ASTM C THERMAL PERFORMANCE TEST REPORT. Rendered to: UNIVERSAL PULTRUSIONS, LLC. PRODUCT: Fiberglass Door Slab

Size: px
Start display at page:

Download "ASTM C THERMAL PERFORMANCE TEST REPORT. Rendered to: UNIVERSAL PULTRUSIONS, LLC. PRODUCT: Fiberglass Door Slab"

Transcription

1 ASTM C THERMAL PERFORMANCE TEST REPORT Rendered to: UNIVERSAL PULTRUSIONS, LLC PRODUCT: Fiberglass Door Slab Summary of Results Thermal Transmittance (Btu/hr.ft².F), U-factor Overall Thermal Resistance (hr.ft².f/btu), R-value(Ru) Reference should be made to ATI Report No. for complete test specimen description and data. 849 Western Avenue North St. Paul, MN phone: fax:

2 ASTM C THERMAL PERFORMANCE TEST REPORT Rendered to: UNIVERSAL PULTRUSIONS, LLC PO Box 1289, 100 Tillco Drive Marshall, Arkansas Report No: Test Date: Report Date: Expiration Date: 03/21/12 04/09/12 03/21/16 Test Sample Identification: Series/Model: Fiberglass Door Slab Overall Size: 35-3/4" wide x 84" tall Test Procedure: The thermal performance was determined in general accordance with ASTM C , Standard Test Method for the Thermal Performance of Building Assemblies by Means of Hot Box Apparatus. Test Results Summary: Thermal Transmittance, U-factor (U): Overall Thermal Resistance(Air-to-Air), (Ru): Thermal Resistance(Surface-to-Surface), (Rc): Btu/hr.ft².F (hr.ft².f)/btu (hr.ft².f)/btu 849 Western Avenue North St. Paul, MN phone: fax:

3 Page 2 of 6 Test Sample Description Overall Size: 35-3/4" wide x 84" tall Specimen Thickness: 1-3/4" Construction: The specimen was comprised of a 1-1/2" thick polyisocyanurate core sandwiched between two 0.135" thick fiberglass skins. Measured Test Data Areas 1. Test Specimen Projected Area (As) ft 2 2. Metering Box Opening Area (Amb) ft 2 3. Metering Box Baffle Area (Ab1) ft 2 Heat Flows 1. Total Measured Input into Metering Box (Qtotal) Btu/hr 2. Metering Box Wall Heat Flow (Qmb) Btu/hr 3. EMF vs Heat Flow Equation (equivalent information) *EMF Net Specimen Heat Loss (Qs) Btu/hr The sample was inspected for the formation of frost or condensation, which may influence the surface temperature measurements. The sample showed no evidence of condensation/frost at the conclusion of the test. A calibration of the ATI 'thermal test chamber' in St. Paul, Minnesota was conducted in October 2011.

4 Page 3 of 6 Thermal Performance Test Conditions 1. Average Metering Room Air Temperature (t h ) F 2. Average Cold Side Air Temperature (t c ) F 3. Average Guard/Environmental Air Temperature F 4. Metering Room Average Relative Humidity % 5. Measured Cold Side Wind Velocity (Perpendicular Flow) mph 6. Measured Static Pressure Difference Across Test Specimen 0.00" ± 0.04"H 2 O Results Thermal Conductance (C) Thermal Resistance (Rc) Overall Thermal Resistance (R u ) Warm Side Surface Resistance (R h ) Cold Side Surface Resistance (R c ) Warm Side Surface Conductance (h h ) Btu/hr ft² F 6.05 hr ft² F/Btu 7.42 hr ft² F/Btu 1.16 hr ft² F/Btu 0.21 hr ft² F/Btu 0.86 Btu/hr ft² F 7. Cold Side Surface Conductance (h c ) 4.75 Btu/hr ft² F 8. Thermal Transmittance (U) Btu/hr ft² F Test Duration 1. The environmental systems were started at 13:31 hrs., 03/20/12 2. The test parameters were considered stable for two consecutive four hour test periods 00:26 hrs., 03/21/12 to 08:26 hrs., 03/21/ The thermal performance test results were derived from 04:26 hrs, 03/21/12 to 08:26 hrs, 03/21/12.

5 Page 4 of 6 Surface Temperatures (as viewed from interior) Individual Surface Temperature Measurements Thermocouple Warm Side (F) Cold Side (F) Thermocouple Warm Side (F) Cold Side (F) Average Warm Side Surface Temperature F 2. Average Cold Side Surface Temperature 1.58 F

6 Page 5 of 6 Representative samples of the test specimen and a copy of this report will be retained by ATI for a period of four years. This report is the exclusive property of the client so named herein and relates only to the fenestration product tested. This report may not be reproduced, except in full, without the approval of the laboratory. Results obtained are tested values and do not constitute an opinion or endorsement by this laboratory. This report does not constitute certification of this product, which may only be granted by an Independent Administrator. For ARCHITECTURAL TESTING, INC. Michael D. Topitzhofer Technician Michael P. Resech Senior Project Manager Individual-In-Responsible-Charge MDT:mpr Attachments: None

7 Page 6 of 6 Revision Log Rev. # Date Page(s) Revision(s) 0 04/09/12 All Original Report Issue. Work requested by Keith Jensen of Universal Pultrusions, LLC

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: NU VISTA WD, INC. SERIES/MODEL: Malibu 250 T TYPE: Fixed

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: NU VISTA WD, INC. SERIES/MODEL: Malibu 250 T TYPE: Fixed NFRC 102-201 THERMAL PERFORMANCE TEST REPORT Rendered to: NU VISTA WD, INC. SERIES/MODEL: Malibu 250 T TYPE: Fixed Summary of Results Standardized Thermal Transmittance (U-Factor) 0.39 Unit Size: 7" x

More information

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: C.R. LAURENCE CO., INC.

