GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN Mitglied der Short-Circuit-Testing Liaison (STL) Test Report

Similar documents
Independent, accredited testing station Member laboratory of STL and LOVAG TEST CONFIRMATION. on the given range of performed tests

SWITCHGEAR: design concepts, testing, standards and safety of persons and installations

Independent, accredited testing station Member laboratory of STL and LOVAG TEST CONFIRMATION. on the given range of performed tests

Thermal-Magnetic Circuit Breaker 2210-S2..

Thermal-Magnetic Circuit Breaker 2210-S2..

Thermal-Magnetic Circuit Breaker 2210-S2..

Thermal-Magnetic Circuit Breaker 2210-S2...

Thermal-Magnetic Circuit Breaker 2210-S2...

DATA RACK BUSBAR. Data Rack Busbar Systems A.

Thermal-Magnetic Circuit Breaker 2210-T2...

SPECIFICATION SS 51/9 400KV COUPLING CAPACITORS FOR POWER LINE CARRIER SYSTEM

THE DIMENSIONING OF ELECTRICAL CONDUCTORS FOR USE IN "PANEL BOARDS" ADDRESSED TO HAZARDOUS AREAS - PART THREE

VX25 Enclosure System. Technical documentation PE conductor connection, current carrying capacity

TEST CERTIFICATES OR REPORTS ISSUED BY VEIKI-VNL LTD.

VEIKI-VNL ELECTRIC LARGE LABORATORIES Ltd. TYPE TEST REPORT

5SJ4...-.HG Circuit Breakers to IEC and UL 489

Varius SUMMARY OF MODELS OF HRC FUSE-LINKS

F F FAULT CURRENT Prospective. 1. Introduction. 2. Types of fault conditions

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-T...

MCB NB1-63H Miniature Circuit Breaker

MKV AC Capacitors Damping B High dielectric strength High peak-current capability Especially suitable for snubber circuits

Internal Components Forms of Separation


BETA Protecting. Low-Voltage Fuse Systems. LV HRC fuse links. 3/36 Siemens ET B1 2008

Issued August DATA SHEET. 3VT3 MCCB up to 630 A

A Novel Optimized Design for Busbar Structures using Finite Element Methods

5SP and 5SY Supplementary Protection UL 1077

FAZ tripping characteristics at 30 C: B, C, D to IEC/EN FAZ tripping characteristics at 30 C: R to IEC/EN

3VT4 Molded Case Circuit Breakers up to 1000 A

SIRCOVER Manual transfer switches from 125 to 3200 A

MR medium rating busbar

Issued August DATA SHEET. 3VT5 MCCB up to 1600 A

Amphenol C 091 A/B/D. Circular Connectors. Amphenol-Tuchel Electronics GmbH

EA Guidelines on the Calibration of Temperature Indicators and Simulators by Electrical Simulation and Measurement

Page 2 of 14 Report Ref. No

NYY-J/-o 34 NYCWY 36 NYCY 37 NAYY 38

Pressure transmitters for industrial applications MBS 32 and MBS 33

WIESON TECHNOLOGIES CO., LTD.

Siemens AG Miniature Circuit Breakers. Totally Integrated Power SENTRON. Configuration. Edition 10/2014. Manual. siemens.

INSULATORS INSULATORS

Sealing possibility Electrical endurance (ops) Mechanical endurance (ops) Overvoltage category Standards

Three Core XLPE/LSF/SWA/LSF Power Cable

TeSys circuit-breakers

Amphenol. Amphenol-Tuchel Electronics GmbH. Circular Connectors C 091 A/B/D Series

Imformation of C091D series

O Plus Dry Bushing 25 kv system, 150 kv BIL, 3000 A

An Optimised High Current Impulse Source

Electrical safety testing Checklist

An Innovative Simple Test Circuit for Single-Phase Short Circuit Making Test of High-Voltage Switching Devices

