SYMMETRICAL FAULTS Revised: 10/8/13 1:49 PM
|
|
- Cori Parks
- 6 years ago
- Views:
Transcription
1 SYMMETRICAL FAULTS Revised: 10/8/13 1:49 PM 10/8/13 Symmetrical Faults 1
2 What is a fault? A faults is any failure which interferes with the normal flow of current. Most faults on transmission lines of 115 kv and higher are caused by lightning, which results in the flashover of insulators causing a low impedance path to ground. Line- to- line faults not involving ground are less common. Experience shows that 70 to 80% of transmission line failures are single line- to- ground faults. Permanent faults are caused by lines being on the ground, insulator strings breaking, ice loads, and equipment failure. 10/8/13 Symmetrical Faults 2
3 What is a fault? Roughly 5% of all faults involve all three phases and these are called symmetrical three- phase faults or just symmetrical faults. Line- to- line faults that do not involve ground and double line- to- ground faults are called unsymmetrical faults since they cause an imbalance between the phases. The currents which flow in a power system immediately a\er the occurrence of a fault differ from those flowing a few cycles later just before the circuit breakers are called upon to open the line on both sides of the fault. 10/8/13 Symmetrical Faults 3
4 What is a fault? Two factors which determine the proper selec^on of circuit breakers are the current flowing immediately a\er the fault occurs and the current which the breaker must interrupt. In fault analysis values of these currents are calculated for different types of faults at different loca^ons in the system. The informa^on obtained form these calcula^ons are used to determine the relay se_ng that control the circuit breakers. 10/8/13 Symmetrical Faults 4
5 Transients in Series RL Circuits The selec^on of a circuit breaker depends on: normal opera^ng current the current it has to interrupt the maximum current it may have to momentarily carry How does an over- current occur? To approach the problem of calcula^ng the ini^al current when a system is short- circuited, consider what happens when an ac voltage is applied to an RL circuit. 10/8/13 Symmetrical Faults 5
6 Mo^va^on Transients in Series RL Circuits t = 0 L R V max sin( ωt + α ) i( t) Differen^al equa^on: Solu^on: i( t) = V max Z V max sin( ωt + α ) = Ri + L di dt sin( ωt + α θ ) e Rt L sin( α θ ) Z = R 2 + ω 2 L 2, θ = tan 1 ( ω L R) 10/8/13 Symmetrical Faults 6
7 Mo^va^on Transients in Series RL Circuits ( ) = V max i t Z α θ = 0 ( ) e Rt L sin( α θ ) sin ωt + α θ ac- component constant amplitude dc- component exponen^ally decaying α θ = π 2 What about when a real synchronous generator is shorted? 10/8/13 Symmetrical Faults 7
8 Review of Synchronous Generators. 10/8/13 Symmetrical Faults 8
9 The Synchronous Generator The synchronous generator is driven by a turbine to convert mechanical energy into electrical energy. The windings of the synchronous machine consdtute a group of inducdvely coupled electric circuits, some of which rotate reladve to others so that the mutual inductances are variable. The models developed for the the various windings are applicable to both steady- state and transient analysis. Only linear magnedc circuits are considered. 10/8/13 Symmetrical Faults 9
10 The Synchronous Generator The two principal parts of a synchronous machine are ferromagnedc structures. The stadonary part (a hollow cylinder), called the armature (see next slide), has longitudinal slots in which there are coils of the armature windings. These carry the current to an electrical load. The rotor is the part of the machine which is mounted on the sham and rotates ins ide the hollow stator. The winding on the rotor, called the field winding, is supplied with dc current. The flux across the air gap between the armature and rotor generates voltages in the coils of the armature windings. 10/8/13 Symmetrical Faults 10
11 The Synchronous Generator Two Types Armature Armature Gap S Rotor N Gap Rotor X X The cylindrical rotor is called a non-salient pole machine. The non-cylindrical rotor is called a salient pole machine. 10/8/13 Symmetrical Faults 11
12 The Synchronous Generator For the two- pole machine, one cycle of voltage is generated for each revoludon of the two- pole rotor. In the four- pole machine, two cycles are generated in each armature coil per revoludon. Since the number of cycles of revoludon equals the number of pairs of poles, the frequency of the generated voltage is: f = P 2 N 60 = P 2 f m Hertz where f is the electrical frequency in Hertz, P is the number of poles, N is the rotor speed in RPM, and f m = N/60 is the mechanical frequency in rpm. We see that a two- pole, 60 Hz machine operates at 3600 rpm, while a four- pole machine operates at 1800 rpm. 10/8/13 Symmetrical Faults 12
13 The Synchronous Generator Cylindrical Rotor, Non- Salient Pole Machine Gap Armature S Rotor N d- axis Direct Axis X X 10/8/13 Symmetrical Faults 13
14 The Synchronous Generator Non- cylindrical Rotor, Salient Pole Machine Armature WE LL COME BACK TO THIS SHORTLY. Gap S N Rotor N d- axis Direct Axis S q- axis Quadrature Axis 10/8/13 Symmetrical Faults 14
15 The Synchronous Generator - Cylindrical Rotor Model d- axis R, L aa a- axis i a a + v a Sta^onary Armature d- axis R, L ff i f rota^on + v f R, L f bb R, L cc b- axis + v b v c + i b i b c c c- axis 10/8/13 Symmetrical Faults 15
16 The Synchronous Generator - Cylindrical Rotor Model R, L aa a- axis i a a + d- axis v a Sta^onary Armature L af R, L ff i f rota^on + v f R, L bb f R, L cc L cf b- axis L bf + v b v c + i b i b c c c- axis 10/8/13 Symmetrical Faults 16
17 The Synchronous Generator - Cylindrical Rotor Model R, L aa a- axis i a a + d- axis v a Sta^onary Armature L af L ab = L ba = M L = L = M s ac ca s R, L ff L aa = L bb = L cc = L s i f rota^on + v f R, L bb f R, L cc L cf b- axis L bf + v b v L i bc = L cb = M c + s b i b c c c- axis 10/8/13 Symmetrical Faults 17
18 The Synchronous Generator - Cylindrical Rotor Model θ d R, L aa a- axis i a a + d- axis v a Sta^onary Armature L af L ab = L ba = M L = L = M s ac ca s R, L ff L aa = L bb = L cc = L s i f rota^on + v f R, L bb f R, L cc L cf b- axis L bf + v b v L i bc = L cb = M c + s b i b c c c- axis 10/8/13 Symmetrical Faults 18
19 The Synchronous Generator - Cylindrical Rotor Model L af = M f cosθ d L bf = M f cos( θ d 120 ) L cf = M f cos( θ d 240 ) 10/8/13 Symmetrical Faults 19
20 Armature Flux Linkages λ a = L aa i a + L ab i b + L ac i c + L af i f = L s i a M s λ b = L ba i a + L bb i b + L bc i c + L bf i f = L s i b M s λ c = L ca i a + L cb i b + L cc i c + L cf i f = L s i c M s Armature Flux Linkages ( i b + i ) c + L af i f ( i a + i ) c + L bf i f ( i a + i ) b + L cf i f Balanced Three- Phase System λ f = L af i a + L bf i b + L cf i c + L ff i f i a + i b + i c = 0 10/8/13 Symmetrical Faults 20
21 Algebra λ a = ( L s + M s )i a + L af i f λ b = ( L s + M s )i b + L bf i f λ c = ( L s + M s )i c + L cf i f Since the field current is dc and the field rotates with constant angular velocity, dθ d dt = ω, θ d = ωt +θ o, i f = I f λ a = ( L s + M s )i a + M f I f cos( ωt +θ ) o λ b = ( L s + M s )i b + M f I f cos( ωt 120 +θ ) o λ c = ( L s + M s )i c + M f I f cos( ωt 240 +θ ) o 10/8/13 Symmetrical Faults 21
22 Circuit Equa^ons dλ v a = R a i a a dt generator = R a i a ( L s + M ) di a s dt + ( ) ω M I sin ωt +θ f f o ( ) e a = 2 E i sin ωt +θ o Internal emf: e a = 2 E i sin( ωt +θ ) o (or synchronous emf) where: E i = ω M f I f 2 For convenience (it s arbitrary anyway) set θ o = δ + 90 We have the circuit model 10/8/13 Symmetrical Faults 22
23 The Synchronous Generator - Cylindrical Rotor Model v a = R a i a ( L s + M ) di a s dt + ω M f I f sin( ωt +θ ) o ~ + _ R L s + M s e b e c i a e a = 2 E i cos( ωt + δ ) a + v a _ L s + M s L s + M s R R 10/8/13 Symmetrical Faults 23 i c v c + c i b b v b +
24 The Synchronous Generator - Cylindrical Rotor Model Also: i a = 2 I a cos( ωt + δ θ ) a i b = 2 I a cos( ωt + δ θ a 120 ) i c = 2 I a cos( ωt + δ θ a 240 ) where θ a is the phase angle of the lag of the current i a with respect to e a. 10/8/13 Symmetrical Faults 24
25 The Synchronous Generator - Cylindrical Rotor Model L s + M s R i a = 2 I a cos( ωt + δ θ ) a + ± e a = 2 E i cos( ωt + δ ) v a = 2 V a cosωt This is a steady- state model that misses details of the field current needed for transient analysis. 10/8/13 Symmetrical Faults 25
