Received: 19 October 2017; Accepted: 26 November 2017; Published: 3 December 2017

Size: px
Start display at page:

Download "Received: 19 October 2017; Accepted: 26 November 2017; Published: 3 December 2017"

Transcription

1 energies Article Performance Prediction Centrifugal Compressor for Drop-In Testing Using Low Global Warming Potential Alternative Refrigerants Performance Test Codes Joo Hoon Park 1,2, Youhwan Shin 2, * Jin Taek Chung 3, * 1 Department Mechanical Engineering, Graduate School Korea University, Seoul, Korea; joohoon82@korea.ac.kr 2 Centre for Urban Energy Research, Korea Institute Science Technology, Seoul, Korea 3 Department Mechanical Engineering, Korea University, Seoul, Korea * Correspondence: yhshin@kist.re.kr (Y.S.); jchung@korea.ac.kr (J.T.C.); Tel.: (Y.S.); (J.T.C.) Received: 19 October 2017; Accepted: 26 November 2017; Published: 3 December 2017 Abstract: As environmental regulations to stall global warming are strengned around world, studies using newly developed low global warming potential (GWP) alternative refrigerants are increasing. In this study, substitute refrigerants, R-1234ze (E) R-1233zd (E), were used in centrifugal compressor an R-134a 2-stage centrifugal chiller with a fixed rotational speed. Performance predictions rmodynamic analyses centrifugal compressor for drop-in testing were performed. A performance prediction method based on existing ASME PTC-10 performance test code was proposed. The proposed method yielded expected area point centrifugal compressor with alternative refrigerants. The rmodynamic performance first second stages centrifugal compressor was calculated as polytropic state. To verify suitability proposed method, drop-in test results two alternative refrigerants were compared. The predicted based on permissible deviation ASME PTC-10 confirmed that temperature difference was very small at same efficiency. Because drop-in test R-1234ze (E) was performed within expected, centrifugal compressor using R-1234ze (E) is considered well predicted. However, predictions point R-1233zd (E) were lower than those drop-in test. The proposed performance prediction method will assist in understing rmodynamic performance at expected point area a centrifugal compressor using alternative gases based on limited design structure information. Keywords: ; point; centrifugal compressor; low-gwp alternative refrigerant; R-1234ze (E); R-1233zd (E); drop-in test; performance test code 1. Introduction At present, hydrluorocarbon (HFC)-series refrigerants are main working refrigerants used in turbo chillers. Since such refrigerants have a high global warming potential (GWP), ir use is being phased out worldwide. Refrigerants that have little or no effect on global warming have been continuously developed to replace existing high-gwp refrigerants. Low-GWP refrigerants include hydrocarbon-based refrigerants, natural refrigerants, hydrluoroolefin (HFO)-based refrigerants. Of se, HFO-based refrigerants, R-1234yf, R-1234ze (E), R-1233zd (E), R-1336mzz, are attracting attention as new alternative refrigerants owing to ir low-gwp characteristics compatibility with existing turbo chiller refrigerants. These alternative refrigerants have been subjected to drop-in Energies 2017, 10, 2043; doi: /en

2 Energies 2017, 10, tests in existing facilities for applicability rmodynamic evaluation. In this regard, studies using HFO-based low-gwp alternative refrigerants have been conducted in various ways. Wang et al. [1] introduced Air-Conditioning, Heating, Refrigeration Institute (AHRI) s Low-GWP Alternative Refrigerant Evaluation Program (Low-GWP AREP) outlined overall scope procedures program. In addition, for low-gwp cidate refrigerants, y provided cycle count up to current state actual test result. Spatz et al. [2] analysed oretical performance several low-gwp refrigerants in a volumetric chiller centrifugal chiller used for air conditioning. The centrifugal chiller is divided into a low-pressure chiller using R-123 a medium-pressure chiller using R-134a. The rotational speed, impeller outlet diameter, coefficient performance (COP) compressor were compared to those conventional high-gwp refrigerants, results were analysed. This study showed that se refrigerants could be applied to existing devices without significant hardware modifications. Ueda et al. [3] performed a drop-in test R-1234ze (E) alternative refrigerant in an R-134a centrifugal chiller. They analysed compatibility products related to lubrication performance chiller via full- partial-load refrigerator tests. The results drop-in test under full load conditions showed that cooling capacity COP were reduced by approximately 29% 3%, respectively, at same inlet volumetric flow rate. Brasz [4] predicted capacity performance a centrifugal compressor using an ideal cycle a rmodynamic property calculation for R-1234ze (E). In study, R-1234ze (E) was injected into an existing R-134a centrifugal compressor to compare aerodynamic performance with rotational speed. The author found that, when using alternative refrigerants, efficiency chiller increased because low rotational speed viscous loss compared to conventional centrifugal compressors, which are larger than centrifugal compressor used in conventional chiller. However, it was suggested that a condenser redesign is necessary to prevent a pressure drop from condenser. Pearson [5] analysed method characteristics R-134a for alternative refrigerants explained primary issues to consider in alternative-refrigerant centrifugal compressor chiller design. The performance developed centrifugal compressor was compared analysed with COP R-134a, R-1234ze (E) was found to be a viable alternative to existing R-134a centrifugal compressor. Mota-Babiloni et al. [6] performed a drop-in test two alternative refrigerants (R-1234yf R-1234ze (E)) in an R-134a vapor compression plant. It was confirmed that volume efficiency, cooling capacity, COP were decreased compared with those R-134a, use an internal heat exchanger could reduce COP difference between alternative refrigerants. Wu Thilges [7] experimentally analysed performance one centrifugal compressor with three alternative refrigerants for various types refrigerators with R-123 as working fluid. The effects isentropic exponent, Reynolds number, blade Mach number, impeller diameter, rotational speed, etc. were studied. Janković et al. [8] analysed performance system heat transfer characteristics a condenser when R-1234yf R-1234ze (E) were applied to simulation model an R-134a small-power refrigeration system, considering actual dimensions. The authors concluded that R-1234ze (E) could perform better than R-1234yf as an alternative refrigerant for R-134a if an overridden compressor with a cooling system could be used. Meng et al. [9] showed oretical performance three mixed gases consisting R-1234ze (E), R-152a, R-1234ze (E) mixed with R-152a, respectively, in drop-in tests. The COP R-1234ze (E) mixture was similar to that R-134a, but cooling capacity was significantly lower. They also showed that a refrigerant composed R-1234ze (E) R-152a with a mixing ratio 50:50 would be suitable as an alternative refrigerant for R-134a. Sethi et al. [10] analysed oretical performance when replacing R-447B R-452B with a domestic reversible heat pump a direct-expansion air-cooled chiller using R-410A. For R-410A

3 Energies 2017, 10, positive displacement chiller, expected conditions components were analysed with alternative refrigerants. In addition, size performance centrifugal compressors based on alternative refrigerants such as R-515A, R-1234ze (E), R-1234yf were oretically analysed for use in R-134a centrifugal chillers. To summarize previous studies to date, studies using low-gwp refrigerants have mainly focused on heat exchangers, heat pumps, rmodynamic cycle analyses. In recent years, some companies have developed centrifugal chillers [11,12] centrifugal compressors [13] that use a low-gwp alternative refrigerant as gas. However, studies on characteristics a centrifugal compressor alone using a low-gwp alternative refrigerant have not yet been published. In particular, when it is difficult to supply alternative refrigerants, a method to predict performance centrifugal compressor in advance would be very useful. In addition, it is necessary to evaluate analyse performance centrifugal compressors when using a substitute gas. In this study, two low-gwp alternative refrigerants, R-1234ze (E) R-1233zd (E), were applied to an R-134a centrifugal compressor with a two-stage turbo chiller. Then, area point centrifugal compressor were predicted via a drop-in test. The existing centrifugal compressor performance test code was improved, expected performance a centrifugal compressor using an alternative refrigerant was calculated rmodynamically analysed. Although R-1233zd (E) is a low-pressure refrigerant, it was used to examine feasibility proposed performance prediction method. 2. Centrifugal Compressor Performance Prediction Method AHRI provides an evaluation program for drop-in testing using low-gwp alternative refrigerants [14]. Based on this program, centrifugal compressor test is applied according to The American Society Mechanical Engineers, Performance Test Code-10 (ASME PTC-10) [15]. ASME PTC-10 provides a performance test procedure permissible deviation required for rmodynamic evaluation centrifugal compressor axial compressor. The ASME PTC-10 performance tests are classified into two types, type 1 type 2, depending on test gas. The type 1 method is used when components design gas test gas are same or similar. The type 2 method is used when components design gas test gas are different. In both types tests, performance centrifugal compressor is compared with design performance, feasibility result is rmodynamically evaluated. However, for each type test result, re is a difference between design performance, type comparison variable, permissible deviation. For a multi-stage compressor, performance is evaluated using information about conditions inlet outlet (inlet duct outlet duct) compressor, impeller outlet diameter at each stage, impeller outlet width at first stage. Here, mass flow rate at inlet outlet should be same. In this study, we used ASME PTC-10 type 2 method for predicting performance improved method to calculate expected expected performance centrifugal compressor using an alternative refrigerant. Performance prediction was conducted for each stage Performance Prediction Procedure 1 shows performance prediction process using an alternative refrigerant. The impeller diameter, impeller outlet width, surface roughness impeller remain constant because centrifugal compressor s shape does not vary with type refrigerant used. The performance prediction process using alternative refrigerants is as follows: STEP-1: Enter information about design conditions. The required information includes name design refrigerant, total pressure total temperature inlet outlet, mass flow rate, rotational speed. STEP-2: Calculate rmodynamic performance based on design conditions. These conditions include total pressure ratio, total temperature ratio, ratio inlet outlet specific volumes,

4 Energies 2017, 10, Energies 2017, 10, isentropic volumes, isentropic polytropic polytropic states, machine states, Mach machine number Mach (defined number in(defined Equation in Equation (3)), machine (3)), Reynolds machine number Reynolds (defined number Equation (defined(4)), Equation so(4)), on. so on. STEP-3: Enter information about expected test conditions. This input information is issimilar to to design conditions. The name selected alternative refrigerant is isentered as as test operation refrigerant. STEP-4: Calculate rmodynamic performance based on expected test conditions. The items to to be be calculated are same as those in STEP-2. STEP-5: Compare following four results obtained from from STEP-2 STEP-2 STEP-4: STEP-4: ratio ratio inlet inlet outlet outlet specific specific volumes, volumes, flow flow coefficient, coefficient, machine machine Mach Mach number, number, machine machine Reynolds Reynolds number. number. The The expected expected operation operation drop-in drop-in test is test calculated is calculated based based on ondesign design result result (STEP-2). (STEP-2). The The allowable allowable deviation deviation in in operation operation is calculated is calculated based based on on type-2 type-2 ASME ASME PTC-10 PTC-10 criteria. criteria. STEP-6: Select Select expected expected point point that meets that meets design design result inresult expected in expected operation operation derived in STEP-5. derived in The STEP-5. expected The expected point is selected point is after selected comparison after comparison with design with results design via results correction via process. correction The outlet process. temperature The outlet temperature pressure pressure selected selected point are reflectedpoint are inlet reflected conditions in inlet conditions next connected stage. next connected stage. 1. Procedure for predicting performance using alternative refrigerants. Table 1 shows permissible deviation required for performance prediction. The Table 1 shows permissible deviation required for performance prediction. The calculation calculation formulas for each comparison variable are as follows: formulas for each comparison variable are as follows: % = = (1) % vr = vr ( t vr = v ) in (1) vr d 60 v out = (2) 2 60, Φ = ṁ ρ = in 2πN, D 3 (2) imp,out (3) =, Mm, = U imp,out =,, (3) a in (4) where, %vr is percentage Rem deviation = U imp,out b imp,out between specific = U imp,out b imp,out volume ratios, vr is specific volume ratio, (4) ν µ in v in Φ is flow coefficient, Mm is machine Mach number, Uimp,out (m/s) is tangential speed at where, impeller % vr outlet, is ain percentage (m/s) is acoustic deviationvelocity, betweenrem specific is volume machine ratios, Reynolds vr is specific number, volume bimp,out is ratio, Φimpeller is flow outlet coefficient, width, νin Mm (m 2 /s) is is machine kinematic Mach viscosity, number, μin U(kg/m s) imp,out (m/s) is isabsolute tangential viscosity, speed at impeller vin (m 3 /kg) outlet, is a in specific (m/s) volume. is acoustic The subscript velocity, in Rem signifies is a machine specific point Reynolds number, inlet duct. b imp,out is

