Start display at page:

Download "MADHYA PRADESH POWER TRANSMISSION COMPANY LIMITED STATE LOAD DESPATCH CENTRE, NAYAGAON, RAMPUR, JABALPUR"

Transcription

1 MADHYA PRADESH POWER TRANSMISSION COMPANY LIMITED STATE LOAD DESPATCH CENTRE, NAYAGAON, RAMPUR, JABALPUR Telephone: (0761) Fax: (0761) / Corporate office: Madhya Pradesh Power Transmission Co. Ltd., Block No.2, Shakti Bhawan, Rampur, Jabalpur , CIN-U40109MP2001SGC014880, -mdtransco.nic.co.in vkbz,l vks : ISO: No.07-05/SG-9B-II/2983 Jabalpur, dated: To As per distribution list Sub: Minutes of 60 th meeting of Operation and Coordination Committee of MP. The Minutes of 60 th meeting of the Operation and Coordination Committee of MP held on 28 th October 2017 at Shree Singhaji Thermal Power Station (SSTPS), MPPGCL, Singhaji, Distt. Khandwa has been uploaded on the website of SLDC and can be downloaded. (R.A. Sharma) Member Secretary, OCC SLDC, MPPTCL, Jabalpur

2 Distribution List 1. The Chief Engineer (Works), MP Power Transmission Co. Limited, Shakti Bhawan, Jabalpur, 2. The Chief Engineer (T&C), MP Power Transmission Co. Limited, Jabalpur. Fax No , The Chief Engineer (Transmission-East Zone), MP Power Transmission Co. Limited, Shakti Bhawan, Jabalpur The Chief Engineer (Transmission-West Zone), MP Power Transmission Co. Limited, Indore. 5. The Chief Engineer (Transmission-Central Zone), MP Power Transmission Co. Limited, Bijlee Nagar, Govindpura, Bhopal, The Chief Engineer (Plg & Des), MP Power Transmission Co. Limited, Jabalpur, Fax No The Chief Engineer (Procurement.), MP Power Transmission Co. Limited, Jabalpur,.Fax No The Executive Director (O & M:Gen), MP Power Generating Company Limited, Jabalpur. Fax No , The Chief Engineer (O&M:Hydel), MP Power Generating Co. Ltd, Jabalpur, Fax No The General Manager(PM), MPPMCL, Jabalpur 11. The Superintending Engineer (GCC), MPPGCL, Jabalpur 12. The General Manger (DCC-EZ), DISCOM Control Centre, MP Poorva Kshetra Vidyut Vitaran Co.Limited, Jabalpur, Fax No , 13. The Dy. General Manager (DCC CZ), DISCOM Control Centre, MP Madhya Kshetra Vidyut Vitaran Co. Limited, Bhopal, Fax No , The Executive Engineer (DCC-WZ), DISCOM Control Centre, MP Paschim Kshetra Vidyut Vitaran Co. Limited, Near Polo Ground, Jail Road, Indore, Fax No , The Executive Engineer, Sub Load Despatch Centre, MPPTCL, Indore, Fax No , 16. The Executive Engineer, Sub Load Despatch Centre, MPPTCL, Bhopal, Fax No , 17. The General Manger(RO), MPPMCL, In front of Bhojpur Club, E-4, Arera Colony,Bhopal, Fax No , 18. The Chief Engineer (PM&C), Narmada Hydroelectric Development Corpn. Ltd, NHDC Parisar, Shamla Hills, Bhopal , Fax No , 19. The Chief Electrical Distribution Engineer, West Central Railway (WCR), General Manager s Office, Electrical Department, Jabalpur (MP), Fax: , - cede@wcr.gov.in, dyceetrdwcr@gmail.com, M , Mr.Satyendra Kumar (Dy.CE), Mob (CEDE, WCR). 20. The General Manager, Indira Sagar Power Station, NHDC Office complex, PO : Narmada Nagar, Distt : Khandwa (MP) , Fax No , nhdc-isp@rediffmail.com 21. The General Manager, Omkareshwar Power Station, Prashsnik Bhawan, Urja Vihar, Sidhwarkut, Distt : Khandwa (MP) , FaxNo , - pksaxena@nhdcl.com, saxena_pks123@rediffmail.com, omkareshwar.nhdc@gmail.com. 22. The Director (Projects), BLA Power Limited, At : Niwari, PO: Khorsipan, Tah : Gadarwara, Distt ; Narsinghpur , Fax No / , manish@bla.co.in 23. The Sr. Vice President, Jaiprakash Power Ventures Ltd., Village Sirchopi Subpost Office-Agasod, Post Office-Bina Distt- Sagar, Fax No , jptpp.switchyard@jalindia.com 24. The Chief Executive Officer, Kalpataru Satpura Transco Pvt. Ltd., Satpura Colony, Betul Road, Old Itarsi, Distt. Hoshangabad, cbhandari@kalpatarupower.com 25. M/s Ujaas Energy Ltd. 701, NRK Business park, Vijay Nagar Sqaure, Indore , id :- solar@ujaas.com 26. M/s Suzlon Global Services Ltd., 1090, Scheme no. 114, Park-2, Ring Road, Universal Hospital Row, - deepesh.sankwa@suzlon.com, Indore , Badree.hirve@suzlon.com

3 MINUTES OF 60 TH MEETING OF OPERATION & COORDINATION COMMITTEE OF MP HELD ON 28 TH OCTOBER 2017 AT 11:00 AM AT SHREE SINGHAJI THERMAL POWER STATION (SSTPS), SINGHAJI, DISTT. KHANDWA The 60 th meeting of Operation & Coordination Committee of MP was held on 28 th October 2017 at 11:00 AM at Shree Singhaji Thermal Power Station. The list of participants is enclosed at Annexure -1.0 Shri G.R.Gupta S.E(MPC), SSTPS welcomed Shri B.L.Newal, E.D(Gen),SSTPS, Shri R.A. Sharma, Member Secretary OCC & Addl. CE SLDC, Shri H.K Sankule, Addl. CE(O&M) and all the participants with bouquet of flowers. Shri Newal welcomed all the guests and participants for the 60 th OCCM at SSTPS and expressed his gratitude for providing the opportunity for hosting the 60 th OCCM at SSTPS. He stated that hopefully in this OCCM many issues & difficulties related to the MP system will be resolved and will help in safe & secure operation of the grid. Further a short telefilm on SSTPS was presented, depicting the stages of STPS planning, installation, its inauguration to its operation. Thereafter Shri G.R.Gupta S.E(MPC), SSTPS requested Shri R.A. Sharma, Member Secretary OCC & Addl. CE SLDC to start the meeting. Member Secretary OCC welcomed all the guests and requested for formal introduction prior to start the meeting. Thereafter Member Secretary OCC expressed his gratitude to SSTPS & the entire Generating Company for conducting the 60 th OCCM at SSTPS and doing such wonderful arrangement. He further stated that once in a while every power engineer should visit such power station to understand its operation, complexity which gives a proper and good exposure in power sector. He further stated that the demand of MP has already crossed MW & is expected to cross 12000MW in this season, in terms of energy demand has already crossed 2200 LU & is expected to cross 2300 LU. Being a surplus state, it is a great challenge to SLDC-MP to maintain the grid in case of outage of generator, as implementing load relief is quite difficult. To meet out such contingencies arrangement of power by MPPMCL is necessary to avoid load shedding. The Member Secretary MP -OCC in his deliberation briefed the committee about important issues of the meeting. He elaborated the committee that during ongoing rabi season due to high MVAR demand and higher the line loading, low voltage problem is expected in the state grid. Recently the low voltage problem has been faced in Indore & Nagda regions which were controlled by switching off reactors, but such frequent switching off/on of reactors is not desirable, hence maximum MVAR support is essential from all the generators as per their capability limits without compromising the MW for maintaining voltages. He also stated that for meeting the demand pre-planning of hydel generation has to be done which requires Tan Daily planning of reservoir level of all Hydel Generators, hence the generating company & NHDC is requested to submit the Tan Daily details on time. Thereafter Member Secretary OCC stated that there is a major issue of over drawl by MP which shall be maintained by proper planning of load & generation balance. Also, due to heavy O/D by MP, in recent past days, the WRLDC has opened some of the interconnected transmission lines, to restrict MP O/D. Due to opening of the lines, system becomes weak. We should not give chance for such action to WRLDC. Member Secretary OCC informed the committee that there is also an issue of Non-availability of telemetry at SLDC due to which monitoring & secure operation of the grid is not possible. Also, CERC has notified Communication Regulation 2017 according to which availability of telemetry shall be 99.9% and it shall be monitored on regular basis, by CERC. Thereafter Member Secretary OCC took up the agenda points, which is indicated hereunder in nutshell: ITEM NO. 1: CONFIRMATION OF MINUTES: Minutes of 59 th meeting of Operation & Coordination Committee of MP held on 12 TH September 2017 at SLDC, MPPTCL, Jabalpur were forwarded to the committee members vide No /SG-9B-II/2402 Jabalpur dated As NO comment received, committee confirmed the minutes. Minutes Of 60th OCCM Of MP 1

4 ITEM NO. 2: REVIEW OF SYSTEM OPERATION DURING THE MONTHS AUG 2017 TO SEPT Frequency Particulars: The Committee was informed that during Aug 2017 the system frequency was below 49.9 Hz for 7.2% of time against % of time during Sept The system frequency was above Hz for % of time during Aug 2017 against 9.73 % of time during Sept The system frequency was within the IEGC range of Hz for 76.82% of the time during Aug 2017 against 78.50% of time during Sept The average monthly frequency was Hz during month of Aug 2017 and Hz during month of Sept The system frequency did not touch Hz during the above period. The detailed frequency particulars for the month of Aug 2017 and Sept 2017 are enclosed at Annexure-2.1. The brief detail of frequency profile is given here under: Month Average frequency Minimum Integrated frequency over an hour Maximum integrated frequency over an hour Instantaneous Minimum Frequency Instantaneous Maximum Frequency Aug Hz Hz Hz Hz Hz Sept Hz Hz Hz Hz Hz Member Secretary OCC stated that the instantaneous minimum frequency during Aug-17 & Sept-17 was very low and is a matter of concerned as from technical view it is not secure for grid operation. Also, the energy rate at this frequency increases tremendously and over drawl at such high rates has commercial implications also, so the frequency should be maintained within the range. The committee has noted the above information. 2.2 Operational Matters Operational Discipline: The Committee was apprised that the system operated in terms of frequency profile for the months Aug 2017 and Sept 2017 is as indicated below for discussion by the committee: Month % of time Frequency Below 49.9 Hz % of time Frequency above Hz % of time frequency within the permissible range of Hz. Average monthly frequency No. of times frequency dipped below 49.2 Hz Aug % 15.98% 76.82% Hz 0 Sept % 9.73% 78.50% Hz 0 The committee has noted the above information. Minutes Of 60th OCCM Of MP 2

