SION Lateral 3AE6 Vacuum Circuit Breaker with Lateral Operating Mechanism

Size: px
Start display at page:

Download "SION Lateral 3AE6 Vacuum Circuit Breaker with Lateral Operating Mechanism"

Transcription

1 Catalog HG.07 Edition 03/ 07 SION Lateral 3AE Vacuum Circuit Breaker with Lateral Operating Mechanism Medium-Voltage Equipment siemens.com/sion

2 R-HG-3.psd Catalog HG / 07

3 SION 3AE Vacuum Circuit Breaker Medium-Voltage Equipment Catalog Abridged HG First edition Contents Page Description 4 General information 4 Construction and mode of operation Standards and maintenance-free design Product range overview 9 Device selection 0 Ordering information and configuration example 0 Selection for 3AE circuit breakers Additional equipment for 3AE circuit breakers 4 Accessories and spare parts 7 Technical data 0 Electrical data, dimensions and masses 0 Dimension drawings Additional technical data Circuit diagrams 9 The products and systems listed in this catalog are manufactured and distributed using a certified management system (according to ISO 900, ISO 400 and BS OHSAS 00). Catalog HG / 07 3

4 Description General information SION 3AE Lateral vacuum circuit breakers from kv to 4 kv SION vacuum circuit breakers control all switching operations in medium-voltage distribution systems and are suitable for installation in all established and new air-insulated mediumvoltage switchgear as well as for retrofitting existing switchgear. They are applicable for operation of e.g. overhead lines, cables, transformers, capacitors and motors. The optional installation accessories enable easy integration into switchgear panels. Our comprehensive range of lateral circuit breakers offers a wide selection of pole-center distances as well as various equipment options for voltage levels from kv to 4 kv. Compact dimensions and well-protected terminals enable simple integration into commonly used medium-voltage switchgear. High reliability and availability are a matter of course, as are 0,000 maintenance-free operating cycles. 3AE SION Lateral for kv 3AE3 SION Lateral for 4 kv HG-07_3AE.tif HG-07_3AE3.tif Thanks to a range of equipment options, SION vacuum circuit breakers can be precisely tailored to your requirements. 4 Catalog HG / 07

5 Siemens AG 07 Description Construction and mode of operation Switching medium 3AE Proven and fully developed for more than 40 years, vacuum switching technology is the principal arc-quenching element used in vacuum interrupters. Pole assemblies 3AE_V_0.ai The pole assemblies consist of vacuum interrupters and pole shells. The vacuum interrupters are air-insulated and freely accessible. The pole assemblies are fixed on the mechanism mounting plate and supported by means of the pole shell (). The vacuum interrupter () is mounted rigidly to the upper interrupter support. The lower part of the interrupter is guided into the lower interrupter support, allowing axial movement. The pole shell () absorbs external forces resulting from switching operations and the contact pressure. Front view Cover of low-voltage interface Operating mechanism The whole operating mechanism with motor (3), releases, indicators and actuating devices is mounted on the mechanism mounting plate (9). This compact design enables very fast operating times. 3 3 The circuit breaker operating mechanism is a stored-energy spring mechanism. The force is transmitted from the operating mechanism to the pole assemblies via operating levers. The closing spring () can be charged either electrically or manually, and latches in automatically when charging is complete. The closing spring () acts as a stored-energy mechanism kv Pole structure 3 Separating shell to the operating mechanism 4 Upper connection Vacuum interrupter Pole shell 7 Lower connection Insulator Trip-free mechanism AE_V_03_kV.ai For charging the closing spring (), the motor (3) operates in short-time duty. Therefore the voltage and power consumption might differ from the data of the motor rating plate. kv In this way, the stored-energy mechanism stores the OPEN CLOSE OPEN operating sequence that is required for an auto-reclosing operation on the system side. All stored-energy mechanisms perform the switching duties of synchronizing, rapid load transfer, and auto-reclosing. The circuit breakers have a trip-free mechanism. In the event of an opening command being given after a closing operation has been initiated, the moving contacts return to the open position and remain there even if the closing command is sustained. However, the vacuum circuit breaker contacts are momentarily in the closed position AE_V_0.ai To close the breaker, the closing spring () can be unlatched either mechanically at the device (ON pushbutton), or electrically by remote control. The closing spring () charges the opening and/or contact-pressure springs as the breaker closes. The now discharged closing spring () will be charged again automatically by the motor (3). Central control board Pole structure 9 Mechanism mounting plate 0 Terminal strip Auxiliary switch Closing spring 3 Motor 4 Gear Catalog HG / 07

6 Description Construction and mode of operation Releases A release is a device which transfers electrical commands from an external source, such as a control room, to the latching mechanism of the vacuum circuit breaker so that it can be opened or closed. The releases are designed for shorttime duty up to minute and are reset internally. The various types of releases available are described in detail below: Closing solenoid The closing solenoid unlatches the charged closing spring of the vacuum circuit breaker, closing it by electrical means. Shunt releases Shunt releases are used for automatic tripping of the circuit breaker by suitable protection relays and for deliberate tripping by electrical means. They are intended for connection to an external power supply (DC or AC voltage). Current-transformer-operated releases Current-transformer-operated releases consist of a stored energy mechanism, an unlatching mechanism and an electro magnet system. They are used when there is no external source of auxiliary power (e.g. a battery). Tripping is effected by means of a protection relay (e.g. overcurrent time protection) acting on the current-transformer-operated release. Undervoltage releases Undervoltage releases consist of a stored-energy mechanism, an unlatching mechanism and an electromagnet system which is permanently connected to the secondary or auxiliary voltage while the circuit breaker is closed. If the voltage falls below a predetermined value, unlatching of the release is enabled and the circuit breaker is opened via the stored-energy mechanism. A maximum of two releases can be equipped in accordance with page 3. The consumption data of the releases is listed on page. Closing spring charged indication The circuit breakers have a mechanically operated spring charged indicator. The charging status of the closing spring can also be queried electrically by means of an integrated position switch. Circuit breaker tripping signal During electrical opening, the NO contact S makes brief contact. This is often used to operate a hazard warning system which should respond to automatic tripping of the circuit breaker. In case of local control, the NO contact S does not close. For the corresponding circuit diagrams, refer to page 9. Interlocking Mechanical interlocking At the interface of the mechanical interlocking of the circuit breaker, sensors on the switchgear side can check the switch position and prevent the associated disconnector from being operated while the circuit breaker is closed. The system also prevents the circuit breaker from being closed while the associated disconnector is in the fault position. Electrical interlocking The auxiliary and signaling contacts which show the switch position of the circuit breaker electrically can be integrated into the switchgear interlocking concept in order to prevent impermissible switching sequences. Low-voltage interface The removable cover of the SION 3AE vacuum circuit breakers enables easy access to the low-voltage interface. All customer-side control and signaling options are concentrated here. Closing and anti-pumping In the standard version, the circuit breakers can be closed electrically via remote. In addition, they can be mechanically closed locally by direct unlatching of the closing spring. If constant electrical signals for CLOSE and OPEN commands are present at the circuit breaker at the same time, the circuit breaker will carry out an OPEN-CLOSE-OPEN or a CLOSE-OPEN operating sequence. A new CLOSE command is given only following a brief interruption of the closing signal. This prevents continuous closing and opening (= pumping ) operations. Catalog HG / 07

7 Description Construction and mode of operation Ambient conditions The circuit breakers are designed for normal operating conditions as defined in IEC Condensation can occasionally occur under the ambient conditions shown opposite. C - C max. 9% per day, on average 90% per month The circuit breakers are suitable for use in the following climatic classes according to IEC 07, Part 3-3: Climatic ambient conditions: Class 3K4 ) Biological ambient conditions: Class 3B Mechanical ambient conditions: Class 3M Chemically-active substances: Class 3CS 3) Mechanically-active substances: Class 3S ) Rated operating current HG-b_en.eps HG-c_en.ai ) Lower temperature limit: C (with order code A40 down to - C) ) Restriction: Clean insulation parts 3) Without appearance of saline fog and simultaneous condensation Current carrying capacity The rated operating currents specified in the diagram have been defined according to IEC 7-00 for an ambient air temperature of + C and apply to open switchgear. For enclosed switchgear, the data of the switchgear manufacturer applies. At ambient air temperatures below +40 C, higher operating currents can be carried (see diagram): Characteristics curve = Rated operating current 30 A Characteristics curve = Rated operating current 00 A Characteristics curve 3 = Rated operating current 0 A Dielectric strength Altitude correction factor Ka Ambient temperature Installation altitude H HG-7c_en.eps The dielectric strength of air insulation decreases with increasing altitude due to lower air density. According to IEC 7-, the rated lightning impulse voltage and the rated short-time AC withstand voltage values specified in the Chapter Technical data apply for an installation altitude of up to 000 m above sea level. For altitudes above 000 m, the insulation level must be corrected according to the diagram opposite. The characteristics curve shown applies to both rated withstand voltages. When selecting the devices, the following applies: U U 0 x K a U Rated withstand voltage under reference atmosphere U 0 Rated withstand voltage requested for the installation location K a Altitude correction factor according to the opposite diagram Example For a requested rated lightning impulse voltage of 7 kv at an altitude of 00 m, an insulation level of at least 90 kv under reference atmosphere is required: 90 kv 7 kv x. Catalog HG / 07 7

8 Description Standards and maintenance-free design Standards The circuit breakers conform to the following standards: IEC 7- IEC 7-00 All circuit breakers fulfill the endurance classes C, E, M and S according to IEC For class C, all circuit breakers fulfill the following values acc. to IEC Line Cable Capacitors Back-to-back capacitor bank Rated voltage Rated line-charging breaking current Rated cable-charging breaking current Rated single-capacitorbank breaking current Rated back-to-back-capacitorbank breaking current Frequency of the inrush current U r I I I c I sb I bb f bi kv, r.m.s. A, r.m.s. A, r.m.s. A, r.m.s. A, r.m.s. Hz Maintenance-free design The circuit breakers are maintenance-free: Under normal ambient conditions according to IEC 7- Up to 0,000 operating cycles no regreasing no readjusting The ratings are independent within their tolerances of the switching frequency or standing times without switching. Catalog HG / 07

