3VT4 Molded Case Circuit Breakers up to 1000 A

Similar documents
Issued August DATA SHEET. 3VT5 MCCB up to 1600 A

Issued August DATA SHEET. 3VT3 MCCB up to 630 A

MOULDED CASE CIRCUIT BREAKERS BL1000S

Varius SUMMARY OF MODELS OF HRC FUSE-LINKS

5SJ4...-.HG Circuit Breakers to IEC and UL 489

08/072 PKZ2 Motor-Protective Circuit-Breakers Tripping Characteristics

Varius SUMMARY OF MODELS OF HRC FUSE-LINKS. Type PVA10 / PV10 PV14 PV22 Rated current I n up to 32 A up to 63 A up to 125 A Rated voltage U n

Sealing possibility Electrical endurance (ops) Mechanical endurance (ops) Overvoltage category Standards

BETA Protecting. Low-Voltage Fuse Systems. LV HRC fuse links. 3/36 Siemens ET B1 2008

TeSys circuit-breakers

FAZ tripping characteristics at 30 C: B, C, D to IEC/EN FAZ tripping characteristics at 30 C: R to IEC/EN

BETA Protecting Miniature Circuit Breakers

Siemens AG Miniature Circuit Breakers. Totally Integrated Power SENTRON. Configuration. Edition 10/2014. Manual. siemens.

MCB NB1-63H Miniature Circuit Breaker

Overload Relays. SIRIUS 3RU1 Thermal Overload Relays. 3RU11 for standard applications. 5/46 Siemens LV 1 AO 2011

5SP and 5SY Supplementary Protection UL 1077

UL 1077 DIN Rail Supplementary Protectors

90 MCB MODULAR CIRCUIT BREAKERS FOR CIRCUIT PROTECTION

Current protection I 2 t long-time protection

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.

Impedance relay and protection assemblies

C60N circuit breakers0 B, C and D curves IEC 60898: 6000 A, IEC : 10 ka

90 MCB range Modular circuit breakers for circuit protection

Thermal-Magnetic Circuit Breaker 2210-S2..

SIRCOVER Manual transfer switches from 125 to 3200 A

Thermal-Magnetic Circuit Breaker 2210-S2...

Thermal-Magnetic Circuit Breaker 2210-S2...

Thermal-Magnetic Circuit Breaker 2210-S2..

THE DIMENSIONING OF ELECTRICAL CONDUCTORS FOR USE IN "PANEL BOARDS" ADDRESSED TO HAZARDOUS AREAS - PART THREE

C120N circuit-breakers B, C and D curves EN 60898/EN 61009: IEC : 10 ka

Thermal-Magnetic Circuit Breaker 2210-S2..

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-T...

General characteristics, Products

Thermal-Magnetic Circuit Breaker 2210-T2...

Instruction. Vacuum Circuit Breaker Operator Module. Type 3AH 4.16kV to 38kV. Power Transmission & Distribution

X T O B P 1 6 B C 1 S

Semiconductor (AC) fuses

ATyS Automatic and remotely operated transfer switches from 125 to 3200 A

SION Lateral 3AE6 Vacuum Circuit Breaker with Lateral Operating Mechanism

NM1. Moulded Case Circuit Breaker NM1 P-084. Moulded Case Circuit Breakers. 2. Type designation. 1. General. 3. Classification N M 1- /

To order, specify : Types Protection functions Current surge Asymmetry and loss of phase. Operating principle

GPS1B. Characteristics. Technical performances

Selecting the current rating for equipment

Semiconductor (AC) fuses

VX25 Enclosure System. Technical documentation PE conductor connection, current carrying capacity

H i g h A m p e r a g e 2 5 t o A M P. T y p e I & I I I V e h i c l e P r o t e c t i o n. I P 6 7 W a t e r p r o o f

INSTRUCTION MANUAL FOR MM10 Relay

Microprocessor Based Characteristics and adjustments

TeSys protection components Thermal-magnetic motor circuit-breakers GV2 ME and GV2 P

400 Volts, 50HZ 480 Volts, 60HZ 600 Volts, 60HZ TECHNICAL REFERENCE MANUAL

Miniatur Circuite Breakers (MCB)

Semiconductor (AC) fuses

MKV AC Capacitors Damping B High dielectric strength High peak-current capability Especially suitable for snubber circuits

2-2. Bulletin 140M Motor Protection Circuit Breakers. Product Overview. Table of Contents. Standards Compliance. Certifications. General Information

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.

