1 . Aircon Energy Saver Evaluation Report for SHUI ON DEVELOPMENTS Report for the testing of the Aircon Energy Saver when installed on DX cooling equipment at Rainbow City, Shanghai, China Test duration June 1st 7th 26 Evaluation carried out for Shui On by Comford Resource Limited 28/F Tesbury Centre 28 Queens Road East Wanchai Hong Kong SAR China Tel: (852)
2 Executive Summary - Rainbow City, Shanghai Shui On Developments have identified and evaluated a means to reduce energy costs for their product purchasers, through the fitting of a UK designed microprocessor control system to the currently, and for the future, installed Air Conditioning equipment. The following report, describes exceptional savings in electricity consumption in the region of 6%, even when mitigating this headline saving value it has major benefits for enhancing the value and quality of property offered to potential and existing customers and also enhancing the corporate reputation and profile of Shui On when compared to any competitors. The enhancement of business returns through the reduction of built property energy costs in Air Conditioning has implications for Shui On business. In addition good corporate energy practice also demonstrates good corporate citizenship, and is in keeping with the company s Corporate management goals.
3 Aircon Energy Saver Evaluation Report for Shui On AES installed at Rainbow City, Shanghai, China Objective The objective of this report is to show the benefits of installing the AES to DX cooling equipment. The report will determine the level of savings achieved with the AES controlling the compressor. Determining the evaluation The evaluation will be completed on the basis of comparison. The existing cooling unit will be monitored with and without the AES, the cooling medium cycle is logged in the two states and compared to determine a percentage reduction. Equipment list The data logging equipment comprised of:- 1. HOBO 4-Channel Indoor Logger ( H8-7-2 ) with AC Current Transformer (CTV-B ) to measure the consumed amps 2. HOBO 4-Channel Indoor Logger ( H8-7-2 ) internal Temperature Sensor to measure the conditioned area temperature (return air).. HOBO 4-Channel Indoor Logger ( H8-7-2 ) internal humidity sensor to measure the conditioned area humidity (return air). Evaluation Air Conditioning Unit The equipment on which the trial was conducted was a Panasonic A1815kw split AC unit with 5.1kw cooling. This was a new installation in a brand new th floor empty apartment. The unit is of the standard packaged split type with separate indoor and outdoor units, controlled from a return air temperature controller that is supplied as an integral part of the complete unit. Testing criteria The logging equipment was installed to data record the operation of the DX unit. It monitored the temperature and the humidity of the conditioned area /F apartment living area. This is to show that the usual conditioned room temperature and humidity are not adversely affected. The current transformer was installed on the supply cable to the outdoor unit and will show the on and off periods of the compressor.
4 To provide a robust trial comparison and remove the influence of daily variations in outside ambient temperature and also variations between morning and afternoon the trial ran for a fixed period each day from 8 to 16 with AES control being switched off or on for a 4 hour period, the switching times being at 8: and 12 hours, the AES period of operation alternated for the following trial day, as illustrated in the following table; Day AES Operating AES Not Operating Day 1 8: 12: 12:1 16: Day 2 12:1 16: 8: 12: Day 8: 12: 12:1 16: Day 4 12:1 16: 8: 12: Day 5 8: 12: 12:1 16: Day 6 12:1 16: 8: 12: Day 7 8: 12: 12:1 16: Day 8 12:1 16: 8: 12: This provides a direct comparison between the AES in control mode where it makes savings, and in bypass mode where the DX unit operates as normal. The logging equipment sampling rate was set to 9 seconds (one minute and seconds) in every device, this value being set to give a continuous period of 8 days for the test. For the purposes of the test the AES was made operable and inoperable at the designated time events by a site based person nominated by Shui On.
