Default values for unit DX-S standard.
|
|
- Virgil Norman
- 6 years ago
- Views:
Transcription
1 Default values for unit DX-S standard. UNIFLAIR ITALIA spa 1. USER (U) : USER PASSWORD FACTORY (F) : FACTORY PASSWORD 177. Prob PROBES Tipo Min Max U.M. Var. Def Presence Superv /1 Presence external air probe B2 0 = absent 1 = NTC Carel /2 Type of humidity/press.temper. probe B3 0 = absent 1 = 0-1Vdc o 0-20mA 2 = 4-20 ma /3 Presence supply air B4 0 = absent 1 = NTC Carel (enable corresponding alarm) F 0 1 flags 1? (0,1) F 0 2 flags 1? (0,2) F 0 1 flags 1? (0,1) I36 I37 I38 /4 Value of humidity/pressure 0 ma, 4mA o 0Vdc /5 Value of humidity/pressure at 20mA o 1Vdc F 0 /5 %RH bar F /4 100 %RH bar /2 0 A /2 0 A37 /6 Calibration probe B1 F C A F /7 Calibration probe B2 F C /1 0 A F /8 Calibration probe B3 F /2 0 A40 /9 Calibration probe B4 F C /3 0 A F /A Digital filter F I39 /b Input limit F I40 /C Unit of measure (0=C,1=F) U 0 1 flag 1 0 D50 Attention the parameter can be various only by user terminal,not BY supervision Default values mp30 DX-S units std.doc Vers. 1.1 del 10/07/03
2 SEtP PROBES Tipo Min Max U.M. Var. Def Presence Superv r1 Temperature Set Point (cooling) U ra rb C/F A11 r2 Cooling differential U C A F r3 Heating differential U C A F r4 Temperature dead zone U C A F r5 Humidity Set Point U rc rd %RH /2 0 A18 r6 Humidification differential U 1 20 %RH /2 0 A21 r7 Dehumidification differential U 1 20 %RH /2 0 A22 r8 Humidity dead zone U 0 20 %RH /2 0 A23 r9 Temperature set point(heating) U ra rb C/F A12 ra Minimum temperature set point(also for F -20 rb C A13 compensation) 4 rb F rb Maximum temperature set point(also for F ra 60 C A14 compensation) ra 140 F rc Minimum humidity set point F 0 rd %RH /2 0 A19 rd Maximum humidity set point F rc 100 %RH /2 0 A20 re Type of temperature regulation: 0 = proportional 1 = proportional+integral F 0 1 flag 1 1 I23 rf Integration time for P+I action F sec re 0 I24 rg Authority(unique for Cooling/Heating) for compensation F /1 0 A24 rh Set point compensation on temp.read by F C /1 0 A25 B2(cooling) F ri Set point compensation on temp.read by F C /1 0 A26 B2 (heating) F rl Free cooling differential F 0 30 C/F /1 0 A27 rn Lower supply temperature limit during free F C/F /1 0 A28 cooling ro Reading from probe B2 / C/F Value /1 0 A3 rp Reading from probe B3 / %RH Value /2 0 A1 Bar rr Reading from probe B4 / C/F Value /3 0 A4 rt Time band setting: 0 = disabled 1 = fan on minimum with temp.monitoring 2 = On/off U 0 2 flag 0 I70 2/8
3 Con COMPRESSOR Tipo Min Max U.M. Var. Def Presence Superv c1 Minimum ON time F sec 1 60 I56 c2 Minimum OFF time F sec 1 60 I57 c3 Time between 2 start-ups F sec I58 c4 On delay between the 2 compressors F sec 1 90 I59 c5 OFF delay between the 2 compressors F sec 1 0 I60 c6 c7 c8 Compressor rotation: 0 = DISABLED 1 = ENABLED Delay compressor On fron supply fan startup Hour counterthreshold for the compressor: 0 = DISABLED 1 = ENABLED F 0 1 flag 1 1 I64 F sec 1 60 I61 U ore 1 0 I17 c9 Hour counter compressor 1 U ore - 0 I13 ca Hour counter compressor 2 U ore - 0 I14 3/8
4 FAn FANS Tipo Min Max U.M. Var. Def Presen. Superv F1 Fan operating mode: 0 = always ON 1 = Proportional speed regulation.if used in condensation the fan is kept at minimum even below the value of F5 2 = Proportional speed regulation.if used in condensation the fan is switched OFF below the value of F5,with an hysteresis of 0.5 bar for pressure or 1 C for temperature F 0 1 flags 1? (0= no RV) (1= with RV) I50 F2 Minimum Triac voltage threshold F 0 F3 step 1? (#) F3 Maximum Triac voltage threshold F F2 100 step 1? (#) I51 I52 F4 Triac pulse width F 0 15 msec 1 2 I53 F5 % regulation band for minimum speed of temperature/pressure for minimum speed in condensation F 0 0 /4 F6 % C bar A34 F6 % regulation band for maximum speed or temperature/pressure for maximum speed in condensation F F /5 % C bar A35 F7 Minimum output value F 0 F8 % 1? (#) I54 F8 Maximun output value F F7 100 % I55 F9 Fan hour counter threshold 0= disabled U ore 10 0 I15 FA Supply fan hour counter U ore - 0 I11 Fb Filter hour counter threshold 0= DISABLED U ore I16 FC Filter hour counter U ore - 0 I12 Fd Supply fan OFF delay F sec 1 10 I62 FE Fan pick-up time in condensation F 0 60 sec 1 0 I71 (#) = see table on page 8. 4/8
5 ALAR ALARM Tipo Min Max U.M. Var. Def Presence Superv P1 Flow alarm delay from fan start-up F sec I65 P2 Flow alarm delay during operation F 0 90 sec. 1 3 I66 P3 P4 Low pressure alarm delay from compressor ON Buzzer activation: 0 = OFF 1-14 = minutes 15 = continuous F sec I67 U 0 15 min 1 1 I44 P5 Reset alarms (various configurations) F 1 5 flag 1 3 I45 P6 P7 Delta from effective set point for low temperature alarm Delta from effective set point for high temperature alarm F 0 50 C/ F A29 F 0 50 C/ F A30 P8 Delta from set point for low humidity alarm F 0 50 %RH /2 0 A31 P9 PA Pb Delta from set point for high humidity alarm Alarm delay high/low temperature/humidity on start-up Type of management of generic alarm input ID5: 0 = no alarm connected 1 = Signal only alarm-automatic reset 2 = Signal only alarm-manual reset 3 = Serious alarm-automatic reset 4 = Serious alarm-manual reset 5 = Serious alarm-automatic reset also active in stand-by 6 = Serious alarm-manual reset also active in stand -by F 0 50 %RH /2 0 A32 U min 1 15 I68 F 6 flag 1 2 I32 PC Generic alarm delay U sec 1 0 Pb 0 I69 Pd Return-supply temp.difference for supply temperature alarm F C/ F /3 0 A33 5/8
