Reminder: Electric Lighting Design Analysis Tools

Size: px
Start display at page:

Download "Reminder: Electric Lighting Design Analysis Tools"

Transcription

1 ELECTRIC LIGHTING DESIGN ANALYSIS Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1 Reminder: Electric Lighting Design Analysis Tools Look-ups: pre-canned solutions provided by product manufacturers to speed adoption of solutions in graphic or tabular format Correlations: product-generic methods such as the zonal cavity method applicable to many solutions First principles: employing basic physics relationships such as the point-to-point method Computer simulations: to tap the data storage and number crunching capabilities of computers often coupled with rendering routines Analog mock-ups: not common except for proof-ofconcept demonstrations Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 2 1

2 Illuminances of Concern Design illuminance = design criterion The target or benchmark that defines success Initial illuminance = the illuminance experienced upon first operating a system (space and equipment are new) LLF is set to 1.0 to estimate initial illuminance Maintained illuminance = the illuminance found in a space after some defined time (perhaps 2, 4, 5 years) Condition that occurs when LLF assumes a real value Maintained illuminance must equal or exceed design illuminance in a successful system Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 3 Design Tool: Lookup Tables product driven and for a specific lamp-luminaire combination in this case a recessed can-type downlight Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 4 2

3 Design Tool: Sample Layout Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 5 Design Tool: Comparative Layouts Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 6 3

4 Design Tool: Zonal Cavity Method this method applies ONLY to uniform illuminance situations and is embodied in a worksheet >> Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 7 Zonal Cavity Method: The Bottom Line # luminaires = (illuminance) (area) (lumens per luminaire) (CU) (LLF) where, illuminance = design illuminance CU = coefficient of utilization LLF = light loss factor area = task (lighted) area lumens per luminaire = lamp lumens x lamps per fixture Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 8 4

5 Zonal Cavity Method: A Second Bottom Line maintained illuminance = (# luminaires)(lumens per luminaire)(cu)(llf) (area) where, # luminaires = a realistic design luminaire count lumens per luminaire = lamp lumens x lamps per fixture CU = coefficient of utilization LLF = light loss factor area = task area Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 9 Zonal Cavity Method: An Unstated Bottom Line initial illuminance = (# luminaires)(lumens per luminaire)(cu)(1) (area) where, # luminaires = a realistic design luminaire count lumens per luminaire = lamp lumens x lamps per fixture CU = coefficient of utilization LLF = has been set to 1.0 area = task area Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 10 5

6 Zonal Cavity Method: Key Metrics CU = coefficient of utilization -- the efficiency (lumens/lumens) of a particular luminaire installed in a particular space in delivering light from lamps to task -- is dimensionless (decimal value) means 65% of lamp light reaches task Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 11 Zonal Cavity Method: Key Metrics LLF = light loss factor(s) -- LLF collectively represents several factors that will cause a deviation between initial and maintained illuminance -- dimensionless (decimal value) LLF means a 25% loss -- total LLF = product of individual LLFs Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 12 6

7 Light Loss Factors Fixed (non-recoverable) factors Non-standard voltage Non-standard ballast Non-standard ambient temperature these factors essentially adjust lamp/ballast performance to account for non-catalog conditions; these effects are generally constant over time (they don t escalate; and they can t be mitigated by normal maintenance) Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 13 Light Loss Factors Progressive (recoverable) factors Burnouts Lamp lumen depreciation Luminaire dirt depreciation Room surface dirt depreciation Luminaire surface depreciation these factors essentially adjust illuminance estimates to account for wear and tear over time; the effects change over time (and can be reversed at a cost) Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 14 7

8 Zonal Cavity Method general data correlators LLFs calculations Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 15 Zonal Cavity Walkthrough start with design illuminance; luminaire selection (a trial selection); and lamp selection (perhaps also a trial) Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 16 8

9 Zonal Cavity Walkthrough select a luminaire (from IESNA Lighting Handbook, textbook, or web site); find CU data for the fixture after the correlating factors are assembled Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 17 Zonal Cavity Walkthrough the IESNA Lighting Handbook, has typical CU data (and more information) for many generic fixture types; manufacturers www sites will have specific fixture CU data Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 18 9

10 Zonal Cavity Walkthrough photometrics basic properties cross section CU values initial luminaire selection will be based upon meeting some design criteria; these criteria can be roughly evaluated from sample luminaire data Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 19 Zonal Cavity Walkthrough find lamp data; from generic tables or manufacturer s catalog information for zonal cavity method need initial lumens and lumen maintenance (lamp LLF) Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 20 10

11 Zonal Cavity Walkthrough define space geometry and reflectances, calculate the correlation variables (cavity ratios and effective reflectances); determine the CU value Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 21 Zonal Cavity Walkthrough extracting CU values to do so you need to know RCR, rho cc, and rho w (rho fc is assumed to be 20%) see next slides Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 22 11

12 Zonal Cavity Walkthrough start with space dimensions (L, W, and H of three cavities ) Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 23 Zonal Cavity Walkthrough calculate cavity ratios for three cavities using above equations (or look-up tables) a non-existent cavity has a ratio of 0 (h = 0) Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 24 12

13 Zonal Cavity Walkthrough cavity ratios can be calculated for non-rectilinear spaces using a more basic equation Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 25 Zonal Cavity Walkthrough rho w = (rho 1 )(area 1 ) + (rho 2 )(area 2 ) + area1 + area2 + wall reflectance (rho w ) is the weighted average reflectance of wall surfaces rho = visible reflectance (%) area = surface area 1, 2, are different finishes or materials in the cavity being considered Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 26 13

14 Zonal Cavity Walkthrough establish effective cavity reflectances for ceiling and floor cavities using this chart; ceiling/floor reflectance, wall reflectance, and cavity ratio are variables Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 27 Zonal Cavity Walkthrough CU adjustment factors are used if floor cavity reflectance (rho fc ) is not 20% Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 28 14

15 Zonal Cavity Walkthrough spacing criterion is the maximum distance luminaires may be spaced apart (usually taken as center line to center line) if illuminance is to be reasonably uniform; given as a multpile of mounting height above task CU values are extracted from data tables on the basis of rho cc, rho w, and RCR in this case from manufacturer s catalog data note the spacing criterion (SC) value (near top of table) Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 29 Zonal Cavity Walkthrough establish LLF values LLF total = (LLF 1 ) (LLF 2 ) ( ) Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 30 15

16 Zonal Cavity Walkthrough Lamp Lumen Depreciation Generic: select a reasonable value for the chosen lamp type Specific: obtain from manufacturer s catalog Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 31 Zonal Cavity Walkthrough Luminaire Dirt Depreciation a multi-step process first, establishing categories luminaires (fixtures) will get dirty (collect dust / attract grime) over time; such dirtiness will reduce the performance of the luminaire; different fixtures do better or worse at staying clean thus this particular LLF Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 32 16

