DISTANCE RELAY SETTINGS

Size: px
Start display at page:

Download "DISTANCE RELAY SETTINGS"

Transcription

1 DISTANCE RELAY SETTINGS Introduction Commonly used >33kV Determine whether impedance measured is within set characteristic. Non-unit protection (boundaries not defined) During normal operation impedance is combination of line, transformers and load ( >> line impedance) o Determine fault location by impedance measured o Measured impedance < line impedance fault o Example A 132kV Z = 30 ohms B LOAD 100MVA o Load Impedance = V 2 / P = /100x10 6 =174.2Ω o Relay Measures = = 204 Ω o Equivalent Circuit A B 30 ohms ohms Source o If have fault at B load impedance shorted out and relay measures 30ohm:

2 A B 30 ohms ohms Source o Above is oversimplification (no errors, angle differences) Time Stepped Distance General: Relays have errors as do CTs and VTs allow 5 to 10%. Line impedance calculation errors allow 10%. o total errors 20%. To ensure whole line covered set to 120% but sees past end and could operate for fault on next line. o Solution 1: time delay A B C relay A Reach relay C reach D relay B reach A to grade with B which grades with C similar to overcurrent end up with slowest operation at the source. o Solution 2: set another zone which cant see past end o Set to 80% of line impedance, instantaneous Set to 80%, inst; to 120%, time delayed.

3 A B C Slowest clearance on any line is time. Zone 3 to provide backup to remote lines, time delayed to grade with. Time Stepped Distance Settings Major requirements: Fault detection: faulted plant is tripped Coordination: only faulted plant is tripped General comment: Impedance generally refers to PPS impedance (covers different fault combinations and earth return via measurement quantities see last week). Settings: So can be set instantaneous (no intentional delay), set as far as possible whilst ensuring doesn t see remote end o = 0.8xZ line...(1) Settings Set to ensure whole line length covered and time delayed to grade with next line protection. Time delay > Remote (say 50msec) + remote CB (say 80msec) + remote trip relay (say 10msec) + local Zone

4 2 timing errors (say 50msec) + safety margin (say 50 to 100msec). o 300msec is common. So can use 300msec, require no Z2 overlap A B C F Z2 AB Z AB + Z1 BC ignoring errors o 1.1xZ2AB 0.9(Z AB + Z1 BC ) including errors o Z2AB 0.8(Z AB + Z1 BC ) o Z2AB 0.8(Z AB + 0.8xZ BC ) as Z1 BC = 0.8xZBC o Z2AB 0.8(Z AB + 0.8xZ BC ) Also require whole line to be covered: Z2AB 1.2xZ AB o 1.2xZ AB 0.8(Z AB + 0.8xZ BC ) o ZBC 0.625xZAB o if remote line < 62.5% of protected line impedance no Z2 that satisfies both equations 2 and 3 o generally set as long as possible Zone 3 settings Time delay > Remote (say 50msec pickup + 300msec time delay) + remote CB (say 80msec) + remote trip relay (say 10msec) + local Zone 3 timing errors (say 50msec) + safety margin (say 50 to 100msec). o 600msec is common. Assuming wanting to coordinate Z3, and set 600msec, require no Z3 overlap: o Z3 AB Z AB + Z2 BC ignoring errors 1.1xZ3AB 0.9(Z AB + Z2 BC ) with errors

5 Z3 AB 0.8(Z AB + Z2 BC ) Z3AB 0.8(Z AB + 0.8(Z BC + 0.8xZ CD )) as Z2 AB 0.8(Z AB + 0.8xZ BC ) Z3AB 0.8xZ AB xZ BC xZCD Assuming wanting to backup line B-C: Z3AB 1.2(Z AB + Z BC ) o 1.2(ZAB + Z BC ) 0.8xZ AB xZ BC xZCD o 0.4xZAB xZ BC 0.512xZCD o ZAB + 1.4xZ BC 1.28xZ CD o Only satisfy if CD much longer than AB or BC. Not generally the case difficult to achieve backup and coordination. If backup preferred Z3TD >> 600msec. Short Line Considerations What if Z BC < 0.625xZ AB ie cant set Z2 to cover line and not overlap next Z2 (on a short line) o Only a problem if short line protected by TSD. Three solutions o Time delay Z2 BC to grade with Z2 AB (ie set 600msec) Slow clearance for remote end faults o Set Z2 BC (300msec) so it doesn t see past Z1 AB and then set Z3 BC to protect 120% of line and to grade with Z2 AB (ie set 600msec) Only worthwhile if 120% reach only just overlaps Z1AB Slow clearance for remote end faults under worse case errors. o Use whole line high speed protection (eg differential, pilot, distance signalling, etc) Expensive as requires comms Short lines often protect by differential as distance doesn t achieve enough fault resistance coverage.

