IGEE 402 Power System Analysis. FINAL EXAMINATION - SAMPLE Fall 2004

Size: px
Start display at page:

Download "IGEE 402 Power System Analysis. FINAL EXAMINATION - SAMPLE Fall 2004"

Transcription

1 IGEE 402 Power System Analysis FINAL EXAMINATION - SAMPLE Fall 2004 Special instructions: - Duration: 80 minutes. - Material allowed: a crib sheet (double sided 8.5 x ), calculator. - Attempt 5 out of 7 questions. - Make any reasonable assumption. - All questions and sub-questions carry equal weight. QUESTION (20 points) A single phase 550 V, 60 Hz feeder supplies 2 loads in parallel: (a) a 20 kw heating load; (b) a 50 kw motor load, with an efficiency of 0.90 and a power factor of 0.80 (lagging). (a) Draw the instantaneous current and voltage waveforms for the total load, indicating peak and rms values. Give the equation for the total instantaneous power and draw the waveform. Indicate the value of the total real power. (b) Draw the V-I vector diagram and the power diagram. Compute total reactive power and power factor. (b) A capacitor is connected in parallel with the loads to increase the power factor to.0. Compute the reactive power required from the capacitor. Redraw the power diagram. (c) Explain the benefits in having a unity power factor from (i) the utility point of view; (ii) the consumer point of view. QUESTION 2 (20 points) A single phase 24 kv/2.4 kv, 60 Hz transformer, with a series equivalent impedance of j.0 Ω referred to the low-voltage side, is connected at the end of a transmission line of impedance 50 + j400 Ω. The transformer feeds a load drawing 200 kw, at a 0.8 power factor lagging, and 2300 V. (a) The feeder voltage is adjusted so that the load voltage is 2300 V. Assume the load voltage has an angle of 0 deg. Find the amplitude and angle of the voltage at the sending end of the transmission line. (Hint: refer all quantities to the low voltage side). (b) Compute the current in the transmission line, the losses in the transmission line and transformer, and the overall system efficiency. (c) Calculate the no-load voltage and the voltage regulation. (d) Explain how the voltage regulation can be reduced. (Hint: consider shunt compensation). QUESTION 3 (20 points) A three-phase feeder supplies three identical single-phase 35 kv/6.9 kv, 60 Hz, 00 MVA transformers, each with a leakage reactance of 0.5 pu on the transformer base, and connected in a

2 IGEE 402 Power System Analysis FINAL EXAMINATION SAMPLE Joós, G. -Y connection. The load is a three-phase Y-connected 2 kv load, with per phase parameters of 60 MW, 0.85 power factor (lagging). A capacitor bank of three elements of impedance (-j5 Ω) connected in is used for power factor correction. The secondary voltage is assumed to be 2 kv. (a) Compute the total power and total reactive power drawn from the feeder. (b) Draw the single line pu circuit, using a 300 MVA (three-phase), 2 kv base. (c) Compute the total line current, the total power and total reactive power drawn from the feeder, in pu. Compute the voltage at the feeder. Compare with results in (a). (d) Phase c of the load becomes an open circuit. In the original V-A three-phase circuit, compute the current in the lines feeding the load, when (i) the load neutral is solidly grounded; (ii) the load neutral is floating. QUESTION 4 (20 points) A 400 km, 38 kv, 60 Hz transmission line has the following distributed parameters: r = 0.06 Ω/km, x = Ω/km, y = j3.36 x 0-6 S/km. Losses are neglected. (a) Compute the nominal π equivalent circuit parameters and draw the circuit. Compute the corresponding ABCD parameters. (b) Find the surge impedance and surge impedance loading. (c) The line delivers 40 MW at 32 kv with a power factor of 0.95 lagging. Using the ABCD parameters, compute the sending end voltage, current and δ angle. Confirm using the nominal π equivalent circuit, and the short line equivalent. (d) Draw the approximate voltage profile of this line for the following power delivered: (i) 0 MW, 20 MW, 50 MW, and surge impedance loading. Indicate the methods available to maintain the voltages within the range of 0.95 and.05. QUESTION 5 (20 points) A two-bus transmission system consists of the following: (i) a voltage regulated bus (.0 pu), the swing bus; (ii) a load bus, with a load of power (0.3 = j.0), and a fixed capacitor, supplying a reactive power of (j.); (iii) a transmission line of impedance (j0.4). (a) Draw the single line diagram. Assuming the load bus voltage magnitude is pu, compute the load angle δ. Compute the Y bus matrix. (b) Formulate the Gauss Seidel solution. Indicate the unknowns. Compute the first iteration. (c) Formulate the Newton Raphson solution. Compute the first iteration. (d) Comment on the features of the 2 methods described above. Indicate approaches to accelerate the convergence to the solution. Indicate the changes required to the formulation above if a voltage-controlled bus replaces the load bus. QUESTION 6 (20 points) A three-phase power system is fed from the secondary of a -Y connected transformer, with a neutral grounded through an impedance of j pu. The transformer series impedance is j0.5 pu. The transmission line impedance is j0.2 pu, with no zero sequence component. The sending end voltage is assumed to be pu. The load is a Y-connected impedance of pu (resistive). (a) Draw the sequence component networks, indicating all the impedance values, and voltage sources. (b) A three-phase symmetrical short circuit occurs at the load end, with a 0. pu impedance. Give the sequence impedance matrix for the fault current. Draw the sequence networks corresponding to the fault. Compute the sequence components of the fault currents. Convert into phase quantities. (c) A single line-to-ground fault occurs on phase a with an impedance of 0. pu. Calculate the sequence components of the fault current. Draw the sequence networks corresponding to the Page 2 of 3

3 IGEE 402 Power System Analysis FINAL EXAMINATION SAMPLE Joós, G. fault. Compute the value of the sequence components of the fault currents. Convert into phase quantities. (d) For the symmetrical three-phase fault and the single line-to-ground fault, compute the symmetrical components of the voltage at the fault, and convert to abc values. Draw conclusions as to the severity and impact of those two types of faults on the voltages at the load.. QUESTION 7 (20 points) A three-phase. 60 Hz, round rotor hydroelectric generator has an H constant of 5 s. It delivers P m =.0 pu power at a power factor of 0.90 lagging to an infinite bus through a transmission line of reactance X = 0.6. The voltage at the infinite bus is.0 pu with an angle of 0 deg. The machine transient reactance X d = 0.3 pu. (a) Compute the transient machine internal voltage and angle δ. Give the corresponding equation for the electric power. (b) Write the pu swing equation. A three-phase bolted short occurs midway along the transmission line. Determine the power angle 4 cycles after the initiation of the short circuit. Assume the mechanical input power remains constant at the initial value. (c) Draw the P- δ curve for the above operating conditions. Indicate the initial conditions, and the fault clearing point. Explain the application of the equal area criterion to this case. (d) Discuss methods to ensure that the machine does not loose synchronism (breaker operation, series compensation, ) APPENDIX A SYMMETRICAL COMPONENT TRANSFORMATION MATRICES A = a 2 a a a 2 A - = a a 2 a 2 a Page 3 of 3