5 Energies 2017, 10, impeller outlet width, ν in (m 2 /s) is kinematic viscosity, µ in (kg/m s) is absolute viscosity, Energies v in (m , 10, /kg) is specific volume. The subscript in signifies a specific point inlet duct. Table 1. Permissible deviations from specified parameters [15]. Table 1. Permissible deviations from specified parameters [15]. Permissible Deviations from Specified Operating Parameters Permissible Deviations from Specified Limit Test Operating Values Parameters as Percentage Design Values Parameter Symbol Limit Test Min. Values as Percentage Max. Design Values Parameter Symbol Specific volume ratio %vr 95% Min. 105% Max. Flow coefficient Φ 96% 104% Specific Machine volume Mach ratio number % vr Mm 95% See 2a 105% Flow coefficient Φ 96% 104% Machine Reynolds number Rem See 2b Machine Mach number Mm See 2a Machine Reynolds number Rem See 2b 2a,b show minimum maximum deviation s for design conditions test conditions, respectively, as permissible machine Mach number machine 2a,b show minimum maximum deviation s for design conditions test Reynolds number. The minimum machine Reynolds number in 2b is greater than 90,000 [15]. conditions, respectively, as permissible machine Mach number machine Reynolds number. The minimum machine Reynolds number in 2b is greater than 90,000 [15]. (a) (b) Allowable diagram: (a) (a) machine Mach number (b) (b) machine Reynolds number adapted from from [15], [15], with with permission from from American Society Mechanical Engineers, In ASME PTC-10, performance a centrifugal compressor is evaluated with polytropic method. Because refrigerant alternative refrigerant are all real gases, method proposed by Schultz [16] is used to calculate polytropic parameters for a real gas.

6 Energies 2017, 10, In ASME PTC-10, performance a centrifugal compressor is evaluated with polytropic method. Because refrigerant alternative refrigerant are all real gases, method proposed by Schultz [16] is used to calculate polytropic parameters for a real gas Calculation Polytropic Exponents The polytropic exponents for a real gas can be calculated using compressibility function proposed by Schultz. The Schultz compressibility functions X Y are: X = T v Y = p v ( ) v 1 (5) T p ( ) v p T Here, Schultz compressibility functions X Y can be calculated by converting volume expansivity calculated using Equation (7) isormal bulk modulus calculated using Equation (8) into Equations (9) (10), respectively: X = T v α = 1 v ( ) [ v 1 = T T p Y = p v ( v p T ( ) v T p ( ) p K T = v (8) v T ( ) ] 1 v 1 = αt 1 (9) v T p ) [ ( ) ] 1 v = p = p (10) v p K T T (6) (7) X m = X in + X out 2 (11) Y m = Y in + Y out 2 where α (1/K) is volume expansivity K T (kpa) is isormal bulk modulus. Since temperature pressure states are different at compressor inlet outlet, compressibility function at compressor inlet outlet are averaged n used. X m Y m, calculated using Equations (11) (12), respectively, are used to calculate polytropic volume exponent, n, polytropic temperature exponent, m. The polytropic exponents are given by Equations (13) (14) [17]. Equation (15) gives isentropic volume exponent (k v ) used to obtain polytropic temperature exponent: 1 + X m n = ( 1 1 k V m = ) ( ηp + X Y 1 m ηp 1 ( )( ) kv Y m 1 1 k V ηp + X m (12) ) (13) (1 + X m ) 2 (14) ( ) k V = ln pout p in ) ln( vin v,is,out (15) where η p is polytropic efficiency v is,out (m 3 /kg) is specific volume at outlet duct in isentropic state.

7 Energies 2017, 10, Calculation Polytropic State In this study, method proposed by ISO 5389 [17] was used to calculate polytropic efficiency a centrifugal compressor. The formula for calculating polytropic efficiency is given by Equation (16) using compressibility functions X Y proposed by Schultz. To evaluate rmodynamic performance centrifugal compressor according to point, we can calculate polytropic work W p (N m/kg) gas power P g (kw) using Equations (17) (18). Equation (19) gives Schultz s work factor, f, for calculating polytropic work [16]: η p = k V (1+X m ) 2 k V Y m 1 1 ln T out T in ln p out p in ( ) n W p = f R Z in T in n 1 X m [ ( pout p in ) ( n 1 n ) ] 1 (16) (17) P g = ( Wp ṁ) η p (18) h f = is,out h [( ) in ] (19) kv k V 1 (p out v is,out p in v in ) where R (N m/kg K) is gas constant, Z in is compressibility factor refrigerant at inlet. duct, m (kg/s) is mass flow rate, h is enthalpy at a specific point Correction Selection Method for Drop-In Test s Expected Operating Point For a single-shaft multi-stage centrifugal compressor connected to return channel, outlet pressure return channel is designed to equalize inlet pressure next stage connected. Therefore, an appropriate predicted point should be selected as entry state next stage among calculated expected operation areas. STEP-6 in 1 is step in which an expected point is selected based on predicted area. In this step, design performance is corrected using results predicted driving. The predicted point drop-in test was selected when polytropic work value calculated correction was equal to polytropic work design performance. If value polytropic work correction result is greater or less than design performance value, outlet temperature pressure predicted point can be adjusted. To correct expected point drop-in test to match design performance, following equations are sequentially calculated: Q corr = Q t N d N t (20). m corr = Q t N ( ) d 1 (v N t v in,corr = v in,d ) in,corr (21) N corr = N t Q d (22) Q t [ (1 ) ( ) η p,corr = 1 ηp,t RAd RA t RA = RB = ( )] RBd RB t [ ] RC ( b imp,out) Rem log( Rem ) log(ε Rem ) RC = Rem (23)

8 Energies 2017, 10, Energies 2017, 10, , =, Rem corr = η (25) p,d (24) where Q (m 3 /s) is volume flow rate at inlet. ηra, p,t RB, RC are machine Reynolds number correction constant constants. The subscript corr ( signifies ) 2 Nd corrected state. W p,corr = W p,t Rem corr (25) N t 2.5. Thermodynamic Properties Refrigerants where Q (m 3 /s) is volume flow rate at inlet. RA, RB, RC are machine Reynolds number The rmodynamic properties all refrigerants used for performance prediction were correction constant constants. The subscript corr signifies corrected state. obtained from NIST REFPROP 9.1 [18]. However, those R-1234ze (E) R-1233zd (E) were 2.5. obtained Thermodynamic from Properties file uploaded Refrigerants to FAQ NIST REFPROP [19]. The refrigerant state equation is Helmholtz equation state recommended by NIST [20]. Microst Excel was used for The rmodynamic properties all refrigerants used for performance prediction were obtained performance prediction, it was possible to acquire state quantity refrigerant in from NIST REFPROP 9.1 [18]. However, those R-1234ze (E) R-1233zd (E) were obtained from conjunction with REFPROP data. file uploaded to FAQ NIST REFPROP [19]. The refrigerant state equation is Helmholtz equation 3. Comparison state recommended Thermodynamic by NIST Characteristics [20]. Microst Excel Low-GWP was used Alternative for performance Refrigerants prediction, it was possible to acquire state quantity refrigerant in conjunction with REFPROP data. 3a,b compare rmodynamic properties R-134a, R-1234ze (E), R-1233zd (E). 3. Comparison 3a shows Thermodynamic saturation curve Characteristics three refrigerants Low-GWPin Alternative a pressure-enthalpy Refrigerants diagram, 3b shows pressure-temperature plot. At same pressure, we can observe that R-1234ze 3a,b compare rmodynamic properties R-134a, R-1234ze (E), R-1233zd (E). (E) is similar to R-134a deviation is not large. However, R-1233zd (E) has a relatively higher 3a shows saturation curve three refrigerants in a pressure-enthalpy diagram, enthalpy higher temperature than R-134a. Although it is a qualitative comparison, R-1234ze (E) 3b shows pressure-temperature plot. At same pressure, we can observe that R-1234ze (E) is considered to be suitable as an alternative refrigerant for R-134a, which is well explained in is similar to R-134a deviation is not large. However, R-1233zd (E) has a relatively higher previous research. Table 2 lists environmental impact (ODP GWP) rmodynamic enthalpy higher temperature than R-134a. Although it is a qualitative comparison, R-1234ze (E) properties for each refrigerant. is considered to be suitable as an alternative refrigerant for R-134a, which is well explained in previous research. Table 2 lists environmental impact (ODP GWP) rmodynamic properties for each refrigerant. (a) 3. Cont.

9 Energies 2017, 10, Energies 2017, 10, (b) Comparison rmodynamic diagrams for for R-134a, R-1234ze (E), (E), R-1233zd (E). (E). (a) (a) Pressure-enthalpy diagram (b) (b) pressure-temperature diagram. Table Table 2. Environmental 2. impact impact rmodynamic properties refrigerants. Refrigerant R-134a R-1234ze (E) R-1233zd (E) Refrigerant R-134a R-1234ze (E) R-1233zd (E) ODP ODP GWP GWP Molar mass (kg/kmol) Molar mass Critical (kg/kmol) temperature (K) Critical temperature (K) Critical pressure (kpa) Critical pressure (kpa) Critical density (kg/m 3 ) Critical density (kg/m 3 ) Description Centrifugal Compressor in a Centrifugal Chiller for a Drop-In Test 4. Description Centrifugal Compressor in a Centrifugal Chiller for a Drop-In Test 4.1. Specifications Operational State 4.1. Specifications Operational State 4a shows R-134a centrifugal chiller (500 RT) for drop-in test using an alternative 4a shows R-134a centrifugal chiller (500 RT) for drop-in test using an alternative refrigerant. 4b shows meridional plane two-stage centrifugal compressor used in refrigerant. 4b shows meridional plane two-stage centrifugal compressor used in chiller. The centrifugal compressor is composed two stages but with a single shaft. There is a chiller. The centrifugal compressor is composed two stages but with a single shaft. There is a return channel between first second stage, economizer is connected before second return channel between first second stage, economizer is connected before second stage s entrance. Therefore, mass flow rate refrigerant entering second stage is larger stage s entrance. Therefore, mass flow rate refrigerant entering second stage is larger than that entering first stage. The first- second-stage diffusers are all vaneless. 5 shows than that entering first stage. The first- second-stage diffusers are all vaneless. 5 shows oretical cycle R-134a centrifugal compressor for a 100% load condition via a oretical cycle R-134a centrifugal compressor for a 100% load condition via pressure-enthalpy diagram. There is no superheat degree at first-stage inlet centrifugal a pressure-enthalpy diagram. There is no superheat degree at first-stage inlet centrifugal compressor, pressure at first-stage outlet second-stage inlet are same. The inlet compressor, pressure at first-stage outlet second-stage inlet are same. The inlet temperature second stage is reduced by approximately 0.3 K from temperature firststage outlet via flow from economizer. temperature second stage is reduced by approximately 0.3 K from temperature first-stage outlet via flow from economizer. The measurement device installation position in performance test centrifugal The measurement device installation position in performance test centrifugal chiller are as follows. A relative pressure transmitter was used for static pressure measurement. The chiller are as follows. A relative pressure transmitter was used for static pressure measurement. accuracy pressure transmitter is 0.1%FS. For temperature measurement, a platinum resistance The accuracy pressure transmitter is 0.1%FS. For temperature measurement, a platinum resistance temperature detector (RTD) with a two-wire-type 1000-Ω sensor was used. The class RTD temperature detector (RTD) with a two-wire-type 1000-Ω sensor was used. The class RTD sensor is A (±(0.15 C 0.002t) C), temperature coefficient resistance is Ω/ C. The sensor is A (±(0.15 C t) C), temperature coefficient resistance is Ω/ C. temperature pressure sensors are installed at first-stage inlet second-stage volute The temperature pressure sensors are installed at first-stage inlet second-stage volute outlet. The measured data were acquired through an in-house system, measured results were outlet. The measured data were acquired through an in-house system, measured results were used to verify performance prediction results. used to verify performance prediction results.