17 Zonal Cavity Walkthrough Luminaire Dirt Depreciation (continued) then, establishing environmental dirt conditions Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 33 Zonal Cavity Walkthrough Luminaire Dirt Depreciation (continued) another way of establishing environmental dirt conditions Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 34 17

18 Zonal Cavity Walkthrough Luminaire Dirt Depreciation (continued) select a reasonable value for chosen luminaire type (category), considering environmental dirt conditions (VC to VD) and cleaning schedule (months) Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 35 Zonal Cavity Walkthrough substantial effect little effect System Voltage Effect (LLF) establishing building voltage impact on lamp output Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 36 18

19 Zonal Cavity Walkthrough crunch numbers a) theoretical # fixtures required b) actual # fixtures desired c) maintained illuminance d) initial illuminance Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 37 Zonal Cavity Walkthrough theoretical analysis (first cut) yields the precise number of fixtures needed to deliver maintained illuminance this may be 24.7 (not possible) or 11 (not symmetrical) Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 38 19

20 Zonal Cavity Walkthrough select an architecturally-desired number of fixtures and recalculate illuminance Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 39 A Different Design Tool: Point-to-Point Method Used with local or supplemental illuminance approach Requires access to luminous intensity data from manufacturer s catalog (specific) common from lighting handbooks (generic) less common Requires no information about materials in the space (considers direct illuminance only) Requires information about the source-task arrangement Should include LLF for lamp lumens/luminaire dirt Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 40 20

21 Point-to-Point Method E = (I) (cos Θ) (LLF) / (d 2 ) where, E = illuminance I = luminous intensity in direction D Θ = angle of incidence LLF = light loss factor d = distance (source to task) see next slide for illustration Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 41 Design Analysis: Point-to-Point Method establish situational geometry find d (between source and P) find Θ P is the illuminated point of interest Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 42 21

22 Point-to-Point Method E = (I) (cos Θ) (LLF) / (d 2 ) involves the cosine law (light spreads over a greater area as the angle of incidence increases) (cos 0 = 1.0; cos 90 = 0) and involves the inverse square law (light spreads over a greater area as distance d increases) photonicswiki.org Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 43 Design Analysis: Point-to-Point Method select luminaire/lamp, then find luminous intensity (candlepower) data at appropriate angles (those of interest to design) Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 44 22

23 there are several formats for luminous intensity data full polar this slide quadrant previous slide Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 45 LED phosphor white LED spectrum (wikimedia) LED is NOT repeat, NOT energy efficient in most applications just yet. There are a few efficient LED products like the CREE downlight and a lot of mediocre, inefficient stuff. Be very selective and don t believe the marketing hype. A good place to learn more about the problems of current LED products is the US DOE s CALIPER reports. James Benya-SBSE listserve (7 Nov 2008) Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 46 23

Artificial light calculation

Artificial light calculation 56 1- Point-by-point method Exercise: Find E at point a & b due to: 1- only one lamp above point a. 2- The 3 lamps shown in the figure 3- E at 85 for both points 1- Ea= 562.5 lx Eb= 85.7 lx 2- Ea= 648.2

More information

Photometric Analysis for Triple Tennis Court

Photometric Analysis for Triple Tennis Court Photometric Analysis for Triple Tennis Court This photometric report will be generated using methods recommended by the Illuminating Engineering Society of North America (IESNA). The calculations in this

More information

Number Eight Lighting Company MPT2-HI-R-6-BK/40/DIM1-M-1000

Number Eight Lighting Company MPT2-HI-R-6-BK/40/DIM1-M-1000 Report No: L121706547 8165 E Kaiser Blvd. Anaheim, CA 92808 www.lightlaboratory.com Report No: L121706547 Issue Date: 1/23/2018 Report Prepared For: Number Eight Lighting Company 526 Portal Street, Cotati,

More information

Number Eight Lighting Company MPT2-HI-R-6-BK/25/DIM1-M-1400

Number Eight Lighting Company MPT2-HI-R-6-BK/25/DIM1-M-1400 Report No: L121706549 8165 E Kaiser Blvd. Anaheim, CA 92808 www.lightlaboratory.com Report No: L121706549 Issue Date: 1/23/2018 Report Prepared For: Number Eight Lighting Company 526 Portal Street, Cotati,

More information

CERTIFIED TEST REPORT No

CERTIFIED TEST REPORT No Lighting Sciences www.lightingsciences.com Lighting Sciences Inc. 7826 E. Evans Road Scottsdale, Arizona 85260 USA Tel: 480-991-9260 Fax: 480-991-0375 INTENSITY(CANDLEPOWER) SUMMARY ANGLE MEAN CP LUMENS

More information

Number Eight Lighting Company. 804/J2-WD-25/DIM WD with FS-P-1-WH trim

Number Eight Lighting Company. 804/J2-WD-25/DIM WD with FS-P-1-WH trim Report No: L121706467 8165 E Kaiser Blvd. Anaheim, CA 92808 www.lightlaboratory.com Report No: L121706467 Issue Date: 1/16/2018 Report Prepared For: Number Eight Lighting Company 526 Portal Street, Cotati,

More information

Lighting Sciences

Lighting Sciences Lighting Sciences www.lightingsciences.com Lighting Sciences Inc. 7826 E. Evans Road Scottsdale, Arizona 85260 USA Tel: 480-991-9260 Fax: 480-991-0375 INTENSITY(CANDLEPOWER) SUMMARY OUTPUT BEAM SIDE LUMENS

More information

Report of Test LLIA

Report of Test LLIA Report of Test LLIA000792-002 Total Light Output Luminaire Power Luminous Efficacy Performance Summary 9457 lm 78.6 W 120.3 lm/w PREPARED FOR : Global Tech LED, 8901 Quality Road, Bonita Springs, FL 34135,

More information

Report of Test LLIA

Report of Test LLIA Report of Test LLIA000792-003 Total Light Output Luminaire Power Luminous Efficacy Performance Summary 8616 lm 70.3 W 122.6 lm/w PREPARED FOR : Global Tech LED, 8901 Quality Road, Bonita Springs, FL 34135,

More information

Report of Test LLIA

Report of Test LLIA Report of Test LLIA000795-002 Total Light Output Luminaire Power Luminous Efficacy Performance Summary 35087 lm 296.1 W 118.5 lm/w PREPARED FOR : Global Tech LED, 8901 Quality Road, Bonita Springs, FL

More information

Chartered Institute of Building Service Engineers (CIBSE) code for interior lighting design

Chartered Institute of Building Service Engineers (CIBSE) code for interior lighting design Chartered Institute of Building Service Engineers (CIBSE) code for interior lighting design The maintenance factor gives an estimate of how lighting conditions will deteriorate through everyday use. Dust

More information

Verification Services Test Report

Verification Services Test Report Customer Company & Address ARTEMIDE S.P.A. Via Bergamo 18 20010 Pregnana Milanese (MI) Manufacturer: Artemide S.P.A. Country of Origin: Italy Country of Export: N/A Product Category: TOLOMEO LED TAVOLO