6 A B C D short line with high speed protection Need to ensure that the zone 2 of line AB does not see into the zone 2 of line CD. 1.1xZ2 AB 0.9(Z AB + Z BC + Z1 CD ) Z2 AB 0.8(Z AB + Z BC + Z1 CD ) This can be satisfied provided: 1.2xZ AB 0.8(Z AB + Z BC + 0.8xZ CD ) 0.4xZ AB 0.8(Z BC + 0.8xZ CD ) Z AB 2xZ BC + 1.6xZ CD )...(8) In an interconnected system this becomes easier due to throttling (infeeds from other lines cause adjacent lines to appear to have larger impedances). Affects of Power Transformers

7 Transformers > 33kV generally use high speed protection grade with Z2 OK. o Check Z2 and Z3 don t see through TX to plant protected by slow protections: Z2 Z Line + ZTX 1.1xZ2 0.9(ZLine + Z TX ) with errors Z2 0.8(Z Line + Z TX ) o What TX impedance to use due to tap position effecting impedance (nominal, worse case) o Also consider TXs run in parallel. o If no TX high speed protection or have to set Z2/3 so can see through, grade Z2 and Z3 with these slower protections. Considerations of Load Load appears as an impedance to a distance relay. Line angle deg, load impedance +/- 40 deg (ie pf of 0.8). On heavily loaded, long lines load impedance will approach line impedance load encroachment. Worse case is minimum voltage conditions and maximum load on line (Z = V/I). X Load R

8 Throttling Change in relay measured impedance due to multiple remote infeeds to fault A ZL1 I1 I2 B ZL2 Fault With no infeed Zr = ZL1 + ZL2. With infeed at B: V A = I 1 Z L1 + (I 1 + I 2 )Z L2 V A Z L1 + Z L2 + I 2 Z L2 = I 1 I1 Potentially large increase in measured impedance; o need to allow for this if setting Z3 to give remote backup, ie extend Z3 but then need to be careful with grading if remote infeeds removed/reduced o Can assist with grading between lines (eg short lines look longer). o Need to be careful of parallel paths and effects of ends opening before others. o Can show we can set Z2 AB so doesn t see past Z1BC ZAB (1+ I 2 /I 1 )1.6xZ BC (compared with Z BC 0.625xZ AB or Z AB 1.6xZ BC previously) Settings for Teed Lines

9 B A C T Throttling at tee point reduces effectiveness of distance. set to 80% of shortest distance to remote ends ignore throttling here as one end could be open. o If external low impedance connection between remote ends may need to pull back Z1. has to protect whole line and thus set to 120% of largest distance to remote ends, plus consider throttling. o Eg Z2 at A = 120% x Z AT + Z tee max where Ztee max is the max of: (1 + ICB/I AB )Z TB For the impedance from T to B (1 + IBC/I AC )Z TC For the impedance from T to C where Ixy is the current from x to y o When checking coordination, assume one end open o Effected by changes to system. o If coordination not possible, use differential or distance signalling.

10 TUTORIAL WEEK 4 1) For the following power system determine, 2 and 3 reach and time delay settings. A G B C F H I D E Impedances, loads a) Generator 0.1pu, 1200A, 11kV b) Line A-G 0.3pu, 1000A c) Line B-C 0.4pu, 800A d) Line D-E 0.35pu, 800A e) Line F-H 0.2pu, 400A f) I has impedance of 0.5pu Assume I operates instantaneously. Allow 300msec safety margin between relays. 2) Check reaches determined in Question 1 do not result in any load encroachment problems. Assume all lines have a line angle of 70 degrees and relays are mho relays. 3) Consider options for short line F-H.

ALPS. Advanced Line Protection System

ALPS. Advanced Line Protection System ALPS Advanced Line Protection System Modified Fourier Calculation High Speed Sampling Phaselet Calculation Variable Window Digital Mimic 2 10 5 EXECUTE PHASELET CALCULATION AND PROTECTION ALGORITHMS High

More information

Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent Elements in Line Protection Applications

Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent Elements in Line Protection Applications Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent Elements in Line Protection Applications Technical Report to the Line Protection Subcommittee of the PES, Power Systems

More information

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager. Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager. 1 -A - Introduction - Thank for your purchasing MITSUBISHI ELECTRIC MELPRO TM D Series Digital Protection

More information

EDSA IEC 909 SHORT CIRCUIT ANALYSIS

EDSA IEC 909 SHORT CIRCUIT ANALYSIS 1.0 Tutorial Exercise This tutorial exercise will serve as a validation and verification test for the EDSA IEC 909 short circuit program. The tutorial will be based on two examples documented in the IEC

More information

Fault Calculation Methods

Fault Calculation Methods ELEC9713 Industrial and Commercial Power Systems Fault Calculation Methods There are two major problems that can occur in electrical systems: these are open circuits and short circuits. Of the two, the

More information

ECE 526 Distance Element Examples

ECE 526 Distance Element Examples Session 7; Page /2 ECE 526 Distance Element Examples The impedances for the system below are given in secondary ohms. The zone reach of the relay at BUS is set to cover 85% of the line. BUS BUS 2 Z S Relay

More information

Reactive Power Solutions

Reactive Power Solutions GE Digital Energy Reactive Power Solutions Effects of Series Capacitors on Line Protection Relaying Design and Settings Presented by: Paul Datka, GE Energy Consulting Luis Polanco, GE Energy Consulting

More information

Distance Elements: Linking Theory With Testing

Distance Elements: Linking Theory With Testing Distance Elements: Linking Theory With Testing Fernando Calero Schweitzer Engineering Laboratories, Inc. Revised edition released August 009 Previously presented at the 6nd Annual Conference for Protective

More information

THE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session

THE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session Name: Student ID: Signature: THE UNIVERSITY OF NEW SOUTH WALES School of Electrical Engineering & Telecommunications FINALEXAMINATION Session 00 ELEC46 Power System Analysis TIME ALLOWED: 3 hours TOTAL

More information

Basic Math for Relay Technicians. Hands On Relay School 2015 Presented by Charlene Reyes

Basic Math for Relay Technicians. Hands On Relay School 2015 Presented by Charlene Reyes Basic Math for Relay Technicians Hands On Relay School 2015 Presented by Charlene Reyes Overview Order of Operations and Order of Magnitude Unit Analysis and Conversions Trigonometry Rectangular and Polar