9 Description Product range overview Product range overview Rated voltage Rated short-circuit breaking current Rated operating current Pole-center distance (in mm) Width across flats (in mm) Type kv ka A AE 30 / 00 / / 00 / 0 30 / 00 / / 00 / / 00 / 0 30 / 00 / 0 Note: The circuit breaker is available with various installation accessories. These versions can be configured on the following pages. Basic equipment Equipment Minimum equipment Alternative equipment Remarks Operating mechanism Electrical operating mechanism - Also for manual operation Closing Closing solenoid and mechanical manual closing - - st release Shunt release - - nd release None Shunt release, Maximum of two releases possible undervoltage release, c.t.-operated release Varistor circuit Standard for 0 V DC - For limiting switching overvoltages Auxiliary switch NO + NC NO + NC - Plug connection 0-pole terminal strip 4-pole plug connector 4-pole plug connector NO + NC not available with 4-pole plug Anti-pumping Available - - Circuit breaker tripping signal None Possible - Operation cycles counter Available - - Mechanical interlocking None Key-operated interlocking Interlock to prevent reclosing Mechanical interlocking Insertion aid None Wheels - Cover Plastic cover Metal cover - Catalog HG / 07 9

10 Device selection Ordering information and configuration example Article number structure The circuit breakers consist of a primary and a secondary part. The primary part covers the main electrical data of the circuit breaker poles. The secondary part covers the auxiliary devices which are necessary for operating and controlling the vacuum circuit breaker. The relevant data makes up the -digit article number. Order codes Individual equipment versions, marked with 9 or Z in the 9th to th position, are explained in more detail by a 3-digit order code. Several order codes can be added to the article number in succession and in any sequence. Special versions ( ) In case of special versions, -Z is added to the article number and a descriptive order code follows. If several special versions are required, the suffix -Z is listed only once. If a requested special version is not in the catalog and can therefore not be ordered via order code, it has to be identified with Y 9 9 after consultation with us. The consultation must take place directly between your sales partner and the order processing department at Siemens. Primary part Secondary part a: letter n: digit Position: Order codes Article No.: 3 A E n n n n a a n n n a a n st position nd position 3rd position 4th position th position th position 7th position th position Superior group Switching devices Main group Circuit breaker Subgroup Circuit breaker type series Circuit breaker version Rated voltage from kv to 4 kv Pole-center distance/width across flats Rated short-circuit breaking current from ka to ka Rated operating current from 30 A to 0 A 9th to th position Secondary equipment, operating mechanism, releases, operating voltages and other auxiliary equipment Order codes Groups of 3 after the article number Format: a n a Special versions ( ) Initiated with "-Z" Groups of 3 after the article number Format: a n n 0 Catalog HG / 07

11 Device selection Selection for 3AE circuit breakers Order codes 3 A E Rated voltage for 0/0 Hz Rated lightning impulse voltage Rated short-time AC withstand voltage Rated short-circuit breaking current with 0% DC share Rated short-circuit making current (at 0/0 Hz) Pole-center distance Width across flats Terminals left/right Rated operating current see page 3 U r U p U d I sc I ma I r kv kv kv ka ka mm mm A 7 40 / R 30 3 A E 0 0 L 30 3 A E 0 40 / 4 0 R 00 3 A E 0 L 00 3 A E 40 / 4 0 R 0 3 A E 0 L 0 3 A E / 0 0 R 30 3 A E L 30 3 A E / 0 R 00 3 A E 0 3 L 00 3 A E / 0 R 0 3 A E 0 3 L 0 3 A E / 0 0 R 30 3 A E L 30 3 A E / 0 R 00 3 A E 0 4 L 00 3 A E 4 3 / 0 R 0 3 A E 0 4 L 0 3 A E / R 30 3 A E 0 L 30 3 A E 0 40 / 4 0 R 00 3 A E L 00 3 A E 40 / 4 0 R 0 3 A E L 0 3 A E / 0 0 R 30 3 A E 3 0 L 30 3 A E / 0 R 00 3 A E 3 L 00 3 A E / 0 R 0 3 A E 3 L 0 3 A E / 0 0 R 30 3 A E 4 0 L 30 3 A E / 0 R 00 3 A E 4 L 00 3 A E 4 3 / 0 R 0 3 A E 4 L 0 3 A E / R 30 3 A E 0 L 30 3 A E / 4 30 R 00 3 A E L 00 3 A E 7 40 / 4 30 R 0 3 A E L 0 3 A E / 30 0 R 30 3 A E 3 0 L 30 3 A E / 30 R 00 3 A E 3 L 00 3 A E / 30 R 0 3 A E 3 L 0 3 A E / 30 0 R 30 3 A E 4 0 L 30 3 A E / 30 R 00 3 A E 4 L 00 3 A E / 30 R 0 3 A E 4 L 0 3 A E / R 30 3 A E 3 0 L 30 3 A E 0 40 / 4 0 R 00 3 A E 3 L 00 3 A E 40 / 4 0 R 0 3 A E 3 L 0 3 A E / 0 0 R 30 3 A E L 30 3 A E / 0 R 00 3 A E 3 3 L 00 3 A E / 0 R 0 3 A E 3 3 L 0 3 A E / 0 0 R 30 3 A E L 30 3 A E / 0 R 00 3 A E 3 4 L 00 3 A E 4 3 / 0 R 0 3 A E 3 4 L 0 3 A E 4 Special versions U d = 4 kv for kv devices, GOST standard - Z E 3 Catalog HG / 07

12 Device selection Selection for 3AE circuit breakers Order codes 3 A E Rated voltage for 0/0 Hz Rated lightning impulse voltage Rated short-time AC withstand voltage Rated short-circuit breaking current with 0% DC share Rated short-circuit making current (at 0/0 Hz) Pole-center distance Width across flats Terminals left/right Rated operating current see page 3 U r U p U d I sc I ma I r kv kv kv ka ka mm mm A / R 30 3 A E 3 0 L 30 3 A E / 4 0 R 00 3 A E 3 L 00 3 A E 3 40 / 4 0 R 0 3 A E 3 L 0 3 A E / R 30 3 A E L 30 3 A E / 0 R 00 3 A E 3 3 L 00 3 A E / 0 R 0 3 A E 3 3 L 0 3 A E / R 30 3 A E L 30 3 A E / 0 R 00 3 A E 3 4 L 00 3 A E / 0 R 0 3 A E 3 4 L 0 3 A E / R 30 3 A E 3 0 L 30 3 A E / 4 30 R 00 3 A E 3 L 00 3 A E / 4 30 R 0 3 A E 3 L 0 3 A E / R 30 3 A E L 30 3 A E / 30 R 00 3 A E 3 3 L 00 3 A E / 30 R 0 3 A E 3 3 L 0 3 A E / R 30 3 A E L 30 3 A E / 30 R 00 3 A E 3 4 L 00 3 A E / 30 R 0 3 A E 3 4 L 0 3 A E / R 30 3 A E L 30 3 A E / 4 0 R 00 3 A E 3 3 L 00 3 A E 3 40 / 4 0 R 0 3 A E 3 3 L 0 3 A E / R 30 3 A E L 30 3 A E / 0 R 00 3 A E L 00 3 A E / 0 R 0 3 A E L 0 3 A E / R 30 3 A E L 30 3 A E / 0 R 00 3 A E L 00 3 A E / 0 R 0 3 A E L 0 3 A E / L 30 3 A E R 30 3 A E / R 00 3 A E 3 4 L 00 3 A E / R 0 3 A E 3 4 L 0 3 A E / R 30 3 A E L 30 3 A E / 300 R 00 3 A E L 00 3 A E / 300 R 0 3 A E L 0 3 A E Catalog HG / 07

13 Device selection Additional equipment for 3AE circuit breakers Order codes 3 A E 9th position Release combination ) Order codes 3 A E st shunt release nd shunt release Undervoltage release Current-transformer-operated release 0. A ) Current-transformer-operated release.0 A ) Current-transformer-operated release with tripping pulse 0. Ws (0 Ω) Current-transformer-operated release with tripping pulse 0. Ws (0 Ω) see page 4 see page 4 see page see page see page see page Rated voltage for 0/0 Hz Rated lightning impulse voltage Rated short-time AC withstand voltage Rated short-circuit breaking current with 0% DC share Rated short-circuit making current (at 0/0 Hz) Pole-center distance Width across flats Terminals left/right Rated operating current see page 3 U r U p U d I sc I ma I r kv kv kv ka ka mm mm A / R 30 3 A E L 30 3 A E / 300 R 00 3 A E L 00 3 A E / 300 R 0 3 A E L 0 3 A E Special versions U d = kv for 4 kv devices - Z E I A I II B I II C I II D I II G I II H I II F I = position of first release II = position of second release ) Operating voltage is selected at positions + ) Special version with A c.t.-operated release can be ordered with order code A49 - Z A 4 9 0th position Operating voltage of the closing solenoid Standard voltages None A 4 V DC B 4 V DC C 0 V DC D 0 V DC E 0 V DC F 00 V AC 0/0 Hz 3) H 0 V AC 0/0 Hz 3) J 30 V AC 0/0 Hz 3) K 30 V DC M 3 V DC N 0 V DC P V DC Q 7 V DC R 40 V DC S 0 V AC 0/0 Hz 3) U V AC 0/0 Hz 3) V 40 V AC 0/0 Hz 3) W 3) The AC frequency 0 or 0 Hz is selected at the th position of the article number together with the language (see page ) Catalog HG / 07 3

