Capacitor Application Issues

Size: px
Start display at page:

Download "Capacitor Application Issues"

Transcription

1 Capacitor Application Issues Thomas Blooming, P.E. Daniel J. Carnovale, P.E. IEEE Industry Applications Society 53 rd Pulp & Paper Industry Technical Conf. Williamsburg, Virginia June 24-29, 2007

2 Introduction Capacitors provide well-known benefits Power factor correction Voltage support Release of system capacity Reduced system losses Many application issues Some basic, some complex Summarized in this paper Make reader aware of the issues and pitfalls

3 Outline Capacitor Sizing Power Factor Penalties Capacitor Ratings Code Requirements and Protection Capacitor Selection Capacitor Placement Harmonics (To Filter Or Not To Filter) Capacitor Switching Transients Capacitors and Fault Current

4 Capacitor Sizing How much kvar do I need? Not necessarily an easy question Power factor not calculated consistently Utility power factor penalties vary Not possible to cover all variations Need to know general concepts Be aware that pf calculation affects the kvar needed calculation Read your utility s published rate

5 Capacitor Sizing Power factor calculations During 15 or 30 minute demand interval Coincident with peak kw or kva load More difficult to meet utility pf target Accumulated kvar-hours and kw-hours Month-long average pf Easier to meet utility pf target Do not need to meet pf target at all times Just be above pf target enough of the time Credit for leading kvar-hours? Possible with some utilities, prohibited by others

6 Capacitor Sizing kvar needed calculation Gather past utility bills, if possible Do multiple monthly calculations Easy to do many calculations quickly with a spreadsheet Do not average kw/kva and pf to do the calculations Can lead to erroneous results Examples shown in the paper

7 Capacitor Sizing TABLE 1 EXAMPLE POWER FACTOR CALCULATIONS, USING MONTHLY DATA,.95 PF TARGET KW PF KVAR NEEDED Probably choose 600 kvar

8 Capacitor Sizing TABLE 2 EXAMPLE POWER FACTOR CALCULATIONS, USING SUMMARIZED DATA,.95 PF TARGET MAXIMUM KW MINIMUM PF KVAR NEEDED MAXIMUM KW AVERAGE PF KVAR NEEDED AVERAGE KW MINIMUM PF KVAR NEEDED AVERAGE KW AVERAGE PF KVAR NEEDED Possibly choose 1000 kvar, with most conservative approach!

9 Outline Capacitor Sizing Power Factor Penalties Capacitor Ratings Code Requirements and Protection Capacitor Selection Capacitor Placement Harmonics (To Filter Or Not To Filter) Capacitor Switching Transients Capacitors and Fault Current

10 Power Factor Penalties Not possible to cover all penalties Table 3 shows some typical methods User should determine which type of penalty (if any) the utility is using Then investigate further Sometimes utility uses multiple penalty methods

11 Power Factor Penalties Most penalties are straightforward Easy to calculate and analyze Power factor penalty may be hidden kva billing No explicit pf penalty, but you will pay more if you have a low power factor (higher kva) Utility rebate for maintaining a certain power factor or higher Not a penalty, but functionally equivalent

12 Power Factor Penalties Usually not practical to correct all the way to unity (1.0) power factor Diminishing benefit per incremental cost May cost more than will be saved in pf penalty reduction, even with kva billing (1.0 pf target) More long run savings, but lower return on the project Leading power factor concerns, at light load Some utilities bill for leading power factor, too May require switched capacitor bank

13 POWER FACTOR PENALTIES RATE TYPE DESCRIPTION OF PF PENALTY EXAMPLE kva (demand) rates PF (kva) adjustment PF ratio (kw demand) adjustment PF magnitude (kw demand) adjustment PF multiplier (PFM) kvar demand charge Penalty for < 1.0 pf; generally applied as a $/kva When the pf is less than X%, the demand may be taken as X% of the measured kva If the pf is < X%, the demand will be adjusted by the following: X%/actual pf * actual demand = adjusted demand. PF adjustment increases or decreases the net (kw) demand charge X% for each Y% the pf is above or below the utility specified pf Demand is increased (or decreased) by a calculated multiplier determined by a utility table or by a formula $X per kva of reactive demand in excess of Y% of the kw demand Demand = 800 kw; pf=80%; kva=1000; demand charge = $10/kVA pf penalty = ( )*$10 = $2000/month When the pf is less than 90%, the demand may be taken as 90% of the measured kva pf=80%; kva=1000; demand charge = $10/kVA Billed demand = 0.90*1000 = 900 kw pf penalty = ( *0.80)*$10 = $1000/month If the pf is < 85%, the demand will be adjusted by the following: 85%/actual pf * actual demand = adjusted demand. Demand = 800 kw; pf=80%; demand charge = $10/kW Adjusted demand = (0.85/0.80)*800=850kW pf penalty = ( )*$10 = $500/month Where the pf is < 85%, the net demand charges shall be increased 1% for each whole 1% the pf is < 90%; likewise, where the pf is higher than 95%, the demand charges will be reduced by 1% for each whole 1% the pf is above 90%. Demand = 800 kw; pf=80%; demand charge = $10/kW Up to 90%, demand adjustment = 800*10%=80kW (from 80% to 90%) = net demand of 880 kw If pf is corrected to 1.0, pf adjustment (reduction) = 800*10%=80kW (from 90%-100%) = net demand of 720kW Correcting pf from 80% to 100%, potential net savings is ( )*$10/kW = $1600/month Demand = 800 kw; pf=80%; PFM = 1.086; demand charge = $10/kVA pf penalty = 800*$10*(0.086) = $688/month $0.45 per kva of reactive demand in excess of 50% of the kw demand Demand = 800 kw; pf=80%; kvar demand = 600; excess kvar demand = *0.50 = 200 kvar pf penalty = 200 kvar*($0.45/kvar) = $90/month kvarh charge $X per kvarh $ per kvarh kvarh = 500,000 pf penalty = 500,000* = $417/month kwh adjustment (note that this often applies where the kw demand is first adjusted) $P/kWh for first Q*kWh*demand $R/kWh for next S*kWh* demand $X/kWh for next Y*kWh demand $Z/kWh for all additional $0.040/kWh for first 100 kwh*demand $0.035/kWh for next 150kWh*demand $0.025/kWh for next 150kWh*demand $0.020/kWh for all additional kwh Actual demand = 800 kw; Adjusted demand = 1000 kw; kwh measured = 500,000 With penalty 100*1000=100, /kWh=$ *1000=150, /kWh=$ *1000=150, /kWh=$3750 (500, , , ,000)*$0.02/kWh = $2000 Total = $15,000 Without penalty 100*800=80, /kWh=$ *800=120, /kWh=$ *800=120, /kWh=$3000 (500,000-80, , ,000)*$0.02/kWh = $3600 Total = $14,000 Penalty = $15,000 - $14,000 = $1,000/month (in addition to demand penalty)

14 Outline Capacitor Sizing Power Factor Penalties Capacitor Ratings Code Requirements and Protection Capacitor Selection Capacitor Placement Harmonics (To Filter Or Not To Filter) Capacitor Switching Transients Capacitors and Fault Current

15 Capacitor Ratings Capacitors are built with tolerances above nameplate ratings Applicable standards IEEE Std , IEEE Standard for Shunt Power Capacitors Older versions in 1992 and 1980 IEEE Std , IEEE Guide for Application of Shunt Power Capacitors

16 Capacitor Ratings IEEE Std continuous overload limits, intended for contingencies and not for a nominal design basis 110% of rated rms voltage 120% of rated peak voltage (including harmonics) 135% of rated rms current (nominal current based on rated kvar and voltage) Was 180% in IEEE Std % of rated reactive power

17 Capacitor Ratings Short time overvoltage limits IEEE Std IEEE Std IEEE Std Capacitor may be expected to see 300 such overvoltages in its service life without superimposed transients or harmonic content.

