Fact-Finding Report on Ambient Temperature Adjustment for Raceway and Cable Systems Exposed to Sunlight on Rooftops
|
|
- Kerrie Daniels
- 5 years ago
- Views:
Transcription
1 Effectiveness of Circuit Breakers in Mitigating Parallel Arcing Faults in the Home Run UL Corporate Research 333 Pfingsten Road Northbrook, IL USA File IN16969 Project 11CA25532 October 10, 2011 Issue Date: 11 October 2011 Fact-Finding Report on Ambient Temperature Adjustment for Raceway and Cable Systems Exposed to Sunlight on Rooftops Prepared for Travis Lindsay Consulting Services, Inc. Las Vegas, Nevada Report by Paul W. Brazis, Jr., PhD Fan He, PhD Reviewed by Pravinray D. Gandhi Copyright 2011 Underwriters Laboratories Inc. Underwriters Laboratories Inc. authorizes the above named company and the National Fire Protection Association to reproduce this Report provided it is reproduced in its entirety.
2 NOTICE Fact-Finding Investigations are undertaken to develop facts and issue a Report for use by the Client in seeking amendments in nationally recognized installation codes and standards. The issuance of this Report does not constitute an endorsement of any proposed amendment and in no way implies Listing, Classification or other recognition by UL and does not authorize the use of UL Listing or Classification Marks or any other reference to Underwriters Laboratories Inc. on, or in connection with, the product. Underwriters Laboratories Inc., its employees, and its agents shall not be responsible to anyone for the use or nonuse of the information contained in this Report, and shall not incur any obligation or liability for damages, including consequential damages, arising out of or in connection with the use of, or inability to use, the information contained in this Report.
3 EXECUTIVE SUMMARY The 2011 National Electrical Code (NEC ) requires for circular raceways exposed to sunlight on rooftops, an adjustment temperature be added to the outdoor temperature when determining ambient temperature and associated correction factors for calculating the ampacity of conductors. This adjustment temperature adder for circular raceways exposed to sunlight on rooftops is to account for solar heating, and is needed to assure that no conductor is used in a manner such that its operating temperature exceeds that for which it is designed. In preparing for the 2011 NEC, a proposal was submitted to include cables into the scope of this requirement. Although supporting documentation included a report of testing with MC cables, the Code Panel chose to reject this proposal since the term cables was too general, and that testing was insufficient since only MC cable in a single size was tested. Some of the Code Panel members also noted the need for a more comprehensive research project to determine the effects of sunlight on wiring systems in general when installed on rooftops. This is a report of a Fact-Finding Investigation intended to provide technical data and other pertinent facts regarding the safety aspects of installing raceways and cables to direct sunlight on or above rooftops. The investigation included tests on 17 different types and sizes of wiring systems, each of which were installed at four different elevations above the roof at an outdoor test facility in Las Vegas, Nevada. In addition to temperature measurements on the wiring system conductors, outdoor ambient temperature, wind speed, and solar irradiance were also recorded during the summer months of By calculating the difference between the temperature on the wiring system conductors and the outdoor ambient temperature during the period of peak solar irradiance during selected days of full sun and minimum wind, inferences could be made about the effects of solar heating on these wiring systems. A statistical analysis of the data also provided insights into how solar heating affects wiring systems in general when installed on or above a rooftop. For all wiring systems mounted directly on the roof, the maximum temperature rise above outdoor ambient with a 95% confidence interval would statistically be 62.2 o F. For all wiring systems mounted at a distance above the roof (1/2 inch and greater) the maximum temperature rise above outdoor ambient with a 95% confidence interval would statistically be 51.4 o F. page 3
4 TABLE OF CONTENTS Notice... 2 Executive Summary... 3 Table of Contents... 4 General... 5 Objective... 6 Wiring Systems and Rooftops... 7 NEC Requirements... 7 Comprehensive Test Program to Address Wiring Systems Exposed to Sunlight on Rooftops... 9 Test Sample Selecetion... 9 Test Considerations Test Results Data Analysis Summary Appendix A Test Samples Appendix B Test Instrumentation Appendix C Graphs of Daily Outdoor Ambient Temperature, Solar Irradiance, and Wind Speed Appendix D Description of Boxplot Diagrams for Data Analysis page 4
5 GENERAL A proposal was accepted for the 2008 National Electrical Code (NEC ), which recommended that for conduits exposed to sunlight on rooftops, an adjustment temperature be added to the outdoor temperature when determining ambient temperature for the correction factors in Tables and The substantiation for this proposal noted that Section required that no conductor shall be used in such a manner that its operating temperature exceeds that designated for the type of insulated conductor involved. It also cited testing that showed the air inside conduits in direct sunlight to be significantly hotter than the surrounding air. This proposal resulted in new Section (B)(2)(c) and new Table (B)(2)(c) for the 2008 NEC 1. For the 2011 NEC, a similar proposal was submitted to include cables into the scope of this requirement. Although supporting documentation included a report of testing with MC cables, the Code Panel chose to reject this proposal since the term cables was too general, and that testing was insufficient since only MC cable in a single size was tested. Some of the Code Panel members noted the need for a more comprehensive research project to determine the effects of sunlight on conduits, MC cable, and cable in general when installed on rooftops. 1 For the 2011 NEC, Sec became Sec (A)(3), Sec (B)(2)(c) became Sec (B)(3)(c), and Table (B)(2)(c) became Table (B)(3)(c). page 5
6 OBJECTIVE The objective for this Fact-Finding Investigation is to provide technical data and other pertinent facts regarding the safety aspects of installing raceways and cables to direct sunlight on or above rooftops. Travis Lindsey Consulting Services Inc. proposes to submit a public proposal to revise Section (B)(3)(c) of the 2011 NEC as follows: (c) Circular Raceways and Cables Exposed to Sunlight on Rooftops. Where conductors or cables are installed in circular raceways or where in cables exposed to direct sunlight on or above rooftops, the adjustments shown in Table (B)(3)(c) shall be added to the outdoor temperature to determine the applicable ambient temperature for application of the correction factors in Table (B)(2)(a) or (B)(2)(b). Table (B)(3)(c) Ambient Temperature Adjustment for Circular Raceways or Cables Exposed to Sunlight on or Above Rooftops Distance Above Roof to Bottom of Conduit Raceway or Cable 0-13 mm (1/2 in.) Above 13 mm (1/2 in.) - 90 mm (3-1/2) in.) Above 90 mm (3-1/2 in.) mm (12 in.) Above 300 mm (12 in.) mm (36 in.) o C Temperature Adder o F page 6
7 WIRING SYSTEMS AND ROOFTOPS NEC Requirements Wiring methods and materials are described in Chapter 3 of the NEC. Included in Chapter 3 are various Articles for different cable types and raceways for containing conductors for general wiring, including wiring that may be installed on a rooftop and exposed to sunlight. Although the uses permitted for these various cables and raceways do not specifically mention rooftops, it could be assumed that if permitted for outdoor use and/or wet locations, and resistant to sunlight, a particular wiring system could be installed on a rooftop exposed to sunlight. Tables 1 and 2 include the various cable and raceway systems from Chapter 3 that could typically be installed on or above rooftops exposed to sunlight as permitted by the NEC. Also included in these tables are the specific NEC Chapter 3 Article, the UL standard, and the range of sizes that would be permitted or could be listed. page 7
