Electrical Test Report on PS3300 Series Uninterruptible Power Supply for Powerstar Inc. Gaithersburg MD

Size: px
Start display at page:

Download "Electrical Test Report on PS3300 Series Uninterruptible Power Supply for Powerstar Inc. Gaithersburg MD"

Transcription

1 Test Report No No. of Pages 88 Electrical Test Report on PS3300 Series Uninterruptible Power Supply for Powerstar Inc. Gaithersburg MD Prepared by NU Laboratories, Inc. 312 Old Allerton Road, Annandale, NJ (908) Prepared By Checked By Approved By D. Welaish Sutphen J. Fred Gardner R.D. McAdoo 30 August August August 2007 Distribution: This report may be reproduced in full, partial reproduction may be made only with the written consent of the laboratory. The results in this report apply only to the equipment tested.

2 EUT: PS3300 Series Uninterruptible Power Supply of 88 Electrical TEST REPORT Manufacturer: Equipment Under Test: Test Report No.: : Powerstar Inc. PS3300 Series Uninterruptible Power Supply DOCUMENT HISTORY Revision Issue Date Affected Page(s) Description of Modifications 0 30 August 2007 Initial release Revised By Approved By TEST PERSONNEL NU Laboratories, Inc. Sean Macdonald 12, 13, 15, 18, 28, 29 June and 2 July 2007 EUT RECEIPT/DISPOSITION INFORMATION Date of Receipt of Equipment Under Test (EUT) Disposition of EUT 12 June 2007 in the electrical test area Retained by Manufacturer Test Facility NU Laboratories, Inc. Address 312 Old Allerton Road City, State Zip Code Annandale, NJ Phone Fax CERTIFICATION OF TECHNICAL CONFORMITY NU Laboratories of Annandale, NJ hereby certifies that, to the best of its knowledge and belief, the technical data delivered herewith under purchase order is complete, accurate, and complies with all requirements of the contract.

3 EUT: PS3300 Series Uninterruptible Power Supply of 88 1 Administrative Summary Reason for test To assure the compliance of Uninterruptible Power Supply to the requirements of MIL-STD-1399, Section 300A, as specified in purchase order Test sample PS3300 Series Uninterruptible Power Supply Model number PS3300RM-GDAIS-LCS-R2 Serial No Power supply 120 V ac / 60 Hz 30 amps max rated current Manufacturer name Address City, State, Zip Code Powerstar Inc Shady Grove Ct. Gaithersburg, MD Mfgr. representative Contact information Test location Tests performed Summary of the test results Jerry Carr Jerry Carr phone fax NU Laboratories, Inc. 312 Old Allerton Rd Annandale, NJ The following MIL-STD-1399, Section 300A, tests were performed: voltage and frequency tolerance test, voltage and frequency transient tolerance and recovery test, voltage spike test, emergency condition test, grounding test, equipment power profile test, current waveform test, equipment test, and voltage and frequency modulation test. Electrical tests were performed on the Uninterruptible Power Supply at the NU Laboratories, Inc. facility from 12 June to 2 July The equipment and associated cables, which may hereinafter be referred to as Equipment Under Test (EUT), were tested in accordance with the general procedures of MIL-STD-1399 Section 300A. The EUT met the requirements for all the tests performed with the exception of the harmonics tests. See the following summary tables for the test results.

4 EUT: PS3300 Series Uninterruptible Power Supply of 88 2 Summary of test results Procedure Voltage and frequency tolerance test Voltage and frequency transient tolerance and recovery test Applicable MIL- STD-1399 Par. Par Par Requirement Summary 123 V ac / 61.8 Hz 107 V ac / 58.2 Hz 138 V ac / 63.3 Hz 92 V ac / 56.7 Hz DATE STARTED DATE COMPLETED PASS/ FAIL 12 June June 07 Pass 13 June June 07 Pass Voltage spike test Par V line to line and line to ground 2 July 07 2 July 07 Pass ms dropout 2 minute dropout Emergency Frequency and voltage decay Par condition test 67.2 Hz / V ac for 2 minutes Table I (r-u) of MIL-STD June June 07 Pass Grounding test Par ,000 ohm line and neutral to ground. 15 June June 07 Pass Equipment power User voltage and power Par profile test characterized 15 June June 07 Pass 120 Hz to 20 khz Current waveform Par % of fundamental up to 32 test harmonic 15 June June 07 Fail * Equipment test Par V dc insulation resistance 29 June June 07 Pass Voltage and Frequency modulation 0.5% frequency Par Voltage modulation 2% modulation test 13 June June 07 Pass * Worst case harmonic 7.59% of the fundamental frequency

5 EUT: PS3300 Series Uninterruptible Power Supply of 88 Table of Contents 1 Administrative Summary Summary of test results Introduction Purpose of Tests Applicable Documents MILITARY OTHER DOCUMENTS Test Sample TABLE: CABLING OF THE EUT ELECTRICAL POWER TEST SAMPLE OPERATION PASS/FAIL CRITERIA MONITORING AND CRITICAL PARAMETERS Test Facility Description TEST SITE; FACILITIES, CONDITIONS AND TOLERANCES TEST EQUIPMENT DEVIATIONS AND EXCLUSIONS Test Setup Detailed Test Results VOLTAGE AND FREQUENCY TOLERANCE TEST VOLTAGE AND FREQUENCY TRANSIENT TOLERANCE AND RECOVERY VOLTAGE SPIKE TEST EMERGENCY CONDITION TEST GROUNDING TEST RESULTS USER EQUIPMENT POWER PROFILE TEST CURRENT WAVEFORM TEST...48 NU Laboratories, Inc EQUIPMENT TEST VOLTAGE AND FREQUENCY MODULATION TEST...85

6 EUT: PS3300 Series Uninterruptible Power Supply of 88 Index of Figures Figure 1. Voltage and frequency tolerance test setup...10 Figure 2. Voltage and frequency tolerance test data sheet cover...11 Figure 3. Voltage and frequency tolerance test data sheet...12 Figure 4. Voltage and frequency tolerance voltage high...13 Figure 5. Voltage and frequency tolerance voltage low...13 Figure 6. Voltage and frequency tolerance frequency high...14 Figure 7. Voltage and frequency tolerance frequency low...14 Figure 8. Voltage and frequency tolerance voltage and frequency high...15 Figure 9. Voltage and frequency tolerance voltage and frequency low...15 Figure 10: Voltage and frequency tolerance recovery test setup...17 Figure 11. Voltage and frequency transient tolerance and recovery test data sheet cover...18 Figure 12. Voltage and frequency transient tolerance and recovery data sheet...19 Figure 13. Transient tolerance and recovery voltage and frequency high...20 Figure 14. Transient tolerance and recovery voltage and frequency low...20 Figure 15. Voltage spike test setup...22 Figure 16. Voltage spike test data sheet cover...23 Figure 17. Voltage spike data sheet...24 Figure 18. Voltage spike line to line calibration...25 Figure 19. Voltage spike line to ground calibration...25 Figure 20. Voltage spike neutral to ground calibration...26 Figure 21. Voltage spike zero degrees positive calibration...26 Figure 22. Voltage spike zero degrees negative calibration...27 Figure 23. Voltage spike ninety degrees positive calibration...27 Figure 24. Voltage spike two-hundred and seventy degrees negative calibration...28 Figure 25. Voltage spike high side 0 º positive...28 Figure 26. Voltage spike high side 0 º negative...29 Figure 27. Voltage spike high side Line to line 90 º positive...29 Figure 28. Voltage spike high side 270 º negative...30 Figure 29. Voltage spike neutral 0 º positive...30 Figure 30. Voltage spike neutral 0 º negative...31 Figure 31. Voltage spike neutral 90 º positive...31 Figure 32. Voltage spike neutral 270 º negative...32 Figure 33: Emergency condition test setup...34 Figure 34. Emergency conditions test data sheet cover...36 Figure 35. Emergency condition data sheet...38 Figure 37. Grounding test setup...40 Figure 38. Emergency conditions test data sheet cover...41 Figure 39. Grounding test data sheet...42 Figure 41. User equipment test setup...44 Figure 42. User equipment power profile data sheet cover...46 Figure 43.User equipment power profile test data sheet...47 Figure 45. Current waveform test setup...49 Figure 46. Current waveform ambient measurements...49 Figure 47. User equipment power profile data sheet cover...51 Figure 48 Current waveform data sheet...52 Figure 50. Current waveform high side...59 Figure 51. Current waveform neutral side...66 Figure 53. Current waveform high side ambient...73 Figure 54: Current waveform neutral ambient...80 Figure 56: Equipment test setup...82 Figure 57. User equipment power profile data sheet cover...83 Figure 58. Equipment test mode...84 Figure 60. Voltage and frequency modulation test setup...86 Figure 61. Voltage and frequency modulation data sheet cover...87 Figure 63. Voltage and frequency modulation test data sheet...88

7 EUT: PS3300 Series Uninterruptible Power Supply of 88 3 Introduction This report documents the worst-case results of a series of MIL-STD-1399 Section 300A measurements performed on the Uninterruptible Power Supply manufactured by Powerstar Inc., of Gaithersburg MD. This series of tests was performed by NU Laboratories, Inc. test facility located in Annandale, NJ. 4 Purpose of Tests The purpose of these tests was to determine if the Uninterruptible Power Supply, hereinafter referred to as the EUT (Equipment Under Test), complied with requirements of MIL-STD-1399, Section 300A, as requested by purchase order No , when subjected to the referenced electrical test conditions. 5 Applicable Documents The following documents, of the exact issue shown, are applicable to the extent specified herein. 5.1 Military MIL-STD-1399, Section 300A, Notice 1, 11 March 1992 Interface Standards for Shipboard Systems, Electric Power, Alternating Current MIL-STD-45662A 01 August 1988 Calibration System Requirements 5.2 Other documents ANSI/NCSL Z540-1 General Requirements for Calibration Laboratories and Measuring and Test equipment 6 Test Sample PS3300 Series Uninterruptible Power Supply Model number: PS3300RM-GDAIS-LCS-R2 Serial number: The test sample is an uninterruptible 3.0 kva power supply operating from 120 V ac 50/60 Hz input power and supplying 120 V ac power to a maximum 2100 watt load. The EUT measures 5.25 high x 19 wide x 23.5 long and weighs approximately 105 lbs. 6.1 Table: Cabling of the EUT No. Description Tested Length Type Connected From Connected To 1.8 meters Unshielded shortened to less 1. Input power line three wire 10 Input power than 1.5 meters gauge for the spike test 2 Output power 1.8 meters Unshielded three wire 10 gauge EUT output California Instrument power source Resistive load bank 6.2 Electrical Power The EUT was powered from a California Instrument 4500L power source or utility 120 V ac source.

8 EUT: PS3300 Series Uninterruptible Power Supply of Test Sample Operation The power supply operates in one of two modes of operation: mode # 1 is normal 120 V ac output supplied from the 120 V ac mains operating into a 2100 watt incandescent light load bank; mode # 2 is supplying 120 V ac into the 2100 watt load bank from internal battery power. 6.4 Pass/Fail Criteria For the harmonic tests the pass/fail criteria were based on the test limits as specified in MIL-STD Signals exceeding these limits were considered out of specification. Signals below the specification limits were considered to pass. For all power tests electrical performance of the EUT was determined based on the successful operation of the EUT when subjected to the conditions identified in MIL-STD Successful operation is defined as no observable change in the output. During the emergency conditions tests the power supply may automatically change from operating mode # 1 to mode # 2. If during testing the EUT detects an over-current (> 30 Amps) at the input power, the power breaker will trip to off and the EUT will automatically switch to operating mode # 2. This is a protection circuit for the EUT and does not constitute a failure. 6.5 Monitoring and Critical Parameters The following items were monitored for proper operation: 1. The power supply output was connected to a 2100 watt incandescent light load bank and was visually monitored for normal operation. 2. The status of the input panel was monitored for normal operation. Monitoring of the EUT and determination of pass/fail was made by the test technician during the real time operation of the EUT. 7 Test Facility Description 7.1 Test Site; Facilities, Conditions and Tolerances Unless otherwise specified, all testing was conducted under the following conditions: Ambient Temperature +10 C to +36 C Relative Humidity Less than 95% Atmospheric Pressure 655 mm to 775 mm Hg 7.2 Test Equipment The equipment absolute performance calibration of the equipment requiring calibration is performed on an as-needed basis in accordance with MIL-STD or ANSI/NCSL. The test equipment is capable of making measurements within tolerances of at least +/- 2 db amplitude and +/-2% frequency deviation. Equipment certifications showing traceability to NIST (National Institute of Standards and Technology) are maintained on file at NU Laboratories, Inc. in Annandale, NJ. All equipment is checked and verified for proper operation before each series of tests. Specific test equipment used for each test is listed in each test section. Refer to the Table of Contents for the location. 7.3 Deviations and Exclusions Testing was performed according to the specification MIL-STD-1399 sec. 300A. Any deviations or exclusions to the tests performed are noted in the individual test sections. 8 Test Setup The EUT was set up in accordance with the manufacturers instructions. Test setup photos are located in each test section.

