DISTRIBUTION SYSTEM ELECTRIC INFRASTRUCTURE RELIABILITY PERFORMANCE INDICATORS

Size: px
Start display at page:

Download "DISTRIBUTION SYSTEM ELECTRIC INFRASTRUCTURE RELIABILITY PERFORMANCE INDICATORS"

Transcription

1 EB-- Exhibit D Page of DISTRIBUTION SYSTEM ELECTRIC INFRASTRUCTURE RELIABILITY PERFORMANCE INDICATORS FIVE-YEAR HISTORICAL RELIABILITY PERFORMANCE THESL tracks System Average Interruption Frequency Index ( SAIFI ), System Average Interruption Duration Index ( SAIDI ), and Customer Average Interruption Duration Index ( CAIDI ) in the following ways: Including all events Excluding Major Event Days ( MEDs ) Excluding MEDs and Loss of Supply In addition to these performance indicators, THESL also provides a breakdown of Scheduled Outages in each of the five years. Similar to Loss of Supply and MEDs, Scheduled Outages affect the system adversely but do not represent the true state of THESL s distribution system. FIVE-YEAR HISTORICAL RELIABILITY PERFORMANCE The following Figures and demonstrate total number of Customers Interrupted ( CI ) and total Customer Hours Interrupted ( CHI ) for the system over the past five years, respectively. The four CI and CHI values for each year represent the effects of MEDs, Loss of Supply and Scheduled Outages relative to all other type of system outages.

2 EB-- Exhibit D Page of Figure : System Level CI Figure : System Level CHI

3 EB-- Exhibit D Page of MAJOR EVENT DAYS An MED is defined by standard P/D of the Institute of Electrical and Electronics Engineers ( IEEE ) as events that are beyond the design and/or operational limits of a utility. The removal of MEDs allows a utility to normalize its reliability data to make trending and goal setting possible. An example of a normalizing application was the OEB-allowed modification of reliability data, in light of the August, provincial blackout. MEDs experienced by THESL since are shown in Table below: Table : Major Event Days Date Description Category SAIDI August, Blackout Loss of Supply days September, Hurricane Isabel Adverse Weather. minutes July, Loss of Supply to Esplanade TS Loss of Supply. minutes August, Major Storm (Thunderstorm) Adverse Weather. minutes August, Major Storm (Thunderstorm) Adverse Weather. minutes July, Major Storm (Thunderstorm) Adverse Weather. minutes August, Loss of Supply to Scarborough TS Loss of Supply. minutes March, Major Ice Storm Adverse Weather. minutes June, Major Storm (Thunderstorm) Adverse Weather. minutes January, Dufferin TS Flooding Adverse Environment. minutes April, Major Storm (Thunderstorm) Adverse Weather. minutes August, Major Storm (Thunderstorm) Adverse Weather. minutes August, Major Storm (Thunderstorm) Adverse Weather. minutes July, Loss of Supply to Manby TS Loss of Supply. minutes Figure demonstrates the contribution of the different categories of MEDs over the past five years:

4 EB-- Exhibit D Page of Figure : SAIDI Impact from MEDs MEDs have played a large part in contributing to system CI and CHI in all years as shown by the following Figures and. The exception is in which THESL did not experience any MEDs. As evident from the graph, adverse weather outages contribute most to THESL MEDs; such outages are largely attributable to the overhead ( OH ) system. THESL capital plan initiatives will help reduce the impact of weather related outages by re-designing the OH system over the past five years. Although adverse weather has the greatest contribution overall, the largest single event, as seen in the adverse environment cause code, was a total station outage due to flooding at Dufferin TS in.

5 EB-- Exhibit D Page of System CI due to MED, LOS, and Planned Outages Customers Interrupted,,,,,,,,,, MED CI Loss of Supply CI Planned Outages CI,,,,,,,,,,,,,, Total,,, Figure : System CI due to Major Event Days, Loss of Supply and Planned Outages LOSS OF SUPPLY Loss of Supply ( LoS ) events continue to have a significant impact on the overall reliability of the system. In, a total of LoS events affected the system while in, such events occurred. The top three events in terms of CI accounted for percent of the total CI due to LoS in. Similarly, the top three LoS events in terms of CHI accounted for percent of the total CHI due to LoS in. These do not include the MED on July,. Figures and show the CI and CHI from the past five years due to the LoS. On a system level, LoS can affect up to ten percent of the SAIDI and SAIFI (excluding MEDs). While THESL does not have direct control over such events, it can reduce the impact of LoS outages through initiatives such as stations ties or feeder

6 EB-- Exhibit D Page of automation. The overall performance of the THESL system is strongly impacted by changes in LoS year-over-year, but THESL has no direct control over LoS. By excluding this factor, THESL is able to monitor and asses the true state of its distribution system. System CHI due to MED, LOS, and Planned Outages Customer Hours Interrupted,,,,,,,, MED CHI Loss of Supply CHI Planned Outages CHI,,,,,,,,,,,,,,, Total,,,, Figure : System CHI due to Major Event Days, Loss of Supply and Planned Outages SCHEDULED OUTAGES Given the deteriorating asset condition of THESL s system, more Scheduled Outages have been required year-over-year since. These outages improve the reliability of the system in a planned manner. Figures and illustrate the impact of such outages on CI and CHI, respectively.

7 EB-- Exhibit D Page of From to, THESL saw a significant increase in the number of scheduled outages that is reflected proportionally in the CI and CHI for this cause code. In, Scheduled Outages contributed. percent to SAIFI and. percent to SAIDI. The increase in the number of Scheduled Outages is required to replace ageing infrastructure. Although this increased capital work has reduced the overall reliability of the system in the short-term, the long-term improvements outweigh the short-term impact. SYSTEM RELIABILITY EXCLUDING LOSS OF SUPPLY, MAJOR EVENT DAYS AND SCHEDULED OUTAGES THESL has very limited control over Major Event Days and Loss of Supply events. As a result, the impact of these factors will be excluded from further analysis of the overall system performance. In addition, because Scheduled Outages are required in order to replace assets that are at end-of-life, THESL will also be excluding the reliability impact of these planned outages from the analysis of the system performance. Taking into account Adverse Environment, Adverse Weather, Defective Equipment, Foreign Interference, Human Element, Lightning, Tree Contacts, Unknown and excluding MEDs, LoS and Scheduled Outages, the true performance of assets that were planned to remain in service for each year can be further analyzed. Figures,, and show the SAIFI, SAIDI, and CAIDI performance indicators of the system, respectively, excluding the following: MEDs, LoS events and Scheduled Outages.

8 EB-- Exhibit D Page of System SAIFI System SAIFI..... Figure : System SAIFI Excluding MEDs, LoS and Scheduled Outages System SAIDI System SAIDI..... Figure : System SAIDI Excluding MEDs, LoS and Scheduled Outages

9 EB-- Exhibit D Page of CAIDI System CAIDI System CAIDI..... Figure : System CAIDI Excluding MEDs, LoS and Scheduled Outages In, system SAIFI remained at the same level as, while system SAIDI saw improvement. The SAIDI improvement is due to lower CHI from defective equipment and foreign interference related outages. Since CAIDI is defined as the ratio of SAIFI to SAIDI, the SAIDI improvement led to the system CAIDI improvement for the year. CAUSE CODE ANALYSIS THESL tracks causes of service interruptions using the ten primary cause codes, as specified in Table. of the Electricity Distribution Rate Handbook. Figures and show the reliability performance for CI and CHI from to for the ten primary cause codes respectively.

10 EB-- Exhibit D Page of Figure : System CI Cause Code Breakdown (Excluding MEDs)

11 EB-- Exhibit D Page of Figure : System CHI Cause Code Breakdown (Excluding MEDs) Table : SAIFI and SAIDI Contributions by Cause Codes Cause Code Contribution % to SAIFI Contribution % to SAIDI Defective Equipment.. *Loss of Supply.. Adverse Weather.. Unknown.. Foreign Interference.. Tree Contacts.. *Scheduled Outage.. Human Element.. Lightning.. Adverse Environment.. *Excluded from further analysis in this document to reflect the true status of the system.

