TECHNICAL INFORMATION MANUAL

Size: px
Start display at page:

Download "TECHNICAL INFORMATION MANUAL"

Transcription

1 TEHNIAL INFORMATION MANUAL AMV9/AV9 40" 90% Gas Furnace Units Model numbers listed on page 3. Refer to Service Manual RS for installation, operation, and troubleshooting information. All safety information must be followed as provided in the Service Manual. Refer to the appropriate Parts atalog for part number information. US This manual is to be used by qualified, professionally trained HVA technicians only. Goodman does not assume any responsibility for property damage or personal injury due to improper service procedures performed by an unqualified person. RT Rev. June 007 is a trademark of Maytag orporation and is used under license to Goodman ompany, L.P. All rights reserved. opyright Goodman ompany, L.P.

2 PRODUT IDENTIFIATION The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information. A M V B X A Product Type G: Gas Furnace Supply Type : ounterflow/horizontal M: Upflow/Horizontal Design Series A: Initial Release Additional Features N: Natural Gas X: Low NOx abinet Width Furnace Type V: Variable - Stage ondensing (90%) A: 14" B: 17 1/" : 1" D: 4 1/" Model Family 9: Air ommand 90 (40" Height) Airflow apability 3: 100 4: : 000 Nominal Input 045: 45,000 Btuh 070: 70,000 Btuh 090: 90,000 Btuh 115: 115,000 Btuh WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. WARNING WARNING Installation and repair of this unit should be performed ONLY by individuals meeting the requirements of an "entry level technician" as specified by the Air onditioning and Refrigeration Institute (ARI). Attempting to install or repair this unit without such background may result in product damage, personal injury or death. Goodman will not be responsibile for any injury or property damage arising from improper service or service procedures. If you install or perform service on this unit, you assume responsibility for any personal injury or property damage which may result. Many jurisdictions require a license to install or service heating and air conditioning equipment.

3 PRODUT IDENTIFIATION The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information. AMV90453BX AMV90704X AMV90905DX AMV91155DX AV90704X AV90905DX WARNING The United States Environmental Protection Agency ( EPA ) has issued various regulations regarding the introduction and disposal of refrigerants introduced into this unit. Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines. These regulations may vary by jurisdiction. Should questions arise, contact your local EPA office. WARNING To prevent the risk of property damage, personal injury, or death, do not store combustible materials or use gasoline or other flammable liquids or vapors in the vicinity of this appliance. WARNING Do not connect or use any device that is not design certified by Goodman for use with this unit. Serious property damage, personal injury, reduced unit performance and/or hazardous conditions may result from the use of such non-approved devices. 3

4 PRODUT DESIGN General Operation The AMV9 and AV9 furnaces are equipped with an electronic ignition device to light the burners and an induced draft blower to exhaust combustion products. An interlock switch prevents furnace operation if the blower door is not in place. Keep the blower access doors in place except for inspection and maintenance. This furnace is also equipped with a self-diagnosing electronic control module. In the event a furnace component is not operating properly, the control module LED will flash on and off in a factory-programmed sequence, depending on the problem encountered. This light can be viewed through the observation window in the blower access door. Refer to the Troubleshooting hart for further explanation of the LED codes and Abnormal Operation - Integrated Ignition ontrol section in the Service Instructions for an explanation of the possible problem. The rated heating capacity of the furnace should be greater than or equal to the total heat loss of the area to be heated. The total heat loss should be calculated by an approved method or in accordance with ASHRAE Guide or Manual J-Load alculations published by the Air onditioning ontractors of America. Obtain from: American National Standards Institute 1430 Broadway New York, NY Location onsiderations The furnace should be as centralized as is practical with respect to the air distribution system. Do not install the furnace directly on carpeting, tile, or combustible material other than wood flooring. When suspending the furnace from rafters or joists, use 3/8" threaded rod and x x 1/8 angle as shown in the Installation and Service Instructions. The length of the rod will depend on the application and clearance necessary. When installed in a residential garage, the furnace must be positioned so the burners and ignition source are located not less than 18 inches (457 mm) above the floor and protected from physical damage by vehicles. Notes: 1. Installer must supply one or two PV pipes: one for combustion air (optional) and one for the flue outlet (required). Vent pipe must be either or 3 in diameter, depending upon furnace input, number of elbows, length of run and installation (1 or pipes). The optional ombustion Air Pipe is dependent on installation/code requirements and must be or 3 diameter PV.. Line voltage wiring can enter through the right or left side of the furnace. Low voltage wiring can enter through the right or left side of furnace. 3. onversion kits for propane gas and high altitude natural and propane gas operation are available. See High Altitude Derate chart for details Installer must supply the following gas line fittings, depending on which entrance is used: Left -- Two 90 Elbows, one close nipple, straight pipe Right -- Straight pipe to reach gas valve. Accessibility learances (Minimum) AMV9 MINIMUM LEARANES TMBUSTIBLE MATERIALS (INHES) POSITION FRONT SIDES REAR TOP FLUE FLOOR Upflow Horizontal = All positioning is determined as installed unit is viewed from the front. = If placed on combustible floor, floor MUST be wood only. N= For instalaltion on non-combustible floors only. A combustible subbase must be used for installations on combustible flooring. AV9 MINIMUM LEARANES TMBUSTIBLE MATERIALS (INHES) POSITION FRONT SIDES REAR TOP FLUE FLOOR Upflow N Horizontal = All positioning is determined as installed unit is viewed from the front. = If placed on combustible floor, floor MUST be wood only. N= For instalaltion on non-combustible floors only. A combustible subbase must be used for installations on combustible flooring. 36" at front is required for servicing or cleaning. Note: In all cases accessibility clearance shall take precedence over clearances from the enclosure where accessibility clearances are greater. All dimensions are given in inches. High Altitude Derate When this furnace is installed at high altitude, the appropriate High Altitude orifice kit must be installed. This is required due to the natural reduction in the density of both the gas fuel and combustion air as altitude increases. The kit will provide the proper design certified input rate within the specified altitude range. Furnace AMV90453BX AMV90704X AMV90905DX AMV91155DX AV90704X AV90905DX No hange No hange No hange 0-7,000 Feet (Standard Altitude) LPM-05 #55 Orifice LPM-05 #55 Orifice LPM-05 #55 Orifice No hange No hange No hange "STANDARD" and "HIGH ALTITUDE" KITS HANG13 #44 Orifice HANG13 #44 Orifice HANG13 #44 Orifice 7,001-9,000 Feet HANG14 HALP11 #56 Orifice HAPS8 #45 Orifice HALP11 #56 Orifice HALP11 #56 Orifice HAPS9 HAPS9 HANG14 #45 Orifice HANG14 #45 Orifice 9,001-11,000 Feet ID Blwr ID Blwr ID Blwr Gas Orifices Gas Orifices Gas Orifices Pressure Pressure Pressure Natural Propane Switch Natural Propane Switch Natural Propane Switch HALP11 #56 Orifice HALP11 #56 Orifice HALP11 #56 Orifice HAPS8 HAPS9 HAPS31 High altitude kits are purchased according to the installation altitude and usage of either natural or propane gas. Refer to the chart above for a tabular listing of appropriate altitude ranges and corresponding manufacturer s high altitude Natural Gas and Propane Gas kits. For a tabular listing of appropriate altitude ranges and corresponding manufacturer's High Altitude Pressure Switch kits, refer to either the Pressure Switch Trip Points & Usage hart in this manual or the Accessory harts in Service Instructions.

5 OMPONENT IDENTIFIATION BLOWER OMPARTMENT BURNER OMPARTMENT Intell-Ignition BLOWER OMPARTMENT Upflow/Horizontal ounterflow /Horizontal 1 Two-Stage Gas Valve Gas Line Entrance (Alternate) 3 Pressure Switch(es) 4 Gas Manifold 5 ombustion Air Intake onnection 6 Hot Surface Igniter 7 Rollout Limit 8 Burners 9 Flame Sensor 10 Flue Pipe onnection 11 Flue Pipe 1 Primary Limit 13 Gas Line Entrance 14 Flue Pipe onnection (Alternate) 15 Rubber Elbow 16 Two- Induced Draft Blower 17 Electrical onnection Inlets (Alternate) 18 oil Front over Pressure 19 oil Front over Drain Port 0 Drain Line Penetrations 1 Drain Trap Blower Door Interlock Switch 3 Inductor (Not All Models) 4 Two-Stage Integrated ontrol Module (with fuse and diagnostic LED) 5 4 Volt Thermostat onnections 6 Transformer (40 VA) 7 EM Variable irculator Blower 8 Auxiliary Limit 9 Junction Box 30 Electrical onnection Inlets 31 oil Front over 3 ombustion Air Inlet Pipe (AV9 only) 5

6 PRODUT DIMENSIONS AMV9 X AIR DISHARGE 8 3/4 3/4 3/4 0 3/16 1/ AIR INTAKE PIPE " PV A B (DISHARGE AIR) 3/4 1/16 VENT/FLUE PIPE " PV AIR DISHARGE 14 ALTERNATE GAS SUPPLY HOLE LEFT SIDE DRAIN LINE HOLES 3 LOW VOLTAGE ELETRIAL HOLE HIGH VOLTAGE ELETRIAL HOLE SIDE UT-OUT 5/8 1 3/4 7 3/8 DRAIN TRAP L 19 3/ /4 9 3/8 30 1/4 40 ONDENSATE DRAIN TRAP w/ 3/4" PV DISHARGE (RIGHT OR LEFT SIDE) 16 5/8 30 1/4 3 13/16 11/16 4 1/8 7 1/8 5/8 19 3/ /4 7 7/8 6 1/8 DRAIN TRAP L 1 3/4 ALTERNATE AIR INTAKE LOATION STANDARD GAS SUPPLY HOLE ALTERNATE VENT/FLUE LOATION RIGHT SIDE DRAIN LINE HOLES LOW VOLTAGE ELETRIAL HOLE HIGH VOLTAGE ELETRIAL HOLE SIDE UT-OUT 1 5/8 1 1/ 3 9/16 BOTTOM KNOK-OUT D BOTTOM KNOK-OUT LEFT SIDE VIEW FRONT VIEW RIGHT SIDE VIEW ABINET SIZE UNITS A B D SMALL 0453BX 17 1/ /8 1 5/8 MEDIUM 0704X /8 14 5/8 LARGE 0905DX 1155DX 4 1/ 3 0 3/8 18 5/8 All dimensions are in inches. 6

7 PRODUT DIMENSIONS LEFT SIDE VIEW AV9 X FRONTVIEW RIGHT SIDE VIEW 8 3/4 3/4 0 1/4 1/ AIR INTAKE PIPE " PV 3/4 A B (RETURN AIR) 3/4 1/16 VENT/FLUE PIPE " PV LOW VOLTAGE ELETRIAL HOLE 1 3/4 40 ONDENSATE DRAIN TRAP w/ 3/4" PV DISHARGE (RIGHT OR LEFT SIDE) 1 3/4 LOW VOLTAGE ELETRIAL HOLE HIGH VOLTAGE ELETRIAL HOLE HIGH VOLTAGE ELETRIAL HOLE LEFT SIDE DRAIN LINE HOLES STANDARD GAS SUPPLY HOLE DRAIN TRAP L 5/8 4 1/8 11 1/ 9 13/ / 8 5/16 8 1/4 8 5/ / / /8 11/ /8 9 3/4 7 3/8 ALTERNATE VENT/FLUE LOATION ALTERNATE AIR INTAKE LOATION DRAIN 5/8 TRAP L RIGHT SIDE DRAIN LINE HOLES ALTERNATE GAS SUPPLY HOLE 18 5/8 UNFOLDED FLANGES 0 5/3 FOLDED FLANGES AIR DISHARGE D UNFOLDED FLANGES E FOLDED FLANGES DISHARGE AIR AIR DISHARGE ABINET SIZE UNITS A B D MEDIUM 0704X /8 14 5/8 LARGE 0905DX 4 1/ 3 0 3/8 18 5/8 All dimensions are in inches. NOTE: Airflow area will be reduced by approximately 18% if duct flanges are not unfolded. This could cause performance issues and noise issues. 7