18 Capacitor Ratings Short time overvoltage limits IEEE Std per unit rms voltage for seconds 2.70 per unit rms voltage for seconds IEEE Std and per unit rms voltage for 0.1 seconds 2.00 per unit rms voltage for 0.25 seconds 1.70 per unit rms voltage for 1 second 1.40 per unit rms voltage for 15 seconds 1.30 per unit rms voltage for 1 minute 1.25 per unit rms voltage for 30 minutes

19 Capacitor Ratings Study engineers Compare measured or calculated voltages and currents against capacitor tolerances Different durations for different cases Harmonics: steady state Compare peak voltage stress on capacitors with continuous limits Transformer energization inrush: < 1 second Compare peak voltage stress on capacitors with certain short time limits Significant inrush is < 1 second, therefore compare against 1.70 pu

20 Capacitor Ratings Heavy duty capacitors Some manufacturers claim tolerances above those required by standards Really just higher voltage capacitors with a de-rated nameplate Not a substitute for good engineering, especially in harmonic filters

21 Capacitor Ratings Capacitor motor starting Apply capacitors at voltage above rating Produce more kvar (square of voltage ratio) Short periods of time, limited times Large motors, typically medium voltage Large voltage drop when starting Switch on capacitors for a short time during starting Minimize kvar draw and voltage drop May be economical, even if shorter life

22 Outline Capacitor Sizing Power Factor Penalties Capacitor Ratings Code Requirements and Protection Capacitor Selection Capacitor Placement Harmonics (To Filter Or Not To Filter) Capacitor Switching Transients Capacitors and Fault Current

23 Code Reqs. and Protection National Electric Code, Article 460 Guidance for installation and protection More information for low voltage capacitors Conductor and Disconnect Sizing NEC Article (A), for LV capacitors: Ampacity of conductors shall not be less than 135% of rated capacitor current NEC Article (C) (3), for LV caps: Rating of the disconnecting means shall not be less than 135% of rated capacitor current

24 Code Reqs. and Protection Conductor and Disconnect Sizing (cont.) Why 135%? Not practical to set capacitor overcurrent protection for overloads Caps draw more current during overvoltages Caps are attractive path for harmonic currents Caps have little/no diversity on all the time Capacitor switching transients could lead to nuisance trips Without tight overload protection, it is necessary oversize the conductors

25 Code Reqs. and Protection Overcurrent protection Protect system: Isolate the fault from the system Protect capacitor: Prevent more energy from reaching a failed capacitor, avoid can rupture NEC Article (Overcurrent protection) For capacitors, Article 460 applies

26 Code Reqs. and Protection Overcurrent protection (continued) NEC Article (B), for LV capacitors: The rating or setting of the overcurrent device shall be as low as practicable. Possible to choose an overcurrent device that does not protect the cable against overloads See recommended wire and fuse/breaker charts for given capacitor sizes published by capacitor manufacturers Set overcurrent devices as low as possible Avoid nuisance trips Realize we do not always protect cable

27 Code Reqs. and Protection Overcurrent protection (continued) Bussman SPD Electrical Protection Handbook recommendations for cap fuses Generally, size dual-element, current-limiting fuses at 150% to 175% of the capacitor rated current and size non-time-delay, fast-acting, current-limiting fuses at 250% to 300% of the capacitor rated current. Large difference? Oversized fuses? Look at time-current characteristics (TCCs) Fuse size based on high current, short time behavior, not by nominal (long time, overload) ratings

28 Code Reqs. and Protection Overcurrent protection (continued) 200 ka interrupting capacity currentlimiting fuses in low voltage cap banks Often specified by consultants Therefore, used in many standard designs Very fast-acting fuses Time current characteristics require a larger nominal fuse size to avoid nuisance tripping Fuses appear to be oversized but are not

29 Code Reqs. and Protection Unbalance protection Large, MV caps can have many capacitors in series and parallel groups Individually fused capacitors Capacitor failure (removed by fuse) results in unbalance in the bank, stressing some of the remaining capacitors Unbalance protection not required by code Used to detect (alarm) and protect (trip) against overvoltage conditions resulting from unbalance

30 Code Reqs. and Protection Capacitor discharge Capacitors are energy storage devices Not safe to retain this energy indefinitely NEC specifies automatic means to discharge NEC Article (A), for LV capacitors: Reduce charge to 50 V or less within 1 minute NEC Article (A), for caps > 600 V: Reduce charge to 50 V or less within 5 minutes Switching before discharge can result in greater than normal switching transients

31 Outline Capacitor Sizing Power Factor Penalties Capacitor Ratings Code Requirements and Protection Capacitor Selection Capacitor Placement Harmonics (To Filter Or Not To Filter) Capacitor Switching Transients Capacitors and Fault Current

32 Capacitor Selection Capacitor selection issues (besides size) Utility penalties Installed cost and payback of equipment Load variability kw losses Self excitation of motors Harmonic resonance Voltage regulation Load requirements (flicker requirements)

33 Capacitor Selection Equipment cost > include installation Payback is main criterion for approval Rough estimate of costs given in the paper Higher $/kvar for multiple small capacitors Lower $/kvar for large capacitors Fixed caps: Caps are only 1/3 of total cost Protective device (breaker or fuse) Installation labor and material Switched caps: Cost of capacitor is typically a larger proportion of the cost

34 Capacitor Selection TABLE 4 INSTALLED COST COMPARISON OF POWER FACTOR CORRECTION EQUIPMENT TYPE OF CORRECTION INSTALLED COST, $/KVAR Fixed (LV motor applied) $15 Fixed (LV) $25 Fixed (MV) $30 Switched (LV) $50 Switched (MV) $50 Static Switched (LV) $75 Switched Harmonic Filter (LV) $75 Switched Harmonic Filter (MV) $60 Active Harmonic Filter (LV) $150

35 Capacitor Selection Nominal size and configuration Caps available in a variety of sizes Smaller kvar increments in smaller kvar sizes 50 or 100 kvar increments in larger sizes Low voltage caps Typically internally connected as a three-phase delta configuration Medium voltage caps Single-phase or three-phase capacitors connected in ungrounded wye or delta configurations

36 Capacitor Selection Fixed versus switched capacitors Power factor correction needs Billed over whole month > fixed Billed in demand interval > switched Load variation More variation > switched Personal preference Operate without user attention > switched Paper has further description about switched capacitors

37 Capacitor Selection Switched capacitors Automatically switches on needed kvar If sized large enough No human input required Harmonics More likely to tune system to critical frequency Switching devices Mechanical contactors Most common, inexpensive (LV) Static switches (LV only, at present time) For loads needing instant response, such as welders

38 Capacitor Selection Switched capacitors (continued) Controller Senses system power factor Voltage measured within cap bank System current measured with external CT(s) Adds/removes capacitor steps Meet target power factor (programmable) Time delays (programmable) Not necessary for static-switched cap bank Avoid hunting for rapidly varying loads Allow trapped charge to dissipate» 1 minute for LV caps» 5 minutes for MV caps

39 Capacitor Selection Switched capacitors (continued) MV versus LV design MV banks typically have fewer & larger steps than LV MV contactors are more expensive and require more space

40 Capacitor Selection Switched capacitors (continued) Stages versus steps Reduce contactors with different size stages Often done in MV systems, sometimes in LV systems Stages: Physical capacitor groups Steps: Connected kvar values possible Example: 1500 kvar MV bank One 300 kvar stage and two 600 kvar stages Five steps in 300 kvar increments, three contactors Disadvantage: Stages not used equally With equal size stages controller can equalize duty Stages, esp. first stage, may be switched more often

41 Capacitor Selection Static switched capacitors For loads requiring very fast kvar compensation High impact loads, such as spot welders Benefits beyond power factor correction Minimize sudden voltage drops and flicker Often configured as harmonic filters standard Power electronic switches (SCR/thyristors) Can switch very quickly (within one cycle, 16.7 msec) Precisely control when capacitors are switched Match system voltage with capacitor voltage Capacitor switching transients largely eliminated Disadvantage: Cost

42 Capacitor Selection Overvoltage considerations Can be caused by leading power factor Possible with fixed capacitors and light load Generators have trouble with leading pf Voltage rise Depends on system stiffness (MVA SC ) and capacitive kvar Other factors (don t just blame capacitors!) Transformer tap selection Utility voltage variation» High voltage at night or on weekends

43 Outline Capacitor Sizing Power Factor Penalties Capacitor Ratings Code Requirements and Protection Capacitor Selection Capacitor Placement Harmonics (To Filter Or Not To Filter) Capacitor Switching Transients Capacitors and Fault Current

44 Capacitor Placement Physical location At motor terminals Great, if power factor is only concern Caps switched as needed, with each motor Reduce overall system losses Harmonics in system may complicate this application Consult tables to choose capacitor size Self-excitation concerns Don t oversize capacitor

45 Capacitor Placement Physical location At motor terminals Self-excitation Sufficient kvar at motor terminals to fully supply motor reactive power needs Load with some inertia Can cause damaging overvoltages Solution: Do not apply too much capacitance» Tables based on not fully correcting motor pf to unity, to avoid self-excitation

