1 Test Report Report No 247/ This Report consists of 41 pages Client Electrical Safety Council 18 Buckingham Gate London SW1E 6LB Authority & date BSI Estimate Acceptance No dated 12 March 2009 Equipment Record No dated 04 March 2009 Items tested Eight samples of recess mounting luminaires, of types and designs as detailed within this Test Report Specification BS EN : A1 and BS EN : 2008 Limited tests as detailed on page 3 of this Test Report Results As detailed within this Test Report repared by R Overington roject Leader Authorized by C Stratford Laboratory Manager, Lighting Technology Issue Date 27 May 2009 Conditions of issue This Test Report is issued subject to the conditions stated in current issue of S082 'General conditions relating to acceptance of testing'. The results contained herein apply only to the particular sample/s tested and to the specific tests carried out, as detailed in this Test Report. The issuing of this Test Report does not indicate any measure of Approval, Certification, Supervision, Control or Surveillance by BSI of any product. No extract, abridgement or abstraction from a Test Report may be published or used to advertise a product without the written consent of the Managing Director, BSI Testing Services, who reserves the absolute right to agree or reject all or any of the details of any items or publicity for which consent may be sought. BSI Maylands Avenue Hemel Hempstead Hertfordshire H2 4SQ Telephone: (08450)

2 Introduction Report Reference No 247/ age 2 of 41 The samples of recess mounted tungsten halogen lamp luminaires were commercially available products that were purchased for testing by the Electrical Safety Council. The samples were submitted on 04 March 2009 for a limited safety assessment according to an agreed test schedule. The samples were allocated the following type references for identification purposes: RL-1: Recess mounting luminaire designed to operate one 12V 35W GX5.3 aluminium reflector tungsten halogen lamp from a remote mounting transformer. For the purpose of the tests, a commercially available lamp and transformer were purchased and used. RL-2: Recess mounting luminaire designed to operate one 12V 50W GU5.3 aluminium reflector tungsten halogen lamp from a remote mounting transformer. For the purpose of the tests, the lamp and transformer supplied with the product were used. RL-3: Recess mounting luminaire designed to operate one 12V 50W MR16 tungsten halogen lamp from a remote mounting transformer. For the purpose of the tests, a commercially available lamp and transformer were purchased and used. RL-4: Recess mounting luminaire designed to operate one 12V 50W GU5.3 aluminium tungsten halogen lamp from a remote mounting transformer. For the purpose of the tests, a commercially available lamp and transformer were purchased and used. RL-5: Recess mounting luminaire designed to operate one 230V 50W GU10 tungsten halogen lamp. For the purpose of the tests, a commercially available lamp was purchased and used. RL-6: Recess mounting luminaire designed to operate one 240V 50W GU10 tungsten halogen lamp. For the purpose of the tests, a commercially available lamp was purchased and used. RL-7: Recess mounting luminaire designed to operate one 12V 50W MR16 tungsten halogen lamp from a remote mounting transformer. For the purpose of the tests, a commercially available lamp and transformer were purchased and used. RL-8: Recess mounting luminaire designed to operate one 12V 50W GX5.3 tungsten halogen lamp from a remote mounting transformer. For the purpose of the tests, a commercially available lamp and transformer were purchased and used. For further details of the samples submitted, please refer to the photographic evidence contained within pages 34 to 41 of this Test Report. Relevant Specifications The Specifications used during the assessments performed were as follows. BS EN : 1997 including Amendment 1 Recess luminaires BS EN : 2008 Luminaires: General requirements and tests

3 age 3 of 41 Test schedule The test schedules applied in the assessment of the lighting chains and transformers were as follows. BS EN : 1997 including Amendment 1 Clause 2.5 Marking Clause 2.6 Construction: Limited to Sub-Clause 4.25 Sharp edges of BS EN : 2008 Clause 2.10 External and internal wiring: Limited to Sub-Clause Sharp edges of BS EN : 2008 Clause 2.12 Endurance tests and thermal tests: Limited to Sub-Clauses 12.3 thermal endurance and 12.4 Thermal test (normal operation) of BS EN : 2008 The Client also requested some additional tests to be performed, to assess the thermal properties of the luminaires under two separate test conditions: 1) Thermal endurance test: Test recess covered with two layers of insulation 2) Abnormal thermal test: Operation with a lamp that does not reflect the heat forwards The applied tests were based upon the guidance provided in the following test Clauses: Notes: BS EN : 1997 including Amendment 1 Clause 2.12 Endurance tests and thermal tests: Limited to Sub-Clauses 12.3 thermal endurance and 12.4 Thermal test (normal operation) of BS EN : 2008 Sample reference RL-4 was not subjected to the additional test with two layers of insulation, as the original test programme covered this mode of operation. The luminaire marking details and installation leaflet for this product allowed the luminaire to be covered in normal use. Sample references RL-5; RL-6; RL-7 & RL-8 were not subjected to the thermal test with a nonaluminium lamp as the original test programme covered this mode of performance. Results The results of the limited tests and inspections performed on the samples submitted are contained on the following pages of this Test Report.

4 RESULTS SECTION Report No 247/ age 4 of 41 Sample RL-1 art 1 Test requirements according to Specification requirements EN Cl. Requirement Test Result 3 MARKING 3.2 Mandatory markings See comments F osition of the marking Format of symbols/text 3.3 Additional information See comments 3.4 Test with water Test with hexane Legible after test Label attached 4 CONSTRUCTION 4.25 No sharp point or edges 5 EXTERNAL AND INTERNAL WIRING Sharp edges etc. 12 ENDURANCE TEST AND THERMAL TEST 12.3 Endurance test 12.4 Thermal test (normal operation) See Table 1 art 2 Additional tests according to Clients own requirements 12 ENDURANCE TEST AND THERMAL TEST 12.3 Endurance test Covered with two layers of insulation: See comments - Thermal test (abnormal operation) Incorrect lamp fitted: See Table 1 Key: = ass F = Fail NT = Not tested

5 age 5 of 41 Table 1: Temperature measurements, thermal tests of Section 12 Type reference... : Lamp used... : Lamp control gear used... : Mounting position of luminaire... : RL-1 12V 35W Electronic transformer rated 240V (11.6V 60VA output) Test recess Supply wattage (W)... : 37.9 Supply current (A)... : Supply voltage (V)... : Table: Measured temperatures corrected for ta = 25 C: Temperature ( C) of part Normal Abnormal Test Limit Test Limit Transformer case Cord grip moulding 59 # 76 # Terminal enclosure side 70 # 104 # Terminal block 79 # 89 # Glass fibre insulated cable at terminal block Terminal block cover 76 # 97 # Glass fibre insulated cable at entry to luminaire enclosure Luminaire body top (metal) Glass fibre insulated cable at lampholder Ceramic lampholder Front bezel cover 67 # 93 # Minimum distance from lighted objects: m Test recess above luminaire Notes 1) The sample was operated at 1.06 x the maximum rated input voltage of the transformer i.e x 240 = 254.4V~. 2) The voltage recorded above is the noted voltage at the time of measurement. 3) # - lastic moulded component and therefore the material and applied thermal limit is unknown 4) The abnormal test is with a non-aluminium reflector lamp fitted

6 Sample RL-2 Report No 247/ age 6 of 41 art 1 Test requirements according to Specification requirements EN Cl. Requirement Test Result 3 MARKING 3.2 Mandatory markings osition of the marking Format of symbols/text See comments F 3.3 Additional information 3.4 Test with water Test with hexane Legible after test Label attached 4 CONSTRUCTION 4.25 No sharp point or edges 5 EXTERNAL AND INTERNAL WIRING Sharp edges etc. 12 ENDURANCE TEST AND THERMAL TEST 12.3 Endurance test 12.4 Thermal test (normal operation) See Table 2 art 2 Additional tests according to Clients own requirements 12 ENDURANCE TEST AND THERMAL TEST 12.3 Endurance test Covered with two layers of insulation - Thermal test (abnormal operation) Incorrect lamp fitted: See Table 2 Key: = ass F = Fail NT = Not tested

7 age 7 of 41 Table 2: Temperature measurements, thermal tests of Section 12 Type reference... : Lamp used... : RL-2 12V 50W Lamp control gear used... : Electronic transformer rated V ( 11.6V 60VA output) Mounting position of luminaire... : Test recess Supply wattage (W)... : 54.4 Supply current (A)... : Supply voltage (V)... : Table: Measured temperatures corrected for ta = 25 C: Temperature ( C) of part Normal Abnormal Test Limit Test Limit Test recess: Mounting hole for luminaire Ceramic lampholder Glass fibre insulated cable at lampholder * Luminaire body top (metal) Glass fibre insulated cable at luminaire Glass fibre insulated cable at transformer plug and socket Low voltage plug and socket 55 # 68 # Transformer case Mains voltage plug and socket body 45 # 57 # Mains voltage plug and socket cover 47 # 62 # Neutral supply wire insulation at mains voltage plug and socket terminal Minimum distance from lighted objects: m Test recess above luminaire Notes 1) The sample was operated at 1.06 x the maximum rated input voltage of the transformer i.e x 240 = 254.4V~. 2) The voltage recorded above is the noted voltage at the time of measurement. 3) # - lastic moulded component and therefore the material and applied thermal limit is unknown 4) The abnormal test is with a non-aluminium reflector lamp fitted 5) * - The Specification states that the applied temperature limit shall be considered with regard to a +5 C tolerance

8 Sample RL-3 Report No 247/ age 8 of 41 art 1 Test requirements according to Specification requirements EN Cl. Requirement Test Result 3 MARKING 3.2 Mandatory markings See comments F osition of the marking Format of symbols/text See comments F 3.3 Additional information 3.4 Test with water Test with hexane Legible after test Label attached 4 CONSTRUCTION 4.25 No sharp point or edges 5 EXTERNAL AND INTERNAL WIRING Sharp edges etc. 12 ENDURANCE TEST AND THERMAL TEST 12.3 Endurance test See comments F 12.4 Thermal test (normal operation) See Table 3 art 2 Additional tests according to Clients own requirements 12 ENDURANCE TEST AND THERMAL TEST 12.3 Endurance test Covered with two layers of insulation: See comments - Thermal test (abnormal operation) Incorrect lamp fitted: See Table 3 F Key: = ass F = Fail NT = Not tested