More information

DIALux simulation for indoor tennis court 300lux

DIALux simulation for indoor tennis court 300lux 2 indoor tennis courts Lamps mounted at 7M height 300lux at 1M above gound 8pcs lamps per court Partner for Contact: Order No.: Company: Customer No.: Date: Operator: Mr. Sander Revelman Table of contents

More information

Report of Test LLIA A

Report of Test LLIA A Report of Test LLIA000998-002A Catalog Number: ML5WL-D-HO-ASY-K40-4-X-VR-X One Osram Optotronic OTi 50/120-277/1A 4 DIM L LED driver labeled as 720mA. Total Light Output Luminaire Power Luminous Efficacy

More information

Report of Test LLIA

Report of Test LLIA eport of Test LLIA000858-002 Total Light Output Luminaire Power Luminous Efficacy Performance Summary 14313 lm 107.5 W 133.1 lm/w PEPAED FO : Topaz Lighting Corp, 925 Waverly Avenue, Holtsville, NY 11742,

More information

UNIVERSITY OF HONG KONG Faculty of Engineering M.Sc.(Eng) in Building Services Engineering MEBS6002 LIGHTING ENGINEERING

UNIVERSITY OF HONG KONG Faculty of Engineering M.Sc.(Eng) in Building Services Engineering MEBS6002 LIGHTING ENGINEERING The following table for rule 2 specifies recommended shielding angles for cut-off type luminaires. Some manufacturers in UK provide data for the CIE method in a graphical form. The degree of glare is assessed

More information

Report of Test LLIA A

Report of Test LLIA A Report of Test LLIA000998-001A Catalog Number: ML3WL-D-HO-ASY-K35-4-X-VR-X One Osram Optotronic OTi 50/120-277/1A 4 DIM L LED driver labeled as 600mA. Total Light Output Luminaire Power Luminous Efficacy

More information

Report of Test LLIA A

Report of Test LLIA A Report of Test LLIA000795-001A Catalog Number: GTSOL112-G2-HO-BR-NL Two Mean Well HLG-240H-C2100B LED drivers 120.0Vac, 60.00Hz, 2.811A, 335.1W, 0.994PF, 5.5%THD(i) Total Light Output Luminaire Power Luminous

More information

Photometric Report. 42 Partners Limited 21 Woden Road Wolverhampton WV10 0AU UK

Photometric Report. 42 Partners Limited 21 Woden Road Wolverhampton WV10 0AU UK 42 Partners Limited 21 Woden Road Wolverhampton WV10 0AU UK www.42partners.com 42@42partners.com T +44 (0) 1902 453650 F +44 (0) 8721 153400 Registered in England: Company Number 3021552 VAT Registration

More information

LM Test Report. For. Simkar Corporation. (Brand Name: ) LED Luminaire. Model name(s):salho2xl350u1

LM Test Report. For. Simkar Corporation. (Brand Name: ) LED Luminaire. Model name(s):salho2xl350u1 LM-79-08 Test Report For Simkar Corporation (Brand Name: ) LED Luminaire Model name(s):salho2xl350u1 Test & Report By: Garman Mo Engineer: Garman Mo Date: Feb.20,2017 Review By: Manager: Tommy Liang Note:

More information

Morris Products 53 Carey Road, Queensbury, NY 12804

Morris Products 53 Carey Road, Queensbury, NY 12804 Catalog Number 71622 UPC Number 60198671622 Description LED Ultra Thin Recessed Canopy Fixture 40W Voltage: 120/208/240/277 Shown with optional recessed mounting Bezel/Trim Cat# 71620 QPL ID # P29AE57D

More information

NVLAP LAB CODE LM Test Report. For. Simkar Corporation. (Brand Name: ) LED Luminaire. Model name(s):salho2xl5s50u1

NVLAP LAB CODE LM Test Report. For. Simkar Corporation. (Brand Name: ) LED Luminaire. Model name(s):salho2xl5s50u1 LM-79-08 Test Report For Simkar Corporation (Brand Name: ) LED Luminaire Model name(s):salho2xl5s50u1 Test & Report By: Garman Mo Engineer: Garman Mo Date: Dec.05,2016 Review By: Manager: Tommy Liang Note:

More information

NVLAP LAB CODE LM Test Report. For. Simkar Corporation. (Brand Name: ) LED Luminaire. Model name(s):salho2xl4s50u1

NVLAP LAB CODE LM Test Report. For. Simkar Corporation. (Brand Name: ) LED Luminaire. Model name(s):salho2xl4s50u1 LM-79-08 Test Report For Simkar Corporation (Brand Name: ) LED Luminaire Model name(s):salho2xl4s50u1 Test & Report By: Garman Mo Engineer: Garman Mo Date: Mar. 01,2017 Review By: Manager: Tommy Liang

More information

8165 E Kaiser Blvd. Anaheim, CA p f NVLAP LAB CODE

8165 E Kaiser Blvd. Anaheim, CA p f NVLAP LAB CODE Test #: L06124406 Date: 7/11/2012 8165 E Kaiser Blvd. Anaheim, CA 92808 p. 714.282.2270 f. 714.676.5558 NVLAP LAB CODE 200927-0 Test Report: Model Number: L06124406 MLFP22E4535 Report Prepared For: MAXLITE

More information

LightLab I N T E R N A T I O N A L

LightLab I N T E R N A T I O N A L Report of Test LL18297 Performance Summary Emergency Classification Luminous flux 89.6 lm Luminaire Power 1.05 W C0 D10 Luminous Efficacy 85.6 lm/w PREPARED FOR : Atom Lighting Ltd., Arundel, QLD 4214.

More information

LightLab I N T E R N A T I O N A L

LightLab I N T E R N A T I O N A L Report of Test LL18299 Performance Summary Emergency Classification Luminous flux 87.6 lm Luminaire Power 1.14 W C0 D10 Luminous Efficacy 76.9 lm/w PREPARED FOR : Atom Lighting Ltd., Arundel, QLD 4214.

