Initial Evaluation of Composite Distribution Pole Technology

Size: px
Start display at page:

Download "Initial Evaluation of Composite Distribution Pole Technology"

Transcription

1 Initial Evaluation of Composite Distribution Pole Technology NEETRAC Project Number: July, 2004 A Research Center of the Georgia Institute of Technology Requested by: Dean Hettenbach Composite Materials Technology, LLC Principal Investigator: Caryn M. Riley, Ph.D. Reviewed by: Frank C. Lambert, P.E.

2 Table Of Contents SECTION 1.0 EXECUTIVE SUMMARY...1 SECTION 2.0 SCOPE...1 SECTION 3.0 TEST SAMPLES...2 SECTION 4.0 PROCEDURES Leakage Current Measurements Critical Impulse Flashover Testing Dry Critical Impulse Flashover Testing Wet...6 SECTION 5.0 RESULTS Leakage Current Measurements Critical Impulse Flashover Testing Dry & Wet...12 SECTION 6.0 CONCLUSIONS...21 SECTION 7.0 EQUIPMENT USED...22 SECTION 8.0 REFERENCES & STANDARDS...22 SECTION 9.0 APPENDIX Impulse Logs...23 NEETRAC Project Number , Draft July 30, 2004 i

3 Table of Tables Table 1: Performance Summary by Pole Type for Electrical Testing...1 Table 2: Electrical tests performed....2 Table 3: List of samples used in project...2 Table 4: Precipitation conditions during wet critical impulse flashover testing...6 Table 5: AC Leakage Current measurements for Sample CCA Table 6: AC Leakage Current measurements for Sample Table 7: AC Leakage Current measurements for Sample 9T...10 Table 8: AC Leakage Current measurements for Sample AT Table 9: Critical Impulse Flashover Test Results...13 Table 10: Atmospheric Conditions During Critical Impulse Flashover Testing...13 Table 12: Summary of Dielectric Test Results by Pole Type...21 Table 13: Impulse log for Sample 10T...23 Table 14: Impulse log for Sample 9B...24 Table 15: Impulse Log for CCA-2 Dry Critical Impulse Flashover Testing...25 Table 16: Impulse log for Sample 10B...25 Table 17: Impulse log for Sample 11T...26 Table 18: Impulse log for Sample CCA-2 Wet Critical Impulse Flashover Testing...28 NEETRAC Project Number , Draft July 30, 2004 ii

4 Table of Figures Figure 1: Leakage current measurement setup for samples 13 and 9T....3 Figure 2: Leakage current measurement setup for samples CCA-1 and AT Figure 3: Critical impulse flashover test setup with sample 10T...5 Figure 4: Example of a flashover event during dry CFO testing of sample 9B...5 Figure 5: Wet critical impulse flashover test setup with sample 11T...7 Figure 6: Example of wet sample 10B...8 Figure 14: CCA Pole on fire during leakage current measurement test...9 Figure 15: Resistive current versus applied voltage for the composite poles tested...11 Figure 16: Watts-Loss versus applied voltage for the composite poles tested...12 Figure 17: Damage to sample 10T after the positive CFO dry testing was complete...14 Figure 18: Closeup view of damaged sample 10T after positive CFO dry testing Figure 19: Damage to sample 9B after the positive CFO testing dry was complete...16 Figure 20: Close up views of sample 9B at neutral connection after positive CFO dry testing.17 Figure 21: Views of sample 10B after the positive CFO wet testing...18 Figure 22: View of sample 11T after positive CFO wet testing was halted...19 Figure 23: Close up views of trapped water within sample 11T after the positive CFO wet testing was halted...20 NEETRAC Project Number , Draft July 30, 2004 iii

5 Initial Evaluation of Composite Distribution Pole Technology NEETRAC Project Number / SECTION 1.0 EXECUTIVE SUMMARY NEETRAC completed an initial evaluation of the dielectric properties of three prototype pole materials manufactured by Composite Materials Technology, LLC. For comparison to current technology, the testing program also included evaluation of CCA pole technology. These poles were supplied by NEETRAC. Three dielectric tests were performed including measurement of the leakage current over a range of applied voltages, and positive critical impulse flashover testing under both dry and wet conditions. A total of nine samples were tested as a part of the dielectric properties evaluation. A new composite pole was installed prior to each dielectric test. Two CCA samples were used for the three dielectric tests performed. Each pole was configured with a pole-top porcelain pin insulator mounted such that it was centered on the pole and the mounting bolt was 4 from the top of the pole. The neutral was mounted on a spool insulator 66 from the top of the pole. The best performing pole type for each dielectric test is listed in Table 1. Table 1: Performance Summary by Pole Type for Electrical Testing Electrical Dielectric Test Best Performing Pole Type Leakage Current CMT Type 3 Positive CFO Dry CMT Type 1 Positive CFO Wet CCA SECTION 2.0 SCOPE In March 2004, Dean Hettenbach from Composite Materials Technology, LLC (hereafter CMT) requested testing services from NEETRAC s electrical and mechanical systems group. Two separate testing programs were initiated and the results of the electrical testing are discussed in this report. The work completed under both testing programs is subject to the proprietary information agreement between CMT and the Georgia Tech Research Corporation. All results and conclusions contained in this report are considered proprietary information. NEETRAC performed three different electrical tests on multiple pole types as listed in Table 2. CMT supplied seven different poles for the electrical testing. NEETRAC supplied the CCA poles for testing. Leakage current measurements were recorded over a range of system voltages from 4kV through 115kV. The positive critical impulse flashover tests were performed as specified in IEEE Std Clause subsection b. The wet testing was performed under the precipitation conditions specified in the Standard test procedure of Table 3 of IEEE Std with the following exception: tap water was used in the testing. NEETRAC Project Number , Draft July 30,

6 Table 2: Electrical tests performed. Test Description Leakage Current Measurement (dry only) Positive Critical Impulse Flashover DRY Positive Critical Impulse Flashover WET Pole types tested CCA, Three CMT types CCA, Two CMT types CCA, Two CMT types SECTION 3.0 TEST SAMPLES Seven poles of three different types were supplied by CMT for the electrical testing. Of the poles supplied by CMT, types 1 & 2 were predrilled and sealed with a caulked gasket (if necessary). NEETRAC drilled pole AT02 with a masonry bit prior to performing the leakage current measurements. NEETRAC supplied two CCA poles for the testing. The complete list including the pole type is contained in Table 3. Table 3: List of samples used in project. Sample ID Description Sample Description Supplied By 13 New/predrilled CMT 10T CMT Type 1 New/predrilled CMT 10B New/predrilled with caulked gasket on top CMT 9T New/predrilled CMT 9B CMT Type 2 New/predrilled CMT 11T New/predrilled w/caulked gasket on top CMT AT02 CMT Type 3 New/not predrilled CMT CCA 1 CCA Pole New NEETRAC CCA 2 CCA Pole Old field-aged 2-3 years NEETRAC Using NEETRAC s pole stand, each pole for the electrical testing was outfitted with a pole-top 25kV pin insulator and a neutral. The pole-top porcelain pin insulator and neutral were mounted on the pre-drilled locations on each CMT prototype pole. For the CCA poles, the pole-top porcelain pin insulator was mounted such that it was centered on the pole and the mounting bolt was 4 from the top of the pole. The neutral was mounted on a spool insulator 66 from the top of the pole. SECTION 4.0 PROCEDURES 4.1 Leakage Current Measurements NEETRAC measured the leakage current of four different pole samples. This test simply evaluated each pole s material; therefore the pole-top pin and spool insulators were removed from the pole configuration described in Section 3.0. The test voltage was applied to the pin of the pole-top pin insulator mounting bracket. The current was then measured from the lower bolt on the insulator mounting bracket to the mounting bolt for the spool insulator. See Figure 1 for an example of the configuration. For samples 13 and 9T, the NEETRAC Field HIVARC test set was used to supply the NEETRAC Project Number , Draft July 30,

7 test voltage. The leakage current drawn by the CCA-1 sample exceeded the available supply of the NEETRAC Field HIVARC test set and required use of the Biddle 700kV Series Resonant test set. Figure 2 shows an example of this configuration. To reduce setup time, the same voltage supply was used to test CMT sample AT02. Measurements of the leakage current and test voltage were recorded from 2.3kV up to 66.4kV (all phase to ground voltages). This voltage range is equivalent to system voltages of 4kV to 115kV. The results of the testing are presented in Section 5.1. Voltage Probe Voltage Supply Figure 1: Leakage current measurement setup for samples 13 and 9T. NEETRAC Project Number , Draft July 30,

