MPM GROUP THERMOGRAPHIC INSPECTION

Size: px
Start display at page:

Download "MPM GROUP THERMOGRAPHIC INSPECTION"

Transcription

1 MPM GROUP 8 th August 2014 THERMOGRAPHIC INSPECTION Client Contact Mr P Sykes Site Hay Street Perth WA Scope of Work Thermographic inspection of electrical installations as per AS/NZS 3019:2007, ISO and ANSI/NETA MTS-2011 Client Order/Reference No To be advised Job Reference No RBNO Client On-site Representative/s N/A Thermographer/Assistant N C Otway and A Tory (EW155253) P Kevin Mitchell ASNT level 2 thermographer for Infra Red Services

2 SUMMARY OF THERMAL FAULTS RECORDED The following is intended for use by the client to record information on the status of fault repairs Fault no. (eg. TIR-R1) ANSI Fault level Page no. Date action scheduled Date action completed Date reinspected (if required) Reinspection result (if required) There were no areas of abnormal temperature detected that require action by the client Fault levels as per ANSI/NETA MTS 2011 Table ΔT of between 1 o C and 3 o C Fault level 1 Possible deficiency, warrants further investigation and/or monitoring ΔT of between 4 o C and 15 o C Fault level 2 Probable deficiency, repair at next scheduled shutdown ΔT of between >15 o C Fault level 3 Major deficiency, repair immediately 2

3 SUMMARY OF COMMENTS RECORDED The following is intended for use by the client to record information on the action taken regarding comments. Comment no. (eg. C1 or TIR-RX) Page no. TIR-R1 4 Date action scheduled Date action completed Date reinspected (if required) Reinspection result (if required) Red highlight indicates a significant comment 3

4 THERMOGRAPHIC INSPECTION REPORT R1 Photograph Analysis & Identification Inspection date Emissivity (E) N/A Ambient temp. o C N/A Location and Roger David equipment Sub board identification: The image shows the circuit breaker was not properly secured to the back panel Repair action taken Repaired by: Action taken: Repair date: 4

5 INTERPRETATION OF RESULTS THE FOLLOWING APPLIES TO ALL IMAGES Grey scale or colour scale D: 45.5 C B: 45.2 C 71.2 C Monochrome imaging - on this grey scale white is hot and black cool Relative temperatures are in shades of grey (256 grey levels) Colour imaging - on this colour scale, white is hot and black cool Relative temperatures are in different colours 50 Spot temperatures in degrees Celsius 45 A number of points on the image/s may be selected 40 eg D 45.5 and A 71.2 on the image on the right An! indicates that a point is the highest temperature object in the frame C: 45.1 C A!: 71.2 C Emissivity refers to the relative infrared radiation given off by the object surface. The measured temperature of the object depends on the estimation of this value, which may be adjusted by the thermographer. In general, a bright, smooth surface has a low emissivity compared with a dull, matt surface. Where both conditions appear on the same thermogram, the low emissivity area may appear cooler or warmer than the high emissivity area, irrespective of the actual temperatures. Note Close proximity to strong electromagnetic fields can result in distortion of the images. CLASSIFICATION OF ABNORMAL CONDITIONS - Electrical surveys The most important variable which affects the severity of an abnormal condition is the load (amps) applicable at the time of the inspection. This must also be compared with the rating of the component/s. eg. A small temperature rise under low load conditions is more significant than a small temperature rise at the component maximum rating. It is not advisable to specify a priority repair (or severity rating) for the abnormal conditions based on the temperature rise/fall between normal and abnormal. Although the load at the time of inspection is recorded, the duration of this specific reading is seldom known for certain. Often it is either impossible to determine exactly, or time consuming and expensive to establish precisely. Other variables also compound the problem. The following should be considered when assessing abnormal conditions: Compare recorded load with component rating and normal operational load 3 phase motors sustain damage operating on two phases Poor connections are not necessarily loose Only surface temperatures are recorded Function of the equipment eg. computer and lift installations Try the simplest remedy first eg. check if screws are not tightened properly Rating of faults 5 Possible causes of heating Any one, or more, of the following can result in abnormal temperatures: Additions to existing plant Expansion and contraction Insufficient contact area Loose connections Overloading/phase imbalance Single phasing Oxidation/corrosion/pitting Vibration Harmonics In the absence of an applicable Australian Standard inspections are carried out in accordance with ANSI/NETA MTS-2011 section 9 Thermography Survey and ISO Table of ANSI/NETA MTS-2011 defines the following fault levels: ΔT of between 1 C and 3 C Fault level 1 Possible deficiency, warrants further investigation and/or monitoring ΔT of between 4 C and 15 C Fault level 2 Probable deficiency, repair at next scheduled shutdown ΔT of between >15 C Fault level 3 Major deficiency, repair immediately Rating numbers have been added by Infra Red Services for ease of interpretation by the client and are not part of the standard Fault ratings are provided as a guide only and must be interpreted with consideration given to the fact that a change in operating conditions, such as ambient temperature or load (current) levels, can drastically alter a fault condition