14 Device selection Additional equipment for 3AE circuit breakers th position Operating voltage of the st release Order codes 3 A E see page see page see page see page Standard voltages Standard voltages 4 V DC 4 V DC 0 V DC 3 0 V DC 4 0 V DC 00 V AC 0/0 Hz ) 0 V AC 0/0 Hz ) 7 30 V AC 0/0 Hz ) 30 V DC 9 L A 3 V DC 9 L B 0 V DC 9 L C V DC 9 L D 7 V DC 9 L E 40 V DC 9 L F 0 V AC 0/0 Hz ) 9 L K V AC 0/0 Hz ) 9 L L 40 V AC 0/0 Hz ) 9 L M th position Operating voltage of the nd release Standard voltages Standard voltages None or c.t.-operated release 0 4 V DC 4 V DC 0 V DC 3 0 V DC 4 0 V DC 00 V AC 0/0 Hz ) 0 V AC 0/0 Hz ) 7 30 V AC 0/0 Hz ) 30 V DC 9 M A 3 V DC 9 M B 0 V DC 9 M C V DC 9 M D 7 V DC 9 M E 40 V DC 9 M F 0 V AC 0/0 Hz ) 9 L K V AC 0/0 Hz ) 9 M L 40 V AC 0/0 Hz ) 9 M M ) The AC frequency 0 or 0 Hz is selected at the th position of the article number together with the language (see page ) 4 Catalog HG / 07

15 Device selection Additional equipment for 3AE circuit breakers 3th position Attachment of wheels Order codes 3 A E Transport/movement wheels No movement wheels 0 With movement wheels 4th position Operating voltage of the drive motor Order codes 3 A E Standard voltages No motor A 4 V DC B 4 V DC C 0 V DC D 0 V DC E 0 V DC F 00 V AC 0/0 Hz ) H 0 V AC 0/0 Hz ) J 30 V AC 0/0 Hz ) K 30 V DC M 3 V DC N 0 V DC P V DC Q 7 V DC R 40 V DC S 0 V AC 0/0 Hz ) U V AC 0/0 Hz ) V 40 V AC 0/0 Hz ) W ) AC voltage refers to the low-voltage equipment th position Interlocking, auxiliary switch, low-voltage interface Order codes 3 A E Mechanical interlocking Auxiliary switch NO + NC NO + NC Circuit breaker tripping signal Low-voltage interface 0-pole terminal strip 4-pole plug connector 4-pole plug connector see page B D F H K M R Q A C E G J L N P Catalog HG / 07

16 Device selection Additional equipment for 3AE circuit breakers th position Language version of the operating instructions and rating plate, as well as AC voltage frequency of the operating voltages ) Order codes 3 A E Language selection Frequency selection German English French Spanish 0 Hz DC or AC 0 Hz Special versions Portuguese, 0 Hz / DC 9 R C Portuguese, 0 Hz 9 R D Italian, 0 Hz / DC 9 R F Russian, 0 Hz / DC 9 R G Polish, 0 Hz / DC 9 R K Other languages on request ) AC voltage refers to the low-voltage equipment Additional equipment Order codes 3 A E Options Wire ends with marking at the plug connector Z A 0 Wiring cables halogen-free and flame-retardant Z A 0 Wiring cables tinned Z A Anti-condensation heating for 0 V AC, 0 W Z A 9 Anti-condensation heating for 30 V AC, 0 W Z A 3 0 Circuit breaker for operation at ambient air temperatures down to - C Z A 4 0 Without upper part of plug Z B 3 Without supplementary equipment Z B 4 Rated short-time AC withstand voltage U d = 4 kv Z E 3 Rated short-time AC withstand voltage U d = kv Z E Routine test certificate enclosed Z F 0 Hand crank (for manual charging of the closing spring) (scope of supply: one hand crank per circuit breaker) Z F 3 0 Metal cover Z J 9 Switch-off interlocking Z J Key-operated interlocking Z J 0 Other special versions not listed here (following consultation with order processing department at Berlin switchgear factory) specified additionally in plain text Z Y 9 9 Catalog HG / 07

17 Device selection Accessories and spare parts Ordering information for accessories and spare parts The article numbers in the spare part overviews are valid for currently manufactured vacuum circuit breakers. When mounting parts or spare parts are being ordered for an existing vacuum circuit breaker, always quote the type designation, serial number and the year of manufacture of the circuit breaker to be sure to get the correct parts. Retrofitting When releases/solenoids are retrofitted, the article numbers of the mounting parts must also be specified. For other additional equipment, the required mounting parts are included in the scope of supply. Spare parts may only be replaced by qualified personnel. Accessories for the plug connector Included in the scope of supply of the basic equipment for 3AE vacuum circuit breakers: For 4-pole plug connector Lower part of plug Crimp sockets according to number of contacts Upper part of plug with screwed contacts (no crimp sockets required) For 4-pole plug connector Lower part of plug Upper part of plug Crimp sockets according to number of contacts Rating plate HG-c_en.ai Rated switching sequence Class acc. to Note: The following 3 details are necessary for any query regarding spare parts, subsequent deliveries, etc.: Type designation Serial No. Year of manufacture Position: 9 Designation Description Feature Article No. Handles Hand crank for circuit breaker 3AX 30-4B Lubricants 0 g of Klüber-Isoflex Topas L3N 3AX 33-3H kg of Klüber-Isoflex Topas L3N 3AX 33-3E kg Molykote grease 3AX 33-L kg Vaseline, Atlantic 3AX 33-4A Covers Metal cover 3AX4 70-4A Plastic cover 3AX4 70-A Catalog HG / 07 7

18 Device selection Accessories and spare parts Position: 9 Designation Description Feature Article No. Closing solenoid 4 3 V DC 3AY4 0-0B 4 V DC 3AY4 0-0C 0 V DC 3AY4 0-0D 0 7 V DC 3AY4 0-0E 0 40 V DC 3AY4 0-0F 00/ V AC, 0/0 Hz 3AY4 0-0J 30/40 V AC, 0/0 Hz 3AY4 0-0K nd shunt release 4 3 V DC 3AX 0-B 4 0 V DC 3AX 0-C 0 7 V DC 3AX 0-E 0 40 V DC 3AX 0-F 00 V AC, 0 Hz 3AX 0-G V AC, 0 Hz 3AX 0-J 00 V AC, 0 Hz 3AX 0-3G V AC, 0 Hz 3AX 0-3J Mounting parts For nd shunt release 3AX4 -A Current-transformer- For rated operating current 0. A 3AX 0-A operated release For rated operating current A 3AX 0-B For tripping impulse 0. Ws, 0 Ω for 7SJ4 protection relay 3AX 04-B For rated operating current A incl. rectifier 3AX4 0-E Mounting parts For current-transformer-operated releases 3AX4 -A Undervoltage release 4 V DC 3AX 03-B 30/3 V DC 3AX 03-L 4 V DC 3AX 03-C 0 V DC 3AX 03-D 0 V DC 3AX 03-E 0/7 V DC 3AX 03-N 0 V DC 3AX 03-F 40 V DC 3AX 03-P 00 V AC, 0 Hz 3AX 03-G 0/ V AC, 0 Hz 3AX 03-H 30 V AC, 0 Hz 3AX 03-J 40 V AC, 0 Hz 3AX 03-M 00 V AC, 0 Hz 3AX 03-3G 0/ V AC, 0 Hz 3AX 03-3H 30 V AC, 0 Hz 3AX 03-3J 40 V AC, 0 Hz 3AX 03-3M Mounting parts For undervoltage releases 3AX4 3-A Drive motor 4/30/3 V DC 3AY4-0B 4/0 V DC 3AY4-0C 0 7 V DC 00 V AC 0 40 V DC 0 40 V AC 3AY4-0E 3AY4-0F Catalog HG / 07

19 Device selection Accessories and spare parts Position: 9 Designation Description Feature Article No. Electronic module 4 0 V DC 3AY4 0-B 0 40 V DC V AC 3AY4 0-E PG cable gland 3AX4-0A Anti-condensation Anti-condensation heating for 30 V AC, 0 W 3AX4 7-A heating Anti-condensation heating for 0 V AC, 0 W 3AX4 7-B Position switches Type SE4 without mounting accessories 3AX4 0-0A Used for: Quantity Electrical anti-pumping (-S3) Electrical interlocking (-S) Motor control (-S, -S) Closing spring charged (-S4) Circuit breaker tripping signal (-S) Auxiliary switches (-S) NO + NC 3SV9 73-AA0 NO + NC 3SV9 74-AA0 Accessories for Crimp pins (for conductor cross-section. mm) 4-pole 3AX 34-3A plug connection Crimp pins (for lower part of plug) 4-pole 3AX 34-4B Crimp sockets (for upper part of plug) 4-pole 3AX 34-4C Crimping pliers 3AX 34-4D Disassembly tool 3AX 34-4G Plug connector, complete 4-pole 3AX 34-7A 4-pole 3AX 34-A Catalog HG / 07 9

20 Technical data Electrical data, dimensions and masses kv 0/0 Hz Article No. Rated operating current Width across flats Pole-center distance Rated switching sequence: O 0.3 s CO s CO Rated short-circuit duration Rated short-circuit breaking current DC share in % of the rated short-circuit breaking current Asymmetric breaking current Rated short-circuit making current (at 0/0 Hz) Rated lightning impulse voltage Rated short-time AC withstand voltage Voltage drop U between the connections (acc. to IEC 7- at 00 A DC) Minimum creepage distance Interrupters Minimum creepage distance Phase-to-earth Minimum clearance Phase-to-phase Minimum clearance Phase-to-earth Mass Detailed dimension drawing (must be explicitly requested) Operating cycle diagram No. (see page ) I r t k I sc I ma U p U d A mm mm s ka % ka ka kv kv mv mm mm mm mm kg 3AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E Catalog HG / 07

21 Technical data Electrical data, dimensions and masses kv 0/0 Hz Article No. Rated operating current Width across flats Pole-center distance Rated switching sequence: O 0.3 s CO s CO Rated short-circuit duration Rated short-circuit breaking current DC share in % of the rated short-circuit breaking current Asymmetric breaking current Rated short-circuit making current (at 0/0 Hz) Rated lightning impulse voltage Rated short-time AC withstand voltage Voltage drop U between the connections (acc. to IEC 7- at 00 A DC) Minimum creepage distance Interrupters Minimum creepage distance Phase-to-earth Minimum clearance Phase-to-phase Minimum clearance Phase-to-earth Mass Detailed dimension drawing (must be explicitly requested) Operating cycle diagram No. (see page ) I r t k I sc I ma U p U d A mm mm s ka % ka ka kv kv mv mm mm mm mm kg 3AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E Catalog HG / 07

