Designing the Data Center. Brian Hansen RCDD, CDT. Leviton Network Solutions Specification Engineer BICSI President

Size: px
Start display at page:

Download "Designing the Data Center. Brian Hansen RCDD, CDT. Leviton Network Solutions Specification Engineer BICSI President"

Transcription

1 Designing the Data Center Brian Hansen RCDD, CDT Leviton Network Solutions Specification Engineer BICSI President 00

2 Talking points What are Data Centers? Why Data Centers? The components of the Data Center Approaching the Data Center design Breakdown of the components The Applications Nuggets of information from TIA Grounding and Bonding from IEEE 00 Forward looking designs for Data Centers P

3 What is a Data Center? A place to locate computer, storage and networking devices safely and securely A place that provides un interruptable power needed to power a Company s mission critical devices A place that provides a temperature controlled environment for equipment to operate properly A place that provides connectivity to other devices inside and outside the data center

4 Components of the Data Center Physical space Raised flooring Electrical Standby Power Cooling Fire Suppression Physical security Physical access Cabling

5 Why are Data Centers Important? Passive connectivity Pass through Cross connect Wiring Closet CEO s, CFO s, CIO s and other senior mgmt don t spend much time and focus on closets Critical Applications ERP CRM SCM Back office ecommerce Data Center Critical Computing Systems Servers Storage Networking

6 The Approach

7 Designing a Data Center KISS Keep it simple sir Flexibility equipment changes Scalability K sq.ft. or M sq.ft. Modularity logical and master plan for equipment Standardize consistency and uniformity The Human Factor promote good habits Don t lose your sanity! Oops will happen. Work with Data Center Professionals

8 What is tiering? Tier Basic Tier Redundant Components Tier Concurrently Maintainable Tier Fault Tolerant Level of availability Percent Downtime per year Six nines. seconds Five nines. minutes and seconds Four nines. minutes and seconds Three nines. hours and minutes Two nines days, hours and 0 minutes

9 What is N? N = Maximum capacity needs N+ = Max. plus extra device(s) N+ = Max. plus extra device(s) N+ = Max. plus extra device(s) N* (N) = doubles need N* (N) = triples need Balance need versus cost and complexity of redundant systems

10 Flexibility Data Centers are not static use products that can be easily changed or moved. Cabinets that can accept various equipment Configurable Panels Outlets that can be changed with a cord

11 Modularity

12 Understanding the components

13 Physical space Data Center selection should consider: Seismic areas use earthquake resistant technologies Ice storms ensure backup generators can run for extended periods Hurricanes shelter against high winds Tornadoes no windows Flooding build on elevated ground Landslides have retention walls Fires install fire resistant walls and suppression systems

14 Physical space continued Polluted air limit outside air or use high filtration air systems EMI build away from sources of EMI Vibration stay away from railroads, airports, major thoroughfares Political climate labor issues and materials delay Flight paths distribute servers Service provider can you get enough bandwidth

15 Raised flooring Raised floor specification should address: Floor height for plenum is average Ensure there is enough ceiling height for heat exhaust Weight bearing capacity should be rated with same strength as sub floor Sub floor shall be sealed to prevent concrete dust ESD floors shall have static control No perforated tiles in main pathways heavy equipment being transported over them can break them Ramps should have a in incline, be in width and have landings on both ends or square for maneuvering equipment

16 Electrical Electrical specification should consider: Separate power sources building system power feed shall be isolated from server equipment power feed Bypass have maintenance bypass options for normal maintenance without taking down equipment Pre wire cabinet locations adds more upfront cost but less disruptive PDU loads do not load circuits more than 0 percent Use whips flexibility for moving power Receptacles limit to per circuit Heavy gauge wire 0 AWG is better than AWG Run six 0 AWG wires phase conductors, neutral, equipment ground and isolated ground Labeling label the circuit and location in circuit panel Convenience outlets do not tie into equipment power feed

17 Rack / Cabinet mounted PDUs

18 Standby power Standby power should be specified with the following considerations: Sizing of UPS Use peak load and not operating load Uptime should be a minimum of 0 minutes at full load with generator backup or hours without a generator backup Generators should be designed into your Data Center if uptime will be critical for extended outages in the area Battery room ensure adequate ventilation Monitoring lights utilize color coded domes and wire the lights into the various backup systems for instant visual clues such as red for UPS and blue for generator

19 Hot and cold aisles Front Power bank HOT tile can output KW BTU s Front For every degrees above ambient temp. (F-F) reduces equipment life by ½ Intel

20 The Applications

21 High Performance Computer Clustering CISCO CSS 000 SERIES CONTENT SERVICES SWITCH 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X CISCO CSS 000 SERIES CONTENT SERVICES SWITCH 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X System p System p System p System p System p System p System p System p System p System p System p System p System p System p System p System p System p System p System p System p System p System p System p System p 0 Gigabit Fiber Link Gigabit Copper Link Gigabit Copper Link Research, financial modeling, digital image rendering and scientific applications Aggregate four 0GBASE-T links to achieve 0 Gig. 0 Gigabit copper link 0 Gigabit copper link 0 Gigabit copper link

22 Network Attached Storage CISCO CSS 000 SERIES CONTENT SERVICES SWITCH 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X CISCO CSS 000 SERIES CONTENT SERVICES SWITCH 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X LAN p p p p p p 0 Gigabit Ethernet Servers 0 Gigabit Ethernet Servers NAS device NAS device Quick transfer of large files All 0GBASE-T links

23 Storage Area Network (SAN) CISCO CSS 000 SERIES CONTENT SERVICES SWITCH 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X 0/00 X X X X X X X X System p System p System p System p System p System p System p System p System p System p System p System p SAN SAN Storage arrays, tape drives Servers Data mining from large repositories of data Upgrade to 0GBASE-T Gig. Fibre Channels GBASE-T links Move to 0GBASE-T using iscsi

24 Cabling

25 TIA Telecommunications Infrastructure Standard for Data Centers What kind of information can I find in the document? Scope Definition Design Overview Cabling system overview Cabling system infrastructure Telecommunications spaces and Related Topologies DC cabling systems DC cabling pathways DC redundancy Multiple Annexes

26 Cabling Topologies Direct Connect Distributed

27 Power Supply Power Supply Catalyst 00 SERIES FAN THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY Sample Application SD SD SD SD SD SD SD SD WS-X-GE-TX P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET WS-X-GE-TX P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET WS-X-GE-TX P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET WS-X-GE-TX P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET WS-X-GE-TX P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET WS-X-GE-TX P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET WS-X-GE-TX P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET WS-X-GE-TX P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET WS-X-GE-TX P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET

28 Power Supply Power Supply Catalyst 00 SERIES FAN THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY Patch Cord into Server Sample Application SD SD SD SD SD SD SD SD WS-X-GE-TX P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET WS-X-GE-TX P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET WS-X-GE-TX P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET 0 WS-X-GE-TX P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET WS-X-GE-TX P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET WS-X-GE-TX P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET 0 WS-X-GE-TX P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET WS-X-GE-TX P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET WS-X-GE-TX P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET 0

29 Switch STAT Power Power Supply Supply Catalyst 00 SERI Zone Distribution Area FA N US THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY ES SD SD SD SD SD SD SD SD WS-X-GE-TX P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET 0 0 WS-X-GE-TX P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET WS-X-GE-TX P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET WS-X-GE-TX P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET 0 0 WS-X-GE-TX P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET 0 0 WS-X-GE-TX P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET 0 0 WS-X-GE-TX P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET 0 0 WS-X-GE-TX P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET 0 0 WS-X-GE-TX P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET 0 0

30 Data Center topology

31 Labeling the floor X Coordinate AA AB AC AD AE AF AG AH AI AJ AK AL AM AN Right Front Corner Sample Cabinet Y Coordinate Sample Cabinet Identifier: AJO

32 Sample of Panel Identifiers on Rack

33 design guidelines In addition to satisfying today s telecommunication requirements, the horizontal cabling should be planned to reduce ongoing maintenance and relocation. It should also accommodate future equipment and service changes. Consideration should be given to accommodating a diversity of user applications in order to reduce or eliminate the probability of requiring changes to the horizontal cabling as equipment needs evolve. Change your equipment and not your cabling!!! Minimum of Category is recommended. Minimum of Laser Optimized 0 micron is recommended.

34 Application: Frequency spectrum requirements 0GBASE-T GBASE-T 00BASE-T 0BASE-T *Shaded ovals show range & concentration of frequencies for Ethernet protocols MHZ

35 Characteristics of the A cable Larger copper conductor up to AWG Shorter twist ratios on pairs. Larger O.D. (UTP) up to. Grooved offset overall jacket (UTP) 00 Ohm impedance Backwards compatible with existing e and applications Interoperable with other Categories Utilizes and PC plug/jack interface Engineered to eliminate Alien Crosstalk Cat A Cat

36 Cross section of A UTP

37 Cross section of A F/UTP AWG tinned copper solid

38 design guidelines Transmission Differences MM vs. SM Systems

39 Differential Modal Delay

40 design guideline continued Power strips shall be labeled with the PDU/panel identifier and circuit breaker number. Racks that are supported by the access floor shall be bolted to the cement slab or a metal channel secured to the slab by threaded rods that penetrate through the floor tiles. Sharp edges on the top of the threaded rods shall be covered using domed nuts or other method. Exposed threads under the access floor should be covered using split tubing or other method. Power strips with indicators but no on/off switch or breaker reset button should be used to minimize accidental shut off.

41 Forward looking design

42 Overhead conveyance or underfloor?

43 Utilize pre terminated Category A systems Draft 0 was approved in Tampa Great for quick network deployment Excellent Channel to Channel characteristics Ideal for data center Server Row designs Lifetime System Warranty No field testing required at all 00% performance tested at factory to TIA CATA UTP or STP cables secured in braided sleeve Jack to Jack or Jack to Open configurations

44 Utilize pre terminated MTP design Consider OM fiber Great for quick network deployment Cabling harness can be changed for new equipment Excellent Channel to Channel characteristics Ideal for data center connector low loss channels Lifetime System Warranty No field testing required at all 00% performance tested at Factory MTP - SC Duplex MTP - LC Duplex MTP - MT-RJ

45 Advantages of Trunks Direct (Point-to-Point) Jumper Cable Installation Distributed Optical PnP Cabling Solution 00 Jumper Cables Trunk Cables

46 Standard Design Plug & Play Topologies Total Loss =.db

47 Standard Design Plug & Play Topologies PNP Topology Issues: Use of MTP Cassette per Cassette Total Path Loss =.db 0Gig Path Budget =.db Flexibility of MTP Not Exploited Requires use of Hybrid Jumper for Future Migration.dB Over Budget 0 Gig Ready

48 Plug & Play: Alternate Building Blocks Plug & Play is more than MTP Cassettes MTP Brackets: Reduce number of Hops Reduce System Loss Reduce System Cost Work above the Floor

49 Alternative Design Plug & Play Topology Total Loss =.0dB

50 Alternative Design Plug & Play Topologies Alternative Plug & Play Topology Advantages: Use of MTP Bracket & Harness per Interface Total Path Loss =.0dB 0Gig Path Budget =.db Flexibility of MTP Fully Exploited Simplified Future Migration Requires Harness Change Out Head Room = 0.dB 0 Gig Ready Allows for Organized Trunk Pre Cabling for Future Expansion

51 See what your equipment looks like Trunk / Harness Technology Simplifies administration Fan Intake Remains Clear Proper Bend Radius Adherence Simplifies Visual Identification Future Growth Is Built In Allows Pre Cabling to Cabinets for Rapid Deployment (servers) Consistent Channel to Channel Characteristics Trunk Cable Feed From Under floor

52 Switch or Server Cabinet Options x CATA UTP ports in U Minimizes server or switch cabinet rack space panel options Standard Flat Angled Recessed Angled

53 Never worry about wiring cabinets again Reduces cabling/congestion inside of cabinet Allows for copper and/or fiber connectivity Supports 0G connectivity No need to wait on cabinets for your data center projects!! P

54 Copper Switch Topology Foundry Example

55 Copper Topology Comm to Server Row

56 SAN Switch Topology Cisco Example P //00

57 The Data Center Professional

58 Great Communicator!! Value added services Understands your current and future requirements Understands codes and standards Deploys design methods that allows you to change your equipment and not cabling Can provide detailed documentation to all parties Calm and steady head

59 Summary Simplify Build it for scalability Build it using modularity Changes to your design can impact other areas Remove the oops factor by planning Associate and network with other Data Center professionals

60 Thank you for your time!

CLASSix UTP Patch Cords

CLASSix UTP Patch Cords Features Patch Cords are used in the work area and cross-connect generic cabling applications Comprise a length of eight-wire flexible patch cable, terminated with snagless high quality, two eight-position