8 Voltage Source Voltage Probe Figure 2: Leakage current measurement setup for samples CCA-1 and AT Critical Impulse Flashover Testing Dry Three new test samples were used to evaluate the critical impulse flashover characteristics of the CCA, CMT type 1 and CMT type 2 pole materials. A Maxwell 2.1MV Impulse generator was used to apply lightning impulses compliant with the specification given in IEEE Std Clause The 50% disruptive discharge voltage test procedure from IEEE Std Clause b (up-and-down method) was used to determine the critical impulse flashover voltage for each sample. In this test, a 1.2/50 lightning impulse is applied to the sample. The voltage level is then increased by V if one or more withstands occur; otherwise it is decreased by the same amount. Each impulse was measured using a Nicolet Power Pro 610 impulse data acquisition system. The peak voltage, front time, and tail time were computed and recorded electronically. The test setup utilized for this testing is pictured in Figure 3. Copper tubing was used to represent the phase voltage and neutral conductors. During the course of the testing, the overshoot values exceeded the tolerances specified in IEEE Std To eliminate this error, a 10kV arrester was used to smooth the impulse voltage peak. For this project, only impulses of positive polarity were applied to evaluate the samples. An example of a flashover event is shown in Figure 4. NEETRAC Project Number , Draft July 30,

9 10kV Arrester Impulse Divider Impulse Generator Figure 3: Critical impulse flashover test setup with sample 10T Figure 4: Example of a flashover event during dry CFO testing of sample 9B NEETRAC Project Number , Draft July 30,

10 4.3 Critical Impulse Flashover Testing Wet For the wet critical impulse flashover testing, two new poles of CMT type 1 and CMT type 2 were utilized. The same pole sample, CCA-2, was used to determine its wet critical impulse flashover characteristics. Either the Maxwell 2.1MV Impulse generator or the Haefely 600kV Impulse generator was used to apply lightning impulses compliant with the specification given in IEEE Std Clause The 50% disruptive discharge voltage test procedure from IEEE Std Clause b (up-and-down method) was used to determine the critical impulse flashover voltage for each sample. In this test, a 1.2/50 lightning impulse is applied to the sample. The voltage level is then increased by V if one or more withstands occur; otherwise it is decreased by the same amount. Each impulse was measured using a Nicolet Power Pro 610 impulse data acquisition system. The peak voltage, front time, and tail time were computed and recorded electronically. The test setup utilized for this testing is pictured in Figure 5 and Figure 6. The precipitation conditions used for each test met the requirements of IEEE Std Clause 14.2 Table 3 Standard Test Procedure with one exception. The testing was performed with tap water and not conditioned water. The precipitation conditions including the resistivity of the water are reported in Table 4. Copper tubing was used to represent the phase voltage and neutral conductors. Samples 10B and 11T were topped with a sealing gasket to remove the possibility of water ingress from the top. During the course of the testing, the overshoot values exceeded the tolerances specified in IEEE Std To eliminate this error, a 10kV arrester was used to smooth the impulse voltage peak. For this project, only impulses of positive polarity were applied to evaluate the samples. Table 4: Precipitation conditions during wet critical impulse flashover testing 1 Sample Number Precipitation Rate Vertical Component in mm/min Horizontal Component in mm/min Collected Water Parameters Temperature in C Resistivity in Ω m 10B T CCA IEEE Std specifies the following limits for the Standard Test Procedure: vertical component mm/min and horizontal component mm/min; Measurements were recorded over the pole section from the pole-top pin insulator to the neutral. NEETRAC Project Number , Draft July 30,

11 Impulse Divider 10kV Arrester Impulse Generator Water Spray Figure 5: Wet critical impulse flashover test setup with sample 11T NEETRAC Project Number , Draft July 30,

12 Figure 6: Example of wet sample 10B NEETRAC Project Number , Draft July 30,

13 SECTION 5.0 RESULTS 5.1 Leakage Current Measurements Four different pole types were tested to determine their leakage properties, three composite poles and one CCA pole. The CCA pole demonstrated the highest leakage currents of the four types tested. In attempting to raise the applied voltage to 7.2kV (12kV system voltage), the pole caught fire internally (see Figure 7) and burned an internal channel. Of the three composite poles, pole AT02 demonstrated the lowest leakage current. Figure 8 and Figure 9 depict the resistive current and wattsloss measured respectively for the three composite poles. The measurement data from this testing is contained in Table 5 through Table 8. System Voltage (Phase to Phase) Table 5: AC Leakage Current measurements for Sample CCA-1 Equivalent Phase to Ground Voltage Applied Vrms in kv I rms in ma I res in ma I cap in ma 2 Watts 4kV 2.3kV kV 3.2kV kV 7.2kV ~6.0 No measurement recorded. Pole caught fire. Smoke Figure 7: CCA Pole on fire during leakage current measurement test. 2 Capacitive current only valid for sine waves, 60Hz. NEETRAC Project Number , Draft July 30,

14 System Voltage (Phase to Phase) Table 6: AC Leakage Current measurements for Sample 13 Equivalent Phase to Ground Voltage Applied Vrms in kv I rms in ma I res in ma I cap in ma 3 Watts 4kV 2.3kV kV 7.2kV kV 8.7kV kV 11.55kV kV 14.4kV kV 15.6kV kV 20.2kV kV 26.6kV kV 39.8kV kV 66.4kV System Voltage (Phase to Phase) Table 7: AC Leakage Current measurements for Sample 9T Equivalent Phase to Ground Voltage Applied Vrms in kv I rms in ma I res in ma I cap in ma 3 Watts 4kV 2.3kV kV 7.2kV kV 8.7kV kV 11.55kV kV 14.4kV kV 15.6kV kV 20.2kV kV 26.6kV kV 39.8kV kV 66.4kV Capacitive Current valid only for sine waves, 60 hz. NEETRAC Project Number , Draft July 30,

15 System Voltage (Phase to Phase) Table 8: AC Leakage Current measurements for Sample AT02 Equivalent Phase to Ground Voltage Applied Vrms in kv I rms in ma I res in ma I cap in ma 4 Watts 4kV 2.3kV kV 7.2kV kV 8.7kV kV 10.55kV kV 14.4kV kV 15.6kV kV 20.2kV kV 26.6kV kV 39.8kV kV 66.4kV Resistive Current vs. Applied Voltage for Composite Poles Tested Resistive Current in ma Applied Vrms in kv Sample 13 Sample 9T Sample AT02 Figure 8: Resistive current versus applied voltage for the composite poles tested 4 Capacitive current only valid for sine waves, 60Hz. NEETRAC Project Number , Draft July 30,

16 Watts-Loss vs. Applied Voltage for Composite Poles Tested Watts Applied Vrms in kv Sample 13 Sample 9T Sample AT02 Figure 9: Watts-Loss versus applied voltage for the composite poles tested. 5.2 Critical Impulse Flashover Testing Dry & Wet The critical impulse flashover test was performed on five different samples. Samples 10T, 9B, and CCA-2 were subjected to the critical impulse flashover test under dry conditions using only positive polarity impulses. Sample CCA-2 was used in the testing due to the internal damage to CCA-1 during the leakage current measurements. Samples 10B, 11T and CCA-2 were subjected to the critical impulse flashover test under wet conditions. The up-and-down 50% disruptive discharge voltage test method as described in IEEE Std was used. A minimum of twenty impulses was required in order to calculate the positive CFO value for any sample. The positive CFO values for each sample are reported in Table 9. The complete impulse logs are contained in the appendix in Section 9.1. In the testing under dry conditions, the CMT poles both exceeded the CFO value for a new CCA pole. However, sample 10T was no longer mechanically viable at the end of the testing. Figure 10 and Figure 11 show the damage experienced by the pole as a result of the testing. CMT pole type 2, sample 9B, had a high CFO value and experienced less damage than CMT pole type 1 as a result of the testing. The greatest damage was seen at the neutral bolt connection (see Figure 13). The CCA pole experienced minimal damage during the CFO test. In the testing under wet conditions, the CCA pole outperformed both CMT pole types. CMT pole type 1, sample 10B, was able to complete the test series, but did show signs of water ingress on the NEETRAC Project Number , Draft July 30,