22 Technical data Electrical data, dimensions and masses kv 0/0 Hz Article No. Rated operating current Width across flats Pole-center distance Rated switching sequence: O 0.3 s CO s CO Rated short-circuit duration Rated short-circuit breaking current DC share in % of the rated short-circuit breaking current Asymmetric breaking current Rated short-circuit making current (at 0/0 Hz) Rated lightning impulse voltage Rated short-time AC withstand voltage Voltage drop U between the connections (acc. to IEC 7- at 00 A DC) Minimum creepage distance Interrupters Minimum creepage distance Phase-to-earth Minimum clearance Phase-to-phase Minimum clearance Phase-to-earth Mass Detailed dimension drawing (must be explicitly requested) Operating cycle diagram No. (see page ) I r t k I sc I ma U p U d A mm mm s ka % ka ka kv kv mv mm mm mm mm kg 3AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E Standard information on rating plate 4 kv 0/0 Hz Article No. Rated operating current Width across flats Pole-center distance Rated switching sequence: O 0.3 s CO s CO Rated short-circuit duration Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Asymmetric breaking current Rated short-circuit making current (at 0/0 Hz) Rated lightning impulse voltage Rated short-time AC withstand voltage Voltage drop U between connections (acc. to IEC 7- at 00 A DC) Minimum creepage distance Interrupters Minimum creepage distance Phase-to-earth Minimum clearance Phase-to-phase Minimum clearance Phase-to-earth Mass Detailed dimension drawing (must be explicitly requested) Operating cycle diagram No. (see page ) I r t k I sc I ma U p U d A mm mm s ka % ka ka kv kv mv mm mm mm mm kg 3AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E Catalog HG / 07

23 Technical data Electrical data, dimensions and masses 4 kv 0/0 Hz Article No. Rated operating current Width across flats Pole-center distance Rated switching sequence: O 0.3 s CO s CO Rated short-circuit duration Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Asymmetric breaking current Rated short-circuit making current (at 0/0 Hz) Rated lightning impulse voltage Rated short-time AC withstand voltage Voltage drop U between connections (acc. to IEC 7- at 00 A DC) Minimum creepage distance Interrupters Minimum creepage distance Phase-to-earth Minimum clearance Phase-to-phase Minimum clearance Phase-to-earth Mass Detailed dimension drawing (must be explicitly requested) Operating cycle diagram No. (see page ) I r t k I sc I ma U p U d A mm mm s ka % ka ka kv kv mv mm mm mm mm kg 3AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E Catalog HG / 07 3

24 Technical data Electrical data, dimensions and masses 4 kv 0/0 Hz Article No. Rated operating current Width across flats Pole-center distance Rated switching sequence: O 0.3 s CO s CO Rated short-circuit duration Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Asymmetric breaking current Rated short-circuit making current (at 0/0 Hz) Rated lightning impulse voltage Rated short-time AC withstand voltage Voltage drop U between connections (acc. to IEC 7- at 00 A DC) Minimum creepage distance Interrupters Minimum creepage distance Phase-to-earth Minimum clearance Phase-to-phase Minimum clearance Phase-to-earth Mass Detailed dimension drawing (must be explicitly requested) Operating cycle diagram No. (see page ) I r t k I sc I ma U p U d A mm mm s ka % ka ka kv kv mv mm mm mm mm kg 3AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E AE / A7E Standard information on rating plate 4 Catalog HG / 07

25 Technical data Electrical data, dimensions and masses Operating cycle diagrams for kv Operating cycle diagrams for 4 kv HG-73c_en eps HG-4b_en.eps Operating cycles Operating cycles , 0 ka 0 0 Breaking current (r.m.s. value) , 0 0 ka 0 Breaking current (r.m.s. value) The permissible number of electrical operating cycles is shown as a function of the breaking current (r.m.s. value). All SION vacuum circuit breakers fulfill the endurance classes E, M and C according to IEC The curve shape beyond the parameters defined in IEC 7-00 is based on average usage data. The number of operating cycles that can actually be reached can be different depending on the respective application. Catalog HG / 07

26 Technical data Dimension drawings 3AE for kv 370 PCD PCD SION 37, AE_Maßzeichnung_kV.ai A 9 U r [kv] I sc [ka] I r [A] PCD [mm] A [mm] Mass [kg] Dimension drawing / 0 / 30 / 00 / A7E / 0 / 30 / 00 / A7E / 0 / 30 / 00 / A7E / 0 / 30 / 00 / A7E Hinweis: Geringe Abweichungen der Maße sind zulässig / Note: Minor deviations from shown dimensions permitted 3AE3 for 4 kv 370 PCD PCD SION 43 37, 3AE_Maßzeichnung_4kV.ai A 9 U r [kv] I sc [ka] I r [A] PCD [mm] A [mm] Mass [kg] Dimension drawing 4 / 0 / 30 / 00 / A7E / 0 / 30 / 00 / A7E / 0 / 30 / 00 / A7E / 0 / 30 / 00 / A7E Hinweis: Geringe Abweichungen der Maße sind zulässig / Note: Minor deviations from shown dimensions permitted For all other details, please refer to the Catalog SION Vacuum Circuit Breakers 3AE and 3AE, HG.0 Catalog HG / 07

27 Technical data Dimension drawings SION AE_V.ai Anschlussfläche, oben Upper terminal Anschlussfläche, unten Lower terminal Leistungsschild Rating plate Anzeige "Gespannt "Charged" indicator Schaltstellungsanzeige Position indicator Schaltspielzähler Operation cycles counter Druckknopf "AUS "OPEN" pushbutton Druckknopf "EIN "CLOSE" pushbutton Öffnung für Handkurbel Opening for hand crank Allgemeine Angaben / General data: Bemessung der Stromschienen nach DIN / 7 Rating of bus bars according to DIN / 7 Catalog HG / 07 7

28 Technical data Additional technical data Operating times and internal times Operating times at rated voltage of the secondary circuit Equipment of circuit breaker Circuit breaker operating time Closing time < 0 ms Opening time st shunt release < 4 ms nd release < 4 ms Arcing time < ms Break time st shunt release < 0 ms nd release < 0 ms Dead time 300 ms CLOSE/OPEN contact time st shunt release < 7 ms nd release < 0 ms Minimum command duration Closing solenoid 4 ms st shunt release 40 ms nd release 0 ms Pulse time for circuit breaker tripping signal st shunt release > 0 ms nd release > ms Charging time for electrical operation < s Synchronism error between the poles ms Motor short-circuit protection (fuse protection of drive motors) Rated voltage of the motor Operating voltage Power consumption of the motor Smallest possible rated current ) of the miniature circuit breaker with C-characteristic V max. V min. V W/VA A 4 DC DC DC 30 0 DC DC AC AC ) The inrush current in the drive motor can be neglected due to its very short presence. Release consumption data Release Power consumption Tripping ranges DC approx. W Operation at Tripping voltage Tripping voltage or tripping current AC 0/0 Hz approx. VA at DC at AC 0/0 Hz Closing solenoid 3AY to 0 % U to 0 % U st shunt release (without stored-energy mechanism) 3AY4 0 nd shunt release (with stored-energy mechanism) 3AX to 0 % U to 0 % U to 0 % U to 0 % U Undervoltage release 3AX to 0 % U 3 to 0 % U Current-transformer-operated release 3AX4 0 0 ) 90 to 0 % I a (rated operating current 0. A, A or A) Current-transformer-operated release 3AX 04 (tripping pulse 0. Ws) ) Consumption at pickup current (90 % of the rated operating current) and open armature. Catalog HG / 07

29 Technical data Circuit diagrams Standard scheme for plug connector st shunt release nd shunt release st transformer-currentoperated release st transformer-currentoperated release A Undervoltage release -Q0 -X. 4 -Q0 -X0 C3 -Q0 -X.. 4 -Q0 -X.. 3 -Q0 -X. -Q0 -X0 D3 -Q0 -X. -Q0 -X. -Q0 -X. 7 -X. -Q0 -S 33 -Q0 -S A -Q0 -Y7 A ) U -Q0 -S3 3 4 A -Q0 -Y A ) U A -Q0 -Y A ) U -Q0 -Y4 A A -Q0 -Y A A -Q0 -X.. 4 -Q0 -X.. 3 -Q0 -X. 3 -Q0 -X. -Q0 -X. -Q0 -X. -Q0 -X. HG- eps S_A7E_449_400_00 S_A7E_449_400_00 S_A7E_449_400_00 S_A7E_449_40_00 S_A7E_449_404_00 S_A7E_449_403_00 S_A7E_449_40_00 Part of basic wiring S_A7E_449_4099_00 Part of basic wiring S_A7E_449_4099_00 Contact assignment for auxiliary switch Hilfsschalter S/Ö Auxiliary switch NO/NC -Q0 -X0 C7 A C C A0 C0 A C A C A3 Aus / Off Ein / On Aus / Off Ein / On Aus / Off Ein / On Aus / Off Ein / On Aus / Off Ein / On Aus / Off Ein / On (-Y9) (-Y) (-Y) (-Y7) Q -S ) ) ) ) ) ) ) ) ) ) ) ) HG-0 eps Q0 -S ) ) ) ) 3) 4) ) ) ) ) ) S_A7E_449_40_40 -Q0 -X0 D7 B D D9 B9 C9 B0 D0 B D B D B3 HG-7 eps S_A7E_449_403_00 Legend see page 3 Catalog HG / 07 9