More information

Qualification Test Report. Modular Plugs, Unshielded and Shielded

Qualification Test Report. Modular Plugs, Unshielded and Shielded Qualification Test Report 501-131013 26 JAN 16 Rev. A Modular Plugs, Unshielded and Shielded 1. INTRODUCTION 1.1. Purpose Testing was performed on modular plugs to determine their conformance to the requirements

More information

INFORMATION TECHNOLOGY SYSTEMS SPDs FOR 19 TECHNOLOGY. NET Protector Surge Arrester. Protects switches, HUBs and telecommunication

INFORMATION TECHNOLOGY SYSTEMS SPDs FOR 19 TECHNOLOGY. NET Protector Surge Arrester. Protects switches, HUBs and telecommunication Surge Arrester Protects switches, HUBs and telecommunication systems Class D according to EN 0 possible (Gigabit Ethernet) Variably equippable patch panels Units available with plug-in inputs and outputs

More information

Catalogue. Make communication more convenient! SHENZHEN LIANXUN INDUSTRIES CO.,LTD. Distributed by SHENZHEN LIANXUN INDUSTRIES CO.,LTD.

Catalogue. Make communication more convenient! SHENZHEN LIANXUN INDUSTRIES CO.,LTD. Distributed by SHENZHEN LIANXUN INDUSTRIES CO.,LTD. Make communication more convenient! Distributed by Catalogue SHENZHEN LIANXUN INDUSTRIES CO.,LTD. W: www.lansancable.com T: +86 755 849 7 F: +86 755 849 33 A: B3 Building, 99 Tongxin Industrial Park, Tongxin

More information

Zone distribution boxes

Zone distribution boxes 87045 LIMOGES Cedex France Telephone: (+33) 05 55 06 87 87 - Fax: (+33) 05 55 06 88 88 CONTENTS Page 1. General characteristics....1 2. Presentation...2 3. Use scenarios....3 4. Technical characteristics...3

More information

SC125MS. Data Sheet and Instruction Manual. ! Warning! Salem Controls Inc. Stepper Motor Driver. Last Updated 12/14/2004

SC125MS. Data Sheet and Instruction Manual. ! Warning! Salem Controls Inc. Stepper Motor Driver.   Last Updated 12/14/2004 SC125MS Stepper Motor Driver Salem Controls Inc. Last Updated 12/14/2004! Warning! Stepper motors and drivers use high current and voltages capable of causing severe injury. Do not operate this product

More information

SECTION 1 - WHAT IS A BTU METER? BTU's = Flow x ΔT Any ISTEC BTU Meter System consists of the following main components:

SECTION 1 - WHAT IS A BTU METER? BTU's = Flow x ΔT Any ISTEC BTU Meter System consists of the following main components: SECTION 1 - WHAT IS A BTU METER? ISTEC BTU Meters measure energy usage by multiplying flow rate and temperature difference. As the water (or other liquid) passes through these lines, the multi-wing turbine

More information

16 Input AC Block I/O Module

16 Input AC Block I/O Module 6 Input AC Module Cat. No. 79-6A0 Series B Installation Mount the block I/O module in a vertical (recommended) or horizontal position. Allow sufficient room around the block for cooling air flow through

More information

32 Input AC Block I/O Module

32 Input AC Block I/O Module Input AC Module Cat. No. 79-A0 Series B Installation Mount the block I/O module in a vertical (recommended) or horizontal position. Allow sufficient room around the block for cooling air to flow through

More information

BEFORE USE... POINTS OF CAUTION COMPONENT IDENTIFICATION INSTRUCTION MANUAL MODEL R7K4DH-1-DAC32D R7K4DH-1-DAC32D

BEFORE USE... POINTS OF CAUTION COMPONENT IDENTIFICATION INSTRUCTION MANUAL MODEL R7K4DH-1-DAC32D R7K4DH-1-DAC32D INSTRUCTION MANUAL PNP DISCRETE INPUT & PNP TRANSISTOR OUTPUT MODULE, 6 points each (High-speed Link System, e-con connector) R7KDH--DACD MODEL R7KDH--DACD BEFORE USE... Thank you for choosing M-System.

More information

technical bulletin Installation Instructions: Wall-Mount Dewpoint Probe ( )

technical bulletin Installation Instructions: Wall-Mount Dewpoint Probe ( ) Installation Instructions: Wall-Mount Dewpoint Probe (809-2011) The HMW90 Wall-Mount Dewpoint Probe (P/N 809-2011) HMW90 measures dewpoint for indoor applications such as anti-sweat heater control and

More information

The Ordering Code for various standard model Recorders with an AC supply and without any additional options are as follows:

The Ordering Code for various standard model Recorders with an AC supply and without any additional options are as follows: The basic PC software is supplied free with the recorder. There is an additional charge for the extensive Data Acquisition Software supplied with communication of RS-232/422/485 or Ethernet. The Ordering

More information

OASIS WIRELESS WEATHER STATION

OASIS WIRELESS WEATHER STATION User Manual 3910-B Royal Avenue, Simi Valley, Ca 93063 805-527-4498 RMIS Part No. 500760 TABLE OF CONTENTS INTRODUCTION General Description 3 General Precautions 3 INSTALLATION Base Preparation 6 Tower

More information

DATA RACK BUSBAR. Data Rack Busbar Systems A.

DATA RACK BUSBAR. Data Rack Busbar Systems A. Data Rack Busbar Systems 250...1000 A www.eae.com.tr Overview Overview To power the mission critical IT infrastructures on the Data Rack Cabinets, EAE offers a highly flexible and reliable Busbar System

More information

2014 / GST Jack System. Better Technology Through Innovation

2014 / GST Jack System. Better Technology Through Innovation 2014 / 2015 Better Technology Through Innovation Introduction The GST jack from HellermannTyton is a compact high performance UTP RJ45 connector. The solution includes Category 6A, Category 6 and Category

More information

3VT4 Molded Case Circuit Breakers up to 1000 A

3VT4 Molded Case Circuit Breakers up to 1000 A VT4 Molded Case Circuit Breakers up to 00 A Catalog Technical nformation VT4 Molded Case Circuit Breakers up to 00 A General data / - Overview Circuit breakers Switch disconnectors / - Selection and ordering