More information

Performance Comparison Between Mho Elements and Incremental Quantity-Based Distance Elements

Performance Comparison Between Mho Elements and Incremental Quantity-Based Distance Elements Performance Comparison Between Mho Elements and Incremental Quantity-Based Distance Elements Gabriel Benmouyal, Normann Fischer, and Brian Smyth, Schweitzer Engineering Laboratories, Inc. Abstract Mho

More information

Dynamic simulation of a five-bus system

Dynamic simulation of a five-bus system ELEC0047 - Power system dynamics, control and stability Dynamic simulation of a five-bus system Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct November 2017 1 / 16 System modelling

More information

Lecture (5) Power Factor,threephase circuits, and Per Unit Calculations

Lecture (5) Power Factor,threephase circuits, and Per Unit Calculations Lecture (5) Power Factor,threephase circuits, and Per Unit Calculations 5-1 Repeating the Example on Power Factor Correction (Given last Class) P? Q? S? Light Motor From source 1000 volts @ 60 Htz 10kW

More information

Z n. 100 kv. 15 kv. pu := 1. MVA := 1000.kW. Transformer nameplate data: X T_pu := 0.1pu S T := 10MVA. V L := 15kV. V H := 100kV

Z n. 100 kv. 15 kv. pu := 1. MVA := 1000.kW. Transformer nameplate data: X T_pu := 0.1pu S T := 10MVA. V L := 15kV. V H := 100kV /9 j := pu := MVA :=.kw 7.. Three MVA, -5 kv transformers have nameplate impedances of % and are connected Δ-Y with the high voltage side Δ. Find the zero sequence equivalent circuit. kv Z n 5 kv Transformer

More information

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester Electrical and Electronics Engineering EE 1352 Power System Analysis (Regulation 2008) Time: Three hours Answer all questions Part A (10

More information

2/7/2013. Topics. 15-System Model Text: One-Line Diagram. One-Line Diagram

2/7/2013. Topics. 15-System Model Text: One-Line Diagram. One-Line Diagram /7/013 Topics 15-ystem Model Text: 5.8 5.11 One-line Diagram ystem Modeling Regulating Transformers ECEGR 451 Power ystems Dr. Henry Louie 1 Dr. Henry Louie Generator us Transformer Transmission line Circuit

More information

Module 3 : Sequence Components and Fault Analysis

Module 3 : Sequence Components and Fault Analysis Module 3 : Sequence Components and Fault Analysis Lecture 13 : Sequence Modeling (Tutorial) Objectives In this lecture we will solve tutorial problems on fault analysis in sequence domain Per unit values

More information

Fault Analysis Power System Representation

Fault Analysis Power System Representation .1. Power System Representation Single Line Diagram: Almost all modern power systems are three phase systems with the phases of equal magnitude and equal phase difference (i.e., 10 o ). These three phase

More information

NEW DESIGN OF GROUND FAULT PROTECTION

NEW DESIGN OF GROUND FAULT PROTECTION NEW DESIGN OF GROUND FAULT PROTECTION The 71st Annual Conference for Protective Relay Engineers Siemens AG 2018 All rights reserved. siemens.com/energy-management Why do we need ground fault protection?

More information

Section 5. TADS Data Reporting Instruction Manual DRAFT Section 5 and Associated Appendices With Proposed Event Type Numbers

Section 5. TADS Data Reporting Instruction Manual DRAFT Section 5 and Associated Appendices With Proposed Event Type Numbers Section 5 TADS Data Reporting Instruction Manual DRAFT Section 5 and Associated Appendices With Proposed Event Type Numbers Rev. 5/10/2010 1 Section 5 Form for Event ID and Event Type Number Data TO s

More information

Securing Sequence-Current Differential Elements

Securing Sequence-Current Differential Elements Securing Sequence-Current Differential Elements Gabriel Benmouyal and Tony Lee Schweitzer Engineering Laboratories, Inc. Presented at the 31st Annual Western Protective Relay Conference Spokane, Washington

More information

ELEC Introduction to power and energy systems. The per unit system. Thierry Van Cutsem

ELEC Introduction to power and energy systems. The per unit system. Thierry Van Cutsem ELEC0014 - Introduction to power and energy systems The per unit system Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct October 2018 1 / 12 Principle The per unit system Principle

More information

SHORT QUESTIONS AND ANSWERS. Year/ Semester/ Class : III/ V/ EEE Academic Year: Subject Code/ Name: EE6501/ Power System Analysis

SHORT QUESTIONS AND ANSWERS. Year/ Semester/ Class : III/ V/ EEE Academic Year: Subject Code/ Name: EE6501/ Power System Analysis Srividya colllege of Engg & Tech,Virudhunagar Sri Vidya College of Engineering And Technology Virudhunagar 626 005 Department of Electrical and Electronics Engineering QUESTION BANK SHORT QUESTIONS AND

More information

Final Exam, Second Semester: 2015/2016 Electrical Engineering Department

Final Exam, Second Semester: 2015/2016 Electrical Engineering Department Philadelphia University Faculty of Engineering Student Name Student No: Serial No Final Exam, Second Semester: 2015/2016 Electrical Engineering Department Course Title: Power II Date: 21 st June 2016 Course