6 GLb GENERAL Tipo Min Max U.M. Var. Def Presence Superv H1 Unit model: 0 = ED unit 1 = CW unit 2 = CW unit (heating/cooling) 3 = shelter F 0 2 flags 1 0 I18 H2 N of units in rotation: 0 = stand-alone unit 1 = 1 unit (master) 2 = 2 units...6 = 6 units U 0 6 flags 1? (0) or (1...6) I33 H3 Address of unit in rotation U 1 6 flag 1? H2 0 I34 (1...6) H4 Rotation time between a series of units 0 = Test mode t=2 minutes U ore H2 0 I35 H5 Operating mode of the 2 cool outputs - Out1/Out2-1 = 1 compressor (con H1=0,1,2) 1 = 1 compres. / 1 Heater. (con H1=3) 2 = 2 compressori on 2 circuit 3 = Three point valve 4 = 2 compressors in binary parallel 5 = 2 compressors. in tandem (50+50%) F 1 5 flags 1 1 I19 H6 Operating mode of the 2 heat outputs OUT3/OUT4 0 = No heating element 1 = 1 heating element 2 = 2 heating element 3 = Three-point valve 4 = 2 heating elements binary 5 = Three-point valve + heating element F 0 4 flags 1? (0,1,3,5 ) I20 H7 3 P valve or damper excursion time F sec I22 H8 Presence of humidifier: 0 = No 1 = Yes F 0 1 flags 1? (0,1) /2 0 I21 H9 Type of dehumidification: 0 = compressor 1 ON 1 = compressor 2 ON 2 = 2 compressor ON 3 = Capacity-controlled cooling damper (100%) 4 = fan speed reduction 5 = action = action = action = action = no action F 0 8 flag 1 5 /2 0 I25 6/8
7 GLb GENERAL Tipo Min Max U.M. Var. Def Presence Superv HA Function of the dehumidification relay: 0 = energised in dehumidification 1 = de-energised in dehumidification 2 = Relay for not serious alarms (follow logics of parameter HF) 3 = Output for rotation control F 0 3 flag 1? (2,3) I31 Hb Function of output Y2 (phase-cut) 0 = Supply fan speed control 1 = Condensation fan speed control using B3 2 = Condensation fan speed control using B2 F 0 2 flags 1 0 I28 HC Function of probe B2: 0 = Compensation 1 = free-cooling using 0-10V 2 = free-cooling using Out3-Out4 4= Condensation control Hd Function of probe B3: 0 = Humidity control 1 = Condensating control F 0 3 flag 1 0 /1 0 I26 F 0 1 flag 1 0 /2 0 I27 HE HF ON-OFF digital imput: 0 = absent 1 = present, on version UNIFLAIR on/off of user terminal 2 = absent, on version UNIFLAIR on/off of user terminal Alarm relay logic: 0 = De-energised in alarm for all alarms 1 = Energised in alarm for all alarms 2 = De-energised in alarm only for serious alarms 3 = Enerised in alarm only for serious alarms U 0 2 flag 1 0 I29 U 0 3 flag 1 0 I30 HG Delay on start -up U sec 1 0 I63 HH USER password U I48 Hi Block parameter modifications U/F(displayed by block) 0 = no block U 0 1 flag 1 0 I41 HL Parameter sets F 0 3 flag- 1 1 I42 7/8
8 GLb GENERAL Tipo Min Max U.M. Var. Def Presence Superv Hn Select data shown on display: 0 = Probes B1, B3 (if present) 1 = Temperature/humidity set point(if present) 2 = day and time (if clock present) F 0 2 flag 1 0 I43 Ho Supervision network serial address U I46 HP Supervision serial baudrate: 1 = 1200 Baud 2 = 2400 Baud 3 = 4800 Baud 4 = 9600 Baud 5 = Baud U 1 5 flag 1 5 I47 Hr Software version / 1.6 I49 Legend: Default values marked in BLACK are standard Carel values common for all unit models. Default values marked in BLUE refer only to the unit configuration mentioned. Default values marked in BLUE with a blue '?' (grey shaded square), are not-common to all units, these values are to be slected when the unit is started. Default values marked in RED are standard Uniflair values common for all unit models. NOTE: After having reset parameters that modify the configuration of the unit (number of compressors, fitting of valves etc.), setting of alarm delays or timing of the compressors, the miocroprocessor control must be turned off and then restarted in order for it to start immediately working with the new unit confirguration. 8/8
9 Fan speed regulation parameters of evaporator Setting and regulation table of F2 - F3 and F7 parameter Nominal voltage S..A S..C Unit model (without electrical resistent) S..A S..C 600 S..A 331 S..C 250 Power fan 147W 300W 147W 300W 147W 300W Voltage measured with a standard voltmeter (medium value) Voltage measured with a TRUE- RMS VOLTMETER (a voltmeter able to measure the effective RMS voltage) ? ? Parameter F2 35? ? Parameter F3 83? ? Parameter F7 26? ? Setting and regulation table of F2 - F3 and F7 parameter Nominal voltage S..A S..C Unit model (with electrical resistent) S..A S..C 600 S..C 300 S..A 331 S..C 250 Power fan 147W 300W 147W 300W 147W 300W 147W 300W Voltage measured with a standard multimeter (medium value) Voltage measured with a TRUE- RMS VOLTMETER (a voltmeter able to measure the effective RMS voltage) ? ? 180? Parameter F2 35? ? 35? Parameter F3 83? ? 83? Parameter F7 26? ? 38? 9/8
HERU Modbus. Reference Modbus addresses for HERU (Gen 3)