9 age 9 of 41 Table 3: Temperature measurements, thermal tests of Section 12 Type reference... : Lamp used... : Lamp control gear used... : Mounting position of luminaire... : RL-3 12V 50W Electronic transformer rated 240V (11.6V 60VA output) Test recess Supply wattage (W)... : 52.7 Supply current (A)... : Supply voltage (V)... : Table: Measured temperatures corrected for ta = 25 C: Temperature ( C) of part Normal Abnormal Test Limit Test Limit Transformer case VC cable at transformer input terminals Glass fibre insulated cable at transformer output Glass fibre insulated cable at terminal block Terminal block 91 # - - Terminal block enclosure base 98 # - - Glass fibre insulated cable at luminaire entry Luminaire top (metal) Glass fibre insulated cable at lampholder Ceramic lampholder Minimum distance from lighted objects: m Test recess above luminaire Notes 1) The sample was operated at 1.06 x the maximum rated input voltage of the transformer i.e x 240 = 254.4V~. 2) The voltage recorded above is the noted voltage at the time of measurement. 3) # - lastic moulded component and therefore the material and applied thermal limit is unknown 4) The abnormal test was not conducted as a non-aluminium reflector lamp was fitted during the normal thermal test

10 Sample RL- 4 Report No 247/ age 10 of 41 art 1 Test requirements according to Specification requirements EN Cl. Requirement Test Result 3 MARKING 3.2 Mandatory markings See comments F osition of the marking Format of symbols/text 3.3 Additional information 3.4 Test with water See comments F Test with hexane See comments NT Legible after test See comments F Label attached 4 CONSTRUCTION 4.25 No sharp point or edges 5 EXTERNAL AND INTERNAL WIRING Sharp edges etc. 12 ENDURANCE TEST AND THERMAL TEST 12.3 Endurance test 12.4 Thermal test (normal operation) See Table 4 art 2 Additional tests according to Clients own requirements 12 ENDURANCE TEST AND THERMAL TEST 12.3 Endurance test Covered with two layers of insulation - Thermal test (abnormal operation) Incorrect lamp fitted: See Table 4 NT Key: = ass F = Fail NT = Not tested

11 age 11 of 41 Table 4: Temperature measurements, thermal tests of Section 12 Type reference... : Lamp used... : Lamp control gear used... : Mounting position of luminaire... : RL-4 12V 50W Electronic transformer rated 240V (11.5V 10-60W output) Test recess Supply wattage (W)... : 53.4 Supply current (A)... : Supply voltage (V)... : Table: Measured temperatures corrected for ta = 25 C: Temperature ( C) of part Normal Abnormal Test Limit Test Limit VC cable at transformer input terminals Transformer case * Glass fibre insulated cable at transformer output lug and socket 61 # 74 # Silicone insulated cable at luminaire entry Rubber boot: Top 86 ** 110 ** Rubber boot: Base 88 ** 143 ** Silicone insulated wiring at lampholder Ceramic lampholder Minimum distance from lighted objects: m Test recess above luminaire Notes 1) The sample was operated at 1.06 x the maximum rated input voltage of the transformer i.e x 240 = 254.4V~. 2) The voltage recorded above is the noted voltage at the time of measurement. 3) # - lastic moulded component and therefore the material and applied thermal limit is unknown 4) The abnormal test is with a non-aluminium reflector lamp fitted 5) * - The Specification states that the applied temperature limit shall be considered with regard to a +5 C tolerance 6) ** - Type of rubber not known and therefore limit cannot be applied 7) The transformer supplied with the product for test failed after the completion of the thermal endurance test. A commercially available transformer was therefore used to enable the tests to continue.

12 Sample RL-5 Report No 247/ age 12 of 41 art 1 Test requirements according to Specification requirements EN Cl. Requirement Test Result 3 MARKING 3.2 Mandatory markings See comments osition of the marking Format of symbols/text See comments F 3.3 Additional information See comments 3.4 Test with water Test with hexane Legible after test Label attached 4 CONSTRUCTION 4.25 No sharp point or edges 5 EXTERNAL AND INTERNAL WIRING Sharp edges etc. 12 ENDURANCE TEST AND THERMAL TEST 12.3 Endurance test See comments F 12.4 Thermal test (normal operation) See Table 5 art 2 Additional tests according to Clients own requirements 12 ENDURANCE TEST AND THERMAL TEST 12.3 Endurance test Covered with two layers of insulation - Thermal test (abnormal operation) Incorrect lamp fitted: See Table 5 Key: = ass F = Fail NT = Not tested

13 age 13 of 41 Table 5: Temperature measurements, thermal tests of Section 12 Type reference... : Lamp used... : Lamp control gear used... : Mounting position of luminaire... : RL-5 240V 50W Not applicable Test recess Supply wattage (W)... : 52.5 Supply current (A)... : Supply voltage (V)... : Table: Measured temperatures corrected for ta = 25 C: Temperature ( C) of part Normal Abnormal Test Limit Test Limit Supply cable in cord restraint 77 75* - - Neutral supply wire insulation at terminal block Terminal block 85 # - - Terminal enclosure cover 75 # - - Glass fibre insulated cable at entry into luminaire enclosure Top of luminaire enclosure Internal wiring at lampholder Ceramic lampholder Front bezel (metal) Mounting surface: Luminaire hole Minimum distance form lighted objects: m Test recess above luminaire Notes 1) The sample was operated at 1.05 x the lamp rated wattage 2) The voltage recorded above is the noted voltage at the time of measurement. 3) # - lastic moulded component and therefore the material and applied thermal limit is unknown 4) The abnormal test was not applicable to this product type 5) * - The Specification states that the applied temperature limit shall be considered with regard to a +5 C tolerance

14 Sample RL-6 Report No 247/ age 14 of 41 art 1 Test requirements according to Specification requirements EN Cl. Requirement Test Result 3 MARKING 3.2 Mandatory markings See comments F osition of the marking Format of symbols/text See comments F 3.3 Additional information 3.4 Test with water Test with hexane Legible after test Label attached 4 CONSTRUCTION 4.25 No sharp point or edges 5 EXTERNAL AND INTERNAL WIRING Sharp edges etc. 12 ENDURANCE TEST AND THERMAL TEST 12.3 Endurance test 12.4 Thermal test (normal operation) See Table 6 art 2 Additional tests according to Clients own requirements 12 ENDURANCE TEST AND THERMAL TEST 12.3 Endurance test Covered with two layers of insulation - Thermal test (abnormal operation) Incorrect lamp fitted: See Table 6 Key: = ass F = Fail NT = Not tested

15 age 15 of 41 Table 6: Temperature measurements, thermal tests of Section 12 Type reference... : Lamp used... : Lamp control gear used... : Mounting position of luminaire... : RL-6 240V 50W Not applicable Test recess Supply wattage (W)... : 52.5 Supply current (A)... : Supply voltage (V)... : Table: Measured temperatures corrected for ta = 25 C: Temperature ( C) of part Normal Abnormal Test Limit Test Limit Supply cable in cord restraint Neutral supply wire insulation at terminal block Terminal block 74 # - - Terminal enclosure cover 70 # - - Glass fibre insulated cable at lampholder Ceramic lampholder Front bezel (metal) Mounting surface: Luminaire hole Minimum distance from lighted objects: m Test recess above luminaire Notes 1) The sample was operated at 1.05 x the lamp rated wattage 2) The voltage recorded above is the noted voltage at the time of measurement. 3) # - lastic moulded component and therefore the material and applied thermal limit is unknown 4) The abnormal test was not applicable to this product type

16 Sample RL-7 Report No 247/ age 16 of 41 art 1 Test requirements according to Specification requirements EN Cl. Requirement Test Result 3 MARKING 3.2 Mandatory markings See comments F osition of the marking Format of symbols/text 3.3 Additional information 3.4 Test with water Test with hexane Legible after test Label attached 4 CONSTRUCTION 4.25 No sharp point or edges 5 EXTERNAL AND INTERNAL WIRING Sharp edges etc. 12 ENDURANCE TEST AND THERMAL TEST 12.3 Endurance test See comments F 12.4 Thermal test (normal operation) See Table 7 art 2 Additional tests according to Clients own requirements 12 ENDURANCE TEST AND THERMAL TEST 12.3 Endurance test Covered with two layers of insulation: See comments - Thermal test (abnormal operation) Incorrect lamp fitted: See Table 7 F Key: = ass F = Fail NT = Not tested

17 age 17 of 41 Table 7: Temperature measurements, thermal tests of Section 12 Type reference... : Lamp used... : Lamp control gear used... : Mounting position of luminaire... : RL-7 12V 50W Electronic transformer rated 240V (11.4V output) Test recess Supply wattage (W)... : 54.1 Supply current (A)... : Supply voltage (V)... : Table: Measured temperatures corrected for ta = 25 C: Temperature ( C) of part Normal Abnormal Test Limit Test Limit Transformer case Glass fibre insulated cable at cord grip Glass fibre insulated cable at terminal block Terminal block 82 # - - Terminal enclosure cover 79 # - - Glass fibre insulated cable at lampholder Ceramic lampholder Front bezel (metal) Mounting surface: luminaire hole Minimum distance from lighted objects: m Test recess above luminaire Notes 1) The sample was operated at 1.06 x the maximum rated input voltage of the transformer i.e x 240 = 254.4V~. 2) The voltage recorded above is the noted voltage at the time of measurement. 3) # - lastic moulded component and therefore the material and applied thermal limit is unknown 4) The abnormal test was not applicable to this product type