9 EUT: PS3300 Series Uninterruptible Power Supply of 88 9 Detailed Test Results This section specifies detailed emissions and susceptibility test results. General test requirements along with equipment used, photographs of the test setup and data sheets are included in this section. 9.1 Voltage and frequency tolerance test Purpose of test This test was to determine the effects of voltage and frequency variations on the EUT. During the performance of this test, the EUT was monitored for signs of susceptibility. Deviations and Exclusions There were no deviations from the MIL-STD-1399, Section 300A test requirement for the voltage and frequency tolerance tests. Test procedure Testing was performed in accordance with MIL-STD-1399, Section 300A, paragraph The EUT was tested at voltage upper limit of 123 volt, lower limit of 107 volts, upper frequency at 61.8 Hz, and lower frequency of 58.2 Hz. Test results During the voltage and frequency tolerance test, no malfunction, degradation of performance, or deviation from specified indications was detected when subjected to the test levels specified in MIL-STD-1399, Section 300A, paragraph Recommendations and conclusions The EUT, as tested, meets the applicable MIL-STD-1399 test specifications for voltage and frequency tolerance test. No further action is required. Test equipment for voltage and frequency tolerance recovery test Description Manufacturer Model Number Asset Number Calibration Due Dates Digital oscilloscope HP 54502A /08/07 10X probe HP 10430A N/A 09/08/07 Multimeter Fluke /23/08 Thermocouple monitor Omega RH /31/07 AC power source California Instruments 4500L 1187 Verified during use Temperature / Humidity Radio Shack /24/08

10 EUT: PS3300 Series Uninterruptible Power Supply of 88 Figure 1. Voltage and frequency tolerance test setup Test data sheets for voltage and frequency tolerance test Table: Index of test data sheets Description of Data sheet Data sheet cover 2 Test data sheet 3 Voltage high 4 Voltage low 5 Frequency high 6 Frequency low 7 Voltage and frequency high 8 Voltage and frequency low 9 Figure No.

11 EUT: PS3300 Series Uninterruptible Power Supply of 88 NU LABORATORIES, INC. Data Sheet Cover CUSTOMER: Powerstar, Inc. SALES ORDER NO: EUT: PS3300 series UPS Serial Number: Test Technician (S): Sean Macdonald Total Number of Pages: Test Witness: Test Witness: Organization: Organization: TEST REQUIREMENT Voltage and frequency tolerance LIMIT LEVEL Part SPECIAL CONDITIONS 123/107 V ac 61.8/58.2 Hz DATE STARTED DATE COMPLETE EUT Mode of Operation: EUT operated in mode # 1 with a 2100 watt resistive load Modulation Characteristics: N/A Sensor Type: N/A Detector Function: V rms / Hz PASS/ FAIL DEV 06/12/07 06/13/07 Pass SIM TECH/ ENGR The EUT meets operational requirements per the Performance Check Test prior to testing: Yes (X) No ( ) The EUT meets operational requirements per the Performance Check Test after testing: Yes (X) No ( ) Test comments: Complied with the voltage frequency tolerance test requirements. Testing was performed as reported: Authorized Signatory: Date: 13 June 2007 Figure 2. Voltage and frequency tolerance test data sheet cover

12 EUT: PS3300 Series Uninterruptible Power Supply of 88 Technician: Sean Macdonald Date: 12 and 13 June 2007 Client: Powerstar Inc. Order No: Operating Mode: 2.1 kva output Witness: EUT Initial Conditions Stabilization Time Voltage (Vac) Frequency (Hz) Temperature ( F) 11: Test Voltage Upper Limit Voltage Lower Limit Freq. Upper Limit Freq. Lower Limit System Stabilization Voltage (Vac) Frequency (Hz) (Time) Min Max Min Max EUT Temp ( F) Observed Effects Pass/ Fail Initial 11: No degradation Pass +30 min +60 min 12: No degradation Pass 12: No degradation Pass Initial 1: No degradation Pass +30 min +60 min 1: No degradation Pass 2: No degradation Pass Initial 2: No degradation Pass +30 min +60 min 2: No degradation Pass 3: No degradation Pass Initial 3: No degradation Pass +30 min +60 min 3: No degradation Pass 4: No degradation Pass Voltage Initial 4: No degradation Pass /Freq. +30 Upper min 4: No degradation Pass Limit +60 min 5: No degradation Pass Voltage Initial 8: No degradation Pass /Freq. +30 Lower min 9: No degradation Pass Limit +60 min 9: No degradation Pass Figure 3. Voltage and frequency tolerance test data sheet

13 EUT: PS3300 Series Uninterruptible Power Supply of 88 Figure 4. Voltage and frequency tolerance voltage high Figure 5. Voltage and frequency tolerance voltage low

14 EUT: PS3300 Series Uninterruptible Power Supply of 88 Figure 6. Voltage and frequency tolerance frequency high Figure 7. Voltage and frequency tolerance frequency low

15 EUT: PS3300 Series Uninterruptible Power Supply of 88 Figure 8. Voltage and frequency tolerance voltage and frequency high Figure 9. Voltage and frequency tolerance voltage and frequency low

16 EUT: PS3300 Series Uninterruptible Power Supply of Voltage and frequency transient tolerance and recovery Purpose of test This test was to determine the effects of voltage and frequency transients on the EUT. During the performance of this test, the EUT was monitored for signs of susceptibility. Deviations and exclusions There were no deviations from the MIL-STD-1399, Section 300A test requirement for the voltage and frequency transient tolerance and recovery tests. Test procedure Testing was performed in accordance with the Electrical MIL-STD-1399, Section 300A, paragraph Transient voltage test (upper limit) With the EUT energized and operating at the nominal voltage and frequency, a transient voltage of 138 V ac, single phase at 63.3 Hz was applied with a rise time of less than 0.1 seconds and held for a period of two (2) seconds while the EUT performance was monitored. Transient voltage test (lower limit) With the EUT energized and operating at the nominal voltage and frequency, a transient voltage of 92 V ac, single phase at 56.7 Hz was applied with a fall time of less than 0.1 seconds and held for a period of two (2) seconds while the EUT performance was monitored. Test results During the voltage and frequency transient tolerance and recovery test, no malfunction, degradation of performance, or deviation from specified indications was detected when subjected to the test levels specified in MIL-STD-1399, Section 300A, paragraph Recommendations and conclusions The EUT, as tested, meets the applicable MIL-STD-1399 test specifications for voltage and frequency transient tolerance and recovery test. No further action is required. Test equipment for voltage and frequency tolerance recovery test Description Manufacturer Model Calibration Due Asset Number Number Dates Digital oscilloscope HP 54502A /08/07 10X probe HP 10430A N/A 09/08/07 Multimeter Fluke /23/08 Thermocouple monitor Omega RH /31/07 AC power source California Instruments 4500L 1187 Verified during use Temperature / Humidity Radio Shack /24/08

17 EUT: PS3300 Series Uninterruptible Power Supply of 88 Figure 10: Voltage and frequency tolerance recovery test setup Test data sheets for voltage and frequency tolerance recovery test Table: Index of test data sheets Description of Data sheet Data sheet cover 11 Test data sheet 12 Voltage and frequency high plot 13 Voltage and frequency low plot 14 Figure No.

18 EUT: PS3300 Series Uninterruptible Power Supply of 88 NU LABORATORIES, INC. Data Sheet Cover CUSTOMER: Powerstar, Inc. SALES ORDER NO: EUT: PS3300 series UPS Serial Number: Test Technician (S): Sean Macdonald Total Number of Pages: Test Witness: Test Witness: Organization: Organization: TEST REQUIREMENT Voltage and frequency transient tolerance and recovery LIMIT LEVEL Part SPECIAL CONDITIONS 138/92 V ac 63.3/56.7 Hz DATE STARTED DATE COMPLETE EUT Mode of Operation: EUT operated in mode # 1 with a 2100 watt resistive load Modulation Characteristics: N/A Sensor Type: N/A Detector Function: Vrms / Hz PASS/ FAIL DEV 06/13/07 06/13/07 Pass SIM TECH/ ENGR The EUT meets operational requirements per the Performance Check Test prior to testing: Yes (X) No ( ) The EUT meets operational requirements per the Performance Check Test after testing: Yes (X) No ( ) Test comments: Complied with the voltage frequency tolerance and recovery test requirements. Testing was performed as reported: Authorized Signatory: Date: 13 June 2007 Figure 11. Voltage and frequency transient tolerance and recovery test data sheet cover

19 EUT: PS3300 Series Uninterruptible Power Supply of 88 Technician: Sean Macdonald Date: 13 June 2007 Client: Powerstar Inc. Order No: Operating Mode: 2.1 kva output Witness: Frequency (Hz) Input Voltage (V ac) Current (amps) Measurement Ambient temperature (º F) Stabilized temperature (º F) Transient Time Duration Min. Freq. Max. Freq. Hz Min. V ac Max V ac (sec) (sec) Hz Test condition Time Anticipated Measured Observed effect Pass/Fail Voltage and frequency high Voltage 138 V ac Frequency 63.3 Hz 63.4 Line current 23.0 No degradation Pass System Stabilized Voltage 115 V ac Frequency 60 Hz 60 Line current 22.7 N/A N/A Voltage low Frequency low Voltage 92 V ac 92.1 Frequency 56.7 Hz 56.9 Line current 22.6 No degradation Pass Figure 12. Voltage and frequency transient tolerance and recovery data sheet

20 EUT: PS3300 Series Uninterruptible Power Supply of 88 Figure 13. Transient tolerance and recovery voltage and frequency high Figure 14. Transient tolerance and recovery voltage and frequency low

21 EUT: PS3300 Series Uninterruptible Power Supply of Voltage spike test Purpose of test This test was to determine the effects of the specified voltage spikes on the EUT. During the performance of this test, the EUT was monitored for signs of susceptibility. Deviations and exclusions Testing was performed to the general requirements of MIL-STD-1399, Section 300A voltage spike test. The neutral to ground spike was less than 50 µs. Attempts to change capacitance and resistance values in accordance with the standard did not increase the pulse duration. Test procedure Testing was performed in accordance with MIL-STD-1399, paragraph With the EUT operating at the normal supply line voltage and frequency, both positive and negative voltage spikes of 1,000 volts were applied to the EUT from line to ground and neutral to ground at 0, 90, and 270 degrees of the power line frequency. The test setup includes line to line testing. The test was performed in accordance with Figure 19 of MIL-STD-1399 Section 300A. Test results During the voltage spike test, no malfunction, degradation of performance, or deviation from specified indications was detected. Recommendations and conclusions The EUT, as tested, meets the applicable MIL-STD-1399 voltage spike test. No further action is recommended. Test equipment for voltage spike test Description Manufacturer Model Number Asset Number Calibration Due Dates Digital oscilloscope HP 54502A /08/07 High voltage probe Tektronics /29/08 Spike generator Solar Verified during use AC power source Utility power N/A N/A N/A Multimeter Fluke /23/08 10 μf Capacitor General Electric 26F7514 N/A N/A 10 μf Capacitor General Electric 26F7514 N/A N/A 10 ohm Resistor N/A N/A N/A Verified 1 Ohm Resistor N/A N/A N/A Verified Thermocouple monitor Omega RH /31/07 Isolation transformer Stancor N/A N/A Cal. not required