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: C.R. LAURENCE CO., INC. NFRC 102-2014 THERMAL PERFORMANCE TEST REPORT Rendered to: C.R. LAURENCE CO., INC. SERIES/MODEL: 45X - High Performance Dual Thermally Broken Storefront TYPE: Glazed Wall Systems (Site-built) Summary of

More information

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: NORTH EAST WINDOWS USA, INC.

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: NORTH EAST WINDOWS USA, INC. NFRC 102-2014 THERMAL PERFORMANCE TEST REPORT Rendered to: NORTH EAST WINDOWS USA, INC. SERIES/MODEL: 100 Double Hung TYPE: Vertical Slider (Double Hung) Summary of Results Standardized Thermal Transmittance

More information

THERMAL PERFORMANCE TEST REPORT

THERMAL PERFORMANCE TEST REPORT THERMAL PERFORMANCE TEST REPORT Manufacture: Address: Coral Architectural Products 7704B Industrial Lane Tampa, Florida 33637 Specifications: ANSI/NFRC 102-2014: Test Procedure for Measuring the Steady-State

More information

SHANGHAI MYLCH WINDOWS & DOORS THERMAL PERFORMANCE TEST REPORT

SHANGHAI MYLCH WINDOWS & DOORS THERMAL PERFORMANCE TEST REPORT SHANGHAI MYLCH WINDOWS & DOORS THERMAL PERFORMANCE TEST REPORT SCOPE OF WORK DR65 FIXED REPORT NUMBER H3108.01-301-46 R0 TEST DATE 11/09/17 ISSUE DATE 11/14/17 RECORD RETENTION END DATE 11/09/22 PAGES

More information

NFRC SOLAR HEAT GAIN COEFFICIENT TEST REPORT. Rendered to: CLEAR FOCUS IMAGING

NFRC SOLAR HEAT GAIN COEFFICIENT TEST REPORT. Rendered to: CLEAR FOCUS IMAGING NFRC 201-2004 SOLAR HEAT GAIN COEFFICIENT TEST REPORT Rendered to: CLEAR FOCUS IMAGING SERIES/MODEL: SunSecure BASE WINDOW: 3/16" Clear Single Glazed PRODUCT TYPE: Window Film on the Interior of Clear

More information

Test Results: Results of the test period on 06/19/16 using the Equivalent CTS Method: Thermal transmittance at test conditions (U s ):

Test Results: Results of the test period on 06/19/16 using the Equivalent CTS Method: Thermal transmittance at test conditions (U s ): NORTH EAST WINDOWS USA, INC. NFRC THERMAL TEST SUMMARY REPORT Report No: NCTL-110-17842-3S Test Specimen NFRC Code Manufacturer: North East Windows USA, Inc. Series/Model: Series CW 300 Window Type: Casement-

More information

AIR-INS inc. 1320, boul. Lionel-Boulet, Varennes (Quebec) J3X 1P7 Tél. : (450) Fax : (450)

AIR-INS inc. 1320, boul. Lionel-Boulet, Varennes (Quebec) J3X 1P7 Tél. : (450) Fax : (450) 1320, boul. Lionel-Boulet, Varennes (Quebec) J3X 1P7 Tél. : (450) 652-0838 Fax : (450) 652-7588 info@air-ins.com THERMAL PERFORMANCE VALIDATION TEST CONDUCTED ON YOUR 300 / 301 FIXED WINDOW IN ACCORDANCE

More information

PERFORMANCE TEST REPORT. Rendered to: WORLDWIDE DOOR COMPONENTS, INC. PRODUCTS: PVC and Composite Door Jamb Material

PERFORMANCE TEST REPORT. Rendered to: WORLDWIDE DOOR COMPONENTS, INC. PRODUCTS: PVC and Composite Door Jamb Material PERFORMANCE TEST REPORT Rendered to: WORLDWIDE DOOR COMPONENTS, INC. PRODUCTS: PVC and Composite Door Jamb Material Report No: Report Date: 10/24/11 Expiration Date: 09/27/15 130 Derry Court York, PA 17406-8405

More information

Report No: NCTL NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 12/14/15

Report No: NCTL NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 12/14/15 MGM INDUSTRIES, INC. Report No: NCTL-110-14571-1 NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 12/14/15 Test Specimen NFRC Code Manufacturer: MGM Industries, Inc. Series/Model: Series 4600 Window Type:

More information

NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 03/31/06

NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 03/31/06 ALL SEASONS DOOR & WINDOW, INC. Report No: NCTL-110-8058-5S NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 03/31/06 Test Specimen NFRC Code Manufacturer : All Seasons Door & Window, Inc. Series/Model

More information

NFRC THERMAL TEST SUMMARY REPORT January 27, 1999 Test Specimen

NFRC THERMAL TEST SUMMARY REPORT January 27, 1999 Test Specimen * This is not the original copy of the test report if you would like an original copy, please contact our East Brunswick office or the NCTL to request a copy. ALL SEASONS DOOR & WINDOW, INC. REPORT NO:

More information

Report No: NCTL S NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 07/14/15. Test Specimen

Report No: NCTL S NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 07/14/15. Test Specimen MGM INDUSTRIES, INC. Report No: NCTL-110-13834-1S NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 07/14/15 Test Specimen NFRC Code Manufacturer: MGM Industries, Inc. Series/Model: 8017 Window Type: Double

More information

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: CMI ARCHITECTURAL PRODUCTS, INC.