HERU Modbus Reference Modbus addresses for HERU 62-250 (Gen 3) Modbus Registers HERU v0.7.xls Coil status (1bit) RW 5.6.2016 Coil status Discrete Output (1bit) R/W Modbus Register Name Description Application
More informationInstallation Operation Commissioning Maintenance
NA 09.13 H 09-2011 Microchip and LCD display electronic regulation and signaling electronic module for liquid coolers and heat pumps Installation Operation Commissioning Maintenance 1 CONTENTS 1 IMPORTANT
More informationMotor thermal protection function
Budapest, November 2011. Motor thermal protection function Basically, the motor thermal protection function measures the three sampled phase currents. Positive sequence and negative sequence basic harmonic
More informationFRENIC-Ace (C2) (Supplement to RS-485 User's Manual)
(Supplement to RS-485 User's Manual) FRENIC-Ace (C2) This document is a supplement to the RS-485 Communication User s Manual (24A7-E-0082, MEH448), and is comprised of section 5.2 (Data ), to which content
More informationCALEFFI. Modulating digital controller for heating and cooling. 161 series 01122/08 GB. replaces dp 01122/05
Modulating digital controller for heating and cooling series REGI ERED SI EN ISO 00:000 Cert. n FM UNI EN ISO 00:000 Cert. n 000 0/0 G replaces dp 0/0 Function The controller can be used with three-point
More informationDIN Timers TD. Options and ordering codes. Specification
DIN imers D 17.5mm or 22.5mm DIN rail mounting Electronic imers Wide coil operation, 24V to 320V AC/DC Multi ime range / Multi function ON-Delay, OFF-Delay, Asymetrical, Star/Delta versions Perfect to
More informationPAX2S Modbus Register Table REVISED 2/20/12 LP0894A
PAX2S Modbus Register Table REVISED 2/2/12 LP894A REGISTER 41 42 43 44 45 46 47 48 49 41 411 412 413 414 415 416 417 418 419 42 421 422 423 424 425 426 427 428 429 43 431 432 481 482 483 484 485 486 487
More informationTEC BACnet MS/TP Network Series Thermostat Controllers Technical Bulletin
TEC BACnet MS/TP Network Series Thermostat Controllers Technical Bulletin Code No. LIT-12011592 Issued June 22, 2010 Supersedes December 1, 2009 Introduction..........................................................
More informationDifferences between PCL-240MK and PCL-240MS
1. General PCL-240MS, which replaces PCL-240MK, can offer S curve acceleration/deceleration control. There are no board or software changes required for S curve acceleration/deceleration. Here are lists
More informationSwegon CASA Smart ModBus Register SCB 3.0
USER SETTINGS 3.0-> 4x5001 RW Operating Mode 0 4 0= Stopped, 1 = Away, 2 = Home, 3 = Boost, 4 = Travelling 3.0-> 4x5019 RW Smart Control -100 100 % Smart control Increase or decrease Ventilation level
More informationCTC 155 / 350 / 660 Dry-block calibrator
CTC 155 / 350 / 660 Dry-block calibrator Wide temperature range: CTC-155: -25 to 155 C CTC-350: 28 to 350 C CTC-660: 28 to 660 C Fast calibration External reference sensor External sensor control Easy
More informationALPS. Advanced Line Protection System
ALPS Advanced Line Protection System Modified Fourier Calculation High Speed Sampling Phaselet Calculation Variable Window Digital Mimic 2 10 5 EXECUTE PHASELET CALCULATION AND PROTECTION ALGORITHMS High
More informationDigital Controller Operation
A Family Company Manufacturing In The USA Since 1969 Full Gauge Digital Controller Operation This manual is specific to the operation and diagnostic guides of the Full Gauge digital controller used in
More information24 volts (0.25 amps current-limited)
Question 1 Questions Suppose the lamp refuses to light up. A voltmeter registers 24 volts between test points C and D: A C E + 24 volts (0.25 amps current-limited) B D F First, list all the possible (single)
More informationElectrical Circuits. Winchester College Physics. makptb. c D. Common Time man. 3rd year Revision Test
Name... Set... Don.... manner~ man makptb Winchester College Physics 3rd year Revision Test Electrical Circuits Common Time 2011 Mark multiple choice answers with a cross (X) using the box below. I A B
More informationPNEUMATIC ENTHALPY COMPARATOR
PNEUATIC ENTHALPY COPARATOR APS ANALYSTS OF PNEUATIC SYSTES LIITED analystsofpneumatic@bellnet.ca http://www.apscontrols.ca PHONE: (9) 6-2333 FAX: (9) 6-2444 CONTENTS PAGE - Preface ------------------------------------------
More informationPTF30 Series. Features. Ordering information. G 6 N N F8 (0 to 5 kgf/cm 2 ) PTF30
eries Features Best pressure transmission solution for small and middle sized project such as indoor heating and air conditioning, water and sewer, or incinerator, etc. Improves noise resistance and minimize
More informationAbstract. Introduction. Experiment
Development of Simultaneous Measurement of Water Vapor dsorption and Proton Conductivity to PEM for PEFC Masayuki Yoshida * R&D, BEL JPN Inc. 2-11-27, Shinkitano Yodogawa-ku OSK, 532-25, JPN e-mail: m.yoshida@nippopn-bel.co.jp
More informationRemote Display Unit. Installers Handbook Copyright 2001 AirSense Technology Ltd. LM Remote Display Unit Installers Handbook Issue 1.
