Wind Pressure and Air Flow in a Full-Scale Building Model under Cross Ventilation
|
|
- Merry Martin
- 5 years ago
- Views:
Transcription
1 International Journal of Ventilation Volume No 4 Wind Pressure and Air Flow in a Full-Scale Building Model under Cross Ventilation Takao Sawachi 1, Ken-ichi Narita, Nobuyoshi Kiyota 3 Hironao Seto 1, Shigeki Nishizawa 1 and Yuumi Ishikawa 1 1 Building Research Institute, Ibaraki, Japan Nihon Institute of Technology, Saitama, Japan 3 Hiroshima Institute of Technology, Hiroshima, Japan Abstract The observation of wind pressure acting on the wall and floor of a full-scale building model under cross ventilation was carried out. The measurement of air flow was also undertaken, and the existing prediction theory of the air flow rate, namely the orifice flow equation, including the discharge coefficient, was evaluated for its accuracy. At the same time, a method of predicting the discharge coefficient has been proposed and tested. In conclusion, a tentative relationship between the discharge coefficient and the difference of wind pressure coefficient across the opening has been developed. In addition, the background concerning the difficulty of using the orifice flow equation has been described. Key words: wind pressure, cross ventilation, full scale building model, air flow rate, wind tunnel, discharge coefficient, orifice flow equation. 1. Introduction Natural ventilation is a method used to control the thermal environment (e.g. it is used for cooling) as well as to dilute pollutants. For cooling, relatively high air flow between outdoors and indoors is needed in order to dissipate the indoor heat. Openable windows are usually used for this purpose. On the other hand, for pollution control, lower rates are usually required and methods may include mechanical systems, intentional openings, which are usually smaller than windows, and/or air leakage through cracks in the building envelope. As a design tool for the pollution control objective, network simulation programs have been introduced for specialized building ventilation engineers. In network programs, the orifice flow equation provides the fundamental relationship between pressure difference and air flow rate through openings. However, for the design of cross ventilation, to achieve larger ventilation rates, there are no fully reliable practical methods to quantify the ventilation rate. This is partly because there has been doubt about the accuracy of the orifice flow equation when applied to the calculation of windinduced ventilation through larger openings. There is a hesitance to apply the orifice flow equation, because the inaccuracy has not been well defined and possible countermeasures have not been clarified. Aynsley (1988) reviewed, quite systematically, the mechanisms that cause inaccuracy of the orifice flow equation. In Vickery et al. (1987), Akabayashi et al. (1989), Murakami et al. (1991) and Kurabuchi et al.(1991, 00), a discharge coefficient in the orifice flow equation was quantified and compared with the usual value. Recently, in an international research collaboration in IEA ECBCS (Energy Conservation in Building and Community Systems), the air flow through large openings has been focused upon as an important phenomenon in the development of hybrid ventilation (Sandberg, 00).. Objective Among factors having an influence on the instability of the discharge coefficient is the air flow field around the building, including the wind angle and the inclination of incoming air flow into the opening. The question is whether it is possible to predict the variation of the discharge coefficient. If it is not possible, the second question is how to deal with the variation of the discharge coefficient when the orifice flow equation, incorporated into the network simulation, is used to calculate the wind induced ventilation rate. To approach the answers to these important questions, experimental data 343
2 T Sawachi, K Narita, N Kiyota, H Seto, S Nishizawa and Y Ishikawa Fan Inlet Outlet Working Section Reference Pressure Outlet Inlet Opening Full Scale Model Turn Table 9000 Honeycomb (a) 36 measurement points on the roof Inlet Outlet Turn Table 9500 þ Honeycomb Working Section Outlet Inletopening Opening Ñ öùo (b) 60 measurement points on the facade (Dimenssion in mm) Figure 1. Section (top) and plan (bottom) of BRI s cross ventilation laboratory wind tunnel. (c) 66 measurement points on the façade with an opening Figure. Positions of the pressure measurement points on the roof and wall. obtained in a wind tunnel with a full-scale building model (Sawachi et al., 1999 and Sawachi, 00), are analysed and a practical direction for solving the problem is searched for. 3. Methods and Experimental Plan 3.1 Description of the Main Research Facility and the Building Model For the air flow and pressure measurement, as well as for the visualization of cross ventilation in buildings, a wind tunnel was specially designed so that a full-scale experiment could be undertaken. Its section and plan are shown in Figure 1. The wind speed range in the working section is m/s, and its distribution was checked to be close to 344 uniform before the construction of the building model (Sawachi et al., 1999). The turbulence intensity is less than 5% at the inlet to the working section, and the temperature can be controlled below 5 C. The dimensions of the present building model are 5.6m x 5.6m x 3.0m, and its blockage ratio is 1% of the cross sectional area of the working section, and 34% of the inlet area. Due to the uniform air velocity in the inlet of this wind tunnel design and to the higher blockage ratio, the wind pressure on the building model should be different from that obtained in conventional wind tunnels having a vertical profile of wind speed with a much lower blockage ratio. In this project, the measurement at full-scale and the reproducibility of the wind pressure condition were critical requirements. As a future necessity for the wind
3 International Journal of Ventilation Volume No A D A-1 A- A-3 A-4 A-5 A-6 A-7 A-8 A-9 A-10 A-1 1 A-1 A-13 A-14 A-15 A-1 6 A-17 A-18 A-19 A-0 A- 1 A- A-3 A-4 A C-1 C- C-3 C-4 C-5 C-6 C-7 C-8 C-9 C-10 C-11 C-1 C-13 C-14 C-15 C-16 C-17 C-18 C-19 C-0 C-1 C- C-3 C-4 C P9,P P6 P5 B 5530 P10,P14 P B-1 B-6 B- B-7 B-3 B-8 B-4 B-9 B-5 B D-1 D- D-6 D-7 D-3 D-4 D-5 D-8 D-9 D B-1 1 B-1 B-13 B-1 6 B-17 B-18 B-14 B-15 B-19 B-0 D-11 D-1 D-13 D-14 D-15 D-16 D-17 D-18 D-19 D P4 P7,P11 P P1 50mm B- 1 B- B-3 B-4 B D-1 D- D-3 D-4 D-5 B D (a) Pressure Measurement Points on the Floor Figure-3 Measurement Points for Pressure Distribution (a) and for among Pressures and Velocity in the Openings (b) P9 B 6-10 Wind Angle Œ ü Anemometers ª è _ Pressure ˆ³ Í Meas. ª è _ P A 840 A 480 WA-390 P7 P8 5-1 P13 P14 P11 P1 DA P8,P1 (b) Pressure Measurement Points (Simultaneous) on the Floor and the Wall mm 30mm TR-90T Type Probe Figure 3. Measurement points for pressure distribution (a) and for correlation among pressures and velocity in the openings (b). Figure-4 4. Shape Shape and Dimension and dimensions of the Probe of for 3D Anemometer the probe for the 3D anemometer. pressure coefficient itself, it is planned to undertake conventional type wind tunnel measurements incorporating scale building models and surrounding structures. 