negatively be affected due to the lower system inertia and the higher synchronous reactance. In this work, the transient stability simulation is performed for IEEE 9-bus system model, in which the effects of various parameters, such as variety of power sources (inverter or rotational machine), load F4 F5 [1] Yagami, M., Hasegawa, T., and Tamura, J Transient Stability Assessment of Synchronous Generator in Power System with High-Penetration Photovoltaics. Journal of Mechanics Engineering and Automation 2: [2] Photovoltaic Power Systems Programme Trends 2014 in Photovoltaic Applications. Report IEA-PVPS T1-25. [3] Anderson, P. M., Fouad, A. A Power System Control and Stability. New York: John Wiley & Sons, Inc. [4] Website of PSCAD. [5] Kobayashi, H., and Suzuki, A Stable Operation Technique for PCS of PV Power Generation at Grid Recovery after Voltage Sag. System Engineering Research Laboratory, Rep. No. R (in Japanese) [6] Kundur, P Power System Stability and Control. New York: McGraw-Hill, Inc. [7] Yagami, M., Murata, T., and Tamura, J An Analysis of Optimal Reclosing for Enhancement of Transient Stability. Electrical Engineering in Japan 147: [8] Yagami, M., and Tamura, J Improvement of Power System Transient Stability Using Superconducting Fault Current Limiter. Trans. on Systems, Signals & Devices 2 (2): [9] Yagami, M., and Tamura, J Hybrid Operation of Fault Current Limiter and Thyristor Controlled Braking Resistor. Journal of Energy and Power Engineering 6: 1-8.
INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous)
INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad - 500 043 ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK Course Name : Computer Methods in Power Systems Course Code : A60222
More informationECE 585 Power System Stability
Homework 1, Due on January 29 ECE 585 Power System Stability Consider the power system below. The network frequency is 60 Hz. At the pre-fault steady state (a) the power generated by the machine is 400
More informationKINGS COLLEGE OF ENGINEERING Punalkulam
KINGS COLLEGE OF ENGINEERING Punalkulam 613 303 DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING POWER SYSTEM ANALYSIS QUESTION BANK UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A (TWO MARK
More informationQUESTION BANK ENGINEERS ACADEMY. Power Systems Power System Stability 1
ower ystems ower ystem tability QUETION BANK. A cylindrical rotor generator delivers 0.5 pu power in the steady-state to an infinite bus through a transmission line of reactance 0.5 pu. The generator no-load
More informationB.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis
B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester Electrical and Electronics Engineering EE 1352 Power System Analysis (Regulation 2008) Time: Three hours Answer all questions Part A (10
More informationMinimization of Shaft Torsional Oscillations by Fuzzy Controlled Braking Resistor Considering Communication Delay
Proceedings of the 7th WSEAS International Conference on Power Systems, Beijing, China, September 15-17, 2007 174 Minimization of Shaft Torsional Oscillations by Fuzzy Controlled Braking Resistor Considering
More information1 Unified Power Flow Controller (UPFC)
Power flow control with UPFC Rusejla Sadikovic Internal report 1 Unified Power Flow Controller (UPFC) The UPFC can provide simultaneous control of all basic power system parameters ( transmission voltage,
More informationSelf-Tuning Control for Synchronous Machine Stabilization
http://dx.doi.org/.5755/j.eee.2.4.2773 ELEKTRONIKA IR ELEKTROTECHNIKA, ISSN 392-25, VOL. 2, NO. 4, 25 Self-Tuning Control for Synchronous Machine Stabilization Jozef Ritonja Faculty of Electrical Engineering
More informationEVALUATION OF THE IMPACT OF POWER SECTOR REFORM ON THE NIGERIA POWER SYSTEM TRANSIENT STABILITY
EVALUATION OF THE IMPACT OF POWER SECTOR REFORM ON THE NIGERIA POWER SYSTEM TRANSIENT STABILITY F. I. Izuegbunam * Department of Electrical & Electronic Engineering, Federal University of Technology, Imo
More informationEE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION
EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION PART: A 1. Define per unit value of an electrical quantity. Write equation for base impedance with respect to 3-phase system. 2. What is bus admittance
More informationDYNAMIC RESPONSE OF A GROUP OF SYNCHRONOUS GENERATORS FOLLOWING DISTURBANCES IN DISTRIBUTION GRID
Engineering Review Vol. 36 Issue 2 8-86 206. 8 DYNAMIC RESPONSE OF A GROUP OF SYNCHRONOUS GENERATORS FOLLOWING DISTURBANCES IN DISTRIBUTION GRID Samir Avdaković * Alija Jusić 2 BiH Electrical Utility Company
More informationQFT Framework for Robust Tuning of Power System Stabilizers
45-E-PSS-75 QFT Framework for Robust Tuning of Power System Stabilizers Seyyed Mohammad Mahdi Alavi, Roozbeh Izadi-Zamanabadi Department of Control Engineering, Aalborg University, Denmark Correspondence
More informationChapter 9: Transient Stability
Chapter 9: Transient Stability 9.1 Introduction The first electric power system was a dc system built by Edison in 1882. The subsequent power systems that were constructed in the late 19 th century were
More informationPOWER SYSTEM STABILITY
LESSON SUMMARY-1:- POWER SYSTEM STABILITY 1. Introduction 2. Classification of Power System Stability 3. Dynamic Equation of Synchronous Machine Power system stability involves the study of the dynamics
More informationComparative Study of Synchronous Machine, Model 1.0 and Model 1.1 in Transient Stability Studies with and without PSS
Comparative Study of Synchronous Machine, Model 1.0 and Model 1.1 in Transient Stability Studies with and without PSS Abhijit N Morab, Abhishek P Jinde, Jayakrishna Narra, Omkar Kokane Guide: Kiran R Patil
More informationUnified Power Flow Controller (UPFC) Based Damping Controllers for Damping Low Frequency Oscillations in a Power System
Unified Power Flow Controller (UPFC) Based Damping Controllers for Damping Low Frequency Oscillations in a Power System (Ms) N Tambey, Non-member Prof M L Kothari, Member This paper presents a systematic
More informationSCHOOL OF ELECTRICAL, MECHANICAL AND MECHATRONIC SYSTEMS. Transient Stability LECTURE NOTES SPRING SEMESTER, 2008
SCHOOL OF ELECTRICAL, MECHANICAL AND MECHATRONIC SYSTEMS LECTURE NOTES Transient Stability SPRING SEMESTER, 008 October 7, 008 Transient Stability Transient stability refers to the ability of a synchronous
More informationGenerators. What its all about
Generators What its all about How do we make a generator? Synchronous Operation Rotor Magnetic Field Stator Magnetic Field Forces and Magnetic Fields Force Between Fields Motoring Generators & motors are
More informationSSSC Modeling and Damping Controller Design for Damping Low Frequency Oscillations
SSSC Modeling and Damping Controller Design for Damping Low Frequency Oscillations Mohammed Osman Hassan, Ahmed Khaled Al-Haj Assistant Professor, Department of Electrical Engineering, Sudan University
More informationRESULTS OF ON-GRID OPERATION OF SUPERCONDUCTOR DYNAMIC SYNCHRONOUS CONDENSER
1 RESULTS OF ON-GRID OPERATION OF SUPERCONDUCTOR DYNAMIC SYNCHRONOUS CONDENSER Dr. Swarn S. Kalsi, David Madura, and Michael Ross American Superconductor Corporation (USA) Abstract: A high-temperature
More informationA Power System Dynamic Simulation Program Using MATLAB/ Simulink
A Power System Dynamic Simulation Program Using MATLAB/ Simulink Linash P. Kunjumuhammed Post doctoral fellow, Department of Electrical and Electronic Engineering, Imperial College London, United Kingdom
More informationDynamic simulation of a five-bus system
ELEC0047 - Power system dynamics, control and stability Dynamic simulation of a five-bus system Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct November 2017 1 / 16 System modelling
More information7. Transient stability
1 7. Transient stability In AC power system, each generator is to keep phase relationship according to the relevant power flow, i.e. for a certain reactance X, the both terminal voltages V1and V2, and
More informationA Computer Application for Power System Control Studies
A Computer Application for Power System Control Studies Dinis C. A. Bucho Student nº55262 of Instituto Superior Técnico Technical University of Lisbon Lisbon, Portugal Abstract - This thesis presents studies