DATA SHEET: TEMPOWER2 ACB

TeSys enclosed starters 2

TYPE. max. working voltage 250 V 350 V 500 V 750 V. max. overload voltage 500 V 700 V 1000 V 1500 V. basic specifications IEC B

Non-Contact Safety Systems CMS

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

Electrical installation solutions for buildings Technical details RCDs

Performance. Standards. Technical data

ISOCON-6. 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER

Technical catalogue SmiSSline electrical protective devices in a system

Universal limit switches

Redline Unibis : the solution Circuit protection

Time - timing relays 1 Industrial relays, solid state output, width 22.5 mm

Moulded Case Circuit Breakers. Breaking capacity code: S:standard H:Higher type/r:current limiting type

Installation Contactors ISU-xxx ISM-xxx

Miniature Circuit Breaker

LD-LP-LL-LC Rope Safety Switches with reset for emergency stop

FL ballasts Electronic fixed output. PC TC PRO sr 1/2x11 42 W PC PRO compact

LEDlight 20 W Universal dimmable series

TEST REPORT IEC/EN Circuit-breakers for over current protection for household and similar installations

Performance. Standards. Technical data

General characteristics

XM1 Motor Protection Relay. Manual XM1 (Revision B)

TEST CERTIFICATES OR REPORTS ISSUED BY VEIKI-VNL LTD.

ST1230C..K SERIES 1745A. Features. Typical Applications. Major Ratings and Characteristics. Bulletin I25194 rev. B 01/00. case style A-24 (K-PUK)

TeSys contactors. TeSys D contactors. 690 V on a and c

Data Bulletin. SEPAM 49RMS Application Note Protection for Motor Applications Class Number SEPAM 49RMS Protection for Motor Applications

EXEMPLAR NATIONAL CERTIFICATE (VOCATIONAL) ELECTRICAL PRINCIPLES AND PRACTICE NQF LEVEL 3 ( ) (X-Paper) 09:00 12:00

LEDlight 30 W Universal dimmable series

FEATURES APPLICATIONS DESCRIPTION QUICK REFERENCE DATA. PILKOR components

AN78xx/AN78xxF Series

AN78Lxx/AN78LxxM Series

ISOCON-3 MAINS POWERED ISOLATING SIGNAL CONVERTER

CALEFFI. Modulating digital controller for heating and cooling. 161 series 01122/08 GB. replaces dp 01122/05

High Ohmic/High Voltage Resistors

Samples. Symbol Parameter Test Conditions Value Unit RMS on-state current T C = 40 C 1.5 A I T(AV) Average on-state current T C

5730A High Performance Multifunction Calibrator. Extended specifications

MODEL: R7K4FML3. Remote I/O R7K4F Series. POWER INPUT DC power R: 24 V DC (Operational voltage range: ±10 %; ripple 10 %p-p max.)

The Ordering Code for various standard model Recorders with an AC supply and without any additional options are as follows:

Single Phase Motors Technical Datasheets

KINGS COLLEGE OF ENGINEERING Punalkulam

Western Electric A V a c u u m T u b e

± 250 ppm / ± 150 ppm / max. working voltage 150 V 200 V 250 V 400 V 700 V

THREE PHASE CAPACITOR For WIND TURBINES

High-ohmic/high-voltage resistors

Conductor Requirements for Superconducting Fault Current Limiters

Transcription:

VT4 Molded Case Circuit Breakers up to 00 A Catalog Technical nformation VT4 Molded Case Circuit Breakers up to 00 A General data / - Overview Circuit breakers Switch disconnectors / - Selection and ordering data / - Accessories / - Technical specifiations VT4 Molded Case Circuit Breakers up to 00 A / Circuit breakers Switch disconnectors /6 - Technical specifications Siemens V 6 008