8 PRODUT DESIGN MODEL SWITH TRIP POINTS AND USAGE HART NEGATIVE ID BLOWER WITH FLUE NOT FIRING TYPIAL SEA LEVEL DATA LOW HIGH NEGATIVE ID BLOWER WITH FLUE FIRING TYPIAL SEA LEVEL DATA LOW HIGH NEGATIVE OIL OVER WITH FLUE NOT FIRING TYPIAL SEA LEVEL DATA LOW HIGH NEGATIVE OIL OVER WITH FLUE FIRING TYPIAL SEA LEVEL DATA LOW HIGH AMV90453BX AMV90704X AMV90905DX AMV91155DX AV90704X AV90904DX Note: The typical sea level negative pressure data represents the minimum pressures expected. Shorter length of flue pipe or single pipe systems compared to dual pipe systems should show higher (greater negative) pressures. SWITH TRIP POINTS AND USAGE HART MODEL TRIP POINT OIL OVER SWITH LOW HIGH OIL OVER SWITH PART # LOW 0 to 7,000 ft. TRIP POINT ID BLOWER SWITH HIGH ID BLOWER SWITH PART # PS1 LABEL OLOR PS LABEL OLOR TRIP POINT OIL OVER SWITH LOW HIGH LOW 7,001 ft. to 11,000 ft. TRIP POINT ID BLOWER SWITH HIGH HIGH ALTITUDE KIT PS1 LABEL OLOR PS LABEL OLOR AMV90453BX AMV90704X PURPLE PINK HAPS GREEN YELLOW AMV90905DX AMV91155DX ITE GRAY HAPS ORANGE LT BLUE AV90704X GREEN PURPLE HAPS YELLOW RED AV90905DX GREEN PURPLE HAPS Note: All installations above 7,000 ft. require a pressure switch change. For installations in anada the AMV9 & AV9 furnaces are certified only to 4500 ft. Note: Replacement pressure switch number is listed below high altitude kit number. Note: All negative pressure readings are in inches of water column (" w.c.). YELLOW RED 8

9 PRODUT DESIGN T.O.D. PRIMARY LIMIT Part Number Open Setting ( F) AMV90453BX 1 AMV90704X 1 AMV90905DX 1 AMV91155DX 1 AV90704X 1 AV90905DX 1 ROLLOUT LIMIT SWITHES Part Number Open Setting ( F) AMV90453BX 1 AMV90704X AMV90905DX AMV91155DX AV90704X AV90905DX AUXILIARY LIMIT SWITHES Part Number Open Setting ( F) AMV90453BX AMV90704X AMV90905DX AMV91155DX AV90704X AV90905DX 9

10 PRODUT DESIGN oil Matches: A large array of Amana brand coils are available for use with the AV9 furnaces, in either counterflow or horizontal applications & with AMV9 furnaces, in either upflow or horizontal applications. These coils are available in both cased and uncased models, with or without a TXV expansion device. These 9%+ and 95%+ furnaces match up with the existing Amana brand coils as shown in the chart below. oil Matches (for Amana Brand units using R and R-410A): A P F 184 A 6 A Product Type : Indoor oil Expansion Device F: Flowrator Revision A: Revision abinet Finish U: Uncased P: Painted : Unpainted ase Refrigerant 6: R- or R-410A : R- 4: R-410A Nominal Width for Gas Furnace Application A: Upflow/Downflow oil H: Horizontal A oil S: Horizontal Slab oil A: Fits 14" Furnace abinet B: Fits 17 1/" Furnace abinet : Fits 1" Furnace abinet D: Fits 4 1/" Furnace abinet N: Does Not Apply (horizontal slab only) Nominal apacity 13 SEER 184: 1 1/ to Tons 3030: 1/ Tons 364: 3 to 3 1/ Tons All APF coils in B,, & D widths have insulated blank off plates for use with one size smaller furnaces. All APF coils have a AUF equivalent. All HPF coils in B, & D heights have an insulated Z bracket for use with one size smaller furnace. All proper coil combinations are subject to being ARI rated with a matched outdoor unit. 10

11 PRODUT DESIGN Thermostats: The following Amana brand thermostats are suggested for use with AMV9 & AV9 Furnace Models: Filters: THERMOSTATS Thermostat Man/Auto Programmable ool Heat Batt. Powered Batt. Bkup Man. Or Auto Yes 3 No No Man. hangeover Yes Yes Yes Man. hangeover No Yes No is the recommended model for the AMV9 & AV9 furnaces when used with a heat pump in a fossil fuel application. It is NOT for use with either the AMV9 or AV9 as a sole heating source thermstats are 4V powered with battery backup. Filters are required with this furnace and must be provided by the installer. The filters used must comply with UL900 or AN/ULS111 standards. Installing this furnace without filters will void the unit warranty Upflow Filters This furnace has provisions for the installation of return air filters at the side and/or bottom return. The furnace will accommodate the following filter sizes depending on cabinet size: abinet Width (in.) SIDE RETURN Nominal Filter Size (in.) Approx. Flow Area (in ) abinet Width (in.) BOTTOM RETURN Nominal Filter Size (in.) Approx. Flow Area (in ) All 16 x 5 x / 14 x 5 x x 5 x / 0 x 5 x Refer to Minimum Filter Area tables to determine filter area requirement. NOTE: Filters can also be installed elsewhere in the duct system such as a central return. UPFLOW OOLING AIRFLOW REQUIREMENT (FM) UPFLOW OOLING AIRFLOW REQUIREMENT (FM) Input Airflow 0453 X X X X Input Airflow 0453 X X X X OUNTERFLOW OOLING AIRFLOW REQUIREMENT (FM) OUNTERFLOW OOLING AIRFLOW REQUIREMENT (FM) Input Airflow 0704 X X Input Airflow 0704 X X Minimum filter area dictated by heating airflow requirement. Disposable Minimum Filter Area (in ) [Based on a 300 ft/min filter face velocity] Minimum filter area dictated by heating airflow requirement. Permanent Minimum Filter Area (in ) [Based on 600 ft/min filter face velocity] 11

12 PRODUT DESIGN ounterflow Filters This furnace has provisions for the installation of return air filters at the counterflow top return. The furnace will accommodate the following filter sizes depending on cabinet size: Optional Access Door Return Air "A" Min ounterflow Top Return abinet Width Filter Area Filter Size Dimension "A" Qty (in ) (in) (in) 17 1/ X 0 X / / X 0 X / / X 0 X / 3.4 Refer to Minimum Filter Area tables to determine filter area requirement. NOTE: Filters can also be installed elsewhere in the duct system such as a central return. 1

13 FURNAE SPEIFIATIONS AMV9 MODEL AMV90453BX AMV90704X AMV90905DX AMV91155DX Btuh Input (US) High Fire 46,000 69,000 9, ,000 Output (US) High Fire 44,300 66,900 88, ,100 Btuh Input (US) Low Fire 3,000 48,000 64,000 80,000 Output (US) Low Fire 30,800 46,400 61,700 77,400 A.F.U.E. 96% 95.5% 95.7% 95.8% Rated External Static (" w.c.) Temperature Rise ( F) High Stage Pressure Switch Trip Point (" w.c.) Low Stage Pressure Switch Trip Point (" w.c.) Front over Pressure Switch Trip Point (" w.c) Blower Wheel (D" x W") 10 x 7 10 x x x 10 Blower Horsepower 1/ 3/4 1 1 Blower s Max 0.5 E.S.P. Refer to airflow charts on pages Power Supply Minimum ircuit Ampacity (MA) Maximum Overcurrent Device Transformer (VA) Heat Anticipator (Amps) Primary Limit Setting ( F) Auxiliary Limit Setting ( F) Rollout Limit Setting ( F) Fan Delay On Heating 30 secs. 30 secs. 30 secs. 30 secs. Off Heating 150 secs. 150 secs. 150 secs. 150 secs. Fan Delay On ooling 5 secs. 5 secs. 5 secs. 5 secs. Off ooling 45 secs. 45 secs. 45 secs. 45 secs. Fan Delay On - Fan Only 5 secs. 5 secs. 5 secs. 5 secs. Gas Supply Pressure (Natural/Propane) (" w.c.) 7 / 11 7 / 11 7 / 11 7 / 11 Manifold Pressure (Natural/Propane) High Stage (" w.c.) 3.5 / / / /10 Manifold Pressure (Natural/Propane) Low Stage ("w.c.) 1.9 / / / / 6.0 Orifice Size (Natural/Propane) #43 / #55 #43 / #55 #43 / #55 #43 / #55 Number of Burners Vent onnector Diameter (inches) 3 3 ombustion Air onnector Diameter (inches) 3 3 Shipping Weight (lbs.) Off Heating - This fan delay timing is adjustable (90, 10, 150 or 180 seconds), 150 seconds as shipped. 1. These furnaces are manufactured for natural gas operation. Optional Kits are available for conversion to propane gas operation.. For elevations above 000 ft. the rating should be reduced by 4% for each 1000 ft. above sea level. The furnace must not be derated, orifice changes should only be made if necessary for altitude. 3. The total heat loss from the structure as expressed in TOTAL BTU/HR must be calculated by the manufactures method in accordance with the "A.S.H.R.A.E. GUIDE" or "MANUAL J-LOAD ALULATIONS" published by the AIR ONDITIONING ONTRATORS OF AMERIA. The total heat loss calculated should be equal to or less than the heating capacity. Output based on D.O.E. test procedures, steady state efficiency times output. 4. Minimum ircuit Ampacity calculated as: (1.5 x irculator Blower Amps) + I.D. Blower Amps. 13

