STUDY ON THE THERMAL PERFORMANCE AND AIR DISTRIBUTION OF A DISPLACEMENT VENTILATION SYSTEM FOR LARGE SPACE APPLICATION

Size: px
Start display at page:

Download "STUDY ON THE THERMAL PERFORMANCE AND AIR DISTRIBUTION OF A DISPLACEMENT VENTILATION SYSTEM FOR LARGE SPACE APPLICATION"

Transcription

1 STUDY ON THE THERMAL PERFORMANCE AND AIR DISTRIBUTION OF A DISPLACEMENT VENTILATION SYSTEM FOR LARGE SPACE APPLICATION K Sakai 1*, E Yamaguchi 2, O Ishihara 3 and M Manabe 1 1 Dept. of Architectural Engineering, Oita University, Oita, JAPAN 2 Graduate School of Science and Technology, Kumamoto University, Kumamoto, JAPAN 3 Dept. of Architecture and Civil Engineering, Kumamoto University, Kumamoto, JAPAN ABSTRACT The purpose of this study is to clarify the usefulness of a displacement ventilation air-conditioning system introduced into a multipurpose hall after CFD simulation and measurement. In the multipurpose hall of Kurume City, a displacement ventilation air-conditioning system equipped with a floor outlet had been adopted. A CFD simulation for the purpose of selecting an air condition system indicated the floor outlet system would be more effective for the design plan of the hall than a ceiling outlet system. Measurements for the purpose of determining the effectiveness and thermal performance of a displacement ventilation system were conducted after construction of the hall, and the obtained results for thermal performance and airflow distribution in the hall were consistent with the CFD simulation. INDEX TERMS Large space, Displacement ventilation, CFD, Measurement, Thermal comfort INTRODUCTION The adoption of the displacement air-conditioning system, one of many air-conditioning systems, was for the purpose of controlling indoor wind velocity and improvement in IAQ or increasing energy-saving performance (ASHRAE, 1997). Air conditioning in large spaces like gymnasiums must consider not only temperature control, but also games affected by wind velocity, such as table tennis and badminton. Although displacement ventilation systems appear to be useful as a cooling system for gymnasiums, and controllability and reduction of wind velocity is possible, there are few application examples in Japan. A displacement ventilation air-conditioning system with an equipped floor outlet has been adopted for the multipurpose hall (completion in 2001) in Kurume City. A CFD simulation had been conducted for selecting an air-conditioning system during the design plan, and after the selection, measurements were taken to determine the effectiveness and thermal performance of the displacement ventilation system. In this paper, the results, based on numerical analysis and measurement, of the estimation of usefulness of applied displacement ventilation systems for large spaces is shown. General features of the hall under study The multipurpose hall in this study has a floor space of 600 m 2, a ceiling height of 10m, and mobile spectator seats collapsed against the wall surface can be extended to accommodate 0 persons for lectures and entertainment. * Contact author sakaik@cc.oita-u.ac.jp 771

2 N 2m N c Air Outlet e a W O E (a) Inside view of the hall Lounge f b (b) Section(W-E) :Air temp. :Wind velo. :Surface temp, : + (c) Plan : +Globe temp.+humidity Figure 1. Diagram of multipurpose hall and measuring points d S Table 1 Specifications of the facility Application Gymnasium, Assembly, Conference Air Conditioning Unit Floor space 522m 2 (29m x 18m) Heat Source Absorption cooling/heating (LiBr) Ceiling height Minimum 8 m, maximum 11m Cooling ability 352kW Outlet area m 2 (0.4m x 70m) Heating ability 2kW Suction area 29 m 2 (1m x 29m) Fan power 880 m 3 /h Audience seating 0 seats O.A. supply 6000 m 3 /h Table 2 Simulation cases CASE Inlet type Supply size Return Location Inlet velocity Inlet Temp. Remarks Case1 Ceiling x 0.3m x 20 Side wall 4.0 m/s 17 C Case2 Floor grille 0.m x 80m Ceiling 0.36 m/s 18 C Case3 Floor grille 0.m x 80m Side wall 0.36 m/s 18 C Case4 Floor grille 0.m x 80m Ceiling 0.36 m/s 18 C with Audience seating Generally, the gymnasium is used for badminton, table tennis, basketball, and other sports. Since the daytime summer temperature may reach 35 C with around 60% relative humidity, introduction of a cooling system is necessary for the Kyushu region in which the hall is located. On the other hand, consideration was required in the selection of an air-conditioning system for the sport of badminton, since the shuttle is affected if the indoor wind velocity exceeds 1.0m/s. Based on research during the design stage, a floor system was adopted because control of indoor wind velocity was possible. The building diagram and air-conditioning system are shown in Figure 1. By using a fan from the machine room, the cold air is blown out through the floor outlet from cold air chambers under the floor around the circumference of the multipurpose hall. The central ceiling is equipped with a suction opening and, using the attic as an exhaust chamber, circulates the air back to the machine room. The facility outline is shown in Table

3 (a) Ceiling nozzle type (velocity vector( :1m/s ), temperature) (b) Floor outlet type(velocity vector( :1m/s ), temperature) Figure 2. Temperature and wind distribution (Simulation results, section:n-s) Table 3 Measurement schedule (July, 2001) Air-Conditioning, Setup Temp. C 14 Air-Conditioning, Setup Temp. C 15 Air-Conditioning, Setup Temp. 22 C, with Audience sheet 16 AC, S.T. C Natural Ventilation AC, S.T. C 17 AC, S.T. C AC, S.T.22 C S.T.20 C S.T.22 C AC, S.T. C S.T. C DESIGN STAGE The steady state thermal performance and air distribution was obtained in the design plan of the hall. Numerical analysis of a ceiling nozzle outlet system and for a floor outlet system was obtained using a CFD simulation. A comparison was then conducted (Nagano, 1992). The m 18m 11m space was divided into 73x48x33 mesh using the standard k-e model with SIMPLEC (Doormaal et al., 1984, Patanker, 1980) in the examination. The wall surface temperature was calculated from outside air conditions and thermal transmittance (wall: 1W/m 2 K, glass: 5W/m 2 K), and the effect of the radiation was not considered. The examination is shown in Table 2. In addition, there appeared to be a problem in applying the k-e model in such a flow field, so reexamination with another turbulence model in future is necessary. Part of the calculation result is shown in Figure 2. In the ceiling nozzle outlet system, the blowing jet reached near the floor surface, and wind velocity in the playing areas reached nearly 1.0m/s when the spectator seats were utilized. The temperature of the interior hall was evenly distributed; however, the ceiling nozzle outlet system was not suited for games affected by wind velocity. In the floor outlet system, the room air velocity was kept at 0.3m/s or less. For temperature distribution, cold air accumulated near the floor surface raising concerns about comfort. From these results, the following conclusions were obtained. In displacement air conditioning the air volume cooled is less than in the ceiling system, and thus it becomes energy saving. In the case of the ceiling system, the blowing jet reached near the floor surface adversely affecting badminton and table tennis games. In displacement air conditioning, the wind velocity in the playing area can be kept at 0.3m/s or less. Since it was advantageous to have the better air quality conditions in the playing areas, the floor outlet system was adopted. In the floor outlet system, there were concerns over comfort level if the blowing air temperature was set low. We decided to set the temperature slightly high as a solution. 773