18 Sample RL-8 Report No 247/ age 18 of 41 art 1 Test requirements according to Specification requirements EN Cl. Requirement Test Result 3 MARKING 3.2 Mandatory markings See comments F osition of the marking See comments F Format of symbols/text See comments F 3.3 Additional information 3.4 Test with water NT Test with hexane Legible after test Label attached NT NT NT 4 CONSTRUCTION 4.25 No sharp point or edges 5 EXTERNAL AND INTERNAL WIRING Sharp edges etc. 12 ENDURANCE TEST AND THERMAL TEST 12.3 Endurance test See comments F 12.4 Thermal test (normal operation) See Table 8 art 2 Additional tests according to Clients own requirements 12 ENDURANCE TEST AND THERMAL TEST 12.3 Endurance test Covered with two layers of insulation: See comments - Thermal test (abnormal operation) Incorrect lamp fitted: See Table 8 F Key: = ass F = Fail NT = Not tested

19 age 19 of 41 Table 8: Temperature measurements, thermal tests of Section 12 Type reference... : Lamp used... : RL-8 12V 50W Lamp control gear used... : Mounting position of luminaire... : Test recess Supply wattage (W)... : 53.5 Supply current (A)... : Supply voltage (V)... : Table: Measured temperatures corrected for ta = 25 C: Temperature ( C) of part Normal Abnormal Test Limit Test Limit Transformer case Glass fibre insulated cable at terminal block (from transformer) Terminal block 83 # - - Silicone insulated wiring at lampholder Ceramic lampholder Luminaire body: Top (metal) Mounting surface: Luminaire hole Minimum distance from lighted objects: m Test recess above luminaire Notes 1) The sample was operated at 1.06 x the maximum rated input voltage of the transformer i.e x 240 = 254.4V~. 2) The voltage recorded above is the noted voltage at the time of measurement. 3) # - lastic moulded component and therefore the material and applied thermal limit is unknown 4) The abnormal test was not applicable to this product type

20 age 20 of 41 COMMENTS SECTION Sample No RL-1 Clause 3.2 Marking on luminaires The assessment was made on the label attached to the luminaire body. However, this label was attached to the exterior surface of the body and would therefore not be seen once installed or during lamp replacement. Sub-Clause Mark of origin The manufacturer s name or trade mark was not shown on the label attached to the luminaire body. Sub-Clause I rating The product packaging indicated that the sample was an I65 rated shower light. The main label did not contain this rating i.e. I65, but had the old graphical symbols that related to the rating of I55. The leaflet supplied with the product contained the symbol of a house and a symbol with an arrow pointing inside (indicating indoor use), with a rating of I20 stated. This conflicts with the product packaging and marking. Sub-Clause Model number or type reference The sample was not marked with the model number as shown on the product packaging. Sub-Clause Luminaires not suitable for mounting on combustible surfaces The sample was not marked with the symbol that denotes that the symbol is unsuitable for mounting on combustible surfaces. However the leaflet provided with the product contained the previously used F Mark symbol with a top hat denoting that it could be mounted on combustible surfaces and covered with insulating material. Clause 3.3 Additional information Sub-Clause Suitable for use indoors The Specification states that I rated luminaires shall have a statement contained within the installation leaflet that they are suitable for use indoors and contain details of the ambient temperature of use. The leaflet supplied with the luminaire for test was relevant to a product rated I20 ordinary and therefore contained no information relevant to an I rated luminaire.

21 age 21 of 41 COMMENTS SECTION Sample No RL-1: Continued/ Additional thermal test Luminaire covered with two layers of insulation In accordance with the Clients request, the sample was subjected to an additional thermal endurance test, when covered with two layers of insulation. This was deemed to be an abnormal mode of operation that ignored the installation instructions that advised that the luminaire should not be covered. The luminaire was operated in accordance with the guidance of Clause 12.3 of the Specification, in an ambient temperature of 35 C and when mounted in a test recess. The test recess was manufactured in accordance with the Specification requirements and taking into account the installation instructions. Under the conditions specified it was noted during the test that the sample cycled on and off, due to the thermal protection device fitted into the electronic transformer. However, the sample showed no signs of scorching or deterioration that would affect safety at the completion of the test period.

22 age 22 of 41 COMMENTS SECTION Sample No RL-2 Clause 3.2 Marking on luminaires The luminaire was noted to have been marked with the required Specification marking details. However, to ensure legibility all text, numerals and symbols shall be subjected to the minimum size requirements. The text and numerals of the main product label were noted to be less than the 2mm minimum limit, having been measured at 1.7mm. Sub-Clause Luminaires not suitable for mounting on combustible surfaces The luminaire was marked with the previously used F Mark symbol to denote that it is suitable for use on normally flammable surfaces. This symbol is no longer required as the product only needs to be marked when the luminaire is not suitable for direct mounting on normally flammable surfaces. Sub-Clause Luminaires not suitable for covering with insulating material The installation leaflet supplied with the luminaire submitted contained a warning notice that the luminaire shall not be covered with insulating material. The Specification requires the relevant symbol to be shown on the luminaire marking details with an explanation of the meaning stated within the leaflet and /or on the luminaire. Additional thermal test with an abnormal lamp condition applied The sample was subjected to a normal thermal test, but with a non-aluminium lamp fitted. Under this test condition the following was noted. o o o The test recess mounting hole for the luminaire limit of 90 C was exceeded The glass fibre sleeved wiring at the lampholder exceeded the 200 C limit specified, but was within the 5 C tolerance allowed The test recess above the luminaire was recorded at 91 C with the Specification limit being 90 C, but was within the 5 C tolerance allowed

23 age 23 of 41 COMMENTS SECTION Sample No RL-3 Clause 3.2 Marking on luminaires The assessment was made on the labels attached to the luminaire body, with one label on the outside and one on the inside. Sub-Clause Class III symbol The sample was not marked with the Class III symbol as required for a 12V design of luminaire. Sub-Clause Luminaires not suitable for mounting on combustible surfaces The luminaire was marked with the previously used F Mark symbol to denote that it is suitable for use on normally flammable surfaces. This symbol is no longer required as the product only needs to be marked when the luminaire is not suitable for direct mounting on normally flammable surfaces. Sub-Clause Luminaires not suitable for covering with insulating material The installation leaflet supplied with the luminaire submitted contained a warning notice that the luminaire shall not be covered with insulating material. The Specification requires the relevant symbol to be shown on the luminaire marking details with an explanation of the meaning stated within the leaflet and /or on the luminaire. Clause 12.3 Thermal endurance test The luminaire was operated in accordance with the Specification requirements for a period of ten days, in an ambient temperature of 35 C and when mounted in a test recess. The test recess was manufactured in accordance with the Specification requirements and taking into account the installation instructions. The inspection after test revealed the following (see also photograph below): o o o Discolouration / browning due to heat of the label Curling of the label making the content unreadable Discoloration of the internal white painted surface of the luminaire enclosure

24 age 24 of 41 COMMENTS SECTION Sample No RL-3: Continued/ Additional thermal test Luminaire covered with two layers of insulation In accordance with the Clients request, the sample was subjected to an additional thermal endurance test, when covered with two layers of insulation. This was deemed to be an abnormal mode of operation that ignored the installation instructions that advised that the luminaire should not be covered. The luminaire was operated in accordance with the guidance of Clause 12.3 of the Specification, in an ambient temperature of 35 C and when mounted in a test recess. The test recess was manufactured in accordance with the Specification requirements and taking into account the installation instructions. The sample failed to operate for the required duration of ten days. An inspection after test revealed that the lampholder wiring had burnt out (see photograph below):

25 age 25 of 41 COMMENTS SECTION Sample No RL-4 Clause 3.2 Marking on luminaires The assessment was made on the labels attached to the luminaire, with one label on the lampholder wiring and one on the rubber boot. Sub-Clause Model number or type reference The sample was not marked with the model number as shown on the product packaging. Sub-Clause Luminaires not suitable for mounting on combustible surfaces The luminaire was marked with the previously used F Mark symbol to denote that it is suitable for use on normally flammable surfaces and being covered with insulating material. This symbol is no longer required as the product only needs to be marked when the luminaire is not suitable for direct mounting on normally flammable surfaces. Clause 3.4 Durability of marking The Specification requires all mandatory marking details to be shown in such a manner that it durable and shall be checked by the application of water and spirit soaked soft cloths for a duration of 15 seconds each. The water soaked cloth was applied for the required duration of 15 seconds and it was noted that the paper fibres had begun to break up rendering the marking unreadable. See photograph below. Due to the above stated failure the spirit soaked cloth was not applied. Additional thermal test with an abnormal lamp condition applied The sample was subjected to a normal thermal test, but with a non-aluminium lamp fitted. Under this test condition the following was noted. o o The silicone insulated wiring at the lampholder exceeded the 200 C limit specified The test recess above the luminaire was recorded at 90 C with the Specification limit being 90 C

26 age 26 of 41 COMMENTS SECTION Sample No RL-5 Clause 3.2 Marking on luminaires The assessment was made on the labels attached to the luminaire body, with one label on the outside and one on the inside. To ensure legibility all text, numerals and symbols shall be subjected to the minimum size requirements. The text and numerals of the main product label were noted to be 2mm with the Specification limit also being 2mm minimum. The Class II symbol i.e. square within a square was noted to have a outer edge dimension of 4.2mm with a limit of 5mm. Sub-Clause Rated supply voltage The label attached to the outside of the luminaire stated the luminaire rated voltage as being 230V AC, whereas the label on the inner surface stated it as being 240V AC. The associated installation leaflet stated the rated voltage as being 230/240V 50Hz. Sub-Clause Rated ambient temperature of use (ta) The sample submitted was not marked with a rated ambient temperature of use (ta) and as such all tests were applied based upon the normal rating of 25 C. However, the installation leaflet supplied with the luminaire submitted states the luminaire temperature range as being: -20 to +40 C. Sub-Clause Luminaires not suitable for mounting on combustible surfaces The luminaire was marked with the previously used F Mark symbol to denote that it is suitable for use on normally flammable surfaces and being covered with insulating material. This symbol is no longer required as the product only needs to be marked when the luminaire is not suitable for direct mounting on normally flammable surfaces. Sub-Clause Luminaires not suitable for covering with insulating material The installation leaflet supplied with the luminaire submitted contained a warning notice that the luminaire shall not be covered with insulating material. The Specification requires the relevant symbol to be shown on the luminaire marking details with an explanation of the meaning stated within the leaflet and /or on the luminaire.

