Contents Kreatryx. All Rights Reserved.

Size: px
Start display at page:

Download "Contents Kreatryx. All Rights Reserved."

Transcription

1

2 Contents Manual for K-Notes... Transmission Lines... 3 Underground Cables Overhead Insulators Distribution Systems Per Unit System Load Flow Study Economic Power Generation... Fault Analysis... 1 Power System Stability... 9 Power System Protection Kreatryx. All Rights Reserved. 1

3 Transmission Lines Skin Effect It is tendency of AC current to be concentrated on the surface of conductor. Cause: Non-uniform distribution of magnitude flux linkages Due to skin effect, the effective area of cross section of conductor decrease and hence resistances increases. In case of DC, There is no skin effect so R R DC With increase in frequency, skin effect increases. With increase in, skin effect increases. r AC Inductance of a Transmission line Single Conductor Internal inductance r 8 External inductance from distance d 1 to r d Lex ln d 1 r r d Total inductance ln 8 r r d r d ln ln 1 re 4 r r.7788r = Geometric mean radius (GMR) d Single phase wire line r d Inductance of single wire ln r Total inductance = L1 L d Lsys ln r If radius of both wire is not same, assume radius of 1 st wire d Lsys ln ra r b r.7788r & r.7788r b b a a r a & that of second wire is r b If instead of a single conductor per phase we use multiple conductor, then GMR is replaced by self GND (Geometric Mean Distance) and d by mutual GMD. 3

4 Self GMD self GMD D 11 D 1...D 1n D 1 D...D n... D n1 D n...d nn Where fwd D r.7788r ii i i Self GMD D ' ' D ' '...D i'm'... D ' '...D ' ' Where bwd ii Mutual GMD D r.7788r i i 1 i ml mm i Mutual GMD D ' D '...D '... D ' D '...D ' m n1 n nm Now, with these terms all the inductance expressions change to 1 m 1 mn 1 n Single wire : d ln self GMD mutual GMD 1, wire: ln Self GMD Three phase Transmission line Symmetrical configuration L ph r D ln r r.7788r 4

5 Asymmetrical configurations If conductors are placed horizontally or vertically. 1 3 D D D D L eq ab bc ca ph D r ln r eq In case of bundled conductor, more than one conductor per phase We replace Dab D = mutual GMD between a phase & b phase abeq Similarly, D bc D bc eq D ca D caeq In place of GMR, Self GMD is used Self GMD= Self GMD Self GMD Self GMD a b c Example: Calculate inductance per phase of following circuit? 1 3 Between successive conductors, distance = 3m, Radius of each conductor = 1m Solution 1 4 D D. D. D. D ab eq a1b1 a1b ab1 ab m 1 4 D m bc eq 1 4 D m ca eq D eq = mutual GMD 1 3 Dab.eq Dbc.eq D ca.eq = 5.71m 5

6 1 4 Self GMD rd D r a a1a aa =.341m Self GMD rd D r b b1b =.467m bb1 1 4 Self GMD rd D r c c1c =.158m cc1 1 3 Self GMD Self GMD Self GMD Self GMD c a =.398m GMD L ln GMD Self ln.634mh/ km.398 Remember, Inductance calculated using these formulas is per unit length. b Transposition of Transmission line The position of different lines are changed after regular intervals to reduce radio interference in neighboring communication lines. Capacitance Single Phase Wire System C ab r D ln rr 1 Line to neutral capacitance 6

7 C an r D ln r 1, C bn r D ln r Three phase single conductor system C ph r GMD ln r For bundled conductors C ph GMD ln Self GMD In capacitance calculations, it must always be remembered that there is no concept of r, we simply use radius in calculating self GMD. Performance of Transmission line Classification of lines based on length 1) Short Line l < 8 km or l*f < 4, Where f = frequency ) Medium Line 8 km < l < km 4 < l*f < 1 3) Long Line l > km l*f > 1 Modeling of transmission lines Transmission lines are modeled as port network Vs AVR BIR Under no load Is CVR DIR IR, Vs AVR, Vs VR A 7

8 No Load Voltage Voltage Regulation V s and IR, I s CV R A Vs VR A 1% V R This current is called as line charging current and is responsible for as effect is called as Ferranti Effect. Ferranti Effect Under no-load or light load conditions receiving end voltage becomes more than sending end voltage due to presence of line charging current. Short transmission line V V I R jwl s R R R R V I Z Vs 1 z VR I 1 I s R A = D (symmetrical) AD BC = 1 (reciprocal) Approximate Voltage Regulation For lagging pf For leading pf IR VR= R cos X sin R V R load pf=cos R I R VR RcosR X sin R VR R 8

9 Medium Transmission Line Normal T Model YZ YZ 1 Z 1 V 4 V s I s Y 1 R YZ IR Here all problems are in actual values & not per unit length. Nominal-π-Model YZ 1 Z V V s R I YZ YZ I s Y 1 1 R 4 Long transmission Line Vx VR cosh X IRZc sinh x V R IR IRcoshx sinh x Zc Where V x & I x are voltage and current at distance x from receiving end. Z c R jl = surge impedance G j C In case of long transmission line, we use all promoters per-unit length. For loss less line, R=G= Z c L C For distribution less line, RC = LG For sending end, x = l V V cosh l I Z sinh l s R R c V R I I coshl+ sinh l s R Zc 9

10 cosh l Z sinh l c V V s R 1 I cosh l I s R Z c A = D (symmetric) AD - BC = 1 (reciprocal) Power Transfer Equation Vs Vr A P r cos V cos B B r For Short TL Vs Vr A Q r sin V sin B B B r Z B Z ; A 1 A A 1, = Vs Vr Vr Pr cos cos Z Z Vs Vr Vr Qr sin sin Z Z If resistance of line is neglected Z jx X and 9 s r s r r R V V V V V Pr sin ; Q = cos X X X Remember, the last expression can be applied between any two bases in a power system as long as transmission line connecting them is loss less. Wave Propagation Due to continuous energy transfer between L & C elements of a transmission line we consider energy propagation from sending to receiving end & hence wave propagation. Z c = Surge impedance or characteristic impedance. 1

11 γ = Propagation constant. For loss less line R jlg j C R = G = O j LC j = attenuation constant = phase constant In case of loss less line (no attenuation) LC Velocity of wave 1, Where L & C are per unit length LC Wavelength LC Surge Impedance Loading When load impedance = surge impedance P L Vr(L L) = Surge Impedance Loading Z C If ZL ZC V I Z R R C According to long line V V coshx+v sinhx V e X R R R x yx So no term containing e & hence no reflected wave & hence whenever surge impedance is connected at load, there is no reflection. 11

12 Surge Traversal Theremin equivalent circuit When surge voltage V is induced on the line & line can be represented as Theremin equivalent circuit shown. Z C Z L = Characteristic impedance of line = load impedance or characteristics impedance of second line connected in series to first. L Transmitted voltage V V potential divider Incident Voltage Reflected voltage V1 V V Z ZL ZC V V V [Voltage continuity] Z Z L C V V Z L Z C V V Reflected current, Refracted current, Incident current Z Z C L V Z C Reflection coefficient: Refraction coefficient: V Z Z L V Z Z L L C C V ZL V Z Z C Voltage Control Usually in case of lagging loads, the voltage at receiving end falls below sending end voltage and to boost the receiving end voltage we connect a shunt capacitor at receiving end. Similarly, in case of leading loads, receiving end voltage is higher than sending end voltage so we connect a shunt reactor to avoid over-voltage. Usually in GATE, we need to calculate rating of capacitor for voltage control & it is illustrated through a question shown below: 1

13 Example: A three phase overhead lines has a resistance & reactance of 5 & respectively. The load at receiving end is 3MW,.85 pf lagging at 33kv & we connect a compensating equipment at receiving end to maintain voltage at each end equal to 33 Kv. Find rating of compensating equipment? Solution: Assuming base (MVA) = 3 MVA Base voltage = 33 kv pu power = 3Mw 1pu 3MVA Base impedance = pu impedance = V 36.3 S 5 j VS VR VR Z.568 ; =75.96 PR cos cos Z Z cos cos V V V QR sin sin Z Z cos sin sin S R R Q R Q L = pu 1 PL tan 1 tancos.85 Q =.6197 pu L QR QL QC QC 1.647pu QC = 37.9 MVAR So, we can observe the steps involved Step 1 : Calculate from P L as capacitor does not consume any real power. Step- : Calculate Q R using calculated above Step-3 : QR QL QC than Calculate Q C 13

14 Power Factor Correction Usually, to improve the supply side power factor we connect a capacitor device like capacitor bank or synchronous condenser (synchronous motor under over excited condition). Suppose, initially a load of real power & lagging pf is connected & we want to improve pf to lagging 1 & we connect a capacitive device which consumes real power P & thus net real power after connection. C P P1 PC cos Q P tan ; Q1 P1 tan 1 QC P1 tan1 P tan P 1 cos 1 In case of capacitor bank, PC P P 1 If we wish to calculate capacitance per phase (in both voltage control & pf correction ) Q C 3CV ph Q C 3V Underground Cables Insulation resistance R R ln l r C ph L = length of cable R = Outer radius (sheath radius) R = conductor radius Capacitance Model C C : Core capacitance C : Core to sheath capacitance S 14

15 Capacitance per phase Cph CS 3CC Calculating C S & C C 1) Any of two cores or conductors are connected to sheath & capacitance is measured between remaining core & sheath. C1 CS CC ) All three cores are connected together & capacitance is measured between any core & sheath. C 3C S C C S 3 C C C C 1 3 C C 1 C C 6 3C1 C Cph CS 3CC 6 3) Any one of core is connected to sheath & capacitance is measured between remaining cores. C 3 3CC CS C C ph 3 15

16 Dielectric loss in a UG cable P 3C V tan ph ph where tan loss tangent 1 tan c R ph R = Insulation resistance Overhead Insulators For suspension type string insulator, the model for 3-discs looks like as shown. Let C m C 1 m V V 1 m S V3 V1 1 m 3m The voltage of disc nearest to the conductor is highest. String efficiency No. of discs V V V V 3 string voltage voltage across bottom disc 1% Distribution Systems Sources fed from both ends 1) Assume from ) Calculate I A I A from V A I in I I, I I I & I I I I V V I I r I I I r I I I I r A B A 1 1 A 1 A ) Substitute A & check for sign change. A 1 A 1 A 1 3 4) Node for minimum potential = Node for sign change 5) Calculate minimum potential by KVL Example: Refer Kuestion power systems for that. 16

17 Per Unit System Base value In pu system, energy quantity is expressed as a ratio of some based value. Absolute value or Actual value pu value= Base value Percentage value = pu value x 1% 1 - System S base, V base, I base, Z base Out of these, value must be known, to convert entire system into pu system. S V I base base base S V V I, Z base V I S base base base base base base base Usually, we assume S base & V base as known. 3 - System S base I base V base S base & V base S base 3 V are assumed base = line to line voltage = 3 phase power For start connection V ph V / 3 V Zbase I ph I S base base base base base base For delta connection V ph V 3V Zbase I ph I / 3 S base base base base base base In per unit system, equivalent impedance of transformer referred to primary or secondary in same. 17

18 Change of base If base of system is changed from Vbase old, Sbase old to Vbase new,sbase new pu Z new Z old Load Flow Study Power System Matrices base base pu Vbase new Sbase old V old S new YBUS matrix y1 y1 y1 YBUS y1 y y1 y3 y3 y y y OBSERVATIONS ) The diagonal elements are sum of all admittance connected to that particular bus. ) The off-diagonal elements are negative of admittance connected between two buses. 3) If two buses are not connected to each other than that elements is zero. 4) Matrix is a symmetrical matrix. Y BUS 5) Most of the elements are zero & hence it is a sparse matrix. Total number of zero elements % sparsity = Total number of elements Z matrix BUS Z BUS Y 1 BUS Z BUS matrix used in fault analysis. Suppose a 3 phase SC fault occurs on bus k then fault current V prefault,k If Z Z V, k Pr e fault voltage at bus 'k' prefault Z kk = elements of Z BUS matrix. Z = fault impedance f kk f Due to fault voltage at other buses are also affected. 18

19 V I V I k k.. Z. V Z BUS BUS BUS I f... V I n n. V I Z k f kk V f If Zf Zkk V Z I " j jk f Z Vj Z kk jk V f Post fault voltage at bus j Z jk V V jf j Vf Z kk If there is generator connected to bus j then current supplied by generator. Eg Vjf I " jx d Classification of buses At each bus, there are 4 parameter: V,,P,Q. At any bus, out of these 4 quantities any are specified. 1) Slack Bus / Swing Bus/Reference Bus V, are know quantities. P, Q are unknown quantities. Any extra power needed by the system is supplied by slack bus. ) Generator Bus / PV Bus P, V is specified Q, are unspecified 19

20 3) Load Bus / PQ Bus P & Q are constant as specified V & are unknown Generally, newton Raphson method is used for load flow solution and we form Jacobian matrix, & the order of Jacobian matrix is n m n m N = no. of total buses M = no. of pv buses Economic Power Generation Incremental cost If is cost required to generate an additional unit of energy. = Incremental cost of generator IC i i IC Gi i C P Gi P = Power generated by i th generator C i = cost of th i generator i th Transmission Loss m P P, P i j m PP B L i j ij i1 j1 : Real power injection at i th & j th buses B ij = loss coefficient m : no. of generator units Penalty Factor 1 L i P L 1 P Gi For economic power sharing IC L i i cons tant Constant is called as incremental cost of system. IC = incremental cost i th unit i L i = penalty factor of i th unit

21 From this expression, for m generator we get ( m 1) equation and m i1 P P P Gi D LOSS P D = total power demand For example, refer kuestions on Power systems. th m equation is Fault Analysis Symmetrical Components For an unbalanced 3 phase system, the analysis is done better by means of symmetrical components. Va Zero sequence components Va1 Va Positive sequence components Negative sequence components V a V a 1 Va1 1 Vb 3 V a 1 V c V 1 s A V p = phase voltage = Symmetrical component V p V s A 1 1 ; Where j1 e Power in terms of symmetrical components P 3 V I V I V I a1 a1 a a a3 a Remember, same transformation exist for current also. Sequence Network Alternators Positive Sequence Network Z 1 positive sequence impedance " Z jx 1 d 1

22 Negative Sequence Network V Z Z I Z a a : Negative sequence impedance X d" X q" j Zero Sequence Network V I Z 3Z Z a a n = Zero sequence impedance Z n =Neutral impedance ( Z X l jx l = leakage reactance in case of delta) Transformers Positive Sequence Network Z 1 = Positive sequence impedance Z jx 1 l Negative Sequence Network Z = Negative sequence impedance Z jx l Zero sequence network Depending upon scheme of connection, we close series or shunt connection & method of grounding.