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: CMI ARCHITECTURAL PRODUCTS, INC. NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT Rendered to: CMI ARCHITECTURAL PRODUCTS, INC. SERIES/MODEL: CTS Thermal Clip Framing System TYPE: Glazed Wall Systems (Site-built) Summary of Results Standardized

More information

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: UNITED STATES ALUMINUM. SERIES/MODEL: 7400 TYPE: Fixed

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: UNITED STATES ALUMINUM. SERIES/MODEL: 7400 TYPE: Fixed NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT Rendered to: UNITED STATES ALUMINUM SERIES/MODEL: 7400 TYPE: Fixed Summary of Results Standardized Thermal Transmittance (U-Factor) 0.37 Unit Size 47-1/4''

More information

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: PARAMOUNT WINDOWS CORPORATION. SERIES/MODEL: 4000 TYPE: Fixed

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: PARAMOUNT WINDOWS CORPORATION. SERIES/MODEL: 4000 TYPE: Fixed Architectural Testing NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT Rendered to: PARAMOUNT WINDOWS CORPORATION SERIES/MODEL: 4000 TYPE: Fixed Summary of Results Standardized Thermal Transmittance (U-Factor)

More information

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: INTERNATIONAL ARCHITECTURAL PRODUCTS, INC. DBA: UNITED STATES ALUMINUM

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: INTERNATIONAL ARCHITECTURAL PRODUCTS, INC. DBA: UNITED STATES ALUMINUM Architectural Testing NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT Rendered to: INTERNATIONAL ARCHITECTURAL PRODUCTS, INC. DBA: UNITED STATES ALUMINUM SERIES/MODEL: 7600 Projected Vent TYPE: Projecting

More information

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: TUBELITE, INC.

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: TUBELITE, INC. Architectural Testing NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT Rendered to: TUBELITE, INC. SERIES/MODEL: T14000 Storefront (Standard) TYPE: Glazed Wall Systems (Site-built) Summary of Results Standardized

More information

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: C.R. LAURENCE CO., INC.

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: C.R. LAURENCE CO., INC. NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT Rendered to: C.R. LAURENCE CO., INC. SERIES/MODEL: 375-T - High Performance Medium Stile Thermal Door (Dual Glazed) TYPE: Swinging Door with Frame Summary

More information

Simulation Report (Revised) Rendered To: Showcase Custom Vinyl Windows 1002 Olde Towne Drive Irving, TX 75061

Simulation Report (Revised) Rendered To: Showcase Custom Vinyl Windows 1002 Olde Towne Drive Irving, TX 75061 ETC Laboratories ETC Laboratories Corporate Offices / Laboratories 297 Buell Road Rochester, NY 14624 (585) 328-7668 Fax: (585) 328-7777 Simulation Report (Revised) Rendered To: Showcase Custom Vinyl Windows

More information

REPORT NUMBER: MID-001 ORIGINAL ISSUE DATE: April 22, 2016 REVISED DATE: NA. EVALUATION CENTER Intertek 8431 Murphy Drive Middleton, WI 53562

REPORT NUMBER: MID-001 ORIGINAL ISSUE DATE: April 22, 2016 REVISED DATE: NA. EVALUATION CENTER Intertek 8431 Murphy Drive Middleton, WI 53562 REPORT NUMBER: 102550917MID-001 ORIGINAL ISSUE DATE: April 22, 2016 REVISED DATE: NA TEST REPORT EVALUATION CENTER Intertek 8431 Murphy Drive Middleton, WI 53562 RENDERED TO Cali Bamboo 6675 Mesa Ridge

More information

PERFORMANCE TEST REPORT. Rendered to: VELUX AMERICA, INC. PRODUCT: SUN TUNNEL Domes TYPES: Acrylic and Polycarbonate

PERFORMANCE TEST REPORT. Rendered to: VELUX AMERICA, INC. PRODUCT: SUN TUNNEL Domes TYPES: Acrylic and Polycarbonate PERFORMANCE TEST REPORT Rendered to: VELUX AMERICA, INC. PRODUCT: SUN TUNNEL Domes TYPES: Acrylic and Polycarbonate Report No.: E3490.01-106-31 Report Date: 07/13/15 Test Record Retention Date: 06/18/19

More information

ROLLEASE ACMEDA ACOUSTICAL PERFORMANCE TEST REPORT

ROLLEASE ACMEDA ACOUSTICAL PERFORMANCE TEST REPORT ROLLEASE ACMEDA ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM C423 SOUND ABSORPTION TESTING ON TEMPE, ROLLER SHADE FABRIC REPORT NUMBER I7375.01-113-11-R0 TEST DATE 08/14/18 ISSUE DATE 09/04/18

More information

TEST METHOD FOR THERMAL TRANSMITTANCE AND AIR INFILTRATION OF GARAGE DOORS

TEST METHOD FOR THERMAL TRANSMITTANCE AND AIR INFILTRATION OF GARAGE DOORS ANSI/DASMA 105-1992 (R2004) AMERICAN NATIONAL STANDARD TEST METHOD FOR THERMAL TRANSMITTANCE AND AIR INFILTRATION OF GARAGE DOORS Door & Access Systems Manufacturers Association, International Sponsor:

More information

SIMULATION TEST REPORT NCTL E0A0

SIMULATION TEST REPORT NCTL E0A0 SIMULATION TEST REPORT NCTL-610-21539-1E0A0 REPORT TO: All Seasons Window & Door System Inc. 1340 Metropolitan Avenue Brooklyn, NY 11237 SIMULATION DATE: 11/20/18 PRODUCT: EU400 Tilt & Turn This report

More information

ASTM C STEADY-STATE HEAT FLUX MEASUREMENTS AND THERMAL TRANSMISSION PROPERTIES BY MEANS OF THE HEAT FLOW METER APPARATUS

ASTM C STEADY-STATE HEAT FLUX MEASUREMENTS AND THERMAL TRANSMISSION PROPERTIES BY MEANS OF THE HEAT FLOW METER APPARATUS Page 1 of 10 ASTM C 518 04 STEADY-STATE HEAT FLUX MEASUREMENTS AND THERMAL TRANSMISSION PROPERTIES BY MEANS OF THE HEAT FLO METER APPARATUS Rockwool Premium Plus Insulation Project No. 3194876SAT-001A

More information

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6956 Revision 1 ARL

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6956 Revision 1 ARL ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT -SA6956 Revision 1 Subject: Sound Absorption Test Date: 04 January 2017 Contents: on Sound Absorption Data, One-third Octave bands Sound

More information

Sound Absorption Test Intertek. kraft paper softwall + softblock modular system. m o l o d e s i g n, l t d

