1 6 Engineering Surveying T J M Kennie BSc, MAppSci (Glasgow), ARICS, MInstCES Lecturer in Engineering Surveying, University of Surrey Contents 6.1 Introduction 6/ Branches of surveying 6/ Principles of surveying 6/ Errors in surveying 6/3 6.2 Surveying instrumentation 6/ Angular measurement using the theodolite 6/ Distance measurement 6/ Height measurement using the level 6/ Surveying methods 6/ Horizontal control surveys 6/ Detail surveys 6/ Vertical control surveys 6/ Deformation monitoring surveys 6/ Computers in surveying 6/ Digital mapping and ground modelling systems 6/ Land information systems 6/ Acknowledgements 6/28 References 6/28 Bibliography 6/29 This page has been reformatted by Knovel to provide easier navigation.

2 6.1 Introduction The work of the land surveyor can be classified into three main areas of responsibility. Firstly, he is concerned with the recording of measurements which allow the size and shape of the Earth to be determined. Secondly, and primarily, he is involved in the collection, processing and presentation of the information necessary to produce maps and plans. Thirdly, he may be required to locate on the surface of the Earth the exact positions to be taken up by new roads, dams or other civil engineering works. As a consequence of the diverse nature of the land surveyor's duties, several distinct branches of the subject have evolved Branches of surveying Geodetic surveys are carried out on a national or international basis in order to locate points large distances apart. This type of survey acts as a framework for 'lower order' surveys. In order to ensure high accuracy, the effect of factors such as the curvature of the Earth on observations must be considered and the necessary corrections applied. Topographic surveys are concerned with the small-scale representation of the physical features of the Earth's surface. Frequently, the data necessary for such an operation will be provided by the use of aerial photography. The science of taking measurements from photography in order to produce maps is known as photogrammetry. Topographic surveys are often the responsibility of a national organization such as, for example, the Ordnance Survey in the UK. Hydrographic surveys, in contrast, involve the representation of the surface of the seabed. The end-product is normally a navigational chart. In recent years this branch has become increasingly important with the development of the offshore oil industry. In this case, in addition to the production of charts, the surveyor may be required to position large structures such as oil production platforms. This type of operation would normally necessitate the use of ground and satellite electronic position-fixing equipment. Cadastral surveys relate to the location and fixing of land boundaries. In many countries in the world, e.g. Australia, the information supplied by the cadastral surveyor may be an integral part of a land registration system. Finally, engineering surveys are required for the preparation of design drawings relating to civil engineering works such as roads, dams or airports. The surveys are normally at a large scale, with scales of 1:500 and 1:1000 being most common. Many of these branches require highly specialized knowledge, beyond the scope of this chapter. In view of this, the aim in this chapter will be to discuss: (1) those aspects of the subject which are required in order to carry out simple surveys for engineering projects; (2) the processes involved in carrying out precise surveys for deformation monitoring projects; and (3) the use of computers in surveying for digital mapping and ground modelling Principles of surveying In spite of the diverse nature of land surveying, it is possible to define certain basic principles which are common to all branches of the subject. These principles have proved over the years to be vital if accurate surveys are to be conducted. The first and most important principle is the provision of an initial framework before observing and fixing the detail of a survey. This process is ofteri known as providing control. It is essential to ensure that the positions of the control points are known to a higher order of accuracy than those of the subsidiary points. By satisfying this principle it is possible to ensure that errors, which inevitably occur, do not accumulate but are contained within the control framework. A second and perhaps more obvious principle is that of planning. All too often it is tempting to rush into a survey without consideration for an overall plan. Of particular importance is the need to define a job specification. This is indispensable since the relationship between cost and accuracy is not linear and an increase in accuracy may have a disproportionate effect on cost. For example, if a distance of 50Om is to be determined to an accuracy of either 5 or 0.5 mm, the cost ratio of the respective accuracies may be of the order of 1:300. It is important, therefore, to choose techniques and instruments appropriate to the survey specification. Of equal importance is the need to plan the reconnaissance stage. Before starting a task it is essential to examine the area carefully, considering all the possible ways of doing the survey and then selecting the most suitable method. Remember, 'time spent on reconnaissance and planning is never wasted'. A third principle is the need to ensure that sufficient independent checks are incorporated into the survey to eliminate or minimize errors. It is important that the checking system is included at all stages of the survey from fieldwork and computations to the final plotting. In addition, the checking system should be independent and not solely a repeat of the initial measurement. Examples of independent checks are: Fieldwork: measure both diagonals of a quadrilateral measure distances in both directions measure angles using different parts of the theodolite circle Computations: use the summation check on angle observations of geometric figures, e.g. sum of interior angles (2«-4) x 90 levelling booking cross-checks Plotting: plot positions of important points by using angles and distance and also using coordinates. The final principle is that of safeguarding. Safeguarding is equally important at all stages of the survey, and refers to the process of ensuring that the survey results can be replicated if accidental, or other, damage occurs to the survey markers or field observations. Thus, it is important when constructing permanent survey markers to take 'witness or reference measurements' to points of prominent detail in the vicinity of the point. Linear measurements of this type enable the point to be relocated if it is damaged, or alternatively if it is difficult to find. The latter situation can often occur with road projects. In many instances there may be a gap of many years between initial survey and final setting-out. During this time the permanent survey markers may become overgrown with vegetation and hence difficult to locate. The use of witness marks and measurements can often be of crucial importance if the permanent marks are to be relocated. Safeguarding of field observations is also of paramount importance. Thus, it is considered good practice to produce abstract sheets from the surveyor's fieldbook at the end of each day. These abstract sheets should summarize the major results from the fieldbook (e.g. rounds of angles, mean distance etc.) and should be carefully filed in the survey office. By such a process the possibility of several days' work being lost if the fieldbook is damaged or misplaced can be eliminated Errors in surveying It is an unfortunate and often misunderstood fact that all measurements are affected by errors. So often, when confronted with the question: 'How accurate do you want the survey to

3 be?', or 'How accurately do you want this point located?', the glib answer 'Exactly!', or 'Spot on!', is given as the reply by a prospective client. If, in addition, the question of errors is raised, it is quickly dispensed with the comment: 'Errors don't occur if you do it properly.' The answer is correct in one respect, i.e. in relation to mistakes, or, more correctly, gross errors. These should not occur if a survey is carried out according to the basic principles of surveying. However, other types of errors do occur which can be much more difficult to handle. Systematic errors, as the name suggests, are errors which follow a pattern or system. Errors of this type are normally related to the variations in physical conditions which can occur when a measurement is made. For example, a steel tape is normally known to be a certain length at some standard temperature. If the temperature under which a measurement is made varies from this standard, a systematic error will occur. By knowing the coefficient of linear expansion a value for the expansion of the tape can be determined and a correction applied. Systematic errors whose effect can be modelled mathematically are, hence, eliminated. Random errors, in contrast, do not follow a standard pattern and are entirely based on the laws of probability. These errors, or rather variations in measurement, will occur after gross and systematic errors have been eliminated. The measurement of a distance by taping can again be taken as an example. It is often not appreciated that the same distance measurement made under the same physical conditions with the same tape will produce different answers. Since it is assumed that the measurements will follow a normal distribution they can be examined using standard statistical techniques. The following formula can therefore be applied to the analysis of random errors: arithmetic mean = Jc = -,, n (6.1) where /= 1, 2,..., n are the observed values and n denotes the number of observed values. The arithmetic mean is significant because it is often taken to be the closest approximation to the 'true' value and as such is known as the most probable value (m.p.v.). The difference between the m.p.v. and the observed value is known as a residual (v). A term often used in order to estimate the precision of a series of measurements is the standard error, where standard error of a single observation is: 0-±( ZV *\ '«'- ± \i^l) (6.2) and standard error of the arithmetic mean is: M ~ ± \n^) (6.3) For surveying purposes, the terms 'standard error', 'standard deviation' and 'root mean square (r.m.s.) error' are synonymous. All such terms are used to give an indication of the precision of the result, i.e. the degree of agreement between successive measurements. High precision may not be indicative of high accuracy, since accuracy is related to the proximity of the measurement to the true value. If, however, all the effects of the bias caused by systematic errors have been eliminated, these indices of precision may also be used as indices of accuracy. For example, suppose an angle has been measured 9 times and the subsequent error analysis indicates that CT^ = 3" and a w = 0.81". What does this information tell us? Firstly, it indicates that the angle has been measured to a high precision. Secondly, it indicates that, statistically, there is a 68% chance or probability of the standard error of a single measurement being less than 3". Furthermore, if one extends the confidence limit to a value 3 times the standard error, or 9", then statistically the probability that the error will be less than 9" is now 99.7% with only a 0.3% chance of the error being greater than 9". This confidence limit is often applied as a rejection criterion to a group of observations. Any observation with a residual greater than 3 times the standard error may then be rejected, on the basis that it is highly unlikely that the variation is solely a consequence of random effects. Similar reasoning would apply to the standard error of the arithmetic mean. Further information on errors and their treatment can be found in Cooper' and Mikhail and Grade Surveying instrumentation Surveying is essentially concerned with the direct measurement of three fundamental quantities: (1) the angle subtended at a point; (2) the distance between two points; and (3) the height of a point above some datum, normally mean sea-level. From the measurement of these three quantities, it is then possible to compute the three-dimensional positions of points. With the exception of electronic methods of determining distance, the instruments used by the surveyor have not radically changed in principle for 40 to 50 years. The advances in technology may have reduced the size and increased the efficiency of the instruments, but the fundamental principles remain unchanged Angular measurement using the theodolite The theodolite is used for the measurement of horizontal and vertical angles. In simple terms, a theodolite consists of a Table 6.1 Characteristics of some modern theodolites Type of theodolite: Typical example: Country of manufacture: Direct reading to By estimation to Telescope magnification Telescope aperture (mm) Sensitivity of plate Level per 2 mm run Weight of instrument (kg) 1" Precise Kern DKM 2A-E Switzerland 1" 0.1" 32 x 40 20" " Engineers Sokkisha TM20ES Japan 20" 5" 28 x 45 30" ' Builders Zeiss(Ober.)TH51 W. Germany 10' r 2Ox 30 45" 2.2 Compass Wild TO Switzerland r 30" 2Ox 28 8' 2.9 Electronic Kern E-2 Switzerland 1" 32 x