6 ELECTRICAL INSPECTION REPORT SCOPE OF WORK Thermographic inspection of all on line/on load electrical installations as specified by the client. Refer to the following list of Electrical Equipment Inspected page 7. THERMOGRAPHIC INSPECTION EQUIPMENT Avio ThermoTVS-200EX serial no Avio R300SR serial no NEC 7102WL serial no NEC 7102WX serial no APPLICATION Where possible, the removal of all escutcheon panels, doors and covers carried out prior to the inspection. In some cases, interlocking, safety or operational conditions may prohibit access. Temperature gradients across the surface of all accessible components assessed at the time of inspection. Reporting by exception, whereby a record of detected abnormal conditions provided as specified by the client. CONDITION REPORT FORMAT Infra Red Services retains copies of all files, images and documentation indefinitely. Historical data is available to clients on request. ed copy of the report sent to the client format PDF file. Hard copies of reports are not issued by default but can be provided on client request at no additional cost. All reports contain: a) A comprehensive list of equipment inspected. b) Detailed information to assist with interpretation of the results. c) Thermographic Inspection Report (TIR) sheets for each abnormal condition detected. Includes: Marked colour identification images Colour and monochrome thermograms of abnormal conditions Detailed equipment identification including electrical load readings - where possible Normal/abnormal temperature information Possible reason for abnormal temperatures INSPECTION RESULTS No areas of abnormal heating were detected. Attention is drawn to the comment on page 4. Refer to pages 2 and 3 for a summary of faults/comments recorded requiring further action. FOLLOW-UP ACTION Regular reinspections (condition monitoring) can be carried out as an alternative to carrying out costly/untimely repairs in some circumstances. A reinspection is recommended to ensure the efficacy of repairs carried out. This is especially true for critical installations eg. UPS and lift components. Due to the dynamic nature of electrical installations (through expansion and contraction, vibration and cycling/switching actions), an annual inspection of all electrical installations is recommended as a minimum requirement. 6

7 ELECTRICAL EQUIPMENT INSPECTED The following electrical switchboards and distribution boards were inspected: Status legend: Blank No abnormal condition detected R* Thermographic Inspection Report No UTO Unable to open OL Off-line NI Not inspected this survey V Vacant - not inspected this survey C* Comment no - at the bottom of the page OOS Out of service SI WI Summer inspection or winter inspection VI Visual inspection only - no load at the time of inspection AREA SWITCHBOARD PANEL STATUS Aug 2014 Roger David Sub board Main switch/circuit breakers/rcds R1 Strandbags Sub board Main switch/circuit breaker chassis back store Basement under Strandbags MSB fire door to WP room front Main switch/meters fuses rear Connections JB Hi-Fi Sub board Main switch/circuit breaker chassis North side 7

8 THIS PAGE HAS BEEN LEFT BLANK INTENTIONALLY

Thermal Imaging Survey. Conducted at Nottingham

Thermal Imaging Survey. Conducted at Nottingham Thermal Imaging Survey Conducted at ----------------- Nottingham [This copy has been edited to remove location details. The original document does not have a "Foxit PDF Editor" header on every page.] 27/01/2010

More information

BUREAU OF INDIAN STANDARDS. Draft Indian Standard GUIDELINES FOR INFRARED THERMOGRAPHY INSPECTION OF ELECTRICAL INSTALLATIONS ICS 19.

BUREAU OF INDIAN STANDARDS. Draft Indian Standard GUIDELINES FOR INFRARED THERMOGRAPHY INSPECTION OF ELECTRICAL INSTALLATIONS ICS 19. For BIS Use Only Doc: MTD 21 (5044)W BUREAU OF INDIAN STANDARDS Draft Indian Standard GUIDELINES FOR INFRARED THERMOGRAPHY INSPECTION OF ELECTRICAL INSTALLATIONS ICS 19.100 Not to be reproduced without

More information

COPPER FOR BUSBARS CHAPTER 4: SHORT-CIRCUIT EFFECTS

COPPER FOR BUSBARS CHAPTER 4: SHORT-CIRCUIT EFFECTS European Copper Institute COPPER FOR BUSBARS CHAPTER 4: SHORT-CIRCUIT EFFECTS David Chapman August 2011 ECI Available from www.leonardo-energy.org Document Issue Control Sheet Document Title: Publication

More information

Periodic Inspection and Testing of Electrical Installations Sample Test ( ) Version 1.3 July 2018

Periodic Inspection and Testing of Electrical Installations Sample Test ( ) Version 1.3 July 2018 Periodic Inspection and Testing of Electrical Installations Sample Test (2391-051) Version 1.3 July 2018 Sample Questions Version and date Change detail Section 1.3 July 2018 Modified questions/answers

More information

6 Securing of the delivery and acceptance

6 Securing of the delivery and acceptance 6 Securing of the delivery and acceptance Sector/Field Ox activities 1 Building Energy consumption 2 Spaces 3 Envelope, walls, roof, base floors, windows and doors Total energy consumption by types of

More information

Emissivity: Understanding the difference between apparent and actual infrared temperatures

Emissivity: Understanding the difference between apparent and actual infrared temperatures Emissivity: Understanding the difference between apparent and actual infrared temperatures By L. Terry Clausing, P.E. ASNT Certified NDT Level III T/IR, for Fluke Corporation Application Note Taking infrared

More information

IR F ( C) ENGLISH INSTRUCTION MANUAL. Thermometer

IR F ( C) ENGLISH INSTRUCTION MANUAL. Thermometer INSTRUCTION MANUAL Thermometer DUAL-LASER TARGETING 12:1 DISTANCE- TO-SPOT RATIO AUTO-SCAN MAX/MIN/AVG/DIFF HIGH/LOW ALARM BACKLIT DISPLAY AUTO POWER-OFF ADJUSTABLE EMISSIVITY IR5 2m -22 752 F (-30 400

More information

OIML R 141 RECOMMENDATION. Edition 2008 (E) ORGANISATION INTERNATIONALE INTERNATIONAL ORGANIZATION

OIML R 141 RECOMMENDATION. Edition 2008 (E) ORGANISATION INTERNATIONALE INTERNATIONAL ORGANIZATION INTERNATIONAL RECOMMENDATION OIML R 141 Edition 2008 (E) Procedure for calibration and verification of the main characteristics of thermographic instruments Procédure pour l'étalonnage et la vérification

More information

SIDEWINDER DRILLING RIG 102 HOUSTON, TEXAS

SIDEWINDER DRILLING RIG 102 HOUSTON, TEXAS SIDEWINDER DRILLING RIG 102 HOUSTON, TEXAS January, 2017 Infrared Inspection Report Sidewinder Drilling Rig 102 St Augustine, Texas Company Contact Jesse Russell Project: 06060117 2605 CHARTER OAK DRIVE,

More information

TECHNICAL DESCRIPTION SPECTRAFLOW ON LINE ANALYZER for BELT CONVEYOR APPLICATION

TECHNICAL DESCRIPTION SPECTRAFLOW ON LINE ANALYZER for BELT CONVEYOR APPLICATION TECHNICAL DESCRIPTION SPECTRAFLOW ON LINE ANALYZER for BELT CONVEYOR APPLICATION TECHNICAL SPECIFICATION SPECTRAFLOW ON LINE ANALYZER FOR BELT CONVEYOR CONTENTS 1. SpectraFlow Technical Description...