EXEMPLAR NATIONAL CERTIFICATE (VOCATIONAL) ELECTRICAL PRINCIPLES AND PRACTICE NQF LEVEL 3 ( ) (X-Paper) 09:00 12:00

90 MCB MODULAR CIRCUIT BREAKERS FOR CIRCUIT PROTECTION

INFORMATION TECHNOLOGY SYSTEMS SPDs FOR 19 TECHNOLOGY. NET Protector Surge Arrester. Protects switches, HUBs and telecommunication

C120N circuit-breakers B, C and D curves EN 60898/EN 61009: IEC : 10 ka

90 MCB range Modular circuit breakers for circuit protection

ATyS Automatic and remotely operated transfer switches from 125 to 3200 A

Table of Contents Pin-Configuration Selection Guide for HDE, HDS, & EFP

8 Installation Equipment

40 CD RANGE FLUSH-MOUNTING DISTRIBUTION BOARDS AND ENCLOSURES

Single Phase Motors Technical Datasheets

TEST REPORT ENVIRONMENTAL EN 60529:1991+A1:2000

Dr. Michael Müller. Thermal Management for LED applications

Product Series Specification Document

O Plus Dry Bushing 69 kv system, 350 kv BIL, 3000 A. Table of contents

16 Appendix 16 Electrical Research Association Report

Analysis of Very Fast Transients in EHV Gas Insulated Substations

Electric Filed Simulation and Structure Optimization for 40.5kV GIS Based on Finite Element Method

C60N circuit breakers0 B, C and D curves IEC 60898: 6000 A, IEC : 10 ka

Amphenol. Amphenol-Tuchel Electronics GmbH. Series C 146 Heavy Duty Connectors Core Programme

Masterpact. Installation recommendations

LD-LP-LL-LC Rope Safety Switches with reset for emergency stop

Non-Contact Safety Systems CMS

VK2 volume flow controller Overview

Film Capacitors. EMI suppression capacitors. Date: June 2018

Fault Calculation Methods

CDS. high density spring connection

UL 1077 DIN Rail Supplementary Protectors

EA-10/14. EA Guidelines on the Calibration of Static Torque Measuring Devices. Publication Reference PURPOSE

Instruction. Vacuum Circuit Breaker Operator Module. Type 3AH 4.16kV to 38kV. Power Transmission & Distribution

BETA Protecting Miniature Circuit Breakers

SION Lateral 3AE6 Vacuum Circuit Breaker with Lateral Operating Mechanism

v = m / s Thermal Flow Sensors TA with thin-film sensor element Probes Probe Guides Measuring Tubes

SUPPLY, ERECTION & COMMISSIONING OF 2 X 3.15 MVA 33/11KV SUB-STATION at Khuntlipalli,Bargarh ( PACKAGE - B )

Identification File of Type ZE64G23

Hydra Fault Current Limiting HTS Cable to be Installed in the Consolidated Edison Grid

Modeling of Transmission Line and Substation for Insulation Coordination Studies

TEST REPORT IEC :2002 Circuit-Breakers for overcorrect protection for household and similar installation

Installation guide 862 MIT / MIR

COPPER FOR BUSBARS CHAPTER 4: SHORT-CIRCUIT EFFECTS

Damping resistor design consideration

EasyDry transformer bushing Better performance made easy. Power and productivity for a better world TM ABB

Ex-Floodlight PXLED. (Ex-Zone 1, 2, 21 and 22)

Impedance relay and protection assemblies

Feasibility of HTS DC Cables on Board a Ship

Report No 247/ This Report consists of 41 pages

Superconducting Fault Current Limiters

FLT5A FLT5A. abc. abc. Thermometer User Guide. Thermometer User Guide. Internet:

Test Report issued under the responsibility of: Report Number...: B Date of issue...: Total number of pages...