5 Data Results ROOM TEMPERATURE The following graphs are of the daily logged temperature D a y 1 ( A E S O p d u r i n g A M ) T e m 1 5 R e t u r n A ir T e m p e r a t u r e / 1 / 6 8 : :. 6 / 1 / 6 8 : 1 5 :. 6 / 1 / 6 8 : :. 6 / 1 / 6 8 : 4 5 :. 6 / 1 / 6 9 : :. 6 / 1 / 6 9 : 1 5 :. 6 / 1 / 6 9 : :. 6 / 1 / 6 9 : 4 5 :. 6 / 1 / 6 1 : :. 6 / 1 / 6 1 : 1 5 :. 6 / 1 / 6 1 : :. 6 / 1 / 6 1 : 4 5 :. 6 / 1 / : :. 6 / 1 / : 1 5 :. 6 / 1 / : :. 6 / 1 / : 4 5 :. 6 / 1 / : :. 6 / 1 / : 1 5 :. 6 / 1 / : :. 6 / 1 / : 4 5 :. 6 / 1 / 6 1 : :. 6 / 1 / 6 1 : 1 5 :. 6 / 1 / 6 1 : :. 6 / 1 / 6 1 : 4 5 :. 6 / 1 / : :. 6 / 1 / : 1 5 :. 6 / 1 / : :. 6 / 1 / : 4 5 :. 6 / 1 / : :. 6 / 1 / : 1 5 :. 6 / 1 / : :. 6 / 1 / : 4 5 :. T i m e D a y 2 ( A E S O p e r a t io n a l P M ) T e m p R e tu r n A ir T e m p e r a tu r e 5 6 / 2 / 6 8 : :. 6 / 2 / 6 8 :1 5 :. 6 / 2 / 6 8 : :. 6 / 2 / 6 8 :4 5 :. 6 / 2 / 6 9 : :. 6 / 2 / 6 9 :1 5 :. 6 / 2 / 6 9 : :. 6 / 2 / 6 9 :4 5 :. 6 / 2 / 6 1 : :. 6 / 2 / 6 1 :1 5 :. 6 / 2 / 6 1 : :. 6 / 2 / 6 1 :4 5 :. 6 / 2 / : :. 6 / 2 / :1 5 :. 6 / 2 / : :. 6 / 2 / :4 5 :. 6 / 2 / : :. 6 / 2 / :1 5 :. 6 / 2 / : :. 6 / 2 / :4 5 :. 6 / 2 / 6 1 : :. 6 / 2 / 6 1 :1 5 :. 6 / 2 / 6 1 : :. 6 / 2 / 6 1 :4 5 :. 6 / 2 / : :. 6 / 2 / :1 5 :. 6 / 2 / : :. 6 / 2 / :4 5 :. 6 / 2 / : :. 6 / 2 / :1 5 :. 6 / 2 / : :. 6 / 2 / :4 5 :. 6 / 2 / : :. T im e D a y ( A E S O p e r a t i o n a l A M ) T e m p R e t u r n A ir T e m p e r a t u r e 5 6 / / 6 8 : :. 6 / / 6 8 : 1 5 :. 6 / / 6 8 : :. 6 / / 6 8 : 4 5 :. 6 / / 6 9 : :. 6 / / 6 9 : 1 5 :. 6 / / 6 9 : :. 6 / / 6 9 : 4 5 :. 6 / / 6 1 : :. 6 / / 6 1 : 1 5 :. 6 / / 6 1 : :. 6 / / 6 1 : 4 5 :. 6 / / : :. 6 / / : 1 5 :. 6 / / : :. 6 / / : 4 5 :. 6 / / : :. 6 / / : 1 5 :. 6 / / : :. 6 / / : 4 5 :. 6 / / 6 1 : :. 6 / / 6 1 : 1 5 :. 6 / / 6 1 : :. 6 / / 6 1 : 4 5 :. 6 / / : :. 6 / / : 1 5 :. 6 / / : :. 6 / / : 4 5 :. 6 / / : :. 6 / / : 1 5 :. 6 / / : :. 6 / / : 4 5 :. 6 / / : :. T i m e
6 D a y 4 (A E S O p e ra tio n a l P M ) T e m p R e tu rn A ir T e m p e ra tu re 1 5 6/4/6 8::. 6/4/6 8:15:. 6/4/6 8::. 6/4/6 8:45:. 6/4/6 9::. 6/4/6 9:15:. 6/4/6 9::. 6/4/6 9:45:. 6/4/6 1::. 6/4/6 1:15:. 6/4/6 1::. 6/4/6 1:45:. 6/4/6 11::. 6/4/6 11:15:. 6/4/6 11::. 6/4/6 11:45:. 6/4/6 12::. 6/4/6 12:15:. 6/4/6 12::. 6/4/6 12:45:. 6/4/6 1::. 6/4/6 1:15:. 6/4/6 1::. 6/4/6 1:45:. 6/4/6 14::. 6/4/6 14:15:. 6/4/6 14::. 6/4/6 14:45:. 6/4/6 15::. 6/4/6 15:15:. 6/4/6 15::. 6/4/6 15:45:. 6/4/6 16::. T im e The graph below shows the temperature profile for the entire test period Entire Test Period Return Air Temperature ::. 19:15:. 6/2/6 6::. 6/2/6 17:45:. 6//6 5::. 6//6 16:15:. 6/4/6 ::. 6/4/6 14:45:. 6/5/6 2::. 6/5/6 1:15:. 6/6/6 ::. 6/6/6 11:45:. 6/6/6 2::. 6/7/6 1:15:. 6/7/6 21::. 6/8/6 8:45:. 6/8/6 2::. 6/9/6 7:15:.
7 ROOM HUMIDITY Entire Test Period Room Humidity %rh 5 4 Return Air Humidity 2 1 8::. 18:19:. 6/2/6 4:9:. 6/2/6 14:58:. 6//6 1:18:. 6//6 11:7:. 6//6 21:57:. 6/4/6 8:16:. 6/4/6 18:6:. 6/5/6 4:55:. 6/5/6 15:15:. 6/6/6 1:4:. 6/6/6 11:54:. 6/6/6 22:1:. 6/7/6 8::. 6/7/6 18:52:. 6/8/6 5:12:. 6/8/6 15:1:. 6/9/6 1:51:. 6/9/6 12:1:. Time
8 COMPRESSOR DATA Typical Graph over 4 hours with the AES not operating ::. 12:24:. 12:48:. 1:12:. 1:6:. 14::. 14:24:. 14:48:. 15:12:. 15:6:. 16::. Typical Graph with the AES operating Current (Amps) c:* ::. 8:24:. 8:48:. 9:12:. 9:6:. 1::. 1:24:. 1:48:. 11:12:. 11:6:. 12::. It can clearly seen by comparing the graphs the reduced run time of the compressor
9 Summation of Logged Data When the compressor operational logged data file is exported to an excel spreadsheet file, this excel file is evaluated and can be summated and tabulated as shown below. The table represents the running cycles for the compressor during the test cycle periods. Compressor on is taken as a current value greater than.7 amp (.6 amps being the baseline ( off ) value). The actual current when the compressor is on has a minimum value of 1.9 amps rising to a maximum of 17 amps. To generating the following table the on or off data log points from within the applicable test cycle period are totalled and documented as shown below; SWITCHING SUMMARY COMPRESSOR OPERATION DURATIONS WITH AES OPERATING WITH AES NOT OPERATING.(OFF) Units = Log points Units = Log points Day Duration ON OFF TOTAL ON OFF TOTAL 1 8am-12pm Off ratio = 66.87% 1 12pm-4pm Off ratio = 11.25% 2 8am-12pm Off ratio = 14.7% 2 12pm-4pm Off ratio = 68.75% 8am-12pm Off ratio = 7.62% 12pm-4pm Off ratio = 25.% 4 8am-12pm Off ratio = 29.7% 4 12pm-4pm Off ratio = 7.62% 5 8am-12pm Off ratio = 7.62% 5 12pm-4pm Off ratio = 29.7% 6 8am-12pm Off ratio = 26.87% 6 12pm-4pm Off ratio = 69.5% 7 8am-12pm Off ratio = 71.25% 7 12pm-4pm 1 16 Off ratio = 18.75% 8 8am-12pm Off ratio = 24.7% 8 12pm-4pm Off ratio = 71.25% Test Total Total Off % 69.92% 22.42% Total ON %.7% 77.57% NOTE: each log point represents 9 seconds Test assessment The prevailing operating conditions during the period of the test can be considered to be a typical of days for time of year and for the site, equipment, and application. The only exception to be noted for the test is the absence of any furniture or occupants and the consequent heat gains; however, the equipment is located within the normal living space of the apartment and is relatively near to the balcony doors where a heat gain relatively greater than the rest of the room may be experienced