More information

Issued August DATA SHEET. 3VT3 MCCB up to 630 A

Issued August DATA SHEET. 3VT3 MCCB up to 630 A ssued August 9 DATA SHEET VT MCCB up to 6 A Based on Siemens Catalog V 6 8 Circuit breakers Switch disconnectors Technical specifications Specifications Type VT 76-AA6/6/56-AA, VT 76-AA6/6/56-AA Circuit

More information

Series 3000 and XE-Series Engineering Data

Series 3000 and XE-Series Engineering Data Series 3000 and XE-Series Engineering Data A C A U S T R A L I A Series 3000 and XE-Series Engineering Data The NEW era of Series 3000 and XE-Series Cooling Towers continue to exceed the industry standard

More information

OPERATION MANUAL. 3 in 1, IR, Type K/J/R/E/T, Pt 100 ohm THERMOMETER. Model : TM-2000

OPERATION MANUAL. 3 in 1, IR, Type K/J/R/E/T, Pt 100 ohm THERMOMETER. Model : TM-2000 3 in 1, IR, Type K/J/R/E/T, Pt 100 ohm THERMOMETER Model : TM-2000 Your purchase of this THERMOMETER marks a step forward for you into the field of precision measurement. Although this THERMOMETER is a

More information

Issued August DATA SHEET. 3VT5 MCCB up to 1600 A

Issued August DATA SHEET. 3VT5 MCCB up to 1600 A ssued August 9 DATA SHEET VT5 MCCB up to 0 A Based on Siemens Catalog V 8 Standard circuit breakers Releases Technical specifications Specifications VT5 circuit breakers Switch disconnectors Type Standards

More information

Installation guide 862 MIT / MIR

Installation guide 862 MIT / MIR Installation guide 862 MIT / MIR in combination with: 864 MTT or 863 MRT or (dual) spot element November 2005 Part no. 4416.232_Rev3 Enraf BV PO Box 812 2600 AV Delft Netherlands Tel. : +31 15 2701 100

More information

Flexitest Switch Assemblies Type FT-19R and FT-19RX Supersedes DB March 2008

Flexitest Switch Assemblies Type FT-19R and FT-19RX Supersedes DB March 2008 Flexitest Switch Assemblies Type FT-19R and FT-19RX Supersedes DB41-078 March 2008 FT-19R and FT-19RX FT-19R 3RU with Individual Clear Covers APPLICATION FEATURES The type FT-19R (standard length) and

More information

ISOCON-6. 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER

ISOCON-6. 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER ISOCON-6 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER Whilst every effort has been taken to ensure the accuracy of this document, we accept no responsibility for damage, injury, loss or expense resulting

More information

Installation and Operation Manual. AllSync Plus Wired Clocks

Installation and Operation Manual. AllSync Plus Wired Clocks and Operation Manual AllSync Plus Wired Clocks Part # H004881 Rev. 4 September 2018 Safety Precautions AllSync Plus Clock & Operation Manual Troubleshooting General Operation Introduction Safety Precautions

More information

Multi-function, economical instrument with 4 functions in the same casing. Accessibility and safety: large-dimension terminals Insulated circuits

Multi-function, economical instrument with 4 functions in the same casing. Accessibility and safety: large-dimension terminals Insulated circuits 200 > Measurement and instrumentation Programmable digital transducers TRIAD 2 range Programmable digital transducers with to 4 analogue outputs Programmable accuracy class PRODUCT ADVANTAGES Up to 4 PROGRAMMABLE

More information

iweathar EDGE V Installation Guide Copyright 2012 iweathar. All rights reserved.

iweathar EDGE V Installation Guide Copyright 2012 iweathar. All rights reserved. iweathar EDGE V Installation Guide Copyright 2012 iweathar. All rights reserved. Table of contents: 1 Introduction...3 2 Station Components...4 3 STATION INSTALLATION PROCEDURE...5 4 Specifications...11

More information

Operating Instructions for Digital Manometer. Model: MAN-SD

Operating Instructions for Digital Manometer. Model: MAN-SD Operating Instructions for Digital Manometer Model: MAN-SD 1. Contents 1. Contents...2 2. Note...3 3. Instrument Inspection...3 4. Regulation Use...4 5. Operating Principle...4 6. Mechanical Connection...5

More information

Alternating Current (AC): Alternating Current is electric current that reverses directions at regular intervals.

Alternating Current (AC): Alternating Current is electric current that reverses directions at regular intervals. Glossary Alternating Current (AC): Alternating Current is electric current that reverses directions at regular intervals. American National Standards Institute (ANSI): American National Standards Institute

More information

THE ENERGY 68,SAVING TDVI. exible Combine Modular 24, 26, 28, 30, 32, 34, 36, 38, 40, 42, 44 HP 60, 62, 64, 66 HP

THE ENERGY 68,SAVING TDVI. exible Combine Modular 24, 26, 28, 30, 32, 34, 36, 38, 40, 42, 44 HP 60, 62, 64, 66 HP I N V E RT E R ion Range exible Combine Modular TDV I TDV I TDV I INVERTER INVERTER INVERTER 14, 16, 18, 20, 22 HP TDV I 24, 26, 28, 30, 32, 34, 36, 38, 40, 42, 44 HP INVERTER INVERTER INVERTER TDV I INVERTER

More information

Peterborough Distribution Inc Ashburnham Drive, PO Box 4125, Station Main Peterborough ON K9J 6Z5

Peterborough Distribution Inc Ashburnham Drive, PO Box 4125, Station Main Peterborough ON K9J 6Z5 Peterborough Distribution Inc. 1867 Ashburnham Drive, PO Box 4125, Station Main Peterborough ON K9J 6Z5 November 15, 2017 Ontario Energy Board PO Box 2319 27 th Floor, 2300 Yonge St Toronto ON M4P 1E4

More information

Common Lightcloud Wiring Applications. Wiring Diagrams. Overview Controller Dimmer Gateway Integrator Sensor Touch. Lightcloud

Common Lightcloud Wiring Applications. Wiring Diagrams. Overview Controller Dimmer Gateway Integrator Sensor Touch. Lightcloud Common Lightcloud Wiring Applications Wiring Diagrams Overview Dimmer Gateway Integrator Sensor Touch Lightcloud Wiring Diagrams The following diagrams are commonly used for Lightcloud installations. If

More information

xlogic SuperRelay is a compact and expandable CPU replacing mini PLCs, multiple timers, relays and counters.