BASE. Rotary limit switch. OptiOnS. FEAtuRES. CERtiFiCAtiOnS

AM 500A 500 WATT AM 1A 1 KILOWATT AM BROADCAST TRANSMITTERS. October, 1999 IM No

TEST REPORT IEC/EN Circuit-breakers for over current protection for household and similar installations

Transcription:

Mitglied der Short-Circuit-Testing Liaison (STL) Test Report Report-No.: 9725Fr Copy-No.: 00 Contents: 16Sheets Equipment under Test: Manufacturer: Client: Metal-enclosed, single-pole metal-clad and SF 6 -insulated medium voltage switchgear 8DA10 (36kV; 2500A; 40kA/3s), circuit-breaker panel with circuit-breaker 3AH Siemens AG, EV MS Siemens AG, EV MS1 G Testing Station: PEHLA Prüffeld Frankfurt / M. Date of Test: 05.06.1997 Applied Test Specifications: IEC 298, 1990-12, clause 6 IEC 694, 1996-05, clause 6 VDE 0670 Teil 6, 1994-03, Abschnitt 6 VDE 0670 Teil 1000, 1995-06, Abschnitt 6 (Entwurf) Tests performed: 1. Temperature-rise test of the circuit-breaker panel with the rated normal current of 2500A. 2. Measurement of the resistance of the main circuits. Test Results: The above mentioned equipment under test has passed the temperature-rise test with the rated normal current of 2500A corresponding to the applied test specifications. GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN Technical Committee Mannheim, 12.06.1997 The test results relate only to the items tested. Without a written permission of PEHLA it is not allowed to make reproduction in extracts of this document. Copying the cover sheet accompanied by sheet 2 and the sheets mentioned here is an exception. DAT-P-013/92-51e

Report-No.: 9725Fr Sheet: 2 Accreditation The PEHLA-Testing station Frankfurt/Main has been approved by the DATech (German accreditation body for technology) according to DIN EN 45001 for tests in the field of high-voltage switchgear and controlgear (Registration-No. DAT-P-013/92-51e). Under reference to DIN EN 45001 PEHLA states the following: - The accreditation of the PEHLA-Testing station or any of its test reports by themselves in no way constitute or imply product approval by DATech or any other body. - If someone refers to a test in an accredited PEHLA-Testing station this reference shall include the accreditation body, i.e. DATech, the relevant scope of the accreditation and the appropriate registration number. PEHLA-Documents A Test Certificate is issued for type tests which have successfully been carried out in full compliance with the relevant specifications or standards and STL Guides valid at the time of the test. For these tests the equipment under test must be clearly identified by technical description, drawings and additional specifications. A Test Document is issued for parts of type tests which have successfully been carried out in full compliance with the relevant specifications or standards and STL Guides valid at the time of test. For these tests the equipment under test must be clearly identified by technical description, drawings and additional specifications. A Test Report is issued for all other tests which have been carried out according to specifications, standards or "PEHLA- Richtlinien" (PEHLA Guides) and/or clients instructions. Similarly, this test report contains all test results, details of the conditions under which the tests were carried out, also details relating to the behaviour of the equipment during test, and its condition after the tests. Addresses: Office: Testing Station: Manufacturer: Client: PEHLA-Geschäftsstelle Hallenweg 40 D-68219 Mannheim PEHLA-Prüffeld Frankfurt/M. Karl - Benz - Str. 22 Siemens AG Power Transmission and Distribution, Medium-Voltage Switchgear and -systems (EV MS) Karl - Benz - Str. 22 D-60386 Frankfurt/M. D-60386 Frankfurt/M. Siemens AG Power Transmission and Distribution, Medium-Voltage Switchgear and -systems (EV MS) EV MS1 G Karl - Benz - Str. 22 D-60386 Frankfurt/M.

Report-No.: 9725Fr Sheet: 3 Table of Contents FRONT SHEET 1 ACCREDITATION 2 TABLE OF CONTENTS 3 PARTICIPANTS OF THE TEST 4 TECHNICAL DATA OF THE EQUIPMENT UNDER TEST 5 TECHNICAL DATA OF THE EQUIPMENT UNDER TEST 6 DRAWING OF THE EQUIPMENT UNDER TEST 7 DRAWING OF THE EQUIPMENT UNDER TEST 8 DRAWING-NO. 9 TEST ARRANGEMENT AND POSITION OF THE MEASURING POINTS 10 MEASUREMENT OF THE RESISTANCE OF THE MAIN CIRCUITS 11 TEMPERATURE-RISE TEST, MEASURANDS 12 TEMPERATURE-RISE TEST, MEASURANDS 13 TEMPERATURE-RISE TEST, DIAGRAM 14 PHOTOS 15 PHOTOS 16

