THE EFFECT OF A THIN FOIL ON THE HEAT LOSSES BEHIND A RADIATOR

Size: px
Start display at page:

Download "THE EFFECT OF A THIN FOIL ON THE HEAT LOSSES BEHIND A RADIATOR"

Transcription

1 F A C U L T Y O F E N G IN E E RIN G A ND SUST A IN A B L E D E V E L OPM E N T THE EFFECT OF A THIN FOIL ON THE HEAT LOSSES BEHIND A RADIATOR Núria Barguilla Jiménez February 2013 Master s Thesis in Energy Systems Master Program in Energy Systems Examiner: Ulf Larsson Supervisor: Mathias Cehlin and Jan A kander

2

3 Abstract This thesis work is the study of the effect of an aluminium foil on the losses that produced by a radiator, situated under a window, through the wall behind it. The reason behind this topic is due to the energy problem and the different goals that governments have set up to try to reduce the use of energy. For example, more specifically a Swedish national goal is to decrease the energy use of the built stock with 50% by For this purpose, an experimental set up was built in the University of Gävle, Sweden. The arrangement was composed by a radiator and a window facing a climate chamber. A total of twenty one temperatures and two heat fluxes in the exterior wall were measured in the set up. Ten different measurement scenarios with different radiator temperature, 40 C, 50 C and 60 C; two different distance between the radiator and the wall, 5 and 9 centimetres and with and without the aluminium foil, were performed. With the experimental results, a CFD model was validated. Two different models were done, first a 2D model and afterwards a 3D model. For the turbulence, the chosen model was standard k ε model. There were 54 cases simulated with the 2D model and the 3D model was used just for validation. The cases had different variables such as radiator temperature, outdoor temperature and wall insulation. With these cases, analysis of the effectiveness of the presence of an aluminium foil behind the radiator is performed to evaluate if there is a significant reduction of the losses. The results showed with both methods that the aluminium foil reduces the losses of the wall behind the radiator. The savings varied depending on the boundary conditions of the case and it were obtained a maximum of 4% and a minimum of 1,3%.

4

5 Nomenclature A Area [m 2 ] D Distance de between radiator and wall [cm] K Constant of the heat power of a radiator equation n Exponent of the heat power of a radiator equation q Heat flux [W/m2] Q extra Q rad Q req Q wall R R e R i T e T i T rad Heat loss at the of the back wall associated with the type of heating system [W] Heat power of the radiator [W] Heating requirement of the room [W] Heat loss at the back wall [W] Conduction resistance of the wall [m 2 K/W] Convection outdoors resistance [m 2 K/W] Convection indoors resistance [m 2 K/W] Outdoor temperature [ C] Indoor temperature [ C] Radiator temperature [ C] U U value [W/m 2 K] y Distance from the floor [cm] ε Emissivity Sub index Al CFD Lab Presence of Aluminium Result from CFD Result from experimental set up

6

7 Table of Contents Nomenclature 5 1 Introduction Background Objectives Related works Theory Aluminium foil CFD Models Boundary Conditions Method Laboratory Assembly Measurements Thermocouples Thermopile Software Methodology Conditions Limitations CFD Gambit Ansys Fluent Savings Calculation Results and discussion Experimental... 35

8 4.2 CFD D Validation D Validation Savings Calculation Comparison of the different cases Conclusion References.. 55 Appendices. 57

9 1 Introduction 1.1 Background Nowadays there is a worldwide problem that needs to be solved in a relatively short period of time. That problem is the production of energy. The consumption of energy is very high and it is going to increase in the next years due to a population growth and increased standard of living in developing countries. Also the data show that around 80% of primary energy used in the world comes from non renewable sources. [1] Because these sources are limited, it is urgent to try to find a solution. Moreover most of these non renewable sources are fossil fuels, which entail the production of CO 2. Linked to this issue there is also the problem of climate change that comes due to the emissions of CO 2. [2] To find the answer to these problems there is two ways face them. The first one is to try to find others ways to produce energy and the second one, try to reduce the consumption or try to make systems that are more efficient. During 2004, the building and service sector account for 40% of the energy use in the EU, thus using more energy than in each of the industrial and transportation sectors [1]. A majority of the consumption comes from the heating in buildings, especially regions with really cold winters such as Sweden. In the next figure, it can be seen the energy consumption divided by sectors in Sweden for the year The energy consumption for residential and services is the 41% of the total consumption. This is equivalent to 166 TWh of which 53 TWh are for heating. [3] 41% 36% Industry Transport Residential and Services 23% Source: Swedish Energy Agency Fig.1: Energy consumption in Sweden (2010) 9

10 Another factor is that a Swedish national goal is to decrease the energy use of the built stock with 50% by 2050, in comparison to energy used in [5] In order to achieve this goal, the energy use of the old building stock has to substantially be reduced, see for example [4]. This will be a costly process, which has to be commenced today and most likely continue beyond The figure number two shows the energy consumption in Sweden during the lasts decades. It can be seen that there is a growing tendency of the energy consumption. [3] The dip in 2009 is due to the global financial crisis (reduced energy use in the industry) and the increase in 2010 is due to a severely cold winter (increase in the energy use of the residential and services sector namely buildings). TWh Industry Transport Residential and Services Total Fig.2: Energy consumption evolution in Sweden Between about 1965 and 1975, the building stock in Sweden expanded immensely due to the million programme, see for example [6]. In essence, a total of one million villas and apartments were erected during this period of time. The quick building pace, in combination with testing new building technologies and to keep cost low together with an insufficient level of maintenance, have resulted in that the buildings from that time are in need of renovation or retrofitting. A characteristic of the building technology of the time is that massive materials were used in external walls, such as bricks and aerated concrete. However the radiators, normally placed under the window, were fit in line with the inner surface of the external wall; leaving the only possibility of having a thin wall 10

11 towards the external environment. Usually wood frame walls with mineral wool were mounted there, commonly with thicknesses of 45, 70 or maximum 95 mm. There is a quite amount of energy produced that is lost by the wall behind the radiator since this wall is to be regarded as being poorly insulated. During the 1980 s, this problem was recognized. One option to reduce this loss was to put an aluminium foil in the wall behind the radiator. The foil was placed on the wall surface to reflect the long wave radiation from the radiator, to minimize the heat transfer through the wall. But there were voices that said that this would not work: if the internal surface temperature of the wall is reduced, the heat transfer by convection will increase and thereby deplete the gains made by long wave radiation. Fig.3: Buildings made in 1950 Figure 3 shows a multifamily building that was erected in The external was are made of a layer of bricks (120 mm), an air cavity (25 mm), aerated concrete blocks (200 mm) and about 25 mm mortar. The wall below the windows is a thinner wood frame walls with a higher U value, which has a higher heat loss as seen in the figure. [7] One problem with actions to reduce energy is that often are expensive and this solution is very affordable and with an easy access for many people. Therefore this thesis tries to study the effect of the aluminium foil in the heat losses of a radiator. 1.2 Objectives The main objective of this thesis intends to find a way to reduce the consumption of energy by trying to make a heating system more efficient with low costs. This study will see the effect of an aluminium foil to reduce the radiator losses, since no 11

12 previous scientific studies have found. The foil is placed on the inside surface of the wall, behind the radiator. This includes the following ones: To quantify the reduction of the radiator losses due to the aluminium foil. To measure the radiator losses in an experimental set up installed in a laboratory room. Temperatures and heat fluxes are monitored. To use the CFD method to obtain the radiator losses. To compare the two methods used to get the results. To study the effect in different cases, these ones will include the outdoor temperature, the thermal insulation level of the wall behind the radiator and the temperature of the radiator. 1.3 Related works There are not a lot of studies in this field but some related works are the following: The effect of wall emissivity on radiator heat output [8]. This work studied variation of the heat output of a panel radiator altering the emissivity of the wall behind the radiator. It was done with both methods, experimental and CFD. The results indicated that the heat that the heat output could be increased by 20% with a black wall instead of a reflective one. The effect of surface roughness and emissivity on radiator output [9]. This work studied the variation of the heat output altering the emissivity and roughness of the wall behind the radiator. Also it was done experimentally and with CFD. The results indicated that high emissivity and large scale surface increased the heat output about 26%. 12

13 2 Theory 2.1 Aluminium foil The reason why the material to reduce the losses of a radiator is aluminium is because of its low emissivity. This makes that the surface with aluminium foil reflects most part of the heat and does not go through the wall. In this way the radiation is reduced and the losses through the wall behind the radiator are lower. 2.2 CFD The abbreviation CFD stands to computational fluid dynamics and it consists of a numerical method used to analyse systems that involve fluid flow, heat transfer and associated phenomena. This technique started to have a heavy use in the 1980s and until today it is known to be a very powerful method that can be used in a wide range of application areas. The CFD codes are structured around numerical algorithms. The mathematical basis is based on conservation of mass, momentum and energy. The main parts of the CFD method consists in the making the grid, defining the models and boundary conditions and afterwards the solving the model and processing data. [10] Models There are three different physical phenomena that are present in this case. These are energy, turbulence and radiation. The energy equation is derived from the first law of thermodynamics. This one states that the rate of change of energy of a fluid particle is equal to the rate of heat addition to the fluid particle plus the rate of work done on the particle. The turbulence model is used to describe the characteristics of the flow. The CFD code for the turbulence model should have a wide applicability, be accurate, simple and economical to run. There are different models to describe the phenomena. The most common are the classical based on time averaged Reynolds equations and the 13

14 large eddy simulation. In this thesis, the model used is a two equation model: the standard k ε. This model is semi empirical based on model transport equations for the turbulence kinetic energy (k) and its dissipation rate (ε). [11] The radiation model used is the discrete ordinates (DO) radiation model solves the radiative transfer equation for a finite number of discrete solid angles, each associated with a vector direction fixed in the global Cartesian system (x, y, z).! [11] Boundary Conditions In this thesis the boundary conditions were wall boundary conditions and a pressure outlet condition. In the wall boundary conditions, there were some parameters that needed to be determined such a fixed temperature, the emissivity or heat transfer coefficient for outdoor convection. To have a good mesh, it has to be evaluated the non dimensional parameter defined as the next equation where Δy & is the distance of the near wall, v the velocity, ρ the density and τ ) the wall shear stress. y * = Δy & v,τ ) ρ Depending of the used turbulence model, the y + has to take a certain value in order to resolve the laminar sublayer. The near wall treatment model in this is enchanted wall treatment that requires y + values lower than 1. 14