5 2.2.2 Voltage Profile: The Committee was informed that during the months Aug 2017 and Sept 2017 the maximum and minimum voltage as recorded at following important 400 KV s/s in MP Grid:- Aug 2017 Sept 2017 Max. Voltage Min. Voltage Max. Voltage Min. Voltage Name of observed Observed Observed Observed Sr. 400 KV Volt Voltage No. Substation Voltage ag Voltage Date Date Date Date KV e KV KV KV 1 Indore Itarsi Bina Gwalior Nagda Satpura Birsinghpur ISP Bhopal Ashta Pithampur Singhaji Member Secretary OCC informed the Committee that during rabi season due to high line loading & MVAR drawal, the low voltages are being observed in Gwalior & Bina regions. Hence all the generators were requested to regulate the MVAR as per the system requirement within their capability limits. The committee has noted the above information Status of Capacitor Banks in sub-transmission system: The Committee was briefed about the updated information of the status of capacitor banks in sub-transmission system as on 30 th Sept 2017 as submitted y DISCOMs is detailed below: - DISCOM Capacitor bank Capacitor installed in good Banks healthy condition (No) but not in service due to control ckt problem KVAR KVAR KVAR KVA R KVA R KVA R Capacitor bank Require Requiremen Capacitor Balance installed but ment of t against banks already capacitor defective & are repair nonrepairable covered under banks to be repairable (No) against each capacitor ADB T-V covered in other unit (No) banks schemes 600 KVA R No of KVAR KVAR KVAR Units required KVAR KVAR KVAR KVAR KVAR KVAR EZ CZ WZ Minutes Of 60th OCCM Of MP 3

6 Representative from East Discom informed the committee that the 25 no. of capacitor bank under Requirement of repair against each unit (No) will be repaired and taken in service before next OCCM in December-17. He further informed that the work is under progress for 77 no. of capacitor bank Balance capacitor banks to be covered in other schemes and will take some time. Representative from Central Discome informed the committee that all the capacitor banks are in service and if any is found defective it is repaired within 7 days. Representative from MPPTCL informed the low voltages are being observed in Sheopur area and on inspection by SE(T&C) MPPTCL /SE(O&M), MPMKVVCL the 30 % capacitor banks installed in that area were found defective and low voltage was existing because of want of capacitor bank. The representative of MPPTCL had also informed that CE(T&C) forwarded the proposal for installing suitable capacity capacitor bank every 33/11 substation at Sheopur, so that low voltage crises in this pocket could be addressed looking to high reactive load. Representative from Central Discom informed the committee that the capacitor banks for 11 KV is being planned in sheopur area and financing arrangement are being made. The present status will be intimated separately. Member Secretary OCC stated that the issue of low voltage in Sheopur area be taken seriously by Central Discom & resolved on priority basis. It is also pointed out that looking to low voltage profile in forthcoming rabi season, it is desired that Discoms & MPPTCL should be ensured healthiness of capacitor bank, otherwise it is not possible to maintained voltage level from Generating end solely. Reactive compensation in transmission system and Discoms end is invariably required. The committee has noted the above information Status of Shunt Capacitor Banks installed at various EHV Transmission Substation: Member Secretary OCC informed the Committee that the updated information of the status of installed capacitor banks Voltage Capacitor bank Capacity Added Capacitor banks TOTAL Capacitor Bank Class installed as on after Last OCC already covered CAPACITY AS Installed but (MVAR) Meeting (MVAR) under ADB T-V ON defective & are not (MVAR) repairable (No & MVAR) 220 KV All in Service 132 KV KV Total (in MVAR) in EHV transmission system as on as submitted by MPPTCL is given below:- Representative from MPPTCL informed the committee that the installation of additional capacitor banks in EHV system is in progress and by Novemebr-17 about 15 no. capacitor banks will be installed and by December-17 remaining planned capacitor banks will be installed. The committee has noted the above information. Status of completion of ongoing Transmission Schemes being executed by MPPTCL: The Committee was apprised regarding various ongoing Transmission Schemes completed during the financial year (up to Sept 2017) and plan for completion of various ongoing Transmission Schemes for the Year is enclosed as Annexure 2.2.5(i) and 2.2.5(ii) respectively. The committee has noted the above informatio Minutes Of 60th OCCM Of MP 4

7 2.2.5 U/F and df/dt Relay Operation (i) (ii) U/F and df/dt Relay Operation: Member Secretary OCC informed the Committee that the frequency did not touch Hz during Aug 2017 and Sept There was no df/dt operation during the same period. Defective u/f, df/dt relays: Member Secretary OCC informed the Committee that MPPTCL has informed that all the df/dt relays are in operation, where the U/F relays are not available, the numerical relays programmed for under frequency operation. df/dt relay installed at 220 KV Ujjain, 220 KV S/s Badnagar & 132 KV S/s Chapda is being replaced shortly, except this all U/F stages are in good/healthy working condition. The committee has noted the above information. 2.3 Power Cuts / Load restrictions/differential Load Shedding by DISCOMS & group allocation to 33 KV feeders: (i) The details of DISCOM wise Power supply given to various domestic categories during the period August 2017 and September 2017 as indicated at Annexure 2.3(i) was put up before the committee for discussion. The committee has noted the above information. (iii) Group Allocation to Newly Commissioned existing EHV substations: - Member Secretary OCC informed the Committee that the region wise list of 33 KV feeders emanating from various newly commissioned/existing EHV substations for which groups have not been allocated is given in Annexure 2.3 (ii). The DISCOM wise details of pending group allocation to 33 KV feeders is given below: - SN DISCOM Region No of 33 KV feeders for which groups to be allocated 01 Jabalpur 0 02 Sagar 0 EAST 03 Rewa 0 04 Total 0 05 Indore WEST Ujjain Total Bhopal CENTRAL Gwalior Total 15 TOTAL Grand Total 16 Discoms are requested to furnish the details as per list enclosed at Annexure-2.3(ii) in the meeting. Representative from Central Discom informed the committee that the 33 KV Simcon Solar Power is a power injecting feeder, hence cannot be group allocated and shall be removed from the list. Further member Secretary informed the committee that the feeder shall be removed from the list of group allocation as per the procedure. Minutes Of 60th OCCM Of MP 5

8 Thereafter representative from Central Discom informed the committee that the 33 KV Nagarpalika feeder has been renamed as Kushalpura and has been group allocated and informed to P&D and requested to update the list. Further he informed that 33 KV Goharganj has also been group allocated. The committee has discussed the matter and noted. ITEM NO. 3 : OPERATIONAL PLANNNING: 3.1 Generating Units under planned outage and proposed maintenance programme: The Committee was informed that the annual maintenance /outages of thermal generating units of MPPGCL during November 2017 to December 17 is Nil as intimated by ED(O&M:Gen.), MPPGCL, Jabalpur. 3.2 Proposed shutdown programme of Transmission lines / Transformers: The proposed shutdown of transmission elements for the period to submitted by MPPTCL as indicated in Annexure-3.2 was put up before committee for information. The committee has noted. 3.3 Long Outages of transmission elements and protections: Member Secretary OCC informed the Committee that the status submitted by MPPGCL /MPPTCL are given below: - Sr. Line/Transformer/ etc Outage date Reason Response from Utility No under long Outage MVA, 132/66/33 KV X mer, CGL make Sr. No at 132 KV S/s Pichhore 12.5MVA X mer, BBL Make (Sr. No.-1428/3) at 132 KV S/s Chapda Not intimated Transformer failed on as intimated by T&C, MPPTCL. X mer failed The load is manageable through (1x20 + 1x40) MVA X mers in running condition at S/s Pichhore. MPPTCL informed that the decommissioning proposal of this x- mer is sent to CE(P&D) vide U.O.No.1788, dt further, the matter is atken up by CE(P&D) with CGM(W), Central Discom vide L.No.04-02/PSS/2291 Dt , After receiving approval from competent authority, the transformer shall be de-commissioned. Representative from T&C, MPPTCL informed the committee that the proposal has been sent to Discom by P&D for its approval and is awaited. The 12.5MVA BBL make Transformer Sl. No. 1428/3 failed and proposed to be withdrawn from system. MPPTCL informed that the de-commissioning proposal of this x- mer is sent to CE(P&D) vide U.O.No.851, dt further, the matter is atken up by CE(P&D) with CGM(W), Central Discom vide L.No.04-02/PSS/2291 Dt , After receiving approval from competent authority, the transformer shall be de-commissioned. Representative from T&C, MPPTCL Minutes Of 60th OCCM Of MP 6

9 MVA, 220/132 KV Sr. No BHEL X mer at 220 KV S/s Jabalpur 50 MVA, 132/33 KV BHEL make X mer, Sr. No at 132 KV S/s Katni 20 MVA, 132/33 KV EMCO make X mer, Sr. No. HT at 400 KV S/s, Katni 40 MVA, 132/33 KV CGL make X mer, Sr. No. T at 220kv s/s Ujjain. 20 MVA, 132/33 KV CGL make X mer, Sr. No. T at 132kv s/s Sonkatch MVA(16.5/6.6 KV), UAT- A, Unit No. 10, STPS, Sarni MVA (400/11.5/6.6KV) Station X mer-2, SSTPP, Khandwa Tripped on Differential indication. Tripped on differential indication. Tripped on differential indication. Tripped on differential indication. Tripped on differential indication. Due to oil leakage from B-Phase LV bushing. B Ph. HV side bushing failed informed the committee that the proposal has been sent to Discom by P&D for its approval and is awaited. Transformer dismantled and sent to M/s BHEL for inspection / repairs as intimated by MPPTCL. Representative from MPPTCL informed the committee that the X mer will be commissioned by end December-17. Representative from MPPTCL informed the committee that X mer failed within guarantee period and it is being sent to M/s BHEL for inspection/ repair. Representative from MPPTCL informed the committee that the X -mer has been sent to M/s BHEL, Jhansi for inspection/ repair. MPPTCL informed that another 40MVA BBL transformer Sl.No. 5564/2 commissioned on Dt Representative from MPPTCL informed the committee that 50 MVA X mer is sent for repair to BHEL and will be utilized in transmission system as per requirement. MPPTCL informed the that the X mer is to be replaced by another 20 MVA X mer by November Representative from MPPTCL informed the committee that another X mer will be commissioned by December-17. MPPTCL informed that the internal inspection of the X mer is pending due to bad weather. MPPTCL informed that the transformer has been declared failed. Another X mer will be commissioned within 2 months. Representative from MPPTCL informed the committee that the X mer has been charged on MPPGCL informed Work completed. Testing and commissioning will be done when unit is under shutdown. Ready for charging and will be taken in service whenever the unit is taken after shut down. MPPGCL informed that repair work of station transformer is under progress at M/s BHEL, Jhansi. Repair work under progress at BHEL, Jhansi. MPPGCL informed that the X mer is expected to taken in service by December-17. Minutes Of 60th OCCM Of MP 7