Report-No.: 9725Fr Sheet: 4 Participants of the Test Representatives of Test Committee: Mr. Schuck Mr. Weinel PEHLA-Prüffeld Frankfurt/M. PEHLA-Prüffeld Mannheim-Rheinau Test Engineer: Mr. Mayer PEHLA-Prüffeld Frankfurt/M. (guidance and performance of the test) Client: Mr. R. Müller Siemens AG, EV MS1 G PG1 Other Participants: Mr. Wolff Mr. Bär Siemens AG, EV MS1 G PG1 Siemens AG, EV MS TVF

Report-No.: 9725Fr Sheet: 5 Technical Data of the Equipment under Test Switchgear Instructions of the manufacturer Equipment under Test: Metal-enclosed, single-pole metal-clad and SF 6 -insulated medium-voltage switchgear Type: 8DA10 Manufacturer: Siemens AG, EV MS Serial-No.: 05-1228 Year of manufacture: 1997 Drawing-No.: 005-4030.3, Änd.-Z. 00, Bl. 1- of 11.01.1997 and 864-6866.3, Änd.-Z. 05, Bl. 1+ of 31.08.1990 The drawings and parts list used for the identification of the equipment under test were stamped and signed by the representatives of the PEHLA-Technical Committee. They are kept to the test documents in the test laboratory. The manufacturer has confirmed with his signature that the equipment under test corresponds to the applied drawings and parts list. (continued on sheet No. 9) Rated voltage Rated lightning impulse withstand voltage Rated switching impulse withstand voltage Rated power frequency withstand voltage Rated frequency Rated normal current Rated peak withstand current Rated short-time withstand current Rated duration of short circuit 36 kv 170 kv - kv 70 kv 50/60 Hz 2500 A 100 ka 40 ka 3 s Insulating agent SF 6 Rated filling gauge pressure (20 C) of the circuit-breaker compartment 0,10 MPa Minimum functional gauge pressure (20 C) of the circuit-breaker compartment 0,08 MPa Rated filling gauge pressure (20 C) of the busbar compartment 0,05 MPa Minimum functional gauge pressure (20 C) of the busbar compartment 0,03 MPa Permitted values under internal arc conditions Peak current Short-circuit alternating current Duration of short circuit - ka - ka - s Essential characteristics and installed devices: (continued on sheet No. 6)

Report-No.: 9725Fr Sheet: 6 Technical Data of the Equipment under Test Switchgear Instructions of the manufacturer Essential characteristics and installed devices: (continued from sheet No. 5) 1. Test arrangement (see photo No. 1 and No. 2) Panel-No. Panel type 7 Circuit breaker panel (36kV;1250A; 40kA/3s) 10 Circuit breaker panel (36kV; 1250A; 40kA/3s) 11 Circuit breaker panel (36kV; 2500A; 40kA/3s) 2. Circuit-breaker: Type 3AH4945-4 / Year of manufacture 1997 Panel-No. Serial-No. of the Type of the Serial-No. of the vacuum tube circuit-breaker module vacuum tube L1 L2 L3 7 S 31676131 VS 30040 / D23 000809 000795 000799 10 S 31676132 VS 30040 / D23 000819 000797 000804 11 S 31676130 VS 30040 / D23 000812 000816 000817 3. Current transformers Panel-No. Type of the Transformation Serial-No. of the current transformers current transformers ratio L1 L2 L3 7 4MC4543 XD 2500A / 5A 97/042876 97/042875 97/042877 3000A / 5A 10 4MC4542 XD 2500A / 5A 97/ 037517 97/037522 97/037516 11 4MC4543 XD 2500A / 5A 3000A / 5A 97/037513 97/037511 97/037512 With the transformation ratio 2500A / 5A the current transformers of the panel No. 11 were used for verification of the test current in panel No. 11 (2500A). 4. The temperature-rise test was performed at the minimum functional gauge pressure of the switchgear (0,08MPa at 20 C in the circuit-breaker compartment and 0,03MPa at 20 C in the busbar compartment). 5. Varnished were the aluminium chambers of the panel No. 11 (see photo No. 1 and No. 2). 6. Black varnished were the following parts or zones of the current path in panel No. 11: - the cooling sheet at the upper connection of the vacuum tube - the cooling sheets in the intermediate chamber and - the outer surfaces of the external copper bars in the intermediate chamber. Date of receipt of the equipment under test : 27.05.1997