More informationCOMPARISON OF DAMPING PERFORMANCE OF CONVENTIONAL AND NEURO FUZZY BASED POWER SYSTEM STABILIZERS APPLIED IN MULTI MACHINE POWER SYSTEMS
Journal of ELECTRICAL ENGINEERING, VOL. 64, NO. 6, 2013, 366 370 COMPARISON OF DAMPING PERFORMANCE OF CONVENTIONAL AND NEURO FUZZY BASED POWER SYSTEM STABILIZERS APPLIED IN MULTI MACHINE POWER SYSTEMS
More informationDESIGNING POWER SYSTEM STABILIZER WITH PID CONTROLLER
International Journal on Technical and Physical Problems of Engineering (IJTPE) Published by International Organization on TPE (IOTPE) ISSN 2077-3528 IJTPE Journal www.iotpe.com ijtpe@iotpe.com June 2010
More informationIEEE PES Task Force on Benchmark Systems for Stability Controls
IEEE PES Task Force on Benchmark Systems for Stability Controls Ian Hiskens November 9, 3 Abstract This report summarizes a study of an IEEE -generator, 39-bus system. Three types of analysis were performed:
More informationTransient Stability Analysis of Single Machine Infinite Bus System by Numerical Methods
International Journal of Electrical and Electronics Research ISSN 348-6988 (online) Vol., Issue 3, pp: (58-66), Month: July - September 04, Available at: www.researchpublish.com Transient Stability Analysis
More informationPower System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur
Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur Lecture - 9 Transmission Line Steady State Operation Welcome to lesson 9, in Power
More informationPARAMETRIC ANALYSIS OF SHAFT TORQUE ESTIMATOR BASED ON OBSERVER
PARAMETRIC ANALYSIS OF SHAFT TORQUE ESTIMATOR BASED ON OBSERVER Tetsuro Kakinoki, Ryuichi Yokoyama Tokyo Metropolitan University t.kakinoki@h4.dion.ne.jp Goro Fujita Shibaura Institute of Technology Kaoru
More information1. Introduction. Keywords Transient Stability Analysis, Power System, Swing Equation, Three-Phase Fault, Fault Clearing Time
Energy and Power 17, 7(1): -36 DOI: 1.593/j.ep.1771.3 Numerical Simulations for Transient Stability Analysis of Two-Machine Power System Considering Three-Phase Fault under Different Fault Clearing Times
More informationPower System Stability GENERATOR CONTROL AND PROTECTION
Power System Stability Outline Basis for Steady-State Stability Transient Stability Effect of Excitation System on Stability Small Signal Stability Power System Stabilizers Speed Based Integral of Accelerating
More informationRobust Tuning of Power System Stabilizers Using Coefficient Diagram Method
International Journal of Electrical Engineering. ISSN 0974-2158 Volume 7, Number 2 (2014), pp. 257-270 International Research Publication House http://www.irphouse.com Robust Tuning of Power System Stabilizers
More informationMitigation of Distributed Generation Impact on Protective Devices in a Distribution Network by Superconducting Fault Current Limiter *
Energy and Power Engineering, 2013, 5, 258-263 doi:10.4236/epe.2013.54b050 Published Online July 2013 (http://www.scirp.org/journal/epe) Mitigation of Distributed Generation Impact on Protective Devices
More informationResearch Paper ANALYSIS OF POWER SYSTEM STABILITY FOR MULTIMACHINE SYSTEM D. Sabapathi a and Dr. R. Anita b
Research Paper ANALYSIS OF POWER SYSTEM STABILITY FOR MULTIMACHINE SYSTEM D. Sabapathi a and Dr. R. Anita b Address for Correspondence a Research Scholar, Department of Electrical & Electronics Engineering,
More informationCHAPTER 3 MATHEMATICAL MODELING OF HYDEL AND STEAM POWER SYSTEMS CONSIDERING GT DYNAMICS
28 CHAPTER 3 MATHEMATICAL MODELING OF HYDEL AND STEAM POWER SYSTEMS CONSIDERING GT DYNAMICS 3.1 INTRODUCTION This chapter focuses on the mathematical state space modeling of all configurations involved
More informationEE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A
EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A 1. What are the advantages of an inter connected system? The advantages of an inter-connected system are
More informationMicro-grid to System Synchronization Based on Pre-Insertion Impedance Method (Version 1.0) By Peter Zhou University of Alberta Jan 30 th, 2015
Micro-grid to System Synchronization Based on Pre-Insertion Impedance Method (Version 1.0) By Peter Zhou University of Alberta Jan 30 th, 2015 Outline 1. What is Synchronization? 2. Synchronization Concerns?