8 Table 1 Cables Suitable for Installation on Rooftops Exposed to Sunlight Wire Size Type NEC Article UL Standard Min Max Comment MV If identified for use in direct sunlight, or as "MV or MC" MC MI Max 4 AWG for 2 & 3 conductor; 6 AWG for 4 conductor; 10 AWG for a 7 conductor UF /0 For use with PV (rooftop) systems; Max 6 AWG for multiple conductors. This can also include single conductor cable listed as PV wire. TC When marked "Sunlight Resistant" SE unspecified Table 2 Conduits and Raceways Suitable for Installation on Rooftops Exposed to Sunlight Trade Size Type NEC Article UL Standard Min Max Comment IMC /2 4 RMC 344 6/6A 3/8 6 LFMC /8 4 PVC /2 6 LFNC /8 4 When listed as suitable for outdoors EMT /797A 1/2 4 Auxiliary Gutters When listed for exposure to sunlight and wet locations Cable Bus 370 When identified for outdoor use Metal Wireways When listed for wet locations Nonmetallic Wireways /5A When listed for wet locations page 8
9 COMPREHENSIVE TEST PROGRAM TO ADDRESS WIRING SYSTEMS EXPOSED TO SUNLIGHT ON ROOFTOPS Test Sample Selection Various test samples were chosen because of their expected use on rooftops exposed to sunlight, and their similarity to other raceway and cable systems that were not tested, but considered to be representative of these other wiring systems for test purposes. For cables, Type MC cable was chosen to represent metal clad and metal sheathed cables and conduits (e.g. Type MC, MI, LFMC, etc.). Sizes 12 AWG, 1/0 AWG, and 500 kcmil were chosen to represent cables of the smaller, medium, and larger sizes. Type SE and TC cable was also chosen in the 1/0 AWG size to represent jacketed cables (e.g. Type SE, TC, MV, UF, etc.) For conduits and tubings, Type RMC and EMT were chosen to represent circular metal raceways (e.g. RMC, IMC, EMT, etc.). To represent the smaller sizes, trade size ½ was chosen for RMC, and trade size ¾ was chosen for EMT. For the medium and larger sizes, trade sizes 1-1/2 and 4 respectively were chosen. Type PVC was chosen to represent nonmetallic conduits and raceways. To represent the smaller sizes, trade size ¾ was chosen, and for the medium and larger sizes, trade sizes 1-1/2 and 4 respectively were chosen. For other metal wiring systems (e.g. metal wireways, gutters, etc.), metal raceway was chosen in the 4x4 inch and 8x8 inch sizes to represent smaller and larger raceways in general. Table 3 is a summary of the proposed testing to consider a comprehensive research program to determine the effects of direct sunlight when conduit, MC cable, and wiring systems in general are installed on or above a rooftop. page 9
10 Table 3 Summary of Test Samples Raceway/ Cable Type Conductor Size* Trade Size Installed Conductor Size* Number of Conductors MC 12 3 MC 1/0 3 MC SE 1/0 3 TC 1/0 3 RMC 1/ RMC 1-1/2 1/0 4 RMC PVC 3/ PVC 1-1/2 1/0 3 PVC EMT 3/ EMT 1-1/2 1/0 5 EMT Metal Raceway 4x4 in. 1/0 3 Metal Raceway 8x8 in * - AWG or kcmil (copper), Type THHN/THWN. Test Considerations Laboratory Site The testing was conducted at an outdoor laboratory site located in Las Vegas, Nevada. This area was chosen for its broad range of days with higher solar radiation intensity. Fig. 1 Las Vegas, Nevada Outdoor Test Site page 10
11 Roof - To support Table (B)(3)(c) from the 2011 NEC, each wiring system was tested directly on the roof, and at distances of 1/2, 3-1/2, and 12 inches above the roof 2. For wiring systems tested directly on the roof and at 1/2 inch above the roof, the roof was asphalt painted black in color to account for additional heating from solar absorption on the roof. For wiring systems tested at distances greater than 1/2 inch above the roof, the roof surface was asphalt painted white in color to account for additional heating from solar reflection from the roof. Each roof structure was flat, approximately five feet off the ground, and measured 13-1/2 by 10 feet, with R19 fiberglass batt insulation under the roof deck. Fig. 2 Samples Mounted Directly on Black Roof Fig. 3 Samples Mounted 12 Inches off White Roof Test Samples Each test sample was 10 feet long exposed along the horizontal length of the roof surface. A thermocouple was secured to each conductor insulation midway along the length of the sample. The thermocouples were type T, No. 24 AWG, with welded junctions. For the Type MC cable samples, the thermocouple was secured near the conductor. For samples with more than three conductors, a maximum of three thermocouples were used. See Appendix A for a thorough description of each test sample. The ends of each wiring system were closed with surgical cotton to restrict air flow. The wires were not energized during the testing since the object of the testing was to obtain a measurement of the wiring system temperature increase due to the influence of exposure to the sun. 2 Although the breakpoints in Table (B)(3)(c) are for distances of above (greater than) ½, 3-1/2, and 12 inches above the roof, the test samples were located at these breakpoint distances to represent a worst-case test condition. page 11
12 Fig. 4 Thermocouples Installed on Conductors Fig. 5 Cotton Used to Close Ends of Wireways Data Measurements - Temperatures were measured at 1 minute increments throughout the day, and the maximum of the 1 minute increments for a 5 minute time period was recorded. This resulted in 12 recorded measurements per hour. In addition to the measurement of temperature of the conductor insulation of each test sample, the near-by outdoor air temperature was measured in two aspirated enclosures located approximately 8 feet and 13 feet above grade level in the vicinity of the roofs and test samples. Wind speed was similarly measured in the same vicinity using two anemometers. Solar irradiance was measured using a pyranometer located in the same plane as the roof surface. Fig. 6 Aspirated Enclosure for Outdoor Temperature Fig. 7 Anemometer for Wind Speed Measurement page 12
13 Solar irradiance and wind speed was recorded along with the test sample temperatures. Measurements were recorded during the months of June, July and August of Sufficient data was recorded to enable supportable and statistical inferences regarding expected ambient temperatures for raceway and cable systems exposed to sunlight on rooftops. Solar Irradiance - Solar irradiance, or radiation from the sun, is measured as power density in Watts per square meter (W/m 2 ). This solar radiation reaching the earth can vary depending on several factors, including as time-of-day, time-of-year, atmospheric conditions such as clouds, haze, rain, etc., as well as geographical location. The maximum solar radiation reaching the earth s atmosphere can approach 1400 W/m 2, however, W/m 2 is more typical of maximum surface irradiance on a sunny day in many parts of the United States, and can be less during the winter, and much less on cloudy days. Solar photovoltaic (PV) modules are tested and rated under what is referred to as standard test conditions, or STC for short. These standard test conditions are solar irradiance of 1000 W/m 2 and air temperature of 25 o C. 3 In the NEC, PV system components, such as wire size and overcurrent protection, are based on these standard test conditions, with adjustment factors for periods of time where the maximum solar irradiance can exceed 1000 W/m 2. 4 Figure 8 shows a graph of the solar irradiance at the test site incident to the test roofs on June 22, The day was full sun, maximum outdoor ambient temperature of 110 o F, and near the time of summer solstice. The solar irradiance that day exceeded 1000 W/m 2 for a three-hour period beginning at 11:10 am. The NEC defines in Article 100 a continuous load as a load where the maximum current is expected to continue for 3 hours or more. 3 Underwriters Laboratories Inc., UL Standard for Safety for Flat-Plate Photovoltaic Modules and Panels, UL See Glossary Section 2.17 for definition of Standard Test Conditions. 4 As an example, see NEC Sec where calculations for maximum circuit current and conductor ampacity involve multipliers of 125%. page 13