10 Energies 2017, 10, Energies 2017, 10, Energies 2017, 10, (a) (a) (b) 4. Centrifugal chiller its drop-in (b) test using low-gwp alternative refrigerants. (a) Centrifugal chiller for drop-in test (b) meridional plane Centrifugal chiller chiller its drop-in its drop-in test usingtest low-gwp using alternative low-gwp refrigerants. alternative (a) refrigerants. Centrifugal chiller (a) Centrifugal for drop-in chiller test for drop-in (b) meridional test plane. (b) meridional plane. 5. Pressure-enthalpy diagram with oretical operational cycle R-134a centrifugal compressor 5. Pressure-enthalpy at 100% load. diagram with oretical operational cycle R-134a centrifugal compressor at 100% load. 5. Pressure-enthalpy diagram with oretical operational cycle R-134a centrifugal compressor at 100% load.

11 Energies 2017, 10, Constraint Conditions Centrifugal Compressor for Predicting Performance Table 3 lists inlet pressure temperature, specific volume ratio, flow coefficient for a full load (100% load) R-134a centrifugal compressor. In centrifugal chiller used in this study, outlet temperature chilled water evaporator was ± 0.3 K even if refrigerant was changed. Therefore, performance compressor was predicted while assuming that inlet temperatures first stage compressor were all identical. Because rotational speed compressor is fixed, re is no change in rotational speed, even with an alternative refrigerant. The percentage deviation specific volume ratio was calculated within tolerance described in Table 1. In addition, flow coefficient was assumed to be unchanged. The performance each stage centrifugal compressor was analysed based on above constraints. In addition, in this study, centrifugal compressor using R-1234ze (E) was designated as DR-34, centrifugal compressor using R-1233zd (E) was designated as DR-33 for convenience. Table 3. Inlet conditions R-134a compressor constrain conditions alternative refrigerants for performance predictions at 100% load state. 1st stage 2nd stage Refrigerant Symbol Unit R-134a (Ref.) R-1234ze (E) R-1233zd (E) Rotational speed N rpm Fixed rotational speed Inlet total pressure p in kpa Inlet total temperature T in K Specific volume ratio vr ~ ~1.65 Deviation specific volume ratios % vr - - 5%~+5% 5%~+5% Flow coefficient Φ Inlet total pressure p in kpa Using calculated data Inlet total temperature T in K from 1st stage Using calculated data from 1st stage Specific volume ratio vr ~ ~1.67 Deviation specific volume ratios % vr - - 5%~+5% -5%~+5% Flow coefficient Φ Results Discussion 5.1. Comparison Permissible Deviation by Alternative Gases 6 shows a comparison between results DR-34 DR-33 in permissible diagram 2. 6a shows results for each stage DR-34 DR-33 in permissible machine Mach number. All stages except for first stage DR-33 were within permissible. For first stage DR-33 to return to permissible, rotational speed must be reduced or sound speed at inlet must increase, as indicated by Equation (3). There are two oretical methods for increasing sound speed at inlet: increasing inlet temperature decreasing inlet pressure. In former case, if a superheat degree approximately 4 K is applied under assumption that re is no pressure decrease by absorption at inlet compressor, machine Mach number shifts into permissible. In latter case, inlet pressure compressor can be reduced by controlling chilled water, but it moves furr away from permissible because inlet temperature is also decreased. Therefore, effect adding superheat needs to be considered. However, for a more precise analysis, this effect should be analysed comprehensively via a cycle simulation performance test. 6b shows results each stage DR-34 DR-33 in permissible machine Reynolds number. The ratio machine Reynolds number DR-33 was relatively lower than that DR-34, but points both refrigerants were in permissible.

12 Energies 2017, 10, Energies 2017, 10, (a) (b) Comparison Comparison allowable allowable diagrams diagrams for for alternative alternative gases. gases. (a) (a) Allowable Allowable machine machine Mach Mach number number (b) (b) allowable allowable machine machine Reynolds Reynolds number. number Prediction Allowable Range Theoretical Operating Point 5.2. Prediction Allowable Range Theoretical Operating Point 7a,b show changes in total temperature, polytropic efficiency, polytropic work as 7a,b show changes in total temperature, polytropic efficiency, polytropic work as a a function changing total pressure in first- second-stage outlets DR-34, respectively. function changing total pressure in first- second-stage outlets DR-34, respectively. Here, flow coefficients DR-1 DR-2 were fixed at , respectively. The deviation Here, flow coefficients DR-1 DR-2 were fixed at , respectively. The deviation specific volume ratios varied from 5% to +6%, which is permissible error. The polytropic specific volume ratios varied from 5% to +6%, which is permissible error. The polytropic efficiency was compared by limiting calculation from 50% to 95%. 7a shows that, as efficiency was compared by limiting calculation from 50% to 95%. 7a shows that, first-stage outlet pressure DR-34 increases, outlet temperature polytropic work increase, as first-stage outlet pressure DR-34 increases, outlet temperature polytropic work while polytropic efficiency decreases. When specific volume ratio increases, minimum increase, while polytropic efficiency decreases. When specific volume ratio increases, maximum values s outlet pressure, outlet temperature, polytropic minimum maximum values s outlet pressure, outlet temperature, work increase. When specific volume ratio decreases, opposite occurs. In 7b, changes polytropic work increase. When specific volume ratio decreases, opposite occurs. In 7b, in outlet temperature polytropic efficiency as a function increasing DR-34 outlet pressure changes in outlet temperature polytropic efficiency as a function increasing DR-34 outlet at second stage show same tendency as that at first stage. However, at first stage, pressure at second stage show same tendency as that at first stage. However, at first polytropic work decreases, minimum maximum values

13 Energies 2017, 10, Energies 2017, 10, stage, polytropic work decreases, minimum maximum values polytropic work increase identically. To analyse difference in tendency polytropic polytropic work increase identically. To analyse difference in tendency polytropic work work first second stages, work factor isentropic volume exponent each stage first second stages, work factor isentropic volume exponent each stage were were compared, compared, as shown as shown in in 8. The 8. work The work factor factor increases increases gradually gradually with increasing with increasing pressure ratio pressure ratio in in first first stage, stage, but it but decreases it decreases in second in second stage. To stage. compare To compare values values isentropic volume isentropic volume exponent exponent in inwork-factor work-factor equation, equation, Equation Equation (19), even (19), when even when pressure pressure ratio changes, ratio changes, isentropic volume exponent is is greater than than 1 (kv 1 (k> V 1) > in 1) in first first stage stage but but less less than than 1 in 1 insecond second stage stage (k V (kv < 1). < 1). Therefore, first term denominator in inequation (19) (19) becomes negative negative in in second second stage. stage. Furrmore, product product outlet outlet pressure pressure outlet outlet isentropic isentropic specific specific volume volume second term second becomes term smaller becomes thansmaller product than product inlet pressure inlet pressure inlet specific inlet volume. Thus, specific second volume. term Thus, also becomes second term negative. also becomes Because negative. Because product product first second first terms second terms denominator, total value denominator becomes greater than denominator, total value denominator becomes greater than difference between difference between enthalpies numerator. As a result, work factor decreases. enthalpies numerator. As a result, work factor decreases. (a) (b) 7. Comparison outlet total temperature, polytropic efficiency, polytropic work for a 7. Comparison outlet total temperature, polytropic efficiency, polytropic work for permissible 5%vr to +5%vr for DR-34. (a) First-stage compressor at Φ = (b) secondstage compressor at Φ = vr to +5% vr for DR-34. (a) First-stage compressor at Φ = a permissible 5% (b) second-stage compressor at Φ =

14 Energies 2017, 10,10, 2043 Energies 2017, 2043 Energies 2017, 10, Comparison Comparison work factor isentropic volume exponent for each stage DR-34 0%. 8. work factor isentropic volume exponent for each stage DR-34 atatat 0% vr.vr 8. Comparison work factor isentropic volume exponent for each stage DR-34 0% vr. 9a shows expected point first-stage outlet 9a shows expected point first-stage outlet 9a shows expected point first-stage outlet DR-34 calculated oretically via proposed method. 9b shows expected DR-34 calculated oretically via proposed method. 9b shows expected DR-34 calculated oretically via proposed method. 9b shows expected expected point inlet outlet in second stage based on expected expected point inlet outlet in second stage based on expected expected point inlet outlet in second stage based on expected point outlet in first stage DR-34. point point outlet outletinin first firststage stagedr-34. DR-34. (a)(a) (b)(b) Calculated point forfor DR-34. (a)(a) First stage (b)(b) second Calculated point DR-34. First stage second 9. Calculated point for DR-34. (a) First stage (b) second stage. stage. stage.

15 Energies 2017, 10, Energies 2017, 10, The expected is defined as pressure when deviation specific The expected is defined as pressure when deviation specific volume ratio is between 5% +5% enthalpy when calculated polytropic volume ratio is between 5% +5% enthalpy when calculated polytropic efficiency efficiency is between 50% 95%, under condition that specific volume ratio R-134a is between 50% 95%, under condition that specific volume ratio R-134a design design DR-34 deviation specific volume ratio are 0%. Within expected DR-34 at deviation this time, centrifugal specific volume compressor ratio has are various 0%. Within expected points. Therefore, oretical at this time, expected centrifugal compressor point needs to has be various calculated using STEP-6 points. in Therefore, 1. The outlet oretical expected points each point stage needs in to be calculated 9a,b were using obtained STEP-6 under in following 1. The outlet limitations: percentage points each stage deviation in 9a,b specific were obtained volume under ratio is 0% following deviation limitations: ratio percentage polytropic work deviation between specific design volume condition ratio is 0% correction result deviation is 0%. ratio polytropic work between design condition correction result 10a,b show is 0%. expected expected points in each stage DR-33. The 10a,b overall showresults expected are similar to those for DR-34 owing expected to rmodynamic points incharacteristics each stage DR-33. R-1233zd The overall (E). results However, areit similar has a lower to those density for DR-34 compared owing to R-1234ze to rmodynamic (E); thus, outlet characteristics pressure R-1233zd in each stage (E). However, DR-33 is itlower has a than lower that density DR-34. compared to R-1234ze (E); thus, outlet pressure in each stage DR-33 is lower than that DR-34. (a) (b) 10. Calculated point for DR-33. (a) First stage (b) second stage. 10. Calculated point for DR-33. (a) First stage (b) second stage.