More informationECE 325 Electric Energy System Components 7- Synchronous Machines. Instructor: Kai Sun Fall 2015
ECE 325 Electric Energy System Components 7- Synchronous Machines Instructor: Kai Sun Fall 2015 1 Content (Materials are from Chapters 16-17) Synchronous Generators Synchronous Motors 2 Synchronous Generators
More informationChapter 8: Unsymmetrical Faults
Chapter 8: Unsymmetrical Faults Introduction The sequence circuits and the sequence networks developed in the previous chapter will now be used for finding out fault current during unsymmetrical faults.
More informationEigenvalue Analysis of Subsynchronous Resonance Study in Series Compensated Wind Farm
e-issn: 2349-9745 p-issn: 2393-8161 Scientific Journal Impact Factor (SJIF): 1.711 International Journal of Modern Trends in Engineering and Research www.ijmter.com Eigenvalue Analysis of Subsynchronous
More informationChapter 3 AUTOMATIC VOLTAGE CONTROL
Chapter 3 AUTOMATIC VOLTAGE CONTROL . INTRODUCTION TO EXCITATION SYSTEM The basic function of an excitation system is to provide direct current to the field winding of the synchronous generator. The excitation
More informationModule 6 : Preventive, Emergency and Restorative Control. Lecture 27 : Normal and Alert State in a Power System. Objectives
Module 6 : Preventive, Emergency and Restorative Control Lecture 27 : Normal and Alert State in a Power System Objectives In this lecture you will learn the following Different states in a power system
More informationLong-term voltage stability : load aspects
ELEC0047 - Power system dynamics, control and stability Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct December 2018 1 / 15 Table of contents Voltage instability results from the
More informationPredicting, controlling and damping inter-area mode oscillations in Power Systems including Wind Parks
3rd IASME/WSEAS Int. Conf. on Energy & Environment, University of Cambridge, UK, February 3-5, 008 Predicting, controlling and damping inter-area mode oscillations in Power Systems including Wind Parks
More informationA STATIC AND DYNAMIC TECHNIQUE CONTINGENCY RANKING ANALYSIS IN VOLTAGE STABILITY ASSESSMENT
A STATIC AND DYNAMIC TECHNIQUE CONTINGENCY RANKING ANALYSIS IN VOLTAGE STABILITY ASSESSMENT Muhammad Nizam Engineering Faculty Sebelas Maret University (Ph.D Student of Electrical, Electronic and System
More informationImpact of Photovoltaic Generation On The Power System Stability
Impact of Photovoltaic Generation On The Power System Stability Eng. Abdelmoezz Ahmed Eid Dept. of Electrical Engineering Al-Azhar University Cairo, Egypt engabdelmoezz@gmail.com Dr. Tarek Mahmoud Dept.