15 3 Method 3.1 Laboratory This chapter is about the experimental study. Here the set up will be described, how were the measurements done and which results were obtained. The experimental study took place in a laboratory room at the University of Gävle, Sweden. The laboratory room was built to look like a room with a window Assembly The laboratory assembly it is not complicated. It took place in a laboratory room which was built to look like housing. This room was situated next to a climate chamber that was used to simulate the outdoor temperature. Therefore a window was made in the wall that was facing the climate chamber. Fig.4: Assembly (left picture), Climate chamber (right picture) 15

16 The simulated window was composed of plywood and has the same U value as a double glazed window, namely about 3.0 W/m² K. After that there was a cavity made under the window where a plane electric radiator was located. The radiator was electric and was the type that was working on and off. Since the study has to be in steady state, a voltage regulator was placed with the radiator in order to have a constant temperature. Therefore the temperature could be changed selecting a voltage. With that different temperatures could be reached with a lower limit of 35 C. The whole assembly was painted black in order to have the same emissivity everywhere. This was done to try to be as close as possible of an emissivity of one, which is the emissivity of a black body. The following image shows the measures of the assembly in metres. Fig.5: Assembly measures: frontal view (left), profile view (right) 16

17 3.1.2 Measurements There were made two different types of measurements, temperatures and heat flux. The temperatures were taken from various points, a total of 21, in the different walls as well as the radiator and the floor. There was a total of twenty one different temperatures that were measured in the assembly. These temperatures were obtained with thermocouples (type T). The heat flux was measured with a heat flux sensor (type Huxeflux HFP01). There were a total of two points in the external wall were the measurements were taken. The wires of the thermocouples and the heat fluxes sensors were connected to a printed circuit board. This one transmitted the data to a computer where data could be saved and visualized. The next picture shows how were these measurements placed. Fig.6: Assembly with measurements devices Thermocouples The thermocouples are active sensors used to measure temperatures. They consist of two different conductors, usually metals, which are joined together in the point of measuring. When the junction is heated or cooled, it generates a small voltage signal based on the energy conversion principles and they don t required any external electrical generation. This electric potential is related to the temperature. Their main advantages are small size, stability, ruggedness, moderate sensibility over a 17

18 wide range of temperatures and also they are inexpensive. The main limitation with thermocouples is accuracy, system errors of less than one degree Celsius can be difficult to achieve. Fig.7: Thermocouple The thermocouples that were used were type T, also named copper constantan. This type has the electrodes made of copper (+) and an alloy of copper and nickel ( ). Their range is very wide from 270 C to +400 C. They were stuck in the wall with some duct tape, except the ones in the wall behind the radiator. For theses ones, there were slots made in the wall to put the wires of the thermocouples. This was done to prevent the thermocouples from disturbing the air flow behind the radiator. As said before, there was a total of twenty one points were the temperature was taken. Four of them were measured in the exterior wall, one in the window and the rest in the wall were the radiator was situated; all of them in the middle of the assembly. The exact positions can be seen in the next image, all the measures are in centimetres. 18

19 Fig.8: Position of the thermocouples in the external wall In the wall behind the radiator there was a total of eight different points were the temperature was measured. Five of them were right in the middle of the wall; two of them were the radiator finished and the last one, between the rests. The exact position of the thermocouples can be seen in the next picture, measures in centimetres. The radiator is showed with a discontinuous line. Fig.9: Wall behind the radiator with thermocouples 19

20 There were three thermocouples in the interior wall. Two of them were in the window and the other one, above the window. All of them were situated in the middle section. It can be seen the exact position in the next image. Distances are in centimetres. Fig.10: Internal wall with thermocouples Also there were two thermocouples that measured the temperature of the floor. All in the middle section and situated in a distance of forty cm and eighty cm from the interior wall. There were two measured temperatures of the radiator in order to know if there were differences in different points in the radiator. The last two measured temperatures were the internal and exterior air Thermopile A heat flux sensor is called thermopile. It is a transducer that generates an electrical signal proportional to the total heat rate applied to the surface of the sensor. It is composed with several thermocouples connected in series and sometimes in 20

21 parallel. The measured heat rate is divided by the surface area of the sensor to determine the heat flux. There were two points were the heat flux was measured, these ones were on the external wall behind the radiator. The exact position can be seen in the following image. The distances are in centimetres Software Fig.11: Heat flux sensor positions The software used to obtain the result is called Labview. This is only used to visualize and obtain the temperatures from the thermocouples and the heat flux. Also it was used to see when the system reached steady state. The program was designed to take a measurement every thirty minutes. The next image shows what it looks like. 21 Fig.12: Screenshot of Labview

22 3.1.3 Methodology The process of the laboratory experiments consists in setting up a tension of the voltage regulator to have a certain temperature of the radiator. Turn on the wind tunnel to simulate the exterior temperature and start the monitoring scheme in order to take the measurements. As it can be seen in the figure 12, the experiment was stopped when it reached steady state, i.e. the temperatures were stable. There were performed a total of ten different cases in the laboratory with three variables. These variables are the distance between the wall and the radiator, the temperature of the radiator and with or without the aluminium foil. There were two different positions for the radiator depending on how close it was to the wall. The two distances were five and nine centimetres. There were two temperatures with the first distance; 40 C and 50 C and three with the second one; 40 C, 50 C and 60 C. With this there are five different cases. The rest were with these exact conditions but with the aluminium foil behind the radiator. Case Temperature ( C) Distance (cm) Aluminium No No No No No Yes Yes Yes Yes Yes Table 1: Laboratory cases Every case was simulated until it reached stationary condition. This took around ten hours in every case. In order to obtain one temperature value, it was calculated the mean value with the data in steady state Conditions There were some conditions that were the same in every simulation. These are the following: The outdoor temperature was 20 ±1 C in all the different cases. This temperature was chosen to simulate in the worst of the cases in a Swedish climate. This temperature could not be entirely stable due the working of the wind tunnel. The indoor temperature was 20 C. To accomplish this temperature the door of the testing room was open in order to achieve the room temperature of 22

23 the laboratories (the heat from the radiator would otherwise give different indoor temperatures). In order to not have internal thermal loads that could influence the system, the lights were turned off in all the simulations Limitations There were some limitations that have to be taken into account. These are the following ones: In order to measure the temperature in the external wall, in the wind tunnel, there was made a hole in the window where the wires went though. This could make that part of the heat was lost though this hole, but should be negligible in comparison the heat output from the radiator. There were some extra heat loads that could not be taken from the test room. These are the computer load and heat loss from the voltage regulator. However, these are more or less constant. All the measurement devices have a margin of error. In this case the thermocouples ±1 C and the thermopiles have an error of ±5%. 3.2 CFD The process of working with CFD can be divided in three main parts: pre processor, solver and post processor. In this thesis the pre processor part has been done with two different softwares: Gambit and Ansys Fluent 14.0., while the solver and the post processor part was done just with Ansys Fluent. The pre processor is the most important part because it contains the model design and conditions. It can be divided in different parts: Definition of the geometry: draw the system of interest to study Mesh generation: divide the regions of study in small elements where the solution will be calculated Selection of physical and chemical phenomena that are needed to be modelled. Phenomena such as energy, turbulence, radiation, etc. Definition of material properties used in the studied system Definition of cell zone conditions: define the material of each region 23

24 Definition of boundary conditions: the exterior and the interior The solver is the part where the solution is calculated. The post processor is the part where the solution has been calculated and it can be showed in different plots form such as vector, lines, contour, etc Gambit The methodology in Gambit can be divided in three parts. These are the following: geometry, mesh and conditions. The first step in Gambit is to create points, after that the points are joint with lines that will create surfaces. In the 3D case the surfaces will be used to create the volumes. In this thesis, the control volume is a part of the room with the radiator. Not all the room was drawn because it would have taken a lot of time of solving and because the important part it is the wall behind the radiator. The measures of the control volume can be seen in the figure five. The next image shows the volume control in 2D. 24 Fig.13: Geometry of the 2D cases

25 At first, the idea was to only do a 2D model. Due to the results obtained with the two dimension model, it will be explained in the chapter four; it was decided to also make a 3D simulation. The control volume of the 3D model was only half of the room since it was symmetrical and the 3D simulation takes a long time to solve. The figure 14 shows this geometry in 3D. Number of cells 2D D Fig.14: Geometry of the 3D case The mesh was created using trial and error in order to fulfil the requirement that the value y + was smaller than one. That is because it was used enchanted wall treatment as explained in chapter two. The form of the mesh is rectangular since all the areas are rectangular. The mesh was sharper all around the radiator and near the walls 25

26 because there were high changes. The total number of cells in both cases can be seen in the table number two as well as the mesh in the figure 15. Number of cells 2D D Table 2: Number of cells Fig.15: Mesh of the 2D and 3D case 26

27 3.2.2 Ansys Fluent The software Ansys Fluent is used to simulate fluid dynamics. With the Gambit file opened, there are different things that need to be done in Fluent. The steps to follow consist of finishing the pre processor, solving and getting the results. The first thing in the pre processor is to set up the gravity in the y direction. Afterward set up the models, materials, cell zone conditions and boundary conditions. There are three different models used in this simulation: energy, turbulence and radiation. These are more detailed in the chapter two. The turbulence model used was Standard k ε with enchanted wall treatment and the radiation model is discrete ordinates. There are four different materials involved in this simulation. These are: Air: used with the default properties except for the density that was changed to incompressible ideal gas Wood: used with the default properties for the exterior part of the wall, both in the inside wall and the exterior Mineral wool: for the insulation inside of the wall with a thermal conductivity of 0,04 W/mK Aluminium: used for the wall behind the radiator with an emissivity of 0,1 After defining the materials, it has to be established which areas have each material. The cell zone condition is where this is done. Every region created in Gambit is attributed with the corresponding material. The following figure shows the materials of the model. 27

28 Fig.16: Materials of the control volume There are three different kinds of boundary conditions in this model. The first one is a pressure outlet since this wall it is not a real wall. The backflow temperature is the room temperature, 20 C. The external wall was set up as a convection free steam with a standard heat transfer outdoor coefficient of 25 W/m 2 K, the outdoor temperature took three different values, 20 C, 10 C and 0 C. Another boundary condition is a fixed temperature. This was set up in the floor and the ceiling with a temperature of 20 C and in the radiator where the temperature took three different 28

29 values: 30 C, 40 C and 50 C. The last one is coupled. This one takes place in the internal wall and it is a predetermined option because this wall is only used to transfer the heat. The emissivity of all the surfaces was set up as 0,9 with the exemption of 0,1 on the wall behind the radiator when the aluminium foil was set up. The boundary conditions for the 3D case are the same except that one of the faces had the condition of symmetrical wall. Fig.17: Boundary Conditions 29