4 40 35 roof inside Tem p. 20 O utdoor 1000 Solar Rad Figure 3. Weather condition 00 Solar Radiation[W /m 2] Vapor Tension[kPa] O utdoor R eturn Supply 0.0 Figure 4. Humidity fluctuation Supply 20 Return 18 Wind V elocity[m /s] a b c d e f 0.0 Figure 5. Supply, Return air temp. fluctuation Figure 6. Wind velocity of floor outlet MEASUREMENT The measurement was important for understanding the thermal environment in the hall and understanding the airflow distribution in the playing area. Summary and measurements are shown in Figure 1. The measurement was conducted using hot wire anemometer for measuring wind velocity, and a T-type thermocouple for measuring surface temperature and air temperature in intervals of 1 minute. The measurement schedule is shown at Table 3. In addition, winter measurements will be taken in February MEASUREMENT RESULTS The measurement was taken on July 13-17, Since the weather was not stable during the measurement period, there was a thermal load in comparison with the equipment ability. As a representative result, the discussion uses July 14th. The fluctuation of outdoor temperature and solar radiation is shown in Figure 3. Air Conditioning System Taking air temperature and blowing vapor tension with suction opening as in Figure 4,5, the wind velocity of each outlet is shown in Figure 6. At the time of air-conditioning, supply temperature was about 23 C, and return temperature was about 29 C. Blowing humidity and suction humidity were almost equivalent. Since measurements were taken under conditions in which there was seldom a thermal load indoors, the system retained reserve cooling ability. The blowing airflow differed greatly depending on the place it blew out from the chamber under the floor. Airflow was a maximum of about 1.2m/s in the east outlet where the chamber airflow was straight, and a minimum of about 0.4m/s in the west outlet. It seems the shape of the chamber controls the velocity of the blowing airflow. Thermal Performance The change in temperature and wind velocity in the central hall is shown in Figure 7, 8. Figure 9 is the temperature change of the wall surface. The temperature 1m above the floor 774

5 h=10m h=7m h=4m h=1m Velocity[m /s] h=0.5m h=1.5m h=2.5m h=3.5m Figure 7. Indoor air temp. fluctuation(point-o) Figure 8. Wind velocity fluctuation(point-o) ceiling north south east west floor Figure 9. Wall surface temp. fluctuation SET*[deg.C] 31 h=3.5m h=2.5m 29 h=1.5m 27 Figure10. Calculation result of SET*(point-O) level was stable at about C and near the ceiling was about C at the time of air-conditioning. Although when using the spectator seats, temperature control to about 4m was a problem, the temperature of the space as a whole was kept almost constant, and thus was considered satisfactory. Room temperature reached the lowest minutes after air-conditioning start and was stabilized about 1 hour afterwards. The time for room temperature to fall below the setting temperature was about 10 minutes, and operation according to hall use was possible. The wind velocity near the floor surface was kept at 0.3m/s or less; velocity near the floor surface was the maximum. It was confirmed that this system was useful for games, which are influenced by wind velocity. For the purpose of evaluating comfort in the hall, SET* (Gagge et al, 1986), which was one of the comfort indices, was calculated using measured values. Figure 10 shows the changes in SET*. SET* becomes about during air-conditioning and the playing area (0-4m height) was comfortable. Figure 11 shows indoor temperature distribution from start time to stable temperature. From immediately after air-conditioning start, temperature decreases from near the floor surface were checked. It was inferred that the indoor temperature had formed temperature stratification and that the blowing air was reaching the playing area. The cooler temperature reached the height of the spectator seats minutes after air conditioning start. It was proven that the room temperature control kept the temperature almost equivalent throughout the whole space. CONCLUSION In this study, the CFD simulation was done in the design stage, and it was possible to obtain effective information to make a decision regarding the air condition system. Based on the measurement results, it was confirmed that this system was useful for games, which are influenced by wind velocity, and achieved the planned purpose of thermal performance and airflow distribution. Though it was exactly impossible, since there was a difference in the conditions, the correspondence of measured values and CFD simulation results confirmed the validity of the case study. In future work, the measurement results will provide feedback for the calculations in order to improve calculation accuracy. 775

6 10:00 10: 10:05 11:00 10:15 12:00 Figure 11. Temperature distribution of the hall (Measurement results, section:s-o-e) ACKNOWLEDGEMENTS The authors extend their sincere gratitude to the members of Ishihara Laboratory of Kumamoto University, Mr. Shimizu and Mr. Baba in Kurume City for their kind cooperation in the completion of the present study. REFERENCES ASHRAE HANDBOOK Fundamentals Chapter 31, SPACE AIR DIFFUSION: American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Doormaal J P, Raithby G D Enhancements of the SIMPLE Method for Predicting Incompressible Fluid Flows. Numerical Heat Transfer, vol.7, pp Gagge A P, Fobelets A P, Berglund L G A Standard Predictive Index of Human Response to the Thermal Environment, ASHRAE Transaction, vol.92, Part 2B, pp Nagano S, Mima T Ventilation Efficiency in a Two-Dimensional Enclosure with a Supply Outlet in the Ceiling or in the Floor. Proceedings of International Symposium on Room Air Convection and Ventilation Effectiveness, pp Tokyo:ASHRAE Sakai K, Ishihara O, Nagano S A Measurement of the Thermal Performance and Air Distribution of Indoor Sports Ground Using Swiring Flow Type Natural Ventilation System. Proceedings of the Eighth International Conference on Indoor Air Quality and Climate, vol. 4, pp Edinburgh:Indoor Air 99. Patanker S V Numerical heat transfer and fluid flows. New York:McGraw-Hill. 776

EVALUATION OF THERMAL ENVIRONMENT AROUND THE BLIND ON NON-UNIFOM RADIANT FIELDS A CFD SIMULATION OF HEAT TRANSFER DISTRIBUTION NEAR THE BLINDS

EVALUATION OF THERMAL ENVIRONMENT AROUND THE BLIND ON NON-UNIFOM RADIANT FIELDS A CFD SIMULATION OF HEAT TRANSFER DISTRIBUTION NEAR THE BLINDS 800 1500 6240 1600 1500 840 Proceedings of BS2015: EVALUATION OF THERMAL ENVIRONMENT AROUND THE BLIND ON NON-UNIFOM RADIANT FIELDS A CFD SIMULATION OF HEAT TRANSFER DISTRIBUTION NEAR THE BLINDS Nozomi

More information

A Numerical Analysis of Indoor Thermal Environment and Human Thermophysiological Responses under Natural Ventilation S. Iizuka 1,*, T. Sakoi 2, T. Sai

A Numerical Analysis of Indoor Thermal Environment and Human Thermophysiological Responses under Natural Ventilation S. Iizuka 1,*, T. Sakoi 2, T. Sai A Numerical Analysis of Indoor Thermal Environment and Human Thermophysiological Responses under Natural Ventilation S. Iizuka 1,*, T. Sakoi 2, T. Saito 1, and S. Kuno 1 1 Graduate School of Environmental

More information

CFD as a Tool for Thermal Comfort Assessment

CFD as a Tool for Thermal Comfort Assessment CFD as a Tool for Thermal Comfort Assessment Dimitrios Koubogiannis dkoubog@teiath.gr G. Tsimperoudis, E. Karvelas Department of Energy Technology Engineering Technological Educational Institute of Athens

More information

Study of air curtains used to restrict infiltration into refrigerated rooms

Study of air curtains used to restrict infiltration into refrigerated rooms Study of air curtains used to restrict infiltration into refrigerated rooms Gregory Verhaeghe 1, Marnix Van Belleghem 1, Arnout Willockx 1, Ivan Verhaert 1, Michel De Paepe 1 1 Ghent University, Department

More information

INVESTIGATION OF THE PERFORMANCE OF COOLING PANELS: CEILING AND FLOOR PANElS.

