1 GE Digital Energy Reactive Power Solutions Effects of Series Capacitors on Line Protection Relaying Design and Settings Presented by: Paul Datka, GE Energy Consulting Luis Polanco, GE Energy Consulting
2 GE Guest Speakers Paul Datka GE Energy Consulting, Principal Over 10 years of T&D experience, Series Capacitor equipment design, ratings, and system studies IEEE, CIGRE Member Holds a patent for Series Capacitor Protection equipment invention Luis Polanco GE Energy Consulting, Principal Over 10 years of substation equipment and line protection system design and settings IEEE Member
3 Agenda Why Series Compensation Series Capacitor Operation During Line Faults Effects of Series Capacitors On Line Protection Relaying Mitigation Techniques Live Q & A
4 Why Series Compensation?
5 Why Series Compensation? Series Compensation are primarily applied to Increase long distance power transfer capability Increase dynamic stability Reduce voltage variation Improve voltage profile of the line Improve load division but requires Protection from line faults
6 System Overview Series Capacitor Current Limiting Damping Reactor Varistor Bypass Gap Bypass Switch Series Compensation is an integrated, custom-designed system that consists of power capacitors arranged in series with the HV transmission line. The capacitors are accompanied by a parallel protective system that will prevent damage to the capacitors under power system events (faults).
7 Series Capacitor Operation During Line Faults And The Resulting Equivalent Impedance
8 Equivalent Impedance During Faults This section we will discuss the following types of faults: Low Current Faults High Current Faults Medium Current Faults
9 Equivalent Impedance During Low Current Faults
10 Equivalent Impedance During Low Current Faults Low current faults summarized Current primarily in the Capacitors Very little MOV current Bank voltage less than protective level Impedance ~= the Capacitive Reactance of the Bank Resulting impedance is almost purely the capacitive reactance
11 Equivalent Impedance During High Current Faults
12 Equivalent Impedance During High Current Faults High current faults summarized Current primarily in the MOVs Very little Capacitor current Bank voltage equal to protective level Impedance ~= small Resistance Resulting impedance approximates a small resistance
13 Equivalent Impedance during Medium Current Faults Medium Current Faults
14 Equivalent Impedance During Medium Current Faults Medium current faults summarized: Current is shared in the MOVs and the Capacitors Capacitors conduct during first part of the half cycle, MOV conduct during the second part of the half cycle Bank voltage less than protective level, but becoming more rectangular Impedance = percentage of the Resistive-Capacitive Reactance of the bank Resulting impedance approximates a resistive and capacitive reactance
15 Equivalent Impedance During Faults Resulting Impedance as seen by the relay Series Capacitors affect the impedance as seen by the relay The resulting impedance may fall outside the relay operating characteristic If severe enough may even cause directional discrimination
16 Effects of Series Capacitors On Line Protection Relaying
17 Series Capacitors On Line Protection Relaying Overreach Conventional distance relays operated by comparing an operating quantity with a stabilizing quantity. Stabilizing quantity as seen by the relay is a voltage drop developed by measured current on line model and is affected by system impedance and fault location. Overreach is caused by the relay not including the negative reactance of the capacitor banks in the impedance model of the line Can cause unnecessary sequential line tripping
18 Series Capacitors On Line Protection Relaying Voltage Inversion SC Inserted SC Bypassed Pre-Fault Voltage Source Fault Voltage -jx c V R jx S jx L I f Relay Fault V R = I f x jx L V R = I f x j(x L - X C ) V R Source Relay SC Bank Fault With the SC bypassed, the voltage at the relay point, V R, is equal to the voltage drop on the line and will lead fault current, I f. With the SC inserted, I f will increase due to lower overall impedance and the relay voltage, V R, will be equal to the voltage drop across the combination of the line and SC reactance. If X c > X L, the voltage at the relay point, V R, will lag fault current. In this case the voltage at the relay point is inverted. Voltage inversion can lead to directional discrimination problems at the relay.
19 Series Capacitors On Line Protection Relaying Current Inversion V R SC Bypassed Pre-Fault Voltage Source SC Inserted Fault Voltage -jx c V R jx S jx L I f Relay Fault Source Relay SC Bank Fault With the SC bypassed, fault current normally flows from the power source towards the fault point and fault current will lag source voltage. With the SC inserted, two conditions could exist, either the resultant reactance (X s X c + X L ) is greater than or less zero. When greater than zero, the condition is similar to when the SC is bypassed. When less than zero, the resultant reactance is capacitive and fault current will lead source voltage. This condition is called current inversion. Current inversion can adversely affect distance relays and needs to be examined when the possibility exists.
20 Series Capacitors On Line Protection Relaying Transients Most transient problems for relays on series compensated lines occur due to subsynchronous oscillations as they cannot be filtered out unless a very long window is used and the relay is effectively slowed down. These oscillations may increase the operating time of distance protection and cause overreaching of instantaneous distance protection zones.
