1 January 19, 2017 Ms. Alix Zapolski Zapolski Real Estate, LLC. 501 Washington Street Durham, NC Re: Limited Indoor Air Quality Assessment Asbestos & Microbial 137 E. Franklin Street, Chapel Hill, NC UNC Institute for the Environment EI Project No. IHMO Dear Ms. Zapolski: The EI Group, Inc. (EI) is pleased to present this report for the Limited Indoor Air Quality (IAQ) assessment performed at the UNC Institute for the Environment located on the sixth floor at 137 E. Franklin St., in Chapel Hill, North Carolina. EI was requested to determine if any airborne fungal spores or asbestos fibers were present in occupied spaces on the sixth floor. A visual inspection, and collection of 12 asbestos PCM samples and 12 air-o-cell samples were utilized to perform this assessment Site Observations Mr. Will Dunlop, visited the project site on Friday, January 13, 2017 to investigate the conditions at the facility. EI inspected the space which consisted multiple offices and common areas. No visual evidence of fungal growth was noted. Additionally, no visibly disturbed areas of asbestos were noted. Mold Sampling Air Sampling Methods and Results Sampling for airborne fungal spores was conducted in the above listed rooms inside the building to determine airborne fungal counts, the genera present, and the relative level of each genus. Air sampling was conducted utilizing ten Air-O-Cell spore-trap sampling media. All air samples were collected utilizing a high volume sampling pump, calibrated with the manufacturers supplied rotometer. The high volume sampling pump was calibrated to 15 liters per minute (LPM) with a sampling time of 5 minutes, giving a total sample volume of liters. Following collection, each sample was given a unique tracking number, placed under chain of custody, and hand delivered to EMSL Analytical Laboratory, located in Morrisville, NC for analysis by direct optical microscopy. EMSL is accredited in environmental microbiology by the American Industrial Hygiene Association. Two samples were also collected from the exterior of the building to establish baseline fungal concentrations of the exterior air. The baseline samples were collected after the collection of the indoor samples. Environmental, Health and Safety Solutions.
2 No quantitative limits exist for exposure to mold spores. Evaluation of the results obtained is performed by comparing spore levels indoors to those found outdoors at the time of sampling. Spores contained in samples collected inside should be equal to or less than, and similar in distribution, to those in outdoor air. Please reference Table 1 (below) for a summary of all sampling locations and findings. Airborne fungal spore concentrations identified in each of the sampled areas was similar in type and lower in concentration as compared to the outdoor air control sample location. A summary of Fungal Spore Sampling Results is shown at Table 1 below and sampling data analytical results is enclosed at the Laboratory Analysis Report appendix at the end of this report. Sample Location Table 1: Summary of Fungal Spore Sampling Results Sample No. Total Spore Count (cts/m 3 ) 6601A G A Elevator Lobby Exterior Rear Exterior Front The EI Group, Inc
3 Conclusions and Recommendations Results of the indoor air quality survey indicate that no excessive concentrations of airborne fungal spores are present in the occupied areas. No visual indications of suspect fungal growth were identified. The sampling and laboratory protocols used in this investigation are in accordance with standard industrial hygiene protocols for indoor air quality assessments and sampling protocol for environmental fungi. Asbestos Sampling Air Sampling Methods and Results Ten air samples were collected on 25 mm mixed cellulose ester (MCE) filters. Additionally, a field blank and a lab blank were submitted for QA purposes. The samples were analyzed by Phase Contrast Microscopy (PCM) using the National Institute Occupational Health (NIOSH) method 7400, B counting rules. Please note that PCM analysis does not distinguish between asbestos fibers and other fibers that may have been collected during the sampling process. PCM results are a count of all fibers found. The Environmental Protection Agency (EPA) requires clearance air samples to have a fiber concentration below 0.01 fiber/cubic centimeter. The analysis results are listed below in Table 2. Sample Location Table 2: Summary of PCM Sampling Results Liters of Air Total Fiber Count (fibers/cm 3 ) Elevator Lobby I B A 1250 Field Blank N/A FB Lab Blank N/A LB The EI Group, Inc
4 Conclusions and Recommendations The results of the samples collected during the abatement were below 0.01 f/cc, which indicates that there is not an elevated concentration of asbestos fibers (as of the day of sampling). Qualifications and Limitations This report summarizes our evaluation of the conditions observed throughout the sixth floor of 137 E. Franklin St.., in Chapel Hill, North Carolina. Our findings are based upon our observations and sampling results obtained at the facility at the time of our visit. The report, results, and subsequent recommendations reported herein are also limited to the information available at the time it was prepared and investigated. Conditions may have been in effect prior to the sampling events that have changed over time and which cannot be predicated within the scope of this limited investigation. Any conditions discovered which deviate from the data contained in this report should be presented to us for our evaluation Alix, we sincerely appreciate the opportunity to provide our services to you and Zapolski Real Estate. Please feel free to contact me at (919) , ext. 257 if you have any questions. Yours Truly, The EI Group, Inc. Willard R. Dunlop III Industrial Hygiene Technician Christopher B. Murray, CIH, CSP Senior Vice President, Operations Enclosures The EI Group, Inc
5 OrderID: Page 1 Of 2
6 OrderID: Page 2 Of 2