4 telescope mounted on a platform which may be levelled to form a horizontal plane by means of a simple spirit bubble. Angles are measured by pointing the telescope at targets and establishing the difference between readings on a circular protractor mounted on the level platform. There is a bewildering choice of theodolites available. Table 6.1 lists the characteristics of a selection of commonly available modern theodolites. The broad distinction can be made between those instruments which measure angles and those such as compass and gyro theodolites which measure bearings, relative to magnetic north and to true north respectively General construction of the theodolite There are certain fundamental relationships and components which are common to all theodolites. Before examining the detailed construction of a modern glass arc theodolite, it is important to appreciate the geometrical arrangement of the axes of a theodolite, as illustrated in Figure 6.1. Figure 6.2 Wild T-2 one second theodolite (Wild Heerbrugg) Figure 6.1 Theodolite axes Telescope objective In this ideal arrangement the vertical axis is vertical, the trunnion axis is perpendicular to it and hence horizontal, and the line of collimation is perpendicular to the trunnion axis. Unfortunately, it is not possible during the manufacturing process to ensure that these orthogonal relationships occur exactly. Similarly, during use over a period of years, wear may occur which may also alter these conditions. The extent to which a theodolite fails to satisfy them can be measured by a series of instrument tests which may be carried out in the field. If, subsequently, the instrument is found to be out of adjustment, the instrument should be returned to the manufacturer or a specialist instrument technician for adjustment. Details of the field tests and methods of adjustment may be found in Cooper. 3 If, however, a modern theodolite is treated with care, and a suitable observational technique is employed, regular servicing should be all that is required in order to obtain good results. The detailed construction of a modern 1 s precise theodolite is shown in Figures 6.2 and 6.3. Examination of these figures illustrates that the theodolite consists essentially of three distinct parts: (1) Base. This consists of two main components: the tribrach and the horizontal circle. The tribrach can be screwed securely to the tripod and, by means of three footscrews, the instrument may be levelled. The circle is made of glass with photographically etched graduations. It is normally graduated in a clockwise manner. A circle-setting screw is also usually provided and the base will generally house an Standard Upper plate (alidade) Horizontal circle Tribrach Trivet stage Figure 6.3 Construction of a theodolite Trunnion axis Telescope eyepiece Plate level Standing axis Footscrew optical plummet. This consists of a small eyepiece with a line of sight which is deviated by 90 in order to point vertically down. By this process it is possible to centre the instrument precisely over a ground point. In some cases the optical plummet may be housed in the alidade. (2) Alidade. This rotatable upper part of the theodolite may also be known as the upper plate. The alidade rotates about the vertical axis. Mounted on the alidade is the plate-level bubble which indicates whether the instrument is level. By

5 means of clamps and slow-motion screws it is possible to rotate and clamp the alidade relative to the base. (3) Telescope. Attached to the trunnion axis of the theodolite is the telescope. The telescope magnifies the object and, by the use of cross-hairs, allows the exact bisection of the target. Focusing of the object and the cross-hairs is carried out using separate focusing screws. A further clamp and slow-motion screw allow precise pointing of the telescope in a vertical plane. Angles of elevation or depression are measured using a vertical circle also attached to the trunnion axis. Prior to measuring a vertical angle it may be necessary to set the altitude bubble. However, most modern theodolites employ an automatic compensating mechanism. In these cases vertical angles may be recorded after the plate level has been set, without recourse to an additional bubble setting. When the vertical circle is to the left of the telescope, the theodolite is in what is conventionally called the face left (FL) position. Conversely, when the vertical circle is to the right of the telescope as it views an object, the theodolite is in the face right (FR) position. micrometer screw of the theodolite. Movement of this screw enables the observer to read, on an auxiliary scale, the lateral shift required in order to bring the image of the main-scale degree graduations into coincidence with the index marks which are built into the optical path. Using this technique it is possible to resolve directly to 20" of arc if the micrometer is reading from one side of the circle. Resolution direct to 1" is possible if a mean-reading optical micrometer is used. In this case, readings from two points diametrically opposite are meaned in order to eliminate the effects of any circle eccentricity. Figures 6.5 and 6.6 illustrate two typical examples of the circle reading systems for both the single- and mean-reading optical micrometers Circle reading By projecting daylight through the standards of the theodolite, it is possible to illuminate the glass scale of both the horizontal and vertical circles. In order to resolve a direction to a higher precision than that to which the circle has been graduated, an optical micrometer is employed. Optical micrometers are the modern equivalent of verniers. The principle of operation involves the use of a plane parallel-sided block of glass as shown in Figure 6.4. When the glass is in the normal position, as shown by position (a), light passing through will be uninterrupted. Rotation of the block of glass, however, produces a lateral shift of the incident beam as shown by position (b). This rotation is controlled by the Figure 6.5 Single reading optical micrometer: circle reading Wild T-1A 05 13' 30" (Wild Heerbrugg) Parallel plate micrometer Uninterrupted light path Circle graduations Refracted light path Figure 6.6 Mean reading optical micrometer: circle reading Wild T ' 44.3" (Wild Heerbrugg) Figure 6.4 Parallel plate micrometer Field procedure Potentially the theodolite is a very precise instrument. It is, however, necessary to follow a strict procedure both in setting-

6 up the instrument and in observing if this potential is to be realized. Incorrect use of a theodolite will undoubtedly result in poor results, regardless Of how precise the instrument may be. Setting-up. Setting-up a theodolite prior to observations being taken consists of three separate operations: centring, levelling and focusing. Centring involves positioning the instrument exactly over a ground point. This may be achieved by means of either a plumb bob suspended from the instrument or a centring rod or an optical plummet. The process of centring and levelling should be considered as iterative in nature, becoming increasingly more precise after each operation. Levelling the theodolite carefully is a necessary prerequisite for precise measurements. The following sequence of operations must be carried out in order to level a theodolite: (1) Approximately level the instrument using the small circular bubble. (2) Set the plate-level bubble parallel to any two footscrews, such as A and B in Figure 6.7(a). Rotate both footscrews together or apart until the bubble is in a central position. Level bubble (3) Rotate the alidade until the bubble is now approximately perpendicular to the initial position, as shown in Figure 6.7(b). Using footscrew C only, centralize the bubble. (4) Return to the initial position and again centralize the bubble using footscrews A and B. Repeat (2) and (3) until the bubble is central in both positions. (5) Rotate the alidade through 180 until the position shown by Figure 6.7(c) is achieved. If the bubble does not remain in a central position, move the bubble until it is in a position midway between a central position and its initial position. (6) Rotate the alidade until the position illustrated by Figure 6.7(d) is achieved. Using footscrew C, move the bubble into the same position as in Figure 6.7(c). The bubble should then remain in the same off-centre position for any alignment of the alidade. The final step before observations begin is to focus both the cross-hairs and the object to which observations will be made. It is important to ensure that both images appear clear and sharp. In addition, it is critical that parallax does not exist. Parallax refers to the apparent movement of the cross-hairs and objects relative to each other when the observer moves his head. It is caused by the image of the object not lying in the same vertical plane as the cross-hairs. If this occurs, the focusing operation must be repeated until it is eliminated. Observational procedure. A strict observational procedure is essential if both human and instrumental errors are to be reduced to a minimum. Consider the problem of measuring the angle shown in Figure 6.8. Level footscrews Figure 6.8 Angle measurement Figure 6.7 Levelling the theodolite The observational procedure which should be adopted is as follows. A booking procedure is illustrated by Table 6.2. (1) Point with telescope in the FL position to the target at X and record the horizontal circle reading, e.g ' 30". (2) Point on FL to target Z and record, e.g '40". Table 6.2 Booking and reduction of theodolite readings Station Y Height of Inst: Observer.Booker...Date.Weather. TO FL FR MEAN ANGLE COMMENTS Round 1 X n U Z ^ 1U Round 2 X Z U ^ ^ Mean angle: 40 05'13"