17 surface (see Figure 14.) CMT pole type 2, sample 11T, was unable to complete the entire test series. A channel was formed in the material during the course of the testing. Figure 16 shows the trapped water within the sample after it was removed from the testing. This pole type did show a positive CFO value of 712kV prior to the channel being formed. This CFO value was calculated from only eight impulses, however, and cannot be considered a true rating. The reported values in Table 9 have been corrected to standard atmospheric conditions according to IEEE Std The atmospheric conditions during each sample s testing are listed in Table 10. Table 9: Critical Impulse Flashover Test Results Sample Pole Type Test Positive CFO in kv 5 10T CMT Pole Type Critical Impulse Flashover 9B CMT Pole Type Dry CCA 2 CCA B CMT Pole Type Critical Impulse Flashover 11T CMT Pole Type 2 N/A Wet CCA 2 CCA 471 Table 10: Atmospheric Conditions During Critical Impulse Flashover Testing 6 Sample Date and Time Uncorrected Barometer Temperature at Barometer Dry Bulb Temperature Wet Bulb Temperature 10T 04/28/2004 2:17 PM mmhg 24.0 ºC 75.0 ºF 55.0 ºF 9B 04/29/2004 9:35 AM mmhg 22.0 ºC 71.0 ºF 58.0 ºF CCA-2 (Dry) 05/07/ :50 AM mmhg 24.0 ºC 76.0 ºF 64.0 ºF 10B 04/30/ :00 AM mmhg 23.0 ºC 75.0 ºF 65.0 ºF 11T 05/04/2004 9:30 AM mmhg 21.0 ºC 70.0 ºF 55.0 ºF CCA-2 (Wet) 05/07/2004 3:00 PM mmhg 24.5 ºC 78.0 ºF 64.0 ºF 5 6 These values have been atmospherically corrected per IEEE Std Note for all atmospheric readings in this report, laboratory location: 33º 39 North latitude, 1,010 elevation. NEETRAC Project Number , Draft July 30,

18 Figure 10: Damage to sample 10T after the positive CFO dry testing was complete. NEETRAC Project Number , Draft July 30,

19 Figure 11: Closeup view of damaged sample 10T after positive CFO dry testing. NEETRAC Project Number , Draft July 30,

20 Figure 12: Damage to sample 9B after the positive CFO testing dry was complete. NEETRAC Project Number , Draft July 30,

21 Figure 13: Close up views of sample 9B at neutral connection after positive CFO dry testing. NEETRAC Project Number , Draft July 30,

22 Trapped water on pole surface Figure 14: Views of sample 10B after the positive CFO wet testing. NEETRAC Project Number , Draft July 30,

23 Water path within the material Figure 15: View of sample 11T after positive CFO wet testing was halted. NEETRAC Project Number , Draft July 30,

24 Trapped water post testing Figure 16: Close up views of trapped water within sample 11T after the positive CFO wet testing was halted. NEETRAC Project Number , Draft July 30,

25 SECTION 6.0 CONCLUSIONS Three dielectric tests were performed to evaluate the electrical characteristics of two CMT pole prototype pole materials. To establish baseline performance information from current pole technology, CCA poles were also subjected to the same testing. A third prototype material only had the leakage current measurements recorded. When compared to the CCA poles tested, the CMT prototype poles demonstrated reduced leakage current properties, higher positive critical impulse flashover dry values (by as much as 29%), and lower positive critical impulse flashover wet values (by as much as 35%). Table 11 compares the dielectric test results by pole type and includes observations about the conditions of the poles after the testing. Although CMT Type 1 completed all of the dielectric tests, the structural integrity of the sample was compromised after positive CFO dry testing was completed. Table 11: Summary of Dielectric Test Results by Pole Type Pole Type Resistive Leakage Current in ma at System Voltage 4kV 115kV Positive CFO Dry in kv Positive CFO Wet in kv CMT Type CMT Type Failed to complete CMT Type Not tested Not tested Observations Severely reduced structural integrity at the end of positive CFO dry testing. Good structural integrity at the end of positive CFO wet testing. Some water trapped on the pole surface. Reduced structural integrity at the end of positive CFO dry testing, holes in the material near the neutral. Channel formed in the material during positive CFO wet testing. Sample damaged and unable to complete the required number of impulses. Lowest overall leakage current measured. Sample was not consistent with typical pole geometry. NEETRAC Project Number , Draft July 30,

26 Pole Type CCA 90.6 Resistive Leakage Current in ma at System Voltage 4kV 115kV Failed to complete Positive CFO Dry in kv Positive CFO Wet in kv Observations Excessive leakage current above 5kV (phase to ground) caused pole fire and an internal channel. Second pole sample used for CFO testing had minimal external damage after testing was complete. SECTION 7.0 EQUIPMENT USED Haefely 600kV Impulse Generator Maxwell 2.1MV Impulse Generator CQ2102 CQ2127 CQ2215 CN2157 CQ2191 CQ2210 CQ2215 CQ2217 CQ2219 SECTION 8.0 Biddle 700kV Series Resonant Test Set Nicolet Power Pro Impulse Scope Hipotronics Damped Capacitive Divider Cole Parmer Psychrodyne Tektronix TDS3014 Digital Phosphor Oscilloscope Fluke 27 Multimeter Princo Barometer Phenix 200kV Voltage Probe NEETRAC Field HIVARC Test Set REFERENCES & STANDARDS IEEE Std IEEE Standard Techniques for High-Voltage Testing L.T. Coffeen and J.E. McBride, 90 WM PWRD, High Voltage AC Resistive Current Measurements Using a Computer Based Digital Watts Technique, IEEE NEETRAC Project Number , Draft July 30,

27 SECTION 9.0 APPENDIX 9.1 Impulse Logs The peak voltage values in each table have not been corrected to standard atmospheric corrections. The values grouped by the dashed line were used to calculate the critical impulse flashover value. Table 12: Impulse log for Sample 10T Date Time Test Description Peak Voltage Front Time Tail / Chop Overshoot in kv in µs Time in µs (%) 4/28/ :53:46 red_10t_ /28/ :55:28 red_10t_ /28/ :58:03 red_10t_ /28/ :00:09 red_10t_ /28/ :01:58 red_10t_ /28/ :05:24 red_10t_ /28/ :30:38 red_10t_ /28/ :33:03 red_10t_ /28/ :35:08 red_10t_ /28/ :37:31 red_10t_ /28/ :16:59 red_10t_ /28/ :19:13 red_10t_ /28/ :21:46 chop_10t_ /28/ :27:24 ws_10t_ /28/ :29:59 ws_10t_ /28/ :32:19 chop_10t_ /28/ :34:50 ws_10t_ /28/ :36:55 chop_10t_ /28/ :38:54 ws_10t_ /28/ :40:47 chop_10t_ /28/ :42:48 ws_10t_ /28/ :44:55 chop_10t_ /28/ :48:40 ws_10t_ /28/ :50:42 chop_10t_ /28/ :52:23 ws_10t_ /28/ :54:08 ws_10t_ /28/ :56:04 chop_10t_ /28/ :58:00 chop_10t_ /28/ :59:49 ws_10t_ /28/ :01:31 chop_10t_ NEETRAC Project Number , Draft July 30,

28 Date Time Test Description Peak Voltage Front Time Tail / Chop in kv in µs Time in µs 4/28/ :03:25 ws_10t_ /28/ :06:52 chop_10t_ /28/ :08:59 ws_10t_ /28/ :11:36 chop_10t_ /28/ :13:23 ws_10t_ Overshoot (%) Table 13: Impulse log for Sample 9B Date Time Test Description Peak Voltage Front Time Tail / Chop in kv in µs Time in µs 4/29/2004 9:44:03 red_9b_ /29/2004 9:46:07 red_9b_ /29/2004 9:48:23 red_9b_ /29/ :15:21 red_9b_ /29/ :17:00 chop_9b_ /29/ :19:21 chop_9b_ /29/ :21:15 ws_9b_ /29/ :22:57 chop_9b_ /29/ :24:39 ws_9b_ /29/ :26:06 ws_9b_ /29/ :27:56 chop_9b_ /29/ :29:22 ws_9b_ /29/ :46:19 chop_9b_ /29/ :48:14 ws_9b_ /29/ :50:41 chop_9b_ /29/ :53:02 ws_9b_ /29/ :54:41 chop_9b_ /29/ :56:47 ws_9b_ /29/ :58:19 chop_9b_ /29/ :00:22 chop_9b_ /29/ :02:03 ws_9b_ /29/ :03:42 chop_9b_ /29/ :05:10 ws_9b_ /29/ :06:30 ws_9b_ /29/ :08:10 chop_9b_ /29/ :10:32 ws_9b_ Overshoot (%) NEETRAC Project Number , Draft July 30,

29 Table 14: Impulse Log for CCA-2 Dry Critical Impulse Flashover Testing Date Time Test Description Peak Voltage in kv Front Time in µs Tail / Chop Time in µs Overshoot (%) 5/7/ :55:39 red_cca_1d /7/ :57:45 red_cca_2d /7/ :59:26 red_cca_3d /7/ :01:29 red_cca_4d /7/ :03:49 ws_cca_5d /7/ :05:47 chop_cca_6d /7/ :07:52 ws_cca_7d /7/ :14:27 chop_cca_8d /7/ :16:47 prefire /7/ :18:05 ws_cca_9d /7/ :20:11 chop_cca_10d /7/ :21:39 ws_cca_11d /7/ :23:15 chop_cca_12d /7/ :25:14 ws_cca_13d /7/ :27:20 chop_cca_14d /7/ :28:42 ws_cca_15d /7/ :31:14 chop_cca_16d /7/ :33:26 chop_cca_17d /7/ :35:21 ws_cca_18d /7/ :37:12 ws_cca_19d /7/ :39:14 chop_cca_20d /7/ :41:05 ws_cca_21d /7/ :43:21 chop_cca_22d /7/ :45:16 ws_cca_23d /7/ :47:09 ws_cca_24d /7/ :48:47 chop_cca_25d /7/ :55:17 ws_cca_26d Table 15: Impulse log for Sample 10B Date Time Test Description Peak Voltage in kv Front Time in µs Tail / Chop Time in µs Overshoot (%) 4/30/ :58:08 red 10B /30/ :13:14 red 10B NEETRAC Project Number , Draft July 30,