Remote Display Unit Installers Handbook Copyright 2001 AirSense Technology Ltd AirSense, ClassiFire, FastLearn PipeCAD, SenseNET, Stratos-HSSD and Stratos-Quadra are trademarks. HSSD is a Registered Trademark.
More informationSinger. Incremental Comfort Systems. K, EK Vintage F. Last Manufactured: Replacement Parts List No Revision C 04/2012
Replacement Parts List No. 055231000 Revision C 04/2012 Singer Incremental Comfort Systems K, EK 07-15 Vintage F Last Manufactured: 1976 To find your Daikin Applied parts distributor, call 1-800-377-2787
More informationElectronic Fan Coil Controller
Electrnic Fan Cil Cntrller EFCB10TU2 EFCB10TU4 EFCB11TU2 EFCB11TU4 EFCB12TU2 EFCB12TU4 (24Vac / 2 relays) (24Vac / 4 relays) (120Vac / 2 relays) (120Vac /4 relays) (240Vac / 2 relays) (240Vac / 4 relays)
More informationDPR User Manual. LG Digital Protection Relays
DPR User Manual LG Digital Protection Relays DPR User Manual LG Digital Protection Relays Contents General descriptions 3 Features 3 Additional functions 4 Environmental characteristics 6 1. Overcurrent
More informationWEATHER MULTI-SENSOR. Vaisala Weather Transmitter WXT510. Change the Way You Measure Weather
WXT510 WEATHER MULTI-SENSOR Vaisala Weather Transmitter WXT510 Change the Way You Measure Weather Vaisala Weather Transmitter WXT510 The Most Essential of Weather The Vaisala Weather Transmitter WXT510
More informationNo /06e. Technical Manual Multistage-Temperature-/Differential Controller TAR x700
Technical Manual Multistage-Temperature-/Differential Controller x700 Software Version 0078 o. 5303-0/06e 700 3700 5700 9700 3700 5700 9700 l Suitable as : Multistage Controller or Differential Controller
More information6-way valve with room temperature controller. Balanced climate control. World premiere! e. Cost and energy economies
6-way valve with room temperature controller. Balanced climate control. We set standards. www.belimo.eu World premiere! e Virtuoso performance to raise comfort and cut costs. Sustainable well-being hinges
More information65 0.26 Pascal-STV/ZB DIFFERENTIAL PRESSURE MEASUREMENT INSTRUMENT WITH ANALOG OUTPUT & DISPLAY 60 0.24 - CLEAN ROOMS - FILTER SYSTEMS - LAMINAR FLOWBOXES - AIR LOCKS 55 0.22 - FUME HOODS - ISOLATORS General
More informationKing Fahd University of Petroleum and Minerals College of Computer Science and Engineering Computer Engineering Department
King Fahd University of Petroleum and Minerals College of Computer Science and Engineering Computer Engineering Department Page 1 of 13 COE 202: Digital Logic Design (3-0-3) Term 112 (Spring 2012) Final
More informationBright Advance Corporation
USER INSTRUCTIONS TABLE OF CONTENTS INSTRUCTIONS FOR USE2 PREPARING TO USE THE SCALE2 DISPLAYS3 KEYBOARD FUNCTION4 OPERATION7 COUNTING14 DIFFERENT KEYBOARD TYPES21 INTERFACE31 POWER SOURCES40 1 INSTRUCTIONS
More informationHD2016. [ GB ] Weighing rain gauge. Rain PART OF G H M GROUP TELEMETRIE & AUTOMATION TELEMETRIE & AUTOMATION
HD2016 [ GB ] Weighing rain gauge Rain PART OF G H M GROUP TELEMETRIE & AUTOMATION TELEMETRIE & AUTOMATION [ GB ] HD2016 Weighing rain gauge [ GB ] HD2016 is a rain gauge that detects the weight of the
More informationWater terminal control solutions
Water Terminal Control Solutions Water terminal control solutions Carrier offers a wide range of fan coil units designed to meet the needs of different systems and applications: from cabinet units in the
More informationIssued August DATA SHEET. 3VT5 MCCB up to 1600 A
ssued August 9 DATA SHEET VT5 MCCB up to 0 A Based on Siemens Catalog V 8 Standard circuit breakers Releases Technical specifications Specifications VT5 circuit breakers Switch disconnectors Type Standards
More informationTECHNICAL MANUAL 820 LX / 910 LX / 1300 LX
TECHNICAL MANUAL 820 LX / 910 LX / 1300 LX LANCER reserves the right to modify, constantly its documentation for its improvement. The values of adjustments indicated in the displays of this manual are
More informationProcess Instrumentation analyzers