7 EMSL Analytical, Inc Gateway Centre Blvd., Suite 600 Morrisville, NC 260 Tel/Fax: (919) / (919) / raleighlab@emsl.com EMSL Order: Customer ID: ENVI67 Customer PO: Project ID: Attn: Will Dunlop Phone: (919) The EI Group, Inc. Fax: (919) Gateway Centre Blvd, Suite 200 Collected: 01/13/2017 Morrisville, NC 260 Received: 01/13/2017 Project: IHMO Analyzed: 01/14/2017 Test Report: Air-O-Cell( ) Analysis of Fungal Spores & Particulates by Optical Microscopy (Methods EMSL 05-TP-003, ASTM D7391) Lab Sample Number: Client Sample ID: Volume (L): Sample Location A G Spore Types Raw Count Count/m³ % of Total Raw Count Count/m³ % of Total Raw Count Count/m³ % of Total Alternaria Ascospores Aspergillus/Penicillium Basidiospores Bipolaris Chaetomium Cladosporium Curvularia Epicoccum Fusarium Ganoderma Myxomycetes Pithomyces Rust Scopulariopsis Stachybotrys Torula Ulocladium Unidentifiable Spores Zygomycetes Spegazzinia Total Fungi Hyphal Fragment Insect Fragment Pollen Analyt. Sensitivity 600x Analyt. Sensitivity 300x - 13* * * - Skin Fragments (1-4) Fibrous Particulate (1-4) Background (1-5) Bipolaris++ = Bipolaris/Drechslera/Exserohilum Myxomycetes++ = Myxomycetes/Periconia/Smut No discernable field blank was submitted with this group of samples. Alan Goldstein, Ph.D., Laboratory Manager or other approved signatory High levels of background particulate can obscure spores and other particulates leading to underestimation. Background levels of 5 indicate an overloading of background particulates, prohibiting accurate detection and quantification. Present = Spores detected on overloaded samples. Results are not blank corrected unless otherwise noted. The detection limit is equal to one fungal spore, structure, pollen, fiber particle or insect fragment. "*" Denotes particles found at 300X. "-" Denotes not detected. Due to method stopping rules, raw counts in excess of 100 are extrapolated based on the percentage analyzed. EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted. Samples analyzed by EMSL Analytical, Inc. Morrisville, NC AIHA-LAP, LLC--EMLAP Lab Report amended: 01/16/ :44:58 Replaces initial report from: 01/14/ :32:21 Reason Code: Data Entry-Change to Location For information on the fungi listed in this report, please visit the Resources section at MIC_M001_0002_ Printed: 01/16/ :45 AM Page 1 of 4
8 EMSL Analytical, Inc Gateway Centre Blvd., Suite 600 Morrisville, NC 260 Tel/Fax: (919) / (919) / raleighlab@emsl.com EMSL Order: Customer ID: ENVI67 Customer PO: Project ID: Attn: Will Dunlop Phone: (919) The EI Group, Inc. Fax: (919) Gateway Centre Blvd, Suite 200 Collected: 01/13/2017 Morrisville, NC 260 Received: 01/13/2017 Project: IHMO Analyzed: 01/14/2017 Test Report: Air-O-Cell( ) Analysis of Fungal Spores & Particulates by Optical Microscopy (Methods EMSL 05-TP-003, ASTM D7391) Lab Sample Number: Client Sample ID: Volume (L): Sample Location Elevator Spore Types Raw Count Count/m³ % of Total Raw Count Count/m³ % of Total Raw Count Count/m³ % of Total Alternaria Ascospores Aspergillus/Penicillium Basidiospores Bipolaris Chaetomium Cladosporium Curvularia Epicoccum Fusarium Ganoderma Myxomycetes Pithomyces Rust Scopulariopsis Stachybotrys Torula Ulocladium Unidentifiable Spores Zygomycetes Spegazzinia Total Fungi Hyphal Fragment Insect Fragment Pollen Analyt. Sensitivity 600x Analyt. Sensitivity 300x - 13* * * - Skin Fragments (1-4) Fibrous Particulate (1-4) Background (1-5) Bipolaris++ = Bipolaris/Drechslera/Exserohilum Myxomycetes++ = Myxomycetes/Periconia/Smut No discernable field blank was submitted with this group of samples. Alan Goldstein, Ph.D., Laboratory Manager or other approved signatory High levels of background particulate can obscure spores and other particulates leading to underestimation. Background levels of 5 indicate an overloading of background particulates, prohibiting accurate detection and quantification. Present = Spores detected on overloaded samples. Results are not blank corrected unless otherwise noted. The detection limit is equal to one fungal spore, structure, pollen, fiber particle or insect fragment. "*" Denotes particles found at 300X. "-" Denotes not detected. Due to method stopping rules, raw counts in excess of 100 are extrapolated based on the percentage analyzed. EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted. Samples analyzed by EMSL Analytical, Inc. Morrisville, NC AIHA-LAP, LLC--EMLAP Lab Report amended: 01/16/ :44:58 Replaces initial report from: 01/14/ :32:21 Reason Code: Data Entry-Change to Location For information on the fungi listed in this report, please visit the Resources section at MIC_M001_0002_ Printed: 01/16/ :45 AM Page 2 of 4
9 EMSL Analytical, Inc Gateway Centre Blvd., Suite 600 Morrisville, NC 260 Tel/Fax: (919) / (919) / raleighlab@emsl.com EMSL Order: Customer ID: ENVI67 Customer PO: Project ID: Attn: Will Dunlop Phone: (919) The EI Group, Inc. Fax: (919) Gateway Centre Blvd, Suite 200 Collected: 01/13/2017 Morrisville, NC 260 Received: 01/13/2017 Project: IHMO Analyzed: 01/14/2017 Test Report: Air-O-Cell( ) Analysis of Fungal Spores & Particulates by Optical Microscopy (Methods EMSL 05-TP-003, ASTM D7391) Lab Sample Number: Client Sample ID: Volume (L): Sample Location A Spore Types Raw Count Count/m³ % of Total Raw Count Count/m³ % of Total Raw Count Count/m³ % of Total Alternaria Ascospores Aspergillus/Penicillium Basidiospores Bipolaris Chaetomium Cladosporium * 40* 33.3 Curvularia Epicoccum Fusarium Ganoderma Myxomycetes * 10* Pithomyces Rust Scopulariopsis Stachybotrys Torula Ulocladium Unidentifiable Spores Zygomycetes Spegazzinia Total Fungi Hyphal Fragment Insect Fragment Pollen Analyt. Sensitivity 600x Analyt. Sensitivity 300x - 13* * * - Skin Fragments (1-4) Fibrous Particulate (1-4) Background (1-5) Bipolaris++ = Bipolaris/Drechslera/Exserohilum Myxomycetes++ = Myxomycetes/Periconia/Smut No discernable field blank was submitted with this group of samples. Alan Goldstein, Ph.D., Laboratory Manager or other approved signatory High levels of background particulate can obscure spores and other particulates leading to underestimation. Background levels of 5 indicate an overloading of background particulates, prohibiting accurate detection and quantification. Present = Spores detected on overloaded samples. Results are not blank corrected unless otherwise noted. The detection limit is equal to one fungal spore, structure, pollen, fiber particle or insect fragment. "*" Denotes particles found at 300X. "-" Denotes not detected. Due to method stopping rules, raw counts in excess of 100 are extrapolated based on the percentage analyzed. EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted. Samples analyzed by EMSL Analytical, Inc. Morrisville, NC AIHA-LAP, LLC--EMLAP Lab Report amended: 01/16/ :44:58 Replaces initial report from: 01/14/ :32:21 Reason Code: Data Entry-Change to Location For information on the fungi listed in this report, please visit the Resources section at MIC_M001_0002_ Printed: 01/16/ :45 AM Page 3 of 4