4 ECSE Power Systems Analysis Final Exam - Solutions QUESTION (8 points) A single phase 550 V, 60 Hz feeder supplies 2 loads in parallel: (a) a 20 kw heating load; (b) a 50 kw motor load, with an efficiency of 0.90 and a power factor of 0.80 (lagging).. Draw the instantaneous current and voltage waveforms for the total load, indicating peak and rms values. Give the equation for the total instantaneous power and draw the waveform. Indicate the value of the total real power. 2. Draw the V-I vector diagram and the power diagram. Compute total reactive power and power factor. 3. A capacitor is connected in parallel with the loads to increase the power factor to.0. Compute the reactive power required from the capacitor. Redraw the power diagram. 4. Explain the benefits in having a unity power factor from (i) the utility point of view; (ii) the consumer point of view. Vl := 550 Pr := Pm := pf_m := 0.80 ω := 2 π 60. Instantaneous voltage, current, and power waveforms Heating Load: Ir := Pr Vl Motor Load: Sm := Pm pf_m Imotor_mag := Sm Vl φ := acos( pf_m) Imotor := Imotor_mag cos φ Combined Load: ( ( ) j sin( φ) ) Is := Ir + Imotor mag( Is) = a_deg( Is) = 28.79

5 Plot Waveforms: t := 0, ( ) it ():= 2mag ( Is) cos ω t + arg( Is) vt ():= 2Vl Ip := 2 mag( Is) Vlp := 2 Vl cos( ω t) 000 it () vt () Vlp = Vl = 550 Ip = mag( Is) = t Instantaneous Power: pt ():= vt ()it Total Real Power: Ptotal := Pm + Pr pt () Ptotal Ptotal = t

6 2. VI vector diagram, total reactive power, power factor, and power triangle ( ) Qt := Sm sin φ Stotal := ( Pm + Pr) + j Qt 80 cos( pf ) = π pf = 0.88 pf := ( Pm + Pr) mag( Stotal) Qt = mag( Stotal) = Calculate the reactive power required from the capacitor The reactive power required from the capacitor is simply the negative of the total reactive power from part 2. This way the load power factor becomes unity and the feeder apparent power has only a real component. The new power triangle looks as follow: 4. Explain the benefits of having unity power factor from (i) the utility point of view and (ii) the customer's point of view. The utility benefits from unity power factor since in this way the reactive power flows on the line become zero. Although this doesn't directly contribute to losses, reactive power flows contribute to increased currents and the associated losses involved. In addition, the increased current may also play a role in reducing the lifespan of the lines and other equipment. Also, providing reactive compensation at the load can help to improve voltage stability In terms of the customer, unity power factor is desirable since it indirectly affects the power quality through the regulation of the voltage. Large inductive loads can cause undervoltages which can be undesirable for sensitive loads. Also, the customer will likely inherit some of the cost due to the losses mentioned above and therefore saving from the point of view of the utility also result in savings for the customer as well.

7 QUESTION 2 (8 points) A single phase 24 kv/2.4 kv, 60 Hz transformer, with a series equivalent impedance of j.0 Ω referred to the low-voltage side, is connected at the end of a transmission line of impedance 50 + j400. The transformer feeds a load drawing 200 kw, at a 0.8 power factor lagging, and 2300 V The feeder voltage is adjusted so that the load voltage is 2300 V. Assume the load voltage has an angle of 0 deg. Find the amplitude and angle of the voltage at the sending end of the transmission line. (Hint: refer all quantities to the low voltage side). Compute the current in the transmission line, the losses in the transmission line and transformer, and the overall system efficiency. Calculate the no-load voltage and the voltage regulation. Explain how the voltage regulation can be reduced. (Hint: consider shunt compensation).. Calculate the feeder voltage and angle Define Load: Pload := pf load := 0.8 Sload := Pload pf load Vload := 2300 Vload 2 Zload mag := Sload ( ( ( ))) Zload := Zload mag pf load + j sin acos pf load Zload = i Calculate Feeder Voltage: mag( Zload) = 2.6 a_deg( Zload) = a := Ztrans := j.0 Zline := ( 50 + j 400) a 2 Zline = i Ztrans Zline Vs := Vload ( + + Zload) Zload mag( Vs) = a_deg( Vs) = 8.24

8 2. Calculate the transmission line current, all losses, and efficiency Current: Iline_low := ( Vs Vload) ( Zline + Ztrans) Iline_high := Iline_low a mag( Iline_high) = 0.87 a_deg( Iline_high) = Losses: Transmission Line Transformer Pline := mag( Iline_low) 2 Re( Zline) Ptrans := mag( Iline_low) 2 Re( Ztrans) Pline = Ptrans = Efficiency: Eff := Pload 00 Pload + Pline + Ptrans Eff = No-load voltage and voltage regulation Since the line contains no shunt components the no-load voltage will equal the magnitude of the source voltage. Vno_load := Vs Vno_load = VR := ( Vno_load Vload) 00 Vload VR = % 4. Improvement of Voltage Regulation The receiving end voltage varies as a function of the current on line which is dependent on the load connected. We can compensate for the change in voltage by adding shunt compensation at the load. In this way the voltage can be regulated to a given reference, say pu. In this way the receiving end voltage may change by only a very small amount between no-load an full-load. Therefore, a decrease in the VR is possible which will depend on the rating of the reactive power source, in the case where the rating of the compensation is infinite the voltage regulation becomes 0%. VR will also depends upon the impedance of the line and therefore, series compensation or installation of a parallel line could also help to limit VR.

9 QUESTION 3 (8 points) A three-phase feeder supplies three identical single-phase 35 kv / 6.9 kv, 60 Hz, 00 MVA transformers, each with a leakage reactance of 0.5 pu on the transformer base, and connected in a -Y connection. The load is a three-phase Y-connected 2 kv load, with per phase parameters of 60 MW, 0.85 power factor (lagging). A capacitor bank of three elements of impedance (-j 5 ) connected in is used for power factor correction. The secondary voltage is assumed to be 2 kv.. Compute the total power and total reactive power drawn from the feeder. 2. Draw the single line pu circuit, using a 300 MVA (three-phase), 2 kv base. 3. Compute the total line current, the total power and total reactive power drawn from the feeder, in pu. Compute the voltage at the feeder. Compare with results in (). 4. Phase c of the load becomes an open circuit. In the original V-A three-phase circuit, compute the current in the lines feeding the load, when (i) the load neutral is solidly grounded; (ii) the load neutral is floating.. Compute the total real and reactive power drawn from the feeder Sbase := Vbase := 2000 Zbase := Vbase 2 Sbase Zbase = 0.48 Load: pf := 0.85 Pload := Sload := Pload pf Sbase Ibase := Sbase 3 Vbase Zload := pf j sin acos pf Sload ( + ( ( ))) Zload = i Capacitor Bank: Xc := j 5 3 Xcpu := Xc Zbase Xcpu = 3.472i Qc := Xcpu Total Real and reactive power: Ptotal := Pload Ptotal = Qtotal := Sbase ( Sload sin( acos( pf )) Qc ) Qtotal =

10 2. Single Line Diagram 3. Total line current, total real and reactive power and power factor in pu. Feeder voltage. Iline := Zload + Xcpu Iline = a_deg( Iline) = Sline := conj( Iline) Pline := Qline := Re( Sline) Im( Sline) Pline = 0.6 Qline = pf line := Pline Sline pf line = 0.99 Compare with (): Pline Sbase = Ptotal = Qline Sbase = Qtotal = Vfeeder := + Iline 0. Zbase Vfeeder =.029 pu Vf_high := Vfeeder Vf_high = V 4. Currents in the line feeding the load with phase c open circuited (i) neutral is solidly grounded We simply refer to the below figure and solve the two loop equations, we disregard the capacitors since we are interested only in the current feeding the load. Va := π Vb := cos Z := j j 0.75 π + j sin Vab := Va Vb

11 Va ia := Z ia Ibase = Vb ib := Z ib Ibase = io := ia + ib io Ibase = a_deg( ia) = (i) neutral is floating a_deg( ib) = a_deg( io) = In this case, the problem is trivial since I 0 = 0, since there is no path for zero sequence current. Therefore, we can say that I a = -I b and the circuit looks as follows: Ia := Vab 2Z Ib := Ia Ia Ibase = a_deg( Ia) = 6.87 Ib Ibase = a_deg( Ib) = 73.3