30 A total of 54 cases there were performed. There were four variables that were combined: the radiator temperature, the outdoor temperature, the U value and the emissivity of the wall behind the radiator. The distance between the radiator and the wall it was always five centimetres. The value of the variables can be seen in the table three. T rad T e U ε ,36 0, ,48 0, ,62 Table 3: Values of the variables 3.3 Savings Calculation To calculate the reduction obtained with the aluminium foil, the methodology is to compare the results based on the idea of satisfying the same heat requirement of the room for both cases. The equation that involves the different heats is the equation 3.1. This one is obtained with a simple energy balance in steady state taking the simulated room as the control volume. The general equation for how much a radiator dissipates heat is: Q /01 = Q /23 + Q 256/0 (3.1) Where Q /23 is the heating requirement on basis of the transmission and ventilation losses, independent of the heating system type. Q 256/0 is the extra heat loss that is associated with the type of heat emitting system that is used, in this case the radiator that gives extra losses by heating the back wall s inner surface to higher temperatures than an ideal system would. The ideal system creates the indoor temperature without generating extra losses. For any heat emitting system, the heating requirement, Q /23, must be met and this is done at a certain temperature for the considered system. In this case, when the requirement of the room must be fulfilled, the radiator temperature with and 30

31 without the foil will not be identical. It is expected that the convective contribution to the room via the channel behind the radiator is less due to the presence of the aluminium foil. The reduction in convective heat from behind must be compensated by increasing heat emission from the front and this requires that the temperature of the radiator is increased. This will in turn increase heat loss from the wall. With the CFD software it can be directly obtained Q rad CFD and the Q extra CFD for every case, together with the radiator temperature that is associated with each Q / The procedure is as follows: When the calculations have converged to a result, the post processing allows finding the total power emitted from the radiator, Q rad CFD and the power that is totally conducted as loss through the back wall, Q wall CFD. The heat loss power Q wall CFD is composed of the heat loss that is system independent, i.e. U )0;; A )0;; T 2 ) and the extra loss that the radiator creates by heating the wall, Q extra CFD Q )0;; 789 = U )0;; A )0;; T 2 ) + Q 256/0 789 (3.2) The total heat emitted by the radiator, Q rad CFD, which is a function of temperature T rad CFD, will therefore supply Q / Cf(T / )E = Q / Q 256/0 789 (3.3) Insertion of equation 3.2 into 3.3 gives Q / Cf(T / )E = Q / Q )0;; 789 U )0;; A )0;; T 2 ) (3.4) The requirement can for the simulation be established (observe that U )0;; A )0;; T 2 ) implicitly is within Q / ) so that Q / = Q / Cf(T / )E Q )0;; U )0;; A )0;; T 2 ) (3.5) Hereby, Q / is converted to be a function of the temperature difference between the radiator and the indoor air temperature, such as defined in EN 442 [12] and for example Q / = K (T / ) G (3.6) 31

32 Giving, expressed with indexes for the case without aluminium: Q / = K (T / ) G Q )0;; U )0;; A )0;; T 2 ) (3.7) For the case with aluminium, the expression is: Q / HI = K H; (T / H; 789 ) G JK Q )0;; 789 H; + U )0;; A )0;; T 2 ) (3.8) In this way, for a given requirement, the radiator temperature can be established for the cases with and without aluminium foil. Finally, when T / without aluminium and T / H; with aluminium are known, the energy savings can be estimated when the two systems prove to fulfil the same heating requirement. It can be concluded, that the difference in heat loss through the wall, is equal to the difference in heat emission, so that Q )0;; 789 Q )0;; 789 H; = K (T / ) G K H; (T / H; 789 ) G JK (3.9) The difference can be expressed as savings with the unit percent, related to the radiators total emission without the foil. The calculus of the U value it is showed in the equation U )0;; = + R + R 2 (3.10) The value of R si and R se are the usual surface thermal resistances (inverse of the sum of the convective and radiative heat transfer coefficients), the interior takes the value of 0,13 m 2 K/W and the exterior 0,04 m 2 K/W. The R is the conduction resistance that depends of the case. This resistance is calculated with the equation R = T 2)0;; q (3.11) Once the heat requirement is obtained, it can be plotted the Q req and the Q rad versus the temperature difference between the radiator and the room in order to obtain the 32

33 equation of the power of the radiator. Therefore the constant K and n are found. In the next graphics can be seen this equations of the Q req and the Q rad. In every pack of cases, the equation is different due to the different air flow conditions around the radiator. With the equation obtained from the plots and with the same Q req, it can be calculated the radiator temperature for the case with and without aluminium. With the temperature obtained now it can be calculated the Q rad for both cases and afterwards calculate the savings with the equation % savings = Q /01 Q /01H; Q / (3.12) 33

34 34

35 4 Results and discussion This chapter consists of the analysis of the data obtained from both methods, experimental and CFD. Also a validation of the CFD model will be made and a comparison of the different cases. 4.1 Experimental As explained in the chapter three, there were two types of measurements performed: temperatures and heat flux. In the next figures the data from the laboratory experiments will be analysed. All the data can be found in the annex. The first figure, fig.18, is a graph that shows the measured heat flux versus the temperature of the radiator. The ten different cases, shown in the table one, can be joined in four different groups. These groups are formed depending on the distance of the radiator from the wall, five or nine centimetres, and presences of an aluminium foil. As the figure shows, with a higher temperature of the radiator, the heat flux also becomes higher, as expected from the theory. The relationship between these two parameters seems to be non linear. This can only be analysed in the cases that the distance between the wall and the radiator is nine because there is not enough data in the case of five centimetres. In the case without aluminium the tendency is logarithmic while the case with aluminium the tendency is exponential. However because there is only one case to be analysed it cannot be assured that these are the real tendencies. These will be analysed with the CFD method. Regarding the differences with different distances between the wall and the radiator, the values with nine centimetres are lower but not enough to say the there is considerable difference. It can be observed that the slope is higher when the distance is nine centimetres. 35

36 q [W/m 2 ] Without Al (5cm) Without Al (9cm) With Al (5cm) With Al (9cm) T rad [ C] Fig.18: Evolution of the heat flux The next graph, fig.19, shows the evolution of the five temperatures measured of the wall behind the radiator in the middle section in relation with the distance from the floor. The first figure is without aluminium foil. It can be seen that the temperatures get higher as the distance increases. That happens until a certain point where the temperature decreases. The points on the wall can be seen on the figure nine in the chapter three. The point more close to the floor has the lowest temperature. That is because of the airflow from the room, which has a temperature of twenty degrees approximately, goes up from behind the radiator. Since the radiation is really high, the view factor makes the ends with a lower temperature. Regarding the temperature gradient, it has the biggest difference of thirteen degrees in the case of five centimetres of the wall and a radiator temperature of 50 C. With the same radiator temperature, logically, the cases with the radiator further from the wall, the temperatures are lower. The temperatures differ at maximum 3 C. With higher radiator temperatures, the temperatures of the wall differ more with the distance. 36

37 T [ C] Trad=40 (5cm) Trad=50 (5cm) Trad=40 (9cm) Trad=50 (9cm) Trad=60 (9cm) y [cm] Fig.19: Temperatures of the wall behind the radiator without aluminium The next figure shows as well the temperatures of the wall behind the radiator but with the aluminium foil. As expected, the temperatures are much lower than without aluminium due to the reduction of radiation. Here unlike without the aluminium foil, the temperatures are higher as it moves away from the floor. That is because the convection has more importance than the radiation and due to the air getting hotter as it rises. The temperatures do not have a big temperature gradient. The difference of temperatures at most differs five degrees in the case number seven seen in the table one. Also there is not much difference in the different cases depending on the distance between the wall and the radiator or the temperature of this one; all the temperatures are gathered between 22 and 16 C. In the case with a radiator temperature of 60 C, the tendency differs from the other ones. That is because with higher radiator temperature, the radiation is more important. The same kinds of results for wall temperature were obtained in [8]. 37

38 y Fig.20: Temperatures of the wall behind the radiator with aluminium If the temperatures are compared for the same case with and without aluminium foil, it can be seen in the next figure the reduction of these ones. In the figure 21, the radiator has a temperature of 40 C. Trad = 40 C y Fig.21: Temperatures of the wall behind the radiator with and without aluminium 38

39 The following table shows the percentage of reduction of the wall temperatures. As said the reduction is more important when the temperature of the radiator is higher. d 5 cm 9 cm T rad % Reduction 35 41,9 35,5 43,1 48,9 Table 4: Reduction of the wall temperatures The thermocouples on the floor showed that the radiator temperature does not have much influence in the floor temperature. It has the same temperature as the room and the highest value reached is 22 C when the radiator has a temperature of 60 C. Regarding the external wall temperature, it has always a temperature around 17 C in all cases. Therefore it seems that it does not matter what temperature the radiator has. However in the laboratory the insulation was very good so that might be the reason of no influence from the radiator temperature. The cases were performed setting a voltage but because of the regulating system, it cannot be assured that the power of the radiator is the same in every case. The temperatures in the cases with the aluminium foil are slightly higher than the same without it. That can be explained with the reflection of the heat that makes the temperature of the radiator increase. The temperatures can be seen in the next table. d 5 cm 9 cm T rad 39,7 50,0 39,9 48,5 59,6 T radal 42,2 53,2 41,4 51,6 60,8 Table 5: Radiator temperatures Concerning the heat fluxes, table six the reduction through the back wall can be seen. However, since the power is not the same, it cannot be assured that this is the real reduction. When the distance between the radiator and the wall increases, the losses in the back wall decreases [9]. 39

40 d 5 cm 9 cm T rad % Reduction 32,51 33,46 25,62 32,83 34,76 Table 6: Reduction of the heat flux 4.2 CFD D Validation In this part, a comparison between the two methods will be made in order to validate the CFD model. The first graph, fig.22, compares the temperatures in the wall behind the radiator in the case of a 40 C in the radiator and five centimetres distance to the wall. T [ C] 35 T rad = 40 C 30 Lab with Al 25 CFD with Al Lab without Al 20 CFD without Al y [cm] Fig.22: Comparison of the two models with T rad = 40 C As it can be seen in the figure 22, the temperatures are more similar in the cases without aluminium foil. The reason that it may differ more in the aluminium cases may be because of the emissivity. The CFD emissivity was 0,1 but this is an estimation of a new foil since it was not possible to measure the emissivity in the laboratory. Also there is also another explanation: aluminium is a superior 40

