SIDEWINDER DRILLING RIG 102 HOUSTON, TEXAS

Size: px
Start display at page:

Download "SIDEWINDER DRILLING RIG 102 HOUSTON, TEXAS"

Transcription

1 SIDEWINDER DRILLING RIG 102 HOUSTON, TEXAS January, 2017 Infrared Inspection Report Sidewinder Drilling Rig 102 St Augustine, Texas Company Contact Jesse Russell Project: CHARTER OAK DRIVE, LITTLE ROCK, AR PHONE: & FAX:

2 ORDER OF REPORT CONTENTS 1: Data To Facilitate Understanding & Utilizing Scan Report 2: Scan Results Overview & Action Taken Form 3: Identified Faulting Conditions, Information & Photographs 4: List Of Facility Equipment Identified By The Customer Representative & Notations Of Faulting Conditions Found DISCLAIMER This report and the recommendations contained in it are based upon conditions and practices observed and information made available to United Spectrographics personnel. This report does not purport to list all hazards or faulty conditions. It is not intended to indicate that other hazards or faulty conditions do not exist. Severity ratings in the report are based on the criteria shown in this report and are intended as guidelines only. No responsibility is assumed for the control of the facility s condition, maintenance practices or correction of conditions indicated herein. By issuing this report, neither United Spectrographics nor any of its employees makes any warranty, expressed or implied, concerning the contents of this report. Furthermore, neither United Spectrographics nor any of its employees shall be liable in any manner (other than liability that may be expressed in any policy of insurance that may be issued by United Spectrographics) for personal injury or property damage or loss of any kind arising from or connected with this inspection or failure to inspect.

3 January 6 th, 2017 Sidewinder Drilling Rig 102 Attn: Jesse Russell 952 Echo Lane Suite 460 Houston, Texas Dear Mr. Russell; During the course of our January 2017 Infrared Inspection of your facility s electrical equipment, no equipment indicating a faulty thermal signature was located at the Sidewinder Drilling Rig 102 San Augustine, Texas facility. Locating no faults is an unusual occurrence for us; we generally encounter only a small percentage of facilities a year with no faults. Your maintenance people appear to be doing an outstanding job. We greatly appreciated the opportunity to complete this project for you and look forward to the next one. If you have any questions concerning this infrared inspection, please call Sincerely, S Richard P. Lincourt United Spectrographics, LLC CHARTER OAK DRIVE, LITTLE ROCK, AR PHONE: & FAX: Logistics@usscanman.com

4 Utilizing Report Contents Included in this report are Photographs and Thermographs of problem areas found during our recent Infrared Inspection of your facility. Each problem area picture is accompanied by: Date Location Information Temperature Calculations Color-coded Temperature Intensity and/or Condition Significance Data A Brief Comment Relating The Item In The Photograph To Its Corresponding Thermograph Suggested Corrective Recommendations. In most cases, problems (faults) found will be listed according to the date and order that they were located, rather then by significance or priority, as we feel that you and/or your personnel can best judge this, keeping in mind circuit importance and thermograph intensity. Thermal intensity is indicated by use of color-coded data inserts that locate a fault s position on the standard electrical failure curve. The color of the insert represents the temperature range of the hottest item, or a portion of the item's circuitry, pointed out in the thermograph. The temperature ranges which the colored inserts represent are grouped as follows: INSERT Red Orange Yellow Green Temperature Range 70ºC/126ºF and higher above Ambient Operating Temp. 40ºC/72ºF to 69ºC/124ºF above Ambient Operating Temp. 25ºC/45ºF to 39ºC/70ºF above Ambient Operating Temp. *10ºC/18ºF to 24ºC/43ºF above Ambient Operating Temp. ( * See page 4)

5 Determining Cost Effective Responses Electrical equipment failures generally follow a standard mechanical/electrical failure curve. Dividing the failure curve into temp. ranges and locating a problem s position on the curve allows us to indicate the probable time to its failure. Knowing a problem s probable time to failure allows you to make a cost effective response to the problem areas that we locate. Below is a depiction of the electrical fault failure curve with the thermal intensity ranges and the colors that we assign to faults detailed in our reports. STANDARD ELECTRICAL FAULT FAILURE CURVE (Does Not Include Area In Blue) MINOR INTERMEDIATE SERIOUS CRITICAL DEVICE TEMP IS AMBIENT, BUT DEVICE IS EITHER FAULTY OR UNSAFE. 10ºC * 18ºF 25ºC 45ºF 40 C 72ºF 70 C 126ºF AMBIENT TEMP YEARS MONTHS MONTHS TO WEEKS WEEKS TO NOW FAULTY EQUIP Built In Trend Monitoring When yearly scans are accomplished, report results allow you to trend monitor your electrical equipment without having to cross reference previous report findings. If a previous year s problem is not repaired it will show up again in the current scan report and its current intensity range indicates a current effective response.

6 Defining Total Temperature and Ambient Operating Temperature And Explanation For Their Use Total Temperature: Total Temperature = Ambient Operating Temperature + Fault temperature Allows you, the customer, to evaluate possible damage to equipment. Leads fail between 90ºC/194ºF and 110ºC/230º Phenolic fails around 200ºC/392ºF Transformers and Motor Insulation failure temperature depends on insulation class rating. Contacts start to fail around 130ºC/266ºF Ambient Operating Temperature (AOT*) for Infrared Scanning Purposes: Temperature within a device container (Box or Cabinet) that is not directly affected by faulting component = Normal Equipment Operating Temperature Contained By Box or Cabinet. If there is no container (Example: Device mounted to a wall) it is the temperature adjacent to the device not affected by the fault. Allows you, the customer, to determine if device will operate at intended amperage. Most switchgear is rated to operate at approximately 40ºC/104ºF (Industrial) to 50ºC/122ºF (Marine) If AOT is enough above normal rated temperature, either of the following conditions can cause an unanticipated trip. 1. An intermittent high load. 2. A minor (Green) or intermediate (Yellow) fault. Report pages with photographs: PH stands for Visible Light Photograph TH stands for Infrared Light Thermograph *AOT stands for Ambient Operating Temperature Both black & white and color infrared thermographs are presented to better depict the fault condition.

7 In addition to the corrective response time frame suggested below and the failure curve located on the previous page, you may want to consider using the military standard responses presented below. Military Standard For Evaluating Faults Located In Electrical Equipment Utilizing Temperature Data Obtained With Infrared Imaging Equipment: Temperatures rise above Ambient Operating Temperature: *10ºC/18ºF to 24ºC/43ºF component failure unlikely, but corrective measures required at next scheduled routine maintenance period or as scheduling permits. (Green Label) 25ºC/45ºF to 39ºC/70ºF component failure probable, unless corrected. (Yellow Label) 40ºC/72ºF to 69ºC/124ºF component failure almost certain, unless corrected. (Orange Label) 70ºC/126ºF and above component failure imminent. Immediately inform the person responsible for continued operation of equipment. (Red Label) Note: United Spectrographics uses a Blue Label to indicate faults that require attention due to either ambient temperature (Ex: Phase Not Operating), faulty equipment elements or unsafe conditions. * Note: Temperature conditions below 10ºC/18ºF rise above AOT are not considered significant enough to record and are usually not included in the reports unless the fault temperature is being affected by a cooling medium such as oil or wind. Fault Correction Recommendation When Our Source Assessment Is Inaccurate: When a fault is indicated in a connection or component and examination by your electrician does not turn up a loose connection or faulty component where we have indicated, a fault does exist. The electrician should continue to investigate the next connection or component to be found in the direction that the heat is coming from until a source is located. Example: If a molded case breaker line side lead connection lug is indicated as a fault source and is found to be secure, but not frozen in place, look for a loose connection or sign of over temp. in the lead holder lug.