26 The Synchronous Generator - Cylindrical Rotor Model To facilitate transient analysis (as with a fault) it is necessary to recast this model into a different form. Recall: λ f = L af i a + L bf i b + L cf i c + L ff i f and: Subs^tu^ng: λ f = M f L af = M f cosθ d L bf = M f cos( θ d 120 ) L cf = M f cos( θ d 240 ) i a cosθ + i cos θ 120 d b d i a cosθ d = 2 I a cosθ d cos ωt + δ θ a ( ) + i c cos( θ d 240 ) ( ) + L i ff f = 2 I a cos( ωt + δ + 90 )cos( ωt + δ θ ) a 10/8/13 Symmetrical Faults 26
27 To facilitate a symmetric fault it helps to recast this model a bit. i a cosθ d = 2 I a cosθ d cos( ωt + δ θ ) a = 2 I a cos( ωt + δ + 90 )cos( ωt + δ θ ) a = I a 2 cos θ + 90 a ( ) + cos( 2ωt + 2δ θ a + 90 ) ( ) = I a 2 sinθ sin 2ωt + 2δ θ a a 2cosα cosβ = cos( α β ) + cos( α + β ) 10/8/13 Symmetrical Faults 27
28 Similarly for the other two terms: Subs^tu^ng: i a cosθ d + i b cos( θ d 120 ) + i c cos( θ d 240 ) = I a 2 = 3 I a 2 sinθ a i b cos( θ d 120 ) = I a i c cos( θ d 240 ) = I a ( ) 2 sinθ sin 2ωt + 2δ θ 120 a a ( ) 2 sinθ sin 2ωt + 2δ θ 240 a a 3sinθ a +sin( 2ωt + 2δ θ a ) + sin( 2ωt + 2δ θ a 120 ) + sin( 2ωt + 2δ θ a 240 ) = 0 This is a balanced second harmonic terms that sums to zero at every point in Dme. 10/8/13 Symmetrical Faults 28
29 Subs^tu^ng: λ f = M f i a cosθ d + i b cos θ d 120 ( ) + i c cos( θ d 240 ) = L ff i f 3 M f I a 2 sinθ a = L ff i f M f i d + L i ff f where i d = 3 I a sinθ a or i d = 2 3 i cosθ + i cos θ 120 a d b d ( ) + i c cos( θ d 240 ) 10/8/13 Symmetrical Faults 29
30 Observa^ons: λ f = L ff i f M f i d, i d = 3 I a sinθ a The flux linkages with the field winding that are due to a combina^on of the the three line currents do not vary with ^me. They can thus be regarded as coming from a steady dc current i d in a fic^^ous dc circuit coincident with the d- axis and thus sta^onary with respect to the field circuit. The two circuits rotate together in synchronism and have mutual inductance (3/2) 1/2 M f between them. Circuit model 10/8/13 Symmetrical Faults 30
31 Alternate Circuit Model Suitable for Transient Analysis a- axis θ d d- axis i d 3 2 M f Armature equivalent winding rota^ng with rotor i f R, L ff b- axis + v f f Field winding rota^ng with rotor c- axis 10/8/13 Symmetrical Faults 31
32 Example A 60- Hz three- phase synchronous generator with negligible armature resistance has the following inductance parameters: L aa = L s = mH, L ab = M s = mH L ff = mH, M f = mH The machine is rated at 635 MVA, 0,9 power- factor lagging, 3600 rpm, 24 kv. When opera^ng under rated condi^ons, the line- to- neutral terminal voltage and the line current of phase a are v a = 19596cosωt V, i a = 21603cos( ωt ) Determine the magnitude of the synchronous internal voltage, the field current I f, and the flux linkages with the field winding. Repeat these calcula^ons when a load of 635 MVA is served at rated voltage and unity power factor. What is the field current for rated armature voltage on a open circuit? 10/8/13 Symmetrical Faults 32
33 Example v amax = 2 24,000 i amax 3 = 19596V = VA V = 2 635, = 21603A θ = cos = , lagging Synchronous Internal Voltage: e a = 2 E i cos( ωt + δ ) =0 = R ia a + v a + ( L s + M ) di a s dt = v a di + ( )10 3 a dt = 19596cosωt ( d )10 3 dt cos( ωt ) = 19596cosωt ω 21603( )10 3 sin ωt ( ) 10/8/13 Symmetrical Faults 33
34 Example Synchronous Internal Voltage: ω = 120π ( ) = sin xcos y cos xsin y sin x y 2 E i cos( ωt + δ ) = 19596cosωt ω 21603( )10 3 sin ωt ( ) = 19596cosωt 33875sin ωt = 34323cosωt 30407sinωt ( ) = 45855cos ωt E i = 45855, δ = ( ) Field Current: E i = ω M f I f 2 I f = 2 E i ω M f = 3838A 10/8/13 Symmetrical Faults 34
35 Example Flux linkages with field windings: λ f = L ff i f 3 M f θ a is the angle of lag measured wrt e a. Since i a lags o behind v a, which lags o behind e a, then θ a = o o = o I a 2 sinθ a Thus: I a sinθ a = sin = A 2 λ f = L ff i f 3 M f I a 2 sinθ a = = = Weber-turns 10/8/13 Symmetrical Faults 35
36 Example Repea^ng for unity power factor: di e a = 2 E i cos( ωt + δ ) = v a + ( )10 3 a dt = 19596cosωt 33785sinωt = 39057cos( ωt ) I f = 2 E i ω M f = = 3269A The current i a is in- phase with v a, and lags e a by o I a sinθ a = 15276sin = 13214A λ f = = = Weber-turns /8/13 Symmetrical Faults 36
37 Example We see that when the power factor of the load goes from 0.9 lagging to 1.0 under rated mega- voltamperes loading and voltage condidons, the field current is reduced from 3838 to 3269 A. Also, the net air- gap flux linking the field winding of the generator is reduced along with the demagnedzing influence of armature reacdon. The field current required to maintain rated terminal voltage in the machine under open- circuit condidons (i a = 0) is I f = 2 E i ω M f = π = 1640A 10/8/13 Symmetrical Faults 37
38 The Synchronous Generator - Salient Rotor Model The round- rotor theory already just considered gives good results for the steady- state performance of the synchronous machine. However, for transient analysis we need to consider a two- axis model. We now introduce the two- axis model by means of the equadons of the salient- pole machine in which the air gap varies between poles. The largest generadng units are steam- turbine driven with round- rotor construcdon; fossil- fired units have two poles and nuclear units have four pole s for reasons of economical design and efficiency. Hydroelectric generators usually have more pole- pairs and are of salient- pole construcdon. These units run at lower speeds so as to avoid mechanical damage due to centrifugal forces. 10/8/13 Symmetrical Faults 38
39 The Synchronous Generator - Salient Rotor Model The three- phase salient- pole machine, like its round- rotor counterpart, has three symmetrically distributed armature windings a, b, and c, and a field winding f on the rotor which produces a sinusoidal flux distribudon around the air gap. In both types of machines the field sees the same air gap and magnedzing paths in the stator regardless of the rotor posidon. Thus, the field winding has constant self- inductance L ff. Moreover, both machine have the same sinusoidal varying mutual inductances as before. The difference is that the self- inductances L aa, L bb, and L cc and the mutual inductances L ab, L bc, and L ca between them are no longer constant but also vary as a funcdon of the rotor angular displacement. 10/8/13 Symmetrical Faults 39
40 The Synchronous Generator - Salient Rotor Model Flux Linkages: λ a = L aa i a + L ab i b + L ac i c + L af i f λ b = L ba i a + L bb i b + L bc i c + L bf i f λ c = L ca i a + L cb i b + L cc i c + L cf i f These look the same as seen before (Slide 19), but unlike the case of the round rotor the L s are no longer well- approximated by constants. X X 10/8/13 Symmetrical Faults 40
41 The Synchronous Generator - Salient Rotor Model For the armature, Self- inductances: L s > L m > 0 Mutual- inductances: L aa = L s + L m cos2θ d ( ) ( ) L bb = L s + L m cos2 θ d 2π 3 L cc = L s + L m cos2 θ d + 2π 3 M s > L m > 0 ( ) ( ) ( ) L ab = L ba = M s L m cos2 θ d + π 6 L bc = L cb = M s L m cos2 θ d π 2 L ca = L ac = M s L m cos2 θ d + 5π 6 Mostly based on geometrical considera^ons 10/8/13 Symmetrical Faults 41
42 The Synchronous Generator - Salient Rotor Model For the rotor, Self- inductances: Field winding: D- Damper winding: Q- Damper winding: L ff L D L Q Mutual- inductances: Field/D- winding: Field/Q- winding: D- winding/q- winding: Armature/Field: M r 0 0 L af = L fa = M f cos2θ d L bf = L fb = M f cos2( θ d 2π 3) ( ) L cf = L fc = M f cos2 θ d 4π 3 Mostly based on geometrical considera^ons 10/8/13 Symmetrical Faults 42
43 The Synchronous Generator - Salient Rotor Model Armature- damper winding mutual- inductances, Armature/D- winding: What are these? Armature/Q- winding: L ad = L Da = M D cos2θ d ( ) ( ) L bd = L Db = M D cos2 θ d 2π 3 L cd = L Dc = M D cos2 θ d 4π 3 L aq = L Qa = M Q cos2θ d L bq = L Qb = M Q cos2( θ d 2π 3) L cq = L Qc = M Q cos2( θ d 4π 3) Mostly based on geometrical considera^ons 10/8/13 Symmetrical Faults 43
44 The Synchronous Generator - Salient Rotor Model Damper Windings or Amortisseur Windings Shorting Bar Field Windings 10/8/13 Symmetrical Faults 44
