Load Frequency Control of Multi-Area Power System

Size: px
Start display at page:

Download "Load Frequency Control of Multi-Area Power System"

Transcription

1 Yurmouk University Al Hijjawi Faculty for Engineering Technology Electrical Power Engineering Department Secondary project: Load Frequency Control of Multi-Area Power System Done by: Hasan Abu Alasal ( ) Mohammed Abu Alhaija ( ) Supervised by: Dr. Muwaffaq Alomoush

2 CONTENTS Page Dedication 3 Abbreviations..4 Summary CHAPTER ONE: REVIEW OF CONTROL SYSTEMS. Introduction to Control Systems...8. Stability The Routh-Hurwitz stability criterion The Root-locus method The PID Controllers.3.. Introduction Basic Operational Amplifier (Op-Amp) Circuit Proportional (P) controller Proportional-Integral (PI) Controller Proportional-Derivative (PD) Controller Proportional-Integral-Derivative (PID) Controller.. 9 CHAPTER TWO: INTRODUCTION TO MATLAB AND SIMULINK. MATLAB SIMULINK CHAPTER THREE: LOAD FREQUENCY CONTROL 3. Frequency-power characteristics of synchronous generators Basic generator control loops The procedure of Load Frequency Control Models and block diagrams Generator Model Load Model Prime Mover Model Governor Model Automatic generation control AGC in single area system AGC in multi-area system Tie-Line Bias Control AGC with Optimal Dispatch of Generation 45 Conclusions and further work.46 References 47

3 DEDICATION This project is dedicated with love and respect to our families for the help, love and emotional support they offered us with no hesitation. And also to our beloved college Alhijjawi for engineering technology for the great environment it gave to us and to our friends and future colleagues, with special thanks to our respectful supervisor Dr. Muwaffaq Alomoush who helped us with all he could, and to the rest of our instructors and friends. So, thanks for every one helped finishing this work. 3

4 ABBREVIATIONS: AGC: Automatic Generation Control. : Load Frequency Control. SD: Speed Droop. ACE: Area Control Error. RA: Reset Action. AVR: Automatic Voltage Regulation. EDG: Economic Dispatch of Generation. 4

5 SUMMERY As the demand of electrical power is increasing and becoming a global issue, the need of interconnecting power systems is growing up; this growth represents a great challenge for power engineers, challenges in making power systems reliable, economic and safe for both supplier and customer, these challenges are represented in different sections of power systems from protection coordination to economic dispatch of generation through other many technical and economical problems. An important problem is the Load Frequency Control () which is directly related to such interconnection in power systems. Other problems related to such interconnection like the Automatic Voltage Regulation (AVR) have less intersection in operation with. So, in this project, we will mainly display the causes and effects of the () problem, trying to configure its mechanism and to simulate the system response to such control. As the name (Load Frequency Control) indicates, this topic deals with the control of frequency of the system as the load (demand) varies. Since the frequency of the system does affect the whole operation of the system, especially for interconnected power systems of multi-area, and as the main objective of control in power systems is to generate and deliver power as economically and reliably as possible, then it is important to consider the control of the frequency of the system. Frequency and generation control is the major problem in interconnected power networks. If a network frequency is changed over ±0%, units can leave from synchronization with the network. These changes are to make impossible the network interconnection. This issue is becoming more significant recently with increasing size, changing structure, and complexity of interconnected power systems. So, to provide the stability of a system, active power balance and 5

6 constant frequency are required. Frequency depends on active power balance. If any change occurs in active power demand/generation in power system, frequency can not be held in its rated value. So, oscillations increase in both power and frequency. Thus, system subjects to a serious instability problems. To improve the stability of a power network, it is necessary to design a load frequency control system that controls the power generation and active power of tie lines. In an interconnected power system network with two or more areas, the generation within each area has to be controlled so as to maintain scheduled power interchange. Because of the relationship between active power and frequency, three-levels of automatic generation control have been proposed by power system researchers. Levels of Load Frequency Control has to be of two main control loops, these are primary and secondary control. In primary control, control action is realized by turbinegovernor system in the plant. In this control level only the active power is balanced. However, maintaining the frequency at scheduled value (e.g. 50 Hz) can not be provided. Therefore, steady state frequency error can occur forever. So this level is not enough for interconnected systems, as the frequency must be equal at all areas. The second level of generation control, called secondary or supplementary control is made in large power systems which include two or more areas. Active power is controlled at the tie lines between neighbor areas by the concept of Automatic Generation Control (AGC) and there are central and local load control and distribution centers. The final level of generation control is Economic Dispatch of Generation (EDG) among the all plants. The major aim of this control is to maintain each unit s generation at the most economic value. Among this project we are interested only in the two main control levels, namely the primary and secondary. 6

7 No one of these control levels could be understood or realized with out understanding the main concepts of control system theory, so a review of some important concepts of the control system theory is given in chapter one of this project, farther more, considering the importance of the PID controllers, being the most kwon and popular controllers in control systems, a special section of chapter one was added. Also, as the facility of simulating the response of our systems of interest is the MATLAB program and its SIMULINK package, another chapter (Chapter two) is given as a review of the basics of MATLAB and SIMULINK. Finally, the main chapter of this project; chapter three is concerned with the analysis of the main elements and loops of, and in the simulation of single and interconnected multi-area (two-area) power systems, respectively. 7

8 CHAPTER REVIEW OF CONTROL SYSTEMS. INTRODUCTION TO CONTROL SYSTEMS The first step in the analysis and design of any control system is the mathematical modeling of the system. The two most common methods are the transfer function approach and the state equation approach. The state equations can be applied to portray linear as well as non-linear systems. As all physical systems are non-linear to some extent, then, in order to use the transfer function and linear state equations, the system must first be linearized. Thus, proper assumptions are made so that the system can be characterized by a linear mathematical model [4]. The model may be validated by analyzing its performance for realistic input conditions and then by comparing with field test data taken from the dynamic system in its operating environment. Once an acceptable controller has been designed and tested on the model, the feedback control strategy is then applied to the actual system to be controlled. When we wish to develop a feedback control system for a specific purpose, the general procedure may be summarized as follows:. Choose a way to adjust the variable to be controlled; e.g. the mechanical load will be positioned with an electric motor or the temperature could be controlled by an electrical resistance heater, (or active power generated can be controlled by adjusting the valves of the governor of the turbine).. Select suitable sensors, power supplies, amplifiers, etc.., to complete the loop. 3. Determine what is required for the system to operate with the specified accuracy in steady-state and for the desired response time. 8

9 4. Analyze the resulting system to determine its stability. 5. Modify the system to provide stability and other desired operating conditions by redesigning the amplifier/controller, or by introducing additional control loops [4]. The objective of the control system is to control the output c(t) in some prescribed manner by the input r(t) through the elements of the control system. Some of the essential characteristics of feedback control system are investigated in the following sections.. STABILITY: Considering the block diagram of a simple closed loop control system as shown in Fig. below, where R(s) is the S-domain reference input, C(s) is the S-domain controlled output, G(s) is the plant transfer function, k is a simple gain controlled, and the feedback element H(s) represents the sensor transfer function. The closedloop transfer function is: C ( s) k G ( s) = T ( S ) = (.) R( s) + ( k G ( s) H ( s)) R (s) k G (s) C (s) H (s) Fig... Block diagram of simple closed loop system. or the s-domain response is: C ( s ) = T ( s ) R ( s ) (.) The gain, k G ( s) H ( s), is commonly referred to as the open-loop transfer function. For a system to be usable, it must be stable. A linear time-invariant 9

10 system is stable if every bounded input produces a bounded output. We call this characteristic stability. The denominator polynomial of the closed-loop transfer function set equal to zero is the system characteristic equation. That is the characteristic equation is given by: + k G ( s) H( s) = 0 (.3) The roots of the characteristic equation are known as the poles of the closedloop transfer function. The response is bounded if the poles of closed-loop system are in the left-hand portion of the s-plane. Thus, a necessary and sufficient condition for a feedback system to be stable is that all the poles of the system transfer function have negative real parts. In the classical control theory, several techniques have been developed requiring little computation for stability analysis, one of these techniques is the Routh-Hurwitz criterion. Consideration of the degree of stability of a system often provides valuable information about its behavior. That is, if it is stable, how close it is to being unstable? This is the concept of relative stability. Usually, relative stability is expressed in terms of the speed of response and overshoot. Other methods frequently used for stability studies are the Bode diagram, Root-locus, Nyquist criterion, and Lypunov s stability criterion, but we are to consider Routh- Hurwitz and Root-locus methods here [4].... THE ROUTH-HURWITZ STABILITY CRITERION The Routh-Hurwitz criterion provides a quick method for determining absolute stability that can be applied to an n th order characteristic equation of the from a s a s a s n n = (.4) n n 0 a 0 The criterion is applied through the use of a Routh table defined as: 0

11 s n a n a n a n 4.. s n a n a n 3 a.. n 5 s n b b b 3.. s n 3 c c c a n, a n-,., a 0 are coefficient of the characteristic equation and b a a a a a n n n n 3 = ; n b = a n a n 4 a n a n a n 5 c b a a b b n 3 n = ; c = b a n 3 a b n b 3 Calculations in each row are continued until only zero elements remain. The necessary and sufficient condition that all roots of (.4) lie in the left of the s-plane is that the elements of the first column of the Routh-Hurwitz array have the same sign. If there are changes of signs in the elements of the first column, the number of sign changes indicates the number of roots with positive real parts. If the first element in a row is zero, it is replaced by a very small positive number Є, and the calculation of the array is completed. If all elements in a row are zero, the system has poles on the imaginary axis, pairs of complex conjugate roots forming symmetry about the origin of the s-plane, or pairs of real roots with opposite sings. In this case, an auxiliary equation is formed from the preceding row. The all-zero row is then replaced with coefficients obtained by differentiating the auxiliary equation [4] [7].

