GENERATORS AND LOADS MODELS TO INVESTIGATE UNCONTROLLED ISLANDING ON ACTIVE DISTRIBUTION NETWORKS

Size: px
Start display at page:

Download "GENERATORS AND LOADS MODELS TO INVESTIGATE UNCONTROLLED ISLANDING ON ACTIVE DISTRIBUTION NETWORKS"

Transcription

1 GENERATORS AND LOADS MODELS TO INVESTIGATE UNCONTROLLED ISLANDING ON ACTIVE DISTRIBUTION NETWORKS Paolo MATTAVELLI, Riccardo SGARBOSSA Roberto TURRI University of Padova Italy ABSTRACT The number of distributed energy resources (DERs) connected to low voltage (LV) distribution networs has increased the concern on the unintentional/uncontrolled islanding operations. To evaluate the effect of the Distributed Generation (DG) on the uncontrolled islanding events in LV networ portions independent studies have been performed, considering different LV load dynamic characterization and inverter based models for a correct evaluation of the islanding issue. P/f and Q/V capabilities and regulation laws required by the DERs stated by the most relevant standards have also been considered. Field measurements, simulations in different simulating environments as Real Time Digital Simulator (RTDS), Simulin/Power System Blocset and DIgSILENT Power Factory are reported. INTRODUCTION To evaluate the effect of the most relevant capabilities and regulation laws required to distributed energy resources (DERs) [1-2] on uncontrolled islanding in distribution networs, two completely independent studies have been performed, based on: 1) field measurements to assess LV load dynamic behavior; 2) digital simulations performed in different simulation environments (RTDS, Simulin/DigSILENT). Suitable models for the inverter based generators and for the loads are essential for a correct evaluation of the phenomena. This need has recently led to the Joint Woring Group C4/C6.35/CIRED: Modelling and dynamic performance of inverter based generation in power system transmission and distribution studies. Considering that inverter based models in standard libraries do not include the several new DER capabilities and may be not adequate for dynamic simulations (EMTtime domain), additional models have been developed. More precisely: University of Padova realized models in the time domain (Power System Blocset), based on switching inverter operation. Subsequently, porting of the model in an equivalent RMS model to be adopted in DigSILENT was performed by simplification firstly to average models and then to RMS-phasor models, in Gianluca SAPIENZA, Giovanni VALVO, Cristiano PEZZATO, Alberto CERRETTI Enel Distribuzione Italy gianluca.sapienza@enel.com giovanni.valvo@enel.com cristiano.pezzato@enel.com alberto.cerretti@enel.com Ettore DE BERARDINIS CESI Italy deberardinis@cesi.it order to be used in dynamic simulation, together with other networ components (load, generator, etc). CESI and ENEL Distribuzione implemented in a Real Time Digital Simulator (RTDS) digital models of PV inverters, synchronous generators, loads and protection systems. The correct dynamic representation of the LV load depending on the voltage and the frequency [3-4] is important for the assessment of unintentional islanding operation. Considering the data in [3-4] outdated, ENEL decided to set up two field measurement campaigns in order to assess the current typical LV equivalent load behavior and to define updated sets of load model parameters. In any case, in order to cover different scenarios for uncontrolled islanding operation, analysis of islanded operation has taen into account both load representations, i.e. the old ones with the coefficient reported in 1993 [3-4] and the new ones as resulting from the two field measurement campaigns. STANDARDS AND CONNECTION RULES Recently, reference technical rules have been revised by standards, introducing for DERs protection interface systems and local control strategies, in order to integrate the growing number of DGs [1-2]. Permissive thresholds for voltage and frequency have also been introduced in compliance with the Fault Ride Through (FRT) philosophy [3-4], as shown in Fig. 1. a) b) Figure 1-a) Frequency permissive and restrictive thresholds. b) voltage FRT thresholds. Moreover, local controls set by standards are required: active and reactive power exchanged by DGs are function of the frequency and voltage levels, as shown in Fig. 2, introducing the droop characteristic Q=f (V) and P=f (f). CIRED2015 1/5

2 These control strategies are aimed at facilitating the electrical system stability but they can potentially increase the ris of uncontrolled islanded networ operation. a) b) Figure 2 - a) Inverters could be required to participate to the voltage regulation using Q injections from a minimum of to the maximum of with respect to the rated power; b) gradual limitation of the generated P according to an over-frequency statism s o =2.4% [1-2]. LV LOAD CHARACTERIZATION For the load static and dynamic characteristics, the approach proposed in [3-4] has been adopted, where the active P out and the reactive Q out load powers depend both on frequency and amplitude of the voltage waveform, i.e.: P out = P 0 {[ f ( pf ) 1] ( u p ) pu } 1sT 1 u o { Q out = Q 0 {[ f ( qf ) 1] ( u p ) (1) qu } 1sT 1 u o where u p = [ u ( 1 1sT 1 ) u o ] and P o and Q o are the active and reactive power respectively absorbed at nominal frequency f 0 and nominal amplitude u 0. Moreover, pf, pu, qf and qu are parameters that describe different type of loads (residential, industrial, agriculture) and the voltage and frequency deviation from their nominal parameters are denoted as u = u u o and f = (f f o ) /f o, respectively. The above-mentioned parameters describe the variation of the load as a function of voltage and frequency, therefore the campaign has been realized by using a suitable synchronous generator able to supply the LV networ independently from the MV/LV transformer, as shown in Fig. 3. MV Networ 20/0.4 V G ~ Synchronous generator Figure 3 Test field realization Tests have been carried out at fixed voltage to determine pf, qf, at fixed frequency to find pf, qf, according to the following equations: V Other lines Residential loads Other load pu = log P P0 log up u0 qu = log Q Q0 log up u0 pf = 1 f ( P P 0 1) = f 0 f f 0 ( P P 0 1) qf = 1 f ( Q 1) = f 0 ( Q 1) Q 0 f f 0 Q 0 where P 0, Q 0, U 0, f 0, are the initial active power reactive power, supply voltage, frequency, for each test. The initial and final values for the active/reactive power at the corresponding values for the voltage or frequency have been determined by interpolating several measurements, for the pu, qu characterization, as shown for the sae of example in Fig. 4. Figure 4 Example of P and Q variation as a function of u p Table 1 shows the mean values measured during these tests. The values are quite different from the IEEE campaign and they refer to a limited number of tests. This difference may be justified by the different type of electrical equipment currently used. Residential loads Other loads pf qf pu qu Table 1 Field tests results (average values). (2) CIRED2015 2/5