3. Wind Pressure on the Wall and Floor under Cross Ventilation The wind pressure was measured using differential pressure transducers (MKS Baratoron 0C) and scanning valves (SCANIVALVE), with hard plastic tubes connecting from behind the pressure taps. The pressure taps themselves comprised short aluminium tubes buried in the surface of the wall, etc. without any protrusion, connected to the scanning valves. Figure shows the positions of the pressure taps on the roof and the wall. When openings are installed on the wall, some additional pressure taps are installed in the periphery of the openings. Figure 3 (a) shows the positions of the pressure taps on the floor inside the building. When the simultaneous measurement of wind pressure at different positions is necessary, the number of taps is reduced to the number of the differential pressure transducers available as shown in Figure 3 (b). In one experiment, the ten pressure taps P1, P6, P7- P14 were used, and in another experiment the six pressure taps P1-P6 were used. 3.3 Three Dimensional Air Flow Inside the Building and its Visualisation Two types of ultra-sonic three-dimensional anemometers were used for measuring air flow; these were:- KAIJO type WA-390 (having a response time of 0.5 second) and KAIJO type DA- 600 (having a response time of 0.05 second). Both types have a common type probe, with dimensions as shown in Figure 4. The horizontal location of the measurement points is shown in Figure 5 (a) for inside and near the building model. Measurements were undertaken at five different heights, i.e:- 30 mm, 710 mm, 1,190 mm, 1,670 mm and,100 mm above the floor. Figure 5 (b) illustrates the locations of the air flow measurement points outside the building model. Data acquisition was undertaken at 10Hz for at least three minutes. More direct observation was obtained by visualization using a SPECTRA-PHYSICS STABILITE 017 and NARK CORP. FIBER HEAD laser light sheet combined with smoke generation. Two different ways of smoke generation were tried. The first was a decay method, in which the openings in the enclosure were closed and filming started after filling the interior space with smoke. The second was a constant generation method, in which the smoke was generated constantly and sourced mainly 345
4 T Sawachi, K Narita, N Kiyota, H Seto, S Nishizawa and Y Ishikawa ; ; ; ; ; ; ; ; ; ; ; ; ; ; ; ; ; Ñ Pf;ã_ù (a) Horizontal Locations of 3D Airflow Measurement inside and near the Building Model = ; = = = = = ; L]ùoPf; ; ; ; ; ; ; ; ; ; ; ; ;[ ; ; ; ; ; ; ; ; ; ; ; Ñ _ Çyù o (b) Horizontal Locations of 3D Airflow Measurement in the Working Section of the Wind Tunnel Figure 5. Measurement points for the 3D air flow. (a) Anemometers in the opening ; ; ; ; ; ; (b) 48 Points for Airflow Measurement in the Opening Figure 6. Measurement of air flow in openings and ventilation rate. X3 in front of the opened inflow opening. In both methods, the laser light sheet was emitted through four lenses, which were installed at each corner of the room (Figure 3 (b)). 3.4 Three Dimensional Air Flow in the Openings and its Visualization The same anemometers were used for the measurement of air flow in the openings, as shown in Figure 6 (a). Figure 6 (b) represents typical air flow measurement points in the opening which is 860 mm wide and 1,740 mm high. Four anemometers attached to a pole were manually traversed to complete the three-dimensional air speed measurement at 48 points in the opening as shown in Figure 6 (b). The length of the vector along the X-axis, which is normal to the opening plane, was multiplied by its representing opening area to give a flow rate in cubic metres per hour. All flow rates for divided areas were summed to give the total flow rate through the entire single opening. Although all 48 vectors were not measured simultaneously, the average air flow vectors, which were calculated from instantaneous data at 10 Hz for three minutes, appeared to be sufficiently accurate to calculate the total flow rate through the opening. 4. Results 4.1 Wind Pressure Distribution on the Wall and the Floor under Cross Ventilation The wind pressure was measured as a pressure difference from the reference static pressure near the top of the wind tunnel s inlet (see Figure 1), and was expressed as a wind pressure coefficient with a dynamic pressure at a reference wind speed, 3m/s, as a denominator. The wind pressure coefficients on the opening were determined by using the pressure data at six points located inside the area for the openings, as shown in Figure and Figure 6 (b). Figure 7 illustrates the pressure distribution on the walls and the floor of the building model for two openings located diagonally to each other. 4. Air Flow Inside and Around the Building The two-dimensional vectors on the horizontal plane at the centre height of the walls (1,190 mm above the floor) for different wind angles are shown in Figure 8. The wind pressure coefficients of points adjacent to the openings are shown at the top of each figure. In addition, the correlation coefficients between the pressure of different points are shown at the bottom. 346
5 International Journal of Ventilation Volume No Figure 7. Distribution of wind pressure coefficient on the wall and floor under cross ventilation. 347
6 T Sawachi, K Narita, N Kiyota, H Seto, S Nishizawa and Y Ishikawa C p beside Opening A C p beside C p beside Opening A C p beside C p beside Opening A C p beside #? % $? % #? % $? % #? % $? % Opening #?A #? % C p beside Opening A #? Opening A $? Wind Angle 0 $? % C p beside #? Opening A #? % C p beside Opening A $? Opening #? A $? $? % #? Opening A Wind Angle 15 C p beside #? % C p beside Opening A #? Opening A Wind Angle 30 $? % C p beside #? % $? C p beside Opening A C p beside Opening #? A Wind Angle 45 $? % #? % $? % C p beside Opening A C p beside Opening #? A Wind Angle 60 #? % C p beside Opening A #? Wind Angle 75 $? % C p beside Opening A #? % C p beside Opening A $? % C p beside Opening A #? #? % C p beside Opening A $? % C p beside #? #? % C p beside Opening A Opening $?B Opening $? B Opening $?B Wind Angle 90 Wind Angle 105 Opening A Wind Angle 10 $? % C p beside #? Opening A Opening $?B Wind Angle 135 Figure 8. Air Flow inside the building and its surroundings Wind Angle 150 Wind Angle 165 FIGURE-9 AIRFLOW INSIDE THE BUILDING AND ITS SURROUNDINGS,
7 International Journal of Ventilation Volume No 4 Ventilation Rate in m3/h 1.0E E E E E+03.00E E Air Flow in the Openings The same three-dimensional anemometers as those used for the measurement inside and near the building, were used for the measurement of air flow through the opening, especially for the measurement of the ventilation rate. The ventilation rate for different wind angles is shown in Figure 9. It can be said that the main cause of changes in flow rate is the change of the wind pressure acting on the openings, but there is another factor, which will be discussed later. The ventilation rate was based on the sum of the flow rate measured through 48 areas in the opening. For each of the 48 areas, an instantaneous air speed at a representing point was measured for 180 seconds at 10 Hz. It was found that both inflow and outflow could coexist at a single opening. Moreover, at some points, the direction of the flow could change from time to time. Figure 10 shows such a situation for all wind angles. For example, in the inflow opening for a wind angle of 10, in the columns Y1 to Y3, stable inflow was observed, while in column Y6, stable outflow was observed. Figure 11 shows the time change of the vectors over two seconds at the medium height of the openings. 5. Analysis Wind Angle in Degree Figure 9. Ventilation rate and wind angle at 3m/s wind speed. 5.1 Calculation of the Discharge Coefficient by using the Difference between the Wind Pressure on the Area of the Closed Opening and on the Floor for Cross Ventilation The wind pressure coefficient is usually measured by using bluff scale models of buildings. In network simulation programs, these coefficients are used as input data for calculating air flow and internal static Wind Angle 0 Inflow Opening Wind Angle 15 Wind Angle 30 Wind Angle 45 Inflow Opening Inflow Opening Inflow Opening $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ + + $ ;;;;;; ;;;;;; ;;;;;; ;;;;;; Outflow Opening Outflow Opening Outflow Opening Outflow Opening $ $ $ $ $ $ $ $ $ $ $ $ $ 1 $ 1 1 $ ;;;;;; ;;;;;; ;;;;;; ;;;;;; Wind Angle 60 Wind Angle 75 Wind Angle 90 Wind Angle 105 Inflow Opening Inflow Opening Inflow Opening Inflow Opening $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ ;;;;;; ;;;;;; ;;;;;; ;;;;;; Outflow Opening Outflow Opening Outflow Opening Outflow Opening $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ 1 $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ 1 1 $ $ $ $ $ $ $ $ $ $ $ $ ;;;;;; ;;;;;; ;;;;;; ;;;;;; Wind Angle 10 Wind Angle 135 Wind Angle 150 Wind Angle 165 Inflow Opening Inflow Opening Inflow Opening Inflow Opening $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ ;;;;;; ;;;;;; ;;;;;; ;;;;;; Outflow Opening Outflow Opening Outflow Opening Outflow Opening $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ ;;;;;; ;;;;;; ;;;;;; ;;;;;; Figure 10. Air flow directions at 48 points for 3D instantaneous air velocity measurement in the openings. I - constant inflow, O - constant outflow and B - points at which a bi-directional air flow was observed. See Figure 6b for locations of measurement points. pressures, etc. A similar procedure was tried in order to identify discharge coefficients by analysing the experimental data, although the adequacy of the approximation of using the exterior wind pressure in a building model without openings could be an important issue. The adequacy seems to depend 349