PCA300 Family Chlorine, ph, ORP and Temperature Analyzers Backlit LCD display Nema 4X protection.10 DPD chlorine measurement method Colorimeter diagnostics Reagent reminder Amplified ph/temperature probe
More informationImpedance relay and protection assemblies
RXZK 21H, 22H, 23H 509 006-BEN Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970175) (SE970184) Features Micro-processor based impedance relay with R and X settings
More informationMODEL: MO Digital DC Milliohm Meter OPERATING INSTRUCTION
MODEL: MO-1210 Digital DC Milliohm Meter OPERATING INSTRUCTION Index 1. Introduction...1 1-1.Brief...1 1-2.Features...1 1-3.Specification...1 2.Machine...4 2-1.Panel......4 2-2.LCD............4 3.Operation...5
More informationAIR COOLED CONDENSING UNIT
EVOLUTION SERIES AIR COOLED CONDENSING UNIT OUTDOOR AIR COOLED CONDENSING UNIT ORIGINAL MANUFACTURED EQUIPMENT Evolution Series BA-503-3 AUS Evolution Air Cooled Condensing Unit Series Content Page Explanation
More informationCHV Series Vector Control Inverter Options. Operating Instructions for Tension Control Card
CHV Series Vector Control Inverter Options Operating Instructions for Control Card 1. Model and Specifications 1.1 Model The model of tension card is CHV00ZL. CHV series inverter can conduct constant
More informationMinimum (-31) every 10 s -35 (-31)
Humidity, and Dew Point Data Logger with LCD ORDERING INFORMATION Standard Data Logger (Data Logger, Software on CD, Battery) Replacement Battery EL-USB-2-LCD BAT 3V6 1/2AA FEATURES 0 to 100 measurement
More informationThe Ordering Code for various standard model Recorders with an AC supply and without any additional options are as follows:
The basic PC software is supplied free with the recorder. There is an additional charge for the extensive Data Acquisition Software supplied with communication of RS-232/422/485 or Ethernet. The Ordering
More information3VT4 Molded Case Circuit Breakers up to 1000 A
VT4 Molded Case Circuit Breakers up to 00 A Catalog Technical nformation VT4 Molded Case Circuit Breakers up to 00 A General data / - Overview Circuit breakers Switch disconnectors / - Selection and ordering
More informationH NT Z N RT L 0 4 n f lt r h v d lt n r n, h p l," "Fl d nd fl d " ( n l d n l tr l t nt r t t n t nt t nt n fr n nl, th t l n r tr t nt. r d n f d rd n t th nd r nt r d t n th t th n r lth h v b n f
More informationExercise 1: RC Time Constants
Exercise 1: RC EXERCISE OBJECTIVE When you have completed this exercise, you will be able to determine the time constant of an RC circuit by using calculated and measured values. You will verify your results
More informationOverload Relays. SIRIUS 3RU1 Thermal Overload Relays. 3RU11 for standard applications. 5/46 Siemens LV 1 AO 2011
SIRIUS 3RU1 Thermal Overview 1 2 7 3 4 6 "Increased safety" type of EEx e according to ATEX directive 94/9/EC The 3RU11 thermal overload relays are suitable for the overload of explosion-proof motors with
More informationLab 3 Revisited. Zener diodes IAP 2008 Lecture 4 1
Lab 3 Revisited Zener diodes R C 6.091 IAP 2008 Lecture 4 1 Lab 3 Revisited +15 Voltage regulators 555 timers 270 1N758 0.1uf 5K pot V+ V- 2N2222 0.1uf V o. V CC V Vin s = 5 V Vc V c Vs 1 e t = RC Threshold
More informationSemiconductor thermogenerator
Semiconductor thermogenerator LEP 4.1.07 Related topics Seebeck effect (thermoelectric effect), thermoelectric e.m.f., efficiency, Peltier coefficient, Thomson coefficient, Seebeck coefficient, direct
More informationParts Manual R410A Models
Parts Manual R410A Models PTAC - PD Series (Electronic Controls) Packaged Terminal Air Conditioners Packaged Terminal Heat Pumps PTAC PARTS E (1-2010) Table of Contents Unit Identification... 2 PTAC System
More informationHD32.2 WBGT Index HD 32.2 INSTRUMENT FOR THE ANALYSIS OF THE WBGT INDEX
HD32.2 WBGT Index HD32.2 instrument can detect simultaneously the following quantities Globe thermometer temperature Tg. Wet bulb temperature with natural ventilation Tn. Environment temperature T. Starting
More informationSafety Precautions WARNING If critical situations that could lead to user s death or serious injury is assumed by mishandling of the product.