30 Date Time Test Description Peak Voltage in kv Front Time in µs Tail / Chop Time in µs Overshoot (%) 4/30/ :15:14 RED 10B /30/ :19:12 WS 10B /30/ :21:17 CHOP 10B /30/ :24:27 CHOP 10B /30/ :26:20 WS 10B /30/ :29:43 CHOP 10B /30/ :32:23 CHOP 10B /30/ :34:37 CHOP 10B /30/ :37:44 WS 10B /30/ :40:24 CHOP 10B /30/ :42:05 WS 10B /30/ :44:14 CHOP 10B /30/ :45:20 WS 10B /30/ :46:57 CHOP 10B /30/ :48:51 WS 10B /30/ :50:12 CHOP 10B /30/ :51:38 WS 10B /30/ :53:13 CHOP 10B /30/ :54:49 WS 10B /30/ :56:06 WS 10B /30/ :58:19 CHOP 10B /30/ :59:18 WS 10B /30/ :01:43 CHOP 10B /30/ :04:14 WS 10B /30/ :06:32 CHOP 10B /30/ :07:48 WS 10B /30/ :09:13 CHOP 10B Table 16: Impulse log for Sample 11T Date Time Test Description Peak Voltage in kv Front Time in µs Tail / Chop Time in µs Overshoot (%) 5/4/ :05:56 red_11t_ /4/ :08:26 red_11t_ /4/ :10:17 red_11t_ /4/ :11:51 red_11t_ NEETRAC Project Number , Draft July 30,

31 Date Time Test Description Peak Voltage in kv Front Time in µs Tail / Chop Time in µs Overshoot (%) 5/4/ :13:23 red_11t_ /4/ :15:28 red_11t_ /4/ :16:50 red_11t_ /4/ :17:50 red_11t_ /4/ :19:21 red_11t_ /4/ :20:19 red_11t_ /4/ :40:32 red_11t_ /4/ :42:10 red_11t_ /4/ :44:04 red_11t_ /4/ :46:26 red_11t_ /4/ :47:58 red_11t_ /4/ :49:50 red_11t_ /4/ :51:53 red_11t_ /4/ :54:05 red_11t_ /4/ :56:15 chop_11t_ /4/ :58:08 chop_11t_ /4/ :59:42 ws_11t_ /4/ :02:01 chop_11t_ /4/ :03:22 chop_11t_ /4/ :04:52 ws_11t_ /4/ :06:39 ws_11t_ /4/ :08:01 ws_11t_ /4/ :10:32 ws_11t_ /4/ :13:10 chop_11t_ /4/ :15:15 ws_11t_ /4/ :17:11 chop_11t_ /4/ :18:56 ws_11t_ /4/ :20:24 chop_11t_ /4/ :22:46 ws_11t_ /4/ :25:28 chop_11t_ /4/ :27:42 chop_11t_ /4/ :29:37 chop_11t_ /4/ :32:05 chop_11t_ /4/ :33:44 chop_11t_ /4/ :37:59 chop_11t_ /4/ :40:02 chop_11t_ NEETRAC Project Number , Draft July 30,

32 Table 17: Impulse log for Sample CCA-2 Wet Critical Impulse Flashover Testing Date Time Test Description Peak Voltage Front Time Tail / Chop in kv in µs Time in µs 5/7/ :04:56 red_cca_1w /7/ :07:23 red_cca_2w /7/ :10:21 ws_cca_3w /7/ :13:26 chop_cca_4w /7/ :16:56 chop_cca_5w /7/ :19:40 chop_cca_6w /7/ :21:24 ws_cca_7w /7/ :23:21 chop_cca_8w /7/ :25:41 ws_cca_9w /7/ :27:54 chop_cca_10w /7/ :32:08 ws_cca_11w /7/ :34:46 chop_cca_12w /7/ :37:29 chop_cca_13w /7/ :39:24 ws_cca_14w /7/ :41:55 chop_cca_15w /7/ :44:47 chop_cca_16w /7/ :46:49 ws_cca_17w /7/ :49:05 chop_cca_18w /7/ :51:12 ws_cca_19w /7/ :53:11 chop_cca_20w /7/ :55:05 ws_cca_21w /7/ :56:44 chop_cca_22w /7/ :58:32 ws_cca_23w Overshoot (%) NEETRAC Project Number , Draft July 30,

O Plus Dry Bushing 69 kv system, 350 kv BIL, 3000 A. Table of contents

O Plus Dry Bushing 69 kv system, 350 kv BIL, 3000 A. Table of contents Type test report O Plus Dry Bushing 69 kv system, 0 kv BIL, 000 A Table of contents Abstract... 2 2 Certification... 2 Introduction.... Description and ratings....2 Overview of tests.... Applicable standards....4

More information

TEST CERTIFICATES OR REPORTS ISSUED BY VEIKI-VNL LTD.

TEST CERTIFICATES OR REPORTS ISSUED BY VEIKI-VNL LTD. Page 2 of 29 TEST CERTIFICATES OR REPORTS ISSUED BY LTD. Type Test Certificate of Complete Type Test This certificate provides the verification of all the rated characteristics of the equipment as assigned

More information

SPECIFICATION SS 51/9 400KV COUPLING CAPACITORS FOR POWER LINE CARRIER SYSTEM

SPECIFICATION SS 51/9 400KV COUPLING CAPACITORS FOR POWER LINE CARRIER SYSTEM INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION January 2017 SPECIFICATION SS 51/9 400KV COUPLING CAPACITORS FOR POWER LINE CARRIER SYSTEM I. SCOPE This

More information

O Plus Dry Bushing 25 kv system, 150 kv BIL, 3000 A

O Plus Dry Bushing 25 kv system, 150 kv BIL, 3000 A TYPE TEST REPORT O Plus Dry Bushing 25 kv system, 150 kv BIL, 3000 A 02 1 Abstract 02 2 Certification 03 3 Introduction 03 3.1 Description and ratings 03 3.2 Overview of tests 03 3.3 Applicable standards

More information

PRODUCT SPECIFICATION

PRODUCT SPECIFICATION Page 1 Page 2 1.0 SCOPE. This specification covers performance, tests and quality requirements for the SIM Card Connector SIM 2055 (Receiver Type, 6-Pin, SMT, 1.8 & 2.2mm Profiles). 2.0 PRODUCT NAME AND

More information

Thermal and temperature cycling tests on solid dielectric switches, interrupters, and reclosers

Thermal and temperature cycling tests on solid dielectric switches, interrupters, and reclosers Thermal and temperature cycling tests on solid dielectric switches, interrupters, and reclosers Reclosers and Other Distribution Equipment Subcommittee Meeting September 21, 2004 Frank C. Lambert Members

More information

Exercise 1: Capacitors

Exercise 1: Capacitors Capacitance AC 1 Fundamentals Exercise 1: Capacitors EXERCISE OBJECTIVE When you have completed this exercise, you will be able to describe the effect a capacitor has on dc and ac circuits by using measured

More information

CSA Design Test Report CS-8 Glass Bells Catalog # PCN160146

CSA Design Test Report CS-8 Glass Bells Catalog # PCN160146 CSA Design Test Report CS-8 Glass Bells Catalog # PCN160146 This design test report records the results of laboratory tests performed on the CS-8 Glass Bells which met or exceeded all performed tests of

More information

IEC Type Test Report Report No. EU1527-H-00.1 PH3 Series Polymer-housed Arrester 10,000 A Line Discharge Class 3

IEC Type Test Report Report No. EU1527-H-00.1 PH3 Series Polymer-housed Arrester 10,000 A Line Discharge Class 3 EU1527-H-00.1 IEC Type Test Report Report No. EU1527-H-00.1 PH3 Series Polymer-housed Arrester 10,000 A Line Discharge Class 3 This report records the results of type tests made on PH3 series 10 ka Line

More information

Blower Motor 3P Connector

Blower Motor 3P Connector 1. Scope Blower Motor P Connector 1.1 Content This specification covers the requirements for product performance, test methods and quality assurance provisions of Blower Motor P connector. Applicable product