3 The T 1 parameter has been determined by applying step voltage variations using the tap changer of the Primary Substation HV/MV transformer. T 1 value has been confirmed to be about 0.1 s. INVERTER AND LV NETWORK DISTRIBUTION MODEL DIgSILENT inverter model RMS vs Simulin/Time domain model (Case A) In this study a detailed inverter model, with embedded voltage and current regulations typical for photovoltaic applications, has initially been developed. In order to study the uncontrolled islanding operations the average values and the phasors representations are superior to the detailed model in terms of computational requirements and numerical convergence issues. Although different conversion module configurations can been considered [5], the analysis has focused on the single-stage system and on the two level Voltage Source Inverter (VSI). A three-phase inverter with EMI filter in addition to the inductive output filter, as shown in Fig. 5, has been considered. Figure 6- Switching and average inverter model The representation has been developed in Maltab/Simulin environment and compared with DIgSILENT software using RMS simulations. The results show a good match between the two environments. i a L v f 1 AB L 1 i b v CA L v f 2 BC L 2 i c L f 3 L 3 C f 1 C f 2 C f 3 R Cf 1 R Cf 2 R Cf 3 Figure 5 Three phase inverter with L 1,2,3 inductive filter and EMI filter composed by L f1,2,3,c f1,2,3 and R Cf1,2,3 as dumping element of the filter (if present). The switching function approach has been initially used to fully represent the switching operation of the inverters, as depicted in Fig. 6. However, for most of the islanded analysis, the detailed switching operation has been neglected, in order to reduce simulation time and facilitate convergence, and an average model, where each state variable is averaged over the PWM switching period, is adopted, as generally shown in Fig. 6. The averaging model is more efficient and with less numerical convergence problem than the detailed switching model. Moreover the presented average model has been transferred in the d,q coordinates using a Par Transformation, and completed with the required current, voltage and Phase-Looed Loop (PLL) regulations and with the required protection functions. At last we obtain a dynamic model expressed in amplitude and phase of voltages and currents instead of instantaneous sinusoidal values. Figure 7 - LV distribution networ used Case A With this modeling approach, the tested LV networ is shown in Fig. 7. It presents a DG unit, three loads, a MV/LV Transformer and cables lines, whose lengths are shown in Fig. 7, and characterized by R=0.164 Ohm/m, X= Ohm/m and B= µs/m. The switching of the breaer starts the islanding events. RTDS model (Case B) After CESI residential loads characterization, a large 4- wires unbalanced LV grid has been implemented by ENEL-CESI in the Real-Time Digital Simulator (RTDS) installed in the ENEL Smart Grid Test Center of Milano. The RTDS allows to simulate a large number of power CIRED2015 3/5

4 system components and control model in real-time, in the time domain, using the Dommel algorithm. The LV grid, represented in Fig. 8, is composed by three feeders (urban, rural, and urban-rural mixed feeder), single and three-phase loads (with the caracteristics and dynamics derived by the CESI load caracterization) and 18 PV inverter-based distributed generators (6 threephase 10 Wp, 3 three-phase 20 Wp, 4 single-phase 6 Wp, 5 single-phase 3 Wp). Each generator is regulated in P,Q mode, where the P setpoint is generated using the P-f characteristic represented in Figure 2 b). Indeed, the Q set-point is generated using the Q-V characteristic represented in Fig. 2a. Generators are synchronized to the grid voltage using a PLL and the coupling to the grid is performed using a transformer with short-circuit impedance equal to 6%. Finally, the interface protection and the capability curve has been modeled for each generator. The LV grid is fed, from the MV grid, by a Dy11 MV/LV transformer. The grid neutral wire is connected to the transformer secondary winding neutral point. Lines are represented using the PI section model, where the zero-sequence impedance taes into account the neutral wire effect. DIgSILENT Power Factory are reported here, but similar results were obtained with the switching and average Simulin models. The tests have been carried out modifying the loads and inverter rated powers, in order to analyze the islanded grid behavior under different initial conditions. Frequency [Hz] P g [W] P L [W] P g = P L P g < P L P g > P L Time [s] Voltage p.u. Time [s] Figure 9 - Frequency and voltage at the LV Busbar 0.4 V Figure 8 - RTDS model of the LV grid (Case B) EXAMPLES OF SIMULATION RESULTS In this wor parametric analyses considering various combinations of Q(V) and P(f) regulations have been performed, taing into account the inertia of rotating machines and the initial active and reactive power unbalance, in order to identify the role of the different parameters in determining islanding conditions. In the following, few samples of the results obtained are presented and discussed. An Example of Results for Case A The inverter model has been tested with dynamic load models, including the residential and industrial model parameters of [3]. Results show how uncontrolled islanding operations occur in a LV networ. Furthermore, the influence of the standards regulation requirements leads to islanding events starting from different power balance conditions between loads and generator. Due to space constraints, only results performed with Fig. 9 shows frequency and voltage of the islanded LV grid portion between the standards imposed thresholds. The uncontrolled islanded condition is facilitated by the regulation of active and reactive power, but also due to a regulation effect of the dynamic load model considered. Examples of Results for Case B RTDS simulation results are shown in Table 2. In this case the load model parameters are based on the updated measurements reported in Table 1. It may be observed that: 1. With only PV static generation, without any Q(V) and P(f) regulation, islanding is not possible even in case of small power unbalance. The same occurs, if part of PV generation is substituted by synchronous machines. 2. With only PV static generation, with Q(V) and P(f) regulation with hysteresis (according to CEI 0-21 Italian rules), islanding is not possible even in case of small power unbalance. Instead, if hysteresis is excluded for P(f) regulation (lie requested in RfG rules from ENTSOE), stable islanding operation is CIRED2015 4/5