More information

c Z ... Ln :E UJ UJ ...J. (f) (f) (f) UJ. (f) (f)

c Z ... Ln :E UJ UJ ...J. (f) (f) (f) UJ. (f) (f) - r1 N......J... co (f) Ln :E UJ UJ u UJ tn > (f) UJ S a. \ r1. c Z... (f) (f) UJ (f) -,... f.. U'....1i I /, IL I.., l..c: :! ta Q, - J "'C r.. c ::::> -u \("'t,; l I o I .\ ( X R+ IX = Zlli --...------------R

More information

Cahier Technique N 11 Guide de réglage de la protection de Distance. Distance Protection (F21) Setting Guide

Cahier Technique N 11 Guide de réglage de la protection de Distance. Distance Protection (F21) Setting Guide Cahier Technique N 11 Guide de réglage de la protection de Distance Distance Protection (F21) Setting Guide (English version) Cahier Technique rédigé en collaboration avec PROTECTA / Technical Guide written

More information

Fault Locating PRESENTED BY ERIK SCHELLENBERG IDAHO POWER

Fault Locating PRESENTED BY ERIK SCHELLENBERG IDAHO POWER Fault Locating PRESENTED BY ERIK SCHELLENBERG IDAHO POWER Topics Impedance Based Reactance Method Takagi Method Modifications to Takagi Method TWS & Double Ended Negative Sequence One Line Equivalent Thevenin

More information

Selecting the current rating for equipment

Selecting the current rating for equipment Selecting the current rating for equipment 1. Rated current: the maximum continuous load current. Short-time withstand current: thermal withstand current term term is given for 1s or 3s short circuit current

More information

Traveling Wave Relays. Fault Location

Traveling Wave Relays. Fault Location Traveling Wave Relays Determining direction requires knowing when the remote terminal detects wave front. et: tr = remote time of detection ts = local time of detection tl = travel time for line Algorithm

More information

Identifying the Proper Impedance Plane and Fault Trajectories in Distance Protection Analysis

Identifying the Proper Impedance Plane and Fault Trajectories in Distance Protection Analysis Identifying the Proper Impedance Plane and Fault Trajectories in Distance Protection Analysis Fernando Calero and Héctor J. Altuve Schweitzer Engineering Laboratories, Inc. Presented at the 66th Annual

More information

Electrical Machines-I Prof. D. Kastha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Electrical Machines-I Prof. D. Kastha Department of Electrical Engineering Indian Institute of Technology, Kharagpur Electrical Machines-I Prof. D. Kastha Department of Electrical Engineering Indian Institute of Technology, Kharagpur Lecture - 20 Potential and Current Transformers (Refer Slide Time: 00:37) So far we

More information

Two Port Networks. Definition of 2-Port Network A two-port network is an electrical network with two separate ports for input and output

Two Port Networks. Definition of 2-Port Network A two-port network is an electrical network with two separate ports for input and output Two Port Networks Definition of 2-Port Network A two-port network is an electrical network with two separate ports for input and output What is a Port? It is a pair of terminals through which a current

More information

The per unit system is based on the formula shown in Equation (1).

The per unit system is based on the formula shown in Equation (1). TECHNCAL ULLETN 007 Overview The per unit system is based on the formula shown in Equation (1). (1) per unit actual quantity base quantity Using this method, all quantities are expressed as ratios of some

More information

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION EE 6501 POWER SYSTEMS UNIT I INTRODUCTION PART A (2 MARKS) 1. What is single line diagram? A Single line diagram is diagrammatic representation of power system in which the components are represented by

More information

ABSTRACT. residential Photovoltaic (PV) systems. The investigation is done on both conventional and

ABSTRACT. residential Photovoltaic (PV) systems. The investigation is done on both conventional and ABSTRACT HOOSHYAR, HOSSEIN. System Protection for High PV-Penetrated Residential Distribution Systems (Green Hubs). (Under the direction of Dr Mesut E. Baran). This study investigates the protection issues

More information

VLSI Physical Design Prof. Indranil Sengupta Department of Computer Science and Engineering Indian Institute of Technology, Kharagpur

VLSI Physical Design Prof. Indranil Sengupta Department of Computer Science and Engineering Indian Institute of Technology, Kharagpur VLSI Physical Design Prof. Indranil Sengupta Department of Computer Science and Engineering Indian Institute of Technology, Kharagpur Lecture - 54 Design for Testability So, in the last lecture we talked

More information

Current protection I 2 t long-time protection

Current protection I 2 t long-time protection I 2 t long-time protection The long-time protection function protects cables against overloads. This function is based on true rms measurements. It is possible to select either I 2 t long-time protection

More information

Symmetrical Fault Current Calculations Unlv

Symmetrical Fault Current Calculations Unlv We have made it easy for you to find a PDF Ebooks without any digging. And by having access to our ebooks online or by storing it on your computer, you have convenient answers with symmetrical fault current

More information

The Operation of a Generator on Infinite Busbars

The Operation of a Generator on Infinite Busbars The Operation of a Generator on Infinite Busbars In order to simplify the ideas as much as possible the resistance of the generator will be neglected; in practice this assumption is usually reasonable.