10 10. STPS Unit # GT Burnt KV Generator Breaker of Unit # 9 of Satpura KV transfer bus, STPS, Sarni MVA, 132/11KV EMCO X mer at 132 KV S/s Sanwer. 40MVA, 132/33KV, CGL X mer at 132 KV S/s Chhindwara Fire in Bushing of GT Aug Problem in Breaker X mer taken out from service since due to aging and no 11KV network at S/S Unit under long forced outage due to GT burnt. MPPGCL informed the committee that Replacement /Purchase work under progress. Representative from MPPGCL informed that GT purchase is under tendering stage and is expected to be in service in about 3 months i.e., by January Replacement completed by Breaker given by MPPTCL, but there is problem in breaker. MPPGCL informed the committee that CGL company engineer has been called for inspection and rectification and the breaker is expected to be commissioned by end of Novemebr- 17 Replacement completed by Breaker given by MPPTCL, but there is problem in breaker. MPPGCL informed the committee that CGL company engineer has been called for inspection and rectification and the breaker is expected to be commissioned by end of Novemebr- 17 Committee may like to discuss & MPPTCL is requested to submit the further action plan. Representative from MPPTCL informed that load is manageable. MPPTCL informed that Discom has to provide its consent to remove it from the asset/availability. After internal inspection X mer declared faulty and is being replaced by 63MVA BHEL transformer by Oct 17. MPPTCL representative informed the committee that the X mer is expected to be commissioned by Nov-17. The committee has noted the above information. ITEM NO. 4 : OPERATIONAL STATISTICS FOR THE MONTH OF AUGUST 2017 AND SEPTEMBER 2017: The Committee was briefed about details of actual generation, Schedule from Central Sector, demand etc. are given in the following Annexures: Annex. 4.1 Annex. 4.2 Annex. 4.3 Annex. 4.4 The unit wise actual Generation of MPPGCL thermal Units and station wise Generation of MPPGCL & NHDC Hydel Units. Power Supply Position. Hourly Average of Availability and Demand. Hourly average schedule Vs Drawal of DISCOMs. The committee has noted the above information. Minutes Of 60th OCCM Of MP 8

11 ITEM NO. 5 : SYSTEM DISTURBANCE IN MP DURING AUGUST 2017 AND SEPTEMBER 2017 : The Committee was intimated that the there was no major grid disturbance in MP during August 2017 and September Moreover, the Grid Disturbances and Grid Incidents in MP during these months are given in Annexure 5. The committee has noted the above information. ITEM NO. 6.0: IMPORTANT OPERATIONAL ISSUES: STATUS OF COMPLETION OF ONGOING SCHEMES FOR COMMISSIONING OF REACTORS / TRANSMISSION ELEMENTS: - The Committee was informed that the present status regarding schedule and commissioning of reactors / transmission elements as indicated hereunder: - S.No. 400 KV S/s Size MVAR Implementing Agency Expected Date of Commissioning as intimated in last OCC 1. Bus Reactor: ISP 2. Line Reactor on 400 kv Satpura ISP line at STPS 3. Bus Reactor at SSTPS 125 MVAR NHDC 50 MVAR MPPGCL 125 MVAR MPPGCL Representative from NHDC informed the committee that road construction is under process for transportation and it is expected to be commissioned by end of Jan-18. In 57 th, 58 th, 59 th OCCM MPPGCL informed the committee that procurement of line reactor is under tendering stage and expected to be commissioned by Oct, Representative from MPPGCL informed the committee that the technical specification of the reactor has to be finalized and reactor is expected to be commissioned by April- 18. Work will be carried out under PSDF as intimated by MPPGCL. MPPGCL informed the committee that the price bid has to be opened and the reactor is expected to be commissioned by June The committee has noted the above information. 6.2 Provision of synchronization facility at EHV sub-stations of MPPTCL: As per Grid Code, the synchronization facility should be available at all the Power Stations, 400 KV Sub-stations and 220 KV Substations and 132 KV sub-stations in the path of black start. In last OCC meeting MPPTCL representative informed the committee that order for 69 no. synchronization trolleys has been placed and 1 no. synchronization trolley has been delivered for checking and testing purpose at 220KV S/S Barwaha. Representative from MPPTCL informed the committee that all the trolley has been delivered on site and the installation work has been started by company engineers and is under progress. Minutes Of 60th OCCM Of MP 9

12 Member Secretary OCC stated that the feasible methods shall be explored for installation of synchronization trolley at 132 KV stations falling under black start path and provision shall be made for installation of line CVT if required. The committee has discussed the matter and noted. 6.3 Ten Daily Reservoir operation table of MPPGCL HPS: - The Committee was intimated that a meeting was convened in Regional Office of MPPMCL at Bhopal on to discuss availability from Sardar Sarovar Project, ISP & OPS and State Hydel Plants for Rabi season, MPPGCL had agreed to obtain ten daily reservoir operation table from WRD and NVDA for their operation of their hydro generators. In last 54 th to 59 th, OCCMs, request has been made to MPPGCL for furnishing the same to SLDC. The Ten Daily programme of hydel power stations is necessary for planning of Load Generation Balance. MPPGCL has not submitted the ten Daily Reservoir Operation Table of all the power stations of MPPGCL for the year It is requested that MPPGCL shall submit the Ten Daily Reservoir Table of all hydel power stations in coordination with NVDA and WRD for optimum utilisation of available water in the reservoirs during real time operation. The matter was discussed in the meeting and Member Secretory OCC requested all the concerned entities to submit the ten daily reservoir operation table and the matter has been discussed in several OCC meetings. The committee has noted. 6.4 Updation of Recovery Procedure for Western Regional ( WR ) Grid-2007 The WRLDC has informed that the Grid Recovery Procedure for Western Region is being updated and the users of WR Grid, STUs and CTU may kindly convey the relevant details for facilitating timely updating of this document. In view of the above all utilities of MP were requested vide letter no 07-05/RPC-38/1951 dated to submit the relevant details as on pertaining to respective entity to SLDC as mentioned in WRLDC letter under reference to this office by 10 th September 2017, so that consolidated information could be forwarded to WRLDC within specified time limit, but no information has been received till date. The matter was discussed and again requested to all participant to arrange to convey the relevant details as indicated below: - a. Contacts Details (Mobile/Land Line Numbers/ -Id) of the Nodal officers identified for crisis management. b. List of New transmission elements and generation units commissioned in c. Shunt Reactive resources (Line Reactors/ Bus Reactors) in STU system. d. Traction Supply Details (As per format enclosed at Annexure-6.4) e. Synchronization facilities at 132 KV/220 KV/400 KV. Minutes Of 60th OCCM Of MP 10

13 f. List of Stations having black start capabilities. g. Any other relevant information. Member Secretary requested all the entities to submit the required details at the earliest to SLDC for onward submission to WRLDC/WRPC. The committee has noted the above information. 6.5 MONITORING OF SCHEMES FUNDED FROM PSDF: - It was decided in the 6th meeting of NPC held on 19th December 2016 at Bengaluru, that all the RPCs in the monthly OCC meetings may follow up with the utilities to expedite the completion of schemes by giving due priority. The implementation of most of the schemes are based on the recommendation of the enquiry committee on grid disturbance of July 2012 headed by Chairperson, CEA. Therefore, timely implementation of these schemes would enhance the grid security and reliability. Accordingly, the details of grant sanctioned from PSDF for the schemes of MP is enclosed at Annexure- 6.5A. The status of implementation of above schemes (physical as well as financial progress) may please be reviewed and the entities are requested to expedite implementation of the schemes. The utilities were advised to furnish the information in the format enclosed at Annexure 6.5B by first week of every month on regular basis to Member Convener, PSDF project monitoring group (AGM, NLDC, POSOCO) with a copy to NPC, WRPC division and SLDC. The status of the same is being monitored by WRPC in OCC meeting of WRPC every month. It is observed that MPPTCL and MPPGCL are not submitting the requisite information to SLDC in first week of every month for onward transmission to WRPC. It is therefore requested that concerned official may please instructed to submit the same regularly to SLDC within time. Representative from MPPGCL requested the committee that there are many problems faced during procurement of any element especially during tendering stage as there are very few vendors/company participating in tendering. Hence it is indicated that the matter shall be discussed with PGCIL and POSOCO for deciding a particular company for procurement and company shall make efforts to expedite the schemes The matter was discussed in the meeting and the committee has noted the above information. 6.6 Tripping of 400 KV Sarni-Koradi line on over voltage on dated : - On dated at Hrs, 400KV Satpura-Koradi line tripped on B-Ph. over voltage indication from Satpura end only. In this context it is mentioned that at time of tripping, the voltage at Satpura end was only 410 KV. It is evident that this line should not be tripped on over voltage indication. It appears maloperation. Vide this office letter dated , the aforesaid issue was raised and CE, STPS, Sarni has been requested to ensure healthiness of relay, CVT and associated equipments at Sarni for remedial action to avoid such mal-operation in future. The setting of over voltage relay at Sarni end are also required to be furnished to Minutes Of 60th OCCM Of MP 11