46 Capacitor Placement Physical location If needed for power factor compensation Apply anywhere downstream of the meter If needed for kva or loss reduction Apply at or near the loads Loss reduction 1-2% of overall kw is possible with distributed capacitors Some may claim more Payback is generally 10 years or more Typically not enough to justify cost to add capacitors

47 Capacitor Placement Physical location Avoid placement downstream of a motor starter in such a way that the capacitor would see sudden voltage changes Can be downstream of main contacts (steady voltage) Avoid placement downstream of softstarts Unless connected via contactor and switched on after softstart is in bypass

48 Capacitor Placement Physical location Harmonic concerns Capacitor on a motor and upstream cable can create a tuned circuit Harmonic filter: just L & C in series This filter can attract harmonics from the system and overload the capacitor Possible result: One or a few capacitors on certain motors keep failing while others are completely unaffected Safer design choice: Apply capacitors at main distribution or MCCs if harmonics are a concern

49 Capacitor Placement Electrical location: LV vs. MV Many LV unit substations? One MV bank may be more cost effective Physical space available? Where? Single MV bank may be more compact than multiple LV banks If room in substation or electrical room

50 Capacitor Placement Electrical location: LV vs. MV Customer preferences? Some companies avoid MV, electricians not trained Harmonics? May be possible to avoid a harmonic resonance situation at LV by applying an MV bank Need to pay greater attention to system/background harmonics with an MV bank

51 Capacitor Placement CT location Important when applying automatically switched capacitors, LV or MV Place CT where where it will measure the full load needing power factor correction Including the capacitor itself, so the capacitor bank can see its impact on the system CT orientation (polarity) is also critical to proper operation of an automatic bank

52 Capacitor Placement CT location Assumption: Load is balanced Concerned about 3-phase pf on bill LV: 3-phase capacitors and contactors MV: Could be three-phase or three single-phase units Usually not possible to separately compensate power factor on different phases, therefore: Measure one phase current and one phase voltage Switch all steps as a three-phase group High-end products may require 2 or 3 CTs Static switched capacitor bank or active filter

53 Capacitor Placement CT location Field errors: CT on the breaker serving the capacitor bank This does nothing to measure the system pf CT on the middle or end of busbar in LV switchgear Does not measure full load CT on the wrong phase or wrong polarity Controller won t calculate pf or switch steps correctly Can be compensated for by making wiring changes» No need to shut down system to move the CT» Change voltage input to controller to match CT phase and polarity

54 Capacitor Placement CT location Commissioning sanity checks Verify that the controller reads a realistic power factor Not just.8, for example, but.8 lagging, not leading some people miss the second part Can often be checked against system metering Confirm that the power factor improves when a step is energized Add steps manually during commissioning, if necessary Pf should get closer to unity from a lagging pf

55 Capacitor Placement CT location Double-ended substations Capacitor bank(s) may be placed on either/both of the secondary buses CTs must be in a shared (additive) arrangement to ensure that both transformer loads are compensated for Capacitors may be placed on both halves of the double-ended substation if each capacitor bank has summed CTs on its main and on the tie How many CTs if automatic capacitor banks on both sides of a double-ended sub?

56 Capacitor Placement CT location Multiple LV services compensated by one capacitor bank, on one of the LV busses Summing CT to aggregate the CT currents from each low voltage bus Need same type of transformer connection (for proper phasing) on each LV CTs at each bus need to be on the same phase LV bus with capacitor needs to be able to handle leading pf, and possible overvoltage When the capacitor bank is doing significant compensation for the other busses

57 Outline Capacitor Sizing Power Factor Penalties Capacitor Ratings Code Requirements and Protection Capacitor Selection Capacitor Placement Harmonics (To Filter Or Not To Filter) Capacitor Switching Transients Capacitors and Fault Current

58 Harmonics (To Filter or Not) Why do we care about harmonics? IEEE Std , Section 6.5: A major concern arising from the use of capacitors in a power system is the possibility of system resonance. This effect imposes voltages and currents that are considerably higher than would be the case without resonance. The reactance of a capacitor bank decreases with frequency, and the bank, therefore, acts as a sink for higher harmonic currents. This effect increases the heating and dielectric stresses. The result of the increased heating and voltage stress brought about by harmonics is a shortened capacitor life.

59 Harmonics (To Filter or Not) Series resonance Inductance (transformer, cable, reactor) in series with capacitance (pf correction capacitor) At some frequency the series combination will be equal and will sum to nearly zero (ignoring R) Very attractive path for harmonic current at that frequency Harmonic filters are purposely series resonant at a fixed frequency to attract harmonic currents Uncontrolled series resonance can result in nuisance fuse operations or breaker trips, as well as capacitor failures

60 Harmonics (To Filter or Not) Utility Transformer VFD PF Cap 100 HP FIGURE 2. SYSTEM SHOWING SERIES RESONANCE

61 Harmonics (To Filter or Not) Series Resonance Equivalent Circuit Transformer and Cable PF Cap Harmonic Current Source FIGURE 3. SERIES RESONANCE, EQUIVALENT CIRCUIT, RESULTS IN HIGH HARMONIC CURRENT

62 Harmonics (To Filter or Not) Parallel resonance Capacitors tune the system to a certain harmonic Known as parallel resonance between the capacitors and the source (including transformer) inductance This frequency is the crossover point at which the inductive and capacitive reactances are equal This frequency can be easily calculated (estimated) Parallel resonance presents a high impedance to harmonics at or near the resonant frequency Amplifying harmonics at these frequencies Causes problems if a source of harmonics exists at or near that frequency Problem more likely if multi-step capacitor bank Several possible resonant frequencies

63 Harmonics (To Filter or Not) Utility Transformer PF Cap VFD 100 HP FIGURE 4. SYSTEM SHOWING PARALLEL RESONANCE

64 Harmonics (To Filter or Not) Parallel Resonance Equivalent Circuit PF Cap Source Impedance Harmonic Current Source FIGURE 5. PARALLEL RESONANCE, EQUIVALENT CIRCUIT, RESULTS IN HIGH HARMONIC CURRENT

65 Harmonics (To Filter or Not) Harmonic filters Configure a capacitor bank as a filter Put inductance in series with capacitance Supplies reactive power Counter intuitively, more kvar WITH the reactor Filters harmonics: passive harmonic filter Avoids parallel resonance problem Parallel resonance below tuning of the filter Typical LV filter tuning is 4.7 th harmonic System parallel resonance around 3.8 th, give or take» Well below any harmonics of concern, except in very rare instances

66 Harmonics (To Filter or Not) When is a harmonic filter needed? Rule of thumb If kvar > 25% of transformer kva and Harmonic-producing load (e.g. drives) is greater than 40% of the transformer kva Below 15% and 25%, respectively, should be okay Better to do resonance calculations Possible problem if both: Significant amount of harmonic load and Resonance point near a characteristic harmonic of harmonic loads (5 th, 7 th for drives) If either or both are in a gray area then a study may be needed

67 Harmonics (To Filter or Not) Harmonic filters Manufacturer explicitly chooses the series tuning point of the filter Typically 4.7 th for LV and small MV banks Won t change, regardless of the system in which the filter is installed Parallel resonance is determined by both filter and the system 4.7 th filter in one system may cause parallel resonance at 3.8 th in one system, 4.1 st in another

68 Harmonics (To Filter or Not) Harmonic filters: Why 4.7 th If tuned right on nominal frequency (5 th ), it may attract excessive harmonic current In excess of component ratings Component tolerances Component drift over time As capacitors age, tuning rises (closer to 5 th ) Good to start a safe distance from 5.0 th tuning MV banks, with many caps: 4.9 th may be okay

69 Harmonics (To Filter or Not) De-tuned banks Harmonic filter, just tuned to 4.2 nd or 4.1 st Good if pf correction is main goal Reduced filtering effect Less concern about overloading filter More of a plug and play solution Small but significant amount of 5th harmonic current will still be filtered Will still filter some 7 th, 11 th, 13 th, etc. Other custom tuning points may be chosen

70 Harmonics (To Filter or Not) Other considerations Multiple capacitors at different locations can cause multiple resonance points Example: Capacitors on multiple motors Distributed capacitors not recommended on system with harmonic sources Assumption: Harmonic filters attract all harmonic currents >>> NOT TRUE! Most filters are 4.7 th tuned, not 5.0 th Absorb roughly half (ballpark: 30-70%) of the harmonic current on a typical system.