12 EB-- Exhibit D Page of In, Defective Equipment continued to be the main contributor to SAIFI and SAIDI, at. percent and. percent respectively. Adverse Weather, which contributed to. percent of SAIFI and. percent of SAIDI in, had a far greater impact on system reliability in compared to. Foreign Interference accounted for. percent of system SAIFI and. percent of system SAIDI, yet improved from levels. Tree Contacts resulted in. percent of system SAIFI and. percent of system SAIDI. When reviewing each cause code year over year, it can be seen that Defective Equipment and Foreign Interference with addition of year are showing an improving trend while Scheduled Outages, Human Element, Adverse Weather and Tree Contacts are showing deterioration. In order to provide a better understand of reliability trend, THESL has provided an in depth analysis of each of these cause codes. DEFECTIVE EQUIPMENT ANALYSIS The following graphs further categorize Defective Equipment CI and CHI contribution by distinguishing between the following four different categories: Underground Equipment ( U/G Equipment ) Overhead Equipment ( O/H Equipment ) Station Equipment ( STN Equipment ) Other Equipment ( OTHER Equipment ) Figure and show the CI and CHI breakdown for each category of Defective Equipment excluding MEDs.

13 EB-- Exhibit D Page of Defective Equipment: CI Contribution Customers Interrupted,,,,,,,, Underground Equipment Overhead Equipment Station Equipment Other Equipment,,,,,,,,,,,,,,,,,,,, Figure : Defective Equipment Breakdown (CI)

14 EB-- Exhibit D Page of Defective Equipment: CHI Contribution, Customers Hours Interrupted,,,,,, Underground Equipment Overhead Equipment Station Equipment Other Equipment,,,,,,,,,,,,,,,,,,,, Figure : Defective Equipment Breakdown (CHI) As can be seen in Figures and, the largest contributors to Defective Equipment CI and CHI in were Defective Overhead and Underground Equipment. In, Overhead Equipment failures counted for percent of the CI due to defective equipment, while counting for percent of the CHI contribution. In comparison, in, overhead equipment counted for percent of the CI and percent of the CHI contribution. This shows that over the years, the overhead system has become a major contributor to the decline of system reliability. Defective Overhead Equipment In, Overhead Defective Equipment accounted for about percent of system-wide SAIFI and about percent of system wide SAIDI. Defective Overhead Equipment has

15 EB-- Exhibit D Page of had a significant impact on overall system reliability and has been deteriorating over the past five years. In general, a significant trend upwards is seen in defective Overhead Equipment failures. More specifically, overhead switches, insulators, and lighting arrestor failures have had increasing contributions to system reliability. These causes account for percent of the CI and percent CHI of the total Overhead Equipment failures in. In addition to these assets, Overhead Conductors are another major contributor to Equipment CI and CHI. Transformers, while not a significant contributor to CI and CHI, have the highest number of failures in the Overhead system with percent of those due to CSP transformers. The number of outages year-over-year is reflected in defective Overhead Equipment CI and CHI. The overhead portion is beginning to show a deteriorating trend over the past three years. From a SAIDI perspective, overhead outages account for percent, percent and percent of the Defective Equipment-related outages from to, and percent, percent and percent of the Defective Equipment-related outages in SAIFI from to, respectively. To further analyze the causes for the increase in CI and CHI of the overhead system, major contributors for CI and CHI across the system are further broken down by individual components. Figures,, and portray the individual overhead system components contribution to CI and CHI, as well as number of outages due to overhead equipment failure. As evidenced by these figures, the major contributors to overhead equipment failure have been deteriorating in the past five years.

16 EB-- Exhibit D Page of Defective OH Equipment: CI Contribution Customers Interrupted,,,,,, Switch Insulator Conductor Lightning Arrestor Transformers,,,,,,,,,,,,,,,,,,,,,,,,, Figure : Overhead Defective Equipment Major Contributors (CI) Defective OH Equipment: CHI Contribution Customer Hours Interrupted,,,,,,,, Switch Insulator Conductor Lightning Arrestor Transformers,,,,,,,,,,,,,,,,,,,,,,,,, Figure : Overhead Defective Equipment Major Contributors (CHI)

17 EB-- Exhibit D Page of Defective OH Equipment: Number of Outages Number of Outages Switch Insulator Conductor Lightning Arrestor Transformers Figure : Overhead Defective Equipment Major Contributors (Outages)

18 EB-- Exhibit D Page of Defective OH Equipment: CI Per Outage Customers Interrupted,,,,, Switch Insulator Conductor Lightning Arrestor Transformers,,,,,,, Figure : CI Impact per Outage from Overhead Equipment Defective OH Equipment: CHI per Outage Customer Hours Interrupted,,,, Switch Insulator Conductor Lightning Arrestor Transformers,,, Figure : CHI Impact per Outage from Overhead Equipment

19 EB-- Exhibit D Page of Insulators The five-year trend for insulators shows a large increase in CI and CHI. Insulators account for percent of the overhead system CHI and percent of the overhead system CI in. Porcelain-type insulators account for approximately percent of the insulator CI and CHI. Although CI and CHI are on the rise, when looking at the number of interruptions, it can be seen that the overall failures in the distribution system has shown a slight improvement from, but a deteriorating trend from. This is due to the proactive insulator replacement in projects. As evidenced by the figures above, while insulator failures are lower in frequency compared to other major overhead assets, such failures have the greatest impact on system reliability. In, an insulator failure on average led to customers interrupted. THESL intends to continue phasing out the porcelain insulators across the system and replacing them with the more reliable polymeric type insulators. Conductors Overhead conductor failures have been trending upwards over the past five years as THESL s overhead assets age. Overhead conductors are addressed as part of overhead rebuild projects. Lightning Arrestors Lightning Arrestors cause about percent of the Overhead Defective Equipment CI and CHI. The system has experienced a decrease in number of outages from this asset class over the past two years as the oldest and highest failure risk Lighting Arrestors have been replaced. However, the five-year CI and CHI trends have been increasing. Overhead Switches From the CI and CHI figures, it can be seen that the CI and CHI closely mirror the number of outages year-over-year. As shown in Figures and, the CI and CHI per

20 EB-- Exhibit D Page of Switch failure have steadily increased to, customers per outage with a total duration of hours per outage. THESL currently plans on addressing the impact of switch failures and restoration time by increasing the number of switches and automated switches in the system. This approach allows the affected locations to be isolated from the system and the rest of the feeder to be restored. As more automated switches are installed, the CI and CHI will improve. Defective Underground Equipment Even though Defective Underground Equipment has shown marked improvement in both CI and CHI contribution over the last five years, it remains a significant contributor to overall system SAIFI and SAIDI. In, Defective Underground Equipment accounted for about percent of system wide SAIFI and about percent of system wide SAIDI. Figures and portray the CI and CHI contributions due to underground equipment failure.