16 Energies 2017, 10, The minimum maximum values pressure temperature in expected at outlet in each stage DR-34 DR-33 are listed in Table 4. At same deviation specific volume ratios, lower efficiency is, higher are pressure temperature. When deviation specific volume ratios increases from 5% to +5%, both pressure temperature increase. When difference deviation, % vr, is analysed, pressure difference DR-34 is greater than that DR-33, pressure difference second stage is greater than that first stage. Furrmore, pressure difference increases furr if efficiency decreases. The temperature difference is approximately 3 K at a polytropic efficiency 95% for both DR-34 DR-33 approximately 6 K at 50% efficiency. Because results are generally more sensitive to temperature than to pressure at same efficiency point, more attention should be focused on temperature control during drop-in test. Table 4. Minimum maximum value pressure temperature at outlet by deviation specific volume ratios for polytropic efficiencies 50% 95%. DR-34 Deviation Specific Volume Ratios P min (kpa) T min (K) P max (kpa) T max (K) 1st stage 2nd stage 5% vr % vr % vr % vr (=5% vr ( 5% vr )) % vr % vr % vr % vr (=5% vr ( 5% vr )) Polytropic efficiency 95% 50% DR-33 Deviation Specific Volume Ratios P min (kpa) T min (K) P max (kpa) T max (K) 1st stage 2nd stage 5% vr % vr % vr % vr (=5% vr ( 5% vr )) % vr % vr % vr % vr (=5% vr ( 5% vr )) Polytropic efficiency 95% 50% 5.3. Validation Thermodynamic Performance Prediction 11a shows a diagram comparing prediction results for first second stages DR-34 with measurement results from drop-in test. The static pressure p s (kpa) static temperature T s (K) at inlet duct first stage centrifugal compressor at outlet second stage were converted to total pressure total temperature using Equations (26) (29), respectively, compared with prediction results. In ASME PTC-10, when fluid Mach number at measured position, Ma, is less than 0.2, it is regarded as incompressible because compressive effect decreases, total pressure is calculated as shown in Equation (26). If fluid Mach number is 0.2 or higher, total pressure should be calculated as shown in Equation (27). Because fluid Mach numbers at inlet outlet ducts are both less than 0.2, total pressure was calculated using Equation (26). Equation (30) gives average fluid speed V (m/s) using cross-sectional area at measured position: p = p s + V2 2 v s (Incompressible flow, Ma < 0.2) (26) [ p = p s 1 + k 1 ] k Ma 2 k 1 (Compressible flow, Ma 0.2) (27) 2

17 where k is ratio specific heats Cp (N m/kg K) is specific heat at constant pressure. The subscript s signifies static state. The measured point at inlet in first stage DR-34 is lower by approximately 11 kpa (approximately 4%) than oretically predicted point. The deviation inlet Energiestemperature 2017, 10, 2043 seems to be due to environment during actual operation closed-1circuit cycle chiller. 21 Under assumption that inlet temperature Ma = V is identical to design condition deviation specific volume ratio is 0%, predicted point is indicated by a solid (28) symbol a solid line in 11a. The pressure at a measured point outlet in second ( V 2 ) stage is lower by approximately 8.7 kpa (approximately 1.2%) than predicted point, but it is in predicted T. = T s Under + (1 0.65) assumption (29) 2 that C inlet condition in first stage p,s DR-34 is converted to measured temperature pressure deviation specific volume. ratio is 0%, predicted point is indicated m vby s an open symbol a short-dashed line in V = (30) 11a. A where k is ratio specific heats C p (N m/kg K) is specific heat at constant pressure. The subscript s signifies static state. Energies 2017, 10, (a) (b) 11. Comparison 11. Comparison predicted results drop-in test test results for for (a) (a) DR-34 DR-34 (b) DR-33. (b) DR-33. When inlet temperature pressure decrease, predicted points at first second-stage outlets decrease. Even when inlet conditions are changed, measured point is within predicted. 11b compares prediction results in first second stages DR-33 with measurements obtained via drop-in test. The solid symbol solid line indicate predicted point at 0%vr. The pressure temperature measured at

18 Energies 2017, 10, The measured point at inlet in first stage DR-34 is lower by approximately 11 kpa (approximately 4%) than oretically predicted point. The deviation inlet temperature seems to be due to environment during actual operation closed-circuit cycle chiller. Under assumption that inlet temperature is identical to design condition deviation specific volume ratio is 0%, predicted point is indicated by a solid symbol a solid line in 11a. The pressure at measured point outlet in second stage is lower by approximately 8.7 kpa (approximately 1.2%) than predicted point, but it is in predicted. Under assumption that inlet condition in first stage DR-34 is converted to measured temperature pressure deviation specific volume ratio is 0%, predicted point is indicated by an open symbol a short-dashed line in 11a. When inlet temperature pressure decrease, predicted points at first second-stage outlets decrease. Even when inlet conditions are changed, measured point is within predicted. 11b compares prediction results in first second stages DR-33 with measurements obtained via drop-in test. The solid symbol solid line indicate predicted point at 0% vr. The pressure temperature measured at inlet first stage are very close to oretically predicted point with a difference less than 0.5%. However, pressure temperature at measured point second-stage outlet are higher by approximately 20 kpa (approximately 15%) by approximately 2.4 K than those at predicted point, respectively. This shows that predicted point is low. The predicted point when operated at +5% vr in first stage DR-33 is indicated by an open symbol a short-dashed line in 11b. Even when deviation specific volume ratio increases in first stage, predicted point at second-stage outlet is low, predicted is lower than measured point. When we examine operation characteristics a general centrifugal compressor, if flow rate decreases at a fixed rotational speed, outlet pressure temperature become higher than design points. Because a decrease in flow rate implies operation at an f-design point, operation information for f-design point R-134a needs to be compared. On or h, from systematic viewpoint chiller, because a low-pressure refrigerant was injected into a medium-pressure refrigerant system, rmodynamic problem occurring in condenser evaporator can be considered. If drop-in test R-1234ze (E) R-1233zd (E) can be performed on a turbo chiller for a low-pressure refrigerant, rmodynamic influence heat exchanger can be analysed with complexity. Table 5 compares total pressure ratio, polytropic efficiency, gas power at calculated point alternative refrigerant with design conditions R-134a. This shows that pressure ratios first second stages are similar even with a different refrigerant. In case DR-34, efficiency second stage is lower than that first stage, but y are more similar in case DR-33. The gas power increases in second stage for both compressors because increase flow rate due to economizer in second stage R-134a was reflected when predicted performance drop-in test was calculated. Furrmore, DR-33 has a very low gas power owing to lower density flow rate compared to or refrigerants. Table 5. Performance prediction results alternative refrigerants at predicted points. Refrigerant Symbol R-134a R-1234ze (E) R-1233zd (E) Deviation specific volume ratio % vr st stage 2nd stage Total-to-total pressure ratio pr Polytropic efficiency (%) η p Gas power (kw) P g Total-to-total pressure ratio pr Polytropic efficiency η p Gas power (kw) P g

19 Energies 2017, 10, Conclusions In this study, a low-gwp alternative refrigerant was used in centrifugal compressor a conventional R-134a turbo chiller, performance centrifugal compressor in each stage, which is required for drop-in test, was predicted. A performance prediction method was proposed by changing existing performance test code, predicted point were calculated using proposed method. The following conclusions were obtained from this study. Polytropic work, which is one rmodynamic performance variables a centrifugal compressor, was found to be affected by isentropic volume exponent value. In predicted s DR-34 DR-33, temperature difference between deviations specific volume ratios was approximately 3 K at 95% polytropic efficiency approximately 6 K or less at 50% polytropic efficiency. This shows that predicted calculated based on permissible deviation ASME PTC-10 is sensitive to temperature at same efficiency point. The predicted DR-33 was small because pressure difference between deviations specific volume ratio was smaller than that DR-34. The predicted point at stage-two outlet DR-34 was higher by approximately 1.2% than that drop-in test. If point was predicted by changing stage-one inlet condition to test result, pressure at stage-two outlet was lower by approximately 2.6% compared to measured value. Although re was a quantitative deviation between measured predicted points because test result was in predicted s for two conditions, proposed method predicted DR-34 well. In case DR-33, predicted point were generally lower than test results. A more accurate evaluation requires additional analysis based on f-design points R-134a rmodynamic influence heat exchanger. In this study, we proposed a performance prediction method that can be used to predict point drop-in test alternative gases by using performance test code an existing centrifugal compressor. The proposed method can be used to predict evaluate performance in each stage a multi-stage centrifugal compressor. The results proved that performance a centrifugal compressor can be predicted when operated with an alternative gas based on limited information about factors such as design conditions shapes. Furrmore, additional information about f-design points a centrifugal compressor will be helpful for identifying predicted point more precisely. Acknowledgments: This research was supported by Technology Innovation Program (Grant No ) by Ministry Trade, Industry & Energy. Author Contributions: All authors contributed to this work by collaboration. Joo Hoon Park is main author this manuscript. Youhwan Shin Jin Taek Chung assisted provided useful suggestions in contents research. All authors revised approved publication. Conflicts Interest: The authors declare no conflict interest. Nomenclature GWP Global warming potential HFOs Hydrluoroolefins ODP Ozone depletion potential A Cross-sectional area flow channel (m 2 ) a Acoustic velocity (m/s) b Tip width (m) C p Specific heat at constant pressure (N m/kg K) D Diameter (m) f Work factor Schultz h Enthalpy total state (kj/kg) K T Isormal bulk modulus (kpa)

20 Energies 2017, 10, k V Isentropic volume exponent k Ratio specific heats (C p /C v ) Mm Machine Mach number Ma Fluid Mach number m Polytropic temperature exponent N Rotational speed (rpm) n Polytropic volume exponent P g Gas power (kw) p Pressure total state Q Volume flow rate at inlet (m 3 /s) R Gas constant (N m/kg K) RA Machine Reynolds number correction constant RB Machine Reynolds number correction constant RC Machine Reynolds number correction constant Rem Machine Reynolds number T Temperature total state (K) U Tangential speed (m/s) V Averaged fluid velocity (m/s) v Specific volume (m 3 /kg) vr Specific volume ratio % vr Percentage deviation between specific volume ratios W Work (N m/kg) X Compressibility function Schultz Y Compressibility function Schultz Z Compressibility factor. m Mass flow rate (kg/s) α Volume expansivity (1/K) η Efficiency µ Absolute viscosity (kg/m s) ν Kinematic viscosity (m 2 /s) ρ Density (kg/m 3 ) Φ Flow coefficient Subscripts imp, out corr d in is m max min out p recal s t vr Impeller outlet Corrected state Design condition or result Inlet Isentropic state Arithmetic mean Maximum value Minimum value Outlet Polytropic state Recalculation Static state Test condition or result Specific volume ratio References 1. Wang, X.; Amrane, K.; Johnson, P. Low global warming potential (GWP) alternative refrigerants evaluation program (Low-GWP AREP). In Proceedings International Refrigeration Air Conditioning Conference, West Lafayette, IN, USA, July 2012; Volume 2233, pp. 1 7.