10 The test can be considered to give a reflection of a slightly higher than normal saving for an occupied apartment. Assessment Calculations Compressor Optimisation So from the table of data the substitutions can be made within the following calculation ((original compressor run log events minus new compressor run log events) / original run events) x 1 to give the percentage change / improvement. For AM comparisons from the above table ((488-19)/488 x 1 = 59.4% improvement For PM comparisons from the above table ((55-192)/55) x 1 = 61.9% improvement For an overall comparison from the above table ((99-85)/99) x1 = 61.22% overall improvement in compressor operation. Assessment Calculations Utility Cost Saving Use of the above improvement figure can be made alongside a mean Ampere drawn value (obtained from the current data logger) to determine credible utility savings. A previously stated the current value seen on the data logger varied between 12. and 17 amps on a baseline of between.4 and.6, using these values produces a mean of (( )/2) (.6+.4)/2) = amps, if this is then applied to an average power factor of.89, ((14.15x24)x.89)/1 a working consumption of.22 kw is obtained. From the table values the A/C unit operated for 77.57% of the test time when AES was not operational so using this and the working consumption of.129kw as a benchmark means that a saving value can be directly obtained; 64 hours test duration with 77.57% A/C use (64/1) x = hours actual utility consumption, hours x.22 kw= 15.1 kwhr consumed during ordinary non-aes consumption, if this normal operational value is multiplied by the AES improvement percentage a value can be obtained that quantifies the AES saving in utility, (15.1 /1) x = 91.8 giving a saving of 91.8 kwhr for a comparable 64 hour period with AES operational. From the data it can be seen that the AES saves 18 1mins of compressor run time each operational hour.
11 Conclusion 1. The daily temperature graphs show that the conditioned room temperature is not adversely affected for comfort level whilst obtaining the imposed savings from the AES. 2. The weekly humidity graph shows that the conditioned room humidity is not adversely affected for comfort level whilst obtaining the imposed savings from the AES.. It can be stated that conditioned room comfort control is not compromised by the AES energy saving. 4. The large gain in savings as a headline number is pleasing but should in reality be mitigated slightly because of the vacant test room. 5. Installation of the AES has obvious running cost benefits to the future apartment occupants. The AES is proved to make excellent savings.
Occupant Behavior Related to Space Cooling in a High Rise Residential Building Located in a Tropical Region N.F. Mat Hanip 1, S.A. Zaki 1,*, A. Hagish
Occupant Behavior Related to Space Cooling in a High Rise Residential Building Located in a Tropical Region N.F. Mat Hanip 1, S.A. Zaki 1,*, A. Hagishima 2, J. Tanimoto 2, and M.S.M. Ali 1 1 Malaysia-Japan
More informationWater terminal control solutions
Water Terminal Control Solutions Water terminal control solutions Carrier offers a wide range of fan coil units designed to meet the needs of different systems and applications: from cabinet units in the
More informationInverter Multi-Split System
Inverter MultiSplit System Specifications Inverter MultiSplit Fan coil unit Fan Coil Unit Model RAVMS3KCVT RAVMS3KCVT RASMS3KCVT RAVM22S3KCVT RAVM24S3KCVT Standard Cooling Capacity (btu/hr) 9,212 12,624
More informationInstitut national des sciences appliquées de Strasbourg GENIE CLIMATIQUE ET ENERGETIQUE APPENDICES
Institut national des sciences appliquées de Strasbourg GENIE CLIMATIQUE ET ENERGETIQUE APPENDICES DEVELOPMENT OF A TOOL, BASED ON THE THERMAL DYNAMIC SIMULATION SOFTWARE TRNSYS, WHICH RUNS PARAMETRIC
More informationLED Lumen Maintenance and Life Test System (LEDLM-80PL) Brochure. Global Office of Lisun Electronics Inc.