14 SLDC along with detailed report of aforesaid tripping so that the tripping incidence may be analyzed. Status of above tripping may please be updated. The matter was discussed in the meeting and MPPGCL informed the committee that aforesaid tripping took place due to theft of cable and the cable is being replaced. 6.7 Grid incidence at SGTPS, Birsinghpur on 7th July, 2017: - On 7 th July 2017 at 18:39 Hrs, the ICT at Birsinghpur S/s was charged from 220 KV side after shut down which was availed for bus bar protection retro fitting work and while synchronizing at 400 KV side, the ICT tripped on differential protection. Differential protection of generator also operated but generator breaker opened after 310 mili sec. The delayed tripping of generator led to LBB operation. There was generation loss of 144 MW. Based on detailed report submitted by MPPGCL, the tripping incidence was analyzed by WRLDC and raised following observations- (i) Why the lines were not uniformly distributed on 220 KV Bus No.1 and Bus No.2 at 400/220 KV Birsinghpur S/s? What is present status of bus bar arrangement? (ii) (iii) What was the reason for tripping of ICT on differential protection? The reason for differential protection for 220 KV GT 1 is also not clear. (iv) This is very serious that two of the feeders from 220 KV Bus No.2 have not tripped due to wrong bus isolator switch selection. This kind of issue during a bus fault would have led to delayed fault clearance and widespread system outage. The aforesaid tripping was discussed by the committee and the MPPGCL had informed the committee that the detailed report is being submitted. The committee has noted the above. 6.8 REPORTING OF FLASH REPORT, DR and EL FOR 400KV, Interstate Transmission Elements & Detailed Tripping Report: - As per the provisions of Regulation 5.2 (r) of CERC (Indian Electricity Grid Code) Regulations 2010 and Regulation of 5(9) of CERC (Indian Electricity Grid Code) (First Amendment) Regulations, 2012 all the Regional Entities of the Region shall furnish the tripping details including DR & SEL output to RLDC with in 24 hrs of the event for analysis and identify the real-time measures required in future to ensure secured grid operation. The flash report is also required to be furnished to SLDC within an hour of tripping. It is observed that FLASH REPORT, DR & EL of station is not made available after tripping of transmission grid element by the State Grid Entities and the flash report is also not being sent after repeated pursuance. It has been intimated by WRLDC wide letter no.- WRLDC/SO-II/1737/2017/ dated that in case of tripping of Inter State & inter Regional lines of voltage class 220 KV & above level, a tripping report along with the DR/EL files shall be submitted to WRLDC. In the matter it is to mention that the detailed report along with DR/EL shall be submitted to WRLDC/WRPC. Several incidences / trippings which occurred during the month of August-2017 for which the details have not been submitted are as below: - Minutes Of 60th OCCM Of MP 12

15 S.no. Element KV Mehgaon - Auriya KV Mehgaon - Auriya KV Mehgaon - Auriya Date of tripping Time of tripping Remark :13 Hrs. MPPTCL is requested to submit the detailed report along with DR/EL files, A/R details, etc. in the meeting :59 Hrs. MPPTCL is requested to submit the detailed report along with DR/EL files, A/R details, etc. in the meeting :50 Hrs. MPPTCL is requested to submit the detailed report along with DR/EL files, A/R details, etc. in the meeting. The MPPTCL representative was requested take up the matter with the field offices and arrange to submit the detailed tripping report to SLDC at the earliest for onward submission to WRLDC/WRPC. The matter was discussed in the meeting and he committee has noted. 6.9 Review of important grid elements list of WRLDC in respect of MP: - MP SLDC has requested WRPC /WRLDC that list of important grid elements (uploaded in WRPC website in decided 497 th OCCM) should be reviewed and only most important elements should be kept in the list. The outage of such less important / critical element have been given by MP SLDC by taking into consideration intra-state grid condition. Accordingly, matter was raised in 499 th meeting of WRPC in Mumbai. Thereafter a meeting was conducted with WRLDC official and after discussion, elements to be excluded from list of important grid elements of WR in respect of MP were decided with following conditions- (i) For availing outages on aforesaid lines/ ICTs, N-1 contingency should be ensured. (ii) The outage of element where different licensees are involved to be incorporated in Google sheet for outage coordination on D-3 basis. No any planned outage shall be entertained if not requested in D-3. (iii) The SLDC will permit shut down only after getting message from competent authority in D-3 basis. It is therefore invariably required that all utilities shall ensure that such outage proposal should have forwarded to SLDC at least 3 days before date of outage. (iv) All outages more than 2 days shall be approved by OCCM as per practice in vogue. (v) All such elements which are excluded from purview of OCCM are Annexure-6.9. a & Annexure-6.9. b. Member Secretary OCC informed the committee that previously the shut down on all the 400 KV intra state elements were given by WRLDC/WRPC. Now some of the elements are exempted from that list and the shut down on those elements can be given by SLDC as per the procedure defined in Annexure-6.9. a & Annexure-6.9. b. Hence all the entities are requested to follow the procedure. The matter was discussed in the meeting and he committee has noted Inspection of Relays of Automatic Under Frequency Load Shedding & Certification thereof: - Member Secretary OCC informed the Committee that it is desired that for safe & secure operation of Minutes Of 60th OCCM Of MP 13

16 integrated system, the under-frequency relay should be connected in the system in healthy condition. Accordingly, WRPC is pressing hard to provide the self-certified status of healthiness of relays of Automatic Under Frequency Load Shedding (AUFLS) and periodic checking of the same. Vide this office correspondence No dated read with 1837 dated and , CE (T&C) and also SE(T&Cs) were requested to provide status of healthiness of relays of Automatic Under Frequency Load Shedding on priority basis to SLDC, so that same may be communicated to WRPC. In-spite of repeated request vide various correspondence, moreover the matter had been raised in 59 th OCC meeting of MP, however the desired information is still awaited from utilities, only a few circles has furnished the detail. It is therefore desired that the above matter may be treated as urgent and status of healthiness of Automatic Under Frequency Relays may be provided to SLDC and also the under frequency may be tested periodically. In this context it is also mentioned that time to time WRPC official as well as SLDC official shall visit the sub-stations to ascertain the healthiness of under frequency relay. Representative from MPPTCL informed the committee that the consolidated report has been recently submitted to SLDC. The committee has noted 6.11 Formation of State Level Relay setting group- Review and Coordination of relay setting in state of MP:- Member Secretary OCC informed the Committee that as decided in 128th Protection Committee meeting of WRPC held on 06th & 07th Dec. 2016, relay review group for state of MP has been constituted vide this officer letter No.07-05/RPC-14/596 Jabalpur dtd In the above context all entities are requested to provide relay settings of all important nodes & all other nodes where relay settings are required to be examined considering protection issues. As desired by WRLDC important nodes like Indore PG, Bhopal etc. required to be examined first, which have huge effect on reliability and security of Grid. The first meeting of State Level Relay Setting Group convened on 18th August 2017 at SLDC for review the existing relay settings of critical state network and state network incidental to ISTS and to provide necessary interface between utilities/entities. All the members were requested to make arrangement to furnish details of relay settings of all important nodes, so that same may be communicated to all members and existing setting of critical nodes could be reviewed & corrective measures may be taken. Attention was also invited to members that SLDC have made multiple correspondences in this regard, however except MPPGCL, no any other utility has provided the desired data. It is accordingly desired that the data may please be provided immediately to SLDC. During discussions, it was envisaged that relay setting of ISPs, OSP nodes required to be examined first, as in recent past, frequent undesirable trappings were observed due to probable mismatch of relay coordination issue. Accordingly, ISP, OSP representatives were requested to provide relay setting of ISP, OSP nodes so that same could be validated by the committee in the next meeting. The issue of relay settings was discussed in broader prospect. The consolidated relay setting data has not been received by the entities. The desired data may kindly be submitted in the meeting by all the entities. Further it is desired that one representative may be nominated Minutes Of 60th OCCM Of MP 14

17 from the office of CE(T&C) for relay setting group so that the relay setting task may be coordinated properly as far as T&C setup is concerned. The matter was discussed in the meeting and Member Secretary OCC requested T&C, MPPTCL to nominate a coordinating officer from CE(T&C) MPPTCL office. All Respective entities were requested to provide desired data immediately. The committee has noted he point Furnishing the Pending protection audit observation compliances: - The Committee was informed that as per Hon ble CERC order dated in petition No. 220/MP/2012 filed by Power Grid, SLDC has regularly submitted the quarterly Protection Audit Report to the WRPC. WRPC vide letter under reference has intimated that the status of Protection Audit Observations is being monitored in the PCM regularly. However, it is observed that the compliances of many Protection Audit Observations are still pending. The list of pending Protection Audit Observations as submitted by the Intrastate entities updated up to June 2017 is enclosed as Annexure It is therefore requested to take the pending Protection Audit Observations with site officials and submit the timeline to resolve the pending Protection Audit Observation, to SLDC so that same could be forwarded to WRPC/CERC. The matter was discussed in the 59 th OCCM and all the concerned entities were requested to submit the required data at the earliest. The details have not been received by SLDC till date. All the entities are requested to submit the details in the meeting. The representative of MPPTCL has informed that the desired information is being submitted. The matter was discussed in the meeting and the committee has noted Frequent simultaneous tripping of all 220 KV feeders on overvoltage radiating from Omkareshwar Hydel Power Station: - Member Secretary OCC informed the Committee that on dtd at 5:42 hrs 220 KV OSP Khandwa line tripped on Zone I indication, thereafter all 220 KV feeders radiating from OSP were tripped on over voltage indication. Similarly, on dated at 04:09 hrs Nimarni Barwaha, 220 KV OSP Chhagaon, 220KV OSP- Khandwa and 220 KV OSP-Barwaha line tripped on over voltage alongwith 220 KV OSP- Julwaniya line. Such incidents were also occurred at 09:59 hrs on dtd and 05:45hrs on dtd The simultaneous tripping of all four 220 KV feeders do affect the stability of system and threatens the grid security. MD, MPPTCL has also shown concerned over these frequent trippings. The WRLDC is also perusing the matter regarding such repeated mal-operation of relay on over voltage, whereas at time of tripping system voltage was within normal range. Considering importance of Omkarshwar Hydel Power station such unwanted trippings is not desirable for smooth operation integrated grid, moreover such incidence may lead to a major grid disturbance. The over voltage relay setting at Omkareshwar Hydel Power Station has been examined by the CE (T&C) MPPTCL, Jabalpur and it is observed that the time delay on all feeders is almost the same, which may be one of the reason of simultaneous tripping of all the feeders under over voltage condition. Therefore, in order to avoid simultaneous tripping of all feeders, it is necessary to provide time grading in the settings of different feeders according to the line length, so that over voltage condition may be normalized prior to tripping Minutes Of 60th OCCM Of MP 15