More informationStudy of Transient Stability with Static Synchronous Series Compensator for an SMIB
Study of Transient Stability with Static Synchronous Series Compensator for an SMIB M.Chandu, Dr.T.R.Jyosthna 2 M.tech, Electrical Department, Andhra University, Andhra Pradesh, India 2 Professor, Electrical
More informationTransient Stability Improvement of a Multi- Machine Power System by Using Superconducting Fault Current Limiters
www.ijep.org International Journal of Energy and Power, Volume 5, 06 doi: 0.4355/ijep.06.05.006 Transient Stability Improvement of a Multi- Machine Power System by Using Superconducting Fault Current Limiters
More informationEE 451 Power System Stability
EE 451 Power System Stability Power system operates in synchronous mode Power system is subjected to a wide range of disturbances (small and large) - Loads and generation changes - Network changes - Faults
More informationFLEXIBLE ac transmission system (FACTS) devices give
694 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 19, NO. 2, APRIL 2004 A Newton-Type Current Injection Model of UPFC for Studying Low-Frequency Oscillations Kwang M. Son, Member, IEEE, and Robert H. Lasseter,
More informationIJSER. 1. Introduction
International Journal of Scientific & Engineering Research, Volume 7, Issue 5, May-2016 1543 Transient Stability Analysis of Generation and Transmission system of a thermal power plant of Pakistan. Izhar
More informationDesign of PSS and SVC Controller Using PSO Algorithm to Enhancing Power System Stability
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 10, Issue 2 Ver. II (Mar Apr. 2015), PP 01-09 www.iosrjournals.org Design of PSS and SVC Controller
More informationControl Lyapunov Functions for Controllable Series Devices
IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 16, NO. 4, NOVEMBER 2001 689 Control Lyapunov Functions for Controllable Series Devices Mehrdad Ghandhari, Member, IEEE, Göran Andersson, Fellow, IEEE, and Ian
More informationPower System Stability and Control. Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India
Power System Stability and Control Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India Contents Chapter 1 Introduction to Power System Stability
More informationThe Mathematical Model of Power System with Thyristor Controlled Series Capacitor in Long Transmission Line
American Journal of Applied Sciences 9 (5): 654-658, 01 ISSN 1546-939 01 Science Publications The Mathematical Model of Power System with Thyristor Controlled Series Capacitor in Long Transmission Line
More informationTransient Stability Assessment and Enhancement Using TCSC with Fuzzy Logic Controller
Transient Stability Assessment and Enhancement Using TCSC with Fuzzy Logic Controller Ali Qasim Hussein Department of Electrical Engineering, Acharya NAgarjuna University, Nagarjuna Nagar,Guntur,522510,Ap,
More informationIEEE 9 Bus System Example
IEEE 9 Bus System Example Version: R0 www.opal-rt.com REVISION HISTORY Author Revision Name Date R0 JP Bérard 23 Oct 2017 Approved Description IEEE 9 Bus System Example CONTENTS Page i 1. IEEE 9 BUS SYSTEM
More informationSimulating a Power System
Simulating a Power System Presented by Prof. Tyrone Fernando School of Electrical and Electronic Engineering (EECE), University of Western Australia (UWA) 1. Motivations In an actual power system, it is
More informationPOWER SEMICONDUCTOR BASED ELECTRIC DRIVES
POWER SEMICONDUCT BASED ELECTRIC DRIVES [Time: 3 Hrs] [Max. Marks: 80] Instructions: Solve any six questions from Q.No (1 or 2), Q.No (3 or 4), Q.No (5 or 6), Q.No (7 or 8), Q.No (9 or 10), Q.No (11 or
More informationIGEE 402 Power System Analysis. FINAL EXAMINATION - SAMPLE Fall 2004
IGEE 402 Power System Analysis FINAL EXAMINATION - SAMPLE Fall 2004 Special instructions: - Duration: 80 minutes. - Material allowed: a crib sheet (double sided 8.5 x ), calculator. - Attempt 5 out of
