EFFECTS OF EHV POWER CIRCUIT BREAKER RECLOSING ON POWER SYSTEM STABILITY

Size: px
Start display at page:

Download "EFFECTS OF EHV POWER CIRCUIT BREAKER RECLOSING ON POWER SYSTEM STABILITY"

Transcription

1 EFFECTS OF EHV POWER CIRCUIT BREAKER RECLOSING ON POWER SYSTEM STABILITY A THESIS Presented to The Faculty of the Division of Graduate Studies By U. C. Roumillat, Jr. In Partial Fulfillment of the Requirements for the Degree Master of Science in Electrical Engineering Georgia Institute of Technology May, 1978

2 EFFECTS OF EHV POWER CIRCUIT BREAKER RECLOSING ON POWER SYSTEM STABILITY Approved: Rogery Webb, Ch airman Chee-Yee Chong ^ Claytoh H. Griffin v "V Ed W. Kamen Date approved by Chairman S"/z3/ r y J S'

3 ii ACKNOWLEDGEMENTS I wish to express my appreciation to all those who have contributed to the successful completion of this thesis. The subject was suggested by Mr. Clayton Griffin, Georgia Power Company Chief Protection Engineer; and, his advice and encouragement is gratefully acknowledged. Thanks are also extended to my thesis advisor, Dr. Roger Webb, and to the reading committee members, Dr. C-Y Chong, Mr. C. H. Griffin, and Dr. E. W. Kamen, for their guidance. I am indebted to the Southern Company's Georgia Power Company and Southern Company Services, Incorporated, for the use of their digital computer facilities. Also, I appreciate the help of Mr. W. R. Startt of Georgia Power Company, Mr. N. J. Balu, and Mr. S. G. Burks of Southern Company Services, Incorporated, in using the computer facilities. Thanks also go to Mrs. W. A. Moncrief for typing the manuscript. I would like to dedicate this thesis to my wife, Lucie. Her sacrifices and understanding were essential for the completion of this work.

4 iii f TABLE OF CONTENTS ACKNOWLEDGEMENT., LIST OF TABLES LIST OF ILLUSTRATIONS LIST OF SYMBOLS AND ABBREVIATIONS SUMMARY Page ii V vi vii viii Chapter I. INTRODUCTION 1 II. FORMULATION OF THE STABILITY STUDY... 7 The Purpose and Approach of the Study 7 Methods Used to Calculate System Behavior Following a Disturbance 7 Cases Studied 8 Definition of Terms Used 13 III. ANALYSIS BY THE USE OF A DIGITAL COMPUTER Introduction 15 Data Preparation 15 Initial Conditions and Method of Analysis Analysis of Case 1 17 Analysis of Case 2 19 Analysis of Case 3 19 Analysis of Case 4 19 Analysis of Cases 5 and 6 22 Analysis of Cases 7 and 8 22 IV. ANALYSIS OF THE REDUCED SYSTEM 26 Approach and Assumptions 26 Analysis of Cases 9 and Analysis of Cases 11 and 12 32

5 iv TABLE OF CONTENTS Chapter Page V. EVALUATION OF REDUCED SYSTEM ANALYSIS AND LIAPUNOV METHOD Purpose 36 Comparison of the Computer Analysis with the Point-By-Point Analysis 36 Comparison of the Point-By-Point Analysis with the Liapunov Method 37 Evaluation of the Comparisons 39 VI. CONCLUSION 4 0 Effect of Reclosing on Stability 40 Basis for Conclusion 40 VII. RECOMMENDATIONS 42 APPENDIX 43 BIBLIOGRAPHY 56

6 V LIST OF TABLES Table Page 1. Load Flow System Parameters Generator Parameters Computer Computation of Case Computer Computation of Case Point-By-Point Computcition of Case Point-By-Point Computation of Case Liapunov Computation of Case 11 55

7 VI LIST OF ILLUSTRATIONS e Page Generator Shaft Torques 4 Reduced 500-KV System 9 Swing Curves of Cases 1 and 9 18 Swing Curves of Cases 2 and Swing Curves of Cases 3 and 4 21 Swing Curves of Cases 5 and 6 23 Swing Curves of Cases 7 and 8 24 Equivalent System 28 Power-Angle Curves of Cases 9 and Rotor Speed-Rotor Angle Curves of Cases 9 and Liapunov Method Cases 11 and 12 38

8 Vll LIST OF SYMBOLS AND ABBREVIATIONS Generator rotor angle relative to an infinite bus. th Change in 6 for the n time interval. Time in seconds. Maximum power transfer. Accelerating power. Electrical power input. Electrical power output. Angular rotor speed above synchronous speed. Power circuit breaker. Extra high voltage. Inertia constant. Per unit on a 100 MVA base. With respect to. Moment of inertia in pound-feet 2 of the entire unit. (Generator, Prime Mover and Exciter.)

9 viii SUMMARY Power circuit breakers have been closed as soon as possible to aid system stability. However, closing a breaker that places a fault near a generator can damage the rotor shaft of the generator due to the resulting torques impressed on the rotor. If the closing of the breakers is delayed ten seconds, the rotor oscillations have decayed sufficiently to prevent shaft damage when a fault is placed near the machine. The purpose of this thesis is to investigate the effects of closing a breaker as rapidly as the breaker manufacturers allow on generator stability. On modern EHV circuit breakers this limitation requires that closing should be delayed by about one-third second. The four large generators at Georgia Power Company's Plant Bowen were reduced to an equivalent generator feeding an infinite bus thirough an equivalent transmission system. This reduction made* it possible to solve the classical swing equation by the point-by-point method. Various fault-clearing and breaker-closing times were, used until the critical closing time was determined. The change in rotor angular velocity with respect to angular displacement was plotted to graphically determine a separatrix curve. A Liapunov function was plotted on the same graph for a comparison of the results. The curves

10 ix illustrate that reclosing into a fault that is not cleared by the critical time can result in generator instability. Digital computer methods were used to reduce the power system to an equivalent 124 bus network. Transient stability conditions, similar to the conditions used in the manual calculations, were studied for comparison. The swing curves resulting from various system conditions are also included. The results obtained by the computer were in close agreement with those obtained by manual calculations.

11 1 CHAPTER I INTRODUCTION The objective of this thesis was to study the stability of a large section of the southeastern electric utility power system. The effect of interconnections of this section with other power systems was included in the study. The power system is constructed by connecting electromechanical generators in a network of transmission lines. The transmission lines are used to supply consumer loads and to connect the generators in synchronous parallel operation. The power supplied by the generators must equal the system losses plus the system load for the generators to maintain synchronous parallel operation. The power system is in stable operation when the generation matches the load. A system disturbance such as a line opening or faulting will produce a power swing in the interconnected system. The effect of the disturbance will be most severe at points in the system that are electrically close to the disturbance. If the disturbance is a three phase fault, all of the generator rotors will accelerate causing a power swing or oscillation to begin. The resulting electrical angular difference between generator rotors during the swing will determine the stability of the system. Electromechanical restoring forces will

12 2 return the rotors of the machines to synchronous operation if the angular difference decreases with successive power swing oscillations after a fault is cleared. If the angular difference of the generator rotors continues to increase with successive oscillations, the generator or group of generators must be automatically separated from the system. This reduces the strength of the system and can cause other generator rotors to swing out of synchronism and collapse the system. A short circuit on a modern power system EHV bus must be cleared quickly by the opening of the power circuit breakers surrounding the short circuit. Protective relay operating time plus breaker clearing time is normally 0.05 second. If the short circuit occurs on a transmission line, the clearing of the fault will result in the loss of the transmission line. Since some short circuits are due to arc discharges to ground that are extinguished when the transmission line is de-energized, the line can possibly be restored to service automatically in 0.47 second. The reclosing time includes breaker opening time plus a preset closing time delay as suggested by the breaker manufacturer. Short circuits near a generator effect the generator and turbine shafts even more than the stator windings since the shafts become torsionally excited and are exposed to oscillatory stresses (l). A typical modern generator shaft system can have six natural resonant frequencies. Three of

13 3 these frequencies are above the power system frequency and three below. Simulated shaft system computer studies have shown that the resulting mechanical shaft torque can be as high as seven times normal after reclosing to a line that is not short circuited. (See Figure 1) To reduce the possibility of fatigue resulting in the generator shaft system one generator manufacturer has suggested that power circuit breaker reclosing near generators be delayed for at least ten seconds. The manufacturer believes the decay of torsional oscillation in the generator shaft will be sufficient to eliminate the risk of shaft fatigue after ten seconds. Manufacturers agree that shaft damage is also possible if an average generator power output change exceeding one-half pea: unit results from normal line switching. The literature on power system stability prior to 1945 included stability studies of interconnected power systems with high speed power circuit breaker reclosing. These stability studies provided the engineer with information on the maximum possible time for de-energization of the faulted circuit without loss of synchronism. The minimum permissible time for de-ionization of the fault arc was the determining factor in setting the reclosing time. The only risk considered in high speed reclosing was that of restriking the fault arc and that was considered to be negligible. In February, 1945, an article appeared in the AIEE

14 High Low Pressure Pressure 1 Intermediate Low Pressure Pressure 2 Generator \ Exciter HHZ] Coupling Mechanical Torque Electrical Torque Figure 1. Generator Shaft Torques ^

15 5 Transactions on Power Apparatus and Systems discussing the transient electrical torques of turbines during short circuits (10). However, the manufacturers of generators did not show much concern until fatigue of a generator shaft was experienced recently by a power company in the western part of the country. This fatigue was attributed to subsynchronous resonance. Subsynchronous resonance is a problem in the western part of the country because generators are frequently connected to the end of long lines with reactances approaching the subsynchronous reactance of the generator. This shaft fatigue experience caused the manufacturers to become concerned about the high speed reclosing of circuit breakers as well as synchronizing and line switching near generators. Generators manufactured recently have inertia constants more than twice the inertia constants of smaller units that were manufactured in the last decade. The subsynchronous, direct axis and quadrature reactances of these later units are about one-fourth the reactances of the earlier units. The accelerating power and available shaft torque during a short circuit condition has increased as a result. When a short circuit occurs on a utility network, a step function of shaft torque is applied to the generator shaft system. Another step function will be applied when the short circuit is cleared by the opening of surrounding circuit breakers. If another system disturbance occurs such as circuit breaker reclosing another step function will be applied to the shaft

16 6 system. These step functions will cause additive or subtractive torques to be applied to the shaft depending on the point of the oscillatory period they occur. The requirements of the manufacturers have resulted in power system operating changes that have created a problem for the power system protection engineer. Resulting power system stability and network line loading as a function of power circuit breaker reclosing time delay must be researched. The data accumulated in this research should help the protection engineer design protective schemes to minimize adverse effects on the power system. Since the protection engineer cannot risk the possibility of subjecting the generator shafts to excessive torques, he must delay reclosing by the time suggested by the manufacturer. He must then design the system protective relaying around the new operating conditions. Therefore, he needs to know the effects of power circuit breaker reclosing on power system stability as a function of reclosing time. He also needs to know the effect of not reclosing until the power swings have decayed.