71 Harmonics (To Filter or Not) Other considerations (continued) Fixed filter applied to an individual load Intention: Filter only harmonics from that load Can attract harmonics from elsewhere Place a reactor upstream of the filter and load Harmonic loads with high pf (e.g. drives) High pf means little kvar needed kvar determines 60 Hz current Filter impedance determines harmonic current» Can sink a large amount of harmonic current, regardless of kvar size Easy to overload Generally ok if just part of the overall load

72 Harmonics (To Filter or Not) Other considerations (continued) Automatic filter banks and harmonic loads Desirable to switch on the filter steps quickly If many harmonic loads switched on at once and If filter steps switch on too slowly One small filter step may be left to sink a lot of harmonic current until the next steps switch on Can also occur with a filter bank with a few fixed steps Recommendation: Avoid fixed steps in a filter

73 Harmonics (To Filter or Not) Other considerations (continued) Specify a harmonic filter First choose 60 Hz pf correction needed Specify tuning point (4.7 th or 4.2 nd ) Harmonic filtering needed? Performing a harmonic study?» If not, consider 4.2 nd Determine harmonic current in filter Easy to determine component values (mh, kvar) More difficult to rate components when designing» Measurements, estimates, studies» LV filters: Oversized, for typical harmonic loads» MV filters: More likely to require studies

74 Harmonics (To Filter or Not) Other considerations (continued) Multiple filters with different tuning Avoid higher order filter amplifying lower order harmonics (parallel resonance!) Switch lowest order on first Switch highest order off first E.g. 5 th and 7 th filters: Switch 5 th on, then 7 th Switch 7 th off, then 5 th 7 th could amplify 5 th harmonic if left online alone» Possible parallel resonance near the 5 th

75 Harmonics (To Filter or Not) Other considerations (continued) Filter capacitors: higher voltage rating Typically 550 V or 600 V caps in 480 V filters Steady-state voltage rise on caps due to reactor» 60 Hz effect, regardless of harmonics Higher peak voltages on caps due to harmonics Cannot convert straight cap bank to filter without properly rated caps Straight banks with higher voltage caps Additional margin, more reliability Possible to convert to a filter later in some designs

76 Harmonics (To Filter or Not) Other considerations (continued) Automatic filter bank Each step must be configured as a filter Each step needs its own tuning reactor LV filter kvar Nominal kvar based on nameplate kvar Actual effective kvar is higher (typically 5% or so) Filter caps specified in kvar at applied voltage Higher voltage filter caps: nameplate kvar at 480 V MV filter kvar Effective kvar, including effect of filter reactors

77 Harmonics (To Filter or Not) Application advice: general steps Perform a resonance calculation Necessary for each step of an automatic bank If resonance is not close to 5 th, 7 th, 11 th, 13 th, etc., apply straight caps If resonance is close, choose filters (4.7 th ), de-tuned bank (4.2 nd ), or further study If very heavy drive or rectifier loads Passive filters may become overloaded Consult the manufacturer or study further

78 Outline Capacitor Sizing Power Factor Penalties Capacitor Ratings Code Requirements and Protection Capacitor Selection Capacitor Placement Harmonics (To Filter Or Not To Filter) Capacitor Switching Transients Capacitors and Fault Current

79 Capacitor Switching Transients Normal system event Possible whenever a capacitor is energized Due to difference in system voltage and capacitor voltage at time of switching Cap voltage can t change instantaneously System voltage pulled down to cap voltage Inrush current as capacitor charges Voltage on capacitor rises, overshoots, and oscillates Characteristic oscillation frequency

80 Capacitor Switching Transients Voltage Figure 6. Capacitor Energization Transient Voltage (per unit) Current (A) Current Hz Degrees FIGURE 6. CAPACITOR ENERGIZATION TRANSIENT

81 Capacitor Switching Transients Back-to-back capacitor switching Second capacitor switched in close (electrical) proximity to a previously energized capacitor High frequency transient as the previously energized capacitor shares its charge with the newly energized capacitor Second, lower frequency, transient as the pair of capacitors oscillate with the utility

82 Capacitor Switching Transients Voltage Voltage (per unit) Current (A) Capacitor #2 Current Hz Degrees FIGURE 7. BACK-TO-BACK CAPACITOR SWITCHING TRANSIENT

83 Capacitor Switching Transients Capacitor contactors/breakers Capable of interrupting capacitor current? Voltage is at a peak when when interruption occurs at a natural current zero Very important at MV Interrupting duty depends on configuration of the capacitor bank and the system Voltage across contacts can be as high as 3 per unit (of the normal line-to-neutral voltage) with ungrounded source» Even higher (3.46 pu) if there is a failed capacitor

84 Capacitor Switching Transients Minimizing Capacitor Transients Switch when system voltage matches capacitor voltage, even if trapped charge Precisely-controlled switching device Static switched capacitors Insert impedance in the circuit Harmonic filters, with inductors in circuit Small inductor in the circuit (often done at MV) LV: Coil wire feeding the capacitor bank Pre-insertion resistance or inductance contactors Excellent solution for unfiltered capacitor banks

85 Capacitor Switching Transients Utility Capacitor Switching Magnification Utility switches MV capacitor bank This transient has a natural frequency Customer has LV capacitor bank If natural frequency of LV circuit matches frequency of MV transient, overvoltage at LV bank can result Relatively rare, but does happen Avoiding voltage magnification Change natural frequency of LV system Change transformer or capacitor size Add inductance (possibly harmonic filters)

86 Capacitor Switching Transients FIGURE 8. VOLTAGE MAGNIFICATION CIRCUIT

87 Capacitor Switching Transients FIGURE 9. UTILITY CAPACITOR ENERGIZED WITH LV CAPACITOR ENERGIZED: VOLTAGE MAGNIFICATION AT 480 V BUS

88 Capacitor Switching Transients FIGURE 10. UTILITY CAPACITOR ENERGIZED WITHOUT LV CAPACITOR ENERGIZED: NO VOLTAGE MAGNIFICATION

89 Outline Capacitor Sizing Power Factor Penalties Capacitor Ratings Code Requirements and Protection Capacitor Selection Capacitor Placement Harmonics (To Filter Or Not To Filter) Capacitor Switching Transients Capacitors and Fault Current

90 Capacitors and Fault Current Include capacitors in fault studies? No, they can be ignored Capacitors do not offer a significant source power during a fault Energized capacitor will discharge into other loads (or the fault) within ¼ cycle (60 Hz) at a much higher frequency Significantly different than motors that will generate back into the faulted system and contribute to the overall fault current

91 Outline Capacitor Sizing Power Factor Penalties Capacitor Ratings Code Requirements and Protection Capacitor Selection Capacitor Placement Harmonics (To Filter Or Not To Filter) Capacitor Switching Transients Capacitors and Fault Current

92 Conclusions and Summary With all of these potential problems, why would anyone apply pf correction capacitors? Capacitors provide well-known benefits With care, PF correction capacitors can be applied safely and effectively

93 The End

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL 1 SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL Power Systems: Generation, Transmission and Distribution Power Systems: Generation, Transmission and Distribution Power Systems:

More information

Tutorial on Shunt Capacitor Banks Design, Application and Protection Considerations

Tutorial on Shunt Capacitor Banks Design, Application and Protection Considerations Tutorial on Shunt Capacitor Banks Design, Application and Protection Considerations Presenter: Pratap Mysore, HDR Minnesota Power Systems Conference November 12, 2015 Topics Covered Power system Considerations,

More information

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur Lecture - 9 Transmission Line Steady State Operation Welcome to lesson 9, in Power

More information

Fault Calculation Methods

Fault Calculation Methods ELEC9713 Industrial and Commercial Power Systems Fault Calculation Methods There are two major problems that can occur in electrical systems: these are open circuits and short circuits. Of the two, the

More information

POWER FACTOR IN THE DIGITAL AGE A N E N V I R O N M E N T A L P O T E N T I A L S W H I T E P A P E R. Power Quality For The Digital Age

POWER FACTOR IN THE DIGITAL AGE A N E N V I R O N M E N T A L P O T E N T I A L S W H I T E P A P E R. Power Quality For The Digital Age Power Quality For The Digital Age POWER FACTOR IN THE DIGITAL AGE A N E N V I R O N M E N T A L P O T E N T I A L S W H I T E P A P E R Introduction One method to measure the efficiency of the electrical