22 EUT: PS3300 Series Uninterruptible Power Supply of 88 Figure 15. Voltage spike test setup Test data sheets for voltage spike test Table: Index of test data sheets Description of Data sheet Data sheet cover 16 Test data sheet 17 Line to line calibration 18 Line to ground calibration 19 Neutral to ground calibration positive calibration negative calibration positive calibration negative calibration positive high side negative high side positive high side negative high side positive neutral negative neutral positive neutral negative neutral 32 Figure No

23 EUT: PS3300 Series Uninterruptible Power Supply of 88 NU LABORATORIES, INC. Data Sheet Cover CUSTOMER: Powerstar Inc. SALES ORDER NO: EUT: PS3300 Series UPS Serial Number: Test Technician (S): Sean Macdonald Total Number of Pages: 10 Test Witness: Test Witness: Organization: Organization: TEST REQUIREMENT Voltage spike test LIMIT LEVEL Part SPECIAL CONDITIONS DATE STARTED DATE COMPLETE PASS/ FAIL DEV 1000 Volts 07/02/07 07/02/07 Pass SIM EUT Mode of Operation: : EUT operated in mode # 1 with a 2100 watt resistive load Modulation Characteristics: N/A Sensor Type: N/A Detector Function: Peak TECH/ ENGR The EUT meets operational requirements per the Performance Check Test prior to testing: Yes (X) No ( ) The EUT meets operational requirements per the Performance Check Test after testing: Yes (X) No ( ) Test comments: The EUT, as tested, complied with the MIL-STD-1399 Section 300A voltage spike test. Testing was performed as reported: Authorized Signatory: Date: 2 July 2007 Figure 16. Voltage spike test data sheet cover

24 EUT: PS3300 Series Uninterruptible Power Supply of 88 NU Laboratories, Inc. Voltage Spike Data Sheet Technician: Sean Macdonald Date: 14, 15, June and 2 July 2007 Client: Powerstar Inc. Order No: Operating Mode: 2.1 kva output Witness: Injected spike 1000 V peak Conductorto-ground Line-Ground Neutral to ground Synchronization angle Polarity Observed Effect Pass/ Fail 0 0 Positive No degradation Pass 90 0 Positive No degradation Pass 0 0 Negative No degradation Pass Negative No degradation Pass 0 0 Positive No degradation Pass 90 0 Positive No degradation Pass 0 0 Negative No degradation Pass Negative No degradation Pass Figure 17. Voltage spike data sheet

25 EUT: PS3300 Series Uninterruptible Power Supply of 88 Figure 18. Voltage spike line to line calibration Figure 19. Voltage spike line to ground calibration

26 EUT: PS3300 Series Uninterruptible Power Supply of 88 Figure 20. Voltage spike neutral to ground calibration Figure 21. Voltage spike zero degrees positive calibration

27 EUT: PS3300 Series Uninterruptible Power Supply of 88 Figure 22. Voltage spike zero degrees negative calibration Figure 23. Voltage spike ninety degrees positive calibration

28 EUT: PS3300 Series Uninterruptible Power Supply of 88 Figure 24. Voltage spike two-hundred and seventy degrees negative calibration Figure 25. Voltage spike high side 0º positive

29 EUT: PS3300 Series Uninterruptible Power Supply of 88 Figure 26. Voltage spike high side 0º negative Figure 27. Voltage spike high side Line to line 90º positive

30 EUT: PS3300 Series Uninterruptible Power Supply of 88 Figure 28. Voltage spike high side 270º negative Figure 29. Voltage spike neutral 0º positive

31 EUT: PS3300 Series Uninterruptible Power Supply of 88 Figure 30. Voltage spike neutral 0º negative Figure 31. Voltage spike neutral 90º positive

32 EUT: PS3300 Series Uninterruptible Power Supply of 88 Figure 32. Voltage spike neutral 270º negative

33 EUT: PS3300 Series Uninterruptible Power Supply of Emergency conditions test Purpose of test This test was to determine the effects of power interruptions, rapid re-application of power after an interruption, power source voltage and frequency decay, and emergency condition voltage and frequency tolerances. During the performance of this test, the EUT was monitored for signs of susceptibility. Deviations and exclusions There were no deviations from the MIL-STD-1399, Section 300A test requirement for the emergency conditions test. Test procedure Testing was performed in accordance with MIL-STD-1399, Section 300A, paragraph The EUT was operated in mode #1 as described in paragraph Milliseconds interruption test With the EUT energized and operating at the nominal voltage and frequency, the input voltage was interrupted for a period of 50 milliseconds. Test results During the 50 millisecond interruption the EUT had an audible sound indicating loss of ac power and switching to battery power. The unit recovered with no loss of output power. This is normal performance for the EUT. After the 50 millisecond interruption, no malfunction, degradation of performance, or deviation from specified indications was detected. Recommendations and conclusions The EUT, as tested, meets the applicable MIL-STD-1399, 50 millisecond interruption test. No further action is required. Two minute interruption test With the EUT energized and operating at the nominal voltage and frequency, the input voltage was interrupted for a period of two (2) minutes. Test results During the two minute interruption, the EUT switched to battery backup with an audible sound every 10 seconds indicating loss of ac power. After the two minute dropout test, no malfunction, degradation of performance, or deviation from specified indications was detected. Recommendations and conclusions The EUT, as tested, meets the applicable MIL-STD-1399 two minute interruption test. No further action is required. Voltage and frequency decay test With the EUT operating at the nominal supply line voltage and frequency, a line voltage and frequency decay having the characteristics of those shown in the Half-Load in Figure 3 of MIL-STD-1399, Section 300A was applied while monitoring the EUT performance. Test results As the voltage approached 90 V ac / 30 Hz, the current draw exceeded 32 amps. The EUT tripped its power breaker to off and switched to battery power. When ac input power was restored, the EUT stayed in the battery mode until the power breaker was manually turned on. There was no loss of output power during this test. After the voltage and frequency decay test, no malfunction, degradation of performance, or deviation from specified indications was detected when the EUT was supplied with normal ac power as specified in MIL-STD-1399, Section 300A.

34 EUT: PS3300 Series Uninterruptible Power Supply of 88 Recommendations and conclusions The EUT, as tested, meets the applicable MIL-STD-1399 voltage and frequency decay test. No further action is required. Emergency condition test The input voltage to the EUT was increased 35% to V ac and the input frequency was increased 12% to 67.2 Hz for a period of two (2) minutes. Test results During the emergency condition test the EUT switched to battery power with an audible sound twice every 5 seconds indicating the change of state. On return to normal power the EUT returned to normal operation without manual intervention. After the emergency condition test, there was no malfunction, degradation of performance, or deviation from specified indications with the EUT operated at normal power levels specified in MIL-STD Recommendations and conclusions The EUT, as tested, meets the applicable MIL-STD-1399 emergency condition test. No further action is required. Test equipment for emergency condition test Description Manufacturer Model Number Asset Number Calibration Due Dates Digital oscilloscope HP 54502A /08/07 10X probe HP 10430A N/A 09/08/07 Multimeter Fluke /23/08 Thermocouple monitor Omega RH /31/07 AC power source California Verified during 4500L 1187 Instruments use Temperature / Humidity Radio Shack /24/08 Figure 33: Emergency condition test setup

35 EUT: PS3300 Series Uninterruptible Power Supply of 88 Test data sheets for emergency condition test Table: Index of test data sheets Description of Data sheet Data sheet cover 34 Emergency conditions data sheet 35 Figure No.

36 EUT: PS3300 Series Uninterruptible Power Supply of 88 NU LABORATORIES, INC. Data Sheet Cover CUSTOMER: Powerstar Inc. SALES ORDER NO: EUT: PS3300 Series UPS Serial Number: Test Technician (S): Sean Macdonald Total Number of Pages: 5 Test Witness: Test Witness: Organization: Organization: TEST REQUIREMENT Emergency conditions LIMIT LEVEL Part SPECIAL CONDITIONS ms dropout 2 minute dropout Frequency and voltage decay 67.2 Hz/ V ac for 2 minutes Table I (r-u) DATE STARTED DATE COMPLETE PASS/ FAIL DEV 06/13/07 06/13/07 Pass SIM EUT Mode of Operation: The EUT was operated in mode # 1 with a 2100 watt resistive load Modulation Characteristics: N/A Sensor Type: N/A Detector Function: Peak TECH/ ENGR The EUT meets operational requirements per the Performance Check Test prior to testing: Yes (X) No ( ) The EUT meets operational requirements per the Performance Check Test after testing: Yes (X) No ( ) Test comments: EUT complied with the emergency test requirement. Testing was performed as reported: Authorized Signatory: Date: 13 June 2007 Figure 34. Emergency conditions test data sheet cover

37 EUT: PS3300 Series Uninterruptible Power Supply of 88

38 EUT: PS3300 Series Uninterruptible Power Supply of 88 Figure 35. Emergency condition data sheet

39 EUT: PS3300 Series Uninterruptible Power Supply of Grounding Test Results Purpose of test This test is to determine the effects of grounding one power line on a system that is normally ungrounded as specified in MIL-STD-1399 Section 300A paragraph Deviations and exclusions There were no deviations from the MIL-STD-1399, Section 300A test requirement for the grounding test. Test procedure Testing was performed in accordance with the MIL-STD-1399, Section 300A, paragraph The EUT was operated in mode # 1as described in Section 6.3. With the EUT energized and operating at the nominal voltage and frequency, the line input was grounded for a period of 1 minute through a 100,000-Ohm resistor. Test results During the grounding test, no malfunction, degradation of performance, or deviation from specified indications was detected. Recommendations and conclusions The EUT, as tested, meets the applicable MIL-STD-1399 grounding test. No further action is required. Test equipment for grounding test Description Manufacturer Model Number Asset Number Calibration Due Dates Digital oscilloscope HP 54502A /08/07 10X probe HP 10430A N/A 09/08/07 Multimeter Fluke /23/08 AC power source California Instruments 4500L 1187 Verified during use Resistor (100,000) ohms Verified before us Circuit breaker Square D QOU110 N/A Cal. not required

40 EUT: PS3300 Series Uninterruptible Power Supply of 88 Figure 36. Grounding test setup Test data sheets for grounding test Table: Index of test data sheets Description of Data sheet Data sheet cover 38 Grounding test data sheet 39 Figure No.