General data Overview / Siemens V 6 008

Circuit breakers, Switch disconnectors Selection and ordering data The switching unit consits of: - VT9 0-8CE0 phase barriers - connecting sets for front connection - busbars connection The switching unit must be fitted with: - overcurrent release ETU DP, MP and UP (circuit breaker) or - VT9 4-6DT00 switch disconnector unit - VT9 0-4WA40 withdrawable device The withdrawable device must be fitted with: - x VT9 0-4EF0 connection set (front connection) or - VT9 0-4RD0 (rear connection) We recommend fitting the switching unit with: - VT9 0-4SA40 mounting bolts set (4 x M8 x 60) Switching units Rated current n Switching capacity cu DT Order no. PS* Weight per PU approx. A ka kg Fixed-mounted version, -pole 00 6 B VT4 7-AA0-0AA0 unit.000 Withdrawable design, -pole 00 6 B VT4 7-AA8-0AA0 unit.000 Withdrawable device Withdrawbale device B VT9 0-4WA40 unit 00 Accessories ETU trip unit Rated current n Set current of the inversetime delayed overload trip units r DT Order no. PS* Weight per PU approx. A A kg System protection, ETU DP, function For protecting lines and transformers... B VT9 4-6AC00 unit 0.0 60... 60 B VT9 46-6AC00 unit 0.0 800... 800 B VT9 480-6AC00 unit 0.0 00 400... 00 B VT9 4-6AC00 unit 6 Motor and generator protection, ETU MP, funktion Direct protection for motors and generators Suitable also for protecting lines and transformers... B VT9 4-6AP00 unit 0.0 60... 60 B VT9 46-6AP00 unit 0.0 800... 800 B VT9 480-6AP00 unit 0.0 00 400... 00 B VT9 4-6AP00 unit 0.90 Universal protection, ETU UP, S function For protecting complicated loads or those not specified in advance... B VT9 4-6AD00 unit 0.0 60... 60 B VT9 46-6AD00 unit 0.0 800... 800 B VT9 480-6AD00 unit 0.0 00 400... 00 B VT9 4-6AD00 unit 0.0 * You can order this quantity or a multiple thereof. Siemens V 6 008 /

Circuit breakers, Switch disconnectors Rated current n Set current of the inversetime delayed overload trip units / r DT Order no. PS* Weight per PU approx. A A kg Switch-disconnector unit 00 Switch-disconnector unit B VT9 4-6DT00 unit 0.474 Signalling unit for overcurrent releases ETU, P and UP B VT9 0-6AE00 unit 0.670 /4 Siemens V 6 008 * You can order this quantity or a multiple thereof.

Circuit breakers, Switch disconnectors Technical specifications Specifications VT4 circuit breakers Switch disconnectors Type Standards EN 60 947-, EC 947- EN 60 947-, EC 947- Approval marks Number of poles Rated current n A, 60, 800, 00 -- Rated normal current u A 00 Rated operational current e A -- 00 Rated operational voltage U e V AC max. 690 AC max. 690 DC max. 440 Rated frequency f n Hz /60 Rated impulse withstand voltage U imp kv 8 Rated insulation voltage U i V 690 Utilization category (selectivity) AC 690 V A, B -- Utilization category (switching mode) available, -- unavailable AC 690 V DC 440 V -- -- AC- B DC- B Rated short-time withstand current U e =AC 690 V cw /t ka/ s ka/ s Rated ultimate short-circuit breaking capacity (rms value) ) cu /U e AC 8 ka/0v AC 6 ka/4v AC 4 ka/0v AC 0 ka/690v Off-time at cu 0 ms -- Rated short-circuit service breaking capacity (rms value) cs /U e AC 4 ka/0v AC 6 ka/4v AC 0 ka/0v AC 0 ka/690v Rated short-circuit making capacity 40 ka/ac 4 V 0 ka/ac 4 V (peak value) cm /U e 0 ka/dc 440 V osses per pole at n = A W 0 Mechanical endurance cycles 000 Electrical endurance (U e = AC 4 V ) cycles 4000 Switching frequency cycles /hr Operating force N 0 Front-side device protection 0 P40 Terminal protection P0 Operating conditions Reference ambient temperature C 40 Ambient temperature range -40... + Working environment Degree of pollution Max. elevation m 000 dry and tropical climate Seismic resistance Hz g (8... ) Design modifications Front/rear connection / Plug-in design -- Withdrawable design Accessories Switches-auxiliary/relative/signal/early Shunt trip/with signal switch Undervoltage release/with early switch with signal switch Manual front operating mechanism/lateral operating mechanism right/left Mechanical interlocking to the manual operating mechanism, by Bowden wire Motorized operating mechanism/with operations counter ocking-type lever Bolt sealing inset/additional cover for overcurrent release / /--/-- /-- / / / /-- -- -- ) n case circuit breaker connection is reversed (input terminals, 4, 6 output terminals,, ), cu does not change. Siemens V 6 008 /