14 FURNAE SPEIFIATIONS AV9 MODEL AV90704X AV90905DX Btuh Input (US) High Fire 69,000 9,000 Output (US) High Fire 65,300 86,500 Btuh Input (US) Low Fire 48,000 64,000 Output (US) Low Fire 45,000 60,100 A.F.U.E. 93.3% 9.7% Rated External Static (" w.c.) Temperature Rise ( F) High Stage Pressure Switch Trip Point (" w.c.) Low Stage Pressure Switch Trip Point (" w.c.) Front over Pressure Switch Trip Point (" w.c) Blower Wheel (D" x W") 10 x x 10 Blower Horsepower 3/4 1 Blower s Max 0.5 E.S.P. Refer to airflow charts on pages Power Supply Minimum ircuit Ampacity (MA) Maximum Overcurrent Device Transformer (VA) Heat Anticipator (Amps) Primary Limit Setting ( F) Auxiliary Limit Setting ( F) Rollout Limit Setting ( F) 0 10 Fan Delay On Heating 30 secs. 30 secs. Off Heating 150 secs. 150 secs. Fan Delay On ooling 5 secs. 5 secs. Off ooling 45 secs. 45 secs. Fan Delay On - Fan Only 5 secs. 5 secs. Gas Supply Pressure (Natural/Propane) (" w.c.) 7 / 11 7 / 11 Manifold Pressure (Natural/Propane) High Stage (" w.c.) 3.5 / /10 Manifold Pressure (Natural/Propane) Low Stage ("w.c.) 1.9 / / 6.0 Orifice Size (Natural/Propane) #43 / #55 #43 / #55 Number of Burners 3 4 Vent onnector Diameter (inches) ombustion Air onnector Diameter (inches) Shipping Weight (lbs.) Off Heating - This fan delay timing is adjustable (90, 10, 150 or 180 seconds), 150 seconds as shipped. 1. These furnaces are manufactured for natural gas operation. Optional Kits are available for conversion to propane gas operation.. For elevations above 000 ft. the rating should be reduced by 4% for each 1000 ft. above sea level. The furnace must not be derated, orifice changes should only be made if necessary for altitude. 3. The total heat loss from the structure as expressed in TOTAL BTU/HR must be calculated by the manufactures method in accordance with the "A.S.H.R.A.E. GUIDE" or "MANUAL J-LOAD ALULATIONS" published by the AIR ONDITIONING ONTRATORS OF AMERIA. The total heat loss calculated should be equal to or less than the heating capacity. Output based on D.O.E. test procedures, steady state efficiency times output. 4. Minimum ircuit Ampacity calculated as: (1.5 x irculator Blower Amps) + I.D. Blower Amps. 14

15 BLOWER PERFORMANE SPEIFIATIONS AMV9 Heating harts Heating A B D Heating A B D AMV90453BX (Rise Range: F) Low Stage FM at.1" -.5" w.c. High Stage FM at.1" -.5" w.c. Rise ( F) Heating Low Stage FM at.1" -.5" w.c. High Stage FM at.1" -.5" w.c. Minus(-) Minus(-) Normal A Normal Plus (+) Plus (+) Minus(-) Minus(-) Normal B Normal Plus (+) Plus (+) Minus(-) Minus(-) Normal Normal Plus (+) Plus (+) Minus(-) Minus(-) Normal D Normal Plus (+) Plus (+) AMV90905DX (Rise Range: F) Low Stage FM at.1" -.5" w.c. High Stage FM at.1" -.5" w.c. Rise ( F) Heating AMV90704X (Rise Range: F) AMV91155DX (Rise Range: F) Low Stage FM at.1" -.5" w.c. High Stage FM at.1" -.5" w.c. Minus(-) Minus(-) Normal A Normal Plus (+) Plus (+) Minus(-) Minus(-) Normal B Normal Plus (+) Plus (+) Minus(-) Minus(-) Normal Normal Plus (+) Plus (+) Minus(-) Minus(-) Normal D Normal Plus (+) Plus (+) Rise ( F) Rise ( F) 1. Units are shipped without filter(s). FM in chart is without filter(s).. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed. The first task is to determine the proper aiflow for the cooling system. 3. For most cooling applications, about 400 FM per ton is desirable. 4. The chart is for information only. For satisfactory operation, external static pressure not to exceed value shown on rating plate. 5. Do not operate above 0.5" in heating mode. Operating between 0.5" w.c. and 0.8" w.c. is tabulated for cooling purposes only. 6. Motor FM minimum. 15

16 BLOWER PERFORMANE SPEIFIATIONS AMV9 High (Single) Stage ooling harts AMV90453BX AMV90704X AMV90905DX AMV91155DX ooling A B D FM at ooling FM at ooling FM at ooling FM at Minus(-) 540 Minus(-) 540 Minus(-) 70 Minus(-) 70 Normal 600 A Normal 600 A Normal 800 A Normal 800 Plus (+) 660 Plus (+) 660 Plus (+) 880 Plus (+) 880 Minus(-) 70 Minus(-) 70 Minus(-) 990 Minus(-) 990 Normal 800 B Normal 800 B Normal 1100 B Normal 1100 Plus (+) 880 Plus (+) 880 Plus (+) 110 Plus (+) 110 Minus(-) 900 Minus(-) 990 Minus(-) 160 Minus(-) 160 Normal 1000 Normal 1100 Normal 1400 Normal 1400 Plus (+) 1100 Plus (+) 110 Plus (+) 1540 Plus (+) 1540 Minus(-) 1080 Minus(-) 186 Minus(-) 160 Minus(-) 160 Normal 100 D Normal 149 D Normal 1800 D Normal 1800 Plus (+) 130 Plus (+) 157 Plus (+) 1980 Plus (+) 1980 AMV9 Low Stage ooling harts AMV90453BX AMV90704X AMV90905DX AMV91155DX ooling A B D FM at ooling FM at ooling FM at ooling FM at Minus(-) 380 Minus(-) 378 Minus(-) 513 Minus(-) 514 Normal 390 A Normal 390 A Normal 50 A Normal 50 Plus (+) 49 Plus (+) 49 Plus (+) 57 Plus (+) 57 Minus(-) 468 Minus(-) 468 Minus(-) 644 Minus(-) 644 Normal 50 B Normal 50 B Normal 715 B Normal 715 Plus (+) 57 Plus (+) 57 Plus (+) 787 Plus (+) 787 Minus(-) 585 Minus(-) 644 Minus(-) 819 Minus(-) 819 Normal 650 Normal 715 Normal 910 Normal 910 Plus (+) 715 Plus (+) 787 Plus (+) 1001 Plus (+) 1001 Minus(-) 70 Minus(-) 836 Minus(-) 1053 Minus(-) 1053 Normal 780 D Normal 99 D Normal 1170 D Normal 1170 Plus (+) 858 Plus (+) 10 Plus (+) 187 Plus (+) Units are shipped without filter(s). FM in chart is without filter(s).. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed. The first task is to determine the proper aiflow for the cooling system. 3. For most cooling applications, about 400 FM per ton is desirable. 4. The chart is for information only. For satisfactory operation, external static pressure not to exceed value shown on rating plate. 5. Do not operate above 0.5" in heating mode. Operating between 0.5" w.c. and 0.8" w.c. is tabulated for cooling purposes only. 6. Motor FM minimum. 16

17 BLOWER PERFORMANE SPEIFIATIONS AMV9 ontinuous Fan hart ooling A B D AMV90453BX FM at ooling AMV90704X FM at ooling AMV90905DX FM at ooling AMV91155DX FM at Minus(-) 380 Minus(-) 380 Minus(-) 513 Minus(-) 514 Normal 380 A Normal 380 A Normal 513 A Normal 514 Plus (+) 380 Plus (+) 380 Plus (+) 513 Plus (+) 514 Minus(-) 403 Minus(-) 403 Minus(-) 554 Minus(-) 554 Normal 448 B Normal 448 B Normal 616 B Normal 616 Plus (+) 493 Plus (+) 493 Plus (+) 678 Plus (+) 678 Minus(-) 504 Minus(-) 554 Minus(-) 706 Minus(-) 706 Normal 560 Normal 616 Normal 784 Normal 784 Plus (+) 616 Plus (+) 678 Plus (+) 86 Plus (+) 86 Minus(-) 505 Minus(-) 70 Minus(-) 907 Minus(-) 907 Normal 67 D Normal 800 D Normal 1008 D Normal 1008 Plus (+) 739 Plus (+) 880 Plus (+) 1109 Plus (+) Units are shipped without filter(s). FM in chart is without filter(s).. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed. The first task is to determine the proper aiflow for the cooling system. 3. For most cooling applications, about 400 FM per ton is desirable. 4. The chart is for information only. For satisfactory operation, external static pressure not to exceed value shown on rating plate. 5. Do not operate above 0.5" in heating mode. Operating between 0.5" w.c. and 0.8" w.c. is tabulated for cooling purposes only. 6. Motor FM minimum. 17

18 BLOWER PERFORMANE SPEIFIATIONS AV9 Heating harts AV90704X (Rise Range: F) AV90905DX (Rise Range: F) Heating Low Stage FM at.1" -.5" w.c. High Stage FM at.1" -.5" w.c. Rise ( F) Heating Low Stage FM at.1" -.5" w.c. High Stage FM at.1" -.5" w.c. Rise ( F) A B D Minus(-) Minus(-) Normal A Normal Plus (+) Plus (+) Minus(-) Minus(-) Normal B Normal Plus (+) Plus (+) Minus(-) Minus(-) Normal Normal Plus (+) Plus (+) Minus(-) Minus(-) Normal D Normal Plus (+) Plus (+) AMV9/AV9 irculator Blower ment Switches Normal + (Plus) - (Minus) F F F F F N F N F F s ( indicates factory setting) ooling A ooling B ooling ooling D F F F F F N F N F F N N Heating A Heating B Heating Heating D F F F F F N F N F F N N Note: There is a green LED adjacent to the integrated control module fuse which is used to verify airflow volume. The green FM LED blinks once for each 100 FM of airflow. Example: 10 blinks = 1,000 FM Note: ontinuous fan speed will be 56% of high stage cooling speed. Example: 1,000 FM of cooling speed will be reduced to 560 FM when fan selector switch is set to on, and no call for cooling. ooling s ( indicates factory setting) Heating s ( indicates factory setting) 1. Units are shipped without filter(s). FM in chart is without filter(s).. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed. The first task is to determine the proper aiflow for the cooling system. 3. For most cooling applications, about 400 FM per ton is desirable. 4. The chart is for information only. For satisfactory operation, external static pressure not to exceed value shown on rating plate. 5. Do not operate above 0.5" in heating mode. Operating between 0.5" w.c. and 0.8" w.c. is tabulated for cooling purposes only. 6. Motor FM minimum. 18

19 BLOWER PERFORMANE SPEIFIATIONS AMV9/AV9 Ramping Profile Ramping Profile A Ramping Profile B Ramping Profile Ramping Profile D O F F O F F F N F N F F N N Note: The multi-speed circulator blower also offers several custom ON/OFF ramping profiles. These profiles may be used to enhance cooling performance and increase comfort level. The ramping profiles are selected using DIP switches 5 and 6. Verify profile selection by counting the green FM LED blinks and timing each step of the ramping profile. Ramping Profiles ( indicates factory setting) AV9 ontinuous Fan hart ooling A B D AV90704X FM at w.c. ooling AV90905DX FM at w.c. Minus(-) 380 Minus(-) 513 Normal 380 A Normal 513 Plus (+) 380 Plus (+) 513 Minus(-) 403 Minus(-) 554 Normal 448 B Normal 616 Plus (+) 493 Plus (+) 678 Minus(-) 554 Minus(-) 706 Normal 616 Normal 784 Plus (+) 678 Plus (+) 86 Minus(-) 70 Minus(-) 907 Normal 800 D Normal 1008 Plus (+) 880 Plus (+) Units are shipped without filter(s). FM in chart is without filter(s).. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed. The first task is to determine the proper aiflow for the cooling system. 3. For most cooling applications, about 400 FM per ton is desirable. 4. The chart is for information only. For satisfactory operation, external static pressure not to exceed value shown on rating plate. 5. Do not operate above 0.5" in heating mode. Operating between 0.5" w.c. and 0.8" w.c. is tabulated for cooling purposes only. 6. Motor FM minimum. 19