18 of all feeders. Accordingly, the following settings are proposed to be adopted at Omkareshwar Power House: - Sr. No. Name of Feeder from Omkareshwar HPS Present setting Proposed Setting KV Nimrani (Tap Barwaha) 108%- 6 Sec. 110%- 4 Sec KV Julwaniya 108% - 5 Sec. 110% - 6 Sec KV PGCIL Khandwa 110% - 5 Sec. 110% - 8 Sec KV Chhegaon 110% - 5 Sec. 110% - 9 Sec KV Barwaha 110% - 5 Sec. 110% - 10 Sec. In view of above, SLDC has requested Omkareshwar HPS that proposed settings may be considered for implementation at Omkareshwar Power House. It is also requested all tripping due to over voltage may be thoroughly investigated and if any other reasons (mal operation of relay etc.) behind this tripping, may also be examined and suitable remedial action be taken accordingly and appraised to SLDC positively. The updated status on the matter be apprised to the Committee. Member Secretary OCC stated that OSP shall adopt the proposed over voltage settings along with time grading as per the system requirement. Thereafter representative from OSP agreed and informed the committee that the settings will be revised after confirmation from testing & maintenance department. The committee has noted Generation target / LGBR preparation for the year :- Member Secretary OCC informed the Committee that A. Electricity Generation Target for the year The Chief Engineer OPM, CEA, New Delhi intimated vide letter dtd that generation target for the year to be fixed up by MoP in consultation with CEA. The exercise is already started by CEA. All utilities of MP have already been requested to provide electricity generation target to CEA under intimation to SLDC. Therefore, all utilities are again requested that aforesaid information may be provided to CEA positively under intimation to MP SLDC. B. LGBR preparation for the year As per the regulation of Central Electricity Regulatory Commission (Indian Electricity Grid Code) ) First Amendment) Regulations 2011, WRPC shall prepared Loan Generation Balance Report for the year in respect of Western Region. In this context all respective utilities were requested to provide desired information upto 10 th Oct so that same may be communicated to WRPC for necessary action. The desired data still awaited from all respective utilities. It is therefore again requested that following data may be provided to SLDC on priority basis: - 1. Generation Units proposed annual Maintenance programme in respect of your system (also under your control area) for the year April March Annual Maintenance programme in respect of transmission elements in your system for the year April March Month-wise restricted an unrestricted requirement of power (MW) and energy (GWH) for the year April 2018 March Minutes Of 60th OCCM Of MP 16

MADHYA PRADESH POWER TRANSMISSION COMPANY LIMITED STATE LOAD DESPATCH CENTRE, NAYAGAON, RAMPUR, JABALPUR

MADHYA PRADESH POWER TRANSMISSION COMPANY LIMITED STATE LOAD DESPATCH CENTRE, NAYAGAON, RAMPUR, JABALPUR MADHYA PRADESH POWER TRANSMISSION COMPANY LIMITED STATE LOAD DESPATCH CENTRE, NAYAGAON, RAMPUR, JABALPUR Telephone: (0761) 2970089 Fax: (0761) 2664343/2970119 email sldcmpjbp@gmail.com Corporate office:

More information

MADHYA PRADESH POWER TRANSMISSION COMPANY LIMITED

MADHYA PRADESH POWER TRANSMISSION COMPANY LIMITED MADHYA PRADESH POWER TRANSMISSION COMPANY LIMITED STATE LOAD DESPATCH CENTRE, NAYAGAON, RAMPUR, JABALPUR Telephone: (0761) 2970089 Fax: (0761) 2664343/2970119 e-mail sldcmpjbp@gmail.com vkbz,l vks : 9001-2008

More information

Corporate office: Madhya Pradesh Power Transmission Co. Ltd., Block No.2, Shakti Bhawan, Rampur, Jabalpur , CIN-U40109MP2001SGC01

Corporate office: Madhya Pradesh Power Transmission Co. Ltd., Block No.2, Shakti Bhawan, Rampur, Jabalpur , CIN-U40109MP2001SGC01 MADHYA PRADESH POWER TRANSMISSION COMPANY LIMITED STATE LOAD DESPATCH CENTRE, NAYAGAON, RAMPUR, JABALPUR Telephone: (0761) 2970089 Fax: (0761) 2664343/2970119 e-mail sldcmpjbp@gmail.com Corporate office:

More information

'l:l1w m:q;n: government of India. ~~gtf'~ Central Electricity Authority. ~m~~

'l:l1w m:q;n: government of India. ~~gtf'~ Central Electricity Authority. ~m~~ 'l:l1w m:q;n: government of India ~~gtf'~ Central Electricity Authority ~m~~ ~~I Western Regional Power Committee IS/ISO: 9001-2008 q;:fi-3, t:;i1.~ Wr, 3iirfr(' ), ~ - 400093 F-3, MIDC Area, Andheri (East),

More information

SECTION 2 BIDDING DATA

SECTION 2 BIDDING DATA SECTION 2 BIDDING DATA The following specific data for the works to be procured shall complement, amend, or supplement the provisions in Section1, Instructions to Bidders. Whenever there is a conflict,

More information

Agenda for Long Term Access NVVNL Solar Power Projects

Agenda for Long Term Access NVVNL Solar Power Projects Agenda for Long Term Access NVVNL Solar Power Projects NTPC Vidyut Vyapar Nigam Ltd. (NVVNL) vide letter dated 04/11/2014 had applied for Long term Access (LTA) for transfer of 150MW power i.e. 100MW from

More information

Pursuant to Section 205 of the Federal Power Act ( FPA ) 1 and the Commission s

Pursuant to Section 205 of the Federal Power Act ( FPA ) 1 and the Commission s PJM Interconnection 2750 Monroe Boulevard Norristown, PA 19403-2497 Steven R. Pincus Associate General Counsel 610.666.4370 fax 610.666.8211 steven.pincus@pjm.com July 31, 2017 Honorable Kimberly D. Bose

More information

PROJECT TITLE: 4.50 MW AKKIHEBBAL MINI HYDEL SCHEME, CAUVERY HYDRO ENERGY LTD., INDIA

PROJECT TITLE: 4.50 MW AKKIHEBBAL MINI HYDEL SCHEME, CAUVERY HYDRO ENERGY LTD., INDIA PROJECT TITLE: 4.50 MW AKKIHEBBAL MINI HYDEL SCHEME, CAUVERY HYDRO ENERGY LTD., INDIA Document Prepared By: Cauvery Hydro Energy Limited Contact Information Cauvery Hydro Energy Limited 67, Lavina Courts,

More information

SECTION 2 BIDDING DATA

SECTION 2 BIDDING DATA SECTION 2 BIDDING DATA The following specific data for the works to be procured shall complement, amend, or supplement the provisions in Section1, Instructions to Bidders. Whenever there is a conflict,

More information

Payment of Funds

Payment of Funds 30 July 1999 CIRCULAR THE FURTHER EDUCATION FUNDING COUNCIL Payment of Funds 1999-2000 Cheylesmore House Quinton Road Coventry CV1 2WT To Principals of colleges Principals of higher education institutions

More information

EBS IT Meeting July 2016

EBS IT Meeting July 2016 EBS IT Meeting 18 19 July 2016 Conference Call Details Conference call: UK Numbers Tel: 0808 238 9819 or Tel: 0207 950 1251 Participant code: 4834 7876... Join online meeting https://meet.nationalgrid.com/antonio.delcastillozas/hq507d31

More information

SNOW REMOVAL - REQUEST FOR PROPOSAL. Snow Removal/Clearing and Sanding/Salting for Winter Fundy Ocean Research Center for Energy

SNOW REMOVAL - REQUEST FOR PROPOSAL. Snow Removal/Clearing and Sanding/Salting for Winter Fundy Ocean Research Center for Energy Fundy Ocean Research Center for Energy SNOW REMOVAL - REQUEST FOR PROPOSAL Snow Removal/Clearing and Sanding/Salting for Winter 2016-17 Sites 1. FORCE Sub-Station Driveway (portion of Old Black Rock Road),

More information

Jawaharlal Nehru National Solar Mission

Jawaharlal Nehru National Solar Mission Jawaharlal Nehru National Solar Mission National Solar Mission-Phase-I Journey so far NTPC Vidyut Vyapar Nigam Ltd. 1 11/5/2012 Background India is located in the equatorial sun belt of the earth, thereby

More information

POLICY ISSUE (INFORMATION)

POLICY ISSUE (INFORMATION) POLICY ISSUE (INFORMATION) August 12, 2011 SECY-11-0112 FOR: FROM: SUBJECT: The Commissioners Michael R. Johnson, Director /RA/ Office of New Reactors STAFF ASSESSMENT OF SELECTED SMALL MODULAR REACTOR

More information

GENERATOR INTERCONNECTION APPLICATION

GENERATOR INTERCONNECTION APPLICATION GENERATOR INTERCONNECTION APPLICATION FOR BUY-ALL/SELL-ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 20 KW BUT LESS THAN OR EQUAL TO 1 MW Electric Utility Contact Information Great Lakes Energy

More information

Peterborough Distribution Inc Ashburnham Drive, PO Box 4125, Station Main Peterborough ON K9J 6Z5

Peterborough Distribution Inc Ashburnham Drive, PO Box 4125, Station Main Peterborough ON K9J 6Z5 Peterborough Distribution Inc. 1867 Ashburnham Drive, PO Box 4125, Station Main Peterborough ON K9J 6Z5 November 15, 2017 Ontario Energy Board PO Box 2319 27 th Floor, 2300 Yonge St Toronto ON M4P 1E4

More information

Outage Coordination and Business Practices

Outage Coordination and Business Practices Outage Coordination and Business Practices 1 2007 Objectives What drove the need for developing a planning/coordination process. Why outage planning/coordination is crucial and important. Determining what

More information

Administration by the CER of the Carbon Revenue Levy

Administration by the CER of the Carbon Revenue Levy Administration by the CER of the Carbon Revenue Levy DOCUMENT TYPE: REFERENCE: DATE PUBLISHED: QUERIES TO: Decision Paper CER/10/171 23 rd September 2010 Clive Bowers cbowers@cer.ie The Commission for

More information

Effects of Capacitor Bank Installation in a Medium Voltage (MV) Substation

Effects of Capacitor Bank Installation in a Medium Voltage (MV) Substation Effects of Capacitor Bank Installation in a Medium Voltage (MV) Substation Adesina, Lambe Mutalub Department of Engineering & Standardization, Eko Electricity Distribution Plc, 24/25, Marina, Lagos Island,

More information

Section 5. TADS Data Reporting Instruction Manual DRAFT Section 5 and Associated Appendices With Proposed Event Type Numbers

Section 5. TADS Data Reporting Instruction Manual DRAFT Section 5 and Associated Appendices With Proposed Event Type Numbers Section 5 TADS Data Reporting Instruction Manual DRAFT Section 5 and Associated Appendices With Proposed Event Type Numbers Rev. 5/10/2010 1 Section 5 Form for Event ID and Event Type Number Data TO s

More information

Case Study on Fault Analysis Using PMU

Case Study on Fault Analysis Using PMU Case Study on Fault Analysis Using PMU Prithwish Mukhopadhyay General Manager, WRLDC prithwish.mukhopadhyay@posoco.in Abhimanyu Gartia Deputy General Manager, WRLDC agartia@posoco.in Pushpa Seshadri Chief