5 possible only if the generation is greater than the load. This is possible because the P(f) may reduce the generation power, according to the frequency growth, until a new balance condition will be restored. The same occurs, if part of PV generation is substituted by synchronous machines. 3. With only PV static generation, with or without any Q(V) and P(f) regulation, transient islanding is always possible even in case of small power unbalance. In this case the generation could be disconnected before fast reclosing (operated on MV side) only if narrow frequency thresholds are activated. On the other hand, if part of PV generation is substituted by synchronous machines, it is possible to disconnect the generation during the fast reclosing only if a large power unbalance is present. Again this phenomenon is due to the inertia increment of rotating machines. Of course, the above mentioned results have to be considered as qualitative and not quantitative due to the variability and uncertainty of all factors influencing the transient to reach the island operation and during the island operation itself: a) V and f measurement methods; b) actuation periods of Q(V) and P(f) regulations; c) loads behavior in function to V and f; d) power factor; e) generators and loads inertia. These factors are not completely determinable because, for some of them, a reference to standards does not exist. CONCLUSIONS Before new networ code on Requirements for Generators (RfG), narrow band frequency thresholds hindered stable island and guaranteed, with very high probability, disconnection before fast reclosing operated by the circuit breaer at the beginning of MV feeder. After RfG requirements (partly introduced in some Countries), the possibility of uncontrolled islanding operation has significantly increased. The conclusions of the present study are, anyway, qualitative, because studies are valid only for the used loads models and generators models; in particular, the different dynamic response of the loads intentionally adopted by the two studies, highly influences the behaviour of the phenomena. In particular, it should be better investigated the dynamic characterization of loads (P and Q variation function of V and f, inertia, cos, etc) in order to achieve sufficient level of details, not below that of IEEE 1993 report [3] which is old and focused on the creation of aggregations at HV level. With regards to generators, different generators capabilities strongly influence the system behaviour. Finally, further potential influencing factors/elements are not still fully investigated: fast voltage support, power system stabilization, synthetic inertia, power factor regulation [6], and energy storage systems. Such elements should be included as well in dynamic studies, in order to assess their effects on the system. REFERENCES [1] CEI Comitato Elettrotecnico Italiano, Standard-CEI 0-16, Reference technical rules for the connection of active and passive consumers to the HV and MV electrical networs of distribution Company, [2] CEI Comitato Elettrotecnico Italiano, Standard-CEI 0-21, Reference technical rules for the connection of active and passive users to the LV electrical Utilities, [3] IEEE Tas Force on Load Representation for Dynamic Performance, 1993 Load Representation for dynamic performance analysis, IEEE Transactions on Power Systems, Vol. 8, No.2. [4] K. Tomiyama et al., 2003, Modeling of Load During and after System faults based on Actual Field Data,Proceedings IEEE Power Engineering Society General Meeting [5] Y. Xue, L. Chang, S. Bæhøj Kjær, J. Bordonau, and T. Shimizu, 2004, " Topologies of Single-Phase Inverters for Small Distributed Power Generators:An Overview", IEEE Trans. on Power Electronics, Vol.19,No. 5, pp [6] L. Cocchi, A. Cerretti et al. Influence of average power factor management on distribution networ power losses" CIRED 2015 Lyon conference. Generation type No regulation Q(V), P(f) Regulation Q(V), P(f) with histeresys CEI 0-21 Regulation Q(V), P(f) without histeresys RfG (soglie strette non attive) P%>0 Stable island (soglie strette non attive) P%>0 Transient island, not permanent operation Narrow tresholds enabled:<0.5 s Narrow tresholds disabled: <0.7 s, scatto V Narrow tresholds enabled:<0.8 s Narrow tresholds disabled: <1 s, scatto V Narrow tresholds enabled: <0.6 s, Narrow tresholds disabled: <5 s, trip V Narrow tresholds enabled:<1.5 s Narrow tresholds disabled: <9 s, large strshold trip Narrow tresholds enabled: <0.6 s Narrow tresholds disabled:<5.2 s, large treshold trip or trip V Narrow tresholds enabled:<3 s Narrow tresholds disabled: <14 s, large strshold trip Disconnection before FR (0.6 s) if P%> 0% If P%> 45% if P%> 10% If P%>99% if P%> 10% if P%> 99% Table 2 RTDS simulation results. CIRED2015 5/5

Transient Stability Assessment of Synchronous Generator in Power System with High-Penetration Photovoltaics (Part 2)

Transient Stability Assessment of Synchronous Generator in Power System with High-Penetration Photovoltaics (Part 2) Journal of Mechanics Engineering and Automation 5 (2015) 401-406 doi: 10.17265/2159-5275/2015.07.003 D DAVID PUBLISHING Transient Stability Assessment of Synchronous Generator in Power System with High-Penetration

More information

HOW TO DEAL WITH ELECTROMAGNETIC DISTURBANCES CAUSED BY NEW INVERTER TECHNOLOGIES CONNECTED TO PUBLIC NETWORK

HOW TO DEAL WITH ELECTROMAGNETIC DISTURBANCES CAUSED BY NEW INVERTER TECHNOLOGIES CONNECTED TO PUBLIC NETWORK HOW TO DEAL WITH ELECTROMAGNETIC DISTURBANCES CAUSED BY NEW INVERTER TECHNOLOGIES CONNECTED TO PUBLIC NETWORK Xavier YANG EDF R&D - France xavier.yang@edf.fr Ludovic BERTIN EDF R&D - France ludovic-g.bertin@edf.fr

More information

Selecting the current rating for equipment

Selecting the current rating for equipment Selecting the current rating for equipment 1. Rated current: the maximum continuous load current. Short-time withstand current: thermal withstand current term term is given for 1s or 3s short circuit current

More information

Centralized Supplementary Controller to Stabilize an Islanded AC Microgrid

Centralized Supplementary Controller to Stabilize an Islanded AC Microgrid Centralized Supplementary Controller to Stabilize an Islanded AC Microgrid ESNRajuP Research Scholar, Electrical Engineering IIT Indore Indore, India Email:pesnraju88@gmail.com Trapti Jain Assistant Professor,

More information

Single-Phase Synchronverter for DC Microgrid Interface with AC Grid

Single-Phase Synchronverter for DC Microgrid Interface with AC Grid The First Power Electronics and Renewable Energy Workshop (PEREW 2017) March 1-2, 2017- Aswan Faculty of Engineering, Aswan Egypt Single-Phase Synchronverter for Microgrid Interface with AC Grid Presenter:

More information

Fault Calculation Methods

Fault Calculation Methods ELEC9713 Industrial and Commercial Power Systems Fault Calculation Methods There are two major problems that can occur in electrical systems: these are open circuits and short circuits. Of the two, the

More information

Analytical Study Based Optimal Placement of Energy Storage Devices in Distribution Systems to Support Voltage and Angle Stability

Analytical Study Based Optimal Placement of Energy Storage Devices in Distribution Systems to Support Voltage and Angle Stability University of Wisconsin Milwaukee UWM Digital Commons Theses and Dissertations June 2017 Analytical Study Based Optimal Placement of Energy Storage Devices in Distribution Systems to Support Voltage and

More information

The influence of the self-excited induction machine into the electrical grid under instability situation - Real case measurement

The influence of the self-excited induction machine into the electrical grid under instability situation - Real case measurement International Conference on Renewable Energies and Power Quality (ICREPQ 17) Malaga (Spain), 4 th to 6 th April, 2017 Renewable Energy and Power Quality Journal (RE&PQJ) ISSN 2172-08 X, No.15 April 2017

More information

Selected paper. Consistent circuit technique for zero-sequence currents evaluation in interconnected single/three-phase power networks

Selected paper. Consistent circuit technique for zero-sequence currents evaluation in interconnected single/three-phase power networks Diego Bellan 1,*, Sergio A. Pignari 1, Gabrio Superti- Furga 2 J. Electrical Systems Special issue AMPE2015 Selected paper Consistent circuit technique for zero-sequence currents evaluation in interconnected

More information

Power Quality. Guide for electrical design engineers. Power Quality. Mitigation of voltage unbalance

Power Quality. Guide for electrical design engineers. Power Quality. Mitigation of voltage unbalance Guide for electrical design engineers Power Quality Zbigniew Hanzelka GH-University of Science & Technology Mitigation of voltage unbalance U U = C = - = L U U = - U = - U Power Quality Power Quality.