More information

NVLAP LAB CODE LM Test Report. For IGT LIGHTING INC. (Brand Name: IG T ) 3755 Lincoln St. Suite B, Riverside, CA 92503

NVLAP LAB CODE LM Test Report. For IGT LIGHTING INC. (Brand Name: IG T ) 3755 Lincoln St. Suite B, Riverside, CA 92503 Report No.: GZE150726-B LM-79-08 Test Report For IGT LIGHTING INC. (Brand Name: IG T ) 3755 Lincoln St. Suite B, Riverside, CA 92503 Four-Foot Linear Replacement Lamps Model name(s): IGTTU-1501850F-4BC

More information

8165 E Kaiser Blvd. Anaheim, CA p f NVLAP LAB CODE MANUFACTURE NAME 8165 E. KAISER BLVD, ANAHEIM, CA 92808

8165 E Kaiser Blvd. Anaheim, CA p f NVLAP LAB CODE MANUFACTURE NAME 8165 E. KAISER BLVD, ANAHEIM, CA 92808 Test #: S01130101 Date: 1/1/2013 8165 E Kaiser Blvd. Anaheim, CA 92808 p. 714.282.2270 f. 714.676.5558 NVLAP LAB CODE 200927-0 Test Report: Model Number: S01130101 LUMINAIRE CATALOG NUMBER Report Prepared

More information

NVLAP LAB CODE LM Test Report. For. Shenzhen Guanke Technologies Co. Ltd. (Brand Name: )

NVLAP LAB CODE LM Test Report. For. Shenzhen Guanke Technologies Co. Ltd. (Brand Name: ) LM-79-08 Test Report For Shenzhen Guanke Technologies Co. Ltd (Brand Name: ) 12th/13th floor of 3th building, Tongfuyu industrial area, heshuikou community, Gongming town 518106 Shenzhen, China. Replacement

More information

NVLAP LAB CODE LM Test Report. For SIMKAR CORPORATION. (Brand Name: ) LED Lamp. Model name(s): SALXS350U1. Model differences: N/A

NVLAP LAB CODE LM Test Report. For SIMKAR CORPORATION. (Brand Name: ) LED Lamp. Model name(s): SALXS350U1. Model differences: N/A LM-79-08 Test Report For SIMKAR CORPORATION (Brand Name: ) LED Lamp Model name(s): SALXS350U1 Model differences: N/A Test & Report By: Johnson Sun Engineer: Johnson Sun Date:Oct.26, 2015 Review By: Manager:

More information

NVLAP LAB CODE LM Test Report. For SIMKAR CORPORATION. (Brand Name: ) LED Lamp. Model name(s): SALXS450U1. Model differences: N/A

NVLAP LAB CODE LM Test Report. For SIMKAR CORPORATION. (Brand Name: ) LED Lamp. Model name(s): SALXS450U1. Model differences: N/A LM-79-08 Test Report For SIMKAR CORPORATION (Brand Name: ) LED Lamp Model name(s): SALXS450U1 Model differences: N/A Test & Report By: Johnson Sun Engineer: Johnson Sun Date:Oct.26, 2015 Review By: Manager:

More information

Calibration Due Date Chroma Programmable AC Source 61604

Calibration Due Date Chroma Programmable AC Source 61604 Test #: L09123902 Date: 9/18/2012 8165 E Kaiser Blvd. Anaheim, CA 92808 p. 714.282.2270 f. 714.676.5558 NVLAP LAB CODE 200927-0 Test Report: Model Number: L09123902 ECO5-JP-3-35F Report Prepared For: BARTCO

More information

Cat# LED High Bay

Cat# LED High Bay Cat# 71403 LED High Bay Model: 71403 Input Voltage Input Current Input Power Power Factor 100-277VAC 50/60HZ 1.7A Max 144 W PF 0.92 OVERALL LAMP Luminance 17371 LM PARAMETERS Luminous Efficiency 118 LM/W

More information

Model No Stock No Calibration Due Date Chroma Programmable AC Source PS-AC02

Model No Stock No Calibration Due Date Chroma Programmable AC Source PS-AC02 Report No: L041608103 Date: 4/28/2016 8165 E Kaiser Blvd. Anaheim, CA 92808 p. 714.282.2270 f. 714.676.5558 NVLAP LAB CODE 200927-0 Report No: L041608103 Report Prepared For: GM LIGHTING 9830 W 190th St,

More information

LED Volumetric Luminaires

LED Volumetric Luminaires LED Volumetric Luminaires Limitless Options for the following applications: When appearance is most important, TCP s LED Volumetric Luminaires turn any location into something truly exceptional. The precision-formed

More information

GM LIGHTING 9830 W 190th St, Torrance, CA 90503

GM LIGHTING 9830 W 190th St, Torrance, CA 90503 Report No: L041609202 Date: 5/3/2016 8165 E Kaiser Blvd. Anaheim, CA 92808 p. 714.282.2270 f. 714.676.5558 NVLAP LAB CODE 200927-0 Report No: L041609202 Report Prepared For: GM LIGHTING 9830 W 190th St,

More information

LightLab I N T E R N A T I O N A L

LightLab I N T E R N A T I O N A L Report of Test LL15785 Performance Summary Luminous flux 540 lm Bare Lamp Power 7.76W SHR Nominal 0.75 SHR Maximum 0.79 PREPARED FOR : Indice Ecotech Pty. Ltd., Richmond, VIC 3121. Page 1 of 7 Performance

More information

8165 E Kaiser Blvd. Anaheim, CA p f NVLAP LAB CODE

8165 E Kaiser Blvd. Anaheim, CA p f NVLAP LAB CODE Report No: L011501402 Date: 1/14/2015 8165 E Kaiser Blvd. Anaheim, CA 92808 p. 714.282.2270 f. 714.676.5558 NVLAP LAB CODE 200927-0 Report No: L011501402 Report Prepared For: Primus Lighting Inc. 3570

More information

8165 E Kaiser Blvd. Anaheim, CA p f NVLAP LAB CODE

8165 E Kaiser Blvd. Anaheim, CA p f NVLAP LAB CODE Report No: L091503801 Date: 9/16/2015 8165 E Kaiser Blvd. Anaheim, CA 92808 p. 714.282.2270 f. 714.676.5558 NVLAP LAB CODE 200927-0 Report No: L091503801 Report Prepared For: LEDCONN 301 Thor Place Model

More information

Model No Stock No Calibration Due Date Chroma Programmable AC Source PS-AC02

Model No Stock No Calibration Due Date Chroma Programmable AC Source PS-AC02 Report No: L041608003 Date: 4/29/2016 8165 E Kaiser Blvd. Anaheim, CA 92808 p. 714.282.2270 f. 714.676.5558 NVLAP LAB CODE 200927-0 Report No: L041608003 Report Prepared For: GM LIGHTING 9830 W 190th St,

More information

M2 V0 IN ON A POLE. Material Aluminium Polycarbonate. Finish White Transparent TECHNICAL CHARACTERISTICS

M2 V0 IN ON A POLE. Material Aluminium Polycarbonate. Finish White Transparent TECHNICAL CHARACTERISTICS 71-5156-14-M2V0 ON A POLE Finish White Transparent IP20 Material Aluminium Polycarbonate 40º 50 TECHNICAL CHARACTERISTICS Light source Light source: LED Output (W): max. 13W Color temperature: Warm White

More information

NVLAP LAB CODE LM Test Report. For MAXLITE INC. (Brand Name: MaxLed) 12 York Ave West Caldwell NJ 07006