7 (3) Change face to FR and point to target Z and record circle reading ' 50". (4) Point on FR to target X and record direction ' 40". In order to reduce the effect of instrument maladjustments to a minimum, the mean of the FL and FR minutes and seconds readings to the same point is averaged and the value entered in the mean column. The difference between the mean circle readings is then derived and entered in the angle column. This constitutes one round of angles. The base setting screw should then be adjusted and the process repeated in order to increase the precision of the angle measurement. A minimum of two rounds is necessary for the least precise measurements; up to sixteen rounds may be required for very precise operations Distance measurement The second fundamental quantity which it is necessary to measure is distance. A wide variety of techniques can be used for the determination of distance. The general distinction can, however, be made between direct, optical and electronic methods. All of the techniques discussed are capable of varying levels of precision depending on the degree of sophistication of the instrumentation and the observational techniques adopted Direct distance measurement (DDM) The simplest method of measuring distance is that of physically measuring the distance with a tape. In the past invar tapes were used for the precise measurement of baselines for triangulation networks. Nowadays, DDM is generally confined to either the precise measurement of short distances for setting-out or control purposes or the less precise measurement of the detailed dimensions of a building or land parcel. There are basically two types of tape in common use. Fibreglass measuring tapes are manufactured from multiple strands of fibreglass coated with PVC. They are waterproof and normally either 30 or 50 m in length. Fibreglass tapes are generally used for detail measurements and have largely superseded the linen tapes which were available previously. For more precise measurements it is necessary to use steel bands. These are typically either 30, 50 or 10Om in length. In order to obtain high precision with either type of tape, it is essential that it is periodically checked against a standard reference tape, the length of which is known to a higher order of accuracy than that of the tape being checked. If a significant variation exists, a standardization correction should be applied. In addition, it is vital that suitable attention is paid to the effect of variations in slope, temperature and tension which may necessitate appropriate corrections being applied to the measured distance. The corrections (C 1, C 2 and C 3 respectively) are: Slope: C 1 = -L(I -cos 0) (6.4) where 9 slope angle, and L = measured slope distance or: C,= -Atf/2L where Ah = height difference between end-points Temperature: C 2 =±al(/ m -g (6.5) where / m = measured temperature in the field, / s = temperature at which the tape was standardized, usually 2O 0 C, and a = coefficient of linear expansion ( for steel bands) Tension: C 3 = ± L(T n -TJAE where T m = measured tension, T s = standard tension, A = crosssectional area of tape, and E= Young's modulus for the tape, typically 200 kn/mm 2 = N/mm 2 Miller 4 details the typical accuracy levels which can be achieved with steel tapes Optical distance measurement (ODM) As an alternative to the direct method of measuring distance, it is also possible to measure distance indirectly by optical methods. The development of ODM began over two centuries ago. James Watt is recorded as having used this approach in his survey of the West of Scotland in Although many instruments and improvements have been introduced since then, they all essentially involve the solution of the same geometrical problem. All methods of ODM are based on the solution of an isosceles triangle, as shown in Figure 6.9. The triangle consists of three important components: the parallactic angle a, the base length B (which may be either in a horizontal or vertical plane), and Z), the horizontal bisector of the base of the triangle. By knowing the relationship between the three components, the horizontal distance D between two points can be determined. Figure 6.9 Optical distance measurement (ODM) Two methods of solution are possible: either an instrument with a fixed parallactic angle is used and the variable base B is measured (Figure 6.10) or a base of fixed length is set up and the variable parallactic angle is measured (Fig. 6.11). In both cases, the variable quantity is proportional to the horizontal distance. By defining the mathematical relationship between the fixed and variable quantities it is therefore possible to determine the horizontal distance. Tacheometry. The first approach described above (fixed angle, variable base) is commonly known as tacheometry or more correctly as vertical staff stadia tacheometry. It is normally used for the measurement of distance where a proportional error of between 1/500 and 1/1000 is acceptable, e.g. in picking-up survey detail points. All modern theodolites have a diaphragm consisting of a main horizontal cross-hair and two horizontal stadia lines

8 Figure 6.10 ODM: fixed angle, variable base where D 5 =slope distance, and 6 vertical angle measured by the theodolite. Therefore: > H = 1005 cos 2 O (6.9) Ah^ = H 1 + V- m (6.10) where zl/i AB = difference in height between A and B, H 1 = height of instrument (trunnion axis to ground), m = middle hair reading, and V= difference in height between middle-hair reading and trunnion axis = 505 sin 29 (6.11) Several self-reducing tacheometers have also been designed. The main advantage of these instruments is their ability to compensate for the effect of the inclination of the theodolite telescope and, hence, allow the direct determination of horizontal distance without additional computation. Two notable examples of this type of instrument are the Wild RDS vertical staff self-reducing tacheometer and the Kern DK- RT horizontal bar double-image self-reducing tacheometer. Details of the construction and use of these instruments may be found in Hodges and Greenwood, 5 and Smith. 6 In recent years, the manufacture of these precise optical devices has ceased, their place being taken by low-cost electronic measuring devices. Figure 6.11 ODM: fixed base, variable angle spaced either side of it. These stadia lines define the fixed parallactic angle. If the theodolite telescope is sighted on to a levelling staff and the readings of the outer lines noted, the difference in the readings, the staff intercept (s), will be directly proportional to the horizontal distance between the instrument and the staff. Generally, the distance between the stadia lines is designed in such a manner that the horizontal distance Z> H between the instrument and staff is given by: Subtense bar. The second approach (fixed base, variable angle) is commonly known as the subtense or horizontal subtense bar method. The method is normally confined to the measurement of distance for control purposes. Using this approach, distances may be determined with a proportional error of up to 1/ The instrumentation required consists of a subtense bar, normally 2m long, and a one-second theodolite, such as the Wild T2. The bar has targets mounted at each end of an invar strip. The strip is protected by a surrounding aluminium strip in order to ensure that, for all practical purposes, the length of the bar remains constant at 2 m. The bar is set up and oriented at right angles to the line of sight of the theodolite, as shown in Figure D H =loqs (6.7) For inclined sights the geometry is as shown in Figure Hence: /) s = 100(5 cos O) (6.8) Figure 6.13 Subtense bar Figure 6.12 Stadia tacheometry: inclined sights The horizontal parallactic angle a is measured with the theodolite. Irrespective of the vertical angle to the bar, the horizontal distance is given by: Z> H = ifccot(a/2) (6.12) with b = 2m /> H = cot(a/2) (6.13) For distances greater than 10Om it is advisable to subdivide the distance to be measured or, alternatively, to use the auxiliary base method (Hodges and Greenwood, 5 and Smith. 6 ).

9 Subtense methods are also tending to be superseded by lowcost electronic methods. Nevertheless, many organizations still possess this type of equipment and for many projects it is a very suitable technique to adopt Electronic distance measurement (EDM) Development. The first generation of EDM instruments was developed in the early 1950s. Typical of the early meters were the Swedish Geodimeter (GEOdetic Distance METER) and the South African Tellurometer instrument. The former, an electrooptical instrument, used visible light measurement, whilst the latter used high-frequency microwaves. Both instruments were primarily developed for military geodetic survey purposes and had the ability to measure long distances, up to 80 km in the case of the Tellurometer, to a precision of a few centimetres. They were also, however, bulky, heavy and expensive in comparison to their modern-day equivalents. During the late 1960s, developments in microelectronics and low-power light-emitting diodes led to the emergence of a second generation of EDM instruments. These electro-optical instruments utilized infra-red radiation as the measuring signal and were developed for the short range (<5km) market. In addition, they were considerably smaller, lighter and less expensive than their predecessors. Probably the best-known example is the Wild DI-IO Distomat. The introduction of microprocessors into the survey world in the early 1970s led to the introduction of a third series of EDM instruments. With this group it became possible, not only to determine slope distance, but also to carry out simple computational tasks in the field. For example, the facility became available to compute automatically the corrected horizontal distance and difference in height between two points by manual input of the vertical angle read from the theodolite. Electronic distance measurement instruments of this type had also been reduced in size to the extent that the EDM unit could be theodolite-mounted. The Wild DI-3 is a typical example of this type of instrument. The most recent short-range EDM instruments are similar to the previous group, but have several additional features worthy of mention. Firstly, the technology now exists to sense automatically the inclination of the EDM unit and therefore to be able to compute automatically the horizontal distance between two points. The Geodimeter 220 (Figure 6.14) has this facility. This instrument also has the ability to measure to a moving target, or track, a useful feature for setting-out purposes. By using an additional unit it is also possible to have one-way speech communication between the instrument and target positions, again valuable when setting-out. This instrument can also be connected to a Geodat 126 hand-held data collector (Figure 6.14), which is able to store automatically distance information from the EDM unit. Other relevant information (numeric or alphanumeric) can be input manually via the keyboard. The Geodimeter 220 has a range of 1.6km with one prism and 2.4km with three prisms determined to a standard error of ± 5 mm± 5 parts per million (p.p.m.) of the distance. The last development in the field of EDM instrumentation is the electronic tacheometer or 'total station'. The former term is more appropriate in view of the different interpretations, by the instrument manufacturers, of the term total station. In essence, an electronic tacheometer is an instrument which combines an EDM unit with an electronic theodolite. Hence, such instruments are capable of measuring, automatically, horizontal and vertical angles and also slope and/or horizontal distance. The majority also have the facility to derive other quantities such as heights or coordinates and store this data in a data collector. Two designs of instrument have evolved during the last 5 years. Figure 6.14 (Geotronics) (a) Geodimeter 220; (b) Geodat 126 data collector The first, the integrated design, consists of one unit which, generally, houses the electronic circle-reading mechanism and the EDM unit. The Wild TCI Tachymat and the Geodimeter 140 (Figure 6.15) are representative of this range of instrument. The second design approach is the modular concept. In this case, the EDM instrument and the electronic theodolite are separate units which can be operated independently. This approach tends to be more flexible and enables units to be exchanged and upgraded as developments occur; it may also be a more cost effective solution for many organizations. The Kern E-2 and Wild T-2000 Systems (Figure 6.16) are representative of this design of electronic tacheometer. Finally, mention should be made of high-precision EDM instruments. These instruments have been designed for projects such as dam deformation or foundation monitoring where extremely high precision is necessary. Instruments which are

10 Figure 6.15 Electronic tacheometer, integrated design: Geodimeter 140 Figure 6.17 High-precision EDM: Comrad Geomensor 204DME 10km with a standard error of ±0.1 mm±0.5p.p.m. Further up-to-date technical information on many modern EDM instruments can be found in Burnside." Figure 6.16 Electronic tacheometer, modular design: Wild T-2000, with DI4 representative of this design include the Tellurometer MA-IOO Jaakola, 7 the Kern ME-3000 Mekometer (see Froome, 8 Meir- Hirmer, 9 and Murname 10 ) and the Comrad Geomensor 204 DME (Figure 6.17). The latter instrument has a range of up to Principle of measurement. Although there is a wide variety of EDM instruments on the market, they all measure distance using the same basic principle. This can be most clearly illustrated by means of the flow diagram (Figure 6.18), which relates specifically to electro-optical instruments. An electromagnetic (EM) signal of wavelength equal to either 560 nm (visible light), 680 nm (HeNe laser) or 910 nm (infra-red) is generated. This signal is subsequently amplitude-modulated before being transmitted through the optical system of the instrument towards a retro-reflector mounted at the end of the line to be measured. The signal is then retro-reflected, or redirected through 180, by a precisely ground glass corner cube. Cheaper acrylic corner cubes may also be used. 12 ' 13 This reflected signal is consequently directed towards the receiving optical system. On entering the optical system of the instrument, the signal is converted by means of a photomultiplier into an electrical signal. The next stage involves the measurement of the phase difference between the transmitted and received signals and the conversion of this information into distance. Figure 6.19 shows the path taken by an EM signal radiated by an EDM instrument together with the instantaneous phase of the signal. It is apparent that the distance X-Y-X travelled by the EM signal is equivalent to twice the distance to be measured. Also, this distance can be seen to be related to the modulation wavelength (A) and the fraction of the wavelength (/4A) by the following relationship:

11 Electromagnetic ^ Transmitting and 2 > = 2.4« (6.16) Dat t a signal optic>retroreflector Phase measurement * ootic Receiving I Slope distance I Corrections Atmospheric Additive constant * Slope Height above MSL Scale I factor Corrected ut"! Y^ Figure 6.18 Principle of operation: electro-optical distance measurement EDM Instrument Retro-reflector Figure 6.19 Double path measurement using EDM 2D = >d + A A (6.14) where n is an unknown integer number of wavelengths. The determination of the distance therefore involves resolving both AX and n. Phase detectors are used to determine AX which effectively measures the phase difference between the transmitted and received signal and, hence, allows the fractional part of the distance less than one full wavelength to be determined. The value of n can be determined by using two or more EM signals of slightly varying wavelengths. For example, assume 2D = 25.5, A 1 = 2.5 m and A 2 = 2.4 m then: ID = 2.5«, +0.5 (6.15) Assuming «, =«2 for short distances, solving for n leads to «=10 (6.17) Substituting in Equations (6.15) or (6.16) D= 12.75m (6.18) This entire process is fully automatic in modern instruments, taking approximately 10 to 20 s to complete. As with any other method of distance measurement, it is necessary to apply several corrections to the measured slope distance in order to determine the corrected horizontal distance. The first correction to be applied is the atmospheric or refractive index correction. Just as a steel tape varies in length with variations in temperature and pressure so, too, does the modulation wavelength of an EDM instrument. It is therefore necessary to measure the temperature, pressure and, in some cases, relative humidity during measurements. A correction is then applied to compensate for the variation in modulation wavelength caused by variations in atmospheric conditions. Many instruments have the facility to compute automatically and apply this correction to observations directly in the field. Temperature, pressure and relative humidity readings are taken and the appropriate reading to be set on the refractive index correction dial is read from a nomogram. A second important correction is the additive zero or prism constant. This correction represents the difference between the electro-optically determined distance and the correct length of line. It is a combination of the errors due to prism offset and the variation in the physical and electrical centres of the EDM instrument. Many manufacturers design their corner cube reflectors in order to eliminate this correction totally. However, if several different types of corner cube are being used, it is essential that a full field calibration be undertaken in order to determine the correction. (See Schwendener, 14 Ashkenazi and Dodson, 15 and Sprent and Zwart 16 for further details of the procedure for instrument calibration.) The slope correction is the same as for DDM. For distances measured above or below mean sea-level (MSL) a correction is necessary in order to reduce the distance to its equivalent at MSL. The correction (C 4 ) is given by: C 4 = (-LHJ/R (6.19) where H m is the mean height of the instrument and reflector above MSL and R is the radius of the Earth (6370 km). Finally, if the distance is to be used for computation of coordinates on the national grid, the horizontal distance at MSL must be multiplied by the local scale factor. For the Transverse Mercator projection, the local scale factor (F) may be approximately calculated from: F= [1.228 x 10~ 14 x (E O) 2 ] (6.20) where E is the mean local national grid easting in metres of the line to be measured Height measurement using the level The third and final quantity which is measured is height or, more correctly, height difference. This is achieved by means of a level.

12 The fundamental principle of the level is illustrated by Figures 6.20 and Figure 6.20 represents the situation which normally exists when the level is initially set up. In this case, the standing axis of the level and the vertical do not coincide. Hence, the line of collimation of the level will not be horizontal. Figure 6.21 represents the geometrical arrangement of the axis when the instrument has been levelled using the procedure outlined in 'Setting up' in section 6.2. L3. It can be seen that completion of this procedure ensures that, firstly, the standing and vertical axes are made coincident and, secondly, if the Horizontal line of sight Line of collimation of level Figure 6.20 Horizontal line of sight Spirit bubble Vertical Standing axis of level Geometry of the level axes: before levelling Line of collimation of level Figure 6.21 Spirit bubble Vertical Geometry of the level axes: after levelling instrument is in perfect adjustment, the line of collimation of th< level is coincident with a horizontal line of sight. Three distinct types of level are available for engineerin survey purposes: (1) the dumpy level; (2) the tilting level; and (3 the automatic level. Spirit bubble Objective Bubble-adjusting screw Line of collimation Dumpy level The dumpy level was so named because of the rather short telescopes which were used with early versions of this instrument. The construction of a typical dumpy level is shown in Figure The most distinctive feature of this type of level is that the axis of the telescope is fixed rigidly to the standing axis of the instrument. In order to satisfy the condition that both the vertical and standing axes are coincident, the standard levelling procedure outlined in section is carried out. Rotation of the telescope will now define a horizontal plane. In the past, this type of level was very popular for general engineering work. It has, however, been replaced in recent years by the automatic level Tilting level The tilting level is a more precise instrument than the dumpy level. Figure 6.23 illustrates the main features. In contrast to the dumpy level, the telescope is not rigidly attached to the standing axis but is able to be tilted in a vertical plane about a pivot point X, by means of a tilting screw. Objective Telescope Levelling screws Figure 6.23 Spirit bubble Pivot X Bubble-adjusting screw Level construction: tilting level Eyepiece - Line of collimation Tilting screw Trivet stage Standing axis Prior to recording an observation, the instrument is approximately levelled. This is normally achieved by means of a 'balland-socket' arrangement and a small circular bubble. In order to set the standing axis exactly vertical, the tilting screw is turned and the main bubble altered until a coincident position (Figure 6.24), as viewed through a small auxiliary eyepiece, is achieved. If the telescope is now rotated horizontally to sight a second or subsequent point, it is important to relevel the main bubble by means of the tilting screw. Telescope Eyepiece Tribrach Levelling screws Trivet stage Standing axis Figure 6.22 Level construction: dumpy level Before levelling After levelling (a) (b) Figure 6.24 Coincidence bubble-reading system

13 Automatic level This type of level is not, as the name suggests, totally automatic. Human intervention is still necessary. However, one major source of human error, that of setting the bubble, is replaced by an automatic compensating system. In common with the tilting level, approximate levelling is still necessary. The tedious and error-prone bubble-setting process, however, is eliminated. As with the dumpy level, the instrument defines a horizontal plane when rotated. The automatic level therefore combines the speed of operation of the dumpy level with the precision of the tilting level. Figure 6.25 illustrates the main components of this type of level. The essential feature of the instrument is the incorporation of an automatic optical-mechanical compensating mechanism. The use of such a system ensures that the line of collimation as defined by the centre cross-hair will trace out a horizontal plane irrespective of the fact that the optical axis of the instrument may not be exactly horizontal. It is, however, necessary to level the instrument approximately in order to ensure that the line of sight is within range of the compensating mechanism. Objective Telescope Levelling screws Optical-mechanical compensator Eyepiece Line of collimation Circular spirit level Tribrach Trivet stage Figure 6.26 Zeiss (Jena) Ni 007 automatic precise level Figure 6.25 Standing axis Level construction: automatic level For high-precision levelling, e.g. in order to detect the settlement of a building, a parallel plate micrometer (PPM), attached to the front of the objective of the telescope normally forms part of the construction of the level. Almost all precise levels in use nowadays are of the automatic design and, ideally, should be designed so that the PPM forms an integral part of the instrument, rather than being an 'add-on' attachment. One such instrument is the Zeiss (Jena) Ni 007 (Figure 6.26). This particular instrument also has an unusual compensating mechanism which results in the 'periscope'-type appearance of the instrument. The PPM operates by deflecting the line of sight to the nearest whole staff graduation, the amount of displacement which is required being measured by a micrometer. This value is then added to the staff reading to give the final staff reading. This is illustrated in Figure Clearly in an operation such as precise levelling it is important to minimize the effects of systematic errors. This is partially overcome by a suitable field procedure, 17 and partially by ensuring that the staff is maintained at a constant length. In order to achieve this, an invar staff with stabilizing arms and a level bubble attachment is normally used A Laser level Lasers are monochromatic, coherent and highly collimated light sources, initially developed in the 1940s. Until relatively Figure 6.27 levelling Deflected line of sight Reading = A Undeflected line of sight Parallel Plate Micrometer Operation of a parallel plate micrometer for precise recently, their use has tended to be restricted to the field of pure scientific research. Nowadays, however, the laser is a widely used tool in land surveying for distance measurement, alignment, 18 and levelling purposes. There are essentially two types of laser in use in civil engineering: (1) the fixed-beam; and (2) the rotating beam laser. The fixed-beam laser projects a single highly collimated light beam to a single point. This design is particularly suited to alignment problems. The rotating-beam laser, in contrast, takes the fixedbeam source and rotates it at high speed, so forming a plane (either in the horizontal or vertical sense), of laser light. This design is more appropriate for levelling or grading purposes. The Spectra-Physics EL-I shown in Figure 6.28 is a typical example of the laser levels currently in use. The laser beam in

