Power Quality. Guide for electrical design engineers. Power Quality. Mitigation of voltage unbalance
|
|
- Antony Waters
- 6 years ago
- Views:
Transcription
1 Guide for electrical design engineers Power Quality Zbigniew Hanzelka GH-University of Science & Technology Mitigation of voltage unbalance U U = C = - = L U U = - U = - U Power Quality
2 Power Quality. ntroduction When the limit values of unbalance factor, specified in standards are exceeded, the use of symmetrizatin systems is required. symmetrizator should not cause significant active power losses during operation; it implies that the symmetrization process shall be carried out by means of reactive elements (LC) or using active methods (power electronic systems).. Symmetrization of the load currents The further analysis, using the method of symmetrical components, concerns the system node in the configuration as in Figure. n asymmetrical load (), symmetrical load (S) and compensator (K) are connected to substation busbars of phase voltage U, supplied from three-phase symmetrical system. COMPENSTOR (K) K K E E E U U U SYMETRC LOD (S) SYMETRC LOD () Fig.. Diagram of the analysed node Since the system of electromotive forces (E) and the supply line are symmetrical, it is assumed that the voltage unbalance at the load terminals is caused by the asymmetry of the load currents. t means that, if the asymmetry of the load currents is eliminated, the voltages at the point of the load connection form the symmetrical three-phase system. This is the case of the supply system protection, and the loads connected to it, against the asymmetry caused by asymmetrical currents of the load () and resulting asymmetrical voltage drops across the equivalent impedances of supply system (on assumption identical in all phases: Z= Z= Z). n obvious conclusion from Figure is that the voltage unbalance at PCC, caused by the load asymmetry, can be mitigated by reduction of the phase equivalent impedances (short-circuit impedances) i.e. by increasing the short-circuit capacity at the point of load connection, what in practice means connecting the load to the point of the system of higher voltage.. The natural symmetrization The first and the most basic operation of the symmetrization process is the arrangement of the actual load connections between the system phases, in such a way that the current unbalance factor (and hence the voltage unbalance factor) was the smallest possible value. n case of connecting a single load to the network, the level of unbalance (measured by the current unbalance factor for zero- or negative-sequence component) does not depend on phase-to-phase or phase-to-neutral voltage, where the load is connected. Similarly, when connecting two singleelement loads, the level of unbalance does not depend on which voltages the loads are connected. However, when these loads will have a different character then, in terms of the natural symmetrization (i.e. the symmetrization, which does not require any additional elements), it is important to take into account the character of the loads and phase angles of the voltages they are connected to.
3 EXMPLE Mitigation of voltage unbalance For the system of three loads on nominal voltage 8 V and powers, respectively: P = 7. kw, Q = 7. kvr (ind.); P = 7. kw, Q = 7. kvr (cap.); P = 7. kw, Q = delta-connected, supplied from three-phase x8/v network, determine the arrangement of their connections to the network phases, ensuring minimum value of the current unbalance factor. From the load active and reactive power the elements of its equivalent admittance can be determined, i.e.: the Q susceptance (B = U ) and conductance (G = P ) (Fig. ). U U N Load (P, Q) U N B G Y Hence: Fig.. The load (P - active power, Q - reactive power) and its equivalent admittance P Y G jb j Q 7. kw 7. kvr = + = = j = (.5 j. 5) S U U ( 8V ) ( 8V ) P Y G jb j Q 7. kw 7. kvr = + = + = + j = (.5+ j. 5) S U U ( 8V ) ( 8V ) P Y G jb j Q 7. kw kvr = + = + = + j =. S U U ( 8V ) ( 8V ) Variant Loads connected as in Fig. : Y Y Y Y = Y = Y = Y Y Y Fig.. Variant of load connection The current unbalance factor: k % ( ) a Y+ Y+ ay = % = % = 68. % () Y + Y + Y a= exp( j ) = + j a = exp( j ) = j
4 Power Quality 4 Three-wire network voltages 4 Three-wire network currents Voltages [V] - Currents [] Time [s] Time [s] Fig. 4. Voltage waveforms: Example Variant Fig. 5. Current waveforms: Example Variant See Figures 4 and 5. Variant - Y = Y Y = Y Y = Y The current unbalance factor: k % ( ) a Y+ Y+ ay = % = % = 8. % () Y + Y + Y This is the minimal value of the current unbalance factor, which can be obtained connecting the impedances to phase-to-phase voltages in various configurations. This configuration has been taken for further considerations (Fig. 6). 4 Three-wire network currents Currents [] Time [s] Fig. 6. Waveforms of currents: Example Variant n cases, where the negative component cannot be sufficiently reduced solely by means of the more uniform distribution of the loads between phases, compensators are used. The purpose of the compensation systems is usually the elimination or mitigation of the negative- and zero-sequence component of currents at the point of connection of asymmetric load. Such process is called symmetrization. 4. Compensator/symmetrizator n the three wire MV systems, usually operated as the isolated neutral point or compensated systems, asymmetrical loads are connected on phase-to-phase voltages. n such case, there is no zero-sequence component of currents, therefore the symmetrization resolves into elimination or mitigation of the negative-sequence component. The LV systems are typically four-wire networks, with grounded neutral point, thus the negative-sequence and zerosequence components are present. The symmetrizator (K) is connected in parallel to the asymmetric load () (Fig. ). The symmetrizator causes the currents K, K, K, which adding to the load currents,,, result in the balanced system of the source currents,,, according to the equation: = + = + = a = + = a (7) K K K 4
5 Mitigation of voltage unbalance s the currents drawn from the network form a balanced system, therefore the negative-sequence and zero-sequence components are equal zero: ( ) ( ) = ( + a+ a ) = = ( + + ) = (8) The load to be balanced can be represented in general as a circuit of six elements in the star/delta connection (Fig. 4), where individual elements are connected to phase-to-neutral, as well as to phase-to-phase voltages. The impedances Z, Z, Z Z, Z Z (or admittances Y, Y, Y Y, YY ), which in the diagram represent the actual load, can be functions of time. Z ) Z ) ( Y ( Y Z ) Z ) ( Y ( Y Z ) Z ) ( Y ( Y Fig. 4. General diagram of the three-phase unbalanced load To establish the rules of compensation and symmetrization, the values of specified impedances should be assumed constant, and generally different from each other. This does not exclude considerations on their variability in time. These impedances can be regarded as a representation of the time-varying load, but only in the specific, selected instants of time the sampling instants. The set of such constant values of impedances represents the load at discrete instants of time. The compensation of asymmetric load will be understood as the compensation of reactive part of the positivesequence symmetrical component (reactive power compensation for the fundamental frequency) and of the zerosequence component (for three-phase, four-wire systems) and negative-sequence component for the fundamental frequency. mong various possible methods, the inductive-capacitive systems are of particular importance. Their practical applications are certain solutions of static follow-up compensators. 