8 SCAN RESULTS OVERVIEW PROMPT ATTENTION ITEMS: Because of: 1. The intensity or heat level indicated at the time of the scan. 2. Deterioration caused by excessive temperature not present at the time of the scan. 3. Physical condition irregularities observed at the time of the scan. We recommend that the following faults be given prompt attention: Faults: No Faults Found Items With Asterisks Have High Total or Ambient Operating Temperatures. United Spectrographics January, 2017

9 SUMMARY OF FINDINGS FAULTS BY CATEGORY NUMBER OF FAULTS FAULT NO./ITEM NO. MINOR 0 0 INTERMEDIATE 0 0 SERIOUS 0 0 CRITICAL 0 0 SERIOUS 0 0 Number of items located at facility: 127 Number of faults: 0

10 ACTION TAKEN Sidewinder Drilling Rig 102 San Augustine, Texas January, 2017 None Required

11 AREA/EQUIPMENT LIST Following is a list of the electrical equipment located at the Sidewinder Drilling Rig 102, Houston, Texas, facility and data relating to its operating condition at the time the scan was performed. NOTE: Items noted as visually inspected were not operational or show no visible load at the time of the inspection. No. Equipment Operating Visually Inspected VFD HOUSE Fault # 1 Drawworks VFD Cabinet X 2 DW Main Breaker X 3 Gen #1 Main Breaker X 4 Gen #2 Main Breaker X 5 MCC Feeder Breaker X 6 Top Drive Feeder Breaker X 7 Gen #3 Feeder Breaker X 8 MP1 VFD Cabinet X 9 MP1 Main Breaker X 10 MP2 VFD Cabinet X 11 MP2 Main Breaker X 12 TD VFD Cabinet X 13 TD Main Breaker X 14 Lighting Panel #1 X 15 Lighting Panel #2 X 16 Plug Board X MCC Amp Incoming Line X 18 DWA Blower X 19 Spare X 20 Backfeed Emergency Breaker X 21 MP1 Supercharger X 22 MP2 Supercharger X

12 No. Equipment Operating Visually Inspected 23 Columbia Unit X Fault # 24 Mud Mixer #1 X 25 Mud Mixer #2 X 26 Desilter X 27 Rig Water Pump #1 X 28 Radiator #1 X 29 Radiator #2 X 30 Desander X 31 Rig Water Pump #2 X 32 Trip Tank #1 X 33 Trip Tank #2 X 34 Radiator #3 X 35 Spare X 36 DW Oiler X 37 Vacuum X 38 DW Heat Exchanger Fan X 39 Spare X 40 DW Resistor Fan X 41 Spare X 42 Spare X 43 MP1 Blower X 44 MP1 Lube Oiler X 45 MP1 Liner Wash X 46 MP2 Blower X 47 MP2 Lube Oiler X 48 MP2 Liner Wash X 49 Spare X 50 Spare X

13 No. Equipment Operating Visually Inspected 51 Spare X 52 Spare X 53 Spare X 54 MP1 Lube Oil Heat Exchanger X 55 Process Pit Agit #1/2 Feeder X 56 Spare X 57 Spare X 58 Trip Tank Agit LOTO 59 Shale Shaker #1 X 60 Shale Shaker #2 X 61 Shale Shaker #3 X 62 Spare X 63 Spare X 64 Wireline (Future) X 65 BOP #1 X 66 BOP #2 X 67 Fuel Pump #1 & 2 X 68 Degasser X 69 HPU #2 - Moving HPU LOTO 70 Spare X 71 Air Comp #1 X 72 Air Comp #2 X 73 Centrifuge #1 X 74 Centrifuge #2 X 75 Camp Feeder X 76 Rig Lighting XFMR X 77 Drill Cabin A/C #2 X 78 HPU Aux Circuit Rig Floor X 79 VFD House AC #1 X 80 VFD House AC #2 X Fault #

14 No. Equipment Operating Visually Inspected 81 30kW Heater #1 X Fault # 82 30kW Heater #2 LOTO 83 30kW Heater #3 X 84 30kW Heater #4 X 85 Pressure Washer #1 LOTO 86 HPU #3 Rig Floor X 87 HPU #1 Rig Floor X 88 HPU #2 Rig Floor X 89 MP2 Lube Oil Heat Exchanger X 90 Boiler Feeder X 91 Spare X 92 Process Pit Agits #3/4/5 X 93 Top Drive HPU LOTO 94 Canrig CIP Feeder X 95 Spare X 96 Pressure Washer #2 LOTO 97 Catwalk HPU X OUTSIDE VFD HOUSE 98 Plug Board (Waterfall) X MUD PUMP AREA 99 Plug Connections (From VFD House) X 100 Mud Pump #1 Motor Lead Junction Box (Could Not Open) 101 Mud Pump #2 Motor Lead Junction Box X kva Lighting Transformer X GENERATOR HOUSE 103 Generator #1 Motor Lead Junction Box X 104 Generator #2 Motor Lead Junction Box X 105 Generator #3 Motor Lead Junction Box X

15 No. Equipment Operating Visually Inspected 106 Air Compressor #1 Control Cabinet X Fault # 107 Air Compressor #2 Control Cabinet X 108 Service Entry / Plug Connections (3) X FESTOON HOUSE kva Transformer X MUD TANK AREA 110 Plug Board X 111 Agitator #1 Motor Control (Could Not Open Under Load) X 112 Agitator #2 Motor Control (Could Not Open Under Load) X 113 Agitator #3 Motor Control (Could Not Open Under Load) X 114 Agitator #4 Motor Control (Could Not Open Under Load) X 115 Agitator #5 Motor Control (Could Not Open Under Load) X HPU AREA 116 Top Drive Drill Floor Motor Control (Coud Not Open) X 117 Redundant Pump Motor Control (Could Not Open) X 118 Wrench Pump Motor Control (Could Not Open) X 119 Cooler Fan Motor Control X DRILL SHACK 120 Lighting Panel X 121 A/C Distribution Panel X 122 A/C Control Cabinet X 123 Canrig Control Cabinet X DRILL FLOOR 124 Plug Board X 125 Drawworks Motor Lead Junction Box X 126 Top Drive Junction Box X 127 Plug Board (Feeding Drill Shack) X

Thermal Imaging Survey. Conducted at Nottingham

Thermal Imaging Survey. Conducted at Nottingham Thermal Imaging Survey Conducted at ----------------- Nottingham [This copy has been edited to remove location details. The original document does not have a "Foxit PDF Editor" header on every page.] 27/01/2010

More information

Cold Weather Preparation

Cold Weather Preparation 0-0.0 January 2012 Country of Origin: United Kingdom Cold Weather Preparation Introduction In addition to the freezing of sprinkler pipes and general water pipes, low temperatures can damage boilers, compressors,