More information

Capacitors. Dominik Pieniazek, P.E. VI Engineering, LLC Nicholas A. Losito Jr. Castle Power Solutions, LLC

Capacitors. Dominik Pieniazek, P.E. VI Engineering, LLC Nicholas A. Losito Jr. Castle Power Solutions, LLC Capacitors Dominik Pieniazek, P.E. VI Engineering, LLC Nicholas A. Losito Jr. Castle Power Solutions, LLC Outline Day 1 Basic Power Calculations Capacitor Fundamentals Capacitor Ratings Capacitor Application

More information

We Make Energy Engaging. Improving Your Power Factor

We Make Energy Engaging. Improving Your Power Factor We Make Energy Engaging Improving Your Power Factor Meet Your Panelist Mike Carter 2 NEEA Northwest Industrial Training Provided by: Northwest Regional Industrial Training Center: (888) 720-6823 industrial-training@industrial.neea.org

More information

CHAPTER 2 OVERVOLTAGE DUE TO SELF-EXCITATION AND INRUSH CURRENT DUE TO CAPACITOR SWITCHING

CHAPTER 2 OVERVOLTAGE DUE TO SELF-EXCITATION AND INRUSH CURRENT DUE TO CAPACITOR SWITCHING 20 CHAPTER 2 OVERVOLTAGE DUE TO SELF-EXCITATION AND INRUSH CURRENT DUE TO CAPACITOR SWITCHING 2.1 INTRODUCTION It is becoming more common to find use of shunt capacitors for the application of powerfactor

More information

Power Systems - Basic Concepts and Applications - Part I

Power Systems - Basic Concepts and Applications - Part I PDHonline Course E104A (1 PDH) Power Systems - Basic Concepts and Applications - Part I Instructor: Shih-Min Hsu, Ph.D., P.E. 01 PDH Online PDH Center 57 Meadow Estates Drive Fairfax, VA 030-6658 Phone

More information

Reactive Power Solutions

Reactive Power Solutions GE Digital Energy Reactive Power Solutions Effects of Series Capacitors on Line Protection Relaying Design and Settings Presented by: Paul Datka, GE Energy Consulting Luis Polanco, GE Energy Consulting

More information

Energy saving in electromechanical equipment with power coefficient correction. Dimitris Al. Katsaprakakis Aeolian Land S.A.

Energy saving in electromechanical equipment with power coefficient correction. Dimitris Al. Katsaprakakis Aeolian Land S.A. Energy saving in electromechanical equipment with power coefficient correction Dimitris Al. Katsaprakakis Aeolian Land S.A. www.aiolikigi.gr Introduction Electricity production companies (utilities) provide

More information

F F FAULT CURRENT Prospective. 1. Introduction. 2. Types of fault conditions

F F FAULT CURRENT Prospective. 1. Introduction. 2. Types of fault conditions FAULT CURRENT F F13-13 FAULT CURRENT - Contents 1. Introduction 2. Types of fault conditions 3 fault current must be determined 3.1 Purposes for which of prospective fault current magnitudes are used 3.2

More information

GENERATOR INTERCONNECTION APPLICATION

GENERATOR INTERCONNECTION APPLICATION GENERATOR INTERCONNECTION APPLICATION FOR BUY-ALL/SELL-ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 20 KW BUT LESS THAN OR EQUAL TO 1 MW Electric Utility Contact Information Great Lakes Energy

More information

KINGS COLLEGE OF ENGINEERING Punalkulam

KINGS COLLEGE OF ENGINEERING Punalkulam KINGS COLLEGE OF ENGINEERING Punalkulam 613 303 DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING POWER SYSTEM ANALYSIS QUESTION BANK UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A (TWO MARK

More information

THF / 1SCC330001M THF 1S1 C

THF / 1SCC330001M THF 1S1 C THF 2247 0191/ 1SCC330001M5803 34 THF 1S1 C Installation and Operation Instruction for THF Filter and Protective Unit THF 1_ THF 1S_ THF 1BS_ General guidelines Due to the fact that most UK building earth

More information

Harmonic Modeling of Networks

Harmonic Modeling of Networks Harmonic Modeling of Networks Thomas H. Ortmeyer ECE Dept. Clarkson University Potsdam, NY 13699-5720 M. Fayyaz Akram Dept. of Elec. Eng. Univ. of Engineering and Technology Lahore, Pakistan Takashi Hiyama

More information

High Voltage Capacitors Designed to Avoid Catastrophic Failure Modes

High Voltage Capacitors Designed to Avoid Catastrophic Failure Modes GENERAL ATOMICS ENERGY PRODUCTS Engineering Bulletin High Voltage Capacitors Designed to Avoid Catastrophic Failure Modes F. W. MacDougall G. L. McKee, J.B. Ennis, R.A. Cooper Maxwell Energy Products,

More information

LO 1: Three Phase Circuits

LO 1: Three Phase Circuits Course: EEL 2043 Principles of Electric Machines Class Instructor: Dr. Haris M. Khalid Email: hkhalid@hct.ac.ae Webpage: www.harismkhalid.com LO 1: Three Phase Circuits Three Phase AC System Three phase

More information

Selecting the current rating for equipment

Selecting the current rating for equipment Selecting the current rating for equipment 1. Rated current: the maximum continuous load current. Short-time withstand current: thermal withstand current term term is given for 1s or 3s short circuit current

More information

Model M3484 Industrial Line Noise Filter Module Customer Reference Manual

Model M3484 Industrial Line Noise Filter Module Customer Reference Manual Model M3484 Industrial Line Noise Filter Module Customer Reference Manual Web: www.bonitron.com Tel: 615-244-2825 Email: info@bonitron.com Bonitron, Inc. Bonitron, Inc. Nashville, TN An industry leader

More information

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A 1. What are the advantages of an inter connected system? The advantages of an inter-connected system are

More information

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager. Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager. 1 -A - Introduction - Thank for your purchasing MITSUBISHI ELECTRIC MELPRO TM D Series Digital Protection

More information

Fault Analysis Power System Representation

Fault Analysis Power System Representation .1. Power System Representation Single Line Diagram: Almost all modern power systems are three phase systems with the phases of equal magnitude and equal phase difference (i.e., 10 o ). These three phase

More information

Effects of Capacitor Bank Installation in a Medium Voltage (MV) Substation

Effects of Capacitor Bank Installation in a Medium Voltage (MV) Substation Effects of Capacitor Bank Installation in a Medium Voltage (MV) Substation Adesina, Lambe Mutalub Department of Engineering & Standardization, Eko Electricity Distribution Plc, 24/25, Marina, Lagos Island,

More information

Chapter 3 AUTOMATIC VOLTAGE CONTROL

Chapter 3 AUTOMATIC VOLTAGE CONTROL Chapter 3 AUTOMATIC VOLTAGE CONTROL . INTRODUCTION TO EXCITATION SYSTEM The basic function of an excitation system is to provide direct current to the field winding of the synchronous generator. The excitation

More information

Keywords: Superconducting Fault Current Limiter (SFCL), Resistive Type SFCL, MATLAB/SIMULINK. Introductions A rapid growth in the power generation

Keywords: Superconducting Fault Current Limiter (SFCL), Resistive Type SFCL, MATLAB/SIMULINK. Introductions A rapid growth in the power generation IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY Performance of a 3.3kV Resistive type Superconducting Fault Current Limiter S.Vasudevamurthy 1, Ashwini.V 2 1 Department of Electrical

More information

1. Explain the various methods of methods of grounding. In power system, grounding or earthing means connecting frame of electrical equipment (non-cur

1. Explain the various methods of methods of grounding. In power system, grounding or earthing means connecting frame of electrical equipment (non-cur 1. Explain the various methods of methods of grounding. In power system, grounding or earthing means connecting frame of electrical equipment (non-current carrying part) or some electrical part of the

More information

An Introduction to Insulation Resistance Testing

An Introduction to Insulation Resistance Testing An Introduction to Insulation Resistance Testing In a perfect world, electrical insulation would allow no current to flow through it. Unfortunately, a number of factors can over time result in the deterioration

More information

400 Volts, 50HZ 480 Volts, 60HZ 600 Volts, 60HZ TECHNICAL REFERENCE MANUAL

400 Volts, 50HZ 480 Volts, 60HZ 600 Volts, 60HZ TECHNICAL REFERENCE MANUAL 400 Volts, 50HZ 480 Volts, 60HZ 600 Volts, 60HZ TECHNICAL REFERENCE MANUAL FORM: MAP-TRM-E REL. July 2013 REV. 015 2013 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation Matrix AP Harmonic

More information

Power Quality. Guide for electrical design engineers. Power Quality. Mitigation of voltage unbalance

Power Quality. Guide for electrical design engineers. Power Quality. Mitigation of voltage unbalance Guide for electrical design engineers Power Quality Zbigniew Hanzelka GH-University of Science & Technology Mitigation of voltage unbalance U U = C = - = L U U = - U = - U Power Quality Power Quality.