8 T Sawachi, K Narita, N Kiyota, H Seto, S Nishizawa and Y Ishikawa Average t=.0s t=0.0s Average Wind Angle 0G Opening A Wind Angle 15G Wind Angle 30G Wind Angle 45 Wind Angle 60 Wind Angle 75 +1[mmAq] 1 3 [m/s] -1[mmAq] Figure 11a. Time average and transition in seconds of the air flow vectors in the openings, and wind pressure beside the openings (for wind angles 0 to 75º). upon the size of the openings that are actually present. In the present experiment, the ratio of the opening area to façade area was around 9%. When network calculations are made of air leakage through narrow cracks, i.e. representing only a very small fraction of total envelope area, the adequacy of using wind pressure coefficients based on bluff buildings has not yet been questioned. The effect of openings on the change of wind pressure on their surrounding area can be found in Figure 7. For example, when comparing the pressure distribution on the windward façade of 0 wind angle with that on the windward façade of 90 wind angle, the information about the change can be obtained. Further comparison is possible by using pressure distribution data based on the totally bluff building model (Figure 1). Except at the vicinity of the openings, no clear change of wind pressure coefficient was found between Figures 7 and
9 International Journal of Ventilation Volume No 4 Average t=.0s t=0.0s Average Wind Angle 90 Opening A Wind Angle 105 Wind Angle 10 Wind Angle 135 Wind Angle 150 Wind Angle [mmAq] 1 3 [m/s] -1[mmAq] Figure 11b. Time average and transition in seconds of the air flow vectors in the openings, and wind pressure beside the openings (for wind angles 90 to 165º). Table 1 gives the results for the determination of wind pressure coefficients and discharge coefficients for different wind angles. Figure 13 shows the average wind pressure coefficient on the exterior wall in the area of the openings and on the floor under conditions of cross ventilation. Since measurements on the floor were divided into four quadrants, the results for each quadrant are presented and are very similar to each other. Figure 14 shows the calculated discharge coefficients based on the wind pressure results of Figure 13 and the ventilation rate given in Figure 9. The horizontal line represents the discharge coefficient of a scale model of the opening, which was measured by the conventional procedure usually used for components of ventilation systems, such as vents, ducts, terminal devices, etc. As shown in Figure 14, the discharge coefficient of the opening (300 mm x 150 mm x 19 mm), which was attached to the pressurized chamber, is As for the inflow 351
10 T Sawachi, K Narita, N Kiyota, H Seto, S Nishizawa and Y Ishikawa Figure 1. Distribution of wind pressure coefficient on the wall without openings and on the roof. (To be compared with Figure 7 for the building with openings). Table 1. Experimental results on wind pressure coefficient and discharge coefficient for different wind angles. 9KPF # PING 8GPVKNCVKQP 9 KPF TGUUWTG % QGHHKEKGPV & KUEJCTIG % QGHHKEKGPV & GITGG 4CVG O J 1RGPKPI # 1RGPKPI $ (NQQT #XGTCIG % QO DKPGF +PHNQY 1 WVHNQY 0QVG&CVC KP RCTGPVJGUGU UGGO U VQ EQPVCKP WPCEEGRVCDNG O GCUWTGO GPV GTTQTUKPEG VJG HNQQT CXGTCIG RTGUUWTG KU PQV DGVY GGP VJG Y KPF RTGUUWTG QP VY Q QRGPKPIU+P FGITGG QPN[ FGNKECVG RTGUUWTG FKHHGTGPEG GZKUVU DGVY GGP VJG VY Q QRGPKPIU Wind Pressure Coefficient Opening A Floor Average Floor B Floor D Floor A Floor C Wind Angle (Degree) Figure 13. Wind pressure coefficient on the exterior wall and on the floor under cross ventilation. Discharge Coefficient Inflow Opening Outflow Opening Combined a= Wind Angle (Degree) Figure 14. Discharge coefficient calculated by using the wind pressure and the ventilation rate.
11 International Journal of Ventilation Volume No 4 opening, at wind angles of 0-30, the discharge coefficient is close to that of the reference discharge coefficient of A minimum value of 0.6 occurs at wind angles of 90 and 105. At 15, the discharge coefficient exceeds the reference value by The average in the range between 0 and 165 is As for the outflow opening, for wind angles of 0-45, 150 and 165, the discharge coefficient is close to the reference value. A maximum value of 0.74 is seen at a wind angle of 60. The average in the range between 0 and 165 is Factors Influencing the Discharge Coefficient Depending on wind angle, the ventilation rate varied from 400 m 3 /h (90 ) to 9,700 m 3 /h (15 ), even although the outside wind speed was kept constant at 3 m/s. The relationship between the ventilation rate (expressed by the average air speed in the opening divided by the outside wind speed) and the discharge coefficient is shown in Figure 15. For the inflow opening, there is a clear linear relationship, expressed by Equation 1. α=0.75k+0. (1) where α is the discharge coefficient and k is the average air speed (m/s) in the opening divided by the outside wind speed (3 m/s). Even at the maximum value of k of 0.6 in the present experiment, the decrease seems to begin. For the outlet opening, the discharge coefficient does not decrease in the range where k is above 0.5. Below this range, the following tentative relationship, given by Equations and 3 could be supposed, although there is a lower discharge coefficient found at a wind angle of 75 : α=1.7k+0. () Q 3,600. A ûc pi k = = =. ûc pi (3) 3,600A 3,600A where Cpi is the difference of the wind pressure coefficient across the opening, i, Q is the flow rate in m 3 /h, A is the opening area in m, and υ is the reference outside wind speed in m/s. As the ratio of the average air speed in the inlet opening to the outside wind speed decreases, the discharge coefficient of the inlet opening decreases linearly. On the other hand, the discharge coefficient of the outlet opening does not decrease in the range of k > 0.5. There is no neighbourhood building around the building model in the present experiment, and the ratio of the air speeds is likely to represent the relative strength of the inflow relative to the outside air speed in the upstream region. As for the outflow opening, if it is assumed that the air speed inside the building is proportional to the ventilation rate, the ratio of the average speed of the outflow opening to the air speed in the upstream region in the building is stable. This can be the reason why the discharge coefficient for the outflow opening does not decrease when k is above 0.5. When k becomes lower than 0.5, the outside air speed in the downstream area of the outflow opening might be influential on the discharge ςdischarge Coefficient α=1.7k+0. () Inflow Opening Outflow Opening k, the ratio of the average air speed in the opening to the outside wind speed 353 α=0.75k+0. (1) Figure 15. Discharge coefficients of the inflow and outflow openings and their relationship with k.
