VEIKI-VNL ELECTRIC LARGE LABORATORIES Ltd. TYPE TEST REPORT

Similar documents
TEST CERTIFICATES OR REPORTS ISSUED BY VEIKI-VNL LTD.

KINECTRICS NORTH AMERICA INC. TEST REPORT FOR 774-KCMIL 3M TM COMPOSITE CONDUCTOR

CTC 460 kcmil ACCC Conductor Stress Strain Tests

NORMAL STRESS. The simplest form of stress is normal stress/direct stress, which is the stress perpendicular to the surface on which it acts.

GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN Mitglied der Short-Circuit-Testing Liaison (STL) Test Report

EA Guidelines on the Calibration of Temperature Indicators and Simulators by Electrical Simulation and Measurement

Structural Calculations for Juliet balconies using BALCONY 2 System (Aerofoil) handrail. Our ref: JULB2NB Date of issue: March 2017

MECE 3321 MECHANICS OF SOLIDS CHAPTER 3

Coefficient of Thermal Expansion for 477-T16 ACCR

Laboratory Evaluation Report for: Dielectric Pipe Unions

Al-Zr Alloy Strand for ACCR Conductor Experimental Measurement of Resistance Temperature Coefficient

Experiment Five (5) Principal of Stress and Strain

THE DIMENSIONING OF ELECTRICAL CONDUCTORS FOR USE IN "PANEL BOARDS" ADDRESSED TO HAZARDOUS AREAS - PART THREE

Composite Conductor Field Trial Summary Report: Western Area Power Administration FARGO

Which expression gives the elastic energy stored in the stretched wire?

The University of Melbourne Engineering Mechanics

STRENGTH OF MATERIALS-I. Unit-1. Simple stresses and strains

Strain Measurement. Prof. Yu Qiao. Department of Structural Engineering, UCSD. Strain Measurement

Fire Resistant Armoured Power Cable

INTERNATIONAL STANDARD

Design and Development of Impact Load Sensor for Dynamic Testing Purposes

STRAIN GAUGES YEDITEPE UNIVERSITY DEPARTMENT OF MECHANICAL ENGINEERING

Strain Gauge Application and Measurement of Unknown Load

Certification of a High Capacity Force Machine for Testing of Load Cells According to OIML R60

Experimental Stress Analysis of Curved Beams Using Strain Gauges

MET 487 Instrumentation and Automatic Controls. Lecture 13 Sensors

INTERNATIONAL STANDARD


Name :. Roll No. :... Invigilator s Signature :.. CS/B.TECH (CE-NEW)/SEM-3/CE-301/ SOLID MECHANICS

STANDARD SAMPLE. Reduced section " Diameter. Diameter. 2" Gauge length. Radius

S P E C I F I C A T I O N S

ME411 Engineering Measurement & Instrumentation. Winter 2017 Lecture 9

Page 2. What is the main purpose of the steel core? To force more current into the outer sheath.

Kinectrics North America Inc. Report No.: K RC-0001-R00 March 20, C.J. Pon, Z. Peter Transmission and Distribution Technologies Business

DC Film Capacitors MKT Axial Type

Laboratory 4 Bending Test of Materials

Procedure To Be Adopted When Working on High Voltage Mechanically Switched Capacitors with Damping Network (MSCDN)

PERFORMANCE TEST REPORT. Rendered to: VELUX AMERICA, INC. PRODUCT: SUN TUNNEL Domes TYPES: Acrylic and Polycarbonate

Stress-Strain Behavior

Single Core XLPE/LSF/AWA/LSF Power Cable

PHYS 2212L - Principles of Physics Laboratory II

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK

ME 243. Mechanics of Solids

GB/T / ISO 527-1:1993

PURE BENDING. If a simply supported beam carries two point loads of 10 kn as shown in the following figure, pure bending occurs at segment BC.

There are three main types of structure - mass, framed and shells.

Periodic Inspection and Testing of Electrical Installations Sample Test ( ) Version 1.3 July 2018

THEME IS FIRST OCCURANCE OF YIELDING THE LIMIT?