More information

Temperature Profile for 36 Marker Spheres on 3M 788 ACCR Conductor 3M Company

Temperature Profile for 36 Marker Spheres on 3M 788 ACCR Conductor 3M Company Temperature Profile for 36 Marker Spheres on 3M 788 ACCR Conductor 3M Company NEETRAC Project Number: 07-113 June 2007 A Research Center of the Georgia Institute of Technology Requested by: Dr. Colin McCullough

More information

MPM GROUP THERMOGRAPHIC INSPECTION

MPM GROUP THERMOGRAPHIC INSPECTION MPM GROUP 8 th August 2014 THERMOGRAPHIC INSPECTION Client Contact Mr P Sykes Site 706-710 Hay Street Perth WA Scope of Work Thermographic inspection of electrical installations as per AS/NZS 3019:2007,

More information

AM 500A 500 WATT AM 1A 1 KILOWATT AM BROADCAST TRANSMITTERS. October, 1999 IM No

AM 500A 500 WATT AM 1A 1 KILOWATT AM BROADCAST TRANSMITTERS. October, 1999 IM No AM 500A 500 WATT AM 1A 1 KILOWATT AM BROADCAST TRANSMITTERS October, 1999 IM No. 597 1112 EQUIPMENT LOST OR DAMAGED IN TRANSIT. When delivering the equipment to you, the truck driver or carrier s agent

More information

REPAIR PARTS. DP13CH Residential Package Heat Pump

REPAIR PARTS. DP13CH Residential Package Heat Pump REPAIR PARTS DP13CH Residential Package Heat Pump DP13CH24AA DP13CH24AB DP13CH30AA DP13CH30AB DP13CH36AA DP13CH36AB DP13CH42AA DP13CH42AB DP13CH48AA DP13CH48AB DP13CH60AA DP13CH60AB nufacturing Company,

More information

REPAIR PARTS. GPH14 H-SERIES R-410A Package Heat Pumps GPH1424H41AA GPH1430H41AA GPH1436H41AA GPH1442H41AA GPH1448H41AA GPH1460H41AA

REPAIR PARTS. GPH14 H-SERIES R-410A Package Heat Pumps GPH1424H41AA GPH1430H41AA GPH1436H41AA GPH1442H41AA GPH1448H41AA GPH1460H41AA REPAIR PARTS GPH14 H-SERIES R-0A Package Heat Pumps GPH1424HAA GPH1430HAA GPH1436HAA GPH1442HAA GPH1448HAA GPH1460HAA This manual is to be used by qualified technicians only. 2009 Goodman Manufacturing

More information

REPAIR PARTS. GPH14 H-Series Package Heat Pumps. This manual is to be used by qualified technicians only. This manual replaces RP-631C.

REPAIR PARTS. GPH14 H-Series Package Heat Pumps. This manual is to be used by qualified technicians only. This manual replaces RP-631C. REPAIR PARTS GPH14 H-Series Package Heat Pumps GPH1424H41AB GPH1424H41AC GPH1424H41BA GPH1424H41CA GPH1424H41DA GPH1430H41AB GPH1430H41AC GPH1430H41BA GPH1430H41CA GPH1436H41AB GPH1436H41AC GPH1436H41BA

More information

REPAIR PARTS. GPC15 Horizontal Package Cooling Units

REPAIR PARTS. GPC15 Horizontal Package Cooling Units REPAIR PARTS GPC15 Horizontal Package Cooling Units GPC1524H41AA GPC1524H41AB GPC1530H41AA GPC1530H41AB GPC1536H41AA GPC1536H41AB GPC1542H41AA GPC1542H41AB GPC1548H41AA GPC1548H41AB GPC1560H41AA GPC1560H41AB

More information

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 2/11/2013 BUILDING SURVEY DATE

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 2/11/2013 BUILDING SURVEY DATE 0912 201 HAZELWOOD DRIVE CHAMPAIGN, ILLINOIS 61820 SYSTEM CONDITION INDEX.137 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 1,205,100 LABORATORY BUILDING GROSS SQUARE FEET

More information

IOWA COUNTY ORDINANCE NO. 22 IOWA COUNTY SNOW & ICE POLICY

IOWA COUNTY ORDINANCE NO. 22 IOWA COUNTY SNOW & ICE POLICY IOWA COUNTY ORDINANCE NO. 22 IOWA COUNTY SNOW & ICE POLICY AN ORDINANCE REPEALING ESTABLISHING THE POLICY AND LEVEL OF SERVICE IN RESPECT TO CLEARANCE OF SNOW AND ICE AND MAINTENANCE OF IOWA COUNTY S SECONDARY

More information

Infrared thermography as a tool to elaborate procedures for predictive maintenance of ball mills equipment

Infrared thermography as a tool to elaborate procedures for predictive maintenance of ball mills equipment 14 th Quantitative InfraRed Thermography Conference Infrared thermography as a tool to elaborate procedures for predictive maintenance of ball mills equipment by R. Władysiak*, T. Pacyniak* * Lodz University

More information

BUREAU OF INDIAN STANDARDS. Draft Indian Standard GUIDELINES FOR INFRARED THERMOGRAPHY INSPECTION OF ELECTRICAL INSTALLATIONS ICS 19.

BUREAU OF INDIAN STANDARDS. Draft Indian Standard GUIDELINES FOR INFRARED THERMOGRAPHY INSPECTION OF ELECTRICAL INSTALLATIONS ICS 19. For BIS Use Only Doc: MTD 21 (5044)W BUREAU OF INDIAN STANDARDS Draft Indian Standard GUIDELINES FOR INFRARED THERMOGRAPHY INSPECTION OF ELECTRICAL INSTALLATIONS ICS 19.100 Not to be reproduced without

More information

Hazard Communication

Hazard Communication Hazard Communication For Company: Address: LC-1009 Rev. 06/16 Page 1 Hazard Communication Program Ref: OSHA 1910.1200 Approved by: Title: Ranking Official's Signature Date: Hazard Communication Coordinator

More information

AIR CONDITIONER (SPLIT TYPE) SERVICE MANUAL

AIR CONDITIONER (SPLIT TYPE) SERVICE MANUAL AIR CONDITIONER (SPLIT TYPE) SERVICE MANUAL FILE No. A10-023-1 REVISION 1 : Mar.2012 Re-edit version.( file volume down) Contents have NOT been changed. Model name: RAS-M10PKVP-E RAS-M13PKVP-E RAS-M16PKVP-E

More information

Resolution Number: (2) Resolution Title: Snow Policy Date Signed: 11/26/12. DAVIS COUNTY Snow Policy Resolution

Resolution Number: (2) Resolution Title: Snow Policy Date Signed: 11/26/12. DAVIS COUNTY Snow Policy Resolution Resolution Number: 112612(2) Resolution Title: Snow Policy Signed: 11/26/12 DAVIS COUNTY Snow Policy Resolution A RESOLUTION TO ESTABLISH THE POLICY AND LEVEL OF SERVICE IN RESPECT TO CLEARANCE OF SNOW

More information

nufacturing Company, L.P San Felipe, Suite

nufacturing Company, L.P San Felipe, Suite Mini-Split Heat Pump Outdoor Unit RXS09LVJU RXS12LVJU RXS15LVJU RXS18LVJU RXS24LVJU REPAIR PARTS nufacturing Company, L.P. 5151 San Felipe, Suite 500 www.amana-hac.com www.amana-hac.com This manual is