INVESTIGATION OF THE PERFORMANCE OF COOLING PANELS: CEILING AND FLOOR PANElS. INVESTIGATION OF THE PERFORMANCE OF COOLING PANELS: CEILING AND FLOOR PANElS. * M. Hammad, Al Helo, S. And Khlaif, B. University of Jordan. Mechanical Engineering Department. hammad@ju.edu.jo 1.0 ABSTRACT:

More information

RELATIONSHIPS BETWEEN OVERALL THERMAL SENSATION, ACCEPTABILITY AND COMFORT

RELATIONSHIPS BETWEEN OVERALL THERMAL SENSATION, ACCEPTABILITY AND COMFORT RELATIONSHIPS BETWEEN OVERALL THERMAL SENSATION, ACCEPTABILITY AND COMFORT Yufeng Zhang 1, and Rongyi Zhao 2 1 State Key Laboratory of Subtropical Building Science, South China University of Technology,

More information

ROOM AVERAGE VELOCITY EQUATION A TOOL TO IMPROVE DESIGN OF THERMAL COMFORT CONDITIONS

ROOM AVERAGE VELOCITY EQUATION A TOOL TO IMPROVE DESIGN OF THERMAL COMFORT CONDITIONS ROOM AVERAGE VELOCITY EQUATION A TOOL TO IMPROVE DESIGN OF THERMAL COMFORT CONDITIONS K Hagström *, O Hakkola and T Moilanen Halton Solutions, Kausala, Finland ABSTRACT For a long time PPD index defined

More information

PROPOSAL OF SEVEN-DAY DESIGN WEATHER DATA FOR HVAC PEAK LOAD CALCULATION

PROPOSAL OF SEVEN-DAY DESIGN WEATHER DATA FOR HVAC PEAK LOAD CALCULATION Ninth International IBPSA Conference Montréal, Canada August 5-8, PROPOSAL OF SEVEN-DAY DESIGN WEATHER DATA FOR HVAC PEAK LOAD CALCULATION Hisaya ISHINO Faculty of Urban Environmental Sciences, Metropolitan

More information

NUMERICAL AND EXPERIMENTAL INVESTIGATIONS OF AIR FLOW AND TEMPERATURE PATTERNS OF A LOW VELOCITY DIFFUSER

NUMERICAL AND EXPERIMENTAL INVESTIGATIONS OF AIR FLOW AND TEMPERATURE PATTERNS OF A LOW VELOCITY DIFFUSER NUMERICAL AND EXPERIMENTAL INVESTIGATIONS OF AIR FLOW AND TEMPERATURE PATTERNS OF A LOW VELOCITY DIFFUSER M Cehlin and B Moshfegh Division of Energy and Mechanical Engineering, Department of Technology,

More information

Development and Validation of Flat-Plate Collector Testing Procedures

Development and Validation of Flat-Plate Collector Testing Procedures Development and Validation of Flat-Plate Collector Testing Procedures Report for March, 2007 Focus on Energy (FOE) supports solar thermal systems that displace conventional fuels by offering cash-back

More information

5. Thermal Design. Objective: Control heat flow to: Maintain comfortable indoor conditions

5. Thermal Design. Objective: Control heat flow to: Maintain comfortable indoor conditions 5. Thermal Design Objective: Control heat flow to: 2. Maintain comfortable indoor conditions 3. Reduce heating/cooling loads, which reduces operating costs 4. Control vapor movement/condensation 5. Design

More information

A CFD SIMULATION AND OPTIMIZATION OF SUBWAY STATION VENTILATION

A CFD SIMULATION AND OPTIMIZATION OF SUBWAY STATION VENTILATION A CFD SIMULATION AND OPTIMIZATION OF SUBWAY STATION VENTILATION L Wang 1,4*, G Tu 2,4, T Zou 3,4 and J Yang 4 1 The School of Environmental Science and Engineering, Tianjin University, Tianjin, China 2

More information

Study on Thermal Load Calculation for Ceiling Radiant Cooling Panel System

Study on Thermal Load Calculation for Ceiling Radiant Cooling Panel System Study on Thermal Load Calculation for Ceiling Radiant Cooling Panel System Sei Ito, Yasunori Akashi, Jongyeon Lim Shimizu Corporation, Tokyo, Japan University of Tokyo, Tokyo, Japan Abstract The ceiling

More information

Section 3.5 Thermal Comfort and Heat Stress

Section 3.5 Thermal Comfort and Heat Stress Section 3.5 Thermal Comfort and Heat Stress Table 3.6 Metabolic rate as a function of physical activity for a 70 kg adult man (abstracted from ASHRAE, 1997). activity metabolic rate (W) metabolic rate

More information

Physiological Response of Human Body and Thermal Sensation for Irradiation and Exercise Load Changes

Physiological Response of Human Body and Thermal Sensation for Irradiation and Exercise Load Changes ICUC9-9 th International Conference on Urban Climate jointly with th Symposium on the Urban Environment Physiological Response of Human Body and Thermal Sensation for Irradiation and Exercise Load Changes

More information

NUMERICAL MODELLING OF TEMPERATURE AND AIR FLOW DISTRIBUTION IN ENCLOSED ROOM

NUMERICAL MODELLING OF TEMPERATURE AND AIR FLOW DISTRIBUTION IN ENCLOSED ROOM NUMERICAL MODELLING OF TEMPERATURE AND AIR FLOW DISTRIBUTION IN ENCLOSED ROOM Igor Bonefacic 1, Bernard Frankovic 2, Ivan Vilicic 3, Vladimir Glazar 4 Faculty of Engineering, Vukovarska 58, Rijeka, Croatia,

More information

Numerical Simulation and Air Conditioning System Improvement for the Experimental Hall at TLS J.C. Chang a, M.T. Ke b, Z.D. Tsai a, and J. R.