More information

IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 31, NO. 5, MAY Xiaolong Chen and Yongli Li

IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 31, NO. 5, MAY Xiaolong Chen and Yongli Li IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 31, NO. 5, MAY 2016 3559 An Islanding Detection Method for Inverter-Based Distributed Generators Based on the Reactive Power Disturbance Xiaolong Chen and Yongli

More information

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester Electrical and Electronics Engineering EE 1352 Power System Analysis (Regulation 2008) Time: Three hours Answer all questions Part A (10

More information

Power System Stability and Control. Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India

Power System Stability and Control. Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India Power System Stability and Control Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India Contents Chapter 1 Introduction to Power System Stability

More information

DYNAMIC RESPONSE OF A GROUP OF SYNCHRONOUS GENERATORS FOLLOWING DISTURBANCES IN DISTRIBUTION GRID

DYNAMIC RESPONSE OF A GROUP OF SYNCHRONOUS GENERATORS FOLLOWING DISTURBANCES IN DISTRIBUTION GRID Engineering Review Vol. 36 Issue 2 8-86 206. 8 DYNAMIC RESPONSE OF A GROUP OF SYNCHRONOUS GENERATORS FOLLOWING DISTURBANCES IN DISTRIBUTION GRID Samir Avdaković * Alija Jusić 2 BiH Electrical Utility Company

More information

ECE 422/522 Power System Operations & Planning/ Power Systems Analysis II 3 Load Modeling

ECE 422/522 Power System Operations & Planning/ Power Systems Analysis II 3 Load Modeling ECE 422/522 Power System Operations & Planning/ Power Systems Analysis II 3 Load Modeling Spring 2014 Instructor: Kai Sun 1 References 1. Load Performance for Dynamic Performance Analysis, IEEE Committee

More information

Basic Distribution Software Tasks

Basic Distribution Software Tasks The Wind Interconnection Workshop Golden, CO May 22, 2013 Tom McDermott, tom@meltran.com MelTran, Inc. Basic Distribution Software Tasks Current Flow and Voltage Drop Conductor Overload? Voltage Range?

More information

Basics of Electric Circuits

Basics of Electric Circuits António Dente Célia de Jesus February 2014 1 Alternating Current Circuits 1.1 Using Phasors There are practical and economic reasons justifying that electrical generators produce emf with alternating and

More information

Chapter 3 AUTOMATIC VOLTAGE CONTROL

Chapter 3 AUTOMATIC VOLTAGE CONTROL Chapter 3 AUTOMATIC VOLTAGE CONTROL . INTRODUCTION TO EXCITATION SYSTEM The basic function of an excitation system is to provide direct current to the field winding of the synchronous generator. The excitation

More information

Hybrid Time Domain Simulation: Application to Fault Induced Delayed Voltage Recovery (FIDVR)

Hybrid Time Domain Simulation: Application to Fault Induced Delayed Voltage Recovery (FIDVR) Hybrid Time Domain Simulation: Application to Fault Induced Delayed Voltage Recovery (FIDVR) Vijay Vittal Arizona State University PSERC Webinar Jan. 2, 25 Presentation background The work presented in

More information

F F FAULT CURRENT Prospective. 1. Introduction. 2. Types of fault conditions

F F FAULT CURRENT Prospective. 1. Introduction. 2. Types of fault conditions FAULT CURRENT F F13-13 FAULT CURRENT - Contents 1. Introduction 2. Types of fault conditions 3 fault current must be determined 3.1 Purposes for which of prospective fault current magnitudes are used 3.2

More information

KINGS COLLEGE OF ENGINEERING Punalkulam

KINGS COLLEGE OF ENGINEERING Punalkulam KINGS COLLEGE OF ENGINEERING Punalkulam 613 303 DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING POWER SYSTEM ANALYSIS QUESTION BANK UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A (TWO MARK

More information

Magnetic Cores Modeling for Ferroresonance Computations using the Harmonic Balance Method

Magnetic Cores Modeling for Ferroresonance Computations using the Harmonic Balance Method 1 Magnetic Cores Modeling for Ferroresonance Computations using the armonic Balance Method N. A. Janssens, Senior Member, IEEE Abstract-- The determination of the ris of ferroresonance in actual V or MV

More information

Q-V droop control using fuzzy logic and reciprocal characteristic

Q-V droop control using fuzzy logic and reciprocal characteristic International Journal of Smart Grid and Clean Energy Q-V droop control using fuzzy logic and reciprocal characteristic Lu Wang a*, Yanting Hu a, Zhe Chen b a School of Engineering and Applied Physics,

More information

A Computer Application for Power System Control Studies

A Computer Application for Power System Control Studies A Computer Application for Power System Control Studies Dinis C. A. Bucho Student nº55262 of Instituto Superior Técnico Technical University of Lisbon Lisbon, Portugal Abstract - This thesis presents studies

More information

Reactive Power Flow Control of a Dual Unified Power Quality Conditioner

Reactive Power Flow Control of a Dual Unified Power Quality Conditioner Reactive Power Flow Control of a Dual Unified Power uality Conditioner aimon M. Fagundes anta Catarina tate University UDEC Electric Power Processing Group - npee 89.19-71, Joinville - C, Brazil saimon.m.f.@gmail.com

More information

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION EE 6501 POWER SYSTEMS UNIT I INTRODUCTION PART A (2 MARKS) 1. What is single line diagram? A Single line diagram is diagrammatic representation of power system in which the components are represented by

More information

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur Lecture - 9 Transmission Line Steady State Operation Welcome to lesson 9, in Power

More information

Grid-connected photovoltaic systems based on nonlinear control.

