Impedance seen by Distance Relays on Lines Fed from Fixed Speed Wind Turbines

Size: px
Start display at page:

Download "Impedance seen by Distance Relays on Lines Fed from Fixed Speed Wind Turbines"

Transcription

1 Ipedance seen by Distance Relays on Lines Fed fro Fixed Speed Wind Turbines Sachin Srivastava, Abhinna Chandra Biswal, Sethuraan Ganesan Power Technologies, ABB Corporate Research Bangalore Abstract This paper deals with line protection challenges experienced in syste having substantial wind generation penetration. Two types of generations: Theral Synchronous Generators and Fixed Speed Wind Turbines based on Squirrel Cage Induction Generators (SCIG) are siulated as thevenin equivalent odel, connected to grid with single circuit transission line. The paper gives coparative discussion and suarizes analytical investigations carried out on the ipedance seen by distance relays by varying fault resistances and grid short circuit MVA, for the protection of such transission lines during faults. Keywords-Wind Generation, Distance Relays, Fault Resistance, Short Circuit MVA, DFIG, WTGU, SCIG ABBREVIATIONS Z BC BC loop ipedance Z AG AG loop ipedance R f Fault resistance Z SA Source ipedance at bus A Z gb Grid equivalent ipedance at bus B Z F General representation for fault loop ipedance K r Coplex factor for fault resitance K 0 Zero Sequence current copensation factor Fault point on line fro Bus A a Coplex nuber ( ) Z LL Load ipedance R +jx Transient ipedance of Induction achine P, Q Pre fault active and reactive power Vr, Ir Relay easured voltage and current V L, I L Load Voltage and current I 1, I 2, I 0 Positive, negative & zero sequence fault point current V F1, V F2, V F0 Positive, negative & zero sequence fault point voltage V A,V B, V C Phase ground voltage at relay point I A, I B, I C Line currents at relay location Ia 1, Ia 2, Ia 0 Positive, negative & zero sequence relay current at bus A V a1, V a2, V a0 Positive, negative & zero sequence relay voltage at bus A C 1, C 2,C 0 Positive, negative & zero sequence current distribution factor Z L1, Z L2,Z L0 Positive, negative & zero sequence line ipedance Z S1, Z S2, Z S0 Positive, negative & zero sequence source side ipedance Z g1, Z g2, Z g0 Positive, negative & zero sequence grid side ipedance W I. INTRODUION ITH the recent developent of technologies, environent concerns and continuously decreasing fossil fuels, wind generation is an inevitable solution and the power grids throughout the world are going with ore and ore wind penetration. For new forat of power transfer where power can be transferred bidirectional i.e. fro EHV to LV and fro LV to EHV, a proper review of the protection U.J.Shenoy Departent of Electrical Engineering, Indian Institute of Science Bangalore ujs@ee.iisc.ernet.in philosophy is needed. These wind generators are priarily squirrel cage induction generators (SCIG) and known as type- 1 wind generators due to their rugged perforance and low aintenance. They are used widely when there is relatively constant wind speed. Modern types of wind generators are doubly fed induction generators (DFIG) which use power electronic controllers to ake wound rotor induction achines (WRIM) work on unity power factor. Line protection at HV/EHV/UHV level is priarily provided with distance protection or ipedance protection due to rugged requireents of better security and dependability. Reference [3] describes that current contribution fro induction achines will be changed with the slip of the achine. Such a property is different fro the conventional synchronous achines, which aintain the constant voltage with the help of independent excitation and Autoatic Voltage Regulator (AVR) syste. Thus there is a need to investigate the effect of these SCIG currents on the ipedance seen by the distance relays with wind far connected to the grid. Reference [4] presents an investigation of trip characteristic of distance relay for phase to earth (Ph-G) fault with change in wind far loading levels and for different sall syste perturbations. The theoretical analysis of dynaic behavior of Wind Turbine Generating Units (WTGU) during three phase and asyetrical voltage dips is explained in [7, 8]. A study is done using DIGISILENT progra with anually applying the wavefors to a distance relay through secondary injection kit and the results are presented in the paper concludes that behavior of distance relay is not as desired [6]. A MATLAB SIMULINK based study for behavior of distance protection loops has been carried out and reported in [12]. This paper presents a Thevenin equivalent odel based analytical study to estiate theaforesaid effect on the ipedance seen by distance relays fed by fixed speed wind turbines. II. IMPEDANCE PRESENTED TO MEASUREMENT LOOP Ipedance easureent by the distance relay depends on the type of fault and the selection of the easureent loop. Siultaneous easureent in three phases to earth loops AG, BG, CG and three phase to phase loops AB, BC, CA is well 1

2 docuented in the literature [1,2] and reported in IEC and IEEE standards. For phase to phase fault (B-C fault) and for phase to earth fault (A-G), ipedance seen by the relay is given by expressions, Z BC = V B V C I B I C andz AG = V A I A +K 0 I 0 respectively where K 0 = (Z L0 Z L1 ) 3Z L1. Effect of fault resistance and pre fault load flow on loop ipedance been discussed in following sections. A. No Load Condition The effect of fault resistance in the easured loop ipedance (Z Fnl (loop ) ) is given by following equation as explained in Appendix A (for 3 different loops) Z Fnl(loop) = Z L1 + K r R F (1) The coplex factor K r is based on the current contribution factors fro each end as explained in the literature [1] K r = 1 C 1 Three phase fault case (2) K r = 1 (C 1 + C 2 ) Ph-Ph fault case (3) K r = 3 C " Ph-earth fault case (4) where, C " = C 1 + C 2 + C 0 Z L0 Z L1 (5) C 1, C 2, C 0 are the coplex current distribution factors of the fault current for positive, negative and zero sequence networks respectively as shown in Figure1.Thus coplex factor K r ake the fault resistance as inductive or capacitive ipedance and the distance relay ay over reach or under reach depending on the current contribution fro the reote end Infeed. Z s C1I1 Zs1 ZL1 C2I2 Zs2 ZL2 C0I0 Zs0 ZL0 Bus A I1 I2 I0 ZL Zg1 E1 (1-)ZL1 Zg2 (1-)ZL2 Zg0 Rf (1-)ZL0 Ph-Gnd fault F C1I1 Zs1 ZL1 (1-)ZL I1 C1I1 Zs1 ZL1 Zg1 Bus B E1 (1-)ZL1 I1 Rf Z g C2I2 Zs2 ZL2 Ph-Ph fault E1 Zg1 Grid I2 (1-)ZL1 3 Ph fault (1-) Figure1Positive negative and zero sequence circuits for Ph-G, Ph-Ph and 3 Ph faults [1] Rf Zg2 ZL2 The coplex current distribution factors depend on the sources at both the ends of the line. In wind generation systes, the source ipedance varies with the speed of the wind and the nuber of wind turbines contribution to the grid. B. Load Condition Distance relay voltage (V r ) and current(i r ) in ters of prefault load voltage (V L ) and load current (I L ) fro [1] can be written as V r = A z V L + B z I L I r = C z V L + D z I L (6) A Z,B Z,C Z,D Z are the coplex ipedance plane paraeters[1]. These paraeters are calculated for different fault loops and for different type of faults.fro (5), the ipedance seen by the relay can be given as Z r = A Z(Z LL + B Z AZ ) C Z (Z LL + D Z CZ ) Where,Z LL = V L I L (7) The A Z, B Z, C Z, D Z paraeters as entioned in [1], is obtained by superposition theore for different type of faults. Coprehensive Table (Table 1) for these paraeters is given for particular type of fault. Table 1: A Z, B Z, C Z, D Z PARAMETERS FOR DIFFERENT FAULT TYPE Loop A Z B Z C Z D Z paraeters 3 Ph- Z F Gnd A Z = Fault A-G B Z = Z LZ s loop 1 C Z = D Z = 1 Z L Ph-Ph Fault A Z = (a2 a)z F BC loop B Z = a2 a Z L Z s1 C Z = (a2 a) D Z = a 2 a (1 Z L ) Ph-Gnd Fault A Z = C" Z F AG loop B Z = Z L( C 2 Z s2 + C 0 Z s0 ) C Z = C D Z = ac" Z F C Z L + a(c 2 Z s2 + C 0 Z s0 ) where = C " Z F + C 1 + C 2 Z F + C 0 Z s0 andc = C 1 + C 0 Z L0 ZL1 Where Z F is Z Fnl (loop ) as given in (1) 2