45 Two- Axis Machine Model Clearly the equadons for the flux linkages of the salient- pole machine are more complicated than their round- rotor counterparts. Fortunately, the equadons of the salient- pole machine can be expressed in a simple form by transforming the a, b, and c variables of the stator into corresponding sets of new variables, called the direct- axis, quadrature- axis, and zero- sequence quanddes which are disdnguished by the subscripts d, q, and 0: respecdvely. The three stator currents i a, i b, and i c can be transformed into three equivalent currents, called the direct- axis current i d, the quadrature- axis current i q and the zero- sequence current i o. The transformadon is made by a matrix P called Park s Transforma^on. 10/8/13 Symmetrical Faults 45
46 Park s Transforma^on Recall for the round rotor machine we found (Slide 30) i d, what we will now call the direct current as: i d = 2 3 i cosθ + i cos θ 120 a d b d ( ) + i c cos( θ d 240 ) q- axis Quadrature Axis S d- axis N S N N Direct Axis X X rota^on S d- axis Note how the q- axis lags the d- axis by 90- degrees. 10/8/13 Symmetrical Faults 46
47 Park s Transforma^on Note how the q- axis lags the d- axis by 90- degrees. i d = 2 3 i cosθ + i cos θ 120 a d b d i q = 2 3 i sinθ + i sin θ 120 a d b d ( ) + i c cos( θ d 240 ) ( ) + i c sin( θ d 240 ) P = 2 3 cosθ d cos( θ d 120 ) cos( θ d 240 ) sinθ d sin( θ d 120 ) sin( θ d 240 )??? Define P as a unitary matrix: P 1 = P T The unitary property assures that the power is unaltered by P. 10/8/13 Symmetrical Faults 47
48 Park s Transforma^on P = 2 3 cosθ d cos( θ d 120 ) cos( θ d 240 ) sinθ d sin( θ d 120 ) sin( θ d 240 ) Park s transformadon gives what is known as the Two- Axis Model of a salient pole generator. 10/8/13 Symmetrical Faults 48
49 Park s Transforma^on i d i q i 0 = P i a i b i c v d v q v 0 = P v a v b v c λ d λ q λ 0 = P λ a λ b λ c The P- transformadon defines a set of currents, voltages, and flux linkages for three ficddous coils, one of which is the stadonary 0- coil. The other two are the d- coil and the q- coil, which rotate in synchronism with the rotor. The d- and q- coils have constant flux linkages with the field and any other windings which may exist on the rotor. The resuldng d, q, and 0 flux- linkage equadons are 10/8/13 Symmetrical Faults 49
50 Park s Transforma^on For example, the resuldng d, q, and 0 flux- linkage equadons are from the stator flux- linkages as follows: λ a = L aa i a + L ab i b + L ac i c + L af i f λ b = L ba i a + L bb i b + L bc i c + L bf i f λ c = L ca i a + L cb i b + L cc i c + L cf i f λ d λ a λ a λ d λ q = P λ b λ b = P 1 λ q λ 0 λ c λ c λ 0 P 1 λ d λ q λ 0 λ d λ q λ 0 = = P L aa L ab L ac L ab L bb L bc L ac L bc L cc L aa L ab L ac L ab L bb L bc L ac L bc L cc P 1 P 1 λ d λ q λ 0 λ a λ b λ c λ d λ q λ 0 = + + P L aa L ab L ac L ab L bb L bc L ac L bc L cc L af L bf L cf L af L bf L cf i f i f i a i b i c + L af L bf L cf i f 10/8/13 Symmetrical Faults 50
51 Park s Transforma^on SubsDtuDng for the L s from the previous table: = L aa L ab L ac L ab L bb L bc L ac L bc L cc ( ) M s L m cos2( θ d + 5π 6) ( ) L s + L m cos2( θ d 2π 3) M s L m cos2( θ d π 2) ( ) M s L m cos2( θ d π 2) L s + L m cos2( θ d + 2π 3) L s + L m cos2θ d M s L m cos2 θ d + π 6 M s L m cos2 θ d + π 6 M s L m cos2 θ d + 5π 6 L s M s M s = M s L s M s M s M s L s ( ) = L s + M s ( ) cos2( θ d + 5π 6) ( ) cos2( θ d 2π 3) cos2( θ d π 2) ( ) cos2( θ d + 2π 3) cos2θ d cos2 θ d + π 6 L m cos2 θ d + π 6 cos2( θ d + 5π 6) cos2 θ d π 2 M ( ) cos2( θ d + 5π 6) ( ) cos2( θ d 2π 3) cos2( θ d π 2) ( ) cos2( θ d + 2π 3) cos2θ d cos2 θ d + π 6 L m cos2 θ d + π 6 cos2( θ d + 5π 6) cos2 θ d π 2 10/8/13 Symmetrical Faults 51
52 Park s Transforma^on Now for the tedious part subsdtute all this L aa L ab L ac L ab L bb L bc L ac L bc L cc = L s + M s ( ) M ( ) cos2( θ d + 5π 6) ( ) cos2( θ d 2π 3) cos2( θ d π 2) ( ) cos2( θ d + 2π 3) cos2θ d cos2 θ d + π 6 L m cos2 θ d + π 6 cos2( θ d + 5π 6) cos2 θ d π 2 λ d λ q λ 0 = P L aa L ab L ac L ab L bb L bc L ac L bc L cc P 1 λ d λ q λ 0 + P M f cos2θ d ( ) ( ) M f cos2 θ d 2π 3 M f cos2 θ d 4π 3 i f P = 2 3 cosθ d cos θ d 120 sinθ d sin θ d 120 ( ) cos( θ d 240 ) ( ) sin( θ d 240 ) , P 1 = P T to get 10/8/13 Symmetrical Faults 52
53 Park s Transforma^on to get λ d λ q λ 0 = L d L q L 0 i d i q i M f 0 0 i f where: Direct- axis inductance: L d = L s + M s L m Quadrature- axis inductance: L q = L s + M s 3 2 L m Zero- sequence inductance: L 0 = L s 2M s all constants! 10/8/13 Symmetrical Faults 53
54 Park s Transforma^on The equadon for the flux linkages of the field circuit remain unchanged (Slide 28): λ f = L ff I f M f i d 10/8/13 Symmetrical Faults 54
55 Park s Transforma^on P 10/8/13 Symmetrical Faults 55
56 Two- Axis Machine Model θ d a- axis Ignore damper winding for the moment. q- axis d- axis i d 3 2 M f R, L q i q R, L d Rota^on i f R, L ff + v f f b- axis All coils rotate together. c- axis 10/8/13 Symmetrical Faults 56
57 Two- Axis Machine Model The constant inductance coefficients make for quite simple to use. Physically, these simpler flux- linkage equadons show that L d is the self- inductance of an equivalent d- axis armature winding which rotates at the same speed as the field and which carries current i d to produce the same mmf on the d- axis as do the actual stator currents i a, i b, and i c. Similarly for L q and i q and the q- axis. The ficddous d- axis winding and the field winding represendng the physical field can be considered to act like two coupled coils which are stadonary with respect to each other as they rotate together sharing the mutual inductance between them. 10/8/13 Symmetrical Faults 57
58 Two- Axis Machine Model Furthermore, the field and the d- axis coil do not couple magnedcally with ficddous q winding since it lags the d- axis in space by 90. The zero- sequence inductance L 0 is associated with a stadonary ficddous armature coil with no coupling to any other coils. Under balanced condidons this coil carries no current, and therefore we omit it from our discussion. 10/8/13 Symmetrical Faults 58
59 Example To get a feeling for Park s Transforma^on Under steady- state operadng condidons the armature of the salient- pole synchronous generator carries symmetrical sinusoidal three- phase currents: i a = i b = i c = 2 I a sin( θ d θ ) a 2 I a sin( θ d 120 θ ) a 2 I a sin( θ d 240 θ ) a Find the corresponding d- q- 0 currents of the armature. 10/8/13 Symmetrical Faults 59
60 Example To get a feeling for Park s Transforma^on i d i q i 0 = 2 3 cosθ d cos( θ d 120 ) cos( θ d 240 ) sinθ d sin( θ d 120 ) sin( θ d 240 ) i a i b i c MulDply through: i d = 2 3 cosθ i + cos ( θ 120 d a d )i b + cos( θ d 240 )i c i q = 2 3 sinθ i + sin ( θ 120 d a d )i b + sin( θ d 240 )i c i 0 = ( ) 2 i a + i b + i c = 0 balanced three- phase 10/8/13 Symmetrical Faults 60
61 Example To get a feeling for Park s Transforma^on Simplifying 2sin xcos y = sin( x + y) + sin( x y) i a cosθ d = 2 I a sin( θ d θ a )cosθ d = I a 2 sin 2θ θ d a i b cos( θ d 120 ) = 2 I a cos( θ d 120 )sin( θ d 120 θ ) d ( ) sinθ a = I a 2 sin 2θ 240 θ d a i c cos( θ d 240 ) = 2 I a cos( θ d 240 )sin( θ d 240 θ ) d ( ) sinθ a = I a 2 sin 2θ 480 θ d a ( ) sinθ a 10/8/13 Symmetrical Faults 61
62 Example To get a feeling for Park s Transforma^on SubsDtuDng i d = 2 3 I a 2 sin ( 2θ θ d a ) + sin( 2θ d 240 θ a ) + sin( 2θ d 480 θ a ) 3sinθ a = 0 = 3 I a sinθ a It should come as no surprise that i q = 3 I a cosθ a Note how the expression for i d is EXACTLY the same as for the round- rotor machine (see Slide 30). 10/8/13 Symmetrical Faults 62
63 VOLTAGE EQUATIONS Remarkably simple in d, q, 0 variables. As before, the line to neutral voltages are: dλ v a = Ri a a dt generator v b = Ri b dλ b dt v c = Ri c dλ c dt These would be EXTREMELY difficult to deal with if lem in terms of a, b, c, but simplify TREMENDOUSLY using Park s transformadon, but going from a, b, c to d, q, 0 is a bit tedious. 10/8/13 Symmetrical Faults 63
64 Voltage Equa^ons General procedure lots of algebra: MulDply both sides by P v a v b v c v d v q v 0 = R = R i a i b i c i d i q i 0 d dt P d dt λ a λ b λ c P 1 P λ d λ q λ 0 v a v b v c = RP i a i b i c P d dt λ a λ b λ c Note: P = P( t) since θ d = ωt +θ o 10/8/13 Symmetrical Faults 64
65 Voltage Equa^ons General procedure lots of algebra: v d v q v 0 = R = R = R i d i q i 0 i d i q i 0 i d i q i 0 P d dt PP 1 d dt d dt P 1 λ d λ q λ 0 λ d λ q λ 0 λ d λ q λ 0 P P d dt PT d dt P 1 10/8/13 Symmetrical Faults 65 λ d λ q λ 0 λ d λ q λ 0 This is the work.