12 QUESTION 4 (8 points) A 400 km, 38 kv, 60 Hz transmission line has the following distributed parameters: r = 0.06 /km, x = /km, y = j3.36 x 0-6 S/km. Losses are neglected. (a) Compute the nominal equivalent circuit parameters and draw the circuit. Compute the corresponding ABCD parameters. (b) Find the surge impedance and surge impedance loading. (c) The line delivers 40 MW at 32 kv with a power factor of 0.95 lagging. Using the ABCD parameters, compute the sending end voltage, current and angle. Confirm using the nominal equivalent circuit, and the short line equivalent. (d) Draw the approximate voltage profile of this line for the following power delivered: (i) 0 MW, 20 MW, 50 MW, and surge impedance loading. Indicate the methods available to maintain the voltages within the range of 0.95 and.05. (a) Compute the nominal π equivalent circuit parameters, ignore losses rl := 0.06 xl := yl := l := 400 Vl := X := ixl l X = 97.2i Y := iyl l Y =.344i 0 3 Vl 3 = Api := + Y X 2 Api = Bpi := X Bpi = 97.2i Cpi := Y + Y X 4 Cpi =.255i 0 3 (b) Find the surge impedance and the SIL xl ( Vl Vl) Zc := Zc = SIL := SIL = yl Zc β := xl yl β = (c) Calculate sending end voltage and angle using ABCD, nominal pi, and short line equivalent Lossless ABCD A := cos( β l) A = 0.87 ( ) B := i Zc sin β l B = i ( ) C := i sin β l C =.285i 0 3 Zc

13 pf := 0.95 Prec := Srated := Prec pf Vrl := Vrl = Srated Ir := 3 Vrl ( pf + j sin ( acos ( pf ))) Ir = a_deg ( Ir ) = 8.95 Sending end voltage and angle,using ABCD, nominal pi, and short line Vsl := A Vrl + BIr Vsl = i 0 4 Vsl = a_deg( Vsl) = Vsl := Api Vrl + Bpi Ir Vsl = i 0 4 Vsl = a_deg( Vsl) = Vsl := Vrl + X Ir Vsl = i 0 4 Vsl = a_deg( Vsl) = Sending end current using ABCD, nominal pi, and short line Isl := C Vrl + AIr Isl = i Isl = a_deg( Isl) = Isl := Cpi Vrl + Api Ir Isl = i Isl = a_deg( Isl) = Isl := Ir Isl = i Isl = a_deg( Isl) = 8.95 (d) Approximate voltage profile for 0 MW, 20 MW, 50 MW, and SIL (49.7 MW) It is possible to keep the receiving end voltage between 0.95 and.05 using shunt compensation in the form of switched capacitors or inductors. Static compensators which are more elegant can be used as well which provide for better adjustment of the reactive power injected or consumed, and can respond much quicker. Examples include Static var compensators (SVCs) and static shunt compensators (STATCOM).

14 QUESTION 5 (8 points) A two-bus transmission system consists of the following: (i) a voltage regulated bus (.0 pu), the swing bus; (ii) a load bus, with a load of power (0.3 + j.0), and a fixed capacitor, supplying a reactive power of (j.); (iii) a transmission line of impedance (j0.4). (a) Draw the single line diagram. Assuming the load bus voltage magnitude is pu, compute the load angle. Compute the Ybus matrix. (b) Formulate the Gauss Seidel solution. Indicate the unknowns. Compute the first iteration. (c) (d) Formulate the Newton Raphson solution. Compute the first iteration. Comment on the features of the 2 methods described above. Indicate approaches to accelerate the convergence to the solution. Indicate the changes required to the formulation above if a voltage-controlled bus replaces the load bus. (a) Draw the single line diagram, calculate load angle, δ assuming V2 =.0, calculate the admittance matrix. Use: P = V V 2 / X sin(δ -δ 2 ) P := 0.3 X := 0.4 y := X Y bus := j δ 2 := asin( P X) 80 Q 2 := 0. δ 2 = π y y y y 2.5i Y bus = 2.5i 2.5i 2.5i P 2 := P (b) Formulate the Gauss-Siedel problem: state the unknows and calculate the st iteration We apply the Guass-Siedel formula to the voltage at the load bus: V 2 (k+) = /Y 22 [ (P 2 - jq 2 )/V 2 - Y 2 *V (k) ] The unknowns are the voltage and angle at bus 2. Once the solution has converged we are able to obtain the unknown flows which are the real and reactive power at bus.

15 So, we calculate the first iteration assuming a flat voltage profile as our initial guess. V 2 := Y bus, ( ) P 2 jq 2 Y bus, 0 V 2 =.047 a_deg V 2 ( ) = (c) Formulate the Newton-Raphson problem: state the unknows and calculate the st iteration In order to calculate the first iteration we need to determine the Jacobian, which will define our search direction. The vector of unknows, x is given by the angle and magnitude of the voltage at the load bus: Initial guess: x := 0 The unknown flows again are the real and reactive power at bus. Which are calculated once the voltage at the load bus has been determined. V2 := x Calculate Jacobian: dp2dδ2 := V2 Y bus V, 0 dp2dv2 := 2V2 Y bus cos arg Y bus Y bus, 0 dq2dδ2 := V2 Y bus, 0 V := V2 sin( arg( V2) arg ( V ) arg( Y bus, 0 )) ( (, )) + V cos, ( arg( V2) arg ( V ) arg( Y bus, 0 )) ( ( ) arg ( V ) arg( Y bus, 0 )) ( ( )) ( ( )) V cos arg V2 y := y = dq2dv2 := 2V2 Y bus sin arg Y bus + Y bus V sin arg( V2) arg ( V ) arg Y bus,,, 0, 0 P 2 Q 2 J := dp2dδ2 dq2dδ2 dp2dv2 dq2dv2 J = Calculate the new voltage: x := J y x = x = x = π x := x + x (d) Comments Newton Raphson is more well suited to solve the load flow equations since it is more often used to solve non-linear equations while Gauss-Siedel is more well suited for solving linear equations. Methods to improve speed of convergence are to use fast-decoupled load flow where the Jacobian is only calculated once, and only inverted once as well. Sparse matrices methods are also implemented for larger systems. If bus 2 becomes a PV bus, the formulation is changed slightly in that x becomes the angle δ 2 and whereas y becomes the known flow P 2. In Gauss-Siedel we iterate w.r.t Q 2 and not V 2

16 QUESTION 6 (8 points) A three-phase power system is fed from the secondary of a -Y connected transformer, with a neutral grounded through an impedance of j pu. The transformer series impedance is j0.5 pu. The transmission line impedance is j 0.2 pu, with no zero sequence component. The sending end voltage is assumed to be pu. The load is a Y-connected impedance of pu (resistive). (a) Draw the sequence component networks, indicating all the impedance values, and voltage sources. (b) A three-phase symmetrical short circuit occurs at the load end, with a 0. pu impedance. Give the sequence impedance matrix for the fault current. Draw the sequence networks corresponding to the fault. Compute the sequence components of the fault currents. Convert into phase quantities. (c) A single line-to-ground fault occurs on phase a with an impedance of 0. pu. Calculate the sequence components of the fault current. Draw the sequence networks corresponding to the fault. Compute the value of the sequence components of the fault currents. Convert into phase quantities. (d) For the symmetrical three-phase fault and the single line-to-ground fault, compute the symmetrical components of the voltage at the fault, and convert to abc values. Draw conclusions as to the severity and impact of those two types of faults on the voltages at the load. (a) Draw the sequence component networks (Note: grounding impedance should be 3Zn)