14 Fig. 8 Solar Irradiance for June 22, 2011 at Las Vegas Test Site Test Results Data measurements were recorded during the months of June, July and August of This time of the year also produced many days of large amounts of solar radiation for the longest periods of time. During these months there were many days of full sun throughout the day where outside temperature exceeded 100 o F, and solar irradiance exceeded 1000 W/m 2. The solar irradiance for days of prolonged full sun peaked near solar noon, which occurred at about 12:45 pm in Las Vegas that time of year (daylight savings time). For analysis of results purposes, 10 days were chosen during this time period where that solar irradiance exceeded 1000 W/m 2 for a prolonged period of time. Although wind speed could not be controlled, these days were also chosen where the wind speed was minimized. This resulted in 5 days in late June, and 5 days in early August as shown in Table 4. For each of these 10 days, the temperature data were analyzed for the period of time that day were the solar irradiance was greater than or equal to 1000 W/m 2. Depending upon the day, this resulted in elapsed times of 3 hours and 5 minutes to 2 hours and 15 minutes as shown in the table. This table also includes the average wind speed and maximum outdoor ambient temperature for that period of time. See Appendix C for complete graphs of the daily outdoor ambient temperature, solar irradiance, and wind speed. page 14
15 Table 4 10 Days of Analyzed Data Period of Solar Radiation 1000 W/m 2 (Hours:Minutes) Outdoor Avg Wind Speed Ambient Day (2011) Beginning End Elapsed Time (MPH) Deg F June 21 11:15 14:05 2 hr 50 min June 22 11:10 14:10 3 hr 00 min June 23 11:20 14:15 2 hr 55 min June 25 11:05 14:10 3 hr 05 min June 26 11:10 14:15 3 hr 05 min August 4 11:35 2 hr 25 min August 5 11:30 14:05 2 hr 35 min August 6 11:35 13:50 2 hr 15 min August 8 11:35 2 hr 25 min August 9 11:45 2 hr 15 min For each test sample, the rise above outdoor ambient temperature for the three thermocouple temperatures were averaged for each five-minute increment to record the temperature rise above outdoor ambient of the test sample for that time measurement increment. An analysis of the variance for the three thermocouple readings of each test sample typically showed a variance of less than 1 o F, except for the tray cable (TC) samples, where the variance was greater because of the orientation of the three thermocouples around the circumference of the cable. For that reason, the maximum temperature of the three thermocouple readings for the tray cable was used for this test sample because of the importance of recording the hottest temperature being experienced by the cable. For each of the ten chosen days, the maximum, minimum, 90 th, 75 th, and 50 th percentile temperatures were calculated for each test sample at each elevation for the period of time that day when the solar irradiance was greater than or equal to 1000 W/m 2. For the accumulated ten days, the overall maximum, minimum, and averages of the 90 th, 75 th and 50 th percentile temperatures were then tabulated. The tables below show that complied data. page 15
16 Table 5 Maximum Temperature Rise Above Outdoor Ambient ( o F) Distance Above Roof 1 Foot 3-1/2 inch 1/2 inch On Roof Circular Raceway - Metal 3/4" EMT /2" RMC /2" EMT /2" RMC " EMT " RMC Circular Raceway - Plastic 3/4" PVC /2" PVC " PVC Square Raceway - Metal 4" DUCT " DUCT Cables #12 MC #1/0 MC #1/0 SE Tray 1/0 SE Tray 1/0 TC #500 MC NEC Adder Table 6 Minimum Temperature Rise Above Outdoor Ambient ( o F) Distance Above Roof 1 Foot 3-1/2 inch 1/2 inch On Roof Circular Raceway - Metal 3/4" EMT /2" RMC /2" EMT /2" RMC " EMT " RMC Circular Raceway - Plastic 1/2" RMC /2" PVC " PVC Square Raceway - Metal 4" DUCT " DUCT Cables #12 MC #1/0 MC #1/0 SE Tray 1/0 SE Tray 1/0 TC #500 MC NEC Adder page 16
17 Circular Raceway - Metal Circular Raceway - Plastic Square Raceway - Metal Cables Table 7 90th Percentile Temperature Rise Above Outdoor Ambient ( o F) Distance Above Roof 1 Foot 3-1/2 inch 1/2 inch On Roof 3/4" EMT /2" RMC /2" EMT /2" RMC " EMT " RMC /4" PVC /2" PVC " PVC " DUCT " DUCT #12 MC #1/0 MC #1/0 SE Tray 1/0 SE Tray 1/0 TC #500 MC NEC Adder Table 8 75th Percentile Temperature Rise Above Outdoor Ambient ( o F) Distance Above Roof 1 Foot 3-1/2 inch 1/2 inch On Roof Circular Raceway - Metal 3/4" EMT /2" RMC /2" EMT /2" RMC " EMT " RMC Circular Raceway - Plastic 3/4" PVC /2" PVC " PVC Square Raceway - Metal 4" DUCT " DUCT Cables #12 MC #1/0 MC #1/0 SE Tray 1/0 SE Tray 1/0 TC #500 MC NEC Adder page 17
18 Table 9 50th Percentile Temperature Rise Above Outdoor Ambient ( o F) Distance Above Roof 1 Foot 3-1/2 inch 1/2 inch On Roof Circular Raceway - Metal 3/4" EMT /2" RMC /2" EMT /2" RMC " EMT " RMC Circular Raceway - Plastic 3/4" PVC /2" PVC " PVC Square Raceway - Metal 4" DUCT " DUCT Cables #12 MC #1/0 MC #1/0 SE Tray 1/0 SE Tray 1/0 TC #500 MC NEC Adder page 18
19 Data Analysis To analyze the differences between wiring systems at different distances from the roof, a compilation of all of the wiring system 90 th percentile temperature rises (Table 7) 5 for the period of time each day where the solar irradiance was greater than or equal to 1000 W/m 2 was made for each of the four elevations. This analysis is shown in Boxplot 6 No.1. Note that for the wiring systems at distances 0.0 and 0.5 inches above the roof, the roof color was black, and for distances 3.5 and 12.0 inches above the roof, the roof color was white. Previous research 7 had shown that at the 0.5 inch distance, there was no significant difference between the black and white roof colors affecting the temperature of the wiring systems. For that reason black was chosen for the color of the roof at that distance. However, this previous research was only conducted with smaller size raceways and cable. It is possible that larger size raceways and cables could have absorbed more of the reflected solar radiation off the roof had the roof been white. This could explain why the mean temperature rise for the wirings systems at 0.5 inches above the roof were less than those at 3.5 and 12.0 inches above the roof. To analyze the differences between the different individual wiring systems, a compilation of all of the different wiring system 90 th percentile temperature rises for the period of time each day where the solar irradiance was greater than or equal to 1000 W/m 2 was made. This analysis is shown in Boxplot No.2. Note that the MC and TC cables were black in color, and the SE cable was light gray in color. 5 The 90 th percentile values were used to eliminate the maximum temperatures that were only being experienced for a very short period of time when the solar irradiance peaked for that day. Note however, there was typically only a few degrees F or less difference between the 90 th and 75 th percentile values. See Tables 7 and 8. 6 See Appendix D for a description of boxplots. 7 Effect of Rooftop Exposure on Cable Temperatures, November 2008, by Travis C. Lindsey. Available for review at the National Fire Protection Association (NFPA) Headquarters, Quincy, MA. Reference Report on Proposals June 2010, Proposal 6-66, Log #2751, NEC-P06. See Fig. 3, Temperature Rise as Function of Roof Color. page 19
20 60 Boxplot No. 1 - All Temperature Data by Distance Above Roof Temperature Rise, Deg F Distance Above Roof (Inches) 12.0 page 20