17 7 CHAPTER II FORMULATION OF THE STABILITY STUDY The Purpose and Approach of the Study The purpose of this thesis was to study the effects of EHV power circuit breaker reclosing on the power system. The approach was to simulate the reclosing of breakers near a large generating facility after a fault was cleared by the opening of breakers. The ressulting power system swings were calculated at 0.17 second time intervals. The time for clearing the initial fault is normally three cycles in practice, and this initial clearing time was used throughout the study. The time taken to clear the fault after the breakers reclose was varied in the cases studied. The reason for varying the time for clearing the fault after reclosing was to determine the effects of reclosing on the power system under abnormal conditions. Abnormal conditions include those that occur due to a stuck breaker, failure of primary protective relays, incorrect operation of reclosing relays or incorrect operation of the control scheme. Methods Used to Calculate System Behavior Following a Disturbance A digital computer was used to reduce the Georgia Power Company system and its interconnections to other

18 8 systems to 124 buses. A portion of this system is shown in Figure 2. A load flow solution was used as the initial system conditions for the stability studies. Three phase faults were placed near the Plant Bowen 500-KV bus. Various reclosing times and fault clearing times were used to disturb the system. System conditions were calculated for every second following the disturbance by the use of a digital computer. Similar system disturbances were calculated by the classical swing equation using a point-by-point solution method, and also by the use of a Liapunov function developed by Gless (9). Cases Studied Case 1 In this case a three phase fault was placed on the Bowen-Sequoyah 500-KV line near the Bowen 500-KV bus. The fault was cleared in three cycles. The fault was replaced by reclosing the associated breakers after 2 8 cycles from the initial disturbance. The second fault remained on the system for 11 cycles before it was cleared. The three cycles clearing time of the initial fault is a normal operation. A closing delay setting of 25 cycles on the EHV breakers would cause a normal reclosing time of approximately 2 8 cycles. However, the 11 cycle clearing time is abnormal. This delayed clearing time will be experienced if a breaker associated with the faulted line fails to trip. In this case a back-up

19 V Bowen Sequoyah T Villa Rica I T Union City Norcross X Wansley Klondike 5HI I Figure 2. Reduced 500-KV System V >

20 10 relaying scheme is employed to trip back-up breakers. The breaker failure clearing time is 11 cycles in this case. This time was chosen because it is the critical switching time to maintain system stability. Case!2 A three phase fault was placed on the Bowen-Sequoyah 500-KV line near Bowen. The fault was cleared in three cycles. The fault was replaced by reclosing the associated breakers after 28 cycles. This time the second fault remained on the system for 12 cycles before it was cleared. The 12 cycle time was chosen since it is probable that breaker failure clearing time could require 12 cycles, and it is one cycle beyond the critical switching time. Case 2 A three phase fault was placed on the Bowen-Norcross 500-KV line near Norcross. The fault was cleared after three cycles and the system was left undisturbed for the remainder of the one second calculating period. This case was chosen to illustrate the system response to a remote fault being cleared in normal time without reclosing. Case A three phase fault was placed on the Bowen-Norcross 500-KV line near Bowen. The fault was cleared after three cycles. The associated breakers closed in 28 cycles placing the fault back on the system. The Bowen breaker tripped in three cycles, but the Norcross breaker remained closed for

21 30 cycles. This case illustrates the effect of leaving the fault connected to the system through the impedance of the Bowen-Norcross line. Case _5 A three phase fault was placed on the Bowen-Norcross 500-KV line near Norcross. The fault was cleared after three cycles. The Norcross breaker reclosed after 28 cycles and remained closed for 30 cycles. This case illustrates the effect of a remote terminal reclosing and failing to clear a fault in primary relaying time. Case S_ A three phase fault was placed on the Bowen-Sequoyah 500-KV line near Bowen. Reclosing occurred after 28 cycles. In this case the fault was removed before reclosing took place. This case was chosen to illustrate reclosing to an unfaulted line. Case ]_ A three phase fault was placed on the Bowen-Sequoyah 500-KV line near Eiowen. Reclosing occurred after 28 cycles with the fault present. The fault was cleared in 11 cycles and then the breakers reclosed again six cycles later. Even though this sequence of events would not likely occur during normal operation of the system, it was chosen to illustrate the resulting power swing. Case8: A three phase fault was placed on the Bowen-Sequoyah

22 500-KV line near Bowen. The fault was cleared at the Bowen terminal in three cycles. The fault was cleared from the Sequoyah terminal after 2 8 cycles. Reclosing of the Bowen- Sequoyah line took place after an additional 25 cycles into a fault that remained nine cycles before it was cleared. The sequence of events that could cause this operation in practice is the failure of primary protective relaying at the Sequoyah terminal. Nornicil reclosing took place in 25 cycles, but the Sequoyah breciker failed to clear the fault. Breaker failure back-up relaying at Sequoyah finally cleared the fault after nine cycles. Case This case was used to compare the results of a pointby-point solution of the swing equation with the results of a digital computer solution. A three phase fault was placed on the Bowen-Sequoyah 500-KV line near the Bowen 500-KV bus. The fault was clecired in three cycles. Reclosing into the fault occurred after 28 cycles. The fault was cleared after 11 cycles. Computations were ended after 1.2 seconds. Case 10 This case was also used to compare the results of a point-by-point solution with a digital computer solution. A three phase fault was placed on the Bowen-Sequoyah 500-KV line near the Bowen 500-KV bus. The fault was cleared in three cycles. Reclosing into the fault occurred after 28 cycles. The fault was cleared after 12 cycles and the Bowen

23 13 generators became unstable. Case 11 A Liapunov function developed by Gless (9) was used to calculate the maximum stable trajectory, in the rotor speed-rotor displacement plane, of the generator stability boundary. Rotor speed is a function of inertia, rotor displacement with respect to a synchronous reference bus, mechanical shaft input power and the power transfer between the generators and the infinite bus. Case 12 The same Liapunov function that was used in Case 11 was used in this case. However, the initial rotor angle is radians and switching into a permanent fault occurs when the rotor angular displacement reaches 1.22 radians. The system conditions simulated are similar to those in Cases 2 and 10. This case was included for comparison of the Liapunov method with the digital computer and point-by-point calculation methods. Definition of_ Terms Used The IEEE standard definition of power system stability is as follows: In a system of two or more synchronous machines connected through an eleictric network, the condition in which the difference of the angular positions of the rotors of the machines either remains constant while not subjected to a disturbance, or becomes constant following an aperiodic disturbance.

24 14 The IEEE standard definition of a Liapunov function is as follows: A scalar differentiable function V(x) defined in some open region including x e such that in that region (1) V(x) > 0 for x ^ x e (where x e = system equilibrium point) (2) V(x e ) = 0 (3) V (x) < 0. The "Critical Angle" is defined as follows: If a severe fault that is placed on a power system is removed before conditions are reached that would lead to instability, the system would remain stable. The maximum time the fault can remain with stable system operation maintained is known as the critical clearing time. The critical condition occurs when the sum of the potential and kinetic energy stored within the system at the instant immediately after clearing the fault does not exceed the maximum amount of potential energy which the system is able to accommodate. The relative rotor angle of the equivalent machine associated with this condition is known as the critical switching angle. The time taken to reach the*, critical switching angle is known as the critical switching time.

25 15 CHAPTER III ANALYSIS BY THE USE OF A DIGITAL COMPUTER Introduction Cases 1 through 8 were the cases studied by the use of a digital computer. In these cases the entire Georgia Power Company system with the interconnections to neighboring companies was reduced to 124 buses. A modified transient stability program by the Philadelphia Electric Company was used for the analysis (3). This program was also used for star-mesh reduction of the network (2]. Equivalent lines were created between buses, and loads were modified to represent the interconnected network by a reduced system. Data Preparation Data was pirepared for transformers and lines, loads, generators, governors and exciters. The impedances of the lines and trans formers were entered into the program in percent quantities on a 100 MVA base. The line charging MVA was also entered. This program assigns half of the charging MVA to each terminal bus. Transformers are distinguished from transmission lines by an entry in the transformer tap field. The transformer tap setting is the actual per-unit ratio of the transformer. Phase shifts introduced by the transformers were also included. Megawatt and megavar loads

26 16 were entered and represented as constant impedances. Initial Conditions and Method of Analysis The results of a load flow program were used as initial conditions for the transient stability study. These results for the generators and buses near Bowen were listed in Table 1. The generators were modeled in the stability study in more detail than the classical models used in load flow programs. The effects of field variations in the synchronous machines were represented. Generator damping was computed and inserted by the computer program on the generator bus for each generator near the fault. Generator saturation constants were entered into the program for calculation of the voltages behind the leakage reactances, which are proportional to the field currents. The excitation system was represented by entering the regulator, exciter, and amplifier time constants and other quantities for detailed modeling of the exciter. The speed governor control during transient periods was represented by transfer functions and time constants describing the steam and control systems. Solution of network performance equations was required to obtain system conditions at the instant after a fault occurs (0+ seconds). In this study, a three phase fault was placed on the network near Plant Bowen. The Gauss-Seidel iterative method was used to solve the network equations (2.).