5. The compensator/symmetrizator parameters The symmetrization and compensation of the fundamental harmonic reactive current is a process, which in practice consists in connecting in parallel to the asymmetric load the asymmetric reactive elements (reactors, capacitors) of such values as to fulfil the conditions (9): ( ) ( ) K ( ) ( ) K () () K + = + = m + = (9) ( ) ( ) ( ) where:,, ( ) ( ) ( ), K, K, K are symmetrical components of the asymmetric load and compensator (index (K)) currents, respectively for the zero- (), positive- () and negative-sequence component; m () denotes the reactive part of the positive-sequence of the load current component (imaginary part in complex numbers notation); is the value of reactive current, which is the measure of the load non-compensating level permitted in the supply conditions by electrical power supplier. Thus, according to the presented notation, the processes of the reactive current compensation and symmetrization (for the zero-sequence and negative-sequence component) have been separated. 5
6 Power Quality For the load as in Fig. 4, the relations, describing the values of the negative- and zero-sequence symmetrical components can be written as follows (according to (8)): ( ) ( ) = U ( Y + ay + a Y ) a Y + Y + ay ( ) U Y a = ( + Y + ay ) (b) f the expressions () are not identically equal zero, and the asymmetry level is inadmissibly high, the load symmetrization is needed and can be made by connecting a symmetrization-compensating device with elements BK BK, BK, connected to the phase-to-neutral voltages and BK BK, BK, connected to the phase-to-phase voltages. The problem resolves into finding the compensating susceptances, which in connection with the admittances to be compensated will constitute a symmetric load. The relations, where the parameters of symmetrizator/compensator are expressed as a function of the equivalent impedances (admittances) of the load to be compensated/symmetrized, will be presented further in this paper. This is particularly useful when designing a symmetrizator. The symmetrizator parameters can be expressed as a function of other quantities, which describe a compensated load, i.e.: the current symmetrical components, values of phase currents or powers, instantaneous values of phase voltages and currents, etc. 6. Symmetrization of a star-connected load with neutral conductor elimination of the zero-sequence symmetrical component n this case the process of compensation comprises of two stages. The first one concerns the elimination of the zero-sequence symmetrical component elimination of the current in neutral conductor. The configuration in Fig. 5 has been taken for further considerations; it is distinguished by the minimum value of the current unbalance factor (the values of elements as in the EXMPLE ). (a) Y Y N Y EXMPLE Fig. 5. Three-phase four-wire network - star-connected load U= V U = a V U = av = UY = (. 5+ j, 5) = ( + j) = UY = ( 5. 6 j4. 6) = UY= ( j9. 5) ( ) N The current in neutral conductor: = = + + = ( 5. 6 j6. 6) where ( ) is the current zero-sequence symmetrical component. The negative-sequence symmetrical component: ( ) = ( + a + a) = (. 4+ j. 5) 6
7 Mitigation of voltage unbalance () The positive-sequence symmetrical component: = ( + a+ a ) = The current unbalance factor: k % ( ) = % = 5% () Y Y Y B K B K N Fig. 6. The elimination of the zero-sequence component (EXMPLE ) [] 4 Supply network currents [] 4 Supply network currents - - [] [s] current in neutral conductor 4 - [] [s] current in neutral conductor [s] Fig. 7. Waveforms of currents: EXMPLE before the elimination of zero-sequence component [s] Fig. 8. Waveforms of currents: EXMPLE after the elimination of zero-sequence component The elimination of the current zero-sequence component is performed by means of the two-element symmetrizator in the example configuration as in Fig. 6. Supply network currents: = U( Y + jbk ) = U( Y + jbk ) = U Y The condition for the current in neutral conductor to become zero takes form: Hence: + + = Reactive part of neutral current: m( + + ) = and ctive part of neutral current: Re( + + ) = Substituting the numerical values: B K -.5 = and.5 + B K.8.5B K = 7
8 Power Quality Hence: BK =. 789S BK =. 789S YΣ= Y + jbk = (. 5 j. 89) S YΣ= Y+ jbk = (. 5+ j. 89) S Y = Y + jb =. S Σ K = UYΣ = (. 5 j. 89) = ( j6. 58) = UYΣ = (. 6 j. 75) = UYΣ = ( + j9. 5) + + The current zero-sequence component has been eliminated (Fig. 8). 7. Symmetrization a three-wire load 7.. Symmetrization of a delta-connected load compensation and symmetrization of the admittance Y compensation of the reactive part of the load admittances B G G G G = B B = B + B + K B K G = + B G G G + + B = B + B + B K G G = + + B + B = B + B + G G () compensation and symmetrization of the admittance Y compensation and symmetrization of the admittance Y symmetrization of the load n practice, the susceptances of a static compensator perform both processes simultaneously, that means symmetrization and reactive current compensation and then the resulting values of the susceptance are defined by (), where B represents the permissible level of non-compensation. s it results from (), the three susceptances that are necessary for reactive current compensation and symmetrization can be expressed through real and imaginary components of the load admittance. The first elements of the right side of the relation () represent the components of the compensation susceptances, necessary for the compensation of the imaginary part of the adequate load admittance. The second element represents the components of the compensator that are necessary for the symmetrization of the real parts of the load admittance. These relations clearly indicate that the process of compensation can also be treated as an activity concerning each of the interphase load admittances separately. E.g. for the load Y compensation of the imaginary part is achieved through parallel connection of a susceptance (-B ) followed by symmetrization of the remaining part of such a single interphase load by connecting the symmetrizing susceptances respectively: (G / ) for the voltage U and (-G / ) for the voltage U. The compensation process of such a load with its indication diagrams has been presented in Fig. 9. For a symmetric system of supply voltages of positive sequence, such a circuit is equivalent to three star-connected resistors, each of them having a conductance G. 8