10 EMSL Analytical, Inc Gateway Centre Blvd., Suite 600 Morrisville, NC 260 Tel/Fax: (919) / (919) / raleighlab@emsl.com EMSL Order: Customer ID: ENVI67 Customer PO: Project ID: Attn: Will Dunlop Phone: (919) The EI Group, Inc. Fax: (919) Gateway Centre Blvd, Suite 200 Collected: 01/13/2017 Morrisville, NC 260 Received: 01/13/2017 Project: IHMO Analyzed: 01/14/2017 Test Report: Air-O-Cell( ) Analysis of Fungal Spores & Particulates by Optical Microscopy (Methods EMSL 05-TP-003, ASTM D7391) Lab Sample Number: Client Sample ID: Volume (L): Sample Location Ext. 1 Franklin St Ext. 2 Alley Behind Bldg. Spore Types Raw Count Count/m³ % of Total Raw Count Count/m³ % of Total Raw Count Count/m³ % of Total Alternaria Ascospores Aspergillus/Penicillium Basidiospores Bipolaris Chaetomium Cladosporium * 10* Curvularia Epicoccum Fusarium Ganoderma Myxomycetes Pithomyces Rust Scopulariopsis Stachybotrys Torula Ulocladium Unidentifiable Spores Zygomycetes Spegazzinia * 10* 0.4 Total Fungi Hyphal Fragment Insect Fragment Pollen Analyt. Sensitivity 600x Analyt. Sensitivity 300x - 13* * * - Skin Fragments (1-4) Fibrous Particulate (1-4) Background (1-5) Bipolaris++ = Bipolaris/Drechslera/Exserohilum Myxomycetes++ = Myxomycetes/Periconia/Smut No discernable field blank was submitted with this group of samples. Alan Goldstein, Ph.D., Laboratory Manager or other approved signatory High levels of background particulate can obscure spores and other particulates leading to underestimation. Background levels of 5 indicate an overloading of background particulates, prohibiting accurate detection and quantification. Present = Spores detected on overloaded samples. Results are not blank corrected unless otherwise noted. The detection limit is equal to one fungal spore, structure, pollen, fiber particle or insect fragment. "*" Denotes particles found at 300X. "-" Denotes not detected. Due to method stopping rules, raw counts in excess of 100 are extrapolated based on the percentage analyzed. EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted. Samples analyzed by EMSL Analytical, Inc. Morrisville, NC AIHA-LAP, LLC--EMLAP Lab Report amended: 01/16/ :44:58 Replaces initial report from: 01/14/ :32:21 Reason Code: Data Entry-Change to Location For information on the fungi listed in this report, please visit the Resources section at MIC_M001_0002_ Printed: 01/16/ :45 AM Page 4 of 4
11 OrderID: Page 1 Of 2
12 OrderID: Page 2 Of 2
13 EMSL Analytical, Inc Gateway Centre Blvd., Suite 600 Morrisville, NC 260 Tel/Fax: (919) / (919) / raleighlab@emsl.com EMSL Order: Customer ID: Customer PO: Project ID: ENVI67 Attention: Will Dunlop Phone: (919) The EI Group, Inc. Fax: (919) Gateway Centre Blvd, Suite 200 Received Date: 01/13/2017 4:30 PM Morrisville, NC 260 Analysis Date: 01/16/2017 Collected Date: 01/13/2017 Project: IHMO Test Report: Fiber Count by Phase Contrast Microscopy (PCM), NIOSH 7400 Method, Revision 3, Issue 2, 8/15/94 Sample Location Sample Date Volume (liters) Fibers Fields LOD (fib/cc) Fibers/ mm² Fibers/ cc Notes 6118 Clearance Sample 1 1/13/ < < Clearance Sample 2 1/13/ < < Clearance Sample 3 1/13/ < < Clearance Sample 4 1/13/ < < Elevator Clearance Sample 5 1/13/ Clearance Sample 6 1/13/ < < Clearance Sample 7 1/13/ < < IU Clearance Sample 8 1/13/ < < B Clearance Sample 9 1/13/ < < A Clearance Sample 10 1/13/ < < FB Field Blank 1/13/2017 < <7.01 Field Blank LB Lab Blank 1/13/2017 < <7.01 Lab Blank The results reported have been blank corrected as applicable. Limit of detection is 7 fibers/mm². Intra-laboratory Sr values: 5-20 fibers = 0.21, fibers = 0.12, fibers = Inter-laboratory Sr values (Average of EMSL round robin data) = EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. EMSL is not responsible for data reported in fibers/cc, which is dependent on volume collected by non-laboratory personnel. Results have been blank corrected as applicable. Samples received in good condition unless otherwise noted. Samples analyzed by EMSL Analytical, Inc. Morrisville, NC AIHA-LAP, LLC--EMLAP Accredited # Initial report from: 01/16/ :49:14 ASB_PCM_NoSig_0003 Printed: 1/16/2017 2:49 PM Page 1 of 2
14 EMSL Analytical, Inc Gateway Centre Blvd., Suite 600 Morrisville, NC 260 Tel/Fax: (919) / (919) / raleighlab@emsl.com EMSL Order: Customer ID: Customer PO: Project ID: ENVI67 Attention: Will Dunlop Phone: (919) The EI Group, Inc. Fax: (919) Gateway Centre Blvd, Suite 200 Received Date: 01/13/2017 4:30 PM Morrisville, NC 260 Analysis Date: 01/16/2017 Collected Date: 01/13/2017 Project: IHMO Test Report: Fiber Count by Phase Contrast Microscopy (PCM), NIOSH 7400 Method, Revision 3, Issue 2, 8/15/94 Sample Location Sample Date Volume (liters) Fibers Fields LOD (fib/cc) Fibers/ mm² Fibers/ cc Notes Analyst(s): Joshua Moorman PCM (12) Billy Barnes, Asbestos Lab Manager or Other Approved Signatory Limit of detection is 7 fibers/mm². Intra-laboratory Sr values: 5-20 fibers = 0.21, fibers = 0.12, fibers = Inter-laboratory Sr values (Average of EMSL round robin data) = EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. EMSL is not responsible for data reported in fibers/cc, which is dependent on volume collected by non-laboratory personnel. Results have been blank corrected as applicable. Samples received in good condition unless otherwise noted. Samples analyzed by EMSL Analytical, Inc. Morrisville, NC AIHA-LAP, LLC--EMLAP Accredited # Initial report from: 01/16/ :49:14 ASB_PCM_NoSig_0003 Printed: 1/16/2017 2:49 PM Page 2 of 2
A visual inspection, and collection of 10 asbestos PCM samples and 12 air-o-cell samples were utilized to perform this assessment
December 9, 2016 Ms. Alix Zapolski Zapolski Real Estate, LLC. 501 Washington Street Durham, NC 27701 Re: Limited Indoor Air Quality Assessment Asbestos & Microbial 137 E. Franklin Street, Chapel Hill,
More informationIn room E 28 slightly elevated concentrations of Stachybotrys were found.