NVLAP LAB CODE LM Test Report. For MAXLITE INC. (Brand Name: MaxLed) 12 York Ave West Caldwell NJ 07006 LM-79-08 Test Report For MAXLITE INC. (Brand Name: MaxLed) 12 York Ave West Caldwell NJ 07006 Architectural Flood and Spot Luminaires Model name(s): FLS20U40B/N FLS20U45B/N FLS20U50B/N FLS20U40W/N FLS20U45W/N

More information

8165 E Kaiser Blvd. Anaheim, CA p f NVLAP LAB CODE

8165 E Kaiser Blvd. Anaheim, CA p f NVLAP LAB CODE Test #: L07121001 Date: 7/6/2012 8165 E Kaiser Blvd. Anaheim, CA 92808 p. 714.282.2270 f. 714.676.5558 NVLAP LAB CODE 200927-0 Test Report: Model Number: L07121001 EDR-36NB-80-T5R-UNV-XXX-XX Report Prepared

More information

8165 E Kaiser Blvd. Anaheim, CA p f NVLAP LAB CODE Fixture is tested with no special conditions.

8165 E Kaiser Blvd. Anaheim, CA p f NVLAP LAB CODE Fixture is tested with no special conditions. Report No: L031603401 Date: 3/15/2016 8165 E Kaiser Blvd. Anaheim, CA 92808 p. 714.282.2270 f. 714.676.5558 NVLAP LAB CODE 200927-0 Report No: L0031603401 Report Prepared For: Osram Sylvania, Inc. Model

More information

NVLAP LAB CODE LM Test Report. For MAXLITE INC. (Brand Name: MaxLed) 12 York Ave West Caldwell NJ 07006

NVLAP LAB CODE LM Test Report. For MAXLITE INC. (Brand Name: MaxLed) 12 York Ave West Caldwell NJ 07006 LM-79-08 Test Report For MAXLITE INC. (Brand Name: MaxLed) 12 York Ave West Caldwell NJ 07006 Architectural Flood and Spot Luminaires Model name(s): FLS20U40B FLS20U45B FLS20U50B FLS20U40W FLS20U45W FLS20U50W

More information

NVLAP LAB CODE LM Test Report. For MAXLITE INC. (Brand Name: MaxLed) 12 York Ave West Caldwell NJ 07006

NVLAP LAB CODE LM Test Report. For MAXLITE INC. (Brand Name: MaxLed) 12 York Ave West Caldwell NJ 07006 LM-79-08 Test Report For MAXLITE INC. (Brand Name: MaxLed) 12 York Ave West Caldwell NJ 07006 Architectural Flood and Spot Luminaires Model name(s): FLS40U40B FLS40U45B FLS40U50B FLS40U40W FLS40U45W FLS40U50W

More information

Lighting fundamentals

Lighting fundamentals Lighting fundamentals About light and photometrics Generation of light Human vision Black body Colour Basic principles of lighting Light sources Light Vision Colour What is light? Light is electromagnetic

More information

Maxlite Jersey Blvd Rancho Cucamonga, CA Electrical and Photometric tests as required by the IESNA test standards.

Maxlite Jersey Blvd Rancho Cucamonga, CA Electrical and Photometric tests as required by the IESNA test standards. Test #: L02144405 Date: 2/21/2014 8165 E Kaiser Blvd. Anaheim, CA 92808 p. 714.282.2270 f. 714.676.5558 NVLAP LAB CODE 200927-0 Test Report: Model Number: L02144405 LSU2406U2050 / DV50 Report Prepared

More information

The Control of Glare by the AS1680 Systems

The Control of Glare by the AS1680 Systems Lab Notes Issue The Control of Glare by the AS1680 Systems 8 1.00 Introduction : This Lab Note is one of several which discusses the matter of glare in the workplace. They have been issued as a series

More information

NVLAP LAB CODE LM Test Report. For DONGGUAN THAILIGHT SEMICONDCTOR LIGHTING CO.,LTD

NVLAP LAB CODE LM Test Report. For DONGGUAN THAILIGHT SEMICONDCTOR LIGHTING CO.,LTD LM-79-08 Test Report For DONGGUAN THAILIGHT SEMICONDCTOR LIGHTING CO.,LTD (Brand Name: THAILIGHT) Sanhui Ind. Area, Cunwei, Hengli, Dongguan, China. Architectural Flood and Spot Luminaires Model name(s):

More information

NVLAP LAB CODE LM Test Report. For DONGGUAN THAILIGHT SEMICONDCTOR LIGHTING CO.,LTD

NVLAP LAB CODE LM Test Report. For DONGGUAN THAILIGHT SEMICONDCTOR LIGHTING CO.,LTD LM-79-08 Test Report For DONGGUAN THAILIGHT SEMICONDCTOR LIGHTING CO.,LTD (Brand Name: THAILIGHT) Sanhui Ind. Area, Cunwei, Hengli, Dongguan, China. Architectural Flood and Spot Luminaires Model name(s):

More information

NVLAP LAB CODE LM Test Report. For AOK LED LIGHT COMPANY LIMITED. (Brand Name: AOK)

NVLAP LAB CODE LM Test Report. For AOK LED LIGHT COMPANY LIMITED. (Brand Name: AOK) LM-79-08 Test Report For AOK LED LIGHT COMPANY LIMITED (Brand Name: AOK) Building 1, St George's Science and Technology Industrial Park, Shajin Street, Shenzhen, Guangdong Province, China Zip 518104 Outdoor

More information

PHOTOMETRIC TESTING & EVALUATION TO IES LM Sample Tested LN130-A30 LED HIGH BAY. Prepared for: Janie Chung

PHOTOMETRIC TESTING & EVALUATION TO IES LM Sample Tested LN130-A30 LED HIGH BAY. Prepared for: Janie Chung PHOTOMETRIC TESTING & EVALUATION TO IES LM-79-08 Sample Tested LN130-A30 LED HIGH BAY Prepared for: Janie Chung KMW Inc. 183-6 Youngcheon-ro, Dongtan-myun Hwasung-si, Gyeonggi-do Korea 445-813 Phone: 253-826-7636

More information

NVLAP LAB CODE LM Test Report. For REMPHOS TECHNOLOGIES LLC. (Brand Name: ) 90 Holten St, Danvers, MA 01923,USA.