3 III. SYSTEM MODELLING The above analysis of distance protection as explained in (1) and (4) is carried out for the following systes. A. Fixed Speed Wind Fars Syste odeled for study is shown in Figure 2. WTGU far of 10.5 MW installed capacity is odeled with fixed speed squirrel cage induction generators (SCIG). WTGU Far V th Z th 33kV 10MVA Bus A 33/132kV 25MVA Z A < 25 k 25 k F Z B < Bus B Z g G2 132 kv Grid Figure 2 WTGU far connected to 132 kv grid Note: Z A and Z B are the distance relays at two ends The data used for the syste of Fig 2 is as follows. Squirrel cage induction achine ( for 1 achine) P g = 1.5 MW ; V n = 0.4 kv ; R s = pu ; X s = pu ; R r = pu ; X r = pu ; X = pu; Q c = 670e3; s nl = ; (slip on wind speed < 8/s); s nl = 0.006; (slip on average wind speed = 12/s) 132kV Syste Data X T =0.12 pu ;Z L = 0.29 Ω/k with X R = 5 Z g = different SCMVA, at 132 kv with X/R = 8;Z L0 = 4Z L1 The far contains a cluster of induction achines of 1.5 MW. Each achine is connected in series with sall distribution transforer of 0.44/33kV, 2 MVA and a 33 kv cable of approxiate 1 k length as seen infigure 3. Fixed shunt copensation of 627 kvar at each achine is provided to reduce the reactive power absorption fro the grid. SCIG/ achines SCIG/ achines Reactive Copensation Reactive Copensation... x No. Of achines 0.44/33kV 2 MVA 0.44/33kV 2 MVA 1 k line 1 k line 33kV Bus W 33/132 kv 25 MVA Figure 3: Squirrel Cage Induction Generator Wind Far The WTGU far interconnecting transforer is studied for Delta Star grounded (DYn) connection.line is odeled as pi section with standard paraeter of X and R, at 132 kv level with X/R ratio considered as 8.Grid is odeled as ideal voltage source with series ipedance. Grid Ipedance is varied as per the Grid SCMVA capacity. Tests have been perfored for 3 types of Grids (229 MVA, 690 MVA and 2800 MVA having axiu 3 ph short circuit current of 1.0 ka, 3.0 ka and 12.0 ka at Grid bus B respectively). Different fault resistances are odeled as for different type of faults. Line to Ground fault has fault resistances fro 0 to 5 Ω, Line to line fault has been siulated till axiu arc fault resistances for particular grid SCMVA calculated by Warrington forulae (5 Ω for 229 MVA grid, 1 Ω for 700 MVA grid and 0.2 Ω for 2800 MVA). A.1 Thevenin Equivalent Model of single cage SCIG The thevenin Equivalent odel for Induction achine is taken fro reference [3], which states positive sequence ipedance for the achine is calculated at unity slip, while negative sequence equivalent ipedance is calculated at rated slip fro the following Fig. 4. The voltage behind the positive sequence ipedance (E ) at the instant of fault is calculated fro (8). E = V 1 + P jq V 1 (R + jx )(8) Since this voltage depends on load flow which in turn on the wind speed hence at different wind speeds different voltage need to be odeled for induction achine. This equivalent odel of each SCIG achine is used in Figure1. Sequence networks offigure1are used to analyze the apparent ipedance seen by distance relays Z A and Z B for all the types of faults. It is not necessary to consider zero sequence odel for Induction achine as the neutral of achine is norally isolated to liit the currents during internal faults. VthPos X1 R1 X X2 R2/s Positive sequence odel of Induction Generator VthNeg X1 R1 X X2 R2/(2-s) Negative sequence odel of Induction Generator Figure 4: Positive and negative sequence equivalent of SCIG B. Synchronous Machine A synchronous achine is odeled as Xs of 0.12 pu with constant voltage source of 1.0 pu in place of WTGU far of fig 2. A separate excitation syste controlled with AVR and other auxiliaries are assued to be in place, which help to aintain the constant voltage. Figure 5shows the syste considered for analysis. 3

4 Positive, negative and zero sequence paraeters are assued to be sae for generator, transforer and grid. Line will have sae ipedance for positive and negative sequence network but different zero sequence ipedance.siilar to wind far case thevenin equivalent odel analysis is perfored on the syste of Figure 5 using pre fault load flow conditions and apparent ipedance equations of Table 1. created at 50% of line (Z=7.25 Ω) for different fault resistances as entioned in syste odeling. SynchMachine Xs Bus A 25 k 25 k F Bus B Z g G2 V th 11kV 10MVA 11/132kV 25MVA Z A < Z B < 132 kv Grid Figure 5: Synchronous achine connected to 132kV grid IV. CASE STUDIES In Thevenin Equivalent Model (TEM) analysis the pre fault load flow is found taking agnitude of the Bus A and Bus B voltage as constant, 1.0 pu. Power flow angle is calculated for three loading conditions i) no load ii) 50% load iii) full rated load. Current flow is calculated fro Bus A to Bus B based on syste paraeters. Based on the equivalent odel as explained in Sec. III, current distribution factorsc 1,C 2 and C 0 paraeters are deterined for both sides distance relays. Coplex Resistance factor K r and distance relay load dependent constants A Z, B Z, C Z and D Z are deterined for different type of faults. The R-X diagra have been plotted to see the effect of different wind speeds (different load flow conditions) on the apparent ipedances seen by both sides relays. Figure 6Ph-Gnd fault WTGU far case(r f varied till 5 Ω) Figure 7Ph-PhWTGU Far case (R f varied till 1 Ω) A. Fixed Speed WTGU Far For a WTGU Far the variation in K r factor can be seen in following table 2Table 2 Grid SCMVA Table 2: KR FAOR FOR WTGU FARM CASE WITH SCIG MACHINE K r for Z A Relay Grid Side K r for Z B Relay WTGU side Angle of K r is approxiately near to zero in all the cases since the syste considered is hoogeneous with respect to X/R ratio.the plots in Figure 6,Figure 7 and Figure 8 show the effect of K r factor (Table 2) for 690 MVA case. The fault is Figure 83 Ph fault WTGU Far case (R f varied till 1 Ω) Observations: Grid side distance relay can see the correct ipedance in all the three fault types with inial effect of fault resistance. Wind far side distance relay can see the correct values of ipedances for bolted fault of all types. However, with higher resistances, a fault resistance of 5 Ω in Ph-G, the fault resistance appear as 15 Ω. Siilarly, for a fault 4