More information

THERMODYNAMICS METHODS OF HEAT TRANSFER RADIATION

THERMODYNAMICS METHODS OF HEAT TRANSFER RADIATION VISUAL PHYSICS ONLINE THERMODYNAMICS METHODS OF HEAT TRANSFER RADIATION Radiation is the energy transferred by electromagnetic waves mainly infrared (IR), visible and ultraviolet (UV). All materials radiate

More information

Infrared thermography as a tool to elaborate procedures for predictive maintenance of ball mills equipment

Infrared thermography as a tool to elaborate procedures for predictive maintenance of ball mills equipment 14 th Quantitative InfraRed Thermography Conference Infrared thermography as a tool to elaborate procedures for predictive maintenance of ball mills equipment by R. Władysiak*, T. Pacyniak* * Lodz University

More information

ISOCON-3 MAINS POWERED ISOLATING SIGNAL CONVERTER

ISOCON-3 MAINS POWERED ISOLATING SIGNAL CONVERTER ISOCON-3 MAINS POWERED ISOLATING SIGNAL CONVERTER CAUTION: This equipment is designed for connection to mains voltages and must be used in accordance with this guide. If it is not, the safety protection

More information

ER2 Short-head Electric Chain Hoist

ER2 Short-head Electric Chain Hoist O/M NO.SHER2-0903-CE-00 ER2 Short-head Electric Chain Hoist (250kg to 5t) Operation Manual (SHER2M/SHER2SG/SHER2SP) Introduction The KITO Short-head Electric Chain Hoist is intended for effective use in

More information

www. ElectricalPartManuals. com Flexitest Switch Assemblies Type FT-19R and FT-19RX INTL APPLICATION

www. ElectricalPartManuals. com Flexitest Switch Assemblies Type FT-19R and FT-19RX INTL APPLICATION Effective: January 2004 Supersedes, dated June 1998 APPLICATION QUALITY FEATURES Descriptive Bulletin 41-078INTL Flexitest Switch Assemblies Type The type FT-19R (standard length) and FT-19RX (extended

More information

Lamp and Control Panel (Lamp Panel)

Lamp and Control Panel (Lamp Panel) www.reinhausen.com Lamp and Control Panel (Lamp Panel) Operating Instructions BA 47/0 EN NOTE! Changes may have been made to a product after going to press with this documentation. We expressly reserve

More information

Model M3484 Industrial Line Noise Filter Module Customer Reference Manual

Model M3484 Industrial Line Noise Filter Module Customer Reference Manual Model M3484 Industrial Line Noise Filter Module Customer Reference Manual Web: www.bonitron.com Tel: 615-244-2825 Email: info@bonitron.com Bonitron, Inc. Bonitron, Inc. Nashville, TN An industry leader

More information

AM 500A 500 WATT AM 1A 1 KILOWATT AM BROADCAST TRANSMITTERS. October, 1999 IM No

AM 500A 500 WATT AM 1A 1 KILOWATT AM BROADCAST TRANSMITTERS. October, 1999 IM No AM 500A 500 WATT AM 1A 1 KILOWATT AM BROADCAST TRANSMITTERS October, 1999 IM No. 597 1112 EQUIPMENT LOST OR DAMAGED IN TRANSIT. When delivering the equipment to you, the truck driver or carrier s agent

More information

ISO INTERNATIONAL STANDARD. Condition monitoring and diagnostics of machines Thermography Part 1: General procedures

ISO INTERNATIONAL STANDARD. Condition monitoring and diagnostics of machines Thermography Part 1: General procedures INTERNATIONAL STANDARD ISO 18434-1 First edition 2008-03-01 Condition monitoring and diagnostics of machines Thermography Part 1: General procedures Surveillance et diagnostic de l'état des machines Thermographie

More information

Edmonton International Airport

Edmonton International Airport Edmonton International Airport ZVL Airside Operations Winter Operations Program 2012/13 September 10, 2012 ZVL_pla.dgn Default 12/17/07 5:10:28 PM AIRSIDE WINTER OPERATIONS PROGRAM (AER-002P) DISTRIBUTION/REVISION

More information

Masterpact. Installation recommendations

Masterpact. Installation recommendations 90 Installation recommendations Presentation Functions and characteristics 9 Dimensions and connection 5 Electrical diagrams 8 Operating conditions 92 Installation in switchboard 9 Door interlock catch

More information

Fault Calculation Methods

Fault Calculation Methods ELEC9713 Industrial and Commercial Power Systems Fault Calculation Methods There are two major problems that can occur in electrical systems: these are open circuits and short circuits. Of the two, the

More information

ISOCON-6. 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER

ISOCON-6. 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER ISOCON-6 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER Whilst every effort has been taken to ensure the accuracy of this document, we accept no responsibility for damage, injury, loss or expense resulting

More information

FLT5A FLT5A. abc. abc. Thermometer User Guide. Thermometer User Guide. Internet:

FLT5A FLT5A. abc. abc. Thermometer User Guide. Thermometer User Guide. Internet: abc instruments international FLT5A Thermometer Land Instruments International Dronfield, S18 1DJ England Telephone: (1246) 417691 Facsimile: (1246) 41585 Email: infrared.sales@landinst.com Internet: www.landinst.com