41 conductor of heat, having the thermal conductivity of 200 W/m K. This will have the effect that it will reduce all temperature gradients and strive to make the aluminium layer isothermal. This tendency is noticed since the curve is almost a straight line. If the deviation is quantified, without aluminium it is about 4 C and with aluminium 3 C. It can be seen in the table 7. Lab CFD Deviation Al No Yes No Yes No Yes Radwall1 27,35 20, ,35 3,03 Radwall2 31,37 19, ,37 1,73 Radwall3 30,76 18, ,24 2,66 Radwall4 29,87 17, ,13 2,58 Radwall5 22,40 16, ,60 1,79 Table 7: Deviation in the temperatures with T rad = 40 C Regarding the heat fluxes, the error is higher than the temperatures. They are not similar, that can be explained with the fact that the problem is not a two dimensional case. The radiator in the laboratory was 59 centimetres long. This is a short radiator and could cause different air flows at the edges. As well as with the temperatures, in the CFD the heat flux is higher than the experimental data. Therefore, a 3D case will be done in order to see the effects all around the radiator. In the next table can be seen the calculated deviation with the heat flux in W/m 2. Without Al With Al q Lab 14,88 10,04 q CFD 18,70 15,00 Deviation 25,70 49,39 Table 8: Deviation (%) in the heat flux with T rad = 40 C The following graph shows also the temperatures behind the radiator in the case of 50 C. Like the 40 C case, the CFD temperatures are higher but not very different from each other. Also the temperatures are similar without the aluminium foil than with it. 41

42 T [ C] 40 T rad = 50 C Lab with Al CFD with Al Lab without Al CFD without Al y [cm] Fig.23: Comparison of the temperatures with T rad = 50 C This time the heat fluxes have a deviation of the same order as in the case of 40 C. Without Al With Al q Lab 15,60 10,38 q CFD 21,00 16,05 Deviation 34,62 54,63 Table 9: Deviation (%) in the heat flux with T rad = 50 C 42

43 D Validation In this part, it will be checked the 3D model. Due to not having enough time, it was only made one simulation with the 3D model. This one has a radiator temperature of 50 C, an external temperature of 20 C and a U value of 0,36 W/m 2 K. The case was without aluminium foil, so it will be compared to the case two in the table one. T [ C] Lab CFD Fig.24: Comparison of the temperatures y [cm] The temperatures, as it happened with the 2D model, are very similar the maximum error is 12%. In the next table the heat flux will be compared. q Lab q CFD Deviation 16,085 15,65 2,70 15,115 15,38 1,75 Table 9: Deviation (%) in the heat flux As the results show, the error has an acceptable value for both types of measurements. Therefore the 3D model can be validated. All the studied cases are in 2D since there was not enough time for do them all with 3D. The mesh for both cases was the same, therefore it is assumed that the 2D model is good for assemblies with wider radiators and windows as it will behave as a 2D model. 43

44 4.2.3 Savings Calculation As explained in the methodology part in the chapter three, the Q req and the Q rad can be plotted. These are seen in the figure 24 and 25. The cases shown are with and outdoor temperature of 20 C and a U value of 0,36 W/m 2 K. Q rad [W] y = 6,4764x 1,0648 R² = 0,9993 With Al Without Al y = 5,8948x 1,0664 R² = 0,9993 Power (With Al) Power (Without Al) T rad T i [ C] Fig.25: Power of the radiator Q req [W] y = 6,056x 1,0771 R² = 0,9994 y = 5,7719x 1,069 R² = 0,9993 With Al Without Al Power (With Al) Power (Without Al) T rad T i [ C] Fig.26: Heat requirement 44

45 The next table shows the savings in the case of outdoor temperature 20 C and a U value of 0,36 W/m 2 K. T rad Q rad Q radal Savings 30 75,67 73,89 2,36 % ,50 151,96 1,64 % ,88 241,66 1,32 % Table 10: Savings As it is shown in the table 10 the savings are approximately around 2%. This savings are not really high but it has to be considered that the thermal insulation was really good and a conclusion cannot be reached with only this results Comparison of the different cases In this part of the thesis, the comparison of the 54 different cases will be done. The data will be analysed considering the different values that the variables took. It will compare the savings for cases with a constant U value, a constant radiator temperature and a constant outdoor temperature. First, the savings will be analysed with a constant U value. The figure 27 shows the savings for the different U values. 45

46 % 4,5 U=0,36 4,0 3,5 3,0 2,5 2,0 1,5 Te= 20 Te= 10 Te=0 1,0 0,5 0, T rad [ C] % 4,5 4,0 3,5 3,0 2,5 2,0 1,5 1,0 0,5 0,0 U=0, T rad [ C] Te= 20 Te= 10 Te=0 % 4,5 4,0 3,5 3,0 2,5 2,0 1,5 1,0 0,5 0,0 U=0, T rad [ C] Te= 20 Te= 10 Te=0 46 Fig.27: Savings for different T e with constant U

47 As can be seen in the previous figure, with a constant U value, with a higher radiator temperature, the savings are smaller. This pattern is followed with all the different U values. This is because even though the radiator power with the aluminium foil it is reduced, it doesn t reduce as much as with the low temperatures. The tendency of the decrease is logarithmic. Regarding the outdoor temperature, it follows a different tendency with the every U value. With the lower U value, the higher savings are made with an external temperature of 10 C and the less savings are made with 20 C. With a U value of 0,48 W/m 2 K, the higher savings are made with an external temperature of 10 C meanwhile the lowest savings are made with 0 C. Finally with the lowest U value, it seems to follow what it would be expected. The highest savings are made with the lowest external temperature and the savings decrease gradually as the external temperature arises. The next figure shows the savings with a constant external temperature comparing them with the different radiator temperatures and U values. % 4,5 4,0 3,5 3,0 2,5 2,0 1,5 1,0 0,5 0,0 T e = 20 C U=0,36 U=0,48 U=0,62 T rad [ C] 47

48 % 4,5 4,0 3,5 3,0 2,5 2,0 1,5 1,0 0,5 0,0 T e = 10 C U=0,36 U=0,48 U=0,62 T rad [ C] % 4,5 4,0 3,5 3,0 2,5 2,0 1,5 1,0 0,5 0,0 T e = 0 C U=0,36 U=0,48 U=0,62 T rad [ C] Fig.28: Savings for different U with constant T e These graphs show, as it was seen with the ones with a U constant value, that with a higher radiator temperature the savings are lower. Again if it is compared with the different U values in every external temperature, they do not follow a pattern. With an outdoor temperature of 20 C, follows what would be thought as logical. With the poorest insulation, the savings are the highest and gradually decreasing as the insulation gets higher. Regarding the 10 C outdoors, the highest saving depends on the radiator temperature. With 30 C temperature, the highest savings are with the 48

49 richest insulation on meanwhile with 50 C the highest are with a U of 0,48 W/m 2 K. Lastly with 0 C, the highest savings are with the poorest insulation and the lowest with the intermediate insulation. These phenomena can be seen clearer in the figure 28. The following figure shows the savings with a constant radiator temperature. % T rad = 30 C 4,5 4,0 3,5 3,0 2,5 2,0 1,5 1,0 0,5 0, U=0,36 U=0,48 U=0,62 T e [ C] % T rad = 40 C 4,5 4,0 3,5 3,0 2,5 2,0 1,5 1,0 0,5 0, U=0,36 U=0,48 U=0,62 T e [ C] 49

50 % T rad = 50 C 4,5 4,0 3,5 3,0 2,5 2,0 1,5 1,0 0,5 0, U=0,36 U=0,48 U=0,62 T e [ C] Fig.29: Savings for different T e with constant T rad The last figure shows an unusual tendency that was not predicted. In one hand, the U values of 0,48 and 0,62 W/m 2 K follow a curve with a highest saving in the outdoor temperature of 10 C. On the other hand, the poorest insulation follows a decreasing tendency when the outdoor temperature gets higher. Comparing the results with the different radiator temperatures, as it gets higher the savings decrease but not in the same rate. With 30 C temperature, it predominates the highest insulation meanwhile with 50 C, it predominates the intermediate. This pattern suggests the there is an optimum with every condition. With only these results, it can be assured the reason of these happenings. This phenomenon can be associated with the fact of the combination of the radiation and convection. A study of this phenomenon can be seen in [13]. Also, it has to be mentioned that in reality not all the cases will be performed on a normal basis. For example with an outdoor temperature of 0 C, it is unlikely that the radiator temperature is 50 C. The savings in all the cases performed do not go higher than 4%. That result is not high but anyway it is a saving. It has to be considered that the area of the aluminium foil was really small compared to the whole room. In a regular home this area will increase so it will probably also increase the savings. 50

51 A recommendation for future works is to study the problem in CFD with a 3D model and investigate the reason for the tendencies seen in the cases studied in this thesis. Also make a study with a wider radiator and window in order to resemble the real heating systems used nowadays. 51

Department of Energy Science & Engineering, IIT Bombay, Mumbai, India. *Corresponding author: Tel: ,

Department of Energy Science & Engineering, IIT Bombay, Mumbai, India. *Corresponding author: Tel: , ICAER 2011 AN EXPERIMENTAL AND COMPUTATIONAL INVESTIGATION OF HEAT LOSSES FROM THE CAVITY RECEIVER USED IN LINEAR FRESNEL REFLECTOR SOLAR THERMAL SYSTEM Sudhansu S. Sahoo* a, Shinu M. Varghese b, Ashwin

More information

Building heat system sizing

Building heat system sizing May 6th, 203 MVK60 Heat and Mass Transfer Project report Building heat system sizing Arnaud BELTOISE Dept. of Energy Sciences, Faculty of Engineering, Lund University, Box 8, 2200 Lund, Sweden . Introduction

More information

The energy performance of an airflow window

The energy performance of an airflow window The energy performance of an airflow window B.(Bram) Kersten / id.nr. 0667606 University of Technology Eindhoven, department of Architecture Building and Planning, unit Building Physics and Systems. 10-08-2011

More information

5. AN INTRODUCTION TO BUILDING PHYSICS

5. AN INTRODUCTION TO BUILDING PHYSICS 5. AN INTRODUCTION TO BUILDING PHYSICS P. Wouters, S. Martin ABSTRACT This chapter places the System Identification Competition in a broader context of evaluating the thermal performances of building components.