30 Technical data Circuit diagrams Additional equipment Closing and anti-pumping -Q0 -X. 7 Closing and anti-pumping -Q0 -X.. Closing and anti-pumping 4 V - 3 V 00 V - 7 V -Q0 -X. 3 Closing and anti-pumping 4 V - 0 V 0 V - 40 V -Q0 -X. 4 Closing and anti-pumping 4 V - 3 V 00 V - 7 V -Q0 -X. 3 Closing and anti-pumping 4 V - 0 V 0 V - 40 V -Q0 -X. 4 Closing and anti-pumping -Q0 -X. -Q0 -X.. Motor charging -Q0 -S3 -Q0 -S3 -Q0 -S3 3 A -Q0 -Y9 A -Q0 -S 4 3 ) U -Q0 -M A M = D ) U 4 -Q0 -X. -Q0 -X. -Q0 -X.. 7 -Q0 -X.. 7 -Q0 -X.. 9 -Q0 -X.. 9 -Q0 -X.. 7 -Q0 -X.. 9 HG- eps -Q0 -X.. HG- eps S_A7E_449_40_00 S_A7E_449_40_00 Additional equipment: Releases Motor charging Signal: Spring charged Circuit breaker tripping signal Anti-condensation heating S_A7E_449_40_003 S_A7E_449_40_004 S_A7E_449_40_00 S_A7E_449_40_00 S_A7E_449_40_00 Part of basic wiring S_A7E_449_4099_00 S_A7E_449_400_00 Part of basic wiring S_A7E_449_4099_00 -Q0 -X. -Q0 -X.. -Q0 -X. -Q0 -X. 0 -Q0 -X. -Q0 -X. -Q0 -X.. -Q0 -X. -Q0 -S -Q0 -S Q0 -S -R0 -Q0 -X.. -Q0 -X. HG-0 eps -Q0 -X. 9-Q0 -X. 0 -Q0 -X.. -Q0 -X.. -Q0 -X.. -Q0 -X. 9 HG- eps S_A7E_449_400_00 S_A7E_449_404_00 S_A7E_449_4043_00 S_A7E_449_4043_00 Part of basic wiring S_A7E_449_4099_00 S_A7E_449_400_00 Order code A30 Legend see page 3 30 Catalog HG / 07

31 Technical data Circuit diagrams Additional equipment: Releases Closing and anti-pumping Closing and anti-pumping -Q0 -K -Q0 -X0 -Q0 -X. -Q0 -X. A (-M) D (-M) 3 3 D (-Y) 4 4 C (-Y) 7 7 C (-S4) 9 9 B (-S4) 0 0 D (-S4) -Q0 -X. -Q0 -X.4 A7 (-S) B7 (-S) 3 (00-7 V) 3 (00-7 V) 4 (0-40 V) 4 (0-40 V) B (-Y9) A (-Y9) 7 7 (-R0) 9 9 (-R0 ) 0 0 HG-3 eps -Q0 -K -Q0 -X X Q0 -X. -Q0 -X.4 3 (4-3 V) 4 (4-0 V) HG-4 eps 3 (4-3 V) 4 (4-0 V) 7 9 -Q0 -X0 A D D C C B D A7 B7 B A (-R0) (-R0 ) (-M) (-M) (-Y) (-Y) (-S4) (-S4) (-S4) (-S) (-S) (-Y9) (-Y9) S_A7E_449_40_0 S_A7E_449_40_03 Legend (for pages 9 to 3) K Contactor (anti-pumping) M Motor operating mechanism Q0 Circuit breaker wiring Q Wiring of withdrawable part R Resistance S Auxiliary switch S3 Position switch (anti-pumping) S4 Position switch (for closing spring charged) S Electrical closing lock-out S Circuit breaker tripping signal S Mechanical interlocking S Position switches S (to deenergize the motor operating mechanism after charging) X0 Plug connector, 4 or 4-pole X Terminal strip, 7-pole Y st shunt release Y nd shunt release Y4 Current-transformer-operated release (rated operating current 0. A or A) Y Current-transformeroperated release (tripping pulse W 0. Ws) Y7 Undervoltage release Y9 Closing solenoid Abbreviations: NC = Normally closed NO = Normally open The circuit diagrams shown here are only examples from the many possible circuit breaker wiring options. Catalog HG / 07 3

32 Siemens AG Energy Management Low Voltage & Products Postfach Regensburg Germany If you would like to obtain more information, please contact our Customer Support Center. Tel.: Fax: support.energy@siemens.com Subject to change without prior notice Article No.: E00-K0-A0-A-700 Dispo 30 KG 037. WÜ En Printed in Germany Siemens AG 07 Errors excepted and subject to change without prior notice. The information provided in this document contains merely general descriptions or characteristics of performance which in case of actual use do not always apply as described or which may change as a result of further development of the products. An obligation to provide the respective characteristics shall exist only if expressly agreed in the terms of contract. 07

5SJ4...-.HG Circuit Breakers to IEC and UL 489

5SJ4...-.HG Circuit Breakers to IEC and UL 489 Siemens AG 009 5SJ...-.HG Circuit Breakers to IEC and UL 89 BETA Low-Voltage Circuit Protection Compliance with industry standards is a must in today's manufacturing environment. Worldwide acceptance is

More information

5SP and 5SY Supplementary Protection UL 1077

5SP and 5SY Supplementary Protection UL 1077 Product Guide 5SP and 5SY Supplementary Protection UL 077 for North merican and International applications usa.siemens.com/5sy Table of contents Certifications, standards, features and description Characteristic

More information

Instruction. Vacuum Circuit Breaker Operator Module. Type 3AH 4.16kV to 38kV. Power Transmission & Distribution

Instruction. Vacuum Circuit Breaker Operator Module. Type 3AH 4.16kV to 38kV. Power Transmission & Distribution Instruction 0001-22-2--00 Vacuum Circuit Breaker Operator Module Type 3AH 4.16kV to 38kV Power Transmission & Distribution Hazardous voltages and high-speed moving parts. Will cause death, serious injury

More information

Issued August DATA SHEET. 3VT5 MCCB up to 1600 A

Issued August DATA SHEET. 3VT5 MCCB up to 1600 A ssued August 9 DATA SHEET VT5 MCCB up to 0 A Based on Siemens Catalog V 8 Standard circuit breakers Releases Technical specifications Specifications VT5 circuit breakers Switch disconnectors Type Standards

More information

Issued August DATA SHEET. 3VT3 MCCB up to 630 A

Issued August DATA SHEET. 3VT3 MCCB up to 630 A ssued August 9 DATA SHEET VT MCCB up to 6 A Based on Siemens Catalog V 6 8 Circuit breakers Switch disconnectors Technical specifications Specifications Type VT 76-AA6/6/56-AA, VT 76-AA6/6/56-AA Circuit

More information

TeSys circuit-breakers

TeSys circuit-breakers Presentation Thermal-magnetic motor circuit-breakers types GV2, GV and GV7 GV2-ME, GV2-P, GV-ME and GV7-R motor circuit-breakers are -pole thermal-magnetic circuit-breakers specifically designed for the

More information

3VT4 Molded Case Circuit Breakers up to 1000 A

3VT4 Molded Case Circuit Breakers up to 1000 A VT4 Molded Case Circuit Breakers up to 00 A Catalog Technical nformation VT4 Molded Case Circuit Breakers up to 00 A General data / - Overview Circuit breakers Switch disconnectors / - Selection and ordering

More information

Varius SUMMARY OF MODELS OF HRC FUSE-LINKS

Varius SUMMARY OF MODELS OF HRC FUSE-LINKS SUMMARY OF MODELS OF HRC FUSE-LINKS Type PNA000 PHNA000 PNA00 PHNA00 Rated current I n up to A up to 0 A up to A up to 0 A Rated voltage U n AC 00 V, 00 V 90 V 00 V 90 V DC 0 V 0 V 0 V 0 V Fuse-link size

More information

Overload Relays. SIRIUS 3RU1 Thermal Overload Relays. 3RU11 for standard applications. 5/46 Siemens LV 1 AO 2011

Overload Relays. SIRIUS 3RU1 Thermal Overload Relays. 3RU11 for standard applications. 5/46 Siemens LV 1 AO 2011 SIRIUS 3RU1 Thermal Overview 1 2 7 3 4 6 "Increased safety" type of EEx e according to ATEX directive 94/9/EC The 3RU11 thermal overload relays are suitable for the overload of explosion-proof motors with

More information

FAZ tripping characteristics at 30 C: B, C, D to IEC/EN FAZ tripping characteristics at 30 C: R to IEC/EN

FAZ tripping characteristics at 30 C: B, C, D to IEC/EN FAZ tripping characteristics at 30 C: R to IEC/EN FAZ, AZ High-Capacity Tripping Characteristics Moeller HPL011-001/00 1/07 FAZ tripping characteristics at 0 C: B, C, D to IEC/EN 0 9 FAZ tripping characteristics at 0 C: R to IEC/EN 0 97 t [s] 700 00 100

More information

BETA Protecting Miniature Circuit Breakers

BETA Protecting Miniature Circuit Breakers Siemens AG 00 / Product overview / High-capacity range 000 A 0000 A 0000 A, high current 0000 A, universal current 000 A ka /0 Comfort range with plug-in terminal / Compact range +N in MW / Additional

More information

Impedance relay and protection assemblies

Impedance relay and protection assemblies RXZK 21H, 22H, 23H 509 006-BEN Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970175) (SE970184) Features Micro-processor based impedance relay with R and X settings

More information

08/072 PKZ2 Motor-Protective Circuit-Breakers Tripping Characteristics

08/072 PKZ2 Motor-Protective Circuit-Breakers Tripping Characteristics 0/07 PKZ Tripping Characteristics Moeller HPL0-00/00 S-PKZ high-capacity contact module, SEA-PKZ contact module Normal switching duty AC-/00V kw A Rated output of three-phase motors 0...0 Hz. 7..... 0.7

More information

BETA Protecting. Low-Voltage Fuse Systems. LV HRC fuse links. 3/36 Siemens ET B1 2008

BETA Protecting. Low-Voltage Fuse Systems. LV HRC fuse links. 3/36 Siemens ET B1 2008 LV HRC fuse links Overview LV HRC fuses are used for installation systems in non-residential, commercial and industrial buildings as well as in switchboards of power supply companies. They therefore protect

More information

Siemens AG Miniature Circuit Breakers. Totally Integrated Power SENTRON. Configuration. Edition 10/2014. Manual. siemens.

Siemens AG Miniature Circuit Breakers. Totally Integrated Power SENTRON. Configuration. Edition 10/2014. Manual. siemens. Siemens AG 05 Totally Integrated Power SENTRON Configuration Manual Edition 0/0 siemens.com/lowvoltage Siemens AG 05 Siemens AG 05 Introduction 5SL miniature circuit breakers 5SY and 5SP miniature circuit

More information

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager. Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager. 1 -A - Introduction - Thank for your purchasing MITSUBISHI ELECTRIC MELPRO TM D Series Digital Protection

More information

UL 1077 DIN Rail Supplementary Protectors

UL 1077 DIN Rail Supplementary Protectors UL 0 DIN Rail Supplementary Protectors Product Overview UL 0 DIN Rail Supplementary Protectors PRODUCT OVERVIEW Product Overview Standard Features WMZS breaker terminals provide finger and back-of-hand

More information

Thermal-Magnetic Circuit Breaker 2210-S2..