Report-No.: 9725Fr Sheet: 7 Drawing of the Equipment under Test

Report-No.: 9725Fr Sheet: 8 Drawing of the Equipment under Test

Report-No.: 9725Fr Sheet: 9 Drawing-No. Position-No. Number of drawing or part list Quantity Description 001.0 005-4046.0 / 000 3 Gehäuse L=410 002.0 861-3196.0 / 000 3 Ring 1 003.0 864-3017.0 / 000 3 Ring Querkupplung 004.0 861-3347.0 / 000 3 Deckel 005.0 861-2031.0 / 000 6 Tragblech 006.0 029-6227.3 / 000 3 Gießharzstützer 007.0 861-3348.0 / 000 3 Deckel 301.0 005-4018.0 / 000 3 Schiene, Cu 80mm x 10mm 302.0 005-4019.0 / 000 3 Schiene, Cu 80mm x 10mm 2 303.0 005-4018.3 / 000 3 Schiene komplett, Cu 80mm x 10mm 304.0 005-3428.0 / 000 3 Kühlblech, Cu 305.0 005-4042.0 / 000 6 Kühlblech, Cu 306.0 005-4043.0 / 000 3 Kühlblech, Cu 101.0 861-3392.0 / 000 3 SS-Gehäuse L=410 3 102.0 005-0232.3 / 000 3 Durchführung 103.0 861-3348.0 / 000 6 Deckel 104.0 862-2403.0 / 000 3 Erdungsbrücke 401.0 005-4024.0 / 000 3 Lasche, Cu 80mm x 10mm 402.0 005-4025.0 / 000 3 Lasche, Cu 80mm x 10mm 403.0 005-4026.0 / 000 3 Schiene, Cu 80mm x 10mm 404.0 005-4022.0 / 000 3 Lasche, Cu 80mm x 10mm 405.0 005-4023.0 / 000 3 Lasche, Cu 80mm x 10mm 4 406.0 861-7035.3 / 000 3 Schienenträger 407.0 861-3256.0 / 000 3 Gegenkontakt 36 408.0 005-4006.0 / 000 3 Anschlußbolzen 409.0 864-3003.0 / 000 3 Anschluß 410.0 005-4032.0 / 000 3 Schiene, Cu 80mm x 10mm 411.0 005-4033.0 / 000 3 Schiene, Cu 80mm x 10mm 412.0 005-4034.0 / 000 3 Schiene, Cu 80mm x 10mm 1) 2) 1) 3) 3) 3) 1) 2) 3) silver-coated and black varnished silver-coated black varnished

Report-No.: 9725Fr Sheet: 10 Test Arrangement and Position of the Measuring Points 7 10 11 Panel- No. 1250A 1250A 2500A Test current, three-phase 2 x size 1/phase 2 x size 1/phase 3 x size 1/phase Plug-in connectors from Pfisterer Terminal Cu cables, 2x(3x95mm 2 )/phase Cu cables, 2x(3x95mm 2 )/phase Cu bars, 3x60mmx10mm/phase - - Cu bars, 2x80mmx10mm Cross section (see photo of terminals no. 3) Short circuiting link (see photo no. 4)