17 (b) Three phase Symmetrical Short Circuit Zo := + j.5 Zo = i Z := + j 0.35 Z = i E := + j 0.35 E = i E = a_deg( E) = 9.29 Z2 := Z Zf := 0. a := j 2 3 I := E Z + Zf I = 2.54 Iph := Aseq I o I I 2 I 2 := 0 a_deg I ( ) = I o := 0 Iph 0 Iph Iph 2 = Aseq := ( ) ( ) ( ) a_deg Iph 0 a_deg Iph a_deg Iph 2 a 2 a = a a

18 (c) Single Line to Ground Fault I := E ( Z + Z2 + Zo + 3Zf ) I 2 := I I o := I I = I ph := Aseq I o I I 2 a_deg I ( ) = I ph0 I ph I ph2 = ( ) = a_deg I ph0 (d) Calculate fault voltages Three phase fault: V 2 := 0 V o := 0 Zf V := E Zf + Z V = i V = 0.25 a_deg V ( ) = 75.44

19 V ph := Aseq V o V V 2 V ph0 V ph V ph2 = ( ) = a_deg V ph0 Line to ground fault: V o := I o Zf V := V o V 2 := V V o = 0.06 a_deg V o ( ) = V ph := Aseq V o V V 2 V ph0 V ph V ph2 = ( ) = a_deg V ph0

20 QUESTION 7 (8 points) A three-phase. 60 Hz, round rotor hydroelectric generator has an H constant of 5 s. It delivers Pm =.0 pu power at a power factor of 0.90 lagging to an infinite bus through a transmission line of reactance X = 0.6. The voltage at the infinite bus is.0 pu with an angle of 0 deg. The machine transient reactance X'd = 0.3 pu. (a) Compute the transient machine internal voltage and angle. Give the corresponding equation for the electric power. (b) Write the pu swing equation. A three-phase bolted short occurs midway along the transmission line. Determine the power angle 4 cycles after the initiation of the short circuit. Assume the mechanical input power remains constant at the initial value. (c) Draw the P- curve for the above operating conditions. Indicate the initial conditions, and the fault clearing point. Explain the application of the equal area criterion to this case. (d) Discuss methods to ensure that the machine does not loose synchronism (breaker operation, series compensation, ) (a) Compute the transient machine internal voltage and angle X := 0.6 Xd := 0.3 pf := 0.9 H:= 5 P := I := P ( pf j sin( acos( pf ))) pf I =. a_deg( I) = E:= + j ( X + Xd) I E =.695 a_deg( E) = (b) Provide and use the swing equation ( 2H) ωsyn ω pu() t 2 d 2 dt δ() t = p m,pu (t) -p e,pu (t) ωsyn := 2 π 60 δ := arg( E) Integrating swing equation twice,assuming p m remains constant we obtain δ() t = ωsyn 4H t2 + δ For four cycles following the fault we determine the new δ δ new := ωsyn 4H δ δ new = δ new = π

21 (c) Draw the P-δ curve for the fault operation p m ( δ) = E sin( δ) = ( X + Xd).8 sin( δ) E ( X + Xd) =.883 δ A := p m dδ δ 0 δ δ 0.0 d δ = δ new δ = δ 2 A 2 := δ ( ).8sinδ p m dδ ( ( ) cos( δ 2 )) ( δ 2 δ ).8 cos δ.8 cos( δ 2 ) + δ 2 =.46 = A := 0.68 δ 2 := δ 2 = π We calculate A using the swing equation and the fault duration to determine the angle at which the fault is cleared, δ. The machine continues to accelerate until A2 = A. We can determine whether the machine retains stability determining whether there in fact does exist and angle δ 2 for which A2 does in fact equal A. Following the above calculations we see that this is true for approximately 22 degrees, and therefore stability is maintained.

22 (d) Discuss methods to maintain stability There exist various methods to help maintain stability. Many of the most common are listed here: Smaller equivalent line impedance (parallel lines, different conductors, smaller transformer leakage reactances, series compensation...) Higher voltages FACTS devices Faster clearing of faults Larger machine inertia

23 Define function mag( x) := ( Re( x) ) 2 + ( Im( x) ) 2 conj( x) := Re( x) Im( x) j a_deg( x) := arg( x) 80 π

24

25 n

26

27

28 r

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester Electrical and Electronics Engineering EE 1352 Power System Analysis (Regulation 2008) Time: Three hours Answer all questions Part A (10

More information

KINGS COLLEGE OF ENGINEERING Punalkulam

KINGS COLLEGE OF ENGINEERING Punalkulam KINGS COLLEGE OF ENGINEERING Punalkulam 613 303 DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING POWER SYSTEM ANALYSIS QUESTION BANK UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A (TWO MARK

More information

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous)

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad - 500 043 ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK Course Name : Computer Methods in Power Systems Course Code : A60222

More information

EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION

EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION PART: A 1. Define per unit value of an electrical quantity. Write equation for base impedance with respect to 3-phase system. 2. What is bus admittance

More information

THE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session

THE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session Name: Student ID: Signature: THE UNIVERSITY OF NEW SOUTH WALES School of Electrical Engineering & Telecommunications FINALEXAMINATION Session 00 ELEC46 Power System Analysis TIME ALLOWED: 3 hours TOTAL

More information

POWER SYSTEM STABILITY

POWER SYSTEM STABILITY LESSON SUMMARY-1:- POWER SYSTEM STABILITY 1. Introduction 2. Classification of Power System Stability 3. Dynamic Equation of Synchronous Machine Power system stability involves the study of the dynamics

More information

Fault Calculation Methods

Fault Calculation Methods ELEC9713 Industrial and Commercial Power Systems Fault Calculation Methods There are two major problems that can occur in electrical systems: these are open circuits and short circuits. Of the two, the

More information

Fault Analysis Power System Representation

Fault Analysis Power System Representation .1. Power System Representation Single Line Diagram: Almost all modern power systems are three phase systems with the phases of equal magnitude and equal phase difference (i.e., 10 o ). These three phase

More information

DHANALAKSHMI SRINIVASAN COLLEGE OF ENGINEERING AND TECHNOLOGY Mamalapuram Chennai QUESTION BANK V SEMESTER. EE6501-Power system Analysis

DHANALAKSHMI SRINIVASAN COLLEGE OF ENGINEERING AND TECHNOLOGY Mamalapuram Chennai QUESTION BANK V SEMESTER. EE6501-Power system Analysis DHANALAKSHMI SRINIVASAN COLLEGE OF ENGINEERING AND TECHNOLOGY Mamalapuram Chennai DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK V SEMESTER EE6501-Power system Analysis Regulation 2013

More information

Final Exam, Second Semester: 2015/2016 Electrical Engineering Department

Final Exam, Second Semester: 2015/2016 Electrical Engineering Department Philadelphia University Faculty of Engineering Student Name Student No: Serial No Final Exam, Second Semester: 2015/2016 Electrical Engineering Department Course Title: Power II Date: 21 st June 2016 Course

More information

ELG4125: Power Transmission Lines Steady State Operation

ELG4125: Power Transmission Lines Steady State Operation ELG4125: Power Transmission Lines Steady State Operation Two-Port Networks and ABCD Models A transmission line can be represented by a two-port network, that is a network that can be isolated from the

More information

Power Factor Improvement

Power Factor Improvement Salman bin AbdulazizUniversity College of Engineering Electrical Engineering Department EE 2050Electrical Circuit Laboratory Power Factor Improvement Experiment # 4 Objectives: 1. To introduce the concept