NVLAP LAB CODE LM Test Report. For REMPHOS TECHNOLOGIES LLC. (Brand Name: ) 90 Holten St, Danvers, MA 01923,USA. LM-79-08 Test Report For REMPHOS TECHNOLOGIES LLC (Brand Name: ) 90 Holten St, Danvers, MA 01923,USA LED Lamp Model name(s): RPT-LEDBIAX-1500LM-4000K Representative (Tested) Model: RPT-LEDBIAX-1500LM-4000K

More information

LEDs in ERCO luminaires

LEDs in ERCO luminaires E LEDs in ERCO luminaires ERCO GmbH Postfach 24 58505 Lüdenscheid Brockhauser Weg 82 58507 Lüdenscheid Germany Tel.: +49 2351 551 0 Fax: +49 2351 551 300 info@erco.com www.erco.com The following pages

More information

Test Report. Report No.: EED35I R1. Address : 701 Millennium Boulevard Greenville, SC : P , P , P , P

Test Report. Report No.: EED35I R1. Address : 701 Millennium Boulevard Greenville, SC : P , P , P , P Test of One Model of LED Track Head Report No.: EED35I000703-2R Prepared for : Progress Lighting Address : 70 Millennium Boulevard Greenville, SC 29607 Model Name : P9082 Model No. : P9082-28, P9082-3,

More information

Test Report. Report No.: EED35I Address : 701 Millennium Boulevard Greenville, SC : P , P , P , P

Test Report. Report No.: EED35I Address : 701 Millennium Boulevard Greenville, SC : P , P , P , P Test of One Model of LED Track Head Report No.: EED35I000702-2 Prepared for : Progress Lighting Address : 70 Millennium Boulevard Greenville, SC 29607 Model Name : P9062 Model No. : P9062-28, P9062-3,

More information

Suxess Inc., dba LUX Dynamics LED-LHB-2-UNV HO LADC

Suxess Inc., dba LUX Dynamics LED-LHB-2-UNV HO LADC Report No: L031601802R02 Date: 5/6/2016 8165 E Kaiser Blvd. Anaheim, CA 92808 p. 714.282.2270 f. 714.676.5558 NVLAP LAB CODE 200927-0 Report No: Prepared For: Model Number: Test: L031601802R02 Suxess Inc.,

More information

LightLab I N T E R N A T I O N A L

LightLab I N T E R N A T I O N A L Report of Test 13232-2 Performance Summary Total Light Output Luminaire Power Luminous Efficacy 3287 lm 35.6 W 92.3 lm/w PREPARED FOR : Ecolite Manufacturing, 9919 East Montgomery, Spokane, WA 99206. Page

More information

NVLAP LAB CODE LM Test Report. For AOK LED LIGHT COMPANY LIMITED. (Brand Name: AOK)

NVLAP LAB CODE LM Test Report. For AOK LED LIGHT COMPANY LIMITED. (Brand Name: AOK) LM-79-08 Test Report For AOK LED LIGHT COMPANY LIMITED (Brand Name: AOK) Building 1, St George's Science and Technology Industrial Park, Shajin Street, Shenzhen, Guangdong Province, China Zip 518104 Outdoor

More information

LightLab I N T E R N A T I O N A L

LightLab I N T E R N A T I O N A L Report of Test LLI-14188-20D Performance Summary Total Light Output 310 lm Min Power Factor 0.46 @ 277 V Luminaire Power 9.79 W Max THD(i)* 30.4 % @ 277 V Luminous Efficacy 31.7 lm/w SC along*, across*

More information

NVLAP LAB CODE LM Test Report. For CE INNOVATIONS LTD. (Brand Name: N/A) 911 Denison St Markham, ON L3R 3K4 Canada

NVLAP LAB CODE LM Test Report. For CE INNOVATIONS LTD. (Brand Name: N/A) 911 Denison St Markham, ON L3R 3K4 Canada LM-79-08 Test Report For CE INNOVATIONS LTD (Brand Name: N/A) 911 Denison St Markham, ON L3R 3K4 Canada Four-Foot Linear Replacement Lamps Model name(s): IR-T8-15W4FT16503500K IR-T8-15W4FT16504000K IR-T8-15W4FT16505000K

More information

V0. PLAY Downlight recessed. Description Recessed for indoor use.

V0. PLAY Downlight recessed. Description Recessed for indoor use. 71-3878-14-37 V0 Downlight recessed Description Recessed for indoor use. For downlighting. Up to 40,000 possible combinations. Lenses allow optimum control of illumination with minimal residual halo.,

More information

IES INDOOR REPORT PHOTOMETRIC FILENAME : RDISE24-LED48FRDMV35.IES. DESCRIPTION INFORMATION (From Photometric File)

IES INDOOR REPORT PHOTOMETRIC FILENAME : RDISE24-LED48FRDMV35.IES. DESCRIPTION INFORMATION (From Photometric File) DESCRIPTION INFORMATION (From Photometric File) IESNA:LM-63-2002 [TEST] LLIA000653-006 [TESTLAB] LightLab International Allentown, LLC [MANUFAC] Mobern Lighting Co., 8200 Stayton Drive, Jessup, MD 20794,

More information

Report of Test LLIA

Report of Test LLIA Report of Test LLIA55- Catalog Number: X One eldoled SOLOdriver 56/S, 5mA/May x25, LED driver 2.Vac, 6.Hz,.837A, 2.98W,.952PF, 5.44%THD(i) Total Light Output Luminaire Power Luminous Efficacy Performance

More information

Page 2 of 14 Report No.: Test sample... : Type of test object... : LED Downlight LED Downlight

Page 2 of 14 Report No.: Test sample... : Type of test object... : LED Downlight LED Downlight Page 2 of 14 Report No.: 68.184.15.296.01 Test sample... : Type of test object... : LED Downlight LED Downlight Trade mark... : Model and/or type reference... : EF150-26W-840 Rating(s)... : 220-240V~;

More information

LED Entryway Light RoHS

LED Entryway Light RoHS 72508 LED Entryway Light RoHS QPL ID # PSMN8JUU Model: 72508 Input Voltage 120-277 VAC 60HZ Input Current 0.5A Max @120V Input Power 25W Power Factor PF 0.95 OVERALL LAMP PARAMETERS Luminance 3,121 LM

More information

REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK 13045

REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK 13045 REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK 13045 FOR THE SCOPE OF ACCREDITATION UNDER NVLAP LAB CODE 100402-0. Project No. G100896445 Date: September 26, 2012 REPORT NO. 100896445CRT-001 TEST OF ONE LED

More information

Project name. Qty. Output (nominal lumens) Colour and colour temperature. Optics (nominal distribution) Narrow spot 10, Narrow 20, Medium 40

Project name. Qty. Output (nominal lumens) Colour and colour temperature. Optics (nominal distribution) Narrow spot 10, Narrow 20, Medium 40 D u m m y Specification sheet Client Project name Order# Type Qty Side view Bottom view Photometric Summary Description The Lumenalpha Discreet Medium Tilt achieves a sleek, trimless appearance without

More information

Using a Quantitative Measure to Achieve a Qualitative Lighting Design Effect! Introduction What is Luminance?