12 ... THE ROOT-LOCUS METHOD The Root-locus method, developed by W.R. Evans, enables us to find the closedloop poles from the open-loop poles for all the values of the gain of the open-loop transfer function. The Root-locus of a system is a plot of the roots of the system characteristic equation as the gain factor k is varied. Therefore, the designer can select a suitable gain factor to achieve the desired performance criteria. If the required performance can not be achieved, a controller can be added to the system to alter the root-locus in the required manner. Consider again the feed-back control system given in Fig.. In general, the open loop transfer function is given by: z p k ( s + )( s + )...( s + ) m k G ( s) H( s) = (.5) ( s + )( s + )... ( s + ) Where m is the number of finite zeros, and n is the number of finite poles of the loop transfer function. If n > m, there are ( n m ) zeros at infinity. The characteristic equation of the closed-loop transfer function is given by (.3); therefore ( s + ( s + p z p z z p p z )( s + )....( s + ) n = k (.6) )( s + )......( s + ) From equation.6 it follows that for a point s o in the s-plane to be on the rootlocus, when 0 < k <, it must satisfy the following two conditions. product product of of vector vector lengths lengths from from finite finite o k = (.7) And m z p poles zeros n to s to s o angles of zeros of G H( s) angles of poles of G H( s) = r(80 ) (.8) where r =±, ±3, ±5, A good knowledge of the characteristics of the root-loci offers insights into the effects of adding poles and zeros to the system transfer function. It is important to know how to construct the root-locus by hand, so we can design a simple system and be able to understand and develop the computer-generated loci [4]. o

13 .3 THE PID CONTROLLERS:.3. Introduction: When working with applications where control of the system output due to changes in the reference value or state is needed, implementation of a control algorithm may be necessary. Examples of such applications are motor control, control of temperature, pressure, flow rate, speed, force,, AVR or other variables. The PID controller can be used to control any measurable variable, as long as this variable can be affected by manipulating some other process variables. Many control solutions have been used over the time, but the PID controller has become the industry standard due to its simplicity and good performance. For further information about the PID controller and its applications the reader should consult other sources [3]. In Figure. a schematic of a system with a PID controller is shown. The PID controller compares the measured process value y with a reference set point value, y 0. The difference or error, e, is then processed to calculate a new process input, u. This input will try to adjust the measured process value back to the desired set point. The alternative to a closed loop control scheme such as the PID controller is an open loop controller. Open loop control (no feedback) is in many cases not satisfactory, and is often impossible due to the system properties. By adding feedback from the system output, performance can be improved. y 0 - e PID u SYSTEM y Figure. Closed Loop System with PID controller Unlike simple control algorithms, the PID controller is capable of manipulating the process inputs based on the history and rate of change of the signal. This gives a more accurate and stable control method. The basic idea is that the controller 3

14 reads the system state by a sensor, and then it subtracts the measurement from a desired reference to generate the error value. The error will be managed in three ways, to handle the present, through the proportional term, recover from the past, using the integral term and finally to anticipate the future, through the derivate term. Figure.3 shows the PID controller schematics, where T p, T i and T d denote the time constants of the proportional, integral, and derivative terms respectively [3]. e T P T d d dt + + u + T i Figure.3 The PID controller schematic..3. Basic Operational Amplifier (Op-Amp) Circuit Figure.4 shows a simple Op-Amp circuit with input voltage V i (s), output voltage V o (s), input impedance Z i (s) and feedback impedance Z f (s) [3]. It can be shown that the transfer function of the circuit can be written as Z Z Vo ( s ) ( s ) f G ( s) = = (.9) Vi ( s) ( s) i Z f (s) V i (s) Z i (s) - + V o (s) Figure.4 Operational amplifier (Op-Amp) schematic of PID controller. 4

15 Simple RC circuits can be used to generate the input and feedback impedances required to generate transfer functions for P, PI, PD, and PID controllers. To understand the implementation of the controllers described below, recall: ) The total impedance of two components in series is the sum of the individual impedances; and ) The inverse of the total impedance of two components in parallel is the sum of the inverses of the individual impedances. Note that the impedance of a resistor with resistance R is Z(s) = R, and the impedance of a capacitor of capacitance C is Z(s) =. (.0) The total impedance of a resistor and a capacitor in series is c s R C s + Z(s) = R + = (.) C s C s The inverse of the total impedance of a resistor and capacitor in parallel is = C s Z(s) R + (.) So the total impedance of the two in parallel is R Z(s) =. (.3) R C s Proportional (P) Controller To form a P controller, let the input impedance be generated by a resistor of resistance R i, and let the feedback impedance be generated by a resistor of resistance R f. In this case, the impedances are Z i (s) = R i and Z f (s) = R f, and the transfer function of the circuit is R R f G ( s) = = Kp = constant. (.4) i The proportional term (P) gives a system control input proportional with the error. Using only P control gives a stationary error in all cases except when the system control input is zero and the system process value equals the desired value. 5

16 In Figure.5 the stationary error in the system process value appears after a change in the desired value (ref). Using a too large P term gives an unstable system. Figure.5. Step response of P controller..3.4 Proportional-Integral (PI) Controller To form a PI controller, let the input impedance be generated by a resistor of resistance R i and a capacitor of capacitance C i in parallel, and let the feedback impedance be generated by a capacitor of capacitance C f. In this case, the impedances are z i R Rici And the transfer function of the circuit is: i = and z =. (.5) f + s c f R C C s + i i i Ki G ( s) = = + = Kp + (.6) s C R S C R C s f i f i f 6

17 The integral term (I) gives an addition from the sum of the previous errors to the system control input. The summing of the error will continue until the system process value equals the desired value and these results in no stationary error when the reference is stable [3]. The most common use of the I term is normally together with the P term, called a PI controller. Using only the I term gives slow response and often an oscillating system. Figure.6 shows the step responses to an I and PI controller. As seen, the PI controller response have no stationary error and the I controller response is very slow. Figure.6. Step response of I and PI controller Proportional-Derivative (PD) Controller To form a PD controller, let the input impedance be generated by a resistor of resistance Ri and a capacitor of capacitance Ci in parallel, and let the feedback impedance be generated by a resistor of resistance R f. In this case, the impedances Ri are: Z i = ; and Z f =R f And the transfer function of the circuit is Ri Ci s + 7

18 R C R [ s] s + i i f G (s) = R = R C s = i + f i k + p k (.7) d R i R i The derivative term (D) gives an addition from the rate of change in the error to the system control input. A rapid change in the error will give an addition to the system control input. This improves the response to a sudden change in the system state or reference value. The D term is typically used with the P or PI as a PD or PID controller. A too large D term usually gives an unstable system. Figure.7 shows D and PD controller responses. The response of the PD controller gives a faster rising system process value than the P controller. Note that the D term essentially behaves as a highpass filter on the error signal and thus easily introduces instability in a system and make it more sensitive to noise. Figure.7 Step response of D and PD controller. 8

19 .3.6. Proportional-Integral-Derivative (PID) Controller To form a PID controller with high frequency gain limit, let the input impedance be generated by a resistor (resistance, R ) be in series with a resistor (resistance, R ) and a capacitor (capacitance C ) that are in parallel, and let the feedback impedance be generated by a resistor (resistance, R f ) and a capacitor (capacitance C f ) in series. In this case, the impedances are R Z = i R R C s + and R s f C f + Z f s C f Then, it can be shown that the transfer function of the circuit is R C R C R C + = (.8) + f f f i G ( s) = + + s = + + s (.9) + + s + k p s k d ( R R ) C ( f R R ) C ( f R R ) R k Using all the terms together, as a PID controller usually gives the best performance. Figure.8 compares the P, PI, and PID controllers. PI improves the P by removing the stationary error, and the PID improves the PI by faster response and no overshoot [3]. Figure.8 Step response P, PI and PID controller. 9

20 CHAPTER INTRODUCTION TO MATLAB AND SIMULINK. MATLAB MATLAB developed by Math works Inc. is a software package for high performance numerical computation and visualization. The combination of analysis capabilities; flexibility, reliability, and power full graphics makes MATLAB the premier software package for electrical engineers. MATLAB provides an interactive environment with hundreds of reliable and accurate built-in mathematical functions. These functions provide solutions to a broad range of mathematical problems [5]. The most important feature of MATLAB is its programming capability which is very easy to learn and use, and which allows user-development functions. There are several optional toolboxes written for special applications such as signal processing, control systems design, system identification, and others. MATLAB has been enhanced by the very powerful SIMULINK program. SIMULINK program is a graphical mouse-driven program for the simulation of dynamic systems. SIMULINK enables students to simulate linear, as well as nonlinear, systems easily and efficiently [4] [5]... SIMULINK SIMULINK is an interactive environment for modelling, analyzing and simulating a wide variety of dynamic systems. SIMULINK provides a graphical user interface for constructing block diagram models using "drag-and-drop" operations. 0

21 A system is configured in terms of block diagram representation from a library of standard components. It is very easy to learn, a system in block diagram representation is built easily and the simulation results are displayed quickly. Simulation algorithms and parameters can be changed in the middle of a simulation with intuitive results, thus providing the user with a ready access learning tools for simulating many of the operational problems found in the real world [5]. SIMULINK is particularly useful for studying the effects of nonlinearities on the behaviour of the system. It is also an ideal research tool, the key features of SIMULINK are: - Interactive simulations with live display. - A comprehensive block library for creating linear, nonlinear, discrete or hybrid multi-input/output systems. - Seven integration methods for fixed step, variable step, and stiff systems. - Mask facility for creating custom blocks and block libraries. Simulation parameters and solvers We can set the simulation parameters and select the solver by choosing parameters from the simulation menu. The simulation parameters dialog box, have three pages: solver, workspace I/O and diagnostic. The solver page allows us to: Set the start and stop points. Choose the solver and specify solver parameters. Some solvers may be more efficient than others at solving particular problems. There are variable step and fixed step solvers:

22 Variable step solver: can modify their step sizes during simulation. These are ode45, ode3, ode3, ode55, ode3s and discrete. Fixed step solver include ode5, ode4, ode3, ode, ode and discrete. Block diagram construction The SIMULINK BLOCK LIBRARY contains seven icons; each icon contains various components in the titled category. The easy to use pull down menus allows you to create a SIMULINK block diagram, or open an existing file, perform the simulation and make any modifications. Generally, when building a model, design it first on paper, and then build it using the computer. When you start putting the blocks together into a model, add the blocks to model window, before adding the lines that connect them. This way, you can reduce how often you need to open block libraries [5].