More informationImproving Transient Stability of Multi-Machine AC/DC Systems via Energy-Function Method
International Journal of Engineering Research and Development e-issn: 2278-67X, p-issn: 2278-8X, www.ijerd.com Volume 1, Issue 8 (August 214), PP.3- Improving Transient Stability of Multi-Machine AC/DC
More informationDynamic Modeling of GE 1.5 and 3.6 Wind Turbine-Generators
GE Power Systems Dynamic Modeling of GE.5 and 3.6 Wind Turbine-Generators Prepared by: Nicholas W. Miller William W. Price Juan J. Sanchez-Gasca October 27, 2003 Version 3.0 GE-Power Systems Energy Consulting
More informationSPEED-GRADIENT-BASED CONTROL OF POWER NETWORK: CASE STUDY
CYBERNETICS AND PHYSICS, VOL. 5, NO. 3, 2016, 85 90 SPEED-GRADIENT-BASED CONTROL OF POWER NETWORK: CASE STUDY Igor Furtat Control of Complex Systems ITMO University Russia cainenash@mail.ru Nikita Tergoev
More informationDESIGN OF POWER SYSTEM STABILIZER USING FUZZY BASED SLIDING MODE CONTROL TECHNIQUE
DESIGN OF POWER SYSTEM STABILIZER USING FUZZY BASED SLIDING MODE CONTROL TECHNIQUE LATHA.R Department of Instrumentation and Control Systems Engineering, PSG College of Technology, Coimbatore, 641004,
More informationTransient stability improvement by using PSS and increasing inertia of synchronous machine
American Journal of Electrical Power and Energy Systems 2014; 3(2): 45-49 Published online April 20, 2014 (http://www.sciencepublishinggroup.com/j/epes) doi:10.11648/j.epes.20140302.15 Transient stability
More informationECE 422/522 Power System Operations & Planning/ Power Systems Analysis II 3 Load Modeling
ECE 422/522 Power System Operations & Planning/ Power Systems Analysis II 3 Load Modeling Spring 2014 Instructor: Kai Sun 1 References 1. Load Performance for Dynamic Performance Analysis, IEEE Committee
More informationSmall Signal Stability Analysis of Power System with Increased Penetration of PV Generation
Kalpa Publications in Engineering Volume, 207, Pages 200 207 ICRISET207. International Conference on Research and Innovations in Science, Engineering &Technology. Selected Papers in Engineering Small Signal
More informationImpact of Distributed Synchronous Generators on Distribution Feeder Stability
Impact of Distributed Synchronous Generators on Distribution Feeder Stability F. M. Gonzalez-Longatt, Student Member Abstract The distributed generation is rapidly becoming a reality. Some technologies
More informationHOW TO DEAL WITH ELECTROMAGNETIC DISTURBANCES CAUSED BY NEW INVERTER TECHNOLOGIES CONNECTED TO PUBLIC NETWORK
HOW TO DEAL WITH ELECTROMAGNETIC DISTURBANCES CAUSED BY NEW INVERTER TECHNOLOGIES CONNECTED TO PUBLIC NETWORK Xavier YANG EDF R&D - France xavier.yang@edf.fr Ludovic BERTIN EDF R&D - France ludovic-g.bertin@edf.fr
More informationECE 422/522 Power System Operations & Planning/Power Systems Analysis II : 7 - Transient Stability
ECE 4/5 Power System Operations & Planning/Power Systems Analysis II : 7 - Transient Stability Spring 014 Instructor: Kai Sun 1 Transient Stability The ability of the power system to maintain synchronism
More informationCritical clearing time evaluation of Nigerian 330kV transmission system
American Journal of Electrical Power and Energy Systems 2013; 2(6): 123-128 Published online October 20, 2013 (http://www.sciencepublishinggroup.com/j/epes) doi: 10.11648/j.epes.20130206.11 Critical clearing
More informationExamples of Applications of Potential Functions in Problem Solving (Web Appendix to the Paper)
Examples of Applications of otential Functions in roblem Solving (Web Appendix to the aper) Ali Mehrizi-Sani and Reza Iravani May 5, 2010 1 Introduction otential functions may be exploited to formulate
More informationSYNCHRONOUS GENERATOR s ROTOR INVESTIGATION OF A HYBRID POWER SYSTEM INCLUDING A.G.