More information

EE 742 Chapter 3: Power System in the Steady State. Y. Baghzouz

EE 742 Chapter 3: Power System in the Steady State. Y. Baghzouz EE 742 Chapter 3: Power System in the Steady State Y. Baghzouz Transmission Line Model Distributed Parameter Model: Terminal Voltage/Current Relations: Characteristic impedance: Propagation constant: π

More information

BASIC PRINCIPLES. Power In Single-Phase AC Circuit

BASIC PRINCIPLES. Power In Single-Phase AC Circuit BASIC PRINCIPLES Power In Single-Phase AC Circuit Let instantaneous voltage be v(t)=v m cos(ωt+θ v ) Let instantaneous current be i(t)=i m cos(ωt+θ i ) The instantaneous p(t) delivered to the load is p(t)=v(t)i(t)=v

More information

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL 1 SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL Power Systems: Generation, Transmission and Distribution Power Systems: Generation, Transmission and Distribution Power Systems:

More information

CHAPTER 2 LOAD FLOW ANALYSIS FOR RADIAL DISTRIBUTION SYSTEM

CHAPTER 2 LOAD FLOW ANALYSIS FOR RADIAL DISTRIBUTION SYSTEM 16 CHAPTER 2 LOAD FLOW ANALYSIS FOR RADIAL DISTRIBUTION SYSTEM 2.1 INTRODUCTION Load flow analysis of power system network is used to determine the steady state solution for a given set of bus loading

More information

QUESTION BANK ENGINEERS ACADEMY. Power Systems Power System Stability 1

QUESTION BANK ENGINEERS ACADEMY. Power Systems Power System Stability 1 ower ystems ower ystem tability QUETION BANK. A cylindrical rotor generator delivers 0.5 pu power in the steady-state to an infinite bus through a transmission line of reactance 0.5 pu. The generator no-load

More information

Chapter 3 AUTOMATIC VOLTAGE CONTROL

Chapter 3 AUTOMATIC VOLTAGE CONTROL Chapter 3 AUTOMATIC VOLTAGE CONTROL . INTRODUCTION TO EXCITATION SYSTEM The basic function of an excitation system is to provide direct current to the field winding of the synchronous generator. The excitation

More information

ECE 585 Power System Stability

ECE 585 Power System Stability Homework 1, Due on January 29 ECE 585 Power System Stability Consider the power system below. The network frequency is 60 Hz. At the pre-fault steady state (a) the power generated by the machine is 400

More information

ECE 325 Electric Energy System Components 7- Synchronous Machines. Instructor: Kai Sun Fall 2015

ECE 325 Electric Energy System Components 7- Synchronous Machines. Instructor: Kai Sun Fall 2015 ECE 325 Electric Energy System Components 7- Synchronous Machines Instructor: Kai Sun Fall 2015 1 Content (Materials are from Chapters 16-17) Synchronous Generators Synchronous Motors 2 Synchronous Generators

More information

11. AC Circuit Power Analysis

11. AC Circuit Power Analysis . AC Circuit Power Analysis Often an integral part of circuit analysis is the determination of either power delivered or power absorbed (or both). In this chapter First, we begin by considering instantaneous

More information

Lecture 11 - AC Power

Lecture 11 - AC Power - AC Power 11/17/2015 Reading: Chapter 11 1 Outline Instantaneous power Complex power Average (real) power Reactive power Apparent power Maximum power transfer Power factor correction 2 Power in AC Circuits

More information

ECE 476 Power System Analysis Fall 2014 Exam #1, Thursday, October 2, :30AM - 10:50AM

ECE 476 Power System Analysis Fall 2014 Exam #1, Thursday, October 2, :30AM - 10:50AM ECE 476 Power System Analysis Fall 4 Exam #, Thursday, October, 4. 9:3AM - :5AM Name: Problem (5 p) Two balanced 3-phase loads are connected in parallel. One is Y-connected and draws 75 kw (3-phase) at.8

More information

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A 1. What are the advantages of an inter connected system? The advantages of an inter-connected system are

More information

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur Lecture - 9 Transmission Line Steady State Operation Welcome to lesson 9, in Power

More information

ECE 420. Review of Three Phase Circuits. Copyright by Chanan Singh, Panida Jirutitijaroen, and Hangtian Lei, For educational use only-not for sale.

ECE 420. Review of Three Phase Circuits. Copyright by Chanan Singh, Panida Jirutitijaroen, and Hangtian Lei, For educational use only-not for sale. ECE 40 Review of Three Phase Circuits Outline Phasor Complex power Power factor Balanced 3Ф circuit Read Appendix A Phasors and in steady state are sinusoidal functions with constant frequency 5 0 15 10

More information

LO 1: Three Phase Circuits

LO 1: Three Phase Circuits Course: EEL 2043 Principles of Electric Machines Class Instructor: Dr. Haris M. Khalid Email: hkhalid@hct.ac.ae Webpage: www.harismkhalid.com LO 1: Three Phase Circuits Three Phase AC System Three phase

More information

ECE 421/521 Electric Energy Systems Power Systems Analysis I 2 Basic Principles. Instructor: Kai Sun Fall 2013

ECE 421/521 Electric Energy Systems Power Systems Analysis I 2 Basic Principles. Instructor: Kai Sun Fall 2013 ECE 41/51 Electric Energy Systems Power Systems Analysis I Basic Principles Instructor: Kai Sun Fall 013 1 Outline Power in a 1-phase AC circuit Complex power Balanced 3-phase circuit Single Phase AC System

More information

SHORT QUESTIONS AND ANSWERS. Year/ Semester/ Class : III/ V/ EEE Academic Year: Subject Code/ Name: EE6501/ Power System Analysis

SHORT QUESTIONS AND ANSWERS. Year/ Semester/ Class : III/ V/ EEE Academic Year: Subject Code/ Name: EE6501/ Power System Analysis Srividya colllege of Engg & Tech,Virudhunagar Sri Vidya College of Engineering And Technology Virudhunagar 626 005 Department of Electrical and Electronics Engineering QUESTION BANK SHORT QUESTIONS AND

More information

EE Branch GATE Paper 2010

EE Branch GATE Paper 2010 Q.1 Q.25 carry one mark each 1. The value of the quantity P, where, is equal to 0 1 e 1/e 2. Divergence of the three-dimensional radial vector field is 3 1/r 3. The period of the signal x(t) = 8 is 0.4

More information

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION EE 6501 POWER SYSTEMS UNIT I INTRODUCTION PART A (2 MARKS) 1. What is single line diagram? A Single line diagram is diagrammatic representation of power system in which the components are represented by

More information

Brief Steady of Power Factor Improvement

Brief Steady of Power Factor Improvement International Journal of Electrical Engineering. ISSN 0974-2158 Volume 6, Number 5 (2013), pp. 531-539 International Research PublicationHouse http://www.irphouse.com Brief Steady of Power Factor Improvement

More information

12. Introduction and Chapter Objectives

12. Introduction and Chapter Objectives Real Analog - Circuits 1 Chapter 1: Steady-State Sinusoidal Power 1. Introduction and Chapter Objectives In this chapter we will address the issue of power transmission via sinusoidal or AC) signals. This

More information

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME: EE 2303 - TRANSMISSION & DISTRIBUTION YEAR / SEM: III/V UNIT-I TRANSMISSION SYSTEM INTRODUCTION PART-A 1. What is

More information

Boise State University Department of Electrical and Computer Engineering ECE 212L Circuit Analysis and Design Lab