23 CHAPTER 3 LOAD FREQUENCY CONTROL 3. FREQUENCIES-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR Since synchronous generators are the most common type of machines used in the generation of electrical power, its characteristics can be used to describe the relationship between frequency and power during load changes []. All generators are driven by a prime mover, which is the generators source of mechanical power. The most common type of prime mover is a steam turbine, but other types include diesel engines, gas turbines, water turbines, and even wind turbines. Regardless of the original power source, all prime movers tend to behave in a similar fashion as the power drawn from them increases, the speed at which they turn decreases. The decrease in speed is in general non-linear, but some form of governor mechanism is usually included to make the decrease in speed linear with an increase in power demand. Whatever mechanism is presented on a prime mover, it will always be adjusted to provide a slight drooping characteristic with increasing load. The Speed Droop (SD) of a prime mover is defined by the equation n n n fl nl fl SD = 00% (3.) Where n nl is the no-load prime-mover speed and n fl is the full-load prime-mover speed. Most generator prime movers have a speed droop of to 4 percent, as defined in equation 3

24 (3.). In addition, most governors have some type of set point adjustment to allow the noload speed of the turbine to be varied. A typical speed-versus-power plot (known as the house curve) is shown in figure (3..a). Mechanical speed, rpm n nl n fl Frequency, Hz 0 P fl Power 0 P fl Power kw kw (a) f nl f fl (b) Figure 3. Speed-power and frequency-power curves (house curves). Although the house curves are only used for studying the parallel operation of two generators or that of a single generator connected to a certain network, it helps understanding the variations of electrical frequency as the power demanded is changed, since the shaft speed is related to the resulting electrical frequency by the equation, f n = (3.) e 0 Then the power output of a synchronous generator is related to its frequency and this is clear in figure (3..b). Frequency-power characteristics of this sort play an essential role in the parallel operation of synchronous generators. The relationship between frequency and power can be described quantitatively by the equation P = (3.3) s P where P = power output of the generator f nl = no-load frequency of the generator f sys = operating frequency of system s p = slope of curve, in kw/hz or MW/ Hz. 4 m p ( ) f nl f sys

25 But this equation is not accurate for multi-area power systems. A similar relationship can be derived for the reactive power Q and terminal voltage V T, for which the AVR control loop is used, which is not of our interest in this project []. 3. BASIC GENERATOR CONTROL LOOPS As real power affects the frequency of a network, whereas no big change in the reactive power due to change in frequency, since reactive power is mainly dependent on voltage magnitude (: controls frequency and real power, AVR: controls voltage magnitude and reactive power). Each of them can be controlled separately and independently []. and AVR for generator are shown in the schematic diagram of Fig 3.. Excitation System Gen. Field Automatic Voltage Regulator (AVR) Voltage Sensor Steam Turbine G P V P G, Q G Valve Control Mechanism P tie P C Load Frequency Control () Frequency sensor Figure 3. and AVR of a synchronous generator. The controllers are set to take care of any changes in load demand to maintain the frequency and voltage within specified limits. Small changes in real power refer to change in the angle δ (rotor angle) and this will affect the frequency. 5

26 Since reactive power depends on V, thus the excitation of the generator is a factor affects reactive power. There is a time constant for each of the prime mover and the generator excitation, and this time is much smaller for prime mover and its transient decay becomes faster. For this reason, the load frequency and voltage excitation are analyzed and controlled separately and independently. 3.3 THE PROCEDURE OF LOAD FREQUENCY CONTROL () There are three operation objectives for : - To maintain reasonably uniform frequency. 3- To control tie-line interchange schedules. - To divide the load between the generators. Changes in frequency and real power are sensed, and these are a measure of changes in rotor angle (δ); so the error δ is to be corrected. Error signals such as f and P are amplified, then mixed, then transformed into a real power signal, which is sent to turbine to cause an increment in torque. Therefore, the prime mover (steam turbine) cause changes in the generator output by certain amount to change the value of f and P within a specified tolerance, this mechanism is discussed in details when we consider the modeling of governor and prime mover. Typical responses to real power changes are illustrated using the simulation techniques available in the SIMULINK package of the MATLAB program, these responses will be viewed for each specified control loop. As illustrated in chapter one there are two common methods for modeling, the transfer function method, and this is used for linear systems only where as; the state variable approach, is used in linear and non-linear systems. If we want to use transfer function method; non-linear systems must be linearized. 6

27 3.4 MODELS AND BLOCK DIAGRAMS Generator Model: We have the equation (the swing equation of synchronous machine) Ω ( s) = [ Pm ( s) Pe ( s)] (3.) H s Where the input is P m (the mechanical input power), and the output is Ω (frequency deviation) and P e is the electrical power and H is the per unit inertia constant having a unit of seconds and ranging from to 0 seconds depending on the type and size of the machine [] [6]. The block diagram is as shown in figure 3.3: P m (s) H s Ω(s) P e (s) Figure 3.3 Generator block diagram Load Model: In power systems, the loads are mainly resistive loads, and this is independent of frequency. And the other type of loads is Motor loads (mainly inductive), which is sensitive to change in frequency, depending on the composite of the speed-load characteristic of all driven devices. Speed load characteristic of composite load is: Pe = PL + D ω (3.) Where; P L : independent frequency loads. D ω: frequency sensitive loads. D: ratio of percent change in load to percent change in frequency. And the block diagram of the load model added to that of generator is shown in Figure 3.4: 7

28 P L (s) P m (s) Hs + D Ω(s) Figure 3.4 Load block diagram Prime Mover Model: It is the source of mechanical power; it may be a hydraulic turbine at waterfalls, steam turbine whose energy comes from burning of gas, coal, and gas turbine. Its model relates changes in mechanical power out put P m to changes in steam valve position P V, then Pm ( s) GT ( s) = = (3.3) P ( s) +τ ( s) V which have a single time constant τ T, and its block diagram is shown in figure 3.5: T P V (s) Figure 3.5 Prime mover block diagram. + τ T s P m (s) The time constant τ T varies from 0. to ms Governor Model: The governor is a device used to sense a turbine speed changes when the load of the generator is suddenly increased, in that case, the electrical power exceeds the input mechanical power. The shortage of this power is supplied by kinetic energy stored in the rotating system, reducing the mechanical power of the turbine, [7] [8]. This reduction in energy causes the turbine speed to fall and thus the generator frequency to fall. Any change in speed is sensed by the turbine governor, which will act to adjust the input valves of the turbine to change the output mechanical power to bring the speed to a new steady state. There are many types of governors; 8

29 the earlier types used mechanical mechanisms of sensing speed changes, and modern governors use electronics. Figure 3.6 shows a schematic for a conventional governing system. Lower M Raise Speed changer Hydraulic amplifier To governorcontrolled valves To close To open Speed Governor Figure 3.6 A schematic of a governing system. The speed governor acts as a comparator whose output P g is the difference between the reference set power P ref and the power ω, that is R P g = P ref ω (3.4) R In the s-domain: Pg ( s) = Pref ( s) Ω( s) (3.5) R where R is the speed regulation. Governors typically have speed regulation of 5 to 6 percent from zero to full load. Consider a simple time constant τ g and assume linear relationship, we have the relation: PV ( s) = Pg ( s) + τ s The block diagram is as shown in figure 3.7: g (3.6) 9

30 P ref (s) P g + τ g ( s ) P V (s) ω(s) R Figure 3.7 Governor Block diagram Combining block diagrams of the preceding models we can find the block diagram of the of an isolated power station, providing the primary level of as shown in Figure 3.8. P ref (s) P g + τ g s P v +τ T s P L (s) P m Hs+D Governor Turbine Rotating mass and load Ω(s) R Figure 3.8 block diagram of an isolated power system. For the purposes of simulation, predetermined parameters are given as: Turbine time constant τ T = 0.5 sec. Governor time constant τ g = 0. sec. Governor inertia constant H = 5.0 sec. Governor speed regulation R = 0.05 per unit, and a sudden load change of 0. per unit is represented by a step input at P L and the load is considered to vary by 0.8 percent for a percent change in frequency, i.e., D = 0.8. The block diagram constructed using Simulink is shown if figure 3.9 followed by the response of the simulation in figure (3.0) with the suggested values of time constants and other parameters []. 30