Safety Precautions Observe the following notices to ensure personal safety or to prevent accidents. To ensure that you use this product correctly, read this User s Manual thoroughly before use. Make sure
More informationLECTURE 28. Analyzing digital computation at a very low level! The Latch Pipelined Datapath Control Signals Concept of State
Today LECTURE 28 Analyzing digital computation at a very low level! The Latch Pipelined Datapath Control Signals Concept of State Time permitting, RC circuits (where we intentionally put in resistance
More informationSUMMARY REPORT PART DESCRIPTION SSM-110-S-DV, TSM S-DV
SUMMARY REPORT PART DESCRIPTION SSM-110-S-DV, TSM-110-01-S-DV File: J:\QA LAB\Test Programs\TC0121-027C-0434\ TC0121-027C-0434.doc Form 01 Rev 01 Page 1 of 11 CERTIFICATION All instruments and measuring
More informationISOCON-6. 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER
ISOCON-6 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER Whilst every effort has been taken to ensure the accuracy of this document, we accept no responsibility for damage, injury, loss or expense resulting
More informationMODEL: R7K4FML3. Remote I/O R7K4F Series. POWER INPUT DC power R: 24 V DC (Operational voltage range: ±10 %; ripple 10 %p-p max.)
Remote I/O R7KF Series I/O MODULE (-III) POWER INPUT DC power R: V DC (Operational voltage range: ±0 %; ripple 0 %p-p max.) 0 (8.7). (.) 7(.8) mm (inch) [] OPTIONS (multiple selections) Output data read
More informationSeries CCR-39S Multi-Throw DC-12 GHz, SP7T & SP8T Latching Coaxial Switch
PART NUMBER CCR-39S DESCRIPTION Commercial Latching Multi-throw, DC-12GHz The CCR-39S is a broadband, multi-throw, electromechanical coaxial switch designed to switch a microwave signal from a common input
More informationRandom Number Generator Digital Design - Demo
Understanding Digital Design The Digital Electronics 2014 Digital Design - Demo This presentation will Review the oard Game Counter block diagram. Review the circuit design of the sequential logic section
More information74F193 Up/Down Binary Counter with Separate Up/Down Clocks
April 1988 Revised September 2000 Up/Down Binary Counter with Separate Up/Down Clocks General Description The is an up/down modulo-16 binary counter. Separate Count Up and Count Down Clocks are used, and
More informationDigital Signal 2 N Most Significant Bit (MSB) Least. Bit (LSB)
1 Digital Signal Binary or two stages: 0 (Low voltage 0-3 V) 1 (High voltage 4-5 V) Binary digit is called bit. Group of bits is called word. 8-bit group is called byte. For N-bit base-2 number = 2 N levels
More information473-SHX Dew Point Mirror
Humidity and Temperature Reference Hygrometer For Temperature up to 125 C Precise and stable chilled mirror dew point mirror technology High temperature optical components High temperature sample fan Cable
More informationASEN 2002 Experimental Laboratory 1: Temperature Measurement and an Blow Dryer Test
ASEN 2002 Experimental Laboratory 1: Temperature Measurement and an Blow Dryer Test Assigned 6 September 2000 Individual Lab Reports due 3 October 2000 OBJECTIVES Learn the basic concepts and definitions
More informationUp/down binary counter with separate up/down clocks
FEATURES Synchronous reversible 4-bit counting Asynchronous parallel load capability Asynchronous reset (clear) Cascadable without external logic DESCRIPTION The is a 4-bit synchronous up/down counter
More informationSeries CCR-39S Multi-Throw DC-12 GHz, SP9T & SP10T Latching Coaxial Switch
PART NUMBER CCR-39S DESCRIPTION Commercial Latching Multi-throw, DC-12GHz The CCR-39Sis a broadband, multi-throw, electromechanical coaxial switch designed to switch a microwave signal from a common input
More informationA L A BA M A L A W R E V IE W
A L A BA M A L A W R E V IE W Volume 52 Fall 2000 Number 1 B E F O R E D I S A B I L I T Y C I V I L R I G HT S : C I V I L W A R P E N S I O N S A N D TH E P O L I T I C S O F D I S A B I L I T Y I N
More informationNetworkable Fan Coil Controller
Netwrkable Fan Cil Cntrller EFCB-OE1 Series EFCB10T OE1 (24Vac / 0 relays) EFCB12T OE1 (240Vac / 0 relays) EFCB10TU4 OE1 (24Vac / 4 relays) EFCB12TU2 OE1 (240Vac / 2 relays) EFCB12TU4 OE1 (240Vac / 4 relays)
More information5V/400mA Low Drop Voltage ILE4275 TECHNICAL DATA
TECHNICAL DATA 5V/400mA Low Drop Voltage ILE4275 is integrated circuits of voltage regulator 5V/400 ma with low-drop voltage. The IC of voltage regulator 5V/400 ma are purposed to supply DC voltage 5V