More information

Analysis of the Cooling Design in Electrical Transformer

Analysis of the Cooling Design in Electrical Transformer Analysis of the Cooling Design in Electrical Transformer Joel de Almeida Mendes E-mail: joeldealmeidamendes@hotmail.com Abstract This work presents the application of a CFD code Fluent to simulate the

More information

Optimization of the Air Gap Spacing In a Solar Water Heater with Double Glass Cover

Optimization of the Air Gap Spacing In a Solar Water Heater with Double Glass Cover Optimization of the Air Gap Spacing In a Solar Water Heater with Double Glass Cover ABSTRACT M. AL-Khaffajy 1 and R. Mossad 2 Faculty of Engineering and Surveying, University of Southern Queensland, QLD

More information

Natural Convection Heat Loss from A Partly Open Cubic Enclosure Timothy N Anderson 1,a * and Stuart E Norris 2,b

Natural Convection Heat Loss from A Partly Open Cubic Enclosure Timothy N Anderson 1,a * and Stuart E Norris 2,b Natural Convection Heat Loss from A Partly Open Cubic Enclosure Timothy N Anderson 1,a * and Stuart E Norris 2,b 1 Auckland University of Technology, New Zealand 2 University of Auckland, New Zealand a

More information

International Journal of Scientific & Engineering Research, Volume 6, Issue 5, May ISSN

International Journal of Scientific & Engineering Research, Volume 6, Issue 5, May ISSN International Journal of Scientific & Engineering Research, Volume 6, Issue 5, May-2015 28 CFD BASED HEAT TRANSFER ANALYSIS OF SOLAR AIR HEATER DUCT PROVIDED WITH ARTIFICIAL ROUGHNESS Vivek Rao, Dr. Ajay

More information

NUMERICAL AND EXPERIMENTAL INVESTIGATIONS OF AIR FLOW AND TEMPERATURE PATTERNS OF A LOW VELOCITY DIFFUSER

NUMERICAL AND EXPERIMENTAL INVESTIGATIONS OF AIR FLOW AND TEMPERATURE PATTERNS OF A LOW VELOCITY DIFFUSER NUMERICAL AND EXPERIMENTAL INVESTIGATIONS OF AIR FLOW AND TEMPERATURE PATTERNS OF A LOW VELOCITY DIFFUSER M Cehlin and B Moshfegh Division of Energy and Mechanical Engineering, Department of Technology,

More information

CFD Analysis of High Temperature and High Velocity System: Plasma Torch

CFD Analysis of High Temperature and High Velocity System: Plasma Torch CFD Analysis of High Temperature and High Velocity System: Plasma Torch Abhishek Pratap Singh Bhadauria 1 1 Department of Mechanical Engineering, K. J. Somaiya College of Engineering, Mumbai, Maharashtra,

More information

CFD AND CONJUGATE HEAT TRANSFER ANALYSIS OF HEAT SINKS WITH DIFFERENT FIN GEOMETRIES SUBJECTED TO FORCED CONVECTION USED IN ELECTRONICS COOLING

CFD AND CONJUGATE HEAT TRANSFER ANALYSIS OF HEAT SINKS WITH DIFFERENT FIN GEOMETRIES SUBJECTED TO FORCED CONVECTION USED IN ELECTRONICS COOLING CFD AND CONJUGATE HEAT TRANSFER ANALYSIS OF HEAT SINKS WITH DIFFERENT FIN GEOMETRIES SUBJECTED TO FORCED CONVECTION USED IN ELECTRONICS COOLING V. M Kulkarni 1, Basavaraj Dotihal 2 1 Professor, Thermal

More information

COMPUTATIONAL SIMULATION OF THE FLOW PAST AN AIRFOIL FOR AN UNMANNED AERIAL VEHICLE

COMPUTATIONAL SIMULATION OF THE FLOW PAST AN AIRFOIL FOR AN UNMANNED AERIAL VEHICLE COMPUTATIONAL SIMULATION OF THE FLOW PAST AN AIRFOIL FOR AN UNMANNED AERIAL VEHICLE L. Velázquez-Araque 1 and J. Nožička 2 1 Division of Thermal fluids, Department of Mechanical Engineering, National University

More information

VALIDATION OF REYNOLDS AVERAGED MODEL AND LARGE EDDY SIMULATION IN ACTUAL FLOOR HEATING ROOM. Hiroki Ono 1 and Koji Sakai 1

VALIDATION OF REYNOLDS AVERAGED MODEL AND LARGE EDDY SIMULATION IN ACTUAL FLOOR HEATING ROOM. Hiroki Ono 1 and Koji Sakai 1 Proceedings of Building Simulation 11: VALDATON OF RYNOLDS AVRAD MODL AND LAR DDY SMULATON N ACTUAL FLOOR HATN ROOM Hiroki Ono 1 and Koji Sakai 1 1 School of Science and Technology, Meiji University, Kawasaki,

More information

A Numerical Analysis of Indoor Thermal Environment and Human Thermophysiological Responses under Natural Ventilation S. Iizuka 1,*, T. Sakoi 2, T. Sai

A Numerical Analysis of Indoor Thermal Environment and Human Thermophysiological Responses under Natural Ventilation S. Iizuka 1,*, T. Sakoi 2, T. Sai A Numerical Analysis of Indoor Thermal Environment and Human Thermophysiological Responses under Natural Ventilation S. Iizuka 1,*, T. Sakoi 2, T. Saito 1, and S. Kuno 1 1 Graduate School of Environmental

More information

Numerical Investigation of Convective Heat Transfer in Pin Fin Type Heat Sink used for Led Application by using CFD

Numerical Investigation of Convective Heat Transfer in Pin Fin Type Heat Sink used for Led Application by using CFD GRD Journals- Global Research and Development Journal for Engineering Volume 1 Issue 8 July 2016 ISSN: 2455-5703 Numerical Investigation of Convective Heat Transfer in Pin Fin Type Heat Sink used for Led

More information

International Journal of Engineering Research and General Science Volume 3, Issue 6, November-December, 2015 ISSN

International Journal of Engineering Research and General Science Volume 3, Issue 6, November-December, 2015 ISSN NUMERICAL AND EXPERIMENTAL INVESTIGATION OF STAGGERED INTERRUPTED FIN ARRANGEMENT IN A NATURAL CONVECTION FIELD Mr.Bhushan S Rane 1, Prof. M D Shende 2 1 (P G Student, Department of Mechanical Engineering,

More information

Comparison of two equations closure turbulence models for the prediction of heat and mass transfer in a mechanically ventilated enclosure

Comparison of two equations closure turbulence models for the prediction of heat and mass transfer in a mechanically ventilated enclosure Proceedings of 4 th ICCHMT May 17-0, 005, Paris-Cachan, FRANCE 381 Comparison of two equations closure turbulence models for the prediction of heat and mass transfer in a mechanically ventilated enclosure

More information

Influence of Heat Transfer Process in Porous Media with Air Cavity- A CFD Analysis

Influence of Heat Transfer Process in Porous Media with Air Cavity- A CFD Analysis Proceedings of the 4 th International Conference of Fluid Flow, Heat and Mass Transfer (FFHMT'17) Toronto, Canada August 21 23, 2017 Paper No. 161 DOI: 10.11159/ffhmt17.161 Influence of Heat Transfer Process

More information

A CFD Analysis Of A Solar Air Heater Having Triangular Rib Roughness On The Absorber Plate

A CFD Analysis Of A Solar Air Heater Having Triangular Rib Roughness On The Absorber Plate International Journal of ChemTech Research CODEN( USA): IJCRGG ISSN : 0974-4290 Vol.5, No.2, pp 964-971, April-June 2013 ICGSEE-2013[14th 16th March 2013] International Conference on Global Scenario in

More information

Aalborg Universitet. Publication date: Document Version Publisher's PDF, also known as Version of record

Aalborg Universitet. Publication date: Document Version Publisher's PDF, also known as Version of record Aalborg Universitet Experimental Investigation of the Influence of Different Flooring Emissivity on Night- Time Cooling using Displacement Ventilation Dreau, Jerome Le; Karlsen, Line Røseth; Litewnicki,

More information

CHAPTER 7 NUMERICAL MODELLING OF A SPIRAL HEAT EXCHANGER USING CFD TECHNIQUE

CHAPTER 7 NUMERICAL MODELLING OF A SPIRAL HEAT EXCHANGER USING CFD TECHNIQUE CHAPTER 7 NUMERICAL MODELLING OF A SPIRAL HEAT EXCHANGER USING CFD TECHNIQUE In this chapter, the governing equations for the proposed numerical model with discretisation methods are presented. Spiral

More information

CAE 331/513 Building Science Fall 2016

CAE 331/513 Building Science Fall 2016 CAE 331/513 Building Science Fall 2016 Week 3: September 8, 2016 Heat transfer in buildings: Finish radiation, then solar radiation and windows Advancing energy, environmental, and sustainability research

More information

EVALUATION OF THERMAL ENVIRONMENT AROUND THE BLIND ON NON-UNIFOM RADIANT FIELDS A CFD SIMULATION OF HEAT TRANSFER DISTRIBUTION NEAR THE BLINDS

EVALUATION OF THERMAL ENVIRONMENT AROUND THE BLIND ON NON-UNIFOM RADIANT FIELDS A CFD SIMULATION OF HEAT TRANSFER DISTRIBUTION NEAR THE BLINDS 800 1500 6240 1600 1500 840 Proceedings of BS2015: EVALUATION OF THERMAL ENVIRONMENT AROUND THE BLIND ON NON-UNIFOM RADIANT FIELDS A CFD SIMULATION OF HEAT TRANSFER DISTRIBUTION NEAR THE BLINDS Nozomi

More information

THE EFFECTS OF CALORIMETER TILT ON THE INWARD-FLOWING FRACTION OF ABSORBED SOLAR RADIATION IN A VENETIAN BLIND

THE EFFECTS OF CALORIMETER TILT ON THE INWARD-FLOWING FRACTION OF ABSORBED SOLAR RADIATION IN A VENETIAN BLIND Collins, M.R., and Harrison, S.J., "The Effects of Calorimeter Tilt on the Inward-Flowing Fraction of Absorbed Solar Radiation in a Venetian Blind", ASHRAE Transactions, Vol. 107 (1), pp. 677-683, 2001.