23 Case 1 Shunt connection are closed for delta connection & series connection are closed for star connection with grounded neutral. If primary & secondary are inter changed then circuit becomes mirror image. If neutral is grounded through an impedance Z n Z Z T 3Zn Case Case 3 Case 4 3

24 Case 5 Transmission Lines Positive Sequence Network Negative Sequence Network Zero Sequence Network Z1 Z Zs Zm Z Zs Zm Z s = Self impedance Z m = mutual impedance Remembers, all sequence networks are always drawn in per unit & never in actual values. Fault Analysis The following short circuit faults are considered 1. LG (Single Line to ground fault). LL (Line to line fault) 3. LLG (Line to Line to Ground fault) 4. 3-phase short circuit fault. 4

25 3-phase short circuit fault comes under the category of symmetrical SC fault whereas other 3 faults are called as unsymmetrical SC fault. Order of severity LG < LL < LLG < 3 - SC But if faults occur at terminal of alternator then LG fault is most severe. Occurrence of SC fault LG > LL > LLG > 3 - SC Transient on a Transmission line Equivalent Circuit it it iss V Rt m sin e sin wt Z V L m L R Z 1 tan ; Z R L Maximum momentary current i mm V Z m sin If resistance is neglected, 9 i mm Vm cos Z Short circuit model of a synchronous machine During initial SC period for 1- cycles, current are induced in field & damper winding of machine so reactance at least & called as sub transient reactance X " After initial sub-transient period, current in damper winding in reduced to zero, and this period is called as transient period & reactance of machine is called as Transient Reactance X " d d 5

26 Finally, when current in field winding is also reduced to zero, we enter steady state period & reactance is called as steady state reactance. X d " X d ' Xd Symmetrical Fault Analysis X d We replace alternators by an emf source in series with sub transient reactance and emf source under no-load is usually pu or terminal voltage in pu. Vt Ef pu V base 1 Transformer & Transmission lines are replaced by reactance. The equivalent circuit can be solved either by finding thevenin equivalent across fault or by simple network analysis & fault in SC is calculated. I f Z eq E f Z f Z f = fault impedance. In symmetrical fault analysis, we only consider positive sequence impedance. 1 SC MVA pu Z Z SCMVA eq MVA Z eq f base Z f MVA For example, refer to kuestion on power systems. Selection of Circuit Breakers Usually, circuit breakers are selected on the basis of most severe fault which is 3 phase SC fault. Three ratings of circuit Breakers are important. 1) Rated momentary current Momentary current ( rms ) = 1.6 Isc I is symmetrical SC current which we calculated in previous section. sc ) Making current Making current =.54 Isc 6

27 3) Symmetrical Interrupting Current We need to recalculate by using sub-transient reactance for alternators & transient I sc reactance for synchronous motors. Induction motors & other loads are neglected. Then, we multiply it by a factor to calculate symmetrical interrupting current. This factor depends on speed of circuit breakers which is measured in terms of numbers of cycles it takes to operate. Speed 8 Cycles or slower 5 Cycles 3 Cycles Cycles Factor Unsymmetrical Faults Analysis Line to Ground Fault We first draw equivalent positive, negative & zero sequence networks & calculate thevenin impedance across fault terminals from each network. Assuming equivalent positive, negative & zero sequence reactance are Z 1,Z & Z respectively. Here all sequence currents are equal. Ia1 Ia Ia I a1 Ea Z Z Z 3Z 1 f Fault current I a I a 3I a1 I a 3Ea Z Z Z 3Z 1 f Short Circuit MVA SC MVA 3E a1,i a1 * 7

28 3 E I a1 Z Z Z 3Z 1 f In pu SCMVA 3 Z Z Z 3Z 1 f pu 3 MVA base Z Z Z 3Z 1 f MVA Line to Line Fault Here, we calculate equivalent positive & negative sequence impedance Z 1 & Z respectively. I a1 Ea Z Z Z 1 f Fault current I b j 3 E Z Z Z 1 a f Short Circuit MVA SC MVA 3 Z Z Z 1 f pu 3 MVA base Z Z Z 1 f MVA Line to Line to Ground Fault I I a1 a Ea Z Z Z 3Z Ia1 Z Z Z 1 f Fault Current = 3 Iao 8

29 Short Circuit MVA SC MVA 3 Z Z 1 3Z Z 1 f pu 3 MVA base Z Z Z 3Z 1 f MVA Remember, all fault analysis will be done in pu system. Power System Stability Two types of stability are studied: 1) Steady State Stability ) Transient Stability Steady State Stability For Steady State Stability dp d And for this condition to be true. P P e max If power demand is greater than maximum demand than machine goes out of synchronous. EV For a loss less machine, P max X Transient Stability Swing Equation Md P P m e dt M = inertia constant ( MJ-S / elect - rad) P m= mechanical input (MW) = electrical output (MW) P e = rotor angle Another Form Hd P P m e f dt H = inertia constant ( MJ / MVA) P & P e both are in pu m S 9

30 GH M 18f GH M f (MJ S / elect - deg) (MJ S / elect - rad) G = machine rating (MVA) If two alternators are swinging coherently. Then they can be replaced by a single alternator having M M M eq 1 But H cannot be added directly, they must first be on same base. If machines are not swinging coherently, then MM 1 Meq M M Accelerating Power, P P P a m e 1 In steady state P m P e In transient, P m P so rotor accelerate or decelerate. e Equal area criterion For system to possess transient stability P d a There are basically 3 stages in stability analysis Before Fault We say maximum power transferrable is P max,1 & e P P sin max,1 During fault We say maximum power transferrable is P max, P P sin e max, After Fault We say maximum power transferrable is P max,3 P P sin e max,3 3

31 Critical clearing angle It is the maximum value of beyond which if the fault is cleared system will be unstable. The time instant corresponding to this angle is called as critical clearing time assuming fault occurs at t =. Case-1 : Fault occurs on TL near to bus Pmax, P max,3 Cr P max,1 clearing angle By equal area criteria P P sin d m max,1 P 1 m sin P max,1 For critical clearing max t Cr max m H Cr = Critical Clearing Time f P Case- : Fault occurs on one of parallel lines close to bus Before Fault P max,1 EV X X X During Fault g 1 EV Pmax, X After Fault P max,3 eq EV X X g 1 31

32 P sin P 1 m max,1 1 Pm max sin P max,3 For transient stability P d a c m m max,3 P d P P sin d c For critical Clearing max t Cr H f Cr P m Case-3 : Fault occurs in middle of one of parallel lines The equivalent reactance during the fault is highest and thus P max, is lowest Pmax,1 Pmax,3 Pmax, P d a c For critical clearing, m max, max,3 m P P sin d P sin P d max c 1 Pm sin P max,3 3

33 P P cos P cos cr cos1 Pmax3 Pmax m max max,3 max max This is a generic formula and can be applied to other two cases as well after substituting value of P max,1, P max, & P max,3. But t cr before. can only be calculated from cr in previous two cases using expression written Power System Protection In our current protection, normally a current transformer is connected between protected elements and the relay. Plug setting multiplier (PSM) Fault current T ratio Pick up current Usually pick up current = Relay setting x Rated secondary current of CT Pick-up current is minimum current above which a relay operates. Differential Relays The current through operating coil k I I 1 If this current is greater than pick-up current then it operates, else it does not operates. K I I I Trip 1 pick up 1 pick up K I I I Block We usually provide a restraining coil to avoid relay mal-operation. Relay operates if Nr I1 I K I I K I N 1 pu I pu = pick up current N r = Number of turns in restraining coil N = Number of turns in operating coil The ratio operating coil current & restraining coil current is called as bias of differential relay. 33

34 Protection of Transmission line 1) Mho relay is at least affected by power surges& thus it is used for protection of long transmission lines. It is inherently directional. ) Impedance relay is used for protection of medium transmission lines. 3) Reactance relay is unaffected by ground resistance & hence used for earth fault protection & also for short transmission Lines. These relays are collectively called as distance relays. Protection of Transformers Differential relays are used for protection of large transformers and CT are always connected in configuration opposite to power transformer. Example: 1) If power transformer is Y then CT is Y : ) If power transformer is then CT is Y Y Buccholz relay used to prevent any incipient fault below oil level in a transformer of small KVA. 34

35 Kuestion Power Systems

36 Contents Manual for Kuestion... Type 1: Capacitance and inductance... 3 Type : SIL loading... 4 Type 3: ABCD parameter... 5 Type 4: Surges... 7 Type 5: Voltage control... 8 Type 6: Power factor correction... 1 Type 7: UG cable Type 8: Overhead Insulators... 1 Type 9: Distribution Systems Type 1: Economic Dispatch Type 11: Per unit system Type 1: Symmetrical Components... Type 13: Fault Analysis... Type 14: Thevenin Impedance... 4 Type 15: Power System Stability... 5 Type 16: Swing equation... 7 Type 17: Power System Matrices... 8 Type 18: Load flow Solution Type 19: Plug setting Multiplier Answer Key Kreatryx. All Rights Reserved. 1

37 Type 1: Capacitance and inductance For Concept, refer to Power Systems K-Notes, Transmission Lines Common Mistake: While calculating capacitance we do not use GMR but rather the radius of conductor, so this is the basic difference in Inductance and Capacitance calculation. Sample problem 1: The conductor of a 1km long, single phase, two wire line are separated by a distance of 1.5m. The diameter of an each conducting is 1cm. If the conductors are of copper, the induction of the circuit is? (A)5.mH (B)45.3mH (C)3.8mH (D) 19.6mH Solution: (C) is correct option Inductor of a single phase circuit with copper conductors d L L.ln( ) ab a r Given d=1.5m, r=.5cm, r =.7788 L L ab ab 1.5.4ln mh / km mH / km For 1km length of the line L ab =3.8 mh m Unsolved Problems: Q.1 Single phase concentric cable 5 km long has a capacitance of. F per km, the relative permeability of the dielectric being 3.5. the diameter of the inner conductor is 1.5 cm and the supply voltage is 66 kv at 5 Hz. Calculate the inner diameter of outer conductor (A) 3.9 cm (B) 1.95 cm (C) 3. cm (D) 1.6 cm Q. A double circuit 3-phse transmission line is shown below. The conductor a,a I ; b,b I and c,c I belong to the same phase respectively. The radius of each conductor is 1.5 cm. Find the inductance of the double circuit line in mh /km /phase. (A).191 (B).455 (C).755 (D).95 3

38 Q.3 A 3 phase double circuit line is shown in the figure. The diameter of each conductor is cm. Determine the capacitance per km length of the line, assume that the line is transposed. (A).11 F (B).15 (C).19 F (D).175 F F Q.4. Fig. shows the spacing s of a double circuit 3-phase overhead line. The phase sequence is ABC and the line is completely transposed. The conductor radius is.75 cm each. Inductance per phase per km is (A).46 mh (B).737 mh (C).63 mh (D).589 mh Q.5 A single phase 6 Hz transmission line and a telephone line both are supported on a horizontal cross-arm in the same horizontal plane. The spacing between transmission line conductors is.5m and conductors of the telephone line are of solid copper spaced.6m between centres. The distance between the nearest conductors of the two lines is cm. A current of 15 A is flowing over the power line. The value of mutual inductance between the circuit is? (A).1 mh/km (B).67 mh/km (C).46 mh/km (D).33 mh/km Type : SIL loading For Concept, refer to Power Systems K-Notes, Transmission Lines Common Mistake: While calculating SIL if we are using standard formula then we need to consider Line to Line Voltage and if we use phase voltage we need to multiply the formula by a factor of 3. Sample problem : A loss less transmission line having Surge Impedance Loading (SIL) of 8 MW is provided with a uniformly distributed series capacitive compensation of 3%. Then, SIL of the compensated transmission line will be (A) 1835 MW (B) 8 MW (C) 75 MW (D) 357 MW Solution: (C) is correct option 4