5 resistance of 1Ω in Ph-Ph and fault appear as 9 Ω and 19Ω respectively at high wind speed. B. Synchronous Machine Siilar to WTGU Far case the variation in K r factor for a synchronous achine case is tabled as follows.angle of K r is approxiately near to zero in all the cases since the syste is considered hoogeneous with respect to X/R ratio. The plots in Figure.9,Figure.10 and Figure.11 show the effect of K r factor (Table 3) for 690 MVA case. The fault is created at 50% of line ( Z =7.25 Ω) for different fault resistances as entioned in syste odeling. Grid SCMVA Table 3: KR FAOR FOR SYNCHRONOUS MACHINE CASE K r for Z A Relay K r for Z B Relay Grid Side WTGU side Figure.11 fault synchronous achine case (R f varied till 1 Ω) Observations: Grid side distance relay can see the correct ipedance in all the three fault types with inial effect of fault resistance. Wind far side distance relay can see the correct values of ipedances for bolted fault of all types. However, with higher resistances, a fault resistance of 5 Ω in Ph-G, fault appear as 14 Ω. Siilarly, for a fault resistance of 1Ω in Ph-Ph and fault appear as 6Ω and 13Ω respectively at rated load. V. DISCUSSION It is observedfro Figure 6 to Figure.11, that apparent ipedance seen by distance relays Z A are siilar in behavior. But the adverse effect of R f and infeed is worse in WTGU case. Based on the above study percentage (%) change in apparent ipedances can be studied by analyzing the effect on K r factor. The % change for K r factor for different grid SCMVA is entioned in Table 4 Figure.9 1Ph-G fault synchronous achinecase (R f varied till 5 Ω) Table 4: % CHANGE IN K r FAOR FOR WTGU AND SYNCHRONOUS MACHINE Grid % change in K r for % change in K r for SCMVA Z A Relay (Grid Side) Z B Relay (WTGU side) Figure.10Ph-Ph fault synchronous achine case(rf varied till 1 Ω) VI. CONCLUSIONS Based on the above observation, following conclusions can be derived fro the studies: i. Availability of zero sequence current for the relay in DYn connection of the I gives distance relay a better operating condition during Ph-G fault. Thus it is recoended to have DYn connection. ii. Distance protection will operate with high reliability and selectivity for solid phase to earth as well as ulti phase faults. 5

6 iii. For higher resistance Ph-G faults additional earth fault protections such as counication added directional earth fault schees, are recoended in addition to distance protection. iv. For high resistive ph-ph and 3ph faults transfer tripping schees are recoended to suppleent distance protection. APPENDIX A (APPARENTLOOPIMPEDANCE WITH FAULT RESISTANCE) With reference to sequence network of Figure1, V a1 =V F1 + C 1 I 1.Z L1 (9) V a2 =V F2 + C 2 I 2.Z L2 (10) V a0 =V F0 + C 0 I 0.Z L0 (11) Also I a1 = C 1 I 1, I a2 = C 2 I 2, I a0 = C 0 I 0 where V F1, V F2 andv F0 are the fault point voltage for positive and negative sequence networksand C 1, C 2, C 0 are distribution factors defined in [1] by current division theore, C 1 = Z g1 + (1 )Z L1 Z g1 + Z L1 + Z s1 C 2 = Z g2 + (1 )Z L2 Z g2 + Z L2 + Z s2 C 0 = Z g0 + (1 )Z L0 Z g0 + Z L0 + Z s0 (12) Phase to phase fault : For a B-C fault in syste of Figure 2, BC loop easureent will be given by Where, Z BC = V B V C I B I C (13) V B V C = a 2 a V a1 V a2 (14) and, I B I C = a 2 a I a1 I a2 Fro Figure1, in ph-ph fault case, V F1 = I 1 R f + V F2 ; I 1 = I 2 (15) Using equation (9),(10),(11),(12),(14),(15) ineq(13), Z BC = Z L + R f C 1 + C 2 (16) Three phase fault : For 3Ph fault in Figure 2and its equivalent sequence coponent network of Figure1, V F1 = I 1 R f ; I 2 = I 0 = 0 (17) Ph-Ph loops will see the ipedance as Z BC = Z L + R f C 1 (18) Ph-Gnd loops will see the ipedance as Z AG = Z L + R f C 1 (19) V F1 + V F2 + V F0 = 3I 1 R f ; I 2 = I 0 = I 1 (21) Z AG = V a1 + V a2 + V a0 I a1 + I a2 + K 0 I a0 (22) Using equations (9),(10),(11),(12),(20),(21) in (22), the A-G loop ipedance will be given by, Z AG = Z L + 3R f C (23) Where C = C 1 + C 2 + C 0 Z L0 REFERENCES [1] V. Cook, Analysis of distance protection, JohnWilley& sons, 1985, pp [2] Walter A Elore, Protective relaying Theory and Application. ABB, 2002, pp [3] Nasser Tleis, Power Systes Modeling and Fault Analysis Elsevier 2008, Ch 5, pp [4] A.K.Pradhan and GezaJoos, Adaptive Distance Relay settings for lines connecting wind fars IEEE transaction on energy conversion, vol 22, March [5] VahanGevorgian and Eduard Muljadi, Wind Power Plant Short-Circuit Current Contribution for Different Fault and Wind Turbine Topologies NREL Conference paper, October [6] S.Jaali et al, Robustness of Distance Relay with Quadrilateral Characteristic against Fault Resistance IEEE PES T&D Conference, China, [7] Jes usl opez,et al Dynaic Behavior of the Doubly Fed Induction Generator During Three-Phase Voltage Dips, IEEE Transactions on energy conversion, vol. 22, no. 3, pp 709 (sep 2007). [8] Jes usl opez,et al Wind Turbines Based on Doubly Fed Induction Generator Under Asyetrical Voltage Dips, IEEE Transactions on energy conversion, vol. 22, no. 3,pp 321 (arch 2008). [9] K.K.Li and L.L.Lai, Ideal operating region of digital distance relay under highresistance earth fault Electric Power Systes Research, 1997 [10] Diogo de Oliveira Fialho Pereira and Arturo SuanBretas, Extended Ground Distance Relaying With Fault Resistance Copensation Modern Electric Power Systes 2010, Wroclaw, Poland [11] Rodrigo HartsteinSali,Denise PivattoMarzecand Arturo SuanBretas, Phase Distance Relaying With Fault Resistance Copensation for Unbalanced Systes IEEE Transactions on power delivery, vol. 26, no. 2, April [12] SachinSrivastava,U.J.Shenoy, Abhinna Chandra Biswal and Sethuraan Ganesan, Effect of Fault Resistance And Grid Short Circuit MVA on Ipedance Seen by Distance Relays on Lines Fed Fro Wind Turbine GeneratingUnits (WTGU) IET-DPSP 2012, April Z L Single phase to ground fault For a AG fault in syste of Figure 2, A-G loop easureent will be given by, Z AG = V AG I A + K 0 I 0 (20) And fro sequence coponent network of Figure1, 6

BEF BEF Chapter 2. Outline BASIC PRINCIPLES 09/10/2013. Introduction. Phasor Representation. Complex Power Triangle.