27 17 Changes in genercitor internal voltage angles and generator speeds were calculated by solving first order differential equations by the modified Euler method (2). Network solutions were obtained for every second after the fault for at least one second. The initial conditions were not varied during the digital computer studies. Since the purpose of this research was to determine the effect of PCB reclosing on system stability, many cases were programmed for various switching conditions. The conditions that produced results of interest are included in the descriptions that follow with reference to the accompanying illustration. Analysis of Case1^ Case 1 was chosen to illustrate the effects of reclosing the Bowen-Sequoyah 50 0-KV line into a fault that remained on the system just long enough to allow the system to remain stable after the fault was cleared. The swing curve for this case is illustrated in Figure 3 as Curve 1. In this case the initial fault was cleared in primary clearing time, but the second fault placed on the system after reclosing took place was cleared in a breaker failure clearing time of 11 cycles. System stability is evident from the computer results at the end of one second. The results show that the relative rotor speed is approaching zero and the accelerating power is decreasing.

28 Case 1, Curve 1: Three phase fault near Bowen on Bowen- Sequoyah line. Fault cleared in three cycles. Reclose into fault at 28 cycles. Clear fault in 11 cycles. Calculation by computer. Case 9, Curve 9: Three phase fault near Bowen on Bowen- Sequoyah line. Fault cleared in three cycles. Reclose into fault at 2 8 cycles. Clear fault in 11 cycles. Manual point-by-point calculation. 160 h en Q) o u <D G <o I <u rh CP U O -P h 8o r 40 h o Time-t-Seconds Figure 3. Swing Curves of Cases 1 and 9 00

29 19 Analysis of Case 2_ Case 2 was chosen to illustrate the effects of reclosing the Bowen-Sequoyah 500-KV line into a fault that remained on the system just long enough to produce instability. The swing curve for this case is illustrated in Figure 4, Curve 2. In this case the initial fault was cleared in primary clearing time, but the second fault placed on the system after reclosing took place was cleared in a breaker failure clearing time of 12 cycles. System instability is evident since the computer results at the end of one second show a relative rotor position in excess of 180 degrees, an increasing accelerating power, and am increasing rotor speed. The one cycle variation in breaker failure clearing time can occur in practice due to variations in operating times of relays in the control circuits. Analysis of Case3^ The swing curve resulting from a fault being placed on the Bowen-Norcross 500-KV line near Norcross is shown in Figure 5 as Curve 3. This is Case 3 in which the initial fault was cleared in primary relaying time. Analysis of Case Case 4 is plotted in Figure 5. In this case the initial fault was cleared in three cycles; however, the line was reclosed after 2 8 cycles placing the fault back on the system. The Plant Bowen breaker tripped in three cycles but

30 Case 2, Curve 2: Three phase fault near Bowen on Bowen-Sequoyah line. Fault cleared in three cycles. Reclose into fault at 2 8 cycles. Clear fault in 12 cycles. Calculation by computer. 200 h 10 en a) (U U tn (U Q l <o i <D -H tp U O 4-> s 160 h 120 h 80I- 40 h Case 10, Curve 10: Three phase fault near Bowen on Bowen-Sequoyah line. Fault cleared in three cycles. Reclose into fault at 28 cycles Clear fault in 12 cycles. Point-by-point calculation Time-t-Seconds Figure 4. Swing Curves of Cases 2 and ro o

31 Case 3, Curve 3: Three phase fault near Norcross on Bowen-Norcross line. Fault cleared in three cycles. No reclosing. Calculation by computer. Case 4, Curve 4: Three phase fault near Bowen on Bowen-Norcross line. Fault cleared in three cycles. Reclose into fault at 28 cycles. Bowen tripped in three cycles. Calculation by computer. w Q) 80 U CP <D Q <o 1.H t^ 40 u 0 4J 0 « Time-t-Seconds Figure 5. Swing Curves of Cases 3 and 4

32 22 the Norcross breaker remained closed for 30 cycles due to failure of the primary protective relays at Norcross. If the fault is removed at this time, the system will remain stable. Stable operation was indicated by a decreasing accelerating power and a decreasing relative rotor angle in the computer results. Analysis of Cases _5 and 6_ Case 5 was used to investigate the effect of a remote breaker reclosing into a fault and failing to trip. The swing curve in Figure 6, Curve 5, resulted from a fault near Norcross which was cleared in three cycles by the breakers at. the Bowen and Norcross terminals. The breaker at Norcross reclosed after 2 8 cycles placing the fault on the system. The breaker at Bowen remained open. This case is stable provided the fault is removed after 30 cycles since the accelerating power and relative rotor angle is decreasing at this point. This case is plotted in the same figure with Case 6 for comparison. Case 6 resulted from reclosing Bowen-Sequoyah after 28 cycles to an unfaulted line. Analysis of Cases 7_ and8_ Cases 7 and 8 are shown in Figure 7. The Case 7 swing curve resulted from a fault near Bowen that was cleared from the system in three cycles. Reclosing into the fault occurred at 2 8 cycles after which the fault was cleared in 11

33 23 Case 5, Curve 5: Three phase fault near Norcross on Bowen-Norcross line. Fault cleared in three cycles. Norcross terminal reclosed into fault at 28 cycles. Fault remained 30 cycles. Calculation by computer Case 6, Curve 6: Three phase fault near Bowen on Bowen-Sequoyah line. Fault cleared in three cycles. Reclose unfaulted line at 28 cycles. Calculation by computer. w <u <D u 0) a i <o I <U rh c 0* < u o -p o « Time-t-Seconds Figure 6. Swing Curves of Cases 5 and 6

34 24 Case 7, Curve 7: Three phase fault near Bowen on Bowen-Sequoyah line. Reclose into fault at 28 cycles. Clear fault in 11 cycles. Reclose in 6 cycles. Calculation by computer. Case 8, Curve 8: Three phase fault near Bowen on Bowen-Sequoyah line. Trip Bowen terminal in three cycles. Trip Sequoyah terminal in 28 cycles. Reclose at 53 cycles into fault,. Fault cleared in nine cycles. Calculation by computer Time-t-Seconds Figure 7. Swing Curves of Cases 7 and 8

35 25 cycles. After six cycles, at 45 cycles, the line was reclosed into the fault. Even though impractical, this shows the effect of six cycle reclosing during a power swing. The resulting swing was large but stability was maintained. In Case 8 the Bowen terminal tripped for the initial fault in three cycles, but the Sequoyah terminal took 28 cycles to trip. Reclosing of the line occurred at 53 cycles into the fault, which was then cleared at 62 cycles. Cases 7 and 8 involved multiple reclosing and produced the largest rotor swings of the cases studied. Reclosing was not found to prevent system instability in any of the cases.

36 26 CHAPTER IV ANALYSIS OF THE REDUCED SYSTEM Approach and Assumptions Two methods of approach to the stability problem are presented in this chapter. Both methods require assumptions that simplify the problem to make it possible to solve without the use of a computer. The first method is referred to as the point-by-point or step-by-step solution. The pointby-point method was used in Cases 9 and 10. The second method involves the use of a Liapunov function. The Liapunov method was used in Cases 11 and 12. Values obtained for relative rotor displacement and speed were plotted to illustrate the comparison of the two methods. Cases 9, 10, 11 and 12 are covered in this chapter. The assumptions made were as follows: (a) a synchronous machine may be represented by a constant voltage back of the machine transient reactance; (b) flux linkages in the rotor circuit of a synchronous machine are constant; (c) torque input into the synchronous machine is constant; (d) angular momentum of the machine is constant; (e) the resistance and capacitive reactance of lines and transformers are neglected; (f) the resistance of machines is neglected; (g) all damping torques are neglected.

37 27 A partial 500-KV one-line diagram is shown in Figure 2. The double lines are 500-KV buses. The "G" at Plant Bowen represents the machine equivalent of the four steam generators connected to the bus. The buses are shown with interconnecting lines and equivalent sources from the interconnected network. were tabulated in the appendix. The line and generator parameters The system can be reduced to an equivalent machine connected to an infinite bus as shown in Figure 8. Since PCB 3 and PCB 4 have to open to clear the fault marked x, line Number 2 represents the impedance of the system with the faulted line removed. The network was reduced by making all of the possible series and parallel combinations of the line reactances surrounding the bus or buses to be retained. The remaining buses were eliminated by star-mesh and delta-wye conversions [8]. The equivalent impedances are shown in Figure 8. The four machines at Plant Bowen swing together during a system disturbance; therefore, the inertias of the machines should be added in deriving the equivalent machine (8) Ml = 180*f = x 10 ~ 3 (D Mi = 3^7-2.1 X 10 3 (2) M 3 = M = X 10" 3 (3) M = jmj = X 10" 3 F-u. power sec. 2 (4) e< 3 electrical degrees

38 28 Plant Bowen o A 1 HD L_]-X- Line 2 iy- B Infinite Bus Line 1 ^ 3 phase fault EHV Power Circuit Breaker o Transmitted Power = a & sin /ga - x-n x e q u-c* *-a Where x EA EI is the equivalent system reactance. P mabv Prefault: C. = 5^Ja = = max i Xl ou - /0 P- u - P max D» rin 9 Fault: C * = - ^ - OS554 = 17 ' 6 P ' U - 2 Pmax Postfault: C 3 = ^A_l = = 46>0Q p ^ Figure 8. Equivalent System

39 29 The solution of the classical swing equation was performed by successively calculating the changes in accelerating power (P ) and machine rotor angle (<5) over a successive second intervals. The Swing Equation: M -4 =: P * = p n " P m sin <5 = P. - P (5) 3t 2 a i m I u Where, P. = Combined shaft power input to the four 1 Bowen units P = Ci, prefault; C 2, during fault; C 3 m postfault P = Electrical power output Since, 51 = OJ = u 0 + 2at (6) u dt M Where, w = Angular rotor speed above synchronous speed Then, 6 = <5 0 + w 0 t + ^ - (7) u =u +^P,, (8) n n-i M a(n-i) «n " S n +1 + At«n _ l + - ^ P a(a. l) (9) A5 n = 5 n " «n-i = **» -! + If 1 *a(n-i) <10) (At) 2 = (0.017) * - = ~ 2 (11) M X 10-3 K X 10 U1) - These equations can be used to derive the following equations that were used to calculate the machine angle for each time interval.