July nd, 0 Mr. Marty Foutch Facilities Director Bixby Public Schools 09 N. Armstrong Bixby, OK 700 RE: CC: Bixby High School - % IAQ Liberty OHM File Number -7 Jarred Doubrava Operations Support Manager/District
More informationLaboratory ID. Laboratory Name. Address. Phone. Lab Manager/Supervisor. QA Officer. Analyst(s) Auditor. Date(s) of Audit
Method(s): Laboratory ID Laboratory Name Address Phone Lab Manager/Supervisor QA Officer Analyst(s) Auditor Date(s) of Audit NEW JERSEY DEPARTMENT OF ENVIRONMENTAL PROTECTION OFFICE OF QUALITY ASSURANCE
More information730 SE Maynard Road Cary, NC
January 31, 2019 P.O. Box 9053 Missoula, MT 59807 CLIENT PROJECT: U of M - McGill Hall, Rm 001A, 001, 015, 19-024 LAB CODE: T190368 Dear Customer: Enclosed are asbestos analysis results for TEM dust wipe
More informationAloha High School Drop Ceiling Replacment - Summer # of 2x2 (ft.) Load -SF. Area Sq. Ft. # of 1x1 (ft.) # of 1x2 (ft.) HVAC Net Ducts?
Aloha High School Drop Ceiling Replacment - Summer 07 Room # Area Sq. Ft. # of x (ft.) Additional Grid New x 4 (ft.) Existing x 4 (ft.) nonrecessed ceilinglight Load -SF # of x (ft.) # of x (ft.) HVAC
More informationMODULE 2B INDUSTRIAL HYGIENE LABORATORY ACCREDITATION PROGRAM (IHLAP) ADDITIONAL REQUIREMENTS
2B.1 SCOPE MODULE 2B INDUSTRIAL HYGIENE LABORATORY ACCREDITATION PROGRAM (IHLAP) ADDITIONAL REQUIREMENTS The AIHA - Laboratory Accreditation Programs (AIHA-LAP), LLC s Industrial Hygiene Laboratory Accreditation
More information- Laboratory Report - Full Particle Identification Project: CI0333/HP107
Conclusions: - Laboratory Report - Full Particle Identification Project: CI0333/HP107 The data obtained during the analysis of the sample indicates the following. The sample is predominantly composed of
More informationAIR-O-CELL CSI. Bioaerosol Sampling Cassette For the collection of viable and non-viable airborne particles. Laboratory & User Manual
AIR-O-CELL CSI Bioaerosol Sampling Cassette For the collection of viable and non-viable airborne particles Laboratory & User Manual Air-O-Cell CSI Sampling Cassette The Air-O-Cell Collector for SEM Identification
More informationREPORT. Limited Asbestos Survey Plaza Latina Stage Two Norcross, Georgia Gwinnett County. Project Number: Report Date: January 18, 2017
REPORT Limited Asbestos Survey Plaza Latina Stage Two Norcross, Georgia Gwinnett County Project Number: 06.69.0 Report Date: January 8, 07 UNITED CONSULTING 65 Holcomb Bridge Road Norcross, GA 3007 (770)
More informationStandard Operating Procedure PCM SOP 1-1. Microscope Calibration, Preparation and Analysis of Air Samples by Phase Contrast Microscopy (PCM)
Standard Operating Procedure PCM SOP 1-1 Microscope Calibration, Preparation and Analysis of Air Samples by Phase Contrast Microscopy (PCM) Scope and Purpose: The scope and purpose of this standard operating
More informationAIR MONITORING REPORT
AIR MONITORING REPORT 1500 Hallway Frost Lake Magnet 1505 East Hoyt Avenue St. Paul, MN 55103 December 21, 2005 Nova Client No.: STPAU006/Project No: H05-1309 AIR MONITORING REPORT 1500 Hallway Frost Lake
More informationSeptember 2, Mr. Abdi Zarrabi NYC School Construction Authority Thomson Avenue Long Island City, NY 11101
36-15A 23 rd Street Long Island City, NY 11106 Tel: 718.383.2626 Fax: 718.383.7780 www.precision-enviro.com September 2, 2015 Mr. Abdi Zarrabi NYC School Construction Authority 30-30 Thomson Avenue Long
More informationIndustrial Hygiene Report
Industrial Hygiene Report Control of Hydrochloric Acid Vapors in a Lab Setting September, 24 2012 Sentry Air Systems 6999 W. Little York Rd, Suite P1 Houston, TX 77040 BACKGROUND: Hydrochloric acid, an
More informationANALYTICAL REPORT. Sampling Parameter: Area 200 cm² Result. (ug/100cm²) RL (ug/sample) Sampling Parameter: Area 300 cm². Result
Report Date: August 07, 2015 Steve Hudson Terracon Consulting 15080 "A" Circle Omaha, NE 68144 Phone: 402-670-3842 E-mail: steve.hudson@terracon.com Analytical s Sample ID: TB-1 Lab ID: 1521876001 Sampling
More informationPROJECT ID: W09341 LABORATORY REPORT NUMBER: L
Serialized: 04/25/2016 09:49am QC21 JERRY HAAG LEBANON BOROUGH ELEMENTARY 6 MAPLE STREET LEBANON,NJ 08833 Regarding: LEBANON BOROUGH ELEMENTARY 6 MAPLE STREET LEBANON, NJ 08833 PROJECT ID: W09341 LABORATORY
More informationIntertek Environmental VOC Emissions
4700 Broadmoor SE, Suite 200 Kentwood, MI 49512 Jesse.ondersma@intertek.com Telephone: 616-656-7401 Facsimile: 616-656-2022 www.intertek.com ELIZABETH FATIMA DO NASCIMENTO AIME P.O.: N.A. Page 1 of 8 Intertek
More informationThe case for culturable air sampling for opportunistic fungi during healthcare construction
The case for culturable air sampling for opportunistic fungi during healthcare construction AIHCE 2007, Philadelphia, PA June 2007 Laurence Lee, CIH Pacific Industrial Hygiene LLC pacific.ih@comcast.net
More informationLincoln County Board of Commissioner s Agenda Item Cover Sheet
Lincoln County Board of Commissioner s Agenda Item Cover Sheet Board Meeting Date: Agenda Item Type: Consent Agenda: Public Hearing: Regular Agenda: Presentation Time (est): Submitting Person: Phone Number/Ext:
More informationCity of Panama City March 14, Harrison Avenue File No.: P Panama City, FL 32401
P a n a m a C i t y O f f i c e 7500 McElvey Road, Suite A Panama City Beach, FL 32408 Tel: (850) 769-4773 Fax: (850) 872-9967 www.soearth.com Geotechnical, Environmental & Construction Materials Testing
More informationEnclosed is a copy of your laboratory report for test samples received by our laboratory on Thursday, February 25, 2010.
Environmental Conservation Laboratories, Inc. 10775 Central Port Drive Orlando FL, 32824 407.826.5314 407.850.6945 Phone: FAX: www.encolabs.com Friday, March 5, 2010 Jones Edmunds & Associates (JO005)
More informationNellis Air Force Base Asbestos and Lead Based Paint Inspection Report
Nellis Air Force Base Asbestos and Lead Based Paint Inspection Report Building Number: 434 Inspection Date: 2/12/2014 Nellis Work Order: 23211 Macrotec Job Number: 14534 Introduction: Macrotec Consulting,
More informationSCOPE OF ACCREDITATION
Standards Council of Canada 600-55 Metcalfe Street Ottawa, ON K1P 6L5 Canada Conseil canadien des normes 55, rue Metcalfe, bureau 600 Ottawa, ON K1P 6L5 Canada SCOPE OF ACCREDITATION Transcat Canada, Inc.