31 Figure 3.9 Simulink block diagram of isolated power system Frequency [pu] Time [sec] Figure 3.0 simulation results of figure 3.9. With the load change - P L (s) as an input, and the frequency deviation Ω(s) as an output, results the block diagram in figure 3. - P L (s) Hs + D Ω(s) R( +τ s)( + τ s) g T Figure 3. with input - P L (s) and output Ω(s) The open loop transfer function is: K G ( s) H( s) = (3.7) R (H s + D)( +τ s)( + s) g τ T And the closed loop transfer function is: 3

32 Ω( s) P ( s) L ( + τ gs)( + τ T s) = (Hs + D)( + τ s)( + τ s) + / R g T = T ( s) (3.8) Or: Ω ( s) = P ( s) T ( s) (3.9) L PL The load change in a step input (i.e. PL ( s) = ) then the steady-state value of s ω is: ω ss = lims Ω( s) = PL (3.0) s 0 ( D + / R) We can find that for the case of no frequency sensitive load (i.e. with D=0) then the steady-state value of the frequency deviation is: ω = ( R (3.) ss P L ) If we have a case of multiple generators with governor speed regulations, R, R,.R n then: ω ss = PL (3.) ( D + / R + / R / R ) n 3.5 AUTOMATIC GENERATION CONTROL (AGC) When the load on the system is increased, the turbine speed drops before the governor can adjust the input of the steam to the new load. As the change in the value of speed diminishes, the error signal becomes smaller and the position of the governor fly-balls gets closer to the point required to maintain a constant speed. However, the new constant speed will not be the set point, and there will be an offset. One way to restore the speed or frequency to its nominal value is to add an integrator; Because of its ability to return a system to its set point, integral action is also known as the reset action. Thus, as the system load changes continuously, the generation is adjusted automatically to restore the frequency to its nominal value. This is known as the Automatic Generation Control (AGC). The role of AGC is to divide the load among system stations and generators to achieve 3

33 maximum economy and to correctly control the scheduled interchanges of power, while maintaining reasonable uniform frequency [], [7], [8] AGC in single area system In order to reduce frequency deviation to zero, we must provide a reset action; the reset action can be achieved by adding integral controller. The system with addition of integral controller is shown in figure 3.. P ref (s) + ( s) + ( s) H s + D τ g P V τ T P L (s) P m Governor Turbine Rotating mass and load ω(s) R K I s Figure 3. AGC for an isolated power system. For the same single area system given before with the same values of τ T, τ g, H, D and P L, with the gain of the I controller suggested to be K I = 7.0. The Simulink diagram constructed is shown in figure 3.3 followed by its response shown in figure 3.4 []. Figure 3.3 Simulink block diagram of isolated power system with AGC loop. 33

34 4 x Frequency [pu] Time [sec] Figure 3.4 Simulation results of figure 3.. Combining the parallel branches results in the following block diagram in fig 3.5: - P L (s) Hs + D ω(s) K I ( + )( )( ) s R +τ s +τ s g T Fig 3.5. Equivalent of AGC of isolated power station. The transfer function is: Ω( s) s( + τ gs)( + τt s) = P ( s) s(hs + D)( + τ s)( + τ s) + K + s L g T I / R (3.3) 34

35 3.5.. AGC in multi-area system: The AGC of multi-area system can be realized by studying first the AGC for a two-area system. Look at figure 3.7. P X Area Area Figure 3.6 Schematic of two-area system. Consider these two areas represented by an equivalent generating units interconnected by a lossless tie line with reactance X tie []. Each area is represented by voltage source behind an equivalent reactance as shown in figure 3.7. X X tie X + - E δ E δ + - Figure 3.7 The equivalent network of two area system. During normal operation the real power transferred over the tie line is given by: E E P = (3.4) sinδ X Where: X = X + X tie + X and δ = δ δ Equation 3.4 can be linearized for a small deviation in the flow P from the nominal value, that is: 35

36 dp P = δ δ = δ 0 dδ s P (3.5) P s : the slope of the power angle curve at the initial operating angleδ = δ 0 δ 0, 0 thus: dp E E P s = δ = cos δ (3.6) dδ 0 0 X Then P = P ( δ ) (3.7) s δ The direction of the flow depends on the phase angle difference; if δ >δ the power flows from area to area. A block diagram for the two area system is shown below in Fig 3.8. R P L (s) P ref (s) P V + τ + τ s gs T P m H s+ D ω (s) Governor Turbine Rotating mass and load + P P s s + P ref (s) P V + τ g s + τ T s Governor Turbine P m P L (s) H s+ D Rotating mass and load ω (s) R Figure 3.8 Two area system with only primary loop (AGC). 36

37 Again, for the purposes of simulation, a two-area system connected by a tie line is suggested to have the following parameters on a 000 MVA common base. Area Speed Regulation R = 0.05 R = Frequency-sens. load coeff. D = 0.6 D = 0.9 Inertia constant H = 5 H = 4 Base power 000 MVA 000 MVA Governor time constant τ g = 0. sec τ g = 0.3 sec Turbine time constant τ T = 0.5 sec τ T = 0.6 sec The Simulink block diagram for such system is shown in figure 3.9, followed by the resulting response in figure 3.0. Figure 3.9 Simulink block diagram of tow area system with AGC loop. 37

38 Figure 3.0 (a) Frequency deviation 0.35 Delta P m 0.3 Delta P m Delta P Power [pu] Time [sec] Figure 3.0 The resulting response of figure 3.9. Figure 3.0 (b) Power deviations 38

39 Consider load change in area is P L, in the steady-state; both areas will have the same steady-state frequency deviation; ω = ω = ω Now, P ω and + P = ω D (3.8) m P PL = D P m The change in mechanical power is determined by the governor speed characteristic, given by: Solving for ω: ω ω Pm = and Pm = (3.9) R R ω = L : + D ) +P ( + D ) R R ( P L = (3.0) B + B Giving B = + R D and, B = + R D where B and B are known as the frequency bias factors. The change in the tieline power is: ( + D ) PL R B P = = ( P L ) (3.) ( + D ) + ( + D ) B + B R R We can easily extend the tie-line bias control to an n-area system. 39

40 3.5.3 Tie-Line Bias Control Up to now, was equipped with only the primary control loop, a change of power in area was met by the increase in generation in both areas associated with a change in the tie-line power, and a reduction in frequency. In the normal operating state, the power system is operated so that the demands of areas are satisfied at the normal frequency [] [7] [8]. As mentioned in section 3.3, a simple control strategy for the normal mode is: Hz). To Keep frequency approximately at the nominal value (50 or 60 schedule. To Maintain the tie-line flow at about changes. Each area should absorb its own load Conventional is based upon tie-line bias control, where each area tends to reduce the Area Control Error (ACE) to zero. The control error for each area consists of a linear combination of frequency and tie-line error. ACE i = n j = P i j + K i ω (3.) The area bias K i determines the amount of interaction during a disturbance in the neighboring areas. An overall satisfactory performance is achieved when K i is selected equal to the frequency bias factor of that area, i.e. B R i + Thus, the ACEs for a two-area system are i D = (3.3) i ω ω ACE = + P B (3.4) ACE = P where P and P are departures from scheduled interchanges. ACEs are used as actuating signals to achieve changes in the reference power set points, and when steady-state is reached, P and ω will be zero. The block diagram of a simple AGC for a two-area system with ACE loops is shown in figure (3.). + B 40

41 B R P L (s) ACE K I s P V + τ g s + τ T s P m H s + D Governor Turbine Rotating mass Go and load ω (s) + P P P s s + + ACE K I s P V + τ g s + τ T s Governor Turbine P m Go H s + D Rotating mass and load ω (s) R P L (s) B Figure 3. A simple AGC for a two-area system with ACE loops. Here the same data is considered for the two area system, except the addition of the ACE loops, adjusting the integrator gain constants for a satisfactory response; the simulation results for K I = K I = 0.3 were obtained. Other than trail and error technique, there is no certain method that suggests an optimal evaluation for the gains of the PID controllers used in such control except using new optimization techniques or artificial intelligence techniques such as fuzzy logic or artificial intelligence, which are all beyond the scope of this project. In this project we used the method of trial and error such that an optimal response was achieved according to the characteristics of optimal step response of control systems. The Simulink block diagram of two area power system with both AGC and ACE loops is shown in figure 3. followed by the resulting response of this simulation shown in figure

42 Figure 3. Simulink block diagram of two area system with both AGC and ACE loops. 4 x 0-3 Delta w Delta w 0 - Frequency [pu] Time [sec] Figure 3.3 (a) Frequency deviation 4

43 Delta P m 0.3 Delta P m Delta P Power [pu] Time [sec] Figure 3.3 The resulting response of figure 3.. Figure 3.3 (b) Power deviation. For a better and more satisfactory response, the I term used in figure 3. for the ACE is replaced by a full PID controller in figure 3.4 followed by its response in figure 3.5 for both frequency and power deviations. Figure 3.4 Simulink block diagram of two area system with both AGC and ACE loops with full PID controller used instead of the I term only. 43

44 x 0-3 Delta w Delta w 0 - Frequency [pu] Time [sec] Figure 3.5 (a). Frequency deviation 0.35 Delta P m 0.3 Delta P m Delta P Power [pu] Time [sec] Figure 3.5. Simulation results of figure 3.4 Figure 3.5(b). Power deviation. 44