Boise State University Department of Electrical and Computer Engineering ECE 212L Circuit Analysis and Design Lab Objectives Boise State University Department of Electrical and Computer Engineering ECE 22L Circuit Analysis and Design Lab Experiment #4: Power Factor Correction The objectives of this laboratory experiment

More information

POWER SEMICONDUCTOR BASED ELECTRIC DRIVES

POWER SEMICONDUCTOR BASED ELECTRIC DRIVES POWER SEMICONDUCT BASED ELECTRIC DRIVES [Time: 3 Hrs] [Max. Marks: 80] Instructions: Solve any six questions from Q.No (1 or 2), Q.No (3 or 4), Q.No (5 or 6), Q.No (7 or 8), Q.No (9 or 10), Q.No (11 or

More information

Three Phase Circuits

Three Phase Circuits Amin Electronics and Electrical Communications Engineering Department (EECE) Cairo University elc.n102.eng@gmail.com http://scholar.cu.edu.eg/refky/ OUTLINE Previously on ELCN102 Three Phase Circuits Balanced

More information

Chapter 33. Alternating Current Circuits

Chapter 33. Alternating Current Circuits Chapter 33 Alternating Current Circuits 1 Capacitor Resistor + Q = C V = I R R I + + Inductance d I Vab = L dt AC power source The AC power source provides an alternative voltage, Notation - Lower case

More information

Transmission and Distribution of Electrical Power

Transmission and Distribution of Electrical Power KINGDOM OF SAUDI ARABIA Ministry Of High Education Umm Al-Qura University College of Engineering & Islamic Architecture Department Of Electrical Engineering Transmission and Distribution of Electrical

More information

ECEN 460 Exam 1 Fall 2018

ECEN 460 Exam 1 Fall 2018 ECEN 460 Exam 1 Fall 2018 Name: KEY UIN: Section: Score: Part 1 / 40 Part 2 / 0 Part / 0 Total / 100 This exam is 75 minutes, closed-book, closed-notes. A standard calculator and one 8.5 x11 note sheet

More information

Chapter 8 VOLTAGE STABILITY

Chapter 8 VOLTAGE STABILITY Chapter 8 VOTAGE STABIITY The small signal and transient angle stability was discussed in Chapter 6 and 7. Another stability issue which is important, other than angle stability, is voltage stability.

More information

Introduction to Synchronous. Machines. Kevin Gaughan

Introduction to Synchronous. Machines. Kevin Gaughan Introduction to Synchronous Machines Kevin Gaughan The Synchronous Machine An AC machine (generator or motor) with a stator winding (usually 3 phase) generating a rotating magnetic field and a rotor carrying

More information

Contents Kreatryx. All Rights Reserved.

Contents Kreatryx. All Rights Reserved. Contents Manual for K-Notes... Transmission Lines... 3 Underground Cables... 14 Overhead Insulators... 16 Distribution Systems... 16 Per Unit System... 17 Load Flow Study... 18 Economic Power Generation...

More information

+ ( )= with initial condition

+ ( )= with initial condition Department of Electrical Engineering PhD. Admission Test Full Marks: 90 Time 90 minutes Date: 02.2.204 NAME: Appl. No: Write your answer on the question paper ONLY. All questions carry equal marks. PART

More information

Module 4. Single-phase AC Circuits

Module 4. Single-phase AC Circuits Module 4 Single-phase AC Circuits Lesson 14 Solution of Current in R-L-C Series Circuits In the last lesson, two points were described: 1. How to represent a sinusoidal (ac) quantity, i.e. voltage/current

More information

ECE 476. Exam #2. Tuesday, November 15, Minutes

ECE 476. Exam #2. Tuesday, November 15, Minutes Name: Answers ECE 476 Exam #2 Tuesday, November 15, 2016 75 Minutes Closed book, closed notes One new note sheet allowed, one old note sheet allowed 1. / 20 2. / 20 3. / 20 4. / 20 5. / 20 Total / 100

More information

In the previous chapter, attention was confined

In the previous chapter, attention was confined 4 4 Principles of Power System CHAPTE CHAPTE 8 Unsymmetrical Fault Calculations 8. Usymmetrical Faults on -Phase System 8. Symmetrical Components Method 8. Operator a 8.4 Symmetrical Components in Terms

More information

Dynamics of the synchronous machine

Dynamics of the synchronous machine ELEC0047 - Power system dynamics, control and stability Dynamics of the synchronous machine Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct October 2018 1 / 38 Time constants and

More information

EE2351 POWER SYSTEM ANALYSIS

EE2351 POWER SYSTEM ANALYSIS EE351 POWER SYSTEM ANALYSIS A.Ahamed Riazudeen EEE DEPARTMENT 1 UNIT I INTRODUCTION Power system network 3 SINGLE LINE DIAGRAM It is a diagrammatic representation of a power system in which the components

More information

Chapter 31 Electromagnetic Oscillations and Alternating Current LC Oscillations, Qualitatively

Chapter 31 Electromagnetic Oscillations and Alternating Current LC Oscillations, Qualitatively Chapter 3 Electromagnetic Oscillations and Alternating Current LC Oscillations, Qualitatively In the LC circuit the charge, current, and potential difference vary sinusoidally (with period T and angular

More information

SCHOOL OF ELECTRICAL, MECHANICAL AND MECHATRONIC SYSTEMS. Transient Stability LECTURE NOTES SPRING SEMESTER, 2008

SCHOOL OF ELECTRICAL, MECHANICAL AND MECHATRONIC SYSTEMS. Transient Stability LECTURE NOTES SPRING SEMESTER, 2008 SCHOOL OF ELECTRICAL, MECHANICAL AND MECHATRONIC SYSTEMS LECTURE NOTES Transient Stability SPRING SEMESTER, 008 October 7, 008 Transient Stability Transient stability refers to the ability of a synchronous

More information

Week No. 6 Chapter Six: Power Factor Improvement

Week No. 6 Chapter Six: Power Factor Improvement Week No. 6 Chapter Six: Power Factor Improvement The electrical energy is almost wholly generated, transmitted and distributed in the form of alternating current. Therefore, the question of power factor

More information

EE301 Three Phase Power

EE301 Three Phase Power Learning Objectives a. Compute the real, reactive and apparent power in three phase systems b. Calculate currents and voltages in more challenging three phase circuit arrangements c. Apply the principles

More information

Transient Stability Assessment of Synchronous Generator in Power System with High-Penetration Photovoltaics (Part 2)

Transient Stability Assessment of Synchronous Generator in Power System with High-Penetration Photovoltaics (Part 2) Journal of Mechanics Engineering and Automation 5 (2015) 401-406 doi: 10.17265/2159-5275/2015.07.003 D DAVID PUBLISHING Transient Stability Assessment of Synchronous Generator in Power System with High-Penetration

More information

BEE701 POWER SYSTEM ANALYSIS

BEE701 POWER SYSTEM ANALYSIS BEE701 POWER SYSTEM ANALYSIS UNIT I POWER SYSTEM COMPONENTS Power system analysis The evaluation of power system is called as power system analysis Functions of power system analysis To monitor the voltage

More information

ELEC4612 Power System Analysis Power Flow Analysis

ELEC4612 Power System Analysis Power Flow Analysis ELEC462 Power Sstem Analsis Power Flow Analsis Dr Jaashri Ravishankar jaashri.ravishankar@unsw.edu.au Busbars The meeting point of various components of a PS is called bus. The bus or busbar is a conductor

More information

Sinusoidal Steady State Analysis (AC Analysis) Part II

Sinusoidal Steady State Analysis (AC Analysis) Part II Sinusoidal Steady State Analysis (AC Analysis) Part II Amin Electronics and Electrical Communications Engineering Department (EECE) Cairo University elc.n102.eng@gmail.com http://scholar.cu.edu.eg/refky/