12 T Sawachi, K Narita, N Kiyota, H Seto, S Nishizawa and Y Ishikawa., Discharge Coefficient Þ = ÂC Inflow Opening Outflow Opening , Squareroot of the Difference of Wind Pressure Coefficient  C p p () Þ =  C p (1) Figure 16. Relationship between discharge coefficient and wind pressure coefficient. coefficient of the opening. If the building is surrounded with other buildings, the reference outside wind speed does not necessarily represent the air speed in the upstream area of the inflow opening nor that in the downstream area of the outflow opening. In such a case, the air speed near the openings might be much lower than the reference outside wind speed. In such a situation, the discharge coefficient might stay higher even when k is less than 0.6 for the inflow opening and greater than 0.5 for the outflow opening. The relationship between the difference of wind pressure coefficient across the opening and the discharge coefficient, can be obtained by substituting Equation 3 into Equations 1 and, as follows:.. 0. = (4) ûc p 1 0. = (5) ûc p Figure 16 shows the relationship between the discharge coefficient, α, and the square root of û pi. Equations such as Equations 4 and 5 can be useful when they are applied to network programs to calculate the air flow pattern and pressures by iteration. In the iteration process, the discharge coefficient is changeable as well as the internal pressure and the flow rate, before convergence. In Figure 8, the pattern of air flow from the upstream area of the inflow opening to the downstream area of the outflow opening is presented. The inclination of the inflow against the façade of the building seems to be determined by the outside air flow direction. At 15, air inflow comes through the opening most vertically, while at other wind angles the inflow is usually inclined to the plane of the opening. This means that even if the shape of the opening does not change the shape of the air flow before, through, and after the opening changes. In the present series of experiments, the shape of the air flow pattern around the opening was found to be affected by:- the wind angle, the existence of the walls including the wall with the opening itself, and by the building. More detailed information about the air flow in the opening is given in Figure 11, where fluctuating vectors of the air flow are shown for a number of two-second records. There are three types of points, namely, constant inflow, constant outflow and bi-directional. At the bi-directional points, the air flow direction (inflow/outflow) changes over time. It seems natural that the orifice flow equation should lose its accuracy, to some extent, when the air flow direction through the opening is not stable. In that case, the average of the air flow rate might not necessarily represent the ventilation rate due to the air exchange through a single opening. Figure 10 shows the air flow for openings at 48 locations of air flow measurement. At wind angles of , almost all points are bi-directional points. 5.3 Distribution of Wind Pressure on the Floor Figure 7 contains the distribution of the wind pressure on the floor in the building. There are some 354
13 International Journal of Ventilation Volume No 4 parts with slightly higher or lower wind pressure compared with their surrounding area. For example, at a wind direction of 15, there is an area of slightly higher wind pressure on the right hand side of the inflow opening to the end of the room opposite to the inflow opening. Although these deviations in floor pressure from the average is almost negligible, compared to the pressure difference across the openings, it seems necessary to describe the change in floor pressure and to identify its causes. This mmaq Along the Flow Tube Average of Overall Floor (96 Points) Point No. 15 Wind Angle X3 Wind Angle 15 mmaq Along the Flow Tube Average of Overall Floor (96 Points) Point No X Wind Angle 60 mmaq Along the Flow Tube Average of Overall Floor (96 Points) Point No Wind Angle 165 mmaq Along the Flow Tube Average of Overall Floor (96 Points) Point Figure 17. Transition of the floor wind pressure along the flow tube at wind angle 0, 15, 60 and
14 T Sawachi, K Narita, N Kiyota, H Seto, S Nishizawa and Y Ishikawa Figure 18. Two dimensional vertical vectors on section X3-X3 (see Figure 16) at wind angle 15. knowledge is useful when one is choosing the location of pressure measurements in other situations such as in field measurements. Figure 17 shows the transition of the wind pressure on the floor along the flow tube compared to a horizontal line representing the average pressure on the floor. At 0, for points -4, slightly higher pressure occurs and at points 7,8 and 10, slightly lower pressure occurs. At 15, in the centre of the flow tube just after entering the opening, points 3-5 show a slightly lower pressure and around the location where the flow tube changes its direction to the left, higher pressure can be observed at points 7-9. Figure 18 shows the two-dimensional vectors for the section X3-X3 for a wind direction of 15. After entering the opening, very vertically, the air goes straight and strikes the end wall opposite to the opening. The flow near the wall turns back toward the inlet opening along the floor surface and meets the incoming air on the way around at points 7-8. At 60, the flow tube hits the wall just before the outflow opening around points 9-11, where the pressure increases slightly. Before these points, slightly lower pressure is observed at points 3-6. Though these local changes of the pressure can be observed, there is no measurable consistent decline of the wind pressure on the floor along the flow tube. It seems that the total pressure does not decrease sensitively in this cross-ventilated room. If the room was narrow enough, such as a duct, there would be friction loss of the total pressure. 6. Conclusions 1) The discharge coefficient in the orifice flow equation for openings tends to decrease depending upon the ratio of the air speed in the openings to the outside velocity. It seems natural that the air flow resistance of openings, with identical shape, should change depending upon the shape of the air flow before and after the opening. Also, the shape of the air flow is affected considerably by the outside air speed and direction. The ratio of the air speed in the opening to the outside velocity seems to be the factor that causes the shape of the air flow through the opening to be influenced by the outside air flow. However, the mechanism has not yet been clarified and needs further investigation. The characteristics of flow at the inlet opening and outlet opening showed differences. In only a few conditions was the discharge coefficient found to be larger than 0.63 (used as a reference value) measured under static pressure difference. ) It seems that it is natural for there to be a limitation for the accurate prediction of the discharge coefficient in cross ventilation through relatively large openings. It is because, in a single opening, a constant coexistence of both inflow and outflow was observed. Moreover, at some points, the direction of air flow was found to change over time. This was especially observed for wind directions between , as shown in Figures 10 and 11. 3) However, a tentative relationship between the discharge coefficient and the difference of wind pressure coefficient across the opening, has been drawn, as shown in Figure 16. Although the relationship seems to be promising for application in network simulations, additional data and validation is necessary. 4) The measurement result of the floor wind pressure shows considerably even distributions except for the area near the place where the flow tube hits the wall or where the flow changes direction. 356
15 International Journal of Ventilation Volume No 4 Acknowledgements This research is funded by Grants-in-Aid for Scientific Research of Japan Society for the Promotion of Science, as No of Category A. Building Research Institute and Ministry of Land, Infrastructure and Transportation funded for the construction of the wind tunnel used for this research, and the related research projects. These are gratefully acknowledged. References Aynsley RM: (1988) A resistance approach to estimating air flow through buildings with large openings due to wind, ASHRAE Transactions, pp , Akabayashi S, Murakami S and Kato S, Hasegawa K and Kim E: (1989) Study on pressure loss coefficient at opening set in housing wall, Summaries of Tech. Papers of Annual Meeting, Architectural Inst. of Japan, Vol. D, pp Etheridge D and Sandberg M: (1996) Building ventilation - theory and measurement, John Wiley & Sons. Kurabuchi T and Kamata M: (1991) Numerical simulation of the combined internal and external airflow for cross ventilation of buildings by means of the multi-mesh method, J. of Architectural Plan. and Environ. Eng., AIJ, (46), pp1-11. Kurabuchi T, Ohba M, Fugo Y and Endoh T: (00) Local similarity model of cross ventilation, Parts 1 and, Proceedings of ROOMVENT 00, September 8-11, Copenhagen. Melikov AK and Sawachi T: (199) Low velocity measurements: Comparative study of different anemometers, Proceedings of ROOMVENT 9, September -4, Aalborg. Murakami S, Kato S, Akabayashi S, Mizutani K and Kim YD: (1991) Wind tunnel test on velocitypressure field of cross-ventilation with open windows, ASHRAE Transactions, 97, Part.1, pp Sandberg M: (00) Wind induced airflow through large openings: Summary - principles of hybrid ventilation (Edited by Per Heiselberg), Aalborg University. Sawachi T, Kiyota N and Kodama Y: (1999) Air flow and wind pressure around a full-size cubical building model in a wind tunnel, Proc. of the PLEA 99 Conference,, pp Sawachi T: (00) Detailed observation of cross ventilation and airflow through large openings by full scale building model in wind tunnel, Proceedings of ROOMVENT 00, September 8-11, Copenhagen. Vickery BJ and Karakasanis C: (1987) External wind pressure distributions and induced internal ventilation flow in low-rise industrial and domestic structures, ASHRAE Transactions, pp
16 T Sawachi, K Narita, N Kiyota, H Seto, S Nishizawa and Y Ishikawa 358
Experimental Evaluation of the Discharge Coefficient of a Centre-Pivot Roof Window Iqbal, Ahsan; Afshari, Alireza; Heiselberg, Per Kvols; Høj, Anders
Aalborg Universitet Experimental Evaluation of the Discharge Coefficient of a Centre-Pivot Roof Window Iqbal, Ahsan; Afshari, Alireza; Heiselberg, Per Kvols; Høj, Anders Published in: Proceedings of CLIMA
More informationBuoyancy-Driven Single-Sided Natural Ventilation in Buildings with Large Openings Yi Jiang a and Qingyan Chen b,*
Jiang, Y. and Chen, Q. 3. Buoyancy-driven single-sided natural ventilation in buildings with large openings, International Journal of Heat and Mass Transfer, 46(6), 973-988. Abstract Buoyancy-Driven Single-Sided
More informationBuilding and Environment
Building and Environment 45 (2010) 2273e2279 Contents lists available at ScienceDirect Building and Environment journal homepage: www.elsevier.com/locate/buildenv The loss factors of building openings
More informationIMPACT OF THE ATMOSPHERIC BOUNDARY LAYER PROFILE ON THE VENTILATION OF A CUBIC BUILDING WITH TWO LARGE OPPOSITE OPENINGS
Ninth International IBPSA Conference Montréal, Canada August 15-18, 2005 IMPACT OF THE ATMOSPHERIC BOUNDARY LAYER PROFILE ON THE VENTILATION OF A CUBIC BUILDING WITH TWO LARGE OPPOSITE OPENINGS Alain BASTIDE,
More informationNUMERICAL AND EXPERIMENTAL INVESTIGATIONS OF AIR FLOW AND TEMPERATURE PATTERNS OF A LOW VELOCITY DIFFUSER
NUMERICAL AND EXPERIMENTAL INVESTIGATIONS OF AIR FLOW AND TEMPERATURE PATTERNS OF A LOW VELOCITY DIFFUSER M Cehlin and B Moshfegh Division of Energy and Mechanical Engineering, Department of Technology,
More informationEXPERIMENTAL STUDY OF THE DISCHARGE COEFFICIENT
The Seventh Asia-Pacific onference on Wind Engineering, November 8-1, 009, Taipei, Taiwan EXPERIMENTAL STUDY OF THE DISHARGE OEFFIIENT OF INTERNAL OPENINGS IN PARTITIONED BUILDINGS hia R. hu 1 and Yu-Wen
More informationVARIETY MODES AND CHAOS IN SMOKE VENTILATION BY CEILING CHAMBER SYSTEM. Katsumichi NITTA
VARIETY MODES AND CHAOS IN SMOKE VENTILATION BY CEILING CHAMBER SYSTEM Katsumichi NITTA Prof., Dr.Eng. Department. Architecture and Design, Faculty of Engineering and Design, Kyoto Institute of Technology.