LED Lumen Maintenance and Life Test System (LEDLM-80PL) Brochure Global Office of Lisun Electronics Inc. Lisun Group (Hong Kong) Limited Add: Room C, 15/F Hua Chiao Commercial Center, 678 Nathan Road,
More informationSolar Control in Traditional Architecture, Potentials for Passive Design in Hot and Arid Climate
Solar Control in Traditional Architecture, Potentials for Passive Design in Hot and Arid Climate Wael A. Yousef Mousa, MA.ᵃ Werner Lang, Prof. Dr.-Ing.ᵇ ᵃ ᵇInstitute of Energy Efficient and Sustainable
More informationCase Study Las Vegas, Nevada By: Susan Farkas Chika Nakazawa Simona Tamutyte Zhi-ya Wu AAE/AAL 330 Design with Climate
Case Study Las Vegas, Nevada By: Susan Farkas Chika Nakazawa Simona Tamutyte Zhi-ya Wu AAE/AAL 330 Design with Climate Professor Alfredo Fernandez-Gonzalez School of Architecture University of Nevada,
More informationWednesday 2 November 2016 Morning
Oxford Cambridge and RSA H Wednesday 2 November 2016 Morning GCSE APPLICATIONS OF MATHEMATICS A381/02 Applications of Mathematics 1 (Higher Tier) *7232534172* Candidates answer on the Question Paper. OCR
More informationLightcloud Application
Controlling Your Lightcloud System Lightcloud Application Lightcloud Application Navigating the Application Devices Device Settings Organize Control Energy Scenes Schedules Demand Response Power Up State
More informationThe Fundamentals of Moisture Calibration
The Fundamentals of Moisture The following guide will provide you with a basic knowledge of humidity calibration, help you to understand your requirements and select an appropriate solution. 1 Why Humidity
More informationWebsite Phone Mobile OVERVIEW Davis Vantage Pro2 Weather Station
OVERVIEW If you're looking for a superior weather station, the Davis Vantage Pro2 Weather Station is as good as they come! Vantage Pro2 offers the professional weather observer and the serious weather
More informationPage No. (and line no. if applicable):
COALITION/IEC (DAYMARK LOAD) - 1 COALITION/IEC (DAYMARK LOAD) 1 Tab and Daymark Load Forecast Page No. Page 3 Appendix: Review (and line no. if applicable): Topic: Price elasticity Sub Topic: Issue: Accuracy
More informationHadrons Desktop U.S. Atomic Clock & Weather Station
Hadrons Desktop U.S. Atomic Clock & Weather Station SN004 Instructions Read and save these instructions. Dear Sharper Image Customer, Thank you for your purchase of a Sharper Image product. We appreciate
More informationPost Show Report The 33 rd China Wedding Expo
Post Show Report The 33 rd China Wedding Expo 01 Show profile 02 Exhibits Scope 03 Exhibitor Analysis 04 Visitor Analysis 05 Media Publicity 06 Concurrent Activities 07 VIP List 08 Moments Show Profile
More informationTHE ENERGY 68,SAVING TDVI. exible Combine Modular 24, 26, 28, 30, 32, 34, 36, 38, 40, 42, 44 HP 60, 62, 64, 66 HP
I N V E RT E R ion Range exible Combine Modular TDV I TDV I TDV I INVERTER INVERTER INVERTER 14, 16, 18, 20, 22 HP TDV I 24, 26, 28, 30, 32, 34, 36, 38, 40, 42, 44 HP INVERTER INVERTER INVERTER TDV I INVERTER
More informationRECORD AND ANALYSE THE PRESSURE-ENTHALPY DIAGRAM FOR A COMPRESSION HEAT PUMP
Thermodynamics Heat cycles Heat Pump RECORD AND ANALYSE THE PRESSURE-ENTHALPY DIAGRAM FOR A COMPRESSION HEAT PUMP Demonstrate how an electric compression heat pump works Quantitatively investigate of the
More informationAMMS-100 Atmospheric Metal Monitoring System
AMMS-100 Atmospheric Metal Monitoring System USEPA Method IO-. compliant Measure 28 toxic metals simultaneously Magnitude of detection limit 0.01-0.1ng/m Associate measurements with time of day or meteorological
More informationTHE UTP SUITE YOUR ALL-IN-ONE SOLUTION FOR BUILDING MODERN TEST SYSTEM SOFTWARE
THE UTP SUITE YOUR ALL-IN-ONE SOLUTION FOR BUILDING MODERN TEST SYSTEM SOFTWARE UTP Suite THE UTP SUITE DEVELOPING A STANDARD Increasing customer requirements, shorter product cycles and higher time to
More informationPREDICTING OVERHEATING RISK IN HOMES
PREDICTING OVERHEATING RISK IN HOMES Susie Diamond Inkling Anastasia Mylona CIBSE Simulation for Health and Wellbeing 27th June 2016 - CIBSE About Inkling Building Physics Consultancy Susie Diamond Claire
More informationSensor fault detection in building energy management systems
Sensor fault detection in building energy management systems Dionissia Kolokotsa Anastasios Pouliezos and George Stavrakakis Technological Educational Institute of Crete Technical University of Crete 7333
More informationPRODUCT SPECIFICATIONS
FEATURES AND BENEFITS* Up to 1,000,000 duty cycles or 10 year DC life 48V DC working voltage Active cell balancing Temperature output Overvoltage outputs available High power density TYPICAL APPLICATIONS
More informationInter-comparison of Raingauges on Rainfall Amount and Intensity Measurements in a Tropical Environment
Inter-comparison of Raingauges on Rainfall Amount and Intensity Measurements in a Tropical Environment CHAN Ying-wa, Yu Choi-loi and TAM Kwong-hung Hong Kong Observatory 134A Nathan Road, Tsim Sha Tsui,
More informationHumidity, and Dew Point Data Logger with LCD ORDERING INFORMATION Standard Data Logger (Data Logger, Software on CD, Battery) Replacement Battery EL-USB-2-LCD BAT 3V6 1/2AA FEATURES 0 to 100 measurement
More informationUnderstanding uncertainties associated with the 5128A RHapid-Cal Humidity Generator
Understanding uncertainties associated with the 5128A RHapid-Cal Humidity Generator Technical Note The Fluke Calibration 5128A RHapid-Cal Humidity Generator provides a portable, stable test environment
More informationPRODUCT SPECIFICATIONS
FEATURES AND BENEFITS* Up to 14 year DC life 56V DC working voltage Resistive cell balancing Overvoltage outputs High power density 4U, half-rack package UL registered TYPICAL APPLICATIONS UPS systems
More informationA Simulation Tool for Radiative Heat Exchangers
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 A Simulation Tool for Radiative Heat Exchangers Yunho Hwang yhhwang@umd.edu