20 BLOWER PERFORMANE SPEIFIATIONS AV9 High (Single) Stage ooling harts ooling A B D AV90704X FM at ooling AV90905DX FM at Minus(-) 540 Minus(-) 70 Normal 600 A Normal 800 Plus (+) 660 Plus (+) 880 Minus(-) 70 Minus(-) 990 Normal 800 B Normal 1100 Plus (+) 880 Plus (+) 110 Minus(-) 990 Minus(-) 160 Normal 1100 Normal 1400 Plus (+) 110 Plus (+) 1540 Minus(-) 186 Minus(-) 160 Normal 149 D Normal 1800 Plus (+) 157 Plus (+) 1980 AV9 Low Stage ooling harts 1. Units are shipped without filter(s). FM in chart is without filter(s).. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed. The first task is to determine the proper aiflow for the cooling system. 3. For most cooling applications, about 400 FM per ton is desirable. 4. The chart is for information only. For satisfactory operation, external static pressure not to exceed value shown on rating plate. 5. Do not operate above 0.5" in heating mode. Operating between 0.5" w.c. and 0.8" w.c. is tabulated for cooling purposes only. 6. Motor FM minimum. 0 ooling A B D AV90704X FM at ooling AV90905DX FM at Minus(-) 378 Minus(-) 513 Normal 390 A Normal 50 Plus (+) 49 Plus (+) 57 Minus(-) 468 Minus(-) 644 Normal 50 B Normal 715 Plus (+) 57 Plus (+) 787 Minus(-) 644 Minus(-) 819 Normal 715 Normal 910 Plus (+) 787 Plus (+) 1001 Minus(-) 836 Minus(-) 1053 Normal 99 D Normal 1170 Plus (+) 10 Plus (+) 187

21 PERFORMANE BTU OUTPUT vs TEMPERATURE RISE HART 600 FM FM FORMULAS BTU OUTPUT = FM x 1.08 x RISE RISE = BTU OUTPUT 1.08 FM OUTPUT BTU/HR x 1000 TEMPERATURE RISE 1

22 Y WIRING DIAGRAMS HIGH VOLTAGE! DISONNET ALL POWER BEFORE SERVIING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURES MAY BE PRESENT. FAILURE TO DO SO MAY AUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. 1 HOT SURFAE IGNITER IRUIT ONNETOR HI TWO STAGE GAS VALVE PM BR AUTO RESET PRIMARY LIMIT ONTROL GY FRONT OVER SWITH MANUAL RESET ROLLOUT LIMIT ONTROLS (SINGLE ONTROL ON 45 kbtu) PK OR VT HIGH PRESS. SWITH NO VT RD GY ID BLOWER TWO-STAGE SWITH ASSEMBLY NO LOW PRESS. SWITH NO YL FLAME SENSOR HASSIS GROUND BU RD BU 3 1 OR JUNTION BOX BU 4V HUM DISONNET DISONNET POWER MUST BE PROPERLY BEFORE SERVIING. WIRING TO UNIT POLARIZED AND GROUNDED. 115 VA/ 1Ø /60 HZ POWER SUPPLY WITH PROTETION DEVIE OVERURRENT WARNING:DISONNET PROPERLY POLARIZED SERVIING. WIRING TO UNIT MUST BE AND GROUNDED. POWER BEFORE TO 115VA/ 1Ø /60 HZ POWER SUPPLY WITH OVERURRENT PROTETION DEVIE WARNING: GND L N TO L GND N DISONNET RD RD TWO-STAGE INTEGRATED ONTROL MODULE 16 WIRE EM MTR HARNESS 3 1 RD BURNER OMPARTMENT BLOWER OMPARTMENT FUSE LO HEAT 4 V 3 A 10 IRULATOR BLOWER MANUAL RESET AUXILIARY LIMIT ONTROL 11 INDUED DRAFT BLOWER GND 4 V THERMOSTAT ONNETIONS DIAGNOSTI LED HI HEAT YL T-STAT SELETOR HEAT OFF DELAY DIP SWITHES EA OOL PARK O HOT YLO RD LINE PK GN PK GY BR VT RD XFMR B/ GN HUM G GY R BU OR VT OR YL 4V HUM. BU INDUTOR OIL 70kBTU,90kBTU, 115kBTU MODELS ONLY NEUTRAL GND W1 W TWIN/ DEHUM 5 IRUIT ONNNETOR PK OR 40 VA TRANS- FORMER PK GY VT BR GY VT 4 VA 115 VA YL VT GN 9 IRUIT ONNETOR BLOWER OMPARTMENT DOOR SWITH (OPEN EN DOOR OPEN) INTEGRATED ONTROL MODULE 4V THERMOSTAT ONNETIONS 4V HUMIDIFIER R W1 YLO W Y G DOOR SWITH 115kBTU MODELS INDUTOR OIL 70kBTU,90kBTU, ONLY FUSE 3 A TO MIRO TH (5) HLO (11) HL1 (6) PS1 (1) MVL(7) PS () GND (10) TR (9) INTEGRATED ONTROL MODULE INDOOR AIR IRULATOR BLWR LINE-H LINE-N XFMR-H EA-H ELETRONI EA-N AIR LEANER HUM-H IGN-H FP (3) IND HI IND LO HUMIDIFIER FLAME SENSOR ID BLWR HOT SURFAE IGNITER 115 VA 4 VA MANUAL RESET AUXILIARY LIMIT ONTROLS FRONT OVER SWITH MVH (1) MV (8) JUNTION BOX 4V HUM. MANUAL RESET ROLLOUT LIMIT ONTROL(S) NO NO 40 VA TRANSFORMER GND GND IND-N HUM-N IGN-N HIGH SWITH XFMR-N NO AUTORESET PRIMARY LIMIT ONTROL LOW SWITH PM HI GAS VALVE INTEGRATED ONTROL MODULE STEADY ON = NORMAL OPERATION 1 FLASH = SYSTEM LOKOUT (RETRIES/REYLES EXEEDED) FLASHES = LOW SWITH STUK LOSED 3 FLASHES = LOW SWITH STUK OPEN 4 FLASHES = THERMAL PROTETIVE DEVIE OPEN 5 FLASHES = FLAME SENSED WITH GAS VALVE DE-ENERGIZED 7 FLASHES = LOW FLAME SENSE SIGNAL 8 FLASHES = HEK IGNITER OR IMPROPER GROUNDING 9 FLASHES = HIGH SWITH STUK OPEN ONTINUOUS FLASHES = 115 VOLT A POWER REVERSED LOW VOLTAGE (4V) LOW VOLTAGE FIELD HI VOLTAGE (115V) HI VOLTAGE FIELD JUNTION TERMINAL INTERNAL TO INTEGRATED ONTROL PLUG ONNETION EQUIPMENT GND FIELD GND FIELD SPLIE SWITH (TEMP.) IGNITER SWITH (PRESS.) OVERURRENT PROT. DEVIE OLOR ODES: YL YELLOW OR ORANGE VT VIOLET GN GREEN BLAK REV.00 PK PINK BR BROWN ITE BU BLUE GY GRAY RD RED NOTES: 1. SET HEAT ANTIIPATOR ON ROOM THERMOSTAT AT 0.7 AMPS.. MANUFATURER'S SPEIFIED REPLAEMENT PARTS MUST BE USED EN SERVIING. 3. IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE FURNAE MUST BE REPLAED, IT MUST BE REPLAED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 105. USE OPPER ONDUTORS ONLY. 4. UNIT MUST BE PERMANENTLY GROUNDED AND ONFORM TO N.E.. AND LOAL ODES. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.

23 SHEMATIS HIGH VOLTAGE! DISONNET ALL POWER BEFORE SERVIING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURES MAY BE PRESENT. FAILURE TO DO SO MAY AUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. PIN 4 PIN 7 PIN 8 PIN 9 9 IRUIT ONNETOR TO MAIN HARNESS LINE FM OFF UT FOR ON S4 DEHUM S3 Intell-Ignition W R TSTAT ON S1 OFF XFMR EA IR HUM HUM XFMR LINE PARK OOL EA HI HEAT US GY OR VT PIN 1 PIN PIN 6 PK GN YL AUXILIARY LIMITS (SIDES OF BLOWER HOUSING) PK 3 1 PIN 5 PIN 4 PIN 3 PIN PIN 1 OR GY INTEGRATED ONTROL MODULE INDUTOR OIL (GUVA070,090,115 MODELS ONLY) PIN 3 PIN 5 TO EM BLWR MOTOR GROUND TO SROLL HOUSING HOT NEUTRAL EM BLOWER MOTOR TWO SINGLE LO HEAT LINE TRANSFORMER LOAD BLOWER ASSEMBLY SHEMATI AMV9/AV9 X MODEL FURNAES This schematic is for reference only. Not all wiring is as shown above, refer to the appropriate wiring diagram for the unit being serviced. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. 3

24 SHEMATIS HIGH VOLTAGE! DISONNET ALL POWER BEFORE SERVIING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURES MAY BE PRESENT. FAILURE TO DO SO MAY AUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. IRULATOR BLOWER ELETRONI AIR LEANER INDUER HUMIDIFIER LOW HEAT HIGH HEAT OOL PARK NEU IR. EA EA NEU IND HI IND LO IND NEU HUM HUMN K7 K8a K R K1 W8 K3 TH 3 AMP AUTOMOTIVE FUSE LINE HOT XFMR 10 VA 4 V.A.. XFMRN LINE NEU.0005 TR R B/ K8b Q K6 1M Y G W W W1 W1 THERMOSTAT Y G FLAME SENSOR PROBE FP IGNN IGNITOR IGN GND STAGE GAS VALVE MV OM P M H1 MVL PS PS1 HLO HIGH LIMIT ROLLOUT SWITH AUX LIMIT HLI MVH MATE WITH AMP USING SOKETS ST STAGE SWITH ND STAGE SWITH TYPIAL SHEMATI AMV9/AV9 X MODEL FURNAES WR 50V61-89 INTEGRATED IGNITION ONTROL This schematic is for reference only. Not all wiring is as shown above. Refer to the appropriate wiring diagram for the unit being serviced. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. 4

TECHNICAL INFORMATION MANUAL

TECHNICAL INFORMATION MANUAL TEHNIAL INFORMATION MANUAL AMV9/AV9 40" 90% Gas Furnace Units Model and manufacturing numbers listed on page 3. Refer to Service Manual RS6300003 Rev. 1 for installation, operation, and troubleshooting

More information

Two-Stage, Variable-Speed Gas Furnace

Two-Stage, Variable-Speed Gas Furnace 80% AFUE GMV8 Two-Stage, Variable-Speed Gas Furnace Heating Input: 60,000 00,000 BTU/h Standard Features Aluminized steel, dual-diameter tubular heat exchanger Two-stage gas valve operates on two-stage

More information

GMVM96 / GCVM96 ComfortNet -Compatible, Multi-Position, Modulating Variable-Speed Gas Furnace

GMVM96 / GCVM96 ComfortNet -Compatible, Multi-Position, Modulating Variable-Speed Gas Furnace / GVM96 omfortnet -ompatible, Multi-Position, Modulating Variable-Speed Gas Furnace Up to 96% AFUE abinet Features Multi-position installation: upflow, horizontal left or right ertified for direct vent

More information

GMVC8. ComfortNet -Compatible. Heating Input: 70, ,000 BTU/h. Two-Stage, Variable-Speed Gas Furnace