41 EUT: PS3300 Series Uninterruptible Power Supply of 88 NU LABORATORIES, INC. Data Sheet Cover CUSTOMER: Powerstar Inc. SALES ORDER NO: EUT: PS3300 Series UPS Serial Number: Test Technician (S): Sean Macdonald Total Number of Pages: 2 Test Witness: Test Witness: Organization: Organization: TEST REQUIREMENT Grounding test LIMIT LEVEL Part SPECIAL CONDITIONS DATE STARTED DATE COMPLETE PASS/ FAIL DEV 100,000 ohm 06/15/07 06/15/07 Pass SIM EUT Mode of Operation: The EUT was operated in mode # 1 with a 2100 watt resistive load Modulation Characteristics: N/A Sensor Type: N/A Detector Function: Peak TECH/ ENGR The EUT meets operational requirements per the Performance Check Test prior to testing: Yes (X) No ( ) The EUT meets operational requirements per the Performance Check Test after testing: Yes (X) No ( ) Test comments: EUT complied with the grounding test requirement. Testing was performed as reported: Authorized Signatory: Date: 15 June 2007 Figure 37. Emergency conditions test data sheet cover

42 EUT: PS3300 Series Uninterruptible Power Supply of 88 NU Laboratories, Inc. Grounding Test Data Sheet Technician: Sean Macdonald Date: 15 June 2007 Client: Powerstar Inc. Order No: Operating Mode: 2.1 kva resistive load Witness: Grounding test high line Breaker Duration Observed Effect Off N/A Operational On 1 minute Operational Grounding test neutral line Breaker Duration Observed Effect Off N/A Operational On 1 minute Operational Figure 38. Grounding test data sheet

43 EUT: PS3300 Series Uninterruptible Power Supply of User Equipment Power profile test Purpose of test This test is to characterize the power demand as specified in MIL-STD-1399 Section 300A paragraph Deviations and exclusions There were no deviations from the MIL-STD-1399, Section 300A test requirement for the user equipment power profile test. Test procedure Testing was performed in accordance with MIL-STD-1399, Section 300A, paragraph with the EUT operated in mode # 1 as described in paragraph 6.3. With the EUT operating normally with input power of 115 V ac / 60Hz, single phase the power input voltages, line current, power factor, and power (kw) were measured and recorded. Additionally, the EUT was de-energized and re-energized to determine surge currents during transition. Test results See the data sheet for the user equipment power profile. Recommendations and conclusions See the data sheets for the power characteristics of the EUT. Test equipment for user equipment power profile test Description Manufacturer Model Number Asset Calibration Due number Dates Digital oscilloscope HP 54502A /08/07 10X probe HP 10430A N/A 09/08/07 Clamp on meter/voltage probe Chauvin Arnoux F /12/08 AC power source California Instruments 4500L 1187 Verified during use Multimeter Fluke /23/08

44 EUT: PS3300 Series Uninterruptible Power Supply of 88 Figure 39. User equipment test setup

45 EUT: PS3300 Series Uninterruptible Power Supply of 88 Test data sheets for user equipment power profile test Table: Index of test data sheets Description of Data sheet Data sheet cover 42 User equipment power profile data sheet 43 Page No.

46 EUT: PS3300 Series Uninterruptible Power Supply of 88 NU LABORATORIES, INC. Data Sheet Cover CUSTOMER: Powerstar Inc. SALES ORDER NO: Test Technician (S): Test Witness: EUT: PS3300 Series UPS Serial Number: Sean Macdonald Total Number of Pages: Organization: 2 Test Witness: Organization: TEST REQUIREMENT User equipment power profile LIMIT LEVEL Part SPECIAL CONDITIONS User equipment profile DATE STARTED DATE COMPLETE EUT Mode of Operation: EUT operated in mode # 1 with a 2100 watt resistive load Modulation Characteristics: N/A Sensor Type: N/A Detector Function: RMS PASS/ FAIL DEV TECH/ ENGR 06/15/07 06/15/07 N/A SIM The EUT meets operational requirements per the Performance Check Test prior to testing: Yes (X) No ( ) The EUT meets operational requirements per the Performance Check Test after testing: Yes (X) No ( ) Test comments: See the data sheets for user equipment power profile Testing was performed as reported: Authorized Signatory: Date: 15 June 2007 Figure 40. User equipment power profile data sheet cover

47 EUT: PS3300 Series Uninterruptible Power Supply of 88 NU Laboratories, Inc. Equipment Power Profile Data Sheet Technician: Sean Macdonald Date: 15 June 2007 Client: Powerstar Inc. Order No: Operating Mode: 2.1 kva resistive load Witness: Equipment Power Measurement Data Equipment Power Profile Min Max Measured Input Power Voltage Input Line Current Power Factor 0.99 leading Power 2.58 kw No load Full load Line Voltage Line Current 2.3 A 22.9 A Surge Current 4.5 A 23.9 A Calculate and Record Type of Power Voltage Power Factor Power Rated (kw) Surge Current Spike Generation Type I single phase ungrounded 115 V ac / 60 Hz 0.99 leading 3.45 kw 23.9 A None detected Power Source Characteristics Power Source Rating Cable Length Cable Type 312 V ac; 5.4 kva / 5 khz; 3 phase 1.8 meters 10 AWG 3 connector FTZ LL57S55 Figure 41.User equipment power profile test data sheet

48 EUT: PS3300 Series Uninterruptible Power Supply of Current waveform test Purpose of test This test is to determine the harmonic content of the EUT input power lines from 120 Hz to 20 khz as specified in MIL-STD-1399 Section 300A paragraph The individual line harmonic current from the second harmonic through the 32 nd harmonic shall not exceed 3% of the fundamental load current. Above the 32 nd harmonic the harmonic current shall not exceed a magnitude of 100/n percent of the EUT s rated full load fundamental current where n equals the line harmonic multiplier. Deviations and exclusions There were no deviations from the MIL-STD-1399, Section 300A test requirement for the current waveform test. Test procedure Testing was performed in accordance with MIL-STD-1399, Section 300A, paragraph with the EUT operated in mode #1 as described in paragraph 6.3. With the EUT operating at the nominal supply line voltage and frequency, the input harmonic content from the line frequency up to 20 khz was measured. Test results The EUT exceed the harmonic content at the 3 rd, 5 th, and 7 th harmonic. Ambient measurements were made and subtracted out of the test data as specified MIL-STD-1399, Section 300A, paragraph Recommendations and conclusions The EUT, as tested, does not meet the applicable MIL-STD-1399 current waveform requirements. Test equipment for current waveform test Description Manufacturer Model Number Serial Number Calibration Due Dates Clamp on meter/voltage probe Chauvin Arnoux F BD DV 06/12/08 AC power source California Instruments 4500L 1187 Cal. not required Multimeter Fluke /23/08 Current probe Electro Metrics PCL /11/07 Analyzer Rockland RS100 Marketing 1 11/09/07

49 EUT: PS3300 Series Uninterruptible Power Supply of 88 Figure 42. Current waveform test setup Figure 43. Current waveform ambient measurements

50 EUT: PS3300 Series Uninterruptible Power Supply of 88 Test data sheets for current waveform test Table: Index of test data sheets Description of Data sheet Data sheet cover 47 Data sheet 48 High side tabulated data 49 Low side tabulated data 50 High side tabulated data 51 Neutral tabulated data 52 Figure No.

51 EUT: PS3300 Series Uninterruptible Power Supply of 88 NU LABORATORIES, INC. Data Sheet Cover CUSTOMER: Powerstar Inc. SALES ORDER NO: EUT: PS3300 Series UPS Serial Number: Test Technician (S): Sean Macdonald Total Number of Pages: 37 Test Witness: Test Witness: Organization: Organization: TEST REQUIREMENT Current waveform test LIMIT LEVEL Part SPECIAL CONDITIONS DATE STARTED DATE COMPLETE PASS/ FAIL DEV TECH/ ENGR 3% harmonic 06/15/07 06/15/07 Fail SIM EUT Mode of Operation: The EUT was operated in mode # 1 with a 2100 watt resistive load Modulation Characteristics: N/A Sensor Type: N/A Detector Function: RMS The EUT meets operational requirements per the Performance Check Test prior to testing: Yes (X) No ( ) The EUT meets operational requirements per the Performance Check Test after testing: Yes (X) No ( ) Test comments: The EUT did not meet the current waveform harmonic requirement at the 3 rd, 5 th, and 7 th harmonic. Testing was performed as reported: Authorized Signatory: Date: 15 June 2007 Figure 44. User equipment power profile data sheet cover

52 EUT: PS3300 Series Uninterruptible Power Supply of 88 NU Laboratories, Inc. Current waveform test data sheet Technician: Sean Macdonald Date: 15 June 2007 Client: Powerstar Inc. Order No: Operating Mode: 2.1 kw resistive Witness: Measured Input Line Current waveform test data Harmonic measured Frequency Measured level (% of fundamental) Pass/Fail 3rd 180 Hz 7.53 Fail 5th 300 Hz 4.20 Fail 7th 420 Hz 3.28 Fail 8 th through 333 rd 480 Hz to 20 khz < limit Pass Neutral 3rd 180 Hz 7.59 Fail 5th 300 Hz 4.19 Fail 7th 420 Hz 3.24 Fail 8 th through 333 rd 480 Hz to 20 khz < limit Pass Figure 45 Current waveform data sheet

53 EUT: PS3300 Series Uninterruptible Power Supply of Powerstar Harmonic Line Current vs Frequency (Line) PS Percentage of Fundamental 0 Harmonic ,320 1,920 2,520 3,120 3,720 4,320 4,920 5,520 6,120 6,720 7,320 7,920 8,520 9,120 9,720 10,320 10,920 11,520 12,120 12,720 13,320 13,920 14,520 15,120 15,720 16,320 16,920 17,520 18,120 18,720 19,320 19,920 Frequency (Hz) Harmonic Limit Frequency Harmonic dbuv PCL-10 dbua Amperes % Limit Status Threshold Fail Fail Fail

54 EUT: PS3300 Series Uninterruptible Power Supply of 88 Frequency Harmonic dbuv PCL-10 dbua Amperes % Limit Status Threshold

55 EUT: PS3300 Series Uninterruptible Power Supply of 88 Frequency Harmonic dbuv PCL-10 dbua Amperes % Limit Status Threshold

56 EUT: PS3300 Series Uninterruptible Power Supply of 88 Frequency Harmonic dbuv PCL-10 dbua Amperes % Limit Status Threshold

57 EUT: PS3300 Series Uninterruptible Power Supply of 88 Frequency Harmonic dbuv PCL-10 dbua Amperes % Limit Status Threshold

58 EUT: PS3300 Series Uninterruptible Power Supply of 88 Frequency Harmonic dbuv PCL-10 dbua Amperes % Limit Status Threshold

59 EUT: PS3300 Series Uninterruptible Power Supply of 88 Frequency Harmonic dbuv PCL-10 dbua Amperes % Limit Status Threshold Figure 46. Current waveform high side

60 EUT: PS3300 Series Uninterruptible Power Supply of Powerstar Harmonic Line Current vs Frequency (Neutral) PS Percentage of Fundamental 0 Harmonic ,320 1,920 2,520 3,120 3,720 4,320 4,920 5,520 6,120 6,720 7,320 7,920 8,520 9,120 9,720 10,320 10,920 11,520 12,120 12,720 13,320 13,920 14,520 15,120 15,720 16,320 16,920 17,520 18,120 18,720 19,320 19,920 Frequency (Hz) Harmonic Limit Frequency Harmonic dbuv PCL-10 dbua Amperes % Limit Status Threshold Fail Fail Fail

61 EUT: PS3300 Series Uninterruptible Power Supply of 88 Frequency Harmonic dbuv PCL-10 dbua Amperes % Limit Status Threshold

62 EUT: PS3300 Series Uninterruptible Power Supply of 88 Frequency Harmonic dbuv PCL-10 dbua Amperes % Limit Status Threshold

63 EUT: PS3300 Series Uninterruptible Power Supply of 88 Frequency Harmonic dbuv PCL-10 dbua Amperes % Limit Status Threshold

64 EUT: PS3300 Series Uninterruptible Power Supply of 88 Frequency Harmonic dbuv PCL-10 dbua Amperes % Limit Status Threshold

65 EUT: PS3300 Series Uninterruptible Power Supply of 88 Frequency Harmonic dbuv PCL-10 dbua Amperes % Limit Status Threshold

66 EUT: PS3300 Series Uninterruptible Power Supply of 88 Frequency Harmonic dbuv PCL-10 dbua Amperes % Limit Status Threshold Figure 47. Current waveform neutral side

67 EUT: PS3300 Series Uninterruptible Power Supply of Powerstar Harmonic Line Current vs Frequency (Line) Ambient 5 Percentage of Fundamental 0 Harmonic ,320 1,920 2,520 3,120 3,720 4,320 4,920 5,520 6,120 6,720 7,320 7,920 8,520 9,120 9,720 10,320 10,920 11,520 12,120 12,720 13,320 13,920 14,520 15,120 15,720 16,320 16,920 17,520 18,120 18,720 19,320 19,920 Frequency (Hz) Harmonic Limit Frequency Harmonic dbuv PCL-10 dbua Amperes % Limit Status Threshold

68 EUT: PS3300 Series Uninterruptible Power Supply of 88 Frequency Harmonic dbuv PCL-10 dbua Amperes % Limit Status Threshold