21 Series Capacitors On Line Protection Relaying Location of Instrument Transformers The selection of the VT and CT locations for line end Series Capacitor banks play an important part in the performance of the protection scheme. Bus Side (CT1 and VT1): Protection is subject to possible voltage and current inversion as well as overreach conditions for line faults. However, the Series Capacitor Bank is in the protection zone and does not require any additional or special protection.
22 Series Capacitors On Line Protection Relaying Location of Instrument Transformers Line Side (CT2 and VT2): Protection is less subject to possible voltage inversion conditions for line faults; however for close in and reverse faults, the negative reactance may affect the protection. The Series Capacitor Banks is not in the protection zone and must be protected separately. Dual Side (CT1 and VT2): Protection is less subject to possible voltage inversion for line faults and the Series Capacitor Bank is in the protection zone, however it is subject to voltage inversion for reverse faults.
23 Series Capacitors On Line Protection Relaying Pilot Protection Schemes on SC Lines Pilot Protection schemes with distance and overcurrent elements - Susceptible to Overreach and Voltage and Current Inversion Pilot Protection schemes using current differential - Susceptible to Current Inversion
24 Mitigation Techniques
25 Mitigation Approaches Protective Zone Reach Reduction Relay Memory Action Adaptive Distance Reach Real Time Digital Simulation (RTDS) and Testing
26 Mitigation Approaches Protective Zone Reach Reduction Reducing the reach of the protective zones can help reduce the affects of overreach in some circumstances. Must be used carefully ensuring line is fully protected. Not fully effective in all cases.
27 Mitigation Approaches Relay Memory Action SC Inserted SC Bypassed Pre-Fault Voltage Source Fault Voltage -jx c V R jx S jx L I f Relay Fault V R V R = I f x jx L V R = I f x j(x L - X C ) Source Relay SC Bank Fault Memory action produces a short duration voltage equivalent to the pre-fault voltage. Can be used to help determine the direction of the fault and aid in proper tripping when voltage inversion is present. Care must be used when setting the duration of the memory action.
28 Mitigation Approaches Adaptive Distance Reach X Original Protective Zone Z Line w/sc Inserted Reach is dynamically reduced based on fault current Reduced Protective Zone Actual Reach for Low Fault Currents R The reach of the relay is dependent on the fault current. Z effective ( I f ) = Z set V/ I f * angle(z set) For high fault currents the reduction is small. For low fault currents the reduction is large. This effectively adapts the reach of the relay to the resulting impedance of the SC bank and therefore properly protects the line for most cases.
29 Mitigation Approaches Real Time Digital Simulation (RTDS) and Testing RTDS TRIP Inputs Current Signals Analog Amplifiers Relay 1 Relay 2 Voltage Signals RTDS Testing is used to test and prove the actual protection settings with the actual relay. An important step as actual relay performance and protection algorithms are difficult to model accurately and in some cases proprietary. Can also be used to test and compare the performance of multiple relay types over a large range of test conditions.
30 Mitigation Approaches Real Time Digital Simulation (RTDS) and Testing RTDS Testing will allow better performance assessments of relay operation. Visualization of the dynamic impedance trajectory can be used/superposed over calculated protective zones to optimize the protection settings based on expectations vs. tested results. RTDS testing is often used to test challenging conditions for the relays.
31 Summary Series Capacitor Banks have protection that operates differently depending on the severity of the fault. Resulting impedance of the banks affects line protection in different ways. There are mitigation approaches available to reduce the severity of the affect. RTDS testing is an important step to ensure the protection system operates correctly and as expected.
32 Look Out For... Further FACTS Educational Webinars For more information go to and select Contact
33 Questions? Opportunity to ask Paul and Luis questions Paul Datka GE Energy Consulting Principal Luis Polanco GE Energy Consulting Principal
34 THANK YOU!
ALPS. Advanced Line Protection System
ALPS Advanced Line Protection System Modified Fourier Calculation High Speed Sampling Phaselet Calculation Variable Window Digital Mimic 2 10 5 EXECUTE PHASELET CALCULATION AND PROTECTION ALGORITHMS High
More informationDetermination of Fault Location in Shunt Capacitor Bank through Compensated Neutral Current
International Journal of Advances in Scientific Research and Engineering (ijasre) E-ISSN : 2454-8006 DOI: http://dx.doi.org/10.7324/ijasre.2018.32630 Volume 4, Issue 3 March - 2018 Determination of Fault
More informationHow to measure complex impedance at high frequencies where phase measurement is unreliable.