Numerical Simulation and Air Conditioning System Improvement for the Experimental Hall at TLS J.C. Chang a, M.T. Ke b, Z.D. Tsai a, and J. R. Numerical Simulation and Air Conditioning System Improvement for the Experimental Hall at TLS J.C. Chang a, M.T. Ke b, Z.D. Tsai a, and J. R. Chen a a National Synchrotron Radiation Research Center (NSRRC)

More information

Thermal performance of the new hall of the historical hospital in Florence

Thermal performance of the new hall of the historical hospital in Florence hermal performance of the new hall of the historical hospital in Florence C. Balocco *,1, E. Marmonti 1 1 Dipartimento di Energetica, Università di Firenze *Corresponding author: via Santa Marta 3,F irenze,

More information

Experimental Performance and Numerical Simulation of Double Glass Wall Thana Ananacha

Experimental Performance and Numerical Simulation of Double Glass Wall Thana Ananacha Experimental Performance and Numerical Simulation of Double Glass Wall Thana Ananacha Abstract This paper reports the numerical and experimental performances of Double Glass Wall are investigated. Two

More information

Project 2. Introduction: 10/23/2016. Josh Rodriguez and Becca Behrens

Project 2. Introduction: 10/23/2016. Josh Rodriguez and Becca Behrens Project 2 Josh Rodriguez and Becca Behrens Introduction: Section I of the site Dry, hot Arizona climate Linen supply and cleaning facility Occupied 4am-10pm with two shifts of employees PHOENIX, ARIZONA

More information

Double-Skin Facade in Low-Latitude: Study on the Absorptance, Reflectance, and Transmittance of Direct Solar Radiation

Double-Skin Facade in Low-Latitude: Study on the Absorptance, Reflectance, and Transmittance of Direct Solar Radiation ouble-skin Facade in Low-Latitude: Study on the Absorptance, Reflectance, and Transmittance of irect Solar Radiation G-LO 011 Rosady Mulyadi epartment of Architecture Faculty of Engineering Hasanuddin

More information

STUDY OF COOLING SYSTEM WITH WATER MIST SPRAYERS FUNDAMENTAL EXAMINATION OF PARTICLE SIZE DISTRIBUTION AND COOLING EFFECTS

STUDY OF COOLING SYSTEM WITH WATER MIST SPRAYERS FUNDAMENTAL EXAMINATION OF PARTICLE SIZE DISTRIBUTION AND COOLING EFFECTS STUDY OF COOLING SYSTEM WITH WATER MIST SPRAYERS FUNDAMENTAL EXAMINATION OF PARTICLE SIZE DISTRIBUTION AND COOLING EFFECTS Yamada Hideki 1, Yoon Gyuyoug 1 Okumiya Masaya 1, Okuyama Hiroyasu 2 1 Graduate

More information

Air Flow Modeling in a Mechanically Ventilated Room

Air Flow Modeling in a Mechanically Ventilated Room Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Air Flow Modeling in a Mechanically Ventilated Room T. P. Ashok Babu National

More information

BSE Public CPD Lecture Numerical Simulation of Thermal Comfort and Contaminant Transport in Rooms with UFAD system on 26 March 2010

BSE Public CPD Lecture Numerical Simulation of Thermal Comfort and Contaminant Transport in Rooms with UFAD system on 26 March 2010 BSE Public CPD Lecture Numerical Simulation of Thermal Comfort and Contaminant Transport in Rooms with UFAD system on 26 March 2010 Organized by the Department of Building Services Engineering, a public

More information

Natural Ventilation. CFD modelling of a double-skin facade. Huw Birch. Supervisor: Abigail Hathway

Natural Ventilation. CFD modelling of a double-skin facade. Huw Birch. Supervisor: Abigail Hathway Natural Ventilation CFD modelling of a double-skin facade Huw Birch Supervisor: Abigail Hathway Introduction Given the high energy demands of traditional mechanical ventilation systems such as humidifiers,

More information

Cooling of Electronics Lecture 2

Cooling of Electronics Lecture 2 Cooling of Electronics Lecture 2 Hans Jonsson Agenda Lecture 2 Introduction to Cooling of Electronics Cooling at different levels Cooling demand calculations Introduction to Cooling of Electronics Both

More information

Subjective Thermal Comfort in the Environment with Spot Cooling System

Subjective Thermal Comfort in the Environment with Spot Cooling System Subjective Thermal Comfort in the Environment with Spot ing System Hayato Ohashi 1, Hitomi Tsutsumi 1, Shin-ichi Tanabe 1, Ken-ichi Kimura 1, Hideaki Murakami 2, Koji Kiyohara 3 1 Department of Architecture,

More information

Thermal Comfort; Operative Temperature in the Sun

Thermal Comfort; Operative Temperature in the Sun Thermal Comfort; Operative Temperature in the Sun Ida Bryn (Ph.d) Marit Smidsrød (MSc) Erichsen&Horgen AS, Postboks 4464 Nydalen, 0403 Oslo, E-mail: ihb@erichsen-horgen.no, telephone: 47 22026333, telefax:

More information

A Discussion of Low Reynolds Number Flow for the Two-Dimensional Benchmark Test Case

A Discussion of Low Reynolds Number Flow for the Two-Dimensional Benchmark Test Case A Discussion of Low Reynolds Number Flow for the Two-Dimensional Benchmark Test Case M. Weng, P. V. Nielsen and L. Liu Aalborg University Introduction. The use of CFD in ventilation research has arrived

More information

therefore cold air is released to the outdoor space, contributing to changes in the outdoor microclimate (Figure 1). This results in a cool spot in th

therefore cold air is released to the outdoor space, contributing to changes in the outdoor microclimate (Figure 1). This results in a cool spot in th Characteristics of Cold-air Release from Air-conditioned and Open-entrance Shops to Outside Street Spaces in Summer T. Asawa 1,*, and Y. Kugimachi 2 1 Interdisciplinary Graduate School of Science and Engineering,

More information

2-D CFD analysis of passenger compartment for thermal comfort and ventilation

2-D CFD analysis of passenger compartment for thermal comfort and ventilation 2-D CFD analysis of passenger compartment for thermal comfort and ventilation Ajay Giri 1*, Brajesh Tripathi 2 and H.C. Thakur 3 *1, 3 School of Engineering, Gautam Buddha University, Greater Noida, U.P,

More information

Study on Reusing Abandoned Chimneys as Solar Chimneys to Induce Breeze in Residential Areas

Study on Reusing Abandoned Chimneys as Solar Chimneys to Induce Breeze in Residential Areas Study on Reusing Abandoned Chimneys as Solar Chimneys to Induce Breeze in Residential Areas AZUSA TAKAYAMA 1, KOICHI ASANO 1, SHIGEMITSU SHUCHI 1 and KENICHI HASEGAWA 1 1 Faculty of Systems Science and

More information

Climatically Adapted Piloti Arrangement and Ratio of Residential Blocks in a Subtropical Climate City

Climatically Adapted Piloti Arrangement and Ratio of Residential Blocks in a Subtropical Climate City Climatically Adapted Piloti Arrangement and Ratio of Residential Blocks in a Subtropical Climate City Zeng Zhou 1, Qinli Deng 2, Akashi Mochida 2 1 Wuhan University, China, haomaoz@hotmail.com 2 Tohoku

More information

Aalborg Universitet. Publication date: Document Version Publisher's PDF, also known as Version of record

Aalborg Universitet. Publication date: Document Version Publisher's PDF, also known as Version of record Aalborg Universitet Experimental Investigation of the Influence of Different Flooring Emissivity on Night- Time Cooling using Displacement Ventilation Dreau, Jerome Le; Karlsen, Line Røseth; Litewnicki,

More information

Simulation of Temperature Stratification in Atriums: Validation of Basic Model Features. Susan Bajracharya

Simulation of Temperature Stratification in Atriums: Validation of Basic Model Features. Susan Bajracharya TUTA/IOE/PCU Journal of the Institute of Engineering, Vol. 10, No. 1, pp. 157 171 TUTA/IOE/PCU All rights reserved. Printed in Nepal Fax: 977-1-5525830 Simulation of Temperature Stratification in Atriums:

More information

Heat Transfer and Natural Ventilation Airflow Rates from Single-sided Heated Solar Chimney for Buildings