Using a Quantitative Measure to Achieve a Qualitative Lighting Design Effect! Introduction What is Luminance? Using a Quantitative Measure to Achieve a Qualitative Lighting Design Effect! Introduction What is Luminance? Luminance in a simple language is the measurement unit of brightness. In realty brightness

More information

NVLAP LAB CODE LM Test Report. For LED PANEL LIGHTING CO.,LTD. (Brand Name: N/A)

NVLAP LAB CODE LM Test Report. For LED PANEL LIGHTING CO.,LTD. (Brand Name: N/A) LM-79-08 Test Report For LED PANEL LIGHTING CO.,LTD. (Brand Name: N/A) 7 F, Jinchangda Industrial Park,zhangkengjing,GuanLan, Baoao,Shenzhen,Guangdong,China 2x2 Luminaires for Ambient Lighting of Interior

More information

LM Test Report. For. Beyond LED Technology. (Brand Name: Beyond LED) 2725 Mountain Industrial Blvd. Suite A-1 Tucker, GA 30084

LM Test Report. For. Beyond LED Technology. (Brand Name: Beyond LED) 2725 Mountain Industrial Blvd. Suite A-1 Tucker, GA 30084 LM-79-08 Test Report For Beyond LED Technology (Brand Name: Beyond LED) 2725 Mountain Industrial Blvd. Suite A-1 Tucker, GA 30084 ZOHO Series LED Flood Light Model name(s): BLTFLD50W5K Representative (Tested)

More information

Hotel Hallway Analysis

Hotel Hallway Analysis Date: Operator: Blacksburg, VA 260 Telephone 5.553.6171 Table of contents Hotel Hallway Analysis Project Cover 1 Table of contents 2 ZUMTOBEL STAFF LIGHTING S5D7108 7108RC S5; S5D; SPEC-5; FORMED STEE...

More information

RoHS. Dimming: PWM/VR/0-10V QPL ID # PL21D5Q1B95E. Cat# W LED FlatPanel Slipfitter Mount. EPA Rating 2.

RoHS. Dimming: PWM/VR/0-10V QPL ID # PL21D5Q1B95E. Cat# W LED FlatPanel Slipfitter Mount.   EPA Rating 2. Cat# 71893 380W LED FlatPanel Slipfitter Mount OVERALL LAMP PARAMETERS LED DRIVER LED Input Voltage Input Current Input Power Power Factor Luminance Luminous Efficiency CRI Beam Angle Main Structure Output

More information

LED Flat Panel 1X4. Solas Ray Lighting 1524 Jackson Street Anderson, Indiana

LED Flat Panel 1X4. Solas Ray Lighting 1524 Jackson Street Anderson, Indiana LED Flat Panel 1X4 Photometric Filename: FP14-036-40-AC-U-D.IES Photometric Filename: FP14-036-40-AC-U-D.IES Descriptive Information (From Photometric File) IESNA:LM-63-2002 [TEST] 1 [TESTLAB] EVERFINE

More information

Test Report. Report No.: EED35I Page 1 of 12. Customer : Revolution Lighting Technologies : 4139 Guardian Street, Simi Valley, CA93063

Test Report. Report No.: EED35I Page 1 of 12. Customer : Revolution Lighting Technologies : 4139 Guardian Street, Simi Valley, CA93063 Report No.: EED35I000235-1 Page 1 of 12 Customer : Revolution Lighting Technologies Address : 4139 Guardian Street, Simi Valley, CA93063 Description of the submitted sample(s): Sample Name : LED TUBE Model/Type

More information

NVLAP LAB CODE LM Test Report. For. LED Wav es,inc. (Brand Name: LED Wav es)

NVLAP LAB CODE LM Test Report. For. LED Wav es,inc. (Brand Name: LED Wav es) LM-79-08 Test Report For LED Wav es,inc (Brand Name: LED Wav es) 4100 1st Ave,The Esquire Building,Brooklyn, NY 11232 2x2 Luminaires for Ambient Lighting of Interior Commercial Spaces Model name(s): SL2-2X2-40W-11

More information

Book 14 Edition 1.1 March Socketable Flat LED Module and LED Light Engine

Book 14 Edition 1.1 March Socketable Flat LED Module and LED Light Engine Book 14 Edition 1.1 March 2017 Socketable Flat LED Module and LED Light Engine Book 14 Summary (informative) Background The Zhaga Consortium is a global lighting-industry organization that aims to standardize

More information

Lab Notes. How to Select the Best Luminaire For Interior Lighting

Lab Notes. How to Select the Best Luminaire For Interior Lighting Lab Notes Issue 12 How to Select the Best Luminaire For Interior Lighting 1.00 Introduction : Lab Note Issue 3 How to Read a Photometric Report, Section 4.3 discusses the various Light Technical Parameters

More information

Project name. Qty. Colour and colour temperature. Optics (nominal distribution) Maximum delivered output. Maximum delivered intensity

Project name. Qty. Colour and colour temperature. Optics (nominal distribution) Maximum delivered output. Maximum delivered intensity D u m m y Specification sheet Client Project name Order# Type Qty Front view Bottom view Photometric Summary Description The Lumenalpha Clear Small is a high-performance adjustable LED downlight for commercial,

More information

Lighting design and calculations

Lighting design and calculations Lighting design and calculations THE LUMEN METHOD This method is also called: Photometrical Computation and mostly used for interior lighting calculation To determine the total number of luminaires required

More information

A theoretical comparison between batwing and lambertian distributions of power LEDs related to an interior lighting system

A theoretical comparison between batwing and lambertian distributions of power LEDs related to an interior lighting system A theoretical comparison between batwing and lambertian distributions of power LEDs related to an interior lighting system GABRIEL ISPAS Electrical and Lighting Department Faculty of Building Services

More information

: Office. Project number : Customer : SLP UK Ltd Processed by : RH Date : Project description:

: Office. Project number : Customer : SLP UK Ltd Processed by : RH Date : Project description: Office Customer : SLP UK Ltd Processed by : RH Project description: The following values are based on exact calculations on calibrated lamps, luminaires and their arrangement. In practice, gradual divergences

More information

8165 E Kaiser Blvd. Anaheim, CA p f NVLAP LAB CODE

8165 E Kaiser Blvd. Anaheim, CA p f NVLAP LAB CODE Test #: L04144701 Date: 4/21/2014 8165 E Kaiser Blvd. Anaheim, CA 92808 p. 714.282.2270 f. 714.676.5558 NVLAP LAB CODE 200927-0 Test Report: Model Number: L04144701 WPW-1C-120 Report Prepared For: EiKO

More information

Photometric Test Report

Photometric Test Report Photometric Test Report Relevant Standards IES LM-79-2008 ANSI C82.77-2002 UL1598-2008/ UL1993-2012 Prepared For Keystone Technologies 1390 Welsh Road,North Wales, PA 19454 Stephanie DeLaurentis, 267-656-2272,

More information

Key objectives in Lighting design

Key objectives in Lighting design Key objectives in Lighting design Visual performance Physiological conditions Visual quality no strong "contrasts" good "color rendering" adequate "light levels" no "disturbing reflections" no direct "glare"