21 EB-- Exhibit D Page of Defective U/G Equipment: CI Contribution Customers Interrupted,,,,,,,,,,,,, Primary Cable & Joints Submersible Transformer Elbow Terminator Switchgear All other types,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, Figure : Underground Defective Equipment Major Contributors (CI)

22 EB-- Exhibit D Page of Figure : Underground Defective Equipment Major Contributors (CHI)

23 EB-- Exhibit D Page of Defective UG Equipment: Number of Outages Number of Outages Primary Cable & Joints Submersible Transformer Elbow Terminator Switchgear All Other Types Figure : Underground Defective Equipment Major Contributors (Outages)

24 EB-- Exhibit D Page of Defective UG Equipment: CI per Outage Customers Interrupted,,,,,, Primary Cable & Joints Submersible Transformer Elbow Terminator Switchgear All Other Types,,,,,, Figure : CI Impact per Outage from Underground Equipment

25 EB-- Exhibit D Page of Defective UG Equipment: CHI per Outage Customers Hours Interrupted,, Primary Cable & Joints Submersible Transformer Elbow Terminator Switchgear All Other Types, Figure : CHI impact per Outage from Underground Equipment Primary Cable As can be seen in Figures and, defective primary cable remains the largest contributing factor to CI and CHI for defective underground equipment. This has a significant overall impact on system reliability. In, defective primary cable contributed percent to overall system SAIFI and percent to overall system SAIDI, and percent to the Underground Defective Equipment category SAIFI and SAIDI. As is evident in Figures and, the average number of customers interrupted per failure is with an average total time of hours. A significant portion of the primary cable faults occur on direct-buried cable, a legacy standard, most of which is beyond the end of its useful life. Capital investments in this asset class have been initiated to replace directburied primary cable with current standard cable in concrete encased duct. This

26 EB-- Exhibit D Page of investment has had favorable impacts on the overall system reliability, and as a result, THESL plans to continue investing in the direct-buried primary cable removal project. Both CI and CHI attributable to primary cable have declined since the introduction of this project in. From to, a total reduction of percent to the CI and percent o the CHI has been realized. Submersible Transformers and Elbows In the second largest contributor to Defective Underground Equipment was submersible transformers accounting for seven percent of Defective Underground Equipment CI and ten percent of Defective Underground Equipment CHI. Due to capital investment in this asset class over the last number of years, the general performance trend is slightly improving. When legacy submersible transformers are replaced with standard switchable ones, the elbows are also replaced because they are at the end of their useful lives. The significant number of submersible transformers replaced over the last few years has had a very favorable impact on the SAIFI and SAIDI contribution of elbows. This trend can be seen in Figures and as elbow-related outages have decreased. Switchgear As can be seen from Figures and, switchgear is also a significant contributor to Defective Underground Equipment. The general trend of CI and CHI contribution from defective switchgear over the last five years has slightly improved. In the past two years, THESL has observed a decrease in the CI and CHI impact to the system from switchgear. As evident from Figures and, customers are interrupted with each failure on average with a total duration of hours. Part of this reliability improvement can be attributed to increased maintenance spending on the inspection and cleaning of padmounted switchgear. Capital expenditures are proposed in the ten-year plan to phase out air insulated pad-mounted switchgear and replace it with sealed-type switch gear. One such example of a sealed-type switchgear is the SF pad-mounted switchgear. The

27 EB-- Exhibit D Page of switch contains SF gas inside of the sealed switchgear housing. This eliminates the contamination from environmental factors that results in the failure of air-insulated switchgear. Human Element Though Human Element has the smallest impact of all the cause codes, the CHI has been showing an upward trend over the past five years and with the exception of, the CI has also been showing a similar trend. Human Element is caused when work by THESL or THESL contractors creates an outage. From to, the significant increase to Scheduled Outages closely mirrors the increase in Human Element events. Like Scheduled Outages, Human Element is directly impacted by the capital program and is closely monitored by THESL as it involves employee safety. Customers Interrupted Human Element CI,,,,, CI,,,,, Figure : Human Element Contribution (CI)

28 EB-- Exhibit D Page of Customers Hours Interrupted Human Element CHI,,,,,, CHI,,,,, Figure : Human Element Contribution (CHI) Adverse Weather In, Adverse Weather contributed towards. percent of the system SAIFI and. percent of the system SAIDI. The number of outages due to Adverse Weather has been trending down over the past five years, but the impact from Adverse Weather over these years has increased. Figures, and show the trend of Adverse Weather outages over the past five years.

29 EB-- Exhibit D Page of, ADVERSE WEATHER CI, Customers Interrupted,,,,, Adverse Weather,,,,, Figure : Adverse Weather Contribution (CHI) Customer Hours Interrupted,,,,,,,,,, Adverse Weather CHI Adverse Weather,,,,, Figure : Adverse Weather Contribution (CHI)

30 EB-- Exhibit D Page of Number of Adverse Weather Outages Adverse Weather Figure : Adverse Weather Contribution (Outages) CI due to adverse weather outages has shown an inconsistent yet upward trend over the past five years. Storm hardening and conversion of overhead plant to underground will reduce the vulnerability of the overhead system to adverse weather conditions. CHI due to adverse weather has also been trending up over the last five years. Introduction of Fault Current Indicators ( FCIs ) into the system will help localize faults and reduce outage restoration times. Foreign Interference Foreign Interference continues to be a significant contributor to system reliability as shown in Figures and. A downward trend of foreign interference CI and CHI contributing. percent to system SAIFI and. percent to system SAIDI, was shown in. In the Foreign Interference category, THESL has some measure of control over animal contact, where the installation of animal guards has led to a reduction in outages.

31 EB-- Exhibit D Page of Figure : Foreign Interference Breakdown (CI)

32 EB-- Exhibit D Page of Figure : Foreign Interference Breakdown (CHI) Tree Contacts In, Tree Contacts had a contribution of. percent to SAIFI and. percent to SAIDI. Tree Contacts can be occur in adverse or normal weather conditions or through brush contact. Figures,, and provide a breakdown of the three types of Tree Contact outages. From Figure, it can be seen that CI due to Tree Contact has remained relatively stable over the past years while Figure shows the CHI increasing from to. Figures and further breaks down the Tree Contact cause code into Adverse Weather, Normal Weather and Brush Contact. There is a significant increase in the Adverse Weather CI and CHI when compared to. When comparing Figures and

33 EB-- Exhibit D Page of, it can be seen that the average number of customers interrupted has remained around, customers per Adverse Weather interruption over the past five years while the duration has increased to, hours. When compared to Defective Equipment CI and CHI per outage, Adverse Weather Tree Contacts would rank as one of the top categories. Tree Contacts: CI Breakdown Customers Interrupted,,,,,, Adverse Weather Normal Weather Brush Contacts,,,,,,,,,,,,,,, Figure : Tree Contact Breakdown (CI)

34 EB-- Exhibit D Page of Tree Contacts: CHI Breakdown Customers Hours Interrupted,,,,,, Adverse Weather Normal Weather Brush Contacts,,,,,,,,,,,,,,, Figure : Tree Contact Breakdown (CHI) Tree Contacts: Number of Outages Number of Outages Adverse Weather Normal Weather Brush Contacts Figure : Tree Contact Breakdown (Outages)

35 EB-- Exhibit D Page of Tree Contacts: CI Per Event Customers Interrupted,, Adverse Weather Normal Weather Brush Contacts,,,,,,, Figure : CI per Tree Contact Event Adverse Weather interruptions are caused by severe storms or high wind conditions. During these times, tree branches can break off and fall onto THESL conductors. From to, THESL has observed,,, and unique days respectively in which Adverse Weather Tree Contacts occurred. A unique Adverse Weather day is any one day in which one or more Adverse Weather Tree Contact takes place. Taking the total number of Adverse Weather Tree Contact interruptions and dividing it by the total number of unique days, will result in the number of Tree Contact outages per Adverse Weather day. This is represented in Figure below.

36 EB-- Exhibit D Page of Tree Contacts: CHI Per Event Customers Hours Interrupted,,,,, Adverse Weather Normal Weather Brush Contacts,,, Figure : CHI per Tree Contact Event

37 EB-- Exhibit D Page of Outages per Adverse Weather Day... Outages.... Outages per Adverse Weather Day..... Figure : Outages per Adverse Weather Day From Figure, it can be seen that even though in THESL had less storm days than any of the previous years, when comparing the Average Outages per Adverse Weather day, there is a significant increase. Though there were fewer days in which Adverse Weather Tree Contacts occurred in, the storms were more severe and caused more damage to the system. CHI is an indication of how quickly THESL can respond to outages across the system. It can be seen from Figure that the CHI due to Adverse Weather increased significantly in. This is due to the concentration of the events occurring simultaneously and adversely affecting THESL response time.