More information

Mitigation of Distributed Generation Impact on Protective Devices in a Distribution Network by Superconducting Fault Current Limiter *

Mitigation of Distributed Generation Impact on Protective Devices in a Distribution Network by Superconducting Fault Current Limiter * Energy and Power Engineering, 2013, 5, 258-263 doi:10.4236/epe.2013.54b050 Published Online July 2013 (http://www.scirp.org/journal/epe) Mitigation of Distributed Generation Impact on Protective Devices

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current Transducer HO-NP series I P N = 4, 6, 12, 15 A Ref: HO 4-NP, HO 6-NP, HO 12-NP, HO 15-NP For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary

More information

POWER SWING AND OUT-OF-STEP CONSIDERATIONS ON TRANSMISSION LINES

POWER SWING AND OUT-OF-STEP CONSIDERATIONS ON TRANSMISSION LINES POWER SWING AND OUT-OF-STEP CONSIDERATIONS ON TRANSMISSION LINES 1 / 59 2005-07-19 POWER SWING AND OUT-OF-STEP CONSIDERATIONS ON TRANSMISSION LINES A report to the Power System Relaying Committee Of the

More information

Analysis of a Relay Operation for an Intercircuit Fault

Analysis of a Relay Operation for an Intercircuit Fault Analysis of a Relay Operation for an Intercircuit Fault Ryan McDaniel Schweitzer Engineering Laboratories, Inc. 2015 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained

More information

Regulating Transformers in Sequence Domain

Regulating Transformers in Sequence Domain ECE523: Lecture 25; Page 1/8 pu 1 Regulating Transformers in Sequence Domain A three-phase voltage regulating transformer has a per unit leakage reactance of.1, and steps the voltage from 69 kv to 35 kv.

More information

POWER SEMICONDUCTOR BASED ELECTRIC DRIVES

POWER SEMICONDUCTOR BASED ELECTRIC DRIVES POWER SEMICONDUCT BASED ELECTRIC DRIVES [Time: 3 Hrs] [Max. Marks: 80] Instructions: Solve any six questions from Q.No (1 or 2), Q.No (3 or 4), Q.No (5 or 6), Q.No (7 or 8), Q.No (9 or 10), Q.No (11 or

More information

Fault Diagnosis in Distribution Networks with Distributed Generation

Fault Diagnosis in Distribution Networks with Distributed Generation Smart Grid and Renewable Energy, 2011, 2, 1-11 doi:10.4236/sgre.2011.21001 Published Online February 2011 (http://www.scirp.org/journal/sgre) 1 Fault Diagnosis in Distribution Networks with Distributed

More information

OVER CURRENT RELAYS PROTECTIVE COORDINATION IN DISTRIBUTION SYSTEMS IN PRESENCE OF DISTRIBUTED GENERATION

OVER CURRENT RELAYS PROTECTIVE COORDINATION IN DISTRIBUTION SYSTEMS IN PRESENCE OF DISTRIBUTED GENERATION International Journal on Technical and Physical Problems of Engineering (IJTPE) Published by International Organization on TPE (IOTPE) ISSN 2077-3528 IJTPE Journal www.iotpe.com ijtpe@iotpe.com June 2011

More information

To order, specify : Types Protection functions Current surge Asymmetry and loss of phase. Operating principle

To order, specify : Types Protection functions Current surge Asymmetry and loss of phase. Operating principle otor protection relays - T - FWIT Since % of -phase motor failures are due to load problems or loss of phase, the CROUZET range of motor protection relays is indispensable! models give motor protection

More information

90 MCB range Modular circuit breakers for circuit protection

90 MCB range Modular circuit breakers for circuit protection MCB - MTC - MT - MTHP Technical data TYPE MTC MT MTC45 MTC60 MTC100 MT 45 MT 60 Rated current (In) (A) 2-32 6-32 6-32 6-40 1-63 Utilization category A A A A A Rated operational voltage (Ue) (V) 230 / 400

More information

Tutorial on Shunt Capacitor Banks Design, Application and Protection Considerations

Tutorial on Shunt Capacitor Banks Design, Application and Protection Considerations Tutorial on Shunt Capacitor Banks Design, Application and Protection Considerations Presenter: Pratap Mysore, HDR Minnesota Power Systems Conference November 12, 2015 Topics Covered Power system Considerations,

More information

Module 3 : Sequence Components and Fault Analysis

Module 3 : Sequence Components and Fault Analysis Module 3 : Sequence Components and Fault Analysis Lecture 12 : Sequence Modeling of Power Apparatus Objectives In this lecture we will discuss Per unit calculation and its advantages. Modeling aspects

More information

90 MCB MODULAR CIRCUIT BREAKERS FOR CIRCUIT PROTECTION

90 MCB MODULAR CIRCUIT BREAKERS FOR CIRCUIT PROTECTION MCB - MTC - MT - MTHP Technical data TYPE MTC MT MTC45 MTC60 MTC100 MT 45 MT 60 Rated current (In) (A) 2-32 6-32 6-32 6-40 1-63 Utilization category A A A A A Rated operational voltage (Ue) (V) 230/400-240/415

More information

Transient Behavior of

Transient Behavior of Transient Behavior of Static Fault Current Limiter in Distribution System by Shahram Najafi, Vijay K. Sood University of Ontario Institute of Technology, Oshawa, Ontario Electrical Power and Energy Conference

More information

NTE4514B & NTE4515B Integrated Circuit CMOS, 4 Bit Latch/4 to 16 Line Decoder

NTE4514B & NTE4515B Integrated Circuit CMOS, 4 Bit Latch/4 to 16 Line Decoder NTE4514B & NTE4515B Integrated Circuit CMOS, 4 Bit Latch/4 to 16 Line Decoder Description: The NTE4514B (output active high option) and NTE4515B (output active low option) are two output options of a 4

More information

SESSION 3. Short Circuit Calculations, Unsymmetrical Faults. Leonard Bohmann, Michigan State University Elham Makram, Clemson University

SESSION 3. Short Circuit Calculations, Unsymmetrical Faults. Leonard Bohmann, Michigan State University Elham Makram, Clemson University SESSON Short Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University Short Circuit Calculations Leonard Bohmann Michigan State University