21 Histogram No. 1 shows the 90 th percentile temperature rise data for wiring systems directly on the roof for the period of time each day where the solar irradiance was greater than or equal to 1000 W/m 2. This analysis shows that for all of the 17 test samples of wiring systems mounted directly on the roof, the mean (average) temperature rise was 48.8 o F with a standard deviation of 6.83 o F. Confidence intervals (C.I) are often used as a statistical estimate to bracket data parameters with a known degree of certainty. A 95% C.I. is suggested as an appropriate safety factor to represent the true population of the data from the sampled population (tested samples). A 95% C.I. is calculated (two-sided) as the mean plus/minus 1.96 times the standard deviation. For this case, maximum temperature rise for all wiring systems mounted directly on the roof with a 95% C.I. would be 62.2 o F. Histogram 1A shows a representation of this with vertical lines at the mean and 95% C.I. points. page 21
22 An observation from Boxplot No. 1 appears to show that there is little difference between mean temperature rises for test samples of wiring systems mounted 0.5, 3.5, and 12.0 inches above the roof. Neglecting any heat convection or reradiation from the surface of the roof, this would be expected since the distance from the sun to the surface of the earth is large as compared to the distance between the three wiring systems. To verify this, an analysis of variance (ANOVA) was conducted with this data for the three distances from the roof. This analysis, shown in Fig. 9, demonstrates there is little difference between the mean temperature rises for all test data from each of the three wiring systems mounted 0.5, 3.5, and 12.0 inches above the roof. This is exemplified by the low value for R sq, which shows that varying the distance from the roof between 0.5 and 12.0 inches does not have any significant effect on the temperature rise within the raceway or cable. It is expected that distances greater than 12.0 inches will also show this minimal difference. page 22
23 One-way ANOVA: 90 th Percentile Data versus Distance from Roof (0.5, 3.5, and 12.0 inches) Source DF SS MS F P Distance Error Total S = 6.6 R-Sq = 6.31% R-Sq(adj) = 2.41% DF = Degrees of Freedom SS = Sum of squares MS = Mean square S = Standard deviation F = F ratio P = p-value R = Correlation coefficient Individual 95% C.I.s for Mean Based on Pooled Standard Deviation of 6.6 Level N Mean StDev ( * ) ( * ) ( * ) Fig. 9 Analysis of Variance for Wiring Systems Mounted Off Roof Histogram No. 2 shows the 90 th percentile temperature rise data for all wiring systems mounted 0.5, 3.5, and 12.0 inches above the roof for the period of time each day where the solar irradiance was greater than or equal to 1000 W/m 2. page 23
24 This analysis shows that for all of the 51 test samples of wiring systems mounted off the roof (0.5, 3.5, and 12.0 inches), the mean temperature rise was 38.5 o F with a standard deviation of 6.60 o F. The maximum temperature rise for all wiring systems mounted off on the roof with a 95% C.I. would be 51.4 o F. Histogram 2A shows a representation of this with vertical lines at the mean and 95% C.I. points. page 24
25 SUMMARY 1. Of the 17 different wiring systems tested, nine are currently addressed by the 2011 NEC Sec (B)(3)(c) requirement for circular raceways exposed to sunlight on rooftops, e.g., EMT, RMC, and PVC, and eight are not, e.g., square raceway and cables. Using the maximum temperature rises from Table 5: a. All of the wiring systems mounted 12 inches from the roof and 3-1/2 inches from the roof exceeded the NEC Table 310.(B)(3)(c) temperature adders of 25 o F and 30 o F respectively. For wiring systems mounted 12 inches from the roof, this ranged from 34.2 to 59.6 o F, and for wiring systems 3-1/2 inches from the roof this ranged from 35.1 to 65.0 o F. b. For wiring systems mounted ½ inch off the roof, all of the cables, and the 4 inch square metal duct exceeded the 40 o F NEC temperature adder. Five of the nine circular raceways also exceeded this 40 o F adder. The range in temperature rises for wiring systems mounted ½ inch off the roof was 34.8 to 53.3 o F. c. For wiring systems mounted on the roof, four of the cables exceeded the 60 o F temperature adder, and three of the circular raceways also exceeded this 60 o F adder. The range in temperature rises for wiring systems mounted on the roof was 43.8 to 71.4 o F. 2. In general, the smaller size wiring systems reached a hotter temperature than wiring systems of the same type but larger. This was especially true of the metallic wiring systems, and when the wiring systems were mounted directly on the roof. This was expected because the larger wiring systems had a larger ratio of surface area to mass, and thus took longer to heat up and cool down. This greater mass could also absorb the radiated heat from the sun (and the conducted heat from the roof) over a greater volume. See Tables The 1/0 SE cable operated much cooler than the similar sized 1/0 MC and 1/0 TC cables. This was expected due to the black outer jacked of the 1/0 MC and 1/0 TC cables having greater absorption properties, e.g., higher emissivity, than the lighter colored SE cable. See Boxplot No. 2. page 25
26 4. Wiring systems mounted 3-1/2 inches off the white roof usually operated hotter than similar wiring systems mounted ½ inch off the black roof. This was likely because of the solar reflection off the white roof producing additional solar power that could be absorbed by the underside of the wiring system 3-1/3 inches from the roof. These results may have been different had the wiring systems mounted ½ inch off the roof been tested with a white roof. However, wiring systems mounted directly on the roof most always operated significantly hotter than wiring systems of the same type mounted off the roof. See Boxplot No For all wiring systems mounted directly on the roof, the 90 th percentile mean temperature rise above outdoor ambient for the period of time each day where the solar irradiance was greater than or equal to 1000 W/m 2 was 48.8 o F with a standard deviation 6.8. For this case, maximum temperature rise above outdoor ambient for all wiring systems mounted directly on the roof with a 95% confidence interval (C.I.) would be 62.2 o F. 6. A statistical analysis of variance of the data for temperature rise above outdoor ambient showed that all test data from wiring systems mounted 0.5, 3.5, and 12.0 inches above the roof were not affected significantly by distance. Therefore, distances greater than 0.5 inches above the roof can be considered far from the roof and roof distance does not need to be a consideration in calculating temperature rise. For all wiring systems mounted 0.5, 3.5, and 12.0 inches above the roof, the 90 th percentile mean temperature rise above outdoor ambient for the period of time each day where the solar irradiance was greater than or equal to 1000 W/m 2 was 38.5 o F with a standard deviation 6.6. For this case, maximum temperature rise above outdoor ambient for all wiring systems mounted off on the roof with a 95% confidence interval (C.I.) would statistically be 51.4 o F. Report by: Reviewed by: David A. Dini, P.E. Research Engineer I Corporate Research Underwriters Laboratories Inc. Paul W. Brazis Jr., PhD Research Manager Corporate Research Underwriters Laboratories Inc. page 26
27 APPENDIX A Test Samples 1. Metal-Clad Cable, Type MC, No. 12 AWG/3 with No. 12 AWG ground. Aluminum interlocked armor with black PVC jacket. Copper THHN/THWN conductors. 2. Rigid Metal Conduit, Type RMC, Trade Size ½. Metallic silver in color. Seven No. 12 AWG copper conductors, Type THHN/THWN installed. 3. Rigid Polyvinyl Chloride Conduit, Type PVC, Trade ¾. Natural gray in color. Three No. 12 AWG copper conductors, Type THHN/THWN installed. Fig. A1 No. 12 MC (1), ½ RMC (2), ¾ PVC (3) 4. Electrical Metallic Tubing, Type EMT, Trade Size ¾. Metallic silver in color. Three No. 12 AWG copper conductors, Type THHN/THWN installed. 5. Metal-Clad Cable, Type MC, No. 1/0 AWG/3 with No. 6 AWG ground. Aluminum interlocked armor with black PVC jacket. Copper THHN/THWN conductors. page 27