9 Mitigation of voltage unbalance The above considerations illustrate the well known Steinmetz rule of symmetrization, according to which any singlephase active load (or active-reactive one, after its equivalent susceptance has been compensated), connected e.g. between phases - (Fig. 9), can be symmetrized by means of reactive elements LC of such values, that the currents fulfil the relations (). = = () The obtained relations () transform any three-phase asymmetric load into the symmetric, resistive or resistiveinductive load with a defined level of reactive current. For a symmetric system of supply voltages of positive sequences the generated circuit is equivalent (for B = ) to three, star connected resistors, each having a conductance value G = G + G + G. The condition for the compensator elements selection can also be expressed as a function of the phase reactive powers of an asymmetric load: Q + Q = Q + Q = Q + Q = Q () K K K Q, Q, Q - the load phase reactive powers, Q K, Q K, Q K - the compensator phase reactive powers, Q - assumed non-compensating level. For the compensator delta-connected elements, the interphase reactive powers can be determined with respect to the load phase reactive powers, according to the relations: QK = Q Q + Q + Q QK =+ Q Q Q + Q () Q = Q + Q Q +Q K G = G C = = L = C G L (a) (b) 9
10 Power Quality U U = C = - = L U U = - U = - U EXMPLE (c) Fig. 9. (a) single-phase system before the symmetrization; (b) single-phase system with the symmetrizator; (c) phasor diagram, which illustrates the process of symmetrization For the loads configuration as in the EXMPLE Variant, susceptances of the delta-connected symmetrizator/ compensator are: BK = B ( G G) =. S BK = B ( G G) =S BK = B ( G G) =. S The sign + preceding the susceptance denotes its capacitive character, the sign - the inductive character. The capacitance of the capacitor connected between phases - is determined from the relation: C K = BK S F f =. π π 5Hz 67. μ The inductance of the reactor connected between phases - is determined from the relation: L K = = 5mH πfb π 5Hz. S K The load and compensator are shown in Fig.. fter connecting the compensator/symmetrizator: * * * = = ( j. ) 4. 89exp( j )
11 Mitigation of voltage unbalance * * * = = (. 945 j7. 988) 4. 87exp( j ) * * * = = ( j7. 987) 4. 87exp( j ) The phase currents of supply network constitute the three-phase symmetrical system. * * Y B K * Y B K Y B K * * * Fig.. Delta-connected asymmetric load with the symmetrizator 4 Three-wire network voltages Voltages [V] Time [s] 8 Three-wire network currents 6 4 Currents [] Time [s] Fig.. Voltage and current waveforms (EXMPLE )
12 Power Quality 7.. Star-connected asymmetrical load The symmetrization of a star-connected load is analysed after star-to-delta transformation. Further procedure of the symmetrizator parameters selection is analogical as in section Static compensators Reactive power static compensators are widely used in transmission and distribution systems, cooperating with medium and large power, rapidly variable loads, which are the most disturbing for the electric power system. Static compensators can perform various tasks, such as compensation of the fundamental component reactive power, symmetrization and mitigation of voltage fluctuations (flicker). lso some active filters configurations have a capability of symmetrization. 8.. Static VR compensators The purpose of a compensator (with control and measuring system) is to measure adequate electric quantities of the load and generate in the compensator such currents, that the resultant load: compensator compensated load, as seen from the supply network, was symmetrical, and the fundamental harmonic reactive current drawn from the network did not exceed the value permitted in the supply conditions. Generally, static compensators are the systems, which comprise reactors and/or capacitors controlled by means of semiconductor circuits. They can be treated as the values of susceptances, controlled according to the needs of compensation/symmetrization. Thyristors in these systems are used as switches or phase-controlled elements. n practice various solutions of compensators are applied. mong the most often used compensators is the FC/TCR compensator with fixed capacitor and controlled (variable) reactor current Compensator/symmetrizator FC/TCR So-called FC/TCR circuits are the most commonly used static Vr compensators/stabilizers in industry. They are composed of a Fixed Capacitor (FC) connected in parallel to a Thyristor-Controlled-Reactor (TCR). FC is most commonly a passive filter, filtering the harmonic/harmonics of a load and/or of the TCR. This solution is an example of the indirect compensation method in which the sum of the basic () TCR current harmonic TCR() and the load reactive current O() is constant, and equals the FC current FC() (Fig. a). The TCR current waveform for three sampled control angles α is shown in Figure b (single-phase circuit). The control angle (with respect to the positive voltage zerocrossing) and the basic current harmonic of TCR can vary in each supply voltage half-cycle, within the range of values π α (, π ). With the increase of the angle α the fundamental harmonic of the reactor current decreases, what is tantamount to the increase of its equivalent inductive reactance for this harmonic and to the decrease in the fundamental harmonic reactive power, drawn by the reactor. The fundamental harmonic of the reactor current is expressed by the formula: m TCR() ( α ) = UBK = ( K () FC() ) = [ ( π α) sin ( π α) ] (4) π where: α control angle of the switch T thyristors, FC() capacitor current, TCR() (α) reactor current (fundamental harmonic), m - the reactor current amplitude for α = π. Thyristor are fully conducting for α = π/. B is the controlled K susceptance of the TCR step, its value is controlled by changing the conduction angle of thyristors. The resultant compensator current i k (t) is the sum of the capacitor and reactor currents: i () t = i () t + i () t (5) k FC TCR
13 Mitigation of voltage unbalance f the current in the reactor branch is equal zero (α = π), then the compensator feeds reactive power to the supply network and its current has a capacitive character. When thyristors are fully conducting, and the reactor power is greater than the capacitor power, the compensator draws reactive power and its current has an inductive character. The compensator current is controlled from FCmax to TCRmax in a continuous manner. The disadvantage of this system is generation of the current harmonics, which results from the phase control of thyristor switch (Fig. c). n the three-phase configuration (Fig. a) the single-phase TCR s (as in Fig. ) are delta-connected in parallel with fixed capacitors; together they constitute a triangle of equivalent phase-to-phase susceptances for the supply network (Fig. b). Their values vary independently and continuously as a result of changes in the control angles (α, α, α ). This way, the circuit implements the Steinmetz procedure in order to compensate and symmetrize the three-phase load. Fig.. (a) Conceptual diagram; (b) TCR current waveforms; (c) harmonics amplitudes per unit of basic current component amplitude L (α ) K α C B K L ( α) K L (α ) α C K B K B K α C (a) Fig.. Diagram of FC/TCR static compensator (b)