More informationAcceleration/Velocity/Displacement VIBRATION METER
Acceleration/Velocity/Displacement VIBRATION METER Model : VB-8220 Your purchase of this VIBRATION METER marks a step forward for you into the field of precision measurement. Although this METER is a complex
More informationAIR CONDITIONER (SPLIT TYPE) SERVICE MANUAL
AIR CONDITIONER (SPLIT TYPE) SERVICE MANUAL FILE No. A10-023-1 REVISION 1 : Mar.2012 Re-edit version.( file volume down) Contents have NOT been changed. Model name: RAS-M10PKVP-E RAS-M13PKVP-E RAS-M16PKVP-E
More informationSF6 Gas Standard Capacitors
TYL series SF6 Gas Standard Capacitors levels up to 95% without condensation. We use special stainless steel to permit the prefect temperature and voltage coefficient stability. The capacitor is provided
More information(Refer Slide Time: 00:32)
Nonlinear Dynamical Systems Prof. Madhu. N. Belur and Prof. Harish. K. Pillai Department of Electrical Engineering Indian Institute of Technology, Bombay Lecture - 12 Scilab simulation of Lotka Volterra
More informationLa Crosse Technology Ws 9160u It Digital Thermometer With Indoor Outdoor Temperature Manual
La Crosse Technology Ws 9160u It Digital Thermometer With Indoor Outdoor Temperature Manual La Crosse Technology TX29U- IT 915 MHz Wireless Temperature Sensor CDN$ 17.47 Oregon Scientific EMR201 Indoor/Outdoor
More informationTest Report. Report No.: EED35I R1. Address : 701 Millennium Boulevard Greenville, SC : P , P , P , P
Test of One Model of LED Track Head Report No.: EED35I000703-2R Prepared for : Progress Lighting Address : 70 Millennium Boulevard Greenville, SC 29607 Model Name : P9082 Model No. : P9082-28, P9082-3,
More informationTest Report. Report No.: EED35I Address : 701 Millennium Boulevard Greenville, SC : P , P , P , P
Test of One Model of LED Track Head Report No.: EED35I000702-2 Prepared for : Progress Lighting Address : 70 Millennium Boulevard Greenville, SC 29607 Model Name : P9062 Model No. : P9062-28, P9062-3,
More informationReport on System-Level Estimation of Demand Response Program Impact
Report on System-Level Estimation of Demand Response Program Impact System & Resource Planning Department New York Independent System Operator April 2012 1 2 Introduction This report provides the details
More informationUnderstanding the uncertainties associated with using the 5128A RHapid Cal portable humidity generator
Understanding the uncertainties associated with using the 5128A RHapid Cal portable humidity generator Introduction Humidity generators are mechanical devices that provide stable temperature and humidity
More informationThermal Comfort; Operative Temperature in the Sun
Thermal Comfort; Operative Temperature in the Sun Ida Bryn (Ph.d) Marit Smidsrød (MSc) Erichsen&Horgen AS, Postboks 4464 Nydalen, 0403 Oslo, E-mail: ihb@erichsen-horgen.no, telephone: 47 22026333, telefax:
More informationNATHAN HALE HIGH SCHOOL PARKING AND TRAFFIC ANALYSIS. Table of Contents
Parking and Traffic Analysis Seattle, WA Prepared for: URS Corporation 1501 4th Avenue, Suite 1400 Seattle, WA 98101-1616 Prepared by: Mirai Transportation Planning & Engineering 11410 NE 122nd Way, Suite
More informationAttachment E: CADP Design Shadow Analysis
Attachment E: CADP Design Shadow Analysis June 6, 2016 TO: Don Lewis San Francisco Planning Department 1650 Mission Street, Suite 400 San Francisco, CA 94103 SUBJECT: 2060 Folsom Street 17 th & Folsom
More informationAcceleration, Velocity, Separate probe VIBRATION METER Model : VB-8202
Acceleration, Velocity, Separate probe VIBRATION METER Model : VB-8202 Your purchase of this VIBRATION METER marks a step forward for you into the field of precision measurement. Although this METER is
More informationModular contactors for installation into distribution
Modular contactors for installation into distribution boards Modular contactors for installation into distribution boards Modular contactor for installation into distribution board Description Modular
More informationKey Energy Variable (KEV) Console Monitoring. Martine McDonald Process Engineer ExxonMobil Texas Technology Showcase December 7, 2006
Key Energy Variable (KEV) Console Monitoring Martine McDonald Process Engineer ExxonMobil Texas Technology Showcase December 7, 2006 Overview What is a KEV? KEV Development Process Baytown Chemical Plant
More informationIntuitive air velocity and IAQ.
Intuitive air velocity and IAQ. The new combines versatility and maximum convenience. 1 The new air velocity & IAQ measuring instrument: versatility in a compact format. Welcome to a new era: the new combines
More informationPNEUMATIC ENTHALPY COMPARATOR
PNEUATIC ENTHALPY COPARATOR APS ANALYSTS OF PNEUATIC SYSTES LIITED analystsofpneumatic@bellnet.ca http://www.apscontrols.ca PHONE: (9) 6-2333 FAX: (9) 6-2444 CONTENTS PAGE - Preface ------------------------------------------
More informationPeterborough Distribution Inc Ashburnham Drive, PO Box 4125, Station Main Peterborough ON K9J 6Z5
Peterborough Distribution Inc. 1867 Ashburnham Drive, PO Box 4125, Station Main Peterborough ON K9J 6Z5 November 15, 2017 Ontario Energy Board PO Box 2319 27 th Floor, 2300 Yonge St Toronto ON M4P 1E4
More informationN-channel enhancement mode Field-Effect Transistor (FET) in a small SOT23 (TO-236AB) Surface-Mounted Device (SMD) plastic package using
Rev. 24 March 29 Product data sheet. Product profile. General description N-channel enhancement mode Field-Effect Transistor (FET) in a small SOT23 (TO-236AB) Surface-Mounted Device (SMD) plastic package
More informationHigh heat resistance halogen-free multi-layer circuit board materials
Data Sheet High heat resistance halogen-free multi-layer circuit board materials Laminate R-1566(S) Prepreg R-1551(S) Mar. 2019 No.19031342 Specification / Laminate R-1566(S) No.; 19031342-1 Property Units
More informationBetter Weather Data Equals Better Results: The Proof is in EE and DR!