A fatigue limit diagram for plastic rail clips

Metallized Polypropylene Film Capacitor DC-Link Capacitor MKP Type

Composite Conductor Field Trial Summary Report: Western Area Power Administration Phoenix

M I N I S T R Y O F C O M M U N I C A T I O N S T E L E C O M M U N I C A T I O N S S E C T O R T E C H N I C A L S T A N D A R D F O R

product manual H-3030, H-3032, H-3033 Concrete Beam Tester

STEEL. General Information

Guidelines on the Calibration of Static Torque Measuring Devices

MET 301 EXPERIMENT # 2 APPLICATION OF BONDED STRAIN GAGES

5SJ4...-.HG Circuit Breakers to IEC and UL 489

CERTIFICATE OF CALIBRATION

Structures - Experiment 3B Sophomore Design - Fall 2006

Trade of Electrician Standards Based Apprenticeship Capacitance Phase 2 Module No. 2.1 Unit No COURSE NOTES

EA-10/14. EA Guidelines on the Calibration of Static Torque Measuring Devices. Publication Reference PURPOSE

16 Appendix 16 Electrical Research Association Report

Three Core XLPE/LSF/SWA/LSF Power Cable

Multi-Capacity Load Cell Concept

The Strain Gauge. James K Beard, Ph.D. Rowan Hall Auditorium November 2, 2006

PHA3/W PHYSICS (SPECIFICATION A) Unit 3 Current Electricity and Elastic Properties of Solids

Physics Assessment Unit AS 1

WW12C, WW08C, WW06C, WW04C, WW02C. Low ohm chip resistors ( power ) Size 1206, 0805, 0603, 0402, 0201

X has a higher value of the Young modulus. Y has a lower maximum tensile stress than X

In-plane Shear Lag of Bolted Connections


Properties of Capacitors and its DC Behavior

Test report CVN Project number Page 2 of 2

Mechanical properties 1 Elastic behaviour of materials

Physics 196 Final Test Point

Metallized Polyester Film Capacitors MKT Radial Potted Types

Standard Test Methods for Glass-Bonded Mica Used as Electrical Insulation 1

DC Film Capacitors MKT Radial Potted Type

Metallized Polyester Film Capacitors MKT Radial Potted Type

Withdrawn at December 31, Guideline DKD-R 5-7. Calibration of Climatic Chambers DEUTSCHER KALIBRIERDIENST

Switch. R 5 V Capacitor. ower upply. Voltmete. Goals. Introduction

UNIT I SIMPLE STRESSES AND STRAINS

DC Film Capacitors MKT Radial Lacquered Type

Peak Strain and Displacement Sensors for Structural Health Monitoring

UNIVERSITY OF BOLTON SCHOOL OF ENGINEERING. BEng (HONS) CIVIL ENGINEERING SEMESTER 1 EXAMINATION 2016/2017 MATHEMATICS & STRUCTURAL ANALYSIS

CHAPTER 6 FRICTION AND WEAR ANALYSIS FOR BUSHING

AC and Pulse Double Metallized Polypropylene Film Capacitors MMKP Radial Potted Type

Dynamic Simulation on a Broken Test of Conductors

Because the third wire carries practically no current (due to the voltmeter's extremely high internal resistance), its resistance will not drop any

QUESTION BANK SEMESTER: III SUBJECT NAME: MECHANICS OF SOLIDS

Determination of particle size distribution Single particle light interaction methods. Part 4:

TURQUOISE SWITCHES V TYPE (ABV)

What is a Strain Gauge? Strain Gauge. Schematic View Of Strain Gauge

Solid Mechanics Homework Answers

8 Deflectionmax. = 5WL 3 384EI

Physics Assessment Unit AS 1

A Model for Calculating ACCC Resistance Based on Fit Method

Strain Gages. Approximate Elastic Constants (from University Physics, Sears Zemansky, and Young, Reading, MA, Shear Modulus, (S) N/m 2

H07RN-F. Flexible Cables and Cords 60 C 450/750 V. Application. Specifications

DEPARTMENT OF MECHANICAL ENIGINEERING, UNIVERSITY OF ENGINEERING & TECHNOLOGY LAHORE (KSK CAMPUS).