14 Power Quality 8... TSC/TCR (Thyristor Switched Capacitor/ Thyristor Controlled Reactor) n this configuration a capacitor bank is divided into the steps, switched by means of thyristor C switches, according to the compensation/symmetrization needs. Synchronization of the instant of switching with respect to the supply voltage waveform guarantees elimination of overvoltages and inrush currents, normally associated with capacitor switching. lso reduced are the values of current high harmonics, as related to the FC/TCR structure of the same nominal power STTCOM The newest solutions of compensating systems are the STTCOM devices, based on C/DC converters. The STTCOM compensator can be considered as a controlled voltage source (VS inverter in GBT or GTO technology) connected to the power supply system through the reactors (Fig. 4), or as an inertialess, three-phase synchronous machine, whose phase voltages their amplitude, phase and frequency are independently controlled. The reactive power/ current flow is controlled by means of the voltage amplitude control. Due to the independent control in each phase of the system, the compensator enables voltage symmetrization by elimination of the negative-sequence component. The relationship between the values and phase angles of the supply network voltages (U bus ) and the compensator output voltages (U VSC ) (before and after the reactor X r Fig. 4) determines the value and character (inductive or capacitive) of the compensator current (power). t the zero phase shift between voltages U bus and U VSC, only reactive current flows. When U bus < U VSC the current is capacitive, for U bus > U VSC the current is inductive (Fig. 5). This way the compensator can be a source or a load of reactive power. The STTCOM compensators are characterized with the following basic features: they can simultaneously perform combine functions of reactive power compensation, load symmetrization and filtering of harmonics, do not require use of passive components; their overall dimensions are several times smaller than those of SVC compensators of analogical power, compared to the TSC/TCR and FC/TCR system they have better dynamic properties, due to the development in power electronics their prices show a declining tendency. i i u x u x u bus i X r u bus u bus u vsc u vsc u vsc LOD VSC Fig. 4. Schematic diagram of a compensator (VSC) connected to the supply network u bus u bus <u vsc >u vsc Fig. 5. Phasor diagrams for different relations between U bus and U VSC 8.. Static series compensators The series compensator can be provided with an additional - aside from the load voltage control - function of symmetrization. The concept of such a compensator and block diagram of the example design is shown in Fig. 6. The series voltages applied to individual phases of the system - ΔU XSR, (X =,, ) can be expressed as the sum of two three-phase systems, which execute two independent processes: - Symmetrization. This function is performed by means of the three-phase system of series voltages, determined on the basis of the measurement of negative-sequence component of load voltages. n result of adding appropriate components of series voltages ( ΔU XS for x =,, ) to the source voltages, the symmetric system of voltages is obtained at the point B (Fig. 6). 4
15 Mitigation of voltage unbalance - Stabilization of the voltage positive-sequence component value. For this purpose, to the source voltages has to be added the symmetric system of series voltages ( ΔU XR for x =,, ), which guarantees an increase or reduction of the load voltages, according to the stabilization needs Fig. 6. Unbalanced system of the supply network voltages ΔU S ΔU SR ΔU R Balanced voltages system with controlled values U ΔU SR U U ΔU S ΔU R ΔU SR U U ΔU S ΔU R SUPPLY NETWORK VOLTGES COMPENSTOR U LOD Fig. 6. Procedure of symmetrization and control of the load voltages by means of the series compensator The example of a practical system, shown in schematic diagram in Fig. 7, of comprises three single-phase dc/ac PWM converters connected in series with the supply line through three single-phase transformers. The load voltages are measured and used for determination of the symmetrical components and hence to the determination of the converters switching patterns, which ensure obtaining the series voltages. t is also possible to employ a three-phase inverter with asymmetrical switching functions in individual branches of the converter. The symmetrization and control / regulation of the load voltage are then performed by means of controlling the amplitude and phase angle of reference voltages. 5
16 Power Quality ΔU SR ΔU ΔU SR rectifier Filters of the voltage symmetrical components U () U () Control system (U () ) reference (U () ) reference References Fig. 7. The schematic diagram of series system of stabilization symmetrization of the load voltage. NS C84.: 995, merican national standard for electric power systems and equipment voltage ratings.. Engineering Recommendation P9: Planning limits for voltage unbalance in the United Kingdom. The Electricity Council (U.K.), Gyugyi L., Otto R.., Putman T.H.: Principles and applications of static, thyristor-controlled shunt compensators. EEE Transactions Vol. PS 97, no 5, Sep./Oct EC 6--, 99: Electromagnetic compatibility-part : Environment-Section : Description of the environment - Electromagnetic environment for low-frequency conducted disturbances and signalling in public power supply systems. 5. EC 6--5, 995: Electromagnetic compatibility-part : Environment-Section 5: Classification of electromagnetic environments. 6. EC --, 995: Electromagnetic compatibility-part : Environment-Section : Compatibility levels for low-frequency conducted disturbances and signalling in public medium-voltage power systems. 7. EC 6-4-7, : Electromagnetic compatibility Part 4-7: Testing and measurement techniques Unbalance, immunity test. 8. EEE P59.: Guide for recorder and data acquisition requirements for characterisation of power quality events. 9. Miller J. E.: Reactive power controlled in electric systems. John Willey & Sons 98.. UE Guide to quality of electrical supply for industrial installations. Part 4: Voltage unbalance This publication is subject to copyright and a disclaimer. Please refer to the Leonardo ENERGY website. 6
KINGS COLLEGE OF ENGINEERING Punalkulam
KINGS COLLEGE OF ENGINEERING Punalkulam 613 303 DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING POWER SYSTEM ANALYSIS QUESTION BANK UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A (TWO MARK
More informationLO 1: Three Phase Circuits
Course: EEL 2043 Principles of Electric Machines Class Instructor: Dr. Haris M. Khalid Email: hkhalid@hct.ac.ae Webpage: www.harismkhalid.com LO 1: Three Phase Circuits Three Phase AC System Three phase
More informationPower System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur
Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur Lecture - 9 Transmission Line Steady State Operation Welcome to lesson 9, in Power
More informationChapter 3 AUTOMATIC VOLTAGE CONTROL
Chapter 3 AUTOMATIC VOLTAGE CONTROL . INTRODUCTION TO EXCITATION SYSTEM The basic function of an excitation system is to provide direct current to the field winding of the synchronous generator. The excitation
More informationEE 6501 POWER SYSTEMS UNIT I INTRODUCTION