More information

Cat. No. 140M-F M-D8E-B

Cat. No. 140M-F M-D8E-B Bulletin 0M Motor Protection Circuit Breakers Product Selection Motor Protection Circuit Breakers Short Circuit Protection Standard Magnetic Trip ( x I e ) Motor Overload Protection Trip Class Rated Operational

More information

Managing Emergency Generators

Managing Emergency Generators Managing Emergency Generators with nonlinear loads Author akshay thakur Application Engineer Kohler Co. Power Systems Division In this paper we will be focusing on the harmonic distortion that occurs in

More information

CHAPTER 6 STEADY-STATE ANALYSIS OF SINGLE-PHASE SELF-EXCITED INDUCTION GENERATORS

CHAPTER 6 STEADY-STATE ANALYSIS OF SINGLE-PHASE SELF-EXCITED INDUCTION GENERATORS 79 CHAPTER 6 STEADY-STATE ANALYSIS OF SINGLE-PHASE SELF-EXCITED INDUCTION GENERATORS 6.. INTRODUCTION The steady-state analysis of six-phase and three-phase self-excited induction generators has been presented

More information

Cahier Technique N 13 Principe de réduction des courants d enclenchement des transformateurs

Cahier Technique N 13 Principe de réduction des courants d enclenchement des transformateurs Cahier Technique N 13 Principe de réduction des courants d enclenchement des transformateurs Numerical transformer inrush current minimizer Principle of the operation Rev 1.0 Document version information

More information

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION EE 6501 POWER SYSTEMS UNIT I INTRODUCTION PART A (2 MARKS) 1. What is single line diagram? A Single line diagram is diagrammatic representation of power system in which the components are represented by

More information

Mitigation of Distributed Generation Impact on Protective Devices in a Distribution Network by Superconducting Fault Current Limiter *

Mitigation of Distributed Generation Impact on Protective Devices in a Distribution Network by Superconducting Fault Current Limiter * Energy and Power Engineering, 2013, 5, 258-263 doi:10.4236/epe.2013.54b050 Published Online July 2013 (http://www.scirp.org/journal/epe) Mitigation of Distributed Generation Impact on Protective Devices

More information

Chapter 21. Harmonic Analysis

Chapter 21. Harmonic Analysis Chapter 21 Harmonic Analysis Because of the wide and ever increasing applications of power electronic devices, such as variable speed drives, uninterruptible power supplies (UPS), static power converters,

More information

Instruction. Vacuum Circuit Breaker Operator Module. Type 3AH 4.16kV to 38kV. Power Transmission & Distribution

Instruction. Vacuum Circuit Breaker Operator Module. Type 3AH 4.16kV to 38kV. Power Transmission & Distribution Instruction 0001-22-2--00 Vacuum Circuit Breaker Operator Module Type 3AH 4.16kV to 38kV Power Transmission & Distribution Hazardous voltages and high-speed moving parts. Will cause death, serious injury

More information

EE Branch GATE Paper 2010

EE Branch GATE Paper 2010 Q.1 Q.25 carry one mark each 1. The value of the quantity P, where, is equal to 0 1 e 1/e 2. Divergence of the three-dimensional radial vector field is 3 1/r 3. The period of the signal x(t) = 8 is 0.4

More information

Low Frequency Transients

Low Frequency Transients Page 1 IEEE Power Engineering Society Summer Meeting Edmonton, July 18-22, 1999 Tutorial: Power System Overvoltages Low Frequency Transients Presented by Bruce Mork Work Done by Slow Transients Task Force

More information

Issued August DATA SHEET. 3VT3 MCCB up to 630 A

Issued August DATA SHEET. 3VT3 MCCB up to 630 A ssued August 9 DATA SHEET VT MCCB up to 6 A Based on Siemens Catalog V 6 8 Circuit breakers Switch disconnectors Technical specifications Specifications Type VT 76-AA6/6/56-AA, VT 76-AA6/6/56-AA Circuit

More information

Current protection I 2 t long-time protection

Current protection I 2 t long-time protection I 2 t long-time protection The long-time protection function protects cables against overloads. This function is based on true rms measurements. It is possible to select either I 2 t long-time protection

More information

TeSys circuit-breakers

TeSys circuit-breakers Presentation Thermal-magnetic motor circuit-breakers types GV2, GV and GV7 GV2-ME, GV2-P, GV-ME and GV7-R motor circuit-breakers are -pole thermal-magnetic circuit-breakers specifically designed for the

More information

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester Electrical and Electronics Engineering EE 1352 Power System Analysis (Regulation 2008) Time: Three hours Answer all questions Part A (10

More information

Issued August DATA SHEET. 3VT5 MCCB up to 1600 A

Issued August DATA SHEET. 3VT5 MCCB up to 1600 A ssued August 9 DATA SHEET VT5 MCCB up to 0 A Based on Siemens Catalog V 8 Standard circuit breakers Releases Technical specifications Specifications VT5 circuit breakers Switch disconnectors Type Standards

More information

Chapter 15 Power And Harmonics in Nonsinusoidal Systems

Chapter 15 Power And Harmonics in Nonsinusoidal Systems Chapter 15 Power And Harmonics in Nonsinusoidal Systems 15.1. Average power in terms of Fourier series 15.2. RMS value of a waveform 15.3. Power factor THD Distortion and Displacement factors 15.4. Power

More information

Tab 18 - Apparent Power, Active Power, Reactive Power Distribution Systems Engineering - Course , Siemens Industry Inc., all rights reserved

Tab 18 - Apparent Power, Active Power, Reactive Power Distribution Systems Engineering - Course , Siemens Industry Inc., all rights reserved Tab 18 - Apparent Power, Active Power, Reactive Power Distribution Systems Engineering - Course 1 01, Siemens Industry Inc., all rights reserved Some Basic Concepts Review of some important definitions:

More information

EE 3120 Electric Energy Systems Study Guide for Prerequisite Test Wednesday, Jan 18, pm, Room TBA

EE 3120 Electric Energy Systems Study Guide for Prerequisite Test Wednesday, Jan 18, pm, Room TBA EE 3120 Electric Energy Systems Study Guide for Prerequisite Test Wednesday, Jan 18, 2006 6-7 pm, Room TBA First retrieve your EE2110 final and other course papers and notes! The test will be closed book

More information

Basics of Electric Circuits

Basics of Electric Circuits António Dente Célia de Jesus February 2014 1 Alternating Current Circuits 1.1 Using Phasors There are practical and economic reasons justifying that electrical generators produce emf with alternating and

More information

Reliability of Bulk Power Systems (cont d)

Reliability of Bulk Power Systems (cont d) Reliability of Bulk Power Systems (cont d) Important requirements of a reliable electric power service Voltage and frequency must be held within close tolerances Synchronous generators must be kept running

More information

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM Unit Objectives Describe the structure of an atom. Identify atoms with a positive charge and atoms with a negative charge. Explain

More information

Brief Steady of Power Factor Improvement

Brief Steady of Power Factor Improvement International Journal of Electrical Engineering. ISSN 0974-2158 Volume 6, Number 5 (2013), pp. 531-539 International Research PublicationHouse http://www.irphouse.com Brief Steady of Power Factor Improvement

More information

Module 3 : Sequence Components and Fault Analysis

Module 3 : Sequence Components and Fault Analysis Module 3 : Sequence Components and Fault Analysis Lecture 12 : Sequence Modeling of Power Apparatus Objectives In this lecture we will discuss Per unit calculation and its advantages. Modeling aspects

More information

CHAPTER 5 STEADY-STATE ANALYSIS OF THREE-PHASE SELF-EXCITED INDUCTION GENERATORS

CHAPTER 5 STEADY-STATE ANALYSIS OF THREE-PHASE SELF-EXCITED INDUCTION GENERATORS 6 CHAPTER 5 STEADY-STATE ANALYSIS OF THREE-PHASE SELF-EXCITED INDUCTION GENERATORS 5.. INTRODUCTION The steady-state analysis of six-phase SEIG has been discussed in the previous chapters. In this chapter,