Grid-connected photovoltaic systems based on nonlinear control. University of Louisville ThinkIR: The University of Louisville's Institutional Repository Electronic Theses and Dissertations 5-2018 Grid-connected photovoltaic systems based on nonlinear control. Pablo

More information

ELECTRIC POWER CIRCUITS BASIC CONCEPTS AND ANALYSIS

ELECTRIC POWER CIRCUITS BASIC CONCEPTS AND ANALYSIS Contents ELEC46 Power ystem Analysis Lecture ELECTRC POWER CRCUT BAC CONCEPT AND ANALY. Circuit analysis. Phasors. Power in single phase circuits 4. Three phase () circuits 5. Power in circuits 6. ingle

More information

DISTURBANCE LOAD MODELLING WITH EQUIVALENT VOLTAGE SOURCE METHOD IN GRID HARMONIC ASSESSMENT

DISTURBANCE LOAD MODELLING WITH EQUIVALENT VOLTAGE SOURCE METHOD IN GRID HARMONIC ASSESSMENT DISTURBANCE LOAD MODELLING WITH EQUIVALENT VOLTAGE SOURCE METHOD IN GRID HARMONIC ASSESSMENT Xavier YANG Xingyan NIU Bruno PASZKIER EDF R&D France EDF R&D China EDF R&D - France xavier.yang@edf.fr xingyan.niu@edf.fr

More information

THREE-PHASE CIRCUITS

THREE-PHASE CIRCUITS THR-HAS CIRCUITS 4.1 Introduction Generation, Transmission and distribution of electricity via the National Grid system is accomplished by three-phase alternating currents. The voltage induced by a single

More information

LO 1: Three Phase Circuits

LO 1: Three Phase Circuits Course: EEL 2043 Principles of Electric Machines Class Instructor: Dr. Haris M. Khalid Email: hkhalid@hct.ac.ae Webpage: www.harismkhalid.com LO 1: Three Phase Circuits Three Phase AC System Three phase

More information

Unit certificate for solar inverters

Unit certificate for solar inverters Unit certificate for solar inverters Certificate number: MOE 09-0326-14 Original 2013-08-07 _ of 4 This certificate replaces certificate number MOE 09-0326-11. For restrictions and conditions of validity,

More information

Modeling and Simulation of DIGSILENT-based Micro-grid System

Modeling and Simulation of DIGSILENT-based Micro-grid System Modeling and Simulation of DIGSILENT-based Micro-grid System Zhang Yang, Zhu Xueling, Li Qiang 2, Liu Tonghe 3 North China University of Water Resources and Electric Power Zhengzhou China-4500 2 Henan

More information

Stability and power sharing in microgrids

Stability and power sharing in microgrids Stability and power sharing in microgrids J. Schiffer 1, R. Ortega 2, J. Raisch 1,3, T. Sezi 4 Joint work with A. Astolfi and T. Seel 1 Control Systems Group, TU Berlin 2 Laboratoire des Signaux et Systémes,

More information

MICROGRID is a future trend of integrating renewable

MICROGRID is a future trend of integrating renewable IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 64, NO. 7, JULY 2017 5741 New Perspectives on Droop Control in AC Microgrid Yao Sun, Xiaochao Hou, Jian Yang, Hua Han, Mei Su, and Josep M. Guerrero Abstract

More information

Optimal Placement & sizing of Distributed Generator (DG)

Optimal Placement & sizing of Distributed Generator (DG) Chapter - 5 Optimal Placement & sizing of Distributed Generator (DG) - A Single Objective Approach CHAPTER - 5 Distributed Generation (DG) for Power Loss Minimization 5. Introduction Distributed generators

More information

RENEWABLE INTEGRATION AND PROTECTION STUDIES ON A 750-NODE DISTRIBUTION GRID USING A REAL-TIME SIMULATOR AND A DELAY-FREE PARALLEL SOLVER

RENEWABLE INTEGRATION AND PROTECTION STUDIES ON A 750-NODE DISTRIBUTION GRID USING A REAL-TIME SIMULATOR AND A DELAY-FREE PARALLEL SOLVER RENEWABLE INTEGRATION AND PROTECTION STUDIES ON A 750-NODE DISTRIBUTION GRID USING A REAL-TIME SIMULATOR AND A DELAY-FREE PARALLEL SOLVER ABSTRACT Christian DUFOUR OPAL-RT Technologies, Canada christian.dufour@opal-rt.com

More information

Reactive power control strategies for UNIFLEX-PM Converter

Reactive power control strategies for UNIFLEX-PM Converter Reactive power control strategies for UNIFLEX-PM Converter S. Pipolo, S. Bifaretti, V. Bonaiuto Dept. of Industrial Engineering University of Rome Tor Vergata Rome, Italy Abstract- The paper presents various

More information

A simple model based control of self excited induction generators over a wide speed range

A simple model based control of self excited induction generators over a wide speed range ISSN 1 746-7233, England, UK World Journal of Modelling and Simulation Vol. 10 (2014) No. 3, pp. 206-213 A simple model based control of self excited induction generators over a wide speed range Krishna

More information

PowerApps Optimal Power Flow Formulation

PowerApps Optimal Power Flow Formulation PowerApps Optimal Power Flow Formulation Page1 Table of Contents 1 OPF Problem Statement... 3 1.1 Vector u... 3 1.1.1 Costs Associated with Vector [u] for Economic Dispatch... 4 1.1.2 Costs Associated

More information

Novel Approach to Develop Behavioral Model Of 12-Pulse Converter

Novel Approach to Develop Behavioral Model Of 12-Pulse Converter Novel Approach to Develop Behavioral Model Of 12-Pulse Converter Amit Sanglikar, and Vinod John, Member, IEEE Abstract--A novel approach to develop behavioral model of 12- pulse converter, which reduces

More information

ADVANCED ISLANDING DETECTION METHODS FOR SINGLE PHASE GRID CONNECTED PV INVERTERS

ADVANCED ISLANDING DETECTION METHODS FOR SINGLE PHASE GRID CONNECTED PV INVERTERS ADVANCED ISLANDING DETECTION METHODS FOR SINGLE PHASE GRID CONNECTED PV INVERTERS by Bahador Mohammadpour A thesis submitted to the Department of Electrical and Computer Engineering In conformity with

More information

An improved deadbeat predictive current control for permanent magnet linear synchronous motor

An improved deadbeat predictive current control for permanent magnet linear synchronous motor Indian Journal of Engineering & Materials Sciences Vol. 22, June 2015, pp. 273-282 An improved deadbeat predictive current control for permanent magnet linear synchronous motor Mingyi Wang, iyi i, Donghua

More information

Control Strategies for Microgrids

Control Strategies for Microgrids Control Strategies for Microgrids Ali Mehrizi-Sani Assistant Professor School of Electrical Engineering and Computer Science Washington State University Graz University of Technology Thursday, November

More information

Application of the Three-Phase STATCOM in Voltage Stability

Application of the Three-Phase STATCOM in Voltage Stability Application of the Three-Phase STATCOM in oltage Stability uan M.Ramírez 1 and.l. Murillo Pérez 1 Center for Research and Advanced Studies, National Polytechnic Institute Prolongación López Mateos Sur