Review of. Florida s Investor-Owned Electric Utilities Service Reliability reports. State of Florida

Review of. Florida s Investor-Owned Electric Utilities Service Reliability reports. State of Florida Review of Florida s Investor-Owned Electric Utilities 2 0 1 1 Service Reliability reports N O V E M B E R 2 0 1 2 State of Florida Florida Public Service Commission Division of ENGINEERING Review of Florida

More information

ELECTRIC SYSTEM RELIABILITY ANNUAL REPORT

ELECTRIC SYSTEM RELIABILITY ANNUAL REPORT ELECTRIC SYSTEM RELIABILITY ANNUAL REPORT 2015 LIBERTY UTILITIES (CALPECO ELECTRIC) LLC (U 933 E) -- PUBLIC VERSION -- Prepared for California Public Utilities Commission July 15, 2016 EXECUTIVE SUMMARY

More information

Review of. Florida s Investor-Owned Electric Utilities Service Reliability reports. State of Florida

Review of. Florida s Investor-Owned Electric Utilities Service Reliability reports. State of Florida Review of Florida s Investor-Owned Electric Utilities 2 0 1 2 Service Reliability reports N O V E M B E R 2 0 1 3 State of Florida Florida Public Service Commission Division of ENGINEERING Review of Florida

More information

PUB NLH 185 Island Interconnected System Supply Issues and Power Outages Page 1 of 9

PUB NLH 185 Island Interconnected System Supply Issues and Power Outages Page 1 of 9 PUB NLH 1 Page 1 of 1 Q. Provide Hydro s list of outage cause codes and indicate how troublemen are managed and trained to properly use the codes. Explain the method used to report outage causes. A. Hydro

More information

Review of Florida s Investor-Owned Electric Utilities Service Reliability Reports. September

Review of Florida s Investor-Owned Electric Utilities Service Reliability Reports. September Review of Florida s Investor-Owned Electric Utilities 2 0 1 5 Service Reliability Reports September 2 0 1 6 State of Florida Florida Public Service Commission Division of Engineering Review of Florida

More information

Review of Florida s Investor-Owned Electric Utilities Service Reliability Reports. November

Review of Florida s Investor-Owned Electric Utilities Service Reliability Reports. November Review of Florida s Investor-Owned Electric Utilities 2 0 1 6 Service Reliability Reports November 2 0 1 7 State of Florida Florida Public Service Commission Division of Engineering Review of Florida

More information

BVES Annual Reliability Public Presentation 2016 Performance

BVES Annual Reliability Public Presentation 2016 Performance BVES Annual Reliability Public Presentation 2016 Performance December 13, 2017 Agenda Company Overview What is Electric Utility Reliability? Requirements & Definitions Reliability Indices 2016 Reliability

More information

Circuit Reliability Review

Circuit Reliability Review Circuit Reliability Review Marina Del Rey January 2018 Building a Smarter Grid for Southern California Southern California Edison is developing an electric grid to support California s transition to a

More information

Report on Reliability of ComEd Electrical Service within Downers Grove. Prepared September 1, 2013

Report on Reliability of ComEd Electrical Service within Downers Grove. Prepared September 1, 2013 Report on Reliability of ComEd Electrical Service within Downers Grove Prepared September 1, 2013 1 Executive Summary Since 2011, the Village of Downers Grove has worked closely with ComEd to improve electrical

More information

Network Quality and Reliability of Supply

Network Quality and Reliability of Supply Network Quality and Reliability of Supply Performance Report 2010/11 Prepared by: Operations Asset & Works Audited by: Qualeng Left blank intentionally DMS 3444560 2 CONTENTS Horizon Power service area

More information

Report on Reliability of ComEd Electrical Service within Downers Grove. Prepared November 13, 2015

Report on Reliability of ComEd Electrical Service within Downers Grove. Prepared November 13, 2015 Report on Reliability of ComEd Electrical Service within Downers Grove Prepared November 13, 2015 1 Executive Summary Since 2011, the Village of Downers Grove has worked closely with ComEd to improve electrical

More information

Debbie Lee, Communications and Public Affairs Officer. Update on Southern California Edison s Capital Improvement Projects

Debbie Lee, Communications and Public Affairs Officer. Update on Southern California Edison s Capital Improvement Projects Information Item Date: June 22, 2015 To: From: Subject: Mayor and City Council Debbie Lee, Communications and Public Affairs Officer Update on Southern California Edison s Capital Improvement Projects

More information

Reven ue Req u i remen t Ap pl icat ion 2004/05 and 2005/06. BC hydro m W. Volume 2. Appendix L. System Performance Indicators

Reven ue Req u i remen t Ap pl icat ion 2004/05 and 2005/06. BC hydro m W. Volume 2. Appendix L. System Performance Indicators Reven ue Req u i remen t Ap pl icat ion 00/0 and 00/0 BC hydro m W Volume Appendix L. System Performance Indicators BChydro m ui Table of Contents LIST OF FIGURES... I LIST OF TABLES... I LIST OF SCHEDULES...

More information

Electric Distribution Storm Hardening Initiatives. Paul V. Stergiou Distribution Engineering October 14 th, 2015

Electric Distribution Storm Hardening Initiatives. Paul V. Stergiou Distribution Engineering October 14 th, 2015 Consolidated Edison Company of New York, Inc. Electric Distribution Storm Hardening Initiatives Paul V. Stergiou Distribution Engineering October 14 th, 2015 Energy For New York City And Westchester 3.3

More information

2013 December Ice Storm

2013 December Ice Storm 2013 December Ice Storm The 2013 December ice storm caused major damage to the Lansing Board of Water & Light (BWL) electric distribution system and had a devastating effect on many BWL customers. We realize

More information

Southern California Edison Wildfire Mitigation & Grid Resiliency

Southern California Edison Wildfire Mitigation & Grid Resiliency Southern California Edison Wildfire Mitigation & Grid Resiliency California State Legislative Conference Committee on Wildfire Preparedness and Response August 7, 2018 CALIFORNIA S WILDFIRE RISK Year-Round

More information

f<~~ ~ Gulf Power April16, 2018

f<~~ ~ Gulf Power April16, 2018 ~ Gulf Power Rhonda J. Alexander One Energy Place I 1anage' Pensacola. ~l 32520-0780 Regulatory Fooecastmg & Procong 850 444 67,13 tel 850.:144 6026 fax r jale>xad @~out her nro com April16, 2018 Ms. Carlotta

More information

Peterborough Distribution Inc Ashburnham Drive, PO Box 4125, Station Main Peterborough ON K9J 6Z5

Peterborough Distribution Inc Ashburnham Drive, PO Box 4125, Station Main Peterborough ON K9J 6Z5 Peterborough Distribution Inc. 1867 Ashburnham Drive, PO Box 4125, Station Main Peterborough ON K9J 6Z5 November 15, 2017 Ontario Energy Board PO Box 2319 27 th Floor, 2300 Yonge St Toronto ON M4P 1E4

More information

Network Quality and Reliability of Supply Code

Network Quality and Reliability of Supply Code Network Quality and Reliability of Supply Code 2017/18 Performance Report Prepared by: Asset Services Left blank intentionally DM#10417247 2017/18 Page 2 of 22 Contents 1. INTRODUCTION 5 2. AUDIT REQUIREMENTS

More information

Staging for Utility Personnel and Mutual Aid. 1. Hermine- Meeting dates were August 29th_31 st, 2016 and September 1st, 2016.