GMVC8. ComfortNet -Compatible. Heating Input: 70, ,000 BTU/h. Two-Stage, Variable-Speed Gas Furnace 80% AFUE Heating Input: 70,000 115,000 BTU/h ComfortNet -Compatible Two-Stage, Variable-Speed Gas Furnace Standard Features Aluminized steel, dual-diameter tubular heat exchanger Two-stage gas valve operates

More information

PRODUCT SPECIFICATIONS

PRODUCT SPECIFICATIONS GMV95/GV9 SERIES UP TO 95% FUE MULTI-POSITION, 2-STGE/VRILE-SPEE GS FURNE HETING PITY: 46,000 115,000 TUH GMV95 Models Qualify for a $200 Tax redit GV9 Models Qualify for a $50 Tax redit Standard Features

More information

Service Parts. AMV9*XA Upflow/Horizontal/Two- Stage/Variable Speed 90% AFUE Gas Furnace. Models and manufacturing numbers in this manual

Service Parts. AMV9*XA Upflow/Horizontal/Two- Stage/Variable Speed 90% AFUE Gas Furnace. Models and manufacturing numbers in this manual Service s AMV9*XA Upflow/Horizontal/Two- Stage/Variable Speed 90% AFUE Gas Furnace AMV90453BXA AMV90704CXA AMV90905DXA AMV91155DXA Models and manufacturing numbers in this manual P1257401F P1257403F P1257405F

More information

ASPT Series. Multi-Position, Internal TXV. Air Handler 1½ to 5 Tons

ASPT Series. Multi-Position, Internal TXV. Air Handler 1½ to 5 Tons Series Multi-Position, Internal TXV Product Features Internal factory-installed thermal expansion valves for cooling and heat pump applications Direct drive, multi-speed ECM blower motor All-aluminum evaporator

More information

REPAIR PARTS. AMH95 Amana brand 95% Hybrid Furnace AMH950453BXAA AMH950703BXAA AMH950704CXAA AMH950904CXAA AMH950905DXAA AMH951155DXAA

REPAIR PARTS. AMH95 Amana brand 95% Hybrid Furnace AMH950453BXAA AMH950703BXAA AMH950704CXAA AMH950904CXAA AMH950905DXAA AMH951155DXAA REPAIR PARTS AMH95 Amana brand 95% Hybrid Furnace AMH950453BXAA AMH950703BXAA AMH950704CXAA AMH950904CXAA AMH950905DXAA AMH9155DXAA Amana is a trademark of Maytag Corporation and used under license to

More information

REPAIR PARTS. *MVM96 Variable Speed Furnace

REPAIR PARTS. *MVM96 Variable Speed Furnace *MVM96 Variable Speed Furnace AMVM960603BXAA AMVM960603BXBA AMVM960805CXAA AMVM960805CXBA AMVM961005DXAA AMVM961005DXBA AMVM9655DXAA AMVM9655DXBA GMVM960603BXAA GMVM960603BXBA GMVM960805CXAA GMVM960805CXBA

More information

REPAIR PARTS. GMS95 Single Stage Upflow Furnace GMS950453BXAB GMS950703BXAB GMS950704CXAB GMS950904CXAB GMS951155DXAB.

REPAIR PARTS. GMS95 Single Stage Upflow Furnace GMS950453BXAB GMS950703BXAB GMS950704CXAB GMS950904CXAB GMS951155DXAB. REPAIR PARTS GMS95 Single Stage Upflow Furnace GMS950453BXAB GMS950703BXAB GMS950704CXAB GMS950904CXAB GMS55DXAB Made in the USA by: Goodman Manufacturing Company, L.P. 2550 North Loop West, Suite 400

More information

nufacturing Company, L.P San Felipe, Suite

nufacturing Company, L.P San Felipe, Suite REPAIR PARTS GMVC 96% ECM Up Flow Furnace GMVC960403BNAA GMVC960603BNAA GMVC960803BNAA GMVC960804CNAA GMVC961005CNAA GMVC961205DNAA nufacturing Company, L.P. 5151 San Felipe, Suite 500 www.amana-hac.com

More information

PARTS MANUAL Gas Furnace F9MAC, G9MAC

PARTS MANUAL Gas Furnace F9MAC, G9MAC Gas Furnace F9MAC, G9MAC Safety Labeling and Signal Words DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of hazard seriousness. The signal

More information

Goodman Manufacturing Company, L.P San Felipe, Suite 500 Houston, TX 77056

Goodman Manufacturing Company, L.P San Felipe, Suite 500 Houston, TX 77056 REPAIR PARTS *CVM 96% Modulating Furnace ACVM960604CXAA ACVM960604CXBA ACVM960805DXAA ACVM960805DXBA ACVM961005DXAA GCVM960604CXAA GCVM960604CXBA GCVM960805DXAA GCVM960805DXBA GCVM961005DXAA GCVM961005DXBA

More information

REPAIR PARTS. GMEC 96% EEM Up Flow Furnace. This manual is to be used by qualified technicians only.

REPAIR PARTS. GMEC 96% EEM Up Flow Furnace. This manual is to be used by qualified technicians only. REPAIR PARTS GMEC 96% EEM Up Flow Furnace GMEC960302BNAA GMEC960402BNAA GMEC960603BNAA GMEC960803BNAA GMEC9004CNAA GMEC9205DNAA www.amana-hac.com This manual is to be used by qualified technicians only.

More information

REPAIR PARTS. GDS8 80% Furnace GDS80453AXCA GDS80453AXCB GDS80703AXCA GDS80703AXCB GDS80904BXCA GDS80904BXCB GDS81155CXCA GDS81155CXCB

REPAIR PARTS. GDS8 80% Furnace GDS80453AXCA GDS80453AXCB GDS80703AXCA GDS80703AXCB GDS80904BXCA GDS80904BXCB GDS81155CXCA GDS81155CXCB REPAIR PARTS GDS8 80% Furnace GDS80453AXCA GDS80453AXCB GDS80703AXCA GDS80703AXCB GDS80904BXCA GDS80904BXCB GDS855CXCA GDS855CXCB This manual is to be used by qualified technicians only. This manual replaces

More information

REPAIR PARTS. GMEC 96% ECM Up Flow Furnace

REPAIR PARTS. GMEC 96% ECM Up Flow Furnace REPAIR PARTS GMEC 96% ECM Up Flow Furnace GMEC960302BNAA GMEC960302BNAB GMEC960402BNAA GMEC960402BNAB GMEC960603BNAA GMEC960603BNAB GMEC960803BNAA GMEC960803BNAB GMEC961004CNAA GMEC961004CNAB GMEC961205DNAA

More information

REPAIR PARTS. *MVC95 Variable Speed Furnace

REPAIR PARTS. *MVC95 Variable Speed Furnace *MVC95 Variable Speed Furnace AMVC950453BXBA AMVC950704CXBA AMVC950905CXBA AMVC950905DXBA AMVC9155DXBA GMVC950453BXBA GMVC950704CXBA GMVC950905CXBA GMVC950905DXBA GMVC9155DXBA REPAIR PARTS This manual

More information

REPAIR PARTS. GMV9* Variable Speed Furnace

REPAIR PARTS. GMV9* Variable Speed Furnace REPAIR PARTS GMV9* Variable Speed Furnace GMV90703BXBA GMV90905CXBA GMV155DXBA GMV950453BXBA GMV950453BXBB GMV950704CXBA GMV950704CXBB GMV950905DXBA GMV950905DXBB GMV9155DXBA GMV9155DXBB GMV9155DXBC Goodman

More information

REPAIR PARTS. *CVC95 C'Flow Variable Speed Furnace ACVC950714CXBA ACVC950915DXBA GCVC950714CXBA GCVC950915DXBA

REPAIR PARTS. *CVC95 C'Flow Variable Speed Furnace ACVC950714CXBA ACVC950915DXBA GCVC950714CXBA GCVC950915DXBA *CVC95 C'Flow Variable Speed Furnace ACVC950714CXBA ACVC950915DXBA GCVC950714CXBA GCVC950915DXBA REPAIR PARTS This manual is to be used by qualified technicians only. 2012 Goodman Manufacturing Company,

More information

PARTS MANUAL Gas Furnace F8MXN, F8MXL, G8MXN, G8MXL

PARTS MANUAL Gas Furnace F8MXN, F8MXL, G8MXN, G8MXL Gas Furnace F8MXN, F8MXL, G8MXN, G8MXL DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAU- TION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER

More information

REPAIR PARTS. *CVC9 90% C'Flow 2-Stage Variable Speed Furnace

REPAIR PARTS. *CVC9 90% C'Flow 2-Stage Variable Speed Furnace REPAIR PARTS *CVC9 90% C'Flow 2-Stage Variable Speed Furnace ACVC90704CXAA ACVC90704CXAB ACVC90905DXAA ACVC90905DXAB ACVC950714CXAA ACVC950915DXAA GCVC90704CXAA GCVC90704CXAB GCVC90905DXAA GCVC90905DXAB

More information

REPAIR PARTS. GMVC 96% ECM Up Flow Furnace. This manual is to be used by qualified technicians only.

REPAIR PARTS. GMVC 96% ECM Up Flow Furnace. This manual is to be used by qualified technicians only. REPAIR PARTS GMVC 96% ECM Up Flow Furnace GMVC960403BNAA GMVC960603BNAA GMVC960803BNAA GMVC960804CNAA GMVC9005CNAA GMVC9205DNAA www.amana-hac.com This manual is to be used by qualified technicians only.

More information

REPAIR PARTS. GMH95 95% Upflow Hybrid Furnace

REPAIR PARTS. GMH95 95% Upflow Hybrid Furnace REPAIR PARTS GMH95 95% Upflow Hybrid Furnace GMH950453BXAD GMH950453BXAE GMH950453BXAF GMH950703BXAE GMH950703BXAF GMH950703BXAG GMH950704CXAD GMH950704CXAE GMH950704CXAF GMH950904CXAE GMH950904CXAF GMH950904CXAG

More information

REPAIR PARTS. AMH95 Amana Brand 95% Hybrid Furnace

REPAIR PARTS. AMH95 Amana Brand 95% Hybrid Furnace REPAIR PARTS AMH95 Amana Brand 95% Hybrid Furnace AMH950453BXAD AMH950453BXAE AMH950703BXAE AMH950703BXAF AMH950704CXAD AMH950704CXAE AMH950904CXAE AMH950904CXAF AMH950905CXAB AMH950905DXAD AMH950905DXAE

More information

ASPT Series. Multi-Position, Internal TXV. Air Handler 1½ to 5 Tons

ASPT Series. Multi-Position, Internal TXV. Air Handler 1½ to 5 Tons Series Multi-Position, Internal TXV Multi-Speed ECM Based Air Handler ½ to Tons Contents Air Handler Nomenclature... Heater Kit Nomenclature... Product Specifications... Dimensions... Airflow Data... Heat

More information

Y1SA Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS

Y1SA Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS TEHNIAL SPEIFIATIONS Y1SA Series EarthDirEX Geothermal Direct Geoexchange Heat Pump ooling capacity,000 to 0,000 Heating capacity 1,000 to,000 EER 19.0 to.0 and OP.8 to.0 The Y1SA Geothermal heat pump,

More information

GMV95/GCV9 MULTI-POSITION, TWO-STAGE/VARIABLE-SPEED GAS FURNACE

GMV95/GCV9 MULTI-POSITION, TWO-STAGE/VARIABLE-SPEED GAS FURNACE GMV95/GV9 MULTI-POSITION, TWO-STGE/VRILE-SPEE GS FURNE The Goodman brand GMV95/ GV9 Two-Stage, Variable- Speed Gas Furnaces feature a patented aluminized-steel tubular heat exchanger and durable Silicon

More information

REPAIR PARTS. GDH8 80% Two-Stage Hybrid Dedicated Downflow Gas Furnace

REPAIR PARTS. GDH8 80% Two-Stage Hybrid Dedicated Downflow Gas Furnace REPAIR PARTS GDH8 80% Two-Stage Hybrid Dedicated Downflow Gas Furnace GDH80453AXAA GDH80453AXAB GDH80453AXAC GDH80703AXAA GDH80703AXAB GDH80703AXAC GDH80904BXAA GDH80904BXAB GDH80904BXAC GDH155CXAA GDH155CXAB

More information

REPAIR PARTS. GCH95 95% Counterflow Hybrid Furnace. This manual is to be used by qualified technicians only. This manual replaces RP-597C.