xlogic SuperRelay is a compact and expandable CPU replacing mini PLCs, multiple timers, relays and counters. SuperRelay S U P E R R E L A Y, T H E P E R F E C T A L T E R N A T I V E T O L O W C O S T P L C s A N D B A S I C R E L A Y S I N T H I S B R O C H U R E : ELC 18 Standard Models ELC 18 Economy Models

More information

5SJ4...-.HG Circuit Breakers to IEC and UL 489

5SJ4...-.HG Circuit Breakers to IEC and UL 489 Siemens AG 009 5SJ...-.HG Circuit Breakers to IEC and UL 89 BETA Low-Voltage Circuit Protection Compliance with industry standards is a must in today's manufacturing environment. Worldwide acceptance is

More information

Impedance relay and protection assemblies

Impedance relay and protection assemblies RXZK 21H, 22H, 23H 509 006-BEN Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970175) (SE970184) Features Micro-processor based impedance relay with R and X settings

More information

Device Specifications

Device Specifications Manual Device Specifications PART NUMBER LCGATEWAY ELECTRICAL The Lightcloud Gateway is designed to be hard-wired to AC power by a qualified electrician. INPUT 120-277 VAC, 50/60 Hz 60-45mA BATTERY Li-ion

More information

Latest generation testo air velocity & IAQ probes with cable handle. Instruction manual

Latest generation testo air velocity & IAQ probes with cable handle. Instruction manual Latest generation testo air velocity & IAQ probes with cable handle Instruction manual Contents Contents 1 About this document... 5 2 Safety and disposal... 5 3 System description... 6 4 Description of

More information

www. ElectricalPartManuals. com Flexitest Switch Assemblies Type FT-19R and FT-19RX INTL APPLICATION

www. ElectricalPartManuals. com Flexitest Switch Assemblies Type FT-19R and FT-19RX INTL APPLICATION Effective: January 2004 Supersedes, dated June 1998 APPLICATION QUALITY FEATURES Descriptive Bulletin 41-078INTL Flexitest Switch Assemblies Type The type FT-19R (standard length) and FT-19RX (extended

More information

Field Pro Operation and Installation Manual

Field Pro Operation and Installation Manual Field Pro Operation and Installation Manual Xtreme Research Corporation SkyScan Division P.O. Box 336, Port Richey, FL 34673-0336 1-800-732-0665 Table of Contents 1. Installation 3 2. Operation 5 3. Care

More information

HyperPlus 5e Plenum. Contact Copper LAN Product Inquiry Phone:

HyperPlus 5e Plenum. Contact Copper LAN Product Inquiry Phone: Berk-Tek's HYPER PLUS 5e Standard Category 5e UTP Cables are designed for horizontal network and voice applications in a structured cabling network to connect between the user outlet and horizontal cross-connect.

More information

VX25 Enclosure System. Technical documentation PE conductor connection, current carrying capacity

VX25 Enclosure System. Technical documentation PE conductor connection, current carrying capacity VX Enclosure System Technical documentation PE conductor connection, current carrying capacity Enclosure system VX Contents Contents. General remarks. Introduction. Notes on the design of the earthing

More information

POINTS OF CAUTION BEFORE USE...

POINTS OF CAUTION BEFORE USE... INSTRUCTION MANUAL NPN DISCRETE INPUT & NPN TRANSISTOR OUTPUT MODULE, 6 points each (-I/-II, e-con connector) MODEL BEFORE USE... Thank you for choosing M-System. Before use, check the contents of the

More information

1. Wind turbines are designed to operate within specified design criteria. Often the operating environment extends beyond these limits and causes

1. Wind turbines are designed to operate within specified design criteria. Often the operating environment extends beyond these limits and causes 1 2 1. Wind turbines are designed to operate within specified design criteria. Often the operating environment extends beyond these limits and causes outages. How these outages are classified can be challenging

More information

COPPER FOR BUSBARS CHAPTER 4: SHORT-CIRCUIT EFFECTS

COPPER FOR BUSBARS CHAPTER 4: SHORT-CIRCUIT EFFECTS European Copper Institute COPPER FOR BUSBARS CHAPTER 4: SHORT-CIRCUIT EFFECTS David Chapman August 2011 ECI Available from www.leonardo-energy.org Document Issue Control Sheet Document Title: Publication

More information

Performance Specifications. SYSTIMAX InstaPATCH 360 Fiber TAP Solution VOLUME FIVE. June 18, 2014

Performance Specifications. SYSTIMAX InstaPATCH 360 Fiber TAP Solution VOLUME FIVE. June 18, 2014 SYSTIMAX InstaPATCH 360 Fiber TAP Solution VOLUME FIVE June 18, 2014 Performance Specifications Contents Introduction 3 Ethernet Applications 4 100 Gigabit Ethernet, 1310 nm WDM (100GBASE-LR4) 4 40 Gigabit

More information

473-SHX Dew Point Mirror

473-SHX Dew Point Mirror Humidity and Temperature Reference Hygrometer For Temperature up to 125 C Precise and stable chilled mirror dew point mirror technology High temperature optical components High temperature sample fan Cable

More information

WE RE HERE TO HELP: 1 (844) LIGHTCLOUD

WE RE HERE TO HELP: 1 (844) LIGHTCLOUD Welcome Controller LCCONTROL20/D10 WE RE HERE TO HELP: 1 (844) LIGHTCLOUD 1 (844) 544-4825 support@lightcloud.com Contents Lightcloud Controller NPT Nut O-ring Instruction Manual Wire Nuts x 4 x 2 Specifications

More information

RC Circuit (Power amplifier, Voltage Sensor)

RC Circuit (Power amplifier, Voltage Sensor) Object: RC Circuit (Power amplifier, Voltage Sensor) To investigate how the voltage across a capacitor varies as it charges and to find its capacitive time constant. Apparatus: Science Workshop, Power

More information

Technical Note Series

Technical Note Series Technical Note Series INCLINOTRAC (T7650) & DUAL-INCLINOTRAC (T7655) S TN0011-0 0 I n c l i n o T r a c / D u a l - I n c l i n o T r a c Page 2 IMPORTANT OPERATION INFORMATION Type BF Equipment Internally

More information

Circular Motion and Centripetal Force

Circular Motion and Centripetal Force [For International Campus Lab ONLY] Objective Measure the centripetal force with the radius, mass, and speed of a particle in uniform circular motion. Theory ----------------------------- Reference --------------------------