66 Voltage Equa^ons It all simplifies to: v d v q v 0 = R i d i q i 0 dλ d dt dλ q dt dλ 0 dt + ωλ q ωλ d 0 where ω = dθ d dt 10/8/13 Symmetrical Faults 66
67 Voltage Equa^ons Summary: d- axis v d = Ri d dλ d dt ωλ q λ f = L ff i f M f i d λ d = L d i d M f i f q- axis v q = Ri q dλ q dt λ q = L q i q + ωλ d and since the field winding is not subject to the P- transformadon v f f = R f i f + dλ f dt 10/8/13 Symmetrical Faults 67
68 Circuit Model i f v d = Ri d L d di d dt ωλ q v f f R f L ff Field winding 3 2 M f L d R i d + v d d- axis armature equivalent winding ωλ q + v f f = R f i f + dλ f dt L q R i q + v q q- axis armature equivalent winding + ωλ d v q = Ri q L q di q dt ωλ d 10/8/13 Symmetrical Faults 68
69 Circuit Model We see that the field coil is mutually coupled to the d- coil on the d- axis. The q- coil is magnedcally uncoupled from the other two windings since the d- axis and the q- axis are spadally in quadrature with one another. However, there is interacdon between the two axes by means of the voltage sources which are rotadonal emfs or speed voltages internal to the machine due to the rotadon of the rotor. Note that the speed voltage in the d- axis depends on λ q, and similarly, the speed voltage in the q- axis depends on λ d. These sources represent ongoing electromechanical energy conversion. 10/8/13 Symmetrical Faults 69
70 Example No numbers, but again to appreciate the model A direct current I f is supplied to the field winding of an unloaded salient- pole synchronous generator rotadng with constant angular velocity ω. Determine the open- circuit armature voltages and their d- q- 0 components. Since open circuited: SubsDtuDng these into: i d i q i 0 = P i a i b i c = v d = Ri d dλ d dt ωλ q, λ f = L ff i f M f i d, λ d = L d i d M f i f v q = Ri q dλ q dt + ωλ d, λ q = L q i q, v f f = R f i f + dλ f dt gives 10/8/13 Symmetrical Faults 70
71 Example No numbers, but again to appreciate the model gives λ d = 3 2 M f i f v d = dλ d dt ωλ q = 0 Thus: λ q = 0 λ 0 = 0 v d v q v 0 = P v a v b v c v q = dλ q dt + ωλ d = ω 3 2 M f i f v 0 = Ri 0 dλ 0 dt v a v b v c = 0 v d = P T v q v 0 10/8/13 Symmetrical Faults 71
72 Example No numbers, but again to appreciate the model v a v b v c v d = P T v q v 0 = 3 2 = 2 3 sinθ d ( ) ( ) sin θ d 120 sin θ d 240 cosθ d sinθ d 1 cos( θ d 120 ) sin( θ d 120 ) cos( θ d 240 ) sin( θ d 240 ) ω M f i f ω M f i f 0 Again this is idendcal to the round- rotor machine. 10/8/13 Symmetrical Faults 72
73 Summary Park's transformadon replaces the physical stadonary windings of the armature by: 1. A direct- axis circuit which rotates with the field circuit and is mutually coupled to it. 2. A quadrature- axis circuit which is displaced 90 from the d- axis, and thus has no mutual inductance with the field or other d- axis circuits although it rotates in synchronism with them, and 3. A stadonary stand- alone 0- coil with no coupling to any other circuit, and thus not shown. This model is most useful in analyzing the performance of the synchronous machine under short- circuit condidons, which we now (finally!) consider. 10/8/13 Symmetrical Faults 73
74 TRANSIENT AND SUBTRANSIENT EFFECTS When a fault occurs in a power network, the current flowing is determined by the internal emfs of the machines in the network, by their impedances, and by the impedances in the network between the machines and the fault. The current flowing in a synchronous machine immediately amer the occurrence of a fault differs from that flowing a few cycles later and from the sustained, or steady- state, value of the fault current. This is because of the effect of the fault current in the armature on the flux generadng the voltage in the machine. The current changes reladvely slowly from its inidal value to its steady- state value owing to the changes in reactance of the synchronous machine. 10/8/13 Symmetrical Faults 74
75 TRANSIENT AND SUBTRANSIENT EFFECTS Our interest now is in the inductance effecdve in the armature of the synchronous machine when a three- phase short circuit suddenly occurs at its terminals. Before the fault occurs, suppose that the armature voltages are v a, v b, and v c, and that these give rise to the voltages v d, v q, and v 0 according to Park s TransformaDon. The short circuit of phases a, b, and c imposes the condidons v a = v b = v c = 0 which lead to the condidons v d = v q = 0. Thus, to simulate short- circuit condidons, the terminals of the d- axis and q- axis circuits of the circuit model must also be shorted. 10/8/13 Symmetrical Faults 75
76 TRANSIENT AND SUBTRANSIENT EFFECTS i f i d v f f R f L ff 3 Field winding 2 M f L d R d- axis + v d S + v d + v d The switches S should be interpreted in a symbolic sense; namely, when the switches are both open, the sources - V d and - V q are in the circuit, and when the switches are closed, the two sources are removed from the circuit. ωλ q + L q R q- axis + ωλ d + v q i q S + v q + v q 10/8/13 Symmetrical Faults 76
77 TRANSIENT AND SUBTRANSIENT EFFECTS Since the model is linear we now use superposidon. Assume that the rotor speed ω remains at its pre- fault steady- state value. With both switches closed we have the steady- state operadon of the machine since the added sources v d and v q do nothing. Suddenly opening the switches adds the series voltage sources v d and v q producing the required short circuits. Thus, the sources v d and v q determine the instantaneous changes from the steady state due to the sudden short- circuit fault. 10/8/13 Symmetrical Faults 77
78 TRANSIENT AND SUBTRANSIENT EFFECTS We can calculate the fault- induced changes of all variables by sewng the external sources v ff, v d and v q equal to zero and suddenly applying the voltages v d and v q to the unexcited rotadng machine, as shown in the next slide. The internal speed voltages ωλ q and ωλ d are inidally zero because flux linkages with all coils are zero in the (next) figure before applying the voltages v d and v q. 10/8/13 Symmetrical Faults 78
79 TRANSIENT AND SUBTRANSIENT EFFECTS i f i d v f f = 0 R f Field winding L ff 3 2 M f L d R d- axis t = 0 + v d ωλ q + = 0 i q R t = 0 + L q q- axis v q + ωλ d = 0 10/8/13 Symmetrical Faults 79
80 TRANSIENT AND SUBTRANSIENT EFFECTS From the d- axis summary: λ f = L ff i f M f i d λ d = L d i d M f i f we compute the change Δλ f = L ff Δi f M f Δi d Δλ d = L d Δi d M f Δi f But since the field winding is a closed, physical winding its flux linkages (field current) cannot change instantaneously, so set Δλ f = 0 Δi f = 1 L ff 3 2 M f Δi d 10/8/13 Symmetrical Faults 80
81 TRANSIENT AND SUBTRANSIENT EFFECTS SubsDtuDng: Δi f = 1 L ff 3 2 M f Δi d into: Δλ d = L d Δi d M f Δi f gives: Δλ d = L d 3 2 M f 2 L ff Δi d The flux linkage per unit current defines the d- axis transient inductance: L d = Δλ d = L Δi d 3 d 2 M f 2 L ff 10/8/13 Symmetrical Faults 81
82 TRANSIENT AND SUBTRANSIENT EFFECTS The d- axis transient inductance: Since 3 2 M f 2 L ff > 0 L d = L d 3 2 M f 2 the direct- axis transient reactance X d = ωl d is always less than the direct- axis synchronous reactance X d = ωl d. Thus, following abrupt changes at its terminals, the synchronous machine reflects in its armature a transient reactance which is less than its steady- state reactance. L ff 10/8/13 Symmetrical Faults 82
83 TRANSIENT AND SUBTRANSIENT EFFECTS Further Considera^ons In defining X d, we assume that the field is the only physical rotor winding. As previously mendoned, most salient- pole machines of pracdcal importance have damper windings consisdng of shorted copper bars through the pole faces of the rotor; and even in a round- rotor machine, under short- circuit condidons eddy currents are induced in the solid rotor as if in damper windings. The effects of the eddy- current damping circuits are represented by direct- axis and quadrature- axis closed coils, which are treated in very much the same way as the field winding except that they have no applied voltage. 10/8/13 Symmetrical Faults 83
84 TRANSIENT AND SUBTRANSIENT EFFECTS Further Considera^ons To account for the addidon of damper windings, we need only add to our model the closed D- circuit and Q- circuit shown on the next slide, which have self- inductances L D and L Q and mutual inductances with the other windings as shown. In the steady state the flux linkages are constant between all circuits on the same rotor axis. The D- and Q- circuits are then passive (having neither induced nor applied voltages) and do not enter into steady- state analysis. 10/8/13 Symmetrical Faults 84
85 TRANSIENT AND SUBTRANSIENT EFFECTS Further Considera^ons + v f f i f R f Lff Field winding M R 3 2 M i f R d L d d- axis + v d + v D = 0 i D R D D- damper winding L D ωλ q M D + v Q = 0 i Q R Q Q- damper winding 3 2 M Q L Q L q R q- axis i q + v q + ωλ d 10/8/13 Symmetrical Faults 85
86 TRANSIENT AND SUBTRANSIENT EFFECTS Further Considera^ons Under short- circuit condidons, however, we can determine from the inidal d- axis flux- linkage changes resuldng from sudden shordng of the synchronous machine with damper- winding effects. The procedure is the same as already discussed. The field and D- damper circuits represendng closed physical windings are mutually coupled to each other and to the d- coil represendng the armature along the direct axis. There cannot be sudden change in the flux linkages of the closed windings, and so we can write the flux- linkage changes along the d- axis by modifying our earlier results as follows: 10/8/13 Symmetrical Faults 86
87 TRANSIENT AND SUBTRANSIENT EFFECTS Further Considera^ons Δλ f = L ff Δi f M f Δi d + M r Δi D = 0 Δλ d = L d Δi d M f Δi f M D Δi D Δλ D = 3 2 M D Δi d + M R Δi f + L D Δi D = 0 Note how these are similar to our previous equadons but have extra terms because of the addidonal self- and mutual inductances associated with the D- damper circuit. 10/8/13 Symmetrical Faults 87
88 TRANSIENT AND SUBTRANSIENT EFFECTS Further Considera^ons Solving: Δi f = 3 2 M f L D 3 2 M r M D L ff L D M r 2 Δi d and subsdtudng: Δi D = 3 2 M D L ff 3 2 M r M f L ff L D M r 2 Δi d Δλ d Δi d = L d = L d 3 2 M f 2 L D + M D 2 L ff 2M f M r M D L ff L D M r 2 This is the direct- axis sub- transient inductance. A similar inductance can be defined for the q- axis. 10/8/13 Symmetrical Faults 88