Sound Absorption Test Intertek. kraft paper softwall + softblock modular system. m o l o d e s i g n, l t d Sound Absorption Test Intertek kraft paper softwall + softblock modular system m o l o d e s i g n, l t d 1470 Venables Street V a n c o u v e r, B. C. C a n a d a V 5 L 2 G 7 t +1 604 696 2501 f +1 604

More information

Standard Test Method for Thermal Conductivity of Refractories 1

Standard Test Method for Thermal Conductivity of Refractories 1 Designation: C 201 93 (Reapproved 1998) Standard Test Method for Thermal Conductivity of Refractories 1 This standard is issued under the fixed designation C 201; the number immediately following the designation

More information

Assessing The Thermal Performance of Building Enclosure Materials Using A Medium-Size Hot Box Chamber Summer Meeting Torkan Fazli

Assessing The Thermal Performance of Building Enclosure Materials Using A Medium-Size Hot Box Chamber Summer Meeting Torkan Fazli Assessing The Thermal Performance of Building Enclosure Materials Using A Medium-Size Hot Box Chamber 2014 Summer Meeting Torkan Fazli Introduction The building construction industry consumes significant

More information

Standard Test Method for Measuring the Steady-State Thermal Transmittance of Fenestration Systems Using Hot Box Methods 1

Standard Test Method for Measuring the Steady-State Thermal Transmittance of Fenestration Systems Using Hot Box Methods 1 Designation: 97 AMERICAN SOCIETY FOR TESTING AND MATERIALS 100 Barr Harbor Dr., West Conshohocken, PA 19428 Reprinted from the Annual Book of ASTM Standards. Copyright ASTM Standard Test Method for Measuring

More information

AR/IA 241 LN 231 Lecture 4: Fundamental of Energy

AR/IA 241 LN 231 Lecture 4: Fundamental of Energy Faculty of Architecture and Planning Thammasat University A/IA 24 LN 23 Lecture 4: Fundamental of Energy Author: Asst. Prof. Chalermwat Tantasavasdi. Heat For a specific substance, the heat given to the

More information

Vincent Barraud SOPREMA BASICS OF THERMAL INSULATION

Vincent Barraud SOPREMA BASICS OF THERMAL INSULATION Vincent Barraud SOPREMA BASICS OF THERMAL INSULATION Summary Part 1 - What is thermal conductivity? Part 2 - How the thermal conductivity is measured? Part 3 How to certify a lambda value? Part 1 - What

More information

WINDOW SIMULATION REPORT

WINDOW SIMULATION REPORT WINDOW SIMULATION REPORT NFRC 100: Procedure for Determining Fenestration Product U-Factors NFRC 200: Solar Heat Gain Coefficient and Visible Transmittance NFRC 500: Procedure for Determining Fenestration

More information

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6986/ARL-SA6987 Revision 0 ARL

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6986/ARL-SA6987 Revision 0 ARL ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT -SA6986/-SA6987 Revision 0 Subject: Sound Absorption Test Date: 01 February 2017 Contents: on Sound Absorption Data, One-third Octave

More information

The information included in the following report presents the results of sound pressure and sound power testing.

The information included in the following report presents the results of sound pressure and sound power testing. ISO 7779:2010 Acoustics -- Measurement of airborne noise emitted by information technology and telecommunications equipment 1 of 14 DEVICES - solid panel case - window panel case Report Date: 06/25/2015

More information

HFM 100 Series. Thermal Conductivity Meter for measurement of insulation and construction materials.

HFM 100 Series. Thermal Conductivity Meter for measurement of insulation and construction materials. HFM 100 Series Conforms to International Standards ASTM C518, ISO 8301, and EN 12667 Thermal Conductivity Meter for measurement of insulation and construction materials. Hot Disk TPS -160 to 1000 C HFM

More information

Reflectec Thermal Fabric & Reflectec Fiberboard

Reflectec Thermal Fabric & Reflectec Fiberboard MODIFIED ASTM E 1354 CONE CALORIMETER THERMAL RESPONSE TEST (Final Report) TEST REPORT Reflectec Thermal Fabric & Reflectec Fiberboard Project No. 16723-113972 April 22, 2003 Prepared for: John W. Mallette

More information

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6712/ARL-SA6713 Revision 0 ARL

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6712/ARL-SA6713 Revision 0 ARL ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT -SA6712/-SA6713 Revision 0 Subject: Sound Absorption Test Date: 17 May 2016 Contents: on Sound Absorption Data, One-third Octave bands

More information

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6266/ARL-SA6274 Revision 0 ARL

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6266/ARL-SA6274 Revision 0 ARL ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT -SA6266/-SA6274 Revision 0 Subject: Sound Absorption Test Date: 17 February 2015 Contents: on Sound Absorption Data, One-third Octave

More information

Standard Test Method for Determination of the Thermal Conductivity of Anode Carbons by the Guarded Heat Flow Meter Technique 1

Standard Test Method for Determination of the Thermal Conductivity of Anode Carbons by the Guarded Heat Flow Meter Technique 1 Designation: D 6744 01 An American National Standard Standard Test Method for Determination of the Thermal Conductivity of Anode Carbons by the Guarded Heat Flow Meter Technique 1 This standard is issued

More information

Use of Phase-Change Materials to Enhance the Thermal Performance of Building Insulations

Use of Phase-Change Materials to Enhance the Thermal Performance of Building Insulations Introduction Use of Phase-Change Materials to Enhance the Thermal Performance of Building Insulations R. J. Alderman, Alderman Research Ltd., Wilmington, DE David W. Yarbrough, R&D Services, Inc., Cookeville,

More information

Radiant Heating Panel Thermal Analysis. Prepared by Tim Fleury Harvard Thermal, Inc. October 7, 2003

Radiant Heating Panel Thermal Analysis. Prepared by Tim Fleury Harvard Thermal, Inc. October 7, 2003 Radiant Heating Panel Thermal Analysis Prepared by Tim Fleury Harvard Thermal, Inc. October 7, 2003 Analysis Objective Perform a thermal test on a small sample of the concrete to determine the Thermal

More information

THE EFFECTS OF CALORIMETER TILT ON THE INWARD-FLOWING FRACTION OF ABSORBED SOLAR RADIATION IN A VENETIAN BLIND

THE EFFECTS OF CALORIMETER TILT ON THE INWARD-FLOWING FRACTION OF ABSORBED SOLAR RADIATION IN A VENETIAN BLIND Collins, M.R., and Harrison, S.J., "The Effects of Calorimeter Tilt on the Inward-Flowing Fraction of Absorbed Solar Radiation in a Venetian Blind", ASHRAE Transactions, Vol. 107 (1), pp. 677-683, 2001.