Better Weather Data Equals Better Results: The Proof is in EE and DR! www.weatherbughome.com Today s Speakers: Amena Ali SVP and General Manager WeatherBug Home Michael Siemann, PhD Senior Research Scientist
More informationEnergy Use in Homes. A series of reports on domestic energy use in England. Energy Efficiency
Energy Use in Homes A series of reports on domestic energy use in England Energy Efficiency Energy Use in Homes A series of reports on domestic energy use in England This is one of a series of three reports
More informationUnipolar & Bipolar Metal Ceramic Tubes
Unipolar & Bipolar Metal Ceramic Tubes Industrial X-Ray Overview 1/1 - V1, specification subject to change without notice Technology with Passion COMET AG Industrial X-Ray Herrengasse 1, CH-317 Flamatt
More informationA powerful site for all chemists CHOICE CRC Handbook of Chemistry and Physics
Chemical Databases Online A powerful site for all chemists CHOICE CRC Handbook of Chemistry and Physics Combined Chemical Dictionary Dictionary of Natural Products Dictionary of Organic Dictionary of Drugs
More informationPATREC PERSPECTIVES Sensing Technology Innovations for Tracking Congestion
PATREC PERSPECTIVES Sensing Technology Innovations for Tracking Congestion Drivers have increasingly been using inexpensive mapping applications imbedded into mobile devices (like Google Maps, MapFactor,
More informationPipex px SUSTAINABLE SYSTEMS
Pipex px SUSTAINABLE SYSTEMS Pipex px Carbon Abatement Systems Met Office Headquarters Building, Exeter, Devon, UK The Project: Met Office, a Trading Fund within the Ministry of Defence, is the UK s national
More informationEarth s Magnetic Field Measurements for the LCLS Undulators
LCLS-TN-05-04 Earth s Magnetic Field Measurements for the LCLS Undulators Kirsten Hacker, Zachary Wolf SLAC February 16, 2005 Abstract Measurements of the earth s magnetic field at several locations at
More informationABOUT UNCERTAINTIES IN SIMULATION MODELS FOR BUILDING SYSTEMS CONTROL
ABOUT UNCERTAINTIES IN SIMULATION MODELS FOR BUILDING SYSTEMS CONTROL Kristina Orehounig, Matthias Schuss, Claus Pröglhöf, and Ardeshir Mahdavi Department of Building Physics and Building Ecology Vienna
More informationSample Alignment (2D detector) Part
Sample Alignment (2D detector) Part Contents Contents 1 How to set Part conditions...1 1.1 Setting conditions... 1 1.2 Customizing scan conditions and slit conditions... 6 2 Sample alignment sequence...13
More informationSample Alignment Part
Sample Alignment Part Contents Contents 1. How to set Part conditions...1 1.1 Setting conditions... 1 1.2 Customizing scan conditions and slit conditions... 6 2. Sample alignment sequence...13 2.1 Direct
More informationMinimum (-31) every 10 s -35 (-31)
Humidity, and Dew Point Data Logger with LCD ORDERING INFORMATION Standard Data Logger (Data Logger, Software on CD, Battery) Replacement Battery EL-USB-2-LCD BAT 3V6 1/2AA FEATURES 0 to 100 measurement
More informationOptimization Methods in Management Science
Problem Set Rules: Optimization Methods in Management Science MIT 15.053, Spring 2013 Problem Set 1 (Second Group of Students) Students with first letter of surnames G Z Due: February 12, 2013 1. Each
More informationEnergy saving in electromechanical equipment with power coefficient correction. Dimitris Al. Katsaprakakis Aeolian Land S.A.
Energy saving in electromechanical equipment with power coefficient correction Dimitris Al. Katsaprakakis Aeolian Land S.A. www.aiolikigi.gr Introduction Electricity production companies (utilities) provide
More informationSafety Precautions WARNING If critical situations that could lead to user s death or serious injury is assumed by mishandling of the product.