Transcription:

Page 1 of 13 TYPE TEST REPORT Test object: Designation: All Aluminium Alloy Conductor (AAAC) 50 mm 2 All Aluminium Alloy Conductor (Code: 49-AL3) Manufacturer: BMET Energy Telecom Industry and Trade LLC. Region: Oromia Subcity: Finfine Special Zone City: Sebeta Woreda: Sebeta-Hawas Kebele: Dima Guranda P.O Box No: 20206/1000 ETHIOPIA Tested for: BMET ENERJİ TELEKOM SAN. VE TİC. A.Ş. Yeşilyurt Mah. Orkide Cad. Eresin Apt. No : 12 Daire No :11, Kat 5 34149-Bakırköy İSTANBUL/TURKEY Date of tests: 12 th January 2015 09 th February 2015 Tested by: Ltd. Budapest HUNGARY Project ID: NAL-33/2014 Order/Contract: 1066/2014, 19 th November 2014 Test specification: EN 50182: 2001 Conductors for overhead lines - Round wire concentric lay stranded conductors Tests performed: The test object, constructed in accordance with the description, drawings and photographs incorporated in this report has been subjected to the following tests: Stress-Strain curves (Clause 6.4.7 and Annex C) Tensile breaking strength (Clause 6.4.8 and Annex C) DC resistance measurement at 25 C, 50 C and 75 C conductor temperatures Test results: The tested conductor type AAAC 50 mm 2 (Code: 49-AL3) fulfilled the requirements of the relevant standards. This Type Test Report has been issued by Ltd. in accordance with above mentioned specification. The Report applies only to the test object. The responsibility for conformity of any product having the same designations with that tested rests with the Manufacturer. This Report comprises 14 sheets in total (13 numbered pages and 1 datasheet). Only integral reproduction of this document is permitted without written permission from Ltd. Ltd. is an independent testing laboratory. Member of Short-circuit Testing Liaison (STL). Ltd. is a testing laboratory, accredited by NAT (Hungarian Accreditation Board) under registration NAT-1-1251/2011. number Budapest, 13 th February, 2015... Lajos Tóth responsible for the test... Norbert Menyhért supervised by... Dr. László Varga managing director 1158 Budapest, Vasgolyó u. 2-4., HUNGARY E-mail: vnl@vnl.hu www. vnl.hu Phone: +36-1-417 3157 Fax: +36-1-417 3163

Page 2 of 13 TEST CERTIFICATES OR REPORTS ISSUED BY LTD. Type Test Certificate of Complete Type Test This certificate provides the verification of all the rated characteristics of the equipment as assigned by the manufacturer, by means of the performance of all type tests specified by the standards. Type Test Certificate of Dielectric Performance This certificate provides the verification of all dielectric ratings, by means of the performance of the appropriate type tests specified by the standards. Type Test Certificate of Temperature-Rise Performance This certificate provides the verification of temperature-rise limits together with measurement of the main circuit resistance, by means of the performance of the appropriate type tests specified by the standards. Type Test Certificate of Short-Circuit / Making and Breaking Performance This certificate provides the verification of rated characteristics with respect short-circuit and/or making and breaking performance, by means of the performance of the appropriate type tests specified by the standards. Type Test Certificate of Switching Performance This certificate provides the verification of the switching ratings (e.g. capacitive current), by means of the performance of the appropriate type tests specified by the standards. Prototype Test Report Prototype tests are required to verify the suitability of the materials and method of manufacture for composite insulators defined by relevant ANSI standards. Design Test Report According to IEC standard: The design tests are intended to verify the suitability of the design, materials and method of manufacture (technology) of composite insulators. According to ANSI standard: The design tests are intended to verify the insulators electrical and mechanical characteristics that depend on its size and shape. Type Test Report This report provides the verification of the rated characteristics of the equipment as assigned by the manufacturer, by means of the performance of the appropriate type tests specified by the standards, for type tests not indicated above. Development Test Report This report is issued when the test is intended only to provide the Client with information about the performance of the equipment. The tests are performed in accordance with relevant standards, but are not intended to verify compliance of the equipment. Control Test Report This report is issued for tests performed on equipment in service, or removed from service. Tests are performed, and compliance is evaluated in accordance with relevant standards. Test Report Test report is issued in all cases not listed above.

Page 3 of 13 Ratings/characteristics assigned by the manufacturer: Test object: All Aluminium Alloy Conductor (AAAC) Designation: 50 mm 2 All Aluminium Alloy Conductor (Code: 49-AL3) Manufacturer: BMET Structure: Centre: Layer 1: Cross-sectional area: 49.5 mm 2 Conductor Diameter: 1 Ø3.00mm Aluminium Alloy wire (Al-Mg-Si) 6 Ø3.00mm Aluminium Alloy wire (Al-Mg-Si) 9 mm Rated Tensile Strength (RTS): 14.6 kn Modulus of Elasticity (E): 60 kn/mm 2 Nominal conductor mass: 135.1 kg/km DC resistance at 20 C: 0.6647 Ω/km The tests were carried out in accordance with the following standards: EN 50182: 2001 Conductors for overhead lines Round wire concentric lay stranded conductors Requirements of manufacturer or purchaser: DC resistance measurement at 25 C, 50 C and 75 C conductor temperature List of manufacturer's drawings for identification of the test object: Technical Datasheet - 50 mm 2 All Aluminium Alloy Conductor Present at the test in charge of manufacturer or purchaser: -