More information

Proximity effect on bare buried conductors connecting together MV/LV substations earth electrodes

Proximity effect on bare buried conductors connecting together MV/LV substations earth electrodes Proceedings of the 6 IASME/WSEAS International onference on Energy & Environmental Systems, halkida, Greece, May 8-, 6 (pp7-) Proximity effect on bare buried conductors connecting together MV/LV s earth

More information

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous)

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad - 500 043 ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK Course Name : Computer Methods in Power Systems Course Code : A60222

More information

HIGH PERFORMANCE MAGNETIC SHIELDING SOLUTION FOR ELF SOURCES

HIGH PERFORMANCE MAGNETIC SHIELDING SOLUTION FOR ELF SOURCES HIGH PERFORMANCE MAGNETIC SHIELDING SOLUTION FOR ELF SOURCES Aldo CANOVA, Luca GIACCONE Dipartimento Energia, Politecnico di Torino -Italy aldo.canova@polito.it ABSTRACT In this paper some particular aspects

More information

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A 1. What are the advantages of an inter connected system? The advantages of an inter-connected system are

More information

Module 4. Single-phase AC Circuits

Module 4. Single-phase AC Circuits Module 4 Single-phase AC Circuits Lesson 14 Solution of Current in R-L-C Series Circuits In the last lesson, two points were described: 1. How to represent a sinusoidal (ac) quantity, i.e. voltage/current

More information

Modeling methodology and fault simulation of distribution networks integrated with inverter-based DG

Modeling methodology and fault simulation of distribution networks integrated with inverter-based DG Wang et al Protection and Control of Modern Power Systems (2017) 2:31 DOI 10116/s41601-017-005-9 Protection and Control of Modern Power Systems METHODOLOGY Modeling methodology and fault simulation of

More information

Dynamic Behavior of Three phase Inductions Motors as Loads in an Electric Power System with Distributed Generation, a Case of Study.

Dynamic Behavior of Three phase Inductions Motors as Loads in an Electric Power System with Distributed Generation, a Case of Study. Dynamic Behavior of Three phase Inductions Motors as Loads in an Electric Power System with Distributed Generation, a Case of Study. Marcelo Rodrigo García Saquicela, Ernesto Ruppert Filho, José Luis Azcue

More information

Mathematical Modeling and Dynamic Simulation of a Class of Drive Systems with Permanent Magnet Synchronous Motors

Mathematical Modeling and Dynamic Simulation of a Class of Drive Systems with Permanent Magnet Synchronous Motors Applied and Computational Mechanics 3 (2009) 331 338 Mathematical Modeling and Dynamic Simulation of a Class of Drive Systems with Permanent Magnet Synchronous Motors M. Mikhov a, a Faculty of Automatics,

More information

Effects of Capacitor Bank Installation in a Medium Voltage (MV) Substation

Effects of Capacitor Bank Installation in a Medium Voltage (MV) Substation Effects of Capacitor Bank Installation in a Medium Voltage (MV) Substation Adesina, Lambe Mutalub Department of Engineering & Standardization, Eko Electricity Distribution Plc, 24/25, Marina, Lagos Island,

More information

Power system modelling under the phasor approximation

Power system modelling under the phasor approximation ELEC0047 - Power system dynamics, control and stability Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct October 2018 1 / 16 Electromagnetic transient vs. phasor-mode simulations

More information

INTRODUCTION TO THE PROBLEMS OF ANALYSIS AND CONTROL OF ELECTRIC POWER SYSTEMS

INTRODUCTION TO THE PROBLEMS OF ANALYSIS AND CONTROL OF ELECTRIC POWER SYSTEMS CHAPTER 1 INTRODUCTION TO THE PROBLEMS OF ANALYSIS AND CONTROL OF ELECTRIC POWER SYSTEMS 1.1. PRELIMINARIES 1.1.1 Electric power can be easily and efficiently transported to locations far from production

More information

Equivalent parameters of induction machines windings in permanent nonsinusoidal regime. Theoretical and experimental determination

Equivalent parameters of induction machines windings in permanent nonsinusoidal regime. Theoretical and experimental determination Proceedings of the 9th WSEAS International Conference on POWE SYSTEMS Equivalent parameters of induction machines windings in permanent nonsinusoidal regime Theoretical and experimental determination SOIN

More information

Impact of Photovoltaic Generation On The Power System Stability

Impact of Photovoltaic Generation On The Power System Stability Impact of Photovoltaic Generation On The Power System Stability Eng. Abdelmoezz Ahmed Eid Dept. of Electrical Engineering Al-Azhar University Cairo, Egypt engabdelmoezz@gmail.com Dr. Tarek Mahmoud Dept.

More information

Keeping medium-voltage grid operation within secure limits

Keeping medium-voltage grid operation within secure limits Chaire académique ORES «Smart Grids Smart Metering» Journée d études, Fac. Polytech. UMons, 20 nov. 2014 Keeping medium-voltage grid operation within secure limits Thierry Van Cutsem Hamid Soleimani Bidgoli

More information

Application Note - SolarEdge Inverters, Power Control Options

Application Note - SolarEdge Inverters, Power Control Options Version 3, December 2017 Application Note - SolarEdge Inverters, Power Control Options Version History Version 3 (December 2017) Added Active Power ramp up option Added new active power phase balancing

More information

The Effects of Mutual Coupling and Transformer Connection Type on Frequency Response of Unbalanced Three Phases Electrical Distribution System

The Effects of Mutual Coupling and Transformer Connection Type on Frequency Response of Unbalanced Three Phases Electrical Distribution System IJSRD - International Journal for Scientific Research & Development Vol. 1, Issue 9, 2013 ISSN (online): 2321-0613 The Effects of Mutual Coupling and Transformer Connection Type on Frequency Response of

More information

Participation in the Frequency Regulation Control of a Resilient Microgrid for a Distribution Network

Participation in the Frequency Regulation Control of a Resilient Microgrid for a Distribution Network International Journal of Integrated Energy Systems, Vol, No, January-June 9 Participation in the Frequency Regulation Control of a Resilient Microgrid for a Distribution Network Peng LI Philippe DEGOBER

More information

An improved methodology for determining MV to LV voltage unbalance transfer coefficient

An improved methodology for determining MV to LV voltage unbalance transfer coefficient University of Wollongong Research Online Faculty of Engineering - Papers (Archive) Faculty of Engineering and Information Sciences 2008 An improved methodology for determining MV to LV voltage unbalance

More information

Effect of core balance current transformer errors on sensitive earth-fault protection in compensated MV networks