More information

data sheet DONATELLO FAST General characteristics Rev. First emission - 01/07/ PRO02 code

data sheet DONATELLO FAST General characteristics Rev. First emission - 01/07/ PRO02 code DONATELLO FAST Automatic floor closed cycle tissue processor for histological specimens Automatic tissue processor for histological specimens DONATELLO FAST code PRO0 RI General characteristics DONATELLO

More information

Assembly and Operation Manual. April 2016

Assembly and Operation Manual. April 2016 Assembly and Operation Manual April 2016 Table of Contents What is in the OurWeather Box? 3 Step by Step Assembly 13 Building the Weather Sensors 18 Testing the OurWeather Weather Station 28 Power Up OurWeather

More information

Overlay Transport Virtualization (OTV) Unicast-Mode Transport Infrastructure Deployment

Overlay Transport Virtualization (OTV) Unicast-Mode Transport Infrastructure Deployment Overlay Transport Virtualization (OTV) Unicast-Mode Transport Infrastructure Deployment July 24, 2012 ALL DESIGNS, SPECIFICATIONS, STATEMENTS, INFORMATION, AND RECOMMENDATIONS (COLLECTIVELY, "DESIGNS")

More information

Lecture (07) Electric Current and Resistance By: Dr. Ahmed ElShafee Dr. Ahmed ElShafee, ACU : Spring 2015, Physics II

Lecture (07) Electric Current and Resistance By: Dr. Ahmed ElShafee Dr. Ahmed ElShafee, ACU : Spring 2015, Physics II Lecture (07) Electric Current and Resistance By: Dr. Ahmed ElShafee ١ The glow of the thin wire filament of a light bulb is caused by the electric current passing through it. Electric energy is transformed

More information

Minute Impulse Clock Controller I01DN

Minute Impulse Clock Controller I01DN 99b-mi USER S MANUAL Minute Impulse Clock Controller Mon Jun 01, 2009 12:00:00 PM DST HOLD ENTER KEY TO BEGIN CANCEL HR I01DN 97 West Street Medfield, MA 02052 U.S.A. (508) 359-4396 Pg. 2 of 20 TABLE OF

More information

Grounding and Shielding

Grounding and Shielding Grounding and Shielding Veljko Radeka, BNL Outline Primary guidelines The Liquid Argon Calorimeter system Prevention of EMI and isolation Safety grounds Interface with other subsystems Status of implementation

More information

KZMb

KZMb -------------------------------------------------------- Electronic zone controller for pressure regulation ---------------------------------------------------------------------- FUNCTION KZM is an electronic

More information

Air distribution systems. Radial outlet RA-N2...

Air distribution systems. Radial outlet RA-N2... Air distribution systems Radial outlet RA-N... DS E 0.01 Radial outlet RA-N Preliminary remark KRANTZ KOMPONENTEN radial outlets RA-N have fixed radial vanes and are available with circular or square face.

More information

W 30 Photoelectric proximity switches: Clear signals even with low remission

W 30 Photoelectric proximity switches: Clear signals even with low remission W 0 Photoelectric proximity switches Photoelectric proximity switches, BGS Photoelectric proximity switches, energetic W 0 Photoelectric proximity switches: Clear signals even with low remission In addition,

More information

SkyScan EWS-PRO - Manual -

SkyScan EWS-PRO - Manual - INTRODUCTION SkyScan EWS-PRO - Manual - EWS-Pro gives you advance weather warning technology you can use at home, indoors or out, and take wherever you go, for any kind of outdoor activity. Your EWS-Pro

More information

Tornadoes Module 2. - Tornado Watch -

Tornadoes Module 2. - Tornado Watch - 1 2 - Tornado Watch - Issued by the National Weather Service when tornadoes are possible in an area Remain alert for approaching storms Remind family/employees of location of safest places Listen to the

More information

Section 1: Electric Charge and Force

Section 1: Electric Charge and Force Electricity Section 1 Section 1: Electric Charge and Force Preview Key Ideas Bellringer Electric Charge Transfer of Electric Charge Induced Charges Charging by Contact Electric Force Electric Field Lines

More information

Krantz Components. Twist outlet DD-N... for ceiling installation. Air distribution systems

Krantz Components. Twist outlet DD-N... for ceiling installation. Air distribution systems Krantz Components Twist outlet DD-N... for ceiling installation Air distribution systems DS E 0. Twist outlet Preliminary remarks and construction design Preliminary remarks Twist outlets for ceiling installation

More information

BETA Protecting. Low-Voltage Fuse Systems. LV HRC fuse links. 3/36 Siemens ET B1 2008

BETA Protecting. Low-Voltage Fuse Systems. LV HRC fuse links. 3/36 Siemens ET B1 2008 LV HRC fuse links Overview LV HRC fuses are used for installation systems in non-residential, commercial and industrial buildings as well as in switchboards of power supply companies. They therefore protect

More information

RS INDUSTRY LIMITED. RS Chip Array ESD Suppressor APPROVAL SHEET. Customer Information. Part No. : Model No. : COMPANY PURCHASE R&D

RS INDUSTRY LIMITED. RS Chip Array ESD Suppressor APPROVAL SHEET. Customer Information. Part No. : Model No. : COMPANY PURCHASE R&D APPROVAL SHEET Customer Information Customer : Part Name : Part No. : Model No. : COMPANY PURCHASE R&D Vendor Information Name: RS INDUSTRY LIMITED Part Name ARRAY TYPE MULTILAYER VARISTOR Part No. RS

More information

473 Dew Point Hygrometer

473 Dew Point Hygrometer High Performance Chilled Mirror Hygrometer With Cable Mounted Measuring Heads Highly precise chilled mirror dew point technology Cable mounted dew point and temperature measurement Aspirated and direct

More information

Amphenol C 091 A/B/D. Circular Connectors. Amphenol-Tuchel Electronics GmbH

Amphenol C 091 A/B/D. Circular Connectors. Amphenol-Tuchel Electronics GmbH Amphenol C 091 A/B/D Circular Connectors Amphenol-Tuchel Electronics GmbH General information These connectors are designed and produced in conformity with the low-voltage directive (/3/EWG) respectively

More information

Amphenol. Amphenol-Tuchel Electronics GmbH. Circular Connectors C 091 A/B/D Series

Amphenol. Amphenol-Tuchel Electronics GmbH. Circular Connectors C 091 A/B/D Series Amphenol Amphenol-Tuchel Electronics GmbH Circular Connectors C 09 A/B/D Series The Company Amphenol-Tuchel Electronics GmbH is a member of the USA based Amphenol Corporation. With our own global presence

More information

TRAM LINE SWITCH POINT HEATING

TRAM LINE SWITCH POINT HEATING ENERGY SAVING SMART WEATHER CONTROL TRAM LINE SWITCH POINT HEATING 50 80% Energy saving Heating controlled by weather conditions and weather forecast Long life heating elements Shield material is Monel

More information

Copyright 2017 by Select Calibration Inc. All rights reserved. Temperature Compensation

Copyright 2017 by Select Calibration Inc. All rights reserved. Temperature Compensation Copyright 2017 by Select Calibration Inc. All rights reserved. Temperature Compensation Table of Contents Introduction... 3 Why 20 C... 3 References... 3 Practical CMM Environments...4 CMM Construction

More information

Safety Precautions WARNING If critical situations that could lead to user s death or serious injury is assumed by mishandling of the product.