28 6. Service-Entrance Cable, Type SE, No. 1/0 AWG/3 with No. 2 AWG ground. Sunlight resistant with light gray jacket. Copper THHN/THWN conductors. 7. Rigid Metal Conduit, Type RMC, Trade Size 1-½. Metallic silver in color. Four No. 1/0 AWG copper conductors, Type THHN/THWN installed. Fig. A2 ¾ EMT (4), No. 1/0 MC (5), No. 1/0 SE (6), 1-1/2 RMC (7) 8. Rigid Polyvinyl Chloride Conduit, Type PVC, Trade1-1/2. Natural gray in color. Three No. 1/0 AWG copper conductors, Type THHN/THWN installed. 9. Electrical Metallic Tubing, Type EMT, Trade Size 1-1/2. Metallic silver in color. Five No. 1/0 AWG copper conductors, Type THHN/THWN installed. page 28
29 Fig. A3 1-1/2 PVC (8), 1-1/2 EMT (9) 10. Service-Entrance Cable, Type SE, No. 1/0 AWG/3 with No. 2 AWG ground. Sunlight resistant with light gray jacket. Copper THHN/THWN conductors. Installed in a cable tray, basket type. 11. Power and Control Tray Cable, Type TC, No. 1/0 AWG/3 with No. 6 AWG bare ground. Sunlight resistant with black jacket. Copper THHN/THWN conductors. Installed in a cable tray, basket type. Fig. A4 No. 1/0 SE (10), No. 1/0 TC (11), Installed in Cable Tray page 29
30 12. Metal-Clad Cable, Type MC, No. 500 kcmil/3 with No. 2 AWG ground. Aluminum interlocked armor with black PVC jacket. Copper THHN/THWN conductors. 13. Rigid Metal Conduit, Type RMC, Trade Size 4. Metallic silver in color. Three No. 500 kcmil copper conductors, Type THHN/THWN installed. Fig. A5 No. 500 MC (12), 4 RMC (13) 14. Rigid Polyvinyl Chloride Conduit, Type PVC, 4. Natural gray in color. Three No. 500 kcmil copper conductors, Type THHN/THWN installed. 15. Electrical Metallic Tubing, Type EMT, Trade Size 4. Metallic silver in color. Three No. 500 kcmil copper conductors, Type THHN/THWN installed. page 30
31 Fig. A6 4 PVC (14), 4 EMT (15) 16. Metal Wireway, 4 in. by 4 in., 16 gauge steel. Gray in color. Three No. 1/0 AWG copper conductors, Type THHN/THWN installed. 17. Metal Wireway, 8 in. by 8 in., 14 gauge steel. Gray in color. Three No. 500 kcmil copper conductors, Type THHN/THWN installed. Fig. A7 4 In. Duct (16), 8 In. Duct (17) page 31
32 APPENDIX B Test Instrumentation Pyranometer Campbell Scientific, CS300 apogee silicon pyranometer. Anemometer - Campbell Scientific, three-cup anemometer. Data Acquisition System - Campbell Scientific, CR5000 Measurement and Control System. Serial No Date of last calibration, April 15, 2011, by Campbell Scientific (A2LA accredited). page 32
33 APPENDIX C Graphs of Daily Outdoor Ambient Temperature, Solar Irradiance, and Wind Speed page 33
34 June 21, Ambient Temperature Deg F June 21, Solar Watts / square meter June 21, Wind Velocity MPH page 34
35 112 June 22, 2011 Ambient Temperature Deg F June 22, 2011 Solar Watts / square meter June 22, Wind Velocity MPH page 35
36 110 June 23, 2011 Ambient Temperature Deg F June 23, 2011 Solar Watts / square meter June 23, Wind Velocity MPH page 36
37 106 June 25, Ambient Temperature Deg F June 25, 2011 Solar Watts / square meter June 25, Wind Velocity MPH page 37
38 107.5 June 26, 2011 Ambient Temperature Deg F June 26, 2011 Solar Watts / square meter June 26, Wind Velocity MPH page 38
39 106 August 4, 2011 Ambient Temperature Deg F August 4, Solar Watts / square meter August 4, Wind Velocity MPH page 39
40 105.0 August 5, 2011 Ambient Temperature Deg F August 5, Solar Watts / square meter August 5, Wind Velocity MPH page 40
41 106 August 6, 2011 Ambient Temperature Deg F August 6, Solar Watts / square meter August 6, Wind Velocity MPH page 41
42 107.5 August 8, 2011 Ambient Temperature Deg F August 8, Solar Watts / square meter August 8, Wind Velocity MPH page 42
43 107.5 August 9, 2011 Ambient Temperature Deg F August 9, Solar Watts / square meter August 9, Wind Velocity MPH page 43
44 APPENDIX D Description of Boxplot Diagrams for Data Analysis Note A crosshairs within a box also represents the mean (average) of the data. page 44
Conductor sizing is a critical step
Quality Assurance Code-Compliant Conductor Sizing Conductor sizing is a critical step in PV system design. You must be sure you satisfy the NEC requirements both for the conductor s ability to carry the
More informationUnit 11 Wire Tables and Conductor Sizes
Wire Tables and Conductor Sizes Objectives: Discuss factors that determine conductor ampacity. Discuss resistance of wire. Determine insulation characteristics. Use temperature correction factors. Determine
More informationBack to Basics: Realizing Cabling Determines Design. F. Patrick Mahoney, CSI CDT, RCDD Direct Supply - Aptura
Back to Basics: Realizing Cabling Determines Design F. Patrick Mahoney, CSI CDT, RCDD Direct Supply - Aptura Back to Basics: Realizing Cabling Determines Design Cabling distribution design implementation
More informationFile SV16101 Project 05CA December 1, 2005 REPORT
File SV16101 Project 05CA51080 December 1, 2005 REPORT on COMMERCIAL INSPECTION AND TESTING INVESTIGATION OF Roof Panel Coatings for Thermal Emittance and Solar Reflectance Astec Paints Australia LTD Australia
More informationTemperature Profile for 36 Marker Spheres on 3M 788 ACCR Conductor 3M Company
Temperature Profile for 36 Marker Spheres on 3M 788 ACCR Conductor 3M Company NEETRAC Project Number: 07-113 June 2007 A Research Center of the Georgia Institute of Technology Requested by: Dr. Colin McCullough
More informationINDUSTRIAL INSULATION for Systems Operating Above Ambient Temperature
INDUSTRIAL INSULATION for Systems Operating Above Ambient Temperature U.S. Department of Energy Energy Efficiency and Renewable Energy Office of Industrial Technologies Washington, D.C. 20585 From September,
More informationD DAVID PUBLISHING. Simulation of Accelerated Ageing of UV-Radiation for Photodegradable Geotextiles/Geomembranes. 1. Introduction
Journal of Geological Resource and Engineering 1 (2016) 44-50 doi:10.17265/2328-2193/2016.01.005 D DAVID PUBLISHING Simulation of Accelerated Ageing of UV-Radiation for Photodegradable Geotextiles/Geomembranes
More informationIBHS Roof Aging Program Data and Condition Summary for 2015
IBHS Roof Aging Program Data and Condition Summary for 2015 Ian M. Giammanco Tanya M. Brown-Giammanco 1 Executive Summary In 2013, the Insurance Institute for Business & Home Safety (IBHS) began a long-term
More informationPre-certification PVC and Rilrld Aluminum Conduit Expansion
6 PVC and Rilrld Aluminum Conduit Expansion Rules 12-1100 to 12-1122 govern the use of PVC conduit for electrical installations. t should be noted that in rule 12-1102 it specifies that PVC conduit shall
More informationTEST METHOD FOR STILL- AND FORCED-AIR JUNCTION-TO- AMBIENT THERMAL RESISTANCE MEASUREMENTS OF INTEGRATED CIRCUIT PACKAGES
SEMI G38-0996 N/A SEMI 1987, 1996 TEST METHOD FOR STILL- AND FORCED-AIR JUNCTION-TO- AMBIENT THERMAL RESISTANCE MEASUREMENTS OF INTEGRATED CIRCUIT PACKAGES 1 Purpose The purpose of this test is to determine
More informationUNDERGROUND DUCTBANK HEATING CONSIDERATIONS
UNDERGROUND DUCTBANK HEATING CONSIDERATIONS A Practical Approach to Determining UG Electrical Ductbank Ampacity Mike Mosman, PE CCG Facilities Integration Incorporated March 2016 Topics 2 PHYSICS of HEAT
More information19.3 Design of Feeders for Industrial Power Systems
19.3 Design of Feeders for Industrial Power Systems Most feeders are comprised of cables enclosed in raceways. Raceways are defined as enclosed channels designed expressly for holding wires, cables, or
More informationMODEL 107 TEMPERATURE PROBE INSTRUCTION MANUAL
MODEL 107 TEMPERATURE PROBE INSTRUCTION MANUAL REVISION: 6/00 COPYRIGHT (c) 1983-2000 CAMPBELL SCIENTIFIC, INC. This is a blank page. Warranty and Assistance The MODEL 107 TEMPERATURE PROBE is warranted
More informationUNIT FOUR SOLAR COLLECTORS
ME 476 Solar Energy UNIT FOUR SOLAR COLLECTORS Flat Plate Collectors Outline 2 What are flat plate collectors? Types of flat plate collectors Applications of flat plate collectors Materials of construction
More informationCONSTRUCTION MATERIALS
CONSTRUCTION MATERIALS T E C H N O L O G I E S PERFORMANCE TEST REPORT FOR Southern Manufacturing Division of Accord Industries IN ACCORDANCE WITH FLORIDA BUILDING CODE (HIGH VELOCITY HURRICANE ZONES)
More informationOptimizing the Photovoltaic Solar Energy Capture on Sunny and Cloudy Days Using a Solar Tracking System