Staging for Utility Personnel and Mutual Aid. 1. Hermine- Meeting dates were August 29th_31 st, 2016 and September 1st, 2016. Town of Havana, Fl. Response to Review of Electric Utility Hurricane Preparedness and Restoration Actions- Applies only to Hermine and Irma. Maria and Nate posed no serious threat to Havana. Staging for

More information

Exploring the Reliability of U.S. Electric Utilities

Exploring the Reliability of U.S. Electric Utilities Exploring the Reliability of U.S. Electric Utilities Peter Larsen (Lawrence Berkeley National Laboratory/Stanford University) Kristina Hamachi LaCommare (LBNL) Joe Eto (LBNL) Jim Sweeney (Stanford) International

More information

Power System Research Group Electrical Engineering Dept., University of Saskatchewan Saskatoon, Canada

Power System Research Group Electrical Engineering Dept., University of Saskatchewan Saskatoon, Canada Abstract Failure Bunching Phenomena in Electric Power Transmission Systems Roy Billinton Gagan Singh Janak Acharya Power System Research Group Electrical Engineering Dept., University of Saskatchewan Saskatoon,

More information

Minnesota Public Utilities Commission Staff Briefing Papers

Minnesota Public Utilities Commission Staff Briefing Papers Minnesota Public Utilities Commission Staff Briefing Papers Meeting Date: March 7, 2006 Agenda Item # *10 Company: Docket Nos. Minnesota Power Northwestern Wisconsin Electric Company Interstate Power and

More information

How Power is Restored After a Severe Storm. Presented by Stacy Shaw, Safety Director & Nolan Hartzler, GIS Mapping Technician

How Power is Restored After a Severe Storm. Presented by Stacy Shaw, Safety Director & Nolan Hartzler, GIS Mapping Technician How Power is Restored After a Severe Storm Presented by Stacy Shaw, Safety Director & Nolan Hartzler, GIS Mapping Technician Hurricanes, ice storms, tornadoes One inch of ice on a single span of electric

More information

URD Cable Fault Prediction Model

URD Cable Fault Prediction Model 1 URD Cable Fault Prediction Model Christopher Gubala ComEd General Engineer Reliability Analysis 2014 IEEE PES General Meeting Utility Current Practices & Challenges of Predictive Distribution Reliability

More information

Smart Grid Opportunities Being Pursued. Stephanie Hamilton Brookhaven National Laboratory June 5, 2013

Smart Grid Opportunities Being Pursued. Stephanie Hamilton Brookhaven National Laboratory June 5, 2013 Smart Grid Opportunities Being Pursued Stephanie Hamilton Brookhaven National Laboratory June 5, 2013 OUR DREAM!! BNL s Smarter Electric Grid Research, Innovation, Development. Demonstration, Deployment

More information

BEFORE THE CORPORATION COMMISSION OF OKLAHOMA

BEFORE THE CORPORATION COMMISSION OF OKLAHOMA BEFORE THE CORPORATION COMMISSION OF OKLAHOMA IN THE MATTER OF THE APPLICATION OF ) OKLAHOMA GAS AND ELECTRIC COMPANY ) FOR AN ORDER OF THE COMMISSION ) CAUSE NO. PUD 20110008 AUTHORIZING APPLICANT TO

More information

Storm Damage Modeling at Pacific Gas & Electric

Storm Damage Modeling at Pacific Gas & Electric 1 Storm Damage Modeling at Pacific Gas & Electric Mike Voss PG&E Applied Technology Insert damage photos March 2015 Gas System Operations Electric Operations Power-Gen/ Hydro 2 Short Term Energy Supply

More information

Transmission & Distribution Electrical Reliability 2007 Annual Report

Transmission & Distribution Electrical Reliability 2007 Annual Report Transmission & Distribution Electrical Reliability 27 Annual Report Table of Contents SECTION 1 Executive Summary Report Summary Indices Synopsis Why We Track Overview of KEYS Reliability Statistics Overview

More information

Risk Analysis for Assessment of Vegetation Impact on Outages in Electric Power Systems. T. DOKIC, P.-C. CHEN, M. KEZUNOVIC Texas A&M University USA

Risk Analysis for Assessment of Vegetation Impact on Outages in Electric Power Systems. T. DOKIC, P.-C. CHEN, M. KEZUNOVIC Texas A&M University USA 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2016 Grid of the Future Symposium Risk Analysis for Assessment of Vegetation Impact on Outages in Electric Power Systems

More information

Vegetation Related Transmission Outage Report

Vegetation Related Transmission Outage Report Vegetation Related Transmission Outage Report Third 2013 3353 Peachtree Road NE Suite 600, North Tower Atlanta, GA 30326 404-446-2560 www.nerc.com Executive Summary The NERC Board of Trustees Compliance

More information

Lake Lure Community Meeting with Duke Energy

Lake Lure Community Meeting with Duke Energy Lake Lure Community Meeting with Duke Energy A community meeting was held on February 11, 2019 at Lake Lure Town Hall to discuss electric service to the town and surrounding areas. Lake Lure staff worked

More information

Big Data Paradigm for Risk- Based Predictive Asset and Outage Management

Big Data Paradigm for Risk- Based Predictive Asset and Outage Management Big Data Paradigm for Risk- Based Predictive Asset and Outage Management M. Kezunovic Life Fellow, IEEE Regents Professor Director, Smart Grid Center Texas A&M University Outline Problems to Solve and

More information

February 2011 Cold Snap. January 23, 2011 y, Earl Shockley, Director of Reliability Risk Management

February 2011 Cold Snap. January 23, 2011 y, Earl Shockley, Director of Reliability Risk Management February 2011 Cold Snap Event Recommendations January 23, 2011 y, Earl Shockley, Director of Reliability Risk Management Recommendations - Electric February 1 5, 2011 event occurred August 15, 2011 joint

More information

Exploring the Reliability of U.S. Electric Utilities. Laboratory

Exploring the Reliability of U.S. Electric Utilities. Laboratory Exploring the Reliability of U.S. Electric Utilities Peter Larsen 1,2, James Sweeney 1, Kristina Hamachi-LaCommare 2, and Joseph Eto 2 1 Management Science & Engineering Department, Stanford University

More information

Clearance around powerlines.

Clearance around powerlines. Clearance around powerlines. Help us keep you safe. Why do trees need to stay clear of powerlines? Trees growing too close to powerlines are a safety risk they could cause fires or even bring down lines

More information

Storm Hardening & Grid Resiliency. Withstanding and Recovering From Extreme Weather Events

Storm Hardening & Grid Resiliency. Withstanding and Recovering From Extreme Weather Events Storm Hardening & Grid Resiliency Withstanding and Recovering From Extreme Weather Events Definition Storm Hardening Physical changes to the utility s infrastructure to make it less susceptible to storm

More information

Norm Hann Performance Manager, Performance Management Department Hydro One Networks Inc.