Proc. of the 5th WSEAS/IASME Int. Conf. on Electric Power Systems, High Voltages, Electric Machines, Tenerife, Spain, December 16-18, 25 (pp59-514) SYNCHRONOUS GENERATOR s ROTOR INVESTIGATION OF A HYBRID
More informationFault Location in Distribution Feeders with Distributed Generation using Positive Sequence Apparent Impedance
Fault Location in Distribution Feeders with Distributed Generation using Positive Sequence Apparent Impedance ARTURO SUMAN BRETAS Federal University of Rio Grande do Sul Department of Electrical Engineering
More informationThe Mathematical Model of Power System with Static Var Compensator in Long Transmission Line
American Journal of Applied Sciences 9 (6): 846-850, 01 ISSN 1546-939 01 Science Publications The Mathematical Model of Power System with Static Var Compensator in Long Transmission Line Prechanon Kumkratug
More informationOptimal Placement & sizing of Distributed Generator (DG)
Chapter - 5 Optimal Placement & sizing of Distributed Generator (DG) - A Single Objective Approach CHAPTER - 5 Distributed Generation (DG) for Power Loss Minimization 5. Introduction Distributed generators
More informationEffect of Inertia Constant on Generator Frequency and Rotor Angle
Engineering and Applied Sciences 2018; 3(1): 6-11 http://www.sciencepublishinggroup.com/j/eas doi: 10.11648/j.eas.20180301.12 ISSN: 2575-2022 (Print); ISSN: 2575-1468 (Online) Effect of Inertia Constant
More informationPOWER SYSTEM STABILITY AND CONTROL
POWER SYSTEM STABILITY AND CONTROL P. KUNDUR Vice-President, Power Engineering Powertech Labs Inc., Surrey, British Columbia Formerly Manager Analytical Methods and Specialized Studies Department Power
More informationLESSON 20 ALTERNATOR OPERATION OF SYNCHRONOUS MACHINES
ET 332b Ac Motors, Generators and Power Systems LESSON 20 ALTERNATOR OPERATION OF SYNCHRONOUS MACHINES 1 LEARNING OBJECTIVES After this presentation you will be able to: Interpret alternator phasor diagrams
More informationDoubly-Fed Induction Generator Wind Turbine Model for Fault Ride-Through Investigation
32 ECTI TRANSACTIONS ON ELECTRICAL ENG., ELECTRONICS, AND COMMUNICATIONS VOL.11, NO.1 February 2013 Doubly-Fed Induction Generator Wind Turbine Model for Fault Ride-Through Investigation Yutana Chongjarearn
More informationModule 3 : Sequence Components and Fault Analysis
Module 3 : Sequence Components and Fault Analysis Lecture 12 : Sequence Modeling of Power Apparatus Objectives In this lecture we will discuss Per unit calculation and its advantages. Modeling aspects
More informationMathematical Modeling and Dynamic Simulation of a Class of Drive Systems with Permanent Magnet Synchronous Motors
Applied and Computational Mechanics 3 (2009) 331 338 Mathematical Modeling and Dynamic Simulation of a Class of Drive Systems with Permanent Magnet Synchronous Motors M. Mikhov a, a Faculty of Automatics,
More informationECEN 667 Power System Stability Lecture 20: Oscillations, Small Signal Stability Analysis
ECEN 667 Power System Stability Lecture 20: Oscillations, Small Signal Stability Analysis Prof. Tom Overbye Dept. of Electrical and Computer Engineering Texas A&M University, overbye@tamu.edu 1 Announcements
More informationFault Calculation Methods
ELEC9713 Industrial and Commercial Power Systems Fault Calculation Methods There are two major problems that can occur in electrical systems: these are open circuits and short circuits. Of the two, the
More informationPowerApps Optimal Power Flow Formulation
PowerApps Optimal Power Flow Formulation Page1 Table of Contents 1 OPF Problem Statement... 3 1.1 Vector u... 3 1.1.1 Costs Associated with Vector [u] for Economic Dispatch... 4 1.1.2 Costs Associated
More informationEE 6501 POWER SYSTEMS UNIT I INTRODUCTION
EE 6501 POWER SYSTEMS UNIT I INTRODUCTION PART A (2 MARKS) 1. What is single line diagram? A Single line diagram is diagrammatic representation of power system in which the components are represented by