40 30 C sin 6 = F (12) n-1 un P - P = P (13) m un an KP = A<5 (14) an n A<5 + 5 =5 (15) n n- I n a) - ^ (16) n At Analysis of Cases 9_ and 10 The solution of each interval is tabulated in Table 6 for switching conditions that produced stable operation. For Case 9 a fault was placed on the Bowen-Sequoyah line for three cycles and then removed. Since the system impedance changes at the switching point, two values of system impedance were inserted in column C at the switching points. The accelerating powei: resulting from each impedance was calculated and averaged to provide a smooth transition between states. The fault was again placed on the system after 28 cycles. In other words, PCB 3 and PCB 4 reclosed in 28 cycles The fault was cleared after 11 cycles and the resulting calculations were listed in Table 6. For Case 10, an unstable swing was produced by leaving the fault connected for one additional cycle. These values are listed in Table 7 and indicate that the critical switching time for a three phase fault on the Sequoyah 500-KV line is 11 cycles. Power-angle curves are shown in Figure 9. The power

41 Case 9, Curve 9: Three phase fault near Bowen on Bowen-Sequoyah line. Fault cleared in three cycles. Reclose into fault at 28 cycles. Clear fault in 11 cycles. Manual point-by-point calculation. Case 10, Curve 10: Three phase fault near Bowen on Bowen-Sequoyah line. Fault cleared in three cycles. Reclose into fault in 28 cycles. Clear fault in 12 cycles. Point-by-point calculation. «! Rotor Angle-6-Degrees Figure 9. Power-Angle Curves of Cases 9 and 10 CJ

42 32 input to the machine was plotted as a straight line. Three maximum electriccil power curves are shown representing the three system reactances resulting from the switching operations. The Case 9 stable trajectory is indicated by single arrows progressing from (<5 ;l) to (<5 2 ). The unstable trajectory (Case 10) is indicated by double arrows. The swing curves are shown in Figures 3 and 4 for the two cases. The computer solutions are also shown plotted on these curves for comparison of the results. Analysis of Cases 11 and 12 The method of Liapunov was applied to the problem to determine if this method is comparable with the point-bypoint method. The Liapunov function developed by Gless (9) was used. The Liapunov theorum states that the equilibrium of a system is stable if there exists a function of time and motion such that its total derivative with respect to time along the trajectories of the system is not positive. The function used is as follows;* V = T + 5!* ( _P i + P m sin (X " V) Where 6 = x + 6 d d(x + 62) _ dx _ 'dt " dt ~ dt " w The time derivative of equation (17) is dx < 17 > 3I = V=.f + i (-P i + P m sin <x )) H (13)

43 33 Since M 7- &0L = P. - P_ sin (x + <5 2 ) dt " i " m v = its ^pi - p m sin < x + 5 a>) + i (- P. + P sin (x + 6 )) f*- (19) 2 M 1 m ' dt Or V = 0 If the integration in equation (17) is performed, the result is 2 1 V = S- + ~ f- P.x - P cos (x + <SJ + P cos 5 2 ) (20) Substituting u> = x = (20) becomes (ffj 2 - I t p i (5 " V + P m (cos 6 - cos S 2 ] 1 + 2V (21) After adding and subtracting and rearranging P.5 + P cos 5 n 1 0 m 0 (H) 2 " I ( p i <«" V +P m < cos * * cos V + H ( P i (6 Ci " 6 2> + p m (cos 6 o " cos 5 2 } ) < 22 > If V = i fp. (6, 2-6 J + P (cos 26, - cos 5 )) M ^ 1 m 0 ; Then w 2 = 1 (p ± (6-6 0 ) + P m (cos 6 - cos <5 0 )) (23)

44 34 The maximum trajectory for stable operation was plotted by solving this equation for successive values of the machine angle (Table 8). The maximum value of the machine angle shown in Figure 11 is known as the saddle point. The w - 6 plot of the solution by the point-by-point method is illustrated in Figure 10 for comparison. Case 12 in Figure 11 illustrates an unstable trajectory comparable with Case 10.

45 Case 9, Curve 9: Three phase fault near Bowen on Bowen-Sequoyah line. Fault cleared in three cycles. Reclose into fault at 28 cycles. Clear fault in 11 cycles. Manual point-by-point calculation. Case 10, Curve 10: Three phase fault near Bowen on Bowen-Sequoyah line. Fault cleared in three cycles. Reclose into fault in 28 cycles. Clear fault in 12 cycles. Pointby-point calculation TJ c o <u en \ to Q) Q) U & Q) Q I 3 I Tf 0) 0) CU cn o -P o PC Rotor Angle-6-Degrees 160 Figure 10. Rotor Speed-Rotor Angle Curves of Cases 9 and

46 36 CHAPTER V EVALUATION OF REDUCED SYSTEM ANALYSIS AND LIAPUNOV METHOD Purpos e The purpose of this evaluation was to make comparisons of the various methods used to study the effects of power circuit breaker reclosing on the stability of the power system. The computer analysis was compared with the pointby-point analysis to determine the effects of making the assumptions that make manual computations practical. The reduced system analysis was then compared with the computation of a Liapunov function that made possible a prediction of the stability boundaries of the system by plotting the separatrix curve of Figure 11. The comparisons were used to make an evaluation of the validity of the reduced system analysis and the Liapunov method. Comparison of the Computer Analysis with the Point-By-Point Analysis The curves in Figure 3 illustrate the solution of the simulated system swing curve by a digital computer (Case 1) and the point-by-point calculation (Case 9). Reclosing took place at 28 cycles into a fault that was cleared in 11 cycles. Case 1 resulted in a larger swing of the Bowen generators.

47 37 However, stability was maintained as evidenced by the relative rotor speed approaching zero and the accelerating power decreasing in Table 4. The curves in Figure 4 illustrate the solution of the simulated system swing curve by a digital computer (Case 2) and the point-by-point calculation (Case 10). Reclosing took place at 28 cycles into a fault that was cleared in 12 cycles. The curves from either solution indicate generator instability at Plant Bowen. The slope of Case 2 is greater than the slope of Case 10 after one second, but the similarity of the solutions is evident. The critical clearing time of 11 cycles was obtained in each study. Therefore, the assumptions made in the reduced analysis did not effect the critical clearing time. Comparison of the Point-By-Point Analysis with the Liapunov Method The point-by-point solution was compared to the Liapunov solution by the use of Figures 10 and 11. The unstable trajectory, (Case 10) beginning at (6 0 ) in Figure 10, crosses the separatrix at 88 degrees rotor angle and 250 degrees per second rotor speed. In Case 12 of Figure 11 the unstable trajectory crosses the separatrix at 94 degrees rotor angle and 241 degrees per second rotor speed. This represents a difference of six percent in rotor angle and four percent in rotor speed. For all practical purposes

48 38 Case 11, Curve 11: Maximum stable trajectory, Bowen Generators, fault on Bowen-Sequoyah 5Q0-KV line. Calculated by Liapunov method. (<5 0 = radian) Case 12, Curve 12: Three phase fault near Bowen on Bowen-Sequoyah line. Reclose at 28 cycles into a 12 cycle fault. Unstable trajectory calculated by Liapunov method. (55» 0.43 radian) 6.0 h c o CD cn \ w <d H td «i 3 I d <u o en u o -P s 4.0 L 2.0 h -2.0 h -4.0 U -6.0 h Rotor Angle-<5-Radians Figure 11. Liapunov Method Cases 11 and 12

49 39 the results of Figures 10 and 11 are identical. Evaluation of the Comparisons In the comparison of the computer analysis with the point-by-point analysis the critical switching time to clear a fault before the units became unstable was found to be the same. Since the point-by-point analysis did not include the influence of machines remote from Plant Bowen, the resulting power swings in the digital computer analysis were greater than those calculated by the point-by-point method. Therefore, the results obtained by the point-by-point analysis are conservative. The Liapunov method was compared to the point-by-point solution. The results of the two methods were almost identical. The ease of solution of the Liapunov function used makes it the most desirable method used in the study. The ease of varying initial conditions in the Liapunov method makes it more useful.

50 40 CHAPTER VI CONCLUSION Effect of Reclosing on Stability System stability was not preserved because of reclosing a line in any of the cases studied. Reclosing did cause system instability when a faulted line was reclosed and left on the system in excess of 11 cycles as shown in Figure 4. The conclusion drawn from the system studied is that high speed reclosing cannot be used to aid generator stability. Basis for Conclusion When reclosing was used, the rotor displacement angle w.r.t. the infinite bus increased rapidly in cases where the fault was still present. The swing curve shown as Curve 6 in Figure 6 did not change appreciably when the unfaulted line was reclosed. The only way to keep the system stable after a three phase fault is placed near the generators is to remove the fault before the generator rotors accumulate more potential energy than the system is able to accommodate. In Figures 10 and 11 the separatrix curve gives a graphical illustration of the trajectory of the generator rotor speed following a three phase fault. Starting at (6 ) in Figure 11 the trajectory will be contained within the separatrix if the fault is cleared in time. If not, the

51 41 system becomes unstable. The OJ-6 curves gave better insight to the operation of the system than the swing curves plotted by a digital computer. In Figure 11 an infinite number of initial rotor angles and reclosing times can be plotted within the separatrix.