More information

Interference suppression film capacitors MKP 336 1

Interference suppression film capacitors MKP 336 1 MKP RADIAL POTTED TYPE PITCH /15/22.5/27.5 mm l b h lt P d t CBA196 Fig.1 Simplified outlines. FEATURES to 27.5 mm lead pitch Supplied loose in box and taped on reel Consists of a low-inductive wound cell

More information

Electrical, Electronic and Computer Engineering ENEL4HB - High Voltage 2

Electrical, Electronic and Computer Engineering ENEL4HB - High Voltage 2 Electrical, Electronic and Computer Engineering ENEL4HB - High Voltage 2 Main Examination October 2015 Instructions Answer all questions and show all working. Time allowed = 2 hours Full marks = 100 Question

More information

High-ohmic/high-voltage resistors

High-ohmic/high-voltage resistors FEATURES These resistors meet the safety requirements of: UL1676 (range 510 kω to 11 MΩ) EN60065 BS60065 (U.K.) NFC 92-130 (France) VDE 0860 (Germany) High pulse loading capability Small size. APPLICATIONS

More information

Power System Engineering Prof. Debrapriya Das Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Power System Engineering Prof. Debrapriya Das Department of Electrical Engineering Indian Institute of Technology, Kharagpur Power System Engineering Prof. Debrapriya Das Department of Electrical Engineering Indian Institute of Technology, Kharagpur Lecture - 01 Overhead Line Insulators So, welcome to this another course that

More information

I n many cold-climate regions of the world, overhead

I n many cold-climate regions of the world, overhead Influence of Air-Gap Length and Position on the Flashover Performance of Ice-Covered Insulators under Switching Overvoltage T. Guerrero, J. Zhang, and M. Farzaneh NSERC / Hydro-Quebec / UQAC Industrial

More information

High Ohmic/High Voltage Resistors

High Ohmic/High Voltage Resistors High Ohmic/High Voltage Resistors VR68 A metal glazed film is deposited on a high grade ceramic body. After a helical groove has been cut in the resistive layer, tinned electrolytic copper wires are welded

More information

Recent Improvements in K-Factor Models

Recent Improvements in K-Factor Models 1 Recent Improvements in K-Factor Models Yixin Zhang NEETRAC, Georgia Institute of Technology 2014 IEEE PES Panel Session Discussions on IEEE Std.4-2013: High-Voltage Testing Techniques 2 Related Standards

More information

STUDIES ON LIGHTNING CHARACTERISTICS

STUDIES ON LIGHTNING CHARACTERISTICS STUDIES ON LIGHTNING CHARACTERISTICS Lohit Singh.G 1, Piyush Kankariya 1, Rakesh Kumar 1, Varun.P 1, Shreyas 1, Madhu Palati 2 1 UG Student, 2 Assistant Professor, 1, 2 Department of Electrical & Electronics

More information

APPLICATION NOTES FOR MULTILAYER CERAMIC CAPACITORS

APPLICATION NOTES FOR MULTILAYER CERAMIC CAPACITORS APPLICATION NOTES FOR MULTILAYER CERAMIC CAPITORS ELECTRICAL CHARTERISTICS The fundamental electrical properties of multilayer ceramic capacitors are as follows: Polarity: Multilayer ceramic capacitors

More information

CDS. high density spring connection

CDS. high density spring connection CDS high density spring connection DENSTY STANDARD 1A CDS DENSTY A A spring connection CDS Series The originality of multipole connectors represents one of the core values of LE, a leading company in this

More information

DDR4 SODIMM Socket 0.5mm Pitch 260Pos

DDR4 SODIMM Socket 0.5mm Pitch 260Pos 1. Introduction 1.1 Testing was performed on DDR4 SODIMM SOCKET 260P to determine if it meets the requirement of Product Specification, 108-115122 Rev.A. 1.2 Scope This report covers the electrical, mechanical

More information

Issued August DATA SHEET. 3VT5 MCCB up to 1600 A

Issued August DATA SHEET. 3VT5 MCCB up to 1600 A ssued August 9 DATA SHEET VT5 MCCB up to 0 A Based on Siemens Catalog V 8 Standard circuit breakers Releases Technical specifications Specifications VT5 circuit breakers Switch disconnectors Type Standards

More information

Flashover Performance of Station Post Insulators under Icing Conditions based on Electric Field Distribution

Flashover Performance of Station Post Insulators under Icing Conditions based on Electric Field Distribution Flashover Performance of Station Post Insulators under Icing Conditions based on Electric Field Distribution V. Jaiswal and M. Farzaneh NSERC / Hydro-Quebec / UQAC Industrial Chair on Atmospheric Icing

More information

Modeling of Transmission Line and Substation for Insulation Coordination Studies

Modeling of Transmission Line and Substation for Insulation Coordination Studies TRAINING DUBROVNIK, CROATIA - APRIL, 27-29 2009 SIMULATION & ANALYSIS OF POWER SYSTEM TRANSIENTS WITH EMTP-RV Modeling of Transmission Line and Substation for Insulation Coordination Studies Prof. Ivo

More information

SPECIFICATION AND PERFORMANCE CHARACTERISTICS OF SCA-2 CONNECTOR SERIES

SPECIFICATION AND PERFORMANCE CHARACTERISTICS OF SCA-2 CONNECTOR SERIES SPECIFICATION AND PERFORMANCE CHARACTERISTICS OF SCA-2 CIRCUIT ASSEMBLY CORP. 18 THOMAS STREET, IRVINE, CA 92618-2777 Page No. 1 CONTENTS CLAUSE PAGE 1.0 SCOPE. 4 1.2 Description. 4 2.0 APPLICABLE DOCUMENTS

More information

CTC 460 kcmil ACCC Conductor Stress Strain Tests

CTC 460 kcmil ACCC Conductor Stress Strain Tests CTC 46 kcmil ACCC Conductor Stress Strain Tests NEETRAC Project Number: 8-45 March, 28 Requested by: Doug Pilling CTC Principal Investigator: Paul Springer, PE Reviewed by: Graham Price CTC 46 kcmil Conductor

More information

WIESON TECHNOLOGIES CO., LTD.

WIESON TECHNOLOGIES CO., LTD. TABLE OF CONTENT 1. Scope.... 2 2. Reference Documents. 2 3. Material and Components.... 2 4. Design and Construction.... 2 5. Rating.. 2 6. Performance and Test Descriptions. 2 7. Test Requirements and

More information

Electrical, Electronic and Computer Engineering ENEL4HB - High Voltage 2

Electrical, Electronic and Computer Engineering ENEL4HB - High Voltage 2 Electrical, Electronic and Computer Engineering ENEL4HB - High oltage 2 Main Examination October 2016 Instructions Answer all questions, show all working and include all necessary comments (it is your

More information

Breakdown of MV Cable Jackets under Impulse Conditions. Caryn Riley, Ray Hill, Nigel Hampton. Spring ICC Sub Committee A

Breakdown of MV Cable Jackets under Impulse Conditions. Caryn Riley, Ray Hill, Nigel Hampton. Spring ICC Sub Committee A Breakdown of MV Cable Jackets under Impulse Conditions Caryn Riley, Ray Hill, Nigel Hampton Spring ICC 2010 - Sub Committee A 1 Background It has been suggested that URD circuits can experience abnormally

More information

Product Specification HYCAP HIGH TEMP, EXTREME SHOCK &VIBRATION. Family >>> HCD HC2D HC3D Max mass 18g 15g 15.5g

Product Specification HYCAP HIGH TEMP, EXTREME SHOCK &VIBRATION. Family >>> HCD HC2D HC3D Max mass 18g 15g 15.5g CPCITOR HYCP HIGH TEMP, &VIBRTION DTE 3/14/16 1.0 SCOPE This document contains specific electrical, mechanical, and environmental requirements and specifications for double- sealed, axial- leaded hybrid

More information

PH2200 Practice Final Exam Summer 2003

PH2200 Practice Final Exam Summer 2003 INSTRUCTIONS 1. Write your name and student identification number on the answer sheet. 2. Please cover your answer sheet at all times. 3. This is a closed book exam. You may use the PH2200 formula sheet

More information

This specification covers the requirements for product performance, test methods and quality assurance provisions of FG Terminal.