Safety Precautions Observe the following notices to ensure personal safety or to prevent accidents. To ensure that you use this product correctly, read this User s Manual thoroughly before use. Make sure
More informationInstruction Manual. Solar Weather Centre With Wireless Weather Vane. Product Code: WS5056C. Solar Powered Outdoor Weather Data Collector
Solar Weather Centre With Wireless Weather Vane Solar Powered Outdoor Weather Data Collector Indoor Receiver Instruction Manual Product Code: WS5056C TECHNICAL DETAILS Thank you for purchasing the Holman
More information4HP13 PRODUCT SPECIFICATIONS 13 SEER SPLIT SYSTEM HEAT PUMP WARRANTY
4HP13 PRODUCT SPECIFICATIONS 13 S SPLIT SYSTEM HEAT PUMP FORM NO. 4HP13-100 (07/2014) R410A Refrigerant High-quality condenser coil with copper tubing and enhanced louvered fin for maximum heat transfer
More informationMeteorological Instruments for Solar Energy
Meteorological Instruments for Solar Energy gillinstruments.com Gill Instruments has been designing and manufacturing professional use compact weather stations and ultrasonic wind speed and direction sensors
More informationTaking the garbage out of energy modeling through calibration
Taking the garbage out of energy modeling through calibration Presented to the Madison Chapter of ASHRAE February 8, 2016 Presented by Benjamin Skelton P.E. BEMP President, Cyclone Energy Group Acknowledgments
More informationToday s A/C systems include:
* www.sgvenergywise.org Replac ing your A/C system REQUIRES a permit from your c ity - it s important. WHY? Because A/C (air conditioning) is a SYSTEM, not just one piece of equipment. The thermostat,
More informationGeneral Photo-Electro-Thermal Theory for LED Systems & the LED Revolution for General Lighting
General Photo-Electro-Thermal Theory for LED Systems & the LED Revolution for General Lighting Ron Hui Center for Power Electronics City University of Hong Kong 1 Content Introduction Lighting Systems
More informationMATHEMATICAL METHODS (CAS) PILOT STUDY
Victorian CertiÞcate of Education 2005 SUPERVISOR TO ATTACH PROCESSING LABEL HERE STUDENT NUMBER Letter Figures Words MATHEMATICAL METHODS (CAS) PILOT STUDY Written examination 2 (Analysis task) Monday
More informationThermal behavior and Energetic Dispersals of the Human Body under Various Indoor Air Temperatures at 50% Relative Humidity
Thermal behavior and Energetic Dispersals of the Human Body under Various Indoor Air Temperatures at 50% Relative Humidity Hakan CALISKAN Usak University, Department of Mechanical Engineering, Usak, Turkey
More informationHigh Speed, Low Loss Multi-layer Materials
Data Sheet High Speed, Low Loss Multi-layer Materials Laminate R-5775 Prepreg R-5670 Jun. 2017 No.17061531 Specification / Laminate R-5775 No.; 17061531-1 Property Units Test Method Condition Value Glass
More informationOCCUPANT BEHAVIOR OF WINDOW OPENING AND CLOSING IN OFFICE BUILDINGS: DATA MINING APPROACHES. Simona D Oca. December 8 th, Washington DC
OCCUPANT BEHAVIOR OF WINDOW OPENING AND CLOSING IN OFFICE BUILDINGS: DATA MINING APPROACHES December 8 th, Washington DC T H E C R E D I B I L I T Y G A P O F B U I L D I N G E N E R G Y C O N S U M P
More informationValidation of IDA Indoor Climate and Energy
Technical report: Validation of IDA Indoor Climate and Energy 4.0 build 4 with respect to ANSI/ASHRAE Standard 140-2004 April 2010 Equa Simulation AB Råsundavägen 100 169 57 Solna Sweden Contents 1 Introduction
More informationflexotherm 230V Heat pump technical specification
flexotherm 230V Heat pump technical specification The flexotherm 230V heat pump is available in 5, 8 and 11kW models Connects to two different sources - ground or water One of the quietest heat pump ranges
More informationLaboratory Worksheet Experiment NE04 - RC Circuit Department of Physics The University of Hong Kong. Name: Student ID: Date:
PHYS1050 / PHYS1250 Laboratory Worksheet Experiment Department of Physics The University of Hong Kong Ref. (Staff Use) Name: Student ID: Date: Draw a schematic diagram of the charging RC circuit with ammeter
More informationAudit Report. Group photo taken during the audit day July 4, Pha Din Station. General Conclusion:
Audit Report Station name: Pha Din, Vietnam 21 34 16 N 103 31 0 E Date: July 4, 2016 Auditor: Prof. Dr. Alfred Wiedensohler (WMO-GAW-WCCAP, TROPOS, Germany) Responsible people: Mr. Günther Wehrle (PSI,
More informationΔ q = ( ψ L) HDH (1) here, Δq is the additional heat transfer caused by the thermal bridge, Ψ and L are the linear thermal transmittance and length of
Balconies in Shanghai, thermal bridges or sun shadings? Ye Yang * School of Planning Building Environment, Berlin Institute of Technology, Berlin, Germany ABSTRACT In the Cfa climate area, such as the
More informationSOFTWARE USER MANUAL. Weather Capture Advance WS1640 WM9280
SOFTWARE USER MANUAL Weather Capture Advance WS1640 WM9280 1 TABLE OF CONTENTS 1. Introduction 3 1.1 System requirements 1.2 Connection of the weather station 1.3 Installation of the Weather Capture Advance
More information4 Way Reversing Valve
STANDARD 4 Way Reversing Valve SHF series four-way reversing valves are applicable for heat pump systems such as central, unitary and room air conditioners to realize switching between cooling mode and
More informationDYNAMIC DAYLIGHT AND SOLAR CONTROL IN TROPICAL CLIMATE
American Journal of Applied Sciences 11 (10): 1766-1772, 2014 ISSN: 1546-9239 2014 Y.W. Lim, This open access article is distributed under a Creative Commons Attribution (CC-BY) 3.0 license doi:10.3844/ajassp.2014.1766.1772
More informationData Sheet. High Speed, Low Loss Multi-layer Materials. Laminate R-5785 Prepreg R-5680
Data Sheet High Speed, Low Loss Multi-layer Materials Laminate R-5785 Prepreg R-5680 Oct. 2018 No.18103128 Specification / Laminate R-5785 & R-5785(N) THERMAL ELECTRICAL PHYSICAL Property Units Test Method
More informationIES LM TEST REPORT For EIKO GLOBAL, LLC
NVLAP LAB CODE:201045-0 Shenzhen Anbotek Compliance Laboratory Limited IES LM-79-08 TEST REPORT For EIKO GLOBAL, LLC Report Number: Product Type: Date of Receipt: Date of Test: Date of Report: Product