More informationThe energy performance of an airflow window
The energy performance of an airflow window B.(Bram) Kersten / id.nr. 0667606 University of Technology Eindhoven, department of Architecture Building and Planning, unit Building Physics and Systems. 10-08-2011
More informationStudy on Stack Effect of Stairwell by Numerical Model of Leakage Flow through Gap of Door
Open Journal of Fluid Dynamics, 13, 3, 41-47 Published Online December 13 (http://www.scirp.org/journal/ojfd) http://dx.doi.org/1.436/ojfd.13.349 Study on Stack Effect of Stairwell by Numerical Model of
More informationCFD Prediction of Airflow in Buildings for Natural Ventilation. Robert N. Meroney. Prepared for. 11 th Americas Conference on Wind Engineering
CFD Prediction of Airflow in Buildings for Natural Ventilation Robert N. Meroney 1 Emeritus Professor of Civil Engineering, Colorado State University, Robert.Meroney@Colostate.Edu Prepared for 11 th Americas
More informationAn Experimental Investigation to Control the Flow Emerging From a Wide Angle Diffuser
IOSR Journal of Engineering (IOSRJEN) ISSN: 5-3 ISBN: 878-879 PP 7-3 National Symposium on engineering and Research An Experimental Investigation to Control the Flow Emerging From a Wide Angle Diffuser
More informationHVAC Clinic. Duct Design
HVAC Clinic Duct Design Table Of Contents Introduction... 3 Fundamentals Of Duct Design... 3 Pressure Changes In A System... 8 Example 1... 13 Duct Design Methods... 15 Example 2... 15 Introduction The
More informationCharacterization of the Airflow from a Bottom Hung Window under Natural Ventilation
Downloaded from vbn.aau.dk on: March 2, 219 Aalborg Universitet Characterization of the Airflow from a Bottom Hung Window under Natural Ventilation Svidt, Kjeld; Heiselberg, Per; Nielsen, Peter V. Publication
More informationEE-489 Modeling Project: Behavior of the. Temperature Changes in a Room
EE-489 Modeling Project: Behavior of the 1 Temperature Changes in a Room Younes Sangsefidi, Saleh Ziaieinejad, Tarik Wahidi, and Takouda Pidename, Abstract A precise heat flow model, which predicts the
More informationSTUDY ON THE THERMAL PERFORMANCE AND AIR DISTRIBUTION OF A DISPLACEMENT VENTILATION SYSTEM FOR LARGE SPACE APPLICATION
STUDY ON THE THERMAL PERFORMANCE AND AIR DISTRIBUTION OF A DISPLACEMENT VENTILATION SYSTEM FOR LARGE SPACE APPLICATION K Sakai 1*, E Yamaguchi 2, O Ishihara 3 and M Manabe 1 1 Dept. of Architectural Engineering,
More informationFACULTY OF CHEMICAL & ENERGY ENGINEERING FLUID MECHANICS LABORATORY TITLE OF EXPERIMENT: MINOR LOSSES IN PIPE (E4)
FACULTY OF CHEMICAL & ENERGY ENGINEERING FLUID MECHANICS LABORATORY TITLE OF EXPERIMENT: MINOR LOSSES IN PIPE (E4) 1 1.0 Objectives The objective of this experiment is to calculate loss coefficient (K
More informationStandard Practices for Air Speed Calibration Testing
Standard Practices for Air Speed Calibration Testing Rachael V. Coquilla Bryza Wind Lab, Fairfield, California Air speed calibration is a test process where the output from a wind measuring instrument
More informationChemical Engineering 3P04 Process Control Tutorial # 1 Learning goals
Chemical Engineering 3P04 Process Control Tutorial # 1 Learning goals 1. Sensor Principles with the flow sensor example 2. The typical manipulated variable: flow through a conduit Sensors: We need them
More informationDEFINING THE PERFORMANCE OF THE DOUBLE SKIN FAÇADE WITH THE USE OF THE SIMULATION MODEL
Eighth International IBPSA Conference Eindhoven, Netherlands August -4, 003 DEFINING THE PERFORMANCE OF THE DOUBLE SKIN FAÇADE WITH THE USE OF THE SIMULATION MODEL Wojtek Stec & Dolf van Paassen Energy
More informationInvestigation of Opening Positions on the Natural Ventilation in a Low-Rise Building by CFD Analysis
Proceedings of the 3 rd International Conference on Fluid Flow, Heat and Mass Transfer (FFHMT 16) Ottawa, Canada May 2 3, 2016 Paper No. 151 Investigation of Opening Positions on the Natural Ventilation
More informationElectrostatic Precipitator Utilizing Gradient-force
Proc. ESA Annual Meeting on Electrostatics 2013 1 Electrostatic Precipitator Utilizing Gradient-force Atsushi Katatani Department of Business Development & Promotion Panasonic Environmental Systems & Engineering
More informationA Numerical Analysis of Indoor Thermal Environment and Human Thermophysiological Responses under Natural Ventilation S. Iizuka 1,*, T. Sakoi 2, T. Sai
A Numerical Analysis of Indoor Thermal Environment and Human Thermophysiological Responses under Natural Ventilation S. Iizuka 1,*, T. Sakoi 2, T. Saito 1, and S. Kuno 1 1 Graduate School of Environmental
More informationSimplified Numerical Models for Complex Air Supply Diffusers Jelena Srebric *, Ph.D.