More information

7. Transient stability

7. Transient stability 1 7. Transient stability In AC power system, each generator is to keep phase relationship according to the relevant power flow, i.e. for a certain reactance X, the both terminal voltages V1and V2, and

More information

HIGH VOLTAGE CAPACITORS DESIGNED TO AVOID CATASTROPHIC FAILURE MODES

HIGH VOLTAGE CAPACITORS DESIGNED TO AVOID CATASTROPHIC FAILURE MODES HIGH VOLTAGE CAPACITORS DESIGNED TO AVOID CATASTROPHIC FAILURE MODES F. W. MacDougall G. L. McKee, J.B. Ennis, R.A. Cooper Maxwell Energy Products, Inc. San Diego, CA. R. M. Ness,- Cymer, Inc. San Diego

More information

3VT4 Molded Case Circuit Breakers up to 1000 A

3VT4 Molded Case Circuit Breakers up to 1000 A VT4 Molded Case Circuit Breakers up to 00 A Catalog Technical nformation VT4 Molded Case Circuit Breakers up to 00 A General data / - Overview Circuit breakers Switch disconnectors / - Selection and ordering

More information

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous)

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad - 500 043 ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK Course Name : Computer Methods in Power Systems Course Code : A60222

More information

Power System Engineering Prof. Debapriya Das Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Power System Engineering Prof. Debapriya Das Department of Electrical Engineering Indian Institute of Technology, Kharagpur Power System Engineering Prof. Debapriya Das Department of Electrical Engineering Indian Institute of Technology, Kharagpur Lecture 41 Application of capacitors in distribution system (Contd.) (Refer Slide

More information

Power Factor Improvement

Power Factor Improvement Salman bin AbdulazizUniversity College of Engineering Electrical Engineering Department EE 2050Electrical Circuit Laboratory Power Factor Improvement Experiment # 4 Objectives: 1. To introduce the concept

More information

ECE2262 Electric Circuits. Chapter 6: Capacitance and Inductance

ECE2262 Electric Circuits. Chapter 6: Capacitance and Inductance ECE2262 Electric Circuits Chapter 6: Capacitance and Inductance Capacitors Inductors Capacitor and Inductor Combinations Op-Amp Integrator and Op-Amp Differentiator 1 CAPACITANCE AND INDUCTANCE Introduces

More information

activar - Performance in Mitigating Voltage Sags Associated with Motor Starting

activar - Performance in Mitigating Voltage Sags Associated with Motor Starting 66 Carey Road TEL: (518) 792-4776 www.nepsi.com Queensbury, NY 12804 FAX: (518) 792-5767 sales@nepsi.com activar - Performance in Mitigating Voltage Sags Associated with Motor Starting We are often asked,

More information

Analysis of factors affecting station capacitor bank switching transients

Analysis of factors affecting station capacitor bank switching transients Scholars' Mine Masters Theses Student Research & Creative Works 1971 Analysis of factors affecting station capacitor bank switching transients M. Davarpanah Follow this and additional works at: http://scholarsmine.mst.edu/masters_theses

More information

ECE 422/522 Power System Operations & Planning/ Power Systems Analysis II 3 Load Modeling

ECE 422/522 Power System Operations & Planning/ Power Systems Analysis II 3 Load Modeling ECE 422/522 Power System Operations & Planning/ Power Systems Analysis II 3 Load Modeling Spring 2014 Instructor: Kai Sun 1 References 1. Load Performance for Dynamic Performance Analysis, IEEE Committee

More information

08/072 PKZ2 Motor-Protective Circuit-Breakers Tripping Characteristics

08/072 PKZ2 Motor-Protective Circuit-Breakers Tripping Characteristics 0/07 PKZ Tripping Characteristics Moeller HPL0-00/00 S-PKZ high-capacity contact module, SEA-PKZ contact module Normal switching duty AC-/00V kw A Rated output of three-phase motors 0...0 Hz. 7..... 0.7

More information

ELECTROMAGNETIC OSCILLATIONS AND ALTERNATING CURRENT

ELECTROMAGNETIC OSCILLATIONS AND ALTERNATING CURRENT Chapter 31: ELECTROMAGNETIC OSCILLATIONS AND ALTERNATING CURRENT 1 A charged capacitor and an inductor are connected in series At time t = 0 the current is zero, but the capacitor is charged If T is the

More information

POWER FACTOR CORRECTION CAPACITOR CELLS SPECIFICATIONS

POWER FACTOR CORRECTION CAPACITOR CELLS SPECIFICATIONS SPECIFICATIONS DESCRIPTION Metallized polypropylene capacitors offer improved performance and proven reliability in applications requiring power factor correction or harmonic filtering. Metallized polypropylene

More information

RESULTS OF ON-GRID OPERATION OF SUPERCONDUCTOR DYNAMIC SYNCHRONOUS CONDENSER

RESULTS OF ON-GRID OPERATION OF SUPERCONDUCTOR DYNAMIC SYNCHRONOUS CONDENSER 1 RESULTS OF ON-GRID OPERATION OF SUPERCONDUCTOR DYNAMIC SYNCHRONOUS CONDENSER Dr. Swarn S. Kalsi, David Madura, and Michael Ross American Superconductor Corporation (USA) Abstract: A high-temperature

More information

POWER SEMICONDUCTOR BASED ELECTRIC DRIVES

POWER SEMICONDUCTOR BASED ELECTRIC DRIVES POWER SEMICONDUCT BASED ELECTRIC DRIVES [Time: 3 Hrs] [Max. Marks: 80] Instructions: Solve any six questions from Q.No (1 or 2), Q.No (3 or 4), Q.No (5 or 6), Q.No (7 or 8), Q.No (9 or 10), Q.No (11 or

More information

PUMP PERFORMANCE MEASUREMENTS Jacques Chaurette p. eng. April 2003

PUMP PERFORMANCE MEASUREMENTS Jacques Chaurette p. eng.  April 2003 PUMP PERFORMANCE MEASUREMENTS Jacques Chaurette p. eng. www.lightmypump.com April 003 Synopsis This article examines how to take flow and pressure measurement and then calculate the total head of a pump

More information

AC Circuits Homework Set

AC Circuits Homework Set Problem 1. In an oscillating LC circuit in which C=4.0 μf, the maximum potential difference across the capacitor during the oscillations is 1.50 V and the maximum current through the inductor is 50.0 ma.

More information

PowerApps Optimal Power Flow Formulation

PowerApps Optimal Power Flow Formulation PowerApps Optimal Power Flow Formulation Page1 Table of Contents 1 OPF Problem Statement... 3 1.1 Vector u... 3 1.1.1 Costs Associated with Vector [u] for Economic Dispatch... 4 1.1.2 Costs Associated

More information

Resistivity and Temperature Coefficients (at 20 C)

Resistivity and Temperature Coefficients (at 20 C) Homework # 4 Resistivity and Temperature Coefficients (at 0 C) Substance Resistivity, Temperature ( m) Coefficient, (C ) - Conductors Silver.59 x 0-0.006 Copper.6 x 0-0.006 Aluminum.65 x 0-0.0049 Tungsten

More information

Lecture 05 Power in AC circuit

Lecture 05 Power in AC circuit CA2627 Building Science Lecture 05 Power in AC circuit Instructor: Jiayu Chen Ph.D. Announcement 1. Makeup Midterm 2. Midterm grade Grade 25 20 15 10 5 0 10 15 20 25 30 35 40 Grade Jiayu Chen, Ph.D. 2

More information

Performance Improvement of the Radial Distribution System by using Switched Capacitor Banks

Performance Improvement of the Radial Distribution System by using Switched Capacitor Banks Int. J. on Recent Trends in Engineering and Technology, Vol. 10, No. 2, Jan 2014 Performance Improvement of the Radial Distribution System by using Switched Capacitor Banks M. Arjun Yadav 1, D. Srikanth

More information

Determination of Fault Location in Shunt Capacitor Bank through Compensated Neutral Current

Determination of Fault Location in Shunt Capacitor Bank through Compensated Neutral Current International Journal of Advances in Scientific Research and Engineering (ijasre) E-ISSN : 2454-8006 DOI: http://dx.doi.org/10.7324/ijasre.2018.32630 Volume 4, Issue 3 March - 2018 Determination of Fault

More information

Congestion Alleviation using Reactive Power Compensation in Radial Distribution Systems

Congestion Alleviation using Reactive Power Compensation in Radial Distribution Systems IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 11, Issue 6 Ver. III (Nov. Dec. 2016), PP 39-45 www.iosrjournals.org Congestion Alleviation

More information

Basic Distribution Software Tasks

Basic Distribution Software Tasks The Wind Interconnection Workshop Golden, CO May 22, 2013 Tom McDermott, tom@meltran.com MelTran, Inc. Basic Distribution Software Tasks Current Flow and Voltage Drop Conductor Overload? Voltage Range?