More information

Goodman Manufacturing Company, L.P San Felipe, Suite 500 Houston, TX 77056

Goodman Manufacturing Company, L.P San Felipe, Suite 500 Houston, TX 77056 REPAIR PARTS *CVM 96% Modulating Furnace ACVM960604CXAA ACVM960604CXBA ACVM960805DXAA ACVM960805DXBA ACVM961005DXAA GCVM960604CXAA GCVM960604CXBA GCVM960805DXAA GCVM960805DXBA GCVM961005DXAA GCVM961005DXBA

More information

ER2 Short-head Electric Chain Hoist

ER2 Short-head Electric Chain Hoist O/M NO.SHER2-0903-CE-00 ER2 Short-head Electric Chain Hoist (250kg to 5t) Operation Manual (SHER2M/SHER2SG/SHER2SP) Introduction The KITO Short-head Electric Chain Hoist is intended for effective use in

More information

REPAIR PARTS. *MVC95 Variable Speed Furnace

REPAIR PARTS. *MVC95 Variable Speed Furnace *MVC95 Variable Speed Furnace AMVC950453BXBA AMVC950704CXBA AMVC950905CXBA AMVC950905DXBA AMVC9155DXBA GMVC950453BXBA GMVC950704CXBA GMVC950905CXBA GMVC950905DXBA GMVC9155DXBA REPAIR PARTS This manual

More information

REPAIR PARTS. GPH14 Multi-Position Residential Package Heat Pump. This manual is to be used by qualified technicians only.

REPAIR PARTS. GPH14 Multi-Position Residential Package Heat Pump. This manual is to be used by qualified technicians only. REPAIR PARTS GPH14 Multi-Position Residential Package Heat Pump GPH1424MAA GPH1424MAB GPH1430MAA GPH1430MAB GPH1436MAA GPH1436MAB GPH1442MAA GPH1442MAB GPH1448MAA GPH1448MAB GPH1460MAA GPH1460MAB This

More information

INSTALLATION INSTRUCTIONS ATV Plow Blade Part Number: (50 ), (54 ), or (60 ) Application: All Terrain Vehicles

INSTALLATION INSTRUCTIONS ATV Plow Blade Part Number: (50 ), (54 ), or (60 ) Application: All Terrain Vehicles INSTALLATION INSTRUCTIONS ATV Plow Blade Part Number: 78950 (50 ), 78954 (54 ), or 78960 (60 ) Application: All Terrain Vehicles Your safety, and the safety of others, is very important. To help you make

More information

REPAIR PARTS. GPH13 "M" Series Horizontal Package Heat Pumps GPH1324M41AA GPH1330M41AA GPH1336M41AA GPH1342M41AA GPH1348M41AA GPH1360M41AA

REPAIR PARTS. GPH13 M Series Horizontal Package Heat Pumps GPH1324M41AA GPH1330M41AA GPH1336M41AA GPH1342M41AA GPH1348M41AA GPH1360M41AA REPAIR PARTS GPH13 "M" Series Horizontal Package Heat Pumps GPH1324MAA GPH1330MAA GPH1336MAA GPH1342MAA GPH1348MAA GPH1360MAA This manual is to be used by qualified technicians only. 2009 Goodman Manufacturing

More information

REPAIR PARTS. GPH13 "H" Model Package Heat Pumps GPH1324H41AB GPH1330H41AB GPH1336H41AB GPH1342H41AB GPH1348H41BB GPH1360H41BB

REPAIR PARTS. GPH13 H Model Package Heat Pumps GPH1324H41AB GPH1330H41AB GPH1336H41AB GPH1342H41AB GPH1348H41BB GPH1360H41BB REPAIR PARTS GPH13 "H" Model Package Heat Pumps GPH1324H41AB GPH1330H41AB GPH1336H41AB GPH1342H41AB GPH1348H41BB GPH1360H41BB This manual is to be used by qualified technicians only. 2010 Goodman Manufacturing

More information

Installation guide 862 MIT / MIR

Installation guide 862 MIT / MIR Installation guide 862 MIT / MIR in combination with: 864 MTT or 863 MRT or (dual) spot element November 2005 Part no. 4416.232_Rev3 Enraf BV PO Box 812 2600 AV Delft Netherlands Tel. : +31 15 2701 100

More information

REPAIR PARTS. DX17VS Outdoor Inverter. This manual is to be used by qualified technicians only.

REPAIR PARTS. DX17VS Outdoor Inverter. This manual is to be used by qualified technicians only. REPAIR PARTS DX17VS Outdoor Inverter DX17VSS181AA DX17VSS241AA DX17VSS01AA DX17VSS61AA DX17VSS421AA DX17VSS481AA DX17VSS601AA This manual is to be used by qualified technicians only. 2018 5151 San Felipe

More information

1. Explain the various methods of methods of grounding. In power system, grounding or earthing means connecting frame of electrical equipment (non-cur

1. Explain the various methods of methods of grounding. In power system, grounding or earthing means connecting frame of electrical equipment (non-cur 1. Explain the various methods of methods of grounding. In power system, grounding or earthing means connecting frame of electrical equipment (non-current carrying part) or some electrical part of the

More information

OEM Silicon Pressure Die

OEM Silicon Pressure Die OEM Silicon Pressure Die SM9520 Series FEATURES High volume, cost effective Gauge configuration Constant current or constant voltage drive Millivolt output Available in 0.15, 0.60 & 1.50 PSIG full-scale

More information

RS1A - RS1M Fast Rectifiers

RS1A - RS1M Fast Rectifiers RSA - RSM Fast Rectifiers Features Glass-Passivated Junction For Surface Mounted Applications uilt-in Strain Relief, Ideal for Automated Placement UL Certified: Certificate # E326243 SMA/DO-24AC COLOR

More information

nufacturing Company, L.P San Felipe, Suite

nufacturing Company, L.P San Felipe, Suite REPAIR PARTS (2,3,4) Multi Zone Heat Pump Outdoor Unit 2MXS18GVJUAA 3MXS24JVJUAA 4MXS32GVJUAA nufacturing Company, L.P. 5151 San Felipe, Suite 500 www.amana-hac.com www.amana-hac.com This manual is to

More information

SignalSure 150. Mid power solution AUTOMOTIVE. SignalSure 150 is a compact, surface-mount, mid power LED signaling

SignalSure 150. Mid power solution AUTOMOTIVE. SignalSure 150 is a compact, surface-mount, mid power LED signaling AUTOMOTIVE SignalSure 150 Mid power solution SignalSure 150 is a compact, surface-mount, mid power LED signaling solution that delivers an elevated standard of light output, flux density, and color uniformity.