14 Figure 6.30 Two-peg test Figure 6.28 Spectra-Physics EL-1 (Spectra-Physics) this case forms a 360 horizontal plane which is detected by a portable sensing device also shown in Figure The laser unit automatically corrects for any error in level of the instrument, providing it has been roughly levelled to within 8 of the vertical. An accuracy of ± 5 to 6 mm per 100 m up to a maximum range of 300 m can be achieved with this type of instrument Collimation error So far the assumption has been made that once the standing axis of the level has been set truly vertical, then the line of collimation will be horizontal. This may not always be the case. If this condition does not occur, then a collimation error is said to exist. This is illustrated in Figure If accurate levelling is to be achieved, it is essential that a regular testing procedure is established in order to check the magnitude of any collimation error that may exist. Line of collimation Horizontal plane Figure 6.29 Collimation error Collimation error A common field procedure which can be used to test a level is known as the 'two-peg test'. The procedure is as follows: (1) Set out two points A and B approximately 50m apart, as shown in Figure 6.30(a). The level is set up at the mid-point of AB and levelled as in section (2) A reading is taken on to a staff held at points A and B and the difference between the two readings calculated. This value represents the true difference in height between A and B. Any collimation error which exists will have an equal effect on both readings and, hence, will not affect the difference between the readings. In this case the difference in height is = 0.483m. (3) The instrument is now moved to a point C close to the staff at B (about 3 to 5 m away), as in Figure 6.30(b). The reading on staff B is recorded (1.301). If no collimation error exists, the reading on staff A should be equal to the reading on staff B ± the true difference in height as established in (2), i.e = 1.784m. (4) The actual observed reading on staff A is now recorded (1.794). Any discrepancy between this value and that derived previously in (3) indicates the magnitude and direction of any collimation error. For example, in this case, the error would be = 10mm per 50m. An error of up to 2 to 3 mm over this distance would be acceptable. If, however, the error is greater than this, the instrument should be adjusted. Unlike theodolite adjustments, this type of adjustment can normally be performed without any great difficulty by the engineer and the procedure is as follows. For the dumpy and automatic level: alter the position of the cross-hairs until the centre cross-hair is reading the value which should have been observed from step (3) above. This is achieved by loosening the small screws around the eyepiece which control the position of the cross-hairs. For the tilting level: again alter the position of the centre cross-hair until it is reading the value previously determined in (3), in this case by tilting the telescope using the tilting-screw. Unfortunately, this will displace the bubble. The bubble must, therefore, be centralized by means of the bubble-adjusting screw. 6.3 Surveying methods Horizontal control surveys Any engineering survey or setting-out project, regardless of its size, requires a control framework of known co-ordinated points. Several different control methods are available as des-

CIV : THEODOLITE ADJUSTMENT

CIV : THEODOLITE ADJUSTMENT Unit CIV2202: Surveying 10.1 CIV2202.10: THEODOLITE ADJUSTMENT Table of Contents PREVIEW...2 Introduction...2 Objectives...2 Readings...2 REGULAR CHECKS...2 Tripod...2 Footscrews...2 Tribrach head...3

More information

INTRODUCTION TO ENGINEERING SURVEYING (CE 1305)

INTRODUCTION TO ENGINEERING SURVEYING (CE 1305) INTRODUCTION TO ENGINEERING SURVEYING (CE 1305) Linear Measurements Sr Dr. Tan Liat Choon Email: tanliatchoon@gmail.com Mobile: 016-4975551 1 EDM, TOTAL STATION, PRISM AND POLE 2 ELECTROMAGNETIC DISTANCE

More information

Leveling. 3.1 Definitions

Leveling. 3.1 Definitions Leveling 3.1 Definitions Leveling is the procedure used to determine differences in elevation between points that are remote from each other. Elevation is a vertical distance above or below a reference

More information

Chapter-2 Direct Measurement Indirect Measurement Method of linear measurement Taping corrections Optical measurement Tachometry EDM Measurement

Chapter-2 Direct Measurement Indirect Measurement Method of linear measurement Taping corrections Optical measurement Tachometry EDM Measurement Chapter-2 Direct Measurement Indirect Measurement Method of linear measurement Taping corrections Optical measurement Tachometry EDM Measurement 1 2 3 4 5 6 7 Methods There are 3 methods of making linear

More information

Objective questions for Practical Examination (CBCS scheme) Introduction to Surveying CE-112

Objective questions for Practical Examination (CBCS scheme) Introduction to Surveying CE-112 Objective questions for Practical Examination (CBCS scheme) Introduction to Surveying CE-112 1. The curvature of the earth s surface, is taken into account only if the extent of survey is more than i)

More information

VALLIAMMAI ENGINEERING COLLEGE Department of Civil Engineering CE6304 SURVEYING I Questions Bank UNIT-I FUNDAMENTALS AND CHAIN SURVEYING Part A 1) Define surveying. 2) What are the types of surveying?

More information

PRIMARY CONTROL SURVEYS

PRIMARY CONTROL SURVEYS STATE CONTROL SURVEY SPECIFICATIONS FOR PRIMARY CONTROL SURVEYS Now Obsolete Caution: This document has been prepared by scanning the original Specifications for Primary Control Surveys - 1984 and using

More information

WATTS MICROPTIC ALIDADE OPERATING INSTRUCTIONS 20-7

WATTS MICROPTIC ALIDADE OPERATING INSTRUCTIONS 20-7 WATTS MICROPTIC ALIDADE 20-7 OPERATING INSTRUCTIONS WATTS Operating Instructions for the WATTS MICROPTIC ALIDADE SA100 SA101 RANK PRECISION INDUSTRIES METROLOGY DIVISION Survey Equipment Sales Langston

More information

UNIT-4 THEODOLITE SURVEYING

UNIT-4 THEODOLITE SURVEYING UNIT-4 THEODOLITE SURVEYING The Theodolite The measurement of horizontal and vertical angles and it is the most precise instrument designed for points on line, prolonging survey lines, establishing grades,

More information

Practice Questions - Revision

Practice Questions - Revision Practice Questions - Revision Question 1: (a) The data from a survey, are shown below. Use either the Rise and Fall method or the Height of Plane of Collimation (HPC) method to reduce the data. Use arithmetic

More information

Measurement of Distance and Elevation Equipment and Procedures

Measurement of Distance and Elevation Equipment and Procedures AMRC 2012 MODULE 2 Measurement of Distance and Elevation Equipment and Procedures CONTENTS Overview... 2-1 Objectives... 2-1 Procedures... 2-1 2.1 Introduction to Methods of Distance Measurement... 2-3

More information

Surveying Prof. Bharat Lohani Indian Institute of Technology, Kanpur. Module 5 Lecture 1

Surveying Prof. Bharat Lohani Indian Institute of Technology, Kanpur. Module 5 Lecture 1 Surveying Prof. Bharat Lohani Indian Institute of Technology, Kanpur (Refer Slide Time: 00:20) Module 5 Lecture 1 Welcome to this another lecture on basic surveying. Today we are going to start a new module.

More information

DETERMINATION OF AREA OF POLYGON BY CHAIN AND CROSS STAFF SURVEY 1. AIM:

DETERMINATION OF AREA OF POLYGON BY CHAIN AND CROSS STAFF SURVEY 1. AIM: Expt. No: 2 Date: DETERMINATION OF AREA OF POLYGON BY CHAIN AND CROSS STAFF SURVEY 1. AIM: To determine the area of a given field with define boundary by conducting cross staff survey. 2. INSTRUMENTS REQUIRED:

More information

AGE 303 AGRICULTURAL LAND SURVEYING INTRODUCTION Land Surveying: It has to do with the determination of relative spatial location of points on or

AGE 303 AGRICULTURAL LAND SURVEYING INTRODUCTION Land Surveying: It has to do with the determination of relative spatial location of points on or AGE 303 AGRICULTURAL LAND SURVEYING INTRODUCTION Land Surveying: It has to do with the determination of relative spatial location of points on or near the surface of the earth. It is the art of measuring

More information

Digital Land Surveying And Mapping(DLS&M) Dr. Jayanta Kumar Ghosh Department of Civil Engineering Indian Institute of Technology, Roorkee

Digital Land Surveying And Mapping(DLS&M) Dr. Jayanta Kumar Ghosh Department of Civil Engineering Indian Institute of Technology, Roorkee Digital Land Surveying And Mapping(DLS&M) Dr. Jayanta Kumar Ghosh Department of Civil Engineering Indian Institute of Technology, Roorkee Lecture - 17 Total Station Introduction Welcome students, this

More information

SURVEYING 1 CE 215 CHAPTER -3- LEVEL AND LEVELING

SURVEYING 1 CE 215 CHAPTER -3- LEVEL AND LEVELING Civil Engineering Department SURVEYING 1 CE 215 CHAPTER -3- LEVEL AND LEVELING 1 CHAPTER -3- LEVEL AND LEVELING 2 1 CONTENTS 1. Level instrument 2. Bubble 3. Tripod 4. Leveling staff 5. Definitions 6.

More information

CHENDU COLLEGE OF ENGINEERING & TECHNOLOGY DEPARTMENT OF CIVIL ENGINEERING SUB CODE & SUB NAME : CE6404 SURVEYING II

CHENDU COLLEGE OF ENGINEERING & TECHNOLOGY DEPARTMENT OF CIVIL ENGINEERING SUB CODE & SUB NAME : CE6404 SURVEYING II CHENDU COLLEGE OF ENGINEERING & TECHNOLOGY DEPARTMENT OF CIVIL ENGINEERING SUB CODE & SUB NAME : CE6404 SURVEYING II UNIT I CONTROL SURVEYING PART A (2 MARKS) 1. What is the main principle involved in

More information

COPYRIGHTED MATERIAL INTRODUCTION CHAPTER 1

COPYRIGHTED MATERIAL INTRODUCTION CHAPTER 1 CHAPTER 1 INTRODUCTION 1.1 INTRODUCTION We currently live in what is often termed the information age. Aided by new and emerging technologies, data are being collected at unprecedented rates in all walks

More information

GEOMATICS ENGINEERING

GEOMATICS ENGINEERING GEOMATICS ENGINEERING CHAPTER 2 Direct and Indirect Distance Measurement Methods Distance Measurement Methods Equipment Classification Usage Fieldwork procedure Booking system Adjustment and plotting Introduction

More information

It is the art of determining the relative positions of natural and artificial features on the earth s surface, vertically and horizontally.

It is the art of determining the relative positions of natural and artificial features on the earth s surface, vertically and horizontally. SVG 105 Lectures Notes March 2011 BASIC INTRODUCTION TO SURVEYING DEFINITION OF SURVEYING It is the art of determining the relative positions of natural and artificial features on the earth s surface,

More information

Optics. Measuring the line spectra of inert gases and metal vapors using a prism spectrometer. LD Physics Leaflets P

Optics. Measuring the line spectra of inert gases and metal vapors using a prism spectrometer. LD Physics Leaflets P Optics Spectrometer Prism spectrometer LD Physics Leaflets P5.7.1.1 Measuring the line spectra of inert gases and metal vapors using a prism spectrometer Objects of the experiment Adjusting the prism spectrometer.