More informationMemorandum. Air Sampling
Memorandum TO: David Yelton, City of Beverly Hills DATE: December 8, 2015 CC: Heidi Rous, PCR Services FROM: Everest Yan and Audrey Vinant Tang, PCR Services RE: BEVERLY HILLS ARSENIC MONITORING MEMO This
More informationLarge-Scale Sediment Retention Device Testing (ASTM D 7351) SedCatch Sediment Basket Inlet Filter Exposed to 6% Sediment Load
Large-Scale Sediment Retention Device Testing (ASTM D 7351) of SedCatch Sediment Basket Inlet Filter Exposed to 6% Sediment Load February 2010 Submitted to: SedCatch Environmental Products 8380 Point O
More informationASBESTOS SURVEY RESULTS 1975 JEFFERSONVILLE ROAD MACON, GEORGIA GEC JOB # PREPARED FOR
ASBESTOS SURVEY RESULTS 1975 JEFFERSONVILLE ROAD MACON, GEORGIA GEC JOB # 160190.240 PREPARED FOR MR. DAVID FORTSON, DIRECTOR MACON BIBB ENGINEERING DEPARTMENT 780 THIRD STREET MACON, GEORGIA 31201 PREPARED
More informationAttached is the report detailing the Adams Spanish Immersion Magnet asbestos abatement project.
CORPORATE HEADQUARTERS Minneapolis, MN OFFICE LOCATIONS Chicago, IL Dallas, TX Denver, CO Duluth, MN Indianapolis, IN Los Angeles, CA Miami, FL Milwaukee, WI New York, NY Salt Lake City, UT San Antonio,
More informationSTANDARD OPERATING PROCEDURES
STANDARD OPERATING PROCEDURES for Spectrophotometric Measurement Chl a, Chl b, and Bulk Carotenoids using Methanol Solvent Prepared by EcoAnalysts, Inc. 1420 South Blaine Street, Suite 14 Moscow, ID 83843
More informationAnalytical Method. Evaluation of mycological structures by microscopic examination ANALYTICAL METHOD 360. (Revision No 2)
Analytical Method Evaluation of mycological structures by microscopic examination (Revision No 2) ANALYTICAL METHOD 360 Applicability This method is used for the semi-quantitative evaluation of mycological
More informationJanuary 18, Dear Mr. Menghini:
January 18, 2018 Michael J. Menghini, District Mining Manager Department of Environmental Protection Pottsville District Mining Office 5 West Laurel Boulevard Pottsville, PA 17901-2454 SUBJECT: Operation
More informationLarge-Scale Sediment Retention Device Testing (ASTM D 7351) SedCatch Sediment Basket Inlet Filter Exposed to 1.5% Sediment Load
Large-Scale Sediment Retention Device Testing (ASTM D 7351) of SedCatch Sediment Basket Inlet Filter Exposed to 1.5% Sediment Load February 2010 Submitted to: SedCatch Environmental Products 8380 Point
More informationSample Date: March 30, 2018 Date Received: March 31, 2018 Date of Report: April 9, 2018 (877) Fax: (877)
U.S. Micro-Solutions, Inc. * 075 South Main Street, Suite 04 * Greensburg, PA 560 Phone: (877) 876-4276 Fax: (724) 853-4049 AIHA-LAP, LLC EMLAP #03009 075 South Main Street, Suite 04 Greensburg, PA 560
More informationHERRON Enterprises USA, Inc.
Phone (303) 763 9639 HERRON Enterprises USA, Inc. Fax (303) 763 9686 E-Mail Lennie.Herron@comcast.net Hazardous Materials*Mold*Asbestos*Lead Paint www.herron-enterprises.com Environmental Services*Industrial
More informationIntroduction to IH Analytical Chemistry
Introduction to IH Analytical Chemistry Sampling and Analysis Manning, Eide, Van Etten (Apr 2013) Foreword Thank you for purchasing the Introduction to IH Analytical Chemistry self-study workbook. Course
More informationEMSL Analytical, Inc.
EMSL Analytical, Inc. Phone: (856) 303-2500 Fax: (856) 858-4571 Email: 2/21/2017 The following analytical report covers the analysis performed on samples submitted to EMSL Analytical, Inc. on 2/17/2017.
More informationSchedule. Draft Section of Lab Report Monday 6pm (Jan 27) Summary of Paper 2 Monday 2pm (Feb 3)
Schedule Assignment Due Date Draft Section of Lab Report Monday 6pm (Jan 27) Quiz for Lab 2 Peer Review of Draft Complete Lab Report 1 Tuesday 9:30am Wednesday 6pm Friday 6pm Summary of Paper 2 Monday
More informationALLOWAY METHOD OUTLINE
ALLOWAY METHOD OUTLINE Standard Laboratory Method SM4500-Cl -G Parameter Residual Chlorine & Free Chlorine Method DPD Colorimetric Test Kit Date Issued Originator: Section Supervisor: QA Manager Date:
More informationKSA Environmental Laboratory Inc.
September 07, 2007 KSA Environmental Laboratory Inc. Amerigrow Recycling Attn: Orlando D. Pagan 10320 West Atlantic Ave Delray Beach, FL 33446 RE: Mulch Metals KSA Workorder: Q006081 Dear Orlando D. Pagan,
More informationA Brief Overview of Radiation and Analytical Water Testing for Radiological Contaminants.