Objectives In this course you will learn the following Various applications of transmission lines. How to measure complex impedance at high frequencies where phase measurement is unreliable. How and why
More informationKINGS COLLEGE OF ENGINEERING Punalkulam
KINGS COLLEGE OF ENGINEERING Punalkulam 613 303 DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING POWER SYSTEM ANALYSIS QUESTION BANK UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A (TWO MARK
More informationA Novel Distance Relaying Scheme to Mitigate Phase Faults on Doubly Fed Transmission Lines
A Novel Distance Relaying Scheme to Mitigate Phase Faults on Doubly Fed Transmission Lines J.Monisha 1, S.Natarajan 2 1 SEEE, SASTRA UNIVERSITY,Thanjavur,Tamilnadu-613 41 2 SEEE, SASTRA UNIVERSITY,Thanjavur,Tamilnadu-613
More informationEE 451 Power System Stability
EE 451 Power System Stability Power system operates in synchronous mode Power system is subjected to a wide range of disturbances (small and large) - Loads and generation changes - Network changes - Faults
More informationPOWER FACTOR IN THE DIGITAL AGE A N E N V I R O N M E N T A L P O T E N T I A L S W H I T E P A P E R. Power Quality For The Digital Age
Power Quality For The Digital Age POWER FACTOR IN THE DIGITAL AGE A N E N V I R O N M E N T A L P O T E N T I A L S W H I T E P A P E R Introduction One method to measure the efficiency of the electrical
More informationPerformance Comparison Between Mho Elements and Incremental Quantity-Based Distance Elements
Performance Comparison Between Mho Elements and Incremental Quantity-Based Distance Elements Gabriel Benmouyal, Normann Fischer, and Brian Smyth, Schweitzer Engineering Laboratories, Inc. Abstract Mho
More information1 Unified Power Flow Controller (UPFC)
Power flow control with UPFC Rusejla Sadikovic Internal report 1 Unified Power Flow Controller (UPFC) The UPFC can provide simultaneous control of all basic power system parameters ( transmission voltage,
More informationAC Circuits Homework Set
Problem 1. In an oscillating LC circuit in which C=4.0 μf, the maximum potential difference across the capacitor during the oscillations is 1.50 V and the maximum current through the inductor is 50.0 ma.
More informationConsiderations in Choosing Directional Polarizing Methods for Ground Overcurrent Elements in Line Protection Applications
Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent Elements in Line Protection Applications Technical Report to the Line Protection Subcommittee of the PES, Power Systems
More informationTHE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session
Name: Student ID: Signature: THE UNIVERSITY OF NEW SOUTH WALES School of Electrical Engineering & Telecommunications FINALEXAMINATION Session 00 ELEC46 Power System Analysis TIME ALLOWED: 3 hours TOTAL
More informationElectrical Circuits Lab Series RC Circuit Phasor Diagram
Electrical Circuits Lab. 0903219 Series RC Circuit Phasor Diagram - Simple steps to draw phasor diagram of a series RC circuit without memorizing: * Start with the quantity (voltage or current) that is
More informationECE 476. Exam #2. Tuesday, November 15, Minutes
Name: Answers ECE 476 Exam #2 Tuesday, November 15, 2016 75 Minutes Closed book, closed notes One new note sheet allowed, one old note sheet allowed 1. / 20 2. / 20 3. / 20 4. / 20 5. / 20 Total / 100
More informationNEW DESIGN OF GROUND FAULT PROTECTION
NEW DESIGN OF GROUND FAULT PROTECTION The 71st Annual Conference for Protective Relay Engineers Siemens AG 2018 All rights reserved. siemens.com/energy-management Why do we need ground fault protection?
More informationFault Calculation Methods
ELEC9713 Industrial and Commercial Power Systems Fault Calculation Methods There are two major problems that can occur in electrical systems: these are open circuits and short circuits. Of the two, the
More informationBASIC PRINCIPLES. Power In Single-Phase AC Circuit
BASIC PRINCIPLES Power In Single-Phase AC Circuit Let instantaneous voltage be v(t)=v m cos(ωt+θ v ) Let instantaneous current be i(t)=i m cos(ωt+θ i ) The instantaneous p(t) delivered to the load is p(t)=v(t)i(t)=v
More informationANALYSIS OF SUBSYNCHRONOUS RESONANCE EFFECT IN SERIES COMPENSATED LINE WITH BOOSTER TRANSFORMER
ANALYSIS OF SUBSYNCHRONOUS RESONANCE EFFECT IN SERIES COMPENSATED LINE WITH BOOSTER TRANSFORMER G.V.RAJASEKHAR, 2 GVSSNS SARMA,2 Department of Electrical Engineering, Aurora Engineering College, Hyderabad,
More informationStudy of Transient Behaviour of the Capacitor Voltage Transformer
Study of Transient Behaviour of the Capacitor Voltage Transformer Amit Kumar 1, Dr. A. G. Thosar 2, Vivek Moroney 3 PG Student [EPS], Dept. of EE, Government College of Engineering, Aurangabad, Maharashtra,
More informationCapacitor Application Issues
Capacitor Application Issues Thomas Blooming, P.E. Daniel J. Carnovale, P.E. IEEE Industry Applications Society 53 rd Pulp & Paper Industry Technical Conf. Williamsburg, Virginia June 24-29, 2007 Introduction
More informationQUESTION BANK ENGINEERS ACADEMY. Power Systems Power System Stability 1
ower ystems ower ystem tability QUETION BANK. A cylindrical rotor generator delivers 0.5 pu power in the steady-state to an infinite bus through a transmission line of reactance 0.5 pu. The generator no-load
More informationSelecting the current rating for equipment
Selecting the current rating for equipment 1. Rated current: the maximum continuous load current. Short-time withstand current: thermal withstand current term term is given for 1s or 3s short circuit current
More informationChapter 8: Unsymmetrical Faults
Chapter 8: Unsymmetrical Faults Introduction The sequence circuits and the sequence networks developed in the previous chapter will now be used for finding out fault current during unsymmetrical faults.