More information

1 Unified Power Flow Controller (UPFC)

1 Unified Power Flow Controller (UPFC) Power flow control with UPFC Rusejla Sadikovic Internal report 1 Unified Power Flow Controller (UPFC) The UPFC can provide simultaneous control of all basic power system parameters ( transmission voltage,

More information

Review of Basic Electrical and Magnetic Circuit Concepts EE

Review of Basic Electrical and Magnetic Circuit Concepts EE Review of Basic Electrical and Magnetic Circuit Concepts EE 442-642 Sinusoidal Linear Circuits: Instantaneous voltage, current and power, rms values Average (real) power, reactive power, apparent power,

More information

Sinusoidal Response of RLC Circuits

Sinusoidal Response of RLC Circuits Sinusoidal Response of RLC Circuits Series RL circuit Series RC circuit Series RLC circuit Parallel RL circuit Parallel RC circuit R-L Series Circuit R-L Series Circuit R-L Series Circuit Instantaneous

More information

1 Phasors and Alternating Currents

1 Phasors and Alternating Currents Physics 4 Chapter : Alternating Current 0/5 Phasors and Alternating Currents alternating current: current that varies sinusoidally with time ac source: any device that supplies a sinusoidally varying potential

More information

Exercise Dr.-Ing. Abdalkarim Awad. Informatik 7 Rechnernetze und Kommunikationssysteme

Exercise Dr.-Ing. Abdalkarim Awad. Informatik 7 Rechnernetze und Kommunikationssysteme Exercise1 1.10.015 Informatik 7 Rechnernetze und Kommunikationssysteme Review of Phasors Goal of phasor analysis is to simplify the analysis of constant frequency ac systems v(t) = max cos(wt + q v ) i(t)

More information

AC Power Analysis. Chapter Objectives:

AC Power Analysis. Chapter Objectives: AC Power Analysis Chapter Objectives: Know the difference between instantaneous power and average power Learn the AC version of maximum power transfer theorem Learn about the concepts of effective or value

More information

Basics of Electric Circuits

Basics of Electric Circuits António Dente Célia de Jesus February 2014 1 Alternating Current Circuits 1.1 Using Phasors There are practical and economic reasons justifying that electrical generators produce emf with alternating and

More information

Chapter 8: Unsymmetrical Faults

Chapter 8: Unsymmetrical Faults Chapter 8: Unsymmetrical Faults Introduction The sequence circuits and the sequence networks developed in the previous chapter will now be used for finding out fault current during unsymmetrical faults.

More information

Work, Energy and Power

Work, Energy and Power 1 Work, Energy and Power Work is an activity of force and movement in the direction of force (Joules) Energy is the capacity for doing work (Joules) Power is the rate of using energy (Watt) P = W / t,

More information

Power and Energy Measurement

Power and Energy Measurement Power and Energy Measurement EIE 240 Electrical and Electronic Measurement April 24, 2015 1 Work, Energy and Power Work is an activity of force and movement in the direction of force (Joules) Energy is

More information

Examples of Applications of Potential Functions in Problem Solving (Web Appendix to the Paper)

Examples of Applications of Potential Functions in Problem Solving (Web Appendix to the Paper) Examples of Applications of otential Functions in roblem Solving (Web Appendix to the aper) Ali Mehrizi-Sani and Reza Iravani May 5, 2010 1 Introduction otential functions may be exploited to formulate

More information

Refresher course on Electrical fundamentals (Basics of A.C. Circuits) by B.M.Vyas

Refresher course on Electrical fundamentals (Basics of A.C. Circuits) by B.M.Vyas Refresher course on Electrical fundamentals (Basics of A.C. Circuits) by B.M.Vyas A specifically designed programme for Da Afghanistan Breshna Sherkat (DABS) Afghanistan 1 Areas Covered Under this Module

More information

EE221 - Practice for the Midterm Exam

EE221 - Practice for the Midterm Exam EE1 - Practice for the Midterm Exam 1. Consider this circuit and corresponding plot of the inductor current: Determine the values of L, R 1 and R : L = H, R 1 = Ω and R = Ω. Hint: Use the plot to determine

More information

ELECTRIC POWER CIRCUITS BASIC CONCEPTS AND ANALYSIS

ELECTRIC POWER CIRCUITS BASIC CONCEPTS AND ANALYSIS Contents ELEC46 Power ystem Analysis Lecture ELECTRC POWER CRCUT BAC CONCEPT AND ANALY. Circuit analysis. Phasors. Power in single phase circuits 4. Three phase () circuits 5. Power in circuits 6. ingle

More information

mywbut.com Lesson 16 Solution of Current in AC Parallel and Seriesparallel

mywbut.com Lesson 16 Solution of Current in AC Parallel and Seriesparallel esson 6 Solution of urrent in Parallel and Seriesparallel ircuits n the last lesson, the following points were described:. How to compute the total impedance/admittance in series/parallel circuits?. How

More information

Lecture (5) Power Factor,threephase circuits, and Per Unit Calculations

Lecture (5) Power Factor,threephase circuits, and Per Unit Calculations Lecture (5) Power Factor,threephase circuits, and Per Unit Calculations 5-1 Repeating the Example on Power Factor Correction (Given last Class) P? Q? S? Light Motor From source 1000 volts @ 60 Htz 10kW

More information

The Operation of a Generator on Infinite Busbars

The Operation of a Generator on Infinite Busbars The Operation of a Generator on Infinite Busbars In order to simplify the ideas as much as possible the resistance of the generator will be neglected; in practice this assumption is usually reasonable.

More information

= V I = Bus Admittance Matrix. Chapter 6: Power Flow. Constructing Ybus. Example. Network Solution. Triangular factorization. Let

= V I = Bus Admittance Matrix. Chapter 6: Power Flow. Constructing Ybus. Example. Network Solution. Triangular factorization. Let Chapter 6: Power Flow Network Matrices Network Solutions Newton-Raphson Method Fast Decoupled Method Bus Admittance Matri Let I = vector of currents injected into nodes V = vector of node voltages Y bus

More information

LESSON 20 ALTERNATOR OPERATION OF SYNCHRONOUS MACHINES

LESSON 20 ALTERNATOR OPERATION OF SYNCHRONOUS MACHINES ET 332b Ac Motors, Generators and Power Systems LESSON 20 ALTERNATOR OPERATION OF SYNCHRONOUS MACHINES 1 LEARNING OBJECTIVES After this presentation you will be able to: Interpret alternator phasor diagrams

More information

Electromagnetic Oscillations and Alternating Current. 1. Electromagnetic oscillations and LC circuit 2. Alternating Current 3.