A Brief Overview of Radiation and Analytical Water Testing for Radiological Contaminants. James Henitz Radioanalytical Services NJ Water Monitoring Council: January 24, 2018 Overview of Presentation What
More informationApplication for Radioactive Material Use
Application for Radioactive Material Use Instructions All Authorized Users (AU) must be approved and authorized by the Radiation Safety Committee prior to using Radioactive Materials. Additionally, requests
More informationON SITE SYSTEMS Chemical Safety Assistant
ON SITE SYSTEMS Chemical Safety Assistant CS ASSISTANT WEB USERS MANUAL On Site Systems 23 N. Gore Ave. Suite 200 St. Louis, MO 63119 Phone 314-963-9934 Fax 314-963-9281 Table of Contents INTRODUCTION
More informationAppendix I-1: Archaeological Records Search
Appendix I-1: Archaeological Records Search South Central Coastal Information Center California State University, Fullerton Department of Anthropology MH-426 800 North State College Boulevard Fullerton,
More informationHAZARDOUS MATERIALS SURVEY
HAZARDOUS MATERIALS SURVEY 1057-1059 Dayton Avenue Saint Paul, Minnesota Prepared For: Ramsey County Tax Forfeited Lands May 1, 2014 Hazardous Materials Survey Peer #24048.00 1057-1059 Dayton Avenue, Saint
More informationAnalytical Report
Analytical Report 386228 for Natural Soap Formulas Project Manager: Wanda Baligad Formula 206 Natural Soap Formulas 20-AUG-10 3231 NW 7th Avenue, Boca Raton, FL 33431 Ph:(561) 447-7373 Fax:(561) 447-6136
More informationOne Stop DIY Shop. PO Box 104 New Germany, MN Carbonyl Assay. Samples Received 09/09/2014. Analysis Report ( )
One Stop DIY Shop PO Box 104 New Germany, MN 55367 Carbonyl Assay Samples Received 09/09/2014 Analysis Report (0914-72) GC/MS Analysis Pentanedione (aka Acetyl propionyl) Diacetyl Enthalpy Analytical,
More informationMOLD, POLLEN AND OTHER CHEMICAL COMPOUNDS IN EFFLUENT AIR OF RESIDENTIAL HOMES
MOLD, POLLEN AND OTHER CHEMICAL COMPOUNDS IN EFFLUENT AIR OF RESIDENTIAL HOMES Brent E. Wholeben, Ph.D. Director, Office of Research, Evaluation, and Policy Studies Northern Illinois University ABSTRACT
More informationAmerican Environmental Testing Laboratory Inc.
American Environmental Testing Laboratory Inc. 2834 & 2908 North Naomi Street Burbank, CA 91504 DOHS NO: 1541, LACSD NO: 10181 Tel: (888) 288-AETL (818) 845-8200 Fax: (818) 845-8840 www.aetlab.com Ordered
More informationQuarterly Groundwater Monitoring Report Third Quarter 2018
Quarterly Groundwater Monitoring Report Third Quarter 2018 Piper s Wine & Spirit Barn 4127 Hanover Pike Manchester, Maryland 21102 MDE Case No. 18-0496CL Facility I.D. No. 17166 AEC Project No. 14-059
More information2655 Park Center Dr., Suite A Simi Valley, CA 93065 T: +1 805 526 7161 F: +1 805 526 7270 www.alsglobal.com LABORATORY REPORT January 7, 2016 Glenn La Fevers Southern California Gas Company 12801 Tampa
More informationAPPLICATION FOR AUTHORIZATION
INSTRUCTIONS: This form is intended to be a template for completion by the applicant, followed by subsequent review by the Radiation Safety Officer, and then the Radiation Safety Committee. Please fill
More informationMicrobac Laboratories, Inc. - Baltimore
Tidewater Meneka Rodrigo 6625 Selnick Drive, Suite A Elkridge, MD 21075 Analytical Testing Parameters - Baltimore 18K1357 Project Name: Twin Ridge Elementary Project / PO Number: N/A Received: 11/29/2018
More informationSFH612A/ SFH655A. Pb Pb-free. Optocoupler, Photodarlington Output. Vishay Semiconductors
Optocoupler, Photodarlington Output Features High Isolation Test Voltage 5300 V RMS Standard Plastic DIP-4 Package Lead-free component Component in accordance to RoHS 2002/95/EC and WEEE 2002/96/EC A 1
More informationANALYTICAL REPORT. Attn: Richard Boelter
ANALYTICAL REPORT TestAmerica Laboratories, Inc. 0 Community Drive Suite South Burlington, VT 00 Tel: (0)0-0 TestAmerica Job ID: 00-- Client For: ARCADIS U.S. Inc Massena Facility, Route East Chevrolet
More informationETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6986/ARL-SA6987 Revision 0 ARL
ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT -SA6986/-SA6987 Revision 0 Subject: Sound Absorption Test Date: 01 February 2017 Contents: on Sound Absorption Data, One-third Octave
More informationRADIOIODINE COLLECTION FILTER EFFICIENCY TESTING PROGRAM at F&J SPECIALTY PRODUCTS, INC. by FRANK M. GAVILA. Atlantic City, New Jersey June 2002
F&J SPECIALTY PRODUCTS, INC. PO Box 2888 Ocala, Florida 34478-2888 Tel: (352) 680-1177 (352) 680-1178 Fax: (352) 680-1454 Email: fandj@fjspecialty.com Internet: www.fjspecialty.com The Nucleus of Quality
More informationHAZARD COMMUNICATION PROGRAM
Revision 1.0 JANUARY 2, 2018 HAZARD COMMUNICATION PROGRAM UNC CHARLOTTE 9201 UNIVERSITY CITY BLVD., CHARLOTTE, NC 28223 January 2018 Hazard Communication Program 1 Table of Contents Purpose... 3 Background...
More informationCOMPLIANCE EMISSIONS TEST California Dept. of Public Health Standard Method Version 1.1 and FloorScore Flooring Evaluation
COMPLIANCE EMISSIONS TEST California Dept. of Public Health Standard Method Version 1.1 and FloorScore Flooring Evaluation SAMPLE DESCRIPTION & TESTING PARAMETERS Tesoro Woods submitted exemplars of their
More informationANALYTICAL REPORT. Attn: Richard Boelter
ANALYTICAL REPORT TestAmerica Laboratories, Inc. 0 Community Drive Suite South Burlington, VT 00 Tel: (0)0-0 TestAmerica Job ID: 00-0- TestAmerica Sample Delivery Group: 00-0- Client For: ARCADIS U.S.