More information

71- Laxmi Nagar (South), Niwaru Road, Jhotwara, Jaipur ,India. Phone: Mob. : /

71- Laxmi Nagar (South), Niwaru Road, Jhotwara, Jaipur ,India. Phone: Mob. : / www.aarekh.com 71- Laxmi Nagar (South), Niwaru Road, Jhotwara, Jaipur 302 012,India. Phone: 0141-2348647 Mob. : +91-9799435640 / 9166936207 1. An invar tape made of an alloy of: A. Copper and steel. B.

More information

COPYRIGHTED MATERIAL INTRODUCTION CHAPTER 1

COPYRIGHTED MATERIAL INTRODUCTION CHAPTER 1 CHAPTER 1 INTRODUCTION 1.1 INTRODUCTION We currently live in what is often termed the information age. Aided by new and emerging technologies, data are being collected at unprecedented rates in all walks

More information

Experiment #4: Optical Spectrometer and the Prism Deviation

Experiment #4: Optical Spectrometer and the Prism Deviation Experiment #4: Optical Spectrometer and the Prism Deviation Carl Adams October 2, 2011 1 Purpose In the first part of this lab you will set up and become familiar with an optical spectrometer. In the second

More information

AU-5029 GURU GHASIDAS VISHWAVIDYALAYA, BILASPUR (C.G.) INSTITUTE OF TECHNOLOGY DEPARTMENT OF CIVIL ENGINEERING B.TECH

AU-5029 GURU GHASIDAS VISHWAVIDYALAYA, BILASPUR (C.G.) INSTITUTE OF TECHNOLOGY DEPARTMENT OF CIVIL ENGINEERING B.TECH AU-5029 GURU GHASIDAS VISHWAVIDYALAYA, BILASPUR (C.G.) INSTITUTE OF TECHNOLOGY DEPARTMENT OF CIVIL ENGINEERING B.TECH 2 nd YEAR, III rd SEMESTER SUBJECT: SURVEYING-I COURSE CODE: 21CE02T Max Marks: 60

More information

Total station LEICA TPS

Total station LEICA TPS Total station LEICA TPS405 200 The perfect solution for all sites Rugged, adaptable total station with accurate angle measurements, dual-axis compensator, powerful EDM, data output in any format, and application

More information

Sub. Code:

Sub. Code: (ISO/IEC - 700-005 Certified) Model Answer: Summer 08 Code: 05 Important Instructions to examiners: ) The answers should be examined by key words and not as word-to-word as given in the model answer scheme.

More information

Measurement of Horizontal Distances. the distance between two points means the horizontal distance

Measurement of Horizontal Distances. the distance between two points means the horizontal distance Measurement of Horizontal Distances the distance between two points means the horizontal distance Pacing Mechanical Devices Taping * Tachymetric Photogrammetric * Electronic Distance Measurement (EDM)

More information

SURVEYING II-2MARKS UNIT-I. 2-Marks

SURVEYING II-2MARKS UNIT-I. 2-Marks SURVEYING II-2MARKS UNIT-I 2-Marks 1. Define Tacheometry: Tacheometry is a branch of angular surveying in which the horizontal and vertical distances (or) points are obtained by optional means as opposed

More information

Package No.-36(Surveyor) Annexure -III

Package No.-36(Surveyor) Annexure -III Package No.-36(Surveyor) Annexure -III Reference- Clause-8 of DTCN S.L.No Item Quantity 1 Abney level.tube is 5 1/8 in. long, Radius arc of 1 1/8 in. graduated in degrees in both directions,vernier reading

More information

Ph 3455/MSE 3255 Experiment 2: Atomic Spectra

Ph 3455/MSE 3255 Experiment 2: Atomic Spectra Ph 3455/MSE 3255 Experiment 2: Atomic Spectra Background Reading: Tipler, Llewellyn pp. 163-165 Apparatus: Spectrometer, sodium lamp, hydrogen lamp, mercury lamp, diffraction grating, watchmaker eyeglass,

More information

UNIT 1- CONTROL SURVEYING PART A

UNIT 1- CONTROL SURVEYING PART A QUESTION BANK (As per Anna University 2013 Regulation) UNIT 1- CONTROL SURVEYING Horizontal and vertical control Methods specifications triangulation- baseline instruments and accessories corrections satellite

More information

MAHATMA GANDHI MISSION S JAWAHARLAL NEHRU ENGINEERING COLLEGE, AURANGABAD. (M.S.)

MAHATMA GANDHI MISSION S JAWAHARLAL NEHRU ENGINEERING COLLEGE, AURANGABAD. (M.S.) MAHATMA GANDHI MISSION S JAWAHARLAL NEHRU ENGINEERING COLLEGE, AURANGABAD. (M.S.) DEPARTMENT OF CIVIL ENGINEERING SURVEYING - II LAB MANUAL Prof.R.V.Wanjule Approved By Lab Incharge Dr. S. B. Shinde H.O.D.

More information

Chapter 2. Altitude Measurement

Chapter 2. Altitude Measurement Chapter Altitude Measurement Although altitudes and zenith distances are equally suitable for navigational calculations, most formulas are traditionally based upon altitudes which are easily accessible

More information

SURVEYING 1 CE 215 CHAPTER -3- LEVEL AND LEVELING

SURVEYING 1 CE 215 CHAPTER -3- LEVEL AND LEVELING Civil Engineering Department SURVEYING 1 CE 215 CHAPTER -3- LEVEL AND LEVELING 1 CHAPTER -3- LEVEL AND LEVELING 2 1 CONTENTS 1. Level instrument 2. Bubble 3. Tripod 4. Leveling staff 5. Definitions 6.

More information

DISPERSION OF A GLASS PRISM

DISPERSION OF A GLASS PRISM PH2 page 1 DISPERSION OF A GLASS PRISM OBJECTIVE The objective of this experiment is to analyze the emission spectrum of helium and to analyze the dispersion of a glass prism by measuring the index of

More information

Owner's Manual NSL100B BUILDERS LEVEL NSL500B TRANSIT LEVEL

Owner's Manual NSL100B BUILDERS LEVEL NSL500B TRANSIT LEVEL Owner's Manual NSL100B BUILDERS LEVEL NSL500B TRANSIT LEVEL 1 1. CONTENTS 2. Nomenclature page 3 3. Care and Maintenance page 4 4. Using your Instrument 4.1 Setting up your Instrument page 5 4.2 Stadia

More information

Surveying Prof. Bharat Lohani Department of Civil Engineering Indian Institute of Technology, Kanpur. Module - 3 Lecture - 4 Linear Measurements

Surveying Prof. Bharat Lohani Department of Civil Engineering Indian Institute of Technology, Kanpur. Module - 3 Lecture - 4 Linear Measurements Surveying Prof. Bharat Lohani Department of Civil Engineering Indian Institute of Technology, Kanpur Module - 3 Lecture - 4 Linear Measurements Welcome again to this another video lecture on basic surveying.

More information

Compass Basics. Quick Map Basics Review For Compass Use

Compass Basics. Quick Map Basics Review For Compass Use Compass Basics Quick Map Basics Review For Compass Use A topographic map tells you where things are and how to get to them, whether you're hiking, biking, hunting, fishing, or just interested in the world

More information

E. K. A. ADVANCED PHYSICS LABORATORY PHYSICS 3081, 4051 FRAUNHOFER DIFFRACTION

E. K. A. ADVANCED PHYSICS LABORATORY PHYSICS 3081, 4051 FRAUNHOFER DIFFRACTION E. K. A. ADVANCED PHYSICS LABORATORY PHYSICS 3081, 4051 FRAUNHOFER DIFFRACTION References for Fraunhofer Diffraction 1. Jenkins and White Fundamentals of Optics. Chapters on Fraunhofer diffraction and

More information

SURVEY AND ALIGNMENT FOR THE SYNCHROTRON LIGHT SOURCE ELETTRA

SURVEY AND ALIGNMENT FOR THE SYNCHROTRON LIGHT SOURCE ELETTRA I/49 SURVEY AND ALIGNMENT FOR THE SYNCHROTRON LIGHT SOURCE ELETTRA ABSTRACT: F.Wei, A.Bergamo, P.Furlan, J.Grgic, A.Wrulich Sincrotrone Trieste Padriciano 99, 34012 Trieste, Italy ELETTRA is a third generation

More information

FOCUS 30/FOCUS 35 Field Calibration with Survey Pro Field Software

FOCUS 30/FOCUS 35 Field Calibration with Survey Pro Field Software GeoInstruments Application Note June 25th, 2015 FOCUS 30/FOCUS 35 Field Calibration with Survey Pro Field Software Summary: This support note outlines the procedure which should be followed to calibrate

More information

Using Map and Compass Together

Using Map and Compass Together Using Map and Compass Together In situations where you foresee a potential evacuation on foot, where there are no roads, and no indication as to the direction of travel (i.e., road signs), it is recommended

More information

S U R V E Y I N G. Lecture Notes. Draft

S U R V E Y I N G. Lecture Notes. Draft S U R V E Y I N G Lecture Notes Draft 1 Introduction efinition of urveying Surveying (Land Surveying in the US) is the art of making measurements of relative positions of natural and man-made features

More information

Carlson CR Robotic/Reflectorless Total Station

Carlson CR Robotic/Reflectorless Total Station 0 West Second Street Suite 00 Maysville, KY 4056 www.carlsonsw.com Phone: 606-564-508 Fax: 606-564-64 Type starts around here Carlson CR Robotic/Reflectorless Total Station Calibration Overview Congratulations

More information

LECTURE NOTE ENGINEERING SURVEYING

LECTURE NOTE ENGINEERING SURVEYING LECTURE NOTE ENGINEERING SURVEYING LECTURE 1 Introduction: Surveying is defined as taking a general view of, by observation and measurement determining the boundaries, size, position, quantity, condition,

More information

22X Builder s Transit Level Model No Instruction Manual

22X Builder s Transit Level Model No Instruction Manual 2595H 7/29/09 10:15 AM Page 1 22X Builder s Transit Level Model No. 40-6910 Instruction Manual Congratulations on your choice of this 22X Builder s Transit Level. We suggest you read this instruction manual

More information

Site Surveying Procedures for Construction and the Built Environment

Site Surveying Procedures for Construction and the Built Environment Unit 27: Site Surveying Procedures for Construction and the Built Environment Unit code: R/601/1291 QCF level: 4 Credit value: 15 Aim This unit develops an understanding of the principles of site surveying

More information

II. COMPASS SURVEYING AND PLANE TABLE SURVEYING :

II. COMPASS SURVEYING AND PLANE TABLE SURVEYING : 1 II. COMPASS SURVEYING AND PLANE TABLE SURVEYING : Prismatic compass surveyor s compass bearing system of conversions Local attraction magnetic declination Dip Traversing Plotting Adjustment of errors

More information

CE 271 Spring Survey Camp

CE 271 Spring Survey Camp PART IV LEVELING A. Importance of Leveling The determination of elevations with a surveying instrument, which is known as leveling, is a relatively simple but extraordinarily important process. B. Definitions

More information

THE GEODETIC INSTRUMENTS produced by Messrs. Carl Zeiss, Jena.