39 Let characteristic impedance Z impedance / km Z 1 sc c admittance / km Z 1 oc 1 pu Given that for line 3% series capacitive compensation is provided. Hence the series impedance of line is.7 or 7% of original value..7 Z.836 pu new 1. V Surge imedance loading (SIL)= Z SIL 1 (SIL) Z Z (SIL) Z c1 c 1 c 1. (SIL) 8M 75 MW.836 Unsolved Problems: c Q.1 The L/C ratio for 13KV and 4KV lines are typically 16*1 3 and 6.5*1 3 respectively. The neutral 3-phase loading for the two line will be respectively? (A) 44 MW and 5 MW (C) 64 MW and 44 MW (B) 44 MW and 64 MW (D) 18.9 MW and 56 MW Type 3: ABCD parameter For Concept, refer to Power Systems K-Notes, Transmission Lines Common Mistake: While using Transmission Parameters the voltages used should be per phase and not line to line voltages. Sample problem 3: The generalized circuit constants of a 3-phase, kv rated voltage, medium length transmission line are A D.936 j B 35.5 j C ( 5.18 j914) 1 6 If the load at the receiving end is 5 MW at kv with a power factor of.9 lagging, then magnitude of line to line sending end voltage should be (A) kv (B). kv (C) kv (D) 46.3kV Solution: (C) is correct option 5

40 Power received by load =5MW Current at receiving end = r 3V I cos r r I A r I cos =.9 = V AV BI KV s r r 3 Line to line sending end voltage = KV KV Magnitude of line to line sending end voltage =3.78KV Unsolved Problems: Q.1 A km 3-phase 5Hz transmission line has the following data A D B / phase C.19 /phase The sending end voltage is 3KV. The receiving end voltage is maintained as kv. The maximum power that can be transmitted and the correspond reactive power. (A) 33.8Mw, 311 MVAR (C) 311Mw, 33.8MVAR (B) 33.8Mw, MVAR (D) 311Mw 33.8 MVAR Q. A 5Hz, 3-phase transmission line is km long has total series impedance of (35 + j 14) ohms / phase and a shunt admittance of 93 x Mhos / phase. It delivers a load of 4Mw at kv with.9 p.f. lag. Find the magnitude of sending voltage for line to line in kv. (A) 3.4 (B) 9.8 (C) 7.6 (D) 36.5 Q.3 The generalized circuit constants of a nominal circuit representing a 3-phase transmission line are A = D =.98.3, B =.5 76 ohm, C =.5 9 mho, The two terminal voltages are held constant at 11 kv. If shunt admittance and the series resistance are zero, steady state stability limit is(mw) (A) (B) (C) (D) Q.4 A short 3 phase transmission line with an impedance of (6 + j8) Ohms per phase has sending and receiving end voltages of 1 kv and 11 kv respectively for some receiving end load at a point of.9 lagging. The sending end power factor is (A).88 lag (B).8 lag (C).84 lag (D).78 lag 6

41 Q.5 Two identical 3-phase transmission lines are connected in parallel to supply a load of 1MW at 13 KV and.8 pf lagging at the receiving-end. The constants of each transmission line are as follows; A.981,B 175 / phase What are the values of constant A and B for the combined network? (A) (C) A 1.961,B 75 (B) A 11,B.9875 (D) A.981,B 575 A.981,B 175 Type 4: Surges For Concept, refer to Power Systems K-Notes, Transmission Lines Common Mistake: If a line is terminated in characteristic impedance then there is no reflection so you need not solve the entire problem if you encounter such a case. Sample problem 4: A surge of kv magnitude travels along a lossless cable towards its junction with two identical lossless overhead transmission lines. The inductance and the capacitance of the cable are.4 mh and.5 μf per km. The inductance and capacitance of the overhead transmission lines are 1.5 mh and.15 μf per km. The magnitude of the voltage at the junction due to surge is (A) 36.7 kv (B) kv (C) 6.7 kv (D) kv Solution: (A) is correct option Surge impedance of cable L Z L=.4 mh/km, C=.5F/km 1 C surge impedance of overhead transmission line L Z Z ; L=1.5 mh/km, C=.15F/km 3 C Now the magnitude of voltage at junction due to surge is being given by as 3 V Z V 36.7KV Z Z

42 Unsolved Problems: Q.1 A 13 kv transmission line AB is connected to a cable BC. The characteristic impedances of the overhead line and the cable are 4 and 8 respectively. Assume that these are purely resistive A 5 kv switching surge travels from A to B. The value of the reflected component of this surge when two first reflection reaches A (A) kv (B) kv (C) kv (D) kv Q. The ends of two long transmission lines A and C are connected by a cable B. The surge impedances of A,B and C are 5, 7 and 6 ohms respectively. A rectangular voltage wave of KV magnitude and of infinite length is initiated in A travels to C. Second impressed voltage on C is (A) 14.1 KV (B) 8.8 KV (C) 3.5 KV (D) 5.3 KV Q.3 A surge f 1KV travelling in a line of natural impedance 6Ω arrives at a junction with two lines of impedance 8Ω and Ω respectively. What is the value of surge voltage? (A)4.9KV (B)43.76KV (C)45.98KV (D)4.4KV Q.4 What is the first impressed surge voltage and currents into line-3 from following network (A)38.96 KV, A (B) KV, 63.4 A (C)77.9 KV, A (D) KV, A Type 5: Voltage control For Concept, refer to Power Systems K-Notes, Transmission Lines Common Mistake: It is always easier to solve these type of problems in pu system rather than actual values. Sample problem 5: A 3-phase 11 kv generator feeds power to a constant power unity power factor load of 1MW through a 3-phase transmission line. The line-to line voltage at the terminals of the machine is maintained constant at 11 kv. The per unit positive sequence impedance of the line based on 1 MVA and 11 kv is j.. The line to line voltage at the load terminals is measured to be less than 11 kv. The total reactive power to be injected at the terminals of the load to increase the line-to-line voltage at the load terminals to 11 kv is (MVAR) (A) 1 (B) 1.1 (C) 1 (D) 1.1 Solution: (D) is correct option 8

43 Given Load Power = 1 MW VS = VR = 11 kv p.u. (KV) j. (11) imedance of line Z j.4 L MV 1 So as to make the sending end voltage and receiving end voltage equal, the net reactive power demand at load must be zero. Let QC be the reactive power injected at load side and Qr be the reactive power received from supply. Q Q Q r C d Q Q Q Q r C C r In this case β=line impedance angle =9.4, =, A 1. V V A s r Pr cos( ) V cos( ) r B B cos(9 ) 11 cos(9 ) sin V V A sin( ) V sin( ) B s r Qr r Q Q r r B MVAR Unsolved Problems: sin( ) 11 sin(9) Q.1 The receiving end voltage of a km long are head transmission line is to be kept constant at 1 KV. Its Voltage regulation is % with a load. It a capacitor is connected in parallel which the load to reduce the regulation to 1% the sending end voltage is (A) 9KV (B) 1KV (C) 11 KV (D) 1KV Q. A 75Kv transmission line has A =.855, B = 75 what is the ratio of compensating equipment required in MVAR at the receiving end to maintain the sending and receiving end voltages at 75kV. The load at the receiving end is 15MW at.8 power factor lagging (A) 7.56 (B) (C) (D) Q.3 Three supply points A, B and C are connected to bus bar M. Supply point A is maintained at a nominal 75 KV and is connected to M through a 75/13 KV transformer (.1p.u.reactance) and a 13 KV line of reactance 5. Supply point B is nominally at 13 KV and is connected to M through a 13 KV line of 5 reactance. Supply point C is nominally at 75 KV and is connected to M by a 75/13 KV transformer (.1p.u reactance) and 13 KV line of 5 reactance. If at a particular point, the line voltage M falls below its nominal value 9

44 by 5KV, calculate the magnitude of reactive volt ampere injection required at M to reestablish the original voltage. The p.u values are expressed on a 5 MVA base and resistance may neglect throughout. (A) 7.6MVAR (B) 15.7 MVAR (C) 3 MVAR (D) 38 MVAR Q.4 A 3-phase, 5 Hz overhead transmission line is feeding a.8 power factor lagging load with both the sending end and receiving end line voltage held at 11KV. The sending-end voltage leads the receiving end voltage by 15 and the line constants are as following A.961,B 183 If a compensating device is required to met the demand of load, then VAR rating (in MVAR) of device should be? (A)4.71 (B).84 (C)19.3 (D) 1.87 Type 6: Power factor correction For Concept, refer to Power Systems K-Notes, Transmission Lines Common Mistake: While using formula for rating of compensating device the real power is always total three phase power. Also, we already consider Q as negative and hence answer comes out as positive for capacitor. Sample problem 6: At an industrial sub-station with a 4 MW load, a capacitor of MVAR is installed to maintain the load power factor at.97 lagging. If the capacitor goes out of service, the load power factor becomes (A).85 lag (B) 1. lag (C).8 lag (D).9 lag Solution: (C) is correct option Let the initial power factor angle =φ1 1 Given cos P tan tan KVAR supplied by capacitor 4 1 (tan tan14.7 ) cos.8 lag Hence if the capacitor goes out of the service the load power factor becomes.8 lag. 1

45 Unsolved Problems: Q.1 An induction motor operating at.8 pf lag consuming 3 KW. A zero power consuming synchronous motor is connected across the induction motor to raise the pf to.9 lagging. The reactive power drawn by the synchronous motor is? (A)97. KVAR lag (C)36 KVAR lag (B)97. KVAR lead (D)36 KVAR lead Q. A 4 V, 5 Hz, three phase balanced source supplies power to a star connected load whose rating is 1 3 kva,.8 pf (lag). The rating (in kvar) of the delta connected (capacitive) reactive power bank necessary to bring the pf to unity is? (A) (B) 1.6 (C) 16.6 (D) 1.47 Type 7: UG cable For Concept, refer to Power Systems K-Notes, Underground Cables. Common Mistake: While connecting core to core and core to sheath make sure that you combine capacitors correctly in series or parallel. Sample problem 7: Consider a three-core, three-phase, 5 Hz, 11 kv cable whose conductors are denoted as R,Y and B in the figure. The inter-phase capacitance(c1) between each line conductor and the sheath is.4 μf. The per-phase charging current is (A). A (B).4 A (C).7 A (D) 3.5 A Solution: (A) is correct option Given 3-Ф, 5 Hz, 11 kv cable C1 =. μf C =.4 μf Charging current IC per phase =? Capacitance Per Phase C = 3C1+ C C = 3*. +.4 = 1 μf ω = πf =

46 V Charging current I V( C) c X c = = Amp 6 Q.1 The charging current drawn by a cable with 3 cores and protected by a metal sheet when switched on to a 11 KV, 5Hz supply. The capacitance between two cores with the third core connected to the sheath is measured to be 3.7.F (A) 9.3 A (B) A (C) 16.3 A (D) A Q. In a 3 core cable capacitance between any two cores is.5µf and capacitance between any one of the core to sheath is.3 µf. What is capacitance measured between any two cores connected together and third core? (A)1.3µF (B) 1.µF (C) 1.1µF (D) 1.5µF Type 8: Overhead Insulators For Concept, refer to Power Systems K-Notes, Overhead Insulators. Common Mistake: Voltage Distribution can be obtained by using Voltage division and also by using KCL. Sample problem 8: Consider a three-phase, 5 Hz, 11 kv distribution system. Each of the conductors is suspended by an insulator string having two identical porcelain insulators. The self-capacitance of the insulator is 5 times the shunt capacitance between the link and the ground, as shown in the figure. The voltages across the two insulators are (A) e 3.74 kv,e.61 kv 1 1 (B) e 3.46 kv,e.89 kv (C) e 6. kv, e 4.3 kv 1 (D) e 5.5 kv, e 5.5 kv 1 Solution: (B) is correct option At A point I I I 1 3 C e 5C e 5C e 1 3 5e 6e......(1) 1 1

47 11k e e 6.35kV.....() 1 3 From equation (1) and () we can get e =.886kV and e =3.46kV 1 Unsolved Problems: Q.1 In a four disc string insulator capacitance grading is employed in order to get 1% string efficiency. The capacitance of shunt capacitor is.5 F and the capacitance of a disc near to cross arm is.1 F. The capacitance of a disc near to power conductor is (A).35 F (B).4 F (C).5 F (D).15 F Q.. The equivalent capacitor arrangement of the two string Insulator is shown below. The maximum voltage that each unit can with stand should not exceed 17.5 kv. The line to line voltage of the system is? (A) 17.5 kv (B) 33 kv (C) kv (D) 3.3 kv Q.3 In a 3 unit insulator string, voltage across the lowest unit is 17.5 KV and string efficiency is 84.8%. The total voltage across the string will be equal to? (A)8.85KV (B)44.5KV (C)88.5KV (D)44.5KV Q.4 If the voltage across the string of a string insulator assembly is 38KV, number of insulators discs are 4 and voltage across the lowest disc is 1KV, string efficiency is? (A)79.1% (B)7% (C)5% (D)1% Q.5 It is required to grade a string consisting of three suspension insulators. Determine the line to pin capacitance that would give the same voltage across each insulator of the string if the pin to earth capacitance are all equal to.5c? (A) C, C, C (C) C, C, C 5 3 (B) C, C, C 16 8 (D) 5C, 8C, 1C 13