Safety Precautions WARNING If critical situations that could lead to user s death or serious injury is assumed by mishandling of the product. Safety Precautions Observe the following notices to ensure personal safety or to prevent accidents. To ensure that you use this product correctly, read this User s Manual thoroughly before use. Make sure

More information

5. DRIVE 1. SAFETY 2. PREPARATION 3. FRAME 4. TRANSMISSION 6. ROW UNIT 7. OPTIONAL EQUIPMENT

5. DRIVE 1. SAFETY 2. PREPARATION 3. FRAME 4. TRANSMISSION 6. ROW UNIT 7. OPTIONAL EQUIPMENT TABLE OF CONTENTS 1. SAFETY 2. PREPARATION 3. FRAME 4. TRANSMISSION 5. DRIVE 6. ROW UNIT 7. OPTIONAL EQUIPMENT DRIVE Standard Turbofan 540, 450 & 1000 RPM with PTO Drive Your Monosem planter will be equipped

More information

PUB NLH 185 Island Interconnected System Supply Issues and Power Outages Page 1 of 9

PUB NLH 185 Island Interconnected System Supply Issues and Power Outages Page 1 of 9 PUB NLH 1 Page 1 of 1 Q. Provide Hydro s list of outage cause codes and indicate how troublemen are managed and trained to properly use the codes. Explain the method used to report outage causes. A. Hydro

More information

Remote Display Unit. Installers Handbook Copyright 2001 AirSense Technology Ltd. LM Remote Display Unit Installers Handbook Issue 1.

Remote Display Unit. Installers Handbook Copyright 2001 AirSense Technology Ltd. LM Remote Display Unit Installers Handbook Issue 1. Remote Display Unit Installers Handbook Copyright 2001 AirSense Technology Ltd AirSense, ClassiFire, FastLearn PipeCAD, SenseNET, Stratos-HSSD and Stratos-Quadra are trademarks. HSSD is a Registered Trademark.

More information

In Association With. Introduces. TPT Contractor

In Association With. Introduces. TPT Contractor In Association With Introduces TPT Contractor Software for Contractors with TENSIONMETERS Table of Contents Capabilities 4 Setup and Use 7 The Dashboard 12 Tower Setup Form 18 Field Calibration Verification

More information

Back to Basics: Realizing Cabling Determines Design. F. Patrick Mahoney, CSI CDT, RCDD Direct Supply - Aptura

Back to Basics: Realizing Cabling Determines Design. F. Patrick Mahoney, CSI CDT, RCDD Direct Supply - Aptura Back to Basics: Realizing Cabling Determines Design F. Patrick Mahoney, CSI CDT, RCDD Direct Supply - Aptura Back to Basics: Realizing Cabling Determines Design Cabling distribution design implementation

More information

Thermal-Magnetic Circuit Breaker 2210-S2..

Thermal-Magnetic Circuit Breaker 2210-S2.. Thermal-Magnetic Circuit Breaker -S.. Description One, two and three pole thermal-magnetic circuit breakers with trip free mechanism and toggle actuation (S-type TM CBE to EN 6094/IEC 94). Designed for

More information

FEATURES APPLICATIONS DESCRIPTION QUICK REFERENCE DATA. PILKOR components

FEATURES APPLICATIONS DESCRIPTION QUICK REFERENCE DATA. PILKOR components FEATURES Excellent anti-surge characteristics Stable characteristics to moisture resistance even in high resistance range. Good replacement for ceramic plate resistors. APPLICATIONS Telecommunication Industrial

More information

AIR CONDITIONER (SPLIT TYPE) SERVICE MANUAL

AIR CONDITIONER (SPLIT TYPE) SERVICE MANUAL AIR CONDITIONER (SPLIT TYPE) SERVICE MANUAL FILE No. A10-023-1 REVISION 1 : Mar.2012 Re-edit version.( file volume down) Contents have NOT been changed. Model name: RAS-M10PKVP-E RAS-M13PKVP-E RAS-M16PKVP-E

More information

473 Dew Point Hygrometer

473 Dew Point Hygrometer gh Performance Chilled Hygrometer With Cable Mounted Measuring Heads ghly precise chilled mirror dew point technology Cable mounted dew point and temperature measurement Aspirated and direct insertion

More information

Microcare LCD Solar MPPT User Documentation

Microcare LCD Solar MPPT User Documentation Microcare LCD Solar MPPT User Documentation 1 CONTENTS 1. INTRODUCTION. 3 1.1. General Description 1.2. Key Features 1.3. Important Notices 1.4. Recommended Array Sizes 1.5. MPPT Description 1.6. MPPT

More information

MetConsole LLWAS (Low Level Wind Shear Alert System)

MetConsole LLWAS (Low Level Wind Shear Alert System) MetConsole LLWAS (Low Level Wind Shear Alert System) Enhancing aircraft safety under wind shear conditions Make the most of your energy SM MetConsole Low Level Wind Shear Alert System The Schneider Electric

More information

W250: Compact photoelectric switch series for a broad range of applications

W250: Compact photoelectric switch series for a broad range of applications W0 Photoelectric switches Photoelectric proximity switches, BGS Photoelectric reflex switches Through-beam photoelectric switches W0: Compact photoelectric switch series for a broad range of applications

More information

Tempest Lighting Product Training. November 2010

Tempest Lighting Product Training. November 2010 Tempest Lighting Product Training November 2010 Tempest Whatever the Weather High-power lights/projectors and outdoor climates means trouble! Rain, Snow Sunlight, Heat and Cold Condensation especially

More information

Chip Inductors. LCCM Series Chip Common Mode Filter FEATURES CONSTRUCTION

Chip Inductors. LCCM Series Chip Common Mode Filter FEATURES CONSTRUCTION FEATURES Small wire wound chip inductor with ferrite core and 2 common mode lines. Highly effective in noise suppression High common-mode impedance at noise band an low differential mode impedance at signal

More information

Electromotive Force. The electromotive force (emf), ε, of a battery is the maximum possible voltage that the battery can provide between its terminals

Electromotive Force. The electromotive force (emf), ε, of a battery is the maximum possible voltage that the battery can provide between its terminals Direct Current When the current in a circuit has a constant magnitude and direction, the current is called direct current Because the potential difference between the terminals of a battery is constant,

More information

Thermal-Magnetic Circuit Breaker 2210-S2...