More information

Facilities Management

Facilities Management Policy Number: 700.20 Title: Chemical Fume Hood Policy Implementation Date: 2002 Last Audited: August, 2017 Last Revised: October 23rd, 2017 Facilities Management Introduction The laboratory chemical fume

More information

Hazard Communication

Hazard Communication Hazard Communication For Company: Address: LC-1009 Rev. 06/16 Page 1 Hazard Communication Program Ref: OSHA 1910.1200 Approved by: Title: Ranking Official's Signature Date: Hazard Communication Coordinator

More information

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager. Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager. 1 -A - Introduction - Thank for your purchasing MITSUBISHI ELECTRIC MELPRO TM D Series Digital Protection

More information

Town of Taos Request for Proposal Historic Preservation GIS Geodatabase Project April 2007

Town of Taos Request for Proposal Historic Preservation GIS Geodatabase Project April 2007 Town of Taos Request for Proposal Historic Preservation GIS Geodatabase Project April 2007 1. Background The Town of Taos is requesting proposals from qualified firms or a team of firms who can develop

More information

I, THERMAL ANALYSIS OF BUS-BAR FOR SWITCH BOARD

I, THERMAL ANALYSIS OF BUS-BAR FOR SWITCH BOARD THERMAL ANALYSIS OF BUS-BAR FOR SWITCH BOARD Krishna Dwivedi*, Kulwant Dhankar**, Smita Ganjare*** & Hemant More**** Assistant Professor, Mechanical Department, LTCOE, Navi Mumbai, Maharashtra Abstract:

More information

NEW YORK CENTRAL SYSTEM HOT BOX DETECTORS JUNE 1, 1959

NEW YORK CENTRAL SYSTEM HOT BOX DETECTORS JUNE 1, 1959 NEW YORK CENTRAL SYSTEM HOT BOX DETECTORS JUNE 1, 1959 N E W Y O R K C E N T R A L S Y S T E M HOT BOX DETECTORS INTRODUCTION The purpose of the information contained herein is to give all concerned a

More information

Power Resistors, for Mounting onto a Heatsink Thick Film Technology

Power Resistors, for Mounting onto a Heatsink Thick Film Technology RCH Manufactured in cermet thick fi lm technology, these power resistors exhibit remarkable characteristics and the series includes 4 types ranging from 5 W to 50 W Designed to be mounted onto a heatsink,

More information

Dr. Michael Müller. Thermal Management for LED applications

Dr. Michael Müller. Thermal Management for LED applications Thermal Management for LED applications Content Thermal Design Basics thermal management Internal thermal management External thermal management 2 1967 founded with the production of insulation parts for

More information

Edmonton International Airport

Edmonton International Airport Edmonton International Airport ZVL Airside Operations Winter Operations Program 2017/18 September, 2017 AIRSIDE WINTER OPERATIONS PROGRAM (AER-002P) DISTRIBUTION/REVISION LIST Distribution Edmonton Airports

More information

Fluid Power Institute Summary Report. Burst Pressure Evaluation Project #52224

Fluid Power Institute Summary Report. Burst Pressure Evaluation Project #52224 Fluid Power Institute Summary Report Burst Pressure Evaluation Project #52224 Test Completion Date: 7/31/2014 Test Specimen: Zero-Leak Gold Plugs (ZLGP) Client: EPCO Products, Inc. Milwaukee School of

More information

Schedule C By-Law Snow and Ice Control Services - Project Specifications for Various Parking Lots

Schedule C By-Law Snow and Ice Control Services - Project Specifications for Various Parking Lots SNOW AND ICE CONTROL SERVICES - (4) SEPARATE DEPARTMENTS SCHEDULE C REQUEST FOR PROPOSAL 2244 Schedule C By-Law Snow and Ice Control Services - Project Specifications for Various Parking Lots 1.0 General

More information

MAINTENANCE EVALUATION CHECKLIST HYDRAULIC ELEVATORS

MAINTENANCE EVALUATION CHECKLIST HYDRAULIC ELEVATORS Manufacturer: Model: Evaluation Performed By: INTRODUCTION: This checklist will enable the user to make an objective appraisal of the condition of the equipment. Given the variety and complexity of the

More information

Technical Concepts - Fault Analysis Methods

Technical Concepts - Fault Analysis Methods RATIO X/R Technical Concepts - Fault Analysis Methods Technical Concepts - Fault Analysis Methods (Continued) "What is the difference between a traditional fault calculation and an ANSI-based fault calculation"

More information

WeatherHub2 Quick Start Guide

WeatherHub2 Quick Start Guide WeatherHub2 Quick Start Guide Table of Contents 1 Introduction... 1 2 Packing List... 1 3 Connections... 1 4 IP Addressing... 2 5 Browser Access... 3 6 System Info... 3 7 Weather Station Settings... 4

More information

MIRUS International Inc.

MIRUS International Inc. MIRUS International Inc. INSTALLATION, OPERATION AND MAINTENANCE GUIDE THE LINEATOR ADVANCED UNIVERSAL HARMONIC FILTER (AUHF) AUHF-M001-A10 IMPORTANT SAFETY INSTRUCTION SAVE THESE INSTRUCTIONS - This manual

More information

REPAIR PARTS. *CVC9 90% C'Flow 2-Stage Variable Speed Furnace

REPAIR PARTS. *CVC9 90% C'Flow 2-Stage Variable Speed Furnace REPAIR PARTS *CVC9 90% C'Flow 2-Stage Variable Speed Furnace ACVC90704CXAA ACVC90704CXAB ACVC90905DXAA ACVC90905DXAB ACVC950714CXAA ACVC950915DXAA GCVC90704CXAA GCVC90704CXAB GCVC90905DXAA GCVC90905DXAB

More information

Telescopic auto dimension measuring system

Telescopic auto dimension measuring system - 0 - Contents Chapter One: Brief introduction 2 Chapter Two: Safety cautions 3 Chapter Three: Spare parts list and name 4 Chapter Four: User manual 7 I. Distance between 250~1140mm (M3:250~900mm) II.