THE GEODETIC INSTRUMENTS produced by Messrs. Carl Zeiss, Jena. THE GEODETIC INSTRUMENTS produced by Messrs. Carl Zeiss, Jena. A BRIEF R E V IE W OF T H E IR O U T S T A N D IN G C H A R A C T E R IS T IC S. Technical progress in the domain of Surveying has, in the

More information

Cleveland State University

Cleveland State University CVE 212 - Surveying Lab #1 MEASURING ANGLES & DISTANCES WITH A TOTAL STATION EQUIPMENT EDMI and Tripod Single prism mounted on a prism pole Field book Pencil 2 Walkie Talkies INTRODUCTION Recent developments

More information

Only for Reference Page 1 of 11

Only for Reference  Page 1 of 11 Only for Reference www.civilpddc2013.weebly.com Page 1 of 11 Seat No.: Enrolment No. PDDC - SEMESTER II EXAMINATION WINTER 2013 Subject Code: X20601 Date: 20-12-2013 Subject Name: Advance Surveying Time:

More information

Surveying I. Unit - I. Different methods and instruments are being used to facilitate the work of

Surveying I. Unit - I. Different methods and instruments are being used to facilitate the work of Surveying I Unit - I Definition of Survey Surveying is the art of determining the relative positions of different objects on the surface of the earth by measuring the horizontal distances between them,

More information

UNIT-2 COMPASS SYRVEYING AND PLANE TABLE SURVEYING

UNIT-2 COMPASS SYRVEYING AND PLANE TABLE SURVEYING UNIT-2 COMPASS SYRVEYING AND PLANE TABLE SURVEYING THE PRISMATIC COMPASS Prismatic compass is the most convenient and portable of magnetic compass which can either be used as a hand instrument or can be

More information

Surveying Prof. Bharat Lohani Indian Institute of Technology, Kanpur. Module - 5 Lecture - 3 Theodolites and Total Stations

Surveying Prof. Bharat Lohani Indian Institute of Technology, Kanpur. Module - 5 Lecture - 3 Theodolites and Total Stations Surveying Prof. Bharat Lohani Indian Institute of Technology, Kanpur Module - 5 Lecture - 3 Theodolites and Total Stations (Refer Slide Time: 00:31) Welcome to another lecture on basic surveying. This

More information

MARINE SEXTANT INTRODUCTION

MARINE SEXTANT INTRODUCTION MARINE SEXTANT INTRODUCTION The marine sextant is used by the mariner to observe the altitude of celestial bodies as well as to measure horizontal and vertical angles of terrestrial objects. On the image

More information

MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION (Autonomous) (ISO/IEC Certified)

MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION (Autonomous) (ISO/IEC Certified) (ISO/IEC - 270-23 Certified) WINTER 17 EXAMINATION Subject Name: SURVEYING Model wer Subject Code: 17310 Important Instructions to examiners: 1) The answers should be examined by key words and not as word-to-word

More information

GE 100: General Surveying I

GE 100: General Surveying I : General I INTRODUCTION TO SURVEYING Lecture No. Caraga State University College of Engineering and Information Technology SURVEYING It is the art and science of determining angular and linear measurements

More information

Surveying Instruments. B Series B20 B30 B40. Automatic Levels

Surveying Instruments. B Series B20 B30 B40. Automatic Levels Surveying Instruments B Series B20 B30 B40 Automatic Levels World-Proven Precision and Durability B20 Automatic Level B30 Automatic Level B40 Automatic Level 28x 1.5mm Accuracy 32x 0.7mm Accuracy 24x 2.0mm

More information

22X Builder s Level Model No Instruction Manual

22X Builder s Level Model No Instruction Manual 2594H 7/29/09 10:12 AM Page 1 22X Builder s Level Model No. 40-6900 Instruction Manual Congratulations on your choice of this 22X Builder s Level. We suggest you read this instruction manual thoroughly

More information

Islamic University of Gaza Civil Engineering Department Surveying II ECIV 2332

Islamic University of Gaza Civil Engineering Department Surveying II ECIV 2332 Islamic University of Gaza Civil Engineering Department Surveying II ECIV 2332 By Belal Almassri Chapter 6 Electronic Distance Measurement EDM - Introduction. - Electro-Optical Instrument. - Microwave

More information

Interferometer for Squareness measurement

Interferometer for Squareness measurement F Interferometer for Squareness measurement The deviation of squareness of two machine axes can be measured as follows: 1. The straightness of a machine axis is measured. 2. The Angular reflector stops

More information

Owner's Manual. for AUTOMATIC LEVEL. NBL Series. FOR CUSTOMER SERVICE, PARTS & REPAIR, CALL Toll Free:

Owner's Manual. for AUTOMATIC LEVEL. NBL Series. FOR CUSTOMER SERVICE, PARTS & REPAIR, CALL Toll Free: Owner's Manual for AUTOMATIC LEVEL NBL Series FOR CUSTOMER SERVICE, PARTS & REPAIR, CALL Toll Free: 1-888-247-1960 1 1. CONTENTS 2. Nomenclature page 3 3. Care and Maintenance page 4 4. Using your Instrument

More information

CE6404 SURVEYING II. 3. Arbitrary Bench Mark: When the RL of some fixed Points are assumed, they are termed a arbitrary Bench mark

CE6404 SURVEYING II. 3. Arbitrary Bench Mark: When the RL of some fixed Points are assumed, they are termed a arbitrary Bench mark CE6404 SURVEYING II UNIT-I Control Surveying Part - A 1. Permanent Bench mark: These are established by different government departments like PWD, Railways, Irrigation etc., The RL of these points are

More information

Experiment #5: Cauchy s Formula

Experiment #5: Cauchy s Formula Experiment #5: Cauchy s Formula Carl Adams October 14, 2011 1 Purpose This experiment is a continuation of Experiment #4. It is assumed you have an aligned spectrometer. 2 Safety/Protocol 1. The gas discharge

More information

Surveying Prof. Bharat Lohani Department of Civil Engineering Indian Institute of Technology, Kanpur. Module - 4 Lecture - 1 Compass Surveying

Surveying Prof. Bharat Lohani Department of Civil Engineering Indian Institute of Technology, Kanpur. Module - 4 Lecture - 1 Compass Surveying Surveying Prof. Bharat Lohani Department of Civil Engineering Indian Institute of Technology, Kanpur Module - 4 Lecture - 1 Compass Surveying Welcome to this video lecture series on basic surveying and

More information

DRAFT MARINE ARTILLERY SURVEY

DRAFT MARINE ARTILLERY SURVEY MARINE ARTILLERY SURVEY Table of Contents Chapter 1: Mission, Organization, and Duties Section I: Mission PARA TITLE PAGE 1-1 Common Grid 1-1 1-2 Components of a Common Grid 1-1 1-3 Fundamentals of Survey

More information

Design Considerations for a Variable Angle Absolute Reflectance Accessory For the LAMBDA 950/850/650 UV/Vis/NIR and UV/Vis Spectrophotometers

Design Considerations for a Variable Angle Absolute Reflectance Accessory For the LAMBDA 950/850/650 UV/Vis/NIR and UV/Vis Spectrophotometers Design Considerations for a Variable Angle Absolute Reflectance Accessory For the LAMBDA 950/850/650 UV/Vis/NIR and UV/Vis Spectrophotometers UV/VIS AND UV/VIS/NIR SPECTROSCOPY A P P L I C A T I O N N

More information

Polar Alignment of LX200R and Ultra Wedge For The Southern Hemisphere by Chris James

Polar Alignment of LX200R and Ultra Wedge For The Southern Hemisphere by Chris James Return To How To Menu Polar Alignment of LX200R and Ultra Wedge For The Southern Hemisphere by Chris James Overview This document goes thru the process required to Polar Align the LX200R using a Ultra

More information

Tutorials. 1. Autocollimator. Angle Dekkor. General

Tutorials. 1. Autocollimator. Angle Dekkor. General Tutorials 1. Autocollimator General An autocollimator is a Precise Optical Instrument for measurement of small angle deviations with very high sensitivity. Autocollimator is essentially an infinity telescope

More information

~.LIETZ ~. LI ETZ INSTRUCTION MANUAL DOUBLE CENTER THEODOLITE TM-20C THE LIETZ COMPANY E. Del Arno Blvd. Carson, Ca (213)

~.LIETZ ~. LI ETZ INSTRUCTION MANUAL DOUBLE CENTER THEODOLITE TM-20C THE LIETZ COMPANY E. Del Arno Blvd. Carson, Ca (213) ~.LIETZ DOUBLE CENTER THEODOLITE TM-20C INSTRUCTION MANUAL f~, ~. LI ETZ THE LIETZ COMPANY 1645 E. Del Arno Blvd. Carson, Ca. 90746. (213)537-0410 n INSTRUMENT NOMENCLATURE cr, il (~ iíl i) Ii: in CD CD

More information

Fig. 1. instrument is in the case

Fig. 1. instrument is in the case 1. Applications The NETH503 series Electronic Theodolite has an optical incremental grading system which features digital angle measurements. It can achieve measurement, calculating, display and memory

More information

Atomic emission spectra experiment

Atomic emission spectra experiment Atomic emission spectra experiment Contents 1 Overview 1 2 Equipment 1 3 Measuring the grating spacing using the sodium D-lines 4 4 Measurement of hydrogen lines and the Rydberg Constant 5 5 Measurement

More information

Cleveland State University

Cleveland State University CVE 212 - Surveying Lab #6 MEASURING ISTANCES USING STAIA METHOS EQUIPMENT Transit or theodolite with stadia hairs and tripod Philadelphia leveling rod Field book No. 3 drafting pencil INTROUCTION When

More information

CHAPTER 11 USE OF SEXTANT IN PILOTING

CHAPTER 11 USE OF SEXTANT IN PILOTING CHAPTER 11 USE OF SEXTANT IN PILOTING FUNDAMENTAL CONCEPTS 1100. Introduction The marine sextant has long been an accurate means for fixing a vessel s position in coastal and confined water circumstances.