27 age 27 of 41 COMMENTS SECTION Sample No RL-5: Continued/ Clause 12.3 Thermal endurance test The luminaire was operated in accordance with the Specification requirements for a period of ten days, in an ambient temperature of 35 C and when mounted in a test recess. The test recess was manufactured in accordance with the Specification requirements and taking into account the installation instructions. The inspection after test revealed the following (see also photograph below): o Curling of the label making the content unreadable Clause 12.4 Thermal test (normal operation) The VC supply cable in the cord restraint was noted to have achieved a temperature of 77 C with an applied Specification limit of 75 C. However, the temperature recorded was within the +5 C tolerance allowed by the Specification. The temperature of the test recess surface hole through which the luminaire is mounted was noted to reach a temperature of 111 C, with an applied Specification limit of 90 C.

28 age 28 of 41 COMMENTS SECTION Sample No RL-6 Clause 3.2 Marking on luminaires The assessment was made on the label attached to the luminaire arm to which the supply terminal block and enclosure are mounted. To ensure legibility all text, numerals and symbols shall be subjected to the minimum size requirements. The text and numerals of the main product label were noted to be 2.1/2.2mm with the Specification limit being 2mm minimum. The Class II symbol i.e. square within a square was noted to have a outer edge dimension of 3.7mm with a limit of 5mm. Sub-Clause Luminaires not suitable for mounting on combustible surfaces The luminaire was marked with the previously used F Mark symbol to denote that it is suitable for use on normally flammable surfaces and being covered with insulating material. This symbol is no longer required as the product only needs to be marked when the luminaire is not suitable for direct mounting on normally flammable surfaces. Sub-Clause Luminaires not suitable for covering with insulating material The installation leaflet supplied with the luminaire submitted contained a warning notice that the luminaire shall not be covered with insulating material. The Specification requires the relevant symbol to be shown on the luminaire marking details with an explanation of the meaning stated within the leaflet and /or on the luminaire.

29 age 29 of 41 COMMENTS SECTION Sample No RL-7 Clause 3.2 Marking on luminaires The assessment was made on the label attached to the luminaire body and to the luminaire arm to which the supply terminal block and enclosure are mounted. Sub-Clause Rated wattage The luminaire was noted to have conflicting marking with regard to the rated wattage. The main product label was noted to show the wattage as being 50W with a second label showing the F Mark symbol with 35W being marked adjacent to this symbol. Attention is drawn to following comment on the use of the F Mark symbol. Sub-Clause Luminaires not suitable for mounting on combustible surfaces The luminaire was marked with the previously used F Mark symbol to denote that it is suitable for use on normally flammable surfaces and being covered with insulating material. This symbol is no longer required as the product only needs to be marked when the luminaire is not suitable for direct mounting on normally flammable surfaces. Sub-Clause Luminaires not suitable for covering with insulating material The installation leaflet supplied with the luminaire submitted contained a warning notice that the luminaire shall not be covered with insulating material. The Specification requires the relevant symbol to be shown on the luminaire marking details with an explanation of the meaning stated within the leaflet and /or on the luminaire. Clause 12.3 Thermal endurance test The luminaire was operated in accordance with the Specification requirements for a period of ten days, in an ambient temperature of 35 C and when mounted in a test recess. The test recess was manufactured in accordance with the Specification requirements and taking into account the installation instructions. The inspection after test revealed the following (see also photograph on following page): o Overheating of the test recess hole through which the luminaire is mounted indicated by signs of scorching of the wood surface

30 age 30 of 41 COMMENTS SECTION Sample No RL-7: Continued/ Clause 12.Thermal endurance test: Continued/ Scorched area Clause 12.4 Thermal test (normal operation) The temperature of the test recess surface hole through which the luminaire is mounted was noted to reach a temperature of 106 C, with an applied Specification limit of 90 C. Additional thermal test Luminaire covered with two layers of insulation In accordance with the Clients request, the sample was subjected to an additional thermal endurance test, when covered with two layers of insulation. This was deemed to be an abnormal mode of operation that ignored the installation instructions that advised that the luminaire should not be covered. The luminaire was operated in accordance with the guidance of Clause 12.3 of the Specification, in an ambient temperature of 35 C and when mounted in a test recess. The test recess was manufactured in accordance with the Specification requirements and taking into account the installation instructions. At the completion of the test period the sample was noted to be operational and the inspection revealed no scorching or deterioration of the luminaire that would affect safety. However, the test recess hole through which the luminaire was mounted was heavily scorched. lease refer to the photographic evidence on the following page of this Test Report.

31 age 31 of 41 COMMENTS SECTION Sample No RL-7: Continued/ Additional thermal test Luminaire covered with two layers of insulation: Continued/ hotographic evidence of test recess after test Scorched area Scorched area with luminaire removed

32 age 32 of 41 COMMENTS SECTION Sample No RL-8 Clause 3.2 Marking on luminaires The relevant Specification requirements could not be assessed on the sample submitted as no labels or other forms of marking had been provided. When marked, the following information is required to be shown: o o o o o o o o Sub-Clause Mark of origin Sub-Clause Rated supply voltage Sub-Clause Rated ambient temperature of use (if other than 25 C) Sub-Clause Class III symbol Sub-Clause Model number or type reference Sub-Clause Rated lamp wattage Sub-Clause Special lamp information Sub-Clause Minimum distance from lighted objects symbol Sub-Clause Luminaires not suitable for covering with insulating material The installation leaflet supplied with the luminaire submitted contained a warning notice that the luminaire shall not be covered with insulating material. The Specification requires the relevant symbol to be shown on the luminaire marking details with an explanation of the meaning stated within the leaflet and /or on the luminaire. Clause 12.3 Thermal endurance test The luminaire was operated in accordance with the Specification requirements for a period of ten days, in an ambient temperature of 35 C and when mounted in a test recess. The test recess was manufactured in accordance with the Specification requirements and taking into account the installation instructions. The inspection after test revealed the following (see also photograph below): o Overheating of the test recess above the luminaire indicated by signs of scorching of the wood surface

33 age 33 of 41 COMMENTS SECTION Sample No RL-8: Continued/ Clause 12.4 Thermal test (normal operation) The silicone insulated lampholder wiring was noted to have achieved a temperature of 219 C with an applied Specification limit of 200 C. The temperature of the test recess surface above the luminaire was noted to reach a temperature of 171 C, with an applied Specification limit of 90 C. Additional thermal test Luminaire covered with two layers of insulation In accordance with the Clients request, the sample was subjected to an additional thermal endurance test, when covered with two layers of insulation. This was deemed to be an abnormal mode of operation that ignored the installation instructions that advised that the luminaire should not be covered. The luminaire was operated in accordance with the guidance of Clause 12.3 of the Specification, in an ambient temperature of 35 C and when mounted in a test recess. The test recess was manufactured in accordance with the Specification requirements and taking into account the installation instructions. During the test period the sample was noted to be non-operational. Further inspection revealed that the lamp had failed. The lamp was replaced and the test continued to the required period of operation. At the completion of the test the sample was noted to be operational and the inspection revealed no scorching or deterioration of the luminaire that would affect safety. However, the test recess above the luminaire was heavily scorched, as shown by the following photograph:

34 HOTOGRAHIC EVIDENCE OF SAMLES SUBMITTED Report No 247/ age 34 of 41 Sample No RL-1

35 HOTOGRAHIC EVIDENCE OF SAMLES SUBMITTED Report No 247/ age 35 of 41 Sample No RL-2

36 HOTOGRAHIC EVIDENCE OF SAMLES SUBMITTED Report No 247/ age 36 of 41 Sample No RL-3

37 Sample No RL-4 HOTOGRAHIC EVIDENCE OF SAMLES SUBMITTED Report No 247/ age 37 of 41

38 Sample No RL-5 HOTOGRAHIC EVIDENCE OF SAMLES SUBMITTED Report No 247/ age 38 of 41

39 HOTOGRAHIC EVIDENCE OF SAMLES SUBMITTED Report No 247/ age 39 of 41 Sample No RL-6

40 Sample No RL-7 HOTOGRAHIC EVIDENCE OF SAMLES SUBMITTED Report No 247/ age 40 of 41

41 HOTOGRAHIC EVIDENCE OF SAMLES SUBMITTED Report No 247/ age 41 of 41 Sample No RL-8

INSTITUTE OF TESTING AND CERTIFICATION (INDIA) PVT.LTD.