This specification covers the requirements for product performance, test methods and quality assurance provisions of FG Terminal. DESIGN OBJECTIVES The product described in this document has not been fully tested to ensure conformance to the requirements outlined below. Therefore AMP Ltd makes no representation or warranty, express

More information

Metallized Polypropylene Film Capacitor DC-Link Capacitor MKP Type

Metallized Polypropylene Film Capacitor DC-Link Capacitor MKP Type Metallized Polypropylene Film Capacitor DC-Link Capacitor MKP Type FEATURES Slim line, low building height Very long useful life time: Up to 100 000 h at U NDC and 70 C High ripple current capability,

More information

MKP-X2 TECHNICAL TERMS EXPLANATION

MKP-X2 TECHNICAL TERMS EXPLANATION TECHNICAL TERMS EXPLANATION Rated capacitance Capacitance referred to 1 khz, 20 +-1ºC, 65+-2% of relative humidity and 96+- 10 kpa. In case of doubt please refer to IEC 60068-1, sub-clause 5.2. Capacitance

More information

Copyright 2015 Elsevier S.A.

Copyright 2015 Elsevier S.A. This is the author s version of a work that was submitted/accepted for publication in the Electric Power Systems Research journal in the following source: Božidar Filipović-Grčić, Dalibor Filipović-Grčić,

More information

EasyDry transformer bushing Better performance made easy. Power and productivity for a better world TM ABB

EasyDry transformer bushing Better performance made easy. Power and productivity for a better world TM ABB EasyDry transformer bushing Better performance made easy Power and productivity for a better world TM ABB ABB, the world leader in high voltage bushing technology Global experience and resources The ABB

More information

OR Explain thermal breakdown in solid dielectrics. How this mechanism is

OR Explain thermal breakdown in solid dielectrics. How this mechanism is Subject : High Voltage Engineering (2090) ITM Universe, Vadodara Electrical Engineering Department Class : Electrical Sem : th Long Questions Sr. No Question Unit No : 0 Explain Charge Simulation method

More information

Code No: RR Set No. 1

Code No: RR Set No. 1 Code No: RR410209 Set No. 1 1. What are the gases mainly used in insulating medium at high pressures? Which is more suitable? Why? What about its dielectric strength? Explain. [16] 2. (a) Define time lags

More information

History II. Main Products II. Contents 1. Capacitor Application Product Scope Technical Data Bushings Characteristics Samwha 4 1-1 High Voltage Power Capacitor Single Phase Capacitor Insulation Level 36kV[50/150]

More information

TYPE. max. working voltage 250 V 350 V 500 V 750 V. max. overload voltage 500 V 700 V 1000 V 1500 V. basic specifications IEC B

TYPE. max. working voltage 250 V 350 V 500 V 750 V. max. overload voltage 500 V 700 V 1000 V 1500 V. basic specifications IEC B FEATURES Non inductive High pulse loading capability. APPLICATIONS Application for overload and high voltage surge hazard circuits. DESCRIPTION A carbon film is deposited on a high grade ceramic body.

More information

1. Explain the various methods of methods of grounding. In power system, grounding or earthing means connecting frame of electrical equipment (non-cur

1. Explain the various methods of methods of grounding. In power system, grounding or earthing means connecting frame of electrical equipment (non-cur 1. Explain the various methods of methods of grounding. In power system, grounding or earthing means connecting frame of electrical equipment (non-current carrying part) or some electrical part of the

More information

Fatima Michael College of Engineering & Technology

Fatima Michael College of Engineering & Technology ANNA UNIVERSITY AFFILIATED COLLEGES BE EEE SEMESTER VI EE2353 - HIGH VOLTAGE ENGINEERING UNIT IOVER VOLTAGES IN ELECTRICAL POWER SYSTEMS 1. What is surge arrester? 2. Name the sources of switching surges.

More information

1W, 1206, Low Resistance Chip Resistor (Lead free / Halogen Free)

1W, 1206, Low Resistance Chip Resistor (Lead free / Halogen Free) 1W, 1206, (Lead free / Halogen Free) 1. Scope This specification applies to 1.6mm x 3.2mm size 1W, fixed metal film chip resistors rectangular type for use in electronic equipment. 2. Type Designation

More information

Prof. Dr. Magdi El-Saadawi

Prof. Dr. Magdi El-Saadawi بسم هللا الرحمن الرحيم رب اشرح لى صدرى ويسر لى أمر واحلل عقدة من لسانى يفقهوا قولى صدق هللا العظيم Prof. Dr. Magdi M. El-Saadawi www.saadawi1.net E-mail : saadawi1@gmail.com www.facebook.com/magdi.saadawi

More information

Växelspänningsprov utförda på en kompositstolpe från Jerol Industri AB

Växelspänningsprov utförda på en kompositstolpe från Jerol Industri AB TEKNISKT MEDDELANDE UTM12-472 Till Avd Datum Projnr Sida Jerol Industri AB R 212-8-14 84646 1(1) Från, tfn Göran Olsson, 24-795 32 Kopior till Växelspänningsprov utförda på en kompositstolpe från Jerol

More information

Low Voltage Contact Electrostatic Discharge Phenomena

Low Voltage Contact Electrostatic Discharge Phenomena Conf Presentation - >SESSION.PAPER< - replace with your Session & Paper # (DOUBLE-CLICK HERE TO EDIT) < 1 Low Voltage Contact Electrostatic Discharge Phenomena Tetsuji Oda, Yuto Ono, Hiraku Miyasaka Abstract

More information

Product Series Specification Document

Product Series Specification Document Product Series 3.96mm pitch board-to-board connectors - Socket SCOPE This document covers 3.96mm socket connectors. The connector will perform to the specifications outlined. All tests have been performed

More information

PFC Input Capacitors PCMP 472 Metallized Polypropylene film capacitors

PFC Input Capacitors PCMP 472 Metallized Polypropylene film capacitors MKP RADIAL LACQUERED CAPACITORS(Dipped Type)-Brown Pitch 10.0/15.0/22.5/27.5mm (reduced pitch 7.5mm) QUICK REFERENCE DATA Capacitance range (E6 series) Capacitance tolerance Rated voltage (DC) Climatic

More information

IEEE ESMOL 2011 WINTER MEETING Las Vegas, Nevada February 14, 2011

IEEE ESMOL 2011 WINTER MEETING Las Vegas, Nevada February 14, 2011 E L E C T R I C A L S Y S T E M S Evaluation of Pole Bonding Methods NEETRAC Project No. 08-226 Shashi Patel IEEE ESMOL 2011 WINTER MEETING Las Vegas, Nevada February 14, 2011 GTRC 2011 1 Overall Project

More information

Digital Current Transducer HO-SW series I P N = A. Ref: HO 100-SW; HO 150-SW; HO 200-SW; HO 250-SW

Digital Current Transducer HO-SW series I P N = A. Ref: HO 100-SW; HO 150-SW; HO 200-SW; HO 250-SW Digital Current Transducer HO-SW series I P N = 100... 250 A Ref: HO 100-SW; HO 150-SW; HO 200-SW; HO 250-SW Bitstream output from on onboard Sigma Delta modulator. For the electronic measurement of current:

More information

Modeling Electric Fields in High Voltage Submersible Changeover Switch

Modeling Electric Fields in High Voltage Submersible Changeover Switch Excerpt from the Proceedings of the COMSOL Conference 2010 Paris Modeling Electric Fields in High Voltage Submersible Changeover Switch K. Follesø, Cand. scient in Experimental Particle Physics from University

More information

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME: EE 2303 - TRANSMISSION & DISTRIBUTION YEAR / SEM: III/V UNIT-I TRANSMISSION SYSTEM INTRODUCTION PART-A 1. What is

More information

Product Data Sheet PD-0037-B

Product Data Sheet PD-0037-B Product Data Sheet PD-0037-B 3M Shielded Compact Ribbon (SCR) Connector 3M Shielded Compact Ribbon (SCR) Boardmount Right Angle 36110-2220 XX 3 Electronic Solutions Division Page: 1 of 12 Table of Contents

More information

Lab 4 RC Circuits. Name. Partner s Name. I. Introduction/Theory

Lab 4 RC Circuits. Name. Partner s Name. I. Introduction/Theory Lab 4 RC Circuits Name Partner s Name I. Introduction/Theory Consider a circuit such as that in Figure 1, in which a potential difference is applied to the series combination of a resistor and a capacitor.