More informationChapter 13. Capacitors
Chapter 13 Capacitors Objectives Describe the basic structure and characteristics of a capacitor Discuss various types of capacitors Analyze series capacitors Analyze parallel capacitors Analyze capacitive
More informationRESULTS OF ON-GRID OPERATION OF SUPERCONDUCTOR DYNAMIC SYNCHRONOUS CONDENSER
1 RESULTS OF ON-GRID OPERATION OF SUPERCONDUCTOR DYNAMIC SYNCHRONOUS CONDENSER Dr. Swarn S. Kalsi, David Madura, and Michael Ross American Superconductor Corporation (USA) Abstract: A high-temperature
More informationLecture 9 Time Domain vs. Frequency Domain
. Topics covered Lecture 9 Time Domain vs. Frequency Domain (a) AC power in the time domain (b) AC power in the frequency domain (c) Reactive power (d) Maximum power transfer in AC circuits (e) Frequency
More informationTutorial on Shunt Capacitor Banks Design, Application and Protection Considerations
Tutorial on Shunt Capacitor Banks Design, Application and Protection Considerations Presenter: Pratap Mysore, HDR Minnesota Power Systems Conference November 12, 2015 Topics Covered Power system Considerations,
More informationChapter 3 AUTOMATIC VOLTAGE CONTROL
Chapter 3 AUTOMATIC VOLTAGE CONTROL . INTRODUCTION TO EXCITATION SYSTEM The basic function of an excitation system is to provide direct current to the field winding of the synchronous generator. The excitation
More informationPower System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur
Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur Lecture - 9 Transmission Line Steady State Operation Welcome to lesson 9, in Power
More informationFault Locating PRESENTED BY ERIK SCHELLENBERG IDAHO POWER
Fault Locating PRESENTED BY ERIK SCHELLENBERG IDAHO POWER Topics Impedance Based Reactance Method Takagi Method Modifications to Takagi Method TWS & Double Ended Negative Sequence One Line Equivalent Thevenin
More informationChapter 8 VOLTAGE STABILITY
Chapter 8 VOTAGE STABIITY The small signal and transient angle stability was discussed in Chapter 6 and 7. Another stability issue which is important, other than angle stability, is voltage stability.
More informationPOWER SEMICONDUCTOR BASED ELECTRIC DRIVES
POWER SEMICONDUCT BASED ELECTRIC DRIVES [Time: 3 Hrs] [Max. Marks: 80] Instructions: Solve any six questions from Q.No (1 or 2), Q.No (3 or 4), Q.No (5 or 6), Q.No (7 or 8), Q.No (9 or 10), Q.No (11 or
More informationUnit 21 Capacitance in AC Circuits
Unit 21 Capacitance in AC Circuits Objectives: Explain why current appears to flow through a capacitor in an AC circuit. Discuss capacitive reactance. Discuss the relationship of voltage and current in
More informationDistance Elements: Linking Theory With Testing
Distance Elements: Linking Theory With Testing Fernando Calero Schweitzer Engineering Laboratories, Inc. Revised edition released August 009 Previously presented at the 6nd Annual Conference for Protective
More informationImplementing an Intelligent Error Back Propagation (EBP) Relay in PSCAD TM /EMTDC 4.2.1
1 Implementing an Intelligent Error Back Propagation (EBP) Relay in PSCAD TM /EMTDC 4.2.1 E. William, IEEE Student Member, Brian K Johnson, IEEE Senior Member, M. Manic, IEEE Senior Member Abstract Power
More informationDAMPING OF SUBSYNCHRONOUS MODES OF OSCILLATIONS
Journal of Engineering Science and Technology Vol. 1, No. 1 (26) 76-88 School of Engineering, Taylor s College DAMPING OF SUBSYNCHRONOUS MODES OF OSCILLATIONS JAGADEESH PASUPULETI School of Engineering,
More informationATP-EMTP evaluation of relaying algorithms for series-compensated line
AP-EMP evaluation o relaying algorithms or series-compensated line M. M. Saha, E. osolowski, J. Izykowski, P. Pierz Abstract A group o the algorithms aimed at measuring a ault-loop impedance or digital
More informationRequest Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.
Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager. 1 -A - Introduction - Thank for your purchasing MITSUBISHI ELECTRIC MELPRO TM D Series Digital Protection
More informationElectromagnetic Oscillations and Alternating Current. 1. Electromagnetic oscillations and LC circuit 2. Alternating Current 3.
Electromagnetic Oscillations and Alternating Current 1. Electromagnetic oscillations and LC circuit 2. Alternating Current 3. RLC circuit in AC 1 RL and RC circuits RL RC Charging Discharging I = emf R
More informationThe Mathematical Model of Power System with Static Var Compensator in Long Transmission Line
American Journal of Applied Sciences 9 (6): 846-850, 01 ISSN 1546-939 01 Science Publications The Mathematical Model of Power System with Static Var Compensator in Long Transmission Line Prechanon Kumkratug
More informationPower Factor Improvement
Salman bin AbdulazizUniversity College of Engineering Electrical Engineering Department EE 2050Electrical Circuit Laboratory Power Factor Improvement Experiment # 4 Objectives: 1. To introduce the concept
More informationLow Frequency Transients
Page 1 IEEE Power Engineering Society Summer Meeting Edmonton, July 18-22, 1999 Tutorial: Power System Overvoltages Low Frequency Transients Presented by Bruce Mork Work Done by Slow Transients Task Force
More informationELECTRIC POWER CIRCUITS BASIC CONCEPTS AND ANALYSIS
Contents ELEC46 Power ystem Analysis Lecture ELECTRC POWER CRCUT BAC CONCEPT AND ANALY. Circuit analysis. Phasors. Power in single phase circuits 4. Three phase () circuits 5. Power in circuits 6. ingle
More informationThe Mathematical Model of Power System with Thyristor Controlled Series Capacitor in Long Transmission Line
American Journal of Applied Sciences 9 (5): 654-658, 01 ISSN 1546-939 01 Science Publications The Mathematical Model of Power System with Thyristor Controlled Series Capacitor in Long Transmission Line
More informationSection 4. Nonlinear Circuits
Section 4 Nonlinear Circuits 1 ) Voltage Comparators V P < V N : V o = V ol V P > V N : V o = V oh One bit A/D converter, Practical gain : 10 3 10 6 V OH and V OL should be far apart enough Response Time:
More informationNEW RECLOSER CHARACTERISTIC TO IMPROVE FUSE SAVING IN DISTRIBUTION NETWORKS WITH DISTRIBUTED GENERATION
Rev. Roum. Sci. Techn. Électrotechn. et Énerg. Vol. 62, 3, pp. 240 245, Bucarest, 2017 NEW RECLOSER CHARACTERISTIC TO IMPROVE FUSE SAVING IN DISTRIBUTION NETWORKS WITH DISTRIBUTED GENERATION SADEGH JAMALI,
More informationSSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL
1 SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL Power Systems: Generation, Transmission and Distribution Power Systems: Generation, Transmission and Distribution Power Systems:
More informationDISTANCE RELAY SETTINGS
DISTANCE RELAY SETTINGS Introduction Commonly used >33kV Determine whether impedance measured is within set characteristic. Non-unit protection (boundaries not defined) During normal operation impedance
More informationModule 3 : Sequence Components and Fault Analysis
Module 3 : Sequence Components and Fault Analysis Lecture 12 : Sequence Modeling of Power Apparatus Objectives In this lecture we will discuss Per unit calculation and its advantages. Modeling aspects
More informationCHAPTER 6 STEADY-STATE ANALYSIS OF SINGLE-PHASE SELF-EXCITED INDUCTION GENERATORS
79 CHAPTER 6 STEADY-STATE ANALYSIS OF SINGLE-PHASE SELF-EXCITED INDUCTION GENERATORS 6.. INTRODUCTION The steady-state analysis of six-phase and three-phase self-excited induction generators has been presented
More informationMaintenance/ Discontinued
oltage Regulators N7xx/N7xxF Series 3-pin positive output voltage regulator ( type) Overview The N7xx series and the N7xxF series are 3- pin, fixed positive output type monolithic voltage regulators. Stabilized
More informationAnalysis of Very Fast Transients in EHV Gas Insulated Substations
Analysis of Very Fast Transients in EHV Gas Insulated Substations A.Raghu Ram, k. Santhosh Kumar raghuram_a@yahoo.com,ksanthosheee@gmail.com Abstract: Gas insulated switchgear (GIS) has been in operation
More informationF F FAULT CURRENT Prospective. 1. Introduction. 2. Types of fault conditions
FAULT CURRENT F F13-13 FAULT CURRENT - Contents 1. Introduction 2. Types of fault conditions 3 fault current must be determined 3.1 Purposes for which of prospective fault current magnitudes are used 3.2