Heat Transfer and Natural Ventilation Airflow Rates from Single-sided Heated Solar Chimney for Buildings Heat Transfer and Natural Ventilation Airflow Rates from Single-sided Heated Solar Chimney for Buildings Angui Li* 1, Phillip Jones 2, Pingge Zhao 3 and Liping Wang 3 1 Professor, Department of Environmental

More information

Heat Transfer Studies on Structured Metal Sheets

Heat Transfer Studies on Structured Metal Sheets KMUTNB Int J Appl Sci Technol, Vol. 9, No., pp. 189 196, 2016 Research Article Heat Transfer Studies on Structured Metal Sheets Josef Egert* and Karel Fraňa Department of Power Engineering Equipment, Faculty

More information

INDIAN INSTITUTE OF TECHNOLOGY ROORKEE NPTEL NPTEL ONLINE CERTIFICATION COURSE. Refrigeration and Air-conditioning. Lecture-37 Thermal Comfort

INDIAN INSTITUTE OF TECHNOLOGY ROORKEE NPTEL NPTEL ONLINE CERTIFICATION COURSE. Refrigeration and Air-conditioning. Lecture-37 Thermal Comfort INDIAN INSTITUTE OF TECHNOLOGY ROORKEE NPTEL NPTEL ONLINE CERTIFICATION COURSE Refrigeration and Air-conditioning Lecture-37 Thermal Comfort with Prof. Ravi Kumar Department of Mechanical and Industrial

More information

EXPERIMENTAL SETUP The experimental test-room was representative of a full-sized office space. This was a natural

EXPERIMENTAL SETUP The experimental test-room was representative of a full-sized office space. This was a natural Seventh International IBPSA Conference Rio de Janeiro, Brazil August 13-15, 2001 ON THE NATURAL DISPLACEMENT VENTILATION FLOW THROUGH A FULL SCALE ENCLOSURE, DRIVEN BY A SOURCE OF BUOYANCY AT FLOOR LEVEL

More information

CAE 331/513 Building Science Fall 2016

CAE 331/513 Building Science Fall 2016 CAE 331/513 Building Science Fall 2016 Week 3: September 8, 2016 Heat transfer in buildings: Finish radiation, then solar radiation and windows Advancing energy, environmental, and sustainability research

More information

VALIDATION OF REYNOLDS AVERAGED MODEL AND LARGE EDDY SIMULATION IN ACTUAL FLOOR HEATING ROOM. Hiroki Ono 1 and Koji Sakai 1

VALIDATION OF REYNOLDS AVERAGED MODEL AND LARGE EDDY SIMULATION IN ACTUAL FLOOR HEATING ROOM. Hiroki Ono 1 and Koji Sakai 1 Proceedings of Building Simulation 11: VALDATON OF RYNOLDS AVRAD MODL AND LAR DDY SMULATON N ACTUAL FLOOR HATN ROOM Hiroki Ono 1 and Koji Sakai 1 1 School of Science and Technology, Meiji University, Kawasaki,

More information

MEASUREMENT OF THE AIRFLOW AND TEMPERATURE FIELDS AROUND LIVE SUBJECTS AND THE EVALUATION OF HUMAN HEAT LOSS

MEASUREMENT OF THE AIRFLOW AND TEMPERATURE FIELDS AROUND LIVE SUBJECTS AND THE EVALUATION OF HUMAN HEAT LOSS MEASUREMENT OF THE AIRFLOW AND TEMPERATURE FIELDS AROUND LIVE SUBJECTS AND THE EVALUATION OF HUMAN HEAT LOSS GH Zhou 1, DL Loveday 1, AH Taki 2 and KC Parsons 3 1 Department of Civil and Building Engineering,

More information

Validation of IDA Indoor Climate and Energy

Validation of IDA Indoor Climate and Energy Technical report: Validation of IDA Indoor Climate and Energy 4.0 build 4 with respect to ANSI/ASHRAE Standard 140-2004 April 2010 Equa Simulation AB Råsundavägen 100 169 57 Solna Sweden Contents 1 Introduction

More information

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Available online at   ScienceDirect. Procedia Engineering 121 (2015 ) Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 121 (2015 ) 2176 2183 9th International Symposium on Heating, Ventilation and Air Conditioning (ISHVAC) and the 3rd International

More information

Performance Assessment of PV/T Air Collector by Using CFD

Performance Assessment of PV/T Air Collector by Using CFD Performance Assessment of /T Air Collector by Using CFD Wang, Z. Department of Built Environment, University of Nottingham (email: laxzw4@nottingham.ac.uk) Abstract Photovoltaic-thermal (/T) collector,

More information

A Numerical Investigation on Active Chilled Beams for Indoor Air Conditioning

A Numerical Investigation on Active Chilled Beams for Indoor Air Conditioning Excerpt from the Proceedings of the COMSOL Conference 2008 Hannover A Numerical Investigation on Active Chilled Beams for Indoor Air Conditioning Cammarata G., Petrone G. * Department of Industrial and

More information

STUDY OF A PASSIVE SOLAR WINTER HEATING SYSTEM BASED ON TROMBE WALL

STUDY OF A PASSIVE SOLAR WINTER HEATING SYSTEM BASED ON TROMBE WALL STUDY OF A PASSIVE SOLAR WINTER HEATING SYSTEM BASED ON TROMBE WALL Dr. G.S.V.L.Narasimham Chief Research Scientist, RAC, Dept. of Mechanical Engineering, Indian Institute of Science,Bengaluru- 560012,

More information

Comparison of two equations closure turbulence models for the prediction of heat and mass transfer in a mechanically ventilated enclosure

Comparison of two equations closure turbulence models for the prediction of heat and mass transfer in a mechanically ventilated enclosure Proceedings of 4 th ICCHMT May 17-0, 005, Paris-Cachan, FRANCE 381 Comparison of two equations closure turbulence models for the prediction of heat and mass transfer in a mechanically ventilated enclosure

More information

Studying the Thermal and Cryogenic Performance of Shevadun in Native (Local) Buildings of Dezful Based on. Modeling and Environmental Measuring

Studying the Thermal and Cryogenic Performance of Shevadun in Native (Local) Buildings of Dezful Based on. Modeling and Environmental Measuring American Journal of Energy Research, 2013, Vol. 1, No. 3, 45-53 Available online at http://pubs.sciepub.com/ajer/1/3/2 Science and Education Publishing DOI:10.12691/ajer-1-3-2 Studying the Thermal and

More information

DYNAMIC INSULATION APPLIED TO THE RESIDENTIAL BUILDING (PART 2) Numerical Evaluation of Thermal Insulation Effect on Air Supply Window System

DYNAMIC INSULATION APPLIED TO THE RESIDENTIAL BUILDING (PART 2) Numerical Evaluation of Thermal Insulation Effect on Air Supply Window System 3 5 7 8 9 DYNAMIC INSULATION APPLIED TO THE RESIDENTIAL BUILDING (PART ) Numerical Evaluation of Thermal Insulation Effect on Air Supply Window System ABSTRACT Sihwan Lee, Tanaka Miho, Shinsuke Kato 3

More information

Increasing Energy Efficiency of HVAC Systems in Buildings Using Phase Change Material

Increasing Energy Efficiency of HVAC Systems in Buildings Using Phase Change Material Washington University in St. Louis Washington University Open Scholarship All Theses and Dissertations (ETDs) January 2011 Increasing Energy Efficiency of HVAC Systems in Buildings Using Phase Change Material