48 Type 9: Distribution Systems For Concept, refer to Power Systems K-Notes, Distribution Systems. Sample problem 9: A distribution feeder of 1 km length having resistance, but negligible reactance, is fed from both the ends by 4V, 5 Hz balanced sources. Both voltage sources S1 and S are in phase. The feeder supplies concentrated loads of unity power factor as shown in the figure. The contributions of S1 and S in 1 A current supplied at location P respectively, are (A) 75 A and 5 A (C) 5 A and 75 A Solution: (D) is correct option Assume point of minimum voltage is A Assume resistance of entire feeder = R V 4 I.4R.(i) A 1 V 4 I.R I.R I 3.R A = 4.6 R I I 3 I 1 1 I = 5.(iii) I + 1R..(ii) From (i) & (ii) 4.4I1R 4.6IR 1R.6I.4I1 1 (iv).4i.4i. (v) 1 Contribution of I to I I 1A Contribution of I to I P 1 P A (B) 5 A and 5 A (D) A and 1 A Unsolved Problems: Q.1. A two line d.c. distributor fed from both ends is shown below. The Minimum Voltage on the distributor is (A) (B).45 (C) (D)

49 Q. A single phase two wire feeder 15m long is shown below what is the voltage at the sending end. The impedance A at the feeder is (.6 +.1) ohms / km (A) (B) 5.56 (C) (D) 45.1 Q.3 A dc wire ring main distributor is shown below. Find the total currents supplied by two sources. The resistance of each conductor.1 ohms/km. The source voltages are equal (A) 9.78 A, 19.8 A (B) 1. A, A (C) A, 94. A (D) 115. A, A Q.4 A wire DC distributor ABCDEA in the form of a ring main is fed at point A at V and is loaded as shown in the figure. The minimum potential on the distributor is (A) V (B)16.15 V (C)16.45 V (D)18.8 V Type 1: Economic Dispatch For Concept, refer to Power Systems K-Notes, Economic Power Generation. Point to Remember: Just remember the basic formulas for factors related to plant and no need to memorize all factor just a few important ones are fine. 15

50 Sample problem 1: The figure shows a two-generator system applying a load of PD = 4MW, connected at bus. The fuel cost of generators G1 and G are : C1(PG1) = 1 Rs/MWh and C(PG) = 15 Rs/MWh and the loss in the line is Ploss(pu)=.5P G1(pu), where the loss coefficient is specified in pu on a 1MVA base. The most economic power generation schedule in MW is (A) PG1 =,PG = (B) PG1 =,PG = (C) PG1 =,PG = (D) PG1 =,PG = 4 Solution: (A) is correct option 1 Let penalty factor of plant G1 L 1 ; PL.5P G1 PL 1 P P P L G1 So,L.5 P P P G1 G1 G1 1 Penalty factor of plant G is L =1 ; PL 1 P For economic power generation C L C L 1 1 where C1 and C are the incremental fuel cost of plant G1 and G 1 So, P G P P pu It is an 1 MVA, so G G1 G1 G P 1 MW G1 5 P P L G Loss P.5 pu 1 MW L

51 Total power, P P P P L G1 G L 4 P P MW G Unsolved Problems: G Q.1 Two power plants interconnected by a tie line as shown in the above figure have loss formula coefficient b11 = 1-3 mw -1. Power is being dispatched economically with plant as 1Mw and plant as 15 Mw. The penalty factor for the plants 1 and are respectively. (A) 1 and 1.5 (B) 1.5 and 1 (C) 1 and zero (D) zero and 1 Q. A two bus system is shown below If 1 Mw is transmitted from plant 1 to the load, a transmission loss of 1 Mw is incurred. Find the required generation for each plant when the system x is Rs.5/mwhr. The incremental fuel costs are dc dp dc. P 16 Rs / Mwhr ;.4 P Rs / Mwhr 1 G1 dp G1 G (A) 14.5 MW and 15 MW (C) MW and 15 MW Q.3 The incremented fuel cost of two plants are given as.1p 15 Rs/ Mwhr IC 1 1 I C Rs/ Mwhr G (B) 15 MW and MW (D) 135. MW and 15 MW The minimum and maximum generation limits are 5 Pi 1, (i 1,) The load on the system is 18 MW. The generation limits are (A) 9 MW and 9 MW (C) 8 MW and 1 MW (B) 1 MW and 8 MW (D) 6 MW and 1 MW Q.4 The power generated by two plants are P1 = 5 mw and P = 4 mw the loss coefficients are B11 =.1, B =.5 and B1 = -.5. The demand on the system will be (A) 9 MW (B) 84.5 MW (C) 79.5 MW (D) 74.5 MW 17

52 Q.5 For the system whose line diagram is shown in figure. I1 = 1. and I =.8 per unit. If the voltage at bus 3 is 1. per unit. Find the loss coefficients B1 line impedances are (.4+j.16) per unit, (.3+j.1) per unit and (.+j.8) per unit for sections a, b and c respectively (A).554p.u. (B).188p.u. (C).477p.u. (D) 1.5p.u. Type 11: Per unit system For Concept, refer to Power Systems K-Notes, Per Unit System. Common Mistake: The voltage ratings of Transformers need not be necessarily be the base values, you need to transform the voltage bases as per transformer voltage ratios. Sample problem 11: Two generator units G1 and G are connected by 15 kv line with a bus at the midpoint as shown below G1 = 5MVA, 15 kv, positive sequence reactance XG1 =5% on its own base G = 1MVA, 15 kv, positive sequence reactance XG =1% on its own base L1 and L = 1km, positive sequence reactance XL =.5 Ω/km For the above system, the positive sequence diagram with the pu values on the 1 MVA common is? 18

53 Solution: (A) is correct option Positive sequence diagram of the above system 1 15 X.5.1 G X.1.1 G X.51 j1. L X.51 j1. L 15 5 Unsolved Problems: Q.1 Assuming S buses of MVA and 4MVA G1 G Tr 3MVA 5MVA 6MVA 11KV 11KV 11KV ( ) : 66KV (Y) X =. pu X =.5 pu X=.1 pu From the figure find the actual impedance in ohm for given Sbase as 5 MVA? (A)j.8874 (B)j.6853 (C)j.63 (D)j.93 Q. For the power system shown in the figure below, the specifications of the components are the following: G1: 5 kv, 1 MVA, X = 9% G: 5 kv, 1 MVA, X = 9% T1: 5 kv/ kv, 9 MVA, X = 1% T: kv/5 kv, 9 MVA, X = 1% 19

54 Line 1: kv, X = 15 ohms Choose 5 kv as the base voltage at the generator G1, and MVA as the MVA base. The impedance diagram is? Type 1: Symmetrical Components For Concept, refer to Power Systems K-Notes, Fault Analysis. Point to Remember: Try to understand the zero sequence network for Transformer using Switch Model. Sample Problem 1: A three-phase alternator generating unbalanced voltages is connected to an unbalanced load through a 3-phase transmission line as shown in figure. The neutral of the alternator and the star point of the load are solidly grounded. The phase voltages of the alternator are E 1 V,E 1 9 V,E 1 1 V. a b c The positive-sequence component of the load current is (A) A (B).33-1 A (C) A (D) A Solution: (D) is correct option Both sides are grounded So, E 1 a I 5 9 a Z j a E 19 b I b Z 3j b

55 E 11 c I.5 3 c Z 4 j c 1 We know that I I I I ; where =1 1 =1 4 a1 a b c 3 1 I ( 18 1 ).5 (4 3 ) a1 3 1 I a1 3 1 I 5j j.883.5j a1 3 Unsolved Problems: Q.1 A single phase load of 1kv is connected across lines b and c of a 3-phase supply of 3.3kv. Determine the positive sequence component of line a is (A) 3.3A (B) 17.5A (C) A (D) 48.5A Q. In a unbalanced 3 phase power system, the currents are measured as Ia = zero, Ib = 66 and Ic = 6-1. The corresponding sequence currents are Ia Ia1 Ia (A) zero 3-j3-3+j3 (B) zero -3+j3 3-j3 (C) zero -9+j33 9-j33 (D) zero 9-j33-9+j33 Q.3 When a 5 MVA, 11 KV 3-phase generator is subjected to a 3-phase fault, the fault current is j 5 p.u. When it is subjected to a line-to-line fault, the positive sequence current is j 4p.u. The positive and negative sequence reactance are respectively (A) j. and j.5 p.u (C) j.5 and j.5 p.u (B) j. and j.5 p.u (D) j.5 and j.5 p.u Q.4 A 3 - line supplies a delta connected load. The line current line1 is 1 A, taking the current in line 1 is as reference, current in line is Positive symmetrical component of line, if phase 3 is only switched off (A) (B) (C) (D)

56 Type 13: Fault Analysis For Concept, refer to Power Systems K-Notes, Fault Analysis. Common Mistake: While calculating any reactance please make sure that unit is correct as answer may be in pu or in ohms. Sample problem 13: A -MVA, 6.6-kV, 3-phase alternator is connected to a 3-phase transmission line. The per unit positive-sequence, negative-sequence and zero-sequence impedances of the alternator are j.1, j.1 and j.4 respectively. The neutral of the alternator is connected to ground through an inductive reactor of j.5 p.u. The per unit positive-, negative- and zerosequence impedances of transmission line are j.1, j.1 and j.3, respectively. All per unit values are based on the machine ratings. A solid ground fault occurs at one phase of the far end of the transmission line. The voltage of the alternator neutral with respect to ground during the fault is? (A)513.8 V (B)889.9 V (C)111. V (D) 64. V Solution: (D) is correct option Total zero sequence impedance, +ve sequence impedance and ve sequence impedances Z = (Z) Line+ (Z) Generator = j.4 + j.3 = j.34 pu Z1 = (Z1) Line+ (Z1) Generator = j.1 + j.1 = j. pu Z = (Z) Line+ (Z) Generator = j.1 + j.1 = j. pu Zn = j.5 pu for L-G fault I I E.1 a a1 Z Z Z 3Z j. j. j.34 j.15 1 n 6 generator MVA A 3 generator KV Base 3 Fault current I 3I I 3 j j A f a Base n n 6.6 Neutral Voltage V =I Z and Z =Z Z n f n n B pu V = V = 64. V j1.1 pu

57 Unsolved Problems: Q.1 A 3-phase 5 Hz generator is rated at 5 MVA, kv with Xd =.p.u.it supplies purely resistive load of 4 Mw at kv. The load is connected directly across the terminal of the generator. If all the three phases of the load are short circuited simultaneously through a fault reactance of.1 p.u, find the initial symmetrical r.m.s. current in the generator in ka in the generator on a base of 5 MVA, kv. (A) 7.17 (B) 7.75 (C) (D) 56.8 Q. When a 5 MVA, 11 KV 3 phase generator is subjected to a 3 phase fault, the fault current is j5 PU. When it is subjected a line to line fault, the positive sequence current is j4pu. The positive and negative sequence reactance s are respectively (A) j., j.5 (B) j., j.5 (C) j.5, j.5 (D) j.5, j.5 Q.3 Two 11 KV, MVA, three phase, star connected generators operate in parallel. The positive, negative and zero sequence reactance s of each being respectively j.18, j.15 and j.1 P.U. The star point of one of the generator is isolated and the other is earthed through a resistor. The potential of the neutral for a line to ground fault in P.U. (A).33 (B).96 (C).89 (D) 1.44 Q.4 In the power system shown, the values are marked are the per unit reactance s taking MVA and 11 KV as base values in the generator circuit. Both transformers are rated for 11/11 KV. A three phase to ground fault with a fault impedance of j.88 pu occurs at bus. The fault current supplied by generator is (A) 154.8A (B) 64.4A (C) 19.6A (D) 17.8A Q.5 A 1 MVA, 13.8 kv alternator has positive, negative and zero sequence reactance of 3%, 4% and 5 % respectively. What reactance must be put in the generator neutral so that the fault current for a line to ground fault of zero fault impedance will not exceed the rated line current. (A) 13.8 (B) 14.8 (C) 15.5 (D)

58 Type 14: Thevenin Impedance For Concept, refer to Power Systems K-Notes, Fault Analysis. Common Mistake: While calculating transfer reactance, shunt branches of pi-network are neglected. Sample problem 14: A generator is connected to a transformer which feeds another transformer through a short feeder. The zero sequence impedance values are expressed In pu on a common base and voltage are indicate in figure. The Thevenin equivalent zero sequence impedance at point B is? (A).8+j.6 (B).75+j. (C).75+j.5 (D) 1.5+j.5 Solution: (B) is correct option Per unit zero sequence reactance diagram of the given single line diagram is shown below. Thevenin equivalent impedance, Zth at B is Zth=j.1+j.5+j.7+.75=.75+j. Unsolved Problems: Q.1 For the network shown, the zero sequence reactance in PU are indicated. The zero sequence driving point reactance of the node 3 is (A).1 PU (B).3 PU (C).1 P.U (D). PU 4