More information

midas NFX 2015 R1 Release Note

midas NFX 2015 R1 Release Note Total Solution for True Analysis-driven Design midas NFX 2015 R1 Release Note 1 midas NFX R E L E A S E N O T E 2 0 1 5 R 1 Accurate whenever you Need Be more efficient by focusing on the right details

More information

Modelling and Experimental Validation Possibilities of Heat Transfer Room Model

Modelling and Experimental Validation Possibilities of Heat Transfer Room Model Excerpt from the Proceedings of the COMSOL Conference 2010 Paris Modelling and Experimental Validation Possibilities of Heat Transfer Room Model Author M. Zalesak 1, Author V. Gerlich *,1 1 Author Tomas

More information

METHOD OF IN-SITU MEASUREMENT OF THERMAL INSULATION PERFORMANCE OF BUILDING ELEMENTS USING INFRARED CAMERA

METHOD OF IN-SITU MEASUREMENT OF THERMAL INSULATION PERFORMANCE OF BUILDING ELEMENTS USING INFRARED CAMERA METHOD OF IN-SITU MEASUREMENT OF THERMAL INSULATION PERFORMANCE OF BUILDING ELEMENTS USING INFRARED CAMERA Shinsuke Kato 1, Katsuichi Kuroki 2, and Shinji Hagihara 2 1 Institute of Industrial Science,

More information

EE-489 Modeling Project: Behavior of the. Temperature Changes in a Room

EE-489 Modeling Project: Behavior of the. Temperature Changes in a Room EE-489 Modeling Project: Behavior of the 1 Temperature Changes in a Room Younes Sangsefidi, Saleh Ziaieinejad, Tarik Wahidi, and Takouda Pidename, Abstract A precise heat flow model, which predicts the

More information

Principles of Convection

Principles of Convection Principles of Convection Point Conduction & convection are similar both require the presence of a material medium. But convection requires the presence of fluid motion. Heat transfer through the: Solid

More information

DEVELOPMENT OF CFD MODEL FOR A SWIRL STABILIZED SPRAY COMBUSTOR

DEVELOPMENT OF CFD MODEL FOR A SWIRL STABILIZED SPRAY COMBUSTOR DRAFT Proceedings of ASME IMECE: International Mechanical Engineering Conference & Exposition Chicago, Illinois Nov. 5-10, 2006 IMECE2006-14867 DEVELOPMENT OF CFD MODEL FOR A SWIRL STABILIZED SPRAY COMBUSTOR

More information

of the heat is dissipated as a result of the flow of electrical current in various conductors. In order to predict temperatures

of the heat is dissipated as a result of the flow of electrical current in various conductors. In order to predict temperatures Transient Coupled Thermal / Electrical Analysis of a Printed Wiring Board Ben Zandi TES International: (248 362-29 bzandi@tesint.com Jeffrey Lewis TES International Hamish Lewis TES International Abstract

More information

STUDY OF A PASSIVE SOLAR WINTER HEATING SYSTEM BASED ON TROMBE WALL

STUDY OF A PASSIVE SOLAR WINTER HEATING SYSTEM BASED ON TROMBE WALL STUDY OF A PASSIVE SOLAR WINTER HEATING SYSTEM BASED ON TROMBE WALL Dr. G.S.V.L.Narasimham Chief Research Scientist, RAC, Dept. of Mechanical Engineering, Indian Institute of Science,Bengaluru- 560012,

More information

THERMAL PERFORMANCE EVALUATION OF AN INNOVATIVE DOUBLE GLAZING WINDOW

THERMAL PERFORMANCE EVALUATION OF AN INNOVATIVE DOUBLE GLAZING WINDOW THERMAL PERFORMANCE EVALUATION OF AN INNOVATIVE DOUBLE GLAZING WINDOW Luigi De Giorgi, Carlo Cima, Emilio Cafaro Dipartimento di Energetica, Politecnico di Torino, Torino, Italy Volfango Bertola School

More information

Theoretical Study of Forced Convective Heat Transfer in Hexagonal Configuration with 7Rod Bundles Using Zirconia-water Nanofluid

Theoretical Study of Forced Convective Heat Transfer in Hexagonal Configuration with 7Rod Bundles Using Zirconia-water Nanofluid Theoretical Study of Forced Convective Heat Transfer in Hexagonal Configuration with 7Rod Bundles Using Zirconia-water Nanofluid Mojtaba Maktabifard1, a*, Nathanael P. Tian1, b 1 Faculty of Mechanical

More information

HFM 100 Series. Thermal Conductivity Meter for measurement of insulation and construction materials.

HFM 100 Series. Thermal Conductivity Meter for measurement of insulation and construction materials. HFM 100 Series Conforms to International Standards ASTM C518, ISO 8301, and EN 12667 Thermal Conductivity Meter for measurement of insulation and construction materials. Hot Disk TPS -160 to 1000 C HFM

More information

Increasing Energy Efficiency of HVAC Systems in Buildings Using Phase Change Material

Increasing Energy Efficiency of HVAC Systems in Buildings Using Phase Change Material Washington University in St. Louis Washington University Open Scholarship All Theses and Dissertations (ETDs) January 2011 Increasing Energy Efficiency of HVAC Systems in Buildings Using Phase Change Material

More information

C ONTENTS CHAPTER TWO HEAT CONDUCTION EQUATION 61 CHAPTER ONE BASICS OF HEAT TRANSFER 1 CHAPTER THREE STEADY HEAT CONDUCTION 127

C ONTENTS CHAPTER TWO HEAT CONDUCTION EQUATION 61 CHAPTER ONE BASICS OF HEAT TRANSFER 1 CHAPTER THREE STEADY HEAT CONDUCTION 127 C ONTENTS Preface xviii Nomenclature xxvi CHAPTER ONE BASICS OF HEAT TRANSFER 1 1-1 Thermodynamics and Heat Transfer 2 Application Areas of Heat Transfer 3 Historical Background 3 1-2 Engineering Heat

More information

Transient Analysis of the Buoyancy Driven Flow in a Passive Solar System for Indoor Heating

Transient Analysis of the Buoyancy Driven Flow in a Passive Solar System for Indoor Heating Excerpt from the Proceedings of the COMSOL Conference 2010 Paris Transient Analysis of the Buoyancy Driven Flow in a Passive Solar System for Indoor Heating Cammarata G., Petrone G. *, Cammarata L. Department

More information

ECONOMIC AND ENERGETIC ASPECTS TO CONSIDER IN WINDOW RENOVATION ALTERNATIVES A case study in a cold climate

ECONOMIC AND ENERGETIC ASPECTS TO CONSIDER IN WINDOW RENOVATION ALTERNATIVES A case study in a cold climate FACULTY OF ENGINEERING AND SUSTAINABLE DEVELOPMENT Department of Building, Energy and Environmental Engineering ECONOMIC AND ENERGETIC ASPECTS TO CONSIDER IN WINDOW RENOVATION ALTERNATIVES A case study

More information

Experiment 1. Measurement of Thermal Conductivity of a Metal (Brass) Bar

Experiment 1. Measurement of Thermal Conductivity of a Metal (Brass) Bar Experiment 1 Measurement of Thermal Conductivity of a Metal (Brass) Bar Introduction: Thermal conductivity is a measure of the ability of a substance to conduct heat, determined by the rate of heat flow

More information

Conjugate heat transfer from an electronic module package cooled by air in a rectangular duct

Conjugate heat transfer from an electronic module package cooled by air in a rectangular duct Conjugate heat transfer from an electronic module package cooled by air in a rectangular duct Hideo Yoshino a, Motoo Fujii b, Xing Zhang b, Takuji Takeuchi a, and Souichi Toyomasu a a) Fujitsu Kyushu System

More information

Energy and Buildings

Energy and Buildings Energy and Buildings 42 (2010) 1753 1758 Contents lists available at ScienceDirect Energy and Buildings journal homepage: www.elsevier.com/locate/enbuild A calculation method for the floor surface temperature

More information

CFD study for cross flow heat exchanger with integral finned tube

CFD study for cross flow heat exchanger with integral finned tube International Journal of Scientific and Research Publications, Volume 6, Issue 6, June 2016 668 CFD study for cross flow heat exchanger with integral finned tube Zena K. Kadhim *, Muna S. Kassim **, Adel

More information

EXTENDED REYNOLDS ANALOGY FOR DIFFERENT FLOW CONDITIONS OF THE HEATED PLATE 83

EXTENDED REYNOLDS ANALOGY FOR DIFFERENT FLOW CONDITIONS OF THE HEATED PLATE 83 EXTENDED REYNOLDS ANALOGY FOR DIFFERENT FLOW CONDITIONS OF THE HEATED PLATE Zygmunt Institute of Fluid-Flow Machinery, University of Warmia and Mazury Maciej KAISER Institute of Aviation Jacek Institute

More information

THERMAL TRANSMITTANCE OF MULTI-LAYER GLAZING WITH ULTRATHIN INTERNAL PARTITIONS. Agnieszka A. Lechowska 1, Jacek A. Schnotale 1

THERMAL TRANSMITTANCE OF MULTI-LAYER GLAZING WITH ULTRATHIN INTERNAL PARTITIONS. Agnieszka A. Lechowska 1, Jacek A. Schnotale 1 THERMAL TRANSMITTANCE OF MULTI-LAYER GLAZING WITH ULTRATHIN INTERNAL PARTITIONS Agnieszka A. Lechowska 1, Jacek A. Schnotale 1 1 Cracow University of Technology, Department of Environmental Engineering,

More information

COMPUTATIONAL ANALYSIS OF LAMINAR FORCED CONVECTION IN RECTANGULAR ENCLOSURES OF DIFFERENT ASPECT RATIOS

COMPUTATIONAL ANALYSIS OF LAMINAR FORCED CONVECTION IN RECTANGULAR ENCLOSURES OF DIFFERENT ASPECT RATIOS HEFAT214 1 th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics 14 16 July 214 Orlando, Florida COMPUTATIONAL ANALYSIS OF LAMINAR FORCED CONVECTION IN RECTANGULAR ENCLOSURES

More information

TREES Training for Renovated Energy Efficient Social housing

TREES Training for Renovated Energy Efficient Social housing TREES Training for Renovated Energy Efficient Social housing Intelligent Energy -Europe programme, contract n EIE/05/110/SI2.420021 Section 2 Tools 2.1 Simplified heating load calculation Tamas CSOKNYAI

More information

FUNDAMENTALS OF HVAC

FUNDAMENTALS OF HVAC FUNDAMENTALS OF HVAC Prof.Dr. Yusuf Ali KARA Res.Asst. Semih AKIN 1 INTRODUCTION Terminology: HVAC: Heating, ventilating, air-conditioning and refrigerating. Air conditioning is the process of treating

More information

CFD-SIMULATIONS OF TRANSPARENT COATED AND GAS-FILLED FACADE PANELS

CFD-SIMULATIONS OF TRANSPARENT COATED AND GAS-FILLED FACADE PANELS Ninth International IBPSA Conference Montréal, Canada August 15-18, 2005 CFD-SIMULATIONS OF TRANSPARENT COATED AND GAS-FILLED FACADE PANELS R.M.J. Bokel 1, B.H.G. Peters 1,2, and M. van der Voorden 1 1

More information

Natural convection heat transfer around a horizontal circular cylinder near an isothermal vertical wall

Natural convection heat transfer around a horizontal circular cylinder near an isothermal vertical wall Natural convection heat transfer around a horizontal circular cylinder near an isothermal vertical wall Marcel Novomestský 1, Richard Lenhard 1, and Ján Siažik 1 1 University of Žilina, Faculty of Mechanical

More information

3D Simulation of the Plunger Cooling during the Hollow Glass Forming Process Model, Validation and Results

3D Simulation of the Plunger Cooling during the Hollow Glass Forming Process Model, Validation and Results Thomas Bewer, Cham, CH 3D Simulation of the Plunger Cooling during the Hollow Glass Forming Process Model, Validation and Results A steady state model to describe the flow and temperature distribution

More information

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur Lecture - 9 Transmission Line Steady State Operation Welcome to lesson 9, in Power

More information

Numerical Simulation and Air Conditioning System Improvement for the Experimental Hall at TLS J.C. Chang a, M.T. Ke b, Z.D. Tsai a, and J. R.