89 TRANSIENT AND SUBTRANSIENT EFFECTS Further Considera^ons The direct- axis sub- transient reactance is X d = ωl d X d is considerably smaller than X d, hence X d < X d < X d We have shown that the synchronous machine has different reactances when it is subjected to short- circuit faults at its terminals. Immediately upon occurrence of the short circuit, the armature of the machine behaves with an effecdve reactance X d, which combines with an effecdve resistance determined by the damping circuits to define a direct- axis, short- circuit sub- transient Dme constant T d, typically in the range of 0.03 seconds. 10/8/13 Symmetrical Faults 89
90 TRANSIENT AND SUBTRANSIENT EFFECTS Further Considera^ons The direct- axis sub- transient reactance is X d = ωl d The period over which X d is effecdve is called the sub- transient period, and this is typically 3 to 4 cycles of system frequency in duradon. When the damper- winding currents decay to negligible levels, the D- and Q- circuits are no longer needed and the model reverts to original one obtained. The machine currents decay more slowly with a direct- axis, short- circuit transient Dme- constant T d determined by X d and a machine resistance which depends on R f of the field. 10/8/13 Symmetrical Faults 90
91 TRANSIENT AND SUBTRANSIENT EFFECTS Further Considera^ons The period of effecdveness of X d is called the transient period and T d is of the order of 1 second. Finally, for sustained steady- state condidons the d- and q- axis reactances X d = ωl d and X q = ωl q determine the performance of the saient- pole machine, just as the synchronous reactance X d applies to the round- rotor synchronous machine in the steady state. The various reactances are supplied by the machine manufacturers. 10/8/13 Symmetrical Faults 91
92 Example Same Example as from Slide 32. Calculate the per- unit value of X d. Use the radngs of 635 MVA and 24 kv as base quanddes. As before: L d = L s + M f = = mH The transient inductance is calculated from: L d = L d 3 2 M f 2 The transient reactance is: ( ) 2 = L ff = mH X d = ω L d = 120π mH = 0.254Ω 10/8/13 Symmetrical Faults 92
93 Example Same Example as from Slide 33. The impedance base on the machine radngs is Z base = V 2 base = 242 VI base 635 = 0.907Ω Thus: X d = = 0.28 per unit Note: X d = ω L d = 120π mH = Ω 1.72 per unit Hence X d X d 10/8/13 Symmetrical Faults 93
94 Short- Circuit Currents As seen in the beginning, when an ac voltage is applied suddenly across a series R- L circuit the current generally has two components: a dc component, which decays according to the Dme constant L/R of the circuit, and a steady- state sinusoidally varying component of constant amplitude. A similar but more complex phenomenon occurs when a short circuit appears suddenly across the terminals of a synchronous machine. We have the model do the short- circuit analysis. 10/8/13 Symmetrical Faults 94
95 Short- Circuit Currents The resuldng phase currents in the machine will have dc components, which cause them to be offset or asymmetrical when ployed as a funcdon of Dme as we have seen. We generally neglect the dc- components of the currents. If we were to examine the current in one of the phases we would find that the ac- component varied as: i( t) = 2 E i cosωt 1 X d X d X d e t T d X d X d e t T d We see the influence of the transient and sub- transient reactances. 10/8/13 Symmetrical Faults 95
96 TRANSIENT AND SUBTRANSIENT EFFECTS i( t) t e T d e t T d c b a 2 E i cosωt X d t = 0 Short occurs at t = 0. Time 2 E i cosωt X d 10/8/13 Symmetrical Faults 96
97 TRANSIENT AND SUBTRANSIENT EFFECTS With the dc levels removed (which wouldn t make through the transformer anyway), the armature phase current has three componetns, two of which decay at different rates over the sub- transient and transient periods. NeglecDng the small armature resistance, the height at point a is the maximum value of the sustained short- circuit current, with rms value given by: I = E i X d = E i X d 10/8/13 Symmetrical Faults 97
98 TRANSIENT AND SUBTRANSIENT EFFECTS If the envelope of the current wave is extended back to zero Dme and the first few cycles where the falloff is very rapid were neglected, the intercept is at height b. The rms value of this current is known as the transient current: I = E i X d Similarly, the rms value of the current whose height is at c is known as the sub- transient current: I = E i X d 10/8/13 Symmetrical Faults 98
99 TRANSIENT AND SUBTRANSIENT EFFECTS The sub- transient current is omen called the inidal symmetrical rms current, a more descripdve name because it conveys the idea of neglecdng the dc component and taking the rms value of the ac component of the current immediately amer the occurrence of the fault. The simple equadons: I = E i X d indicate a method of determining the fault current in a generator when its reactances are known. I = E i X d 10/8/13 Symmetrical Faults 99
100 TRANSIENT AND SUBTRANSIENT EFFECTS If the generator is unloaded when the fault occurs, the machine is represented by the no- load voltage to neutral in series with the proper reactance: j X d j X d jx d ± E i ± E i ± E i Used to calculate currents for sub- transient condidons. Used to calculate currents for transient condidons. Used to calculate currents for steady- state condidons. 10/8/13 Symmetrical Faults 100
101 Example Two generators are connected in parallel to the low- voltage side of a three- phase Δ - Y transformer as shown. G 1 G 2 Δ- Y Generator 1 is rated 50,000 kva, 13.8 kv. Generator 2 is rated 25,000 kva, 13.8 kv. Each generator has a sub- transient reactance of 25% on its own own base. The transformer is rated 75,000 kva, 13.8Δ /69Y kv, with a reactance of 10%. Before the fault occurs, the voltage on the high- voltage side of the transformer is 66 kv. The transformer is unloaded and there is no circuladng current between the generators. Find the sub- transient current in each generator when a three- phase short circuit occurs on the high- voltage side of the transformer. 10/8/13 Symmetrical Faults 101
102 Example Select 69 kv, 75,000 kva as the base in the high- voltage circuit. Then, the base voltage on the low- voltage side is 13.8 kv. E i1 = E i2 = = p.u. G 1 G 2 50,000 kva 13.8 kv 25,000 kva 13.8 kv VA Base = 75,000 kva V Base = 13.8 kv VA Base = 75,000 kva V Base = 69 kv Δ- Y 75,000 kva 13.8Δ /69Y kv For Generator 1: X d1 = ,000 50,000 = p.u. Note: How did I get this? Z p.u. = Z rated V rated V base 2 VABase VA rated. 10/8/13 Symmetrical Faults 102
103 Example Select 69 kv, 75,000 kva as the base in the high- voltage circuit. Then, the base voltage on the low- voltage side is 13.8 kv. E i1 = E i2 = = p.u. G 1 G 2 50,000 kva 13.8 kv 25,000 kva 13.8 kv VA Base = 75,000 kva V Base = 13.8 kv VA Base = 75,000 kva V Base = 69 kv Δ- Y 75,000 kva 13.8Δ /69Y kv For Generator 2: Transformer: X d 2 = ,000 25,000 X t = 0.1 p.u. = p.u. 10/8/13 Symmetrical Faults 103
104 Example Pictured below is the reactance diagram before the fault. A three- phase fault is simulated by closing the switch. The internal voltages of the two machines may be considered to be in parallel since they are idendcal in magnitude and phase and no circuladng current flows between them. G 1 E i1 j X d1 = j0.375 jx t = j0.1 P (fault) G 2 E i2 j X d 2 = j0.75 S 10/8/13 Symmetrical Faults 104
105 Example The equivalent sub- transient reactance is: X d = X d1 j X d 2 = X d1 X d 2 = X d1 + X d = 0.25 p.u. With E i1 = E i2 = E i the current in the short- circuit is: = X d1 j X d 2 = I = E i X d1 X d 2 = X d1 + X d 2 ( ) = j( ) j X d + X t = 0.25 p.u. = j2.735 p.u. 10/8/13 Symmetrical Faults 105
106 Example The voltage on the Δ- side of the transformer is: V t = I jx t = j2.735 j0.1= p.u. In generators 1 and 2: I 1 = E V i 1 t = j X d1 I 2 = E V i 2 t = j X d j j0.75 = j1.823 p.u. = j0.912 p.u. 10/8/13 Symmetrical Faults 106
107 Summary The steady- state performance of the synchronous machine relies on the concept of synchronous reactance X d, which is the basis of the steady- state equivalent circuit of the machine. Transient analysis of the synchronous generator requires a two- axis machine model. We have seen that the corresponding equadons involving physical a- b- c phase variables can be simplified by Park s transformadon, which introduces d,q,0 currents, voltages, and flux linkages. Simplified equivalent circuits which follow from the d- q- 0 equadons of the machine allow definidons of the subtransient reactance X d and transient reactance X d. The transient reactance is also important for system stability analysis. 10/8/13 Symmetrical Faults 107
108 Power Systems Three- Phase Short Circuits AssumpDons made to calculate the sub- transient fault current for a three- phase short circuit in a power system: 1. Transformers are represented by their leakage reactances. Winding resistances, shunt admiyances, and Δ Y phase shims are neglected. 2. Transmission lines are represented by their equivalent series reactances. Series resistances and shunt admiyances are neglected. 3. Synchronous machines are represented by constant- voltage sources behind subtransient reactances. Armature resistance, saliency, and saturadon are neglected. 10/8/13 Symmetrical Faults 108
109 Power Systems Three- Phase Short Circuits These assumpdons are made for simplicity, and may not always apply. For example, in distribudon systems, the resistances of primary and secondary distribudon lines may in some cases significantly reduce fault current magnitudes. Saliency: The word saliency is used as a short expression for the fact that the rotor of a synchronous machine has different electric and magnedc properdes on two axes 90 o apart; the direct axis, or axis of symmetry of a field pole, and the quadrature axis, or axis of symmetry midway between two field poles. This difference between the two axes is present not only in salient- pole machines but also, to a lesser extent, in round- rotor machines, because of the presence of the field winding on the direct axis only. 10/8/13 Symmetrical Faults 109
110 Power Systems Three- Phase Short Circuits Consider a generator that is loaded when a fault occurs. Pre- Fault Model Synchronous reactance No- Load voltage jx dg + + E g V t Z ext Pre- fault current Terminal voltage Neutral Fault loca^on P I L + Z L V L = V f This is a steady- state model. It does not capture transient behavior. If a three- phase short circuit fault occurs from P to neutral, the equivalent circuit shown above does not sadsfy the condidons for calculadng sub- transient current. 10/8/13 Symmetrical Faults 110