BEF BEF Chapter 2. Outline BASIC PRINCIPLES 09/10/2013. Introduction. Phasor Representation. Complex Power Triangle. BEF 5503 BEF 5503 Chapter BASC PRNCPLES Outline 1 3 4 5 6 7 8 9 ntroduction Phasor Representation Coplex Power Triangle Power Factor Coplex Power in AC Single Phase Circuits Coplex Power in Balanced Three-Phase

More information

ELG3311: Assignment 3

ELG3311: Assignment 3 LG33: ssignent 3 roble 6-: The Y-connected synchronous otor whose naeplate is shown in Figure 6- has a perunit synchronous reactance of 0.9 and a per-unit resistance of 0.0. (a What is the rated input

More information

Chapter 10 Objectives

Chapter 10 Objectives Chapter 10 Engr8 Circuit Analysis Dr Curtis Nelson Chapter 10 Objectives Understand the following AC power concepts: Instantaneous power; Average power; Root Mean Squared (RMS) value; Reactive power; Coplex

More information

Study Committee B5 Colloquium 2005 September Calgary, CANADA

Study Committee B5 Colloquium 2005 September Calgary, CANADA 36 Study oittee B olloquiu Septeber 4-6 algary, ND ero Sequence urrent opensation for Distance Protection applied to Series opensated Parallel Lines TKHRO KSE* PHL G BEUMONT Toshiba nternational (Europe

More information

Research on Capacitance Current Compensation Scheme of Current Differential Protection of Complex Four-Circuit Transmission Lines on the Same Tower

Research on Capacitance Current Compensation Scheme of Current Differential Protection of Complex Four-Circuit Transmission Lines on the Same Tower energies Article Research on apacitance urrent opensation Schee of urrent Differential Protection of oplex Four-ircuit Transission Lines on the Sae Tower ui Tang 1,2, * ID, Xianggen Yin 1,2 and Zhe Zhang

More information

THE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session

THE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session Name: Student ID: Signature: THE UNIVERSITY OF NEW SOUTH WALES School of Electrical Engineering & Telecommunications FINALEXAMINATION Session 00 ELEC46 Power System Analysis TIME ALLOWED: 3 hours TOTAL

More information

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL 1 SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL Power Systems: Generation, Transmission and Distribution Power Systems: Generation, Transmission and Distribution Power Systems:

More information

Simulation and Analysis of Electromagnetic Transient Characteristics of Controllable Reactor of Transformer Type

Simulation and Analysis of Electromagnetic Transient Characteristics of Controllable Reactor of Transformer Type Siulation and Analysis of Electroagnetic Transient Characteristics of Controllable eactor of Transforer Type TIAN MINGXING, ZHAO QIANU, YIN JIANNING, LIU YIBIN Autoation and Electrical Engineering Lanzhou

More information

Incorporation of Asynchronous Generators as PQ Model in Load Flow Analysis for Power Systems with Wind Generation

Incorporation of Asynchronous Generators as PQ Model in Load Flow Analysis for Power Systems with Wind Generation Incorporation of Asynchronous Generators as PQ Model in Load Flow Analysis for Power Systems with Wind Generation James Ranjith Kumar. R, Member, IEEE, Amit Jain, Member, IEEE, Power Systems Division,

More information

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester Electrical and Electronics Engineering EE 1352 Power System Analysis (Regulation 2008) Time: Three hours Answer all questions Part A (10

More information

Module 3 : Sequence Components and Fault Analysis

Module 3 : Sequence Components and Fault Analysis Module 3 : Sequence Components and Fault Analysis Lecture 12 : Sequence Modeling of Power Apparatus Objectives In this lecture we will discuss Per unit calculation and its advantages. Modeling aspects

More information

Design of Sliding Mode Stabilizer for Wind Turbine Generator using Dynamic Compensation Observer Technique

Design of Sliding Mode Stabilizer for Wind Turbine Generator using Dynamic Compensation Observer Technique Proceedings of the 6th WSES International Conference on Power Systes, Lisbon, Portugal, Septeber -4, 6 84 Design of Sliding Mode Stabilizer for Wind urbine Generator using Dynaic Copensation Observer echnique

More information

Chapter 10 ACSS Power

Chapter 10 ACSS Power Objectives: Power concepts: instantaneous power, average power, reactive power, coplex power, power factor Relationships aong power concepts the power triangle Balancing power in AC circuits Condition

More information

EE5900 Spring Lecture 4 IC interconnect modeling methods Zhuo Feng

EE5900 Spring Lecture 4 IC interconnect modeling methods Zhuo Feng EE59 Spring Parallel LSI AD Algoriths Lecture I interconnect odeling ethods Zhuo Feng. Z. Feng MTU EE59 So far we ve considered only tie doain analyses We ll soon see that it is soeties preferable to odel

More information

A Simplified Analytical Approach for Efficiency Evaluation of the Weaving Machines with Automatic Filling Repair

A Simplified Analytical Approach for Efficiency Evaluation of the Weaving Machines with Automatic Filling Repair Proceedings of the 6th SEAS International Conference on Siulation, Modelling and Optiization, Lisbon, Portugal, Septeber -4, 006 0 A Siplified Analytical Approach for Efficiency Evaluation of the eaving

More information

ECE 325 Electric Energy System Components 7- Synchronous Machines. Instructor: Kai Sun Fall 2015

ECE 325 Electric Energy System Components 7- Synchronous Machines. Instructor: Kai Sun Fall 2015 ECE 325 Electric Energy System Components 7- Synchronous Machines Instructor: Kai Sun Fall 2015 1 Content (Materials are from Chapters 16-17) Synchronous Generators Synchronous Motors 2 Synchronous Generators

More information

Electric Power System Transient Stability Analysis Methods

Electric Power System Transient Stability Analysis Methods 1 Electric Power Syste Transient Stability Analysis Methods João Pedro de Carvalho Mateus, IST Abstract In this paper are presented the state of the art of Electric Power Syste transient stability analysis

More information

Sensorless Control of Induction Motor Drive Using SVPWM - MRAS Speed Observer

Sensorless Control of Induction Motor Drive Using SVPWM - MRAS Speed Observer Journal of Eerging Trends in Engineering and Applied Sciences (JETEAS) 2 (3): 509-513 Journal Scholarlink of Eerging Research Trends Institute in Engineering Journals, 2011 and Applied (ISSN: 2141-7016)

More information

Transient Stability Improvement of IEEE 9 Bus System Using Power World Simulator

Transient Stability Improvement of IEEE 9 Bus System Using Power World Simulator Transient Stability Iproveent of IEEE 9 Bus Syste Using Power World Siulator Raandeep Kaur 1, Divesh Kuar 2 1,2 Departent of Electrical Engineering, Bhai Gurdas Institue of Engineering and Technology,

More information

Power Systems Oscillations Damping with Regard the Finite Speed of Propagation the Electromechanical Waves

Power Systems Oscillations Damping with Regard the Finite Speed of Propagation the Electromechanical Waves International Journal of Energy and Power Engineering 15; 4(): 71-83 Published online March 14, 15 (http://www.sciencepublishinggroup.co/j/ijepe) doi: 1.11648/j.ijepe.154.18 ISSN: 36-957X (Print); ISSN:

More information

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION EE 6501 POWER SYSTEMS UNIT I INTRODUCTION PART A (2 MARKS) 1. What is single line diagram? A Single line diagram is diagrammatic representation of power system in which the components are represented by

More information

Eigenvalue Analysis of Subsynchronous Resonance Study in Series Compensated Wind Farm

Eigenvalue Analysis of Subsynchronous Resonance Study in Series Compensated Wind Farm e-issn: 2349-9745 p-issn: 2393-8161 Scientific Journal Impact Factor (SJIF): 1.711 International Journal of Modern Trends in Engineering and Research www.ijmter.com Eigenvalue Analysis of Subsynchronous

More information

Fault Calculation Methods

Fault Calculation Methods ELEC9713 Industrial and Commercial Power Systems Fault Calculation Methods There are two major problems that can occur in electrical systems: these are open circuits and short circuits. Of the two, the

More information

EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION

EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION PART: A 1. Define per unit value of an electrical quantity. Write equation for base impedance with respect to 3-phase system. 2. What is bus admittance

More information

KINGS COLLEGE OF ENGINEERING Punalkulam

KINGS COLLEGE OF ENGINEERING Punalkulam KINGS COLLEGE OF ENGINEERING Punalkulam 613 303 DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING POWER SYSTEM ANALYSIS QUESTION BANK UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A (TWO MARK