45 Comparing between the responses of both the I term and the full PID controller, we can observe that the response of the PID controller is more satisfactory according to the optimized step response characteristics, including lower overshoot, less vibration, lower rise time and settling time and almost zero steadystate error AGC With Optimal Dispatch Of Generation (EDG) There are several factors that affect the power generation at minimum cost; these are efficiencies, fuel cost, and transmission losses and other many factors. Many types of programs were developed to find the optimal dispatch of generation of an interconnected power system [] [8]. The optimal dispatch of generation may be treated within the framework of as the third level. In direct digital control systems, the digital computer is included in the control loop which scans the unit generation and tie-line flows, the results are compared with the optimal settings that found from the solution of optimal dispatch programs. Now, if the actual settings are off from the optimal values, the computer generates the raise/lower pulses which sent to the individual units. With the development of control theory, several concepts are included in the AGC which go beyond the simple tie-line bias control. The fundamental approach is the use of more extended mathematical models. Other concepts of the modern control theory are being employed, such as state estimation and optimal control with linear regulator utilizing constant feedback gains. 45

46 Conclusions and further work. Load frequency control investigated in this project has recently come into question in operation of interconnected power networks. Frequency is a sensitive parameter which affects the system operation so it is controlled certainly. Therefore, power utilities consider the frequency and active power balance throughout their networks to sustain the interconnection. In interconnection between national/continental networks, providing the constant frequency between areas is a serious operational problem. Hence fast and no delay decision-making mechanism have to be installed in network control units namely the.. The load frequency control is achieved within tree levels, considering many issues from maintaining constant frequency and the minimization of losses through tie lines to the optimal dispatch of generation between units or even areas. 3. The simulation techniques are very useful in studying and predicting the response of control systems, giving the opportunity to optimize the response and so the behavior of the system under study. 4. The great importance of the PID controllers is recognized, considering the facilities it offers by the different combinations of its terms. 5. As a further work, study could be extended to consider methods of optimal design of the gains of the PID controllers, like considering the artificial intelligence methods or the fussy logic giving the opportunity to obtain an optimal response of the control systems. 6. The economic dispatch of generation plays a vital rule in the AGC, and this issue could be studied as an extension of this project, adding an additional dimension to the task of our project. 7. A larger and more complex control system could be considered by combining both and AVR systems together with the EDG system. 46

47 REFERENCES: []. Electric Machinery Fundamentals, By Stephen J. Chapman. 4 th Edition (005). []. Power System Analysis, by Hadi Saadat. nd Edition (00). [3]. PID Controllers, by K. J. Astrom and T. Hagglund (995). [4]. Modern Control Systems, by Richard C. Dorf and Robert H. Bishop. 9 th Edition (000). [5]. Demos of MATLAB program (version 7.6). [6]. Power Generation Operation and Control, by A.J. Wood and B.F. Wollenberg, John Wiley & Sons, New York, 984. [7]. Power System Stability and Control, by Kundur P, McGraw-Hill, NewYork 994. [8]. Electric Energy Systems Theory: An Introduction, By Olle I. Elgerd, University of Florida. 47

ECE 422/522 Power System Operations & Planning/ Power Systems Analysis II 4 Active Power and Frequency Control

ECE 422/522 Power System Operations & Planning/ Power Systems Analysis II 4 Active Power and Frequency Control ECE 422/522 Power System Operations & Planning/ Power Systems Analysis II 4 Active Power and Frequency Control Spring 2014 Instructor: Kai Sun 1 References Chapter 12 of Saadat s book Chapter 11.1 of Kundur

More information

Relationships between Load, Speed Regulation and Frequency. Slope= -R

Relationships between Load, Speed Regulation and Frequency. Slope= -R elationships between Load, Speed egulation and Frequency Governor Speed characteristic Slope= - Slope=1/D D=2 Frequency-sensitive Load Characteristic Frequency-insensitive Load Characteristic If D (more

More information

CHAPTER 2 MODELING OF POWER SYSTEM

CHAPTER 2 MODELING OF POWER SYSTEM 38 CHAPTER 2 MODELING OF POWER SYSTEM 2.1 INTRODUCTION In the day to day scenario, power is an essential commodity to the human beings. The demand is more in developed countries and there is increase in

More information

CHAPTER 2 MATHEMATICAL MODELLING OF AN ISOLATED HYBRID POWER SYSTEM FOR LFC AND BPC

CHAPTER 2 MATHEMATICAL MODELLING OF AN ISOLATED HYBRID POWER SYSTEM FOR LFC AND BPC 20 CHAPTER 2 MATHEMATICAL MODELLING OF AN ISOLATED HYBRID POWER SYSTEM FOR LFC AND BPC 2.1 INTRODUCTION The technology of the hybrid power system is at an exciting stage of development. Much research effort

More information

(b) A unity feedback system is characterized by the transfer function. Design a suitable compensator to meet the following specifications:

(b) A unity feedback system is characterized by the transfer function. Design a suitable compensator to meet the following specifications: 1. (a) The open loop transfer function of a unity feedback control system is given by G(S) = K/S(1+0.1S)(1+S) (i) Determine the value of K so that the resonance peak M r of the system is equal to 1.4.

More information

Chapter 9: Transient Stability

Chapter 9: Transient Stability Chapter 9: Transient Stability 9.1 Introduction The first electric power system was a dc system built by Edison in 1882. The subsequent power systems that were constructed in the late 19 th century were

More information

Automatic Generation Control. Meth Bandara and Hassan Oukacha

Automatic Generation Control. Meth Bandara and Hassan Oukacha Automatic Generation Control Meth Bandara and Hassan Oukacha EE194 Advanced Controls Theory February 25, 2013 Outline Introduction System Modeling Single Generator AGC Going Forward Conclusion Introduction

More information

POWER SYSTEM STABILITY

POWER SYSTEM STABILITY LESSON SUMMARY-1:- POWER SYSTEM STABILITY 1. Introduction 2. Classification of Power System Stability 3. Dynamic Equation of Synchronous Machine Power system stability involves the study of the dynamics

More information

Chapter 3 AUTOMATIC VOLTAGE CONTROL

Chapter 3 AUTOMATIC VOLTAGE CONTROL Chapter 3 AUTOMATIC VOLTAGE CONTROL . INTRODUCTION TO EXCITATION SYSTEM The basic function of an excitation system is to provide direct current to the field winding of the synchronous generator. The excitation

More information

Frequency-Bias Tie-Line Control of Hydroelectric Generating Stations for Long Distances

Frequency-Bias Tie-Line Control of Hydroelectric Generating Stations for Long Distances Frequency-Bias Tie-Line Control of Hydroelectric Generating Stations for Long Distances Sukhbir Singh Abstract In this work I have tried to apply effective dedicated online control systems to two equal

More information

Index. Index. More information. in this web service Cambridge University Press

Index. Index. More information.  in this web service Cambridge University Press A-type elements, 4 7, 18, 31, 168, 198, 202, 219, 220, 222, 225 A-type variables. See Across variable ac current, 172, 251 ac induction motor, 251 Acceleration rotational, 30 translational, 16 Accumulator,

More information

B1-1. Closed-loop control. Chapter 1. Fundamentals of closed-loop control technology. Festo Didactic Process Control System

B1-1. Closed-loop control. Chapter 1. Fundamentals of closed-loop control technology. Festo Didactic Process Control System B1-1 Chapter 1 Fundamentals of closed-loop control technology B1-2 This chapter outlines the differences between closed-loop and openloop control and gives an introduction to closed-loop control technology.

More information

Alireza Mousavi Brunel University

Alireza Mousavi Brunel University Alireza Mousavi Brunel University 1 » Control Process» Control Systems Design & Analysis 2 Open-Loop Control: Is normally a simple switch on and switch off process, for example a light in a room is switched

More information

Appendix A: Exercise Problems on Classical Feedback Control Theory (Chaps. 1 and 2)

Appendix A: Exercise Problems on Classical Feedback Control Theory (Chaps. 1 and 2) Appendix A: Exercise Problems on Classical Feedback Control Theory (Chaps. 1 and 2) For all calculations in this book, you can use the MathCad software or any other mathematical software that you are familiar

More information

UNIT-I Economic Operation of Power Systems -1

UNIT-I Economic Operation of Power Systems -1 UNIT-I Economic Operation of Power Systems -1 Overview Economic Distribution of Loads between the Units of a Plant Generating Limits Economic Sharing of Loads between Different Plants Automatic Generation

More information

Transient Stability Analysis with PowerWorld Simulator

Transient Stability Analysis with PowerWorld Simulator Transient Stability Analysis with PowerWorld Simulator T1: Transient Stability Overview, Models and Relationships 2001 South First Street Champaign, Illinois 61820 +1 (217) 384.6330 support@powerworld.com

More information

Improving the Control System for Pumped Storage Hydro Plant

Improving the Control System for Pumped Storage Hydro Plant 011 International Conference on Computer Communication and Management Proc.of CSIT vol.5 (011) (011) IACSIT Press, Singapore Improving the Control System for Pumped Storage Hydro Plant 1 Sa ad. P. Mansoor

More information

Feedback Control of Linear SISO systems. Process Dynamics and Control

Feedback Control of Linear SISO systems. Process Dynamics and Control Feedback Control of Linear SISO systems Process Dynamics and Control 1 Open-Loop Process The study of dynamics was limited to open-loop systems Observe process behavior as a result of specific input signals

More information

Economic Operation of Power Systems

Economic Operation of Power Systems Economic Operation of Power Systems Section I: Economic Operation Of Power System Economic Distribution of Loads between the Units of a Plant Generating Limits Economic Sharing of Loads between Different

More information

QFT Framework for Robust Tuning of Power System Stabilizers

QFT Framework for Robust Tuning of Power System Stabilizers 45-E-PSS-75 QFT Framework for Robust Tuning of Power System Stabilizers Seyyed Mohammad Mahdi Alavi, Roozbeh Izadi-Zamanabadi Department of Control Engineering, Aalborg University, Denmark Correspondence

More information

Cascade Control of a Continuous Stirred Tank Reactor (CSTR)

Cascade Control of a Continuous Stirred Tank Reactor (CSTR) Journal of Applied and Industrial Sciences, 213, 1 (4): 16-23, ISSN: 2328-4595 (PRINT), ISSN: 2328-469 (ONLINE) Research Article Cascade Control of a Continuous Stirred Tank Reactor (CSTR) 16 A. O. Ahmed

More information

Lab 3: Quanser Hardware and Proportional Control

Lab 3: Quanser Hardware and Proportional Control Lab 3: Quanser Hardware and Proportional Control The worst wheel of the cart makes the most noise. Benjamin Franklin 1 Objectives The goal of this lab is to: 1. familiarize you with Quanser s QuaRC tools

More information

The synchronous machine (SM) in the power system (2) (Where does the electricity come from)?