Effect of core balance current transformer errors on sensitive earth-fault protection in compensated MV networks 24th International Conference & Exhibition on Electricity Distribution CIRED) 12-15 June 2017 Session 3: Operation, control and protection Effect of core balance current transformer errors on sensitive

More information

Dynamic Modeling of Surface Mounted Permanent Synchronous Motor for Servo motor application

Dynamic Modeling of Surface Mounted Permanent Synchronous Motor for Servo motor application 797 Dynamic Modeling of Surface Mounted Permanent Synchronous Motor for Servo motor application Ritu Tak 1, Sudhir Y Kumar 2, B.S.Rajpurohit 3 1,2 Electrical Engineering, Mody University of Science & Technology,

More information

Cahier Technique N 13 Principe de réduction des courants d enclenchement des transformateurs

Cahier Technique N 13 Principe de réduction des courants d enclenchement des transformateurs Cahier Technique N 13 Principe de réduction des courants d enclenchement des transformateurs Numerical transformer inrush current minimizer Principle of the operation Rev 1.0 Document version information

More information

Three Phase Circuits

Three Phase Circuits Amin Electronics and Electrical Communications Engineering Department (EECE) Cairo University elc.n102.eng@gmail.com http://scholar.cu.edu.eg/refky/ OUTLINE Previously on ELCN102 Three Phase Circuits Balanced

More information

ECE 585 Power System Stability

ECE 585 Power System Stability Homework 1, Due on January 29 ECE 585 Power System Stability Consider the power system below. The network frequency is 60 Hz. At the pre-fault steady state (a) the power generated by the machine is 400

More information

Chapter 8 VOLTAGE STABILITY

Chapter 8 VOLTAGE STABILITY Chapter 8 VOTAGE STABIITY The small signal and transient angle stability was discussed in Chapter 6 and 7. Another stability issue which is important, other than angle stability, is voltage stability.

More information

Modeling of Power System Components During Electromagnetic Transients

Modeling of Power System Components During Electromagnetic Transients Modeling of Power System Components During Electromagnetic Transients 1 Paweł Sowa, 2 Rafał Kumala and 3 Katarzyna Łuszcz 1, 2,3 Faculty of Electrical Engineering, Silesian University of Technology/ Institute

More information

Fault Location in Distribution Feeders with Distributed Generation using Positive Sequence Apparent Impedance

Fault Location in Distribution Feeders with Distributed Generation using Positive Sequence Apparent Impedance Fault Location in Distribution Feeders with Distributed Generation using Positive Sequence Apparent Impedance ARTURO SUMAN BRETAS Federal University of Rio Grande do Sul Department of Electrical Engineering

More information

Locating Distributed Generation. Units in Radial Systems

Locating Distributed Generation. Units in Radial Systems Contemporary Engineering Sciences, Vol. 10, 2017, no. 21, 1035-1046 HIKARI Ltd, www.m-hikari.com https://doi.org/10.12988/ces.2017.79112 Locating Distributed Generation Units in Radial Systems Gabriel

More information

Parameter Prediction and Modelling Methods for Traction Motor of Hybrid Electric Vehicle

Parameter Prediction and Modelling Methods for Traction Motor of Hybrid Electric Vehicle Page 359 World Electric Vehicle Journal Vol. 3 - ISSN 232-6653 - 29 AVERE Parameter Prediction and Modelling Methods for Traction Motor of Hybrid Electric Vehicle Tao Sun, Soon-O Kwon, Geun-Ho Lee, Jung-Pyo

More information

EE 742 Chapter 3: Power System in the Steady State. Y. Baghzouz

EE 742 Chapter 3: Power System in the Steady State. Y. Baghzouz EE 742 Chapter 3: Power System in the Steady State Y. Baghzouz Transmission Line Model Distributed Parameter Model: Terminal Voltage/Current Relations: Characteristic impedance: Propagation constant: π

More information

ABSTRACT. residential Photovoltaic (PV) systems. The investigation is done on both conventional and

ABSTRACT. residential Photovoltaic (PV) systems. The investigation is done on both conventional and ABSTRACT HOOSHYAR, HOSSEIN. System Protection for High PV-Penetrated Residential Distribution Systems (Green Hubs). (Under the direction of Dr Mesut E. Baran). This study investigates the protection issues

More information

Application Note - SolarEdge Inverters, Power Control Options

Application Note - SolarEdge Inverters, Power Control Options Application Note - SolarEdge Inverters, Power Control Options Contents Introduction... 1 Installation Note for Three Phase Inverters... 1 The Power Control Menu... 2 Energy Manager... 2 RRCR Conf.... 2

More information

Ref: HLSR 16-PW; HLSR 32-PW; HLSR 40-PW-000; HLSR 50-PW-000,

Ref: HLSR 16-PW; HLSR 32-PW; HLSR 40-PW-000; HLSR 50-PW-000, Digital Current Transducer HLSR-PW series I P N = 16... 50 A Ref: HLSR 16-PW; HLSR 32-PW; HLSR 40-PW-000; HLSR 50-PW-000, Bitstream output from on onboard Sigma Delta modulator. For the electronic measurement

More information

GENERATOR INTERCONNECTION APPLICATION

GENERATOR INTERCONNECTION APPLICATION GENERATOR INTERCONNECTION APPLICATION FOR BUY-ALL/SELL-ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 20 KW BUT LESS THAN OR EQUAL TO 1 MW Electric Utility Contact Information Great Lakes Energy

More information

Dynamic Modeling of GE 1.5 and 3.6 Wind Turbine-Generators

Dynamic Modeling of GE 1.5 and 3.6 Wind Turbine-Generators GE Power Systems Dynamic Modeling of GE.5 and 3.6 Wind Turbine-Generators Prepared by: Nicholas W. Miller William W. Price Juan J. Sanchez-Gasca October 27, 2003 Version 3.0 GE-Power Systems Energy Consulting

More information

An Novel Continuation Power Flow Method Based on Line Voltage Stability Index

An Novel Continuation Power Flow Method Based on Line Voltage Stability Index IOP Conference Series: Earth and Environmental Science PAPER OPEN ACCESS An Novel Continuation Power Flow Method Based on Line Voltage Stability Index To cite this article: Jianfang Zhou et al 2018 IOP

More information

POWER SEMICONDUCTOR BASED ELECTRIC DRIVES

POWER SEMICONDUCTOR BASED ELECTRIC DRIVES POWER SEMICONDUCT BASED ELECTRIC DRIVES [Time: 3 Hrs] [Max. Marks: 80] Instructions: Solve any six questions from Q.No (1 or 2), Q.No (3 or 4), Q.No (5 or 6), Q.No (7 or 8), Q.No (9 or 10), Q.No (11 or