More information

SELF-AUDIT CHECKLIST

SELF-AUDIT CHECKLIST SELF-AUDIT CHECKLIST Service Department Location: Date: Conducted By: Dept: GENERAL 1. Is proper footwear worn in the Service Department? ( ) ( ) ( ) ( ) 2. Are smoking rules posted where there is a serious

More information

REPAIR PARTS. DZ13SA Remote Heat Pumps (3-Phase) DZ13SA0363AA DZ13SA0483AA DZ13SA0484AA DZ13SA0603AA DZ13SA0604AA

REPAIR PARTS. DZ13SA Remote Heat Pumps (3-Phase) DZ13SA0363AA DZ13SA0483AA DZ13SA0484AA DZ13SA0603AA DZ13SA0604AA DZ13SA Remote Heat Pumps (3-Phase) DZ13SA0363AA DZ13SA0483AA DZ13SA0484AA DZ13SA0603AA DZ13SA0604AA REPAIR PARTS This manual is to be used by qualified technicians only. 2013 Daikin Manufacturing Company,

More information

REPAIR PARTS. *CVC9 90% C'Flow 2-Stage Variable Speed Furnace

REPAIR PARTS. *CVC9 90% C'Flow 2-Stage Variable Speed Furnace REPAIR PARTS *CVC9 90% C'Flow 2-Stage Variable Speed Furnace ACVC90704CXAA ACVC90704CXAB ACVC90905DXAA ACVC90905DXAB ACVC950714CXAA ACVC950915DXAA GCVC90704CXAA GCVC90704CXAB GCVC90905DXAA GCVC90905DXAB

More information

Commercial Generator Parts Catalog. PROTEC Series

Commercial Generator Parts Catalog. PROTEC Series Commercial Generator Parts Catalog PROTEC Series YD ÁÁ ÁÁ To avoid errors or delay in filling your parts order, always give the MODEL, SPEC NO. and SERIAL NO. from the Onan nameplate. For handy reference,

More information

DELAWARE COUNTY ORDINANCE NO. 3

DELAWARE COUNTY ORDINANCE NO. 3 DELAWARE COUNTY ORDINANCE NO. 3 AN ORDINANCE TO ESTABLISH THE POLICY AND LEVEL OF SERVICE IN RESPECT TO CLEARANCE OF SNOW OR ICE AND MAINTENANCE OF THIS COUNTY'S SECONDARY ROADS DURING THE WINTER MONTHS.

More information

Hydra Fault Current Limiting HTS Cable to be Installed in the Consolidated Edison Grid

Hydra Fault Current Limiting HTS Cable to be Installed in the Consolidated Edison Grid Hydra Fault Current Limiting HTS Cable to be Installed in the Consolidated Edison Grid J. McCall, J. Yuan, D. Folts, N. Henderson, American Superconductor D. Knoll, Southwire M. Gouge, R. Duckworth, J.

More information

Transient thermal measurements and thermal equivalent circuit models

Transient thermal measurements and thermal equivalent circuit models AN 2015-10 Transient thermal measurements and thermal equivalent circuit Replaces AN2008-03 About this document Scope and purpose The basis of a power electronic design is the interaction of power losses

More information

REPAIR PARTS. GPH16 Horizontal Package Heat Pumps. This manual is to be used by qualified technicians only.

REPAIR PARTS. GPH16 Horizontal Package Heat Pumps. This manual is to be used by qualified technicians only. REPAIR PARTS GPH16 Horizontal Package Heat Pumps GPH1624H41AA GPH1630H41AA GPH1636H41AA GPH1642H41AA GPH1648H41AA nufacturing Company, L.P. 5151 San Felipe, Suite 500 www.amana-hac.com www.amana-hac.com

More information

Melton Series. Owners Manual. Lab Centrifuge. Model # s A C, A C, B C, B C, C C, C C, D C, D C

Melton Series. Owners Manual. Lab Centrifuge. Model # s A C, A C, B C, B C, C C, C C, D C, D C Melton Series Owners Manual Lab Centrifuge Model # s A-4-115-C, A-4-220-C, B-4-115-C, B-4-220-C, C-4-115-C, C-4-220-C, D-4-115-C, D-4-220-C Serial Numbers 85500 & Above NOTICE Wire this centrifuge according

More information

HVAC Electrical Wiring Diagrams / Ohm s Law / Sequence of Operation RV

HVAC Electrical Wiring Diagrams / Ohm s Law / Sequence of Operation RV PLEASE DO NOT BOOKMARK ANY ANYTIMECE WEBPAGES! Our system will remember the last page you viewed when logging out and back in but please DO NOT exit out when taking a test. Your place will NOT be saved.

More information

GMVC 80% Variable Speed Communicating Furnace

GMVC 80% Variable Speed Communicating Furnace REPAIR PARTS GMVC 80% Variable Speed Communicating Furnace GMVC80604BNAA GMVC80604BNBA GMVC80604BNBB GMVC80604BNBC GMVC80604BXAA GMVC80604BXBA GMVC80604BXBB GMVC80604BXBC GMVC80805CNAA GMVC80805CNBA GMVC80805CNBB

More information

REPAIR PARTS. GPH14 "M" Series Residential Package Heat Pump. This manual is to be used by qualified technicians only.

REPAIR PARTS. GPH14 M Series Residential Package Heat Pump. This manual is to be used by qualified technicians only. REPAIR PARTS GPH14 "M" Series Residential Package Heat Pump GPH1424MAA GPH1430MAA GPH1436MAA GPH1442MAA GPH1448MAA GPH1460MAA nufacturing Company, L.P. 5151 San Felipe, Suite 500 www.amana-hac.com www.amana-hac.com

More information

Introduction to Oil&Gas Well Drilling

Introduction to Oil&Gas Well Drilling Introduction to Oil&Gas Well Drilling Drilling Introduction to Oil&Gas Well Drilling The term drilling indicates the whole complex of operations necessary to construct wells of circular section applying

More information

Technical Notes. Introduction. PCB (printed circuit board) Design. Issue 1 January 2010

Technical Notes. Introduction. PCB (printed circuit board) Design. Issue 1 January 2010 Technical Notes Introduction Thermal Management for LEDs Poor thermal management can lead to early LED product failure. This Technical Note discusses thermal management techniques and good system design.

More information

REPAIR PARTS. DSZC 16/18 SEER Remote Heat Pump

REPAIR PARTS. DSZC 16/18 SEER Remote Heat Pump DSZC 16/18 SEER Remote Heat Pump DSZC160241AA DSZC160241AB DSZC160241AC DSZC160241AD DSZC160241AE DSZC160361AA DSZC160361AB DSZC160361AC DSZC160361AD DSZC160361AE DSZC160481AA DSZC160481AB DSZC160481AC

More information

REPAIR PARTS. *CVC95 C'Flow Variable Speed Furnace ACVC950714CXBA ACVC950915DXBA GCVC950714CXBA GCVC950915DXBA

REPAIR PARTS. *CVC95 C'Flow Variable Speed Furnace ACVC950714CXBA ACVC950915DXBA GCVC950714CXBA GCVC950915DXBA *CVC95 C'Flow Variable Speed Furnace ACVC950714CXBA ACVC950915DXBA GCVC950714CXBA GCVC950915DXBA REPAIR PARTS This manual is to be used by qualified technicians only. 2012 Goodman Manufacturing Company,

More information

PARTS MANUAL Gas Furnace F9MAC, G9MAC

PARTS MANUAL Gas Furnace F9MAC, G9MAC Gas Furnace F9MAC, G9MAC Safety Labeling and Signal Words DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of hazard seriousness. The signal

More information

Oil and Gas Production and Exploration, Part I

Oil and Gas Production and Exploration, Part I Oil and Gas Production and Exploration, Part I Presented by: Steven Marzuola American Translators Association 52 nd Annual Conference Boston, October 26, 2011 1 Introduction Dope, Joints, Tripping Internal