More informationSinusoidal Steady-State Analysis
Sinusoidal Steady-State Analysis Almost all electrical systems, whether signal or power, operate with alternating currents and voltages. We have seen that when any circuit is disturbed (switched on or
More informationPower System Engineering Prof. Debapriya Das Department of Electrical Engineering Indian Institute of Technology, Kharagpur
Power System Engineering Prof. Debapriya Das Department of Electrical Engineering Indian Institute of Technology, Kharagpur Lecture 41 Application of capacitors in distribution system (Contd.) (Refer Slide
More informationNonlinear Control Design of Series FACTS Devices for Damping Power System Oscillation
American Journal of Applied Sciences 8 (): 4-8, 0 ISSN 546-939 00 Science Publications Nonlinear Control Design of Series FACTS Devices for Damping Power System Oscillation Prechanon Kumkratug Department
More informationCapacitors. Dominik Pieniazek, P.E. VI Engineering, LLC Nicholas A. Losito Jr. Castle Power Solutions, LLC
Capacitors Dominik Pieniazek, P.E. VI Engineering, LLC Nicholas A. Losito Jr. Castle Power Solutions, LLC Outline Day 1 Basic Power Calculations Capacitor Fundamentals Capacitor Ratings Capacitor Application
More informationEE 6501 POWER SYSTEMS UNIT I INTRODUCTION
EE 6501 POWER SYSTEMS UNIT I INTRODUCTION PART A (2 MARKS) 1. What is single line diagram? A Single line diagram is diagrammatic representation of power system in which the components are represented by
More informationESTIMATION OF CAPACITOR BANK SWITCHING OVERVOLTAGES USING ARTIFICIAL NEURAL NETWORK
ESTIMATION OF CAPACITOR BANK SWITCHING OVERVOLTAGES USING ARTIFICIAL NEURAL NETWORK sayed A. Ward mahmoud N. Ali drsayedw@yahoo.com Mahmoud.nour@yahoo.com hesham Said eng_hesham19902011@yahoo.com Faculty
More informationRadio Frequency Electronics
Radio Frequency Electronics Preliminaries III Lee de Forest Born in Council Bluffs, Iowa in 1873 Had 180 patents Invented the vacuum tube that allows for building electronic amplifiers Vacuum tube started
More informationConsider a simple RC circuit. We might like to know how much power is being supplied by the source. We probably need to find the current.
AC power Consider a simple RC circuit We might like to know how much power is being supplied by the source We probably need to find the current R 10! R 10! is VS Vmcosωt Vm 10 V f 60 Hz V m 10 V C 150
More informationTransformer. Transformer comprises two or more windings coupled by a common magnetic circuit (M.C.).
. Transformers Transformer Transformer comprises two or more windings coupled by a common magnetic circuit (M.C.). f the primary side is connected to an AC voltage source v (t), an AC flux (t) will be
More informationControl Strategies for Microgrids
Control Strategies for Microgrids Ali Mehrizi-Sani Assistant Professor School of Electrical Engineering and Computer Science Washington State University Graz University of Technology Thursday, November
More informationCHAPTER 2 OVERVOLTAGE DUE TO SELF-EXCITATION AND INRUSH CURRENT DUE TO CAPACITOR SWITCHING
20 CHAPTER 2 OVERVOLTAGE DUE TO SELF-EXCITATION AND INRUSH CURRENT DUE TO CAPACITOR SWITCHING 2.1 INTRODUCTION It is becoming more common to find use of shunt capacitors for the application of powerfactor
More informationFigure 1-44: 4-Wire Wye PT Configurations
Principles and Practice ii) PT onnection There are two most common PT combinations on three-phase, three-wire systems as shown in Figure 1-43. The vector diagrams are identical between PT configurations
More informationPHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA.
PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA What are phasors??? In normal practice, the phasor represents the rms maximum value of the positive half cycle of the sinusoid
More informationSymmetrical Components. References
Symmetrical Components Review of basics Sequence Equivalents Fault Analysis Symmetrical Components Fall 28 References Your power systems analysis class text book NPAG: Chapter 4 (analysis) Chapter 5 (equipment
More informationECE 420. Review of Three Phase Circuits. Copyright by Chanan Singh, Panida Jirutitijaroen, and Hangtian Lei, For educational use only-not for sale.