INSTITUTE OF TESTING AND CERTIFICATION (INDIA) PVT.LTD. (INDIA) VT.LTD. 60598-1 Requirement Result/Remarks Verdict 2.2 2.3 2.4 2.5 3.2.1 3.2.2 3.2.3 3.2.4 3.2.5 3.2.6 3.2.7 3.2.8 3.2.9 2 Classification of Luminaries Classification according to type of protection

More information

FLT5A FLT5A. abc. abc. Thermometer User Guide. Thermometer User Guide. Internet:

FLT5A FLT5A. abc. abc. Thermometer User Guide. Thermometer User Guide. Internet: abc instruments international FLT5A Thermometer Land Instruments International Dronfield, S18 1DJ England Telephone: (1246) 417691 Facsimile: (1246) 41585 Email: infrared.sales@landinst.com Internet: www.landinst.com

More information

TEST REPORT REPORT NO.: QAV PAGE: 1 OF 31

TEST REPORT REPORT NO.: QAV PAGE: 1 OF 31 QAV Technologies Sdn. Bhd. (616788-U) 116, Lintang Kampung Jawa, NFIZ 3, Taman erindustrian Bayan Lepas, MK 12, 11900 enang, Malaysia. Tel No : 604 643 8317 Fax No : 604 643 8597 Email : qavtech@qavtech.com

More information

THE DIMENSIONING OF ELECTRICAL CONDUCTORS FOR USE IN "PANEL BOARDS" ADDRESSED TO HAZARDOUS AREAS - PART THREE

THE DIMENSIONING OF ELECTRICAL CONDUCTORS FOR USE IN PANEL BOARDS ADDRESSED TO HAZARDOUS AREAS - PART THREE July 04 THE DIMENSIONING OF ELECTRICAL CONDUCTORS FOR USE IN "PANEL BOARDS" ADDRESSED TO HAZARDOUS AREAS - PART THREE In this third part. we want to speak about how important is the correct sizing of the

More information

FL ballasts Electronic fixed output. PC TC PRO sr 1/2x11 42 W PC PRO compact

FL ballasts Electronic fixed output. PC TC PRO sr 1/2x11 42 W PC PRO compact FL ballasts EL HE PC TC PRO sr 1/2x11 42 W PC PRO compact Product description CELMA Energy Efficiency Index A2 BAT / A2 T Nominal life-time up to 50,000 h (at ta 50 C with a failure rate max. 0.2 % per

More information

WIESON TECHNOLOGIES CO., LTD.

WIESON TECHNOLOGIES CO., LTD. TABLE OF CONTENT 1. Scope.... 2 2. Reference Documents. 2 3. Material and Components.... 2 4. Design and Construction.... 2 5. Rating.. 2 6. Performance and Test Descriptions. 2 7. Test Requirements and

More information

Recommended Hole Pattern: [mm]

Recommended Hole Pattern: [mm] Dimensions: [mm] Recommended Hole Pattern: [mm] Electrical Properties: Properties Test conditions Value Unit Tol. Capacitance 1 V/ 1 khz ± 0.2 khz C 680 nf ±10% Rated Voltage U R 400 V (DC) Insulation

More information

Operating Instructions for Digital Manometer. Model: MAN-SD

Operating Instructions for Digital Manometer. Model: MAN-SD Operating Instructions for Digital Manometer Model: MAN-SD 1. Contents 1. Contents...2 2. Note...3 3. Instrument Inspection...3 4. Regulation Use...4 5. Operating Principle...4 6. Mechanical Connection...5

More information

The slimmest Panel with highest efficacy in the market

The slimmest Panel with highest efficacy in the market Lighting The slimmest Panel with highest efficacy in the market GreenPerform Panel GreenPerform Panel is the slimmest Panel with highest efficacy in the market. It offers two lumen options with four dimension

More information

CLUSTERLITE CONTENTS MEGAMAN

CLUSTERLITE CONTENTS MEGAMAN CONTENTS Specifications for... 2.1 Maximum Temperature Declaration... 2.3 Lumen Maintenance Curve... 2.4 Vs. Temperature... 2.6 Run-up Time... 2.8 Specifications for Power Supply... 2.1 Line Drawings for

More information

Periodic Inspection and Testing of Electrical Installations Sample Test ( ) Version 1.3 July 2018

Periodic Inspection and Testing of Electrical Installations Sample Test ( ) Version 1.3 July 2018 Periodic Inspection and Testing of Electrical Installations Sample Test (2391-051) Version 1.3 July 2018 Sample Questions Version and date Change detail Section 1.3 July 2018 Modified questions/answers

More information

Test Report No.: GZHL HM Date: Aug 08, 2016 Page 1 of 10

Test Report No.: GZHL HM Date: Aug 08, 2016 Page 1 of 10 Test Report No.: GZHL1607032559HM Date: Aug 08, 2016 Page 1 of 10 ZHEJIANG BIO INDUSTRY&TRADE CO.,LTD NUM 1269,BADA ROAD,QIUBIN INDUSTRY PARK,JINHUA,CITY,ZHEJIANG PTOVINCE,CHINA. The following sample(s)

More information

V0. PLAY Downlight recessed. Description Recessed for indoor use.

V0. PLAY Downlight recessed. Description Recessed for indoor use. 71-3878-14-37 V0 Downlight recessed Description Recessed for indoor use. For downlighting. Up to 40,000 possible combinations. Lenses allow optimum control of illumination with minimal residual halo.,

More information

WCAP-FTXX Film Capacitors

WCAP-FTXX Film Capacitors A Dimensions: [mm] B Recommended hole pattern: [mm] D1 Electrical Properties: Properties Test conditions Value Unit Tol. Capacitance 1 V/ 1 khz ± 0.2 khz C 0.1000 µf ± 10% Rated voltage U R 310 V (AC)

More information

TEST REPORT IEC/EN Circuit-breakers for over current protection for household and similar installations

TEST REPORT IEC/EN Circuit-breakers for over current protection for household and similar installations Test Report issued under the responsibility of: TEST REORT IEC/EN 60898-1 Circuit-breakers for over current protection for household and similar installations Report Reference No.... : 130100913SHA-004

More information

Recommended Land Pattern: [mm]

Recommended Land Pattern: [mm] Dimensions: [mm] Recommended Land Pattern: [mm] Electrical Properties: Properties Test conditions Value Unit Tol. Capacitance 1 V/ 1 khz ± 0.2 khz C 150 nf ±10% Rated Voltage U R 310 V (AC) max. Rated

More information

M2 V0 IN ON A POLE. Material Aluminium Polycarbonate. Finish White Transparent TECHNICAL CHARACTERISTICS

M2 V0 IN ON A POLE. Material Aluminium Polycarbonate. Finish White Transparent TECHNICAL CHARACTERISTICS 71-5156-14-M2V0 ON A POLE Finish White Transparent IP20 Material Aluminium Polycarbonate 40º 50 TECHNICAL CHARACTERISTICS Light source Light source: LED Output (W): max. 13W Color temperature: Warm White

More information

2.12. Ex-Linear light fittings for fluorescent lamps - max. ambient temperature + 60 C - nllk W - 58 W for Zone 2 and 22

2.12. Ex-Linear light fittings for fluorescent lamps - max. ambient temperature + 60 C - nllk W - 58 W for Zone 2 and 22 .1 Ex-Linear light fittings for fluorescent lamps - max. ambient temperature + C - nllk 09 18 W - 58 W for Zone and The lighting solution for high temperatures up to C The linear luminaires series nllk

More information

FIXED THICK FILM CHIP RESISTORS; RECTANGULAR TYPE & HIGH OHM. RoHS COMPLIANCE ITEM Halogen and Antimony Free

FIXED THICK FILM CHIP RESISTORS; RECTANGULAR TYPE & HIGH OHM. RoHS COMPLIANCE ITEM Halogen and Antimony Free Spec. No.: RHC K HTS 0001 /8 Date: 2017. 1. 10 Specification Title: FIXED THICK FILM CHIP RESISTORS; RECTANGULAR TYPE & HIGH OHM Style:,20 RoHS COMPLIANCE ITEM Halogen and Antimony Free Product specification

More information

Economic and Social Council

Economic and Social Council United Nations Economic and Social Council ECE/TRANS/WP.9/GRE/010/53 Distr.: General 3 July 010 Original: English English and French only Economic Commission for Europe Inland Transport Committee World

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current Transducer LDSR 0.3-TP/SP1 I P R N = 300 ma For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Features Closed

More information

EX-EMERGENCY LIGHT FITTINGS

EX-EMERGENCY LIGHT FITTINGS EX-EMERGENCY LIGHT FITTINGS nllk 0...N 1-36 W Plastic version for Zone 2 and Zone 21/22 The explosion-protected light fittings of the series nllk 0 N are conform to the requirements of the ATEX-Directive

More information

Data sheet FIXED CHIP RESISTORS; RECTANGULAR TYPE & WIDE TERMINATION. AEC-Q200 qualified. RoHS COMPLIANCE ITEM Halogen and Antimony Free

Data sheet FIXED CHIP RESISTORS; RECTANGULAR TYPE & WIDE TERMINATION. AEC-Q200 qualified. RoHS COMPLIANCE ITEM Halogen and Antimony Free No.: TWMC K HTS-0001 /4 Date: 2017. 4. 21 Data sheet Title: FIXED CHIP RESISTORS; RECTANGULAR TYPE & WIDE TERMINATION Style: TWMC32, 50, 63 AEC-Q200 qualified RoHS COMPLIANCE ITEM Halogen and Antimony

More information

ABB SpA COMEM Operating Unit Strada Regionale 11, Signolo Montebello Vicentino (VI) - ITALY

ABB SpA COMEM Operating Unit Strada Regionale 11, Signolo Montebello Vicentino (VI) - ITALY ABB SpA COMEM Operating Unit Strada Regionale 11, Signolo 22 36054 Montebello Vicentino (VI) - ITALY www.abb.com/transformercomponents The information contained in this document is for general information

More information

Test Report No.: GZHL HM-01 Date: Aug 16, 2016 Page 1 of 10

Test Report No.: GZHL HM-01 Date: Aug 16, 2016 Page 1 of 10 Test Report No.: GZHL1608034628HM-01 Date: Aug 16, 2016 Page 1 of 10 ZHEJIANG BIO INDUSTRY&TRADE CO.,LTD NUM 1269,BADA ROAD,QIUBIN INDUSTRY PARK,JINHUA,CITY,ZHEJIANG PTOVINCE,CHINA. The following sample(s)

More information

Book 14 Edition 1.1 March Socketable Flat LED Module and LED Light Engine

Book 14 Edition 1.1 March Socketable Flat LED Module and LED Light Engine Book 14 Edition 1.1 March 2017 Socketable Flat LED Module and LED Light Engine Book 14 Summary (informative) Background The Zhaga Consortium is a global lighting-industry organization that aims to standardize

More information

Data sheet FIXED THICK FILM CHIP RESISTORS; RECTANGULAR TYPE ANDULTRAHIGH VOLTAGE. AEC-Q200 qualified. RoHS COMPLIANCE ITEM Halogen and Antimony Free

Data sheet FIXED THICK FILM CHIP RESISTORS; RECTANGULAR TYPE ANDULTRAHIGH VOLTAGE. AEC-Q200 qualified. RoHS COMPLIANCE ITEM Halogen and Antimony Free No.: RZC K HTS 0001 /6 Date: 2017. 4. 21 Data sheet Title: FIXED THICK FILM CHIP RESISTORS; RECTANGULAR TYPE ANDULTRAHIGH VOLTAGE Style: RZC50, 63 AEC-Q200 qualified RoHS COMPLIANCE ITEM Halogen and Antimony

More information

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-T...