More information

Michelson Interferometer

Michelson Interferometer Michelson Interferometer Objective Determination of the wave length of the light of the helium-neon laser by means of Michelson interferometer subsectionprinciple and Task Light is made to produce interference

More information

-I g in y e SURVEYING-I rv u S

-I g in y e SURVEYING-I rv u S SURVEYING-I Modern Surveying Chains & other Equipment Measuring Distance The historical method measuring distance is surveying chain. for the One of the first chains used in the U.S. was the Gunter s chain.

More information

Fig. 8.1 illustrates the three measurements. air medium A. ray 1. air medium A. ray 2. air medium A. ray 3. Fig For Examiner s Use

Fig. 8.1 illustrates the three measurements. air medium A. ray 1. air medium A. ray 2. air medium A. ray 3. Fig For Examiner s Use 9 9 9 14 8 In an optics lesson, a Physics student traces the paths of three s of light near the boundary between medium A and. The student uses a protractor to measure the various angles. Fig. 8.1 illustrates

More information

DOWNLOAD PDF PLANE AND GEODETIC SURVEYING FOR ENGINEERS

DOWNLOAD PDF PLANE AND GEODETIC SURVEYING FOR ENGINEERS Chapter 1 : Difference Between Plane Surveying and Geodetic Surveying Geodetic surveying. Effect of the curvature of the earth surface is ignored. The earth surface is assumed to be plane, i.e. two dimensional.

More information

INTRODUCTION TO THE TELESCOPE

INTRODUCTION TO THE TELESCOPE INTRODUCTION TO THE TELESCOPE What will you learn in this Lab? For a few of the labs this semester, you will be using an 8-inch Celestron telescope to take observations. This lab will introduce you to

More information

DATA SOURCES AND INPUT IN GIS. By Prof. A. Balasubramanian Centre for Advanced Studies in Earth Science, University of Mysore, Mysore

DATA SOURCES AND INPUT IN GIS. By Prof. A. Balasubramanian Centre for Advanced Studies in Earth Science, University of Mysore, Mysore DATA SOURCES AND INPUT IN GIS By Prof. A. Balasubramanian Centre for Advanced Studies in Earth Science, University of Mysore, Mysore 1 1. GIS stands for 'Geographic Information System'. It is a computer-based

More information

Physics 476LW Advanced Physics Laboratory Michelson Interferometer

Physics 476LW Advanced Physics Laboratory Michelson Interferometer Physics 476LW Advanced Physics Laboratory Michelson Interferometer Introduction An optical interferometer is an instrument which splits a beam of light into two beams, each beam follows a different path

More information

1 Line Length I Bearing

1 Line Length I Bearing being 6 15'W. Calculate the true bearing of the line also error of closure and relative error of closure. 1 Line Length I Bearing AB 470m 343 52' BC 635 m 87 50' CD 430 m 172 40' DA 563 m 265 12' 9. (a)

More information

To determine the wavelengths of light emitted by a mercury vapour lamp by using a diffraction grating.

To determine the wavelengths of light emitted by a mercury vapour lamp by using a diffraction grating. 12. Diffraction grating OBJECT To determine the wavelengths of light emitted by a mercury vapour lamp by using a diffraction grating. INTRODUCTION: Consider a light beam transmitted through an aperture

More information

Engineering Metrology

Engineering Metrology Albaha University Faculty of Engineering Mechanical Engineering Department Engineering Metrology Lecture 04: Angular Measurements Ossama Abouelatta o_abouelatta@yahoo.com Mechanical Engineering Department

More information

Dispersion and resolving power of the prism and grating spectroscope (Item No.: P )

Dispersion and resolving power of the prism and grating spectroscope (Item No.: P ) Dispersion and resolving power of the prism and grating spectroscope (Item No.: P2210300) Curricular Relevance Area of Expertise: Physics Education Level: University Topic: Light and Optics Subtopic: Diffraction

More information

ALPHA COLLEGE OF ENGINEERING

ALPHA COLLEGE OF ENGINEERING ALPHA COLLEGE OF ENGINEERING DEPARTMENT OF CIVIL ENGINEERING QUESTION BANK 10CV34 SURVEYING-I UNIT -01 INTRODUCTION 1. Explain plane surveying and geodetic surveying. 2. Write a note on precision and accuracy

More information

Lab Title: Parallax and Astronomical Distances. Equipment: Sextant Meter sticks (or tape measures) Calipers Magnetic compasses.

Lab Title: Parallax and Astronomical Distances. Equipment: Sextant Meter sticks (or tape measures) Calipers Magnetic compasses. Lab Title: Parallax and Astronomical Distances Equipment: Sextant Meter sticks (or tape measures) Calipers Magnetic compasses Introduction: Since we cannot travel to most celestial objects in order to

More information

GIET COLLEGE OF ENGINEERING DEPARTMENT OF CIVIL ENGINEERING SURVEYING LAB MANUAL FAMILARITY WITH INSTRUMENTS USED IN CHAIN SURVEYING

GIET COLLEGE OF ENGINEERING DEPARTMENT OF CIVIL ENGINEERING SURVEYING LAB MANUAL FAMILARITY WITH INSTRUMENTS USED IN CHAIN SURVEYING GIET COLLEGE OF ENGINEERING DEPARTMENT OF CIVIL ENGINEERING SURVEYING LAB MANUAL FAMILARITY WITH INSTRUMENTS USED IN CHAIN SURVEYING OBJECTIVE: Study of various instruments used in chain surveying and

More information

Introduction to Telescopes Pre-lab

Introduction to Telescopes Pre-lab AST 114 Spring 2005 Introduction to Telescopes Introduction to Telescopes Pre-lab 1. Read through the "Parts of a Telescope" section of the lab. You may be asked to point out the different parts of the

More information

NORTHERN ILLINOIS UNIVERSITY PHYSICS DEPARTMENT. Physics 211 E&M and Quantum Physics Spring Lab #9: Diffraction Spectroscopy

NORTHERN ILLINOIS UNIVERSITY PHYSICS DEPARTMENT. Physics 211 E&M and Quantum Physics Spring Lab #9: Diffraction Spectroscopy NORTHERN ILLINOIS UNIVERSITY PHYSICS DEPARTMENT Physics 211 E&M and Quantum Physics Spring 2018 Lab #9: Diffraction Spectroscopy Lab Writeup Due: Mon/Wed/Thu/Fri, April 30/ May 2/3/4, 2018 Background All

More information

GEOMATICS ENGINEERING / SURVEYING

GEOMATICS ENGINEERING / SURVEYING 1 GEOMATICS ENGINEERING / SURVEYING CHAPTER 1 Dr. Muhammad Ashraf Javid Assistant Professor Department of Civil and Environmental Engineering Email: muhammad.javid@unizwa.edu.om 2 Geomatics Engineering

More information

Topic 4 &11 Review Waves & Oscillations

Topic 4 &11 Review Waves & Oscillations Name: Date: Topic 4 &11 Review Waves & Oscillations 1. A source produces water waves of frequency 10 Hz. The graph shows the variation with horizontal position of the vertical displacement of the surface

More information

Using Calibrated Specular Reflectance Standards for Absolute and Relative Reflectance Measurements

Using Calibrated Specular Reflectance Standards for Absolute and Relative Reflectance Measurements Using Calibrated Specular Reflectance Standards for Absolute and Relative Reflectance Measurements Applications Overview here are two fundamental techniques for measuring specular reflectance with a UV/VIS/NIR

More information

OPERATIONS SUPPLEMENT FOR THE COMPARISON AUTOCOLLIMATOR, D600

OPERATIONS SUPPLEMENT FOR THE COMPARISON AUTOCOLLIMATOR, D600 STANFORD UNIVERSITY W.W. HANSEN EXPERIMENTAL PHYSICS LABORATORY GRAVITY PROBE B, RELATIVITY GYROSCOPE EXPERIMENT STANFORD, CALIFORNIA 94305-4085 P0354 SU/GP-B P0354 OPERATIONS SUPPLEMENT FOR THE COMPARISON

More information

5. What is not typically considered to be a cause of natural error when using EDM devices?

5. What is not typically considered to be a cause of natural error when using EDM devices? Student ID: 22093585 Exam: 498868RR - Introduction to Surveying and Measurement When you have completed your exam and reviewed your answers, click Submit Exam. Answers will not be recorded until you hit

More information

Introduction To Metrology

Introduction To Metrology Introduction To Metrology Meaning of Metrology Metrology is the science of measurement. Metrology may be divided depending upon the quantity to be measured like metrology of length, metrology of time.

More information

ABOUT SPOTTINGSCOPES Background on Telescopes

ABOUT SPOTTINGSCOPES Background on Telescopes 22 November 2010 ABOUT SPOTTINGSCOPES A spotting scope is a compact telescope designed primarily for terrestrial observing and is used in applications which require magnifications beyond the range of a

More information

NCEES FS Practice Exam

NCEES FS Practice Exam NCEES FS Practice Exam Terrametra Resources Lynn Patten 1. One corner of a 60-ft. 120-ft. lot, otherwise rectangular, is a curve with a radius of 20 ft. and a central angle of 90. The area (ft. 2 ) of

More information