Thermal-Magnetic Circuit Breaker 2210-S2.. Thermal-Magnetic Circuit Breaker -S.. Description One, two and three pole thermal-magnetic circuit breakers with trip-free mechanism and toggle actuation (S-type TM CBE to EN 60934/IEC 934). Designed for

More information

Thermal-Magnetic Circuit Breaker 2210-S2..

Thermal-Magnetic Circuit Breaker 2210-S2.. Thermal-Magnetic Circuit Breaker -S.. Description One, two and three pole thermal-magnetic circuit breakers with trip free mechanism and toggle actuation (S-type TM CBE to EN 60934/IEC 934). Designed for

More information

THE DIMENSIONING OF ELECTRICAL CONDUCTORS FOR USE IN "PANEL BOARDS" ADDRESSED TO HAZARDOUS AREAS - PART THREE

THE DIMENSIONING OF ELECTRICAL CONDUCTORS FOR USE IN PANEL BOARDS ADDRESSED TO HAZARDOUS AREAS - PART THREE July 04 THE DIMENSIONING OF ELECTRICAL CONDUCTORS FOR USE IN "PANEL BOARDS" ADDRESSED TO HAZARDOUS AREAS - PART THREE In this third part. we want to speak about how important is the correct sizing of the

More information

Sealing possibility Electrical endurance (ops) Mechanical endurance (ops) Overvoltage category Standards

Sealing possibility Electrical endurance (ops) Mechanical endurance (ops) Overvoltage category Standards Miniature circuit breaker ETIMAT 7,7 0.5 Rated voltage Rated current Rated frequency Rated short-circuit capacity Energy limiting class characteristic Build-in width Mounting on the rail 0/00 V AC, max.

More information

Thermal-Magnetic Circuit Breaker 2210-S2..

Thermal-Magnetic Circuit Breaker 2210-S2.. Thermal-Magnetic Circuit Breaker -S.. Description One, two and three pole thermal-magnetic circuit breakers with trip free mechanism and toggle actuation (S-type TM CBE to EN 6094/IEC 94). Designed for

More information

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-T...

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-T... Magnetic and Hydraulic-Magnetic Circuit Breaker 830-T... Description ngle, two and three pole magnetic and hydraulic-magnetic circuit breakers with trip-free mechanism and toggle actuation. A choice of

More information

TeSys enclosed starters 2

TeSys enclosed starters 2 Characteristics, references TeSys enclosed starters D..L. starters for motor control 0. to. kw with -phase thermal overload relay with protected phases Characteristics () Conforming to standards IEC 0--,

More information

Thermal-Magnetic Circuit Breaker 2210-S2...

Thermal-Magnetic Circuit Breaker 2210-S2... Thermal-Magnetic Circuit Breaker 0-S... Description One, two and three pole thermal-magnetic circuit breakers with trip free mechanism and toggle actuation (S-type TM CBE to EN 60934/IEC 934). Designed

More information

Thermal-Magnetic Circuit Breaker 2210-S2...

Thermal-Magnetic Circuit Breaker 2210-S2... Description One, two and three pole thermal-magnetic circuit breakers with trip free mechanism and toggle actuation (S-type TM CBE to EN 6094/IEC 94). Designed for panel or plug-in mounting. Available

More information

Thermal-Magnetic Circuit Breaker 2210-T2...

Thermal-Magnetic Circuit Breaker 2210-T2... Thermal-Magnetic Circuit Breaker 0-T... Description One, two and three pole thermal-magnetic circuit breakers with trip-free mechanism and toggle actuation (S-type TM CBE to EN 6094/IEC 94). Featuring

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current Transducer HO-NP series I P N = 4, 6, 12, 15 A Ref: HO 4-NP, HO 6-NP, HO 12-NP, HO 15-NP For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary

More information

PHOENIX CONTACT - 04/2016. Features

PHOENIX CONTACT - 04/2016. Features Signal conditioner Data sheet 100238_de_06 1 Description PHOENIX CONTACT - 04/2016 Features The MCR-C-UI-UI(-450)-DCI(-NC) 3-way isolation amplifier is used to electrically isolate and convert analog signals.

More information

Non-Contact Safety Systems CMS

Non-Contact Safety Systems CMS Selection table for non-contact safety system // Evaluation units Connection Desi Read head contact assembly Assured switch-on distance S ao [mm] Assured switch-on distance S ar [mm] Number of outputs

More information

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager. Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager. 1 -C - Safety section - This Safety section should be read before starting any work on the relay.

More information

Digital Current Transducer HO-SW series I P N = A. Ref: HO 100-SW; HO 150-SW; HO 200-SW; HO 250-SW

Digital Current Transducer HO-SW series I P N = A. Ref: HO 100-SW; HO 150-SW; HO 200-SW; HO 250-SW Digital Current Transducer HO-SW series I P N = 100... 250 A Ref: HO 100-SW; HO 150-SW; HO 200-SW; HO 250-SW Bitstream output from on onboard Sigma Delta modulator. For the electronic measurement of current:

More information

ATyS Automatic and remotely operated transfer switches from 125 to 3200 A

ATyS Automatic and remotely operated transfer switches from 125 to 3200 A atys-p_001_b atys_d_001_a_1_cat ATyS p I-0-II 4P ATyS d I-0-II 4P Function The ATyS are three-phase motorised transfer switches with positive break indication. They enable the on load transfer of two three-phase

More information

C60N circuit breakers0 B, C and D curves IEC 60898: 6000 A, IEC : 10 ka

C60N circuit breakers0 B, C and D curves IEC 60898: 6000 A, IEC : 10 ka C0N circuit breakers0 B, C and s IEC 0898: 000 A, IEC 097-: 0 ka Function b The circuit-breakers combine the following functions: v protection of circuits against short-circuit currents v protection of

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current Transducer LDSR 0.3-TP/SP1 I P R N = 300 ma For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Features Closed

More information

General characteristics, Products

General characteristics, Products The Feature Packed line of Manual Motor Protectors Eaton s new XT family of Manual Motor Protectors (MMPs) features a pushbutton or rotary ON/OFF manual disconnect, Class adjustable bimetallic overload

More information

MCB NB1-63H Miniature Circuit Breaker

MCB NB1-63H Miniature Circuit Breaker NB-H Miniature Circuit Breaker. General. Function protection of circuits against short-circuit currents, protection of circuits against overload currents, switch, isolation, NB-H circuit-breakers are used

More information

Amphenol C 091 A/B/D. Circular Connectors. Amphenol-Tuchel Electronics GmbH

Amphenol C 091 A/B/D. Circular Connectors. Amphenol-Tuchel Electronics GmbH Amphenol C 091 A/B/D Circular Connectors Amphenol-Tuchel Electronics GmbH General information These connectors are designed and produced in conformity with the low-voltage directive (/3/EWG) respectively

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current Transducer HO-NP/SP33 series I PN = 8, 15, 25 A Ref: HO 8-NP/SP33, HO 15-NP/SP33, HO 25-NP/SP33 For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the

More information

MKV AC Capacitors Damping B High dielectric strength High peak-current capability Especially suitable for snubber circuits

MKV AC Capacitors Damping B High dielectric strength High peak-current capability Especially suitable for snubber circuits MKV AC Capacitors B 25 835 High dielectric strength High peak-current capability Especially suitable for snubber circuits Construction Self-healing Plastic dielectric Oil-impregnated tubular windings (no

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current Transducer HO-NSM series I PN = 8, 15, 25 A Ref: HO 8-NSM, HO 15-NSM, HO 25-NSM For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the

More information

90 MCB MODULAR CIRCUIT BREAKERS FOR CIRCUIT PROTECTION

90 MCB MODULAR CIRCUIT BREAKERS FOR CIRCUIT PROTECTION MCB - MTC - MT - MTHP Technical data TYPE MTC MT MTC45 MTC60 MTC100 MT 45 MT 60 Rated current (In) (A) 2-32 6-32 6-32 6-40 1-63 Utilization category A A A A A Rated operational voltage (Ue) (V) 230/400-240/415

More information

90 MCB range Modular circuit breakers for circuit protection

90 MCB range Modular circuit breakers for circuit protection MCB - MTC - MT - MTHP Technical data TYPE MTC MT MTC45 MTC60 MTC100 MT 45 MT 60 Rated current (In) (A) 2-32 6-32 6-32 6-40 1-63 Utilization category A A A A A Rated operational voltage (Ue) (V) 230 / 400

More information

Varius SUMMARY OF MODELS OF HRC FUSE-LINKS. Type PVA10 / PV10 PV14 PV22 Rated current I n up to 32 A up to 63 A up to 125 A Rated voltage U n

Varius SUMMARY OF MODELS OF HRC FUSE-LINKS. Type PVA10 / PV10 PV14 PV22 Rated current I n up to 32 A up to 63 A up to 125 A Rated voltage U n Varius SUMMARY OF MODELS OF HRC FUSE-LINKS Type A / Rated current I n up to A up to up to A Rated voltage U n AC V, V V, V, 9 V V, V, 9 V DC V V V Fuse-link size x8 x x8 Utilization category of the fuse-link

More information

BASE. Rotary limit switch. OptiOnS. FEAtuRES. CERtiFiCAtiOnS

BASE. Rotary limit switch. OptiOnS. FEAtuRES. CERtiFiCAtiOnS Rotary limit switch BASE Rotary limit switch used to control and measure the movement of industrial machines. Its compact size make it suitable for use in narrow spaces. FEAtuRES It consists of a gear