More information

Use of Infrared Thermography for Building Inspection

Use of Infrared Thermography for Building Inspection Use of Infrared Thermography for Building Inspection Seminar on Building Diagnostic and Inspection Testing & Certification Association of Engineering Professionals in Society Ltd K.K. Lee, Kenneth Introduction

More information

The greater the thickness the darker the colour may appear, as less light can transfer through.

The greater the thickness the darker the colour may appear, as less light can transfer through. T h e s p e c i f i e r s g u i d e t o P r o d u c t s u m m a r y P r o d u c t i o n F a b r i c a t i o n S h e e t s i z e s C u s t o m s h e e t s F i n i s h e s C o l o u r s Marblo * is a cross-linked

More information

GENERATOR INTERCONNECTION APPLICATION

GENERATOR INTERCONNECTION APPLICATION GENERATOR INTERCONNECTION APPLICATION FOR BUY-ALL/SELL-ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 20 KW BUT LESS THAN OR EQUAL TO 1 MW Electric Utility Contact Information Great Lakes Energy

More information

FOR POLARIS ATV s P/N ASSEMBLY / OWNERS MANUAL

FOR POLARIS ATV s P/N ASSEMBLY / OWNERS MANUAL MID-MOUNT KIT FOR POLARIS ATV s P/N 15-3591 ASSEMBLY / OWNERS MANUAL Application PLOW PUSH FRAME NO. 15-0070, 33-0000 or 33-0070 Before you begin, please read these instructions and check to be sure all

More information

Instruction. Vacuum Circuit Breaker Operator Module. Type 3AH 4.16kV to 38kV. Power Transmission & Distribution

Instruction. Vacuum Circuit Breaker Operator Module. Type 3AH 4.16kV to 38kV. Power Transmission & Distribution Instruction 0001-22-2--00 Vacuum Circuit Breaker Operator Module Type 3AH 4.16kV to 38kV Power Transmission & Distribution Hazardous voltages and high-speed moving parts. Will cause death, serious injury

More information

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager. Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager. 1 -C - Safety section - This Safety section should be read before starting any work on the relay.

More information

Surrounding Effects on Temperature and Emissivity Measurement of Equipment in Electrical Distribution System

Surrounding Effects on Temperature and Emissivity Measurement of Equipment in Electrical Distribution System , October 21-23, 2015, San Francisco, USA Surrounding Effects on Temperature and Emissivity Measurement of Equipment in Electrical Distribution System T. Nunak, N. Nunak, V. Tipsuwanporn, and T. Suesut

More information

Outage Coordination and Business Practices

Outage Coordination and Business Practices Outage Coordination and Business Practices 1 2007 Objectives What drove the need for developing a planning/coordination process. Why outage planning/coordination is crucial and important. Determining what

More information

ASSET INTEGRITY INTELLIGENCE. Featured Article. ACHIEVING A COMPREHENSIVE FIRED HEATER HEALTH MONITORING PROGRAM By Tim Hill, Quest Integrity Group

ASSET INTEGRITY INTELLIGENCE. Featured Article. ACHIEVING A COMPREHENSIVE FIRED HEATER HEALTH MONITORING PROGRAM By Tim Hill, Quest Integrity Group ASSET INTEGRITY INTELLIGENCE Featured Article ACHIEVING A COMPREHENSIVE FIRED HEATER HEALTH MONITORING PROGRAM By Tim Hill, Quest Integrity Group VOLUME 20, ISSUE 5 SEPTEMBER OCTOBER 2014 ACHIEVING A COMPREHENSIVE

More information

ATTACHMENT Mitigating Systems

ATTACHMENT Mitigating Systems ATTACHMENT 71111.01 INSPECTABLE AREA: Adverse Weather Protection CORNERSTONE: Initiating Events Mitigating Systems EFFECTIVE DATE: January 1, 2010 INSPECTION BASES: Weather conditions leading to loss of

More information

Table of Contents Pin-Configuration Selection Guide for HDE, HDS, & EFP

Table of Contents Pin-Configuration Selection Guide for HDE, HDS, & EFP Table of Contents -Configuration Selection Guide for HDE, HDS, & EFP Service Voltage Rating... Electrical Service Ratings... Ampacity Ratings by Contact... Electrical Service Ratings Explained... Operating

More information

Reference Only Spec. No. JEFL243B 0003F-01 P 1/ 6

Reference Only Spec. No. JEFL243B 0003F-01 P 1/ 6 Spec. No. JEFL243B 0003F-01 P 1/ 6 DC Common Mode Choke Coil PLT09HN2003R0P1B Reference Specification 1. Scope This reference specification applies to DC Common Mode Choke Coil (PLT09H Series). 2. Part

More information

1. The type of energy described by Energy C is which type of energy?

1. The type of energy described by Energy C is which type of energy? Energy A Energy B Energy C Energy D Energy E Energy stores within a particle (measured by the particle s temperature). Energy generated by the sun. Energy released when particles react to form a new substance.

More information

TANDEX TEST LABS, INC Business Ctr. Dr. Irwindale CA Phone : Fax :

TANDEX TEST LABS, INC Business Ctr. Dr. Irwindale CA Phone : Fax : Page1 TANDEX TEST LABS, INC. 15849 Business Ctr. Dr. Irwindale CA. 91706 Phone : 626-962-7166 Fax : 626-960-6896 Failure Analysis TANDEX ELECTRONICS TTL# TAN-106-90-W Date: October 4, 1999 Part Number:

More information

Coefficient of Thermal Expansion for 477-T16 ACCR

Coefficient of Thermal Expansion for 477-T16 ACCR Coefficient of Thermal Expansion for 477-T16 ACCR Summary: The Coefficient of Thermal Expansion (CTE) was measured for a 477-T16 ACCR conductor. Thermal expansion as a function of temperature displays

More information

Solenoid valves Type EVUL

Solenoid valves Type EVUL Data sheet Solenoid valves EVUL EVUL solenoid valves are designed to fit into compact refrigeration systems. Available in servo operated versions they can be applied in liquid, suction, and hot gas lines.