69 EUT: PS3300 Series Uninterruptible Power Supply of 88 Frequency Harmonic dbuv PCL-10 dbua Amperes % Limit Status Threshold

70 EUT: PS3300 Series Uninterruptible Power Supply of 88 Frequency Harmonic dbuv PCL-10 dbua Amperes % Limit Status Threshold

71 EUT: PS3300 Series Uninterruptible Power Supply of 88 Frequency Harmonic dbuv PCL-10 dbua Amperes % Limit Status Threshold

72 EUT: PS3300 Series Uninterruptible Power Supply of 88 Frequency Harmonic dbuv PCL-10 dbua Amperes % Limit Status Threshold

73 EUT: PS3300 Series Uninterruptible Power Supply of 88 Frequency Harmonic dbuv PCL-10 dbua Amperes % Limit Status Threshold Figure 48. Current waveform high side ambient

74 EUT: PS3300 Series Uninterruptible Power Supply of Powerstar Harmonic Line Current vs Frequency (Neutral) Ambient 5 Percentage of Fundamental 0 Harmonic ,320 1,920 2,520 3,120 3,720 4,320 4,920 5,520 6,120 6,720 7,320 7,920 8,520 9,120 9,720 10,320 10,920 11,520 12,120 12,720 13,320 13,920 14,520 15,120 15,720 16,320 16,920 17,520 18,120 18,720 19,320 19,920 Frequency (Hz) Harmonic Limit Frequency Harmonic dbuv PCL-10 dbua Amperes % Limit Status Threshold

75 EUT: PS3300 Series Uninterruptible Power Supply of 88 Frequency Harmonic dbuv PCL-10 dbua Amperes % Limit Status Threshold

76 EUT: PS3300 Series Uninterruptible Power Supply of 88 Frequency Harmonic dbuv PCL-10 dbua Amperes % Limit Status Threshold

77 EUT: PS3300 Series Uninterruptible Power Supply of 88 Frequency Harmonic dbuv PCL-10 dbua Amperes % Limit Status Threshold

78 EUT: PS3300 Series Uninterruptible Power Supply of 88 Frequency Harmonic dbuv PCL-10 dbua Amperes % Limit Status Threshold

79 EUT: PS3300 Series Uninterruptible Power Supply of 88 Frequency Harmonic dbuv PCL-10 dbua Amperes % Limit Status Threshold

80 EUT: PS3300 Series Uninterruptible Power Supply of 88 Frequency Harmonic dbuv PCL-10 dbua Amperes % Limit Status Threshold Figure 49: Current waveform neutral ambient

81 EUT: PS3300 Series Uninterruptible Power Supply of Equipment test Purpose of test This test was to determine the insulation resistance of the EUT input power lines with the normal input power disconnected. Deviations and exclusions There were no deviations from the MIL-STD-1399, Section 300A test requirement for the equipment test. Test procedure Testing was performed in accordance with MIL-STD-1399, Section 300A, paragraph The input power lines of the EUT were subjected to a 500 V dc insulation resistance test with the input power disconnected. After completion of the test, the EUT power was connected, the EUT was energized, and the operation checked under normal power. Test results No malfunction, degradation of performance, or deviation from specified indications was detected after performing the insulation resistance test when the EUT was subjected to the test levels specified in MIL-STD-1399, Section 300A, paragraph Recommendations and conclusions The EUT, as tested, meets the modified MIL-STD-1399 equipment test requirements. No further action is required. Test equipment for equipment test Description Manufacturer Model Number Asset number Calibration Due Dates AC power source California Instruments 4500L 1187 Verified before use Megohmmeter GenRad /25/08 Clamp on meter/voltage probe Chauvin Arnoux F /12/08

82 EUT: PS3300 Series Uninterruptible Power Supply of 88 Figure 50: Equipment test setup Test data sheets for equipment test Table: Index of test data sheets Description of Data sheet Data sheet cover 57 Insulation resistance data sheet 58 Figure No.

83 EUT: PS3300 Series Uninterruptible Power Supply of 88 NU LABORATORIES, INC. Data Sheet Cover CUSTOMER: Powerstar Inc. SALES ORDER NO: Test Technician (S): Test Witness: EUT: PS3300 Series UPS Serial Number: Sean Macdonald Total Number of Pages: Organization: 2 Test Witness: Organization: TEST REQUIREMENT Equipment test LIMIT LEVEL Part SPECIAL CONDITIONS DATE STARTED DATE COMPLETE PASS/ FAIL DEV 500 volts 06/29/07 06/29/07 Pass SIM EUT Mode of Operation: EUT operated in mode # 1 with a 2100 watt resistive load Modulation Characteristics: N/A Sensor Type: Megohmeter Detector Function: Ohms TECH/ ENGR The EUT meets operational requirements per the Performance Check Test prior to testing: Yes (X) No ( ) The EUT meets operational requirements per the Performance Check Test after testing: Yes (X) No ( ) Test comments: The EUT, as tested meets the MIL-STD-1399 equipment test requirement. Testing was performed as reported: Authorized Signatory: Date: 29 June 2007 Figure 51. User equipment power profile data sheet cover

84 EUT: PS3300 Series Uninterruptible Power Supply of 88 NU Laboratories, Inc. Equipment Test Data Sheet Technician: Sean Macdonald Date: 29 June 2007 Client: Powerstar Inc. Order No: Operating Mode: 2.1 KW into a resistive load Witness: Equipment Test Data-Line to Chassis Equipment Test Line to Case Ground DC Megohmmeter Measured 500 V dc Insulation resistance 530 M Ω Equipment Test Data-Neutral to Chassis Equipment Test Neutral to Case Ground DC Megohmmeter Measured 500 V dc Insulation resistance 400 M Ω Figure 52. Equipment test mode

85 EUT: PS3300 Series Uninterruptible Power Supply of Voltage and frequency modulation test Purpose of test This test was to determine the effects of voltage and frequency modulation on the EUT. During the performance of this test, the EUT was monitored for signs of susceptibility. Deviations and exclusions There were no deviations from the MIL-STD-1399, Section 300A test requirement for the voltage and frequency modulation test. Test procedure Testing was performed in accordance with MIL-STD-1399, Section 300A, paragraph with the EUT operated in mode #1 as described in paragraph 6.3. With the EUT operating at the normal voltage and frequency, the input voltage and frequency were varied separately and then simultaneously in accordance with a frequency modulation of 0.5% and a voltage modulation of 2%. Test results During the voltage and frequency modulation test, no malfunction, degradation of performance, or deviation from specified indications was detected when subjected to the test levels specified in MIL-STD-1399, Section 300A, paragraph Recommendations and Conclusions The EUT, as tested, meets the applicable MIL-STD-1399 voltage and frequency modulation requirements. No further action is required. Test equipment for voltage frequency and modulation test Description Manufacturer Model Number Assent Calibration Due number Dates Digital oscilloscope HP 54502A /08/07 10X probe HP 10430A N/A 09/08/07 Clamp on meter/voltage probe Chauvin Arnoux F /12/08 Thermocouple monitor Omega RH /31/07 AC power source California Instruments 4500L 1187 Verified during use

86 EUT: PS3300 Series Uninterruptible Power Supply of 88 Figure 53. Voltage and frequency modulation test setup Test data for voltage frequency and modulation test Table: Index of test data sheets Description of Data sheet Data sheet cover 61 Test data sheet 62 Figure No.

87 EUT: PS3300 Series Uninterruptible Power Supply of 88 NU LABORATORIES, INC. Data Sheet Cover CUSTOMER: Powerstar Inc. SALES ORDER NO: EUT: PS3300 Series UPS Serial Number: Test Technician (S): Sean Macdonald Total Number of Pages: 2 Test Witness: Test Witness: Organization: Organization: TEST REQUIREMENT Voltage and frequency modulation LIMIT LEVEL Part SPECIAL CONDITIONS Frequency modulation 0.5% Voltage modulation 2% DATE STARTED DATE COMPLETE EUT Mode of Operation: EUT operated in mode # 1 with a 2100 watt resistive load Modulation Characteristics: N/A Sensor Type: N/A Detector Function: RMS PASS/ FAIL DEV 06/13/07 06/13/07 Pass SIM TECH/ ENGR The EUT meets operational requirements per the Performance Check Test prior to testing: Yes (X) No ( ) The EUT meets operational requirements per the Performance Check Test after testing: Yes (X) No ( ) Test comments: The EUT, as tested meets the MIL-STD-1399 frequency modulation test requirement. Testing was performed as reported: Authorized Signatory: Date: 13 June 2007 Figure 54. Voltage and frequency modulation data sheet cover

88 EUT: PS3300 Series Uninterruptible Power Supply of 88 Figure 55. Voltage and frequency modulation test data sheet

792A AC/DC Transfer Standard

792A AC/DC Transfer Standard 92A AC/DC Transfer Standard Technical Data Support for your most demanding ac measurement requirements ppm total uncertainty Traceable to national standards range: 2 mv to 00 V Frequency range: Hz to 1

More information

792A AC/DC Transfer Standard

792A AC/DC Transfer Standard 92A AC/DC Transfer Standard Technical Data Support for your most demanding ac measurement requirements ppm total uncertainty Traceable to national standards range: 2 mv to 00 V Frequency range: Hz to 1

More information

Test Report EN (2008)

Test Report EN (2008) Test Report EN 62233 (2008) Product Name and address of the applicant Name and address of the manufacturer Model Rating Brand name Heating elements for building into floors Advanced Heating Technologies

More information

SUMMARY REPORT PART DESCRIPTION SSM-110-S-DV, TSM S-DV

SUMMARY REPORT PART DESCRIPTION SSM-110-S-DV, TSM S-DV SUMMARY REPORT PART DESCRIPTION SSM-110-S-DV, TSM-110-01-S-DV File: J:\QA LAB\Test Programs\TC0121-027C-0434\ TC0121-027C-0434.doc Form 01 Rev 01 Page 1 of 11 CERTIFICATION All instruments and measuring

More information

Film Capacitors. EMI suppression capacitors. Date: June 2018

Film Capacitors. EMI suppression capacitors. Date: June 2018 Film Capacitors EMI suppression capacitors Date: June 2018 EPCOS AG 2018. Reproduction, publication and dissemination of this publication, enclosures hereto and the information contained therein without

More information

WIESON TECHNOLOGIES CO., LTD.