111 Power Systems Three- Phase Short Circuits AMer the fault occurs, here is the correct circuit: Z ext P I L + j X dg + + E g V t Neutral S V f Z L Fault Model ( X ) dg I L E g = V t + j X dg I L = V f + Z ext + j 10/8/13 Symmetrical Faults 111
112 Power Systems Three- Phase Short Circuits With the switch open: ( X ) dg I L E g = V t + j X dg I L = V f + Z ext + j This equadons defines E g, the sub- transient internal voltage, is used to calculate the subtransient current I. Similarly, to calculate the transient current I, it must be supplied through the transient reactance X dg and the transient internal voltage E g : ( X ) dg I L E g = V t + j X dg I L = V f + Z ext + j 10/8/13 Symmetrical Faults 112
113 Power Systems Three- Phase Short Circuits Thus, the value of the load current I L determines the values of the voltages E g and E g, which are both equal to the no- load voltage E g only when I L is zero so that E g is then equal to V t. It is important to note that the pardcular value of E g in series with X g represents the generator immediately before and immediately amer the fault occurs only if the prefault current in the generator has the corresponding value of I L. On the other hand, E g in series with the synchronous reactance X dg is the equivalent circuit of the machine under steady- state condidons for any value of the load current. The magnitude of E g is determined by the field current of the machine, and so for a different value of I L in the pre- fault circuit le g I would remain the same but a new value of E g would be required. 10/8/13 Symmetrical Faults 113
114 Power Systems Three- Phase Short Circuits Synchronous motors have reactances of the same type as generators. When a motor is short- circuited, it no longer receives electric energy from the power line, but its field remains energized and the inerda of its rotor and connected load keeps it rotadng for a short period of Dme. 10/8/13 Symmetrical Faults 114
115 Power Systems Three- Phase Short Circuits The internal voltage of a synchronous motor causes it to contribute current to the system, for it is then acdng like a generator. By comparison with the corresponding formulas for a generator the subtransient internal voltage E m and transient internal voltage E m for a synchronous motor are given by E m = V t j X dm I L E m = V t j X dm I L where V t is now the terminal voltage of the motor. 10/8/13 Symmetrical Faults 115
116 Power Systems Three- Phase Short Circuits Fault currents in systems containing generators and motors under load may be solved in one of two ways: 1. by calculadng the subtransient (or transient) internal voltages of the machines or 2. by using Thévenin's theorem. An example will illustrate. 10/8/13 Symmetrical Faults 116
117 Power Systems Three- Phase Short Circuits Suppose that a synchronous generator is connected to a synchronous motor by a line of external impedance Z ext. The motor is drawing load current I L from the generator when a symmetrical three- phase fault occurs at the motor terminals. The equivalent circuits and current flows of the system immediately before and immediately amer the fault occurs are 10/8/13 Symmetrical Faults 117
118 Power Systems Three- Phase Short Circuits Before the Fault: Z ext P I L + + j X dg j X dm + E g V t V f + E m Neutral 10/8/13 Symmetrical Faults 118
119 Power Systems Three- Phase Short Circuits A\er the Fault: Z ext I g P I m + j X dg + I '' f j X dm + E g V t V f + E m Neutral 10/8/13 Symmetrical Faults 119
ECE 422/522 Power System Operations & Planning/ Power Systems Analysis II 2 Synchronous Machine Modeling
ECE 422/522 Power System Operations & Planning/ Power Systems Analysis II 2 Synchronous achine odeling Spring 214 Instructor: Kai Sun 1 Outline Synchronous achine odeling Per Unit Representation Simplified
More informationBehaviour of synchronous machine during a short-circuit (a simple example of electromagnetic transients)
ELEC0047 - Power system dynamics, control and stability (a simple example of electromagnetic transients) Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct October 2018 1 / 25 Objectives
More informationEquivalent Circuits with Multiple Damper Windings (e.g. Round rotor Machines)
Equivalent Circuits with Multiple Damper Windings (e.g. Round rotor Machines) d axis: L fd L F - M R fd F L 1d L D - M R 1d D R fd R F e fd e F R 1d R D Subscript Notations: ( ) fd ~ field winding quantities
More informationThe synchronous machine (detailed model)
ELEC0029 - Electric Power System Analysis The synchronous machine (detailed model) Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct February 2018 1 / 6 Objectives The synchronous
More informationDynamics of the synchronous machine
ELEC0047 - Power system dynamics, control and stability Dynamics of the synchronous machine Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct October 2018 1 / 38 Time constants and
More informationChapter 8: Unsymmetrical Faults
Chapter 8: Unsymmetrical Faults Introduction The sequence circuits and the sequence networks developed in the previous chapter will now be used for finding out fault current during unsymmetrical faults.
More informationSynchronous Machine Modeling
ECE 53 Session ; Page / Fall 07 Synchronous Machine Moeling Reference θ Quarature Axis B C Direct Axis Q G F D A F G Q A D C B Transient Moel for a Synchronous Machine Generator Convention ECE 53 Session
More informationMassachusetts Institute of Technology Department of Electrical Engineering and Computer Science Electric Machines
Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science 6.685 Electric Machines Problem Set 10 Issued November 11, 2013 Due November 20, 2013 Problem 1: Permanent
More informationFrom now, we ignore the superbar - with variables in per unit. ψ ψ. l ad ad ad ψ. ψ ψ ψ
From now, we ignore the superbar - with variables in per unit. ψ 0 L0 i0 ψ L + L L L i d l ad ad ad d ψ F Lad LF MR if = ψ D Lad MR LD id ψ q Ll + Laq L aq i q ψ Q Laq LQ iq 41 Equivalent Circuits for
More informationECE 421/521 Electric Energy Systems Power Systems Analysis I 3 Generators, Transformers and the Per-Unit System. Instructor: Kai Sun Fall 2013
ECE 41/51 Electric Energy Systems Power Systems Analysis I 3 Generators, Transformers and the Per-Unit System Instructor: Kai Sun Fall 013 1 Outline Synchronous Generators Power Transformers The Per-Unit
More informationEE 742 Chapter 3: Power System in the Steady State. Y. Baghzouz
EE 742 Chapter 3: Power System in the Steady State Y. Baghzouz Transmission Line Model Distributed Parameter Model: Terminal Voltage/Current Relations: Characteristic impedance: Propagation constant: π
More informationUnderstanding the Inductances
Understanding the Inductances We have identified six different inductances (or reactances) for characterizing machine dynamics. These are: d, q (synchronous), ' d, ' q (transient), '' d,'' q (subtransient)
More informationModule 3 : Sequence Components and Fault Analysis
Module 3 : Sequence Components and Fault Analysis Lecture 12 : Sequence Modeling of Power Apparatus Objectives In this lecture we will discuss Per unit calculation and its advantages. Modeling aspects
More informationSynchronous Machines
Synchronous Machines Synchronous generators or alternators are used to convert mechanical power derived from steam, gas, or hydraulic-turbine to ac electric power Synchronous generators are the primary
More informationROEVER COLLEGE OF ENGINEERING & TECHNOLOGY ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING ELECTRICAL MACHINES I
ROEVER COLLEGE OF ENGINEERING & TECHNOLOGY ELAMBALUR, PERAMBALUR-621220 DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING ELECTRICAL MACHINES I Unit I Introduction 1. What are the three basic types
More information(Refer Slide Time: 00:55) Friends, today we shall continue to study about the modelling of synchronous machine. (Refer Slide Time: 01:09)
(Refer Slide Time: 00:55) Power System Dynamics Prof. M. L. Kothari Department of Electrical Engineering Indian Institute of Technology, Delhi Lecture - 09 Modelling of Synchronous Machine (Contd ) Friends,
More informationEE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A
EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A 1. What are the advantages of an inter connected system? The advantages of an inter-connected system are
More informationSECTION 7: FAULT ANALYSIS. ESE 470 Energy Distribution Systems
SECTION 7: FAULT ANALYSIS ESE 470 Energy Distribution Systems 2 Introduction Power System Faults 3 Faults in three-phase power systems are short circuits Line-to-ground Line-to-line Result in the flow
More informationLesson 17: Synchronous Machines
Lesson 17: Synchronous Machines ET 332b Ac Motors, Generators and Power Systems Lesson 17_et332b.pptx 1 Learning Objectives After this presentation you will be able to: Explain how synchronous machines
More informationIntroduction to Synchronous. Machines. Kevin Gaughan
Introduction to Synchronous Machines Kevin Gaughan The Synchronous Machine An AC machine (generator or motor) with a stator winding (usually 3 phase) generating a rotating magnetic field and a rotor carrying
More informationEE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION
EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION PART: A 1. Define per unit value of an electrical quantity. Write equation for base impedance with respect to 3-phase system. 2. What is bus admittance
More informationChapter 4. Synchronous Generators. Basic Topology
Basic Topology Chapter 4 ynchronous Generators In stator, a three-phase winding similar to the one described in chapter 4. ince the main voltage is induced in this winding, it is also called armature winding.
More informationAn Introduction to Electrical Machines. P. Di Barba, University of Pavia, Italy
An Introduction to Electrical Machines P. Di Barba, University of Pavia, Italy Academic year 0-0 Contents Transformer. An overview of the device. Principle of operation of a single-phase transformer 3.
More informationECE 325 Electric Energy System Components 7- Synchronous Machines. Instructor: Kai Sun Fall 2015
ECE 325 Electric Energy System Components 7- Synchronous Machines Instructor: Kai Sun Fall 2015 1 Content (Materials are from Chapters 16-17) Synchronous Generators Synchronous Motors 2 Synchronous Generators
More informationYou know for EE 303 that electrical speed for a generator equals the mechanical speed times the number of poles, per eq. (1).