More information

A. P. Sakis Meliopoulos and George J. Cokkinides Power System Relaying, Theory and Applications. Chapter 8 2 Generator Protection 2

A. P. Sakis Meliopoulos and George J. Cokkinides Power System Relaying, Theory and Applications. Chapter 8 2 Generator Protection 2 DRAFT and INCOMPLETE Table of Contents from A. P. Sakis Meliopoulos and George J. Cokkinides Power System Relaying, Theory and Applications Chapter 8 Generator Protection 8. Introduction 8. Generator Protection

More information

Series & Parallel Resistors 3/17/2015 1

Series & Parallel Resistors 3/17/2015 1 Series & Parallel Resistors 3/17/2015 1 Series Resistors & Voltage Division Consider the single-loop circuit as shown in figure. The two resistors are in series, since the same current i flows in both

More information

Chapter 8: Unsymmetrical Faults

Chapter 8: Unsymmetrical Faults Chapter 8: Unsymmetrical Faults Introduction The sequence circuits and the sequence networks developed in the previous chapter will now be used for finding out fault current during unsymmetrical faults.

More information

ECE 524: Reducing Capacitor Switching Transients

ECE 524: Reducing Capacitor Switching Transients ECE 54: Session 6; Page / Spring 08 ECE 54: Reducing Capacitor Switching Transients Define units: MW 000kW MVA MW MVAr MVA Example : f 60Hz ω πf ω 76.99 rad s t 0 0.00000sec 60 sec Add inductive reactance

More information

ECE 524: Lecture 15 Reducing Capacitor Switching Transients. jx s C 2 C 1. Define units: MW 1000kW MVA MW MVAr MVA. rad s

ECE 524: Lecture 15 Reducing Capacitor Switching Transients. jx s C 2 C 1. Define units: MW 1000kW MVA MW MVAr MVA. rad s ECE 54: Session 5; Page / Spring 04 ECE 54: Lecture 5 Reducing Capacitor Switching Transients Define units: MW 000kW MVA MW MVAr MVA Example : f 60Hz ω πf ω 76.99 rad s t 0 0.00000sec 60 sec Add inductive

More information

Chapter 33 - Electric Fields and Potential. Chapter 34 - Electric Current

Chapter 33 - Electric Fields and Potential. Chapter 34 - Electric Current Chapter 33 - Electric Fields and Potential Chapter 34 - Electric Current Electric Force acts through a field An electric field surrounds every electric charge. It exerts a force that causes electric charges

More information

QUESTION BANK ENGINEERS ACADEMY. Power Systems Power System Stability 1

QUESTION BANK ENGINEERS ACADEMY. Power Systems Power System Stability 1 ower ystems ower ystem tability QUETION BANK. A cylindrical rotor generator delivers 0.5 pu power in the steady-state to an infinite bus through a transmission line of reactance 0.5 pu. The generator no-load

More information

EE 451 Power System Stability

EE 451 Power System Stability EE 451 Power System Stability Power system operates in synchronous mode Power system is subjected to a wide range of disturbances (small and large) - Loads and generation changes - Network changes - Faults

More information

Name. Section. Short Answer Questions. 1. (20 Pts) 2. (10 Pts) 3. (5 Pts) 4. (10 Pts) 5. (10 Pts) Regular Questions. 6. (25 Pts) 7.

Name. Section. Short Answer Questions. 1. (20 Pts) 2. (10 Pts) 3. (5 Pts) 4. (10 Pts) 5. (10 Pts) Regular Questions. 6. (25 Pts) 7. Name Section Short Answer Questions 1. (20 Pts) 2. (10 Pts) 3. (5 Pts). (10 Pts) 5. (10 Pts) Regular Questions 6. (25 Pts) 7. (20 Pts) Notes: 1. Please read over all questions before you begin your work.

More information

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA.

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA What are phasors??? In normal practice, the phasor represents the rms maximum value of the positive half cycle of the sinusoid

More information

Switched-Capacitor Filters

Switched-Capacitor Filters Switched-Capacitor Filters Analog sampled-data filters: Continuous amplitude Quantized time Applications: Oversampled and D/A converters Analog front-ends (CDS, etc) Standalone filters E.g. National Semiconductor

More information

KINGS COLLEGE OF ENGINEERING Punalkulam

KINGS COLLEGE OF ENGINEERING Punalkulam KINGS COLLEGE OF ENGINEERING Punalkulam 613 303 DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING POWER SYSTEM ANALYSIS QUESTION BANK UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A (TWO MARK

More information

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager. Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager. 1 -C - Safety section - This Safety section should be read before starting any work on the relay.

More information

Mathcad Examples. Define units: MVA 1000kW MW MVA kw kvar kw. pu Entering Phasors in Polar Notation

Mathcad Examples. Define units: MVA 1000kW MW MVA kw kvar kw. pu Entering Phasors in Polar Notation ECE 53: Session ; Page / Fall 07 Mathcad Examples Define units: MVA 000kW MW MVA kva kw kvar kw pu. Entering Phasors in Polar Notation Step : Go to: "Help Menu" -- "Quick Sheets" Step : Choose "Extra Math

More information

I. Impedance of an R-L circuit.

I. Impedance of an R-L circuit. I. Impedance of an R-L circuit. [For inductor in an AC Circuit, see Chapter 31, pg. 1024] Consider the R-L circuit shown in Figure: 1. A current i(t) = I cos(ωt) is driven across the circuit using an AC