More information

Power Resistors for Mounting Onto a Heatsink Thick Film Technology

Power Resistors for Mounting Onto a Heatsink Thick Film Technology Power Resistors for Mounting Onto a Heatsink Thick Film Technology DESIGN SUPPORT TOOLS click logo to get started FEATURES 1% tolerance available High power rating = 200 W Wide ohmic value range = 0.046

More information

Low Pressure Sensor Amplified Analog Output SM6295-BCM-S

Low Pressure Sensor Amplified Analog Output SM6295-BCM-S Low Pressure Sensor Amplified Analog Output SM6295-BCM-S-040-000 FEATURES Pressure range from 0 to 40 cmh 2 O 5.0 V operation Amplified analog output (10 to 90%Vdd) Compensated temperature range: 0 to

More information

CEDAR COUNTY ORDINANCE NO. 6

CEDAR COUNTY ORDINANCE NO. 6 CEDAR COUNTY ORDINANCE NO. 6 AN ORDINANCE TO ESTABLISH THE POLICY AND LEVEL OF SERVICE IN RESPECT TO CLEARANCE OF SNOW OR ICE AND MAINTENANCE OF THIS COUNTY'S SECONDARY ROADS DURING THE WINTER MONTHS.

More information

REPAIR PARTS. GMS95 Single Stage Upflow Furnace GMS950453BXAB GMS950703BXAB GMS950704CXAB GMS950904CXAB GMS951155DXAB.

REPAIR PARTS. GMS95 Single Stage Upflow Furnace GMS950453BXAB GMS950703BXAB GMS950704CXAB GMS950904CXAB GMS951155DXAB. REPAIR PARTS GMS95 Single Stage Upflow Furnace GMS950453BXAB GMS950703BXAB GMS950704CXAB GMS950904CXAB GMS55DXAB Made in the USA by: Goodman Manufacturing Company, L.P. 2550 North Loop West, Suite 400

More information

TELUX LED FEATURES APPLICATIONS COORDINATE. FORWARD VOLTAGE (V) (ma) at I F (ma) (ma) MIN. TYP. MAX. MIN. TYP. MAX. MIN. TYP. MAX. 0.33, 0.

TELUX LED FEATURES APPLICATIONS COORDINATE. FORWARD VOLTAGE (V) (ma) at I F (ma) (ma) MIN. TYP. MAX. MIN. TYP. MAX. MIN. TYP. MAX. 0.33, 0. TELUX LED DESCRIPTION The TELUX series is a clear, non diffused LED for high end applications where supreme luminous flux is required. It is designed in an industry standard 7.62 mm square package utilizing

More information

PARTS MANUAL Gas Furnace F8MXN, F8MXL, G8MXN, G8MXL

PARTS MANUAL Gas Furnace F8MXN, F8MXL, G8MXN, G8MXL Gas Furnace F8MXN, F8MXL, G8MXN, G8MXL DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAU- TION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER

More information

MMBZ5221BLT1 Series. Zener Voltage Regulators. 225 mw SOT 23 Surface Mount

MMBZ5221BLT1 Series. Zener Voltage Regulators. 225 mw SOT 23 Surface Mount MMBZ5BLT Series Zener Voltage Regulators 5 mw SOT Surface Mount This series of Zener diodes is offered in the convenient, surface mount plastic SOT package. These devices are designed to provide voltage

More information

CL-L102-C7D. 1. Scope of Application. These specifications apply to LED package, model CL-L102-C7D. 2. Part code

CL-L102-C7D. 1. Scope of Application. These specifications apply to LED package, model CL-L102-C7D. 2. Part code Specification sheet 1/10 1. Scope of Application These specifications apply to LED package, model. 2. Part code Series L102 : High power LED for general lighting Watt Class C7 : 7 watt class package Lighting

More information

GAP3SLT33-220FP 3300 V SiC MPS Diode

GAP3SLT33-220FP 3300 V SiC MPS Diode Silicon Carbide Schottky Diode V RRM = 3300 V I F (Tc 125 C) = 0.3 A Q C = 3 nc Features High Avalanche (UIS) Capability Enhanced Surge Current Capability Superior Figure of Merit Q C /I F Low Thermal

More information

REPAIR PARTS. GMVC8 80% Variable Speed Communicating Furnace

REPAIR PARTS. GMVC8 80% Variable Speed Communicating Furnace REPAIR PARTS GMVC8 80% Variable Speed Communicating Furnace GMVC80604BNAA GMVC80604BNBA GMVC80604BNBB GMVC80604BNBC GMVC80604BXAA GMVC80604BXBA GMVC80604BXBB GMVC80604BXBC GMVC80805CNAA GMVC80805CNBA GMVC80805CNBB

More information

BETA Protecting. Low-Voltage Fuse Systems. LV HRC fuse links. 3/36 Siemens ET B1 2008

BETA Protecting. Low-Voltage Fuse Systems. LV HRC fuse links. 3/36 Siemens ET B1 2008 LV HRC fuse links Overview LV HRC fuses are used for installation systems in non-residential, commercial and industrial buildings as well as in switchboards of power supply companies. They therefore protect

More information

REPAIR PARTS. GPH14 "H" Residential Package Heat Pump

REPAIR PARTS. GPH14 H Residential Package Heat Pump REPAIR PARTS GPH14 "H" Residential Package Heat Pump GPH1424H41AB GPH1424H41AC GPH1424H41BA GPH1424H41CA GPH1424H41DA GPH1424H41DB GPH1430H41AB GPH1430H41AC GPH1430H41BA GPH1430H41CA GPH1430H41DB GPH1436H41AB

More information

LM135/LM235/LM335, LM135A/LM235A/LM335A Precision Temperature Sensors

LM135/LM235/LM335, LM135A/LM235A/LM335A Precision Temperature Sensors LM135/LM235/LM335, LM135A/LM235A/LM335A Precision Temperature Sensors General Description The LM135 series are precision, easily-calibrated, integrated circuit temperature sensors. Operating as a 2-terminal

More information

BOONE COUNTY Snow Removal Program and Policy SECTION 1, INTRODUCTION:

BOONE COUNTY Snow Removal Program and Policy SECTION 1, INTRODUCTION: BOONE COUNTY Snow Removal Program and Policy SECTION 1, INTRODUCTION: The Roads Department of Boone County is responsible for providing snow removal for approximately 1100 miles of county roads. The Roads

More information

MJW18020G. NPN Silicon Power Transistors High Voltage Planar 30 AMPERES 1000 VOLTS BV CES 450 VOLTS BV CEO, 250 WATTS

MJW18020G. NPN Silicon Power Transistors High Voltage Planar 30 AMPERES 1000 VOLTS BV CES 450 VOLTS BV CEO, 250 WATTS NPN Silicon Power Transistors High Voltage Planar The MJW18020 planar High Voltage Power Transistor is specifically Designed for motor control applications, high power supplies and UPS s for which the

More information

REPAIR PARTS. GPG14 "M" Series Residential Package Gas Units. This manual is to be used by qualified technicians only. This manual replaces RP-G3001.