Report-No.: 9725Fr Sheet: 11 Measurement of the Resistance of the Main Circuits 1. Before the temperature-rise test Measuring section between the measuring points Resistance of the main circuits µω (see sheet 10) L1 L2 L3 1-2 - 4,40-2 - 3-3,10-3 - 4-1,70-4 - 5-11,90-5 - 6-0,60-6 - 7-1,50-7 - 8-1,40-8 - 9-2,20-9 - 10-14,60-10 - 11-0,30-11 - 13-9,90-13 - 14 9,90 9,30 11,10 1-13 - 51,60-2. After the temperature-rise test Measuring section between the measuring points Resistance of the main circuits µω (see sheet 10) L1 L2 L3 1-2 - 4,20-2 - 3-3,20-3 - 4-1,60-4 - 5-13,90-5 - 6-0,50-6 - 7-1,70-7 - 8-1,30-8 - 9-2,30-9 - 10-14,70-10 - 11-0,40-11 - 13-9,60-13 - 14 9,90 9,80 11,00 1-13 - 55,50 - Remarks: Resistance measurement at a direct current of: 100 A

Report-No.: 9725Fr Sheet: 12 Temperature-rise Test, Measurands Date of test: 05.06.1997 Duration of test: 18,5 h Ambient air temperature: 24,5 C Test current: 2500 A Test frequency: 50 Hz Measuring point (see sheet 10) Description of the measuring point Nature of the measuring point Connection, Final temperature C Final temperature rise K Permissible temperature rise K 1 L2 Main busbar bolted or equivalent, 73,0 48,5 75,0 Main busbar Cu silver-coated in SF 6 Metal part in contact 2 L2 at cast resin with insulation 74,0 49,5 65,0 bushing Busbar at material class A Metal part in contact 3 L2 cast resin post with insulation 78,0 53,5 65,0 insulator material class A 4 L2 Fixed contact of Contact, 80,5 56,0 65,0 the isolator Cu silver-coated in SF 6 Fixed contact of Contact, 5 L2 the isolator at cast Cu silver-coated in SF 6 86,5 62,0 65,0 resin bushing Copper bar at Metal part in contact 6 L2 cast resin with insulation 84,0 59,5 65,0 bushing Copper bar at material class A Metal part in contact 7 L2 cast resin post with insulation 86,0 61,5 65,0 insulator Bolted joint between material class A Connection, 8 L2 copper bar and bolted or equivalent, 90,0 65,5 75,0 flexible connector Cu silver-coated in SF 6 Bolted joint between Connection, 9 L2 flexible connector and bolted or equivalent, 97,5 73,0 75,0 vacuum tube Cu silver-coated in SF 6 Lower bolted joint Connection, 10 L2 at the bolted or equivalent, 98,5 74,0 75,0 vacuum tube Cu silver-coated in SF 6 Remarks: The permissible temperature rises are valid for an ambient air temperature of 40 C. The stagnation was reached after 9,0 hours.

Report-No.: 9725Fr Sheet: 13 Temperature-rise Test, Measurands Date of test: 05.06.1997 Duration of test: 18,5 h Ambient air temperature: 24,5 C Test current: 2500 A Test frequency: 50 Hz Measuring point (see sheet 10) Description of the measuring point Nature of the measuring point Connection, Final temperature C Final temperature rise K Permissible temperature rise K 11 L2 Connector bolted or equivalent, 97,0 72,5 75,0 Threaded bush in Cu silver-coated in SF 6 Metal part in contact 12 L2 the cast resin with insulation 80,5 56,0 65,0 support ring material class A L1 Copper bar Terminal, bolted, 63,5 39,0 13 L2 at terminal Cu silver-coated in air 64,0 39,5 65,0 L3 63,5 39,0 L1 Copper bar, 58,5 34,0 14 L2 1m distance to - 61,0 36,5 - L3 measuring point 13 58,5 34,0 Remarks: The permissible temperature rises are valid for an ambient air temperature of 40 C. The stagnation was reached after 9,0 hours.

Report-No.: 9725Fr Sheet: 14 Temperature-rise Test, Diagram

Report-No.: 9725Fr Sheet: 15 Photos

Report-No.: 9725Fr Sheet: 16 Photos