Numerical Simulation and Air Conditioning System Improvement for the Experimental Hall at TLS J.C. Chang a, M.T. Ke b, Z.D. Tsai a, and J. R. Numerical Simulation and Air Conditioning System Improvement for the Experimental Hall at TLS J.C. Chang a, M.T. Ke b, Z.D. Tsai a, and J. R. Chen a a National Synchrotron Radiation Research Center (NSRRC)

More information

CFD as a Tool for Thermal Comfort Assessment

CFD as a Tool for Thermal Comfort Assessment CFD as a Tool for Thermal Comfort Assessment Dimitrios Koubogiannis dkoubog@teiath.gr G. Tsimperoudis, E. Karvelas Department of Energy Technology Engineering Technological Educational Institute of Athens

More information

Thermal Systems. What and How? Physical Mechanisms and Rate Equations Conservation of Energy Requirement Control Volume Surface Energy Balance

Thermal Systems. What and How? Physical Mechanisms and Rate Equations Conservation of Energy Requirement Control Volume Surface Energy Balance Introduction to Heat Transfer What and How? Physical Mechanisms and Rate Equations Conservation of Energy Requirement Control Volume Surface Energy Balance Thermal Resistance Thermal Capacitance Thermal

More information

Memory Thermal Management 101

Memory Thermal Management 101 Memory Thermal Management 101 Overview With the continuing industry trends towards smaller, faster, and higher power memories, thermal management is becoming increasingly important. Not only are device

More information

Building Envelope Requirements Overview Page 3-4

Building Envelope Requirements Overview Page 3-4 Building Envelope Requirements Overview Page 3-4 The benefit of a high reflectance surface is obvious: while dark surfaces absorb the sun s energy (visible light, invisible infrared. and ultraviolet radiation)

More information

ADVANCED ROOF COATINGS: MATERIALS AND THEIR APPLICATIONS

ADVANCED ROOF COATINGS: MATERIALS AND THEIR APPLICATIONS ADVANCED ROOF COATINGS: MATERIALS AND THEIR APPLICATIONS Abstract J.M. Bell 1 and G.B. Smith 2 The use of low emittance and high solar reflectance coatings is widespread in window glazings, wall and roof

More information

Simulation of Free Convection with Conjugate Heat Transfer

Simulation of Free Convection with Conjugate Heat Transfer Simulation of Free Convection with Conjugate Heat Transfer Hong Xu, Chokri Guetari, Kurt Svihla ANSYS, Inc. Abstract This study focuses on free convective and conjugate heat transfer in a naturally ventilated,

More information

MODA. Modelling data documenting one simulation. NewSOL energy storage tank

MODA. Modelling data documenting one simulation. NewSOL energy storage tank MODA Modelling data documenting one simulation NewSOL energy storage tank Metadata for these elements are to be elaborated over time Purpose of this document: Definition of a data organisation that is

More information

Thermal mass vs. thermal response factors: determining optimal geometrical properties and envelope assemblies of building materials

Thermal mass vs. thermal response factors: determining optimal geometrical properties and envelope assemblies of building materials International Conference Passive and Low Energy Cooling 345 Thermal mass vs. thermal response factors: determining optimal geometrical properties and envelope assemblies of building materials K.J. Kontoleon

More information

SIMULATION OF FRAME CAVITY HEAT TRANSFER USING BISCO v10w

SIMULATION OF FRAME CAVITY HEAT TRANSFER USING BISCO v10w PHYSIBEL SIMULATION OF FRAME CAVITY HEAT TRANSFER USING BISCO v10w Introduction In construction elements such as window frames and bricks, the heat transfer through air cavities is often a quite important

More information

Laminar flow heat transfer studies in a twisted square duct for constant wall heat flux boundary condition

Laminar flow heat transfer studies in a twisted square duct for constant wall heat flux boundary condition Sādhanā Vol. 40, Part 2, April 2015, pp. 467 485. c Indian Academy of Sciences Laminar flow heat transfer studies in a twisted square duct for constant wall heat flux boundary condition RAMBIR BHADOURIYA,

More information

Finite Element Analysis of the Heat Transfer in a Copper Mould during Continuous Casting of Steel Slabs. 14 May 2005

Finite Element Analysis of the Heat Transfer in a Copper Mould during Continuous Casting of Steel Slabs. 14 May 2005 Finite Element Analysis of the Heat Transfer in a Copper Mould during Continuous Casting of Steel Slabs 14 May 2005 D. Hodgson, Sami Vapalahti, and B.G. Thomas Department of Mechanical and Industrial Engineering

More information

NUMERICAL AND EXPERIMENTAL INVESTIGATION OF THE TEMPERATURE DISTRIBUTION INSIDE OIL-COOLED TRANSFORMER WINDINGS

NUMERICAL AND EXPERIMENTAL INVESTIGATION OF THE TEMPERATURE DISTRIBUTION INSIDE OIL-COOLED TRANSFORMER WINDINGS NUMERICAL AND EXPERIMENTAL INVESTIGATION OF THE TEMPERATURE DISTRIBUTION INSIDE OIL-COOLED TRANSFORMER WINDINGS N. Schmidt 1* and S. Tenbohlen 1 and S. Chen 2 and C. Breuer 3 1 University of Stuttgart,

More information

CFD MODELLING OF CONVECTIVE HEAT TRANSFER FROM A WINDOW WITH ADJACENT VENETIAN BLINDS

CFD MODELLING OF CONVECTIVE HEAT TRANSFER FROM A WINDOW WITH ADJACENT VENETIAN BLINDS Ninth International IBPSA Conference Montréal, Canada August 15-18, 2005 CFD MODELLING OF CONVECTIVE HEAT TRANSFER FROM A WINDOW WITH ADJACENT VENETIAN BLINDS Ljiljana Marjanovic 1,2, Malcom Cook 2, Vic

More information

A Discussion of Low Reynolds Number Flow for the Two-Dimensional Benchmark Test Case

A Discussion of Low Reynolds Number Flow for the Two-Dimensional Benchmark Test Case A Discussion of Low Reynolds Number Flow for the Two-Dimensional Benchmark Test Case M. Weng, P. V. Nielsen and L. Liu Aalborg University Introduction. The use of CFD in ventilation research has arrived

More information

Modelling conjugate flow and heat transfer in a ventilated room for indoor

Modelling conjugate flow and heat transfer in a ventilated room for indoor Modelling conjugate flow and heat transfer in a ventilated room for indoor thermal comfort assessment Kana Horikiri 1, Yufeng Yao 2, *, Jun Yao 3 1 Faculty of Science, Engineering and Computing, Kingston

More information

Design strategy for Low e windows with effective insulation

Design strategy for Low e windows with effective insulation Design strategy for Low e windows with effective insulation Michael P.C. Watts, Impattern Solutions, www.impattern.com Keywords; insulating windows. low emission glass, ABSTRACT Optimal window glass assemblies

More information

Numerical investigation to study effect of radiation on thermal performance of radiator for onan cooling configuration of transformer

Numerical investigation to study effect of radiation on thermal performance of radiator for onan cooling configuration of transformer IOP Conference Series: Materials Science and Engineering PAPER OPEN ACCESS Numerical investigation to study effect of radiation on thermal performance of radiator for onan cooling configuration of transformer

More information

the distance of conduction (the thickness), the greater the heat flow.

the distance of conduction (the thickness), the greater the heat flow. R-Values In heat conduction, the rate of heat flow depends on the temperature difference between sides, the thickness, and the area in contact. The greater the temperature difference, the greater the heat

More information

Lecture 22. Temperature and Heat

Lecture 22. Temperature and Heat Lecture 22 Temperature and Heat Today s Topics: 0 th Law of Thermodynamics Temperature Scales Thermometers Thermal Expansion Heat, Internal Energy and Work Heat Transfer Temperature and the Zeroth Law

More information

EFFECT OF DISTRIBUTION OF VOLUMETRIC HEAT GENERATION ON MODERATOR TEMPERATURE DISTRIBUTION

EFFECT OF DISTRIBUTION OF VOLUMETRIC HEAT GENERATION ON MODERATOR TEMPERATURE DISTRIBUTION EFFECT OF DISTRIBUTION OF VOLUMETRIC HEAT GENERATION ON MODERATOR TEMPERATURE DISTRIBUTION A. K. Kansal, P. Suryanarayana, N. K. Maheshwari Reactor Engineering Division, Bhabha Atomic Research Centre,

More information

Extensions to the Finite Element Technique for the Magneto-Thermal Analysis of Aged Oil Cooled-Insulated Power Transformers

Extensions to the Finite Element Technique for the Magneto-Thermal Analysis of Aged Oil Cooled-Insulated Power Transformers Journal of Electromagnetic Analysis and Applications, 2012, 4, 167-176 http://dx.doi.org/10.4236/jemaa.2012.44022 Published Online April 2012 (http://www.scirp.org/journal/jemaa) 167 Extensions to the

More information

Unit 11: Temperature and heat

Unit 11: Temperature and heat Unit 11: Temperature and heat 1. Thermal energy 2. Temperature 3. Heat and thermal equlibrium 4. Effects of heat 5. Transference of heat 6. Conductors and insulators Think and answer a. Is it the same

More information

Semiconductor Thermal Resistance Standards versus Real Life. Bernie Siegal Thermal Engineering Associates, Inc.