59 Q. For the diagram shown below, the steady state symmetrical fault current for a 3 phase fault on the 11 kv feeder is (A) 1 p.u (B) 15 p.u (C) p.u (D) 5 p.u Q.3 A 3-phase fault occurs at the middle point F on the transmission line as shown in the figure. The transfer reactance appearing between the generator and the infinite bus is? (A)j.9 pu (B) j.575 pu (C)j.6 pu (D)j.65 pu Q.4 For figure shown below calculate the max power transfer (during the fault ), when the system is healthy, fault occurs at the middle of the line and fault is cleared by the breaker? (A)1.567 pu (B).7 pu (C).6 pu (D).618 pu Type 15: Power System Stability For Concept, refer to Power Systems K-Notes, Power System Stability. Point to Remember: If you are not able to remember the entire expression for critical clearing angle then better understand the method and you can compute using integration. Sample problem 15: A cylinder rotor generator delivers.5 pu power in the steady-state to an infinite bus through a transmission line of reactance.5 pu. The generator no-load voltage is 1.5 pu and the infinite bus voltage is 1 pu. The inertia constant of the generator is 5MW-s/MVA and the generator reactance is 1 pu. The critical clearing angle, in degrees, for a three-phase dead short circuit fault at the generator terminal is (A) 53.5 (B) 6. (C) 7.8 (D)

60 Solution: (D) is correct option Total reactance X= j1+j.5 =j1.5 pu Ps=Pe1=.5 pu EV Before fault P 1. pu m1 X 1.5 During fault Pm= pu After the fault Pm3=1. pu 1 Ps sin 3 Pm1 3 (radians).5 rad 18 1 P s sin 18 sin 15 max P 1 m3 15 (radians).168 rad max 18 1 P ( ) P cos s max m3 max 1.5(.168.5) 1. cos15 Critical clearing angle cos cos c P 1. m Unsolved Problems: c Q.1 A synchronous generator is connected to an infinite bus through a loss less double circuit transmission line. The generator is delivering 1. P.U power at a load angle at 3. When a sudden fault reduces are peak power that can transmitted to.5 P.U. After clearance of fault the peak power that can be transmitted becomes 1.5 per limit. Find the critical clearing angle (A) (B) (C) 6.3 (D) 56.6 Q. A 5 Hz 3-phase generator is supplying 6% of man power to an infinite bus though a reactive network. A fault occurs which will increase the reactance of the network between the generator to the infinite bus to 4% of the original value. When the fault is cleared, the maximum power that can be delivered is 8% of the original maximum value. Determine the critical clearing angle for the condition described. (A) 56.6 (B) 6.4 (C) 66.5 (D)

61 Q.3 The single line diagram of the power system is having a three phase fault at the point P. The generator is delivering 1. P.U. power at the instant preceding the fault. The Maximum power transfer before, during and fault in P.U. are (A).3,.8,.3 (B) 1.5,.8,.3 (C).3,,.3 (D).3,, 1.5 Q.4 A 5 Hz, 6 pole generator with H=4. pu delivers 1. pu to an infinite bus bar through a network in which resistance is negligible, and is supplying 45% of its peak power capacity as shown. A 3-phase fault occurs at the point F of the outgoing radial line. Faulted line is cleared by the opening of the line circuit breaker. Critical clearing time is (A).34 sec (B).78 sec (C).37 sec (D).6 sec Type 16: Swing equation For Concept, refer to Power Systems K-Notes, Power System Stability. Common Mistake: Both M and H are inertia constants and the only way to distinguish between them is through their units. Sample problem 16: A 5 MW, 1 kv, 5 Hz, 3-phase, -pole synchronous generator having a rated p.f=.9, has a moment of inertia of 7.5 X 1 3 # kg-m.the inertia constant (H ) will be (A).44 s (B).71 s (C) 4.88 s (D) 5.4 s Solution: (A) is correct option Given Synchronous generator of 5 MW, 1 kv, 5 Hz, 3-φ, -pole, P.F =.9, Moment of inertia M = 7.5 *1 3 kg-m Inertia constant H =? P 5 MW Generator rating in MVA G MVA cos.9 1 f 1 5 N 3 rpm pole 7

62 1 1 N stored K.E. = M M 7.51 MJ MJ 6 6 Stored Kinetic Energy inertia costant (H)= Rating of generator (MVA) H=.44 sec Q.1 A 5Hz two pole turbo attenuator rated 5 MVA, 13. kv has an inertia constant H = 5 MJ / MVA. The input less the rotational losses is 65, HP and the electrical power developed is 4 Mw. Determine the angular acceleration in electrical deg/sec is (A) (B) 9.45 (C) (D) 3.4 Q. A pole, 5 Hz, 11KV turbo-generator has a rating of 6 MW, power factor.85 lagging. Its rotor has a moment of inertia of 88 kg-m. The inertia constant in MJ per MVA and its momentum in MJ-s/electrical degree respectively are? (A)8.5149,.1447 (B)7.376,.485 (C)6.15,.185 (D)6.15,.1447 Q.3 A synchronous generator of reactance 1.pu is connected to an infinite bus-bar through a transformer and a line of total reactance of.6pu. The infinite bus-bar voltage is 1.pu and the generator no load voltage is 1.pu. The inertia constant is H=4 Mw-sec/MVA. The resistance and machine damping may be assumed negligible. The system frequency is 5Hz. The frequency of oscillations in Hz if the alternator is loaded to 5% of maximum power limit. (A).63 (B).758 (C).48 (D).54 Q.4 A 1 MVA synchronous Generator operates on full load at a frequency of 5Hz. The load is suddenly reduced to 5 Mw. Due to time lag in governor system the Steam value begins to close after.4 seconds. Determine the change in frequency that occurs in this time. Given H = 5 kw S/kVA. (A) 5.5 Hz (B) 5 Hz (C) 51.5 Hz (D) 5 Hz Q.5 A power station consists of two synchronous generators A and B at rating 5MVA and 5MVA with inertia constant at 1.6 p.u and 1 p.u respectively on their own base MVA ratings. The equivalent p.u inertia constant in the system on 1 MVA common base will be (A).6 p.u (B).615 p.u (C) 1.65 p.u (D) 9 p.u Type 17: Power System Matrices For Concept, refer to Power Systems K-Notes, Load Flow Study. Common Mistake: Number of non-zero off-diagonal elements in bus admittance matrix are double the number of transmission lines in a power system network. 8

63 Sample problem 17: The network shown in the given figure has impedances in p.u. as indicated. The diagonal element Y of the bus admittance matrix YBUS of the network is (A) j19.8 (B) +j. (C) +j. (D) j19.95 Solution: (D) is correct option I = V Y + (V - V )Y =.5V - j1(v - V ) =- j9.95v + j1v I = (V - V )Y + (V - V )Y = j1v - j9.9v - j.1v 1 3 Y = Y + Y + Y 11 3 =- j j j =- j19.95 Fault analysis using Z bus Sample problem 18: For a power system the admittance and impedance matrices for the fault studies are as follows. j8.75 j1.5 j.5 j.16 j.8 j.1 Y j1.5 j6.5 j.5 bus ; Z bus j.8 j.4 j.16 j.5 j.5 j5. j.1 j.16 j.34 The pre-fault voltages are 1. pu. at all the buses. The system was unloaded prior to the fault. A solid 3-phase fault takes place at bus. The post fault voltages at buses 1 and 3 in per unit respectively are (A).4,.63 (B).31,.76 (C).33,.67 (D).67,.33 Solution: (D) is correct option The post fault voltage at bus 1 and 3 are. Pre fault voltage. V 1 1 bus V 1 3 V V 1 At bus solid fault occurs Z(f) =, r = 9

64 Fault current I f Z f V V r Z Z Z Z rr f f 1 4 j j.4 V(f) = V () - Z I(f), i i ir i 1 i 1 f f 3 ;V = Prefault voltage V (f) = V - Z I = 1 -j.8(-j4) = V (f) =.68 pu V (f) = V - Z I = 1 -j.16(-j4) = V (f) =.36 pu Unsolved Problems: Q.1 A single line diagram of a power system is shown. The diagonal elements of the Y bus matrix is (A) j.7 pu, j.75 pu, j.45pu (B) -j.7pu, -j.75pu, -j.45pu (C) -j7.pu, -j6pu, -j9.pu (D) j7. pu, j6.pu, j9.pu Q. The Reactance s between the various buses in a power system are given in the table below. Y and Y33 of YBUS are Buses Reactance in p.u (A) -j.85, -j 1.15 (B) -j 19, -j 3 (C) -j.65, -j 1.15 (D) -j 16, -j 8.5 3

65 Q.3 The power system network shown in figure, where bus numbers impedances are marked, assuming equal R/X of impedances, find the bus impedance matrix element z. (A). (B).5 (C) 3.5 (D) 4.5 Q.4 The Ybus matrix of a 1-bus interconnected system is 9% sparse. Hence the number of transmission lines in the system must be? (A)45 (B)8 (C)1 (D)6 Type 18: Load flow Solution For Concept, refer to Power Systems K-Notes, Load Flow Study. Common Mistake: These type of questions are based on basic power angle equation and performance equations of short Transmission Line. Sample problem 19: In the following network, the voltage magnitudes at all buses are equal to 1 pu, the voltage phase angles are very small, and the line resistances are negligible. All the line reactance s are equal to j1ω The voltage phase angles in rad at buses and 3 are (A) ϴ =-.1, ϴ3 =-. (B) ϴ =, ϴ3 =-.1 (C) ϴ =.1, ϴ3 =.1 (D) ϴ =.1, ϴ3 =. Solution: (B) is correct option.1pu power must flow from slack bus to Bus3 so that demand at Bus 3 is satisfied and therefore, VV 1 3 1*1 Power P sin( ) sin( ) X 1 Therefore, 3 13 sin 3 3.1rad Since, no power flows from Bus1 to Bus so both must have same angles Therefore, rad 31

66 Unsolved Problems: Q.1 Figure shows a 3-phase system supplied at 11 KV at A. The load currents are balanced and the pf s (all lagging) are with respect to supply voltage at A. The impedances shown are per phase values. Voltage at load point C is (A) 9.93 KV (B) 1.3 KV (C) 1.66 KV (D) 9.7 KV Q. A simple power system has been shown in fig. all quantities are phasors VA = 1pv, ZAB = j.5 pv, SDA =. pu, SDB =. pu. If QGB is made as a zero, voltage VB is (A).7 3 (B).5 4 (C) (D) Q.3 The station loads are equalized by the flow of power in the cable. The Generator can generate a maximum of. pu real power. Reactive power flow in the cable (A).638 pu (B).638 pu (C) 1.76 pu (D) Q.4 For a 15 bus power system with 3 voltage controlled bus, the size of Jocobian Matrix is (A) 11 x 11 (B) 1 x 1 (C) 4 x 4 (D) 5 x 5 Q.5 A 5Hz transmission line 3km long has a total series impedance of 4+j15 ohms and a total shunt admittance of 1-3 mho. The receiving end load is 5MW at kv with.8 lagging power factor. Find the sending power with the short line approximating (A) 5.15MW (B) 53.MW (C) 5.58MW (D) 51.15MW 3

67 Type 19: Plug setting Multiplier For Concept, refer to Power Systems K-Notes, Power System Protection. Common Mistake: Remember to consider the relay setting while calculating Pick-up Current, it is not necessarily equal to rated secondary current of Current Transformer. Sample problem : The overcurrent relays for the line protection and loads connected at the buses are shown in the figure. The relays are IDMT in nature having the characteristic t.14 Time Multiplier Setting (Plug setting multiplier) 1 op. The maximum and minimum fault currents at bus B are A and 5 A respectively. Assuming the time multiplier setting and plug setting for relay RB to be.1 and 5A respectively, the operating time of RB (in seconds) is (A).67s (B).356s (C).145s (D).148s Solution: (A) is correct option CT ratio = : 1 PSM = Maximum fault current CT primary current 1 Top = =.67 s Unsolved Problems: Q.1 A fault current of A is passing on the primary side of a 4/5 CT. on the secondary side of the CT an inverse-time over current relay is connected whose plug setting is set at 5%. The plug setting multiplier will be (A) 5 (B) 5 (C) 1 (D) 3 33

68 Q. The rated secondary current of a current transformer (CT) is 5A. The plug setting of relay connected to the secondary is.5 A. If the effective VA burden on the CT is 1 VA, then the VA burden of the relay at.5 A plug setting is (A).75 A (B) 3 A (C) 6 A (D) 1 A Q.3 An over-current relay, having a current setting of 1.5% is connected to a supply circuit through a current transformer of ratio 4/5. The pick-up current value is? (A).65A (B)1A (C)1.5A (D)15A 34

69 Answer Key Type 1 A B C C B Type B Type 3 B B B A B Type 4 C A D B Type 5 C B D A Type 6 B D Type 7 B B Type 8 B C B A A Type 9 A A B B Type 1 B C C B B Type 11 B B Type 1 B B B D Type 13 B A B C B Type 14 C B A D Type 15 B C D D Type 16 A C B B D Type 17 C D C A Type 18 C D C D B Type 19 C C C 35

70 Kreatryx Subject Test Power Systems

71 KST- General Instructions during Examination 1. Total Duration of KST is 6 minutes.. The question paper consists of parts. Questions 1-1 carry one mark each and Question 11- carry marks each. 3. The question paper may consist of questions of Multiple Choice Type (MCQ) and Numerical Answer Type. 4. Multiple choice type questions will have four choices against A, B, C, D, out of which only ONE is the correct answer. 5. All questions that are not attempted will result in zero marks. However, wrong answers for multiple choice type questions (MCQ) will result in NEGATIVE marks. For all MCQ questions a wrong answer will result in deduction of 1/3 marks for a 1-mark question and /3 marks for a -mark question. 6. There is NO NEGATIVE MARKING for questions of NUMERICAL ANSWER TYPE. 7. Non-programmable type Calculator is allowed. Charts, graph sheets, and mathematical tables are NOT allowed during the Examination. 1