More information

2. Climate (Outdoor) Altitude. Distance from the ocean. Conditions of the ocean. Store/release heat. angle of solar radiation Amount of solar energy

2. Climate (Outdoor) Altitude. Distance from the ocean. Conditions of the ocean. Store/release heat. angle of solar radiation Amount of solar energy 2. Climate (Outdoor) Weather - General atmospheric conditions at a given place to a given time with respect to: Temperature Humidity Rain (precipitation)/snow Wind/air movement Radiation It is a dynamic

More information

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Paper ID 0076 ISBN: 978-83-7947-232-1 Experimental Study of the Airflow Distribution Close to the Human Body with a Downward Plane Jet Marie

More information

PAUL RUDOLPH Oriental Masonic Gardens

PAUL RUDOLPH Oriental Masonic Gardens 1 PAUL RUDOLPH Oriental Masonic Gardens Latitude _ 41.3 N Longitude _ 72.9 W Climate: transition between Cfa _ Humid Subtropical and Dfa_ Humid Continental climate 2 Paul Rudolph INTRODUCTION Fig. 1 -

More information

Air Diffusion Designing for Comfort

Air Diffusion Designing for Comfort Air Diffusion Designing for Comfort Occupant Comfort Air Diffusion Selection ADPI Air Diffusion Performance index Ventilation Effectiveness Induction Room Space Induction Design Criteria ISO7730 ASHRAE

More information

Thermodynamics I Spring 1432/1433H (2011/2012H) Saturday, Wednesday 8:00am - 10:00am & Monday 8:00am - 9:00am MEP 261 Class ZA

Thermodynamics I Spring 1432/1433H (2011/2012H) Saturday, Wednesday 8:00am - 10:00am & Monday 8:00am - 9:00am MEP 261 Class ZA Thermodynamics I Spring 1432/1433H (2011/2012H) Saturday, Wednesday 8:00am - 10:00am & Monday 8:00am - 9:00am MEP 261 Class ZA Dr. Walid A. Aissa Associate Professor, Mech. Engg. Dept. Faculty of Engineering

More information

Design strategy for Low e windows with effective insulation

Design strategy for Low e windows with effective insulation Design strategy for Low e windows with effective insulation Michael P.C. Watts, Impattern Solutions, www.impattern.com Keywords; insulating windows. low emission glass, ABSTRACT Optimal window glass assemblies

More information

AN EVALUATIVE METHOD FOR HIGH-PERFORMANCE WINDOW SYSTEM AND WINDOW SIDE RADIATION ENVIRONMENT

AN EVALUATIVE METHOD FOR HIGH-PERFORMANCE WINDOW SYSTEM AND WINDOW SIDE RADIATION ENVIRONMENT AN EVALUATIVE METHOD FOR HIGH-PERFORMANCE WINDOW SYSTEM AND WINDOW SIDE RADIATION ENVIRONMENT Kimiko Kohri Department of Energy and Environmental Science, Graduate School of Engineering, Utsunomiya University

More information

IMPACT OF THE ATMOSPHERIC BOUNDARY LAYER PROFILE ON THE VENTILATION OF A CUBIC BUILDING WITH TWO LARGE OPPOSITE OPENINGS

IMPACT OF THE ATMOSPHERIC BOUNDARY LAYER PROFILE ON THE VENTILATION OF A CUBIC BUILDING WITH TWO LARGE OPPOSITE OPENINGS Ninth International IBPSA Conference Montréal, Canada August 15-18, 2005 IMPACT OF THE ATMOSPHERIC BOUNDARY LAYER PROFILE ON THE VENTILATION OF A CUBIC BUILDING WITH TWO LARGE OPPOSITE OPENINGS Alain BASTIDE,

More information

EXPERIMENTAL ANALYSIS OF AIR-CONDITIONING IN HOSPITAL ROOMS BY MEANS OF LIGHT RADIANT CEILINGS

EXPERIMENTAL ANALYSIS OF AIR-CONDITIONING IN HOSPITAL ROOMS BY MEANS OF LIGHT RADIANT CEILINGS EXPERIMENTAL ANALYSIS OF AIR-CONDITIONING IN HOSPITAL ROOMS BY MEANS OF LIGHT RADIANT CEILINGS Renato M. Lazzarin renato@gest.unipd.it Francesco Castellotti caste@gest.unipd.it Filippo Busato busato@gest.unipd.it

More information

Thermal Unit Operation (ChEg3113)

Thermal Unit Operation (ChEg3113) Thermal Unit Operation (ChEg3113) Lecture 3- Examples on problems having different heat transfer modes Instructor: Mr. Tedla Yeshitila (M.Sc.) Today Review Examples Multimode heat transfer Heat exchanger

More information

CZECH TECHNICAL UNIVERSITY IN PRAGUE FACULTY OF MECHANICAL ENGINEERING DEPARTMENT OF ENVIRONMENTAL ENGINEERING

CZECH TECHNICAL UNIVERSITY IN PRAGUE FACULTY OF MECHANICAL ENGINEERING DEPARTMENT OF ENVIRONMENTAL ENGINEERING CZECH TECHNICAL UNIVERSITY IN PRAGUE FACULTY OF MECHANICAL ENGINEERING DEPARTMENT OF ENVIRONMENTAL ENGINEERING APPLICABILITY OF CHILLED BEAM-SYSTEM IN THE MIDDLE EAST BACHELOR THESIS JACQUES MATTA 2 EE

More information

Environmental Engineering

Environmental Engineering Environmental Engineering 1 Indoor Environment and Thermal Comfort Vladimír Zmrhal (room no. 814) Master degree course 1 st semester (winter) Dpt. of Environmental Engineering 1 Environmental Engineering

More information

Development and Validation of Flat-Plate Collector Testing Procedures

Development and Validation of Flat-Plate Collector Testing Procedures Development and Validation of Flat-Plate Collector Testing Procedures Report for February, 2007 Focus on Energy (FOE) supports solar thermal systems that displace conventional fuels by offering cash-back

More information

ARCH 348 BUILDING AND ENVIRONMENTAL SYSTEMS

ARCH 348 BUILDING AND ENVIRONMENTAL SYSTEMS ARCH 348 BUILDING AND ENVIRONMENTAL SYSTEMS Instructor: Prof. Dr. Uğur Atikol Web site for instructor: http://staff.emu.edu.tr/uguratikol/ Web site for the course: http://staff.emu.edu.tr/uguratikol/en/teaching/courses/arch348-building-andenvironmental-systems-in-architecture

More information

Air distribution systems. Linear whirl outlet WL...