EE 6501 POWER SYSTEMS UNIT I INTRODUCTION PART A (2 MARKS) 1. What is single line diagram? A Single line diagram is diagrammatic representation of power system in which the components are represented by
More informationSinusoidal Response of RLC Circuits
Sinusoidal Response of RLC Circuits Series RL circuit Series RC circuit Series RLC circuit Parallel RL circuit Parallel RC circuit R-L Series Circuit R-L Series Circuit R-L Series Circuit Instantaneous
More informationSSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL
1 SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL Power Systems: Generation, Transmission and Distribution Power Systems: Generation, Transmission and Distribution Power Systems:
More informationIn the previous chapter, attention was confined
4 4 Principles of Power System CHAPTE CHAPTE 8 Unsymmetrical Fault Calculations 8. Usymmetrical Faults on -Phase System 8. Symmetrical Components Method 8. Operator a 8.4 Symmetrical Components in Terms
More informationSingle Phase Parallel AC Circuits
Single Phase Parallel AC Circuits 1 Single Phase Parallel A.C. Circuits (Much of this material has come from Electrical & Electronic Principles & Technology by John Bird) n parallel a.c. circuits similar
More informationLecture 05 Power in AC circuit
CA2627 Building Science Lecture 05 Power in AC circuit Instructor: Jiayu Chen Ph.D. Announcement 1. Makeup Midterm 2. Midterm grade Grade 25 20 15 10 5 0 10 15 20 25 30 35 40 Grade Jiayu Chen, Ph.D. 2
More informationmywbut.com Lesson 16 Solution of Current in AC Parallel and Seriesparallel
esson 6 Solution of urrent in Parallel and Seriesparallel ircuits n the last lesson, the following points were described:. How to compute the total impedance/admittance in series/parallel circuits?. How
More informationCHAPTER 6 STEADY-STATE ANALYSIS OF SINGLE-PHASE SELF-EXCITED INDUCTION GENERATORS
79 CHAPTER 6 STEADY-STATE ANALYSIS OF SINGLE-PHASE SELF-EXCITED INDUCTION GENERATORS 6.. INTRODUCTION The steady-state analysis of six-phase and three-phase self-excited induction generators has been presented
More informationModule 3 : Sequence Components and Fault Analysis
Module 3 : Sequence Components and Fault Analysis Lecture 12 : Sequence Modeling of Power Apparatus Objectives In this lecture we will discuss Per unit calculation and its advantages. Modeling aspects
More informationSHORT QUESTIONS AND ANSWERS. Year/ Semester/ Class : III/ V/ EEE Academic Year: Subject Code/ Name: EE6501/ Power System Analysis
Srividya colllege of Engg & Tech,Virudhunagar Sri Vidya College of Engineering And Technology Virudhunagar 626 005 Department of Electrical and Electronics Engineering QUESTION BANK SHORT QUESTIONS AND
More informationB.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis
B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester Electrical and Electronics Engineering EE 1352 Power System Analysis (Regulation 2008) Time: Three hours Answer all questions Part A (10
More informationBasics of Electric Circuits
António Dente Célia de Jesus February 2014 1 Alternating Current Circuits 1.1 Using Phasors There are practical and economic reasons justifying that electrical generators produce emf with alternating and
More informationELECTRIC POWER CIRCUITS BASIC CONCEPTS AND ANALYSIS
Contents ELEC46 Power ystem Analysis Lecture ELECTRC POWER CRCUT BAC CONCEPT AND ANALY. Circuit analysis. Phasors. Power in single phase circuits 4. Three phase () circuits 5. Power in circuits 6. ingle
More informationTotal No. of Questions :09] [Total No. of Pages : 03
EE 4 (RR) Total No. of Questions :09] [Total No. of Pages : 03 II/IV B.Tech. DEGREE EXAMINATIONS, APRIL/MAY- 016 Second Semester ELECTRICAL & ELECTRONICS NETWORK ANALYSIS Time: Three Hours Answer Question
More informationPower Factor Improvement
Salman bin AbdulazizUniversity College of Engineering Electrical Engineering Department EE 2050Electrical Circuit Laboratory Power Factor Improvement Experiment # 4 Objectives: 1. To introduce the concept
More informationProceedings of the 13th WSEAS International Conference on CIRCUITS
About some FACTS devices from the power systems MARICEL ADAM, ADRIAN BARABOI, CATALIN PANCU Power Systems Department, Faculty of Electrical Engineering Gh. Asachi Technical University 51-53, D. Mangeron,
More informationPower System Engineering Prof. Debapriya Das Department of Electrical Engineering Indian Institute of Technology, Kharagpur
Power System Engineering Prof. Debapriya Das Department of Electrical Engineering Indian Institute of Technology, Kharagpur Lecture 41 Application of capacitors in distribution system (Contd.) (Refer Slide
More informationEE Branch GATE Paper 2010
Q.1 Q.25 carry one mark each 1. The value of the quantity P, where, is equal to 0 1 e 1/e 2. Divergence of the three-dimensional radial vector field is 3 1/r 3. The period of the signal x(t) = 8 is 0.4
More informationChapter 15 Power And Harmonics in Nonsinusoidal Systems
Chapter 15 Power And Harmonics in Nonsinusoidal Systems 15.1. Average power in terms of Fourier series 15.2. RMS value of a waveform 15.3. Power factor THD Distortion and Displacement factors 15.4. Power
More informationHarmonic Domain Periodic Steady State Modeling of Power Electronics Apparatus: SVC and TCSC
960 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 18, NO. 3, JULY 2003 Harmonic Domain Periodic Steady State Modeling of Power Electronics Apparatus: SVC and TCSC Leonardo T. G. Lima, Member, IEEE, Adam Semlyen,
More informationDEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME: EE 2303 - TRANSMISSION & DISTRIBUTION YEAR / SEM: III/V UNIT-I TRANSMISSION SYSTEM INTRODUCTION PART-A 1. What is
More informationModule 4. Single-phase AC circuits. Version 2 EE IIT, Kharagpur
Module 4 Single-phase circuits ersion EE T, Kharagpur esson 6 Solution of urrent in Parallel and Seriesparallel ircuits ersion EE T, Kharagpur n the last lesson, the following points were described:. How
More informationCHAPTER 3 ANALYSIS OF THREE PHASE AND SINGLE PHASE SELF-EXCITED INDUCTION GENERATORS
26 CHAPTER 3 ANALYSIS OF THREE PHASE AND SINGLE PHASE SELF-EXCITED INDUCTION GENERATORS 3.1. INTRODUCTION Recently increase in energy demand and limited energy sources in the world caused the researchers
More informationF F FAULT CURRENT Prospective. 1. Introduction. 2. Types of fault conditions
FAULT CURRENT F F13-13 FAULT CURRENT - Contents 1. Introduction 2. Types of fault conditions 3 fault current must be determined 3.1 Purposes for which of prospective fault current magnitudes are used 3.2
More informationBridge Measurement 2.1 INTRODUCTION Advantages of Bridge Circuit
2 Bridge Measurement 2.1 INTRODUCTION Bridges are often used for the precision measurement of component values, like resistance, inductance, capacitance, etc. The simplest form of a bridge circuit consists
More informationPOWER SEMICONDUCTOR BASED ELECTRIC DRIVES
POWER SEMICONDUCT BASED ELECTRIC DRIVES [Time: 3 Hrs] [Max. Marks: 80] Instructions: Solve any six questions from Q.No (1 or 2), Q.No (3 or 4), Q.No (5 or 6), Q.No (7 or 8), Q.No (9 or 10), Q.No (11 or
More informationShunt Hybrid Power Filter combined with Thyristor- Controlled Reactor for Power Quality Improvement.