Optimizing the Photovoltaic Solar Energy Capture on Sunny and Cloudy Days Using a Solar Tracking System Nelson A. Kelly and Thomas L. Gibson Chemical Sciences and Material Systems Laboratory General Motors
More informationSMAM 314 Practice Final Examination Winter 2003
SMAM 314 Practice Final Examination Winter 2003 You may use your textbook, one page of notes and a calculator. Please hand in the notes with your exam. 1. Mark the following statements True T or False
More informationRelating Storage Tank Stock Temperature to Meteorological Data
Relating Storage Tank Stock Temperature to Meteorological Data September 11, 2008 Prepared by: Robert L. Ferry J. Randolph Kissell The TGB Partnership Prepared for: American Petroleum Institute 1220 L
More informationBuilding Envelope Requirements Overview Page 3-4
Building Envelope Requirements Overview Page 3-4 The benefit of a high reflectance surface is obvious: while dark surfaces absorb the sun s energy (visible light, invisible infrared. and ultraviolet radiation)
More informationInside Wall Temperature Measurements of DSTs Using an Infrared Temperature Sensor
TEST PLAN Inside Wall Temperature Measurements of DSTs Using an Infrared Temperature Sensor Date submitted: December 18, 2015 Prepared by: Aparna Aravelli, Ph.D. Florida International University Collaborators:
More informationNusselt Correlations for Select Substation Bus. Presented by: Tony Pribble IEEE JTC Orange County, CA January, 2019
1 Nusselt Correlations for Select Substation Bus Presented by: Tony Pribble IEEE JTC Orange County, CA January, 2019 2 NEETRAC Overview Non-profit, 37 member industry consortium at Georgia Tech 37 Members
More information1 A 3 C 2 B 4 D. 5. During which month does the minimum duration of insolation occur in New York State? 1 February 3 September 2 July 4 December
INSOLATION REVIEW 1. The map below shows isolines of average daily insolation received in calories per square centimeter per minute at the Earth s surface. If identical solar collectors are placed at the
More informationPeltier Application Note
Peltier Application Note Early 19th century scientists, Thomas Seebeck and Jean Peltier, first discovered the phenomena that are the basis for today s thermoelectric industry. Seebeck found that if you
More informationSP-LITE SILICON PYRANOMETER INSTRUCTION MANUAL
SP-LITE SILICON PYRANOMETER INSTRUCTION MANUAL REVISION: 5/02 COPYRIGHT (c) 1998-2002 CAMPBELL SCIENTIFIC, INC. This is a blank page. Warranty and Assistance The SP-LITE SILICON PYRANOMETER is warranted
More informationME 476 Solar Energy UNIT THREE SOLAR RADIATION
ME 476 Solar Energy UNIT THREE SOLAR RADIATION Unit Outline 2 What is the sun? Radiation from the sun Factors affecting solar radiation Atmospheric effects Solar radiation intensity Air mass Seasonal variations
More informationInstallation Manual. Installation manual for PerfectEnergy Solar Modules. Content
Installation manual for PerfectEnergy Solar Modules Content 1. Preface 2. Technical data/general 3. Safety instructions 4. Mechanical Installation 5. Electrical installation 6. Grounding 7. Maintenance
More informationEFFECT OF WIND SPEED ON PERFORMANCE OF A SOLAR PV ARRAY
EFFECT OF WIND SPEED ON PERFORMANCE OF A SOLAR PV ARRAY Brian D. Vick USDA-Agricultural Research Service Conservation and Production Research Laboratory P.O. Drawer 1 Bushland, TX 7912 E-mail: brian.vick@ars.usda.gov
More informationWeathertightness testing of Solar Slate Plate to MCS012. Prepared for: Michael Share. Solar Slate Plate. 24 th June Test report number
Weathertightness testing of Solar Slate Plate to MCS012 Prepared for: Michael Share Solar Slate Plate 24 th June 2014 Prepared by Name Mr Devinder Athwal Position Laboratory technician, Building Technology
More informationCM3 PYRANOMETER INSTRUCTION MANUAL
CM3 PYRANOMETER INSTRUCTION MANUAL REVISION: 10/02 COPYRIGHT (c) 1999-2002 CAMPBELL SCIENTIFIC, INC. This is a blank page. WARRANTY AND ASSISTANCE This equipment is warranted by CAMPBELL SCIENTIFIC (CANADA)
More informationPERFORMANCE TEST REPORT. Rendered to: VELUX AMERICA, INC. PRODUCT: SUN TUNNEL Domes TYPES: Acrylic and Polycarbonate
PERFORMANCE TEST REPORT Rendered to: VELUX AMERICA, INC. PRODUCT: SUN TUNNEL Domes TYPES: Acrylic and Polycarbonate Report No.: E3490.01-106-31 Report Date: 07/13/15 Test Record Retention Date: 06/18/19
More informationIRTS-P PRECISION INFRARED TEMPERATURE SENSOR INSTRUCTION MANUAL
IRTS-P PRECISION INFRARED TEMPERATURE SENSOR INSTRUCTION MANUAL 4/02 COPYRIGHT (c) 2002 CAMPBELL SCIENTIFIC, INC., APOGEE INSTRUMENTS, INC. This is a blank page. Warranty and Assistance The IRTS-P PRECISION
More informationSHANGHAI MYLCH WINDOWS & DOORS THERMAL PERFORMANCE TEST REPORT
SHANGHAI MYLCH WINDOWS & DOORS THERMAL PERFORMANCE TEST REPORT SCOPE OF WORK DR65 FIXED REPORT NUMBER H3108.01-301-46 R0 TEST DATE 11/09/17 ISSUE DATE 11/14/17 RECORD RETENTION END DATE 11/09/22 PAGES
More informationBlocks and Holders POWR-BLOKS. Connectors. Ampere Ratings. Ordering Information. Applications. Specifications. Distribution/Splicer Blocks and Covers
Connectors Box lug connectors are designed for use with a single, solid or class B or C stranded conductor. Use of more than one conductor per connector opening or use of extra-flexible, fine stranded
More informationR E V I E W R E P O R T
Dr hab. inż. Dorota Chwieduk, prof. PW Politechnika Warszawska Warszawa, 30.05.2018 W y d z i a ł M e c h a n i c z n y E n e r g e t y k i i L o t n i c t w a I n s t y t u t T e c h n i k i C i e p l
More informationDesignation: NWI DIF Horizontal Hail impact Standard
Designation: NWI DIF Horizontal Hail impact Standard 2.1.2015 Standard Test Method for Materials attached to Vertical or Near Vertical Surfaces and Their Resistance to Horizontally Propelled Freezer Ice
More informationADVANCED ROOF COATINGS: MATERIALS AND THEIR APPLICATIONS
ADVANCED ROOF COATINGS: MATERIALS AND THEIR APPLICATIONS Abstract J.M. Bell 1 and G.B. Smith 2 The use of low emittance and high solar reflectance coatings is widespread in window glazings, wall and roof
More informationModel 3024 Albedometer. User s Manual 1165 NATIONAL DRIVE SACRAMENTO, CALIFORNIA WWW. ALLWEATHERINC. COM
Model 3024 Albedometer User s Manual 1165 NATIONAL DRIVE SACRAMENTO, CALIFORNIA 95834 WWW. ALLWEATHERINC. COM TABLE OF CONTENTS INTRODUCTION... 1 THEORY OF OPERATION... 2 General Description... 2 Accuracy...
More informationLP PYRA Installation and Mounting of the Pyranometer for the Measurement of Global Radiation:
CENTRO DI TARATURA SIT N 124 TEL. +39.049.8977150 r.a. FAX +39.049.635596 1 Introduction LP PYRA 03 The LP PYRA 03 pyranometer measures the irradiance on a plane surface (Watt/ m 2 ). Measured irradiance
More informationHIMARC Simulations Divergent Thinking, Convergent Engineering
HIMARC Simulations Divergent Thinking, Convergent Engineering 8117 W. Manchester Avenue, Suite 504 Los Angeles, CA 90293 Ph: (310) 657-7992 Horizontal Superconducting Magnet, ID 1.6m 1 1 Design definition
More informationEE Properties of Sunlight. Y. Baghzouz Professor of Electrical Engineering
EE 495-695 2.2 Properties of Sunlight Y. Baghzouz Professor of Electrical Engineering Azimuth angle The azimuth angle is the compass direction from which the sunlight is coming. At the equinoxes, the sun
More informationNABCEP Entry Level Exam Review Solfest practice test by Sean White
1. A fall protection system must be in place for all work done at heights in excess of a. 4 feet b. 6 feet c. 8 feet d. 10 feet 2. A circuit breaker performs the same function a. as a fuse b. as a switch
More informationStandard Practice for Heat Aging of Plastics Without Load 1
Designation: D 3045 92 (Reapproved 2003) Standard Practice for Heat Aging of Plastics Without Load 1 This standard is issued under the fixed designation D 3045; the number immediately following the designation
More informationInterview with Dr. Jaya Singh. 1. How critical is weather monitoring in a solar power plant and what are all the parameters to be monitored?