More information

UNCERTAINTIES IN THE APPLICATION OF ATMOSPHERIC AND ALTITUDE CORRECTIONS AS RECOMMENDED IN IEC STANDARDS

UNCERTAINTIES IN THE APPLICATION OF ATMOSPHERIC AND ALTITUDE CORRECTIONS AS RECOMMENDED IN IEC STANDARDS Paper Published on the16th International Syposiu on High Voltage Engineering, Cape Town, South Africa, 2009 UNCERTAINTIES IN THE APPLICATION OF ATMOSPHERIC AND ALTITUDE CORRECTIONS AS RECOMMENDED IN IEC

More information

DIRECT TORQUE CONTROL OF INDUCTION MACHINES CONSIDERING THE IRON LOSSES

DIRECT TORQUE CONTROL OF INDUCTION MACHINES CONSIDERING THE IRON LOSSES DIRECT TORQUE CONTROL OF INDUCTION MACHINES CONSIDERING THE IRON LOSSES TRUC PHAM-DINH A thesis subitted in partial fulfilent of the requireents of Liverpool John Moores University for the degree of Doctor

More information

Busbar Protection Scheme Based on Alienation Coefficients for Current Signals

Busbar Protection Scheme Based on Alienation Coefficients for Current Signals International Journal of Engineering and Advanced Technology IJEAT ISSN: 49 898, Volue-3, Issue-4, April 4 Busbar Protection Schee Based on Alienation Coefficients for Current Signals R. Abd Allah Abstract

More information

Chapter 8: Unsymmetrical Faults

Chapter 8: Unsymmetrical Faults Chapter 8: Unsymmetrical Faults Introduction The sequence circuits and the sequence networks developed in the previous chapter will now be used for finding out fault current during unsymmetrical faults.

More information

LONGER TERM STABILISATION OF WIND POWER PLANT VOLTAGE/REACTIVE POWER FLUCTUATIONS BY FACTS SOLUTION

LONGER TERM STABILISATION OF WIND POWER PLANT VOLTAGE/REACTIVE POWER FLUCTUATIONS BY FACTS SOLUTION LONGER TERM TABILIATION OF WIND POWER PLANT VOLTAGE/REACTIVE POWER FLUCTUATION BY FACT OLUTION NIJAZ DIZDAREVIĆ, MATILAV MAJTROVIĆ Energy Institute HRVOJE POŽAR avska 63, HR- Zagreb Croatia www.eihp.hr/~ndizdar

More information

Modeling of Photovoltaic System in the Large Ocean-going Ship Based on Simulink

Modeling of Photovoltaic System in the Large Ocean-going Ship Based on Simulink 2016 International Conference on Materials, Inforation, Mechanical, Electronic and Coputer Engineering (MIMECE 2016) IBN: 978-1-60595-420-2 Modeling of Photovoltaic yste in the Large Ocean-going hip Based

More information

Effects of the Controller Performance of DFIG on its Inertia Response

Effects of the Controller Performance of DFIG on its Inertia Response Global Journal of Research in Engineering Volume 11 Issue 3 Version 1.0 April 011 Type: Double Blind Peer Reviewed International Research Journal Publisher: Global Journals Inc. (USA) ISSN: 0975-5861 Effects

More information

Power Quality Analysis Including Dips and Swells

Power Quality Analysis Including Dips and Swells International Journal of Electrical Engineering. ISSN 0974-158 Volue 4, Nuber 6 (011), pp. 697-709 International Research Publication House http://www.irphouse.co Power Quality Analysis Including Dips

More information

Control of Wind Turbine Generators. James Cale Guest Lecturer EE 566, Fall Semester 2014 Colorado State University

Control of Wind Turbine Generators. James Cale Guest Lecturer EE 566, Fall Semester 2014 Colorado State University Control of Wind Turbine Generators James Cale Guest Lecturer EE 566, Fall Semester 2014 Colorado State University Review from Day 1 Review Last time, we started with basic concepts from physics such as

More information

Design of 25 KA Current Injection Transformer Core with Finite Element Method

Design of 25 KA Current Injection Transformer Core with Finite Element Method 1 Design of 5 KA Current Injection Transforer Core ith Finite Eleent Method HOSSEIN HEYDARI, MOHSEN ARIANNEJAD, FARAMARZ FAGHIHI Iran University of Science and Technology, Tehran, Iran Abstract.Since Current

More information

About the definition of parameters and regimes of active two-port networks with variable loads on the basis of projective geometry

About the definition of parameters and regimes of active two-port networks with variable loads on the basis of projective geometry About the definition of paraeters and regies of active two-port networks with variable loads on the basis of projective geoetry PENN ALEXANDR nstitute of Electronic Engineering and Nanotechnologies "D

More information

Mitigation of Distributed Generation Impact on Protective Devices in a Distribution Network by Superconducting Fault Current Limiter *

Mitigation of Distributed Generation Impact on Protective Devices in a Distribution Network by Superconducting Fault Current Limiter * Energy and Power Engineering, 2013, 5, 258-263 doi:10.4236/epe.2013.54b050 Published Online July 2013 (http://www.scirp.org/journal/epe) Mitigation of Distributed Generation Impact on Protective Devices

More information

Analysis on the Effect of the Nonlinear Resistance on the Locomotive Operating Overvoltages

Analysis on the Effect of the Nonlinear Resistance on the Locomotive Operating Overvoltages Energy and Power Engineering, 3, 5, 43-48 doi:.436/epe.3.54b36 Published Online July 3 (http://www.scirp.org/journal/epe) Analysis on the Effect of the Nonlinear Resistance on the Locootive Operating Overvoltages

More information

Lecture 2 Introduction

Lecture 2 Introduction EE 333 POWER SYSTEMS ENGNEERNG Lecture 2 ntroduction Dr. Lei Wu Departent of Electrical and Coputer Engineering Clarkson University Resilient Underground Microgrid in Potsda, NY Funded by NYSERDAR + National

More information

Mutual capacitor and its applications

Mutual capacitor and its applications Mutual capacitor and its applications Chun Li, Jason Li, Jieing Li CALSON Technologies, Toronto, Canada E-ail: calandli@yahoo.ca Published in The Journal of Engineering; Received on 27th October 2013;

More information

On Constant Power Water-filling

On Constant Power Water-filling On Constant Power Water-filling Wei Yu and John M. Cioffi Electrical Engineering Departent Stanford University, Stanford, CA94305, U.S.A. eails: {weiyu,cioffi}@stanford.edu Abstract This paper derives

More information

IDAN Shock Mount Isolation Vibration Study November 1, The operation of shock and vibration isolation base plate

IDAN Shock Mount Isolation Vibration Study November 1, The operation of shock and vibration isolation base plate dr. Istvan Koller RTD USA BME Laboratory. Background In 998, Real Tie Devices USA, Inc. introduced a novel packaging concept for ebedded PC/04 odules to build Intelligent Data Acquisition Nodes. This syste,

More information

MSEC MODELING OF DEGRADATION PROCESSES TO OBTAIN AN OPTIMAL SOLUTION FOR MAINTENANCE AND PERFORMANCE

MSEC MODELING OF DEGRADATION PROCESSES TO OBTAIN AN OPTIMAL SOLUTION FOR MAINTENANCE AND PERFORMANCE Proceeding of the ASME 9 International Manufacturing Science and Engineering Conference MSEC9 October 4-7, 9, West Lafayette, Indiana, USA MSEC9-8466 MODELING OF DEGRADATION PROCESSES TO OBTAIN AN OPTIMAL

More information

Intelligent Systems: Reasoning and Recognition. Perceptrons and Support Vector Machines