Srebric, J. and Chen, Q. 2002. Simplified numerical models for complex air supply diffusers, HVAC&R Research, 8(3), 277-294. Simplified Numerical Models for Complex Air Supply Diffusers Jelena Srebric
More informationExperimental Investigation of the Aerodynamic Forces and Pressures on Dome Roofs: Reynolds Number Effects
Experimental Investigation of the Aerodynamic Forces and Pressures on Dome Roofs: Reynolds Number Effects *Ying Sun 1), Ning Su 2), Yue Wu 3) and Qiu Jin 4) 1), 2), 3), 4) Key Lab of Structures Dynamic
More informationME332 FLUID MECHANICS LABORATORY (PART I)
ME332 FLUID MECHANICS LABORATORY (PART I) Mihir Sen Department of Aerospace and Mechanical Engineering University of Notre Dame Notre Dame, IN 46556 Version: January 14, 2002 Contents Unit 1: Hydrostatics
More informationNatural Ventilation. CFD modelling of a double-skin facade. Huw Birch. Supervisor: Abigail Hathway
Natural Ventilation CFD modelling of a double-skin facade Huw Birch Supervisor: Abigail Hathway Introduction Given the high energy demands of traditional mechanical ventilation systems such as humidifiers,
More informationAalborg Universitet. Published in: Proceedings of Roomvent Publication date: 2007
Aalborg Universitet On the Use of Hot-Sphere Anemometers in a Highly Transient Flow in a Double-Skin Facade Jensen, Rasmus Lund; Larsen, Olena Kalyanova; Hyldgård, Carl Erik Published in: Proceedings of
More informationFEDSM AERODYNAMIC NOISE SIMULATION OF PROPELLER FAN BY LARGE EDDY SIMULATION
Proceedings of FEDSM27 5th Joint ASME/JSME Fluids Engineering Conference July 3-August 2, 27 San Diego, California USA FEDSM27-37145 AERODYNAMIC NOISE SIMULATION OF PROPELLER FAN BY LARGE EDDY SIMULATION
More informationStudy on under-floor flow to reduce ballast flying phenomena. Railway Technical Research Institute, Tokyo, Japan 1
Study on under-floor flow to reduce ballast flying phenomena 1 A.Ido, S.Saitou, K.Nakade, S.Iikura Railway Technical Research Institute, Tokyo, Japan 1 Abstract Between under-floors of cars and tracks,
More informationUSE OF CFD TOOL ANSYS FLUENT FOR FIRE SAFETY IMPROVEMENT OF AN INDOOR SPORTS ARENA
USE OF CFD TOOL ANSYS FLUENT FOR FIRE SAFETY IMPROVEMENT OF AN INDOOR SPORTS ARENA Ondřej ZAVILA 1 Abstract: Key words: The focus of the article is the design of a HVAC (heating, ventilation and air-conditioning)
More informationAeroacoustic simulation of automotive ventilation outlets
Aeroacoustic simulation of automotive ventilation outlets J.-L. Adam a, D. Ricot a, F. Dubief a and C. Guy b a Renault SAS, 1 avenue du golf, 78288 Guyancourt, France b Ligeron, Les Algorithmes Bâtiment
More informationWind Tunnel at LABINTHAP (Updated)
Energy and Power Engineering, 2, 3, 6-73 doi:.4236/epe.2.347 Published Online September 2 (http://www.scirp.org/journal/epe) Wind Tunnel at LABINTHAP (Updated) Abstract Rosas Quiterio Pedro, Toledo Velázquez
More informationAalborg Universitet. Windows Heiselberg, Per Kvols; Svidt, Kjeld; Nielsen, Peter Vilhelm. Publication date: 2000
Aalborg Universitet Windows Heiselberg, Per Kvols; Svidt, Kjeld; Nielsen, Peter Vilhelm Publication date: 2000 Document Version Publisher's PDF, also known as Version of record Link to publication from
More informationStudy of air curtains used to restrict infiltration into refrigerated rooms
Study of air curtains used to restrict infiltration into refrigerated rooms Gregory Verhaeghe 1, Marnix Van Belleghem 1, Arnout Willockx 1, Ivan Verhaert 1, Michel De Paepe 1 1 Ghent University, Department
More informationAnalysis of Flow inside Soundproofing Ventilation Unit using CFD
International Journal of Emerging Engineering Research and Technology Volume 6, Issue 8, 2018, PP 1-8 ISSN 2349-4395 (Print) & ISSN 2349-4409 (Online) Analysis of Flow inside Soundproofing Ventilation
More informationSound Rating of Ducted Air Moving and Conditioning Equipment
AHRI Standard 260 (I-P) 2017 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify or guarantee the
More informationAir Flow through Woven Stainless Steel Mesh
Air Flow through Woven Stainless Steel Mesh Abstract It was known that a mesh screen placed across an airflow will have an evening effect, distributing both the velocity and pressure across the screen,
More informationEVALUATION OF VENTILATION PERFORMANCE IN VOID SPACE BY EXCEEDANCE PROBABILITIES BASED ON CFD SIMULATION
EVALUATION OF VENTILATION PERFORMANCE IN VOID SPACE BY EXCEEDANCE PROBABILITIES BASED ON CFD SIMULATION Zhen BU 1, Shinsuke KATO 2, Yoshihiro ISHIDA 2, and Hong HUANG 2 1 Graduate School of Engineering,
More informationTRACER GAS TECHNIQUES FOR MEASUREMENT OF VENTILATION IN MULTI-ZONE BUILDINGS - A REVIEW
Proceedings: Indoor Air TRACER GAS TECHNIQUES FOR MEASUREMENT OF VENTILATION IN MULTI-ZONE BUILDINGS - A REVIEW H Stymne *, M Sandberg and CA Boman University of Gävle, Department of Built Environment,
More informationCHAPTER 4 AIR FLOW THROUGH OPENINGS
CHAPTER 4 AIR FLOW THROUGH OPENINGS Learning Objectives This chapter introduces the equations that describe airflow through openings. After you have studied this chapter and completed the personal feedback
More informationTEST METHOD FOR STILL- AND FORCED-AIR JUNCTION-TO- AMBIENT THERMAL RESISTANCE MEASUREMENTS OF INTEGRATED CIRCUIT PACKAGES
SEMI G38-0996 N/A SEMI 1987, 1996 TEST METHOD FOR STILL- AND FORCED-AIR JUNCTION-TO- AMBIENT THERMAL RESISTANCE MEASUREMENTS OF INTEGRATED CIRCUIT PACKAGES 1 Purpose The purpose of this test is to determine
More informationStudy on the natural air cooling design of electronic equipment casings: Effects of the height and size of outlet vent on the flow resistances
Journal of Physics: Conference Series Study on the natural air cooling design of electronic equipment casings: Effects of the height and size of outlet vent on the flow resistances To cite this article:
More informationROOM AVERAGE VELOCITY EQUATION A TOOL TO IMPROVE DESIGN OF THERMAL COMFORT CONDITIONS
ROOM AVERAGE VELOCITY EQUATION A TOOL TO IMPROVE DESIGN OF THERMAL COMFORT CONDITIONS K Hagström *, O Hakkola and T Moilanen Halton Solutions, Kausala, Finland ABSTRACT For a long time PPD index defined
More informationAnemometer Calibration Requirements for Wind Energy Applications
Anemometer Calibration Requirements for Wind Energy Applications Presented y: Rachael Ishaya ryza Wind Lab, Inc., Fairfield, California American Meteorological Society 17th Symposium on Meteorological
More informationThis is the published version of a paper presented at Healthy Buildings 2017 Europe, Lublin, Poland.
http://www.diva-portal.org This is the published version of a paper presented at Healthy Buildings 2017 Europe, Lublin, Poland. Citation for the original published paper: Kabanshi, A., Sattari, A., Linden,
More informationDESIGN AND PERFORMANCE OF THE CONVERGING-DIVERGING VORTEX FLOWMETER
Metrol. Meas. Syst., Vol. XVIII (011), No. 1, pp. 19-136 METROLOGY AND MEASUREMENT SYSTEMS Index 330930, ISSN 0860-89 www.metrology.pg.gda.pl DESIGN AND PERFORMANCE OF THE CONVERGING-DIVERGING VORTEX FLOWMETER
More informationReview of Anemometer Calibration Standards
Review of Anemometer Calibration Standards Rachael V. Coquilla rvcoquilla@otechwind.com Otech Engineering, Inc., Davis, CA Anemometer calibration defines a relationship between the measured signals from
More informationEVALUATION OF THERMAL ENVIRONMENT AROUND THE BLIND ON NON-UNIFOM RADIANT FIELDS A CFD SIMULATION OF HEAT TRANSFER DISTRIBUTION NEAR THE BLINDS
800 1500 6240 1600 1500 840 Proceedings of BS2015: EVALUATION OF THERMAL ENVIRONMENT AROUND THE BLIND ON NON-UNIFOM RADIANT FIELDS A CFD SIMULATION OF HEAT TRANSFER DISTRIBUTION NEAR THE BLINDS Nozomi
More informationSudden Expansion Exercise
Sudden Expansion Exercise EAS 361, Fall 2009 Before coming to the lab, read sections 1 through 4 of this document. Engineering of Everyday Things Gerald Recktenwald Portland State University gerry@me.pdx.edu
More informationComparison of Numerical Prediction of Pressure Coefficient on Rectangular Small Building
May 26, Volume 3, Issue 5 Comparison of Numerical Prediction of Pressure Coefficient on Rectangular Small Building Neel M. Patel, 2 Satyen D. Ramani PG Student, Department of Civil Engineering, 2 Asst.
More informationPRESSURE BOUNDARY CONDITIONS IN MULTI-ZONE AND CFD PROGRAM COUPLING
PRESSURE BOUNDARY CONDITIONS IN MULTI-ZONE AND CFD PROGRAM COUPLING Zhiqiang (John) Zhai, Ph.D. Department of Civil, Environmental & Architectural Engineering, University of Colorado 48 UCB, Engineering
More informationNatural Convection Heat Loss from A Partly Open Cubic Enclosure Timothy N Anderson 1,a * and Stuart E Norris 2,b
Natural Convection Heat Loss from A Partly Open Cubic Enclosure Timothy N Anderson 1,a * and Stuart E Norris 2,b 1 Auckland University of Technology, New Zealand 2 University of Auckland, New Zealand a
More informationTwin City Fan Companies. Fan System Effects
Fan System Effects Outline Fan Testing Review Definition of System Effect Old ASHRAE guidelines AMCA 201 System Effect Factors Examples Demonstration Aimed at the fan system designer There are two goals:
More informationHeat Transfer F12-ENG Lab #4 Forced convection School of Engineering, UC Merced.