Air distribution systems. Linear whirl outlet WL... Air distribution systems Linear whirl outlet WL... DS 0 E 1.013 Preliminary remarks Mode of operation The linear whirl outlet generates turbulent mixing ventilation. It can be installed on or in a wall

More information

Today s A/C systems include:

Today s A/C systems include: * www.sgvenergywise.org Replac ing your A/C system REQUIRES a permit from your c ity - it s important. WHY? Because A/C (air conditioning) is a SYSTEM, not just one piece of equipment. The thermostat,

More information

Combined GIS, CFD and Neural Network Multi-Zone Model for Urban Planning and Building Simulation. Methods

Combined GIS, CFD and Neural Network Multi-Zone Model for Urban Planning and Building Simulation. Methods Combined GIS, CFD and Neural Network Multi-Zone Model for Urban Planning and Building Simulation Meng Kong 1, Mingshi Yu 2, Ning Liu 1, Peng Gao 2, Yanzhi Wang 1, Jianshun Zhang 1 1 School of Engineering

More information

Aalborg Universitet. Comparison between Different Air Distribution Systems Nielsen, Peter Vilhelm. Publication date: 2006

Aalborg Universitet. Comparison between Different Air Distribution Systems Nielsen, Peter Vilhelm. Publication date: 2006 Aalborg Universitet Comparison between Different Air Distribution Systems Nielsen, Peter Vilhelm Publication date: 2006 Document Version Publisher's PDF, also known as Version of record Link to publication

More information

LONGITUDINAL VENTILATION OF BROILER HOUSE SIMULATION OF VARIANTS.

LONGITUDINAL VENTILATION OF BROILER HOUSE SIMULATION OF VARIANTS. LONGITUDINAL VENTILATION OF BROILER HOUSE SIMULATION OF VARIANTS Milan Zajicek 1, Pavel Kic 2 1 Academy of Science of the Czech Republic; 2 Czech University of Life Sciences zajicek@utia.cas.cz, kic@tf.czu.cz

More information

ScienceDirect. Experimental study of influence of movements on airflow under stratum ventilation

ScienceDirect. Experimental study of influence of movements on airflow under stratum ventilation Available online at www.sciencedirect.com ScienceDirect Energy Procedia 7 (15 ) 7 11 th International Building Physics Conference, IBPC 15 Experimental study of influence of movements on airflow under

More information

Analysis of Natural Wind Characteristics and Review of Their Correlations with Human Thermal Sense through Actual Measurements

Analysis of Natural Wind Characteristics and Review of Their Correlations with Human Thermal Sense through Actual Measurements Analysis of Natural Wind Characteristics and Review of Their Correlations with Human Thermal Sense through Actual Measurements Ki Nam Kang 1,a, Jin Yu 1,b, Doo Sam Song 2,c, Hee Jung Ham 3,d, Kook Jeong

More information

Dynamic Modelling of Refrigerated Truck Chambers

Dynamic Modelling of Refrigerated Truck Chambers Dynamic Modelling of Refrigerated Truck Chambers R.A.Pitarma 1, P.D.Gaspar 2 & M.G.Carvalho 3 1 Department of Mechanical Engineering, Polytechnic Institute of Guarda, Portugal. 2 Department of Electromechanical

More information

THERMAL ENVIRONMENT PREDICTION USING CFD WITH A VIRTUAL MANNEQUIN MODEL AND EXPERIMENT WITH SUBJECT IN A FLOOR HEATING ROOM

THERMAL ENVIRONMENT PREDICTION USING CFD WITH A VIRTUAL MANNEQUIN MODEL AND EXPERIMENT WITH SUBJECT IN A FLOOR HEATING ROOM Proceedings of Building Simulation 11: THERMAL ENVIRONMENT PREDICTION USING CFD WITH A VIRTUAL MANNEQUIN MODEL AND EXPERIMENT WITH SUBJECT IN A FLOOR HEATING ROOM Ryoichi Kajiya 1, Kodai Hiruta, Koji Sakai

More information

Chapter 1: 20, 23, 35, 41, 68, 71, 76, 77, 80, 85, 90, 101, 103 and 104.

Chapter 1: 20, 23, 35, 41, 68, 71, 76, 77, 80, 85, 90, 101, 103 and 104. Chapter 1: 0, 3, 35, 1, 68, 71, 76, 77, 80, 85, 90, 101, 103 and 10. 1-0 The filament of a 150 W incandescent lamp is 5 cm long and has a diameter of 0.5 mm. The heat flux on the surface of the filament,

More information

COMMERCIAL HEAT GAIN - HEAT LOSS CALCULATION LOAD FORM

COMMERCIAL HEAT GAIN - HEAT LOSS CALCULATION LOAD FORM COMMERCIAL HEAT GAIN - HEAT LOSS CALCULATION LOAD FORM Job Name: Address: Phone/Fax/Email: Contractor: Address: Phone/Fax/Email: Heat Gain Summary Sensible Heat (Btu/h) Latent Heat (Btu/h) Total Heat Gain

More information

OPERATIVE TEMPERATURE SIMULATION OF ENCLOSED SPACE WITH INFRARED RADIATION SOURCE AS A SECONDARY HEATER

OPERATIVE TEMPERATURE SIMULATION OF ENCLOSED SPACE WITH INFRARED RADIATION SOURCE AS A SECONDARY HEATER OPERATIVE TEMPERATURE SIMULATION OF ENCLOSED SPACE WITH INFRARED RADIATION SOURCE AS A SECONDARY HEATER L. Hach 1, K. Hemzal 2, Y. Katoh 3 1 Institute of Applied Physics and Mathematics, Faculty of Chemical

More information

Thermal simulation of a complete vehicle using manikin models

Thermal simulation of a complete vehicle using manikin models Thermal simulation of a complete vehicle using manikin models Dr. Stefan Paulke, Dr. Daniel Köster, Dr. Regina Hass (P+Z Engineering GmbH) Dr. Viktor Bader, Dr. Stephan Menzel, Andreas Gubalke (Volkswagen

More information

ARCHITECTURE IN THE DAYLIGHT

ARCHITECTURE IN THE DAYLIGHT ARCHITECTURE IN THE DAYLIGHT Site Location MANUS LEUNG HARVARD GSD FALL 2015 The house is located in Jl. Intern Corn Kebun Jeruk Blok U3 No.18, Kembangan District of Jakarta 11640 Indonesia. 01 OBJECTIVES

More information

Institut national des sciences appliquées de Strasbourg GENIE CLIMATIQUE ET ENERGETIQUE APPENDICES

Institut national des sciences appliquées de Strasbourg GENIE CLIMATIQUE ET ENERGETIQUE APPENDICES Institut national des sciences appliquées de Strasbourg GENIE CLIMATIQUE ET ENERGETIQUE APPENDICES DEVELOPMENT OF A TOOL, BASED ON THE THERMAL DYNAMIC SIMULATION SOFTWARE TRNSYS, WHICH RUNS PARAMETRIC

More information

TEST METHOD FOR STILL- AND FORCED-AIR JUNCTION-TO- AMBIENT THERMAL RESISTANCE MEASUREMENTS OF INTEGRATED CIRCUIT PACKAGES

TEST METHOD FOR STILL- AND FORCED-AIR JUNCTION-TO- AMBIENT THERMAL RESISTANCE MEASUREMENTS OF INTEGRATED CIRCUIT PACKAGES SEMI G38-0996 N/A SEMI 1987, 1996 TEST METHOD FOR STILL- AND FORCED-AIR JUNCTION-TO- AMBIENT THERMAL RESISTANCE MEASUREMENTS OF INTEGRATED CIRCUIT PACKAGES 1 Purpose The purpose of this test is to determine

More information

A Simulation Tool for Radiative Heat Exchangers

A Simulation Tool for Radiative Heat Exchangers Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 A Simulation Tool for Radiative Heat Exchangers Yunho Hwang yhhwang@umd.edu

More information

Principles and Applications of Building Science Dr. E Rajasekar Department of Civil Engineering Indian Institute of Technology, Roorkee