Intelligent Systems: Reasoning and Recognition. Perceptrons and Support Vector Machines Intelligent Systes: Reasoning and Recognition Jaes L. Crowley osig 1 Winter Seester 2018 Lesson 6 27 February 2018 Outline Perceptrons and Support Vector achines Notation...2 Linear odels...3 Lines, Planes

More information

Adaptive Controller Design for a Synchronous Generator with Unknown Perturbation in Mechanical Power

Adaptive Controller Design for a Synchronous Generator with Unknown Perturbation in Mechanical Power 308 International Journal of Control Xiaohong Autoation Jiao Yuanzhang and Systes Sun vol and 3 Tielong no (special Shen edition) pp 308-34 June 005 Adaptive Controller Design for a Synchronous Generator

More information

Symmetrical Components. References

Symmetrical Components. References Symmetrical Components Review of basics Sequence Equivalents Fault Analysis Symmetrical Components Fall 28 References Your power systems analysis class text book NPAG: Chapter 4 (analysis) Chapter 5 (equipment

More information

SPECTRUM sensing is a core concept of cognitive radio

SPECTRUM sensing is a core concept of cognitive radio World Acadey of Science, Engineering and Technology International Journal of Electronics and Counication Engineering Vol:6, o:2, 202 Efficient Detection Using Sequential Probability Ratio Test in Mobile

More information

SHORT QUESTIONS AND ANSWERS. Year/ Semester/ Class : III/ V/ EEE Academic Year: Subject Code/ Name: EE6501/ Power System Analysis

SHORT QUESTIONS AND ANSWERS. Year/ Semester/ Class : III/ V/ EEE Academic Year: Subject Code/ Name: EE6501/ Power System Analysis Srividya colllege of Engg & Tech,Virudhunagar Sri Vidya College of Engineering And Technology Virudhunagar 626 005 Department of Electrical and Electronics Engineering QUESTION BANK SHORT QUESTIONS AND

More information

EG2040 Wind Power Systems Assignment 2 - Grid Integration of Wind Power Systems

EG2040 Wind Power Systems Assignment 2 - Grid Integration of Wind Power Systems EG2040 Wind Power Systems Assignment 2 - Grid Integration of Wind Power Systems Problem formulation We consider the system in Figure 1, and want to determine what the maximum capacity of the wind farm

More information

WIRELESS DRIVE OF PIEZOELECTRIC COMPONENTS SATYANARAYAN BHUYAN 2011

WIRELESS DRIVE OF PIEZOELECTRIC COMPONENTS SATYANARAYAN BHUYAN 2011 WIRELESS DRIVE OF PIEZOELECTRIC COMPONENTS SATYANARAYAN BHUYAN 011 WIRELESS DRIVE OF PIEZOELECTRIC COMPONENTS SATYANARAYAN BHUYAN SCHOOL OF ELECTRICAL & ELECTRONIC ENGINEERING 011 SATYANARAYAN BHUYAN WIRELESS

More information

Steady State Performance of Doubly Fed Induction Generator Used in Wind Power Generation

Steady State Performance of Doubly Fed Induction Generator Used in Wind Power Generation Steady State Performance of Doubly Fed Induction Generator Used in Wind Power Generation Indubhushan Kumar Mewar University Department of Electrical Engineering Chittorgarh, Rajasthan-312902 Abstract:

More information

Chapter 10: Sinusoidal Steady-State Analysis

Chapter 10: Sinusoidal Steady-State Analysis Chapter 0: Sinusoidal Steady-State Analysis Sinusoidal Sources If a circuit is driven by a sinusoidal source, after 5 tie constants, the circuit reaches a steady-state (reeber the RC lab with t = τ). Consequently,

More information

An Approach of Converter Transformer Condition Evaluation Based on The Belief Rule Base Inference Methodology and Evidence Reasoning

An Approach of Converter Transformer Condition Evaluation Based on The Belief Rule Base Inference Methodology and Evidence Reasoning International Conference on Civil, Transportation and Environent (ICCTE 206) An Approach of Converter Transforer Condition Evaluation Based on The Belief Rule Base Inference Methodology and Evidence Reasoning

More information

An Approximate Model for the Theoretical Prediction of the Velocity Increase in the Intermediate Ballistics Period

An Approximate Model for the Theoretical Prediction of the Velocity Increase in the Intermediate Ballistics Period An Approxiate Model for the Theoretical Prediction of the Velocity... 77 Central European Journal of Energetic Materials, 205, 2(), 77-88 ISSN 2353-843 An Approxiate Model for the Theoretical Prediction

More information

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A 1. What are the advantages of an inter connected system? The advantages of an inter-connected system are

More information

Torsion Experiment. Encoder #3 ( 3 ) Third encoder/disk for Model 205a only. Figure 1: ECP Torsion Experiment

Torsion Experiment. Encoder #3 ( 3 ) Third encoder/disk for Model 205a only. Figure 1: ECP Torsion Experiment Torsion Experient Introduction For the Torsion lab, there are two required experients to perfor and one extra credit assignent at the end. In experient 1, the syste paraeters need to be identified so that

More information

Chapter 3 AUTOMATIC VOLTAGE CONTROL

Chapter 3 AUTOMATIC VOLTAGE CONTROL Chapter 3 AUTOMATIC VOLTAGE CONTROL . INTRODUCTION TO EXCITATION SYSTEM The basic function of an excitation system is to provide direct current to the field winding of the synchronous generator. The excitation

More information

RESULTS OF ON-GRID OPERATION OF SUPERCONDUCTOR DYNAMIC SYNCHRONOUS CONDENSER

RESULTS OF ON-GRID OPERATION OF SUPERCONDUCTOR DYNAMIC SYNCHRONOUS CONDENSER 1 RESULTS OF ON-GRID OPERATION OF SUPERCONDUCTOR DYNAMIC SYNCHRONOUS CONDENSER Dr. Swarn S. Kalsi, David Madura, and Michael Ross American Superconductor Corporation (USA) Abstract: A high-temperature

More information

Electromagnetic fields modeling of power line communication (PLC)

Electromagnetic fields modeling of power line communication (PLC) Electroagnetic fields odeling of power line counication (PLC) Wei Weiqi UROP 3 School of Electrical and Electronic Engineering Nanyang echnological University E-ail: 4794486@ntu.edu.sg Keyword: power line

More information

Comparative Analysis of an integration of a Wind Energy Conversion System of PMSG and DFIG Models Connected to Power Grid

Comparative Analysis of an integration of a Wind Energy Conversion System of PMSG and DFIG Models Connected to Power Grid International Journal of Electrical Engineering. ISSN 0974-2158 Volume 6, Number 3 (2013), pp. 231-248 International Research Publication House http://www.irphouse.com Comparative Analysis of an integration

More information

th Annual IEEE Power Electronics Specialists Conference Aachen, Germany, Parallel Connection of Piezoelectric Transformers

th Annual IEEE Power Electronics Specialists Conference Aachen, Germany, Parallel Connection of Piezoelectric Transformers 004 35th Annual IEEE ower Electronics Specialists Conference Aachen, Gerany, 004 arallel Connection of iezoelectric Transforers Svetlana Bronstein, Gregory Ivensky and Sa Ben-Yaakov* ower Electronics Laboratory

More information

Optimal Placement & sizing of Distributed Generator (DG)

Optimal Placement & sizing of Distributed Generator (DG) Chapter - 5 Optimal Placement & sizing of Distributed Generator (DG) - A Single Objective Approach CHAPTER - 5 Distributed Generation (DG) for Power Loss Minimization 5. Introduction Distributed generators

More information

TRANSIENT ANALYSIS OF SELF-EXCITED INDUCTION GENERATOR UNDER BALANCED AND UNBALANCED OPERATING CONDITIONS

TRANSIENT ANALYSIS OF SELF-EXCITED INDUCTION GENERATOR UNDER BALANCED AND UNBALANCED OPERATING CONDITIONS TRANSIENT ANALYSIS OF SELF-EXCITED INDUCTION GENERATOR UNDER BALANCED AND UNBALANCED OPERATING CONDITIONS G. HARI BABU Assistant Professor Department of EEE Gitam(Deemed to be University), Visakhapatnam

More information

Impact of Photovoltaic Generation On The Power System Stability

Impact of Photovoltaic Generation On The Power System Stability Impact of Photovoltaic Generation On The Power System Stability Eng. Abdelmoezz Ahmed Eid Dept. of Electrical Engineering Al-Azhar University Cairo, Egypt engabdelmoezz@gmail.com Dr. Tarek Mahmoud Dept.