More information

The Influence of Abnormal Data on Relay Protection

The Influence of Abnormal Data on Relay Protection Energy and Power Engineering, 7, 9, 95- http://www.scirp.org/journal/epe ISS Online: 97-388 ISS Print: 99-3X The Influence of Abnormal Data on Relay Protection Xuze Zhang, Xiaoning Kang, Yali Ma, Hao Wang,

More information

Chapter 2 Circuit Elements

Chapter 2 Circuit Elements Chapter 2 Circuit Elements 2.1 Voltage and Current Sources 2.2 Electrical Resistance (Ohm s Law) 2.3 Construction of a Circuit Model 2.4 Kirchhoff s Laws 2.5 Analysis of a Circuit Containing Dependent

More information

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA I m VECTOR. Cause I m committing crimes with magnitude and direction at the same time!" What are phasors??? In normal practice,

More information

Adaptive Distance Relaying Scheme for Power Swing Tripping Prevention

Adaptive Distance Relaying Scheme for Power Swing Tripping Prevention Adaptive Distance Relaying Scheme for Power Swing Tripping Prevention 1 NOR ZULAILY MOHAMAD, AHMAD FARID ABIDIN, 3 ISMAIL MUSIRIN Centre of Electrical Power Engineering Studies Universiti Teknologi MARA

More information

Remote Display Unit. Installers Handbook Copyright 2001 AirSense Technology Ltd. LM Remote Display Unit Installers Handbook Issue 1.

Remote Display Unit. Installers Handbook Copyright 2001 AirSense Technology Ltd. LM Remote Display Unit Installers Handbook Issue 1. Remote Display Unit Installers Handbook Copyright 2001 AirSense Technology Ltd AirSense, ClassiFire, FastLearn PipeCAD, SenseNET, Stratos-HSSD and Stratos-Quadra are trademarks. HSSD is a Registered Trademark.

More information

Worked Example for the Calculation of Earthing Current and Electric Shock Hazard Potential Difference in a Rod and Grid Earthing System

Worked Example for the Calculation of Earthing Current and Electric Shock Hazard Potential Difference in a Rod and Grid Earthing System Appendix H Worked Example for the Calculation of Earthing Current and Electric Shock Hazard Potential Difference in a Rod and Grid Earthing System H.1 WORKED EXAMPLE A 33 kv overhead line terminates at

More information

4/27 Friday. I have all the old homework if you need to collect them.

4/27 Friday. I have all the old homework if you need to collect them. 4/27 Friday Last HW: do not need to turn it. Solution will be posted on the web. I have all the old homework if you need to collect them. Final exam: 7-9pm, Monday, 4/30 at Lambert Fieldhouse F101 Calculator

More information

ECE 421: Per Unit Examples

ECE 421: Per Unit Examples ECE 41: Session 14; Page 1/13 Fall 013 ECE 41: Per Unit Examples Define units: MVA 1000kW MW MVA kva kw kvar kw pu 1 Example 1: A three-phase transformer rated 5 MVA, 115/13. kv has per-phase series impedance

More information

Electromagnetic Oscillations and Alternating Current. 1. Electromagnetic oscillations and LC circuit 2. Alternating Current 3.

Electromagnetic Oscillations and Alternating Current. 1. Electromagnetic oscillations and LC circuit 2. Alternating Current 3. Electromagnetic Oscillations and Alternating Current 1. Electromagnetic oscillations and LC circuit 2. Alternating Current 3. RLC circuit in AC 1 RL and RC circuits RL RC Charging Discharging I = emf R

More information

T-PRO Application in Reactor Protection Using Neutral Differential and Timed Over-Current Back-up Protection

T-PRO Application in Reactor Protection Using Neutral Differential and Timed Over-Current Back-up Protection T-PRO Application in Reactor Protection Using Neutral Differential and Timed Over-Current Back-up Protection 87N Neutral Differential Neutral Differential protection (87N), which is also known as Restricted

More information

Microprocessor Based Characteristics and adjustments

Microprocessor Based Characteristics and adjustments Microprocessor Based Characteristics and adjustments 7- Range Operation Settings Operation and Examples 0 Ground Fault and Pre-rip larm LED ndication and OCR Controller ime/current Curves - OCR Checker

More information

Computer Science 324 Computer Architecture Mount Holyoke College Fall Topic Notes: Digital Logic

Computer Science 324 Computer Architecture Mount Holyoke College Fall Topic Notes: Digital Logic Computer Science 324 Computer Architecture Mount Holyoke College Fall 2007 Topic Notes: Digital Logic Our goal for the next few weeks is to paint a a reasonably complete picture of how we can go from transistor

More information

Preventing Voltage Collapse with Protection Systems that Incorporate Optimal Reactive Power Control

Preventing Voltage Collapse with Protection Systems that Incorporate Optimal Reactive Power Control PSERC Preventing Voltage Collapse with Protection Systems that Incorporate Optimal Reactive Power Control Final Project Report Power Systems Engineering Research Center A National Science Foundation Industry/University

More information

Chapter 5 Steady-State Sinusoidal Analysis

Chapter 5 Steady-State Sinusoidal Analysis Chapter 5 Steady-State Sinusoidal Analysis Chapter 5 Steady-State Sinusoidal Analysis 1. Identify the frequency, angular frequency, peak value, rms value, and phase of a sinusoidal signal. 2. Solve steady-state

More information

The Ordering Code for various standard model Recorders with an AC supply and without any additional options are as follows:

The Ordering Code for various standard model Recorders with an AC supply and without any additional options are as follows: The basic PC software is supplied free with the recorder. There is an additional charge for the extensive Data Acquisition Software supplied with communication of RS-232/422/485 or Ethernet. The Ordering