More informationPHASED OUT. FL ballasts Electronic dimming. PCA TC BASIC Y II, W BASIC compact
EL Product description Processor-controlled ballast with y II inside Highest possible energy class CELMA EEI = A BAT Noise-free precise control via DSI signal, switchdim or corridorfunction Nominal life
More informationDifferential Pressure Sensor
Differential Pressure Sensor MDP200 Series Features Pressure range up to ±500Pa with high accuracy of ±3.0% m.v. Pressure based on thermal micro-flow measurement Outstanding hysteresis and repeatability
More informationVidyalankar S.E. Sem. III [INFT] Analog and Digital Circuits Prelim Question Paper Solution
. (a). (b) S.E. Sem. III [INFT] Analog and Digital Circuits Prelim Question Paper Solution Practical Features of OpAmp (A 74) i) Large voltage gain (of the order of 2 0 5 ) ii) Very high input resistance
More informationSUBJECT TO CHANGE WITHOUT NOTICE
EARTH LEAKAGE RELAY ELR VI Programmable Multi-function Relay www.sifamtinsley.co.uk Multifunction Meters Transducers & Isolators Temperature Controllers Converters & Recorders Digital Panel Meters Current
More informationNo HOT WIRE ANEMOMETER MODEL SK-27V. SPECIFICATIONS Measurement object : Clean air at normal pressure and humidity
ELECTRIC INSTRUMENTS HOT WIRE ANEMOMETERS No. 7693-00 HOT WIRE ANEMOMETER MODEL SK-73D Measurement object: Clean air at normal pressure and humidity Measuring range Air velocity : 0 to 30 m/s Air temperature:
More informationMcQuay Climate Control Singer
Replacement Parts List No. 055204800 Revision B 01/2017 McQuay Climate Control Singer Vertical Water Source Heat Pump FC, FG, FW 240, 330, 400, 500 Vintages C, D Last Manufactured: 1986 To find your Daikin
More informationInstrument Test Report ITR 656. Evaluation of Milos 500 AWS unit
Instrument Test Report ITR 656 Evaluation of Milos 500 AWS unit Glenn Bowkett Physics Laboratory, OEB 23 November, 1999 Authorisation Tasia Livaditis A/LAB Physics Laboratory Distribution All RDs, ROMs,
More informationINTEGRATED CIRCUITS. For a complete data sheet, please also download:
INTEGRATED CIRCUITS DATA SHEET For a complete data sheet, please also download: The IC06 74HC/HCT/HCU/HCMOS Logic Family Specificatio The IC06 74HC/HCT/HCU/HCMOS Logic Package Information The IC06 74HC/HCT/HCU/HCMOS
More informationNational 5 Physics. Relevant Past Paper Questions from SQA Standard Grade Credit and Intermediate 2 papers. Unit 1: Energy and Electricity.
National 5 Physics Relevant Past Paper Questions from SQA Standard Grade Credit and Intermediate 2 papers Unit 1: Energy and Electricity March 2014 Transforming lives through learning N5 Physics Past Paper
More informationTHM80X Series Feature Application. Temperature & Humidity / Flow Measuring Specialist
THM80X Series Feature Application IP67 protection degree, rugged aluminum case, fit in variety harsh environment Capable of temperature compensation Linear adjustment temperature & humidity by computer,
More informationMULTI-OUTPUT PROGRAMMABLE CONTROLLERS MODELS UMX-4 & UMX-8
February 1994 20/20 Interface Products MULTI-OUTPUT PROGRAMMABLE CONTROLLERS MODELS & DESCRIPTION The is a Multi-output Programmable Controller which expands the input or output capability of building
More informationOperating instructions Pressure sensor PN / / 2007
Operating instructions Pressure sensor PN42 704298 / 00 0 / 2007 Contents afety instructions... 3 2 Function and features... 4 3 Function... 5 3. witching function... 5 4 Installation... 5 5 Electrical
More informationElios X3 DIGITAL CONTROL SYSTEM FOR THE MANAGEMENT OF SOLAR HEAT PLANT
Elios X3 DIGITAL CONTROL SYSTEM FOR THE MANAGEMENT OF SOLAR HEAT PLANT DESCRIPTION Programmable digital control for thermal solar systems inclusive of solar collectors, circulation pumps and / or diverter
More informationHD32.2 WBGT Index HD32.3 WBGT-PMV. [ GB ] - WBGT index. - PMV index and PPD
HD32.2 WBGT Index HD32.3 WBGT-PMV [ GB ] - WBGT index. - PMV index and PPD [ GB ] [ GB ] Description HD32.2 WBGT Index is an instrument made by Delta Ohm srl for the analysis of WBGT index (Wet Bulb Glob
More informationSeries CCR-39S Multi-Throw DC-12 GHz, SP9T & SP10T Latching Coaxial Switch
COAX SWITCHES Series CCR-39S PART NUMBER CCR-39S DESCRIPTION Commercial Latching Multi-throw, DC-12GHz The CCR-39Sis a broadband, multi-throw, electromechanical coaxial switch designed to switch a microwave
More informationMotors Automation Energy Transmission & Distribution Coatings. Servo Drive SCA06 V1.5X. Addendum to the Programming Manual SCA06 V1.