More information

ELG4125: Power Transmission Lines Steady State Operation

ELG4125: Power Transmission Lines Steady State Operation ELG4125: Power Transmission Lines Steady State Operation Two-Port Networks and ABCD Models A transmission line can be represented by a two-port network, that is a network that can be isolated from the

More information

ECE 585 Power System Stability

ECE 585 Power System Stability Homework 1, Due on January 29 ECE 585 Power System Stability Consider the power system below. The network frequency is 60 Hz. At the pre-fault steady state (a) the power generated by the machine is 400

More information

LO 1: Three Phase Circuits

LO 1: Three Phase Circuits Course: EEL 2043 Principles of Electric Machines Class Instructor: Dr. Haris M. Khalid Email: hkhalid@hct.ac.ae Webpage: www.harismkhalid.com LO 1: Three Phase Circuits Three Phase AC System Three phase

More information

In this chapter, we consider several graph-theoretic and probabilistic models

In this chapter, we consider several graph-theoretic and probabilistic models THREE ONE GRAPH-THEORETIC AND STATISTICAL MODELS 3.1 INTRODUCTION In this chapter, we consider several graph-theoretic and probabilistic odels for a social network, which we do under different assuptions

More information

Dynamic simulation of a five-bus system

Dynamic simulation of a five-bus system ELEC0047 - Power system dynamics, control and stability Dynamic simulation of a five-bus system Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct November 2017 1 / 16 System modelling

More information

Transient Analysis of Doubly Fed Wind Power Induction Generator Using Coupled Field-Circuit Model

Transient Analysis of Doubly Fed Wind Power Induction Generator Using Coupled Field-Circuit Model Publication P2 Seman, S., Kanerva, S., Niiranen, J., Arkkio, A. 24. Transient Analysis of Wind Power Doubly Fed Induction Generator Using Coupled Field Circuit Model, Proceedings of ICEM 24, 5-8 September

More information

University of Jordan Faculty of Engineering & Technology Electric Power Engineering Department

University of Jordan Faculty of Engineering & Technology Electric Power Engineering Department University of Jordan Faculty of Engineering & Technology Electric Power Engineering Department EE471: Electrical Machines-II Tutorial # 2: 3-ph Induction Motor/Generator Question #1 A 100 hp, 60-Hz, three-phase

More information

Harmonic Modeling of Networks

Harmonic Modeling of Networks Harmonic Modeling of Networks Thomas H. Ortmeyer ECE Dept. Clarkson University Potsdam, NY 13699-5720 M. Fayyaz Akram Dept. of Elec. Eng. Univ. of Engineering and Technology Lahore, Pakistan Takashi Hiyama

More information

Now multiply the left-hand-side by ω and the right-hand side by dδ/dt (recall ω= dδ/dt) to get:

Now multiply the left-hand-side by ω and the right-hand side by dδ/dt (recall ω= dδ/dt) to get: Equal Area Criterion.0 Developent of equal area criterion As in previous notes, all powers are in per-unit. I want to show you the equal area criterion a little differently than the book does it. Let s

More information

ECEN 460 Exam 1 Fall 2018

ECEN 460 Exam 1 Fall 2018 ECEN 460 Exam 1 Fall 2018 Name: KEY UIN: Section: Score: Part 1 / 40 Part 2 / 0 Part / 0 Total / 100 This exam is 75 minutes, closed-book, closed-notes. A standard calculator and one 8.5 x11 note sheet

More information

Filtering and Fusion based Reconstruction of Angle of Attack

Filtering and Fusion based Reconstruction of Angle of Attack Filtering and Fusion based Reconstruction of Angle of Attack N Shantha Kuar Scientist, FMC Division NAL, Bangalore 7 E-ail: nskuar@css.nal.res.in Girija G Scientist, FMC Division NAL, Bangalore 7 E-ail:

More information

Voltage Deviation of Wind Power Generation due to Wind Velocity Change

Voltage Deviation of Wind Power Generation due to Wind Velocity Change Proceedings of the 7th WSEAS International Conference on Power Systems, Beijing, China, September 15-17, 2007 242 Voltage Deviation of Wind Power Generation due to Wind Velocity Change JUNICHI ARAI, Department

More information

On the Analysis of the Quantum-inspired Evolutionary Algorithm with a Single Individual

On the Analysis of the Quantum-inspired Evolutionary Algorithm with a Single Individual 6 IEEE Congress on Evolutionary Coputation Sheraton Vancouver Wall Centre Hotel, Vancouver, BC, Canada July 16-1, 6 On the Analysis of the Quantu-inspired Evolutionary Algorith with a Single Individual

More information

EEE3405 ELECTRICAL ENGINEERING PRINCIPLES 2 - TEST

EEE3405 ELECTRICAL ENGINEERING PRINCIPLES 2 - TEST ATTEMPT ALL QUESTIONS (EACH QUESTION 20 Marks, FULL MAKS = 60) Given v 1 = 100 sin(100πt+π/6) (i) Find the MS, period and the frequency of v 1 (ii) If v 2 =75sin(100πt-π/10) find V 1, V 2, 2V 1 -V 2 (phasor)

More information

Seismic Analysis of Structures by TK Dutta, Civil Department, IIT Delhi, New Delhi.

Seismic Analysis of Structures by TK Dutta, Civil Department, IIT Delhi, New Delhi. Seisic Analysis of Structures by K Dutta, Civil Departent, II Delhi, New Delhi. Module 5: Response Spectru Method of Analysis Exercise Probles : 5.8. or the stick odel of a building shear frae shown in

More information

Characteristic Study for Integration of Fixed and Variable Speed Wind Turbines into Transmission Grid

Characteristic Study for Integration of Fixed and Variable Speed Wind Turbines into Transmission Grid Characteristic Study for Integration of Fixed and Variable Speed Wind Turbines into Transmission Grid Shuhui Li 1, Tim Haskew 1, R. Challoo 1 Department of Electrical and Computer Engineering The University

More information

Selecting the current rating for equipment

Selecting the current rating for equipment Selecting the current rating for equipment 1. Rated current: the maximum continuous load current. Short-time withstand current: thermal withstand current term term is given for 1s or 3s short circuit current

More information

ANALYSIS OF SUBSYNCHRONOUS RESONANCE EFFECT IN SERIES COMPENSATED LINE WITH BOOSTER TRANSFORMER

ANALYSIS OF SUBSYNCHRONOUS RESONANCE EFFECT IN SERIES COMPENSATED LINE WITH BOOSTER TRANSFORMER ANALYSIS OF SUBSYNCHRONOUS RESONANCE EFFECT IN SERIES COMPENSATED LINE WITH BOOSTER TRANSFORMER G.V.RAJASEKHAR, 2 GVSSNS SARMA,2 Department of Electrical Engineering, Aurora Engineering College, Hyderabad,