Technical specifications The electronic overcurrent release consists of a separate and interchangeable unit, which is supplied with the VT4 7-AA..- 0AA0 switching unit. By exchanging the overcurrent release, the range of the circuit breaker s rated current can be easily changed. Releases for the VT4 7-AA0-0AA0 switching unit are produced in four current ranges n =, 60, 800 and 00 A. The releases, including their adjustment, cover rated currents ranging from to 00 A. Depending on the needs for adjusting the release s tripping characteristics to the protected device and to the variability of the characteristics with regard to selectivity, the following release devices are available: ETU DP is a zone of high overcurrents and includes protection against ultimate short-circuit currents. For ETU MP releases, the time delay can be set at 0 or ms. t r i NSO0_007 They have one type of characteristics with adjustable r and rm. ETU MP t r tr i NSO0_0074 They have more kinds of characteristics with adjustable r, t r and rm. ETU UP They have universal characteristics, with the greatest variability in adjustment: r, t r, sd, t sd and i. ETU DP, MP and UP Proper functioning of releases does not depend on the form of current in the main circuit. The function of the release is supported by a microprocessor, which processes a sampled signal of the power circuit and recalculates it to obtain an rms value. Therefore, digital releases are suitable for protecting circuits where the sinusoidal current is distorted by high harmonics (e.g. circuits with controlled rectifiers, power factor compensators, pulse loading, and the like). All the releases protect a circuit against short-circuiting and overloading. Setting of selective cascading of circuit breakers is especially enabled by the ETU UP release. Tripping characteristics of the releases are independent of the ambient temperature. The release is affixed to the switching unit by two bolts. The translucent cover over the adjustment controls can be sealed. Adjustment of the tripping characteristics for ETU DP and MP releases The tripping characteristics of the overcurrent releases are defined by standard EN 60 947-. The characteristics are adjusted in two zones using latched switches on the overcurrent release unit: is a zone of low overcurrents and includes the area of thermal protection. /6 Siemens V 6 008