21 Energies 2017, 10, Spatz, M.W.; Sethi, A.; Yana Motta, S.F. Latest Developments Low Global Warming Refrigerants for Chillers. In Proceedings International Refrigeration Air Conditioning Conference, West Lafayette, IN, USA, July 2012; Volume 2595, pp Ueda, K.; Hasegawa, Y.; Wajima, K.; Nitta, M.; Kamada, Y.; Yokoyama, A. Deployment a new series eco turbo ETI chillers. Mitsubishi Heavy Ind. Tech. Rev. 2012, 49, Brasz, J.J. Oil-free Centrifugal Refrigeration Compressors: From HFC134a to HFO1234ze (E). In Proceedings 8th International Conference on Compressors ir Systems, London, UK, 9 10 September 2013; pp Pearson, A.B. R-1234ze for Variable Speed Centrifugal Chillers. In Proceedings Institute Refrigeration Session ; The Institute Refrigeration: London, UK, 2013; pp Available online: http: //turbocor.com/uploaded/1304_pearson%20tg310%20in%20london.pdf (accessed on 4 September 2017). 6. Mota-Babiloni, A.; Navarro-Esbrí, J.; Barragan, A.; Moles, F.; Peris, B. Drop-in energy performance evaluation R1234yf R1234ze (E) in a vapor compression system as R134a replacements. Appl. Therm. Eng. 2014, 71, [CrossRef] 7. Wu, Y.; Thilges, C. Centrifugal Compressor Performance Deviations with Various Refrigerants, Impeller Sizes Shaft Speeds. In Proceedings International Compressor Engineering Conference, West Lafayette, IN, USA, July 2014; Volume 1225, pp Janković, Z.; Atienza, J.S.; Suárez, J.A.M. Thermodynamic heat transfer analyses for R1234yf R1234ze (E) as drop-in replacements for R134a in a small power refrigerating system. Appl. Therm. Eng. 2015, 80, [CrossRef] 9. Meng, Z.; Zhang, H.; Qiu, J.; Lei, M. Theoretical analysis R1234ze (E), R152a, R1234ze (E)/R152a mixtures as replacements R134a in vapor compression system. Adv. Mech. Eng. 2016, 8, [CrossRef] 10. Sethi, A.; Yana Motta, S. Low GWP Refrigerants for Air Conditioning Chiller Applications. In Proceedings International Refrigeration Air Conditioning Conference, West Lafayette, IN, USA, July 2016; Volume 2649, pp TRANE CenTraVac Chillers. Available online: us/en/products-systems/equipment/chillers/water-cooled-chiller/centrifugal-liquid-cooled-chillers/ earthwise-centravac.html (accessed on 4 September 2017). 12. Mitsubishi Heavy Industries. Development Centrifugal Chiller Heat Pump Using Low GWP Refrigerant. Available online: (accessed on 4 September 2017). 13. Danfoss Turbocor TG310. Available online: compressors-for-air-conditioning--heating/tg/#/ (accessed on 4 September 2017). 14. Air-Conditioning, Heating, Refrigeration Institute. AHRI Low GWP Alternative Refrigerants Evaluation Program Available online: (accessed on 1 August 2017). 15. ASME PTC-10:1997. Performance Test code on Compressors Exhausters; ASME: New York, NK, USA, Schultz, J.M. The polytropic analysis centrifugal compressors. J. Eng. Power 1962, 84, [CrossRef] 17. ISO 5389:2005. Turbocompressors Performance Test Code; International Organization for Stardization: Geneva, Switzerl, Lemmon, E.W.; Huber, M.L.; McLinden, M.O. NIST Stard Reference Database 23: Reference Fluid Thermodynamic Transport Properties REFPROP (Version 9.1); National Institute Stards Technology, Stard Reference Data Program: Gairsburg, MD, USA, HFO-1234yf, 1234ze(E), 1234ze(E), 1233zd(E), Refrigerant Mixtures in Answers to Frequently Asked Questions. Available online: (accessed on 1 February 2017). 20. Thol, M.; Lemmon, E.W. Equation State for Thermodynamic Properties trans-1,3,3,3-tetrafluoropropene [R-1234ze (E)]. Int. J. Thermophys. 2016, 37, 28. [CrossRef] 2017 by authors. Licensee MDPI, Basel, Switzerl. This article is an open access article distributed under terms conditions Creative Commons Attribution (CC BY) license (

Performance Comparison in Retrofit

Performance Comparison in Retrofit Influence of Heat Transfer Fluid Conditions in an Evaporator on Refrigerant Performance Comparison in Retrofit (Part 2: Evaporator) Influence of Heat Transfer Fluid Conditions in an Evaporator on Refrigerant

More information

CHAPTER 5 MASS AND ENERGY ANALYSIS OF CONTROL VOLUMES

CHAPTER 5 MASS AND ENERGY ANALYSIS OF CONTROL VOLUMES Thermodynamics: An Engineering Approach 8th Edition in SI Units Yunus A. Çengel, Michael A. Boles McGraw-Hill, 2015 CHAPTER 5 MASS AND ENERGY ANALYSIS OF CONTROL VOLUMES Lecture slides by Dr. Fawzi Elfghi

More information

BME-A PREVIOUS YEAR QUESTIONS

BME-A PREVIOUS YEAR QUESTIONS BME-A PREVIOUS YEAR QUESTIONS CREDITS CHANGE ACCHA HAI TEAM UNIT-1 Introduction: Introduction to Thermodynamics, Concepts of systems, control volume, state, properties, equilibrium, quasi-static process,

More information

Introduction to Turbomachinery

Introduction to Turbomachinery 1. Coordinate System Introduction to Turbomachinery Since there are stationary and rotating blades in turbomachines, they tend to form a cylindrical form, represented in three directions; 1. Axial 2. Radial

More information

Two mark questions and answers UNIT I BASIC CONCEPT AND FIRST LAW SVCET

Two mark questions and answers UNIT I BASIC CONCEPT AND FIRST LAW SVCET Two mark questions and answers UNIT I BASIC CONCEPT AND FIRST LAW 1. What do you understand by pure substance? A pure substance is defined as one that is homogeneous and invariable in chemical composition

More information

Department of Mechanical Engineering, Kasetsart University, Si Racha Campus, Chonburi, Thailand *

Department of Mechanical Engineering, Kasetsart University, Si Racha Campus, Chonburi, Thailand * Influence of heat transfer fluid conditions in a condenser on refrigerant performance comparison in retrofit (Part 1: condenser) Influence of Heat Transfer Fluid Conditions in a Condenser on Refrigerant

More information

ENERGY TRANSFER BETWEEN FLUID AND ROTOR. Dr. Ir. Harinaldi, M.Eng Mechanical Engineering Department Faculty of Engineering University of Indonesia

ENERGY TRANSFER BETWEEN FLUID AND ROTOR. Dr. Ir. Harinaldi, M.Eng Mechanical Engineering Department Faculty of Engineering University of Indonesia ENERGY TRANSFER BETWEEN FLUID AND ROTOR Dr. Ir. Harinaldi, M.Eng Mechanical Engineering Department Faculty of Engineering University of Indonesia Basic Laws and Equations Continuity Equation m m ρ mass

More information

CHME 302 CHEMICAL ENGINEERING LABOATORY-I EXPERIMENT 302-V FREE AND FORCED CONVECTION

CHME 302 CHEMICAL ENGINEERING LABOATORY-I EXPERIMENT 302-V FREE AND FORCED CONVECTION CHME 302 CHEMICAL ENGINEERING LABOATORY-I EXPERIMENT 302-V FREE AND FORCED CONVECTION OBJECTIVE The objective of the experiment is to compare the heat transfer characteristics of free and forced convection.

More information

Simple, stable and reliable modeling of gas properties of organic working fluids in aerodynamic designs of turbomachinery for ORC and VCC

Simple, stable and reliable modeling of gas properties of organic working fluids in aerodynamic designs of turbomachinery for ORC and VCC IOP Conference Series: Materials Science and Engineering PAPER OPEN ACCESS Simple, stable and reliable modeling of gas properties of organic working fluids in aerodynamic designs of turbomachinery for

More information

In this lecture... Centrifugal compressors Thermodynamics of centrifugal compressors Components of a centrifugal compressor

In this lecture... Centrifugal compressors Thermodynamics of centrifugal compressors Components of a centrifugal compressor Lect- 3 In this lecture... Centrifugal compressors Thermodynamics of centrifugal compressors Components of a centrifugal compressor Centrifugal compressors Centrifugal compressors were used in the first

More information

Property Data for Low-GWP Refrigerants: What Do We Know and What Don t We Know?

Property Data for Low-GWP Refrigerants: What Do We Know and What Don t We Know? Property Data for Low-GWP Refrigerants: What Do We Know and What Don t We Know? Mark O. McLinden Thermophysical Properties Division National Institute of Standards and Technology Boulder, Colorado USA

More information

Prof. Dr.-Ing. F.-K. Benra. ISE batchelor course

Prof. Dr.-Ing. F.-K. Benra. ISE batchelor course University Duisburg-Essen Campus Duisburg Faculty of engineering Science Department of Mechanical Engineering Examination: Fluid Machines Examiner: Prof. Dr.-Ing. F.-K. Benra Date of examination: 06.03.2006

More information

Contents. 2 Basic Components Aerofoils Force Generation Performance Parameters xvii

Contents. 2 Basic Components Aerofoils Force Generation Performance Parameters xvii Contents 1 Working Principles... 1 1.1 Definition of a Turbomachine... 1 1.2 Examples of Axial Turbomachines... 2 1.2.1 Axial Hydraulic Turbine... 2 1.2.2 Axial Pump... 4 1.3 Mean Line Analysis... 5 1.4

More information

10 minutes reading time is allowed for this paper.

10 minutes reading time is allowed for this paper. EGT1 ENGINEERING TRIPOS PART IB Tuesday 31 May 2016 2 to 4 Paper 4 THERMOFLUID MECHANICS Answer not more than four questions. Answer not more than two questions from each section. All questions carry the

More information

Principles of Turbomachinery

Principles of Turbomachinery Principles of Turbomachinery To J. M. T. Principles of Turbomachinery R. K. Turton Lecturer in Mechanical Engineering Loughborough University of Technology London New York E. & F. N. Spon ISBN 978-94-010-9691-1

More information

The Effects of Friction Factors on Capillary Tube Length

The Effects of Friction Factors on Capillary Tube Length The Effects of Friction Factors on Capillary Tube Length M.A. Akintunde, Ph.D. Department of Mechanical Engineering, Federal University of Technology, P.M.B. 7, Akure, Nigeria. E-mail: ajyinka@yahoo.com

More information

R13. II B. Tech I Semester Regular Examinations, Jan THERMODYNAMICS (Com. to ME, AE, AME) PART- A

R13. II B. Tech I Semester Regular Examinations, Jan THERMODYNAMICS (Com. to ME, AE, AME) PART- A SET - 1 II B. Tech I Semester Regular Examinations, Jan - 2015 THERMODYNAMICS (Com. to ME, AE, AME) Time: 3 hours Max. Marks: 70 Note 1. Question Paper consists of two parts (Part-A and Part-B) 2. Answer

More information

MECA-H-402: Turbomachinery course Axial compressors

MECA-H-402: Turbomachinery course Axial compressors MECA-H-40: Turbomachinery course Axial compressors Pr. Patrick Hendrick Aero-Thermo-Mecanics Year 013-014 Contents List of figures iii 1 Axial compressors 1 1.1 Introduction...............................