More information

NHÀ THI ĐẤU ĐA NĂNG - ĐẠI HỌC TÂY NGUYÊN

NHÀ THI ĐẤU ĐA NĂNG - ĐẠI HỌC TÂY NGUYÊN THIẾT KẾ CHIẾU SÁNG NHÀ THI ĐẤU ĐA NĂNG SỬ DỤNG ĐÈN LED POTECH Partner for Contact: Mr. KHÔI Order No.: PT-022 Company: TRƯỜNG ĐẠI HỌC TÂY NGUYÊN Customer No.: 005 Date: Operator: BUI CONG CUONG Table

More information

Wet Locations Use 71400A 120 W PF V 2.9A 93% 144 pcs. Philips 130 LM/W 5000K Hrs. 5 Years. 24-1/4 Lbs 665*530*120 1 PCS

Wet Locations Use 71400A 120 W PF V 2.9A 93% 144 pcs. Philips 130 LM/W 5000K Hrs. 5 Years. 24-1/4 Lbs 665*530*120 1 PCS 71400A GAS STATION Canopy Luminaire Wet Locations Use QPL ID # PL9D2UU8ZA41 OVERALL LAMP PARAMETERS LED DRIVER LED LIFESPAN & ENVIRONMENT SAFETY&EMC OTHERS Model: Input Voltage Input Current Input Power

More information

Lighting Sciences

Lighting Sciences Lighting Sciences www.lightingsciences.com Lighting Sciences Inc. 7826 E. Evans Road Scottsdale, Arizona 85260 USA Tel: 480-991-9260 Fax: 480-991-0375 IESNA CUTOFF CLASSIFICATION: NON-CUTOFF 3 1/2" 7"

More information

Photometric Test Report

Photometric Test Report Photometric Test Report Relevant Standards IES LM-79-2008 ANSI C82.77-2002 UL1598-2008/ UL1993-2012 Prepared For MaxLite Inc 10 York Avenue, West Caldwell, NJ 07006 Ramesh Raghavan, 973-244-7300 x146,

More information

Cat# LED Linear High Bay 100W

Cat# LED Linear High Bay 100W Cat# 71724 LED Linear High Bay 100W QPL ID # PRNKSMPK OVERALL LAMP PARAMETERS LED DRIVER LIFESPAN & ENVIRONMENT OTHERS Model: Input Voltage Input Current Input Power Power Factor Luminance Luminous Efficiency

More information

8165 E Kaiser Blvd. Anaheim, CA p f NVLAP LAB CODE SPJ Lighting 2107 Chino Ave. South El Monte, CA.

8165 E Kaiser Blvd. Anaheim, CA p f NVLAP LAB CODE SPJ Lighting 2107 Chino Ave. South El Monte, CA. Report No: L051503301 Date: 5/21/2015 8165 E Kaiser Blvd. Anaheim, CA 92808 p. 714.282.2270 f. 714.676.5558 NVLAP LAB CODE 200927-0 Report No: L051503301 Report Prepared For: SPJ Lighting 2107 Chino Ave.

More information

NVLAP LAB CODE LM Test Report. For. Hocan Group Co.,Ltd (Brand Name: SEPICN LED LIGHTING)

NVLAP LAB CODE LM Test Report. For. Hocan Group Co.,Ltd (Brand Name: SEPICN LED LIGHTING) LM-79-08 Test Report For Hocan Group Co.,Ltd (Brand Name: SEPICN LED LIGHTING) Rm 1902, Easey Comm Bldg,253-261 Hennessy Rd Wanchai, HONG KONG Four-Foot Linear Replacement Lamps Model name(s): HC-T8-4FT-13W-ID(X,

More information

NVLAP LAB CODE LM Test Report. For. Hocan Group Co.,Ltd (Brand Name: SEPICN LED LIGHTING)

NVLAP LAB CODE LM Test Report. For. Hocan Group Co.,Ltd (Brand Name: SEPICN LED LIGHTING) LM-79-08 Test Report For Hocan Group Co.,Ltd (Brand Name: SEPICN LED LIGHTING) Rm 1902, Easey Comm Bldg,253-261 Hennessy Rd Wanchai, HONG KONG Four-Foot Linear Replacement Lamps Model name(s): HC-T8-4FT-22W-ID(X,Clear)

More information

1 General 1.1 Product Information Manufacturer Maxlite.Inc Page 2 of 17 Manufacturer Address 12 York Ave West Caldwell, NJ Brand Name Luminaire

1 General 1.1 Product Information Manufacturer Maxlite.Inc Page 2 of 17 Manufacturer Address 12 York Ave West Caldwell, NJ Brand Name Luminaire TESTING Report No.:BL160912008-9A NVLAP LAB CODE 600102-0 Test report of IES LM-79-08 Approved Method: Electrical and Photometric Measurements of Solid-State Lighting Products Applicant: Maxlite.Inc Address:

More information

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630 FOR THE SCOPE OF ACCREDITATION UNDER ALA TO ISO/IEC 170:00. REPORT 800 COMMERCENTRE DRIVE, LAKE FOREST, CA 90 Project No. G10171817 Date: August, 01 REPORT NO. 10171817LAX-00 TEST OF ONE GARAUGE LUMINAIRE

More information

ENVIRONMENTAL SYSTEMS

ENVIRONMENTAL SYSTEMS LIGHT http://map.gsfc.nasa.gov/media/ Ball State Architecture ENVIRONMENTAL SYSTEMS 1 Grondzik 1 study carrel in Phillips Exeter Library; a celebration of light and of material (by L. Kahn) Kahn on Light

More information

Adaptive architectural lighting systems IES Report

Adaptive architectural lighting systems IES Report Adaptive architectural lighting systems IES Report BoxRail 107 107-BX-X-4-48-X-X-X-X-X-X-Z-HO-35-S2-X-BL-X The performance data in black text is confirmed through third party testing (see the following

More information

Cree Engineering Services Testing Laboratory (CESTL) Photometric Testing and Evaluation Report

Cree Engineering Services Testing Laboratory (CESTL) Photometric Testing and Evaluation Report Report Number: Model: PL08073-001A S-DL6-63L-27K w_s-dl6t-w-ss-c Date: 05/09/2016 Cree Engineering Services Testing Laboratory (CESTL) Photometric Testing and Evaluation Report Prepared For: Jonathan Vollers

More information

8165 E Kaiser Blvd. Anaheim, CA p f NVLAP LAB CODE Old Conejo Road #118, Newbury Park, CA, 91320

8165 E Kaiser Blvd. Anaheim, CA p f NVLAP LAB CODE Old Conejo Road #118, Newbury Park, CA, 91320 Report No: L051602710 Date: 5/24/2016 8165 E Kaiser Blvd. Anaheim, CA 92808 p. 714.282.2270 f. 714.676.5558 NVLAP LAB CODE 200927-0 Report No: Prepared For: Model Number: Test: L051602710 HK Lighting Group

More information