Interview with Dr. Jaya Singh Dr. Jaya Singh is an entrepreneur and scientist with experience in a range of industries including biotech, environmental sciences, and agriculture. She currently drives strategy
More informationAmplified Pyranometer SP-212 & 215
Amplified Pyranometer SP-212 & 215 Amplified Pyranometer Sensor This sensor is calibrated to measure total shortwave radiation. The evaporation of water from soil and the transpiration of water from plant
More informationCentralized Forecasting Registration and Communication Requirements for Distribution Connected Variable Generators. IESO Training
Centralized Forecasting Registration and Communication Requirements for Distribution Connected Variable Generators IESO Training May 2017 Centralized Forecasting - Registration and Communication Requirements
More informationReflectec Thermal Fabric & Reflectec Fiberboard
MODIFIED ASTM E 1354 CONE CALORIMETER THERMAL RESPONSE TEST (Final Report) TEST REPORT Reflectec Thermal Fabric & Reflectec Fiberboard Project No. 16723-113972 April 22, 2003 Prepared for: John W. Mallette
More informationA) usually less B) dark colored and rough D) light colored with a smooth surface A) transparency of the atmosphere D) rough, black surface
1. Base your answer to the following question on the diagram below which shows two identical houses, A and B, in a city in North Carolina. One house was built on the east side of a factory, and the other
More informationGlint and Glare Analysis
Oasis C7 CPV Tracker Glint and Glare Analysis Abstract. Assessment of potential hazards from glint and glare from concentrated solar installations is an important requirement for public safety. This paper
More informationCCMR Educational Programs
CCMR Educational Programs Title: Date Created: August 10, 2006 Latest Revision: August 10, 2006 Author(s): Myriam Ibarra Appropriate Level: Grades 8-10 Abstract: Energy and the Angle of Insolation Sun
More informationPERFORMANCE EVALUATION OF REFLECTIVE COATINGS ON ROOFTOP UNITS
PERFORMANCE EVALUATION OF REFLECTIVE COATINGS ON ROOFTOP UNITS Report on DRAFT Prepared for: California Energy Commission 1516 9th Street Sacramento, CA 95814 Prepared by: Design & Engineering Services
More informationDr. Michael Müller. Thermal Management for LED applications
Thermal Management for LED applications Content Thermal Design Basics thermal management Internal thermal management External thermal management 2 1967 founded with the production of insulation parts for
More informationIntegrated Circuits Thermal Test Method Environment Conditions - Natural Convection (Still Air)
EIA/JEDEC STANDARD Integrated Circuits Thermal Test Method Environment Conditions - Natural Convection (Still Air) EIA/JESD51-2 DECEMBER 1995 ELECTRONIC INDUSTRIES ASSOCIATION ENGINEERING DEPARTMENT NOTICE
More informationnot for commercial-scale installations. Thus, there is a need to study the effects of snow on
1. Problem Statement There is a great deal of uncertainty regarding the effects of snow depth on energy production from large-scale photovoltaic (PV) solar installations. The solar energy industry claims
More informationCoefficient of Friction Measurement On Polywater s Friction Table
American Polywater s A Publication for Engineers Involved in Cable Installations Coefficient of Friction Measurement On Polywater s Friction Table Polywater maintains a leadership position in cable pulling
More information東莞永力電業有限公司 YUNG LI CO., LTD REVISION RECORD YUNG LI. Customer : Parts No. : Draw No. : CY-U0003 TC02CCCCYY-95 CUSTOMER APPROVED
東莞永力電業有限公司 YUNG LI CO., LTD Da Pu Industrial Zone, Gang Zi, Changping Town, Dong Guan City, Guangdong 523571 China.P.R.C TEL:0769-3396797~8 E-mail: sales@yung-li.com FAX:0769-3396796 Description : YP-11/YC-13
More informationResearch Article Improving the Electrical Parameters of a Photovoltaic Panel by Means of an Induced or Forced Air Stream
International Photoenergy Volume 2, Article ID 83968, 1 pages http://dx.doi.org/1.15/2/83968 Research Article Improving the Electrical Parameters of a Photovoltaic Panel by Means of an Induced or Forced
More informationREPORT NUMBER: GZU-001 ORIGINAL ISSUE DATE:
REPORT NUMBER: 131119020GZU-001 ORIGINAL ISSUE DATE: 2013-12-12 EVALUATION CENTER TEST REPORT Intertek Testing Services Shenzhen Ltd. Guangzhou Branch Block E, No.7-2 Guang Dong Software Science Park,
More informationIntroduction to Photovoltaics
INTRODUCTION Objectives Understand the photovoltaic effect. Understand the properties of light. Describe frequency and wavelength. Understand the factors that determine available light energy. Use software
More informationThe Electrodynamics of a Pair of PV Modules with Connected Building Resistance
Proc. of the 3rd IASME/WSEAS Int. Conf. on Energy, Environment, Ecosystems and Sustainable Development, Agios Nikolaos, Greece, July 24-26, 2007 563 he Electrodynamics of a Pair of s with Connected Building
More informationM I N I S T R Y O F C O M M U N I C A T I O N S T E L E C O M M U N I C A T I O N S S E C T O R T E C H N I C A L S T A N D A R D F O R
M I N I S T R Y O F C O M M U N I C A T I O N S T E L E C O M M U N I C A T I O N S S E C T O R T E C H N I C A L S T A N D A R D F O R M A T E R I A L S N O. G 2 0 : 1 0 : 0 0 1 : 1 8 J U M P E R W I
More informationAssessment & Specifications for Noise Controls
Project 772600 Rev 1 Cargill North Vancouver Grain Terminal Assessment & Specifications for Noise Controls TABLE OF CONTENTS 1. INTRODUCTION...1 1.1 Background...1 1.2 Site Description...1 2. SOUND LEVEL
More informationA low-cost method for measuring solar irradiance using a lux meter
SHE Technical Report TR-17 A low-cost method for measuring solar irradiance using a lux meter Paul Arveson Director of Research, Solar Household Energy, Inc. March 29, 2017 Citation: Technical Report no.
More informationPOWER SYSTEM OPERATING PROCEDURE LOAD FORECASTING
POWER SYSTEM OPERATING PROCEDURE LOAD FORECASTING PREPARED BY: PROCEDURE TYPE: DOCUMENT REFERENCE: FINAL APPROVER: Systems Capability System Operating Procedure SO_OP_3710 Christian Schaefer DOC. VERSION:
More informationDepartment of Mechanical Engineering ME 96. Free and Forced Convection Experiment. Revised: 25 April Introduction
CALIFORNIA INSTITUTE OF TECHNOLOGY Department of Mechanical Engineering ME 96 Free and Forced Convection Experiment Revised: 25 April 1994 1. Introduction The term forced convection refers to heat transport
More informationThermal modelling of low concentrator photovoltaic systems
Thermal modelling of low concentrator photovoltaic systems JD Gerber MA Benecke FJ Vorster EE van Dyk Nelson Mandela Metropolitan University, Port Elizabeth Abstract Efficient thermal management of low
More informationBRE Client Report. Aging of light pipe materials (4000 hours artificial ageing) Prepared for: James McGowan Monodraught. BRE Watford, Herts WD25 9XX
BRE Client Report Aging of light pipe materials (4000 hours artificial ageing) Prepared for: James McGowan Date: 24 February 2015 Report Number: 298-109 Issue: 4 BRE Watford, Herts WD25 9XX Prepared for:
More informationFire Resistant Armoured Power Cable
Power and Wiring Cables Fire Resistant Armoured Power Cable 00/00V Application Armoured fire resistant cable for use in fixed wiring installations where it is necessary for the cable to retain circuit
More informationSIMPLE LOW CONCENTRATING MODULE DESIGN INCRESES SOLAR CELL OUTPUT 25%
SIMPLE LOW CONCENTRATING MODULE DESIGN INCRESES SOLAR CELL OUTPUT 25% Daniel Simon 3D Solar, Inc. 5555 N. Sheridan Rd. #1003 Chicago, IL 60640 e-mail: daniel@3dsolar.com ABSTRACT We present a simple low
More informationAM 500A 500 WATT AM 1A 1 KILOWATT AM BROADCAST TRANSMITTERS. October, 1999 IM No
AM 500A 500 WATT AM 1A 1 KILOWATT AM BROADCAST TRANSMITTERS October, 1999 IM No. 597 1112 EQUIPMENT LOST OR DAMAGED IN TRANSIT. When delivering the equipment to you, the truck driver or carrier s agent
More informationINSTRUCTION MANUAL. SP Lite2 Pyranometer. August Copyright 2017 Campbell Scientific (Canada) Corp.