More information

An introduction to thermodynamics applied to Organic Rankine Cycles

An introduction to thermodynamics applied to Organic Rankine Cycles An introduction to thermodynamics applied to Organic Rankine Cycles By : Sylvain Quoilin PhD Student at the University of Liège November 2008 1 Definition of a few thermodynamic variables 1.1 Main thermodynamics

More information

Contents. 1 Introduction to Gas-Turbine Engines Overview of Turbomachinery Nomenclature...9

Contents. 1 Introduction to Gas-Turbine Engines Overview of Turbomachinery Nomenclature...9 Preface page xv 1 Introduction to Gas-Turbine Engines...1 Definition 1 Advantages of Gas-Turbine Engines 1 Applications of Gas-Turbine Engines 3 The Gas Generator 3 Air Intake and Inlet Flow Passage 3

More information

International Journal of Research in Advent Technology Available Online at:

International Journal of Research in Advent Technology Available Online at: A COMPUTER PROGRAMMED DESIGN OPTIMISATION AND ANALYSIS OF COMPRESSOR IMPELLER G. Naga Malleshwar Rao 1, Dr. S.L.V. Prasad 2, Dr. S. Sudhakarbabu 3 1, 2 Professor of Mechanical Engineering, Shri Shirdi

More information

Lecture 44: Review Thermodynamics I

Lecture 44: Review Thermodynamics I ME 00 Thermodynamics I Lecture 44: Review Thermodynamics I Yong Li Shanghai Jiao Tong University Institute of Refrigeration and Cryogenics 800 Dong Chuan Road Shanghai, 0040, P. R. China Email : liyo@sjtu.edu.cn

More information

Chapter 5. Mass and Energy Analysis of Control Volumes

Chapter 5. Mass and Energy Analysis of Control Volumes Chapter 5 Mass and Energy Analysis of Control Volumes Conservation Principles for Control volumes The conservation of mass and the conservation of energy principles for open systems (or control volumes)

More information

Modeling of Surge Characteristics in Turbo Heat Pumps

Modeling of Surge Characteristics in Turbo Heat Pumps Modeling of Surge Characteristics in Turbo Heat Pumps Hye Rim Kim e-mail: hrimkim@snu.ac.kr Seung Jin Song e-mail: sjsong@snu.ac.kr Mechanical and Aerospace Engineering, Seoul National University, Seoul

More information

1. (10) Calorically perfect ideal air at 300 K, 100 kpa, 1000 m/s, is brought to rest isentropically. Determine its final temperature.

1. (10) Calorically perfect ideal air at 300 K, 100 kpa, 1000 m/s, is brought to rest isentropically. Determine its final temperature. AME 5053 Intermediate Thermodynamics Examination Prof J M Powers 30 September 0 0 Calorically perfect ideal air at 300 K, 00 kpa, 000 m/s, is brought to rest isentropically Determine its final temperature

More information

First Law of Thermodynamics

First Law of Thermodynamics CH2303 Chemical Engineering Thermodynamics I Unit II First Law of Thermodynamics Dr. M. Subramanian 07-July-2011 Associate Professor Department of Chemical Engineering Sri Sivasubramaniya Nadar College

More information

Chapter 5. Mass and Energy Analysis of Control Volumes. by Asst. Prof. Dr.Woranee Paengjuntuek and Asst. Prof. Dr.Worarattana Pattaraprakorn

Chapter 5. Mass and Energy Analysis of Control Volumes. by Asst. Prof. Dr.Woranee Paengjuntuek and Asst. Prof. Dr.Worarattana Pattaraprakorn Chapter 5 Mass and Energy Analysis of Control Volumes by Asst. Prof. Dr.Woranee Paengjuntuek and Asst. Prof. Dr.Worarattana Pattaraprakorn Reference: Cengel, Yunus A. and Michael A. Boles, Thermodynamics:

More information

Where F1 is the force and dl1 is the infinitesimal displacement, but F1 = p1a1

Where F1 is the force and dl1 is the infinitesimal displacement, but F1 = p1a1 In order to force the fluid to flow across the boundary of the system against a pressure p1, work is done on the boundary of the system. The amount of work done is dw = - F1.dl1, Where F1 is the force

More information

UBMCC11 - THERMODYNAMICS. B.E (Marine Engineering) B 16 BASIC CONCEPTS AND FIRST LAW PART- A

UBMCC11 - THERMODYNAMICS. B.E (Marine Engineering) B 16 BASIC CONCEPTS AND FIRST LAW PART- A UBMCC11 - THERMODYNAMICS B.E (Marine Engineering) B 16 UNIT I BASIC CONCEPTS AND FIRST LAW PART- A 1. What do you understand by pure substance? 2. Define thermodynamic system. 3. Name the different types

More information

Prof. Dr.-Ing. F.-K. Benra. ISE Bachelor Course

Prof. Dr.-Ing. F.-K. Benra. ISE Bachelor Course University Duisburg-Essen Campus Duisburg Faculty of Engineering Science Department of Mechanical Engineering Name Matr.- Nr. Examination: Fluid Machines Examiner: Prof. Dr.-Ing. F.-K. Benra Date of examination:

More information

Please welcome for any correction or misprint in the entire manuscript and your valuable suggestions kindly mail us

Please welcome for any correction or misprint in the entire manuscript and your valuable suggestions kindly mail us Problems of Practices Of Fluid Mechanics Compressible Fluid Flow Prepared By Brij Bhooshan Asst. Professor B. S. A. College of Engg. And Technology Mathura, Uttar Pradesh, (India) Supported By: Purvi Bhooshan

More information

THE METHOD OF THE WORKING FLUID SELECTION FOR ORGANIC RANKINE CYCLE (ORC) SYSTEM WITH VOLUMETRIC EXPANDER. * Corresponding Author ABSTRACT

THE METHOD OF THE WORKING FLUID SELECTION FOR ORGANIC RANKINE CYCLE (ORC) SYSTEM WITH VOLUMETRIC EXPANDER. * Corresponding Author ABSTRACT Paper ID: 79, Page 1 THE METHOD OF THE WORKING FLUID SELECTION FOR ORGANIC RANKINE CYCLE (ORC) SYSTEM WITH VOLUMETRIC EXPANDER Piotr Kolasiński* 1 1 Wrocław University of Technology, Department of Thermodynamics,

More information

ISO 9906 INTERNATIONAL STANDARD. Rotodynamic pumps Hydraulic performance acceptance tests Grades 1 and 2

ISO 9906 INTERNATIONAL STANDARD. Rotodynamic pumps Hydraulic performance acceptance tests Grades 1 and 2 INTERNATIONAL STANDARD ISO 9906 First edition 1999-1-15 Rotodynamic pumps Hydraulic performance acceptance tests Grades 1 and Pompes rotodynamiques Essais de fonctionnement hydraulique pour la réception

More information

A computerized analytical model for evaluating hydrocarbon fluids as natural alternative refrigerants

A computerized analytical model for evaluating hydrocarbon fluids as natural alternative refrigerants ISSN 1 746-7233, England, UK World Journal of Modelling and Simulation Vol. 5 (2009) No. 3, pp. 232-240 A computerized analytical model for evaluating hydrocarbon fluids as natural alternative refrigerants

More information

SHORTCUT CALCULATIONS AND GRAPHICAL COMPRESSOR SELECTION PROCEDURES

SHORTCUT CALCULATIONS AND GRAPHICAL COMPRESSOR SELECTION PROCEDURES APPENDIX B SHORTCUT CALCULATIONS AND GRAPHICAL COMPRESSOR SELECTION PROCEDURES B.1 SELECTION GUIDE FOR ELLIOTT MULTISTAGE CENTRIFUGAL COMPRESSORS* * Reprinted from a 1994 Elliott Company sales bulletin.

More information

FE Exam Fluids Review October 23, Important Concepts

FE Exam Fluids Review October 23, Important Concepts FE Exam Fluids Review October 3, 013 mportant Concepts Density, specific volume, specific weight, specific gravity (Water 1000 kg/m^3, Air 1. kg/m^3) Meaning & Symbols? Stress, Pressure, Viscosity; Meaning

More information

(Refer Slide Time: 4:41)

(Refer Slide Time: 4:41) Fluid Machines. Professor Sankar Kumar Som. Department Of Mechanical Engineering. Indian Institute Of Technology Kharagpur. Lecture-30. Basic Principle and Energy Transfer in Centrifugal Compressor Part

More information

TOLERANCES AND UNCERTAINTIES IN PERFORMANCE DATA OF REFRIGERANT COMPRESSORS JANUARY 2017

TOLERANCES AND UNCERTAINTIES IN PERFORMANCE DATA OF REFRIGERANT COMPRESSORS JANUARY 2017 TOLERANCES AND UNCERTAINTIES IN PERFORMANCE DATA OF REFRIGERANT COMPRESSORS JANUARY 017 111 Wilson Blvd, Suite 500 Arlington, Virginia 01 USA +001 (703) 54-8800 Published by: TABLE OF CONTENTS SECTION

More information

ME 354 THERMODYNAMICS 2 MIDTERM EXAMINATION. Instructor: R. Culham. Name: Student ID Number: Instructions

ME 354 THERMODYNAMICS 2 MIDTERM EXAMINATION. Instructor: R. Culham. Name: Student ID Number: Instructions ME 354 THERMODYNAMICS 2 MIDTERM EXAMINATION February 14, 2011 5:30 pm - 7:30 pm Instructor: R. Culham Name: Student ID Number: Instructions 1. This is a 2 hour, closed-book examination. 2. Answer all questions

More information

EFFECT OF FORCED ROTATING VANELESS DIFFUSERS ON CENTRIFUGAL COMPRESSOR STAGE PERFORMANCE

EFFECT OF FORCED ROTATING VANELESS DIFFUSERS ON CENTRIFUGAL COMPRESSOR STAGE PERFORMANCE Journal of Engineering Science and Technology Vol. 6, No. 5 (2011) 558-574 School of Engineering, Taylor s University EFFECT OF FORCED ROTATING VANELESS DIFFUSERS ON CENTRIFUGAL COMPRESSOR STAGE PERFORMANCE

More information

Evaporation Heat Transfer Coefficients Of R-446A And R-1234ze(E)

Evaporation Heat Transfer Coefficients Of R-446A And R-1234ze(E) Proceedings of the 2 nd World Congress on Mechanical, Chemical, and Material Engineering (MCM'16) Budapest, Hungary August 22 23, 2016 Paper No. HTFF 144 DOI: 10.11159/htff16.144 Evaporation Heat Transfer

More information

c Dr. Md. Zahurul Haq (BUET) Thermodynamic Processes & Efficiency ME 6101 (2017) 2 / 25 T145 = Q + W cv + i h 2 = h (V2 1 V 2 2)

c Dr. Md. Zahurul Haq (BUET) Thermodynamic Processes & Efficiency ME 6101 (2017) 2 / 25 T145 = Q + W cv + i h 2 = h (V2 1 V 2 2) Thermodynamic Processes & Isentropic Efficiency Dr. Md. Zahurul Haq Professor Department of Mechanical Engineering Bangladesh University of Engineering & Technology (BUET Dhaka-1000, Bangladesh zahurul@me.buet.ac.bd