More informationInternational Conference on Mechanics, Materials and Structural Engineering (ICMMSE 2016)
International Conference on Mechanics, Materials and Structural Engineering (ICMMSE 2016) hermal Model Parameter Estimation for HVAC Facility using Recursive Least Square Method Dae Ki Kim1, a, Kyu Chul
More informationWeatherHawk Weather Station Protocol
WeatherHawk Weather Station Protocol Purpose To log atmosphere data using a WeatherHawk TM weather station Overview A weather station is setup to measure and record atmospheric measurements at 15 minute
More informationEAS 535 Laboratory Exercise Weather Station Setup and Verification
EAS 535 Laboratory Exercise Weather Station Setup and Verification Lab Objectives: In this lab exercise, you are going to examine and describe the error characteristics of several instruments, all purportedly
More informationTN TN Thermocouple Calibration (required only to familiarise with the process of creating polynomials within Microsoft Excel)
Substituting Polynomials in Place of Lookup Tables There are times when it may be necessary to track sequences of points. Some examples of this include flow profiles in rivers, liquid volume in non-uniform
More informationScienceDirect. Experimental study of influence of movements on airflow under stratum ventilation
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 7 (15 ) 7 11 th International Building Physics Conference, IBPC 15 Experimental study of influence of movements on airflow under
More informationInvestigations on effect of the orientation on thermal comfort in terraced housing in Malaysia
Investigations on effect of the orientation on thermal comfort in terraced housing in Malaysia Dr Mohamed Ali Abdul Hussain Al-Obaidi 1 and Prof. Peter Woods 2 1 Senior lecturer, Center for Equatorial
More informationPascal ET is an handheld multifunction calibrator for the measurement and simulation of the following parameters: - pressure
DATASHEET Pascal ET Pascal ET is an handheld multifunction calibrator for the measurement and simulation of the following parameters: - pressure - electrical signals (ma, mv, V, ) - temperature (TC and
More informationDewpoint Meter Data Sheet / Instructions
Paint Test Equipment Dewpoint Meter Data Sheet / Instructions Dewpoint Meter Information ISO 8502-4: Preparation of steel substrates before application of paints and related products. Tests for the assessment
More informationb. Why do you suppose the percentage of women doctors has been increasing over the past 40 years?
Special Topics: U3. L2. Inv 1 Name: Homework: Math XL Unit 3: HW: 9/14-9/18 Week 2(Due Friday, 9/18, by 11:59 pm) Lesson Target: Being able to formulate linear equations and inequalities and solutions
More informationOptimization Methods in Management Science
Problem Set Rules: Optimization Methods in Management Science MIT 15.053, Spring 2013 Problem Set 1 (First Group of Students) Students with first letter of surnames A F Due: February 12, 2013 1. Each student
More informationThis is the author s version of a work that was submitted/accepted for publication in the following source:
This is the author s version of a work that was submitted/accepted for publication in the following source: Omrani, Sara, Garcia-Hansen, Veronica, Drogemuller, Robin, & Capra, Bianca (2016) Predicting
More informationCPTC Thermistor: PP Series
Features. RoHS compliant 2. Lead type 3. Voltage rating: 270Vac~500Vac 4. Resistance range:0~000ω 5. Stable over a long time 6. Operating temperature range: -20 ~ +85 C (V=Vmax) -40 ~ +25 C (V=0) 7. Agency
More informationInter-comparison of Raingauges in a Sub-tropical Environment
Inter-comparison of Raingauges in a Sub-tropical Environment TAM Kwong-hung, CHAN Ying-wa, CHAN Pak-wai and SIN Kau-chuen Hong Kong Observatory 134A Nathan Road, Tsim Sha Tsui, Kowloon, Hong Kong, China
More informationIn data sheets and application notes which still contain NXP or Philips Semiconductors references, use the references to Nexperia, as shown below.
Important notice Dear Customer, On 7 February 2017 the former NXP Standard Product business became a new company with the tradename Nexperia. Nexperia is an industry leading supplier of Discrete, Logic
More informationOptimization of Power Consumption for Centrifugation Process Based on Attenuation Measurements
Journal of Physics: Conference Series Optimization of Power Consumption for Centrifugation Process Based on Attenuation Measurements To cite this article: M S Salim et al 2013 J. Phys.: Conf. Ser. 423
More informationAalborg Universitet. Publication date: Document Version Publisher's PDF, also known as Version of record
Aalborg Universitet Experimental Investigation of the Influence of Different Flooring Emissivity on Night- Time Cooling using Displacement Ventilation Dreau, Jerome Le; Karlsen, Line Røseth; Litewnicki,
More informationR E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G 2 December 2008 / 1
R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G 2 December 2008 / 1 Headquarters R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G 2 December 2008 / 2 Executive Committee Jørgen
More informationMODE button MAX/MIN button CHANNEL button / C/ F / RCC button SNOOZE / LIGHT button Battery compartment A/C in-jack 3. 4.
KL4912 Desktop weather station Instruction Manual Introduction This weather station comes with backlight, indoor and outdoor temperature & humidity display, and alarm clock with calendar. Fig. 1 Front
More informationDr. OligoTM DNA / RNA / OLIGO SYNTHESIZERS
Dr. OligoTM DNA / RNA / OLIGO SYNTHESIZERS High Throughput Oligo Synthesis Synthesize Cleave Deprotect Desalt Elute Dr. Oligo TM The Dr. Oligo TM High Throughput Oligo Synthesizer is available in four
More informationResidual Chlorine Monitor
Data Sheet SS/AW00 Issue Residual Chlorine Monitor AW00 Total and Free Residual Chlorine Measurement add potassium iodide to reagent to convert free chlorine measurement to total chlorine Reagentless Operation
More information