Norm Hann Performance Manager, Performance Management Department Hydro One Networks Inc. Norm Hann Performance Manager, Performance Management Department Hydro One Networks Inc. Phone: (416)-345-5407 Email: Norm.Hann@HydroOne.com Closing the Crevice Achieving A Process For Asset Performance

More information

P.O BOX 429, NUKU ALOFA, Tel: (676) Fax: (676)

P.O BOX 429, NUKU ALOFA, Tel: (676) Fax: (676) P.O BOX 429, NUKU ALOFA, Tel: (676) 21-400 Fax: (676) 23-047 Email: afernando@tongapower.to 27 February, 2015 Lord Dalgety Electricity Commission Tu atakilangi Nuku alofa Dear Lord Dalgety Re: Monthly

More information

The Hardening of Utility Lines Implications for Utility Pole Design and Use

The Hardening of Utility Lines Implications for Utility Pole Design and Use NORTH AMERICAN WOOD POLE COUNCIL TECHNICAL BULLETIN The Hardening of Utility Lines Implications for Utility Pole Design and Use Prepared by: Martin Rollins, P.E. Abstract The hurricanes of 2005 caused

More information

RESILIENCE: THE NEW REALITY JEFFREY D. KNUEPPEL DEPUTY GENERAL MANAGER MARCH 17, 2015

RESILIENCE: THE NEW REALITY JEFFREY D. KNUEPPEL DEPUTY GENERAL MANAGER MARCH 17, 2015 RESILIENCE: THE NEW REALITY JEFFREY D. KNUEPPEL DEPUTY GENERAL MANAGER MARCH 17, 2015 EXTREME WEATHER = EXTREME COST EIGHT SEPARATE BILLION DOLLAR EXTREME WEATHER EVENTS ACROSS U.S. IN 2014 JANUARY 2014

More information

Reliability Assessment of Radial distribution system incorporating weather effects

Reliability Assessment of Radial distribution system incorporating weather effects International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn: 2278-800X, www.ijerd.com Volume 6, Issue 7 (pril 2013), PP. 45-51 Reliability ssessment of Radial distribution system

More information

STORM IMPLEMENTATION PLAN & ANNUAL RELIABILITY PERFORMANCE REPORTS

STORM IMPLEMENTATION PLAN & ANNUAL RELIABILITY PERFORMANCE REPORTS 2015 STORM IMPLEMENTATION PLAN & ANNUAL RELIABILITY PERFORMANCE REPORTS FILED: March 1, 2016 REVISED: August 24, 2016 2015 Storm Implementation Plan & Annual Reliability Performance Reports Tampa Electric

More information

1. Wind turbines are designed to operate within specified design criteria. Often the operating environment extends beyond these limits and causes

1. Wind turbines are designed to operate within specified design criteria. Often the operating environment extends beyond these limits and causes 1 2 1. Wind turbines are designed to operate within specified design criteria. Often the operating environment extends beyond these limits and causes outages. How these outages are classified can be challenging

More information

Director, Operations Services, Met-Ed

Director, Operations Services, Met-Ed Director, Operations Services, Met-Ed Pennsylvania House Republican Policy Committee Hearing on Storm Response Tobyhanna Township Municipal Building Pocono Pines, Pa. August 9, 2018 Planning and Forecast

More information

A Markov model for estimating the remaining life of electrical insulation in distribution transformer

A Markov model for estimating the remaining life of electrical insulation in distribution transformer AMERICAN JOURNAL OF SCIENTIFIC AND INDUSTRIAL RESEARCH 2010, Science Huβ, http://www.scihub.org/ajsir ISSN: 2153-649X doi:10.5251/ajsir.2010.1.3.539.548 A Markov model for estimating the remaining life

More information

STORM IMPLEMENTATION PLAN & ANNUAL RELIABILITY PERFORMANCE REPORTS

STORM IMPLEMENTATION PLAN & ANNUAL RELIABILITY PERFORMANCE REPORTS 2014 STORM IMPLEMENTATION PLAN & ANNUAL RELIABILITY PERFORMANCE REPORTS FILED: March 2, 2015 REVISED: August 17, 2015 2014 Storm Implementation Plan & Annual Reliability Performance Reports EXECUTIVE SUMMARY...

More information

ADVANCED METHODS FOR PREDICTION OF ANIMAL-RELATED OUTAGES IN OVERHEAD DISTRIBUTION SYSTEMS MIN GUI

ADVANCED METHODS FOR PREDICTION OF ANIMAL-RELATED OUTAGES IN OVERHEAD DISTRIBUTION SYSTEMS MIN GUI ADVANCED METHODS FOR PREDICTION OF ANIMAL-RELATED OUTAGES IN OVERHEAD DISTRIBUTION SYSTEMS by MIN GUI B.S., Central South University, 2 M.S.,Central South University, 23 AN ABSTRACT OF A DISSERTATION submitted

More information

QuantumWeather. A weather based decision support system for the utility industry. Bob Pasken and Bill Dannevik Saint Louis University

QuantumWeather. A weather based decision support system for the utility industry. Bob Pasken and Bill Dannevik Saint Louis University A weather based decision support system for the utility industry Bob Pasken and Bill Dannevik Saint Louis University Before we start I would like to say thank you to Dave Wakeman Kevin Anders Steve Brophy

More information

Resiliency of Power Grids After Earthquakes

Resiliency of Power Grids After Earthquakes Resiliency of Power Grids After Earthquakes John Eidinger, Alex Tang ATC 16th US - Japan - New Zealand Workshop Nara, June 27-29, 2016 eidinger@geengineeringsystems.com alexktang@mac.com No Power = No

More information

A new FMECA model for reliability computations in electrical distribution systems

A new FMECA model for reliability computations in electrical distribution systems Proceedings of the 6th WSEAS/IASME Int. Conf. on Electric Power Systems, High Voltages, Electric Machines, Tenerife, Spain, December 6-8, 2006 A new FMECA model for reliability computations in electrical

More information

Extreme Weather and Risks to Infrastructure. Heather Auld & Neil Comer Risk Sciences International

Extreme Weather and Risks to Infrastructure. Heather Auld & Neil Comer Risk Sciences International Extreme Weather and Risks to Infrastructure Heather Auld & Neil Comer Risk Sciences International The Science is Valid and the Evidence grows Stronger AGREE Climate Change Disagree More Intense Rainfall

More information

DRAFT IEEE PES Winter Technical Meeting 2008 San Antonio, Texas Meeting Minutes

DRAFT IEEE PES Winter Technical Meeting 2008 San Antonio, Texas Meeting Minutes DRAFT IEEE PES Winter Technical Meeting 2008 San Antonio, Texas Meeting Minutes Working Group on Distribution Reliability Part 1 Tuesday January 8th, 2008 10:00 to 4:00 pm Chair - Cheri Warren (mailto:

More information

AUSLEY MCMULLEN ATTORNEYS AND COUNSELORS AT LAW 123 SOUTH CALHOUN STREET. P.O. BOX 391 (zip 32302) TALLAHASSEE, FLORIDA 32301

AUSLEY MCMULLEN ATTORNEYS AND COUNSELORS AT LAW 123 SOUTH CALHOUN STREET. P.O. BOX 391 (zip 32302) TALLAHASSEE, FLORIDA 32301 AUSLEY MCMULLEN ATTORNEYS AND COUNSELORS AT LAW 123 SOUTH CALHOUN STREET P.O. BOX 391 (zip 32302) TALLAHASSEE, FLORIDA 32301 (8501 224-9115 FAX (8501 222-7560 March I, 2018 VIA: ELECTRONIC MAIL Mr. Tom

More information

IS YOUR BUSINESS PREPARED FOR A POWER OUTAGE?

IS YOUR BUSINESS PREPARED FOR A POWER OUTAGE? IS YOUR BUSINESS PREPARED FOR A POWER OUTAGE? Keeping your power on is our business Whether your business is large, small or somewhere in between, we understand that a power outage presents special challenges

More information

5.2 IDENTIFICATION OF HAZARDS OF CONCERN

5.2 IDENTIFICATION OF HAZARDS OF CONCERN 5.2 IDENTIFICATION OF HAZARDS OF CONCERN 2015 HMP Update Changes The 2010 HMP hazard identification was presented in Section 6. For the 2015 HMP update, the hazard identification is presented in subsection

More information

Multi Hazard Evaluation of a High Voltage Transmission Network. John Eidinger 1 and Leon Kempner 2

Multi Hazard Evaluation of a High Voltage Transmission Network. John Eidinger 1 and Leon Kempner 2 Multi Hazard Evaluation of a High Voltage Transmission Network John Eidinger 1 and Leon Kempner 2 1 G&E Engineering Systems Inc., P. O. Box 3592 Olympic Valley, CA 96146-3592; eidinger@earthlink.net. 2

More information

BEFORE THE PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA PACIFICORP. Direct Testimony of Heidemarie C. Caswell

BEFORE THE PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA PACIFICORP. Direct Testimony of Heidemarie C. Caswell Application No. -0- Exhibit No. Witness: Heidemarie C. Caswell BEFORE THE PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA PACIFICORP April 0 Caswell/i TABLE OF CONTENTS WITNESS QUALIFICATIONS...