Stability 1 1. Introduction We now begin Chapter 14.1 in your text. Our previous work in this course has focused on analysis of currents during faulted conditions in order to design protective systems
More informationB.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis
B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester Electrical and Electronics Engineering EE 1352 Power System Analysis (Regulation 2008) Time: Three hours Answer all questions Part A (10
More informationEEE3405 ELECTRICAL ENGINEERING PRINCIPLES 2 - TEST
ATTEMPT ALL QUESTIONS (EACH QUESTION 20 Marks, FULL MAKS = 60) Given v 1 = 100 sin(100πt+π/6) (i) Find the MS, period and the frequency of v 1 (ii) If v 2 =75sin(100πt-π/10) find V 1, V 2, 2V 1 -V 2 (phasor)
More informationRevision Guide for Chapter 15
Revision Guide for Chapter 15 Contents tudent s Checklist Revision otes Transformer... 4 Electromagnetic induction... 4 Generator... 5 Electric motor... 6 Magnetic field... 8 Magnetic flux... 9 Force on
More informationTHREE PHASE SYSTEMS Part 1
ERT105: ELECTRCAL TECHNOLOGY CHAPTER 3 THREE PHASE SYSTEMS Part 1 1 Objectives Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate
More informationINDUCTION MOTOR MODEL AND PARAMETERS
APPENDIX C INDUCTION MOTOR MODEL AND PARAMETERS C.1 Dynamic Model of the Induction Motor in Stationary Reference Frame A three phase induction machine can be represented by an equivalent two phase machine
More informationELECTROMAGNETIC OSCILLATIONS AND ALTERNATING CURRENT
Chapter 31: ELECTROMAGNETIC OSCILLATIONS AND ALTERNATING CURRENT 1 A charged capacitor and an inductor are connected in series At time t = 0 the current is zero, but the capacitor is charged If T is the
More informationMassachusetts Institute of Technology Department of Electrical Engineering and Computer Science
Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science 6.685 Electric Machines Class Notes 4: Elementary Synchronous Machine Models September 14, 2005 c 2005 James
More informationEE 6501 POWER SYSTEMS UNIT I INTRODUCTION
EE 6501 POWER SYSTEMS UNIT I INTRODUCTION PART A (2 MARKS) 1. What is single line diagram? A Single line diagram is diagrammatic representation of power system in which the components are represented by
More informationPhysics 142 AC Circuits Page 1. AC Circuits. I ve had a perfectly lovely evening but this wasn t it. Groucho Marx
Physics 142 A ircuits Page 1 A ircuits I ve had a perfectly lovely evening but this wasn t it. Groucho Marx Alternating current: generators and values It is relatively easy to devise a source (a generator
More informationSSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL
1 SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL Power Systems: Generation, Transmission and Distribution Power Systems: Generation, Transmission and Distribution Power Systems:
More informationKINGS COLLEGE OF ENGINEERING Punalkulam
KINGS COLLEGE OF ENGINEERING Punalkulam 613 303 DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING POWER SYSTEM ANALYSIS QUESTION BANK UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A (TWO MARK
More informationGeneralized Theory of Electrical Machines- A Review
Generalized Theory of Electrical Machines- A Review Dr. Sandip Mehta Department of Electrical and Electronics Engineering, JIET Group of Institutions, Jodhpur Abstract:-This paper provides an overview
More informationCHAPTER 8 DC MACHINERY FUNDAMENTALS
CHAPTER 8 DC MACHINERY FUNDAMENTALS Summary: 1. A Simple Rotating Loop between Curved Pole Faces - The Voltage Induced in a Rotating Loop - Getting DC voltage out of the Rotating Loop - The Induced Torque
More information+ ( )= with initial condition
Department of Electrical Engineering PhD. Admission Test Full Marks: 90 Time 90 minutes Date: 02.2.204 NAME: Appl. No: Write your answer on the question paper ONLY. All questions carry equal marks. PART
More informationChapter 3 AUTOMATIC VOLTAGE CONTROL
Chapter 3 AUTOMATIC VOLTAGE CONTROL . INTRODUCTION TO EXCITATION SYSTEM The basic function of an excitation system is to provide direct current to the field winding of the synchronous generator. The excitation
More informationPROBLEM SOLUTIONS: Chapter 4
48 PROBLEM SOLUTIONS: Chapter 4 Problem 4.1 ω m = 100 π/30 = 40π rad/sec part (b): 60 Hz; 10π rad/sec part (c): 100 5/6 = 1000 r/min Problem 4. The voltages in the remaining two phases can be expressed
More informationGeneration, transmission and distribution, as well as power supplied to industrial and commercial customers uses a 3 phase system.
Three-phase Circuits Generation, transmission and distribution, as well as power supplied to industrial and commercial customers uses a 3 phase system. Where 3 voltages are supplied of equal magnitude,
More informationLecture 9: Space-Vector Models
1 / 30 Lecture 9: Space-Vector Models ELEC-E8405 Electric Drives (5 ECTS) Marko Hinkkanen Autumn 2017 2 / 30 Learning Outcomes After this lecture and exercises you will be able to: Include the number of
More informationECE 585 Power System Stability
Homework 1, Due on January 29 ECE 585 Power System Stability Consider the power system below. The network frequency is 60 Hz. At the pre-fault steady state (a) the power generated by the machine is 400
More informationRLC Circuit (3) We can then write the differential equation for charge on the capacitor. The solution of this differential equation is
RLC Circuit (3) We can then write the differential equation for charge on the capacitor The solution of this differential equation is (damped harmonic oscillation!), where 25 RLC Circuit (4) If we charge
More informationTutorial Sheet Fig. Q1
Tutorial Sheet - 04 1. The magnetic circuit shown in Fig. Q1 has dimensions A c = A g = 9 cm 2, g = 0.050 cm, l c = 30 cm, and N = 500 turns. Assume the value of the relative permeability,µ r = 70,000
More informationEstimation of synchronous generator parameters using an observer for damper currents and a graphical user interface
Electric Power Systems Research 69 (2004) 7 16 Estimation of synchronous generator parameters using an observer for damper currents and a graphical user interface Elias Kyriakides, Gerald T. Heydt Department
More informationRevision Guide for Chapter 15
Revision Guide for Chapter 15 Contents Revision Checklist Revision otes Transformer...4 Electromagnetic induction...4 Lenz's law...5 Generator...6 Electric motor...7 Magnetic field...9 Magnetic flux...
More informationCHAPTER 5 SIMULATION AND TEST SETUP FOR FAULT ANALYSIS
47 CHAPTER 5 SIMULATION AND TEST SETUP FOR FAULT ANALYSIS 5.1 INTRODUCTION This chapter describes the simulation model and experimental set up used for the fault analysis. For the simulation set up, the
More informationPrince Sattam bin Abdulaziz University College of Engineering. Electrical Engineering Department EE 3360 Electrical Machines (II)
Chapter # 4 Three-Phase Induction Machines 1- Introduction (General Principles) Generally, conversion of electrical power into mechanical power takes place in the rotating part of an electric motor. In
More informationFault Analysis Power System Representation
.1. Power System Representation Single Line Diagram: Almost all modern power systems are three phase systems with the phases of equal magnitude and equal phase difference (i.e., 10 o ). These three phase
More informationECE 692 Advanced Topics on Power System Stability 2 Power System Modeling
ECE 692 Avance Topics on Power System Stability 2 Power System Moeling Spring 2016 Instructor: Kai Sun 1 Outline Moeling of synchronous generators for Stability Stuies Moeling of loas Moeling of frequency
More informationLecture 1: Induction Motor
1 / 22 Lecture 1: Induction Motor ELEC-E8402 Control of Electric Drives and Power Converters (5 ECTS) Marko Hinkkanen Aalto University School of Electrical Engineering Spring 2016 2 / 22 Learning Outcomes
More informationPROBLEMS - chapter 3 *
OpenStax-CNX module: m28362 1 PROBLEMS - chapter 3 * NGUYEN Phuc This work is produced by OpenStax-CNX and licensed under the Creative Commons Attribution License 3.0 PROBLEMS This lecture note is based
More informationTransformer Fundamentals
Transformer Fundamentals 1 Introduction The physical basis of the transformer is mutual induction between two circuits linked by a common magnetic field. Transformer is required to pass electrical energy
More informationUNIT I INTRODUCTION Part A- Two marks questions
ROEVER COLLEGE OF ENGINEERING & TECHNOLOGY ELAMBALUR, PERAMBALUR-621220 DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING DESIGN OF ELECTRICAL MACHINES UNIT I INTRODUCTION 1. Define specific magnetic
More informationThree Phase Circuits
Amin Electronics and Electrical Communications Engineering Department (EECE) Cairo University elc.n102.eng@gmail.com http://scholar.cu.edu.eg/refky/ OUTLINE Previously on ELCN102 Three Phase Circuits Balanced
More informationMassachusetts Institute of Technology Department of Electrical Engineering and Computer Science
Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science 6.685 Electric Machines Class Notes 7: Permanent Magnet Brushless DC Motors September 5, 005 c 005 James
More informationELECTROMAGNETIC INDUCTION
ELECTROMAGNETIC INDUCTION 1. Magnetic Flux 2. Faraday s Experiments 3. Faraday s Laws of Electromagnetic Induction 4. Lenz s Law and Law of Conservation of Energy 5. Expression for Induced emf based on
More informationAlternating Current. Symbol for A.C. source. A.C.
Alternating Current Kirchoff s rules for loops and junctions may be used to analyze complicated circuits such as the one below, powered by an alternating current (A.C.) source. But the analysis can quickly
More informationAC Circuits Homework Set
Problem 1. In an oscillating LC circuit in which C=4.0 μf, the maximum potential difference across the capacitor during the oscillations is 1.50 V and the maximum current through the inductor is 50.0 ma.