REPAIR PARTS. GCH95 95% Counterflow Hybrid Furnace. This manual is to be used by qualified technicians only. This manual replaces RP-597C. REPAIR PARTS GCH95 95% Counterflow Hybrid Furnace GCH950453BXAA GCH950453BXAB GCH950453BXAD GCH950703BXAA GCH950703BXAB GCH950703BXAD GCH950704CXAA GCH950704CXAB GCH950704CXAD GCH950904CXAA GCH950904CXAB

More information

REPAIR PARTS. GMSS 96% PSC Up Flow Furnace. This manual is to be used by qualified technicians only.

REPAIR PARTS. GMSS 96% PSC Up Flow Furnace. This manual is to be used by qualified technicians only. REPAIR PARTS GMSS 96% PSC Up Flow Furnace GMSS960402BNAA GMSS960603BNAA GMSS960803BNAA GMSS960804CNAA GMSS960805CNAA GMSS9005CNAA GMSS9205DNAA www.amana-hac.com This manual is to be used by qualified technicians

More information

GB5BM Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Air Handler WARRANTY

GB5BM Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Air Handler WARRANTY TECHNICAL SPECIFICATIONS GB5BM Series Air Handler 13 SEER Residential System 18,000-60,000 Btuh (Heat Pump & Air Conditioner) The GB5BM Series of air handlers, when combined with our heat pump or air conditioner,

More information

AMVC 80% Variable Speed Communicating Furnace

AMVC 80% Variable Speed Communicating Furnace REPAIR PARTS AMVC 80% Variable Speed Communicating Furnace AMVC80604BNAA AMVC80604BNBA AMVC80604BNBB AMVC80604BNBC AMVC80604BXAA AMVC80604BXBA AMVC80604BXBB AMVC80604BXBC AMVC80805CNAA AMVC80805CNBA AMVC80805CNBB

More information

REPAIR PARTS. GMS9*XA Gas Furnace

REPAIR PARTS. GMS9*XA Gas Furnace REPAIR PARTS GMS9*XA Gas Furnace GMS90453BXA P1256801F GMS90453BXA P1256807F GMS90703BXA P1256802F GMS90703BXA P1256808F GMS90904CXA P1256804F GMS90904CXA P1256809F GMS155DXA P1256806F Goodman Manufacturing

More information

ENVIRONMENTALLY SOUND R 410A REFRIGERANT

ENVIRONMENTALLY SOUND R 410A REFRIGERANT ENVIRONMENTALLY SOUND REFRIGERANT N4H3 Performance Series Product Specifications EFFICIENT 13 SEER HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase,

More information

GMV95/GCV9 PRODUCT SPECIFICATIONS 95%/93% AFUE GAS FURNACE MULTI-POSITION, TWO-STAGE/VARIABLE-SPEED HEATING INPUT: 46, ,000 BTU/H

GMV95/GCV9 PRODUCT SPECIFICATIONS 95%/93% AFUE GAS FURNACE MULTI-POSITION, TWO-STAGE/VARIABLE-SPEED HEATING INPUT: 46, ,000 BTU/H GMV95/GV9 GS FURNE PROUT SPEIFITIONS The Goodman GMV95/GV9 95%/93% FUE Two-Stage, Variable-Speed Gas Furnaces feature a patented aluminizedsteel tubular heat exchanger and durable Silicon Nitride Hot Surface

More information

REPAIR PARTS. GDS8 80% Furnace

REPAIR PARTS. GDS8 80% Furnace REPAIR PARTS GDS8 80% Furnace GDS80403ANAA GDS80403ANBA GDS80403ANBB GDS80403AXAA GDS80403AXBA GDS80403AXBB GDS80603ANAA GDS80603ANBA GDS80603ANBB GDS80603AXAA GDS80603AXBA GDS80603AXBB GDS80804BNAA GDS80804BNBA

More information

REPAIR PARTS. GKS9 Single Stage PSC Upflow Furnace. This manual is to be used by qualified technicians only. This manual replaces RP-606B.

REPAIR PARTS. GKS9 Single Stage PSC Upflow Furnace. This manual is to be used by qualified technicians only. This manual replaces RP-606B. REPAIR PARTS GKS9 Single Stage PSC Upflow Furnace GKS90453BXAD GKS90453BXAE GKS90453BXAF GKS90703BXAF GKS90703BXAG GKS90703BXAH GKS90704CXAD GKS90704CXAE GKS90704CXAF GKS90904CXAF GKS90904CXAG GKS90904CXAH

More information

AMVC95/ACVC95. Gas Furnaces ACVC95: up to 95% AFUE. Heating Input: 46, ,000 BTU/h

AMVC95/ACVC95. Gas Furnaces ACVC95: up to 95% AFUE. Heating Input: 46, ,000 BTU/h Heating Input: 46,000 5,000 TU/h Standard Features Millionir stainless-steel, dual-diameter tubular heat exchanger Two-stage gas valve operates on two-stage or single-stage thermostats omfortnet ommunications

More information

B6VMAX Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS

B6VMAX Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS TECHNICAL SPECIFICATIONS B6VMAX Series Air Handler with TXV 13-19 SEER Residential System 18,000-60,000 Btuh (Heat Pump & Air Conditioner) R-410A Refrigerant The B6VMAX Series of air handlers, when combined

More information

GMVC 80% Variable Speed Communicating Furnace

GMVC 80% Variable Speed Communicating Furnace REPAIR PARTS GMVC 80% Variable Speed Communicating Furnace GMVC80604BNAA GMVC80604BNBA GMVC80604BNBB GMVC80604BNBC GMVC80604BXAA GMVC80604BXBA GMVC80604BXBB GMVC80604BXBC GMVC80805CNAA GMVC80805CNBA GMVC80805CNBB

More information

(HSI) LIMITED WARRANTY

(HSI) LIMITED WARRANTY ama The Payne PG8MAA/JAA 80% AFUE Gas Furnaces feature 4-way multipoise design and through-the-furnace downflow venting. The PG8MAA/JAA furnaces are approved f use with natural propane gas, and the PG8JAA

More information

REPAIR PARTS. GMVC8 80% Variable Speed Communicating Furnace

REPAIR PARTS. GMVC8 80% Variable Speed Communicating Furnace REPAIR PARTS GMVC8 80% Variable Speed Communicating Furnace GMVC80604BNAA GMVC80604BNBA GMVC80604BNBB GMVC80604BNBC GMVC80604BXAA GMVC80604BXBA GMVC80604BXBB GMVC80604BXBC GMVC80805CNAA GMVC80805CNBA GMVC80805CNBB

More information

END4X, ENW4X, ENA4X. Product Specifications VERTICAL EVAPORATOR COILS ALL N COIL MODELS CASED N COILS UNCASED N COILS ENA4X WARRANTY*

END4X, ENW4X, ENA4X. Product Specifications VERTICAL EVAPORATOR COILS ALL N COIL MODELS CASED N COILS UNCASED N COILS ENA4X WARRANTY* ENVIRONMENTALLY SOUND REFRIGERANT VERTICAL EVAPORATOR COILS ALL N COIL MODELS 1½ thru 5 Tons Available for environmentally sound R 410A systems Copper tube / aluminum fin N coil with latest high tech fin

More information

ENH4X. Product Specifications HORIZONTAL EVAPORATOR COILS ALL CASED N COIL MODELS WARRANTY*

ENH4X. Product Specifications HORIZONTAL EVAPORATOR COILS ALL CASED N COIL MODELS WARRANTY* ENVIRONMENTALLY SOUND REFRIGERANT ENH4X Product Specifications HORIZONTAL EVAPORATOR COILS ALL CASED N COIL MODELS 2 thru 5 Tons Available for environmentally sound R 410A systems Copper tube / aluminum

More information

Product Data. CAPVU Evaporator Coil A Coil --- Uncased Upflow, Downflow CAPVU

Product Data. CAPVU Evaporator Coil A Coil --- Uncased Upflow, Downflow CAPVU CAPVU Evaporator Coil A Coil --- Uncased Upflow, Downflow Product Data CAPVU A06002 The CAPVU evaporator coils incorporate proven standards for reliable system operation and performance throughout the

More information

EFFICIENT 13 SEER HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz

EFFICIENT 13 SEER HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz ENVIRONMENTALLY SOUND REFRIGERANT N4H3 Performance Series Product Specifications EFFICIENT 13 SEER HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase,

More information

REPAIR PARTS. GUP, GUPI, and GUPX "B" SERIES

REPAIR PARTS. GUP, GUPI, and GUPX B SERIES REPAIR PARTS GUP, GUPI, and GUPX "B" SERIES GUPI050-3 GUPI075-3 GUPI075-4 GUPI100-4 GUPI100-5 GUPI120-5 GUPS050-2 GUPS075-3 GUPS100-3 GUPS100-4 GUPS120-4 GUPS120-5 GUPS140-5 GUPX050-3B GUPX075-4B GUPX100-5B

More information

R- 410A R-22 Size (tons) Shipping Weight (lbs) WLAU184AA 1-1/ WLAU182AA 1-1/ WLAU244AA. Model /2

R- 410A R-22 Size (tons) Shipping Weight (lbs) WLAU184AA 1-1/ WLAU182AA 1-1/ WLAU244AA. Model /2 EVAPORATOR COILS A COIL - UNCASED R- 410A or R- 22 SYSTEMS 1 1/2 5 Tons WLAU Use of the AHRI Certified TM Mark indicates a manufacturer s participation in the program. For verification of certification

More information

REPAIR PARTS. GME8 80% Upflow Furnace

REPAIR PARTS. GME8 80% Upflow Furnace REPAIR PARTS GME8 80% Upflow Furnace GME80603BNAA GME80603BNBA GME80603BNBB GME80603BXAA GME80603BXBA GME80603BXBB GME80805CNAA GME80805CNBA GME80805CNBB GME80805CXAA GME80805CXBA GME80805CXBB GME80805DNAA

More information

REPAIR PARTS. A/GPG13 Package Gas Units

REPAIR PARTS. A/GPG13 Package Gas Units REPAIR PARTS A/GPG13 Package Gas Units APG1324045MBA APG1324070MBA APG1330045MBA APG1330070MBA APG1336045MBA APG1336070MBA APG1336090MBA APG1342070MBA APG1342090MBA APG1348070MBA APG1348090MBA APG13485MBA

More information

579(XX).(X)(X)(X)(X) Modularized Roof Top Air Conditioner

579(XX).(X)(X)(X)(X) Modularized Roof Top Air Conditioner When ordering parts, always state: MODEL NO. - PRODUT NO. - QUANTITY - PART NUMBER - DESRIPTION For Electric Details also state: VOLTAGE - WATTAGE USA SERVIE OFFIE Dometic orporation 0 Industrial Parkway

More information

Product Data. CNPVP, CNRVP, CNPVT, CNRVT, CNPVU, CNRVU Evaporator Coil N Coil Cased and Uncased Upflow, Downflow

Product Data. CNPVP, CNRVP, CNPVT, CNRVT, CNPVU, CNRVU Evaporator Coil N Coil Cased and Uncased Upflow, Downflow CNPVP, CNRVP, CNPVT, CNRVT, CNPVU, CNRVU Evaporator Coil N Coil Cased and Uncased Upflow, Downflow Product Data CN(P,R)VP CN(P,R)VT (Transition) A06008 A06007 This vertical design N -coil is a furnace

More information

REPAIR PARTS. APG10*A 10 SEER Package Gas Unit

REPAIR PARTS. APG10*A 10 SEER Package Gas Unit REPAIR PARTS APG10*A 10 SEER Package Gas Unit APG102404A APG10240701A APG10300701A APG10360701A APG10360901A APG10360903A APG10420701A APG10420901A APG10480901A APG10480903A APG1048A APG10600901A APG10600903A

More information

REPAIR PARTS. GPG14 "M" Series Residential Package Gas Units. This manual is to be used by qualified technicians only. This manual replaces RP-G3001.