More information

Heat Transfer and Flow Simulation in PCB

Heat Transfer and Flow Simulation in PCB Logic Fruit Technologies White Paper 806, 8 th Floor, BPTP Park Centra, Sector 30, Gurgaon. Pin: 122001 T: +91-124-4117336 W: http://www.logic-fruit.com Heat Transfer and Flow Simulation in PCB By: Sagar

More information

the firm: Tel.: REMENT

the firm: Tel.: REMENT Evaluations performed by the firm: Alena Chmelová, Prokopa Holého 258/4, Opava, Czech Republic EU VAT no.: CZ7357281987 Tel.: (+420) 607 594 827, (+420) 602 769 785 Email: termotest@seznam.cz, http://

More information

MLCC APPLICATION GUIDE

MLCC APPLICATION GUIDE MLCC APPLICATION GUIDE 1/11 No. Process Condition 1 Operating Condition (Storage) 1) The capacitor must be stored in an ambient temperature between 5 ~ 40 with a relative humidity of 20 ~ 70%. The products

More information

Temporal analysis for implicit compensation of local variations of emission coefficient applied for laser induced crack checking

Temporal analysis for implicit compensation of local variations of emission coefficient applied for laser induced crack checking More Info at Open Access Database www.ndt.net/?id=17661 Abstract Temporal analysis for implicit compensation of local variations of emission coefficient applied for laser induced crack checking by G. Traxler*,

More information

Flexitest Switch Assemblies Type FT-19R and FT-19RX Supersedes DB March 2008

Flexitest Switch Assemblies Type FT-19R and FT-19RX Supersedes DB March 2008 Flexitest Switch Assemblies Type FT-19R and FT-19RX Supersedes DB41-078 March 2008 FT-19R and FT-19RX FT-19R 3RU with Individual Clear Covers APPLICATION FEATURES The type FT-19R (standard length) and

More information

Thermal Subsidence Tool in Move

Thermal Subsidence Tool in Move Thermal Subsidence Tool in Move During the formation of rift basins, the continental crust is stretched and thinned. As it thins, the asthenosphere rises to fill the space created by the thinned continental

More information

Laboratory Chemical Hood Hibernation

Laboratory Chemical Hood Hibernation 1.0 Purpose Fume hoods that are candidates for temporary decommissioning are those that are not being used and can be shut off for at least 3 months. The purpose of this document is to define the temporary

More information

Technical Explanation for Axial Fans

Technical Explanation for Axial Fans CSM_Axial_TG_E Introduction What Is an Axial? Axial fans are used for stable cooling in many different applications and locations. If the temperature of a device increases, the lives of its internal parts

More information

Thermal Expansion Experiment

Thermal Expansion Experiment 1 of 5 5/20/2008 4:09 PM Thermal Expansion Experiment This document introduces the Thermal Expansion Experiment from the Physics laboratory at the University of Toronto. It is intended to be used before

More information

PLOW MOUNT KIT FOR POLARIS RANGER P/N ASSEMBLY / OWNERS MANUAL

PLOW MOUNT KIT FOR POLARIS RANGER P/N ASSEMBLY / OWNERS MANUAL PLOW MOUNT KIT FOR POLARIS RANGER P/N 34-3010 ASSEMBLY / OWNERS MANUAL Application PLOW PUSH FRAME NO. 34-0000 or 34-0070 Before you begin, please read these instructions and check to be sure all parts

More information

Guide Specifications Section

Guide Specifications Section Guide Specifications Section 08 87 23 SAFETY-AND-SECURITY FILMS LLumar Safety-and-Security Series Note: Click on Show/Hide button to reveal "Specifier Notes" throughout section. Delete this text when editing

More information

METHOD OF IN-SITU MEASUREMENT OF THERMAL INSULATION PERFORMANCE OF BUILDING ELEMENTS USING INFRARED CAMERA

METHOD OF IN-SITU MEASUREMENT OF THERMAL INSULATION PERFORMANCE OF BUILDING ELEMENTS USING INFRARED CAMERA METHOD OF IN-SITU MEASUREMENT OF THERMAL INSULATION PERFORMANCE OF BUILDING ELEMENTS USING INFRARED CAMERA Shinsuke Kato 1, Katsuichi Kuroki 2, and Shinji Hagihara 2 1 Institute of Industrial Science,

More information

Alternating Current (AC): Alternating Current is electric current that reverses directions at regular intervals.

Alternating Current (AC): Alternating Current is electric current that reverses directions at regular intervals. Glossary Alternating Current (AC): Alternating Current is electric current that reverses directions at regular intervals. American National Standards Institute (ANSI): American National Standards Institute

More information

AIR CONDITIONER (SPLIT TYPE) SERVICE MANUAL

AIR CONDITIONER (SPLIT TYPE) SERVICE MANUAL AIR CONDITIONER (SPLIT TYPE) SERVICE MANUAL FILE No. A10-023-1 REVISION 1 : Mar.2012 Re-edit version.( file volume down) Contents have NOT been changed. Model name: RAS-M10PKVP-E RAS-M13PKVP-E RAS-M16PKVP-E

More information

product manual H-3220A Benkelman Beam

product manual H-3220A Benkelman Beam 05.12 product manual H-3220A Benkelman Beam General The H-3220A Benkelman Beam Apparatus is a convenient and accurate device used for measuring the deflection of flexible pavements under moving wheel

More information

1. Wind turbines are designed to operate within specified design criteria. Often the operating environment extends beyond these limits and causes