REPAIR PARTS. GPG14 M Series Residential Package Gas Units. This manual is to be used by qualified technicians only. This manual replaces RP-G3001. REPAIR PARTS GPG14 "M" Series Residential Package Gas Units GPG1424040MAA GPG1424040MAB GPG1424060MAA GPG1424060MAB GPG1430040MAA GPG1430040MAB GPG1430060MAA GPG1430060MAB GPG1436040MAA GPG1436040MAB GPG1436060MAA

More information

SN74LS157MEL. Quad 2 Input Multiplexer LOW POWER SCHOTTKY

SN74LS157MEL. Quad 2 Input Multiplexer LOW POWER SCHOTTKY Quad 2 Input Multiplexer The LSTTL/ MSI is a high speed Quad 2-Input Multiplexer. Four bits of data from two sources can be selected using the common Select and Enable inputs. The four buffered outputs

More information

nufacturing Company, L.P San Felipe, Suite

nufacturing Company, L.P San Felipe, Suite REPAIR PARTS GMVC 96% ECM Up Flow Furnace GMVC960403BNAA GMVC960603BNAA GMVC960803BNAA GMVC960804CNAA GMVC961005CNAA GMVC961205DNAA nufacturing Company, L.P. 5151 San Felipe, Suite 500 www.amana-hac.com

More information

STATE OF COLORADO DESIGN CRITERIA FOR POTABLE WATER SYSTEMS WATER QUALITY CONTROL DIVISION. Price: $5.00. Revised March 31, 1997

STATE OF COLORADO DESIGN CRITERIA FOR POTABLE WATER SYSTEMS WATER QUALITY CONTROL DIVISION. Price: $5.00. Revised March 31, 1997 STATE OF COLORADO DESIGN CRITERIA FOR POTABLE WATER SYSTEMS WATER QUALITY CONTROL DIVISION Revised March 31, 1997 Price: $5.00 a. an arrangement where the water pipe to be injected with chlorine enters

More information

ISOCON-6. 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER

ISOCON-6. 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER ISOCON-6 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER Whilst every effort has been taken to ensure the accuracy of this document, we accept no responsibility for damage, injury, loss or expense resulting

More information

MUR3020PTG SUR83020PTG MUR3040PTG MUR3060PTG SUR83060PTG. SWITCHMODE Power Rectifiers ULTRAFAST RECTIFIERS 30 AMPERES, VOLTS

MUR3020PTG SUR83020PTG MUR3040PTG MUR3060PTG SUR83060PTG. SWITCHMODE Power Rectifiers ULTRAFAST RECTIFIERS 30 AMPERES, VOLTS MUR00PTG, SUR00PTG, MUR00PTG, MUR00PTG, SUR00PTG SWITCHMODE Power Rectifiers These state of the art devices are designed for use in switching power supplies, inverters and as free wheeling diodes. Features

More information

RADIATION SAFETY GUIDELINES FOR NON-USERS

RADIATION SAFETY GUIDELINES FOR NON-USERS RADIATION SAFETY GUIDELINES FOR NON-USERS This is a Read and Sign Awareness Training document. You should read and sign this document if you: 1. DO NOT work directly with radioactive materials, but 2.

More information

TELUX LED FEATURES APPLICATIONS WAVELENGTH. (ma) MIN. TYP. MAX. MIN. TYP. MAX. MIN. TYP. MAX.

TELUX LED FEATURES APPLICATIONS WAVELENGTH. (ma) MIN. TYP. MAX. MIN. TYP. MAX. MIN. TYP. MAX. TELUX LED DESCRIPTION 9232 The TELUX series is a clear, non-diffused LED for applications where supreme luminous flux is required. It is designed in an industry standard 7.62 mm square package utilizing

More information

Issued August DATA SHEET. 3VT3 MCCB up to 630 A

Issued August DATA SHEET. 3VT3 MCCB up to 630 A ssued August 9 DATA SHEET VT MCCB up to 6 A Based on Siemens Catalog V 6 8 Circuit breakers Switch disconnectors Technical specifications Specifications Type VT 76-AA6/6/56-AA, VT 76-AA6/6/56-AA Circuit

More information

REPAIR PARTS. GPC13 "M" Series 3-5 Ton Package Coolers

REPAIR PARTS. GPC13 M Series 3-5 Ton Package Coolers REPAIR PARTS GPC13 "M" Series 3-5 Ton Package Coolers GPC1336MAA GPC1336MBA GPC1336MCA GPC1336M43AA GPC1348MAA GPC1348MBA GPC1348MCA GPC1348M43AA GPC1348M43BA GPC1360MAA GPC1360MBA GPC1360MCA GPC1360M43AA

More information

High Power Factors and Contaminants in Transformer Oil

High Power Factors and Contaminants in Transformer Oil High Power Factors and Contaminants in Transformer Oil By Russ Crutcher and Ken Warner HIGH POWER FACTORS AND CONTAMINANTS IN TRANSFORMER OIL Russ Crutcher and Ken Warner Microlab Northwest Abstract New

More information

Introduction to Oil and Gas Production

Introduction to Oil and Gas Production Introduction to Oil and Gas Production Steven Marzuola ATA Energy Conference May 4-6, 2007 Houston Texas Introduction Dope, Joints, Tripping Strippers Casing, Tubing, Liner API - American Petroleum Institute

More information

MMBZ5221BLT1 Series. Zener Voltage Regulators. 225 mw SOT 23 Surface Mount

MMBZ5221BLT1 Series. Zener Voltage Regulators. 225 mw SOT 23 Surface Mount MMBZ5BLT Series Preferred Device Zener Voltage Regulators 5 mw SOT Surface Mount This series of Zener diodes is offered in the convenient, surface mount plastic SOT package. These devices are designed

More information

High-Voltage Types Ordering Information, Mica Capacitors

High-Voltage Types Ordering Information, Mica Capacitors High-Voltage Types Ordering Information, Mica Capacitors Ordering Information Ordering Information: Order by complete part number, as below. For other options,write your requirements on your quote request

More information

REPAIR PARTS. AVPTC Air Handler. This manual is to be used by qualified technicians only. This manual replaces RP-775E.

REPAIR PARTS. AVPTC Air Handler. This manual is to be used by qualified technicians only. This manual replaces RP-775E. REPAIR PARTS AVPTC Air Handler AVPTC24B14AA AVPTC24B14AB AVPTC24B14AC AVPTC30C14AA AVPTC30C14AB AVPTC36C14AA AVPTC36C14AB AVPTC42D14AA AVPTC42D14AB AVPTC42D14AC AVPTC48C14AA AVPTC48C14AB AVPTC48D14AA AVPTC48D14AB

More information

Passivated ultra sensitive gate thyristor in a SOT54 plastic package. Earth leakage circuit breakers or Ground Fault Circuit Interrupters (GFCI)

Passivated ultra sensitive gate thyristor in a SOT54 plastic package. Earth leakage circuit breakers or Ground Fault Circuit Interrupters (GFCI) Rev. 2 31 July 28 Product data sheet 1. Product profile 1.1 General description Passivated ultra sensitive gate thyristor in a SOT54 plastic package. 1.2 Features Ultra sensitive gate Direct interfacing

More information

COMPANY NEWS JANUARY 2019 BE PREPARED FOR OUTAGES

COMPANY NEWS JANUARY 2019 BE PREPARED FOR OUTAGES COMPANY NEWS JANUARY 2019 BE PREPARED FOR OUTAGES None of us will forget the monster storm in January 2012 where snow and ice blanketed Western Washington. Plunging temperatures and freezing rain encased