72 Q.1 A generated station has a maximum demand of 3 MW, a load factor of 6% and plant capacity factor of 5%. The reserve capacity of the plant is (A) 5 MW (B) 4 MW (C) 6 MW (D) 1 MW Q. Consider a step voltage wave of magnitude 1 pu travelling along a loss less transmission line that terminates in a reactor. The voltage magnitude across reactor at the instant the travelling wave reaches the reactor is (A) 1 pu (B) 1pu (C) pu (D) 3 pu Q.3 Consider two buses connected by an impedance of j 5. The bus 1 voltage is 13, and bus voltage is 1. The real and reactive supplied by bus 1, respectively are (A) 1W, 67.9 VAr (C) 76.9 W, 56.7Var (B) 1W, 134 Var (D) 76.9 W, 56.7 Var Q.4 Two power plants interconnected by a tie-line as shown in the above figure have loss formula coefficient B11 = 1 3 MW 1. Power is being dispatched economically with plant 1 as 1 MW and plant as 15 MW. The penalty factory for plants 1 and are respectively. (A) 1 and 1.5 (B) 1.5 and 1 (C) 1 and zero (D) zero and 1 Q.5 A relay is connected to 4/5 CT and set at 15% with primary current of 4 A, the plug setting multiplier is Q.6 In a 14 bus power system network, there are 5 voltage controlled buses. The size of the Jacobian matrix useful for power flow analysis will be: (A) 16 x 16 (B) 3 x 3 (C) 1 x 1 (D) 8 x 8

73 Q.7 Two alternators each having 4% speed regulation are working in parallel. Alternator 1 is rated for 1 MW and alternator is rated for 8 MW when the total load is 1 MW the Loads shared by alternators 1 and would be respectively (A) 4 MW and 6 MW (B) 6 MW and 4 MW (C) 5 MW and 5 MW (D) 1 MW and zero Q.8 A generator is connected to a transformer which feeds another transformer through a short feeder (see. Fig.) The zero sequence impedance value are expressed in pu on a common base and are indicated in fig. The venin equivalent zero sequence impedance at point B is (A).8 + j.6 (B).75 + j. (C).75 + j.5 (D) j.5 Q.9 In the system shown in figure a three phase static capacitive reactor of reactance 1 P.U. per Phase is connected through a switch at motor bus bar. The limit of steady state power, if the switch is closed is (A).49 P.U (B).965 P.U (C) 1.44 P.U. (D).99 P.U Q.1 A synchronous generator is connected to an infinite bus through a lossless double circuit transmission line. The generator is delivering 1. PU power at a load angle of 3 º when a sudden fault reduces peak power that can be transmitted to.5 P.U after clearance of fault, the peck power that can be transmitted becomes 1.5 P.U. The critical clearing angle is (A).35 radians (C) 1.1 radians (B) 1.35 radians (D) 1.1 radians 3

74 Q.11 A three phase star-connected alternator is rated 3MVA, 13.8 KV and has following sequence reactance values: X1.5P.U, X.35P.U, X.1P.U The neutral of alternator is solidly grounded. The alternator line currents when a double lineground fault occurs on its terminals (Assume Alternator is unloaded) will be (A) 3.5 P.U (B).37 P.U (C).68 P.U (D) 4.81 P.U Q.1 For a single circuit transmission line delivering a load of 45 MVA at 13kV and power factor.8 lag. Has transmission line parameters as A = D =.99.3 º, C = º, B = 7 69º sending end line voltage is (A) KV (B) 76.1 KV (C) KV (D) KV Q.13 A 1 MVA, 138 KV alternator has positive, negative and zero sequence reactance of 3%, 4% and 5% respectively. What reactance must be put in the generator so that the fault current for a line to ground fault of zero fault impedance will not exceed the rated line current? (A) 14.8 Ω (B) 1.38 Ω (C) 16.1 Ω (D) 1.8 Ω Q.14 A 3 unsymmetrical spaced transmission line configuration is shown below. What are the values of interline capacitances conductor is 1 cm (A).11,.11, 1.9 (B) 8.44, 8.44, 7.66 (C) 4., 4., 3.83 (D) none of the above C, C and ab bc C ac respectively in nf/km Radius of each Q.15 A 3 bus power system is shown below. The inductance is having P.U. Reactance and capacitance having P.U. susceptance. The Total self-admittances are (A) J 3.8, j 5.7, j 8.5 (B)-j14, -j 1.5, j4.5 (C) j15.5, -15, -6.5 (D)-18.5, ,

75 Q.16 Synchronous generator rated as 6 MW,.8 pf lag 5 Hz, 4-pole has moment of Inertia of 3, kg-. The Angular momentum in MJ-sec/Mech rad is. m (A).8 (B).41 (C)4.71 (D).35 Q.17 1 MVA, 11KV, 3-phase synchronous Generator is working at No load, rated voltage. The positive sequence Sub-transient current of symmetrical fault on general terminal is 5. P.U. The negative sequence reactance is 9% of positive sequence reactance and zero sequence reactance is % of positive sequence reactance. The neutral of the general is solidity grounded. The short circuit MVA of line to ground fault is. (A)5 (B)38 (C)456 (D)715 Q.18 Two conductor cables 1km long loaded distribution system as shown in figure. Both ends are 5v, at end A current is 9A. If minimum allowable voltage to the consumer is 45 and 1.7 cm then the cross section of each conductor in is. cm Q.19 At a 33kv, 5Hz bus a load of 3 Mw at.8 lagging power factor is connected to improve the power factor to unity a synchronous phase modifier is connected across load which is taking a real power of 5 MW. If the synchronous phase modifier is represented as a -connected lossy capacitor bank where each lossy capacitor represented as an RC parallel network then what is R, C values respectively. (A) 17.8,.639F (B) 653.4,.13F (C) 653.4,.639F (D) 17.8,.13F Q. A 6 Hz generator connected directly to an infinite bus operating at a voltage of 1 p.u. has a synchronous reactance of 1.35p.u. The generator no load voltage is 1.1p.u. and its interia constant H is 4 MJ/MVA. The generator is suddenly loaded to 6% its maximum power limit. The frequency of the resulting oscillation of the generator rotor is (A).44 Hz (B).55 Hz (C).88 Hz (D)5.5 Hz 5

KINGS COLLEGE OF ENGINEERING Punalkulam

KINGS COLLEGE OF ENGINEERING Punalkulam KINGS COLLEGE OF ENGINEERING Punalkulam 613 303 DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING POWER SYSTEM ANALYSIS QUESTION BANK UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A (TWO MARK

More information

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME: EE 2303 - TRANSMISSION & DISTRIBUTION YEAR / SEM: III/V UNIT-I TRANSMISSION SYSTEM INTRODUCTION PART-A 1. What is

More information

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester Electrical and Electronics Engineering EE 1352 Power System Analysis (Regulation 2008) Time: Three hours Answer all questions Part A (10

More information

IGEE 402 Power System Analysis. FINAL EXAMINATION - SAMPLE Fall 2004

IGEE 402 Power System Analysis. FINAL EXAMINATION - SAMPLE Fall 2004 IGEE 402 Power System Analysis FINAL EXAMINATION - SAMPLE Fall 2004 Special instructions: - Duration: 80 minutes. - Material allowed: a crib sheet (double sided 8.5 x ), calculator. - Attempt 5 out of

More information

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL 1 SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL Power Systems: Generation, Transmission and Distribution Power Systems: Generation, Transmission and Distribution Power Systems:

More information

EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION

EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION PART: A 1. Define per unit value of an electrical quantity. Write equation for base impedance with respect to 3-phase system. 2. What is bus admittance

More information

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous)

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad - 500 043 ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK Course Name : Computer Methods in Power Systems Course Code : A60222

More information

EE Branch GATE Paper 2010

EE Branch GATE Paper 2010 Q.1 Q.25 carry one mark each 1. The value of the quantity P, where, is equal to 0 1 e 1/e 2. Divergence of the three-dimensional radial vector field is 3 1/r 3. The period of the signal x(t) = 8 is 0.4

More information

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A 1. What are the advantages of an inter connected system? The advantages of an inter-connected system are

More information

ELG4125: Power Transmission Lines Steady State Operation

ELG4125: Power Transmission Lines Steady State Operation ELG4125: Power Transmission Lines Steady State Operation Two-Port Networks and ABCD Models A transmission line can be represented by a two-port network, that is a network that can be isolated from the

More information

Transmission and Distribution of Electrical Power

Transmission and Distribution of Electrical Power KINGDOM OF SAUDI ARABIA Ministry Of High Education Umm Al-Qura University College of Engineering & Islamic Architecture Department Of Electrical Engineering Transmission and Distribution of Electrical

More information

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur Lecture - 9 Transmission Line Steady State Operation Welcome to lesson 9, in Power

More information

THE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session

THE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session Name: Student ID: Signature: THE UNIVERSITY OF NEW SOUTH WALES School of Electrical Engineering & Telecommunications FINALEXAMINATION Session 00 ELEC46 Power System Analysis TIME ALLOWED: 3 hours TOTAL

More information

LO 1: Three Phase Circuits

LO 1: Three Phase Circuits Course: EEL 2043 Principles of Electric Machines Class Instructor: Dr. Haris M. Khalid Email: hkhalid@hct.ac.ae Webpage: www.harismkhalid.com LO 1: Three Phase Circuits Three Phase AC System Three phase

More information

QUESTION BANK ENGINEERS ACADEMY. Power Systems Power System Stability 1

QUESTION BANK ENGINEERS ACADEMY. Power Systems Power System Stability 1 ower ystems ower ystem tability QUETION BANK. A cylindrical rotor generator delivers 0.5 pu power in the steady-state to an infinite bus through a transmission line of reactance 0.5 pu. The generator no-load

More information

ECE 325 Electric Energy System Components 5 Transmission Lines. Instructor: Kai Sun Fall 2015

ECE 325 Electric Energy System Components 5 Transmission Lines. Instructor: Kai Sun Fall 2015 ECE 325 Electric Energy System Components 5 Transmission Lines Instructor: Kai Sun Fall 2015 1 Content (Materials are from Chapter 25) Overview of power lines Equivalent circuit of a line Voltage regulation

More information

In the previous chapter, attention was confined

In the previous chapter, attention was confined 4 4 Principles of Power System CHAPTE CHAPTE 8 Unsymmetrical Fault Calculations 8. Usymmetrical Faults on -Phase System 8. Symmetrical Components Method 8. Operator a 8.4 Symmetrical Components in Terms

More information

Chapter 3 AUTOMATIC VOLTAGE CONTROL

Chapter 3 AUTOMATIC VOLTAGE CONTROL Chapter 3 AUTOMATIC VOLTAGE CONTROL . INTRODUCTION TO EXCITATION SYSTEM The basic function of an excitation system is to provide direct current to the field winding of the synchronous generator. The excitation

More information

DHANALAKSHMI SRINIVASAN COLLEGE OF ENGINEERING AND TECHNOLOGY Mamalapuram Chennai QUESTION BANK V SEMESTER. EE6501-Power system Analysis

DHANALAKSHMI SRINIVASAN COLLEGE OF ENGINEERING AND TECHNOLOGY Mamalapuram Chennai QUESTION BANK V SEMESTER. EE6501-Power system Analysis DHANALAKSHMI SRINIVASAN COLLEGE OF ENGINEERING AND TECHNOLOGY Mamalapuram Chennai DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK V SEMESTER EE6501-Power system Analysis Regulation 2013

More information

Module 3 : Sequence Components and Fault Analysis

Module 3 : Sequence Components and Fault Analysis Module 3 : Sequence Components and Fault Analysis Lecture 12 : Sequence Modeling of Power Apparatus Objectives In this lecture we will discuss Per unit calculation and its advantages. Modeling aspects

More information

GATE 2010 Electrical Engineering

GATE 2010 Electrical Engineering GATE 2010 Electrical Engineering Q.1 Q.25 carry one mark each 1. The value of the quantity P, where P = xe dx, is equal to (A) 0 (B) 1 (C) e (D) 1/e 2. Divergence of the three-dimensional radial vector

More information

POWER SYSTEM STABILITY

POWER SYSTEM STABILITY LESSON SUMMARY-1:- POWER SYSTEM STABILITY 1. Introduction 2. Classification of Power System Stability 3. Dynamic Equation of Synchronous Machine Power system stability involves the study of the dynamics

More information

GATE SOLVED PAPER - EE

GATE SOLVED PAPER - EE YEA 0 TWO MAKS Q. For a power system network with n nodes, Z of its bus impedance matrix is j0. 5 per unit. The voltage at node is. - 0c per unit. If a capacitor having reactance of - j. 5per unit is now

More information

MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION (Autonomous) (ISO/IEC Certified) MODEL ANSWER

MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION (Autonomous) (ISO/IEC Certified) MODEL ANSWER Important Instructions to examiners: 1) The answers should be examined by key words and not as word-to-word as given in the model answer scheme. 2) The model answer and the answer written by candidate