More information

Applied Fluid Mechanics

Applied Fluid Mechanics Applied Fluid Mechanics 1. The Nature of Fluid and the Study of Fluid Mechanics 2. Viscosity of Fluid 3. Pressure Measurement 4. Forces Due to Static Fluid 5. Buoyancy and Stability 6. Flow of Fluid and

More information

Chapter Two. Basic Thermodynamics, Fluid Mechanics: Definitions of Efficiency. Laith Batarseh

Chapter Two. Basic Thermodynamics, Fluid Mechanics: Definitions of Efficiency. Laith Batarseh Chapter Two Basic Thermodynamics, Fluid Mechanics: Definitions of Efficiency Laith Batarseh The equation of continuity Most analyses in this book are limited to one-dimensional steady flows where the velocity

More information

ME 201 Thermodynamics

ME 201 Thermodynamics Spring 01 ME 01 Thermodynamics Property Evaluation Practice Problems II Solutions 1. Air at 100 K and 1 MPa goes to MPa isenthapically. Determine the entropy change. Substance Type: Ideal Gas (air) Process:

More information

Dishwasher. Heater. Homework Solutions ME Thermodynamics I Spring HW-1 (25 points)

Dishwasher. Heater. Homework Solutions ME Thermodynamics I Spring HW-1 (25 points) HW-1 (25 points) (a) Given: 1 for writing given, find, EFD, etc., Schematic of a household piping system Find: Identify system and location on the system boundary where the system interacts with the environment

More information

Readings for this homework assignment and upcoming lectures

Readings for this homework assignment and upcoming lectures Homework #3 (group) Tuesday, February 13 by 4:00 pm 5290 exercises (individual) Thursday, February 15 by 4:00 pm extra credit (individual) Thursday, February 15 by 4:00 pm Readings for this homework assignment

More information

CHAPTER EIGHT P U M P I N G O F L I Q U I D S

CHAPTER EIGHT P U M P I N G O F L I Q U I D S CHAPTER EIGHT P U M P I N G O F L I Q U I D S Pupmps are devices for supplying energy or head to a flowing liquid in order to overcome head losses due to friction and also if necessary, to raise liquid

More information

SECOND ENGINEER REG. III/2 APPLIED HEAT

SECOND ENGINEER REG. III/2 APPLIED HEAT SECOND ENGINEER REG. III/2 APPLIED HEAT LIST OF TOPICS A B C D E F G H I J K Pressure, Temperature, Energy Heat Transfer Internal Energy, Thermodynamic systems. First Law of Thermodynamics Gas Laws, Displacement

More information

ME Thermodynamics I

ME Thermodynamics I Homework - Week 01 HW-01 (25 points) Given: 5 Schematic of the solar cell/solar panel Find: 5 Identify the system and the heat/work interactions associated with it. Show the direction of the interactions.

More information

MCE380: Measurements and Instrumentation Lab

MCE380: Measurements and Instrumentation Lab MCE380: Measurements and Instrumentation Lab Chapter 8: Flow Measurements Topics: Basic Flow Equations Flow Obstruction Meters Positive Displacement Flowmeters Other Methods Holman, Ch. 7 Cleveland State

More information

Theory of turbo machine Effect of Blade Configuration on Characteristics of Centrifugal machines. Unit 2 (Potters & Wiggert Sec

Theory of turbo machine Effect of Blade Configuration on Characteristics of Centrifugal machines. Unit 2 (Potters & Wiggert Sec Theory of turbo machine Effect of Blade Configuration on Characteristics of Centrifugal machines Unit (Potters & Wiggert Sec. 1..1, &-607) Expression relating Q, H, P developed by Rotary machines Rotary

More information

Akshay Khadse, Lauren Blanchette, Mahmood Mohagheghi, Jayanta Kapat

Akshay Khadse, Lauren Blanchette, Mahmood Mohagheghi, Jayanta Kapat Impact of S-CO2 Properties on Centrifugal Compressor Impeller: Comparison of Two Loss Models for Mean Line Analyses The Supercritical CO2 Power Cycles Symposium 2016 Akshay Khadse, Lauren Blanchette, Mahmood

More information

Design of Multistage Turbine

Design of Multistage Turbine Turbomachinery Lecture Notes 7-9-4 Design of Multistage Turbine Damian Vogt Course MJ49 Nomenclature Subscripts Symbol Denotation Unit c Absolute velocity m/s c p Specific heat J/kgK h Enthalpy J/kg m&

More information

MAE 11. Homework 8: Solutions 11/30/2018

MAE 11. Homework 8: Solutions 11/30/2018 MAE 11 Homework 8: Solutions 11/30/2018 MAE 11 Fall 2018 HW #8 Due: Friday, November 30 (beginning of class at 12:00p) Requirements:: Include T s diagram for all cycles. Also include p v diagrams for Ch

More information

Turbomachinery. Hasan Ozcan Assistant Professor. Mechanical Engineering Department Faculty of Engineering Karabuk University

Turbomachinery. Hasan Ozcan Assistant Professor. Mechanical Engineering Department Faculty of Engineering Karabuk University Turbomachinery Hasan Ozcan Assistant Professor Mechanical Engineering Department Faculty of Engineering Karabuk University Introduction Hasan Ozcan, Ph.D, (Assistant Professor) B.Sc :Erciyes University,

More information

Prof. Dr.-Ing. F.-K. Benra. ISE Bachelor Course

Prof. Dr.-Ing. F.-K. Benra. ISE Bachelor Course University Duisburg-Essen Campus Duisburg Faculty of Engineering Science Examination: Fluid Machines Examiner: Prof. Dr.-Ing. F.-K. Benra Date of examination: 07.08.2006 Handling time: 120 Minutes ISE

More information

Journal of Mechatronics, Electrical Power, and Vehicular Technology

Journal of Mechatronics, Electrical Power, and Vehicular Technology J. Mechatron. Electr. Power Veh. Technol 06 (2015) 39 8 Journal of Mechatronics, Electrical Power, and Vehicular Technology e-issn:2088-6985 p-issn: 2087-3379 www.mevjournal.com GEOMETRY ANALYSIS AND EFFECT

More information

II/IV B.Tech (Regular) DEGREE EXAMINATION. (1X12 = 12 Marks) Answer ONE question from each unit.

II/IV B.Tech (Regular) DEGREE EXAMINATION. (1X12 = 12 Marks) Answer ONE question from each unit. Page 1 of 8 Hall Ticket Number: 14CH 404 II/IV B.Tech (Regular) DEGREE EXAMINATION June, 2016 Chemical Engineering Fourth Semester Engineering Thermodynamics Time: Three Hours Maximum : 60 Marks Answer

More information

Chapter 7. Entropy. by Asst.Prof. Dr.Woranee Paengjuntuek and Asst. Prof. Dr.Worarattana Pattaraprakorn

Chapter 7. Entropy. by Asst.Prof. Dr.Woranee Paengjuntuek and Asst. Prof. Dr.Worarattana Pattaraprakorn Chapter 7 Entropy by Asst.Prof. Dr.Woranee Paengjuntuek and Asst. Prof. Dr.Worarattana Pattaraprakorn Reference: Cengel, Yunus A. and Michael A. Boles, Thermodynamics: An Engineering Approach, 5th ed.,

More information

Radial Compressors. Damian Vogt Course MJ2429. Nomenclature

Radial Compressors. Damian Vogt Course MJ2429. Nomenclature Turbomachinery Lecture Notes 1 007-10-04 Radial Compressors Damian Vogt Course MJ49 Nomenclature Subscripts Symbol Denotation Unit c Absolute velocity m/s h Enthalpy J/kg m& Mass flow rate kg/s r Radius

More information

ME 201 Thermodynamics

ME 201 Thermodynamics ME 0 Thermodynamics Solutions First Law Practice Problems. Consider a balloon that has been blown up inside a building and has been allowed to come to equilibrium with the inside temperature of 5 C and

More information

first law of ThermodyNamics

first law of ThermodyNamics first law of ThermodyNamics First law of thermodynamics - Principle of conservation of energy - Energy can be neither created nor destroyed Basic statement When any closed system is taken through a cycle,

More information

MATHEMATICAL MODEL OF A VAPOUR ABSORPTION REFRIGERATION UNIT

MATHEMATICAL MODEL OF A VAPOUR ABSORPTION REFRIGERATION UNIT ISSN 1726-4529 Int j simul model 9 (2010) 2, 86-97 Original scientific paper MATHEMATICAL MODEL OF A VAPOUR ABSORPTION REFRIGERATION UNIT Micallef, D. & Micallef, C. University of Malta, Department of

More information

QUESTION BANK UNIT-1 INTRODUCTION. 2. State zeroth law of thermodynamics? Write its importance in thermodynamics.

QUESTION BANK UNIT-1 INTRODUCTION. 2. State zeroth law of thermodynamics? Write its importance in thermodynamics. QUESTION BANK UNIT-1 INTRODUCTION 1. What do you mean by thermodynamic equilibrium? How does it differ from thermal equilibrium? [05 Marks, June-2015] 2. State zeroth law of thermodynamics? Write its importance

More information

ME 2322 Thermodynamics I PRE-LECTURE Lesson 10 Complete the items below Name:

ME 2322 Thermodynamics I PRE-LECTURE Lesson 10 Complete the items below Name: Lesson 10 1. (5 pt) If P > P sat (T), the phase is a subcooled liquid. 2. (5 pt) if P < P sat (T), the phase is superheated vapor. 3. (5 pt) if T > T sat (P), the phase is superheated vapor. 4. (5 pt)

More information

I. (20%) Answer the following True (T) or False (F). If false, explain why for full credit.

I. (20%) Answer the following True (T) or False (F). If false, explain why for full credit. I. (20%) Answer the following True (T) or False (F). If false, explain why for full credit. Both the Kelvin and Fahrenheit scales are absolute temperature scales. Specific volume, v, is an intensive property,

More information

TURBOMACHINES. VIJAYAVITHAL BONGALE Associate Professor and Head Department of Mechanical Engineering Malnad College of Engineering, Hassan

TURBOMACHINES. VIJAYAVITHAL BONGALE Associate Professor and Head Department of Mechanical Engineering Malnad College of Engineering, Hassan TURBOMACHINES VIJAYAVITHAL BONGALE Associate Professor and Head Department of Mechanical Engineering Malnad College of Engineering, Hassan 573 201. Mobile No:9448821954 E-mail : vvb@mcehassan.ac.in 1 Dimensional

More information

Heat Transfer Predictions for Carbon Dioxide in Boiling Through Fundamental Modelling Implementing a Combination of Nusselt Number Correlations

Heat Transfer Predictions for Carbon Dioxide in Boiling Through Fundamental Modelling Implementing a Combination of Nusselt Number Correlations Heat Transfer Predictions for Carbon Dioxide in Boiling Through Fundamental Modelling Implementing a Combination of Nusselt Number Correlations L. Makaum, P.v.Z. Venter and M. van Eldik Abstract Refrigerants

More information

MAHALAKSHMI ENGINEERING COLLEGE

MAHALAKSHMI ENGINEERING COLLEGE MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI-621213. Department: Mechanical Subject Code: ME2202 U N IT - 1 Semester: III Subject Name: ENGG. THERMODYNAMICS 1. 1 kg of gas at 1.1 bar, 27 o C is compressed

More information

A NEW METHOD FOR PREDICITING THE PERFORAMNCE MAP OF A SINGLE STAGE OF A CENTRIFUGAL COMPRESSOR

A NEW METHOD FOR PREDICITING THE PERFORAMNCE MAP OF A SINGLE STAGE OF A CENTRIFUGAL COMPRESSOR Proceedings of the 1st Global Power and Propulsion Forum GPPF 2017 Jan 16-18, 2014, Zurich, Switzerland www.pps.global GPPF-2017-119 A NEW METHOD FOR PREDICITING THE PERFORAMNCE MAP OF A SINGLE STAGE OF

More information

THE VAPOR COMPRESSION REFRIGERATION PROCESS

THE VAPOR COMPRESSION REFRIGERATION PROCESS SUSTAINABLE ENERGY UTILIZATION - COMPUTER LAB 2 SEU-CL2 THE VAPOR COMPRESSION REFRIGERATION PROCESS OBJECTIVES The primary objective of this computer lab is to develop a simple model of the vapour compression

More information

Chapter 6. Using Entropy

Chapter 6. Using Entropy Chapter 6 Using Entropy Learning Outcomes Demonstrate understanding of key concepts related to entropy and the second law... including entropy transfer, entropy production, and the increase in entropy

More information

Content. Entropy and principle of increasing entropy. Change of entropy in an ideal gas.