1. Wind turbines are designed to operate within specified design criteria. Often the operating environment extends beyond these limits and causes 1 2 1. Wind turbines are designed to operate within specified design criteria. Often the operating environment extends beyond these limits and causes outages. How these outages are classified can be challenging

More information

PREJECTION INDUSTRIAL CORP. 百泉工業股份有限公司

PREJECTION INDUSTRIAL CORP. 百泉工業股份有限公司 : 1 OF 11 1. Features High performance (Isat) realized by metal dust core. Performance low resistance,high current rating. Low loss realized with low DCR. Frequency range : up to (1.0 MHz). 100% lead (pb)

More information

Creation and modification of a geological model Program: Stratigraphy

Creation and modification of a geological model Program: Stratigraphy Engineering manual No. 39 Updated: 11/2018 Creation and modification of a geological model Program: Stratigraphy File: Demo_manual_39.gsg Introduction The aim of this engineering manual is to explain the

More information

SK Series BOX PLOW INSTALLATION & OWNER S MANUAL TABLE OF CONTENTS

SK Series BOX PLOW INSTALLATION & OWNER S MANUAL TABLE OF CONTENTS SK Series BOX PLOW INSTALLATION & OWNER S MANUAL TABLE OF CONTENTS SAFETY... 2 INTRODUCTIONS... 5 TIPS ON PLOWING SNOW... 6 BOX PLOW ASSEMBLY PROCEDURE... 7 BOX PLOW BLADE ASSEMBLY DRAWING AND PARTS LIST...

More information

Monitoring and shaping the thermal processes of the Detritiation Pilot Plant using infrared thermography

Monitoring and shaping the thermal processes of the Detritiation Pilot Plant using infrared thermography Monitoring and shaping the thermal processes of the Detritiation Pilot Plant using infrared thermography SORIN GHERGHINESCU National R&D Institute for Cryogenics and Isotopic Technologies (ICIT) code 240050

More information

Compliance with the National requirements of EUROPEAN GROUP DIFFERENCES AND NATIONAL DIFFERENCES for EN 62471:2008.

Compliance with the National requirements of EUROPEAN GROUP DIFFERENCES AND NATIONAL DIFFERENCES for EN 62471:2008. age 2 of 14 Report o.: GLESO10020059801 Summary of testing: Tests performed (name of test and test clause): These tests fulfil the requirements of standard ISO/IEC 17025. When determining the test conclusion,

More information

*Contents in this sheet are subject to change without prior notice.

*Contents in this sheet are subject to change without prior notice. MULTILAYER CERAMIC CAPACITORS Automotive Capacitor Arrays Series (MY) Qualified to 4 x 0402, 4 x 0603 Sizes NP0 & X7R Dielectrics Halogen Free & RoHS Compliance *Contents in this sheet are subject to change

More information

University of Oklahoma Emergency Response Plan for INSERT EVENT NAME HERE.

University of Oklahoma Emergency Response Plan for INSERT EVENT NAME HERE. University of Oklahoma Emergency Response Plan for INSERT EVENT NAME HERE. Time/Date of Event: INSERT BOTH START & END TIME/DATE HERE. Location of Event: LIST ALL LOCATIONS HERE OF EVENT, INCLUDING ADDRESS.

More information

Checklist: Deposing the Driver in an Auto Accident

Checklist: Deposing the Driver in an Auto Accident Checklist: Deposing the Driver in an Auto Accident 1. PERSONAL BACKGROUND All names ever used Present and past residences for 10 years If the deponent has rented a residence, get the name and address of

More information

32 Input AC Block I/O Module

32 Input AC Block I/O Module Input AC Module Cat. No. 79-A0 Series B Installation Mount the block I/O module in a vertical (recommended) or horizontal position. Allow sufficient room around the block for cooling air to flow through

More information

6.Ebz!boe!8.Ebz!!! Gpsfdbtufst!!! G U I D E n catio Lo

6.Ebz!boe!8.Ebz!!! Gpsfdbtufst!!! G U I D E n catio Lo GUIDE Location Contents Ambient Devices TM, the Ambient logo, Ambient Information Network TM and Ambient 5-Day and 7-Day Forecasters TM are trademarks or registered trademarks of Ambient Devices, Inc.

More information

F F FAULT CURRENT Prospective. 1. Introduction. 2. Types of fault conditions

F F FAULT CURRENT Prospective. 1. Introduction. 2. Types of fault conditions FAULT CURRENT F F13-13 FAULT CURRENT - Contents 1. Introduction 2. Types of fault conditions 3 fault current must be determined 3.1 Purposes for which of prospective fault current magnitudes are used 3.2

More information

Singer. Incremental Comfort Systems. K, EK Vintage F. Last Manufactured: Replacement Parts List No Revision C 04/2012

Singer. Incremental Comfort Systems. K, EK Vintage F. Last Manufactured: Replacement Parts List No Revision C 04/2012 Replacement Parts List No. 055231000 Revision C 04/2012 Singer Incremental Comfort Systems K, EK 07-15 Vintage F Last Manufactured: 1976 To find your Daikin Applied parts distributor, call 1-800-377-2787

More information

Deployment of Infrared Inspection Technologies at Sandia National Laboratories

Deployment of Infrared Inspection Technologies at Sandia National Laboratories Deployment of Infrared Inspection Technologies at Sandia National Laboratories Experimental Mechanics/NDE & Model Validation Non Destructive Test Laboratory Sandia National Laboratories Albuquerque, New

More information

Materials: One (1) sheet of Red/Black PU laminated fabric, 410 White, 210 Den NY, Model #

Materials: One (1) sheet of Red/Black PU laminated fabric, 410 White, 210 Den NY, Model # USA Page: 1 of 8 Summary: A Red/Black PU laminated fabric (diving suit material), submitted by Diving Unlimited International Inc. was evaluated for its permeation resistance against five chemical solutions