REPAIR PARTS. GPG14 M Series Residential Package Gas Units. This manual is to be used by qualified technicians only. This manual replaces RP-G3001. REPAIR PARTS GPG14 "M" Series Residential Package Gas Units GPG1424040MAA GPG1424040MAB GPG1424060MAA GPG1424060MAB GPG1430040MAA GPG1430040MAB GPG1430060MAA GPG1430060MAB GPG1436040MAA GPG1436040MAB GPG1436060MAA

More information

Field Pro Operation and Installation Manual

Field Pro Operation and Installation Manual Field Pro Operation and Installation Manual Xtreme Research Corporation SkyScan Division P.O. Box 336, Port Richey, FL 34673-0336 1-800-732-0665 Table of Contents 1. Installation 3 2. Operation 5 3. Care

More information

42C/V. Fan Coil Unit 42C/V

42C/V. Fan Coil Unit 42C/V 2/V Fan oil Unit 2/V arrier makes the world a better place to live by creating a comfortable, productive and healthy environment regardless of climate. It is our mission is to be customer s first choice

More information

AIR CONDITIONER (SPLIT TYPE) SERVICE MANUAL

AIR CONDITIONER (SPLIT TYPE) SERVICE MANUAL AIR CONDITIONER (SPLIT TYPE) SERVICE MANUAL FILE No. A10-023-1 REVISION 1 : Mar.2012 Re-edit version.( file volume down) Contents have NOT been changed. Model name: RAS-M10PKVP-E RAS-M13PKVP-E RAS-M16PKVP-E

More information

DGCU165-5B 36 W. Five-Burner Cooktop

DGCU165-5B 36 W. Five-Burner Cooktop Standard Features & Accessories All models include Dimensioned fit the majority of similarly sized cookp cuuts Sealed burners with brass flame ports and porcelain/cast iron burner caps Burners mounted

More information

REPAIR PARTS 14 SEER DUEL FUEL PACKAGE MODELS

REPAIR PARTS 14 SEER DUEL FUEL PACKAGE MODELS 14 SEER DUEL FUEL PACKAGE MODELS APD1424070M41AA APD1430090M41AA APD1436090M41AA APD14425M41AA APD14485M41AA GPD1424070M41AA GPD1430090M41AA GPD1436090M41AA GPD14425M41AA GPD14485M41AA REPAIR PARTS This

More information

DCG Commercial. 7½ - 12½ Ton Packaged Gas/ Electric Up to 11.3 EER / 80% AFUE

DCG Commercial. 7½ - 12½ Ton Packaged Gas/ Electric Up to 11.3 EER / 80% AFUE DG ommercial ½ - ½ Ton Packaged Gas/ Electric Up to. EER / 0% AUE ooling apacity:,000,000 BTU/h Heating apacity (Output):,000 BTU/h ontents Nomenclature... Product Specifications... Expanded ooling Data...

More information

10-year industry best core warranty. 2-year warranty on balance of unit.

10-year industry best core warranty. 2-year warranty on balance of unit. MODEL FEATURES MERV-8 filters Fully insulated case Large cores for high efficiency No condensate pan or drain required AHRI Certified Rainhood included Access door for easy maintenance and Cleaning Integral

More information

Instruction. Vacuum Circuit Breaker Operator Module. Type 3AH 4.16kV to 38kV. Power Transmission & Distribution

Instruction. Vacuum Circuit Breaker Operator Module. Type 3AH 4.16kV to 38kV. Power Transmission & Distribution Instruction 0001-22-2--00 Vacuum Circuit Breaker Operator Module Type 3AH 4.16kV to 38kV Power Transmission & Distribution Hazardous voltages and high-speed moving parts. Will cause death, serious injury

More information

REPAIR PARTS. [A/G]PG15 Package Gas-Electric Units

REPAIR PARTS. [A/G]PG15 Package Gas-Electric Units REPAIR PARTS [A/G]PG15 Package Gas-Electric Units APG152407041AA APG153009041AA APG153609041AA APG153609041AB APG153709041AA APG1542541AA APG1548541AA APG1548541AB APG1549541AA APG156014041AA APG156014041AB

More information

SECTION 1 - WHAT IS A BTU METER? BTU's = Flow x ΔT Any ISTEC BTU Meter System consists of the following main components:

SECTION 1 - WHAT IS A BTU METER? BTU's = Flow x ΔT Any ISTEC BTU Meter System consists of the following main components: SECTION 1 - WHAT IS A BTU METER? ISTEC BTU Meters measure energy usage by multiplying flow rate and temperature difference. As the water (or other liquid) passes through these lines, the multi-wing turbine

More information

Chimney Sizing. Project Name: Location: Type Appliance: Hot Water Heater Incinerator. LP Gas #2 Oil #6 Oil Wood/Coal Waste (Type ) Appliance Input:

Chimney Sizing. Project Name: Location: Type Appliance: Hot Water Heater Incinerator. LP Gas #2 Oil #6 Oil Wood/Coal Waste (Type ) Appliance Input: Chimney Sizing Project Name: Location: Type Appliance: Type Fuel: Appliance Input: Boiler Hot Water Heater Incinerator Natural Gas LP Gas #2 Oil #6 Oil Wood/Coal Waste (Type ) BTU Hp Lbs/hr Height Above

More information

Cooling Water Flow Regulator

Cooling Water Flow Regulator Temperature controlled, indirectly and directly actuated diaphragm valves / seat valves Port size G 3/8 to G DN 0 to DN 0 ontinuous regulation High accuracy No auxiliary energy required Technical data

More information

REPAIR PARTS. *PD14 Dual Fuel Package Units

REPAIR PARTS. *PD14 Dual Fuel Package Units *PD14 Dual Fuel Package Units APD1424070M41AA APD1424070M41BA APD1430090M41AA APD1430090M41BA APD1436090M41AA APD1436090M41BA APD1437090M41AA APD14425M41AA APD14425M41BA APD14485M41AA APD14485M41BA GPD1424070M41AA

More information

SRP RESIDENTIAL GARAGE HEATERS

SRP RESIDENTIAL GARAGE HEATERS SRP RESIDENTIAL GARAGE HEATERS GR RESIDENTIAL GARAGE HEATERS ARE SHIPPED FULLY ASSEMBLED C / W THERMOSTAT, WALL THIMBLE, 8 INTAKE / EXHAUST PIPES, GAS FLEX CONNECTOR AND CEILING SUSPENSION HARDWARE. BOTH

More information

3 Port, 2-Ton Outdoor Heat Pump

3 Port, 2-Ton Outdoor Heat Pump Job Name: Tag# Submittal Data Sheet 3 Port, 2-Ton Outdoor Heat Pump 3MXS24NMVJU Efficiency SEER EER HSPF Non-Ducted 17.9 12.7 12.5 Ducted 14 9.7 8.2 Mixed 15.95 11.2 10.35 Performance Cooling (Btu/hr)

More information

nufacturing Company, L.P San Felipe, Suite 500

nufacturing Company, L.P San Felipe, Suite 500 REPAIR PARTS AWUF Vertical Mount Air Handlers AWUF18051AA AWUF18051BA AWUF180516AA AWUF18081AA AWUF18081BA AWUF180816AA AWUF24051AA AWUF24051BA AWUF240516AA AWUF24081AA AWUF24081BA AWUF240816AA AWUF201AA

More information

REPAIR PARTS. GPG13 "M" Series Package Gas Unit

REPAIR PARTS. GPG13 M Series Package Gas Unit REPAIR PARTS GPG13 "M" Series Package Gas Unit GPG1324045MAA GPG1324070MAA GPG1330045MAA GPG1330070MAA GPG1336045MAA GPG1336070MAA GPG1336090MAA GPG1336090M43AA GPG1342070MAA GPG1342090MAA GPG1348070MAA

More information

PARTS LIST GAS BOILERS MODELS: CG320 (E) CG325 (E) CG330 (E)

PARTS LIST GAS BOILERS MODELS: CG320 (E) CG325 (E) CG330 (E) PARTS LIST GAS BOILERS MODELS: CG320 (E) CG325 (E) CG330 (E) CROWN FOOD SERVICE EQUIPMENT LTD. 70 OAKDALE ROAD, DOWNSVIEW, (TORONTO), ONTARIO, CANADA, M3N 1V9 TELEPHONE: (416) 746-2358, FAX: (416) 746-8324

More information

Product Data. CNPHP, CNRHP Evaporator Coil N Coil --- Cased Horizontal CNPHP / CNRHP

Product Data. CNPHP, CNRHP Evaporator Coil N Coil --- Cased Horizontal CNPHP / CNRHP CNPHP, CNRHP Evaporator Coil N Coil --- Cased Horizontal Product Data 06005 This horizontal design N -coil is an evaporator coil designed to provide the highest standards of reliability and durability.

More information

IR F ( C) ENGLISH INSTRUCTION MANUAL. Thermometer

IR F ( C) ENGLISH INSTRUCTION MANUAL. Thermometer INSTRUCTION MANUAL Thermometer DUAL-LASER TARGETING 12:1 DISTANCE- TO-SPOT RATIO AUTO-SCAN MAX/MIN/AVG/DIFF HIGH/LOW ALARM BACKLIT DISPLAY AUTO POWER-OFF ADJUSTABLE EMISSIVITY IR5 2m -22 752 F (-30 400

More information

Flexitest Switch Assemblies Type FT-19R and FT-19RX Supersedes DB March 2008

Flexitest Switch Assemblies Type FT-19R and FT-19RX Supersedes DB March 2008 Flexitest Switch Assemblies Type FT-19R and FT-19RX Supersedes DB41-078 March 2008 FT-19R and FT-19RX FT-19R 3RU with Individual Clear Covers APPLICATION FEATURES The type FT-19R (standard length) and

More information

Singer. Incremental Comfort Systems. K, EK Vintage F. Last Manufactured: Replacement Parts List No Revision C 04/2012

Singer. Incremental Comfort Systems. K, EK Vintage F. Last Manufactured: Replacement Parts List No Revision C 04/2012 Replacement Parts List No. 055231000 Revision C 04/2012 Singer Incremental Comfort Systems K, EK 07-15 Vintage F Last Manufactured: 1976 To find your Daikin Applied parts distributor, call 1-800-377-2787

More information

Automatic and Manual Safety Pilot Kits

Automatic and Manual Safety Pilot Kits Automatic and Manual Safety Pilot Kits Technical Control Systems Information For Peterson Vented Gas Logs RH Peterson Co. 14724 Proctor Ave * City of Industry * CA 91746 * 1(800) 332 3973 Website: www.rhpeterson.com

More information

Operating Instructions for Digital Manometer. Model: MAN-SD

Operating Instructions for Digital Manometer. Model: MAN-SD Operating Instructions for Digital Manometer Model: MAN-SD 1. Contents 1. Contents...2 2. Note...3 3. Instrument Inspection...3 4. Regulation Use...4 5. Operating Principle...4 6. Mechanical Connection...5

More information

Protective Coatings: Non-lead orange paint RAL red (optional) non-lead paint Hot dipped galvanized conforming to ASTM A-153.