More information

Standard Guide for Determination of the Thermal Resistance of Low-Density Blanket-Type Mineral Fiber Insulation 1

Standard Guide for Determination of the Thermal Resistance of Low-Density Blanket-Type Mineral Fiber Insulation 1 Designation: C 653 97 Standard Guide for Determination of the Thermal Resistance of Low-Density Blanket-Type Mineral Fiber Insulation 1 This standard is issued under the fixed designation C 653; the number

More information

DeFelsko PosiTector Dew Point Meter with Anemometer (DPMA)

DeFelsko PosiTector Dew Point Meter with Anemometer (DPMA) Management Procedure 2562 Revision: A Date Issued: March 24, 2017 Date Revised: Calibration Procedure DeFelsko PosiTector Dew Point Meter with Anemometer (DPMA) Table of Contents 1. Introduction and UUC

More information

Making Decisions with Insulation

Making Decisions with Insulation PDHonline Course K115 (3 PDH) Making Decisions with Insulation Instructor: Christopher Haslego, B.S. ChE 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088

More information

CONSTRUCTION MATERIALS

CONSTRUCTION MATERIALS CONSTRUCTION MATERIALS T E C H N O L O G I E S LABORATORY TEST REPORT Report for: 6 Cherry Ave Penticton, BC VA L7 Canada Product(s): Deksmart Ultra 68mil Decking Membrane Manufacturer: O Sullivan Films,

More information

RIVERBANK ACOUSTICAL LABORATORIES

RIVERBANK ACOUSTICAL LABORATORIES FOR: Atlanta, GA Sound Absorption CONDUCTED: 2016-10-14 Page 1 of 8 ON: D-GIK Panels TEST METHOD Riverbank Acoustical Laboratories is accredited by the U.S. Department of Commerce, National Institute of

More information

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630 FOR THE SCOPE OF ACCREDITATION UNDER ALA TO ISO/IEC 170:00. REPORT 800 COMMERCENTRE DRIVE, LAKE FOREST, CA 90 Project No. G10171817 Date: August, 01 REPORT NO. 10171817LAX-00 TEST OF ONE GARAUGE LUMINAIRE

More information

Standard Test Method for Coefficient of Linear Thermal Expansion of Plastics Between 30 C and 30 C with a Vitreous Silica Dilatometer 1

Standard Test Method for Coefficient of Linear Thermal Expansion of Plastics Between 30 C and 30 C with a Vitreous Silica Dilatometer 1 Designation: D 696 08 Standard Test Method for Coefficient of Linear Thermal Expansion of Plastics Between 30 C and 30 C with a Vitreous Silica Dilatometer 1 This standard is issued under the fixed designation

More information

O Plus Dry Bushing 69 kv system, 350 kv BIL, 3000 A. Table of contents

O Plus Dry Bushing 69 kv system, 350 kv BIL, 3000 A. Table of contents Type test report O Plus Dry Bushing 69 kv system, 0 kv BIL, 000 A Table of contents Abstract... 2 2 Certification... 2 Introduction.... Description and ratings....2 Overview of tests.... Applicable standards....4

More information

Determination of installed thermal resistance into a roof of TRISO-SUPER 12 BOOST R

Determination of installed thermal resistance into a roof of TRISO-SUPER 12 BOOST R INSTITUTE OF ARCHITECTURE AND CONSTRUCTION OF KAUNAS UNIVERSITY OF TECHNOLOGY LABORATORY OF BUILDING PHYSICS Notified Body number: 2018 TEST REPORT No. 037-10/11(C) SF/15 Date: 26 of November 2015 page

More information

announcements 4/17/08

announcements 4/17/08 Heat Transfer and the Building Envelope ARCH 331/431 Spring 2008 Lecture 6 announcements 4/17/08 A3: Envelope Heat Transfer Assignment: Available later today (course website) References: Available by this

More information

KINECTRICS NORTH AMERICA INC. TEST REPORT FOR 774-KCMIL 3M TM COMPOSITE CONDUCTOR

KINECTRICS NORTH AMERICA INC. TEST REPORT FOR 774-KCMIL 3M TM COMPOSITE CONDUCTOR KINECTRICS NORTH AMERICA INC. TEST REPORT FOR 774-KCMIL 3M TM COMPOSITE CONDUCTOR Test Name: SUSTAINED LOAD TEST ON COMPRESSION DEADEND FITTING FOR 774-KCMIL 3M TM COMPOSITE CONDUCTOR AT ROOM TEMPERATURE

More information

TEST REPORT. Date. W. O. No.

TEST REPORT. Date. W. O. No. In account with STRATASYS, INC. 7640 COMMERCE WAY EDEN PRAIRIE, MN 55344 USA Date W. O. No. 25 November 2014 Page 1 of 4 Pages T 46715-2 Identification As noted P. O. No. Shipper 800009247 None IDENTIFICATION

More information

Thermal and mechanical modeling of thermal breaks in structural steel point transmittances

Thermal and mechanical modeling of thermal breaks in structural steel point transmittances Thermal and mechanical modeling of thermal breaks in structural steel point transmittances Presented to the American Society of Mechanical Engineers Presented by: Scott Hamel P.E., Ph.D. Co-Author: Sava

More information

Determination of thermal transmittance of window (test title)

Determination of thermal transmittance of window (test title) INSTITUTE OF ARCHITECTURE AND CONSTRUCTION OF KAUNAS UNIVERSITY OF TECHNOLOGY SCIENCE LABORATORY OF BUILDING THERMAL PHYSICS Notified Body number: 2018 BANDYMAI ISO/IEC 17025 Nr. LA. 01.031 page (pages)

More information

This specification covers the requirements for product performance, test methods and quality assurance provisions of FG Terminal.