Principles and Applications of Building Science Dr. E Rajasekar Department of Civil Engineering Indian Institute of Technology, Roorkee Principles and Applications of Building Science Dr. E Rajasekar Department of Civil Engineering Indian Institute of Technology, Roorkee Lecture - 04 Thermal Comfort in Built Environment 2 In previous module,

More information

DEVELOPMENT OF COOLING LOAD TEMPERATURE DIFFERENTIAL VALUES FOR BUILDING ENVELOPES IN THAILAND

DEVELOPMENT OF COOLING LOAD TEMPERATURE DIFFERENTIAL VALUES FOR BUILDING ENVELOPES IN THAILAND DEVELOPMENT OF COOLING LOAD TEMPERATURE DIFFERENTIAL VALUES FOR BUILDING ENVELOPES IN THAILAND Somsak Chaiyapinunt*, Khemmachart Mangkornsaksit, and Boonyarit Phueakphongsuriya ABSTRACT This article describes

More information

ADVANCED ROOF COATINGS: MATERIALS AND THEIR APPLICATIONS

ADVANCED ROOF COATINGS: MATERIALS AND THEIR APPLICATIONS ADVANCED ROOF COATINGS: MATERIALS AND THEIR APPLICATIONS Abstract J.M. Bell 1 and G.B. Smith 2 The use of low emittance and high solar reflectance coatings is widespread in window glazings, wall and roof

More information

Energy and Buildings

Energy and Buildings Energy and Buildings 42 (2010) 29 33 Contents lists available at ScienceDirect Energy and Buildings journal homepage: www.elsevier.com/locate/enbuild A simplified calculation method for estimating heat

More information

INVESTIGATING GLAZING SYSTEM SIMULATED RESULTS WITH REAL MEASUREMENTS

INVESTIGATING GLAZING SYSTEM SIMULATED RESULTS WITH REAL MEASUREMENTS INVESTIGATING GLAZING SYSTEM SIMULATED RESULTS WITH REAL MEASUREMENTS Mark Luther 1, Timothy Anderson 2, and Tim Brain 3 1 School of Architecture and Building, Deakin University, Geelong, Australia 2 School

More information

Heat Transfer Analysis of Machine Tool Main Spindle

Heat Transfer Analysis of Machine Tool Main Spindle Technical Paper Heat Transfer Analysis of Machine Tool Main Spindle oshimitsu HIRASAWA Yukimitsu YAMAMOTO CAE analysis is very useful for shortening development time and reducing the need for development

More information

Prototype Heat Island Application

Prototype Heat Island Application CHAM Limited Pioneering CFD Software for Education & Industry Prototype Heat Island Application PHOENICS-2011 Introduction Heat islands are large-scale phenomena in which the general urban temperature

More information

Numerical Study of Convective Heat Transfer for Flat Unglazed Transpired Solar Collectors

Numerical Study of Convective Heat Transfer for Flat Unglazed Transpired Solar Collectors Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2012 Numerical Study of Convective Heat Transfer for Flat Unglazed Transpired Solar

More information

A NEW MODEL FOR ESTIMATING NEUTRAL PLANE IN FIRE SITUATION

A NEW MODEL FOR ESTIMATING NEUTRAL PLANE IN FIRE SITUATION A NEW MODEL FOR ESTIMATING NEUTRAL PLANE IN FIRE SITUATION JY Zhang¹,*, Jane WZ Lu² and R Huo¹ 1 PhD student, State Key Laboratory of Fire Science, University of Science and Technology of China, Hefei,

More information

The energy performance of an airflow window

The energy performance of an airflow window The energy performance of an airflow window B.(Bram) Kersten / id.nr. 0667606 University of Technology Eindhoven, department of Architecture Building and Planning, unit Building Physics and Systems. 10-08-2011

More information

FUNDAMENTALS OF HVAC

FUNDAMENTALS OF HVAC FUNDAMENTALS OF HVAC Prof.Dr. Yusuf Ali KARA Res.Asst. Semih AKIN 1 INTRODUCTION Terminology: HVAC: Heating, ventilating, air-conditioning and refrigerating. Air conditioning is the process of treating

More information

Greenhouse Steady State Energy Balance Model

Greenhouse Steady State Energy Balance Model Greenhouse Steady State Energy Balance Model The energy balance for the greenhouse was obtained by applying energy conservation to the greenhouse system as a control volume and identifying the energy terms.

More information

Qasim Hammodi Hassan*, Sabah Tarik Ahmed**, Ala'a Abbas Mahdi***

Qasim Hammodi Hassan*, Sabah Tarik Ahmed**, Ala'a Abbas Mahdi*** International Journal of Scientific & Engineering Research, Volume 5, Issue 4, April-2014 32 Numerical Simulation of Air Velocity and Temperature Distribution in an Office Room ventilated by Displacement

More information

In the Psy. Ch., plot point o, r, h r = 51.0 kj/kg, h o = 85 kj/kg

In the Psy. Ch., plot point o, r, h r = 51.0 kj/kg, h o = 85 kj/kg & Marking Scheme (Page 1 of 8 ) 1. (a)(i) In the Psy. Ch., plot point o, r, h r = 51.0 kj/kg, h o = 85 kj/kg SHR = rs/rt = 63/70 = 0.9 Draw a line with SHR= 0.9 from r and intercept at s or cc in such

More information

USE OF CFD TOOL ANSYS FLUENT FOR FIRE SAFETY IMPROVEMENT OF AN INDOOR SPORTS ARENA

USE OF CFD TOOL ANSYS FLUENT FOR FIRE SAFETY IMPROVEMENT OF AN INDOOR SPORTS ARENA USE OF CFD TOOL ANSYS FLUENT FOR FIRE SAFETY IMPROVEMENT OF AN INDOOR SPORTS ARENA Ondřej ZAVILA 1 Abstract: Key words: The focus of the article is the design of a HVAC (heating, ventilation and air-conditioning)

More information

Aalborg Universitet. Empirical Test Case Specification Larsen, Olena Kalyanova; Heiselberg, Per Kvols. Publication date: 2006

Aalborg Universitet. Empirical Test Case Specification Larsen, Olena Kalyanova; Heiselberg, Per Kvols. Publication date: 2006 Aalborg Universitet Empirical Test Case Specification Larsen, Olena Kalyanova; Heiselberg, Per Kvols Publication date: 2006 Document Version Publisher's PDF, also known as Version of record Link to publication

More information

THE EFFECT OF A THIN FOIL ON THE HEAT LOSSES BEHIND A RADIATOR

THE EFFECT OF A THIN FOIL ON THE HEAT LOSSES BEHIND A RADIATOR F A C U L T Y O F E N G IN E E RIN G A ND SUST A IN A B L E D E V E L OPM E N T THE EFFECT OF A THIN FOIL ON THE HEAT LOSSES BEHIND A RADIATOR Núria Barguilla Jiménez February 2013 Master s Thesis in Energy

More information

Theory & Applications of Computational Fluid Dynamics CFD

Theory & Applications of Computational Fluid Dynamics CFD جمعية رواد الھندسة والتكنولوجيا Theory & Applications of Computational Fluid Dynamics CFD Prepared and Presented By: Hesham Sami Abdul Munem Mechanical Engineer Pressure Vessels Department ENPPI Contents:

More information