More information

2016 HURRICANE SEASON PREPARATION. March 30, 2016

2016 HURRICANE SEASON PREPARATION. March 30, 2016 2016 HURRICANE SEASON PREPARATION March 30, 2016 Hurricane Season Plan Preparation Communication Restoration Distribution Vegetation Management Mainline Trimming (3 Year Cycle) Mainline Annual Trim Schedule

More information

2018 General Rate Case Rebuttal Testimony

2018 General Rate Case Rebuttal Testimony Application No.: A.16-09-001 Exhibit No.: SCE-18, Vol. 05 Witnesses: A. Edeson (U 338-E) 2018 General Rate Case Rebuttal Testimony Transmission & Distribution (T&D) Volume 05 - Distribution Construction

More information

Estimating the Spatial Distribution of Power Outages during Hurricanes for Risk Management

Estimating the Spatial Distribution of Power Outages during Hurricanes for Risk Management Estimating the Spatial Distribution of Power Outages during Hurricanes for Risk Management Marco Palmeri Independent Consultant Master s Candidate, San Francisco State University Dept. of Geography September

More information

Doppler Weather Radars and Weather Decision Support for DP Vessels

Doppler Weather Radars and Weather Decision Support for DP Vessels Author s Name Name of the Paper Session DYNAMIC POSITIONING CONFERENCE October 14-15, 2014 RISK SESSION Doppler Weather Radars and By Michael D. Eilts and Mike Arellano Weather Decision Technologies, Inc.

More information

Reliability Indices Measurement Reliability Indices Measurement for three 11 kv and 66 kv substations in Brunei Darussalam (PWR 01)

Reliability Indices Measurement Reliability Indices Measurement for three 11 kv and 66 kv substations in Brunei Darussalam (PWR 01) BNERI Reliability Indices Measurement Reliability Indices Measurement for three 11 kv and 66 kv substations in Brunei Darussalam (PWR 01) NUR SABIQAH HAJI ROSLI ACKNOWLEDGEMENT I would like to express

More information

An Introduction to Insulation Resistance Testing

An Introduction to Insulation Resistance Testing An Introduction to Insulation Resistance Testing In a perfect world, electrical insulation would allow no current to flow through it. Unfortunately, a number of factors can over time result in the deterioration

More information

The Study of Overhead Line Fault Probability Model Based on Fuzzy Theory

The Study of Overhead Line Fault Probability Model Based on Fuzzy Theory Energy and Power Engineering, 2013, 5, 625-629 doi:10.4236/epe.2013.54b121 Published Online July 2013 (http://www.scirp.org/journal/epe) The Study of Overhead Line Fault Probability Model Based on Fuzzy

More information

Responses to Questions Related to the October 10, 2012, Partners in Business Meeting

Responses to Questions Related to the October 10, 2012, Partners in Business Meeting Responses to Questions Related to the October 10, 2012, Partners in Business Meeting Question 1: Regarding the update on the ITC-Entergy transaction, what is the expected impact to ITC Midwest rates and

More information

Deep Thunder. Local Area Precision Forecasting for Weather-Sensitive Business Operations (e.g. Electric Utility)

Deep Thunder. Local Area Precision Forecasting for Weather-Sensitive Business Operations (e.g. Electric Utility) 1 Deep Thunder Local Area Precision Forecasting for Weather-Sensitive Business Operations (e.g. Electric Utility) Dipl. Ing. Helmut Ludwar Chief Technologist Wien, im Oktober 2010 Forecasts for Weather-Sensitive

More information

OPALCO Outage Analysis. December 2017 Board Meeting

OPALCO Outage Analysis. December 2017 Board Meeting OPALCO Outage Analysis December 217 Board Meeting What causes power outages in the islands? Wind Rain Major outages happen most often during wind storms - when winds are blowing above 3 miles per hour.

More information

A Model for Assessment of Power System Outages on Nigerian Transmission Network.

A Model for Assessment of Power System Outages on Nigerian Transmission Network. The International Journal Of Engineering And Science (IJES) Volume 4 Issue 4 Pages PP.73-8 215 ISSN (e): 2319 1813 ISSN (p): 2319 185 A Model for Assessment of Power System Outages on Nigerian Transmission

More information

NEWS RELEASE. Province boosts winter highway safety measures

NEWS RELEASE. Province boosts winter highway safety measures For Immediate Release 2018TRAN0045-000567 April 4, 2018 NEWS RELEASE Province boosts winter highway safety measures VICTORIA Following an intense winter, the is undertaking several improvements to make

More information

5.2 IDENTIFICATION OF HAZARDS OF CONCERN

5.2 IDENTIFICATION OF HAZARDS OF CONCERN 5.2 IDENTIFICATION OF HAZARDS OF CONCERN 2016 HMP Update Changes The 2011 HMP hazard identification was presented in Section 3. For the 2016 HMP update, the hazard identification is presented in subsection

More information

New Jersey Department of Transportation Extreme Weather Asset Management Pilot Study

New Jersey Department of Transportation Extreme Weather Asset Management Pilot Study New Jersey Department of Transportation Extreme Weather Asset Management Pilot Study Overview Prepared for: June 26, 2018 Introduction Overview of Pilot Study New Jersey s Climate New Jersey s Transportation

More information

Real-Time Weather Hazard Assessment for Power System Emergency Risk Management

Real-Time Weather Hazard Assessment for Power System Emergency Risk Management Real-Time Weather Hazard Assessment for Power System Emergency Risk Management Tatjana Dokic, Mladen Kezunovic Texas A&M University CIGRE 2017 Grid of the Future Symposium Cleveland, OH, October 24, 2017

More information

APPENDIX D AIRPORT SURVEY METHODS AND RESULTS

APPENDIX D AIRPORT SURVEY METHODS AND RESULTS APPENDIX D AIRPORT SURVEY METHODS AND RESULTS D.1.1 Approach Survey Development The project team developed the survey with the intention of gathering information about the types of weather events experienced

More information

Monday, November 19, :30 a.m. EST

Monday, November 19, :30 a.m. EST Monday, November 19, 2018 8:30 a.m. EST Significant Activity Nov 16-19 Significant Events: CA Wildfires Tropical Activity: Atlantic No new tropical cyclones are expected during the next 5 days Eastern

More information

How Graphic Representations of Outages at Alabama Power Are Made Simple

How Graphic Representations of Outages at Alabama Power Are Made Simple How Graphic Representations of Outages at Alabama Power Are Made Simple Presentation Overview This presentation will discuss the steps we took at Alabama Power using GIS to create a couple of different

More information

Processes and Impact of Natural Hazards

Processes and Impact of Natural Hazards The Big Island of Hawaii is the largest of the Hawaiian Islands. It is also home to a very active volcano. The Kilauea volcano has been active since 1983. The lava that flows from the Kilauea volcano has

More information

Tel Fax

Tel Fax Robert l. McGee, Jr. One Energy Place Regulatory & Pricing Manager Pensacola, Florida 0-0780 Tel 80..60 Fax 80..606 RLMCGEE@southernco.com GULF«, POWER A SOUTHERN COMPANY February 7, 0 Mr. Thomas Ballinger,

More information

Reliability Based Vegetation Management Through Intelligent System Monitoring

Reliability Based Vegetation Management Through Intelligent System Monitoring PSERC Reliability Based Vegetation Management Through Intelligent System Monitoring Final Project Report Power Systems Engineering Research Center A National Science Foundation Industry/University Cooperative