This specification covers the requirements for product performance, test methods and quality assurance provisions of FG Terminal. DESIGN OBJECTIVES The product described in this document has not been fully tested to ensure conformance to the requirements outlined below. Therefore AMP Ltd makes no representation or warranty, express

More information

AIR MONITORING REPORT

AIR MONITORING REPORT AIR MONITORING REPORT 1500 Hallway Frost Lake Magnet 1505 East Hoyt Avenue St. Paul, MN 55103 December 21, 2005 Nova Client No.: STPAU006/Project No: H05-1309 AIR MONITORING REPORT 1500 Hallway Frost Lake

More information

Standard Test Methods for Glass-Bonded Mica Used as Electrical Insulation 1

Standard Test Methods for Glass-Bonded Mica Used as Electrical Insulation 1 Designation: D 1039 94 (Reapproved 1999) e1 An American National Standard Standard Test Methods for Glass-Bonded Mica Used as Electrical Insulation 1 This standard is issued under the fixed designation

More information

A L I O N Technical Center. Test Report. Port Coquitlam, British Columbia, Canada

A L I O N Technical Center. Test Report. Port Coquitlam, British Columbia, Canada FOR: Port Coquitlam, British Columbia, Canada Sound Absorption CONDUCTED: 2018-03-19 Page 1 of 7 ON: Model F202-2448 - Hercules absorption panels TEST METHOD Riverbank Acoustical Laboratories is accredited

More information

REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK 13045

REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK 13045 REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK 13045 FOR THE SCOPE OF ACCREDITATION UNDER NVLAP LAB CODE 100402-0. Project No. G100896445 Date: September 26, 2012 REPORT NO. 100896445CRT-001 TEST OF ONE LED

More information

National Fenestration Rating Council. Incorporated. NFRC [E0A1] Procedure for Determining Fenestration Product Condensation Resistance Values

National Fenestration Rating Council. Incorporated. NFRC [E0A1] Procedure for Determining Fenestration Product Condensation Resistance Values National Fenestration Rating Council Incorporated NFRC 500-2010 [E0A1] Procedure for Determining Fenestration Product Condensation Resistance Values 2010 NATIONAL FENESTRATION RATING COUNCIL, INC. PREPARED

More information

EA Guidelines on the Calibration of Temperature Indicators and Simulators by Electrical Simulation and Measurement

EA Guidelines on the Calibration of Temperature Indicators and Simulators by Electrical Simulation and Measurement Publication Reference EA-10/11 EA Guidelines on the Calibration of Temperature Indicators and Simulators by Electrical PURPOSE This document has been produced by EA as a means of giving advice for calibrating

More information

AM01 - System Offices. Purchase Order

AM01 - System Offices. Purchase Order Page 1 of 6 AM01 - System Offices Purchase Order P.O. Date: 12/16/2016 Purchase Order Number AM01-17-P041212 SHOW THIS NUMBER ON ALL PACKAGES, INVOICES AND SHIPPING PAPERS. V E N D O R Vendor Number: 00001945

More information

Winter Night. Thermos 6mm Outdoors # #

Winter Night. Thermos 6mm Outdoors # # February 26, 2016 By Gagnon, Stephan stephan@thermosrn.ca Thermos 3mm à 6mm vs Climaguard 80/70 Make-up Name Make-up Icon Transmittance Reflectance U-Value Visible (τ v %) (τ e %) Visible ρ v % out ρ v

More information

ANSI/AHRI Standard (Formerly ARI Standard ) 2006 Standard for Performance Rating of Desuperheater/Water Heaters

ANSI/AHRI Standard (Formerly ARI Standard ) 2006 Standard for Performance Rating of Desuperheater/Water Heaters ANSI/AHRI Standard 470-2006 (Formerly ARI Standard 470-2006) 2006 Standard for Performance Rating of Desuperheater/Water Heaters IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does

More information

DOC SCIENCE INTERNAL SERIES 15

DOC SCIENCE INTERNAL SERIES 15 Condensation in Glow-worm Cave, Waitomo, New Zealand Management guidelines DOC SCIENCE INTERNAL SERIES 15 Antje Anna Schmekal and Chris R. de Freitas Published by Department of Conservation P.O. Box 10-420

More information

EA-10/13. EA Guidelines on the Calibration of Temperature Block Calibrators. Publication Reference PURPOSE

EA-10/13. EA Guidelines on the Calibration of Temperature Block Calibrators. Publication Reference PURPOSE Publication Reference EA-10/13 EA Guidelines on the Calibration of Temperature Block Calibrators PURPOSE This document been produced by EA to improve the harmonisation in the calibration of temperature

More information

Measuring Humidity in the Charters of Freedom Encasements Using a Moisture Condensation Method

Measuring Humidity in the Charters of Freedom Encasements Using a Moisture Condensation Method Measuring Humidity in the Charters of Freedom Encasements Using a Moisture Condensation Method Speaker: Cecil G. Burkett NASA Langley Research Center Mail Stop 236 Hampton VA 23681 PH: 757-864-4720 FAX:

More information

Introduction to Infrared Thermometry

Introduction to Infrared Thermometry TS-104 Introduction to Infrared Thermometry Fig. 1 - Blackbody Radiation Characteristics General Infrared thermometers have the ability to measure temperature without physical contact. The ability to accomplish

More information

IBHS Roof Aging Program Data and Condition Summary for 2015

IBHS Roof Aging Program Data and Condition Summary for 2015 IBHS Roof Aging Program Data and Condition Summary for 2015 Ian M. Giammanco Tanya M. Brown-Giammanco 1 Executive Summary In 2013, the Insurance Institute for Business & Home Safety (IBHS) began a long-term

More information

Memorandum. Air Sampling

Memorandum. Air Sampling Memorandum TO: David Yelton, City of Beverly Hills DATE: December 8, 2015 CC: Heidi Rous, PCR Services FROM: Everest Yan and Audrey Vinant Tang, PCR Services RE: BEVERLY HILLS ARSENIC MONITORING MEMO This

More information

August 3,1999. Stiffness and Strength Properties for Basic Sandwich Material Core Types UCRL-JC B. Kim, R.M. Christensen.