More information

Ref: HLSR 16-PW; HLSR 32-PW; HLSR 40-PW-000; HLSR 50-PW-000,

Ref: HLSR 16-PW; HLSR 32-PW; HLSR 40-PW-000; HLSR 50-PW-000, Digital Current Transducer HLSR-PW series I P N = 16... 50 A Ref: HLSR 16-PW; HLSR 32-PW; HLSR 40-PW-000; HLSR 50-PW-000, Bitstream output from on onboard Sigma Delta modulator. For the electronic measurement

More information

Amphenol. Amphenol-Tuchel Electronics GmbH. Circular Connectors C 091 A/B/D Series

Amphenol. Amphenol-Tuchel Electronics GmbH. Circular Connectors C 091 A/B/D Series Amphenol Amphenol-Tuchel Electronics GmbH Circular Connectors C 09 A/B/D Series The Company Amphenol-Tuchel Electronics GmbH is a member of the USA based Amphenol Corporation. With our own global presence

More information

To order, specify : Types Protection functions Current surge Asymmetry and loss of phase. Operating principle

To order, specify : Types Protection functions Current surge Asymmetry and loss of phase. Operating principle otor protection relays - T - FWIT Since % of -phase motor failures are due to load problems or loss of phase, the CROUZET range of motor protection relays is indispensable! models give motor protection

More information

ISM_LD Series. Vacuum Circuit Breakers 15kV,...20kA, A 27kV,...16kA,...800A. With CM_1501 and CM_16 Series Control Modules

ISM_LD Series. Vacuum Circuit Breakers 15kV,...20kA, A 27kV,...16kA,...800A. With CM_1501 and CM_16 Series Control Modules ISM_LD Series Vacuum Circuit Breakers 15kV,...20kA,...1000A 27kV,...16kA,...800A 5 With CM_1501 and CM_16 Series Control Modules 165 ± 0,5 50 ± 0,2 100 112 0 45 10 279 474 Application Guide MAN5002252

More information

O Plus Dry Bushing 69 kv system, 350 kv BIL, 3000 A. Table of contents

O Plus Dry Bushing 69 kv system, 350 kv BIL, 3000 A. Table of contents Type test report O Plus Dry Bushing 69 kv system, 0 kv BIL, 000 A Table of contents Abstract... 2 2 Certification... 2 Introduction.... Description and ratings....2 Overview of tests.... Applicable standards....4

More information

Operating Instructions for Digital Manometer. Model: MAN-SD

Operating Instructions for Digital Manometer. Model: MAN-SD Operating Instructions for Digital Manometer Model: MAN-SD 1. Contents 1. Contents...2 2. Note...3 3. Instrument Inspection...3 4. Regulation Use...4 5. Operating Principle...4 6. Mechanical Connection...5

More information

XD1-L Cable Differential Protection Relay

XD1-L Cable Differential Protection Relay XD1-L Cable Differential Protection Relay Manual XD1-L (Revision B) Woodward Manual XD1-L GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information

More information

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM Unit Objectives Describe the structure of an atom. Identify atoms with a positive charge and atoms with a negative charge. Explain

More information

ISEmax CAM40/CAS40. Technical Information

ISEmax CAM40/CAS40. Technical Information Technical Information Online measurement of nutrient parameters Ion-selective electrode system for the continuous measurement of ammonium and nitrate Application The ion-selective electrode system works

More information

VCB. Vacuum Circuit Breaker 17.5kV, kA, A 24kV,...16kA,...800A. User Guide

VCB. Vacuum Circuit Breaker 17.5kV, kA, A 24kV,...16kA,...800A. User Guide VCB Vacuum Circuit Breaker 7.5kV,...3.5kA,...2000A 24kV,...6kA,...800A User Guide Contents. Product description... 4. Abbreviations... 5.2 Definitions... 5.3 Main technical parameters... 6.4 Disclaimers...

More information

ISOCON-6. 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER

ISOCON-6. 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER ISOCON-6 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER Whilst every effort has been taken to ensure the accuracy of this document, we accept no responsibility for damage, injury, loss or expense resulting

More information

VK2 volume flow controller Overview

VK2 volume flow controller Overview New option with sound attenuator Maintenance-free VK2 volume flow controller that operates without an auxiliary power supply, for ventilation and air conditioning systems. Adjustable on site. Outstanding

More information

Turbine Meter TRZ 03 PRODUCT INFORMATION. Reliable Measurement of Gas

Turbine Meter TRZ 03 PRODUCT INFORMATION. Reliable Measurement of Gas Turbine Meter TRZ 0 PRODUCT INFORMATION Reliable Measurement of Gas TURBINE METER TRZ 0 Method of operation, Construction Method of operation The TRZ 0 turbine meter is a flow meter suitable for gas measurement

More information

Electric amplifiers. RE 30044/02.12 Replaces: Type VT-VRPA X/V0/RTS-2STV. Component series 2X 1/8

Electric amplifiers. RE 30044/02.12 Replaces: Type VT-VRPA X/V0/RTS-2STV. Component series 2X 1/8 Electric amplifiers RE 30044/02.12 Replaces: 11.02 1/8 Type VT-VRPA1-527-2X/V0/RTS-2STV Component series 2X Table of contents Contents Page Features 1 Ordering code, accessories 2 Front plate 2 Block diagram

More information

Lamp and Control Panel (Lamp Panel)

Lamp and Control Panel (Lamp Panel) www.reinhausen.com Lamp and Control Panel (Lamp Panel) Operating Instructions BA 47/0 EN NOTE! Changes may have been made to a product after going to press with this documentation. We expressly reserve

More information

Pushbutton Units and Indicator Lights

Pushbutton Units and Indicator Lights Insert labels and insert caps Clear, illuminated and indicator lights can be fitted with insert labels and caps for identification purposes. These labels and caps are made of a semi-transparent molded

More information

MOULDED CASE CIRCUIT BREAKERS BL1000S

MOULDED CASE CIRCUIT BREAKERS BL1000S G MOUDED CASE CRCUT BREAKERS BS G BS COMMERCA NFORMATON P Switching units, withdrawable device, plug-in device...g Overcurrent releases...g Signalling units...g Connecting sets...h Switches...H Shunt trips...h

More information

SPECIFICATION SS 51/9 400KV COUPLING CAPACITORS FOR POWER LINE CARRIER SYSTEM

SPECIFICATION SS 51/9 400KV COUPLING CAPACITORS FOR POWER LINE CARRIER SYSTEM INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION January 2017 SPECIFICATION SS 51/9 400KV COUPLING CAPACITORS FOR POWER LINE CARRIER SYSTEM I. SCOPE This

More information

Modular contactors for installation into distribution

Modular contactors for installation into distribution Modular contactors for installation into distribution boards Modular contactors for installation into distribution boards Modular contactor for installation into distribution board Description Modular

More information

ISOCON-3 MAINS POWERED ISOLATING SIGNAL CONVERTER

ISOCON-3 MAINS POWERED ISOLATING SIGNAL CONVERTER ISOCON-3 MAINS POWERED ISOLATING SIGNAL CONVERTER CAUTION: This equipment is designed for connection to mains voltages and must be used in accordance with this guide. If it is not, the safety protection

More information

EX-CONTROL AND DISTRIBUTION SYSTEMS

EX-CONTROL AND DISTRIBUTION SYSTEMS EX-CONTROL AND DISTRIBUTION SYSTEMS Cooper Crouse-Hinds 00 - all rights reserved EX-DISTRIBUTION IN PLASTIC DESIGN. EX-DISTRIBUTION IN STAINLESS STEEL EX-D BUILT-IN COMPONENTS.. 9 EX-E EMPTY ENCLOSURES

More information

LD-LP-LL-LC Rope Safety Switches with reset for emergency stop

LD-LP-LL-LC Rope Safety Switches with reset for emergency stop TECHNICA DATASHEET D-P--C Rope Safety Switches with reset for emergency stop Metal or polymer housing, from one or three conduit entries Protection degree IP6 In conformity with EN ISO 13850 contact blocks

More information

GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN Mitglied der Short-Circuit-Testing Liaison (STL) Test Report

GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN Mitglied der Short-Circuit-Testing Liaison (STL) Test Report Mitglied der Short-Circuit-Testing Liaison (STL) Test Report Report-No.: 9725Fr Copy-No.: 00 Contents: 16Sheets Equipment under Test: Manufacturer: Client: Metal-enclosed, single-pole metal-clad and SF

More information

8 Installation Equipment

8 Installation Equipment 8 Installation Equipment Plugs and Sockets CES System Series 8, 88, 8, 881 Te plugs and sockets in te CES system comply wit CEE publication 1 and European standards EN 0 01. Te small 1 A socket as switcing

More information

Rotary modules.

Rotary modules. Rotary modules www.comoso.com www.comoso.com Rotary modules ROTARY MODULES Series Size Page Rotary modules RM swivel unit 156 RM 08 160 RM 10 162 RM 12 164 RM 15 168 RM 21 172 RM rotor 176 RM 50 180 RM

More information

EXEMPLAR NATIONAL CERTIFICATE (VOCATIONAL) ELECTRICAL PRINCIPLES AND PRACTICE NQF LEVEL 3 ( ) (X-Paper) 09:00 12:00

EXEMPLAR NATIONAL CERTIFICATE (VOCATIONAL) ELECTRICAL PRINCIPLES AND PRACTICE NQF LEVEL 3 ( ) (X-Paper) 09:00 12:00 NATIONAL CERTIFICATE (VOCATIONAL) ELECTRICAL PRINCIPLES AND PRACTICE NQF LEVEL 3 2008 (12041002) (X-Paper) 09:00 12:00 EXEMPLAR This question paper consists of 7 pages. EXEMPLAR -2- NC(V) TIME: 3 HOURS

More information

Table of Contents Pin-Configuration Selection Guide for HDE, HDS, & EFP

Table of Contents Pin-Configuration Selection Guide for HDE, HDS, & EFP Table of Contents -Configuration Selection Guide for HDE, HDS, & EFP Service Voltage Rating... Electrical Service Ratings... Ampacity Ratings by Contact... Electrical Service Ratings Explained... Operating

More information

SWITCHGEAR: design concepts, testing, standards and safety of persons and installations