More information

Fault Calculation Methods

Fault Calculation Methods ELEC9713 Industrial and Commercial Power Systems Fault Calculation Methods There are two major problems that can occur in electrical systems: these are open circuits and short circuits. Of the two, the

More information

Fault Analysis Power System Representation

Fault Analysis Power System Representation .1. Power System Representation Single Line Diagram: Almost all modern power systems are three phase systems with the phases of equal magnitude and equal phase difference (i.e., 10 o ). These three phase

More information

Lecture (5) Power Factor,threephase circuits, and Per Unit Calculations

Lecture (5) Power Factor,threephase circuits, and Per Unit Calculations Lecture (5) Power Factor,threephase circuits, and Per Unit Calculations 5-1 Repeating the Example on Power Factor Correction (Given last Class) P? Q? S? Light Motor From source 1000 volts @ 60 Htz 10kW

More information

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION EE 6501 POWER SYSTEMS UNIT I INTRODUCTION PART A (2 MARKS) 1. What is single line diagram? A Single line diagram is diagrammatic representation of power system in which the components are represented by

More information

ECEN 460 Exam 1 Fall 2018

ECEN 460 Exam 1 Fall 2018 ECEN 460 Exam 1 Fall 2018 Name: KEY UIN: Section: Score: Part 1 / 40 Part 2 / 0 Part / 0 Total / 100 This exam is 75 minutes, closed-book, closed-notes. A standard calculator and one 8.5 x11 note sheet

More information

Sinusoidal Steady State Power Calculations

Sinusoidal Steady State Power Calculations 10 Sinusoidal Steady State Power Calculations Assessment Problems AP 10.1 [a] V = 100/ 45 V, Therefore I = 20/15 A P = 1 (100)(20)cos[ 45 (15)] = 500W, 2 A B Q = 1000sin 60 = 866.03 VAR, B A [b] V = 100/

More information

Transients on Integrated Power System

Transients on Integrated Power System Chapter 3 Transients on Integrated Power System 3.1 Line Dropping and Load Rejection 3.1.1 Line Dropping In three phase circuit capacitance switching, the determination of the voltage trapped after switching

More information

Exercise Dr.-Ing. Abdalkarim Awad. Informatik 7 Rechnernetze und Kommunikationssysteme

Exercise Dr.-Ing. Abdalkarim Awad. Informatik 7 Rechnernetze und Kommunikationssysteme Exercise1 1.10.015 Informatik 7 Rechnernetze und Kommunikationssysteme Review of Phasors Goal of phasor analysis is to simplify the analysis of constant frequency ac systems v(t) = max cos(wt + q v ) i(t)

More information

ELECTRO MAGNETIC INDUCTION

ELECTRO MAGNETIC INDUCTION ELECTRO MAGNETIC INDUCTION 1) A Circular coil is placed near a current carrying conductor. The induced current is anti clock wise when the coil is, 1. Stationary 2. Moved away from the conductor 3. Moved

More information

SHORT QUESTIONS AND ANSWERS. Year/ Semester/ Class : III/ V/ EEE Academic Year: Subject Code/ Name: EE6501/ Power System Analysis

SHORT QUESTIONS AND ANSWERS. Year/ Semester/ Class : III/ V/ EEE Academic Year: Subject Code/ Name: EE6501/ Power System Analysis Srividya colllege of Engg & Tech,Virudhunagar Sri Vidya College of Engineering And Technology Virudhunagar 626 005 Department of Electrical and Electronics Engineering QUESTION BANK SHORT QUESTIONS AND

More information

EE2351 POWER SYSTEM ANALYSIS

EE2351 POWER SYSTEM ANALYSIS EE351 POWER SYSTEM ANALYSIS A.Ahamed Riazudeen EEE DEPARTMENT 1 UNIT I INTRODUCTION Power system network 3 SINGLE LINE DIAGRAM It is a diagrammatic representation of a power system in which the components

More information

Chapter 8: Unsymmetrical Faults

Chapter 8: Unsymmetrical Faults Chapter 8: Unsymmetrical Faults Introduction The sequence circuits and the sequence networks developed in the previous chapter will now be used for finding out fault current during unsymmetrical faults.

More information

POWER SEMICONDUCTOR BASED ELECTRIC DRIVES

POWER SEMICONDUCTOR BASED ELECTRIC DRIVES POWER SEMICONDUCT BASED ELECTRIC DRIVES [Time: 3 Hrs] [Max. Marks: 80] Instructions: Solve any six questions from Q.No (1 or 2), Q.No (3 or 4), Q.No (5 or 6), Q.No (7 or 8), Q.No (9 or 10), Q.No (11 or

More information

Power Systems. (Solutions for Volume 1 Class Room Practice Questions) Z pu new = Z pu old. X pu new = X pu = 50. X pu. new = 0.

Power Systems. (Solutions for Volume 1 Class Room Practice Questions) Z pu new = Z pu old. X pu new = X pu = 50. X pu. new = 0. ower Systems (Solutions for Volume lass Room ractice Questions) ower Systems - j.75 j. j.5. U System, Symmetrical omponents & Fault Analysis. Sol: Given data, Synchronous generator (or) synchronous motor

More information

3- BASICS. YTransformation. for balanced load. \V ab 120 = \V bc. \V ab 240 = \V ca \I a 120 = \I b \I a 240 = \I c V ab I a

3- BASICS. YTransformation. for balanced load. \V ab 120 = \V bc. \V ab 240 = \V ca \I a 120 = \I b \I a 240 = \I c V ab I a 3- BASICS YTransformation for balanced load Z =3Z Y Balanced 3- Systems \V ab 10 = \V bc \V ab 40 = \V ca \I a 10 = \I b \I a 40 = \I c V ab I a = p 3 V an = p 3 I ab \V ab 30 = \V an \I ab 30 = \I a S

More information

TRANSMISSION LINES. All aluminum alloy conductor (AAAC) Aluminum conductor alloy reinforced (ACAR)

TRANSMISSION LINES. All aluminum alloy conductor (AAAC) Aluminum conductor alloy reinforced (ACAR) TRANSMISSION LINES. Transmission Structures An overhead transmission line consists of conductor, insulators, support structures and in most cases shield wires. Overhead power transmission lines are classified

More information

Power Factor Improvement

Power Factor Improvement Salman bin AbdulazizUniversity College of Engineering Electrical Engineering Department EE 2050Electrical Circuit Laboratory Power Factor Improvement Experiment # 4 Objectives: 1. To introduce the concept

More information

ECE 325 Electric Energy System Components 7- Synchronous Machines. Instructor: Kai Sun Fall 2015

ECE 325 Electric Energy System Components 7- Synchronous Machines. Instructor: Kai Sun Fall 2015 ECE 325 Electric Energy System Components 7- Synchronous Machines Instructor: Kai Sun Fall 2015 1 Content (Materials are from Chapters 16-17) Synchronous Generators Synchronous Motors 2 Synchronous Generators

More information

EE 742 Chapter 3: Power System in the Steady State. Y. Baghzouz

EE 742 Chapter 3: Power System in the Steady State. Y. Baghzouz EE 742 Chapter 3: Power System in the Steady State Y. Baghzouz Transmission Line Model Distributed Parameter Model: Terminal Voltage/Current Relations: Characteristic impedance: Propagation constant: π

More information

Calculations of Capacitance for Transposed Bundled Conductor Transmission Lines

Calculations of Capacitance for Transposed Bundled Conductor Transmission Lines Calculations of Capacitance for Transposed Bundled Conductor Transmission Lines Multi-conductor Lines. An example with a conductor bundle r: conductor radius, d: distance between conductors of the same

More information

Sinusoidal Steady State Analysis (AC Analysis) Part II

Sinusoidal Steady State Analysis (AC Analysis) Part II Sinusoidal Steady State Analysis (AC Analysis) Part II Amin Electronics and Electrical Communications Engineering Department (EECE) Cairo University elc.n102.eng@gmail.com http://scholar.cu.edu.eg/refky/

More information

PHYS 241 EXAM #2 November 9, 2006

PHYS 241 EXAM #2 November 9, 2006 1. ( 5 points) A resistance R and a 3.9 H inductance are in series across a 60 Hz AC voltage. The voltage across the resistor is 23 V and the voltage across the inductor is 35 V. Assume that all voltages

More information

PowerApps Optimal Power Flow Formulation

PowerApps Optimal Power Flow Formulation PowerApps Optimal Power Flow Formulation Page1 Table of Contents 1 OPF Problem Statement... 3 1.1 Vector u... 3 1.1.1 Costs Associated with Vector [u] for Economic Dispatch... 4 1.1.2 Costs Associated

More information

Conventional Paper-I-2011 PART-A

Conventional Paper-I-2011 PART-A Conventional Paper-I-0 PART-A.a Give five properties of static magnetic field intensity. What are the different methods by which it can be calculated? Write a Maxwell s equation relating this in integral

More information

ECE 476. Exam #2. Tuesday, November 15, Minutes

ECE 476. Exam #2. Tuesday, November 15, Minutes Name: Answers ECE 476 Exam #2 Tuesday, November 15, 2016 75 Minutes Closed book, closed notes One new note sheet allowed, one old note sheet allowed 1. / 20 2. / 20 3. / 20 4. / 20 5. / 20 Total / 100

More information

Power and Energy Measurement

Power and Energy Measurement Power and Energy Measurement EIE 240 Electrical and Electronic Measurement April 24, 2015 1 Work, Energy and Power Work is an activity of force and movement in the direction of force (Joules) Energy is

More information

Work, Energy and Power

Work, Energy and Power 1 Work, Energy and Power Work is an activity of force and movement in the direction of force (Joules) Energy is the capacity for doing work (Joules) Power is the rate of using energy (Watt) P = W / t,

More information

Q. 1 Q. 25 carry one mark each.

Q. 1 Q. 25 carry one mark each. Q. 1 Q. 25 carry one mark each. Q.1 Given ff(zz) = gg(zz) + h(zz), where ff, gg, h are complex valued functions of a complex variable zz. Which one of the following statements is TUE? (A) If ff(zz) is

More information

PHYSICS : CLASS XII ALL SUBJECTIVE ASSESSMENT TEST ASAT

PHYSICS : CLASS XII ALL SUBJECTIVE ASSESSMENT TEST ASAT PHYSICS 202 203: CLASS XII ALL SUBJECTIVE ASSESSMENT TEST ASAT MM MARKS: 70] [TIME: 3 HOUR General Instructions: All the questions are compulsory Question no. to 8 consist of one marks questions, which

More information

+ ( )= with initial condition

+ ( )= with initial condition Department of Electrical Engineering PhD. Admission Test Full Marks: 90 Time 90 minutes Date: 02.2.204 NAME: Appl. No: Write your answer on the question paper ONLY. All questions carry equal marks. PART

More information

BEE701 POWER SYSTEM ANALYSIS

BEE701 POWER SYSTEM ANALYSIS BEE701 POWER SYSTEM ANALYSIS UNIT I POWER SYSTEM COMPONENTS Power system analysis The evaluation of power system is called as power system analysis Functions of power system analysis To monitor the voltage

More information

Introduction to Synchronous. Machines. Kevin Gaughan

Introduction to Synchronous. Machines. Kevin Gaughan Introduction to Synchronous Machines Kevin Gaughan The Synchronous Machine An AC machine (generator or motor) with a stator winding (usually 3 phase) generating a rotating magnetic field and a rotor carrying

More information

ECE 585 Power System Stability

ECE 585 Power System Stability Homework 1, Due on January 29 ECE 585 Power System Stability Consider the power system below. The network frequency is 60 Hz. At the pre-fault steady state (a) the power generated by the machine is 400

More information

Three Phase Circuits

Three Phase Circuits Amin Electronics and Electrical Communications Engineering Department (EECE) Cairo University elc.n102.eng@gmail.com http://scholar.cu.edu.eg/refky/ OUTLINE Previously on ELCN102 Three Phase Circuits Balanced

More information

Unit-3. Question Bank

Unit-3. Question Bank Unit- Question Bank Q.1 A delta connected load draw a current of 15A at lagging P.F. of.85 from 400, -hase, 50Hz suly. Find & of each hase. Given P = = 400 0 I = 15A Ans. 4.98, 5.7mH So I P = 15 =8.66A

More information

Behaviour of synchronous machine during a short-circuit (a simple example of electromagnetic transients)

Behaviour of synchronous machine during a short-circuit (a simple example of electromagnetic transients) ELEC0047 - Power system dynamics, control and stability (a simple example of electromagnetic transients) Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct October 2018 1 / 25 Objectives

More information

11. AC Circuit Power Analysis

11. AC Circuit Power Analysis . AC Circuit Power Analysis Often an integral part of circuit analysis is the determination of either power delivered or power absorbed (or both). In this chapter First, we begin by considering instantaneous

More information

Two point charges, A and B, lie along a line separated by a distance L. The point x is the midpoint of their separation.

Two point charges, A and B, lie along a line separated by a distance L. The point x is the midpoint of their separation. Use the following to answer question 1. Two point charges, A and B, lie along a line separated by a distance L. The point x is the midpoint of their separation. 1. Which combination of charges would yield

More information

ECE 420. Review of Three Phase Circuits. Copyright by Chanan Singh, Panida Jirutitijaroen, and Hangtian Lei, For educational use only-not for sale.