More information

High Voltage MLC Chips

High Voltage MLC Chips NEW 630V RANGE HOW TO ORDER 1808 A A 271 High value, low leakage and small size are difficult parameters to obtain in capacitors for high voltage systems. AVX special high voltage MLC chip capacitors meet

More information

All part numbers in the coding below start with "TC-" and end with "203"

All part numbers in the coding below start with TC- and end with 203 1. Scope: This specification for approval relates to 2. Type designation: The type designation shall be in the following form : All part numbers in the coding below start with "TC-" and end with "203"

More information

High Ohmic/High Voltage Resistors

High Ohmic/High Voltage Resistors High Ohmic/High Voltage Resistors A metal glazed film is deposited on a high grade ceramic body. After a helical groove has been cut in the resistive layer, tinned electrolytic copper wires are welded

More information

Effect of Humidity on the Flashover Voltage of Insulators at Varying Humidity and Temperature Conditions

Effect of Humidity on the Flashover Voltage of Insulators at Varying Humidity and Temperature Conditions 4299 J. Basic. Appl. Sci. Res., 2(4)4299-4303, 2012 2012, TextRoad Publication ISSN 2090-4304 Journal of Basic and Applied Scientific Research www.textroad.com Effect of Humidity on the Flashover Voltage

More information

Metallized PPS Capacitors for extreme capacitance stability. 1 min / 23 C B

Metallized PPS Capacitors for extreme capacitance stability. 1 min / 23 C B Replaces CKM 501 B series Applications & Characteristics Railway signalling High-temperature (125 C) High capacitance stability Harmonized circuits Filtering High-reliability circuits Security applications

More information

Funkentstör-Kondensatoren der Klasse X2

Funkentstör-Kondensatoren der Klasse X2 STÖRSCHUTZ-KONDENSATOREN Funkentstör-Kondensatoren der Klasse X2 TECHNICAL TERMS EXPLANATION Rated capacitance Capacitance referred to 1 khz, 20 +-1ºC, 65+-2% of relative humidity and 96+- 10 kpa. In case

More information

Electromagnetic Interference Suppression Capacitors Class X2 305/310VAC TECHNICAL SPECIFICATION. Metallized Polypropylene Film Capacitors (MKP)

Electromagnetic Interference Suppression Capacitors Class X2 305/310VAC TECHNICAL SPECIFICATION. Metallized Polypropylene Film Capacitors (MKP) Electromagnetic Interference Suppression Capacitors Class X2 305/310VAC ISKRA, d.d. Type: KNB1580 Issue: April 2018 PE ISKRA KONDENZATORJI d.d., Vajdova ulica 71, 8333 Semič, SLOVENIA Phone: +386 738 49

More information

Electrical Engineering Fundamentals for Non-Electrical Engineers

Electrical Engineering Fundamentals for Non-Electrical Engineers Electrical Engineering Fundamentals for Non-Electrical Engineers by Brad Meyer, PE Contents Introduction... 3 Definitions... 3 Power Sources... 4 Series vs. Parallel... 9 Current Behavior at a Node...

More information

2W, 2816, SL Type Low Resistance Chip Resistor (Lead / Halogen Free)

2W, 2816, SL Type Low Resistance Chip Resistor (Lead / Halogen Free) 2W, 2816, SL Type (Lead / Halogen Free) 1. Scope This specification applies to 4.2mm x 7.1mm size 2W, fixed metal foil current sensing resistors used in electronic equipment. 2. Features / Applications

More information

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad - 00 0 Department of Electrical and Electronics Engineering TUTORIAL QUESTION BANK Course Name : HIGH VOLTAGE ENGINEERING Course Code

More information

DATA SHEET General Purpose Thick Film Chip Resistor CR Series

DATA SHEET General Purpose Thick Film Chip Resistor CR Series Towards Excellence in Quality, Service & Innovation DATA SHEET General Purpose Thick Film Chip Resistor 1% TO 5%, TCR -200 TO +600 SIZE: 01005/0201/0402/0603/0805/1206/1210/2010/2512 RoHs Compliant Jan

More information

WCAP-FTXX Film Capacitors

WCAP-FTXX Film Capacitors A Dimensions: [mm] B Recommended hole pattern: [mm] D1 Electrical Properties: Properties Test conditions Value Unit Tol. Capacitance 1 V/ 1 khz ± 0.2 khz C 0.1000 µf ± 10% Rated voltage U R 310 V (AC)

More information

Overhead lines. 110 kv wood tower with guy wires

Overhead lines. 110 kv wood tower with guy wires Overhead lines a) ja b) 0 kv wood poles c) free standing 0 kv metal tower with I-strings d) free standing 440 kv metal tower with V-strings e) 400 kv metal tower with guy wires 0 kv wood tower with guy

More information

Lightning Flashover Rates of Overhead Distribution Lines Applying EMTP and IEEE Std.1410

Lightning Flashover Rates of Overhead Distribution Lines Applying EMTP and IEEE Std.1410 Lightning Flashover Rates of Overhead Distribution Lines Applying EMTP and IEEE Std.1410 123 Lightning Flashover Rates of Overhead Distribution Lines Applying EMTP and IEEE Std.1410 Thanaphong Thanasaksiri

More information

PRELIMINARY PRODUCT SPECIFICATION. Part Number Product Description Doc Number

PRELIMINARY PRODUCT SPECIFICATION. Part Number Product Description Doc Number Page 1 PRELIMINARY Page 2 1.0 SCOPE. This specification covers performance, tests and quality requirements for the USB Type C Receptacle range. USB4050, USB4055, USB4060, USB4065. 2.0 PRODUCT NAME AND

More information

Conventional Paper-I-2011 PART-A

Conventional Paper-I-2011 PART-A Conventional Paper-I-0 PART-A.a Give five properties of static magnetic field intensity. What are the different methods by which it can be calculated? Write a Maxwell s equation relating this in integral

More information

Independent, accredited testing station Member laboratory of STL and LOVAG TEST CONFIRMATION. on the given range of performed tests

Independent, accredited testing station Member laboratory of STL and LOVAG TEST CONFIRMATION. on the given range of performed tests Independent, accredited testing station Member laboratory of STL and LOVAG TEST CONFIRMATION on the given range of performed tests 3M Laboratories Europe Zweigniederlassung der 3M Deutschland GmbH Carl-Schurz-Str.

More information

KCSE PHYSICS PAPER SECTION A (25 marks) Answer all the questions in this section in the spaces provided.

KCSE PHYSICS PAPER SECTION A (25 marks) Answer all the questions in this section in the spaces provided. KCSE PHYSICS PAPER 1 2014 SECTION A (25 marks) Answer all the questions in this section in the spaces provided. 1. Figure 1 shows part of the main scale and vernier scale of a vernier callipers. Record

More information

Table of Contents Pin-Configuration Selection Guide for HDE, HDS, & EFP

Table of Contents Pin-Configuration Selection Guide for HDE, HDS, & EFP Table of Contents -Configuration Selection Guide for HDE, HDS, & EFP Service Voltage Rating... Electrical Service Ratings... Ampacity Ratings by Contact... Electrical Service Ratings Explained... Operating

More information

Capacitors. Dominik Pieniazek, P.E. VI Engineering, LLC Nicholas A. Losito Jr. Castle Power Solutions, LLC

Capacitors. Dominik Pieniazek, P.E. VI Engineering, LLC Nicholas A. Losito Jr. Castle Power Solutions, LLC Capacitors Dominik Pieniazek, P.E. VI Engineering, LLC Nicholas A. Losito Jr. Castle Power Solutions, LLC Outline Day 1 Basic Power Calculations Capacitor Fundamentals Capacitor Ratings Capacitor Application

More information

Finite Element Analysis of Disc Insulator Type and Corona Ring Effect on Electric Field Distribution over 230-kV Insulator Strings

Finite Element Analysis of Disc Insulator Type and Corona Ring Effect on Electric Field Distribution over 230-kV Insulator Strings International Journal of Engineering and Technology, 1 (4) (2012) 407-419 Science Publishing Corporation www.sciencepubco.com/index.php/ijet Finite Element Analysis of Disc Insulator Type and Corona Ring

More information

THERMAL FIELD ANALYSIS IN DESIGN AND MANUFACTURING OF A PERMANENT MAGNET LINEAR SYNCHRONOUS MOTOR

THERMAL FIELD ANALYSIS IN DESIGN AND MANUFACTURING OF A PERMANENT MAGNET LINEAR SYNCHRONOUS MOTOR THERMAL FIELD ANALYSIS IN DESIGN AND MANUFACTURING OF A PERMANENT MAGNET LINEAR SYNCHRONOUS MOTOR Petar UZUNOV 1 ABSTRACT: The modern Permanent Magnet Linear Synchronous Motors (PMLSM) has a wide range

More information

Issued August DATA SHEET. 3VT3 MCCB up to 630 A

Issued August DATA SHEET. 3VT3 MCCB up to 630 A ssued August 9 DATA SHEET VT MCCB up to 6 A Based on Siemens Catalog V 6 8 Circuit breakers Switch disconnectors Technical specifications Specifications Type VT 76-AA6/6/56-AA, VT 76-AA6/6/56-AA Circuit

More information

DATA SHEET Metal Element Current Sensing Chip Resistor (Jumper) CLS Series

DATA SHEET Metal Element Current Sensing Chip Resistor (Jumper) CLS Series DATA SHEET Metal Element Current Sensing Chip Resistor (Jumper) 5% SIZE: 0805,1206 & 2512 RoHs Compliant January 19, 2017 V.5 DS-ENG-009 Page: 2 of 14 1. SCOPE 1.1 This specification is applicable to lead

More information

MKV AC Capacitors Damping B High dielectric strength High peak-current capability Especially suitable for snubber circuits

MKV AC Capacitors Damping B High dielectric strength High peak-current capability Especially suitable for snubber circuits MKV AC Capacitors B 25 835 High dielectric strength High peak-current capability Especially suitable for snubber circuits Construction Self-healing Plastic dielectric Oil-impregnated tubular windings (no

More information

Advanced Technique for Dielectric Analyses

Advanced Technique for Dielectric Analyses Chroma Systems Solutions, Inc. Advanced Technique for Dielectric Analyses 190xx Series Hipot Testers Keywords: Dielectric Analyses, Destructive testing, Threshold Detection, Breakdown, Test Damage. Title:

More information

DIRECT STROKE LIGHTNING PROTECTION DESIGN

DIRECT STROKE LIGHTNING PROTECTION DESIGN International Journal of Research in Engineering and Applied Sciences(IJREAS) Available online at http://euroasiapub.org/journals.php Vol. 7 Issue 1,January7, pp. 1~12cv ISSN (O): 2249-3905, ISSN(P) :

More information

PRODUCT. Part. A1 Micro USB USB3140. Rev. Page. Description Doc USB3140.