SWITCHGEAR: design concepts, testing, standards and safety of persons and installations MEDIUM AND LOW VOLTAGE Part 1 SWITCHGEAR: design concepts, testing, standards and safety of persons and installations Presented by: Sergio Feitoza Costa COGNITOR Consultancy, R&D & training Ltd www.cognitor.com.br

More information

Number of poles 1-pole 2-pole Minimum Enclosure Contact G2R-1A-E G2R-1-E

Number of poles 1-pole 2-pole Minimum Enclosure Contact G2R-1A-E G2R-1-E The Best Seller eneral purpose power elays of single-pole0 A and double-pole A. Safety-oriented design with dielectric strength of,000 V between coil and contacts, and surge resistance of 0,000 V. and

More information

Acceleration/Velocity/Displacement VIBRATION METER

Acceleration/Velocity/Displacement VIBRATION METER Acceleration/Velocity/Displacement VIBRATION METER Model : VB-8220 Your purchase of this VIBRATION METER marks a step forward for you into the field of precision measurement. Although this METER is a complex

More information

Sales: Malux Finland Oy, P.O.Box 69, FI Porvoo, Phone , Fax ,

Sales: Malux Finland Oy, P.O.Box 69, FI Porvoo, Phone , Fax , E X - L I G H T F I T T I N G S nllk 0... 1 - W All-plastic design for Zone 2 and Zone 21/22 The explosion-protected light fittings of the series nllk 0 conform to the requirements of the ATEX-Directive

More information

INSTRUCTION MANUAL FOR MM10 Relay

INSTRUCTION MANUAL FOR MM10 Relay INSTRUCTION MANUAL FOR MM10 Relay Motor Protection Relay Front Panel Overview V1 250614 MM10 Motor Protection Relay a I L1 b I L2 I L3 c h i d e I L1 Figure 1: Front panel overview f g I L2 a Run LED b

More information

Model M3484 Industrial Line Noise Filter Module Customer Reference Manual

Model M3484 Industrial Line Noise Filter Module Customer Reference Manual Model M3484 Industrial Line Noise Filter Module Customer Reference Manual Web: www.bonitron.com Tel: 615-244-2825 Email: info@bonitron.com Bonitron, Inc. Bonitron, Inc. Nashville, TN An industry leader

More information

T20WN. Data Sheet. Torque transducers. Special features. Installation example with bellows couplings. B en

T20WN. Data Sheet. Torque transducers. Special features. Installation example with bellows couplings. B en T20WN Torque transducers Data Sheet Special features - Nominal (rated) torques 0.1 N m, 0.2 N m, 0. N m, 1 N m, 2 N m, N m, 10 N m, 20 N m, 0 N m, 100 N m, 200 N m - Accuracy class: 0.2 - Contactless transmission

More information

Power Resistor for Mounting onto a Heatsink Thick Film Technology

Power Resistor for Mounting onto a Heatsink Thick Film Technology DIMENSIONS in millimeters Power Resistor for Mounting onto a Heatsink Thick Film Technology FEATURES 300 W at 85 C bottom case temperature Wide resistance range: 0.3 Ω to 900 kω E24 series Non inductive

More information

TEST CERTIFICATES OR REPORTS ISSUED BY VEIKI-VNL LTD.

TEST CERTIFICATES OR REPORTS ISSUED BY VEIKI-VNL LTD. Page 2 of 29 TEST CERTIFICATES OR REPORTS ISSUED BY LTD. Type Test Certificate of Complete Type Test This certificate provides the verification of all the rated characteristics of the equipment as assigned

More information

SVH with HYDROVAR (HVL range)

SVH with HYDROVAR (HVL range) SVH with HYDROVAR (HVL range) SVH-HVL Rev. B Ed.9/1 (EN) SVH SERIES (e-sv WITH HYDROVAR) Background and context For all pumping needs in commercial or residential building and in industry applications,

More information

Acceleration, Velocity, Separate probe VIBRATION METER Model : VB-8202

Acceleration, Velocity, Separate probe VIBRATION METER Model : VB-8202 Acceleration, Velocity, Separate probe VIBRATION METER Model : VB-8202 Your purchase of this VIBRATION METER marks a step forward for you into the field of precision measurement. Although this METER is

More information

Product description. Compact Modules. Characteristic features. Further highlights

Product description. Compact Modules. Characteristic features. Further highlights 4 Compact Modules Product description Characteristic features Five fine-tuned sizes based on a compact precision aluminum profile with two integrated pre-tensioned ball rail systems Identical external

More information

LED light engine / OLED LED compact. Umodule STARK DLE CLASSIC STARK DLE 82,8 54,4. Ordering data

LED light engine / OLED LED compact. Umodule STARK DLE CLASSIC STARK DLE 82,8 54,4. Ordering data Product description Downlights High-flux LED module Low tolerances for colour temperatures (MacAdams 4) Compact design Excellent thermal management 1 NTC for temperature control High-power LED module in

More information

Semiconductor (AC) fuses

Semiconductor (AC) fuses PSC gr sizes 7x - 690 VAC Main characteristics 6,9 grb 71 PA 200 6,9 grb 73 TTF 1000 + MS7V1-5 UR Ferraz Shawmut PSC-gRB 690 VAC fuse-links provide maximum flexibility in equipment design and ultimate

More information

Fault Calculation Methods

Fault Calculation Methods ELEC9713 Industrial and Commercial Power Systems Fault Calculation Methods There are two major problems that can occur in electrical systems: these are open circuits and short circuits. Of the two, the

More information

C120N circuit-breakers B, C and D curves EN 60898/EN 61009: IEC : 10 ka

C120N circuit-breakers B, C and D curves EN 60898/EN 61009: IEC : 10 ka C0N circuit-breakers B, C and D curves EN 09/EN 009: 0000 - IEC 097-: 0 ka function # protection of cables against overloads and short-circuits in final distribution # manual control and isolation # earth

More information

EX-EMERGENCY LIGHT FITTINGS

EX-EMERGENCY LIGHT FITTINGS EX-EMERGENCY LIGHT FITTINGS nllk 0...N 1-36 W Plastic version for Zone 2 and Zone 21/22 The explosion-protected light fittings of the series nllk 0 N are conform to the requirements of the ATEX-Directive

More information

Film Capacitors. EMI suppression capacitors. Date: June 2018

Film Capacitors. EMI suppression capacitors. Date: June 2018 Film Capacitors EMI suppression capacitors Date: June 2018 EPCOS AG 2018. Reproduction, publication and dissemination of this publication, enclosures hereto and the information contained therein without

More information

SINEAX VK 636 Programmable Temperature Transmitter with PROFIBUS-PA protocol

SINEAX VK 636 Programmable Temperature Transmitter with PROFIBUS-PA protocol with PROFIBUS-PA procol for installation in the terminal head of a temperature sensor DIN 79, shape B Application 00 II () G FISCO The SINEAX VK 66 is a temperature transducer for use in aumation systems

More information

VX25 Enclosure System. Technical documentation PE conductor connection, current carrying capacity

VX25 Enclosure System. Technical documentation PE conductor connection, current carrying capacity VX Enclosure System Technical documentation PE conductor connection, current carrying capacity Enclosure system VX Contents Contents. General remarks. Introduction. Notes on the design of the earthing

More information

CALEFFI. Modulating digital controller for heating and cooling. 161 series 01122/08 GB. replaces dp 01122/05

CALEFFI. Modulating digital controller for heating and cooling. 161 series 01122/08 GB. replaces dp 01122/05 Modulating digital controller for heating and cooling series REGI ERED SI EN ISO 00:000 Cert. n FM UNI EN ISO 00:000 Cert. n 000 0/0 G replaces dp 0/0 Function The controller can be used with three-point

More information

2.9. Namur Valves 2.9. page 175. Namur 1/4 also called Namur 1 in accordance to VDI / VDE Namur 1/2 also called Namur 2.

2.9. Namur Valves 2.9. page 175. Namur 1/4 also called Namur 1 in accordance to VDI / VDE Namur 1/2 also called Namur 2. 2.9 page 175 Namur 1/4 also called Namur 1 in accordance to VDI / VDE 3845. Namur 1/2 also called Namur 2. 2.9 Namur Valves + Selected models are available for low temperature application. Temperature-range:

More information

XM1 Motor Protection Relay. Manual XM1 (Revision B)

XM1 Motor Protection Relay. Manual XM1 (Revision B) XM1 Motor Protection Relay Manual XM1 (Revision B) Woodward Manual XM1 GB Woodward Kempen GmbH reserves the right to update any portion of this publication at any time. Information provided by Woodward

More information

Pascal ET is an handheld multifunction calibrator for the measurement and simulation of the following parameters: - pressure

Pascal ET is an handheld multifunction calibrator for the measurement and simulation of the following parameters: - pressure DATASHEET Pascal ET Pascal ET is an handheld multifunction calibrator for the measurement and simulation of the following parameters: - pressure - electrical signals (ma, mv, V, ) - temperature (TC and

More information

PHASED OUT. FL ballasts Electronic dimming. PCA TC BASIC Y II, W BASIC compact

PHASED OUT. FL ballasts Electronic dimming. PCA TC BASIC Y II, W BASIC compact EL Product description Processor-controlled ballast with y II inside Highest possible energy class CELMA EEI = A BAT Noise-free precise control via DSI signal, switchdim or corridorfunction Nominal life

More information

Semiconductor (AC) fuses

Semiconductor (AC) fuses gr 690 VAC sizes 000 to (full range) Ferraz Shawmut PROTISTOR NH grb 690 VAC fuselinks provide maximum flexibility in equipment design and ultimate protection for today s power conversion equipment. This

More information

LED light engine / OLED LED compact. Uengine DLE G2 integrated ADV

LED light engine / OLED LED compact. Uengine DLE G2 integrated ADV Uengine DLE G2 integrated ADV uengine DLE Product description Module with integrated electronics For downlights Light engine operating with 23 V AC Luminous flux range from 1,24 2,43 lm High system efficacy

More information

Direct-operated 2/2-way solenoid valves Type EV210B

Direct-operated 2/2-way solenoid valves Type EV210B Data sheet Direct-operated 2/2-way solenoid valves Type EV20B EV20B covers a wide range of direct-operated 2/2-way solenoid valves for universal use. EV20B is a very robust valve program with high performance

More information