Page 4 of 13 TESTS PERFORMED ON THE APPARATUS No. Description Relevant clauses of the standard 1 Stress-Strain curves EN 50182: 2001 Clause 6.4.7, Annex C 2 Tensile breaking strength EN 50182: 2001 Clause 6.4.8, Annex C 3 DC resistance measurement Client's requirement 1. Stress-Strain curves 1.1. Test method and parameters DESCRIPTION OF THE TESTS Stress strain test was carried out on overhead line conductor type AAAC 50 mm 2 (Photo 1) in accordance with standard EN 50182 Clause 6.4.7 and Annex C. The ends of the conductor specimens were terminated with epoxy-resin dead-end and fixed in the end fittings (Photo 3). The test was performed in a tensile machine; with gauge length of 10.04 m. The conductor was tensioned according to the following table: Table 1: Loading schedule for stress-strain test Initial load (5% of RTS): 0.7 kn To straighten the conductor and set the strain gage to zero. Load (30% of RTS): 4.4 kn 30 min, then released to initial load. Load (50% of RTS): 7.3 kn 60 min, then released to initial load. Load (70% of RTS): 10.2 kn 60 min, then released to initial load. Load (85% of RTS): 12.4 kn 60 min, then released to initial load. During the test the conductor sample was supported along its length to keep the conductor straight and minimize the sag. The test set-up for the stress-strain test is shown in Figure 1 and on Photo 2. The test was carried out in a temperature-controlled laboratory at 20 C±2 C. Figure 1 Test arrangement

Page 5 of 13 1.2. Test results The modulus of elasticity of the conductor was determined from the Force-Elongation curve by simple linear regression. Figure 2 shows the lines of best fit placed on the unloading segments of the curve. Figure 2 Lines of best fit placed on the unloading segments The Modulus of Elasticity obtained at 30, 50, 70 and 85% RTS are summarised in Table 2. Table 2: Modulus of elasticity Load Line of best fit Slope Modulus of Elasticity ( y m x b ) ( m) l0 ( E m ) A 30% RTS kn y1 0.2682 x 0.0256 0.2682 54.40 2 mm 50% RTS kn y2 0.2871 x 0.7786 0.2871 58.23 2 mm 70% RTS kn y3 0.2918 x 1.4980 0.2918 59.19 2 mm 85% RTS kn y4 0.2861 x 2.2681 0.2861 58.03 2 mm

Page 6 of 13 The measured curves were corrected to cross zero by 0.04038% strain for the conductor. The corrected force-strain curves of the conductor are plotted in Figure 3. Figure 3 Stress-Strain curve (Conductor) The stress-strain values obtained at the end of each hold period are summarized in Table 3. Table 3: Stress and strain of the conductor Load Strain [%] Stress of Conductor [N/mm 2 ] 30% RTS 0.2017 88.8889 50% RTS 0.3183 147.2525 70% RTS 0.4378 206.2626 85% RTS 0.5485 250.3000 The initial curve was obtained by fitting 4 th coefficients are as follows: order polynomial curve to above points. The - Conductor: y = -1119.7x 4 + 571.47x 3 + 122.9x 2 + 401.76x where: x: strain [%] y: stress [N/mm 2 ], calculated with the cross-sectional area of the whole conductor

Page 7 of 13 The coefficients of the regression line fitted to the unloading segment of the stress-strain curves are as follows: - Conductor: y = 585.39x 70.792 where: x: strain [%] y: stress [N/mm 2 ], calculated with the cross-sectional area of the whole conductor 2. Tensile breaking strength 2.1. Test method and parameters The verification of tensile breaking strength was carried out on overhead line conductor type AAAC 50 mm 2 in accordance with standard EN 50182 Clause 6.4.8 and Annex C. The test was carried on the same conductor specimen, which was subjected to stress-strain test. 2.2. Test results The tensile specimen broke at the load of 17.89 kn. This value is higher than 13.9 kn (95 % of the 14.6 kn RTS), which is the acceptance criterion of the relevant standard. Based on the test results; the conductor AAAC 50 mm 2 fulfilled the requirements of tensile breaking strength. The obtained Force-Elongation curve is shown in Figure 4. The fractured wires are shown on Photo 4. Figure 4 Tensile test of the conductor