1 Heat Transfer F12-ENG-135 - Lab #4 Forced convection School of Engineering, UC Merced. October 23, 2012 1 General purpose of the Laboratory To gain a physical understanding of the behavior of the average
More informationWhite Paper FINAL REPORT AN EVALUATION OF THE HYDRODYNAMICS MECHANISMS WHICH DRIVE THE PERFORMANCE OF THE WESTFALL STATIC MIXER.
White Paper FINAL REPORT AN EVALUATION OF THE HYDRODYNAMICS MECHANISMS WHICH DRIVE THE PERFORMANCE OF THE WESTFALL STATIC MIXER Prepared by: Dr. Thomas J. Gieseke NUWCDIVNPT - Code 8233 March 29, 1999
More informationEUROVENT 8/12 SOUND TEST METHOD FOR DUCTED FAN COIL UNITS. FCP 2008 testing procedures FCP acoustical test method pag. 1
EUROVENT 8/12 SOUND TEST METHOD FOR DUCTED FAN COIL UNITS FCP 2008 testing procedures FCP acoustical test method pag. 1 CONTENTS 1 - PURPOSE... 3 2 - NORMATIVE REFERENCES... 3 3 - DEFINITIONS... 3 3.1
More informationTURBULENCE MODELING OF AIR CIRCULATION IN AN ENCLOSURE WITH MULTIPLE OPENINGS AND LOCAL HEAT SOURCES
TURBULENCE MODELING OF AIR CIRCULATION IN AN ENCLOSURE WITH MULTIPLE OPENINGS AND LOCAL HEAT SOURCES Marc Dupuis and Edgar Dernedde Alcan International Limited, Arvida Research and Development Centre Jonquière,
More informationAEROSPACE ENGINEERING DEPARTMENT. Second Year - Second Term ( ) Fluid Mechanics & Gas Dynamics
AEROSPACE ENGINEERING DEPARTMENT Second Year - Second Term (2008-2009) Fluid Mechanics & Gas Dynamics Similitude,Dimensional Analysis &Modeling (1) [7.2R*] Some common variables in fluid mechanics include:
More informationExperimental and Numerical Investigation of Two- Phase Flow through Enlarging Singularity
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 212 Experimental and Numerical Investigation of Two- Phase Flow through Enlarging
More informationVortex shedding from slender surface mounted pyramids
Vortex shedding from slender surface mounted pyramids M. J. Morrison 1, R. J. Martinuzzi 3, E. Savory 1, G. A. Kopp 2 1 Department of Mechanical and Materials Engineering, University of Western Ontario,
More informationPoultry Housing Tips Side wall inlet light hoods. Volume 15 Number 8 September, 2003
The University of Georgia Cooperative Extension Service College of Agricultural and Environmental Science/Athens, Georgia 362-4356 Poultry Housing Tips Side wall inlet light hoods. Volume 15 Number 8 September,
More informationAIJ COOPERATIVE PROJECT FOR PRACTICAL APPLICATIONS OF CFD TO URBAN VENTILATION
The Seventh Asia-Pacific Conference on Wind Engineering, November 8-2, 29, Taipei, Taiwan AIJ COOPERATIVE PROJECT FOR PRACTICAL APPLICATIONS OF CFD TO URBAN VENTILATION Ryuichiro Yoshie, Akashi Mochida
More informationFlow disturbance due to presence of the vane anemometer
Journal of Physics: Conference Series OPEN ACCESS Flow disturbance due to presence of the vane anemometer To cite this article: M Bujalski et al 24 J. Phys.: Conf. Ser. 53 245 View the article online for
More informationSymmetry of Turbulent Characteristics Inside Urban Intersection
Colloquium FLUID DYNAMICS 2007 Institute of Thermomechanics AS CR, v. v. i., Prague, October 24-26, 2007 p.1 Symmetry of Turbulent Characteristics Inside Urban Intersection Radka Kellnerová 1,2 Zbyněk
More informationIndoor Testing of Solar Systems: A Solar Simulator for Multidisciplinary Research on Solar Technologies
A publication of VOL. 39, 2014 CHEMICAL ENGINEERING TRANSACTIONS Guest Editors: Petar Sabev Varbanov, Jiří Jaromír Klemeš, Peng Yen Liew, Jun Yow Yong Copyright 2014, AIDIC Servizi S.r.l., ISBN 978-88-95608-30-3;
More informationExperiments in Natural Ventilation for Passive Cooling
OPTIMUM VENTILATION AND AIR FLOW CONTROL IN BUILDINGS 7 th AIVC Conference, Gothenburg, Sweden, 7-0 September, 996 Experiments in Natural Ventilation for Passive Cooling F. Flourentzou, J. van der Maas,
More informationIntroduction to Fluid Mechanics - Su First experiment: Flow through a Venturi
530.327 - Introduction to Fluid Mechanics - Su First experiment: Flow through a Venturi 1 Background and objectives. In this experiment, we will study the flow through a Venturi section using both flow
More informationAtrium assisted natural ventilation of multi storey buildings
Atrium assisted natural ventilation of multi storey buildings Ji, Y and Cook, M Title Authors Type URL Published Date 005 Atrium assisted natural ventilation of multi storey buildings Ji, Y and Cook, M
More informationNumerical and Experimental Study on the Effect of Guide Vane Insertion on the Flow Characteristics in a 90º Rectangular Elbow
Numerical and Experimental Study on the Effect of Guide Vane Insertion on the Flow Characteristics in a 90º Rectangular Elbow Sutardi 1, Wawan A. W., Nadia, N. and Puspita, K. 1 Mechanical Engineering
More informationMOISTURE TRANSPORT THROUGH
ANNEX 41 MOIST-ENG, Working Meeting, October 22-24 2007, Porto, Portugal MOISTURE TRANSPORT THROUGH A HORIZONTAL OPENING Test setup and initial results Sergio Vera, Jiwu Rao, Paul Fazio Building Envelope
More informationVisualization of flow pattern over or around immersed objects in open channel flow.
EXPERIMENT SEVEN: FLOW VISUALIZATION AND ANALYSIS I OBJECTIVE OF THE EXPERIMENT: Visualization of flow pattern over or around immersed objects in open channel flow. II THEORY AND EQUATION: Open channel:
More informationEvaluation of the Convective Heat Transfer Coefficient of the Human Body Using the Wind Tunnel and Thermal Manikin
Evaluation of the Convective Heat Transfer Coefficient of the Human Body Using the Wind Tunnel and Thermal Manikin 1, Shinsuke Kato 2 and Janghoo Seo* 3 1 Assistant Professor, School of Architecture, Yeungnam
More informationPillai and Yoshie. Journal of Urban and Environmental Engineering, v.7, n.1, p ISSN doi: /juee.2013.v7n1.
Pillai and Yoshie 74 J U E E Journal of Urban and Environmental Engineering, v.7, n.1, p.74-81 ISSN 1982-3932 doi: 10.4090/juee.2013.v7n1.074081 Journal of Urban and Environmental Engineering www.journal-uee.org
More informationFan Stage Broadband Noise Benchmarking Programme
Fan Stage Broadband Noise Benchmarking Programme Specification of Fundamental Test Case 3 (FC3) Version 1 : 26 January 2015 Test Case Coordinator John Coupland ISVR University of Southampton UK E-mail
More informationAir Flow Modeling in a Mechanically Ventilated Room
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Air Flow Modeling in a Mechanically Ventilated Room T. P. Ashok Babu National
More informationNATURAL VENTILATION DESIGN FOR LOW-RISE BUILDINGS: COMPARISON BETWEEN A NODAL MODEL AND WIND TUNNEL TESTS
NATURAL VENTILATION DESIGN FOR LOW-RISE BUILDINGS: COMPARISON BETWEEN A NODAL MODEL AND WIND TUNNEL TESTS François Demouge and Xavier Faure Centre Scientifique et Technique du Bâtiment Département Climatologie
More informationExperimental and numerical studies on reverberation characteristics in a rectangular room with unevenly distributed absorbers
Acoust. Sci. & Tech. 7, () PAPER Experimental and numerical studies on reverberation characteristics in a rectangular room with unevenly distributed absorbers Yosuke Yasuda ;, Ayumi Ushiyama ;y, Shinichi
More informationAir distribution systems. Linear whirl outlet WL...