Shunt Hybrid Power Filter combined with Thyristor- Controlled Reactor for Power Quality Improvement. 1 Pallavi P, Pooja P S, Chethan H R, 4 Nandish B M 1, Student,,4 ssistant professor Electrical and Electronics
More informationBalanced three-phase systems and operation
ELEC0014 - Introduction to power and energy systems Balanced three-phase systems and operation Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct October 2017 1 / 17 system used for
More informationFault Calculation Methods
ELEC9713 Industrial and Commercial Power Systems Fault Calculation Methods There are two major problems that can occur in electrical systems: these are open circuits and short circuits. Of the two, the
More informationBrief Steady of Power Factor Improvement
International Journal of Electrical Engineering. ISSN 0974-2158 Volume 6, Number 5 (2013), pp. 531-539 International Research PublicationHouse http://www.irphouse.com Brief Steady of Power Factor Improvement
More informationThe Effects of Mutual Coupling and Transformer Connection Type on Frequency Response of Unbalanced Three Phases Electrical Distribution System
IJSRD - International Journal for Scientific Research & Development Vol. 1, Issue 9, 2013 ISSN (online): 2321-0613 The Effects of Mutual Coupling and Transformer Connection Type on Frequency Response of
More informationModeling & Simulation of Passive Shunt Filter for Power Quality Improvement Using TCR and TSC Combination By MATLAB/Simulink
Modeling & Simulation of Passive Shunt Filter for Power Quality Improvement Using TCR and TSC Combination By MATLAB/Simulink Neha Shaktawat*,Manjari Sharma** EEE departement, (M. Tech student) M.I.T. Mandsaur,
More informationHOW TO DEAL WITH ELECTROMAGNETIC DISTURBANCES CAUSED BY NEW INVERTER TECHNOLOGIES CONNECTED TO PUBLIC NETWORK
HOW TO DEAL WITH ELECTROMAGNETIC DISTURBANCES CAUSED BY NEW INVERTER TECHNOLOGIES CONNECTED TO PUBLIC NETWORK Xavier YANG EDF R&D - France xavier.yang@edf.fr Ludovic BERTIN EDF R&D - France ludovic-g.bertin@edf.fr
More informationBASIC NETWORK ANALYSIS
SECTION 1 BASIC NETWORK ANALYSIS A. Wayne Galli, Ph.D. Project Engineer Newport News Shipbuilding Series-Parallel dc Network Analysis......................... 1.1 Branch-Current Analysis of a dc Network......................
More informationReview of Basic Electrical and Magnetic Circuit Concepts EE
Review of Basic Electrical and Magnetic Circuit Concepts EE 442-642 Sinusoidal Linear Circuits: Instantaneous voltage, current and power, rms values Average (real) power, reactive power, apparent power,
More information400 Volts, 50HZ 480 Volts, 60HZ 600 Volts, 60HZ TECHNICAL REFERENCE MANUAL
400 Volts, 50HZ 480 Volts, 60HZ 600 Volts, 60HZ TECHNICAL REFERENCE MANUAL FORM: MAP-TRM-E REL. July 2013 REV. 015 2013 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation Matrix AP Harmonic
More informationAlternating Current Circuits
Alternating Current Circuits AC Circuit An AC circuit consists of a combination of circuit elements and an AC generator or source. The output of an AC generator is sinusoidal and varies with time according
More informationCHAPTER 5 STEADY-STATE ANALYSIS OF THREE-PHASE SELF-EXCITED INDUCTION GENERATORS
6 CHAPTER 5 STEADY-STATE ANALYSIS OF THREE-PHASE SELF-EXCITED INDUCTION GENERATORS 5.. INTRODUCTION The steady-state analysis of six-phase SEIG has been discussed in the previous chapters. In this chapter,
More informationCapacitor Application Issues
Capacitor Application Issues Thomas Blooming, P.E. Daniel J. Carnovale, P.E. IEEE Industry Applications Society 53 rd Pulp & Paper Industry Technical Conf. Williamsburg, Virginia June 24-29, 2007 Introduction
More informationEEE3405 ELECTRICAL ENGINEERING PRINCIPLES 2 - TEST
ATTEMPT ALL QUESTIONS (EACH QUESTION 20 Marks, FULL MAKS = 60) Given v 1 = 100 sin(100πt+π/6) (i) Find the MS, period and the frequency of v 1 (ii) If v 2 =75sin(100πt-π/10) find V 1, V 2, 2V 1 -V 2 (phasor)
More informationEE 3120 Electric Energy Systems Study Guide for Prerequisite Test Wednesday, Jan 18, pm, Room TBA
EE 3120 Electric Energy Systems Study Guide for Prerequisite Test Wednesday, Jan 18, 2006 6-7 pm, Room TBA First retrieve your EE2110 final and other course papers and notes! The test will be closed book
More informationWork, Energy and Power
1 Work, Energy and Power Work is an activity of force and movement in the direction of force (Joules) Energy is the capacity for doing work (Joules) Power is the rate of using energy (Watt) P = W / t,
More informationECE 476 Power System Analysis Fall 2014 Exam #1, Thursday, October 2, :30AM - 10:50AM
ECE 476 Power System Analysis Fall 4 Exam #, Thursday, October, 4. 9:3AM - :5AM Name: Problem (5 p) Two balanced 3-phase loads are connected in parallel. One is Y-connected and draws 75 kw (3-phase) at.8
More informationChapter 2 Voltage-, Current-, and Z-source Converters
Chapter 2 Voltage-, Current-, and Z-source Converters Some fundamental concepts are to be introduced in this chapter, such as voltage sources, current sources, impedance networks, Z-source, two-port network,
More informationCo-ordinated control of FACTS Devices using Optimal Power Flow Technique
International Journal of Engineering Research and Development eissn: 227867X, pissn: 22788X, www.ijerd.com Volume 11, Issue 12 (December 215), PP.112 Coordinated control of FACTS Devices using Optimal
More informationDISTURBANCE LOAD MODELLING WITH EQUIVALENT VOLTAGE SOURCE METHOD IN GRID HARMONIC ASSESSMENT
DISTURBANCE LOAD MODELLING WITH EQUIVALENT VOLTAGE SOURCE METHOD IN GRID HARMONIC ASSESSMENT Xavier YANG Xingyan NIU Bruno PASZKIER EDF R&D France EDF R&D China EDF R&D - France xavier.yang@edf.fr xingyan.niu@edf.fr
More informationSelected paper. Consistent circuit technique for zero-sequence currents evaluation in interconnected single/three-phase power networks
Diego Bellan 1,*, Sergio A. Pignari 1, Gabrio Superti- Furga 2 J. Electrical Systems Special issue AMPE2015 Selected paper Consistent circuit technique for zero-sequence currents evaluation in interconnected
More informationNotes on Electric Circuits (Dr. Ramakant Srivastava)
Notes on Electric ircuits (Dr. Ramakant Srivastava) Passive Sign onvention (PS) Passive sign convention deals with the designation of the polarity of the voltage and the direction of the current arrow
More informationTHREE PHASE SYSTEMS Part 1
ERT105: ELECTRCAL TECHNOLOGY CHAPTER 3 THREE PHASE SYSTEMS Part 1 1 Objectives Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate
More informationWeek No. 6 Chapter Six: Power Factor Improvement
Week No. 6 Chapter Six: Power Factor Improvement The electrical energy is almost wholly generated, transmitted and distributed in the form of alternating current. Therefore, the question of power factor
More informationSinusoidal Steady State Analysis (AC Analysis) Part I
Sinusoidal Steady State Analysis (AC Analysis) Part I Amin Electronics and Electrical Communications Engineering Department (EECE) Cairo University elc.n102.eng@gmail.com http://scholar.cu.edu.eg/refky/
More informationResearch of Hybrid Three-phase equilibrium Technology
IOP Conference Series: Earth and Environmental Science PAPER OPEN ACCESS Research of Hybrid Three-phase equilibrium Technology To cite this article: K Xu et al 2016 IOP Conf. Ser.: Earth Environ. Sci.