More informationFault Analysis Power System Representation
.1. Power System Representation Single Line Diagram: Almost all modern power systems are three phase systems with the phases of equal magnitude and equal phase difference (i.e., 10 o ). These three phase
More informationBehaviour of synchronous machine during a short-circuit (a simple example of electromagnetic transients)
ELEC0047 - Power system dynamics, control and stability (a simple example of electromagnetic transients) Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct October 2018 1 / 25 Objectives
More informationSSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL
1 SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL Power Systems: Generation, Transmission and Distribution Power Systems: Generation, Transmission and Distribution Power Systems:
More informationEE 742 Chapter 3: Power System in the Steady State. Y. Baghzouz
EE 742 Chapter 3: Power System in the Steady State Y. Baghzouz Transmission Line Model Distributed Parameter Model: Terminal Voltage/Current Relations: Characteristic impedance: Propagation constant: π
More informationWind Generator Stabilization with Doubly-Fed Asynchronous Machine
Wind Generator Stabilization with DoublyFed Asynchronous Machine Li Wu*, Junji Tamura,Zhixin Wang* Electrical Engineering Department,Shanghai Jiao Tong University 1954 Huashan Road,200030,P.R.hina wuli@sjtu.edu.cn
More informationA Technique for Enhancement of Power System Dynamic Stability
International Journal of Engineering Science Invention arch. 3 A Technique for Enhancement of Power System Dynamic Stability Dr. Ramesh Kumar, ithilesh Das, R.K.andal 3, Ruchita 4 National Institute of
More informationANALYSIS OF SUBSYNCHRONOUS RESONANCE EFFECT IN SERIES COMPENSATED LINE WITH BOOSTER TRANSFORMER
ANALYSIS OF SUBSYNCHRONOUS RESONANCE EFFECT IN SERIES COMPENSATED LINE WITH BOOSTER TRANSFORMER G.V.RAJASEKHAR, 2 GVSSNS SARMA,2 Department of Electrical Engineering, Aurora Engineering College, Hyderabad,
More informationIncorporation of Asynchronous Generators as PQ Model in Load Flow Analysis for Power Systems with Wind Generation
Incorporation of Asynchronous Generators as PQ Model in Load Flow Analysis for Power Systems with Wind Generation James Ranjith Kumar. R, Member, IEEE, Amit Jain, Member, IEEE, Power Systems Division,
More informationLabVIEW Based Simulation of Static VAR Compensator for Transient Stability Enhancement in Electric Power Systems
International Journal of Electrical Engineering. ISSN 0974-2158 Volume 4, Number 1 (2011), pp.143-160 International Research Publication House http://www.irphouse.com LabVIEW Based Simulation of Static
More informationA. P. Sakis Meliopoulos and George J. Cokkinides Power System Relaying, Theory and Applications. Chapter 8 2 Generator Protection 2
DRAFT and INCOMPLETE Table of Contents from A. P. Sakis Meliopoulos and George J. Cokkinides Power System Relaying, Theory and Applications Chapter 8 Generator Protection 8. Introduction 8. Generator Protection
More informationEE Branch GATE Paper 2010
Q.1 Q.25 carry one mark each 1. The value of the quantity P, where, is equal to 0 1 e 1/e 2. Divergence of the three-dimensional radial vector field is 3 1/r 3. The period of the signal x(t) = 8 is 0.4
More informationUNIT-I Economic Operation of Power Systems -1
UNIT-I Economic Operation of Power Systems -1 Overview Economic Distribution of Loads between the Units of a Plant Generating Limits Economic Sharing of Loads between Different Plants Automatic Generation
More informationCHAPTER 2 DYNAMIC STABILITY MODEL OF THE POWER SYSTEM
20 CHAPTER 2 DYNAMIC STABILITY MODEL OF THE POWER SYSTEM 2. GENERAL Dynamic stability of a power system is concerned with the dynamic behavior of the system under small perturbations around an operating
More information