Protective Coatings: Non-lead orange paint RAL red (optional) non-lead paint Hot dipped galvanized conforming to ASTM A-153. Technical Services: Tel: (66) 500-76 / Fax: (01) 71-7317 www.grinnell.com Grinnell Mechanical Products Grooved Fittings, Ductile Iron & Fabricated Steel General Description Grooved fittings provide an

More information

REPAIR PARTS. GPH14 H-SERIES R-410A Package Heat Pumps GPH1424H41AA GPH1430H41AA GPH1436H41AA GPH1442H41AA GPH1448H41AA GPH1460H41AA

REPAIR PARTS. GPH14 H-SERIES R-410A Package Heat Pumps GPH1424H41AA GPH1430H41AA GPH1436H41AA GPH1442H41AA GPH1448H41AA GPH1460H41AA REPAIR PARTS GPH14 H-SERIES R-0A Package Heat Pumps GPH1424HAA GPH1430HAA GPH1436HAA GPH1442HAA GPH1448HAA GPH1460HAA This manual is to be used by qualified technicians only. 2009 Goodman Manufacturing

More information

50 Gordon Drive, Rockland, Maine HC Series Snowplows. Installation Instructions CAUTION

50 Gordon Drive, Rockland, Maine HC Series Snowplows. Installation Instructions CAUTION Fisher Engineering 79000, 79200 (CH), 79250, 79350 50 Gordon Drive, Rockland, Maine 04841 2139 www.fisherplows.com May 15, 2018 Lit. No. 77138, Rev. 00 HC Series Snowplows Installation Instructions Read

More information

M2 SERIES THERMOSTATS 0 F to 240 F, Narrow Differential, Hermetically Sealed ½

M2 SERIES THERMOSTATS 0 F to 240 F, Narrow Differential, Hermetically Sealed ½ M2 SERIES THERMOSTATS 0 F to 240 F, Narrow Differential, Hermetically Sealed ½ Introduction The Klixon M2 thermostat is constructed with a snap acting bimetal disc that serves as the actuating element.

More information

REPAIR PARTS. GPH13 "M" Series Horizontal Package Heat Pumps GPH1324M41AA GPH1330M41AA GPH1336M41AA GPH1342M41AA GPH1348M41AA GPH1360M41AA

REPAIR PARTS. GPH13 M Series Horizontal Package Heat Pumps GPH1324M41AA GPH1330M41AA GPH1336M41AA GPH1342M41AA GPH1348M41AA GPH1360M41AA REPAIR PARTS GPH13 "M" Series Horizontal Package Heat Pumps GPH1324MAA GPH1330MAA GPH1336MAA GPH1342MAA GPH1348MAA GPH1360MAA This manual is to be used by qualified technicians only. 2009 Goodman Manufacturing

More information

Repair Parts List DUEL FUEL RANGE MODEL NUMBER SVD48600BC. When requesting service or ordering parts, always provide the following information:

Repair Parts List DUEL FUEL RANGE MODEL NUMBER SVD48600BC. When requesting service or ordering parts, always provide the following information: Repair Parts List DUEL FUEL RANGE MODEL NUMBER SVD48600BC When requesting service or ordering parts, always provide the following information: - Product Type - Part Number - Model Number - Part Description

More information

ClimateMaster s Tranquility 22. Raj Hiremath Director of Residential Marketing

ClimateMaster s Tranquility 22. Raj Hiremath Director of Residential Marketing ClimateMaster s Tranquility 22 Raj Hiremath Director of Residential Marketing 1 CLIMATEMASTER Industry leader since 1950 s First to introduce 2-stage 27 EER unit First to introduce Outdoor split system

More information

McQuay. Water Source Heat Pump. VF, VG, VP Vintage E, F, G. Last Manufactured: Replacement Parts List No Revision B 02/2017

McQuay. Water Source Heat Pump. VF, VG, VP Vintage E, F, G. Last Manufactured: Replacement Parts List No Revision B 02/2017 Replacement s List No. 055206700 Revision B 02/2017 McQuay Water Source Heat Pump VF, VG, VP 240-390 Vintage E, F, G Last Manufactured: 1992 To find your Daikin Applied parts distributor, call 1-800-377-2787

More information

ISOCON-6. 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER

ISOCON-6. 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER ISOCON-6 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER Whilst every effort has been taken to ensure the accuracy of this document, we accept no responsibility for damage, injury, loss or expense resulting

More information

Installation guide 862 MIT / MIR

Installation guide 862 MIT / MIR Installation guide 862 MIT / MIR in combination with: 864 MTT or 863 MRT or (dual) spot element November 2005 Part no. 4416.232_Rev3 Enraf BV PO Box 812 2600 AV Delft Netherlands Tel. : +31 15 2701 100

More information

Commercial Generator Parts Catalog. PROTEC Series

Commercial Generator Parts Catalog. PROTEC Series Commercial Generator Parts Catalog PROTEC Series YD ÁÁ ÁÁ To avoid errors or delay in filling your parts order, always give the MODEL, SPEC NO. and SERIAL NO. from the Onan nameplate. For handy reference,

More information

THE ENERGY 68,SAVING TDVI. exible Combine Modular 24, 26, 28, 30, 32, 34, 36, 38, 40, 42, 44 HP 60, 62, 64, 66 HP

THE ENERGY 68,SAVING TDVI. exible Combine Modular 24, 26, 28, 30, 32, 34, 36, 38, 40, 42, 44 HP 60, 62, 64, 66 HP I N V E RT E R ion Range exible Combine Modular TDV I TDV I TDV I INVERTER INVERTER INVERTER 14, 16, 18, 20, 22 HP TDV I 24, 26, 28, 30, 32, 34, 36, 38, 40, 42, 44 HP INVERTER INVERTER INVERTER TDV I INVERTER

More information

HVAC Electrical Wiring Diagrams / Ohm s Law / Sequence of Operation RV

HVAC Electrical Wiring Diagrams / Ohm s Law / Sequence of Operation RV PLEASE DO NOT BOOKMARK ANY ANYTIMECE WEBPAGES! Our system will remember the last page you viewed when logging out and back in but please DO NOT exit out when taking a test. Your place will NOT be saved.

More information

Important Instructions

Important Instructions Important Instructions Subject Use With Cabinet Hardmount Trunnion Replacement Cabinet Hardmount 8-60 Pound Washer-Extractors and Kits F77000, F7700, F7700, F7700, F7700, F7700, F9P and F9P WARNING This

More information

Model 33SZ Basic Unit OPTIONAL FILTER RH COIL CONNECTION PRIMARY/ DEDICATED OUTDOOR AIR MULTI-POINT FLOW SENSOR 5 3/4" (146)

Model 33SZ Basic Unit OPTIONAL FILTER RH COIL CONNECTION PRIMARY/ DEDICATED OUTDOOR AIR MULTI-POINT FLOW SENSOR 5 3/4 (146) DESRIPTION: Sensible cooling coil on the induced air inlet handles zone sensible load. Opposite side to controls location. luminum ripple fins (10 PI) and 1/" (13) copper tubes. and of coil connection

More information

4HP13 PRODUCT SPECIFICATIONS 13 SEER SPLIT SYSTEM HEAT PUMP WARRANTY

4HP13 PRODUCT SPECIFICATIONS 13 SEER SPLIT SYSTEM HEAT PUMP WARRANTY 4HP13 PRODUCT SPECIFICATIONS 13 S SPLIT SYSTEM HEAT PUMP FORM NO. 4HP13-100 (07/2014) R410A Refrigerant High-quality condenser coil with copper tubing and enhanced louvered fin for maximum heat transfer

More information

CALEFFI. Modulating digital controller for heating and cooling. 161 series 01122/08 GB. replaces dp 01122/05

CALEFFI. Modulating digital controller for heating and cooling. 161 series 01122/08 GB. replaces dp 01122/05 Modulating digital controller for heating and cooling series REGI ERED SI EN ISO 00:000 Cert. n FM UNI EN ISO 00:000 Cert. n 000 0/0 G replaces dp 0/0 Function The controller can be used with three-point

More information

C7400A and C7400C Enthalpy Sensors

C7400A and C7400C Enthalpy Sensors 70 and 70 Enthalpy Sensors PROUT T FETURES PPLITION The 70 Enthalpy Sensor is used with the economizer logic modules with the,,, and performance curves; the 70 sensor is used with the logic modules with

More information

Operating instructions Vortex flow meter. SVxxx / / 2015

Operating instructions Vortex flow meter. SVxxx / / 2015 Operating instructions Vortex flow meter SVxxx0 80229859 / 00 06 / 2015 Contents 1 Safety instructions...3 2 Functions and features...3 3 Function...4 4 Installation...4 5 Electrical connection...6 6 Operating

More information

Product Data CNPVP, CNPVT, CNPVU, CNRVU EVAPORATOR COIL N COIL - CASED AND UNCASED UPFLOW, DOWNFLOW

Product Data CNPVP, CNPVT, CNPVU, CNRVU EVAPORATOR COIL N COIL - CASED AND UNCASED UPFLOW, DOWNFLOW CNPVP, CNPVT, CNPVU, CNRVU EVPORTOR COIL N COIL - CSED ND UNCSED UPFLOW, DOWNFLOW Product Data CNPVP CNPVT (Transition) CN(P,R)VU 06008 06007 06004 This vertical design N -coil is a furnace coil designed

More information

REPAIR PARTS. GPH13 "H" Model Package Heat Pumps GPH1324H41AB GPH1330H41AB GPH1336H41AB GPH1342H41AB GPH1348H41BB GPH1360H41BB

REPAIR PARTS. GPH13 H Model Package Heat Pumps GPH1324H41AB GPH1330H41AB GPH1336H41AB GPH1342H41AB GPH1348H41BB GPH1360H41BB REPAIR PARTS GPH13 "H" Model Package Heat Pumps GPH1324H41AB GPH1330H41AB GPH1336H41AB GPH1342H41AB GPH1348H41BB GPH1360H41BB This manual is to be used by qualified technicians only. 2010 Goodman Manufacturing

More information

Today s A/C systems include:

Today s A/C systems include: * www.sgvenergywise.org Replac ing your A/C system REQUIRES a permit from your c ity - it s important. WHY? Because A/C (air conditioning) is a SYSTEM, not just one piece of equipment. The thermostat,

More information