52 42 CHAPTER VII RECOMMENDATIONS High speed reclosing of EHV breakers near generating plants should not be used to improve system stability. The possibility of causing fatigue to the generator shaft system is reason enough to make this choice; furthermore, the possibility of protective relay or breaker malfunction causing delayed fault clearing and instability is also present. Further research is necessary to determine a safe system impedance between the generators and the fault to insure that the generator shaft would not be damaged after a reclosure or switching operation. Also, a simplified method for calculating system stability is needed to reduce computer time. Since the separatrix curve that was calculated from the Liapunov function used in this thesis is a conservative estimate of system, stability, this method could be used in an on-line computer to determine stability limits under actual system operating conditions. The weak points could then be further examined by a detailed transient stability analysis. Rotor swings resulting from actual system disturbances could be plotted to determine the accuracy of the results.

53 APPENDIX 43

54 44 Table 1. Load Flow Bus Bowen Bus Voltage Mag. p.u. Angle degrees Norcross Klondike Union City Wansley Sequoyah To Norcross To Union City To Villa Rica To Gen. No. 1 To Gen. No. 2 To Gen. No. 3 To Gen. No. 4 To Equivalent To Sequoyah To Bowen To Klondike To Equivalent To Norcross To Union City To Equivalent To Bowen To Union City To Wansley To Equivalent To Villa Rica To Equivalent To Gen. No. 1 To Bowen To Equivalent To Gen. No. 1 MW Power Flow MVAR

55 45 Table 2. System Parameters From Bus To Bus Reactance Charging Percent MVA Bowen Unit 1 Bowen 500-KV Bowen Unit 2 Bowen 500-KV Bowen Unit 3 Bowen 500-KV Bowen Unit 4 Bowen 500-KV Bowen 500-KV Norcross 500-KV Bowen 500-KV Sequoyah 500-KV Bowen 500-KV Union City 500-KV Bowen 500-KV Villa Rica 500-KV Klondike 500-KV Norcross 500-KV Klondike 500-KV Union City 500-KV Union City 500-KV Villa Rica 500-KV Villa Rica 500-KV Wansley 500-KV

56 Table 3. Plant Bowen Generator Parameters Unit 1 Unit 2 Unit 3 Manufacturer Westinghouse General General Electric Electric Rated Output (KW) 805, , ,000 Rated Output (KVA) 948, ,000 1,120,000 WR 2 738, , ,280 Rated Voltage 25,000 25,000 18,000 Rated Current (Amperes) 21,893 21,431 35,924 XI (p.u.)* x (p.u.)* X^ (p.u.)* H (MWS/MVA) * Each generator is a 3-phase, 60 Hertz, 3600 RPM unit. *On a 100 MVA base. Unit 4 General Electric 952,000 1,120, ,000 35, >» Ov

57 47 Table 4 Computer Computation of Case 1 Time P 6 0) Sec. 12 degrees degrees/sec p.u

58 Table 4. Continued Time P u <5 Sec. p.u. degrees

59 49 Table 5. Computer Computation of Case 2 Time P u 5 OJ Sec. p.u. degrees degrees/sec

60 50 Table 5. Continued Time p u 5 0) Sec. p.u. degrees degrees/sec ,

POWER SYSTEM STABILITY

POWER SYSTEM STABILITY LESSON SUMMARY-1:- POWER SYSTEM STABILITY 1. Introduction 2. Classification of Power System Stability 3. Dynamic Equation of Synchronous Machine Power system stability involves the study of the dynamics

More information

Power System Stability and Control. Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India

Power System Stability and Control. Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India Power System Stability and Control Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India Contents Chapter 1 Introduction to Power System Stability

More information

POWER SYSTEM STABILITY AND CONTROL

POWER SYSTEM STABILITY AND CONTROL POWER SYSTEM STABILITY AND CONTROL P. KUNDUR Vice-President, Power Engineering Powertech Labs Inc., Surrey, British Columbia Formerly Manager Analytical Methods and Specialized Studies Department Power

More information

ECE 585 Power System Stability

ECE 585 Power System Stability Homework 1, Due on January 29 ECE 585 Power System Stability Consider the power system below. The network frequency is 60 Hz. At the pre-fault steady state (a) the power generated by the machine is 400

More information

KINGS COLLEGE OF ENGINEERING Punalkulam

KINGS COLLEGE OF ENGINEERING Punalkulam KINGS COLLEGE OF ENGINEERING Punalkulam 613 303 DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING POWER SYSTEM ANALYSIS QUESTION BANK UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A (TWO MARK

More information

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester Electrical and Electronics Engineering EE 1352 Power System Analysis (Regulation 2008) Time: Three hours Answer all questions Part A (10

More information

Final Exam, Second Semester: 2015/2016 Electrical Engineering Department

Final Exam, Second Semester: 2015/2016 Electrical Engineering Department Philadelphia University Faculty of Engineering Student Name Student No: Serial No Final Exam, Second Semester: 2015/2016 Electrical Engineering Department Course Title: Power II Date: 21 st June 2016 Course

More information

ANALYSIS OF SUBSYNCHRONOUS RESONANCE EFFECT IN SERIES COMPENSATED LINE WITH BOOSTER TRANSFORMER

ANALYSIS OF SUBSYNCHRONOUS RESONANCE EFFECT IN SERIES COMPENSATED LINE WITH BOOSTER TRANSFORMER ANALYSIS OF SUBSYNCHRONOUS RESONANCE EFFECT IN SERIES COMPENSATED LINE WITH BOOSTER TRANSFORMER G.V.RAJASEKHAR, 2 GVSSNS SARMA,2 Department of Electrical Engineering, Aurora Engineering College, Hyderabad,

More information

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II : 7 - Transient Stability

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II : 7 - Transient Stability ECE 4/5 Power System Operations & Planning/Power Systems Analysis II : 7 - Transient Stability Spring 014 Instructor: Kai Sun 1 Transient Stability The ability of the power system to maintain synchronism

More information

Power System Stability GENERATOR CONTROL AND PROTECTION

Power System Stability GENERATOR CONTROL AND PROTECTION Power System Stability Outline Basis for Steady-State Stability Transient Stability Effect of Excitation System on Stability Small Signal Stability Power System Stabilizers Speed Based Integral of Accelerating

More information

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A 1. What are the advantages of an inter connected system? The advantages of an inter-connected system are

More information

QUESTION BANK ENGINEERS ACADEMY. Power Systems Power System Stability 1

QUESTION BANK ENGINEERS ACADEMY. Power Systems Power System Stability 1 ower ystems ower ystem tability QUETION BANK. A cylindrical rotor generator delivers 0.5 pu power in the steady-state to an infinite bus through a transmission line of reactance 0.5 pu. The generator no-load

More information

7. Transient stability

7. Transient stability 1 7. Transient stability In AC power system, each generator is to keep phase relationship according to the relevant power flow, i.e. for a certain reactance X, the both terminal voltages V1and V2, and

More information

SCHOOL OF ELECTRICAL, MECHANICAL AND MECHATRONIC SYSTEMS. Transient Stability LECTURE NOTES SPRING SEMESTER, 2008

SCHOOL OF ELECTRICAL, MECHANICAL AND MECHATRONIC SYSTEMS. Transient Stability LECTURE NOTES SPRING SEMESTER, 2008 SCHOOL OF ELECTRICAL, MECHANICAL AND MECHATRONIC SYSTEMS LECTURE NOTES Transient Stability SPRING SEMESTER, 008 October 7, 008 Transient Stability Transient stability refers to the ability of a synchronous

More information

Chapter 9: Transient Stability

Chapter 9: Transient Stability Chapter 9: Transient Stability 9.1 Introduction The first electric power system was a dc system built by Edison in 1882. The subsequent power systems that were constructed in the late 19 th century were

More information

Module 3 : Sequence Components and Fault Analysis

Module 3 : Sequence Components and Fault Analysis Module 3 : Sequence Components and Fault Analysis Lecture 12 : Sequence Modeling of Power Apparatus Objectives In this lecture we will discuss Per unit calculation and its advantages. Modeling aspects

More information

LESSON 20 ALTERNATOR OPERATION OF SYNCHRONOUS MACHINES

LESSON 20 ALTERNATOR OPERATION OF SYNCHRONOUS MACHINES ET 332b Ac Motors, Generators and Power Systems LESSON 20 ALTERNATOR OPERATION OF SYNCHRONOUS MACHINES 1 LEARNING OBJECTIVES After this presentation you will be able to: Interpret alternator phasor diagrams

More information

Comparative Study of Synchronous Machine, Model 1.0 and Model 1.1 in Transient Stability Studies with and without PSS

Comparative Study of Synchronous Machine, Model 1.0 and Model 1.1 in Transient Stability Studies with and without PSS Comparative Study of Synchronous Machine, Model 1.0 and Model 1.1 in Transient Stability Studies with and without PSS Abhijit N Morab, Abhishek P Jinde, Jayakrishna Narra, Omkar Kokane Guide: Kiran R Patil

More information

1. Introduction. Keywords Transient Stability Analysis, Power System, Swing Equation, Three-Phase Fault, Fault Clearing Time

1. Introduction. Keywords Transient Stability Analysis, Power System, Swing Equation, Three-Phase Fault, Fault Clearing Time Energy and Power 17, 7(1): -36 DOI: 1.593/j.ep.1771.3 Numerical Simulations for Transient Stability Analysis of Two-Machine Power System Considering Three-Phase Fault under Different Fault Clearing Times

More information

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous)

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad - 500 043 ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK Course Name : Computer Methods in Power Systems Course Code : A60222

More information

Examples of Applications of Potential Functions in Problem Solving (Web Appendix to the Paper)

Examples of Applications of Potential Functions in Problem Solving (Web Appendix to the Paper) Examples of Applications of otential Functions in roblem Solving (Web Appendix to the aper) Ali Mehrizi-Sani and Reza Iravani May 5, 2010 1 Introduction otential functions may be exploited to formulate

More information

A. P. Sakis Meliopoulos and George J. Cokkinides Power System Relaying, Theory and Applications. Chapter 8 2 Generator Protection 2