. Dependent release (thermal) The dependent release ETU DP is adjusted using one r switch. The r switch is used to adjust the circuit breaker s rated current. The characteristic is moved on the current axis. By means of its internal circuitry, the release is set to one type of characteristic. The dependent release ETU MP is adjusted using two switches, r and t r. The first ( r ) switch is used to adjust the circuit breaker s rated current. The characteristics are moved on the current axis. By turning the other switch (t r ), the time after which the circuit breaker will trip while passing through 7. r. The tripping characteristic thus moves on the time axis. Using the tr switch, it is possible to set a total of 8 characteristics. Four characteristics are available for motors protection. Breaking times correspond with the release class A,, 0, 0. By changing t r, it is possible to select the characteristics according to the required motor starting (light, medium, heavy or very heavy starting). For protecting transformers and lines, 4 characteristics can be set. t is not possible to turn the device back on right after the dependent release has been actuated and circuit breaker tripped. The release must be allowed to cool off, because it has a thermal memory. The memory can be disabled by turning the restart switch from the normal T t position to the T 0 position. The dependent release remains active, and only its thermal memory is inactivated. The thermal memory should be switched off only in justified cases, and with the knowledge that the temperature could rise in the protected device with repeated tripping.. ndependent instantaneous release (short-circuit release) The independent instantaneous release in designs ETU DP and ETU MP is adjusted using one switch, i. The i switch is used for setting up the short-circuit current that, upon its being reached or exceeded, causes instantaneous tripping of the circuit breaker. Regulation of the short-circuit release takes in settings for the characteristic appropriate for protecting lines and motors. The wave form of the tripping characteristic is adjusted using latched switches on the release s front panel according to the needs of the protected device. A visual demonstration on setting the tripping characteristics can be found in the SMARS design. Tripping characteristics of ETU DP and MP releases with load The tripping characteristics from the cold state indicate the tripping times during which it is assumed that, up to the moment when an overcurrent develops, no current is flowing through the circuit breaker. The tripping characteristics tripped from warm state, indicate the tripping times during which it k [-] 0.6 0.4 0. NSO0_007 0.0 60 70 80 90 0 r [%] is assumed that, before the moment when an overcurrent develops, current is flowing through the circuit breaker. Characteristics of electronic releases are independent of the ambient temperature and are plotted in a cold state. Digital releases enable simulation of a release in warm state. The tripping times become shorter in a steady state, as shown in the following graph. The steady state is a period during which the characteristics do not change. f the circuit breaker is loaded with a reduced current for at least 0 minutes, the tripping times will be cut by a half. f the load is less than 70% of r, the tripping time does not become shorter. T Siemens V 6 008 /7

ETU DP and MP tripping times shortening with load T - When tripping from the release s warm state, the tripping time of the characteristic is cut short during the standstill time t u by coefficient k. Thermal standstill time of the characteristics For all kinds of characteristics t r, the thermal standstill time for ETU DP and MP releases is t u 0 min. During this time, the short-circuit tripping time t v is cut short from the cold-state characteristic by the coefficient k. The real tripping time is t s = k. t v Example The shortening constant can be read from the diagram. With steady current 8% of r the real tripping time will be shortened to: t s = 0.74. t v k [ ] time shortening coefficient r [A] adjusted rated current of the overcurrent release t v [s] tripping time of the release derived from the characteristic t s [s] real tripping time of the release tripped from warm state t u [s] standstill period for particular characteristics are set by the manufacturer r = min Restart = T (t) rm = min, 0 ms t r = TV, min /8 Siemens V 6 008

Adjustment of tripping characteristics, Trip unit ETU UP t NSO0_0046 r S t r sd t OFF t ON t sd The tripping characteristics of overcurrent releases are defined by standard EN 60 947-. The characteristics are adjusted in three zones using latched switches on the overcurrent release unit: - is a zone of low overcurrents and includes the area of thermal protection. S - is a zone of medium overcurrents and includes long-distance short-circuit protection for lines. ntentional delay in tripping of these low short-circuit currents can be used to achieve selectivity of protective devices. This type of delay can be set only in self-contained releases (full version). - is a zone of high overcurrents and includes protection against ultimate short-circuiting without time delay. t - Characteristic setting in the ON position represents a constant value of energy passed through. f fuses are used as protective elements for outgoing branch feeders, it is possible to adjust the selective part of the characteristics to better suit the shape of the fuse characteristics.. Dependent release (thermal) i The dependent release ETU UP is adjusted using two switches, r and t r. Using the first switch, r, the circuit breaker s rated current is adjusted. The characteristics are moved on the current axis. Turning the second switch, t r, adjusts the time after which the circuit breaker will trip while passing through 7. r. The tripping characteristics thus move on the time axis. Using the t r switch, a total of 8 characteristics can be set. Breaking times correspond with the release class A,, 0, 0. t is not possible to turn the device back on right after the dependent release has been actuated and circuit breaker tripped. The release must be allowed to cool off, because it has a thermal memory. The memory can be disabled by turning the restart switch from the normal T t position to the T 0 position. The dependent release remains active, and only its thermal memory is inactivated. The thermal memory should be switched off only in justified cases, and with the knowledge that there could be rising temperature in the protected device with repeated tripping.. Delayed independent releases S The delayed independent release has the function of a delayed short-circuit release. t is used to set up a selective cascade of circuit breakers. t is set up using specifications sd and t sd. sd is an n-multiple of current r ( sd = n r ). t is a shortcircuit current that, within the span of sd to rm, will trip the circuit breaker with delay t sd, where t sd is a delay set up for switching off the release. The delayed independent release actuates the circuit breaker if the current in the circuit reaches at least the preset n-multiple and lasts at least the preset delay time t sd. The independent release can be disabled by setting the parameter n ( sd = n r ) into the position. Parameter t sd can be set to values with respect to the energy that passed through l t (switch position l t on). The preset time values are then applicable for currents higher than x current r. Tripping times of k-multiples of r for k < are defined as follows: t = t v k. ndependent instantaneous release The independent instantaneous release has the function of a short-circuit release. t is set up only on parameter rm. rm is a short-circuit current that, upon its being reached or exceeded, causes the circuit breaker to switch off instantaneously. t is set up directly in ka on the release. The wave form of the tripping characteristic is adjusted using latched switches on the release s front panel according to the needs of the protected device. A visual demonstration on setting the tripping characteristic can be found in the SMARS design. Siemens V 6 008 /9