More information

Bridge Risk Modeling

Bridge Risk Modeling time good Bridge Risk Modeling Current Florida DOT Research condition bad Paul D. Thompson, Consultant Background Research team Florida State University John Sobanjo (PI) Paul D. Thompson (co-pi) Florida

More information

Empowering water/wastewater network management with GIS

Empowering water/wastewater network management with GIS Empowering water/wastewater network management with GIS Ioannis Kavouras_GIS Manager Surveying Engineer, MSc, MBA The Company responsible for fresh water distribution & sanitation serving 1.500.000 citizens

More information

Daily Operations Briefing Tuesday, April 4, :30 a.m. EDT

Daily Operations Briefing Tuesday, April 4, :30 a.m. EDT Daily Operations Briefing Tuesday, April 4, 2017 8:30 a.m. EDT Significant Activity Apr 3-4 Significant Events: Severe Weather Southern Plains to Southeast Significant Weather: Severe Thunderstorms and

More information

Contents: Platte-Clay Electric

Contents: Platte-Clay Electric Contents: Platte-Clay Electric Section 1: Introduction... 2 Section 2: Asset Inventory... 5 Section 3: Risk Assessment... 8 A. Historical Hazards... 10 Tornadoes... 10 Severe Thunderstorms, High Winds

More information

Climate change and power systems

Climate change and power systems Workshop DNV/NTNU 2011-09-27 Climate change and power systems Oddbjørn Gjerde, 1 Outline Introduction and background Climatic vulnerability today Climate prognoses Impact of climate changes on power systems

More information

Table of Contents. Annual Report

Table of Contents. Annual Report Blackout Tracker Table of Contents Introduction... 3 Productivity and Monetary Loss... 3 Significant Outages in Canada... 4 Provinces ranked by Outage... 5 What You Can Do to Protect Your Business... 5

More information

An Online Platform for Sustainable Water Management for Ontario Sod Producers

An Online Platform for Sustainable Water Management for Ontario Sod Producers An Online Platform for Sustainable Water Management for Ontario Sod Producers 2014 Season Update Kyle McFadden January 30, 2015 Overview In 2014, 26 weather stations in four configurations were installed

More information

Superstorm Sandy What Risk Managers and Underwriters Learned

Superstorm Sandy What Risk Managers and Underwriters Learned Superstorm Sandy What Risk Managers and Underwriters Learned Gary Ladman Vice President, Property Underwriting AEGIS Insurance Services, Inc. Superstorm Sandy Change in the Weather Recent years appears

More information

MACHINE LEARNING METHODS FOR THE ESTIMATION OF WEATHER AND ANIMAL-RELATED POWER OUTAGES ON OVERHEAD DISTRIBUTION FEEDERS PADMAVATHY KANKANALA

MACHINE LEARNING METHODS FOR THE ESTIMATION OF WEATHER AND ANIMAL-RELATED POWER OUTAGES ON OVERHEAD DISTRIBUTION FEEDERS PADMAVATHY KANKANALA MACHINE LEARNING METHODS FOR THE ESTIMATION OF WEATHER AND ANIMAL-RELATED POWER OUTAGES ON OVERHEAD DISTRIBUTION FEEDERS by PADMAVATHY KANKANALA B.Tech., Jawaharlal Nehru Technological University, 6 M.S.,

More information

Major Event Response Reporting Guelph Hydro Electric Systems Inc. (Guelph Hydro) May 4, 2018 Wind Storm

Major Event Response Reporting Guelph Hydro Electric Systems Inc. (Guelph Hydro) May 4, 2018 Wind Storm Major Event Response Reporting (Guelph Hydro) May 4, 2018 Wind Storm Page 2 of 16 Contents Introduction... 3 Prior to the Major Event... 4 During the Major Event... 7 After the Major Event... 14 Appendix

More information

FROM:~Keith Levchenko, Senior Legislative Analyst

FROM:~Keith Levchenko, Senior Legislative Analyst AGENDA ITEM #5 July 24,2012 Briefing MEMORANDUM July 20,2012 TO: County Council FROM:~Keith Levchenko, Senior Legislative Analyst SUBJECT: Briefing by the Office of Emergency Management and Homeland Security

More information

Complete Weather Intelligence for Public Safety from DTN

Complete Weather Intelligence for Public Safety from DTN Complete Weather Intelligence for Public Safety from DTN September 2017 White Paper www.dtn.com / 1.800.610.0777 From flooding to tornados to severe winter storms, the threats to public safety from weather-related

More information

Section 5. TADS Data Reporting Instruction Manual DRAFT Section 5 and Associated Appendices With Proposed Event Type Numbers

Section 5. TADS Data Reporting Instruction Manual DRAFT Section 5 and Associated Appendices With Proposed Event Type Numbers Section 5 TADS Data Reporting Instruction Manual DRAFT Section 5 and Associated Appendices With Proposed Event Type Numbers Rev. 5/10/2010 1 Section 5 Form for Event ID and Event Type Number Data TO s

More information

COMPANY NEWS JANUARY 2019 BE PREPARED FOR OUTAGES

COMPANY NEWS JANUARY 2019 BE PREPARED FOR OUTAGES COMPANY NEWS JANUARY 2019 BE PREPARED FOR OUTAGES None of us will forget the monster storm in January 2012 where snow and ice blanketed Western Washington. Plunging temperatures and freezing rain encased

More information

Storm Damage Modeling at the University of Connecticut

Storm Damage Modeling at the University of Connecticut Storm Damage Modeling at the University of Connecticut Brian Hartman, PhD ASA 31 January 2014.0 (but I don t care, it doesn t matter) Workshop on Insurance Mathematics Quebec, QC Acknowledgements The UConn

More information

GIS Solution For Electric Utilities With Integration With Distribution Management System

GIS Solution For Electric Utilities With Integration With Distribution Management System GIS Solution For Electric Utilities With Integration With Distribution Management System Agenda Importance Of The GIS GIS - DMS Integration Requirements Distribution Management System The Benefits Of The

More information

The Pennsylvania State University. The Graduate School. College of Engineering PREDICTIVE ANALYTICS FOR ENHANCING CUSTOMER SERVICE IN ELECTRIC UTILITY

The Pennsylvania State University. The Graduate School. College of Engineering PREDICTIVE ANALYTICS FOR ENHANCING CUSTOMER SERVICE IN ELECTRIC UTILITY The Pennsylvania State University The Graduate School College of Engineering PREDICTIVE ANALYTICS FOR ENHANCING CUSTOMER SERVICE IN ELECTRIC UTILITY A Thesis in Industrial Engineering by Raghav Goyal 2016

More information

Business Case: UV Facility Backup Generator

Business Case: UV Facility Backup Generator Business Case: UV Facility Backup Generator Eric Brainich December 13, 2010 Background The Portland Water Bureau is currently working on the design for a new Ultra Violet (UV) Treatment Facility and the

More information

Winter Preparation for Severe Weather Events

Winter Preparation for Severe Weather Events Winter Preparation for Severe Weather Events Jule Tate, Associate Director, Event Analysis Richard Hackman, Senior Reliability Advisor, Reliability Risk Management Mark Olson, Senior Engineer, Reliability

More information

Page No. (and line no. if applicable):

Page No. (and line no. if applicable): COALITION/IEC (DAYMARK LOAD) - 1 COALITION/IEC (DAYMARK LOAD) 1 Tab and Daymark Load Forecast Page No. Page 3 Appendix: Review (and line no. if applicable): Topic: Price elasticity Sub Topic: Issue: Accuracy

More information

AHEAD OF THE STORM: Extreme Weather Resilience in the City of Toronto

AHEAD OF THE STORM: Extreme Weather Resilience in the City of Toronto AHEAD OF THE STORM: Extreme Weather Resilience in the City of Toronto David MacLeod Toronto Environment and Energy Office Environmental Applied Science and Management Symposium 2013 March 21, 2013 Ahead

More information