More information

Derogation Criteria for the Requirements for Generators Network Code

Derogation Criteria for the Requirements for Generators Network Code Derogation Criteria for the Requirements for Generators Network Code Decision Paper Reference: CER/17/084 Date Published: 13/04/2017 Closing Date: 0 Executive Summary Commission Regulation (EU) 2016/631

More information

Agenda for the meeting to discuss Revision of LTA quantum in respect of Kudgi STPS

Agenda for the meeting to discuss Revision of LTA quantum in respect of Kudgi STPS Agenda for the meeting to discuss Revision of LTA quantum in respect of Kudgi STPS 1. LTA pertaining to Kudgi STPS a. KSEB vide letter dated 25-09-2017 (ANNEXURE A) had stated that with installed capacity

More information

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION. Interconnection for Wind Energy ) Docket No. RM

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION. Interconnection for Wind Energy ) Docket No. RM UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION Interconnection for Wind Energy ) Docket No. RM05-4-000 REQUEST FOR REHEARING OF THE NORTH AMERICAN ELECTRIC RELIABILITY COUNCIL

More information

Commissioning and Testing of AVR and PSS

Commissioning and Testing of AVR and PSS Commissioning and Testing of AVR and PSS Excitation System Upgrade and commissioning challenges Vetti Bala Principal C&I Engineer G E N E S I S E N E R G Y L I M I T E D Contents Asset Testing - AVR AVR

More information

REGULATORY INFORMATION REPORT FOR THE QUARTER : 4th

REGULATORY INFORMATION REPORT FOR THE QUARTER : 4th REGULATORY INFORMATION REPORT FOR THE QUARTER : 4th 2007-08 PREPARED BY : "UGVCL,Mehsana" SUBMITTED TO : GUJARAT ELECTRICITY REGULATORY COMMISSION DATE : Jan-08 To March-08 Page 1 C:\Documents and Settings\UB

More information

SUBPART MULTIYEAR CONTRACTING (Revised December 19, 2006)

SUBPART MULTIYEAR CONTRACTING (Revised December 19, 2006) SUBPART 217.1--MULTIYEAR CONTRACTING (Revised December 19, 2006) 217.103 Definitions. As used in this subpart-- Advance procurement means an exception to the full funding policy that allows acquisition

More information

Copernicus Relays. Roles and responsibilities of the Copernicus Relays. user uptake

Copernicus Relays. Roles and responsibilities of the Copernicus Relays. user uptake Copernicus Relays user uptake Roles and responsibilities of the Copernicus Relays The European Commission has launched two Networks, the Copernicus Relays and the Copernicus Academy, to contribute to spreading

More information

UPDATE ELECTRICITY STATEMENT OF OPPORTUNITIES FOR THE NATIONAL ELECTRICITY MARKET

UPDATE ELECTRICITY STATEMENT OF OPPORTUNITIES FOR THE NATIONAL ELECTRICITY MARKET UPDATE ELECTRICITY STATEMENT OF OPPORTUNITIES FOR THE NATIONAL ELECTRICITY MARKET Published: 26 October 2015 ELECTRICITY STATEMENT OF OPPORTUNITIES IMPORTANT NOTICE Purpose AEMO publishes the Electricity

More information

2018 Annual Review of Availability Assessment Hours

2018 Annual Review of Availability Assessment Hours 2018 Annual Review of Availability Assessment Hours Amber Motley Manager, Short Term Forecasting Clyde Loutan Principal, Renewable Energy Integration Karl Meeusen Senior Advisor, Infrastructure & Regulatory

More information

URTDSM Initiative in India and Controlled Islanding using PMU Measurements

URTDSM Initiative in India and Controlled Islanding using PMU Measurements URTDSM Initiative in India and Controlled Islanding using PMU Measurements Akhil Raj Gopal Gajjar Meenal Chougule Narayanan Rajagopal Prashant Navalkar Rajeev Gajbhiye S. A. Soman PowerAnser Labs, IIT

More information

Subject: Availability of New and Revised Public Housing Agency (PHA) Five-Year and Annual Plan Templates and Other Forms

Subject: Availability of New and Revised Public Housing Agency (PHA) Five-Year and Annual Plan Templates and Other Forms Special Attention: U.S. Department of Housing and Urban Development Office of Public and Indian Housing Public Housing Agencies (PHA) NOTICE PIH-2015-18 (HA) Public Housing Hub Office Directors Public

More information

NORDIC AND BALTIC GRID DISTURBANCE STATISTICS 2015

NORDIC AND BALTIC GRID DISTURBANCE STATISTICS 2015 NORDIC AND BALTIC GRID DISTURBANCE STATISTICS 23.01.2017 REGIONAL GROUP NORDIC 1 INTRODUCTION... 4 1.1 DESCRIPTION OF THE REPORT... 4 1.2 CONTACT PERSONS... 5 1.3 VOLTAGE LEVELS IN THE NORDIC AND BALTIC

More information

CAISO Participating Intermittent Resource Program for Wind Generation

CAISO Participating Intermittent Resource Program for Wind Generation CAISO Participating Intermittent Resource Program for Wind Generation Jim Blatchford CAISO Account Manager Agenda CAISO Market Concepts Wind Availability in California How State Supports Intermittent Resources

More information

Establishment of Space Weather Information Service

Establishment of Space Weather Information Service Establishment of Space Weather Information Service For International Air Navigation Raul Romero Technical Officer MET ICAO Headquarters, Montreal NAM/CAR/SAM Seminar on Space Weather and ICAO Weather Information

More information

REVISED UPDATED PREPARED DIRECT SAFETY ENHANCEMENT COST ALLOCATION TESTIMONY OF GARY LENART SAN DIEGO GAS & ELECTRIC COMPANY AND

REVISED UPDATED PREPARED DIRECT SAFETY ENHANCEMENT COST ALLOCATION TESTIMONY OF GARY LENART SAN DIEGO GAS & ELECTRIC COMPANY AND Application No: Exhibit No.: Witness: A.--00 ) In the Matter of the Application of San Diego Gas & ) Electric Company (U 0 G) and Southern California ) Gas Company (U 0 G) for Authority to Revise ) Their

More information

Pool Campus Drive for BE/Diploma Pass Out 2013 batch

Pool Campus Drive for BE/Diploma Pass Out 2013 batch Pool Campus Drive for BE/Diploma Pass Out 203 batch Dear All Students, Subject - Pool Campus Interview of final year 203 batch passed out BE/Diploma students for their engagement as Graduate / Technical

More information

CONTENTS. and 62 of MCDR Flow Diagram for Notice of opening of mine under Rule 20, 2.1 Rule - 18 Beneficiation studies to be carried out 11

CONTENTS. and 62 of MCDR Flow Diagram for Notice of opening of mine under Rule 20, 2.1 Rule - 18 Beneficiation studies to be carried out 11 Part NO. CONTENTS CHAPTER I Flow Diagram for Rule 20, 21, 28, 30, 35, 45, 49, 50, 51 and 62 of MCDR 2017 1.1 Flow Diagram for Notice of opening of mine under Rule 20, PAGE NO. 1 MCDR 2017 1.2 Flow diagram

More information

SUMMARY. Executive Summary: NAVAREA VIII provides the paper of MSI Self Assessment for CPRNW 10

SUMMARY. Executive Summary: NAVAREA VIII provides the paper of MSI Self Assessment for CPRNW 10 CPRNW Meeting 10 Agenda Item 3.2.1 CPRNW10/3/2/VIII MSI Self Assessment - NAVAREA VIII Submitted by INDIA SUMMARY Executive Summary: NAVAREA VIII provides the paper of MSI Self Assessment for CPRNW 10

More information

Performance Improvement of the Radial Distribution System by using Switched Capacitor Banks

Performance Improvement of the Radial Distribution System by using Switched Capacitor Banks Int. J. on Recent Trends in Engineering and Technology, Vol. 10, No. 2, Jan 2014 Performance Improvement of the Radial Distribution System by using Switched Capacitor Banks M. Arjun Yadav 1, D. Srikanth

More information

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester Electrical and Electronics Engineering EE 1352 Power System Analysis (Regulation 2008) Time: Three hours Answer all questions Part A (10

More information

KEELE UNIVERSITY SNOW AND SEVERE WEATHER MANAGEMENT PLAN

KEELE UNIVERSITY SNOW AND SEVERE WEATHER MANAGEMENT PLAN 1.0 Introduction 1.1 It is recognised that severe weather conditions, particularly snow and ice, can make it difficult for people to travel. However, as a residential campus, even during severe weather

More information

J L. INN Exhilarating Hospitality. Date: 18'h September, 2018

J L. INN Exhilarating Hospitality. Date: 18'h September, 2018 To, The Manager Listing Department BSE Limited Phiroze Jeejeebhoy Towers, Dalal Street, Fort, Mumbai 400 001 Date: 18'h September, 2018 Sub: Disclosure of Results of 32'' Annual General Meeting (AGM) Ref:

More information

CHEMICAL MANAGEMENT PLAN

CHEMICAL MANAGEMENT PLAN POLICY EDB CHEMICAL MANAGEMENT PLAN Section I: Annual Review The Chemical Management Plan shall be reviewed at least annually by the Chemical Management Officer and the Chemical Management Committee. Section

More information

Quarterly Review Report on Green Banking Activities of Banks & Financial Institutions and Green Refinance Activities of Bangladesh Bank

Quarterly Review Report on Green Banking Activities of Banks & Financial Institutions and Green Refinance Activities of Bangladesh Bank Quarterly Review Report on Green Banking Activities of Banks & Financial Institutions and Green Refinance Activities of Bangladesh Bank January-March, 2015 Green Banking and CSR Department Bangladesh Bank

More information

Performance Evaluation and Review of System Protection Scheme Design with the help of Synchrophasor Measurements

Performance Evaluation and Review of System Protection Scheme Design with the help of Synchrophasor Measurements Performance Evaluation and Review of System Protection Scheme Design with the help of Synchrophasor Measurements P. Mukhopadhyay V. Pandey Rajkumar Anumasula Chandan Kumar Sunil Patil Srinivas Chitturi

More information

PUB NLH 185 Island Interconnected System Supply Issues and Power Outages Page 1 of 9

PUB NLH 185 Island Interconnected System Supply Issues and Power Outages Page 1 of 9 PUB NLH 1 Page 1 of 1 Q. Provide Hydro s list of outage cause codes and indicate how troublemen are managed and trained to properly use the codes. Explain the method used to report outage causes. A. Hydro

More information

Temporary College Closure Due to Inclement Weather or Other Adverse Conditions.