INSTRUCTION MANUAL SP Lite2 Pyranometer August 2017 Copyright 2017 Campbell Scientific (Canada) Corp. WARRANTY AND ASSISTANCE This equipment is warranted by CAMPBELL SCIENTIFIC (CANADA) CORP. ("CSC")
More informationCHARACTERIZATION OF WIND VELOCITY DISTRIBUTIONS WITHIN A FULL-SCALE HELIOSTAT FIELD
CHARACTERIZATION OF WIND VELOCITY DISTRIBUTIONS WITHIN A FULL-SCALE HELIOSTAT FIELD Jeremy Sment and Clifford K. Ho Concentrating Solar Technologies Department Sandia National Laboratories P.O. Box 800,
More informationGHI CORRELATIONS WITH DHI AND DNI AND THE EFFECTS OF CLOUDINESS ON ONE-MINUTE DATA
GHI CORRELATIONS WITH DHI AND DNI AND THE EFFECTS OF CLOUDINESS ON ONE-MINUTE DATA Frank Vignola Department of Physics 1274 University of Oregon Eugene, OR 97403-1274 e-mail: fev@uoregon.edu ABSTRACT The
More informationAverage Weather For Coeur d'alene, Idaho, USA
Average Weather For Coeur d'alene, Idaho, USA Information courtesy of weatherspark.com Location This report describes the typical weather at the Coeur d'alene Air Terminal (Coeur d'alene, Idaho, United
More informationKinectrics North America Inc. Report No.: K RC-0001-R00 March 20, C.J. Pon, Z. Peter Transmission and Distribution Technologies Business
To: Colin McCullough 3M Company Bldg. 21-2-A-39 St. Paul, MN 144-1 USA KINECTRICS NORTH AMERICA INC. REPORT FOR 3M COMPANY TO TEST SHORT CIRCUIT BEHAVIOUR OF 79-T16 ACCR IN A TWO-CONDUCTOR BUNDLE CONFIGURATION
More informationANSI/SPRI ES-1 Test Reports UL Classified Products
Introduction to ES-1 The ANSI/SPRI ES-1 Roof Edge Standard is a reference for those who design, specify or install edge materials used with low slope roofs. This standard focuses primarily on design for
More informationEnergy and Insolation Review 2
Energy and Insolation Review 2 The diagram below shows a container of water that is being heated. 1. The movement of water shown by the arrows is most likely caused by (1) density differences (2) insolation
More informationON-LINE SOLAR RADIATION MONITORING SYSTEM, IN CLUJ NAPOCA, ROMANIA
ON-LINE SOLAR RADIATION MONITORING SYSTEM, IN CLUJ NAPOCA, ROMANIA Mugur BĂLAN, Lorentz JÄNTSCHI Introduction Sun can be considered a huge source of free energy, being also the unique energy source able
More informationElectrical installation solutions for buildings Technical details Arc Fault Detection Devices
/1 Electrical installation solutions for buildings Technical details Arc Fault Detection Devices Index Functions and classification criteria for AFDD /2 Power loss, derating and performance in altitude
More informationSolar Time, Angles, and Irradiance Calculator: User Manual
Solar Time, Angles, and Irradiance Calculator: User Manual Circular 674 Thomas Jenkins and Gabriel Bolivar-Mendoza 1 Cooperative Extension Service Engineering New Mexico Resource Network College of Agricultural,
More informationNFRC THERMAL TEST SUMMARY REPORT January 27, 1999 Test Specimen
* This is not the original copy of the test report if you would like an original copy, please contact our East Brunswick office or the NCTL to request a copy. ALL SEASONS DOOR & WINDOW, INC. REPORT NO:
More informationTechnical Notes. Introduction. PCB (printed circuit board) Design. Issue 1 January 2010
Technical Notes Introduction Thermal Management for LEDs Poor thermal management can lead to early LED product failure. This Technical Note discusses thermal management techniques and good system design.
More informationOverhead lines. 110 kv wood tower with guy wires
Overhead lines a) ja b) 0 kv wood poles c) free standing 0 kv metal tower with I-strings d) free standing 440 kv metal tower with V-strings e) 400 kv metal tower with guy wires 0 kv wood tower with guy
More informationNFRC SOLAR HEAT GAIN COEFFICIENT TEST REPORT. Rendered to: CLEAR FOCUS IMAGING
NFRC 201-2004 SOLAR HEAT GAIN COEFFICIENT TEST REPORT Rendered to: CLEAR FOCUS IMAGING SERIES/MODEL: SunSecure BASE WINDOW: 3/16" Clear Single Glazed PRODUCT TYPE: Window Film on the Interior of Clear
More informationSolar Flat Plate Thermal Collector
Solar Flat Plate Thermal Collector INTRODUCTION: Solar heater is one of the simplest and basic technologies in the solar energy field. Collector is the heart of any solar heating system. It absorbs and
More informationAverage Weather In March For Fukuoka, Japan
Average Weather In March For Fukuoka, Japan Location This report describes the typical weather at the Fukuoka Airport (Fukuoka, Japan) weather station over the course of an average March. It is based on
More informationELECTROMAGNETIC-ACOUSTIC TRANSDUCERS FOR IN-SERVICE MANUAL TESTING OF HEATED OBJECTS
17th World Conference on Nondestructive Testing, 25-28 Oct 2008, Shanghai, China ELECTROMAGNETIC-ACOUSTIC TRANSDUCERS FOR IN-SERVICE MANUAL TESTING OF HEATED OBJECTS Vladimir T. BOBROV, Andrey A. SAMOKRUTOV,
More informationVermont Soil Climate Analysis Network (SCAN) sites at Lye Brook and Mount Mansfield
Vermont Soil Climate Analysis Network (SCAN) sites at Lye Brook and Mount Mansfield 13 Years of Soil Temperature and Soil Moisture Data Collection September 2000 September 2013 Soil Climate Analysis Network
More informationDevelopment and Validation of Flat-Plate Collector Testing Procedures
Development and Validation of Flat-Plate Collector Testing Procedures Report for February, 2007 Focus on Energy (FOE) supports solar thermal systems that displace conventional fuels by offering cash-back
More information16 Appendix 16 Electrical Research Association Report
Guide to the Wiring Regulations 16 Appendix 16 Electrical Research Association Report (ERA) report on armoured cables with external CPCs The attached report was commissioned by the ECA and is copyright
More informationResistivity and Temperature Coefficients (at 20 C)
Homework # 4 Resistivity and Temperature Coefficients (at 0 C) Substance Resistivity, Temperature ( m) Coefficient, (C ) - Conductors Silver.59 x 0-0.006 Copper.6 x 0-0.006 Aluminum.65 x 0-0.0049 Tungsten
More informationNear Vertical Incidence Skywave (NVIS)
Near Vertical Incidence Skywave (NVIS) Larry Randall WA5BEN WA5BEN@ARRL.NET Revision: 1.4.5 Issue Date: 17 October 2007 Topics Terminology Why do we need NVIS Defining NVIS Relationship between Path Length
More informationSunlight and Temperature
Sunlight and Temperature Name Purpose: Study microclimate differences due to sunlight exposure, location, and surface; practice environmental measurements; study natural energy flows; compare measurements;
More informationPRODUCT CATALOG THERM-O-LINK, INC. / VULKOR, INC FREEDOM STREET PO BOX 285 GARRETTSVILLE, OHIO
PRODUCT CATALOG THERM-O-LINK, INC. / VULKOR, INC. 10513 FREEDOM STREET PO BOX 285 GARRETTSVILLE, OHIO 44231 Telephone: 330-527-2124 Fax: 330-527-2123 Email: sales@thermolink.com Web: www.tolwire.com 8
More informationCopyright , Larry Randall, d/b/a The NRE Group All Rights Reserved
NEAR VERTICAL INCIDENCE SKYWAVE (NVIS) Larry Randall -WA5BEN The NRE Group larry@nregroup.net Revision: 1.6 Issue Date: 06 Nov 2014 Copyright 2007 2015, Larry Randall, d/b/a The NRE Group All Rights Reserved
More informationPANDUCT Type E Slotted Wall Wiring Duct
PANDUCT Type E Slotted Wall Wiring Duct Type E Wiring Duct Standard Colors : LG DG WH Light Gray Dark Gray White BL Black IB IntrinsicBlue Colors shown are approximate. Ordering Information: Order number
More informationPHOTOVOLTAIC SOLAR ENERGY TRAINER DL SOLAR-D1 Manual
PHOTOVOLTAIC SOLAR ENERGY TRAINER DL SOLAR-D1 Manual DL SOLAR-D1 Contents 1. Solar energy: our commitment 5 to the environment 1.1. Basic principles and concepts 6 Mechanical work, energy and power: 6
More informationRenewable Energy Systems
Renewable Energy Systems 2 Buchla, Kissell, Floyd Chapter Outline Electrical Fundamentals 2 Buchla, Kissell, Floyd 2-1 ENERGY, CHARGE, AND VOLTAGE 2-2 ELECTRICAL CURRENT 2-3 RESISTANCE AND OHM'S LAW 2-4
More informationApplications. Remote Weather Station with Telephone Communications. Tripod Tower Weather Station with 4-20 ma Outputs
Tripod Tower Weather Station with 4-20 ma Outputs Remote Weather Station with Telephone Communications NEMA-4X Enclosure with Two Translator Boards and Analog Barometer Typical Analog Output Evaporation
More informationPeriodic Inspection and Testing of Electrical Installations Sample Test ( ) Version 1.3 July 2018
Periodic Inspection and Testing of Electrical Installations Sample Test (2391-051) Version 1.3 July 2018 Sample Questions Version and date Change detail Section 1.3 July 2018 Modified questions/answers
More informationWIND DATA REPORT. Lynn, MA
WIND DATA REPORT Lynn, MA September 2005 Prepared for Massachusetts Technology Collaborative 75 North Drive Westborough, MA 01581 by Kai Wu James F. Manwell Anthony L. Rogers Anthony F. Ellis February
More information