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-T... Magnetic and Hydraulic-Magnetic Circuit Breaker 830-T... Description ngle, two and three pole magnetic and hydraulic-magnetic circuit breakers with trip-free mechanism and toggle actuation. A choice of

More information

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager. Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager. 1 -A - Introduction - Thank for your purchasing MITSUBISHI ELECTRIC MELPRO TM D Series Digital Protection

More information

Lamp and Control Panel (Lamp Panel)

Lamp and Control Panel (Lamp Panel) www.reinhausen.com Lamp and Control Panel (Lamp Panel) Operating Instructions BA 47/0 EN NOTE! Changes may have been made to a product after going to press with this documentation. We expressly reserve

More information

ISOCON-3 MAINS POWERED ISOLATING SIGNAL CONVERTER

ISOCON-3 MAINS POWERED ISOLATING SIGNAL CONVERTER ISOCON-3 MAINS POWERED ISOLATING SIGNAL CONVERTER CAUTION: This equipment is designed for connection to mains voltages and must be used in accordance with this guide. If it is not, the safety protection

More information

5484BN/R7DC-AHJB/XR/MS(ELA)

5484BN/R7DC-AHJB/XR/MS(ELA) Features High luminous intensity output Oval Shape Well defined spatial radiation Wide viewing angle (2θ 1/2 ) : 110 / 40 UV resistant epoxy The product itself will remain within RoHS compliant version

More information

LuxSpace recessed high efficiency, visual comfort and a stylish design

LuxSpace recessed high efficiency, visual comfort and a stylish design Lighting LuxSpace recessed high efficiency, visual comfort and a stylish design LuxSpace Mini, recessed Customers are looking to optimize all their resources, and that means not just their running costs

More information

PHASED OUT. FL ballasts Electronic dimming. PCA TC BASIC Y II, W BASIC compact

PHASED OUT. FL ballasts Electronic dimming. PCA TC BASIC Y II, W BASIC compact EL Product description Processor-controlled ballast with y II inside Highest possible energy class CELMA EEI = A BAT Noise-free precise control via DSI signal, switchdim or corridorfunction Nominal life

More information

Universal limit switches

Universal limit switches SWITCHES.CROUZET.COM 1 LIMIT SWITCHES 0/016 Universal limit switches 8384 standard 8384 with positive break operation Conformity to standards IEC / EN 60947--1, including Annex K for version with positive

More information

Pressure Measurement. Transmitters for basic requirements SITRANS P MPS (submersible sensor) Transmitter for hydrostatic level 2/27

Pressure Measurement. Transmitters for basic requirements SITRANS P MPS (submersible sensor) Transmitter for hydrostatic level 2/27 Overview Siemens AG 011 Function s are for measuring the liquid levels in wells, tanks, channels and dams. Diaphragm p Sensor U const. U + (brown) I EM I -1 (blue) 0, U B s are submersible sensors for

More information

Data sheet FIXED THICK FILM CHIP RESISTORS; RECTANGULAR TYPE AND HIGH POWER ANTI SURGE. AEC-Q200 qualified

Data sheet FIXED THICK FILM CHIP RESISTORS; RECTANGULAR TYPE AND HIGH POWER ANTI SURGE. AEC-Q200 qualified No.: RPCH-K-HTS-0001 /2 Date: 2017.4.21 Data sheet Title: Style: FIXED THICK FILM CHIP RESISTORS; RECTANGULAR TYPE AND HIGH POWER ANTI SURGE RPCH16,20,32,35 AEC-Q200 qualified RoHS COMPLIANCE ITEM Halogen

More information

TCLT10.. Series. Optocoupler with Phototransistor Output. Vishay Semiconductors. Description. Applications. VDE Standards

TCLT10.. Series. Optocoupler with Phototransistor Output. Vishay Semiconductors. Description. Applications. VDE Standards Optocoupler with Phototransistor Output Description The TCLT1.. Series consists of a phototransistor optically coupled to a gallium arsenide infraredemitting diode in a 4-lead SO6L package. The elements

More information

ISOCON-6. 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER

ISOCON-6. 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER ISOCON-6 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER Whilst every effort has been taken to ensure the accuracy of this document, we accept no responsibility for damage, injury, loss or expense resulting

More information

BETA Protecting. Low-Voltage Fuse Systems. LV HRC fuse links. 3/36 Siemens ET B1 2008

BETA Protecting. Low-Voltage Fuse Systems. LV HRC fuse links. 3/36 Siemens ET B1 2008 LV HRC fuse links Overview LV HRC fuses are used for installation systems in non-residential, commercial and industrial buildings as well as in switchboards of power supply companies. They therefore protect

More information

Data sheet FIXED THICK FILM CHIP RESISTORS; RECTANGULAR TYPE RMC1/32,1/20,1/16S,1/16,1/10,1/8,1/4,1/2,1. AEC-Q200 qualified (Without RMC1/32)

Data sheet FIXED THICK FILM CHIP RESISTORS; RECTANGULAR TYPE RMC1/32,1/20,1/16S,1/16,1/10,1/8,1/4,1/2,1. AEC-Q200 qualified (Without RMC1/32) No.: RMC-K-HTS-0006 /11 Date: 2017. 4. 18 Data sheet Title: Style: RMC1/32,1/20,1/16S,1/16,1/10,1/8,1/4,1/2,1 AEC-Q200 qualified (Without RMC1/32) RoHS COMPLIANCE ITEM Halogen and Antimony Free Note: Stock

More information

industry hall : highbay luminaire NJ700 LED Project number : sample system Customer : Processed by : Siteco Light Consulting Date : 07/2013

industry hall : highbay luminaire NJ700 LED Project number : sample system Customer : Processed by : Siteco Light Consulting Date : 07/2013 industry hall Customer : Processed by : Siteco Light Consulting Project description: spatial geometry (L*W*H): 54,00m*21,00m*9m reflection values (C*W*F): 70*50*20 maintenance factor: 0,67 user surface

More information

NR ROTARY RING TABLE: FLEXIBLE IN EVERY RESPECT

NR ROTARY RING TABLE: FLEXIBLE IN EVERY RESPECT NR FREELY PROGRAMMABLE ROTARY TABLES NR ROTARY RING TABLE All NR rings allow customer-specific drive motors to be connected NR ROTARY RING TABLE: FLEXIBLE IN EVERY RESPECT WHEN IT S GOT TO BE EXACT We

More information

Ex-Floodlight PXLED. (Ex-Zone 1, 2, 21 and 22)

Ex-Floodlight PXLED. (Ex-Zone 1, 2, 21 and 22) Ex-Floodlight PXLED (Ex-Zone 1, 2, 21 and 22) Lighting under harsh conditions The new modular LED floodlight series PXLED is suited for nearly every kind of lighting task in hazardous areas, including

More information

All part numbers in the coding below start with "TC-" and end with "203"

All part numbers in the coding below start with TC- and end with 203 1. Scope: This specification for approval relates to 2. Type designation: The type designation shall be in the following form : All part numbers in the coding below start with "TC-" and end with "203"

More information

LED light engine / OLED LED compact. Umodule STARK CLE CLASSIC EM STARK CLE STARK-CLE EM STARK-CLE EM-SO Ø315

LED light engine / OLED LED compact. Umodule STARK CLE CLASSIC EM STARK CLE STARK-CLE EM STARK-CLE EM-SO Ø315 D Product description Ideal for ceiling-mounted and wallmounted luminaires Based on annular and compact fluorescent lamps Efficiency of the module up to 127 lm/w SO version is compatible with SWITCH Sensor

More information

LED light engine / OLED LED compact. Uengine DLE G2 integrated ADV

LED light engine / OLED LED compact. Uengine DLE G2 integrated ADV Uengine DLE G2 integrated ADV uengine DLE Product description Module with integrated electronics For downlights Light engine operating with 23 V AC Luminous flux range from 1,24 2,43 lm High system efficacy

More information

Rectifying Diode RR2LAM6STF

Rectifying Diode RR2LAM6STF Rectifying Diode RR2LAM6STF Datasheet AEC-Q0 Qualified Series Dimensions (Unit : mm) Land Size Figure (Unit : mm) Standard Rectifier 2.50±0.20 0.7± 0.0 0.05 2.0 ().4 Applications General rectification

More information

LED light engine / OLED LED compact. Uready2apply DLA G1 SNC China domestic

LED light engine / OLED LED compact. Uready2apply DLA G1 SNC China domestic Uready2apply DLA G1 SNC China domestic uready2apply DLA Product description Downlight module suitable for direct installation in ceilings (ready2apply) Module with integrated electronics and heatsink Light

More information

Cree Racine Engineering Services Testing Laboratory (RESTL) Photometric Testing and Evaluation Report

Cree Racine Engineering Services Testing Laboratory (RESTL) Photometric Testing and Evaluation Report NVLAP Lab Code 500089-0 Report Number: Model: RESTL-2013-0013 E-WP6L03CZ Date: 8/30/2013 Cree Racine Engineering Services Testing Laboratory (RESTL) Photometric Testing and Evaluation Report Prepared For:

More information

Get your city ready for the future with DigiStreet

Get your city ready for the future with DigiStreet Lighting Get your city ready for the future with DigiStreet DigiStreet Developed with the aim of becoming your long-term partner,the system-ready architecture of DigiStreet enables you to enjoy the benefits