ECE 420. Review of Three Phase Circuits. Copyright by Chanan Singh, Panida Jirutitijaroen, and Hangtian Lei, For educational use only-not for sale. ECE 40 Review of Three Phase Circuits Outline Phasor Complex power Power factor Balanced 3Ф circuit Read Appendix A Phasors and in steady state are sinusoidal functions with constant frequency 5 0 15 10

More information

Review of Basic Electrical and Magnetic Circuit Concepts EE

Review of Basic Electrical and Magnetic Circuit Concepts EE Review of Basic Electrical and Magnetic Circuit Concepts EE 442-642 Sinusoidal Linear Circuits: Instantaneous voltage, current and power, rms values Average (real) power, reactive power, apparent power,

More information

ROEVER COLLEGE OF ENGINEERING & TECHNOLOGY ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING ELECTRICAL MACHINES I

ROEVER COLLEGE OF ENGINEERING & TECHNOLOGY ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING ELECTRICAL MACHINES I ROEVER COLLEGE OF ENGINEERING & TECHNOLOGY ELAMBALUR, PERAMBALUR-621220 DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING ELECTRICAL MACHINES I Unit I Introduction 1. What are the three basic types

More information

Distribution System Line Models

Distribution System Line Models FAKULTA ELEKTROTECHNIKY A KOMUNIKAČNÍCH TECHNOLOGIÍ VYSOKÉ UČENÍ TECHNICKÉ V BRNĚ Distribution System Line Models Authors: Ing. Mayada Daboul doc. Ing. Jaroslava Orságová, Ph.D. May 2013 epower Inovace

More information

BASIC NETWORK ANALYSIS

BASIC NETWORK ANALYSIS SECTION 1 BASIC NETWORK ANALYSIS A. Wayne Galli, Ph.D. Project Engineer Newport News Shipbuilding Series-Parallel dc Network Analysis......................... 1.1 Branch-Current Analysis of a dc Network......................

More information

Sinusoidal Steady State Analysis

Sinusoidal Steady State Analysis Sinusoidal Steady State Analysis 9 Assessment Problems AP 9. [a] V = 70/ 40 V [b] 0 sin(000t +20 ) = 0 cos(000t 70 ).. I = 0/ 70 A [c] I =5/36.87 + 0/ 53.3 =4+j3+6 j8 =0 j5 =.8/ 26.57 A [d] sin(20,000πt

More information

ECE 476 Power System Analysis Fall 2014 Exam #1, Thursday, October 2, :30AM - 10:50AM

ECE 476 Power System Analysis Fall 2014 Exam #1, Thursday, October 2, :30AM - 10:50AM ECE 476 Power System Analysis Fall 4 Exam #, Thursday, October, 4. 9:3AM - :5AM Name: Problem (5 p) Two balanced 3-phase loads are connected in parallel. One is Y-connected and draws 75 kw (3-phase) at.8

More information

ELECTROMAGNETIC OSCILLATIONS AND ALTERNATING CURRENT

ELECTROMAGNETIC OSCILLATIONS AND ALTERNATING CURRENT Chapter 31: ELECTROMAGNETIC OSCILLATIONS AND ALTERNATING CURRENT 1 A charged capacitor and an inductor are connected in series At time t = 0 the current is zero, but the capacitor is charged If T is the

More information

SECTION 7: FAULT ANALYSIS. ESE 470 Energy Distribution Systems

SECTION 7: FAULT ANALYSIS. ESE 470 Energy Distribution Systems SECTION 7: FAULT ANALYSIS ESE 470 Energy Distribution Systems 2 Introduction Power System Faults 3 Faults in three-phase power systems are short circuits Line-to-ground Line-to-line Result in the flow

More information

Synchronous Machines

Synchronous Machines Synchronous Machines Synchronous generators or alternators are used to convert mechanical power derived from steam, gas, or hydraulic-turbine to ac electric power Synchronous generators are the primary

More information

ELEC Introduction to power and energy systems. The per unit system. Thierry Van Cutsem

ELEC Introduction to power and energy systems. The per unit system. Thierry Van Cutsem ELEC0014 - Introduction to power and energy systems The per unit system Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct October 2018 1 / 12 Principle The per unit system Principle

More information

Chapter 32A AC Circuits. A PowerPoint Presentation by Paul E. Tippens, Professor of Physics Southern Polytechnic State University

Chapter 32A AC Circuits. A PowerPoint Presentation by Paul E. Tippens, Professor of Physics Southern Polytechnic State University Chapter 32A AC Circuits A PowerPoint Presentation by Paul E. Tippens, Professor of Physics Southern Polytechnic State University 2007 Objectives: After completing this module, you should be able to: Describe

More information

EXP. NO. 3 Power on (resistive inductive & capacitive) load Series connection

EXP. NO. 3 Power on (resistive inductive & capacitive) load Series connection OBJECT: To examine the power distribution on (R, L, C) series circuit. APPARATUS 1-signal function generator 2- Oscilloscope, A.V.O meter 3- Resisters & inductor &capacitor THEORY the following form for

More information

Power and Energy Measurement

Power and Energy Measurement Power and Energy Measurement ENE 240 Electrical and Electronic Measurement Class 11, February 4, 2009 werapon.chi@kmutt.ac.th 1 Work, Energy and Power Work is an activity of force and movement in the direction

More information

coil of the circuit. [8+8]

coil of the circuit. [8+8] Code No: R05310202 Set No. 1 III B.Tech I Semester Regular Examinations, November 2008 ELECTRICAL MEASUREMENTS (Electrical & Electronic Engineering) Time: 3 hours Max Marks: 80 Answer any FIVE Questions

More information

Driven RLC Circuits Challenge Problem Solutions

Driven RLC Circuits Challenge Problem Solutions Driven LC Circuits Challenge Problem Solutions Problem : Using the same circuit as in problem 6, only this time leaving the function generator on and driving below resonance, which in the following pairs

More information

GATE 2008 Electrical Engineering

GATE 2008 Electrical Engineering GATE 2008 Electrical Engineering Q.1 Q. 20 carry one mark each. 1. The number of chords in the graph of the given circuit will be + _ (A) 3 (B) 4 (C) 5 (D) 6 2. The Thevenin'a equivalent of a circuit operating

More information

Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science Electric Machines

Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science Electric Machines Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science 6.685 Electric Machines Problem Set 10 Issued November 11, 2013 Due November 20, 2013 Problem 1: Permanent

More information

Basics of Electric Circuits

Basics of Electric Circuits António Dente Célia de Jesus February 2014 1 Alternating Current Circuits 1.1 Using Phasors There are practical and economic reasons justifying that electrical generators produce emf with alternating and

More information

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM Unit Objectives Describe the structure of an atom. Identify atoms with a positive charge and atoms with a negative charge. Explain

More information

PARALLEL A.C. CIRCUITS

PARALLEL A.C. CIRCUITS C H A P T E R 4 earning Objectives Solving Parallel Circuits Vector or Phasor Method Admittance Method Application of Admittance Method Complex or Phasor Algebra Series-Parallel Circuits Series Equivalent

More information

Week No. 6 Chapter Six: Power Factor Improvement

Week No. 6 Chapter Six: Power Factor Improvement Week No. 6 Chapter Six: Power Factor Improvement The electrical energy is almost wholly generated, transmitted and distributed in the form of alternating current. Therefore, the question of power factor

More information

ELECTRIC POWER CIRCUITS BASIC CONCEPTS AND ANALYSIS

ELECTRIC POWER CIRCUITS BASIC CONCEPTS AND ANALYSIS Contents ELEC46 Power ystem Analysis Lecture ELECTRC POWER CRCUT BAC CONCEPT AND ANALY. Circuit analysis. Phasors. Power in single phase circuits 4. Three phase () circuits 5. Power in circuits 6. ingle

More information

Final Exam, Second Semester: 2015/2016 Electrical Engineering Department

Final Exam, Second Semester: 2015/2016 Electrical Engineering Department Philadelphia University Faculty of Engineering Student Name Student No: Serial No Final Exam, Second Semester: 2015/2016 Electrical Engineering Department Course Title: Power II Date: 21 st June 2016 Course

More information

Transformer. Transformer comprises two or more windings coupled by a common magnetic circuit (M.C.).

Transformer. Transformer comprises two or more windings coupled by a common magnetic circuit (M.C.). . Transformers Transformer Transformer comprises two or more windings coupled by a common magnetic circuit (M.C.). f the primary side is connected to an AC voltage source v (t), an AC flux (t) will be

More information

Brief Steady of Power Factor Improvement

Brief Steady of Power Factor Improvement International Journal of Electrical Engineering. ISSN 0974-2158 Volume 6, Number 5 (2013), pp. 531-539 International Research PublicationHouse http://www.irphouse.com Brief Steady of Power Factor Improvement

More information

ADMISSION TEST INDUSTRIAL AUTOMATION ENGINEERING

ADMISSION TEST INDUSTRIAL AUTOMATION ENGINEERING UNIVERSITÀ DEGLI STUDI DI PAVIA ADMISSION TEST INDUSTRIAL AUTOMATION ENGINEERING September 26, 2016 The candidates are required to answer the following multiple choice test which includes 30 questions;

More information

Lecture 11 - AC Power

Lecture 11 - AC Power - AC Power 11/17/2015 Reading: Chapter 11 1 Outline Instantaneous power Complex power Average (real) power Reactive power Apparent power Maximum power transfer Power factor correction 2 Power in AC Circuits

More information

EE 212 PASSIVE AC CIRCUITS

EE 212 PASSIVE AC CIRCUITS EE 212 PASSIVE AC CIRCUITS Condensed Text Prepared by: Rajesh Karki, Ph.D., P.Eng. Dept. of Electrical Engineering University of Saskatchewan About the EE 212 Condensed Text The major topics in the course

More information

Transmission Lines. Plane wave propagating in air Y unguided wave propagation. Transmission lines / waveguides Y. guided wave propagation

Transmission Lines. Plane wave propagating in air Y unguided wave propagation. Transmission lines / waveguides Y. guided wave propagation Transmission Lines Transmission lines and waveguides may be defined as devices used to guide energy from one point to another (from a source to a load). Transmission lines can consist of a set of conductors,

More information

04-Electric Power. ECEGR 452 Renewable Energy Systems

04-Electric Power. ECEGR 452 Renewable Energy Systems 04-Electric Power ECEGR 452 Renewable Energy Systems Overview Review of Electric Circuits Phasor Representation Electrical Power Power Factor Dr. Louie 2 Introduction Majority of the electrical energy

More information

AC Circuits. The Capacitor

AC Circuits. The Capacitor The Capacitor Two conductors in close proximity (and electrically isolated from one another) form a capacitor. An electric field is produced by charge differences between the conductors. The capacitance

More information

Lecture 05 Power in AC circuit

Lecture 05 Power in AC circuit CA2627 Building Science Lecture 05 Power in AC circuit Instructor: Jiayu Chen Ph.D. Announcement 1. Makeup Midterm 2. Midterm grade Grade 25 20 15 10 5 0 10 15 20 25 30 35 40 Grade Jiayu Chen, Ph.D. 2

More information

LESSON 20 ALTERNATOR OPERATION OF SYNCHRONOUS MACHINES

LESSON 20 ALTERNATOR OPERATION OF SYNCHRONOUS MACHINES ET 332b Ac Motors, Generators and Power Systems LESSON 20 ALTERNATOR OPERATION OF SYNCHRONOUS MACHINES 1 LEARNING OBJECTIVES After this presentation you will be able to: Interpret alternator phasor diagrams

More information

Two-Port Networks Admittance Parameters CHAPTER16 THE LEARNING GOALS FOR THIS CHAPTER ARE THAT STUDENTS SHOULD BE ABLE TO:

Two-Port Networks Admittance Parameters CHAPTER16 THE LEARNING GOALS FOR THIS CHAPTER ARE THAT STUDENTS SHOULD BE ABLE TO: CHAPTER16 Two-Port Networks THE LEARNING GOALS FOR THIS CHAPTER ARE THAT STUDENTS SHOULD BE ABLE TO: Calculate the admittance, impedance, hybrid, and transmission parameter for two-port networks. Convert

More information

Prince Sattam bin Abdulaziz University College of Engineering. Electrical Engineering Department EE 3360 Electrical Machines (II)

Prince Sattam bin Abdulaziz University College of Engineering. Electrical Engineering Department EE 3360 Electrical Machines (II) Chapter # 4 Three-Phase Induction Machines 1- Introduction (General Principles) Generally, conversion of electrical power into mechanical power takes place in the rotating part of an electric motor. In

More information

ECE2262 Electric Circuits. Chapter 6: Capacitance and Inductance

ECE2262 Electric Circuits. Chapter 6: Capacitance and Inductance ECE2262 Electric Circuits Chapter 6: Capacitance and Inductance Capacitors Inductors Capacitor and Inductor Combinations Op-Amp Integrator and Op-Amp Differentiator 1 CAPACITANCE AND INDUCTANCE Introduces

More information

Chapter 31 Electromagnetic Oscillations and Alternating Current LC Oscillations, Qualitatively

Chapter 31 Electromagnetic Oscillations and Alternating Current LC Oscillations, Qualitatively Chapter 3 Electromagnetic Oscillations and Alternating Current LC Oscillations, Qualitatively In the LC circuit the charge, current, and potential difference vary sinusoidally (with period T and angular

More information