WIESON TECHNOLOGIES CO., LTD. TABLE OF CONTENT 1. Scope.... 2 2. Reference Documents. 2 3. Material and Components.... 2 4. Design and Construction.... 2 5. Rating.. 2 6. Performance and Test Descriptions. 2 7. Test Requirements and

More information

GENERATOR INTERCONNECTION APPLICATION

GENERATOR INTERCONNECTION APPLICATION GENERATOR INTERCONNECTION APPLICATION FOR BUY-ALL/SELL-ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 20 KW BUT LESS THAN OR EQUAL TO 1 MW Electric Utility Contact Information Great Lakes Energy

More information

Qualification Test Report. Modular Plugs, Unshielded and Shielded

Qualification Test Report. Modular Plugs, Unshielded and Shielded Qualification Test Report 501-131013 26 JAN 16 Rev. A Modular Plugs, Unshielded and Shielded 1. INTRODUCTION 1.1. Purpose Testing was performed on modular plugs to determine their conformance to the requirements

More information

Solder Joint Reliability Lucent X Summary Report

Solder Joint Reliability Lucent X Summary Report Project Number: Tracking Code: 0217--0671 Requested by: Danny Boesing Date: 4/23/02 Product Rev: 4 Part #: QTS-100-01-L-D-RA Lot #: 01/02/02 Tech: Troy Cook Eng: John Tozier Part description: 0.635mm Double

More information

Chip tantalum capacitors (Fail-safe open structure type)

Chip tantalum capacitors (Fail-safe open structure type) TCFG1C6M8R Chip tantalum capacitors (Fail-safe open structure type) TCFG Series Case Features 1) Safety design by open function built - in. 2) Wide capacitance range 3) Screening by thermal shock. Dimensions

More information

Solder Joint Reliability Report

Solder Joint Reliability Report Project Number: NA Tracking Code: 0218--0678 Requested by: Brian Vicich Date: 4/30/02 Product Rev: A Part #: QTS-100-01-L-D-A / QSS-100-01-L-D-A Lot #: 1/02/02 Tech: Troy Cook Eng: John Tozier Qty to test:

More information

Chip tantalum capacitors (Fail-safe open structure type)

Chip tantalum capacitors (Fail-safe open structure type) TCFG0J106M8R Chip tantalum capacitors (Fail-safe open structure type) TCFG Series Case Features 1) Safety design by open function built - in. 2) Wide capacitance range 3) Screening by thermal shock. Dimensions

More information

Model M3484 Industrial Line Noise Filter Module Customer Reference Manual

Model M3484 Industrial Line Noise Filter Module Customer Reference Manual Model M3484 Industrial Line Noise Filter Module Customer Reference Manual Web: www.bonitron.com Tel: 615-244-2825 Email: info@bonitron.com Bonitron, Inc. Bonitron, Inc. Nashville, TN An industry leader

More information

Distributing Tomorrow s Technologies For Today s Designs Toll-Free:

Distributing Tomorrow s Technologies For Today s Designs Toll-Free: 2W, Ultra-High Isolation DIP, Single & DC/DC s Key Features Low Cost 6 Isolation MTBF > 6, Hours Short Circuit Protection Input, and 24 Output,, 1, {, { and {1 Regulated Outputs Low Isolation Capacitance

More information

Exercise 1: Capacitors

Exercise 1: Capacitors Capacitance AC 1 Fundamentals Exercise 1: Capacitors EXERCISE OBJECTIVE When you have completed this exercise, you will be able to describe the effect a capacitor has on dc and ac circuits by using measured

More information

APPLICATION NOTES FOR MULTILAYER CERAMIC CAPACITORS

APPLICATION NOTES FOR MULTILAYER CERAMIC CAPACITORS APPLICATION NOTES FOR MULTILAYER CERAMIC CAPITORS ELECTRICAL CHARTERISTICS The fundamental electrical properties of multilayer ceramic capacitors are as follows: Polarity: Multilayer ceramic capacitors

More information

PRODUCT SPECIFICATION

PRODUCT SPECIFICATION Page 1 Page 2 1.0 SCOPE. This specification covers performance, tests and quality requirements for the SIM Card Connector SIM 2055 (Receiver Type, 6-Pin, SMT, 1.8 & 2.2mm Profiles). 2.0 PRODUCT NAME AND

More information

ELECTROMAGNETIC OSCILLATIONS AND ALTERNATING CURRENT

ELECTROMAGNETIC OSCILLATIONS AND ALTERNATING CURRENT Chapter 31: ELECTROMAGNETIC OSCILLATIONS AND ALTERNATING CURRENT 1 A charged capacitor and an inductor are connected in series At time t = 0 the current is zero, but the capacitor is charged If T is the

More information

CALIBRATION REPORT FOR THERMOHYDROMETER

CALIBRATION REPORT FOR THERMOHYDROMETER CALIBRATION REPORT FOR THERMOHYDROMETER SAMPLE CUSTOMER S/N: XXXXX Report Number: Y205188 Page 1 of 5 Report No. Y205188 ICL CALIBRATION LABORATORIES, INC. ISO/IEC 17025 and ANSI/NCSL Z540-1 accredited

More information

TEST REPORT. Test Method : See the attached sheets.

TEST REPORT. Test Method : See the attached sheets. Applicant: Radomir Klabal Komenskeho 446, Bilovice nad Svitavou, Czech Republic Sample Description Product : Compact Fluorescent Lamp Model No. : CFL20T2S27E27 Brand Name : Divetta Electrical Rating :

More information

DVSA2800D Series HIGH RELIABILITY HYBRID DC-DC CONVERTERS DESCRIPTION FEATURES

DVSA2800D Series HIGH RELIABILITY HYBRID DC-DC CONVERTERS DESCRIPTION FEATURES HIGH RELIABILITY HYBRID DC-DC CONVERTERS DESCRIPTION The DVSA series of high reliability DC-DC converters is operable over the full military (- C to +12 C) temperature range with no power derating. Unique

More information

TECHNICAL INFORMATION

TECHNICAL INFORMATION TECHNICAL INFORMATION RATED PRIMARY OLTAGE () This is the supply assigned to the transformer by the manufacturer. RATED SECONDARY OLTAGE () This is the secondary output assigned to the transformer when

More information

CERTIFICATE OF CALIBRATION

CERTIFICATE OF CALIBRATION Issued By Transmille Ltd. Date of Issue 20 January 2016 0324 Approved Signatory Transmille Ltd. Unit 4, Select Business Centre Lodge Road Staplehurst, Kent. TN12 0QW. TEL 01580 890700 FAX 01580 890711

More information

DeFelsko PosiTector Dew Point Meter with Anemometer (DPMA)

DeFelsko PosiTector Dew Point Meter with Anemometer (DPMA) Management Procedure 2562 Revision: A Date Issued: March 24, 2017 Date Revised: Calibration Procedure DeFelsko PosiTector Dew Point Meter with Anemometer (DPMA) Table of Contents 1. Introduction and UUC

More information

THE DIMENSIONING OF ELECTRICAL CONDUCTORS FOR USE IN "PANEL BOARDS" ADDRESSED TO HAZARDOUS AREAS - PART THREE

THE DIMENSIONING OF ELECTRICAL CONDUCTORS FOR USE IN PANEL BOARDS ADDRESSED TO HAZARDOUS AREAS - PART THREE July 04 THE DIMENSIONING OF ELECTRICAL CONDUCTORS FOR USE IN "PANEL BOARDS" ADDRESSED TO HAZARDOUS AREAS - PART THREE In this third part. we want to speak about how important is the correct sizing of the

More information

TEST REPORT. Page 1 of 11

TEST REPORT. Page 1 of 11 Applicant: Radomir Klabal Komenskeho 446, Bilovice nad Svitavou, Czech Republic Sample Description Product : Compact Fluorescent Lamp Model No. : CFL15T2S27E27 Brand Name : Divetta Electrical Rating :

More information

5730A High Performance Multifunction Calibrator. Extended specifications

5730A High Performance Multifunction Calibrator. Extended specifications 730A High Performance Multifunction Calibrator Extended specifications General Specifications Warm-Up Time... Twice the time since last warmed up, to a maximum of 30 minutes. System Installation... Rack

More information

Prepare for this experiment!

Prepare for this experiment! Notes on Experiment #8 Theorems of Linear Networks Prepare for this experiment! If you prepare, you can finish in 90 minutes. If you do not prepare, you will not finish even half of this experiment. So,

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current Transducer LDSR 0.3-TP/SP1 I P R N = 300 ma For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Features Closed

More information

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM Unit Objectives Describe the structure of an atom. Identify atoms with a positive charge and atoms with a negative charge. Explain

More information

Electromagnetic Compatibility IEC :2013 A Technical Guide to Flicker Measurement

Electromagnetic Compatibility IEC :2013 A Technical Guide to Flicker Measurement Electromagnetic Compatibility IEC61000-3-3:2013 A Technical Guide to Flicker Measurement This technical article will discuss the Electromagnetic Compatibility (EMC) IEC61000-3-3:2013 testing standard,

More information

OIML R 50-3 RECOMMENDATION. Edition 2014 (E) ORGANISATION INTERNATIONALE INTERNATIONAL ORGANIZATION

OIML R 50-3 RECOMMENDATION. Edition 2014 (E) ORGANISATION INTERNATIONALE INTERNATIONAL ORGANIZATION INTERNATIONAL RECOMMENDATION OIML R 50-3 Edition 2014 (E) Continuous totalizing automatic weighing instruments (belt weighers). Part 3: Test report format Instruments de pesage totalisateurs continus à

More information

STATEWIDE CAREER/TECHNICAL EDUCATION COURSE ARTICULATION REVIEW MINUTES

STATEWIDE CAREER/TECHNICAL EDUCATION COURSE ARTICULATION REVIEW MINUTES STATEWIDE CAREER/TECHNICAL EDUCATION COURSE ARTICULATION REVIEW MINUTES Articulation Agreement Identifier: _ELT 107/ELT 108 (2011-1) Plan-of-Instruction version number (e.g.; INT 100 (2007-1)). Identifier

More information

APPROVAL SHEET FOR AL. ELECTROLYTIC CAPACITORS

APPROVAL SHEET FOR AL. ELECTROLYTIC CAPACITORS NO : ED-A5540 TO : APPROVED APPROVAL SHEET FOR AL. ELECTROLYTIC CAPACITORS : BY: Series Description Part No. HV series, PLEASE RETURN US ONE COPY YOUR SIGED SPECIFICATION AFTER YOU APPROVED OF IT. APPROVED

More information

HV CAPACITOR SCREENING PROCEDURE FOR THE GYROSCOPE SUSPENSION SYSTEM (GSS) HV AMP/BRIDGE (HVA) BOARD. GP-B Procedure P0688 Rev -

HV CAPACITOR SCREENING PROCEDURE FOR THE GYROSCOPE SUSPENSION SYSTEM (GSS) HV AMP/BRIDGE (HVA) BOARD. GP-B Procedure P0688 Rev - W. W. Hansen Experimental Physics Laboratory STANFORD UNIVERSITY STANFORD, CALIFORNIA 94305-4085 Gravity Probe B Relativity Mission HV CAPACITOR SCREENING PROCEDURE FOR THE GYROSCOPE SUSPENSION SYSTEM

More information

Certificate of Calibration Sound Level Calibrator

Certificate of Calibration Sound Level Calibrator NATacoustic Acoustic Caliration & Testing Laoratory Level, 48A Elizaeth Street., Surry Hills NSW 200 AUSTRALIA Ph: (02) 828 0570 email: service@natacoustic.com.au wesite: www.natacoustic.com.au A division

More information

MODEL 107 TEMPERATURE PROBE INSTRUCTION MANUAL

MODEL 107 TEMPERATURE PROBE INSTRUCTION MANUAL MODEL 107 TEMPERATURE PROBE INSTRUCTION MANUAL REVISION: 6/00 COPYRIGHT (c) 1983-2000 CAMPBELL SCIENTIFIC, INC. This is a blank page. Warranty and Assistance The MODEL 107 TEMPERATURE PROBE is warranted

More information

DC Film Capacitors MKT Radial Lacquered Type

DC Film Capacitors MKT Radial Lacquered Type l 467 w FEATURES Available taped and loose in box RoHS compliant Seating plane (1) h APPLICATIONS Blocking and coupling, bypass and energy reservoir. α (2) l t REFERENCE STANDARDS IEC 60384-2 MARKING C-value;

More information

Renewable Energy Systems

Renewable Energy Systems Renewable Energy Systems 2 Buchla, Kissell, Floyd Chapter Outline Electrical Fundamentals 2 Buchla, Kissell, Floyd 2-1 ENERGY, CHARGE, AND VOLTAGE 2-2 ELECTRICAL CURRENT 2-3 RESISTANCE AND OHM'S LAW 2-4

More information

Alternating Current (AC): Alternating Current is electric current that reverses directions at regular intervals.