More information

Cree Racine Engineering Services Testing Laboratory (RESTL) Photometric Testing and Evaluation Report

Cree Racine Engineering Services Testing Laboratory (RESTL) Photometric Testing and Evaluation Report Report Number: Model: PL03375-001 CPY250-A-xx-D-C-UL-xx-40K or Date: 03/24/2014 BXCCAxD04-UW7 or XCCAxD04-UW7 Cree Racine Engineering Services Testing Laboratory (RESTL) Photometric Testing and Evaluation

More information

Non-destructive testing of steel forgings- Part 1: Magnetic particle inspection (BS EN :1999)

Non-destructive testing of steel forgings- Part 1: Magnetic particle inspection (BS EN :1999) Non-destructive testing of steel forgings- Part 1: Magnetic particle inspection (BS EN 10228-1:1999) 1 Scope This part of EN 10228 describes the method and acceptance criteria to be used for the magnetic

More information

Chip tantalum capacitors (Fail-safe open structure type)

Chip tantalum capacitors (Fail-safe open structure type) TCFG1C6M8R Chip tantalum capacitors (Fail-safe open structure type) TCFG Series Case Features 1) Safety design by open function built - in. 2) Wide capacitance range 3) Screening by thermal shock. Dimensions

More information

Sales: Malux Finland Oy, P.O.Box 69, FI Porvoo, Phone , Fax ,

Sales: Malux Finland Oy, P.O.Box 69, FI Porvoo, Phone , Fax , E X - L I G H T F I T T I N G S nllk 0... 1 - W All-plastic design for Zone 2 and Zone 21/22 The explosion-protected light fittings of the series nllk 0 conform to the requirements of the ATEX-Directive

More information

Transmitters for basic requirements SITRANS P MPS (submersible sensor) Transmitter for hydrostatic level

Transmitters for basic requirements SITRANS P MPS (submersible sensor) Transmitter for hydrostatic level Overview Function s are for measuring the liquid levels in wells, tanks, channels and dams. Sensor Diaphragm p U const. U +2 (brown) I EM I - (blue) 0, U B s are submersible sensors for hydrostatic level

More information

Chip tantalum capacitors (Fail-safe open structure type)

Chip tantalum capacitors (Fail-safe open structure type) TCFG0J106M8R Chip tantalum capacitors (Fail-safe open structure type) TCFG Series Case Features 1) Safety design by open function built - in. 2) Wide capacitance range 3) Screening by thermal shock. Dimensions

More information

PHASED OUT. LED light engine / OLED LED linear / area. Umodule STARK QLE G2 CLASSIC STARK QLE

PHASED OUT. LED light engine / OLED LED linear / area. Umodule STARK QLE G2 CLASSIC STARK QLE Product description Ideal for linear and panel lights Luminous flux range from 1,19 1,53 lm LED system solution with outstanding system efficiency up to 125 lm/w, consisting of squared LED modules and

More information

Fire Resistant Armoured Power Cable

Fire Resistant Armoured Power Cable Power and Wiring Cables Fire Resistant Armoured Power Cable 00/00V Application Armoured fire resistant cable for use in fixed wiring installations where it is necessary for the cable to retain circuit

More information

I nllk 08018/18 I nllk I nllk 08036/36 I nllk I I nllk 08058/58 I

I nllk 08018/18 I nllk I nllk 08036/36 I nllk I I nllk 08058/58 I I nllk / I x W x W x W x W x W Technical data Cooper Crouse-Hinds - all rights reserved nllk / nllk nllk / nllk nllk / Marking to //EC II G Ex na II T / II D td A IP T C EC Conformity Statement PTB ATEX

More information

4.13. Ex-Floodlights of the series FMV LED / NSSFMV. (Zone 2, 22) service life and a high level of efficiency. NFMV floodlights for highpressure

4.13. Ex-Floodlights of the series FMV LED / NSSFMV. (Zone 2, 22) service life and a high level of efficiency. NFMV floodlights for highpressure .13 Ex-Floodlights of the series / (Zone 2, 22) The powerful LED floodlights FMV LED The new series of energy-saving FMV floodlights in LED technology are ideal for all general lighting applications in

More information

Schottky Barrier Diode RBR10NS40AFH

Schottky Barrier Diode RBR10NS40AFH Schottky Barrier Diode RBRNS4AFH AEC-Q1 Qualified Application Dimensions (Unit : mm) Land size figure (Unit : mm) Switching power supply (2) 11 2.5 Features 1) Cathode common dual type 2) High reliability

More information

TEST CERTIFICATES OR REPORTS ISSUED BY VEIKI-VNL LTD.

TEST CERTIFICATES OR REPORTS ISSUED BY VEIKI-VNL LTD. Page 2 of 29 TEST CERTIFICATES OR REPORTS ISSUED BY LTD. Type Test Certificate of Complete Type Test This certificate provides the verification of all the rated characteristics of the equipment as assigned

More information

Thermal-Magnetic Circuit Breaker 2210-T2...

Thermal-Magnetic Circuit Breaker 2210-T2... Thermal-Magnetic Circuit Breaker 0-T... Description One, two and three pole thermal-magnetic circuit breakers with trip-free mechanism and toggle actuation (S-type TM CBE to EN 6094/IEC 94). Featuring

More information

High-Voltage Types Ordering Information, Mica Capacitors

High-Voltage Types Ordering Information, Mica Capacitors High-Voltage Types Ordering Information, Mica Capacitors Ordering Information Ordering Information: Order by complete part number, as below. For other options,write your requirements on your quote request

More information

Tunable White LED compact

Tunable White LED compact Module TW DLE G2 60mm 3000lm 927-965 DLE modules Product description module for Downlights with adjustable colour temperature from 2,700 to 6,500 K at constant luminous flux High colour rendering index

More information

Rectifier Diode RR2L4S

Rectifier Diode RR2L4S 5.3±0. 0.05 9.5±0. 5.5±0.05 ±0..75±0. Rectifier Diode RRL4S Series Dimensions (Unit : mm) Land size figure (Unit : mm) Standard Rectifier.0.0 4.5±0. 5.0±0.3.±0.3.6±0. Application 4. General rectification

More information

Explosion-protected recessed ceiling LED-light and fluorescent light fittings

Explosion-protected recessed ceiling LED-light and fluorescent light fittings .7 Explosion-protected recessed ceiling LED-light and fluorescent light fittings LED 600, RLF LED 100 and self-contained emergency luminaire RLF LED 600 N, RLF LED 100 N RLF/RLF-INOX 50 18-58 W / RLF/RLF-INOX

More information

FL ballasts Electronic dimming. PCA TC ECO Y II, W ECO compact

FL ballasts Electronic dimming. PCA TC ECO Y II, W ECO compact FL ballasts EL TC-F TC-SEL TC-L HE TC-DD Tc PCA TC ECO Y II, 7 W ECO compact Product description Processor-controlled ballast with y II inside Highest possible energy class CELMA EEI = A BAT Noise-free

More information

Metal Oxide Film Resistors Axial Connections Metal Oxide Film Resistors 1/4W, 5% Components

Metal Oxide Film Resistors Axial Connections Metal Oxide Film Resistors 1/4W, 5% Components Metal Oxide Film Resistors Axial Connections Metal Oxide Film Resistors 1/4W, 5% Components High safety standard, high purity ceramic core Excellent non-flame coating Stable performance in diverse environment,

More information

Procedure To Be Adopted When Working on High Voltage Mechanically Switched Capacitors with Damping Network (MSCDN)

Procedure To Be Adopted When Working on High Voltage Mechanically Switched Capacitors with Damping Network (MSCDN) 1. SCOPE This document details the procedures to be adopted when working on High Voltage Mechanically Switched Capacitors with. 2. ISSUE RECORD This is a Reference document. The current version is held

More information

LED light engine / OLED LED compact. Umodule STARK DLE CLASSIC STARK DLE 82,8 54,4. Ordering data

LED light engine / OLED LED compact. Umodule STARK DLE CLASSIC STARK DLE 82,8 54,4. Ordering data Product description Downlights High-flux LED module Low tolerances for colour temperatures (MacAdams 4) Compact design Excellent thermal management 1 NTC for temperature control High-power LED module in

More information

Kingspan Smart-Lite Kite Luminaire

Kingspan Smart-Lite Kite Luminaire Kingspan Smart-Lite Kite Luminaire The Kite High Bay products are designed to complement the ZEL (Zero Energy Lighting) initiative championed by Kingspan. The combination of pressure die-cast aluminium

More information

Installation guide 862 MIT / MIR

Installation guide 862 MIT / MIR Installation guide 862 MIT / MIR in combination with: 864 MTT or 863 MRT or (dual) spot element November 2005 Part no. 4416.232_Rev3 Enraf BV PO Box 812 2600 AV Delft Netherlands Tel. : +31 15 2701 100

More information

AIR CONDITIONER (SPLIT TYPE) SERVICE MANUAL

AIR CONDITIONER (SPLIT TYPE) SERVICE MANUAL AIR CONDITIONER (SPLIT TYPE) SERVICE MANUAL FILE No. A10-023-1 REVISION 1 : Mar.2012 Re-edit version.( file volume down) Contents have NOT been changed. Model name: RAS-M10PKVP-E RAS-M13PKVP-E RAS-M16PKVP-E

More information

Cree Racine Engineering Services Testing Laboratory (RESTL) Photometric Testing and Evaluation Report

Cree Racine Engineering Services Testing Laboratory (RESTL) Photometric Testing and Evaluation Report NVLAP Lab Code 500089-0 Report Number: Model: PL10023-003B ARE-EDG-2MB-xx-06-E-UL-xx-525-xxxx-40K Date: 02/28/2017 Cree Racine Engineering Services Testing Laboratory (RESTL) Photometric Testing and Evaluation