Temporary College Closure Due to Inclement Weather or Other Adverse Conditions. OTHER TOPICS Index No. X-1 PROCEDURES MEMORANDUM TO: FROM: SUBJECT: MCC Students and Staff Office of the President Temporary College Closure Due to Inclement Weather or Other Adverse Conditions. DATE:

More information

Public Disclosure Copy. First Part of the Second Phase of the Niger Basin Water Resources Development and Sustainable

Public Disclosure Copy. First Part of the Second Phase of the Niger Basin Water Resources Development and Sustainable Public Disclosure Authorized First Part of the Second Phase of the Niger Basin Water Resources Development and Sustainable Ecosystems AFRICA Western Africa Water Global Practice IBRD/IDA Investment Project

More information

YORK REGION DISTRICT SCHOOL BOARD. Procedure #NP464.0, Snow/Ice Clearance and Removal

YORK REGION DISTRICT SCHOOL BOARD. Procedure #NP464.0, Snow/Ice Clearance and Removal YORK REGION DISTRICT SCHOOL BOARD Procedure #NP464.0, Snow/Ice Clearance and Removal Application The Snow/Ice Clearance and Removal procedure addresses the practices to be followed with regards to the

More information

RESOLUTION NOW, THEREFORE, BE IT RESOLVED BY THE BOARD OF SUPERVISORS OF THE CORKSCREW FARMS COMMUNITY DEVELOPMENT DISTRICT:

RESOLUTION NOW, THEREFORE, BE IT RESOLVED BY THE BOARD OF SUPERVISORS OF THE CORKSCREW FARMS COMMUNITY DEVELOPMENT DISTRICT: RESOLUTION 2017-08 A RESOLUTION OF THE BOARD OF SUPERVISORS OF THE CORKSCREW FARMS COMMUNITY DEVELOPMENT DISTRICT APPROVING PROPOSED BUDGET(S) FOR FISCAL YEAR 2017/2018 AND SETTING A PUBLIC HEARING THEREON

More information

Facilities Management

Facilities Management Policy Number: 700.20 Title: Chemical Fume Hood Policy Implementation Date: 2002 Last Audited: August, 2017 Last Revised: October 23rd, 2017 Facilities Management Introduction The laboratory chemical fume

More information

Public Disclosure Copy

Public Disclosure Copy Public Disclosure Authorized Public Disclosure Authorized Public Disclosure Authorized Public Disclosure Authorized SOUTH ASIA South Asia Transport & ICT Global Practice IBRD/IDA Investment Project Financing

More information

Public Disclosure Copy. Implementation Status & Results Report Strengthening Institutional Capacity for Government Effectiveness Project (P149176)

Public Disclosure Copy. Implementation Status & Results Report Strengthening Institutional Capacity for Government Effectiveness Project (P149176) Public Disclosure Authorized AFRICA Burundi Governance Global Practice IBRD/IDA Investment Project Financing FY 2015 Seq No: 4 ARCHIVED on 10-Jul-2017 ISR28718 Implementing Agencies: Government of Burundi,

More information

March 5, British Columbia Utilities Commission 6 th Floor, 900 Howe Street Vancouver, BC V6Z 2N3

March 5, British Columbia Utilities Commission 6 th Floor, 900 Howe Street Vancouver, BC V6Z 2N3 Tom A. Loski Chief Regulatory Officer March 5, 2010 British Columbia Utilities Commission 6 th Floor, 900 Howe Street Vancouver, BC V6Z 2N3 16705 Fraser Highway Surrey, B.C. V4N 0E8 Tel: (604) 592-7464

More information

Approved by: A. Cherrie Epps, Ph.D., President and Chief Executive Officer

Approved by: A. Cherrie Epps, Ph.D., President and Chief Executive Officer Page 1 of 5 Retired: Revised: Approved by: A. Cherrie Epps, Ph.D., President and Chief Executive Officer Subject: Office of General Counsel/Compliance - Inclement Weather and Emergency Closing Policy PURPOSE:

More information

Public Disclosure Copy. Implementation Status & Results Report Upper Cisokan Pumped Storage Hydro-Electrical Power (1040 MW) Project (P112158)

Public Disclosure Copy. Implementation Status & Results Report Upper Cisokan Pumped Storage Hydro-Electrical Power (1040 MW) Project (P112158) Public Disclosure Authorized EAST ASIA AND PACIFIC Indonesia Energy & Extractives Global Practice IBRD/IDA Specific Investment Loan FY 2011 Seq No: 9 ARCHIVED on 27-Jun-2016 ISR23590 Implementing Agencies:

More information

MINISTRY OF POWER O/O CHIEF CONTROLLER OF ACCOUNTS SEWA BHAWAN, RK PURAM

MINISTRY OF POWER O/O CHIEF CONTROLLER OF ACCOUNTS SEWA BHAWAN, RK PURAM MINISTRY OF POWER O/O CHIEF CONTROLLER OF ACCOUNTS SEWA BHAWAN, RK PURAM NEW DELHI-110066 Statement of Receipts and Disbursements/Cash Flow for the year 2017-18 Head/Item Actuals up to COPPY % Variation

More information

Testimony. Before the Subcommittee on Environment, Energy, and Natural Resources, Committee on Government Operations House of Representatives

Testimony. Before the Subcommittee on Environment, Energy, and Natural Resources, Committee on Government Operations House of Representatives GAO United States General kccounting Office Testimony Before the Subcommittee on Environment, Energy, and Natural Resources, Committee on Government Operations House of Representatives For Release on Delivery

More information

13 August Dear Shareholders UPDATE. I am writing to update shareholders on the profit impact of the recent poor harvest and associated matters.

13 August Dear Shareholders UPDATE. I am writing to update shareholders on the profit impact of the recent poor harvest and associated matters. 13 August 2014 Dear Shareholders UPDATE I am writing to update shareholders on the profit impact of the recent poor harvest and associated matters. 2014 Profit Due principally to the lower than average

More information

Implementation of the NPT Safeguards Agreement in the Republic of Korea

Implementation of the NPT Safeguards Agreement in the Republic of Korea International Atomic Energy Agency Board of Governors GOV/2004/84 Date: 11 November 2004 Restricted Distribution Original: English For official use only Item 4(c) of the provisional agenda (GOV/2004/82)

More information

Economic and Social Council

Economic and Social Council United Nations Economic and Social Council Distr.: General 18 July 2016 Original: English Committee of Experts on Global Geospatial Information Management Sixth session New York, 3-5 August 2016 Item 2

More information

MINISTRY OF POWER O/O CHIEF CONTROLLER OF ACCOUNTS SEWA BHAWAN, RK PURAM

MINISTRY OF POWER O/O CHIEF CONTROLLER OF ACCOUNTS SEWA BHAWAN, RK PURAM MINISTRY OF POWER O/O CHIEF CONTROLLER OF ACCOUNTS SEWA BHAWAN, RK PURAM NEW DELHI-110066 Statement of Receipts and Disbursements/Cash Flow for the year 2017-18 Head/Item Actuals up to COPPY % Variation

More information

PPA PROCUREMENT PLAN (Textual Part)

PPA PROCUREMENT PLAN (Textual Part) PPA PROCUREMENT PLAN (Textual Part) Project information: Nigeria Electrification Project P161885 Project agency: Rural Electrification Agency Date of the Plan: [Jan 2018] Period covered by this Plan: [PPA]

More information

Request for Empanelment

Request for Empanelment Request for Empanelment (Empanelment is method/procedure/way to seek technical & financial or financial quotation from eligible firm/organization/academic institute to short list eligible contender for

More information

ESTA governance Quality Assurance System for Seed Treatment and Treated Seed

ESTA governance Quality Assurance System for Seed Treatment and Treated Seed ESTA governance Quality Assurance System for Seed Treatment and Treated Seed Version 2.1 Contents On the scope and purpose of this Quality Assurance system... 1 Legislation... 1 Governance aspects covered

More information

Failure Analysis of Medium Voltage Capacitor Banks: The Egyptian Experience

Failure Analysis of Medium Voltage Capacitor Banks: The Egyptian Experience Failure Analysis of Medium Voltage Capacitor Banks: The Egyptian Experience Mohamed A. EL-HADIDY Dalal H. HELMI Tech. Consultant dr_alhadidy@hotmail.com Studies and Research Dept. dalalhelmi@hotmail.com

More information

System Impact Assessment Addendum #2 Greenfield & St. Clair Energy Centres

System Impact Assessment Addendum #2 Greenfield & St. Clair Energy Centres IESO_REP_0292 System Impact Assessment Addendum #2 Greenfield & St. lair Energy entres onnection Assessment & Approval Process Issue 3.0 Greenfield Energy entre AA I 2004-167 Applicant: Greenfield Energy

More information

OTTER POINT ADVISORY PLANNING COMMISSION. Notice of Meeting on Tuesday, June 5, 2018 at 7 p.m.

OTTER POINT ADVISORY PLANNING COMMISSION. Notice of Meeting on Tuesday, June 5, 2018 at 7 p.m. OTTER POINT ADVISORY PLANNING COMMISSION Notice of Meeting on Tuesday, June 5, 2018 at 7 p.m. Juan de Fuca Local Area Services Building, #3 7450 Butler Road, Otter Point, BC 1. Elections 2. Approval of

More information

PPA PROCUREMENT PLAN (Textual Part)

PPA PROCUREMENT PLAN (Textual Part) PPA PROCUREMENT PLAN (Textual Part) Project information: Nigeria Electrification Project P161885 Project agency: Rural Electrification Agency Date of the Plan: [Jan 2018] Period covered by this Plan: [PPA]

More information

Internal Audit Report

Internal Audit Report Internal Audit Report Right of Way Mapping TxDOT Internal Audit Division Objective To determine the efficiency and effectiveness of district mapping procedures. Opinion Based on the audit scope areas reviewed,

More information

DEMAND FORECASTING PROTOCOL

DEMAND FORECASTING PROTOCOL FIRST REPLACEMENT VOLUME NO. II Original Sheet No. 443 DEMAND FORECASTING PROTOCOL FIRST REPLACEMENT VOLUME NO. II Original Sheet No. 444 DEMAND FORECASTING PROTOCOL Table of Contents DFP 1 OBJECTIVES,

More information

Operations Report. Tag B. Short, Director South Region Operations. Entergy Regional State Committee (ERSC) February 14, 2018

Operations Report. Tag B. Short, Director South Region Operations. Entergy Regional State Committee (ERSC) February 14, 2018 Operations Report Tag B. Short, Director South Region Operations Entergy Regional State Committee (ERSC) February 14, 2018 1 Winter Operations Highlights South Region Max Gen Event Regional Dispatch Transfer

More information

International Workshop on Wind Energy Development Cairo, Egypt. ERCOT Wind Experience

International Workshop on Wind Energy Development Cairo, Egypt. ERCOT Wind Experience International Workshop on Wind Energy Development Cairo, Egypt ERCOT Wind Experience March 22, 21 Joel Mickey Direcr of Grid Operations Electric Reliability Council of Texas jmickey@ercot.com ERCOT 2 2

More information

CASE No. 33 of In the matter of Determination of Generic Tariff for Renewable Energy for FY

CASE No. 33 of In the matter of Determination of Generic Tariff for Renewable Energy for FY Before the MAHARASHTRA ELECTRICITY REGULATORY COMMISSION 13 th Floor, Centre No.1, World Trade Centre, Cuffe Parade, Mumbai- 400 005 Tel: 22163964/65/69 Fax: 22163976 E-mail: mercindia@merc.gov.in Website:

More information

Energy saving in electromechanical equipment with power coefficient correction. Dimitris Al. Katsaprakakis Aeolian Land S.A.