Alternating Current (AC): Alternating Current is electric current that reverses directions at regular intervals. Glossary Alternating Current (AC): Alternating Current is electric current that reverses directions at regular intervals. American National Standards Institute (ANSI): American National Standards Institute

More information

CALIBRATION CERTIFICATE # 503

CALIBRATION CERTIFICATE # 503 CALIBRATION CERTIFICATE # 503 Calibration date : 2011-02-23 Certificate issued : 2012-04-18 Company name Company address City, Province, Canada CLAS 2009-02 Calibration of Mass flow meter Micro Motion

More information

Product Data Sheet PD-0037-B

Product Data Sheet PD-0037-B Product Data Sheet PD-0037-B 3M Shielded Compact Ribbon (SCR) Connector 3M Shielded Compact Ribbon (SCR) Boardmount Right Angle 36110-2220 XX 3 Electronic Solutions Division Page: 1 of 12 Table of Contents

More information

CERTIFICATE OF CALIBRATION

CERTIFICATE OF CALIBRATION CERTIFICATE OF CALIBRATION 12100 WEST 6TH AVE LAKEWOOD, CO 80228 ANAB AC-2489.02 Manufacturer: Ruska Instruments Corp. Model Number: 7250i : Pressure Calibrator Serial Number: 69718 ID: TE10768 As-Found:

More information

Digital Current Transducer HO-SW series I P N = A. Ref: HO 100-SW; HO 150-SW; HO 200-SW; HO 250-SW

Digital Current Transducer HO-SW series I P N = A. Ref: HO 100-SW; HO 150-SW; HO 200-SW; HO 250-SW Digital Current Transducer HO-SW series I P N = 100... 250 A Ref: HO 100-SW; HO 150-SW; HO 200-SW; HO 250-SW Bitstream output from on onboard Sigma Delta modulator. For the electronic measurement of current:

More information

MILITARY SPECIFICATION MICROCIRCUITS, DIGITAL, BIPOLAR, SCHOTTKY TTL, FLIP-FLOPS, CASCADABLE, MONOLITHIC SILICON

MILITARY SPECIFICATION MICROCIRCUITS, DIGITAL, BIPOLAR, SCHOTTKY TTL, FLIP-FLOPS, CASCADABLE, MONOLITHIC SILICON INCH-POUND 2 November 2005 SUPERSEDING MIL-M-38510/71C 23 July 1984 MILITARY SPECIFICATION MICROCIRCUITS, DIGITAL, BIPOLAR, SCHOTTKY TTL, FLIP-FLOPS, CASCADABLE, MONOLITHIC SILICON This specification is

More information

Power Resistor for Mounting onto a Heatsink Thick Film Technology

Power Resistor for Mounting onto a Heatsink Thick Film Technology DIMENSIONS in millimeters Power Resistor for Mounting onto a Heatsink Thick Film Technology FEATURES 300 W at 85 C bottom case temperature Wide resistance range: 0.3 Ω to 900 kω E24 series Non inductive

More information

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager. Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager. 1 -A - Introduction - Thank for your purchasing MITSUBISHI ELECTRIC MELPRO TM D Series Digital Protection

More information

Suppressor film capacitor Highlight and Application in Series with the main

Suppressor film capacitor Highlight and Application in Series with the main Suppressor film capacitor Highlight and Application in Series with the main April 2007 Paola Bettacchi - Product Manager 1 Film capacitor : main features and performances Process flow charts Self-healing

More information

Reference Only Spec. No. JEFL243B 0003F-01 P 1/ 6

Reference Only Spec. No. JEFL243B 0003F-01 P 1/ 6 Spec. No. JEFL243B 0003F-01 P 1/ 6 DC Common Mode Choke Coil PLT09HN2003R0P1B Reference Specification 1. Scope This reference specification applies to DC Common Mode Choke Coil (PLT09H Series). 2. Part

More information

Low Drop Voltage Regulator TLE 4295

Low Drop Voltage Regulator TLE 4295 Low Drop Voltage Regulator TLE 4295 Features Four versions: 2.6 V, 3.0 V, 3.3 V, 5.0 V tolerance ±4% Very low drop voltage Output current: 30 ma Power fail output Low quiescent current consumption Wide

More information

The RC Circuit INTRODUCTION. Part 1: Capacitor Discharging Through a Resistor. Part 2: The Series RC Circuit and the Oscilloscope

The RC Circuit INTRODUCTION. Part 1: Capacitor Discharging Through a Resistor. Part 2: The Series RC Circuit and the Oscilloscope The RC Circuit INTRODUCTION The goal in this lab is to observe the time-varying voltages in several simple circuits involving a capacitor and resistor. In the first part, you will use very simple tools

More information

SuperTan Extended (STE) Capacitors, Wet Tantalum Capacitors with Hermetic Seal

SuperTan Extended (STE) Capacitors, Wet Tantalum Capacitors with Hermetic Seal SuperTan Extended () Capacitors, Wet Tantalum Capacitors with Hermetic Seal FEATURES SuperTan Extended () represents a major breakthrough in wet tantalum capacitor Available technology. Its unique cathode

More information

PRELIMINARY SPECIFICATION

PRELIMINARY SPECIFICATION Positive Adjustable V tor AVAILABLE AS MILITARY / SPACE SPECIFICATIONS SMD 5962-99517 pending Radiation Tolerant MIL-STD-88, 1.2.1 QML pending FEATURES Guaranteed 0.5A Output Current Radiation Guaranteed

More information

TEST REPORT RP

TEST REPORT RP Page 1 of 36 Environmental and material tests (ENV) SECTOR Product description: Tested Models: Manufacturer: Led lights Sample 01 -> Led Puma -> 28234/LED/AS Sample 02 -> Extreme Led -> 556600_04 Sample

More information

CR10TCR THERMOCOUPLE REFERENCE

CR10TCR THERMOCOUPLE REFERENCE CR10TCR THERMOCOUPLE REFERENCE REVISION: 12/96 COPYRIGHT (c) 1995-1996 CAMPBELL SCIENTIFIC, INC. This is a blank page. WARRANTY AND ASSISTANCE The CR10TCR THERMOCOUPLE REFERENCE is warranted by CAMPBELL

More information

IES LM TEST REPORT For EIKO GLOBAL, LLC

IES LM TEST REPORT For EIKO GLOBAL, LLC NVLAP LAB CODE:201045-0 Shenzhen Anbotek Compliance Laboratory Limited IES LM-79-08 TEST REPORT For EIKO GLOBAL, LLC Report Number: Product Type: Date of Receipt: Date of Test: Date of Report: Product

More information

S R O T C U D IN & MYRRA

S R O T C U D IN & MYRRA TRANSFORMERS & INDUCTORS MYRRA...Of course! TECHNICAL INFORMATION RATED PRIMARY OLTAGE () This is the supply assigned to the transformer by the manufacturer. RATED SECONDARY OLTAGE () This is the secondary

More information

Pascal ET is an handheld multifunction calibrator for the measurement and simulation of the following parameters: - pressure

Pascal ET is an handheld multifunction calibrator for the measurement and simulation of the following parameters: - pressure DATASHEET Pascal ET Pascal ET is an handheld multifunction calibrator for the measurement and simulation of the following parameters: - pressure - electrical signals (ma, mv, V, ) - temperature (TC and

More information

DC Film Capacitors MKT Axial Type

DC Film Capacitors MKT Axial Type MKT181 DC Film Capacitors MKT Axial Type FEATURES Supplied loose in box, taped on ammopack or reel Material categorization: For definitions of compliance please see www.vishay.com/doc?9991 APPLICATIONS

More information

Solid Tantalum SMD Capacitors TANTAMOUNT, Hi-Rel COTS, Low ESR, Metal Case

Solid Tantalum SMD Capacitors TANTAMOUNT, Hi-Rel COTS, Low ESR, Metal Case Solid Tantalum SMD Capacitors TANTAMOUNT, Hi-Rel COTS, Low ESR, Metal Case PERFORMANCE CHARACTERISTICS Operating Temperature: -55 C to +125 C (above 85 C, voltage derating is required) Capacitance Range:

More information

Lab 4 RC Circuits. Name. Partner s Name. I. Introduction/Theory

Lab 4 RC Circuits. Name. Partner s Name. I. Introduction/Theory Lab 4 RC Circuits Name Partner s Name I. Introduction/Theory Consider a circuit such as that in Figure 1, in which a potential difference is applied to the series combination of a resistor and a capacitor.

More information

Low Drop Voltage Regulator TLE

Low Drop Voltage Regulator TLE Low Drop Voltage Regulator TLE 4296-2 Features Two versions: 3.3 V, 5.0 V Output voltage tolerance ±4% Very low drop voltage Output current: 30 ma Inhibit input Low quiescent current consumption Wide operation

More information

Aluminum Capacitors Power Printed Wiring Style

Aluminum Capacitors Power Printed Wiring Style FEATURES Polarized aluminum electrolytic capacitors, non-solid electrolyte Large types, cylindrical aluminum case, insulated Provided with keyed polarity Very long useful life: 000 h at 8 C Low ESR, high

More information

Ref: HLSR 16-PW; HLSR 32-PW; HLSR 40-PW-000; HLSR 50-PW-000,

Ref: HLSR 16-PW; HLSR 32-PW; HLSR 40-PW-000; HLSR 50-PW-000, Digital Current Transducer HLSR-PW series I P N = 16... 50 A Ref: HLSR 16-PW; HLSR 32-PW; HLSR 40-PW-000; HLSR 50-PW-000, Bitstream output from on onboard Sigma Delta modulator. For the electronic measurement

More information

FEATURES. Note 138D 306 X0 006 C 2 E3 MODEL CAPACITANCE CAPACITANCE TOLERANCE DC VOLTAGE RATING AT +85 C

FEATURES. Note 138D 306 X0 006 C 2 E3 MODEL CAPACITANCE CAPACITANCE TOLERANCE DC VOLTAGE RATING AT +85 C Wet Tantalum Capacitors Silver Case TANTALEX Capacitors Hermetically-Sealed FEURES Terminations: axial, standard tin / lead (SnPb), 100 % tin (RoHS-compliant) available Available Model is the commercial

More information

EMC Standards. Samuel Burri 2013, EPFL

EMC Standards. Samuel Burri 2013, EPFL EMC Standards Samuel Burri 2013, EPFL Outline Introduction History Compliance Requirements Procedures Example: WLAN Standards in power networks Conclusion Samuel Burri, EPFL 2 Introduction EMC is concerned

More information

MILITARY SPECIFICATION MICROCIRCUITS, DIGITAL, BIPOLAR, TTL, DECODERS MONOLITHIC SILICON. Inactive for new design after 7 September 1995.

MILITARY SPECIFICATION MICROCIRCUITS, DIGITAL, BIPOLAR, TTL, DECODERS MONOLITHIC SILICON. Inactive for new design after 7 September 1995. INCH-POUND 16 February 2005 SUPERSEDING MIL-M-38510/10C 3 March 1986 MILITARY SPECIFICATION MICROCIRCUITS, DIGITAL, BIPOLAR, TTL, DECODERS MONOLITHIC SILICON This specification is approved for use by all

More information

Fundamentals of Polymeric PTC 0vercurrent Circuit Protection

Fundamentals of Polymeric PTC 0vercurrent Circuit Protection Fundamentals of Polymeric PTC 0vercurrent Circuit Protection 2 Polymeric PTC Technology The Problem of Overcurrents An overcurrent is an abnormally high current that has the potential to cause failure

More information

OIML R 76-2 RECOMMENDATION. Edition 2007 (E) ORGANISATION INTERNATIONALE INTERNATIONAL ORGANIZATION. Non-automatic weighing instruments

OIML R 76-2 RECOMMENDATION. Edition 2007 (E) ORGANISATION INTERNATIONALE INTERNATIONAL ORGANIZATION. Non-automatic weighing instruments INTERNATIONAL RECOMMENDATION OIML R 76-2 Edition 2007 (E) Non-automatic weighing instruments Part 2: Test report format Instruments de pesage à fonctionnement non automatique Partie 2: Format du rapport

More information

REVISIONS SYMBOL DESCRIPTION DATE APPROVAL

REVISIONS SYMBOL DESCRIPTION DATE APPROVAL REVISIONS SYMBOL DESCRIPTION DATE APPROVAL - A Initial Release Revised per RN A-159 03/11/2008 07/17/2009 JS SHEET REVISION STATUS SH 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 REV A A A A A A

More information

O Plus Dry Bushing 25 kv system, 150 kv BIL, 3000 A

O Plus Dry Bushing 25 kv system, 150 kv BIL, 3000 A TYPE TEST REPORT O Plus Dry Bushing 25 kv system, 150 kv BIL, 3000 A 02 1 Abstract 02 2 Certification 03 3 Introduction 03 3.1 Description and ratings 03 3.2 Overview of tests 03 3.3 Applicable standards