More information

Cree Racine Engineering Services Testing Laboratory (RESTL) Photometric Testing and Evaluation Report

Cree Racine Engineering Services Testing Laboratory (RESTL) Photometric Testing and Evaluation Report Report Number: Model: PL05642-001B CPY250AxxDB-UL40Kxxxx / BXCCAxD13-Ux7xxxx Date: 06/26/2015 Cree Racine Engineering Services Testing Laboratory (RESTL) Photometric Testing and Evaluation Report Prepared

More information

solid state LED LED LED LED LED LED Light Emitting Diode: LED LED module Self - ballasted LED module Integral LED module

solid state LED LED LED LED LED LED Light Emitting Diode: LED LED module Self - ballasted LED module Integral LED module Light Emitting Diode: p-n solid state module Self - ballasted module Integral module Integral Self - ballasted module Built - in module Built - in Self - ballasted module Independent module Independent

More information

MKP-X2 TECHNICAL TERMS EXPLANATION

MKP-X2 TECHNICAL TERMS EXPLANATION TECHNICAL TERMS EXPLANATION Rated capacitance Capacitance referred to 1 khz, 20 +-1ºC, 65+-2% of relative humidity and 96+- 10 kpa. In case of doubt please refer to IEC 60068-1, sub-clause 5.2. Capacitance

More information

TEST REPORT IEC :2002 Circuit-Breakers for overcorrect protection for household and similar installation

TEST REPORT IEC :2002 Circuit-Breakers for overcorrect protection for household and similar installation age 1 of 92 R e port ref. No.: C009-CB2012CQC-044407 Test Report issued under the responsibility of: TEST REORT IEC 60 898-1:2002 Circuit-Breakers for overcorrect protection for household and similar installation

More information

Film Capacitors. EMI suppression capacitors. Date: June 2018

Film Capacitors. EMI suppression capacitors. Date: June 2018 Film Capacitors EMI suppression capacitors Date: June 2018 EPCOS AG 2018. Reproduction, publication and dissemination of this publication, enclosures hereto and the information contained therein without

More information

Cree Racine Engineering Services Testing Laboratory (RESTL) Photometric Testing and Evaluation Report

Cree Racine Engineering Services Testing Laboratory (RESTL) Photometric Testing and Evaluation Report Report Number: Model: PL05591-001B CPY250AxxFB-UL40Kxxxx / BXCCAxA13-Ux7xxxx Date: 06/26/2015 Cree Racine Engineering Services Testing Laboratory (RESTL) Photometric Testing and Evaluation Report Prepared

More information

Cree Racine Engineering Services Testing Laboratory (RESTL) Photometric Testing and Evaluation Report

Cree Racine Engineering Services Testing Laboratory (RESTL) Photometric Testing and Evaluation Report Report Number: Model: PL09285-001 ARE-EDG-5M-xx-06-E-UL-xx-700-xxxx-40K Date: 09/13/2016 Cree Racine Engineering Services Testing Laboratory (RESTL) Photometric Testing and Evaluation Report Prepared For:

More information

Cree Racine Engineering Services Testing Laboratory (RESTL) Photometric Testing and Evaluation Report

Cree Racine Engineering Services Testing Laboratory (RESTL) Photometric Testing and Evaluation Report Report Number: Model: PL09294-001A ARE-EDG-3M-xx-06-E-UL-xx-700-xxxx Date: 09/14/2016 Cree Racine Engineering Services Testing Laboratory (RESTL) Photometric Testing and Evaluation Report Prepared For:

More information

Thermal-Magnetic Circuit Breaker 2210-S2..

Thermal-Magnetic Circuit Breaker 2210-S2.. Thermal-Magnetic Circuit Breaker -S.. Description One, two and three pole thermal-magnetic circuit breakers with trip free mechanism and toggle actuation (S-type TM CBE to EN 60934/IEC 934). Designed for

More information

Internal Components Forms of Separation

Internal Components Forms of Separation IEC 60439-1 One or more of the following conditions can be attained by dividing ASSEMBLIES by means of partitions or barriers (metallic or non-metallic) into separate compartments or enclosed protected

More information

Cree Racine Engineering Services Testing Laboratory (RESTL) Photometric Testing and Evaluation Report

Cree Racine Engineering Services Testing Laboratory (RESTL) Photometric Testing and Evaluation Report Report Number: Model: PL06410-001A CPY250-A-xx-D-D-UL-40K-xxxx or BXCCAxD17-Ux7xxxx Date: 07/17/2015 Cree Racine Engineering Services Testing Laboratory (RESTL) Photometric Testing and Evaluation Report

More information

CAPACITORS, FIXED, TUBULAR, POROUS TANTALUM CATHODE AND ANODE, GELLED ELECTROLYTE, HERMETICALLY SEALED BASED ON TYPE ST79

CAPACITORS, FIXED, TUBULAR, POROUS TANTALUM CATHODE AND ANODE, GELLED ELECTROLYTE, HERMETICALLY SEALED BASED ON TYPE ST79 Pages 1 to 15 CAPACITORS, FIXED, TUBULAR, POROUS TANTALUM CATHODE AND ANODE, GELLED ELECTROLYTE, HERMETICALLY SEALED BASED ON TYPE ST79 Issue 1 November 2007 Document Custodian: European Space Agency -

More information

ISSPRO 3 3/8 Programmable Tachometer High Performance EV Line Part Numbers R5535M, R6535M

ISSPRO 3 3/8 Programmable Tachometer High Performance EV Line Part Numbers R5535M, R6535M General Information: I n c o r p o r a t e d ISSPRO 3 3/8 Programmable Tachometer High Performance EV Line Part Numbers R5535M, R6535M ISSPRO, INC. 2515 N.E. Riverside Way, Portland OR 97211 Telephone:

More information

Table of Contents Pin-Configuration Selection Guide for HDE, HDS, & EFP

Table of Contents Pin-Configuration Selection Guide for HDE, HDS, & EFP Table of Contents -Configuration Selection Guide for HDE, HDS, & EFP Service Voltage Rating... Electrical Service Ratings... Ampacity Ratings by Contact... Electrical Service Ratings Explained... Operating

More information

Cree Racine Engineering Services Testing Laboratory (RESTL) Photometric Testing and Evaluation Report

Cree Racine Engineering Services Testing Laboratory (RESTL) Photometric Testing and Evaluation Report Report Number: Model: PL06411-001A CPY250-A-xx-F-D-UL-40K-xxxx or BXCCAxA17-Ux7xxxx Date: 07/17/2015 Cree Racine Engineering Services Testing Laboratory (RESTL) Photometric Testing and Evaluation Report

More information

PRODUCT FAMILY DATASHEET LEDVANCE FLOODLIGHT LED

PRODUCT FAMILY DATASHEET LEDVANCE FLOODLIGHT LED LEDVANCE FLOODLIGHT LED LED floodlight luminaires AREAS OF APPLICATION Replacement for floodlights with halogen lamps Car parks and underpasses Garages Public areas Building facades Construction areas

More information

Ex-Floodlights of the series FMV LED / NFMV / NSSFMV. Stainless steel NSSFMV floodlights for particularly. in harsh environments

Ex-Floodlights of the series FMV LED / NFMV / NSSFMV. Stainless steel NSSFMV floodlights for particularly. in harsh environments .13 Ex-Floodlights of the series / / (Zone 2, 21, 22) The powerful LED floodlights FMV/nFMV LED The new series of energy-saving FMV floodlights in LED technology are ideal for all ge neral lighting applications

More information

TEST REPORT. Page 1 of 11

TEST REPORT. Page 1 of 11 Applicant: Radomir Klabal Komenskeho 446, Bilovice nad Svitavou, Czech Republic Sample Description Product : Compact Fluorescent Lamp Model No. : CFL15T2S27E27 Brand Name : Divetta Electrical Rating :

More information

PHASED OUT. LED light engine / OLED LED compact. Umodule SLE G4 15mm 2000lm 8x0 H ADV D50

PHASED OUT. LED light engine / OLED LED compact. Umodule SLE G4 15mm 2000lm 8x0 H ADV D50 w LED light engine / OLED Product description For spotlights and downlights Housing with Snap-On feature for easy reflector mounting Luminous flux up to 2,92 lm at tp = 65 C High efficacy up to 147 lm/w

More information

PHASED OUT. LED light engine / OLED LED compact. Umodule SLE G4 15mm 2000lm 9x0 H EXC D50

PHASED OUT. LED light engine / OLED LED compact. Umodule SLE G4 15mm 2000lm 9x0 H EXC D50 w LED light engine / OLED Product description For spotlights and downlights Housing with Snap-On feature for easy reflector mounting Luminous flux up to 2,51 lm at tp = 65 C High efficacy up to 124 lm/w

More information

The FLUX F 430 with mechanical seal

The FLUX F 430 with mechanical seal The FLUX F 0 with mechanical seal Flexible coupling between motor and pump The pump must be used with many varying liquids, consequently the smallest residual left within the pump is unacceptable. You

More information

Amphenol. Amphenol-Tuchel Electronics GmbH. Series C 146 Heavy Duty Connectors Core Programme

Amphenol. Amphenol-Tuchel Electronics GmbH. Series C 146 Heavy Duty Connectors Core Programme Amphenol Amphenol-Tuchel Electronics GmbH Series C 146 Heavy Duty Connectors Core Programme The Company General information These connectors are designed and produced in conformity with the voltage directive

More information

Emergency lighting units EM Inverter

Emergency lighting units EM Inverter T T TC- TC-F DE TC- TC-SE TC-TE TC-DD Tc EM G, 0 0 V 0/0 Hz BASIC version Product description Emergency lighting supply unit for manual testing For linear and compact fluorescent lamps ow-profile casing

More information

8 Installation Equipment

8 Installation Equipment 8 Installation Equipment Plugs and Sockets CES System Series 8, 88, 8, 881 Te plugs and sockets in te CES system comply wit CEE publication 1 and European standards EN 0 01. Te small 1 A socket as switcing

More information