More informationHarmonic Modeling of Networks
Harmonic Modeling of Networks Thomas H. Ortmeyer ECE Dept. Clarkson University Potsdam, NY 13699-5720 M. Fayyaz Akram Dept. of Elec. Eng. Univ. of Engineering and Technology Lahore, Pakistan Takashi Hiyama
More informationFault Analysis Power System Representation
.1. Power System Representation Single Line Diagram: Almost all modern power systems are three phase systems with the phases of equal magnitude and equal phase difference (i.e., 10 o ). These three phase
More informationCHAPTER 2 CAPACITANCE REQUIREMENTS OF SIX-PHASE SELF-EXCITED INDUCTION GENERATORS
9 CHAPTER 2 CAPACITANCE REQUIREMENTS OF SIX-PHASE SELF-EXCITED INDUCTION GENERATORS 2.. INTRODUCTION Rapidly depleting rate of conventional energy sources, has led the scientists to explore the possibility
More informationECE 420. Review of Three Phase Circuits. Copyright by Chanan Singh, Panida Jirutitijaroen, and Hangtian Lei, For educational use only-not for sale.
ECE 40 Review of Three Phase Circuits Outline Phasor Complex power Power factor Balanced 3Ф circuit Read Appendix A Phasors and in steady state are sinusoidal functions with constant frequency 5 0 15 10
More information1 Phasors and Alternating Currents
Physics 4 Chapter : Alternating Current 0/5 Phasors and Alternating Currents alternating current: current that varies sinusoidally with time ac source: any device that supplies a sinusoidally varying potential
More informationTransmission and Distribution of Electrical Power
KINGDOM OF SAUDI ARABIA Ministry Of High Education Umm Al-Qura University College of Engineering & Islamic Architecture Department Of Electrical Engineering Transmission and Distribution of Electrical
More information4 Fault Calculations. Introduction 4.1. Three phase fault calculations 4.2. Symmetrical component analysis 4.3 of a three-phase network
ault Calculations ntroduction 4. Three phase fault calculations 4. Symmetrical component analysis 4.3 of a three-phase network Equations and network connections 4.4 for various types of faults Current
More informationTransmission Lines. Plane wave propagating in air Y unguided wave propagation. Transmission lines / waveguides Y. guided wave propagation
Transmission Lines Transmission lines and waveguides may be defined as devices used to guide energy from one point to another (from a source to a load). Transmission lines can consist of a set of conductors,
More informationAN019. A Better Approach of Dealing with Ripple Noise of LDO. Introduction. The influence of inductor effect over LDO
Better pproach of Dealing with ipple Noise of Introduction It has been a trend that cellular phones, audio systems, cordless phones and portable appliances have a requirement for low noise power supplies.
More informationElectrical Engineering Fundamentals for Non-Electrical Engineers
Electrical Engineering Fundamentals for Non-Electrical Engineers by Brad Meyer, PE Contents Introduction... 3 Definitions... 3 Power Sources... 4 Series vs. Parallel... 9 Current Behavior at a Node...
More informationUnit-3. Question Bank
Unit- Question Bank Q.1 A delta connected load draw a current of 15A at lagging P.F. of.85 from 400, -hase, 50Hz suly. Find & of each hase. Given P = = 400 0 I = 15A Ans. 4.98, 5.7mH So I P = 15 =8.66A
More informationEE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION
EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION PART: A 1. Define per unit value of an electrical quantity. Write equation for base impedance with respect to 3-phase system. 2. What is bus admittance
More informationLCR Series Circuits. AC Theory. Introduction to LCR Series Circuits. Module. What you'll learn in Module 9. Module 9 Introduction
Module 9 AC Theory LCR Series Circuits Introduction to LCR Series Circuits What you'll learn in Module 9. Module 9 Introduction Introduction to LCR Series Circuits. Section 9.1 LCR Series Circuits. Amazing
More informationNZQA registered unit standard version 2 Page 1 of 6
Page 1 of 6 Title Demonstrate and apply knowledge of capacitance, inductance, power factor, and power factor correction Level 3 Credits 7 Purpose This unit standard covers an introduction to alternating
More informationINSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous)
INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad - 500 043 ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK Course Name : Computer Methods in Power Systems Course Code : A60222
More informationHarmonic Study and Suppression on the Current of CSCT
Proceedings of the World Congress on Engineering and Computer Science 008 WCECS 008, October - 4, 008, San Francisco, USA Harmonic Study and Suppression on the Current of CSCT Mohammad Tavaoli Bina, GNAlexandrov
More informationModeling of Transmission Line and Substation for Insulation Coordination Studies
TRAINING DUBROVNIK, CROATIA - APRIL, 27-29 2009 SIMULATION & ANALYSIS OF POWER SYSTEM TRANSIENTS WITH EMTP-RV Modeling of Transmission Line and Substation for Insulation Coordination Studies Prof. Ivo
More informationAC Circuit Analysis and Measurement Lab Assignment 8
Electric Circuit Lab Assignments elcirc_lab87.fm - 1 AC Circuit Analysis and Measurement Lab Assignment 8 Introduction When analyzing an electric circuit that contains reactive components, inductors and
More informationEE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A
EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A 1. What are the advantages of an inter connected system? The advantages of an inter-connected system are
More informationPower and Energy Measurement
Power and Energy Measurement EIE 240 Electrical and Electronic Measurement April 24, 2015 1 Work, Energy and Power Work is an activity of force and movement in the direction of force (Joules) Energy is
More informationThree Phase Circuits
Amin Electronics and Electrical Communications Engineering Department (EECE) Cairo University elc.n102.eng@gmail.com http://scholar.cu.edu.eg/refky/ OUTLINE Previously on ELCN102 Three Phase Circuits Balanced
More informationTEPZZ A T EP A2 (19) (11) EP A2 (12) EUROPEAN PATENT APPLICATION. (51) Int Cl.: H02M 7/483 ( )
(19) TEPZZ 7849 6A T (11) EP 2 784 926 A2 (12) EUROPEAN PATENT APPLICATION (43) Date of publication: 01..14 Bulletin 14/40 (1) Int Cl.: H02M 7/483 (07.01) (21) Application number: 14162389.2 (22) Date
More informationWork, Energy and Power