Motors Automation Energy Transmission & Distribution Coatings Servo Drive SCA06 V1.5X SCA06 V1.4X Series: SCA06 Language: English Document Number: 10003604017 / 01 Software Version: V1.5X Publication Date:
More informationProperty of American Airlines
L L L PE INCOMING POWER 0V/PH/0HZ/00AMPS C CIRCIT REAKER REMOTE OVER CRRENT ISCONNECT REQI PER NEC AWG CIRCIT REAKER CONTACTOR CONTROL RELAY CRRENT TRANSCER MOTOR STARTER OVERLOA RELAY NIT - RIGE INTERCONNECTION
More informationMcQuay Climate Control. Water Source Heat Pump Horizontal. CC, CG, CW Vintage C, D. Last Manufactured: 1984
Replacement Parts List No. 055204000 Revision C 01/2017 McQuay Climate Control Water Source Heat Pump Horizontal CC, CG, CW 260-330 Vintage C, D Last Manufactured: 1984 To find your Daikin Applied parts
More informationT4 TIMER - PROJECT DESCRIPTION - rev. 5.10
1. Display Logic A. When displaying in HH:MM, it will not be obvious from the display that the timer is counting, the 4 dots at the bottom of the display chase from left to right to indicate its counting
More informationOperating Instructions for Digital Manometer. Model: MAN-SD
Operating Instructions for Digital Manometer Model: MAN-SD 1. Contents 1. Contents...2 2. Note...3 3. Instrument Inspection...3 4. Regulation Use...4 5. Operating Principle...4 6. Mechanical Connection...5
More informationGeorgia Institute of Technology School of Electrical and Computer Engineering. Midterm-1 Exam (Solution)
Georgia Institute of Technology School of Electrical and Computer Engineering Midterm-1 Exam (Solution) ECE-6414 Spring 2012 Friday, Feb. 17, 2012 Duration: 50min First name Solutions Last name Solutions
More informationINSTRUCTION AND MAINTENANCE MANUAL FOR TECHTROL COUNTER CONTROLLER & TOTALISER (TCCT)
INSTRUCTION AND MAINTENANCE MANUAL FOR TECHTROL COUNTER CONTROLLER & TOTALISER (TCCT) ( Document No. : MAN / TCCT / Rev. 01 / 09-2006. ) V:001453Ltr T Time:H0086:M43 THERMAX CONTENTS 1 Introduction & Working
More informationThermal System Closed-Loop Temperature Control
Thermal System Closed-Loop Temperature Control aluminum plate thin-film resistive heater ceramic insulation conduction and convection heat transfer AD590 temperature sensor microcontroller on-off closed-loop
More informationPhysics - Grade 12. Revision Sheet for the Final Exam / Second Term. Academic Year: 2018/2019. Student s Name:.. Date: /3/2018
Physics - Grade 12 Revision Sheet for the Final Exam / Second Term Academic Year: 2018/2019 Student s Name:.. Date: /3/2018 Required Material: Chapter 18: Sections 1,2 & 3 (Textbook Pages: 628-661) Chapter
More informationE6C-N. Ideal for Out-of-step Detection of Stepping Motors and Position Control of Rotors and Unloaders
Multi-turn High-precision Encoder Ideal for Out-of-step Detection of Stepping Motors and Position Control of Rotors and Unloaders Reset function for easy origin alignment when built-into equipment. Multi-turn
More information2014 Technological Studies. Advanced Higher. Finalised Marking Instructions
204 Technological Studies Advanced Higher Finalised Marking Instructions Scottish Qualifications Authority 204 The information in this publication may be reproduced to support SQA qualifications only on
More informationSTRAIN GAUGE MEASUREMENT
STRAIN GAUGE MEASUREMENT INTRODUCTION There are many possible ways of measuring strain gauges using a Datascan. All methods measure the change in resistance of the gauge within a bridge circuit and the
More informationE THERMADATA LOGGER Humidity & temperature recording meter
E 07 00 THERMADATA LOGGER Humidity & temperature recording meter THERMADATA LOGGER Data-loggers are electronic devices that record temperature over a period of time for analysis at a later date. The user
More informationSingle cam type. Double cam type. Grip force N. Type Model/size Stroke Screw type straight style. Screw type tee style
Type Model/size Stroke -SS-0-N. -SS-0-N. Single cam type -SS- 7. -SS-. -SS-4. -SD-0 Double cam type -SD- -SD-4. Screw type straight style Screw type tee style -FS- -FT- -FS- -FT- 0.9 1. 1.. 1. 4 Grip forcen
More informationRequest Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.
Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager. 1 -A - Introduction - Thank for your purchasing MITSUBISHI ELECTRIC MELPRO TM D Series Digital Protection
More informationFlow-meter calibrations for the ID of the ATLAS Experiment
Flow-meter calibrations for the ID of the ATLAS Experiment Supervisors: Stephen McMahon and Vaclav Vacek Collaborators: R. Marek, M. Doubek and M. Vítek 31.1.29 CTU IN PRAGUE ATLAS SCT Abstract This report
More information/ NTSSeries NTFSeries Temperature cycle : 1000 cycles
/ NTSSeries NTFSeries Temperature cycle : 00 cycles FEATURES 1. Large capacitance by small size. 2. Excellent noise absorption. 3. High permissible ripple current capability. 4. NTF: Temperature cycle
More informationMeasurement of Nonlinear Thermal Parameters AN 19
Measurement of Nonlinear Thermal Parameters AN 9 Application Note to the KLIPPEL R&D SYSTEM Traditional modeling describes the heat flow in loudspeakers by an equivalent circuit using integrators with
More information5-V Low Drop Fixed Voltage Regulator TLE 4299
5-V Low Drop Fixed Voltage Regulator TLE 4299 Features Output voltage 5 V ± 2% 150 ma Output current Extreme low current consumption typical 65 µa in ON state Inhibit function: Below 1 µa current consumption
More informationInstallation Instructions: ICON Anti-Condensate Controller
TECHNICAL BULLETIN Installation Instructions: ICON Anti-Condensate Controller System Overview The ICON Anti-Condensate Controller System (pat. pend.) is a stand-alone controller for antisweat heaters in
More informationVISY-Quick Communication Protocol
VISY-Quick Communication Protocol Rev. Protocol Version Modification VI Version Date Name 0 1.00 First release 2.0.1 2000-03-29 Willmer 1 1.10 New commands date and time (3.2... 3.5) 2.0.2 2000-07-07 Willmer
More informationDATA SHEET. Thermocouple module with digital I²C-Interface - THMOD-I²C. Characteristic features. Areas of application. Features.
Description Characteristic features Industrial temperature measuring method Wide measuring range, -270...+1360 C Digital I²C-interface Simple integration to micro-controller Scope of supply with thermocouple,
More information