More information

NTJD4105C. Small Signal MOSFET. 20 V / 8.0 V, Complementary, A / A, SC 88

NTJD4105C. Small Signal MOSFET. 20 V / 8.0 V, Complementary, A / A, SC 88 NTJD5C Small Signal MOSFET V / 8. V, Complementary, +.63 A /.775 A, SC 88 Features Complementary N and P Channel Device Leading 8. V Trench for Low R DS(on) Performance ESD Protected Gate ESD Rating: Class

More information

Features. Symbol Parameter N-Channel P-Channel Units. Drain-Source Voltage, Power Supply Voltage V V GSS. Gate-Source Voltage, 8-8 V I D

Features. Symbol Parameter N-Channel P-Channel Units. Drain-Source Voltage, Power Supply Voltage V V GSS. Gate-Source Voltage, 8-8 V I D FC6C ual N & P Channel, igital FET General escription These dual N & P Channel logic level enhancement mode field effect transistors are produced using ON Semiconductor's proprietary, high cell density,

More information

REPAIR PARTS. GCH95 95% Counterflow Hybrid Furnace. This manual is to be used by qualified technicians only. This manual replaces RP-597C.

REPAIR PARTS. GCH95 95% Counterflow Hybrid Furnace. This manual is to be used by qualified technicians only. This manual replaces RP-597C. REPAIR PARTS GCH95 95% Counterflow Hybrid Furnace GCH950453BXAA GCH950453BXAB GCH950453BXAD GCH950703BXAA GCH950703BXAB GCH950703BXAD GCH950704CXAA GCH950704CXAB GCH950704CXAD GCH950904CXAA GCH950904CXAB

More information

Silicon PIN Photodiode

Silicon PIN Photodiode Silicon PIN Photodiode DESCRIPTION is a high speed and high sensitive PIN photodiode with enhanced sensitivity for visible light. It is a low profile surface-mount device (SMD) including the chip with

More information

AMVC 80% Variable Speed Communicating Furnace

AMVC 80% Variable Speed Communicating Furnace REPAIR PARTS AMVC 80% Variable Speed Communicating Furnace AMVC80604BNAA AMVC80604BNBA AMVC80604BNBB AMVC80604BNBC AMVC80604BXAA AMVC80604BXBA AMVC80604BXBB AMVC80604BXBC AMVC80805CNAA AMVC80805CNBA AMVC80805CNBB

More information

ASPT Series. Multi-Position, Internal TXV. Air Handler 1½ to 5 Tons

ASPT Series. Multi-Position, Internal TXV. Air Handler 1½ to 5 Tons Series Multi-Position, Internal TXV Product Features Internal factory-installed thermal expansion valves for cooling and heat pump applications Direct drive, multi-speed ECM blower motor All-aluminum evaporator

More information

REPAIR PARTS. GPH H-SERIES Package Heat Pumps

REPAIR PARTS. GPH H-SERIES Package Heat Pumps REPAIR PARTS GPH H-SERIES Package Heat Pumps GPH1324HAB GPH1324HAC GPH1324HAD GPH1324HA GPH1330HAB GPH1330HAC GPH1330HAD GPH1330HA GPH1336HAB GPH1336HAC GPH1336HAD GPH1336HAE GPH1336HA GPH1342HAB GPH1342HAC

More information

1. Wind turbines are designed to operate within specified design criteria. Often the operating environment extends beyond these limits and causes

1. Wind turbines are designed to operate within specified design criteria. Often the operating environment extends beyond these limits and causes 1 2 1. Wind turbines are designed to operate within specified design criteria. Often the operating environment extends beyond these limits and causes outages. How these outages are classified can be challenging

More information

REQUEST FOR PROPOSALS

REQUEST FOR PROPOSALS REQUEST FOR PROPOSALS 10782 Wattsburg Road Erie, PA 16509 The WATTSBURG AREA SCHOOL DISTRICT invites qualified vendors to submit proposals for CONTRACTED SNOW REMOVAL MANDATORY PRE-SUBMISSION MEETING All

More information

For personal use only

For personal use only 28 May 2012 Farm Out Arrangements Turner Bayou Project Pryme Energy Limited (Pryme) and its partners in the Turner Bayou project have established arrangements for farming out of a portion of their project

More information

Issued August DATA SHEET. 3VT5 MCCB up to 1600 A

Issued August DATA SHEET. 3VT5 MCCB up to 1600 A ssued August 9 DATA SHEET VT5 MCCB up to 0 A Based on Siemens Catalog V 8 Standard circuit breakers Releases Technical specifications Specifications VT5 circuit breakers Switch disconnectors Type Standards

More information

REPAIR PARTS. A/GPG13 Package Gas Units

REPAIR PARTS. A/GPG13 Package Gas Units REPAIR PARTS A/GPG13 Package Gas Units APG1324045MBA APG1324070MBA APG1330045MBA APG1330070MBA APG1336045MBA APG1336070MBA APG1336090MBA APG1342070MBA APG1342090MBA APG1348070MBA APG1348090MBA APG13485MBA

More information

MUR405, MUR410, MUR415, MUR420, MUR440, MUR460

MUR405, MUR410, MUR415, MUR420, MUR440, MUR460 4, 4, 41, 42, 44, 46 42 and 46 are Preferred Devices SWITCHMODE Power Rectifiers These state of the art devices are a series designed for use in switching power supplies, inverters and as free wheeling

More information

An Introduction to Insulation Resistance Testing

An Introduction to Insulation Resistance Testing An Introduction to Insulation Resistance Testing In a perfect world, electrical insulation would allow no current to flow through it. Unfortunately, a number of factors can over time result in the deterioration

More information

Inside Wall Temperature Measurements of DSTs Using an Infrared Temperature Sensor

Inside Wall Temperature Measurements of DSTs Using an Infrared Temperature Sensor TEST PLAN Inside Wall Temperature Measurements of DSTs Using an Infrared Temperature Sensor Date submitted: December 18, 2015 Prepared by: Aparna Aravelli, Ph.D. Florida International University Collaborators:

More information

S3A - S3N General-Purpose Rectifiers

S3A - S3N General-Purpose Rectifiers S3A - S3N General-Purpose Rectifiers Features Low-Profile Package Glass-Passivated Junction UL Flammability Classification: 94V-0 UL Certified, UL #E258596 SMC/DO-214AB COLOR BAND DENOTES CATHODE ELECTRICAL

More information

REPAIR PARTS. *MVM96 Variable Speed Furnace

REPAIR PARTS. *MVM96 Variable Speed Furnace *MVM96 Variable Speed Furnace AMVM960603BXAA AMVM960603BXBA AMVM960805CXAA AMVM960805CXBA AMVM961005DXAA AMVM961005DXBA AMVM9655DXAA AMVM9655DXBA GMVM960603BXAA GMVM960603BXBA GMVM960805CXAA GMVM960805CXBA

More information

Alternating Current (AC): Alternating Current is electric current that reverses directions at regular intervals.

Alternating Current (AC): Alternating Current is electric current that reverses directions at regular intervals. Glossary Alternating Current (AC): Alternating Current is electric current that reverses directions at regular intervals. American National Standards Institute (ANSI): American National Standards Institute

More information