Thermal-Magnetic Circuit Breaker 2210-S2... Thermal-Magnetic Circuit Breaker 0-S... Description One, two and three pole thermal-magnetic circuit breakers with trip free mechanism and toggle actuation (S-type TM CBE to EN 60934/IEC 934). Designed

More information

Section 1 Electric Charge and Force

Section 1 Electric Charge and Force CHAPTER OUTLINE Section 1 Electric Charge and Force Key Idea questions > What are the different kinds of electric charge? > How do materials become charged when rubbed together? > What force is responsible

More information

Electric Distribution Storm Hardening Initiatives. Paul V. Stergiou Distribution Engineering October 14 th, 2015

Electric Distribution Storm Hardening Initiatives. Paul V. Stergiou Distribution Engineering October 14 th, 2015 Consolidated Edison Company of New York, Inc. Electric Distribution Storm Hardening Initiatives Paul V. Stergiou Distribution Engineering October 14 th, 2015 Energy For New York City And Westchester 3.3

More information

CHV Series Vector Control Inverter Options. Operating Instructions for Tension Control Card

CHV Series Vector Control Inverter Options. Operating Instructions for Tension Control Card CHV Series Vector Control Inverter Options Operating Instructions for Control Card 1. Model and Specifications 1.1 Model The model of tension card is CHV00ZL. CHV series inverter can conduct constant

More information

Thermal-Magnetic Circuit Breaker 2210-S2...

Thermal-Magnetic Circuit Breaker 2210-S2... Description One, two and three pole thermal-magnetic circuit breakers with trip free mechanism and toggle actuation (S-type TM CBE to EN 6094/IEC 94). Designed for panel or plug-in mounting. Available

More information

Quad 10GBASE-T to XAUI Converter

Quad 10GBASE-T to XAUI Converter T-ENET-QU-10G PS-248-3 FETURES + + (4) 10G Ethernet hannels + + Protocol conversion between 10GSE-T and XUI + + Perfect for routing multiple 10 Gigabit Ethernet connections into systems and to and from

More information

SGM48753 CMOS Analog Switch

SGM48753 CMOS Analog Switch GENERAL DESCRIPTION The is a CMOS analog IC configured as three single-pole/double-throw (SPDT) switches. This CMOS device can operate from 2.5V to 5.5V single supplies. Each switch can handle rail-to-rail

More information

S Sapling INSTALLATION MANUAL FOR FIELD SELECTABLE ANALOG CLOCKS SAA SERIES SPECIFICATIONS. advanced time and control systems

S Sapling INSTALLATION MANUAL FOR FIELD SELECTABLE ANALOG CLOCKS SAA SERIES SPECIFICATIONS. advanced time and control systems INSTALLATION MANUAL FOR FIELD SELECTABLE ANALOG CLOCKS SAA SERIES SPECIFICATIONS Time base: 60 Hz (3-wire system) Quartz (2-wire system) Power input: 85 135 VAC / 60 Hz 7 28 VAC / 60 Hz Current consumption:

More information

ELECTRICITY Electric Fence Experiment.

ELECTRICITY Electric Fence Experiment. ELECTRICITY Electric Fence Experiment. Can you guess what will happen? What would life be like without electricity? List 4 things that you would miss the most: 1) 2) 3) 4) Positive and Negative Charge

More information

STATIC GAS MONITOR Type SGM/DEW Revision A of 20 aprile 2016

STATIC GAS MONITOR Type SGM/DEW Revision A of 20 aprile 2016 APPLICATIONS Moisture monitoring of air or gas (SF6) Suitable for indoor or outdoor Industrial, medical or aerospace fields HIGHLIGHTS High voltage circuit breakers commonly used for distribution and transmission

More information

BASIC ELECTRICITY STUDY COURSE

BASIC ELECTRICITY STUDY COURSE BASIC ELECTRICITY STUDY COURSE for Home Appliances HOW TO READ: VOLT-OHM-MILLIAMMETER TEST INSTRUMENTS VOLT-OHM-MILLIAMMETER TEST LEADS Module 4 LIT 787742 Rev. B WHIRLPOOL CORPORATION does not assume

More information

Assembly Instructions for the 1-Wire Weather Station V2.0/V3.0

Assembly Instructions for the 1-Wire Weather Station V2.0/V3.0 Assembly Instructions for the 1-Wire Weather Station V2.0/V3.0 Tools and Supplies Required (not included): Phillips screwdriver 3/8" wrench Drill with 5/32" bit "U" type mounting bracket (i.e., part number

More information

SPECIFICATION SS 51/9 400KV COUPLING CAPACITORS FOR POWER LINE CARRIER SYSTEM

SPECIFICATION SS 51/9 400KV COUPLING CAPACITORS FOR POWER LINE CARRIER SYSTEM INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION January 2017 SPECIFICATION SS 51/9 400KV COUPLING CAPACITORS FOR POWER LINE CARRIER SYSTEM I. SCOPE This

More information

Section 5. TADS Data Reporting Instruction Manual DRAFT Section 5 and Associated Appendices With Proposed Event Type Numbers

Section 5. TADS Data Reporting Instruction Manual DRAFT Section 5 and Associated Appendices With Proposed Event Type Numbers Section 5 TADS Data Reporting Instruction Manual DRAFT Section 5 and Associated Appendices With Proposed Event Type Numbers Rev. 5/10/2010 1 Section 5 Form for Event ID and Event Type Number Data TO s

More information

ISOCON-3 MAINS POWERED ISOLATING SIGNAL CONVERTER

ISOCON-3 MAINS POWERED ISOLATING SIGNAL CONVERTER ISOCON-3 MAINS POWERED ISOLATING SIGNAL CONVERTER CAUTION: This equipment is designed for connection to mains voltages and must be used in accordance with this guide. If it is not, the safety protection

More information