More informationANALYTICAL REPORT. Attn: Richard Boelter
ANALYTICAL REPORT TestAmerica Laboratories, Inc. 0 Community Drive Suite South Burlington, VT 00 Tel: (0)0-0 TestAmerica Job ID: 00-- TestAmerica Sample Delivery Group: 00- Client For: ARCADIS U.S. Inc
More informationETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6956 Revision 1 ARL
ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT -SA6956 Revision 1 Subject: Sound Absorption Test Date: 04 January 2017 Contents: on Sound Absorption Data, One-third Octave bands Sound
More informationETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6712/ARL-SA6713 Revision 0 ARL
ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT -SA6712/-SA6713 Revision 0 Subject: Sound Absorption Test Date: 17 May 2016 Contents: on Sound Absorption Data, One-third Octave bands
More informationISO INTERNATIONAL STANDARD
INTERNATIONAL STANDARD ISO 11201 Second edition 2010-05-15 Acoustics Noise emitted by machinery and equipment Determination of emission sound pressure levels at a work station and at other specified positions
More informationETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6266/ARL-SA6274 Revision 0 ARL
ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT -SA6266/-SA6274 Revision 0 Subject: Sound Absorption Test Date: 17 February 2015 Contents: on Sound Absorption Data, One-third Octave
More informationANALYTICAL REPORT. Attn: Richard Boelter
ANALYTICAL REPORT TestAmerica Laboratories, Inc. 0 Community Drive Suite South Burlington, VT 00 Tel: (0)0- TestAmerica Job ID: 00-- TestAmerica Sample Delivery Group: 00- Client For: ARCADIS U.S. Inc
More informationANALYTICAL REPORT. Attn: Richard Boelter
ANALYTICAL REPORT TestAmerica Laboratories, Inc. 0 Community Drive Suite South Burlington, VT 00 Tel: (0)0-0 TestAmerica Job ID: 00-0- TestAmerica Sample Delivery Group: 00-0 Client For: ARCADIS U.S. Inc
More informationSUMMARY REPORT OF AIR MONITORING FOR LEED CERTIFICATION PHASE 2 SWANSFIELD ELEMENTARY SCHOOL 5610 CEDAR LANE COLUMBIA, MD PREPARED FOR:
SUMMARY REPORT OF AIR MONITORING FOR LEED CERTIFICATION PHASE 2 SWANSFIELD ELEMENTARY SCHOOL 5610 CEDAR LANE COLUMBIA, MD 21044 PREPARED FOR: HOWARD COUNTY PUBLIC SCHOOL SYSTEM 10910 ROUTE 108 ELLICOTT
More informationQuality System Document. INDUSTRIAL HYGIENCE LABORATORY ACCREDITATON PROGRAM (IHLAP) Fields of Testing Category 2 (FoT)/Matrix
Title: Scope/PT Table Page 1 of 8 Chromatography Core Spectrometry Core INDUSTRIAL HYGIENCE LABORATORY ACCREDITATON PROGRAM (IHLAP) Can be used as optional PT for alternate The following FoTs cover all
More informationThis document is a preview generated by EVS
INTERNATIONAL STANDARD ISO 14382 First edition 2012-12-01 Workplace atmospheres Determination of toluene diisocyanate vapours using 1-(2-pyridyl) piperazine-coated glass fibre filters and analysis by high
More informationCopyright ENCO Laboratories, Inc. II. Quality Control. A. Introduction
II. Quality Control A. Introduction ENCO adheres to strict quality control practices in order to assure our clients that the data provided are accurate and reliable. We are required by the EPA to analyze
More informationNaturally Occurring Asbestos:
RJ LeeGroup, Inc. Naturally Occurring Asbestos: A Recurring Public Policy Challenge R. J. Lee, B. R. Strohmeier, K. L. Bunker, and D. R. Van Orden RJ Lee Group, Inc. 350 Hochberg Road Monroeville, PA 15146
More informationUNITED STATES ENVIRONMENTAL PROTECTION AGENCY RE.GION BROADWAY NEW YORK, NEW YORK
UNITED STATES ENVIRONMENTAL PROTECTION AGENCY RE.GION 2 290 BROADWAY NEW YORK, NEW YORK 10007-1866 June 18,2010 Mr. Edward A. Gerdts Managing Principal TRC Environmental Corporation 1430 Broadway - 10
More informationDocument No: TR 12 Issue No: 1
ESTIMATION OF THE UNCERTAINTY OF MEASUREMENT BY CALIBRATION LABORATORIES AND SPECIFICATION OF CALIBRATION AND MEASUREMENT CAPABILITY ON SCHEDULES OF ACCREDITATION Prepared by: SADCAS Technical Manage Approved
More informationFacilities Management
Policy Number: 700.20 Title: Chemical Fume Hood Policy Implementation Date: 2002 Last Audited: August, 2017 Last Revised: October 23rd, 2017 Facilities Management Introduction The laboratory chemical fume
More informationArt, Science or Voodoo?
Industrial Hygiene Art, Science or Voodoo? Presented by: Ed Parsons Outreach Program Coordinator Gulf Coast Safety Institute Objectives At the completion of this session, the participants will: Know what
More informationINDUSTRIAL HYGIENE DIRECT READING SINGLE STRESSOR SAMPLE SURVEY FORM
INDUSTRIAL HYGIENE DIRECT READING SINGLE STRESSOR SAMPLE SURVEY FORM Sample Date: IH UIC: Activity: UIC: Field Office: Bldg./Hull #: Shop Location: Shop Code/Name: Shift: 1. Day Frequency of 1. Daily 2.
More informationRIGHT SOLUTIONS RIGHT PARTNER
2655 Park Center Dr., Suite A Simi Valley, CA 93065 T: +1 805 526 7161 F: +1 805 526 7270 www.alsglobal.com LABORATORY REPORT March 14, 2016 Glenn La Fevers Southern California Gas Company 12801 Tampa
More informationASTM C STEADY-STATE HEAT FLUX MEASUREMENTS AND THERMAL TRANSMISSION PROPERTIES BY MEANS OF THE HEAT FLOW METER APPARATUS
Page 1 of 10 ASTM C 518 04 STEADY-STATE HEAT FLUX MEASUREMENTS AND THERMAL TRANSMISSION PROPERTIES BY MEANS OF THE HEAT FLO METER APPARATUS Rockwool Premium Plus Insulation Project No. 3194876SAT-001A
More informationLEAD IN DRINKING WATER REPORT
181 US Hwy 46 Mine Hill, NJ 07803 (908) 654-8068 (800) 783-0567 Fax 908-654-8069 LEAD IN DRINKING WATER REPORT Performed At: Montrose School 356 Clark St., South Orange, NJ 07079 Performed For: South Orange
More informationPinchin Ltd. Asbestos Laboratory Certificate of Analysis
M. Adams / B. Ficko Date Received: March 24, 2017 Lab Reference No.: b167122 Date Analyzed: March 25, 2017 Analyst(s): C. Luong / T. Ly # Samples submitted: 9 # Phases analyzed: 18 Method of Analysis:
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD ISO 8426 Second edition 2008-02-01 Hydraulic fluid power Positive displacement pumps and motors Determination of derived capacity Transmissions hydrauliques Pompes et moteurs volumétriques
More informationApproval Block. Prepared by: Signature Date Evan Parnell 08 NOV Reviewed by: Signature Date. Approved by: Signature Date
ATS-SOI-3660 Page: 1 of 6 Approval Block Prepared by: Signature Date Evan Parnell 08 NOV 2013 Reviewed by: Signature Date Brian Flynn 08 NOV 2013 Approved by: Signature Date Kristal Jewell 08 NOV 2013
More informationUniversity of Tennessee Safety Procedure
University of Tennessee Safety Procedure Program Subject: Chemicals Requiring Review Prior to Use Procedure Review/Revised: 12/15/08 Affected Area/Department: Laboratories at the University Date Effective:
More informationReflectec Thermal Fabric & Reflectec Fiberboard
MODIFIED ASTM E 1354 CONE CALORIMETER THERMAL RESPONSE TEST (Final Report) TEST REPORT Reflectec Thermal Fabric & Reflectec Fiberboard Project No. 16723-113972 April 22, 2003 Prepared for: John W. Mallette
More informationPeterborough Distribution Inc Ashburnham Drive, PO Box 4125, Station Main Peterborough ON K9J 6Z5
Peterborough Distribution Inc. 1867 Ashburnham Drive, PO Box 4125, Station Main Peterborough ON K9J 6Z5 November 15, 2017 Ontario Energy Board PO Box 2319 27 th Floor, 2300 Yonge St Toronto ON M4P 1E4
More informationStandard Practice for Calculating Formulation Physical Constants of Paints and Coatings 1
Designation: D 5201 05 Standard Practice for Calculating Formulation Physical Constants of Paints and Coatings 1 This standard is issued under the fixed designation D 5201; the number immediately following
More informationKESTREL. April 26, Mr. Stephen Evans Maine Yankee 321 Old Ferry Road Wiscasset, Maine 04578
KESTREL ENVIRONMENTAL TECHNOLOGIES, INC. Mr. Stephen Evans Maine Yankee 321 Old Ferry Road Wiscasset, Maine 04578 RE: Project No.: Maine Yankee Soil Samples Lab Name: Katahdin Analytical Services, Westbrook,
More informationAPPENDIX G ESTIMATION OF UNCERTAINTY OF MEASUREMENT
APPENDIX G ESTIMATION OF UNCERTAINTY OF MEASUREMENT Table of Contents 1. SCOPE... 2 2. REFERENCES... 2 3. TERMS AND DEFINITIONS... 2 4. BACKGROUND... 4 5. ESTIMATION OF UNCERTAINTY OF MEASUREMENT POLICY...