More informationTransients on Integrated Power System
Chapter 3 Transients on Integrated Power System 3.1 Line Dropping and Load Rejection 3.1.1 Line Dropping In three phase circuit capacitance switching, the determination of the voltage trapped after switching
More informationParameter Sensitivity Analysis of an Industrial Synchronous Generator
Parameter Sensitivity Analysis of an Industrial Synchronous Generator Attila Fodor, Attila Magyar, Katalin M. Hangos Abstract A previously developed simple dynamic model of an industrial size synchronous
More informationControl of Wind Turbine Generators. James Cale Guest Lecturer EE 566, Fall Semester 2014 Colorado State University
Control of Wind Turbine Generators James Cale Guest Lecturer EE 566, Fall Semester 2014 Colorado State University Review from Day 1 Review Last time, we started with basic concepts from physics such as
More informationGenerators. What its all about
Generators What its all about How do we make a generator? Synchronous Operation Rotor Magnetic Field Stator Magnetic Field Forces and Magnetic Fields Force Between Fields Motoring Generators & motors are
More informationGet Discount Coupons for your Coaching institute and FREE Study Material at ELECTROMAGNETIC INDUCTION
ELECTROMAGNETIC INDUCTION 1. Magnetic Flux 2. Faraday s Experiments 3. Faraday s Laws of Electromagnetic Induction 4. Lenz s Law and Law of Conservation of Energy 5. Expression for Induced emf based on
More informationFault Calculation Methods
ELEC9713 Industrial and Commercial Power Systems Fault Calculation Methods There are two major problems that can occur in electrical systems: these are open circuits and short circuits. Of the two, the
More informationSESSION 3. Short Circuit Calculations, Unsymmetrical Faults. Leonard Bohmann, Michigan State University Elham Makram, Clemson University
SESSON Short Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University Short Circuit Calculations Leonard Bohmann Michigan State University
More informationElectric Machines I Three Phase Induction Motor. Dr. Firas Obeidat
Electric Machines I Three Phase Induction Motor Dr. Firas Obeidat 1 Table of contents 1 General Principles 2 Construction 3 Production of Rotating Field 4 Why Does the Rotor Rotate 5 The Slip and Rotor
More informationComparative Study of Synchronous Machine, Model 1.0 and Model 1.1 in Transient Stability Studies with and without PSS
Comparative Study of Synchronous Machine, Model 1.0 and Model 1.1 in Transient Stability Studies with and without PSS Abhijit N Morab, Abhishek P Jinde, Jayakrishna Narra, Omkar Kokane Guide: Kiran R Patil
More informationStep Motor Modeling. Step Motor Modeling K. Craig 1
Step Motor Modeling Step Motor Modeling K. Craig 1 Stepper Motor Models Under steady operation at low speeds, we usually do not need to differentiate between VR motors and PM motors (a hybrid motor is
More informationSimulations and Control of Direct Driven Permanent Magnet Synchronous Generator
Simulations and Control of Direct Driven Permanent Magnet Synchronous Generator Project Work Dmitry Svechkarenko Royal Institute of Technology Department of Electrical Engineering Electrical Machines and
More informationPart 4: Electromagnetism. 4.1: Induction. A. Faraday's Law. The magnetic flux through a loop of wire is
1 Part 4: Electromagnetism 4.1: Induction A. Faraday's Law The magnetic flux through a loop of wire is Φ = BA cos θ B A B = magnetic field penetrating loop [T] A = area of loop [m 2 ] = angle between field
More informationBEE701 POWER SYSTEM ANALYSIS
BEE701 POWER SYSTEM ANALYSIS UNIT I POWER SYSTEM COMPONENTS Power system analysis The evaluation of power system is called as power system analysis Functions of power system analysis To monitor the voltage
More informationJRE SCHOOL OF Engineering
JRE SCHOOL OF Engineering Class Test-1 Examinations September 2014 Subject Name Electromechanical Energy Conversion-II Subject Code EEE -501 Roll No. of Student Max Marks 30 Marks Max Duration 1 hour Date
More informationUnified Torque Expressions of AC Machines. Qian Wu
Unified Torque Expressions of AC Machines Qian Wu Outline 1. Review of torque calculation methods. 2. Interaction between two magnetic fields. 3. Unified torque expression for AC machines. Permanent Magnet
More informationEddy Current Heating in Large Salient Pole Generators
Eddy Current Heating in Large Salient Pole Generators C.P.Riley and A.M. Michaelides Vector Fields Ltd., 24 Bankside, Kidlington, Oxford OX5 1JE, UK phone: (+44) 1865 370151, fax: (+44) 1865 370277 e-mail:
More informationINSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous)
INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad - 500 043 ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK Course Name : Computer Methods in Power Systems Course Code : A60222
More informationChapter 33. Alternating Current Circuits
Chapter 33 Alternating Current Circuits 1 Capacitor Resistor + Q = C V = I R R I + + Inductance d I Vab = L dt AC power source The AC power source provides an alternative voltage, Notation - Lower case
More informationPOWER SYSTEM STABILITY
LESSON SUMMARY-1:- POWER SYSTEM STABILITY 1. Introduction 2. Classification of Power System Stability 3. Dynamic Equation of Synchronous Machine Power system stability involves the study of the dynamics
More information1 Phasors and Alternating Currents
Physics 4 Chapter : Alternating Current 0/5 Phasors and Alternating Currents alternating current: current that varies sinusoidally with time ac source: any device that supplies a sinusoidally varying potential
More informationChapter 5 Three phase induction machine (1) Shengnan Li
Chapter 5 Three phase induction machine (1) Shengnan Li Main content Structure of three phase induction motor Operating principle of three phase induction motor Rotating magnetic field Graphical representation
More informationEnergy Converters. CAD and System Dynamics
Institut für Elektrische Energiewandlung Energy Converters CAD and System Dynamics - Tutorials - Issue 2017/2018 M.Sc. Sascha Neusüs / M.Sc. Marcel Lehr Professor Dr.-Ing. habil. Dr. h.c. Andreas Binder
More information12 Chapter Driven RLC Circuits
hapter Driven ircuits. A Sources... -. A ircuits with a Source and One ircuit Element... -3.. Purely esistive oad... -3.. Purely Inductive oad... -6..3 Purely apacitive oad... -8.3 The Series ircuit...
More informationSHORT QUESTIONS AND ANSWERS. Year/ Semester/ Class : III/ V/ EEE Academic Year: Subject Code/ Name: EE6501/ Power System Analysis
Srividya colllege of Engg & Tech,Virudhunagar Sri Vidya College of Engineering And Technology Virudhunagar 626 005 Department of Electrical and Electronics Engineering QUESTION BANK SHORT QUESTIONS AND
More informationDynamic Modeling of Surface Mounted Permanent Synchronous Motor for Servo motor application
797 Dynamic Modeling of Surface Mounted Permanent Synchronous Motor for Servo motor application Ritu Tak 1, Sudhir Y Kumar 2, B.S.Rajpurohit 3 1,2 Electrical Engineering, Mody University of Science & Technology,
More informationElectrical Machines and Energy Systems: Operating Principles (Part 1) SYED A Rizvi
Electrical Machines and Energy Systems: Operating Principles (Part 1) SYED A Rizvi AC Machines Operating Principles: Rotating Magnetic Field The key to the functioning of AC machines is the rotating magnetic
More informationPower System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur
Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur Lecture - 9 Transmission Line Steady State Operation Welcome to lesson 9, in Power
More informationTHE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session
Name: Student ID: Signature: THE UNIVERSITY OF NEW SOUTH WALES School of Electrical Engineering & Telecommunications FINALEXAMINATION Session 00 ELEC46 Power System Analysis TIME ALLOWED: 3 hours TOTAL
More informationModeling Free Acceleration of a Salient Synchronous Machine Using Two-Axis Theory
1 Modeling ree Acceleration of a Salient Synchronous Machine Using Two-Axis Theory Abdullah H. Akca and Lingling an, Senior Member, IEEE Abstract This paper investigates a nonlinear simulation model of
More informationMathematical Modeling and Dynamic Simulation of a Class of Drive Systems with Permanent Magnet Synchronous Motors
Applied and Computational Mechanics 3 (2009) 331 338 Mathematical Modeling and Dynamic Simulation of a Class of Drive Systems with Permanent Magnet Synchronous Motors M. Mikhov a, a Faculty of Automatics,
More informationThe Linear Induction Motor, a Useful Model for examining Finite Element Methods on General Induction Machines
The Linear Induction Motor, a Useful Model for examining Finite Element Methods on General Induction Machines Herbert De Gersem, Bruno Renier, Kay Hameyer and Ronnie Belmans Katholieke Universiteit Leuven
More informationChapter 6. Induction Motors. Copyright The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
Chapter 6 Induction Motors 1 The Development of Induced Torque in an Induction Motor Figure 6-6 The development of induced torque in an induction motor. (a) The rotating stator field B S induces a voltage
More informationStepping Motors. Chapter 11 L E L F L D
Chapter 11 Stepping Motors In the synchronous motor, the combination of sinusoidally distributed windings and sinusoidally time varying current produces a smoothly rotating magnetic field. We can eliminate
More informationGenerators for wind power conversion
Generators for wind power conversion B. G. Fernandes Department of Electrical Engineering Indian Institute of Technology, Bombay Email : bgf@ee.iitb.ac.in Outline of The Talk Introduction Constant speed
More informationEN Power Electronics and Machines
1/19 - Power Electronics and Machines Transformers Suryanarayana Doolla Department of Energy Science and Engineering Indian Institute of Technology, Bombay suryad@iitb.ac.in Lecture Organization - Modules
More informationEE Branch GATE Paper 2010
Q.1 Q.25 carry one mark each 1. The value of the quantity P, where, is equal to 0 1 e 1/e 2. Divergence of the three-dimensional radial vector field is 3 1/r 3. The period of the signal x(t) = 8 is 0.4
More informationQUESTION BANK ENGINEERS ACADEMY. Power Systems Power System Stability 1
ower ystems ower ystem tability QUETION BANK. A cylindrical rotor generator delivers 0.5 pu power in the steady-state to an infinite bus through a transmission line of reactance 0.5 pu. The generator no-load
More informationEE 451 Power System Stability
EE 451 Power System Stability Power system operates in synchronous mode Power system is subjected to a wide range of disturbances (small and large) - Loads and generation changes - Network changes - Faults
More informationIn the previous chapter, attention was confined
4 4 Principles of Power System CHAPTE CHAPTE 8 Unsymmetrical Fault Calculations 8. Usymmetrical Faults on -Phase System 8. Symmetrical Components Method 8. Operator a 8.4 Symmetrical Components in Terms
More information