More information

Week No. 6 Chapter Six: Power Factor Improvement

Week No. 6 Chapter Six: Power Factor Improvement Week No. 6 Chapter Six: Power Factor Improvement The electrical energy is almost wholly generated, transmitted and distributed in the form of alternating current. Therefore, the question of power factor

More information

Alternating Current (AC): Alternating Current is electric current that reverses directions at regular intervals.

Alternating Current (AC): Alternating Current is electric current that reverses directions at regular intervals. Glossary Alternating Current (AC): Alternating Current is electric current that reverses directions at regular intervals. American National Standards Institute (ANSI): American National Standards Institute

More information

What happens when things change. Transient current and voltage relationships in a simple resistive circuit.

What happens when things change. Transient current and voltage relationships in a simple resistive circuit. Module 4 AC Theory What happens when things change. What you'll learn in Module 4. 4.1 Resistors in DC Circuits Transient events in DC circuits. The difference between Ideal and Practical circuits Transient

More information

ECEN 460 Exam 1 Fall 2018

ECEN 460 Exam 1 Fall 2018 ECEN 460 Exam 1 Fall 2018 Name: KEY UIN: Section: Score: Part 1 / 40 Part 2 / 0 Part / 0 Total / 100 This exam is 75 minutes, closed-book, closed-notes. A standard calculator and one 8.5 x11 note sheet

More information

An Intelligent Control Strategy for Power Factor Compensation on Distorted Low Voltage Power Systems

An Intelligent Control Strategy for Power Factor Compensation on Distorted Low Voltage Power Systems 1562 IEEE TRANSACTIONS ON SMART GRID, VOL. 3, NO. 3, SEPTEMBER 2012 An Intelligent Control Strategy for Power Factor Compensation on Distorted Low Voltage Power Systems Shunfu Lin, Member, IEEE, Diogo

More information

Introduction to AC Circuits (Capacitors and Inductors)

Introduction to AC Circuits (Capacitors and Inductors) Introduction to AC Circuits (Capacitors and Inductors) Amin Electronics and Electrical Communications Engineering Department (EECE) Cairo University elc.n102.eng@gmail.com http://scholar.cu.edu.eg/refky/

More information

90 MCB MODULAR CIRCUIT BREAKERS FOR CIRCUIT PROTECTION

90 MCB MODULAR CIRCUIT BREAKERS FOR CIRCUIT PROTECTION MCB - MTC - MT - MTHP Technical data TYPE MTC MT MTC45 MTC60 MTC100 MT 45 MT 60 Rated current (In) (A) 2-32 6-32 6-32 6-40 1-63 Utilization category A A A A A Rated operational voltage (Ue) (V) 230/400-240/415

More information

440V 500V V / / /2 12.

440V 500V V / / /2 12. -26 Manual Motor Protectors March 0 B-Frame D-Frame Table -6. XTPR Rotary Manual Motor Protectors with Screw Terminals Global Ratings and North American Ratings Type and Type 2 Coordination Motor Protective

More information

The Effects of Mutual Coupling and Transformer Connection Type on Frequency Response of Unbalanced Three Phases Electrical Distribution System

The Effects of Mutual Coupling and Transformer Connection Type on Frequency Response of Unbalanced Three Phases Electrical Distribution System IJSRD - International Journal for Scientific Research & Development Vol. 1, Issue 9, 2013 ISSN (online): 2321-0613 The Effects of Mutual Coupling and Transformer Connection Type on Frequency Response of

More information

3.3V Power Supply Isolated Current Sensor with Common Mode Field Rejection

3.3V Power Supply Isolated Current Sensor with Common Mode Field Rejection Fully Integrated Current Sensor IC 3.3V Power Supply Isolated Current Sensor with Common Mode Field Rejection Description The Senko Micro s provides economical and precise solutions for AC or DC current

More information

Pre-Lab. Introduction

Pre-Lab. Introduction Pre-Lab Read through this entire lab. Perform all of your calculations (calculated values) prior to making the required circuit measurements. You may need to measure circuit component values to obtain

More information

Trade of Electrician Standards Based Apprenticeship Capacitance Phase 2 Module No. 2.1 Unit No COURSE NOTES

Trade of Electrician Standards Based Apprenticeship Capacitance Phase 2 Module No. 2.1 Unit No COURSE NOTES Trade of Electrician Standards Based Apprenticeship Capacitance Phase 2 Module No. 2.1 Unit No. 2.1.8 COURSE NOTES Certification & Standards Department Created by Gerry Ryan - Galway TC Revision 1 April

More information

Exercise Dr.-Ing. Abdalkarim Awad. Informatik 7 Rechnernetze und Kommunikationssysteme

Exercise Dr.-Ing. Abdalkarim Awad. Informatik 7 Rechnernetze und Kommunikationssysteme Exercise1 1.10.015 Informatik 7 Rechnernetze und Kommunikationssysteme Review of Phasors Goal of phasor analysis is to simplify the analysis of constant frequency ac systems v(t) = max cos(wt + q v ) i(t)

More information

ECE 325 Electric Energy System Components 7- Synchronous Machines. Instructor: Kai Sun Fall 2015

ECE 325 Electric Energy System Components 7- Synchronous Machines. Instructor: Kai Sun Fall 2015 ECE 325 Electric Energy System Components 7- Synchronous Machines Instructor: Kai Sun Fall 2015 1 Content (Materials are from Chapters 16-17) Synchronous Generators Synchronous Motors 2 Synchronous Generators

More information

Secured Busbar Differential Protection Using A Computationally Efficient Dot Product Technique

Secured Busbar Differential Protection Using A Computationally Efficient Dot Product Technique Secured Busbar Differential Protection Using A Computationally Efficient Dot Product Technique Krish Narendra, ERLPhase Power Technologies Dave Fedirchuk, ERLPhase Power Technologies Abstract The use of

More information

COPPER FOR BUSBARS CHAPTER 4: SHORT-CIRCUIT EFFECTS

COPPER FOR BUSBARS CHAPTER 4: SHORT-CIRCUIT EFFECTS European Copper Institute COPPER FOR BUSBARS CHAPTER 4: SHORT-CIRCUIT EFFECTS David Chapman August 2011 ECI Available from www.leonardo-energy.org Document Issue Control Sheet Document Title: Publication

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current Transducer LDSR 0.3-TP/SP1 I P R N = 300 ma For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Features Closed

More information

UNISONIC TECHNOLOGIES CO., LTD LM78XX

UNISONIC TECHNOLOGIES CO., LTD LM78XX UNISONIC TECHNOLOGIES CO., LTD LM78XX 3-TERMINAL 1A POSITIVE VOLTAGE REGULATOR 1 TO-220 DESCRIPTION The UTC LM78XX family is monolithic fixed voltage regulator integrated circuit. They are suitable for

More information

An Ultra Low Resistance Continuity Checker

An Ultra Low Resistance Continuity Checker An Ultra Low Resistance Continuity Checker By R. G. Sparber Copyleft protects this document. 1 Some understanding of electronics is assumed. Although the title claims this is a continuity checker, its

More information

GATE 2010 Electrical Engineering

GATE 2010 Electrical Engineering GATE 2010 Electrical Engineering Q.1 Q.25 carry one mark each 1. The value of the quantity P, where P = xe dx, is equal to (A) 0 (B) 1 (C) e (D) 1/e 2. Divergence of the three-dimensional radial vector

More information

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME: EE 2303 - TRANSMISSION & DISTRIBUTION YEAR / SEM: III/V UNIT-I TRANSMISSION SYSTEM INTRODUCTION PART-A 1. What is

More information

5-V Low-Drop Fixed Voltage Regulator TLE 4269

5-V Low-Drop Fixed Voltage Regulator TLE 4269 5-V Low-Drop Fixed Voltage Regulator TLE 4269 Features Output voltage tolerance ±2 % 15 ma current capability Very low current consumption Early warning Reset output low down to V Q = 1 V Overtemperature

More information