Page 8 of 13 3. DC resistance measurement 3.1. Test method and parameters The DC resistance measurement was carried out on overhead line conductor type AAAC 50 mm 2 according to the test procedure agreed with Client. The conductor was placed in a 6 m long test span. The conductor was fixed by electrically ant thermally isolated fittings; the applied force was 2.9 kn (20% of RTS). The ends of the conductor were led to the power transformer and connected by bolted current clamps. The current was measured by CT and a data logger. Conductor temperature was measured by thermocouples installed under the outer layer at ends and middle of the tested section. The currents were applied to the conductor until its temperature reached steady state condition. The DC resistance measurement was made by a DC micro-ohmmeter (4-wire method). The voltage drop was measured in a 3 m long section at the middle of the span. The DC resistance measurement was performed at 25 C, 50 C and 75 C conductor temperature. The test arrangement is shown in Figure 5. 3 m Figure 5 Test circuit diagram for DC resistance measurement

Page 9 of 13 3.2. Test results The DC resistance of the conductor measured at the temperature of 20.2 C was as the following: R _3m 1994.1 R 1930.7 643.6 0.6436 3m m km The resistance value obtained was corrected to 20 C by the following formula: R R 0.6436 0.6431 1 20 1 3.6 10 20.2 20 km 20 3 20 where R is the measured resistance is the temperature in degree Celsius 20 is the thermal coefficient of resistance ( ) The measured resistance of the conductor (0.6431 Ω/km) was lower than the specified maximum 0.6647 Ω/km; therefore the conductor met the DC resistance requirement of the data sheet. The DC resistances measured at 25 C, 50 C and 75 C conductor temperatures are summarized in Table 4. Table 4: Results of DC resistance measurement Average Heating Temperature Current [ C] [A] Measured DC-Resistance [µω] DC-Resistance [Ω/km] 20.2-1930.7 0.6436 25.6 50.8 1969.6 0.6565 50.0 120.9 2147.8 0.7159 74.9 165.9 2327.4 0.7758 The conductor temperature and the heating current are plotted in Figure 6.

Page 10 of 13 Figure 6 Conductor temperature and heating current

Page 11 of 13 Uncertainty of measurements Current measurement: ± 1 % Temperature measurement: ± 2 C Tensile force measurement: ± 1 % Resistance measurement: ± 0.2 % The uncertainty values given in this report are the standard deviation values multiplied by k=2. Measurement uncertainty was estimated according to the method described in the EA-4/02 document. Measuring devices used for the tests: Designation Manufacturer Type S/N: Data Logger FLUKE 2635A 2443009 Current Transformer TETTEX 4724 103361 DC Microohm-meter MO-1 001 Power Analyser HIOKI 3193 05021 4964 Load Cell TENZI TCD-S-100kN 101102 Tensile test machine (300 kn) BARABÁS Mérnökiroda Kft. KSZ 001/2011

Page 12 of 13 PHOTOS Photo 1 Cross-sectional view of the tested conductor Photo 2 Stress-Strain test arrangement

Page 13 of 13 Photo 3 Dead-end fitting Photo 4 Fractured wires after the tensile breaking test

TECHNICAL DATASHEET 50 mm² All Aluminum Alloy Conductor Type AAAC Code 49-AL3 Old Coed 50 According to regulation BS EN 50182_2001 Size/nominal sectional area mm² 50 Number of Wires 7 Wire Diameter mm² 3.00 Ultimate tensile strength (before stranding) N/mm² 295 Conductivity at 20²C % IACS 53 Calculated Area mm² 49.5 Minumum breaking strength kn 14.6 Conductor Diameter mm 9 Standard weight kg/km 135.1 Calculated resistance 20 C (DC) Ohm/km 0.6647 Modulus of elasticity (Final) N/mm² 60000 Coefficient of linear expansion per C 23*10^-6 Lay Ratio Outer: 10-14 Direction of Lay Outer: Right Length of each reel m 4000 Reel Type mm 1000 * 550 * 640 Net weight per drum (without grease) kg 540 Gross weight per drum kg 620