The synchronous machine (SM) in the power system (2) (Where does the electricity come from)? 1 The synchronous machine (SM) in the power system (2) (Where does the electricity come from)? 2 Lecture overview Synchronous machines with more than 2 magnetic poles The relation between the number of

More information

ECE 325 Electric Energy System Components 7- Synchronous Machines. Instructor: Kai Sun Fall 2015

ECE 325 Electric Energy System Components 7- Synchronous Machines. Instructor: Kai Sun Fall 2015 ECE 325 Electric Energy System Components 7- Synchronous Machines Instructor: Kai Sun Fall 2015 1 Content (Materials are from Chapters 16-17) Synchronous Generators Synchronous Motors 2 Synchronous Generators

More information

LESSON 20 ALTERNATOR OPERATION OF SYNCHRONOUS MACHINES

LESSON 20 ALTERNATOR OPERATION OF SYNCHRONOUS MACHINES ET 332b Ac Motors, Generators and Power Systems LESSON 20 ALTERNATOR OPERATION OF SYNCHRONOUS MACHINES 1 LEARNING OBJECTIVES After this presentation you will be able to: Interpret alternator phasor diagrams

More information

General procedure for formulation of robot dynamics STEP 1 STEP 3. Module 9 : Robot Dynamics & controls

General procedure for formulation of robot dynamics STEP 1 STEP 3. Module 9 : Robot Dynamics & controls Module 9 : Robot Dynamics & controls Lecture 32 : General procedure for dynamics equation forming and introduction to control Objectives In this course you will learn the following Lagrangian Formulation

More information

Compensator Design to Improve Transient Performance Using Root Locus

Compensator Design to Improve Transient Performance Using Root Locus 1 Compensator Design to Improve Transient Performance Using Root Locus Prof. Guy Beale Electrical and Computer Engineering Department George Mason University Fairfax, Virginia Correspondence concerning

More information

Dynamic simulation of a five-bus system

Dynamic simulation of a five-bus system ELEC0047 - Power system dynamics, control and stability Dynamic simulation of a five-bus system Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct November 2017 1 / 16 System modelling

More information

ECE 585 Power System Stability

ECE 585 Power System Stability Homework 1, Due on January 29 ECE 585 Power System Stability Consider the power system below. The network frequency is 60 Hz. At the pre-fault steady state (a) the power generated by the machine is 400

More information

Lecture 10: Proportional, Integral and Derivative Actions

Lecture 10: Proportional, Integral and Derivative Actions MCE441: Intr. Linear Control Systems Lecture 10: Proportional, Integral and Derivative Actions Stability Concepts BIBO Stability and The Routh-Hurwitz Criterion Dorf, Sections 6.1, 6.2, 7.6 Cleveland State

More information

Comparative Study of Synchronous Machine, Model 1.0 and Model 1.1 in Transient Stability Studies with and without PSS

Comparative Study of Synchronous Machine, Model 1.0 and Model 1.1 in Transient Stability Studies with and without PSS Comparative Study of Synchronous Machine, Model 1.0 and Model 1.1 in Transient Stability Studies with and without PSS Abhijit N Morab, Abhishek P Jinde, Jayakrishna Narra, Omkar Kokane Guide: Kiran R Patil

More information

Dr Ian R. Manchester Dr Ian R. Manchester AMME 3500 : Review

Dr Ian R. Manchester Dr Ian R. Manchester AMME 3500 : Review Week Date Content Notes 1 6 Mar Introduction 2 13 Mar Frequency Domain Modelling 3 20 Mar Transient Performance and the s-plane 4 27 Mar Block Diagrams Assign 1 Due 5 3 Apr Feedback System Characteristics

More information

Laplace Transform Analysis of Signals and Systems

Laplace Transform Analysis of Signals and Systems Laplace Transform Analysis of Signals and Systems Transfer Functions Transfer functions of CT systems can be found from analysis of Differential Equations Block Diagrams Circuit Diagrams 5/10/04 M. J.

More information

DESIGNING POWER SYSTEM STABILIZER WITH PID CONTROLLER

DESIGNING POWER SYSTEM STABILIZER WITH PID CONTROLLER International Journal on Technical and Physical Problems of Engineering (IJTPE) Published by International Organization on TPE (IOTPE) ISSN 2077-3528 IJTPE Journal www.iotpe.com ijtpe@iotpe.com June 2010

More information

Transient Stability Assessment of Synchronous Generator in Power System with High-Penetration Photovoltaics (Part 2)

Transient Stability Assessment of Synchronous Generator in Power System with High-Penetration Photovoltaics (Part 2) Journal of Mechanics Engineering and Automation 5 (2015) 401-406 doi: 10.17265/2159-5275/2015.07.003 D DAVID PUBLISHING Transient Stability Assessment of Synchronous Generator in Power System with High-Penetration

More information

QUESTION BANK ENGINEERS ACADEMY. Power Systems Power System Stability 1

QUESTION BANK ENGINEERS ACADEMY. Power Systems Power System Stability 1 ower ystems ower ystem tability QUETION BANK. A cylindrical rotor generator delivers 0.5 pu power in the steady-state to an infinite bus through a transmission line of reactance 0.5 pu. The generator no-load

More information

A Computer Application for Power System Control Studies

A Computer Application for Power System Control Studies A Computer Application for Power System Control Studies Dinis C. A. Bucho Student nº55262 of Instituto Superior Técnico Technical University of Lisbon Lisbon, Portugal Abstract - This thesis presents studies

More information

Power System Stability and Control. Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India

Power System Stability and Control. Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India Power System Stability and Control Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India Contents Chapter 1 Introduction to Power System Stability

More information

Chemical Process Dynamics and Control. Aisha Osman Mohamed Ahmed Department of Chemical Engineering Faculty of Engineering, Red Sea University

Chemical Process Dynamics and Control. Aisha Osman Mohamed Ahmed Department of Chemical Engineering Faculty of Engineering, Red Sea University Chemical Process Dynamics and Control Aisha Osman Mohamed Ahmed Department of Chemical Engineering Faculty of Engineering, Red Sea University 1 Chapter 4 System Stability 2 Chapter Objectives End of this

More information

(Refer Slide Time: 1:42)

(Refer Slide Time: 1:42) Control Engineering Prof. Madan Gopal Department of Electrical Engineering Indian Institute of Technology, Delhi Lecture - 21 Basic Principles of Feedback Control (Contd..) Friends, let me get started

More information

Generators. What its all about

Generators. What its all about Generators What its all about How do we make a generator? Synchronous Operation Rotor Magnetic Field Stator Magnetic Field Forces and Magnetic Fields Force Between Fields Motoring Generators & motors are

More information

Dr Ian R. Manchester Dr Ian R. Manchester AMME 3500 : Root Locus

Dr Ian R. Manchester Dr Ian R. Manchester AMME 3500 : Root Locus Week Content Notes 1 Introduction 2 Frequency Domain Modelling 3 Transient Performance and the s-plane 4 Block Diagrams 5 Feedback System Characteristics Assign 1 Due 6 Root Locus 7 Root Locus 2 Assign

More information

Introduction to Synchronous. Machines. Kevin Gaughan

Introduction to Synchronous. Machines. Kevin Gaughan Introduction to Synchronous Machines Kevin Gaughan The Synchronous Machine An AC machine (generator or motor) with a stator winding (usually 3 phase) generating a rotating magnetic field and a rotor carrying

More information

University of Jordan Faculty of Engineering & Technology Electric Power Engineering Department

University of Jordan Faculty of Engineering & Technology Electric Power Engineering Department University of Jordan Faculty of Engineering & Technology Electric Power Engineering Department EE471: Electrical Machines-II Tutorial # 2: 3-ph Induction Motor/Generator Question #1 A 100 hp, 60-Hz, three-phase

More information

LOAD FREQUENCY CONTROL IN A SINGLE AREA POWER SYSTEM

LOAD FREQUENCY CONTROL IN A SINGLE AREA POWER SYSTEM LOAD FREQUENCY CONTROL IN A SINGLE AREA POWER SYSTEM PRANAB PATNAIK (109EE0294) Department of Electrical Engineering National Institute of Technology Rourkela LOAD FREQUENCY CONTROL IN A SINGLE AREA POWER

More information

Bangladesh University of Engineering and Technology. EEE 402: Control System I Laboratory

Bangladesh University of Engineering and Technology. EEE 402: Control System I Laboratory Bangladesh University of Engineering and Technology Electrical and Electronic Engineering Department EEE 402: Control System I Laboratory Experiment No. 4 a) Effect of input waveform, loop gain, and system

More information

Module 6 : Preventive, Emergency and Restorative Control. Lecture 27 : Normal and Alert State in a Power System. Objectives

Module 6 : Preventive, Emergency and Restorative Control. Lecture 27 : Normal and Alert State in a Power System. Objectives Module 6 : Preventive, Emergency and Restorative Control Lecture 27 : Normal and Alert State in a Power System Objectives In this lecture you will learn the following Different states in a power system

More information

Predicting, controlling and damping inter-area mode oscillations in Power Systems including Wind Parks

Predicting, controlling and damping inter-area mode oscillations in Power Systems including Wind Parks 3rd IASME/WSEAS Int. Conf. on Energy & Environment, University of Cambridge, UK, February 3-5, 008 Predicting, controlling and damping inter-area mode oscillations in Power Systems including Wind Parks

More information

The Operation of a Generator on Infinite Busbars

The Operation of a Generator on Infinite Busbars The Operation of a Generator on Infinite Busbars In order to simplify the ideas as much as possible the resistance of the generator will be neglected; in practice this assumption is usually reasonable.