A. P. Sakis Meliopoulos and George J. Cokkinides Power System Relaying, Theory and Applications. Chapter 8 2 Generator Protection 2 DRAFT and INCOMPLETE Table of Contents from A. P. Sakis Meliopoulos and George J. Cokkinides Power System Relaying, Theory and Applications Chapter 8 Generator Protection 8. Introduction 8. Generator Protection

More information

EE 451 Power System Stability

EE 451 Power System Stability EE 451 Power System Stability Power system operates in synchronous mode Power system is subjected to a wide range of disturbances (small and large) - Loads and generation changes - Network changes - Faults

More information

ECE 325 Electric Energy System Components 7- Synchronous Machines. Instructor: Kai Sun Fall 2015

ECE 325 Electric Energy System Components 7- Synchronous Machines. Instructor: Kai Sun Fall 2015 ECE 325 Electric Energy System Components 7- Synchronous Machines Instructor: Kai Sun Fall 2015 1 Content (Materials are from Chapters 16-17) Synchronous Generators Synchronous Motors 2 Synchronous Generators

More information

Generators. What its all about

Generators. What its all about Generators What its all about How do we make a generator? Synchronous Operation Rotor Magnetic Field Stator Magnetic Field Forces and Magnetic Fields Force Between Fields Motoring Generators & motors are

More information

DAMPING OF SUBSYNCHRONOUS MODES OF OSCILLATIONS

DAMPING OF SUBSYNCHRONOUS MODES OF OSCILLATIONS Journal of Engineering Science and Technology Vol. 1, No. 1 (26) 76-88 School of Engineering, Taylor s College DAMPING OF SUBSYNCHRONOUS MODES OF OSCILLATIONS JAGADEESH PASUPULETI School of Engineering,

More information

Mitigating Subsynchronous resonance torques using dynamic braking resistor S. Helmy and Amged S. El-Wakeel M. Abdel Rahman and M. A. L.

Mitigating Subsynchronous resonance torques using dynamic braking resistor S. Helmy and Amged S. El-Wakeel M. Abdel Rahman and M. A. L. Proceedings of the 14 th International Middle East Power Systems Conference (MEPCON 1), Cairo University, Egypt, December 19-21, 21, Paper ID 192. Mitigating Subsynchronous resonance torques using dynamic

More information

Chapter 3 AUTOMATIC VOLTAGE CONTROL

Chapter 3 AUTOMATIC VOLTAGE CONTROL Chapter 3 AUTOMATIC VOLTAGE CONTROL . INTRODUCTION TO EXCITATION SYSTEM The basic function of an excitation system is to provide direct current to the field winding of the synchronous generator. The excitation

More information

The Effects of Machine Components on Bifurcation and Chaos as Applied to Multimachine System

The Effects of Machine Components on Bifurcation and Chaos as Applied to Multimachine System 1 The Effects of Machine Components on Bifurcation and Chaos as Applied to Multimachine System M. M. Alomari and B. S. Rodanski University of Technology, Sydney (UTS) P.O. Box 123, Broadway NSW 2007, Australia

More information

Predicting, controlling and damping inter-area mode oscillations in Power Systems including Wind Parks

Predicting, controlling and damping inter-area mode oscillations in Power Systems including Wind Parks 3rd IASME/WSEAS Int. Conf. on Energy & Environment, University of Cambridge, UK, February 3-5, 008 Predicting, controlling and damping inter-area mode oscillations in Power Systems including Wind Parks

More information

Frequency and Damping Characteristics of Generators in Power Systems

Frequency and Damping Characteristics of Generators in Power Systems Frequency and Damping Characteristics of Generators in Power Systems Xiaolan Zou Thesis submitted to the Faculty of the Virginia Polytechnic Institute and State University in partial fulfillment of the

More information

GENERATOR INTERCONNECTION APPLICATION

GENERATOR INTERCONNECTION APPLICATION GENERATOR INTERCONNECTION APPLICATION FOR BUY-ALL/SELL-ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 20 KW BUT LESS THAN OR EQUAL TO 1 MW Electric Utility Contact Information Great Lakes Energy

More information

FOR REDUCE SUB-SYNCHRONOUS RESONANCE TORQUE BY USING TCSC

FOR REDUCE SUB-SYNCHRONOUS RESONANCE TORQUE BY USING TCSC FOR REDUCE SUB-SYNCHRONOUS RESONANCE TORQUE BY USING TCSC Shrikant patel 1, N.K.Singh 2, Tushar kumar 3 Department of Electrical Engineering, Scope College of Engineering Bhopal,(M.P.) Emil:Shrikantcseb@gmail.com

More information

Transient stability improvement by using PSS and increasing inertia of synchronous machine

Transient stability improvement by using PSS and increasing inertia of synchronous machine American Journal of Electrical Power and Energy Systems 2014; 3(2): 45-49 Published online April 20, 2014 (http://www.sciencepublishinggroup.com/j/epes) doi:10.11648/j.epes.20140302.15 Transient stability

More information

Reliability of Bulk Power Systems (cont d)

Reliability of Bulk Power Systems (cont d) Reliability of Bulk Power Systems (cont d) Important requirements of a reliable electric power service Voltage and frequency must be held within close tolerances Synchronous generators must be kept running

More information

Introduction to Synchronous. Machines. Kevin Gaughan

Introduction to Synchronous. Machines. Kevin Gaughan Introduction to Synchronous Machines Kevin Gaughan The Synchronous Machine An AC machine (generator or motor) with a stator winding (usually 3 phase) generating a rotating magnetic field and a rotor carrying

More information

EVALUATION OF THE IMPACT OF POWER SECTOR REFORM ON THE NIGERIA POWER SYSTEM TRANSIENT STABILITY

EVALUATION OF THE IMPACT OF POWER SECTOR REFORM ON THE NIGERIA POWER SYSTEM TRANSIENT STABILITY EVALUATION OF THE IMPACT OF POWER SECTOR REFORM ON THE NIGERIA POWER SYSTEM TRANSIENT STABILITY F. I. Izuegbunam * Department of Electrical & Electronic Engineering, Federal University of Technology, Imo

More information

EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION

EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION PART: A 1. Define per unit value of an electrical quantity. Write equation for base impedance with respect to 3-phase system. 2. What is bus admittance

More information

CHAPTER 2 OVERVOLTAGE DUE TO SELF-EXCITATION AND INRUSH CURRENT DUE TO CAPACITOR SWITCHING

CHAPTER 2 OVERVOLTAGE DUE TO SELF-EXCITATION AND INRUSH CURRENT DUE TO CAPACITOR SWITCHING 20 CHAPTER 2 OVERVOLTAGE DUE TO SELF-EXCITATION AND INRUSH CURRENT DUE TO CAPACITOR SWITCHING 2.1 INTRODUCTION It is becoming more common to find use of shunt capacitors for the application of powerfactor

More information

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION EE 6501 POWER SYSTEMS UNIT I INTRODUCTION PART A (2 MARKS) 1. What is single line diagram? A Single line diagram is diagrammatic representation of power system in which the components are represented by

More information

DYNAMIC RESPONSE OF A GROUP OF SYNCHRONOUS GENERATORS FOLLOWING DISTURBANCES IN DISTRIBUTION GRID

DYNAMIC RESPONSE OF A GROUP OF SYNCHRONOUS GENERATORS FOLLOWING DISTURBANCES IN DISTRIBUTION GRID Engineering Review Vol. 36 Issue 2 8-86 206. 8 DYNAMIC RESPONSE OF A GROUP OF SYNCHRONOUS GENERATORS FOLLOWING DISTURBANCES IN DISTRIBUTION GRID Samir Avdaković * Alija Jusić 2 BiH Electrical Utility Company

More information

You know for EE 303 that electrical speed for a generator equals the mechanical speed times the number of poles, per eq. (1).

You know for EE 303 that electrical speed for a generator equals the mechanical speed times the number of poles, per eq. (1). Stability 1 1. Introduction We now begin Chapter 14.1 in your text. Our previous work in this course has focused on analysis of currents during faulted conditions in order to design protective systems

More information

Transient Stability Assessment and Enhancement Using TCSC with Fuzzy Logic Controller

Transient Stability Assessment and Enhancement Using TCSC with Fuzzy Logic Controller Transient Stability Assessment and Enhancement Using TCSC with Fuzzy Logic Controller Ali Qasim Hussein Department of Electrical Engineering, Acharya NAgarjuna University, Nagarjuna Nagar,Guntur,522510,Ap,

More information

Dynamic simulation of a five-bus system

Dynamic simulation of a five-bus system ELEC0047 - Power system dynamics, control and stability Dynamic simulation of a five-bus system Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct November 2017 1 / 16 System modelling

More information

Minimization of Shaft Torsional Oscillations by Fuzzy Controlled Braking Resistor Considering Communication Delay

Minimization of Shaft Torsional Oscillations by Fuzzy Controlled Braking Resistor Considering Communication Delay Proceedings of the 7th WSEAS International Conference on Power Systems, Beijing, China, September 15-17, 2007 174 Minimization of Shaft Torsional Oscillations by Fuzzy Controlled Braking Resistor Considering

More information

Computer Applications in Electrical Engineering

Computer Applications in Electrical Engineering Computer Applications in Electrical Engineering Influence of disturbances in power network on torsional torques in big power turbines-generator shafts Józef Wiśniewski Technical University of Lodz 9-94

More information

Fault Analysis Power System Representation

Fault Analysis Power System Representation .1. Power System Representation Single Line Diagram: Almost all modern power systems are three phase systems with the phases of equal magnitude and equal phase difference (i.e., 10 o ). These three phase

More information

Critical clearing time evaluation of Nigerian 330kV transmission system

Critical clearing time evaluation of Nigerian 330kV transmission system American Journal of Electrical Power and Energy Systems 2013; 2(6): 123-128 Published online October 20, 2013 (http://www.sciencepublishinggroup.com/j/epes) doi: 10.11648/j.epes.20130206.11 Critical clearing

More information

ECEN 667 Power System Stability Lecture 15: PIDs, Governors, Transient Stability Solutions