More information

1 Unified Power Flow Controller (UPFC)

1 Unified Power Flow Controller (UPFC) Power flow control with UPFC Rusejla Sadikovic Internal report 1 Unified Power Flow Controller (UPFC) The UPFC can provide simultaneous control of all basic power system parameters ( transmission voltage,

More information

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME: EE 2303 - TRANSMISSION & DISTRIBUTION YEAR / SEM: III/V UNIT-I TRANSMISSION SYSTEM INTRODUCTION PART-A 1. What is

More information

Dynamic Voltage Stability Enhancement of a Microgrid with Static and Dynamic Loads Using Microgrid Voltage Stabilizer

Dynamic Voltage Stability Enhancement of a Microgrid with Static and Dynamic Loads Using Microgrid Voltage Stabilizer Dynamic Voltage Stability Enhancement of a Microgrid with Static and Dynamic Loads Using Microgrid Voltage Stabilizer Kenan Hatipoglu 1, Ismail Fidan 2, Ghadir Radman 3 1 Electrical and Computer Engineering

More information

Risk indexes for studying interconnected earthing systems inside MV networks

Risk indexes for studying interconnected earthing systems inside MV networks Risk Analysis V: Simulation and Hazard Mitigation 67 Risk indexes for studying interconnected earthing systems inside MV networks A. Campoccia & G. Zizzo Department of Electrical, Electronic and Telecommunications

More information

+ ( )= with initial condition

+ ( )= with initial condition Department of Electrical Engineering PhD. Admission Test Full Marks: 90 Time 90 minutes Date: 02.2.204 NAME: Appl. No: Write your answer on the question paper ONLY. All questions carry equal marks. PART

More information

Chapter 2 Control and Modeling of Microgrids

Chapter 2 Control and Modeling of Microgrids Chapter 2 Control and Modeling of Microgrids In this chapter, the control objectives in AC and DC microgrids are discussed separately. This chapter brings together the existing AC and DC microgrid control

More information

Adaptive Fuzzy Logic Power Filter for Nonlinear Systems

Adaptive Fuzzy Logic Power Filter for Nonlinear Systems IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 78-1676,p-ISSN: 30-3331, Volume 11, Issue Ver. I (Mar. Apr. 016), PP 66-73 www.iosrjournals.org Adaptive Fuzzy Logic Power Filter

More information

Grid-Forming Inverters in Microgrids

Grid-Forming Inverters in Microgrids Axel Seibel, Peter Unruh Department: Converters and Drive Technology Fraunhofer IWES Slide 1 Contents Introduction Improving the control of grid-forming inverters SelfSync Improving SelfSync Robust control

More information

CHAPTER 2 MODELING OF POWER SYSTEM

CHAPTER 2 MODELING OF POWER SYSTEM 38 CHAPTER 2 MODELING OF POWER SYSTEM 2.1 INTRODUCTION In the day to day scenario, power is an essential commodity to the human beings. The demand is more in developed countries and there is increase in

More information

Behaviour of synchronous machine during a short-circuit (a simple example of electromagnetic transients)

Behaviour of synchronous machine during a short-circuit (a simple example of electromagnetic transients) ELEC0047 - Power system dynamics, control and stability (a simple example of electromagnetic transients) Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct October 2018 1 / 25 Objectives

More information

IEEE TRANSACTIONS ON SMART GRID, VOL. 6, NO. 6, NOVEMBER Hung D. Nguyen, Student Member, IEEE and Konstantin Turitsyn, Member, IEEE

IEEE TRANSACTIONS ON SMART GRID, VOL. 6, NO. 6, NOVEMBER Hung D. Nguyen, Student Member, IEEE and Konstantin Turitsyn, Member, IEEE IEEE TRANSACTIONS ON SMART GRID, VOL. 6, NO. 6, NOVEMBER 2015 2985 Voltage Multistability and Pulse Emergency Control for Distribution System With Power Flow Reversal Hung D. Nguyen, Student Member, IEEE

More information

Lecture 11 - AC Power

Lecture 11 - AC Power - AC Power 11/17/2015 Reading: Chapter 11 1 Outline Instantaneous power Complex power Average (real) power Reactive power Apparent power Maximum power transfer Power factor correction 2 Power in AC Circuits

More information

Adaptive under frequency load shedding using synchrophasor measurement

Adaptive under frequency load shedding using synchrophasor measurement Adaptive under load shedding using synchrophasor measurement Abstract - The imbalance between the generation and the demand is the major factor that causes instability in a power system. Conventional Under

More information

Analysis of Wind Generator Operations under Unbalanced Voltage Dips in the Light of the Spanish Grid Code

Analysis of Wind Generator Operations under Unbalanced Voltage Dips in the Light of the Spanish Grid Code Energies 0, 4, 48-6; doi:0.3390/en40848 OPEN ACCESS energies ISSN 996-073 www.mdpi.com/journal/energies Article Analysis of Wind Generator Operations under Unbalanced oltage Dips in the Light of the Spanish

More information

Role of Synchronized Measurements In Operation of Smart Grids

Role of Synchronized Measurements In Operation of Smart Grids Role of Synchronized Measurements In Operation of Smart Grids Ali Abur Electrical and Computer Engineering Department Northeastern University Boston, Massachusetts Boston University CISE Seminar November

More information

DEVELOPMENT OF DIRECT TORQUE CONTROL MODELWITH USING SVI FOR THREE PHASE INDUCTION MOTOR

DEVELOPMENT OF DIRECT TORQUE CONTROL MODELWITH USING SVI FOR THREE PHASE INDUCTION MOTOR DEVELOPMENT OF DIRECT TORQUE CONTROL MODELWITH USING SVI FOR THREE PHASE INDUCTION MOTOR MUKESH KUMAR ARYA * Electrical Engg. Department, Madhav Institute of Technology & Science, Gwalior, Gwalior, 474005,

More information

EE Branch GATE Paper 2010

EE Branch GATE Paper 2010 Q.1 Q.25 carry one mark each 1. The value of the quantity P, where, is equal to 0 1 e 1/e 2. Divergence of the three-dimensional radial vector field is 3 1/r 3. The period of the signal x(t) = 8 is 0.4

More information

Total No. of Questions :09] [Total No. of Pages : 03

Total No. of Questions :09] [Total No. of Pages : 03 EE 4 (RR) Total No. of Questions :09] [Total No. of Pages : 03 II/IV B.Tech. DEGREE EXAMINATIONS, APRIL/MAY- 016 Second Semester ELECTRICAL & ELECTRONICS NETWORK ANALYSIS Time: Three Hours Answer Question

More information