More information

A Study on Performance of Fuzzy And Fuzyy Model Reference Learning Pss In Presence of Interaction Between Lfc and avr Loops

A Study on Performance of Fuzzy And Fuzyy Model Reference Learning Pss In Presence of Interaction Between Lfc and avr Loops Australian Journal of Basic and Applied Sciences, 5(2): 258-263, 20 ISSN 99-878 A Study on Performance of Fuzzy And Fuzyy Model Reference Learning Pss In Presence of Interaction Between Lfc and avr Loops

More information

ECEN 667 Power System Stability Lecture 18: Voltage Stability, Load Models

ECEN 667 Power System Stability Lecture 18: Voltage Stability, Load Models ECEN 667 Power System Stability Lecture 18: Voltage Stability, Load Models Prof. Tom Overbye Dept. of Electrical and Computer Engineering Texas A&M University, overbye@tamu.edu 1 Announcements Read Chapter

More information

Power System Operations and Control Prof. S.N. Singh Department of Electrical Engineering Indian Institute of Technology, Kanpur. Module 3 Lecture 8

Power System Operations and Control Prof. S.N. Singh Department of Electrical Engineering Indian Institute of Technology, Kanpur. Module 3 Lecture 8 Power System Operations and Control Prof. S.N. Singh Department of Electrical Engineering Indian Institute of Technology, Kanpur Module 3 Lecture 8 Welcome to lecture number 8 of module 3. In the previous

More information

DYNAMIC RESPONSE OF A GROUP OF SYNCHRONOUS GENERATORS FOLLOWING DISTURBANCES IN DISTRIBUTION GRID

DYNAMIC RESPONSE OF A GROUP OF SYNCHRONOUS GENERATORS FOLLOWING DISTURBANCES IN DISTRIBUTION GRID Engineering Review Vol. 36 Issue 2 8-86 206. 8 DYNAMIC RESPONSE OF A GROUP OF SYNCHRONOUS GENERATORS FOLLOWING DISTURBANCES IN DISTRIBUTION GRID Samir Avdaković * Alija Jusić 2 BiH Electrical Utility Company

More information

Modeling of Hydraulic Turbine and Governor for Dynamic Studies of HPP

Modeling of Hydraulic Turbine and Governor for Dynamic Studies of HPP Modeling of Hydraulic Turbine and Governor for Dynamic Studies of HPP Nanaware R. A. Department of Electronics, Shivaji University, Kolhapur Sawant S. R. Department of Technology, Shivaji University, Kolhapur

More information

FEEDBACK CONTROL SYSTEMS

FEEDBACK CONTROL SYSTEMS FEEDBAC CONTROL SYSTEMS. Control System Design. Open and Closed-Loop Control Systems 3. Why Closed-Loop Control? 4. Case Study --- Speed Control of a DC Motor 5. Steady-State Errors in Unity Feedback Control

More information

Stability of Feedback Control Systems: Absolute and Relative

Stability of Feedback Control Systems: Absolute and Relative Stability of Feedback Control Systems: Absolute and Relative Dr. Kevin Craig Greenheck Chair in Engineering Design & Professor of Mechanical Engineering Marquette University Stability: Absolute and Relative

More information

EE 451 Power System Stability

EE 451 Power System Stability EE 451 Power System Stability Power system operates in synchronous mode Power system is subjected to a wide range of disturbances (small and large) - Loads and generation changes - Network changes - Faults

More information

Lecture 14 - Using the MATLAB Control System Toolbox and Simulink Friday, February 8, 2013

Lecture 14 - Using the MATLAB Control System Toolbox and Simulink Friday, February 8, 2013 Today s Objectives ENGR 105: Feedback Control Design Winter 2013 Lecture 14 - Using the MATLAB Control System Toolbox and Simulink Friday, February 8, 2013 1. introduce the MATLAB Control System Toolbox

More information

Lecture 5 Classical Control Overview III. Dr. Radhakant Padhi Asst. Professor Dept. of Aerospace Engineering Indian Institute of Science - Bangalore

Lecture 5 Classical Control Overview III. Dr. Radhakant Padhi Asst. Professor Dept. of Aerospace Engineering Indian Institute of Science - Bangalore Lecture 5 Classical Control Overview III Dr. Radhakant Padhi Asst. Professor Dept. of Aerospace Engineering Indian Institute of Science - Bangalore A Fundamental Problem in Control Systems Poles of open

More information

Robust Tuning of Power System Stabilizers Using Coefficient Diagram Method

Robust Tuning of Power System Stabilizers Using Coefficient Diagram Method International Journal of Electrical Engineering. ISSN 0974-2158 Volume 7, Number 2 (2014), pp. 257-270 International Research Publication House http://www.irphouse.com Robust Tuning of Power System Stabilizers

More information

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous)

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad - 500 043 ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK Course Name : Computer Methods in Power Systems Course Code : A60222

More information

KINGS COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRONICS AND COMMUNICATION ENGINEERING

KINGS COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRONICS AND COMMUNICATION ENGINEERING KINGS COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRONICS AND COMMUNICATION ENGINEERING QUESTION BANK SUB.NAME : CONTROL SYSTEMS BRANCH : ECE YEAR : II SEMESTER: IV 1. What is control system? 2. Define open

More information

1 Unified Power Flow Controller (UPFC)

1 Unified Power Flow Controller (UPFC) Power flow control with UPFC Rusejla Sadikovic Internal report 1 Unified Power Flow Controller (UPFC) The UPFC can provide simultaneous control of all basic power system parameters ( transmission voltage,

More information

Software Engineering 3DX3. Slides 8: Root Locus Techniques

Software Engineering 3DX3. Slides 8: Root Locus Techniques Software Engineering 3DX3 Slides 8: Root Locus Techniques Dr. Ryan Leduc Department of Computing and Software McMaster University Material based on Control Systems Engineering by N. Nise. c 2006, 2007

More information

EE Branch GATE Paper 2010

EE Branch GATE Paper 2010 Q.1 Q.25 carry one mark each 1. The value of the quantity P, where, is equal to 0 1 e 1/e 2. Divergence of the three-dimensional radial vector field is 3 1/r 3. The period of the signal x(t) = 8 is 0.4

More information

Transient Stability Analysis of Single Machine Infinite Bus System by Numerical Methods

Transient Stability Analysis of Single Machine Infinite Bus System by Numerical Methods International Journal of Electrical and Electronics Research ISSN 348-6988 (online) Vol., Issue 3, pp: (58-66), Month: July - September 04, Available at: www.researchpublish.com Transient Stability Analysis

More information

Analysis of Coupling Dynamics for Power Systems with Iterative Discrete Decision Making Architectures

Analysis of Coupling Dynamics for Power Systems with Iterative Discrete Decision Making Architectures Analysis of Coupling Dynamics for Power Systems with Iterative Discrete Decision Making Architectures Zhixin Miao Department of Electrical Engineering, University of South Florida, Tampa FL USA 3362. Email:

More information

CHAPTER 2 CAPACITANCE REQUIREMENTS OF SIX-PHASE SELF-EXCITED INDUCTION GENERATORS

CHAPTER 2 CAPACITANCE REQUIREMENTS OF SIX-PHASE SELF-EXCITED INDUCTION GENERATORS 9 CHAPTER 2 CAPACITANCE REQUIREMENTS OF SIX-PHASE SELF-EXCITED INDUCTION GENERATORS 2.. INTRODUCTION Rapidly depleting rate of conventional energy sources, has led the scientists to explore the possibility

More information

7.4 STEP BY STEP PROCEDURE TO DRAW THE ROOT LOCUS DIAGRAM

7.4 STEP BY STEP PROCEDURE TO DRAW THE ROOT LOCUS DIAGRAM ROOT LOCUS TECHNIQUE. Values of on the root loci The value of at any point s on the root loci is determined from the following equation G( s) H( s) Product of lengths of vectors from poles of G( s)h( s)

More information

CYBER EXPLORATION LABORATORY EXPERIMENTS

CYBER EXPLORATION LABORATORY EXPERIMENTS CYBER EXPLORATION LABORATORY EXPERIMENTS 1 2 Cyber Exploration oratory Experiments Chapter 2 Experiment 1 Objectives To learn to use MATLAB to: (1) generate polynomial, (2) manipulate polynomials, (3)

More information

ES205 Analysis and Design of Engineering Systems: Lab 1: An Introductory Tutorial: Getting Started with SIMULINK

ES205 Analysis and Design of Engineering Systems: Lab 1: An Introductory Tutorial: Getting Started with SIMULINK ES205 Analysis and Design of Engineering Systems: Lab 1: An Introductory Tutorial: Getting Started with SIMULINK What is SIMULINK? SIMULINK is a software package for modeling, simulating, and analyzing