Energy saving in electromechanical equipment with power coefficient correction. Dimitris Al. Katsaprakakis Aeolian Land S.A. Energy saving in electromechanical equipment with power coefficient correction Dimitris Al. Katsaprakakis Aeolian Land S.A. www.aiolikigi.gr Introduction Electricity production companies (utilities) provide

More information

AM 500A 500 WATT AM 1A 1 KILOWATT AM BROADCAST TRANSMITTERS. October, 1999 IM No

AM 500A 500 WATT AM 1A 1 KILOWATT AM BROADCAST TRANSMITTERS. October, 1999 IM No AM 500A 500 WATT AM 1A 1 KILOWATT AM BROADCAST TRANSMITTERS October, 1999 IM No. 597 1112 EQUIPMENT LOST OR DAMAGED IN TRANSIT. When delivering the equipment to you, the truck driver or carrier s agent

More information

Technical Requirements. Version No. 1.0 Effective Date 10/1/2008

Technical Requirements. Version No. 1.0 Effective Date 10/1/2008 PURPOSE This document applies to wind Generators and describes technical standards that such wind Generators must satisfy to be qualified as a Participating Intermittent Resource (PIR) under the CAISO

More information

Implementation Status & Results Djibouti Djibouti Power Access and Diversification Project (P086379)

Implementation Status & Results Djibouti Djibouti Power Access and Diversification Project (P086379) Public Disclosure Authorized Public Disclosure Authorized The World Bank Implementation Status & Results Djibouti Djibouti Power Access and Diversification Project (P086379) Operation Name: Djibouti Power

More information

Hydra Fault Current Limiting HTS Cable to be Installed in the Consolidated Edison Grid

Hydra Fault Current Limiting HTS Cable to be Installed in the Consolidated Edison Grid Hydra Fault Current Limiting HTS Cable to be Installed in the Consolidated Edison Grid J. McCall, J. Yuan, D. Folts, N. Henderson, American Superconductor D. Knoll, Southwire M. Gouge, R. Duckworth, J.

More information

The World Bank Indonesia National Slum Upgrading Project (P154782)

The World Bank Indonesia National Slum Upgrading Project (P154782) Public Disclosure Authorized EAST ASIA AND PACIFIC Indonesia Social, Urban, Rural and Resilience Global Practice Global Practice IBRD/IDA Investment Project Financing FY 2017 Seq No: 2 ARCHIVED on 19-May-2017

More information

Economic Operation of Power Systems

Economic Operation of Power Systems Economic Operation of Power Systems Section I: Economic Operation Of Power System Economic Distribution of Loads between the Units of a Plant Generating Limits Economic Sharing of Loads between Different

More information

The World Bank Caribbean Regional Communications Infrastructure Program (P114963)

The World Bank Caribbean Regional Communications Infrastructure Program (P114963) Public Disclosure Authorized LATIN AMERICA AND CARIBBEAN Caribbean Transport & ICT Global Practice IBRD/IDA Adaptable Program Loan FY 2012 Seq No: 9 ARCHIVED on 25-Jan-2017 ISR26209 Implementing Agencies:

More information

CEDAR CREST MUTUAL DOMESTIC WATER CONSUMERS & SEWAGE WORKS ASSOCIATION. December 31, 2016

CEDAR CREST MUTUAL DOMESTIC WATER CONSUMERS & SEWAGE WORKS ASSOCIATION. December 31, 2016 CEDAR CREST MUTUAL DOMESTIC WATER CONSUMERS Table of Contents Page Official Roster i Independent Accountants Report on Applying Agreed Upon Procedures 1 Schedule of Revenues and Expenditures Budget and

More information

FINAL REPORT EVALUATION REVIEW OF TVA'S LOAD FORECAST RISK

FINAL REPORT EVALUATION REVIEW OF TVA'S LOAD FORECAST RISK Memorandum from the Office of the Inspector General Robert Irvin, WT 9C-K FINAL REPORT EVALUATION 2012-14507 REVIEW OF TVA'S LOAD FORECAST RISK As part of a series of reviews to evaluate the Tennessee

More information

Chapter 3 AUTOMATIC VOLTAGE CONTROL

Chapter 3 AUTOMATIC VOLTAGE CONTROL Chapter 3 AUTOMATIC VOLTAGE CONTROL . INTRODUCTION TO EXCITATION SYSTEM The basic function of an excitation system is to provide direct current to the field winding of the synchronous generator. The excitation

More information

Geomagnetic Disturbance Operating Plan

Geomagnetic Disturbance Operating Plan APPLICABILITY: Reliability Coordinator (RC) I. Purpose The purpose of this is three-fold: To define the manner in which the geomagnetic disturbance (GMD) space weather notifications are disseminated, To

More information

INCLEMENT WEATHER CLOSING CODES

INCLEMENT WEATHER CLOSING CODES INCLEMENT WEATHER CLOSING CODES Code 0 Code 1 Code 2 Code 3 Code 4 Code 5 Code 6 ALL operations are closed and no employees should report to work. Transportation personnel, maintenance personnel, ALL custodial

More information

The World Bank Indonesia National Slum Upgrading Project (P154782)

The World Bank Indonesia National Slum Upgrading Project (P154782) Public Disclosure Authorized EAST ASIA AND PACIFIC Indonesia Social, Urban, Rural and Resilience Global Practice Global Practice IBRD/IDA Investment Project Financing FY 2017 Seq No: 4 ARCHIVED on 04-Apr-2018

More information

The World Bank Bangladesh Modern Food Storage Facilities Project (P120583)

The World Bank Bangladesh Modern Food Storage Facilities Project (P120583) Public Disclosure Authorized SOUTH ASIA Bangladesh Agriculture Global Practice IBRD/IDA Investment Project Financing FY 2014 Seq No: 8 ARCHIVED on 10-Nov-2017 ISR28544 Implementing Agencies: Government

More information

LOS ANGELES UNIFIED SCHOOL DISTRICT REFERENCE GUIDE

LOS ANGELES UNIFIED SCHOOL DISTRICT REFERENCE GUIDE REFERENCE GUIDE TITLE: NUMBER: ISSUER: Chemical Safety Coordinators REF-1563.3 Yi Hwa Kim, Interim Director Enrique G. Boull t Chief Operating Officer ROUTING All Secondary Schools All Middle Schools All

More information

Responsibilities: Effective Date: November Revision Date: February 8, VP, Facilities and Construction Management. Issuing Authority:

Responsibilities: Effective Date: November Revision Date: February 8, VP, Facilities and Construction Management. Issuing Authority: Title: Chemical Hygiene Written Program Effective Date: November 2005 Revision Date: February 8, 2017 Issuing Authority: Responsible Officer: VP, Facilities and Construction Management Director Environmental

More information

F F FAULT CURRENT Prospective. 1. Introduction. 2. Types of fault conditions

F F FAULT CURRENT Prospective. 1. Introduction. 2. Types of fault conditions FAULT CURRENT F F13-13 FAULT CURRENT - Contents 1. Introduction 2. Types of fault conditions 3 fault current must be determined 3.1 Purposes for which of prospective fault current magnitudes are used 3.2

More information

Congestion Alleviation using Reactive Power Compensation in Radial Distribution Systems

Congestion Alleviation using Reactive Power Compensation in Radial Distribution Systems IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 11, Issue 6 Ver. III (Nov. Dec. 2016), PP 39-45 www.iosrjournals.org Congestion Alleviation

More information

Status of implementation of the INSPIRE Directive 2016 Country Fiches. COUNTRY FICHE Malta

Status of implementation of the INSPIRE Directive 2016 Country Fiches. COUNTRY FICHE Malta Status of implementation of the INSPIRE Directive 2016 Country Fiches COUNTRY FICHE Malta Introduction... 1 1. State of Play... 2 1.1 Coordination... 2 1.2 Functioning and coordination of the infrastructure...

More information

Multivariate Regression Model Results

Multivariate Regression Model Results Updated: August, 0 Page of Multivariate Regression Model Results 4 5 6 7 8 This exhibit provides the results of the load model forecast discussed in Schedule. Included is the forecast of short term system

More information

Department of Energy OffIce of Worker Protection Programs and Hazards Management Radiological Control Technical Position RCTP

Department of Energy OffIce of Worker Protection Programs and Hazards Management Radiological Control Technical Position RCTP OffIce of Worker Protection Programs and Hazards Management Issue: The occupational radiation protection regulations established by the (DOE) and Nuclear Regulatory Commission (NRC) are similar in many

More information

entertainment network (India) limited

entertainment network (India) limited entertainment network (India) limited Corporate Office: Trade Gardens, Ground Floor, Kamala Mills Compound, Senapati Bapat Marg, Lower Parel (West), Mumbai 400 013, India. Tel: 022 6753 6983. Fax: 022

More information

Implementation Status & Results Burundi Burundi - Emergency Energy Project from IDA CRW (P122217)

Implementation Status & Results Burundi Burundi - Emergency Energy Project from IDA CRW (P122217) Public Disclosure Authorized Public Disclosure Authorized The World Bank Implementation Status & Results Burundi Burundi - Emergency Energy Project from IDA CRW (P122217) Operation Name: Burundi - Emergency

More information

R E A D : E S S E N T I A L S C R U M : A P R A C T I C A L G U I D E T O T H E M O S T P O P U L A R A G I L E P R O C E S S. C H.

R E A D : E S S E N T I A L S C R U M : A P R A C T I C A L G U I D E T O T H E M O S T P O P U L A R A G I L E P R O C E S S. C H. R E A D : E S S E N T I A L S C R U M : A P R A C T I C A L G U I D E T O T H E M O S T P O P U L A R A G I L E P R O C E S S. C H. 5 S O F T W A R E E N G I N E E R I N G B Y S O M M E R V I L L E S E

More information