ECE 40 Review of Three Phase Circuits Outline Phasor Complex power Power factor Balanced 3Ф circuit Read Appendix A Phasors and in steady state are sinusoidal functions with constant frequency 5 0 15 10
More informationRailway Research. Study of Superconducting Fault Current Limiter Device in a AC Railway System. 1. Introduction. International Journal of
International Journal of Railway Research, (2015), Vol.2, No1, pp 10-14 ISSN: 236153768187 International Journal of Railway Research Study of Superconducting Fault Current Limiter Device in a AC Railway
More information400 Volts, 50HZ 480 Volts, 60HZ 600 Volts, 60HZ TECHNICAL REFERENCE MANUAL
400 Volts, 50HZ 480 Volts, 60HZ 600 Volts, 60HZ TECHNICAL REFERENCE MANUAL FORM: MAP-TRM-E REL. July 2013 REV. 015 2013 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation Matrix AP Harmonic
More informationExamination paper for TFY4185 Measurement Technique/ Måleteknikk
Page 1 of 14 Department of Physics Examination paper for TFY4185 Measurement Technique/ Måleteknikk Academic contact during examination: Patrick Espy Phone: +47 41 38 65 78 Examination date: 15 August
More informationPerformance Improvement of the Radial Distribution System by using Switched Capacitor Banks
Int. J. on Recent Trends in Engineering and Technology, Vol. 10, No. 2, Jan 2014 Performance Improvement of the Radial Distribution System by using Switched Capacitor Banks M. Arjun Yadav 1, D. Srikanth
More informationTHF / 1SCC330001M THF 1S1 C
THF 2247 0191/ 1SCC330001M5803 34 THF 1S1 C Installation and Operation Instruction for THF Filter and Protective Unit THF 1_ THF 1S_ THF 1BS_ General guidelines Due to the fact that most UK building earth
More informationModel M3484 Industrial Line Noise Filter Module Customer Reference Manual
Model M3484 Industrial Line Noise Filter Module Customer Reference Manual Web: www.bonitron.com Tel: 615-244-2825 Email: info@bonitron.com Bonitron, Inc. Bonitron, Inc. Nashville, TN An industry leader
More informationSeries and Parallel ac Circuits
Series and Parallel ac Circuits 15 Objectives Become familiar with the characteristics of series and parallel ac networks and be able to find current, voltage, and power levels for each element. Be able
More informationmywbut.com Lesson 16 Solution of Current in AC Parallel and Seriesparallel
esson 6 Solution of urrent in Parallel and Seriesparallel ircuits n the last lesson, the following points were described:. How to compute the total impedance/admittance in series/parallel circuits?. How
More informationPHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA
PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA I m VECTOR. Cause I m committing crimes with magnitude and direction at the same time!" What are phasors??? In normal practice,
More informationSimulating a Power System
Simulating a Power System Presented by Prof. Tyrone Fernando School of Electrical and Electronic Engineering (EECE), University of Western Australia (UWA) 1. Motivations In an actual power system, it is
More informationDamping SSR in Power Systems using Double Order SVS Auxiliary Controller with an Induction Machine Damping Unit and Controlled Series Compensation
614 Damping SSR in Power Systems using Double Order SVS Auxiliary Controller with an Induction Machine Damping Unit and Controlled Series Compensation Sushil K Gupta, Narendra Kumar and A K Gupta Abstract--This
More informationMicro-grid to System Synchronization Based on Pre-Insertion Impedance Method (Version 1.0) By Peter Zhou University of Alberta Jan 30 th, 2015
Micro-grid to System Synchronization Based on Pre-Insertion Impedance Method (Version 1.0) By Peter Zhou University of Alberta Jan 30 th, 2015 Outline 1. What is Synchronization? 2. Synchronization Concerns?
More informationLecture 11 - AC Power
- AC Power 11/17/2015 Reading: Chapter 11 1 Outline Instantaneous power Complex power Average (real) power Reactive power Apparent power Maximum power transfer Power factor correction 2 Power in AC Circuits
More informationPower Systems - Basic Concepts and Applications - Part I
PDHonline Course E104A (1 PDH) Power Systems - Basic Concepts and Applications - Part I Instructor: Shih-Min Hsu, Ph.D., P.E. 01 PDH Online PDH Center 57 Meadow Estates Drive Fairfax, VA 030-6658 Phone
More informationChapter 32A AC Circuits. A PowerPoint Presentation by Paul E. Tippens, Professor of Physics Southern Polytechnic State University
Chapter 32A AC Circuits A PowerPoint Presentation by Paul E. Tippens, Professor of Physics Southern Polytechnic State University 2007 Objectives: After completing this module, you should be able to: Describe
More informationECE 325 Electric Energy System Components 5 Transmission Lines. Instructor: Kai Sun Fall 2015
ECE 325 Electric Energy System Components 5 Transmission Lines Instructor: Kai Sun Fall 2015 1 Content (Materials are from Chapter 25) Overview of power lines Equivalent circuit of a line Voltage regulation
More informationSwitched Capacitor Circuits I. Prof. Paul Hasler Georgia Institute of Technology
Switched Capacitor Circuits I Prof. Paul Hasler Georgia Institute of Technology Switched Capacitor Circuits Making a resistor using a capacitor and switches; therefore resistance is set by a digital clock
More informationFACULTY OF ENGINEERING LAB SHEET. IM1: Wheatstone and Maxwell Wien Bridges
FCULTY OF ENGINEEING LB SHEET EEL96 Instrumentation & Measurement Techniques TIMESTE 08-09 IM: Wheatstone and Maxwell Wien Bridges *Note: Please calculate the computed values for Tables. and. before the
More informationPower System Stability GENERATOR CONTROL AND PROTECTION
Power System Stability Outline Basis for Steady-State Stability Transient Stability Effect of Excitation System on Stability Small Signal Stability Power System Stabilizers Speed Based Integral of Accelerating
More informationFatima Michael College of Engineering & Technology
ANNA UNIVERSITY AFFILIATED COLLEGES BE EEE SEMESTER VI EE2353 - HIGH VOLTAGE ENGINEERING UNIT IOVER VOLTAGES IN ELECTRICAL POWER SYSTEMS 1. What is surge arrester? 2. Name the sources of switching surges.