More information

Decentralized Adaptive Control of Nonlinear Systems Using Radial Basis Neural Networks

Decentralized Adaptive Control of Nonlinear Systems Using Radial Basis Neural Networks 050 IEEE TRANSACTIONS ON AUTOMATIC CONTROL, VOL. 44, NO., NOVEMBER 999 Decentralized Adaptive Control of Nonlinear Systes Using Radial Basis Neural Networks Jeffrey T. Spooner and Kevin M. Passino Abstract

More information

REAL TIME CONTROL OF DOUBLY FED INDUCTION GENERATOR. Benmeziane Meriem, Zebirate Soraya, Chaker Abelkader Laboratory SCAMRE, ENPO, Oran, Algeria

REAL TIME CONTROL OF DOUBLY FED INDUCTION GENERATOR. Benmeziane Meriem, Zebirate Soraya, Chaker Abelkader Laboratory SCAMRE, ENPO, Oran, Algeria REAL TIME CONTROL OF DOUBLY FED INDUCTION GENERATOR Benmeziane Meriem, Zebirate Soraya, Chaker Abelkader Laboratory SCAMRE, ENPO, Oran, Algeria This paper presents a real time simulation method of wind

More information

Performance Evaluation of DFIG to Changes in Network Frequency

Performance Evaluation of DFIG to Changes in Network Frequency 019 CIENCELINE Journal of World s Electrical Engineering and Technology J. World. Elect. Eng. Tech. 8(1): 01-06, 019 JWEET Performance Evaluation of DFIG to Changes in Network Frequency Ramin Tayebi-Derazkolaie

More information

Introduction to Synchronous. Machines. Kevin Gaughan

Introduction to Synchronous. Machines. Kevin Gaughan Introduction to Synchronous Machines Kevin Gaughan The Synchronous Machine An AC machine (generator or motor) with a stator winding (usually 3 phase) generating a rotating magnetic field and a rotor carrying

More information

Generators. What its all about

Generators. What its all about Generators What its all about How do we make a generator? Synchronous Operation Rotor Magnetic Field Stator Magnetic Field Forces and Magnetic Fields Force Between Fields Motoring Generators & motors are

More information

Fault Analysis Power System Representation

Fault Analysis Power System Representation .1. Power System Representation Single Line Diagram: Almost all modern power systems are three phase systems with the phases of equal magnitude and equal phase difference (i.e., 10 o ). These three phase

More information

Estimation of ADC Nonlinearities from the Measurement in Input Voltage Intervals

Estimation of ADC Nonlinearities from the Measurement in Input Voltage Intervals Estiation of ADC Nonlinearities fro the Measureent in Input Voltage Intervals M. Godla, L. Michaeli, 3 J. Šaliga, 4 R. Palenčár,,3 Deptartent of Electronics and Multiedia Counications, FEI TU of Košice,

More information

8.1 Force Laws Hooke s Law

8.1 Force Laws Hooke s Law 8.1 Force Laws There are forces that don't change appreciably fro one instant to another, which we refer to as constant in tie, and forces that don't change appreciably fro one point to another, which

More information

Symbolic Analysis as Universal Tool for Deriving Properties of Non-linear Algorithms Case study of EM Algorithm

Symbolic Analysis as Universal Tool for Deriving Properties of Non-linear Algorithms Case study of EM Algorithm Acta Polytechnica Hungarica Vol., No., 04 Sybolic Analysis as Universal Tool for Deriving Properties of Non-linear Algoriths Case study of EM Algorith Vladiir Mladenović, Miroslav Lutovac, Dana Porrat

More information

TCSC PLACEMENT FOR LOSS MINIMISATION USING SELF ADAPTIVE FIREFLY ALGORITHM

TCSC PLACEMENT FOR LOSS MINIMISATION USING SELF ADAPTIVE FIREFLY ALGORITHM Journal of Engineering Science and Technology Vol. 10, No. 3 (2015) 21-306 School of Engineering, Taylor s University PLACEMENT FOR LOSS MINIMISATION USING SELF ADAPTIVE FIREFLY ALGORITHM R. SELVARASU*,

More information

A STATIC AND DYNAMIC TECHNIQUE CONTINGENCY RANKING ANALYSIS IN VOLTAGE STABILITY ASSESSMENT

A STATIC AND DYNAMIC TECHNIQUE CONTINGENCY RANKING ANALYSIS IN VOLTAGE STABILITY ASSESSMENT A STATIC AND DYNAMIC TECHNIQUE CONTINGENCY RANKING ANALYSIS IN VOLTAGE STABILITY ASSESSMENT Muhammad Nizam Engineering Faculty Sebelas Maret University (Ph.D Student of Electrical, Electronic and System

More information

PH 222-2C Fall Electromagnetic Oscillations and Alternating Current. Lectures 18-19

PH 222-2C Fall Electromagnetic Oscillations and Alternating Current. Lectures 18-19 H - Fall 0 Electroagnetic Oscillations and Alternating urrent ectures 8-9 hapter 3 (Halliday/esnick/Walker, Fundaentals of hysics 8 th edition) hapter 3 Electroagnetic Oscillations and Alternating urrent

More information

Transient Stability Analysis of Single Machine Infinite Bus System by Numerical Methods

Transient Stability Analysis of Single Machine Infinite Bus System by Numerical Methods International Journal of Electrical and Electronics Research ISSN 348-6988 (online) Vol., Issue 3, pp: (58-66), Month: July - September 04, Available at: www.researchpublish.com Transient Stability Analysis

More information

Comparative Study of Synchronous Machine, Model 1.0 and Model 1.1 in Transient Stability Studies with and without PSS

Comparative Study of Synchronous Machine, Model 1.0 and Model 1.1 in Transient Stability Studies with and without PSS Comparative Study of Synchronous Machine, Model 1.0 and Model 1.1 in Transient Stability Studies with and without PSS Abhijit N Morab, Abhishek P Jinde, Jayakrishna Narra, Omkar Kokane Guide: Kiran R Patil

More information

Effective joint probabilistic data association using maximum a posteriori estimates of target states

Effective joint probabilistic data association using maximum a posteriori estimates of target states Effective joint probabilistic data association using axiu a posteriori estiates of target states 1 Viji Paul Panakkal, 2 Rajbabu Velurugan 1 Central Research Laboratory, Bharat Electronics Ltd., Bangalore,

More information

Fault Location in Distribution Feeders with Distributed Generation using Positive Sequence Apparent Impedance

Fault Location in Distribution Feeders with Distributed Generation using Positive Sequence Apparent Impedance Fault Location in Distribution Feeders with Distributed Generation using Positive Sequence Apparent Impedance ARTURO SUMAN BRETAS Federal University of Rio Grande do Sul Department of Electrical Engineering

More information

Applying Experienced Self-Tuning PID Controllers to Position Control of Slider Crank Mechanisms

Applying Experienced Self-Tuning PID Controllers to Position Control of Slider Crank Mechanisms (00/7) 7 80 Applying Experienced Self-Tuning Controllers to osition Control of Slider Crank Mechaniss Chih-Cheng ao cckao@cc.kyit.edu.tw epartent of Electrical Engineering ao Yuan nstitute of Technology

More information

Modeling of Power System Components During Electromagnetic Transients

Modeling of Power System Components During Electromagnetic Transients Modeling of Power System Components During Electromagnetic Transients 1 Paweł Sowa, 2 Rafał Kumala and 3 Katarzyna Łuszcz 1, 2,3 Faculty of Electrical Engineering, Silesian University of Technology/ Institute

More information