More information

ALUMINUM ELECTROLYTIC CAPACITORS REFERENCE SHEET

ALUMINUM ELECTROLYTIC CAPACITORS REFERENCE SHEET TO Messrs. AVNET ABACUS ALUMINUM ELECTROLYTIC CAPACITORS REFERENCE SHEET CUSTOMER PART No. Rubycon PART No. 35 TLV 470 M 12.5X13.5 DRAWING No. RERS 011758 ISSUE No. 1 ISSUE DATE 25 AUGUST 2010 ENGINEERING

More information

OIML R 51-2 RECOMMENDATION. Edition 2006 (E) ORGANISATION INTERNATIONALE INTERNATIONAL ORGANIZATION. Automatic catchweighing instruments

OIML R 51-2 RECOMMENDATION. Edition 2006 (E) ORGANISATION INTERNATIONALE INTERNATIONAL ORGANIZATION. Automatic catchweighing instruments INTERNATIONAL RECOMMENDATION OIML R 51-2 Edition 2006 (E) Automatic catchweighing instruments Part 2: Test report format Instruments de pesage trieurs-étiqueteurs à fonctionnement automatique Partie 2:

More information

PHYSICS 171 UNIVERSITY PHYSICS LAB II. Experiment 6. Transient Response of An RC Circuit

PHYSICS 171 UNIVERSITY PHYSICS LAB II. Experiment 6. Transient Response of An RC Circuit PHYSICS 171 UNIVERSITY PHYSICS LAB II Experiment 6 Transient Response of An RC Circuit Equipment: Supplies: Function Generator, Dual Trace Oscilloscope.002 Microfarad, 0.1 Microfarad capacitors; 1 Kilohm,

More information

Tantalum Through-Hole Capacitors Molded Radial T370 & T378 Micron MIL-PRF-49137/6 (CX06 Style) Applications

Tantalum Through-Hole Capacitors Molded Radial T370 & T378 Micron MIL-PRF-49137/6 (CX06 Style) Applications Overview The KEMET T370 and T378 Micron MIL-PRF-49137/6 (CX06 Style) capacitors are available in a variety of case styles and sizes. These capacitors are designed to operate from 55 C to +85 C at full

More information

DATA SHEET SURFACE-MOUNT CERAMIC MULTILAYER CAPACITORS General purpose & High capacitance Class 2, X5R

DATA SHEET SURFACE-MOUNT CERAMIC MULTILAYER CAPACITORS General purpose & High capacitance Class 2, X5R DATA SHEET SURFACE-MOUNT CERAMIC MULTILAYER CAPACITORS General purpose & High capacitance Class 2, 6.3 V TO 50 V 10 nf to 100 µf RoHS compliant Product Specification Product specification 2 Surface-Mount

More information

AC and Pulse Metallized Polypropylene Film Capacitors MKP Axial Type

AC and Pulse Metallized Polypropylene Film Capacitors MKP Axial Type Vishay Roederstein AC and Pulse Metallized Polypropylene Film Capacitors FEATURES Supplied loose in box, taped on ammopack or reel available on request l t APPLICATIONS High current and high pulse operations

More information

400 Volts, 50HZ 480 Volts, 60HZ 600 Volts, 60HZ TECHNICAL REFERENCE MANUAL

400 Volts, 50HZ 480 Volts, 60HZ 600 Volts, 60HZ TECHNICAL REFERENCE MANUAL 400 Volts, 50HZ 480 Volts, 60HZ 600 Volts, 60HZ TECHNICAL REFERENCE MANUAL FORM: MAP-TRM-E REL. July 2013 REV. 015 2013 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation Matrix AP Harmonic

More information

CERTIFICATE OF CALIBRATION

CERTIFICATE OF CALIBRATION Page 1 of 10 CALIBRATION OF Sound Level Meter: Brüel & Kjær Type 3050-A-040 No: 3050-100751 Id: - Microphone: Brüel & Kjær Type 4189 No: 2621142 Preamplifier: Brüel & Kjær Type 2669 No: 2679073 Supplied

More information

5SJ4...-.HG Circuit Breakers to IEC and UL 489

5SJ4...-.HG Circuit Breakers to IEC and UL 489 Siemens AG 009 5SJ...-.HG Circuit Breakers to IEC and UL 89 BETA Low-Voltage Circuit Protection Compliance with industry standards is a must in today's manufacturing environment. Worldwide acceptance is

More information

Independent, accredited testing station Member laboratory of STL and LOVAG TEST CONFIRMATION. on the given range of performed tests

Independent, accredited testing station Member laboratory of STL and LOVAG TEST CONFIRMATION. on the given range of performed tests Independent, accredited testing station Member laboratory of STL and LOVAG TEST CONFIRMATION on the given range of performed tests 3M Laboratories Europe Zweigniederlassung der 3M Deutschland GmbH Carl-Schurz-Str.

More information

POWER QUALITY MEASUREMENT PROCEDURE. Version 4 October Power-Quality-Oct-2009-Version-4.doc Page 1 / 12

POWER QUALITY MEASUREMENT PROCEDURE. Version 4 October Power-Quality-Oct-2009-Version-4.doc Page 1 / 12 POWER QUALITY MEASUREMENT PROCEDURE Version 4 October 2009 Power-Quality-Oct-2009-Version-4.doc Page 1 / 12 MEASNET 2009 Copyright all rights reserved This publication may not be reproduced or utilized

More information

Glossary Innovative Measurement Solutions

Glossary Innovative Measurement Solutions Glossary GLOSSARY OF TERMS FOR TRANSDUCERS, LOAD CELLS AND WEIGH MODULES This purpose of this document is to provide a comprehensive, alphabetical list of terms and definitions commonly employed in the

More information

FEATURES STANDARD CONFIGURATION

FEATURES STANDARD CONFIGURATION Metallized Polypropylene 5MP1 SERIES Metallized Polypropylene Metallized Polypropylene and Military Styles CFR13 and CFR14."Hi-Rel" replacement for electrolytics for a broad range of commercial and military

More information

CGS ALUMINUM ELECTROLYTIC CAPACITORS

CGS ALUMINUM ELECTROLYTIC CAPACITORS CGS ALUMINUM ELECTROLYTIC CAPACITORS EXTREME APPLICATON HIGHLIGHTS APPLICATION Capacitance 50-500,000µF U.P.S Systems Voltage 15 to 500 WVDc Inverters/P.C.U.s. -10%, + 20% Tolerance and Motor Special Controls

More information

Double Thyristor Module For Phase Control MT A2

Double Thyristor Module For Phase Control MT A2 Electrically isolated base plate Industrial standard package Simplified mechanical design, rapid assembly Pressure contact PROTON-ELECTROTEX RUSSIA Double Thyristor Module For Phase Control MT3-595-18-A2

More information

DC Film Capacitors MKT Radial Lacquered Type

DC Film Capacitors MKT Radial Lacquered Type DC Film Capacitors MKT Radial Lacquered Type FEATURES Available taped and loose in box Material categorization: for definitions of compliance please see www.vishay.com/doc?99912 APPLICATIONS Blocking and

More information

Experiment P43: RC Circuit (Power Amplifier, Voltage Sensor)

Experiment P43: RC Circuit (Power Amplifier, Voltage Sensor) PASCO scientific Vol. 2 Physics Lab Manual: P43-1 Experiment P43: (Power Amplifier, Voltage Sensor) Concept Time SW Interface Macintosh file Windows file circuits 30 m 700 P43 P43_RCCI.SWS EQUIPMENT NEEDED

More information

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL 1 SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL Power Systems: Generation, Transmission and Distribution Power Systems: Generation, Transmission and Distribution Power Systems:

More information

MILITARY SPECIFICATION MICROCIRCUITS, LINEAR, LOW OFFSET OPERATIONAL AMPLIFIERS, MONOLITHIC SILICON

MILITARY SPECIFICATION MICROCIRCUITS, LINEAR, LOW OFFSET OPERATIONAL AMPLIFIERS, MONOLITHIC SILICON INCH-POUND MIL-M-38510/135G 22 March 2010 SUPERSEDING MIL-M-38510/135F 8 April 2008 MILITARY SPECIFICATION MICROCIRCUITS, LINEAR, LOW OFFSET OPERATIONAL AMPLIFIERS, MONOLITHIC SILICON Reactivated after

More information

EXP. NO. 3 Power on (resistive inductive & capacitive) load Series connection

EXP. NO. 3 Power on (resistive inductive & capacitive) load Series connection OBJECT: To examine the power distribution on (R, L, C) series circuit. APPARATUS 1-signal function generator 2- Oscilloscope, A.V.O meter 3- Resisters & inductor &capacitor THEORY the following form for

More information

Gas Discharge Tube (GDT) Data Sheet

Gas Discharge Tube (GDT) Data Sheet Gas Discharge Tube (GDT) Data Sheet Features Provide ultra-fast response to surge voltage from slow-rising surge of 100V/s to rapid-rising surge of 1KV/μs. Stable breakdown voltage. High insulation resistance.

More information

Power Resistor for Mounting onto a Heatsink Thick Film Technology

Power Resistor for Mounting onto a Heatsink Thick Film Technology DIMENSIONS in millimeters Power Resistor for Mounting onto a Heatsink Thick Film Technology FEATURES 800 W at 85 C bottom case temperature Wide resistance range: 0.3 Ω to 900 kω E24 series Non inductive

More information

MIL-STD-750 NOTICE 5 METHOD

MIL-STD-750 NOTICE 5 METHOD MIL-STD-750 *STEADY-STATE THERMAL IMPEDANCE AND TRANSIENT THERMAL IMPEDANCE TESTING OF TRANSISTORS (DELTA BASE EMITTER VOLTAGE METHOD) * 1. Purpose. The purpose of this test is to determine the thermal

More information

Metallized Polyester Film Capacitors (MKT-S)

Metallized Polyester Film Capacitors (MKT-S) Metallized Polyester Film Capacitors (MKT-S) Series/Type: B32538 The following products presented in this data sheet are being withdrawn. Ordering Code Substitute Product Date of Withdrawal Deadline Last

More information

100 pf to 47µF RoHS compliant & Halogen free

100 pf to 47µF RoHS compliant & Halogen free Product Specification August 7, 2017 V.4 DATA SHEET SURFACE MOUNT MULTILAYER CERAMIC CAPACITORS General purpose class II X6S 4 V TO 50 V 0 pf to 47µF RoHS compliant & Halogen free 2 SCOPE This specification

More information

MATERIAL TEST REPORT STATIC DECAY AND SURFACE RESISTIVITY TESTING OF SOCK AND SPUNBOND SAMPLES NEW PIG CORPORATION FEBRUARY 28, 2008

MATERIAL TEST REPORT STATIC DECAY AND SURFACE RESISTIVITY TESTING OF SOCK AND SPUNBOND SAMPLES NEW PIG CORPORATION FEBRUARY 28, 2008 MATERIAL TEST REPORT STATIC DECAY AND SURFACE RESISTIVITY TESTING OF SOCK AND SPUNBOND SAMPLES NEW PIG CORPORATION FEBRUARY 28, 2008 1 MATERIAL EVALUATION REPORT Static Decay and Surface Resistivity Testing

More information

5-V Low Drop Fixed Voltage Regulator TLE

5-V Low Drop Fixed Voltage Regulator TLE 5-V Low Drop Fixed Voltage Regulator TLE 427-2 Features Output voltage tolerance ±2% 65 ma output current capability Low-drop voltage Reset functionality Adjustable reset time Suitable for use in automotive

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current Transducer HO-NP series I P N = 4, 6, 12, 15 A Ref: HO 4-NP, HO 6-NP, HO 12-NP, HO 15-NP For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary

More information

Wet Tantalum Capacitors, High Energy, Ultra High Capacitance, -55 C to +125 C Operation

Wet Tantalum Capacitors, High Energy, Ultra High Capacitance, -55 C to +125 C Operation Wet Tantalum Capacitors, High Energy, Ultra High Capacitance, -55 C to +125 C Operation FEATURES High energy, very high capacitance design All tantalum, hermetically sealed case Utilizes proven SuperTan

More information