Content. Entropy and principle of increasing entropy. Change of entropy in an ideal gas. Entropy Content Entropy and principle of increasing entropy. Change of entropy in an ideal gas. Entropy Entropy can be viewed as a measure of molecular disorder, or molecular randomness. As a system becomes

More information

PUMP SYSTEM ANALYSIS AND SIZING. BY JACQUES CHAURETTE p. eng.

PUMP SYSTEM ANALYSIS AND SIZING. BY JACQUES CHAURETTE p. eng. PUMP SYSTEM ANALYSIS AND SIZING BY JACQUES CHAURETTE p. eng. 5 th Edition February 2003 Published by Fluide Design Inc. www.fluidedesign.com Copyright 1994 I TABLE OF CONTENTS Introduction Symbols Chapter

More information

CHAPTER 7 ENTROPY. Copyright Hany A. Al-Ansary and S. I. Abdel-Khalik (2014) 1

CHAPTER 7 ENTROPY. Copyright Hany A. Al-Ansary and S. I. Abdel-Khalik (2014) 1 CHAPTER 7 ENTROPY S. I. Abdel-Khalik (2014) 1 ENTROPY The Clausius Inequality The Clausius inequality states that for for all cycles, reversible or irreversible, engines or refrigerators: For internally-reversible

More information

Refrigeration. 05/04/2011 T.Al-Shemmeri 1

Refrigeration. 05/04/2011 T.Al-Shemmeri 1 Refrigeration is a process of controlled removal of heat from a substance to keep it at a temperature below the ambient condition, often below the freezing point of water (0 O C) 05/04/0 T.Al-Shemmeri

More information

Design of a Refrigerator. Department of Aerospace and Mechanical Engineering. Abdallah Soliman. Masih Ahmed. Ryan Seballos. EMAE 355 Project 4

Design of a Refrigerator. Department of Aerospace and Mechanical Engineering. Abdallah Soliman. Masih Ahmed. Ryan Seballos. EMAE 355 Project 4 Design of a Refrigerator Department of Aerospace and Mechanical Engineering Abdallah Soliman Masih Ahmed Ryan Seballos EMAE 355 Project 4 Professor Dr. J.R. Kadambi Teaching Assistants Bo Tan Henry Brown

More information

Performance characteristics of turbo blower in a refuse collecting system according to operation conditions

Performance characteristics of turbo blower in a refuse collecting system according to operation conditions Journal of Mechanical Science and Technology 22 (2008) 1896~1901 Journal of Mechanical Science and Technology www.springerlink.com/content/1738-494x DOI 10.1007/s12206-008-0729-6 Performance characteristics

More information

MAE 320 HW 7B. 1e. For an isolated system, please circle the parameter which will change with time. (a) Total energy;

MAE 320 HW 7B. 1e. For an isolated system, please circle the parameter which will change with time. (a) Total energy; MAE 320 HW 7B his comprehensive homework is due Monday, December 5 th, 206. Each problem is worth the points indicated. Copying of the solution from another is not acceptable. Multi-choice, multi-answer

More information

TankExampleNov2016. Table of contents. Layout

TankExampleNov2016. Table of contents. Layout Table of contents Task... 2 Calculation of heat loss of storage tanks... 3 Properties ambient air Properties of air... 7 Heat transfer outside, roof Heat transfer in flow past a plane wall... 8 Properties

More information

Performance Investigation of High Pressure Ratio Centrifugal Compressor using CFD

Performance Investigation of High Pressure Ratio Centrifugal Compressor using CFD International Journal of Ignited Minds (IJIMIINDS) Performance Investigation of High Pressure Ratio Centrifugal Compressor using CFD Manjunath DC a, Rajesh b, Dr.V.M.Kulkarni c a PG student, Department

More information

Dr Ali Jawarneh. Hashemite University

Dr Ali Jawarneh. Hashemite University Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University Examine the moving boundary work or P d work commonly encountered in reciprocating devices such as automotive engines and compressors.

More information

CERN, 1211 Geneva 23, Switzerland *Laboratoire des Signaux et Systèmes, UMR 8506 CNRS-Supélec, Gif-sur-Yvette, France

CERN, 1211 Geneva 23, Switzerland *Laboratoire des Signaux et Systèmes, UMR 8506 CNRS-Supélec, Gif-sur-Yvette, France Proceedings of ICEC 22-ICMC 2008, edited by Ho-Myung CHANG et al. c 2009 The Korea Institute of Applied Superconductivity and Cryogenics 978-89-957138-2-2 Dynamic Simulation of a 1.8K Refrigeration Unit

More information

CLASS Fourth Units (Second part)

CLASS Fourth Units (Second part) CLASS Fourth Units (Second part) Energy analysis of closed systems Copyright The McGraw-Hill Companies, Inc. Permission required for reproduction or display. MOVING BOUNDARY WORK Moving boundary work (P

More information

a. Key Laboratory of Efficient Utilization of Low and Medium Grade Energy, MOE, Tianjin University, Tianjin , China

a. Key Laboratory of Efficient Utilization of Low and Medium Grade Energy, MOE, Tianjin University, Tianjin , China Research on condensation heat transfer characteristics of R7A, R13ze, R13a and R3 in multi-port micro-channel tubes Minxia Li a*, Qiang Guo a, Jiatong Lv a a. Key Laboratory of Efficient Utilization of

More information

3 Energy Exchange in Turbomachines

3 Energy Exchange in Turbomachines 3 Energy Exchange in Turbomachines Problem 1 The solved and unsolved examples of this chapter are meant to illustrate the various forms of velocity triangles and the variety of the turbomachines. In addition,

More information

Performance Predictions of Dry and Wet Vapors Ejectors Over Entire Operational Range

Performance Predictions of Dry and Wet Vapors Ejectors Over Entire Operational Range energies Article Performance Predictions of Dry and Wet Vapors Ejectors Over Entire Operational Range Fenglei Li 1, Zhao Chang 1, Qi Tian 1, *, Changzhi Wu and Xiangyu Wang 1 College of Environmental Science

More information

Convection Heat Transfer. Introduction

Convection Heat Transfer. Introduction Convection Heat Transfer Reading Problems 12-1 12-8 12-40, 12-49, 12-68, 12-70, 12-87, 12-98 13-1 13-6 13-39, 13-47, 13-59 14-1 14-4 14-18, 14-24, 14-45, 14-82 Introduction Newton s Law of Cooling Controlling

More information

5/6/ :41 PM. Chapter 6. Using Entropy. Dr. Mohammad Abuhaiba, PE

5/6/ :41 PM. Chapter 6. Using Entropy. Dr. Mohammad Abuhaiba, PE Chapter 6 Using Entropy 1 2 Chapter Objective Means are introduced for analyzing systems from the 2 nd law perspective as they undergo processes that are not necessarily cycles. Objective: introduce entropy

More information

Investigations Of Heat Transfer And Components Efficiencies In Two-Phase Isobutane Injector

Investigations Of Heat Transfer And Components Efficiencies In Two-Phase Isobutane Injector Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering July 208 Investigations Of Heat Transfer And Components Efficiencies In Two-Phase

More information

Experimental Investigation on the Acoustic Scattering Matrix for a Centrifugal Pump

Experimental Investigation on the Acoustic Scattering Matrix for a Centrifugal Pump Proceedings Experimental Investigation on the Acoustic Scattering Matrix for a Centrifugal Pump Guidong Li 1,2, Jorge Parrondo 1, * and Yang Wang 2 1 Department of Energy, University of Oviedo, Campus

More information

Introduction to Fluid Machines and Compressible Flow Prof. S. K. Som Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

Introduction to Fluid Machines and Compressible Flow Prof. S. K. Som Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Introduction to Fluid Machines and Compressible Flow Prof. S. K. Som Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture - 21 Centrifugal Compressor Part I Good morning

More information

Applied Fluid Mechanics

Applied Fluid Mechanics Applied Fluid Mechanics 1. The Nature of Fluid and the Study of Fluid Mechanics 2. Viscosity of Fluid 3. Pressure Measurement 4. Forces Due to Static Fluid 5. Buoyancy and Stability 6. Flow of Fluid and

More information

Axial Flow and Radial Flow Gas Turbines

Axial Flow and Radial Flow Gas Turbines 7 Axial Flow and Radial Flow Gas Turbines 7.1 INTRODUCTION TO AXIAL FLOW TURBINES The axial flow gas turbine is used in almost all applications of gas turbine power plant. Development of the axial flow

More information

Chapter 1 Introduction and Basic Concepts

Chapter 1 Introduction and Basic Concepts Chapter 1 Introduction and Basic Concepts 1-1 Thermodynamics and Energy Application Areas of Thermodynamics 1-2 Importance of Dimensions and Units Some SI and English Units Dimensional Homogeneity Unity

More information

CEA Saclay Seminar. Cryogenic Research for HTS Transmission Cables in Korea

CEA Saclay Seminar. Cryogenic Research for HTS Transmission Cables in Korea CEA Saclay Seminar Cryogenic Research for HTS Transmission Cables in Korea Overview 10 min 10 kw Brayton Refrigerator 10 min He-LN 2 Heat Exchanger 15 min Cryogenic Design for Future 15 min April 22, 2016

More information

Applied Fluid Mechanics

Applied Fluid Mechanics Applied Fluid Mechanics 1. The Nature of Fluid and the Study of Fluid Mechanics 2. Viscosity of Fluid 3. Pressure Measurement 4. Forces Due to Static Fluid 5. Buoyancy and Stability 6. Flow of Fluid and

More information

Feasibility Study of Replacing Steam Ejector with Liquid Ring Vacuum Pump (LRVP) in 210 MW Plant of Vijayawada Thermal Power Station (V.T.P.

Feasibility Study of Replacing Steam Ejector with Liquid Ring Vacuum Pump (LRVP) in 210 MW Plant of Vijayawada Thermal Power Station (V.T.P. Feasibility Study of Replacing Steam Ejector with Liquid Ring Vacuum Pump (LRVP) in 210 MW Plant of Vijayawada Thermal Power Station (V.T.P.S) V.SAIRAM M.Tech student, Department of Mechanical Engineering

More information