More information

Introduction to Karnaugh Maps

Introduction to Karnaugh Maps Introduction to Karnaugh Maps Review So far, you (the students) have been introduced to truth tables, and how to derive a Boolean circuit from them. We will do an example. Consider the truth table for

More information

NEW RECLOSER CHARACTERISTIC TO IMPROVE FUSE SAVING IN DISTRIBUTION NETWORKS WITH DISTRIBUTED GENERATION

NEW RECLOSER CHARACTERISTIC TO IMPROVE FUSE SAVING IN DISTRIBUTION NETWORKS WITH DISTRIBUTED GENERATION Rev. Roum. Sci. Techn. Électrotechn. et Énerg. Vol. 62, 3, pp. 240 245, Bucarest, 2017 NEW RECLOSER CHARACTERISTIC TO IMPROVE FUSE SAVING IN DISTRIBUTION NETWORKS WITH DISTRIBUTED GENERATION SADEGH JAMALI,

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current Transducer HO-NSM series I PN = 8, 15, 25 A Ref: HO 8-NSM, HO 15-NSM, HO 25-NSM For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the

More information

INSTRUCTION MANUAL FOR MM10 Relay

INSTRUCTION MANUAL FOR MM10 Relay INSTRUCTION MANUAL FOR MM10 Relay Motor Protection Relay Front Panel Overview V1 250614 MM10 Motor Protection Relay a I L1 b I L2 I L3 c h i d e I L1 Figure 1: Front panel overview f g I L2 a Run LED b

More information

IGEE 402 Power System Analysis. FINAL EXAMINATION - SAMPLE Fall 2004

IGEE 402 Power System Analysis. FINAL EXAMINATION - SAMPLE Fall 2004 IGEE 402 Power System Analysis FINAL EXAMINATION - SAMPLE Fall 2004 Special instructions: - Duration: 80 minutes. - Material allowed: a crib sheet (double sided 8.5 x ), calculator. - Attempt 5 out of

More information

ECE 476. Exam #2. Tuesday, November 15, Minutes

ECE 476. Exam #2. Tuesday, November 15, Minutes Name: Answers ECE 476 Exam #2 Tuesday, November 15, 2016 75 Minutes Closed book, closed notes One new note sheet allowed, one old note sheet allowed 1. / 20 2. / 20 3. / 20 4. / 20 5. / 20 Total / 100

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current Transducer HO-NP/SP33 series I PN = 8, 15, 25 A Ref: HO 8-NP/SP33, HO 15-NP/SP33, HO 25-NP/SP33 For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the

More information

Digital Current Transducer HO-SW series I P N = A. Ref: HO 100-SW; HO 150-SW; HO 200-SW; HO 250-SW

Digital Current Transducer HO-SW series I P N = A. Ref: HO 100-SW; HO 150-SW; HO 200-SW; HO 250-SW Digital Current Transducer HO-SW series I P N = 100... 250 A Ref: HO 100-SW; HO 150-SW; HO 200-SW; HO 250-SW Bitstream output from on onboard Sigma Delta modulator. For the electronic measurement of current:

More information

LESSON 20 ALTERNATOR OPERATION OF SYNCHRONOUS MACHINES

LESSON 20 ALTERNATOR OPERATION OF SYNCHRONOUS MACHINES ET 332b Ac Motors, Generators and Power Systems LESSON 20 ALTERNATOR OPERATION OF SYNCHRONOUS MACHINES 1 LEARNING OBJECTIVES After this presentation you will be able to: Interpret alternator phasor diagrams

More information

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous)

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad - 500 043 ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK Course Name : Computer Methods in Power Systems Course Code : A60222

More information

TSTE25 Power Electronics. Lecture 3 Tomas Jonsson ICS/ISY

TSTE25 Power Electronics. Lecture 3 Tomas Jonsson ICS/ISY TSTE25 Power Electronics Lecture 3 Tomas Jonsson ICS/ISY 2016-11-09 2 Outline Rectifiers Current commutation Rectifiers, cont. Three phase Inrush and short circuit current Exercises 5-5, 5-8, 3-100, 3-101,

More information

Research Article A Novel Algorithm for Power Flow Transferring Identification Based on WAMS

Research Article A Novel Algorithm for Power Flow Transferring Identification Based on WAMS Mathematical Problems in Engineering Volume 015, Article ID 60850, 17 pages http://dxdoiorg/101155/015/60850 Research Article A vel Algorithm for Power Flow Transferring Identification Based on WAMS Xu

More information

What happens when things change. Transient current and voltage relationships in a simple resistive circuit.

What happens when things change. Transient current and voltage relationships in a simple resistive circuit. Module 4 AC Theory What happens when things change. What you'll learn in Module 4. 4.1 Resistors in DC Circuits Transient events in DC circuits. The difference between Ideal and Practical circuits Transient

More information

max clear Figure 1 below illustrates a stable case. P post (f) (g) (e) A 2 (d) (c)

max clear Figure 1 below illustrates a stable case. P post (f) (g) (e) A 2 (d) (c) Stability 4. Introduction In the previous notes (Stability 3, we developed the equal area iterion, which says that For stability, A =A, which means the decelerating energy (A must equal the accelerating

More information

Homework 1 solutions

Homework 1 solutions Electric Circuits 1 Homework 1 solutions (Due date: 2014/3/3) This assignment covers Ch1 and Ch2 of the textbook. The full credit is 100 points. For each question, detailed derivation processes and accurate

More information