ECEN 667 Power System Stability Lecture 15: PIDs, Governors, Transient Stability Solutions ECEN 667 Power System Stability Lecture 15: PIDs, Governors, Transient Stability Solutions Prof. Tom Overbye Dept. of Electrical and Computer Engineering Texas A&M University, overbye@tamu.edu 1 Announcements

More information

PARAMETRIC ANALYSIS OF SHAFT TORQUE ESTIMATOR BASED ON OBSERVER

PARAMETRIC ANALYSIS OF SHAFT TORQUE ESTIMATOR BASED ON OBSERVER PARAMETRIC ANALYSIS OF SHAFT TORQUE ESTIMATOR BASED ON OBSERVER Tetsuro Kakinoki, Ryuichi Yokoyama Tokyo Metropolitan University t.kakinoki@h4.dion.ne.jp Goro Fujita Shibaura Institute of Technology Kaoru

More information

THE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session

THE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session Name: Student ID: Signature: THE UNIVERSITY OF NEW SOUTH WALES School of Electrical Engineering & Telecommunications FINALEXAMINATION Session 00 ELEC46 Power System Analysis TIME ALLOWED: 3 hours TOTAL

More information

Transient Stability Analysis of Single Machine Infinite Bus System by Numerical Methods

Transient Stability Analysis of Single Machine Infinite Bus System by Numerical Methods International Journal of Electrical and Electronics Research ISSN 348-6988 (online) Vol., Issue 3, pp: (58-66), Month: July - September 04, Available at: www.researchpublish.com Transient Stability Analysis

More information

INDUCTION MOTOR TORQUE DURING FAST BUS TRANSFERS

INDUCTION MOTOR TORQUE DURING FAST BUS TRANSFERS INDUCTION MOTOR TORQUE DURING FAST BUS TRANSFERS BY JAMES W. KOLODZIEJ THESIS Submitted in partial fulfillment of the requirements for the degree of Master of Science in Electrical and Computer Engineering

More information

11.1 Power System Stability Overview

11.1 Power System Stability Overview 11.1 Power System Stability Overview This introductory section provides a general description of the power system stability phenomena including fundamental concepts, classification, and definition of associated

More information

Transient Stability Assessment of Synchronous Generator in Power System with High-Penetration Photovoltaics (Part 2)

Transient Stability Assessment of Synchronous Generator in Power System with High-Penetration Photovoltaics (Part 2) Journal of Mechanics Engineering and Automation 5 (2015) 401-406 doi: 10.17265/2159-5275/2015.07.003 D DAVID PUBLISHING Transient Stability Assessment of Synchronous Generator in Power System with High-Penetration

More information

Power system stability - computaton of critical clearing time and stability margin index.

Power system stability - computaton of critical clearing time and stability margin index. Lehigh University Lehigh Preserve Theses and Dissertations 1-1-1976 Power system stability - computaton of critical clearing time and stability margin index. James K. Robinson Follow this and additional

More information

Transient Stability Analysis with PowerWorld Simulator

Transient Stability Analysis with PowerWorld Simulator Transient Stability Analysis with PowerWorld Simulator T1: Transient Stability Overview, Models and Relationships 2001 South First Street Champaign, Illinois 61820 +1 (217) 384.6330 support@powerworld.com

More information

Transients on Integrated Power System

Transients on Integrated Power System Chapter 3 Transients on Integrated Power System 3.1 Line Dropping and Load Rejection 3.1.1 Line Dropping In three phase circuit capacitance switching, the determination of the voltage trapped after switching

More information

EE2351 POWER SYSTEM ANALYSIS

EE2351 POWER SYSTEM ANALYSIS EE351 POWER SYSTEM ANALYSIS A.Ahamed Riazudeen EEE DEPARTMENT 1 UNIT I INTRODUCTION Power system network 3 SINGLE LINE DIAGRAM It is a diagrammatic representation of a power system in which the components

More information

The Operation of a Generator on Infinite Busbars

The Operation of a Generator on Infinite Busbars The Operation of a Generator on Infinite Busbars In order to simplify the ideas as much as possible the resistance of the generator will be neglected; in practice this assumption is usually reasonable.

More information

Analysis of factors affecting station capacitor bank switching transients

Analysis of factors affecting station capacitor bank switching transients Scholars' Mine Masters Theses Student Research & Creative Works 1971 Analysis of factors affecting station capacitor bank switching transients M. Davarpanah Follow this and additional works at: http://scholarsmine.mst.edu/masters_theses

More information

Dynamic Behavior of Three phase Inductions Motors as Loads in an Electric Power System with Distributed Generation, a Case of Study.

Dynamic Behavior of Three phase Inductions Motors as Loads in an Electric Power System with Distributed Generation, a Case of Study. Dynamic Behavior of Three phase Inductions Motors as Loads in an Electric Power System with Distributed Generation, a Case of Study. Marcelo Rodrigo García Saquicela, Ernesto Ruppert Filho, José Luis Azcue

More information

A Computer Application for Power System Control Studies

A Computer Application for Power System Control Studies A Computer Application for Power System Control Studies Dinis C. A. Bucho Student nº55262 of Instituto Superior Técnico Technical University of Lisbon Lisbon, Portugal Abstract - This thesis presents studies

More information

Dynamics of the synchronous machine

Dynamics of the synchronous machine ELEC0047 - Power system dynamics, control and stability Dynamics of the synchronous machine Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct October 2018 1 / 38 Time constants and

More information

From now, we ignore the superbar - with variables in per unit. ψ ψ. l ad ad ad ψ. ψ ψ ψ

From now, we ignore the superbar - with variables in per unit. ψ ψ. l ad ad ad ψ. ψ ψ ψ From now, we ignore the superbar - with variables in per unit. ψ 0 L0 i0 ψ L + L L L i d l ad ad ad d ψ F Lad LF MR if = ψ D Lad MR LD id ψ q Ll + Laq L aq i q ψ Q Laq LQ iq 41 Equivalent Circuits for

More information

Research Paper ANALYSIS OF POWER SYSTEM STABILITY FOR MULTIMACHINE SYSTEM D. Sabapathi a and Dr. R. Anita b

Research Paper ANALYSIS OF POWER SYSTEM STABILITY FOR MULTIMACHINE SYSTEM D. Sabapathi a and Dr. R. Anita b Research Paper ANALYSIS OF POWER SYSTEM STABILITY FOR MULTIMACHINE SYSTEM D. Sabapathi a and Dr. R. Anita b Address for Correspondence a Research Scholar, Department of Electrical & Electronics Engineering,

More information

DESIGN OF POWER SYSTEM STABILIZER USING FUZZY BASED SLIDING MODE CONTROL TECHNIQUE

DESIGN OF POWER SYSTEM STABILIZER USING FUZZY BASED SLIDING MODE CONTROL TECHNIQUE DESIGN OF POWER SYSTEM STABILIZER USING FUZZY BASED SLIDING MODE CONTROL TECHNIQUE LATHA.R Department of Instrumentation and Control Systems Engineering, PSG College of Technology, Coimbatore, 641004,

More information

ECEN 667 Power System Stability Lecture 25: FFT, Energy Methods

ECEN 667 Power System Stability Lecture 25: FFT, Energy Methods ECEN 667 Power System Stability Lecture 5: FFT, Energy Methods Prof. Tom Overbye Dept. of Electrical and Computer Engineering Texas A&M University, overbye@tamu.edu 1 Announcements Read Chapter 9 Final

More information

CHAPTER 5 SIMULATION AND TEST SETUP FOR FAULT ANALYSIS

CHAPTER 5 SIMULATION AND TEST SETUP FOR FAULT ANALYSIS 47 CHAPTER 5 SIMULATION AND TEST SETUP FOR FAULT ANALYSIS 5.1 INTRODUCTION This chapter describes the simulation model and experimental set up used for the fault analysis. For the simulation set up, the

More information

1. Explain the various methods of methods of grounding. In power system, grounding or earthing means connecting frame of electrical equipment (non-cur

1. Explain the various methods of methods of grounding. In power system, grounding or earthing means connecting frame of electrical equipment (non-cur 1. Explain the various methods of methods of grounding. In power system, grounding or earthing means connecting frame of electrical equipment (non-current carrying part) or some electrical part of the

More information

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL 1 SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL Power Systems: Generation, Transmission and Distribution Power Systems: Generation, Transmission and Distribution Power Systems:

More information

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur Lecture - 9 Transmission Line Steady State Operation Welcome to lesson 9, in Power

More information

Micro-grid to System Synchronization Based on Pre-Insertion Impedance Method (Version 1.0) By Peter Zhou University of Alberta Jan 30 th, 2015

Micro-grid to System Synchronization Based on Pre-Insertion Impedance Method (Version 1.0) By Peter Zhou University of Alberta Jan 30 th, 2015 Micro-grid to System Synchronization Based on Pre-Insertion Impedance Method (Version 1.0) By Peter Zhou University of Alberta Jan 30 th, 2015 Outline 1. What is Synchronization? 2. Synchronization Concerns?

More information

Enhancement of transient stability analysis of multimachine power system

Enhancement of transient stability analysis of multimachine power system WWJMRD 2016; 2(6): 41-45 www.wwjmrd.com Impact Factor MJIF: 4.25 e-issn: 2454-6615 Oyediran Oyebode Olumide Department of Computer Engineering, Osun State Polytechnic Iree, Osun State, Nigeria Ogunwuyi

More information

Mitigation of Distributed Generation Impact on Protective Devices in a Distribution Network by Superconducting Fault Current Limiter *

Mitigation of Distributed Generation Impact on Protective Devices in a Distribution Network by Superconducting Fault Current Limiter * Energy and Power Engineering, 2013, 5, 258-263 doi:10.4236/epe.2013.54b050 Published Online July 2013 (http://www.scirp.org/journal/epe) Mitigation of Distributed Generation Impact on Protective Devices

More information

A COMPUTER PROGRAM FOR SHORT CIRCUIT ANALYSIS OF ELECTRIC POWER SYSTEMS

A COMPUTER PROGRAM FOR SHORT CIRCUIT ANALYSIS OF ELECTRIC POWER SYSTEMS NIJOTECH VOL. 5 NO. 1 MARCH 1981 EJEBE 46 A COMPUTER PROGRAM FOR SHORT CIRCUIT ANALYSIS OF ELECTRIC POWER SYSTEMS BY G.C. EJEBE DEPARTMENT OF ELECTRICAL/ELECTRONIC ENGINEERING UNIVERSITY OF NIGERIA, NSUKKA.