Semiconductor Thermal Resistance Standards versus Real Life. Bernie Siegal Thermal Engineering Associates, Inc. Semiconductor Thermal Resistance Standards versus Real Life Bernie Siegal Thermal Engineering Associates, Inc. bsiegal@thermengr.com Overview Introduction Objective Temperature vs. Thermal Current Standard

More information

Performance Assessment of PV/T Air Collector by Using CFD

Performance Assessment of PV/T Air Collector by Using CFD Performance Assessment of /T Air Collector by Using CFD Wang, Z. Department of Built Environment, University of Nottingham (email: laxzw4@nottingham.ac.uk) Abstract Photovoltaic-thermal (/T) collector,

More information

Thermo-Hydraulic performance of Internal finned tube Automobile Radiator

Thermo-Hydraulic performance of Internal finned tube Automobile Radiator Thermo-Hydraulic performance of Internal finned tube Automobile Radiator Dr.Kailash Mohapatra 1, Deepiarani Swain 2 1 Department of Mechanical Engineering, Raajdhani Engineering College, Bhubaneswar, 751017,

More information

ME 4/549 Lab Assignment 5: Single Block Experiment Spring 2006 due 1 June 2006

ME 4/549 Lab Assignment 5: Single Block Experiment Spring 2006 due 1 June 2006 ME 4/549 Lab Assignment 5: Single Block Experiment Spring 2006 due 1 June 2006 version May 23, 2006 1 Objective The objective of the laboratory exercise is to measure the convective heat transfer coefficient

More information

INTERNATIONAL JOURNAL OF SCIENTIFIC & TECHNOLOGY RESEARCH VOLUME 5, ISSUE 09, SEPTEMBER 2016 ISSN

INTERNATIONAL JOURNAL OF SCIENTIFIC & TECHNOLOGY RESEARCH VOLUME 5, ISSUE 09, SEPTEMBER 2016 ISSN Numerical Analysis Of Heat Transfer And Fluid Flow Characteristics In Different V-Shaped Roughness Elements On The Absorber Plate Of Solar Air Heater Duct Jitesh Rana, Anshuman Silori, Rohan Ramola Abstract:

More information

Table of Contents. Foreword... xiii. Preface... xv

Table of Contents. Foreword... xiii. Preface... xv Table of Contents Foreword.... xiii Preface... xv Chapter 1. Fundamental Equations, Dimensionless Numbers... 1 1.1. Fundamental equations... 1 1.1.1. Local equations... 1 1.1.2. Integral conservation equations...

More information

Thermodynamics I Spring 1432/1433H (2011/2012H) Saturday, Wednesday 8:00am - 10:00am & Monday 8:00am - 9:00am MEP 261 Class ZA

Thermodynamics I Spring 1432/1433H (2011/2012H) Saturday, Wednesday 8:00am - 10:00am & Monday 8:00am - 9:00am MEP 261 Class ZA Thermodynamics I Spring 1432/1433H (2011/2012H) Saturday, Wednesday 8:00am - 10:00am & Monday 8:00am - 9:00am MEP 261 Class ZA Dr. Walid A. Aissa Associate Professor, Mech. Engg. Dept. Faculty of Engineering

More information

Simulation and improvement of the ventilation of a welding workshop using a Finite volume scheme code

Simulation and improvement of the ventilation of a welding workshop using a Finite volume scheme code 1 st. Annual (National) Conference on Industrial Ventilation-IVC2010 Feb 24-25, 2010, Sharif University of Technology, Tehran, Iran IVC2010 Simulation and improvement of the ventilation of a welding workshop

More information

Heat Transfer Studies on Structured Metal Sheets

Heat Transfer Studies on Structured Metal Sheets KMUTNB Int J Appl Sci Technol, Vol. 9, No., pp. 189 196, 2016 Research Article Heat Transfer Studies on Structured Metal Sheets Josef Egert* and Karel Fraňa Department of Power Engineering Equipment, Faculty

More information

Experimental Verification of CFD Modeling of Turbulent Flow over Circular Cavities using FLUENT

Experimental Verification of CFD Modeling of Turbulent Flow over Circular Cavities using FLUENT Experimental Verification of CFD Modeling of Turbulent Flow over Circular Cavities using FLUENT T Hering, J Dybenko, E Savory Mech. & Material Engineering Dept., University of Western Ontario, London,

More information

Experimental Study of Heat Transfer Enhancement in a Tilted Semi-Cylindrical Cavity with Triangular Type of Vortex Generator in Various Arrangements.

Experimental Study of Heat Transfer Enhancement in a Tilted Semi-Cylindrical Cavity with Triangular Type of Vortex Generator in Various Arrangements. Experimental Study of Heat Transfer Enhancement in a Tilted Semi-Cylindrical Cavity with Triangular Type of Vortex Generator in Various Arrangements. #1 Korake Supriya S, #2 Dr Borse Sachin L #1 P.G. Student,

More information

CFD Analysis of the Effect of Material Properties of Nose Cone on the Heat Flux and Thermal Field during Re-entry of Space Vehicle

CFD Analysis of the Effect of Material Properties of Nose Cone on the Heat Flux and Thermal Field during Re-entry of Space Vehicle CFD Analysis of the Effect of Material Properties of Nose Cone on the Heat Flux and Thermal Field during Re-entry of Space Vehicle [1] K.V.Sreenivas Rao, [2] Sujan.P, [3] Sachin H.S [1] Professor, [2][3]

More information

COMPUTATIONAL FLUID DYNAMICS (CFD) FOR THE OPTIMIZATION OF PRODUCTS AND PROCESSES

COMPUTATIONAL FLUID DYNAMICS (CFD) FOR THE OPTIMIZATION OF PRODUCTS AND PROCESSES THE INTERNATIONAL CONFERENCE OF THE CARPATHIAN EURO-REGION SPECIALISTS IN INDUSTRIAL SYSTEMS 7 th EDITION COMPUTATIONAL FLUID DYNAMICS (CFD) FOR THE OPTIMIZATION OF PRODUCTS AND PROCESSES Franz, Haas DI

More information

NUMERICAL MODELLING OF TEMPERATURE AND AIR FLOW DISTRIBUTION IN ENCLOSED ROOM

NUMERICAL MODELLING OF TEMPERATURE AND AIR FLOW DISTRIBUTION IN ENCLOSED ROOM NUMERICAL MODELLING OF TEMPERATURE AND AIR FLOW DISTRIBUTION IN ENCLOSED ROOM Igor Bonefacic 1, Bernard Frankovic 2, Ivan Vilicic 3, Vladimir Glazar 4 Faculty of Engineering, Vukovarska 58, Rijeka, Croatia,

More information

STUDY ON THE THERMAL PERFORMANCE AND AIR DISTRIBUTION OF A DISPLACEMENT VENTILATION SYSTEM FOR LARGE SPACE APPLICATION

STUDY ON THE THERMAL PERFORMANCE AND AIR DISTRIBUTION OF A DISPLACEMENT VENTILATION SYSTEM FOR LARGE SPACE APPLICATION STUDY ON THE THERMAL PERFORMANCE AND AIR DISTRIBUTION OF A DISPLACEMENT VENTILATION SYSTEM FOR LARGE SPACE APPLICATION K Sakai 1*, E Yamaguchi 2, O Ishihara 3 and M Manabe 1 1 Dept. of Architectural Engineering,

More information

AN IMPACT OF AIR INFILTRATION ON HEAT TRANSFER THROUGH LIGHTWEIGHT BUILDING PARTITIONS FILLED WITH LOOSE MINERAL WOOL PHD THESIS ABSTRACT

AN IMPACT OF AIR INFILTRATION ON HEAT TRANSFER THROUGH LIGHTWEIGHT BUILDING PARTITIONS FILLED WITH LOOSE MINERAL WOOL PHD THESIS ABSTRACT Białystok University of Technology Faculty of Civil and Environmental Engineering AN IMPACT OF AIR INFILTRATION ON HEAT TRANSFER THROUGH LIGHTWEIGHT BUILDING PARTITIONS FILLED WITH LOOSE MINERAL WOOL PHD

More information

Using Excel to Implement the Finite Difference Method for 2-D Heat Transfer in a Mechanical Engineering Technology Course

Using Excel to Implement the Finite Difference Method for 2-D Heat Transfer in a Mechanical Engineering Technology Course Paper ID #9196 Using Excel to Implement the Finite Difference Method for -D Heat ransfer in a Mechanical Engineering echnology Course Mr. Robert Edwards, Pennsylvania State University, Erie Bob Edwards

More information

Today we begin the first technical topic related directly to the course that is: Equilibrium Carrier Concentration.

Today we begin the first technical topic related directly to the course that is: Equilibrium Carrier Concentration. Solid State Devices Dr. S. Karmalkar Department of Electronics and Communication Engineering Indian Institute of Technology, Madras Lecture - 3 Equilibrium and Carrier Concentration Today we begin the

More information

Numerical analysis of fluid flow and heat transfer in 2D sinusoidal wavy channel

Numerical analysis of fluid flow and heat transfer in 2D sinusoidal wavy channel Numerical analysis of fluid flow and heat transfer in 2D sinusoidal wavy channel Arunanshu Chakravarty 1* 1 CTU in Prague, Faculty of Mechanical Engineering, Department of Process Engineering,Technická

More information

Arctice Engineering Module 3a Page 1 of 32

Arctice Engineering Module 3a Page 1 of 32 Welcome back to the second part of the second learning module for Fundamentals of Arctic Engineering online. We re going to review in this module the fundamental principles of heat transfer. Exchange of

More information

Experimental Performance and Numerical Simulation of Double Glass Wall Thana Ananacha

Experimental Performance and Numerical Simulation of Double Glass Wall Thana Ananacha Experimental Performance and Numerical Simulation of Double Glass Wall Thana Ananacha Abstract This paper reports the numerical and experimental performances of Double Glass Wall are investigated. Two

More information

Design and Optimization of Energy Systems Prof. C. Balaji Department of Mechanical Engineering Indian Institute of Technology, Madras

Design and Optimization of Energy Systems Prof. C. Balaji Department of Mechanical Engineering Indian Institute of Technology, Madras Design and Optimization of Energy Systems Prof. C. Balaji Department of Mechanical Engineering Indian Institute of Technology, Madras Lecture - 13 Introduction to Curve Fitting Good afternoon. So, we will

More information

COVENANT UNIVERSITY NIGERIA TUTORIAL KIT OMEGA SEMESTER PROGRAMME: MECHANICAL ENGINEERING

COVENANT UNIVERSITY NIGERIA TUTORIAL KIT OMEGA SEMESTER PROGRAMME: MECHANICAL ENGINEERING COVENANT UNIVERSITY NIGERIA TUTORIAL KIT OMEGA SEMESTER PROGRAMME: MECHANICAL ENGINEERING COURSE: MCE 524 DISCLAIMER The contents of this document are intended for practice and leaning purposes at the

More information

International Journal of Advanced Engineering Technology E-ISSN

International Journal of Advanced Engineering Technology E-ISSN Research Article EFFECT OF ROUGHNESS ELEMENT PITCH ON HEAT TRANSFER AND FRICTION CHARACTERISTICS OF ARTIFICIALLY ROUGHENED SOLAR AIR HEATER DUCT Aman Soi*, Ranjit Singh, Brij Bhushan Address for Correspondence

More information

The effect of geometric parameters on the head loss factor in headers

The effect of geometric parameters on the head loss factor in headers Fluid Structure Interaction V 355 The effect of geometric parameters on the head loss factor in headers A. Mansourpour & S. Shayamehr Mechanical Engineering Department, Azad University of Karaj, Iran Abstract

More information