More informationPower and Energy Measurement
Power and Energy Measurement EIE 240 Electrical and Electronic Measurement April 24, 2015 1 Work, Energy and Power Work is an activity of force and movement in the direction of force (Joules) Energy is
More informationPOWER SWING AND OUT-OF-STEP CONSIDERATIONS ON TRANSMISSION LINES
POWER SWING AND OUT-OF-STEP CONSIDERATIONS ON TRANSMISSION LINES 1 / 59 2005-07-19 POWER SWING AND OUT-OF-STEP CONSIDERATIONS ON TRANSMISSION LINES A report to the Power System Relaying Committee Of the
More informationDetection of Broken Conductor with Ground Contact Faults in Medium Voltage Power Networks
FACTA UNIVERSITATIS (NIŠ) SER.: ELEC. ENERG. vol.19, no. 3, December 006, 49-438 Detection of Broken Conductor with Ground Contact Faults in Medium Voltage Power Networks Dumitru Toader, Ştefan Haraguş,
More informationADVANCED ISLANDING DETECTION METHODS FOR SINGLE PHASE GRID CONNECTED PV INVERTERS
ADVANCED ISLANDING DETECTION METHODS FOR SINGLE PHASE GRID CONNECTED PV INVERTERS by Bahador Mohammadpour A thesis submitted to the Department of Electrical and Computer Engineering In conformity with
More informationSSSC Modeling and Damping Controller Design for Damping Low Frequency Oscillations
SSSC Modeling and Damping Controller Design for Damping Low Frequency Oscillations Mohammed Osman Hassan, Ahmed Khaled Al-Haj Assistant Professor, Department of Electrical Engineering, Sudan University
More informationMitigation of Distributed Generation Impact on Protective Devices in a Distribution Network by Superconducting Fault Current Limiter *
Energy and Power Engineering, 2013, 5, 258-263 doi:10.4236/epe.2013.54b050 Published Online July 2013 (http://www.scirp.org/journal/epe) Mitigation of Distributed Generation Impact on Protective Devices
More informationSchedule. ECEN 301 Discussion #20 Exam 2 Review 1. Lab Due date. Title Chapters HW Due date. Date Day Class No. 10 Nov Mon 20 Exam Review.
Schedule Date Day lass No. 0 Nov Mon 0 Exam Review Nov Tue Title hapters HW Due date Nov Wed Boolean Algebra 3. 3.3 ab Due date AB 7 Exam EXAM 3 Nov Thu 4 Nov Fri Recitation 5 Nov Sat 6 Nov Sun 7 Nov Mon
More informationCHAPTER 2 LOAD FLOW ANALYSIS FOR RADIAL DISTRIBUTION SYSTEM
16 CHAPTER 2 LOAD FLOW ANALYSIS FOR RADIAL DISTRIBUTION SYSTEM 2.1 INTRODUCTION Load flow analysis of power system network is used to determine the steady state solution for a given set of bus loading
More informationChapter 10: Sinusoids and Phasors
Chapter 10: Sinusoids and Phasors 1. Motivation 2. Sinusoid Features 3. Phasors 4. Phasor Relationships for Circuit Elements 5. Impedance and Admittance 6. Kirchhoff s Laws in the Frequency Domain 7. Impedance
More informationExploring Autonomous Memory Circuit Operation
Exploring Autonomous Memory Circuit Operation October 21, 2014 Autonomous Au-to-no-mous: Merriam-Webster Dictionary (on-line) a. Existing independently of the whole. b. Reacting independently of the whole.
More informationHigher National Unit specification: general information
Higher National Unit specification: general information Unit code: FY9E 34 Superclass: XJ Publication date: November 2011 Source: Scottish Qualifications Authority Version: 01 Unit purpose This Unit is
More informationINSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous)
INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad - 500 043 ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK Course Name : Computer Methods in Power Systems Course Code : A60222
More information