1 Work, Energy and Power Work is an activity of force and movement in the direction of force (Joules) Energy is the capacity for doing work (Joules) Power is the rate of using energy (Watt) P = W / t,
More informationECE 325 Electric Energy System Components 5 Transmission Lines. Instructor: Kai Sun Fall 2015
ECE 325 Electric Energy System Components 5 Transmission Lines Instructor: Kai Sun Fall 2015 1 Content (Materials are from Chapter 25) Overview of power lines Equivalent circuit of a line Voltage regulation
More informationET4119 Electronic Power Conversion 2011/2012 Solutions 27 January 2012
ET4119 Electronic Power Conversion 2011/2012 Solutions 27 January 2012 1. In the single-phase rectifier shown below in Fig 1a., s = 1mH and I d = 10A. The input voltage v s has the pulse waveform shown
More informationManaging Emergency Generators
Managing Emergency Generators with nonlinear loads Author akshay thakur Application Engineer Kohler Co. Power Systems Division In this paper we will be focusing on the harmonic distortion that occurs in
More informationGATE 2010 Electrical Engineering
GATE 2010 Electrical Engineering Q.1 Q.25 carry one mark each 1. The value of the quantity P, where P = xe dx, is equal to (A) 0 (B) 1 (C) e (D) 1/e 2. Divergence of the three-dimensional radial vector
More informationReactive Power Flow Control of a Dual Unified Power Quality Conditioner
Reactive Power Flow Control of a Dual Unified Power uality Conditioner aimon M. Fagundes anta Catarina tate University UDEC Electric Power Processing Group - npee 89.19-71, Joinville - C, Brazil saimon.m.f.@gmail.com
More informationEXPERIMENT 07 TO STUDY DC RC CIRCUIT AND TRANSIENT PHENOMENA
EXPERIMENT 07 TO STUDY DC RC CIRCUIT AND TRANSIENT PHENOMENA DISCUSSION The capacitor is a element which stores electric energy by charging the charge on it. Bear in mind that the charge on a capacitor
More informationRLC Circuit (3) We can then write the differential equation for charge on the capacitor. The solution of this differential equation is
RLC Circuit (3) We can then write the differential equation for charge on the capacitor The solution of this differential equation is (damped harmonic oscillation!), where 25 RLC Circuit (4) If we charge
More informationReactive Power Solutions
GE Digital Energy Reactive Power Solutions Effects of Series Capacitors on Line Protection Relaying Design and Settings Presented by: Paul Datka, GE Energy Consulting Luis Polanco, GE Energy Consulting
More informationCahier Technique N 13 Principe de réduction des courants d enclenchement des transformateurs
Cahier Technique N 13 Principe de réduction des courants d enclenchement des transformateurs Numerical transformer inrush current minimizer Principle of the operation Rev 1.0 Document version information
More informationUniversity of Erlangen-Nuremberg Faculty of Engineering Sciences
University of Erlangen-Nuremberg Faculty of Engineering Sciences Institute of Electrical Power Systems Prof. Dr.-Ing. G. Herold Analytical Method for Investigation of three-phase Converter Systems in steady
More informationCHAPTER 22 ELECTROMAGNETIC INDUCTION
CHAPTER 22 ELECTROMAGNETIC INDUCTION PROBLEMS 47. REASONING AND Using Equation 22.7, we find emf 2 M I or M ( emf 2 ) t ( 0.2 V) ( 0.4 s) t I (.6 A) ( 3.4 A) 9.3 0 3 H 49. SSM REASONING AND From the results
More information1 Unified Power Flow Controller (UPFC)
Power flow control with UPFC Rusejla Sadikovic Internal report 1 Unified Power Flow Controller (UPFC) The UPFC can provide simultaneous control of all basic power system parameters ( transmission voltage,
More informationSECOND ENGINEER REG III/2 MARINE ELECTRO-TECHNOLOGY. 1. Understands the physical construction and characteristics of basic components.
SECOND ENGINEER REG III/ MARINE ELECTRO-TECHNOLOGY LIST OF TOPICS A B C D Electric and Electronic Components Electric Circuit Principles Electromagnetism Electrical Machines The expected learning outcome
More informationBoise State University Department of Electrical and Computer Engineering ECE 212L Circuit Analysis and Design Lab
Objectives Boise State University Department of Electrical and Computer Engineering ECE 22L Circuit Analysis and Design Lab Experiment #4: Power Factor Correction The objectives of this laboratory experiment
More informationWe are IntechOpen, the world s leading publisher of Open Access books Built by scientists, for scientists. International authors and editors
We are IntechOpen, the world s leading publisher of Open Access boos Built by scientists, for scientists 4,100 116,000 10M Open access boos available International authors and editors Downloads Our authors
More informationactivar - Performance in Mitigating Voltage Sags Associated with Motor Starting
66 Carey Road TEL: (518) 792-4776 www.nepsi.com Queensbury, NY 12804 FAX: (518) 792-5767 sales@nepsi.com activar - Performance in Mitigating Voltage Sags Associated with Motor Starting We are often asked,
More informationEE 742 Chapter 3: Power System in the Steady State. Y. Baghzouz
EE 742 Chapter 3: Power System in the Steady State Y. Baghzouz Transmission Line Model Distributed Parameter Model: Terminal Voltage/Current Relations: Characteristic impedance: Propagation constant: π
More informationECE2262 Electric Circuits. Chapter 6: Capacitance and Inductance
ECE2262 Electric Circuits Chapter 6: Capacitance and Inductance Capacitors Inductors Capacitor and Inductor Combinations Op-Amp Integrator and Op-Amp Differentiator 1 CAPACITANCE AND INDUCTANCE Introduces
More informationIncorporation of Asynchronous Generators as PQ Model in Load Flow Analysis for Power Systems with Wind Generation
Incorporation of Asynchronous Generators as PQ Model in Load Flow Analysis for Power Systems with Wind Generation James Ranjith Kumar. R, Member, IEEE, Amit Jain, Member, IEEE, Power Systems Division,
More informationPower and Energy Measurement
Power and Energy Measurement ENE 240 Electrical and Electronic Measurement Class 11, February 4, 2009 werapon.chi@kmutt.ac.th 1 Work, Energy and Power Work is an activity of force and movement in the direction
More informationElectromagnetic Oscillations and Alternating Current. 1. Electromagnetic oscillations and LC circuit 2. Alternating Current 3.
Electromagnetic Oscillations and Alternating Current 1. Electromagnetic oscillations and LC circuit 2. Alternating Current 3. RLC circuit in AC 1 RL and RC circuits RL RC Charging Discharging I = emf R
More information