More information

CHAPTER 2 DYNAMIC STABILITY MODEL OF THE POWER SYSTEM

CHAPTER 2 DYNAMIC STABILITY MODEL OF THE POWER SYSTEM 20 CHAPTER 2 DYNAMIC STABILITY MODEL OF THE POWER SYSTEM 2. GENERAL Dynamic stability of a power system is concerned with the dynamic behavior of the system under small perturbations around an operating

More information

Delayed Feedback Controller for Stabilizing Subsynchronous Oscillations in Power Systems

Delayed Feedback Controller for Stabilizing Subsynchronous Oscillations in Power Systems Delayed Feedback Controller for Stabilizing Subsynchronous Oscillations in Power Systems Yaar Küçükefe 1 and Adnan Kaypmaz 2 1 National Power Enerji, Tekirda, Turkey yasar.kucukefe@ieee.org 2 stanbul Technical

More information

1 Unified Power Flow Controller (UPFC)

1 Unified Power Flow Controller (UPFC) Power flow control with UPFC Rusejla Sadikovic Internal report 1 Unified Power Flow Controller (UPFC) The UPFC can provide simultaneous control of all basic power system parameters ( transmission voltage,

More information

Low Frequency Transients

Low Frequency Transients Page 1 IEEE Power Engineering Society Summer Meeting Edmonton, July 18-22, 1999 Tutorial: Power System Overvoltages Low Frequency Transients Presented by Bruce Mork Work Done by Slow Transients Task Force

More information

Chapter 8: Unsymmetrical Faults

Chapter 8: Unsymmetrical Faults Chapter 8: Unsymmetrical Faults Introduction The sequence circuits and the sequence networks developed in the previous chapter will now be used for finding out fault current during unsymmetrical faults.

More information

Damping SSR in Power Systems using Double Order SVS Auxiliary Controller with an Induction Machine Damping Unit and Controlled Series Compensation

Damping SSR in Power Systems using Double Order SVS Auxiliary Controller with an Induction Machine Damping Unit and Controlled Series Compensation 614 Damping SSR in Power Systems using Double Order SVS Auxiliary Controller with an Induction Machine Damping Unit and Controlled Series Compensation Sushil K Gupta, Narendra Kumar and A K Gupta Abstract--This

More information

Self-Tuning Control for Synchronous Machine Stabilization

Self-Tuning Control for Synchronous Machine Stabilization http://dx.doi.org/.5755/j.eee.2.4.2773 ELEKTRONIKA IR ELEKTROTECHNIKA, ISSN 392-25, VOL. 2, NO. 4, 25 Self-Tuning Control for Synchronous Machine Stabilization Jozef Ritonja Faculty of Electrical Engineering

More information

Electromagnetic Torque From Event Report Data A Measure of Machine Performance

Electromagnetic Torque From Event Report Data A Measure of Machine Performance Electromagnetic Torque From Event Report Data A Measure of Machine Performance Derrick Haas and Dale Finney Schweitzer Engineering Laboratories, Inc. 7 SEL Overview Electromagnetic torque calculation Modeling

More information

3 d Calculate the product of the motor constant and the pole flux KΦ in this operating point. 2 e Calculate the torque.

3 d Calculate the product of the motor constant and the pole flux KΦ in this operating point. 2 e Calculate the torque. Exam Electrical Machines and Drives (ET4117) 11 November 011 from 14.00 to 17.00. This exam consists of 5 problems on 4 pages. Page 5 can be used to answer problem 4 question b. The number before a question

More information

IEEE PES Task Force on Benchmark Systems for Stability Controls

IEEE PES Task Force on Benchmark Systems for Stability Controls IEEE PES Task Force on Benchmark Systems for Stability Controls Ian Hiskens November 9, 3 Abstract This report summarizes a study of an IEEE -generator, 39-bus system. Three types of analysis were performed:

More information

CHAPTER 3 MATHEMATICAL MODELING OF HYDEL AND STEAM POWER SYSTEMS CONSIDERING GT DYNAMICS

CHAPTER 3 MATHEMATICAL MODELING OF HYDEL AND STEAM POWER SYSTEMS CONSIDERING GT DYNAMICS 28 CHAPTER 3 MATHEMATICAL MODELING OF HYDEL AND STEAM POWER SYSTEMS CONSIDERING GT DYNAMICS 3.1 INTRODUCTION This chapter focuses on the mathematical state space modeling of all configurations involved

More information

SHORT QUESTIONS AND ANSWERS. Year/ Semester/ Class : III/ V/ EEE Academic Year: Subject Code/ Name: EE6501/ Power System Analysis

SHORT QUESTIONS AND ANSWERS. Year/ Semester/ Class : III/ V/ EEE Academic Year: Subject Code/ Name: EE6501/ Power System Analysis Srividya colllege of Engg & Tech,Virudhunagar Sri Vidya College of Engineering And Technology Virudhunagar 626 005 Department of Electrical and Electronics Engineering QUESTION BANK SHORT QUESTIONS AND

More information

Power Angle & Time Domain Plots 1.0 The power-angle curves

Power Angle & Time Domain Plots 1.0 The power-angle curves Power Angle & Time Domain Plots 1.0 The power-angle curves Consider a generator connected to an infinite bus through a network, as shown in Fig. 1 below (all in pu). E E NETWORK X V V 0 Fig. 1 We assume

More information

Dynamic Voltage Stability Enhancement of a Microgrid with Static and Dynamic Loads Using Microgrid Voltage Stabilizer

Dynamic Voltage Stability Enhancement of a Microgrid with Static and Dynamic Loads Using Microgrid Voltage Stabilizer Dynamic Voltage Stability Enhancement of a Microgrid with Static and Dynamic Loads Using Microgrid Voltage Stabilizer Kenan Hatipoglu 1, Ismail Fidan 2, Ghadir Radman 3 1 Electrical and Computer Engineering

More information

Torques 1.0 Two torques We have written the swing equation where speed is in rad/sec as:

Torques 1.0 Two torques We have written the swing equation where speed is in rad/sec as: Torques 1.0 Two torques We have written the swing equation where speed is in rad/sec as: 2H Re ( t) T au T mu T eu (1) and when speed is in per-unit as 2H u ( t) Tau Tmu Teu (2) We note that in both cases

More information

Behaviour of synchronous machine during a short-circuit (a simple example of electromagnetic transients)

Behaviour of synchronous machine during a short-circuit (a simple example of electromagnetic transients) ELEC0047 - Power system dynamics, control and stability (a simple example of electromagnetic transients) Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct October 2018 1 / 25 Objectives

More information

A New Improved Method to Damp Inter-Area Oscillations in. Power Systems with SSR Mitigation and Zone Protection. Compensation

A New Improved Method to Damp Inter-Area Oscillations in. Power Systems with SSR Mitigation and Zone Protection. Compensation A New Improved Method to Damp Inter-Area Oscillations in Power Systems with SSR Mitigation and Zone Protection Compensation Thesis submitted for the degree of Doctor of Philosophy at the University of

More information

Experimental Testing and Model Validation of a Small-scale Generator Set for Stability Analysis.

Experimental Testing and Model Validation of a Small-scale Generator Set for Stability Analysis. Experimental Testing and Model Validation of a Small-scale Generator Set for Stability Analysis. G. Quiñonez-Varela and A. Cruden Abstract The integration of numerous small-scale generators into existing

More information

Modeling of Hydraulic Turbine and Governor for Dynamic Studies of HPP

Modeling of Hydraulic Turbine and Governor for Dynamic Studies of HPP Modeling of Hydraulic Turbine and Governor for Dynamic Studies of HPP Nanaware R. A. Department of Electronics, Shivaji University, Kolhapur Sawant S. R. Department of Technology, Shivaji University, Kolhapur

More information

Evaluation of the risk of failure due to switching overvoltages of a phase to phase insulation

Evaluation of the risk of failure due to switching overvoltages of a phase to phase insulation Evaluation of the risk of failure due to switching overvoltages of a phase to phase insulation A. Xemard, J. Michaud, A. Guerrier, I. Uglesic, G. Levacic, M. Mesic Abstract-- The upgrade of an overhead

More information

Performance Of Power System Stabilizerusing Fuzzy Logic Controller

Performance Of Power System Stabilizerusing Fuzzy Logic Controller IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 9, Issue 3 Ver. I (May Jun. 2014), PP 42-49 Performance Of Power System Stabilizerusing Fuzzy

More information

AVOLTAGE SAG is a short-duration reduction in rms

AVOLTAGE SAG is a short-duration reduction in rms IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20 NO. 2, APRIL 2005 1683 Symmetrical and Unsymmetrical Voltage Sag Effects on Three-Phase Transformers Joaquín Pedra, Member, IEEE, Luis Sáinz, Felipe Córcoles,

More information

CHAPTER 2 MODELING OF POWER SYSTEM

CHAPTER 2 MODELING OF POWER SYSTEM 38 CHAPTER 2 MODELING OF POWER SYSTEM 2.1 INTRODUCTION In the day to day scenario, power is an essential commodity to the human beings. The demand is more in developed countries and there is increase in

More information

Minimax Approximation Synthesis in PSS Design by Embedding

Minimax Approximation Synthesis in PSS Design by Embedding Minimax Approximation Synthesis in PSS Design by Embedding Gravitational Search Algorithm Dr. Akash Saxena Department of Electrical Engineering Swami Keshvanand Institute of Technology Jaipur, India Power

More information