Electromagnetic Oscillations and Alternating Current. 1. Electromagnetic oscillations and LC circuit 2. Alternating Current 3. Electromagnetic Oscillations and Alternating Current 1. Electromagnetic oscillations and LC circuit 2. Alternating Current 3. RLC circuit in AC 1 RL and RC circuits RL RC Charging Discharging I = emf R

More information

Power System Engineering Prof. Debapriya Das Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Power System Engineering Prof. Debapriya Das Department of Electrical Engineering Indian Institute of Technology, Kharagpur Power System Engineering Prof. Debapriya Das Department of Electrical Engineering Indian Institute of Technology, Kharagpur Lecture 41 Application of capacitors in distribution system (Contd.) (Refer Slide

More information

Analysis of AC Power RMS and Phasors Power Factor. Power Factor. Eduardo Campero Littlewood

Analysis of AC Power RMS and Phasors Power Factor. Power Factor. Eduardo Campero Littlewood Power Factor Eduardo Campero Littlewood Universidad Autónoma Metropolitana Azcapotzalco Campus Energy Department Content 1 Analysis of AC Power 2 RMS and Phasors 3 Power Factor Recommended Bibliography

More information

EE 451 Power System Stability

EE 451 Power System Stability EE 451 Power System Stability Power system operates in synchronous mode Power system is subjected to a wide range of disturbances (small and large) - Loads and generation changes - Network changes - Faults

More information

3- BASICS. YTransformation. for balanced load. \V ab 120 = \V bc. \V ab 240 = \V ca \I a 120 = \I b \I a 240 = \I c V ab I a

3- BASICS. YTransformation. for balanced load. \V ab 120 = \V bc. \V ab 240 = \V ca \I a 120 = \I b \I a 240 = \I c V ab I a 3- BASICS YTransformation for balanced load Z =3Z Y Balanced 3- Systems \V ab 10 = \V bc \V ab 40 = \V ca \I a 10 = \I b \I a 40 = \I c V ab I a = p 3 V an = p 3 I ab \V ab 30 = \V an \I ab 30 = \I a S

More information

Power and Energy Measurement

Power and Energy Measurement Power and Energy Measurement ENE 240 Electrical and Electronic Measurement Class 11, February 4, 2009 werapon.chi@kmutt.ac.th 1 Work, Energy and Power Work is an activity of force and movement in the direction

More information

CHAPTER 5 STEADY-STATE ANALYSIS OF THREE-PHASE SELF-EXCITED INDUCTION GENERATORS

CHAPTER 5 STEADY-STATE ANALYSIS OF THREE-PHASE SELF-EXCITED INDUCTION GENERATORS 6 CHAPTER 5 STEADY-STATE ANALYSIS OF THREE-PHASE SELF-EXCITED INDUCTION GENERATORS 5.. INTRODUCTION The steady-state analysis of six-phase SEIG has been discussed in the previous chapters. In this chapter,

More information

Chapter 9: Transient Stability

Chapter 9: Transient Stability Chapter 9: Transient Stability 9.1 Introduction The first electric power system was a dc system built by Edison in 1882. The subsequent power systems that were constructed in the late 19 th century were

More information

Chapter 2-3 Transformers

Chapter 2-3 Transformers Principles of Electric Machines and Power Electronics Chapter 2-3 Transformers Third Edition P. C. Sen Auto transformer Per unit system S b = S rate V b1 = V rate1 V b2 = V rate2 S b I b1 = = S rate =

More information

GATE 2010 Electrical Engineering

GATE 2010 Electrical Engineering GATE 2010 Electrical Engineering Q.1 Q.25 carry one mark each 1. The value of the quantity P, where P = xe dx, is equal to (A) 0 (B) 1 (C) e (D) 1/e 2. Divergence of the three-dimensional radial vector

More information

ECE 201 Fall 2009 Final Exam

ECE 201 Fall 2009 Final Exam ECE 01 Fall 009 Final Exam December 16, 009 Division 0101: Tan (11:30am) Division 001: Clark (7:30 am) Division 0301: Elliott (1:30 pm) Instructions 1. DO NOT START UNTIL TOLD TO DO SO.. Write your Name,

More information

AC Circuits Homework Set

AC Circuits Homework Set Problem 1. In an oscillating LC circuit in which C=4.0 μf, the maximum potential difference across the capacitor during the oscillations is 1.50 V and the maximum current through the inductor is 50.0 ma.

More information

GATE 2008 Electrical Engineering

GATE 2008 Electrical Engineering GATE 2008 Electrical Engineering Q.1 Q. 20 carry one mark each. 1. The number of chords in the graph of the given circuit will be + _ (A) 3 (B) 4 (C) 5 (D) 6 2. The Thevenin'a equivalent of a circuit operating

More information

Generators. What its all about

Generators. What its all about Generators What its all about How do we make a generator? Synchronous Operation Rotor Magnetic Field Stator Magnetic Field Forces and Magnetic Fields Force Between Fields Motoring Generators & motors are

More information

Module 3 : Sequence Components and Fault Analysis

Module 3 : Sequence Components and Fault Analysis Module 3 : Sequence Components and Fault Analysis Lecture 12 : Sequence Modeling of Power Apparatus Objectives In this lecture we will discuss Per unit calculation and its advantages. Modeling aspects

More information

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II : 7 - Transient Stability

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II : 7 - Transient Stability ECE 4/5 Power System Operations & Planning/Power Systems Analysis II : 7 - Transient Stability Spring 014 Instructor: Kai Sun 1 Transient Stability The ability of the power system to maintain synchronism

More information

Exercise 2: Power Factor

Exercise 2: Power Factor Power in AC Circuits AC 2 Fundamentals Exercise 2: Power Factor EXERCISE OBJECTIVE When you have completed this exercise, you will be able to determine the power factor of ac circuits by using standard

More information

RESULTS OF ON-GRID OPERATION OF SUPERCONDUCTOR DYNAMIC SYNCHRONOUS CONDENSER

RESULTS OF ON-GRID OPERATION OF SUPERCONDUCTOR DYNAMIC SYNCHRONOUS CONDENSER 1 RESULTS OF ON-GRID OPERATION OF SUPERCONDUCTOR DYNAMIC SYNCHRONOUS CONDENSER Dr. Swarn S. Kalsi, David Madura, and Michael Ross American Superconductor Corporation (USA) Abstract: A high-temperature

More information

RLC Series Circuit. We can define effective resistances for capacitors and inductors: 1 = Capacitive reactance:

RLC Series Circuit. We can define effective resistances for capacitors and inductors: 1 = Capacitive reactance: RLC Series Circuit In this exercise you will investigate the effects of changing inductance, capacitance, resistance, and frequency on an RLC series AC circuit. We can define effective resistances for

More information

POWER SYSTEMS. First Course on. Ned Mohan. Copyright Ned Mohan

POWER SYSTEMS. First Course on. Ned Mohan. Copyright Ned Mohan First Course on POWER SYSTEMS Ned Mohan Oscar A. Schott Professor of Power Electronics and Systems Department of Electrical and Computer Engineering University of Minnesota Minneapolis, MN 55455 USA Copyright

More information

EXP. NO. 3 Power on (resistive inductive & capacitive) load Series connection

EXP. NO. 3 Power on (resistive inductive & capacitive) load Series connection OBJECT: To examine the power distribution on (R, L, C) series circuit. APPARATUS 1-signal function generator 2- Oscilloscope, A.V.O meter 3- Resisters & inductor &capacitor THEORY the following form for

More information

Design of PSS and SVC Controller Using PSO Algorithm to Enhancing Power System Stability

Design of PSS and SVC Controller Using PSO Algorithm to Enhancing Power System Stability IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 10, Issue 2 Ver. II (Mar Apr. 2015), PP 01-09 www.iosrjournals.org Design of PSS and SVC Controller

More information

Incorporation of Asynchronous Generators as PQ Model in Load Flow Analysis for Power Systems with Wind Generation

Incorporation of Asynchronous Generators as PQ Model in Load Flow Analysis for Power Systems with Wind Generation Incorporation of Asynchronous Generators as PQ Model in Load Flow Analysis for Power Systems with Wind Generation James Ranjith Kumar. R, Member, IEEE, Amit Jain, Member, IEEE, Power Systems Division,

More information

Long-term voltage stability : load aspects

Long-term voltage stability : load aspects ELEC0047 - Power system dynamics, control and stability Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct December 2018 1 / 15 Table of contents Voltage instability results from the

More information