More information

Procedures for the Installation, Adjustment, Maintenance and. Inspection of CWR as Required by 49 CFR

Procedures for the Installation, Adjustment, Maintenance and. Inspection of CWR as Required by 49 CFR Procedures for the Installation, Adjustment, Maintenance and Inspection of CWR as Required by 49 CFR 213.119 Effective October 09, 2009 Procedures for the Installation, Adjustment, Maintenance and Inspection

More information

iweathar EDGE V Installation Guide Copyright 2012 iweathar. All rights reserved.

iweathar EDGE V Installation Guide Copyright 2012 iweathar. All rights reserved. iweathar EDGE V Installation Guide Copyright 2012 iweathar. All rights reserved. Table of contents: 1 Introduction...3 2 Station Components...4 3 STATION INSTALLATION PROCEDURE...5 4 Specifications...11

More information

Data Bulletin. SEPAM 49RMS Application Note Protection for Motor Applications Class Number SEPAM 49RMS Protection for Motor Applications

Data Bulletin. SEPAM 49RMS Application Note Protection for Motor Applications Class Number SEPAM 49RMS Protection for Motor Applications Data Bulletin 3000DB08 09/008 LaVergne, TN, USA SEPAM 49RMS Application Note Protection for Motor Applications Class Number 3000 SEPAM 49RMS Protection for Motor Applications Introduction Thermal protection

More information

Professor Haig Gulvanessian CBE Civil Engineering and Eurocodes Consultant, Visiting Professor, Imperial College London

Professor Haig Gulvanessian CBE Civil Engineering and Eurocodes Consultant, Visiting Professor, Imperial College London EN 1991-1-5: Eurocode 1: Actions on structures: General Actions: Part 1.5: Thermal Actions CBE Civil Engineering and Eurocodes Consultant, Visiting Professor, Imperial College London Section 1 General

More information

Inductance at fl at point at 25 C. Tol. L1 (μh) (%) (%) min. min. max. ETQP6F1R2HFA 1.2 ±30 ETQP6F2R0HFA ETQP6F3R2HFA 4.

Inductance at fl at point at 25 C. Tol. L1 (μh) (%) (%) min. min. max. ETQP6F1R2HFA 1.2 ±30 ETQP6F2R0HFA ETQP6F3R2HFA 4. Power Choke Coil Series: PCC-F126F (N6) Thin, compact and high power Features High power (Isat 20 A /100 C) Thin profi le (5.7 mm height)/smd Low leakage fl ux RoHS compliant Recommended Applications DC-DC

More information

Instructions for the use of mobile curving machine on site. Zambelli RIB-ROOF GmbH & Co. KG Zambelli Dach + Fassadentechnik GmbH

Instructions for the use of mobile curving machine on site. Zambelli RIB-ROOF GmbH & Co. KG Zambelli Dach + Fassadentechnik GmbH Instructions for the use of mobile curving machine on site Zambelli RIB-ROOF GmbH & Co. KG Zambelli Dach + Fassadentechnik GmbH 1. Preliminary Remark The instructions for the use of the mobile curving

More information

REX Evaluation Guide. American Micro Detection Systems Inc March Lane, Suite 200 Stockton, CA 95219

REX Evaluation Guide. American Micro Detection Systems Inc March Lane, Suite 200 Stockton, CA 95219 REX Evaluation Guide American Micro Detection Systems Inc. 2800 March Lane, Suite 200 Stockton, CA 95219 I. INTRODUCTION REX (Real-time Elemental X-ray Fluorescence System) is the only instrument capable

More information

Science 7 Unit C: Heat and Temperature. Topic 6. Transferring Energy. pp WORKBOOK. Name:

Science 7 Unit C: Heat and Temperature. Topic 6. Transferring Energy. pp WORKBOOK. Name: Science 7 Unit C: Heat and Temperature Topic 6 Transferring Energy pp. 226-236 WORKBOOK Name: 0 Read pp. 226-227 object or material that can transfer energy to other objects Example: light bulb, the Sun

More information

UL 1077 DIN Rail Supplementary Protectors

UL 1077 DIN Rail Supplementary Protectors UL 0 DIN Rail Supplementary Protectors Product Overview UL 0 DIN Rail Supplementary Protectors PRODUCT OVERVIEW Product Overview Standard Features WMZS breaker terminals provide finger and back-of-hand

More information

FIELD GUIDE FOR HORUS SCOPES

FIELD GUIDE FOR HORUS SCOPES www.horusvision.com TM FIELD GUIDE FOR HORUS SCOPES Your Horus scope combines fine-quality optics, combat-proven hardware and the patented Horus reticle to deliver speed and accuracy for all shooters.

More information

INSTALLATION INSTRUCTIONS ATV Plow Blade Part Number: (50 ), (54 ), or (60 ) Application: All Terrain Vehicles

INSTALLATION INSTRUCTIONS ATV Plow Blade Part Number: (50 ), (54 ), or (60 ) Application: All Terrain Vehicles INSTALLATION INSTRUCTIONS ATV Plow Blade Part Number: 78950 (50 ), 78954 (54 ), or 78960 (60 ) Application: All Terrain Vehicles Your safety, and the safety of others, is very important. To help you make

More information

Issued August DATA SHEET. 3VT5 MCCB up to 1600 A

Issued August DATA SHEET. 3VT5 MCCB up to 1600 A ssued August 9 DATA SHEET VT5 MCCB up to 0 A Based on Siemens Catalog V 8 Standard circuit breakers Releases Technical specifications Specifications VT5 circuit breakers Switch disconnectors Type Standards

More information

Measurement method for the proficiency testing program

Measurement method for the proficiency testing program APLAC T088 Appendix Measurement method for the proficiency testing program Introductions This measurement method is prepared for use by the APLAC Proficiency Testing Program Photometric measurement of

More information