August 3,1999. Stiffness and Strength Properties for Basic Sandwich Material Core Types UCRL-JC B. Kim, R.M. Christensen. Preprint UCRL-JC-135347 Stiffness and Strength Properties for Basic Sandwich Material Core Types B. Kim, R.M. Christensen This article was submitted to ASME IMECE 99, Nashville, TN, November 14-19, 1999

More information

TEST METHOD FOR STILL- AND FORCED-AIR JUNCTION-TO- AMBIENT THERMAL RESISTANCE MEASUREMENTS OF INTEGRATED CIRCUIT PACKAGES

TEST METHOD FOR STILL- AND FORCED-AIR JUNCTION-TO- AMBIENT THERMAL RESISTANCE MEASUREMENTS OF INTEGRATED CIRCUIT PACKAGES SEMI G38-0996 N/A SEMI 1987, 1996 TEST METHOD FOR STILL- AND FORCED-AIR JUNCTION-TO- AMBIENT THERMAL RESISTANCE MEASUREMENTS OF INTEGRATED CIRCUIT PACKAGES 1 Purpose The purpose of this test is to determine

More information

Weathertightness testing of Solar Slate Plate to MCS012. Prepared for: Michael Share. Solar Slate Plate. 24 th June Test report number

Weathertightness testing of Solar Slate Plate to MCS012. Prepared for: Michael Share. Solar Slate Plate. 24 th June Test report number Weathertightness testing of Solar Slate Plate to MCS012 Prepared for: Michael Share Solar Slate Plate 24 th June 2014 Prepared by Name Mr Devinder Athwal Position Laboratory technician, Building Technology

More information

Standard Practice for Heat Aging of Plastics Without Load 1

Standard Practice for Heat Aging of Plastics Without Load 1 Designation: D 3045 92 (Reapproved 2003) Standard Practice for Heat Aging of Plastics Without Load 1 This standard is issued under the fixed designation D 3045; the number immediately following the designation

More information

Township 34 North, Range 9 West, NMPM (NUL) Section 3: E/2

Township 34 North, Range 9 West, NMPM (NUL) Section 3: E/2 BEFORE THE OIL AND GAS CONSERVATION COMMISSION OF THE STATE OF COLORADO IN THE MATTER OF THE APPLICATION OF CHEVRON MIDCONTINENT, L.P., IGNACIO-BLANCO FIELD, LA PLATA COUNTY, COLORADO. CAUSE NO. 112 DOCKET

More information

Page 2 of 14 Report Ref. No

Page 2 of 14 Report Ref. No age 2 of 14 Summary of testing: Tests performed (name of test and test clause): Clause 6.1, Initial measurements: - MST 01: Visual inspection - 10.2: Maximum power determination - MST 16: Dielectric withstand

More information

THERMAL PROPERTY MEASUREMENT TECHNIQUES. AND SOME RESULTS FOR CdTe. H. F. Poppendiek D. J. Connelly R. K. Livett

THERMAL PROPERTY MEASUREMENT TECHNIQUES. AND SOME RESULTS FOR CdTe. H. F. Poppendiek D. J. Connelly R. K. Livett THERMAL PROPERTY MEASUREMENT TECHNIQUES AND SOME RESULTS FOR CdTe H. F. Poppendiek D. J. Connelly R. K. Livett QUARTERLY REPORT NO. 1 PERIOD: MARCH 10 TO JUNE 10, 1983 "The views and conclusions contained

More information

DEVELOPMENT OF THE MEASURING SYSTEM FOR ANALYSING THE THERMAL PROPERTIES OF CLOTHING

DEVELOPMENT OF THE MEASURING SYSTEM FOR ANALYSING THE THERMAL PROPERTIES OF CLOTHING DEVELOPMENT OF THE MEASURING SYSTEM FOR ANALYSING THE THERMAL PROPERTIES OF CLOTHING Dubravko ROGALE; Snježana FIRŠT ROGALE & Ivana ŠPELIĆ Abstract:The measuring system for assessing static and dynamic

More information

This page left blank.

This page left blank. This page left blank. FP-14-44 ii TABLE OF ONTENTS MULTIPLE LOATION QUALIFIATION... i LIST OF TABLES... iv LIST OF FIGURES... iv LIST OF SYMBOLS...v TEST RESULTS...1 TEST DESRIPTION... 21 1. INTRODUTION...

More information

Determining of Thermal Conductivity Coefficient of Pressed Straw (Name of test)

Determining of Thermal Conductivity Coefficient of Pressed Straw (Name of test) CONSTRUCTION HEAT PHYSICS LABORATORY INSTITUTE OF ARCHITECTURE AND CONSTRUCTION OF KAUNAS UNIVERSITY Test and calculation carried out according to: Product: 12 December 2012 LITHUANIAN NATIONAL ACCREDITATION

More information

Certificate of Accreditation

Certificate of Accreditation PERRY JOHNSON LABORATORY ACCREDITATION, INC. Certificate of Accreditation Perry Johnson Laboratory Accreditation, Inc. has assessed the Laboratory of: (Hereinafter called the Organization) and hereby declares

More information

Lincoln County Board of Commissioner s Agenda Item Cover Sheet

Lincoln County Board of Commissioner s Agenda Item Cover Sheet Lincoln County Board of Commissioner s Agenda Item Cover Sheet Board Meeting Date: Agenda Item Type: Consent Agenda: Public Hearing: Regular Agenda: Presentation Time (est): Submitting Person: Phone Number/Ext:

More information

CONSTRUCTION MATERIALS

CONSTRUCTION MATERIALS CONSTRUCTION MATERIALS T E C H N O L O G I E S PERFORMANCE TEST REPORT FOR Southern Manufacturing Division of Accord Industries IN ACCORDANCE WITH FLORIDA BUILDING CODE (HIGH VELOCITY HURRICANE ZONES)