More information

Dr Ian R. Manchester

Dr Ian R. Manchester Week Content Notes 1 Introduction 2 Frequency Domain Modelling 3 Transient Performance and the s-plane 4 Block Diagrams 5 Feedback System Characteristics Assign 1 Due 6 Root Locus 7 Root Locus 2 Assign

More information

Turbines and speed governors

Turbines and speed governors ELEC0047 - Power system dynamics, control and stability Turbines and speed governors Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct November 2017 1 / 31 2 / 31 Steam turbines Turbines

More information

Mathematical Modelling Using SimScape (Electrical Systems)

Mathematical Modelling Using SimScape (Electrical Systems) Experiment Three Mathematical Modelling Using SimScape (Electrical Systems) Control Systems Laboratory Dr. Zaer Abo Hammour Dr. Zaer Abo Hammour Control Systems Laboratory 1. Model and simulate MultiDomain

More information

EC CONTROL SYSTEM UNIT I- CONTROL SYSTEM MODELING

EC CONTROL SYSTEM UNIT I- CONTROL SYSTEM MODELING EC 2255 - CONTROL SYSTEM UNIT I- CONTROL SYSTEM MODELING 1. What is meant by a system? It is an arrangement of physical components related in such a manner as to form an entire unit. 2. List the two types

More information

Torques 1.0 Two torques We have written the swing equation where speed is in rad/sec as:

Torques 1.0 Two torques We have written the swing equation where speed is in rad/sec as: Torques 1.0 Two torques We have written the swing equation where speed is in rad/sec as: 2H Re ( t) T au T mu T eu (1) and when speed is in per-unit as 2H u ( t) Tau Tmu Teu (2) We note that in both cases

More information

Course Summary. The course cannot be summarized in one lecture.

Course Summary. The course cannot be summarized in one lecture. Course Summary Unit 1: Introduction Unit 2: Modeling in the Frequency Domain Unit 3: Time Response Unit 4: Block Diagram Reduction Unit 5: Stability Unit 6: Steady-State Error Unit 7: Root Locus Techniques

More information

Lab 1: Dynamic Simulation Using Simulink and Matlab

Lab 1: Dynamic Simulation Using Simulink and Matlab Lab 1: Dynamic Simulation Using Simulink and Matlab Objectives In this lab you will learn how to use a program called Simulink to simulate dynamic systems. Simulink runs under Matlab and uses block diagrams

More information

Performance Of Power System Stabilizerusing Fuzzy Logic Controller

Performance Of Power System Stabilizerusing Fuzzy Logic Controller IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 9, Issue 3 Ver. I (May Jun. 2014), PP 42-49 Performance Of Power System Stabilizerusing Fuzzy

More information

DESIGN OF POWER SYSTEM STABILIZER USING FUZZY BASED SLIDING MODE CONTROL TECHNIQUE

DESIGN OF POWER SYSTEM STABILIZER USING FUZZY BASED SLIDING MODE CONTROL TECHNIQUE DESIGN OF POWER SYSTEM STABILIZER USING FUZZY BASED SLIDING MODE CONTROL TECHNIQUE LATHA.R Department of Instrumentation and Control Systems Engineering, PSG College of Technology, Coimbatore, 641004,

More information

Dynamic simulation of DH house stations

Dynamic simulation of DH house stations Article Dynamic simulation of DH house stations Jan Eric Thorsen, Director, DHS Application Centre, Danfoss A/S www.danfoss.com Jan Eric Thorsen, Director, DHS Application Centre, Danfoss A/S Presented

More information

Contents. PART I METHODS AND CONCEPTS 2. Transfer Function Approach Frequency Domain Representations... 42

Contents. PART I METHODS AND CONCEPTS 2. Transfer Function Approach Frequency Domain Representations... 42 Contents Preface.............................................. xiii 1. Introduction......................................... 1 1.1 Continuous and Discrete Control Systems................. 4 1.2 Open-Loop

More information

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester Electrical and Electronics Engineering EE 1352 Power System Analysis (Regulation 2008) Time: Three hours Answer all questions Part A (10

More information

1. Introduction. Keywords Transient Stability Analysis, Power System, Swing Equation, Three-Phase Fault, Fault Clearing Time

1. Introduction. Keywords Transient Stability Analysis, Power System, Swing Equation, Three-Phase Fault, Fault Clearing Time Energy and Power 17, 7(1): -36 DOI: 1.593/j.ep.1771.3 Numerical Simulations for Transient Stability Analysis of Two-Machine Power System Considering Three-Phase Fault under Different Fault Clearing Times

More information

Positioning Servo Design Example

Positioning Servo Design Example Positioning Servo Design Example 1 Goal. The goal in this design example is to design a control system that will be used in a pick-and-place robot to move the link of a robot between two positions. Usually

More information

Outline. Classical Control. Lecture 1

Outline. Classical Control. Lecture 1 Outline Outline Outline 1 Introduction 2 Prerequisites Block diagram for system modeling Modeling Mechanical Electrical Outline Introduction Background Basic Systems Models/Transfers functions 1 Introduction

More information

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur Lecture - 9 Transmission Line Steady State Operation Welcome to lesson 9, in Power

More information

CHAPTER 5 ROBUSTNESS ANALYSIS OF THE CONTROLLER

CHAPTER 5 ROBUSTNESS ANALYSIS OF THE CONTROLLER 114 CHAPTER 5 ROBUSTNESS ANALYSIS OF THE CONTROLLER 5.1 INTRODUCTION Robust control is a branch of control theory that explicitly deals with uncertainty in its approach to controller design. It also refers

More information

Alireza Mousavi Brunel University

Alireza Mousavi Brunel University Alireza Mousavi Brunel University 1 » Online Lecture Material at (www.brunel.ac.uk/~emstaam)» C. W. De Silva, Modelling and Control of Engineering Systems, CRC Press, Francis & Taylor, 2009.» M. P. Groover,

More information

IC6501 CONTROL SYSTEMS

IC6501 CONTROL SYSTEMS DHANALAKSHMI COLLEGE OF ENGINEERING CHENNAI DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING YEAR/SEMESTER: II/IV IC6501 CONTROL SYSTEMS UNIT I SYSTEMS AND THEIR REPRESENTATION 1. What is the mathematical

More information

(Refer Slide Time: 00:01:30 min)

(Refer Slide Time: 00:01:30 min) Control Engineering Prof. M. Gopal Department of Electrical Engineering Indian Institute of Technology, Delhi Lecture - 3 Introduction to Control Problem (Contd.) Well friends, I have been giving you various

More information

EEE 184 Project: Option 1

EEE 184 Project: Option 1 EEE 184 Project: Option 1 Date: November 16th 2012 Due: December 3rd 2012 Work Alone, show your work, and comment your results. Comments, clarity, and organization are important. Same wrong result or same

More information

CHAPTER 1 Basic Concepts of Control System. CHAPTER 6 Hydraulic Control System

CHAPTER 1 Basic Concepts of Control System. CHAPTER 6 Hydraulic Control System CHAPTER 1 Basic Concepts of Control System 1. What is open loop control systems and closed loop control systems? Compare open loop control system with closed loop control system. Write down major advantages

More information

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A 1. What are the advantages of an inter connected system? The advantages of an inter-connected system are

More information

Application Note #3413

Application Note #3413 Application Note #3413 Manual Tuning Methods Tuning the controller seems to be a difficult task to some users; however, after getting familiar with the theories and tricks behind it, one might find the

More information

Analysis and Design of Control Systems in the Time Domain

Analysis and Design of Control Systems in the Time Domain Chapter 6 Analysis and Design of Control Systems in the Time Domain 6. Concepts of feedback control Given a system, we can classify it as an open loop or a closed loop depends on the usage of the feedback.

More information

MATLAB SIMULINK Based DQ Modeling and Dynamic Characteristics of Three Phase Self Excited Induction Generator

MATLAB SIMULINK Based DQ Modeling and Dynamic Characteristics of Three Phase Self Excited Induction Generator 628 Progress In Electromagnetics Research Symposium 2006, Cambridge, USA, March 26-29 MATLAB SIMULINK Based DQ Modeling and Dynamic Characteristics of Three Phase Self Excited Induction Generator A. Kishore,

More information

100 (s + 10) (s + 100) e 0.5s. s 100 (s + 10) (s + 100). G(s) =

100 (s + 10) (s + 100) e 0.5s. s 100 (s + 10) (s + 100). G(s) = 1 AME 3315; Spring 215; Midterm 2 Review (not graded) Problems: 9.3 9.8 9.9 9.12 except parts 5 and 6. 9.13 except parts 4 and 5 9.28 9.34 You are given the transfer function: G(s) = 1) Plot the bode plot

More information

You know for EE 303 that electrical speed for a generator equals the mechanical speed times the number of poles, per eq. (1).

You know for EE 303 that electrical speed for a generator equals the mechanical speed times the number of poles, per eq. (1). Stability 1 1. Introduction We now begin Chapter 14.1 in your text. Our previous work in this course has focused on analysis of currents during faulted conditions in order to design protective systems

More information

Self-Tuning Control for Synchronous Machine Stabilization

Self-Tuning Control for Synchronous Machine Stabilization http://dx.doi.org/.5755/j.eee.2.4.2773 ELEKTRONIKA IR ELEKTROTECHNIKA, ISSN 392-25, VOL. 2, NO. 4, 25 Self-Tuning Control for Synchronous Machine Stabilization Jozef Ritonja Faculty of Electrical Engineering

More information