Air distribution systems Linear whirl outlet WL... DS 0 E 1.013 Preliminary remarks Mode of operation The linear whirl outlet generates turbulent mixing ventilation. It can be installed on or in a wall
More informationEffects of Free-Stream Vorticity on the Blasius Boundary Layer
17 th Australasian Fluid Mechanics Conference Auckland, New Zealand 5-9 December 2010 Effects of Free-Stream Vorticity on the Boundary Layer D.A. Pook, J.H. Watmuff School of Aerospace, Mechanical & Manufacturing
More informationGRAVITY EFFECT ON THE DISTRIBUTION OF REFRIGERANT FLOW IN A MULTI-CIRCUITED CONDENSER
Proceedings of Fifth International Conference on Enhanced, Compact and Ultra-Compact Heat Exchangers: Science, Engineering and Technology, Eds. R.K. Shah, M. Ishizuka, T.M. Rudy, and V.V. Wadekar, Engineering
More information3.2 Wind direction / wind velocity
3.2 Wind direction / wind velocity The direction from which air moves to is called the wind direction, and the distance air moves per unit time is the wind velocity. Wind has to be measured not only as
More informationDesign and simulation of Open Circuit Blowdown type Wind Tunnel
Design and simulation of Open Circuit Blowdown type Wind Tunnel Sanjeev Kumar Gupta a, V.K.Dwivedi b, Jitendra Kumar Chauhan c, and Rahul Goswami c a Assistant Professor, Department of Mechanical Engineering,
More informationDensity Field Measurement by Digital Laser Speckle Photography
Density Field Measurement by Digital Laser Speckle Photography by M. Kawahashi and H. Hirahara Saitama University Department of Mechanical Engineering Shimo-Okubo 255, Urawa, Saitama, 338-8570, Japan ABSTRACT
More information2 Experimental arrangement The test is carried out in the wind tunnel of TJ-3 atmospheric boundary layer in the State Key Laboratory of Disaster Reduc
Extreme value distribution of surface aerodynamic pressure of hyperbolic cooling tower X. P. Liu, L. Zhao, Y. J. Ge State Key Laboratory for Disaster Reduction in Civil Engineering, Tongji University,
More informationPART 1B EXPERIMENTAL ENGINEERING. SUBJECT: FLUID MECHANICS & HEAT TRANSFER LOCATION: HYDRAULICS LAB (Gnd Floor Inglis Bldg) BOUNDARY LAYERS AND DRAG
1 PART 1B EXPERIMENTAL ENGINEERING SUBJECT: FLUID MECHANICS & HEAT TRANSFER LOCATION: HYDRAULICS LAB (Gnd Floor Inglis Bldg) EXPERIMENT T3 (LONG) BOUNDARY LAYERS AND DRAG OBJECTIVES a) To measure the velocity
More informationAalborg Universitet. Comparative Test Case Specification Larsen, Olena Kalyanova; Heiselberg, Per Kvols. Publication date: 2007
Aalborg Universitet Comparative Test Case Specification Larsen, Olena Kalyanova; Heiselberg, Per Kvols Publication date: 2007 Document Version Publisher's PDF, also known as Version of record Link to publication
More informationREPORT OF SPECIAL TEST
REPORT OF SPECIAL TEST OF AIR SPEED INSTRUMENTATION April, 001, System Serial Number 090000 submitted by 05 Perry Parkway Gaithersburg, MD 0877 (Reference: Purchase Order Number 510140 dated April 4, 001)
More informationAIR BARRIERS USED FOR SEPARATING SMOKE FREE ZONES IN CASE OF FIRE IN TUNNEL
- 110 - AIR BARRIERS USED FOR SEPARATING SMOKE FREE ZONES IN CASE OF FIRE IN TUNNEL Gregory Krajewski 1 1 Building Research Institute Fire Research Department, Poland ABSTRACT The aim of this paper is
More informationComparison between Numerical and Experimental for UVP Measurement in Double Bent Pipe with Out-of-Plane Angle
Journal of Flow Control, Measurement & Visualization, 24, 2, 54-64 Published Online October 24 in SciRes. http://www.scirp.org/journal/jfcmv http://dx.doi.org/.4236/jfcmv.24.247 Comparison between Numerical
More informationWind tunnel test on mean wind forces and peak pressures acting on wind turbine nacelles
WIND ENERGY Wind Energ. (2012) Published online in Wiley Online Library (wileyonlinelibrary.com)..1551 RESEARCH ARTICLE Wind tunnel test on mean wind forces and peak pressures acting on wind turbine nacelles
More informationThe Electrodynamics of a Pair of PV Modules with Connected Building Resistance
Proc. of the 3rd IASME/WSEAS Int. Conf. on Energy, Environment, Ecosystems and Sustainable Development, Agios Nikolaos, Greece, July 24-26, 2007 563 he Electrodynamics of a Pair of s with Connected Building
More informationA dynamic model of a vertical direct expansion ground heat exchanger
A dynamic model of a vertical direct expansion ground heat exchanger B. Beauchamp 1, L. Lamarche 1 and S. Kajl 1 1 Department of mechanical engineering École de technologie supérieure 1100 Notre-Dame Ouest,
More informationInfluence of Geometry of Channel on the Flow Noise Parameters
Mechanics and Mechanical Engineering Vol. 22, No. 2 (2018) 541 551 c Lodz University of Technology Influence of Geometry of Channel on the Flow Noise Parameters Patryk Gaj Institute of Power Engineering
More informationTheoretical Gas Flow through Gaps in Screw-type Machines
Theoretical Gas Flow through Gaps in Screw-type Machines Prof. Dr.-Ing. K. Kauder, Dipl.-Ing. D. Stratmann University of Dortmund, Fachgebiet Fluidenergiemaschinen (The experimental part of these studies
More informationThe Effect Of Volute Tongue And Passage Configuration On The Performance Of Centrifugal Fan
Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 22 The Effect Of Volute Tongue And Passage Configuration On The Performance Of Centrifugal
More informationInfluence of the shape of surgical lights on the disturbance of the airflow Zoon, W.A.C.; van der Heijden, M.G.M.; Hensen, J.L.M.; Loomans, M.G.L.C.
Influence of the shape of surgical lights on the disturbance of the airflow Zoon, W.A.C.; van der Heijden, M.G.M.; Hensen, J.L.M.; Loomans, M.G.L.C. Published in: Proceedings of the 11th International
More informationISO INTERNATIONAL STANDARD. Acoustics Acoustic insulation for pipes, valves and flanges
INTERNATIONAL STANDARD ISO 15665 First edition 2003-08-15 Acoustics Acoustic insulation for pipes, valves and flanges Acoustique Isolation acoustique des tuyaux, clapets et brides Reference number ISO
More informationTHE EFFECT OF WIND-DRIVEN RAIN ON CLADDING PRESSURE OF BUILDINGS UNDER WIND AND RAIN CONDITIONS
BBAA VI International Colloquium on: Bluff Bodies Aerodynamics & Applications Milano, Italy, July, 0-4 008 THE EFFECT OF WIND-DRIVEN RAIN ON CLADDING PRESSURE OF BUILDINGS UNDER WIND AND RAIN CONDITIONS
More informationEXPERIMENT NO. 4 CALIBRATION OF AN ORIFICE PLATE FLOWMETER MECHANICAL ENGINEERING DEPARTMENT KING SAUD UNIVERSITY RIYADH
EXPERIMENT NO. 4 CALIBRATION OF AN ORIFICE PLATE FLOWMETER MECHANICAL ENGINEERING DEPARTMENT KING SAUD UNIVERSITY RIYADH Submitted By: ABDULLAH IBN ABDULRAHMAN ID: 13456789 GROUP A EXPERIMENT PERFORMED
More informationFluid Dynamic Simulations of Wind Turbines. John Abraham, Brian Plourde, Greg Mowry University of St. Thomas
Fluid Dynamic Simulations of Wind Turbines John Abraham, Brian Plourde, Greg Mowry University of St. Thomas 1 Presentation Overview Why vertical-axis turbines? How are they modeled? How much energy can
More information