More information

Correlation of SODAR and Meteorological Tower Measurements. Prepared for: West Virginia Division of Energy

Correlation of SODAR and Meteorological Tower Measurements. Prepared for: West Virginia Division of Energy Correlation of SODAR and Meteorological Tower Measurements Prepared for: West Virginia Division of Energy 4/18/2011 CORRELATION OF SODAR AND MET TOWER MEASUREMENTS Authors: Principal Investigator: Christine

More information

Standard Test Method for Flat Particles, Elongated Particles, or Flat and Elongated Particles in Coarse Aggregate 1

Standard Test Method for Flat Particles, Elongated Particles, or Flat and Elongated Particles in Coarse Aggregate 1 Designation: D479 0 Standard Test Method for Flat Particles, Elongated Particles, or Flat and Elongated Particles in Coarse Aggregate This standard is issued under the fixed designation D479; the number

More information

A visual inspection, and collection of 10 asbestos PCM samples and 12 air-o-cell samples were utilized to perform this assessment

A visual inspection, and collection of 10 asbestos PCM samples and 12 air-o-cell samples were utilized to perform this assessment December 9, 2016 Ms. Alix Zapolski Zapolski Real Estate, LLC. 501 Washington Street Durham, NC 27701 Re: Limited Indoor Air Quality Assessment Asbestos & Microbial 137 E. Franklin Street, Chapel Hill,

More information

THERMAL CONDUCTIVITY OF BUILDING MATERIALS: AN OVERVIEW OF ITS DETERMINATION

THERMAL CONDUCTIVITY OF BUILDING MATERIALS: AN OVERVIEW OF ITS DETERMINATION 15 THERMAL CONDUCTIVITY OF BUILDING MATERIALS: AN OVERVIEW OF ITS DETERMINATION E Latif *, M Pruteanu *** and G R Rhydwen *, D C Wijeyesekera *, S Tucker **, M A Ciupala *, D Newport * * School of Computing,

More information

Thermodynamics. Thermodynamics is the study of the collective properties of a system containing many bodies (typically of order 10 23!

Thermodynamics. Thermodynamics is the study of the collective properties of a system containing many bodies (typically of order 10 23! Thermodynamics Thermodynamics is the study of the collective properties of a system containing many bodies (typically of order 10 23!) Chapter18 Thermodynamics Thermodynamics is the study of the thermal

More information

Fluid Power Institute Summary Report. Burst Pressure Evaluation Project #52224

Fluid Power Institute Summary Report. Burst Pressure Evaluation Project #52224 Fluid Power Institute Summary Report Burst Pressure Evaluation Project #52224 Test Completion Date: 7/31/2014 Test Specimen: Zero-Leak Gold Plugs (ZLGP) Client: EPCO Products, Inc. Milwaukee School of

More information

Test Report. Report Number: L14139 Date: Jul 21, Issued by: Dialight Optics Laboratory 1501 Route 34 South, Farmingdale, NJ 07727

Test Report. Report Number: L14139 Date: Jul 21, Issued by: Dialight Optics Laboratory 1501 Route 34 South, Farmingdale, NJ 07727 Test Report Report Number: L14139 Date: Jul 21, 2015 Issued by: 1501 Route 34 South, Farmingdale, NJ 07727 Test of one Vigilant Highbay Fixture Unit manufacturer: Dialight Corporation Unit model number:

More information

MOLEKULE INC. TEST REPORT

MOLEKULE INC. TEST REPORT MOLEKULE INC. TEST REPORT SCOPE OF WORK VOC Emissions on Part C Test 1 REPORT NUMBER 103658037GRR-002 ISSUE DATE 18-October-2018 PAGES 8 DOCUMENT CONTROL NUMBER Per GFT-OP-10 (6-March-2017) 2018 INTERTEK

More information

Controlled Environment Testing Report

Controlled Environment Testing Report Client: Controlled Environment Testing Report Services Conducted: Product Testing Project Contact: Stefan Hocom Project Manager: Stefan E. Hocom 323 Spreckels Drive, Ste. B Aptos, CA 95003 The final approval

More information

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 & ANSI/NCSL Z

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 & ANSI/NCSL Z SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 & ANSI/NCSL Z540-1-1994 PROTEMP MECHANICAL, INC. 3350 Scott Blvd, Bldg. #3 Santa Clara, CA 95054 Martin L. Reich Phone: 408 244 9821 CALIBRATION Valid To: August

More information

Certificate of Conformance

Certificate of Conformance Certificate of Conformance Product: Silver Impregnated Zeolite, Type Ag 400 G13 Mesh: 16 x 40 Mesh Part Number: AGX-4 Manufacturing Lot Number: 0507182-1 Purchase Order: Ref. Doc Number: Material Cure

More information

ACCEPTANCE PROCEDURE FOR ROMET ROTARY METER BODIES AND/OR MECHANICAL NON-CONVERTING AND CONVERTING MODULES

ACCEPTANCE PROCEDURE FOR ROMET ROTARY METER BODIES AND/OR MECHANICAL NON-CONVERTING AND CONVERTING MODULES ACCEPTANCE PROCEDURE FOR ROMET ROTARY METER BODIES AND/OR MECHANICAL NON-CONVERTING AND CONVERTING MODULES (RPB-01) Approved by: Date: SECTION PAGE # 1.0 Scope 2.0 Definitions 3.0 References 4.0 Inspection

More information

Double-Skin Facade in Low-Latitude: Study on the Absorptance, Reflectance, and Transmittance of Direct Solar Radiation

Double-Skin Facade in Low-Latitude: Study on the Absorptance, Reflectance, and Transmittance of Direct Solar Radiation ouble-skin Facade in Low-Latitude: Study on the Absorptance, Reflectance, and Transmittance of irect Solar Radiation G-LO 011 Rosady Mulyadi epartment of Architecture Faculty of Engineering Hasanuddin

More information