PRODUCT. Part. A1 Micro USB USB3140. Rev. Page. Description Doc USB3140. 1 PREL LIM MI IN AR RY 1.0 SCOPE. This specification covers performance, tests and quality requirements for the Receptacle (Type B, SMT, Vertical)..0 NAME AND PART NUMBER. Receptacle, 5 Pins, SMT, Type

More information

3/4W, 2010 Low Resistance Chip Resistor

3/4W, 2010 Low Resistance Chip Resistor 1. Scope 3/4W, 2010 This specification applies to 2.5mm x 5.0mm size 3/4W, fixed metal film chip resistors rectangular type for use in electronic equipment. 2. Type Designation RL2550 L - Where (1) (2)

More information

Independent, accredited testing station Member laboratory of STL and LOVAG TEST CONFIRMATION. on the given range of performed tests

Independent, accredited testing station Member laboratory of STL and LOVAG TEST CONFIRMATION. on the given range of performed tests Independent, accredited testing station Member laboratory of STL and LOVAG TEST CONFIRMATION on the given range of performed tests 3M Laboratories Europe Zweigniederlassung der 3M Deutschland GmbH Carl-Schurz-Str.

More information

Metal Case Hermetically-Sealed Metalized Polyester-Film Capacitors

Metal Case Hermetically-Sealed Metalized Polyester-Film Capacitors Type 28P Metal Case Hermetically-Sealed Metalized Polyester-Film Capacitors EECTRICA SPECIFICATIONS Operating Temperature: -55 C to +25 C Capacitance Range: 0.00 μf to 2.0 μf Voltage Range: 00 VC to 400

More information

Voltage Breakdown Mechanisms in High Voltage Rated, Surface Mount MLCCs

Voltage Breakdown Mechanisms in High Voltage Rated, Surface Mount MLCCs CARTS USA 2007, 27 th Symposium for Passive Electronic Components, Albuquerque, New Mexico, USA, March 26 29, 2007 Voltage Breakdown Mechanisms in High Voltage Rated, Surface Mount MLCCs J. Bultitude,

More information

AREP Series Aluminum Solid Electrolytic Capacitors Aluminum Solid Electrolytic Capacitors

AREP Series Aluminum Solid Electrolytic Capacitors Aluminum Solid Electrolytic Capacitors Features -Super low ESR, high ripple current capability -Rated voltage:6.3~35vdc -Endurance:5,000 hours at 105ºC -Suitable for DC-DC converters, voltage regulators and decoupling applications -RoHS Compliant

More information

K04 TYPE -40 C +85 C 20000H

K04 TYPE -40 C +85 C 20000H K04 TYPE -40 C +85 C 20000H Extended life. Surge-proof capacitor in aluminium can with insulation sleeve. To be mounted with ring clips or with threaded stud. Designed for high resistances to voltage spikes.

More information

Qualification Test Report

Qualification Test Report Qualification Test Report 501-97 28Jun10 Rev E Connector, Shielded, Miniature Circular DIN, PCB Mounted 1. INTRODUCTION 1.1. Purpose Testing was performed on Tyco Electronics Mini DIN Printed Circuit Board

More information

Evaluation of the risk of failure due to switching overvoltages of a phase to phase insulation

Evaluation of the risk of failure due to switching overvoltages of a phase to phase insulation Evaluation of the risk of failure due to switching overvoltages of a phase to phase insulation A. Xemard, J. Michaud, A. Guerrier, I. Uglesic, G. Levacic, M. Mesic Abstract-- The upgrade of an overhead

More information

2011 New Products of MLCC

2011 New Products of MLCC 2011 New Products of MLCC 1 SAFETY CERTIFIED CHIP CAPACITOR. The The safety safety capacitors capacitors offered offered by by are are designed designed for for surge surge or or lightning lightning immunity

More information

farads or 10 µf. The letter indicates the part tolerance (how close should the actual value be to the marking).

farads or 10 µf. The letter indicates the part tolerance (how close should the actual value be to the marking). p1 EE1050/60 Capacitors Lab University of Utah Electrical Engineering Department EE1050/1060 Capacitors A. Stolp, 10/4/99 rev 3/17/01 Objectives 1.) Observe charging and discharging of a capacitor. 2.)

More information

REVISED HIGHER PHYSICS REVISION BOOKLET ELECTRONS AND ENERGY

REVISED HIGHER PHYSICS REVISION BOOKLET ELECTRONS AND ENERGY REVSED HGHER PHYSCS REVSON BOOKLET ELECTRONS AND ENERGY Kinross High School Monitoring and measuring a.c. Alternating current: Mains supply a.c.; batteries/cells supply d.c. Electrons moving back and forth,

More information

The ESD5451R is available in DFP1006-2L package. Standard products are Pb-free and Halogen-free. Circuit diagram

The ESD5451R is available in DFP1006-2L package. Standard products are Pb-free and Halogen-free. Circuit diagram ESD5451R 1-Line, Bi-directional, Transient Voltage Suppressors http//:www.sh-willsemi.com Descriptions The ESD5451R is a bi-directional TVS (Transient Voltage Suppressor). It is specifically designed to

More information

Power Resistor for Mounting onto a Heatsink Thick Film Technology

Power Resistor for Mounting onto a Heatsink Thick Film Technology DIMENSIONS in millimeters Power Resistor for Mounting onto a Heatsink Thick Film Technology FEATURES 300 W at 85 C bottom case temperature Wide resistance range: 0.3 Ω to 900 kω E24 series Non inductive

More information

HIGH VOLTAGE MULTILAYER CERAMIC CAPACITORS

HIGH VOLTAGE MULTILAYER CERAMIC CAPACITORS DESCRIPTION: RoHS compliant (*) Capacitors 0805 to 6560 Rated voltage 1000V to 10KV Dielectric Type I and II SMD and leaded versions * Non RoHS version still maintained for current applications. I. Foreword

More information

INSTITUTE OF AERONAUTICAL ENGINERING DUNDIGAL ELECTRICAL AND ELECTRONICS ENGINEERING

INSTITUTE OF AERONAUTICAL ENGINERING DUNDIGAL ELECTRICAL AND ELECTRONICS ENGINEERING INSTITUTE OF AERONAUTICAL ENGINERING DUNDIGAL ELECTRICAL AND ELECTRONICS ENGINEERING Course code : 5067(07-08) Course title : High voltage engineering Course structure Lectures Tutorials Practical credits

More information

Film Capacitors. EMI suppression capacitors. Date: June 2018

Film Capacitors. EMI suppression capacitors. Date: June 2018 Film Capacitors EMI suppression capacitors Date: June 2018 EPCOS AG 2018. Reproduction, publication and dissemination of this publication, enclosures hereto and the information contained therein without

More information

"Can cleanroom garments create electrostatic risks?"

Can cleanroom garments create electrostatic risks? "Can cleanroom garments create electrostatic risks?" J. N. Chubb (John Chubb Instrumentation,UK) P. Holdstock (British Textile Technology Group, UK) M. Dyer (William Barnet and Son Inc, US) Measurements

More information

MOLEX TAIWAN LTD ( GC ) TITLE : SINGLE PORT UP-RIGHT TYPE USB CONNECTOR

MOLEX TAIWAN LTD ( GC ) TITLE : SINGLE PORT UP-RIGHT TYPE USB CONNECTOR SINGLE PORT UP-RIGHT TYPE USB CONNECTOR 971205 1 of 8 1.0 SCOPE This specification covers the USB series product. 2.0 APPLICABLE DOCUMENTS The following documents form a part of this specification to the

More information