More informationU.S. General Services Administration FOIA Requester Service Center (H1F) 1800 F Street, NW, Room 7308 Washington, DC Fax:
Description of document: Requested date: Released date: Posted date: Source of document: List of General Services Administration (GSA) properties from the REXUS (Real Estate Across the United States) database
More informationNovember 23, Mr. Shawn Liddle District Clerk Albion Central School District 324 East Avenue Albion, NY 14411
November 23, 2016 Mr. Shawn Liddle District Clerk Albion Central School District 324 East Avenue Albion, NY 14411 Re: Lead in Sampling Report Albion Central School District Sodoma Elementary School Dear
More informationR SANAS Page 1 of 7
ESTIMATION OF THE UNCERTAINTY OF MEASUREMENT BY CALIBRATION LABORATORIES AND SPECIFICATION OF CALIBRATION AND MEASUREMENT CAPABILITY ON SCHEDULES OF ACCREDITATION Approved By: Chief Executive Officer:
More informationXRAL X-RAY Bharti Engineering Associates Inc Lasalle Blvd. P O Box 2336 Sudbury (M P3A4S8. DATE SUBMITTED 9-Aug-89
XRAL X-RAY 1885 LESLIE S TEL: (416)445 41113SE9429 2.12731 ULSTER 010 C ERT X F X O A.T E TO: BHARTI ENGINEERING ASSOCIATES INC. ATTN: HAROLD J. TRACANELLI 1009 LASALLE BLVD P.O. BOX 2336 SUDBURY, ONTARIO
More informationStandard Test Method for Coefficient of Linear Thermal Expansion of Plastics Between 30 C and 30 C with a Vitreous Silica Dilatometer 1
Designation: D 696 08 Standard Test Method for Coefficient of Linear Thermal Expansion of Plastics Between 30 C and 30 C with a Vitreous Silica Dilatometer 1 This standard is issued under the fixed designation
More informationAPPENDIX G EVALUATION OF MEASUREMENT UNCERTAINTY
APPENDIX G EVALUATION OF MEASUREMENT UNCERTAINTY Table of Contents 1. SCOPE... 2 2. REFERENCES... 2 3. TERMS AND DEFINITIONS... 2 4. BACKGROUND... 4 5. EVALUATION OF MEASUREMENT UNCERTAINTY POLICY... 5
More informationSimulation Report (Revised) Rendered To: Showcase Custom Vinyl Windows 1002 Olde Towne Drive Irving, TX 75061
ETC Laboratories ETC Laboratories Corporate Offices / Laboratories 297 Buell Road Rochester, NY 14624 (585) 328-7668 Fax: (585) 328-7777 Simulation Report (Revised) Rendered To: Showcase Custom Vinyl Windows
More informationSome analyses have been subcontracted outside of the Pace Network. The subcontracted laboratory report has been attached.
#=CL# Pace Analytical Services, LLC Broad Hollow Road Melville, NY ()-00 LIMS USE: FR - ROB KING LIMS OBJECT ID: 0 July, 0 Rob King Hampton Bays Water District P.O. Box Hampton Bays, NY RE: Project: PFC
More informationArdaman & Associates, Inc. Geotechnical, Environmental and Materials Consultants
SUBSURFACE SOIL EXPLORATION 42-INCH FORCE MAIN REPLACEMENT CHIQUITA BOULEVARD S AND SW 34 TH STREET CAPE CORAL, LEE COUNTY, FLORIDA Ardaman & Associates, Inc. Geotechnical, Environmental and Materials
More information2019 MICHAEL E. BEARD CONFERENCE: SAMPLING, ANALYSIS, MANAGEMENT OF ASBESTOS, AND OTHER MICROSCOPIC PARTICLES
2019 MICHAEL E. BEARD CONFERENCE: SAMPLING, ANALYSIS, MANAGEMENT OF ASBESTOS, AND OTHER MICROSCOPIC PARTICLES Sponsored by ASTM Committee D22 on Air Quality April 4-5, 2019 Sheraton Denver Downtown Hotel
More informationTest Report. Project No: Report No: aR01 Report Issued Date: Customer Company & Address:
Customer Company & Address: Edison Opto Corporation ADD: 4F, No.800, Chung-Cheng Rd., Chung-Ho Dist, New Taipei City Contact erson: Telephone: Zhen Chuang 886-2-8227-6996 Fax: zhenchuang@edisonopto.com.tw
More informationTest Report EN (2008)
Test Report EN 62233 (2008) Product Name and address of the applicant Name and address of the manufacturer Model Rating Brand name Heating elements for building into floors Advanced Heating Technologies
More informationRADIATION SAFETY GUIDELINES FOR NON-USERS
RADIATION SAFETY GUIDELINES FOR NON-USERS This is a Read and Sign Awareness Training document. You should read and sign this document if you: 1. DO NOT work directly with radioactive materials, but 2.
More informationASTM C THERMAL PERFORMANCE TEST REPORT. Rendered to: UNIVERSAL PULTRUSIONS, LLC. PRODUCT: Fiberglass Door Slab
ASTM C 1363-11 THERMAL PERFORMANCE TEST REPORT Rendered to: UNIVERSAL PULTRUSIONS, LLC PRODUCT: Fiberglass Door Slab Summary of Results Thermal Transmittance (Btu/hr.ft².F), U-factor Overall Thermal Resistance
More information