Tripping characteristics for ETU UP release with load The tripping characteristics from the cold state indicate the tripping times during which it is assumed that, up to the moment when an overcurrent develops, no current is flowing through the circuit breaker. The tripping characteristics tripped from warm state indicate the tripping times during which it is assumed that, before the moment when an overcurrent develops, current is flowing through the circuit breaker. Characteristics of electronic releases are independent of the ambient temperature and are plotted in a cold state. Digital releases enable simulation of a release in warm state. The tripping times become shorter in a steady state, as shown in the following diagram. The steady state is a period during which the characteristics do not change. f the circuit breaker is loaded with a reduced current for at least 0 minutes, the tripping times will be cut by half. f the load is less than 70% of r, the tripping time does not become shorter. k [-] NSO0_007 Example The shortening constant can be read from the diagram. With steady current 8% of r, the real tripping time will be shortened to: t s = 0.74. t v k [ ] time shortening coefficient r [A] adjusted rated current release t v [s] tripping time of the release derived from the characteristics t s [s] real tripping time of the release tripped from warm state t u [s] standstill period for particular characteristics are set by the manufacturer r = min Restart = T (t) rm = min t r = min t v = min, t - ON sd = min Manufacturer r = min 0.6 0.4 0. T Restart = T (t) rm = min, 0 ms t r = TV, t (t), min sd = 0 ms, min = 0. r 0.0 60 70 80 90 0 r [%] T - When tripping from the release s warm state, the tripping time of the characteristics are cut short during the standstill time t u by coefficient k. Thermal standstill time of the characteristics For all kinds of characteristics t r the thermal standstill period for ETU UP releases is t u 0 min. During this time, the short-circuit tripping time t v is cut short from the cold-state characteristics by the coefficient k. The real tripping time is ts = k.t v / Siemens V 6 008

ETU DP-Distribution Protecting lines and transformers The VT9 4..-6AC00 release is intended only for the VT4 7- AA..-0AA0 switching unit. Operation of the release is controlled by a microprocessor. The release is fitted with a thermal memory that can be disabled by turning the switch on the front panel from position T (t) to position T (0). After having disabled the thermal memory, the thermal release remains active. A practical advantage of the release are special tripping characteristics that provide for optimized use of transformers up to. n. Another advantage of this release is the simple adjustment of the tripping characteristics. Set-up includes only the rated current in a range of 0.4 to of n and the short-circuit tripping level. The reaching of 80% and % of r is indicated by ED diodes on the front panel denoted as > 80% and > % of r. On the lower part of the release cover are four photocells for communicating with the VT9 0-6AE00 signalling unit are mounted. Tripping characteristics 000 00 t [s] 000 00 0 00 0 0 0. 0. min. n=60a n = A n=00a n = 60 A n=a n = 800 A n=600a n = 00 A n = A n = 60 A n = 800 A n = 00 A 0. 0. r max....0..0.0.0.0 4.0.0 4.0 6.0.0 7.0 9.0 NSO0_0077 0 x n r. 0...0.0 4.0.0 6.0 8.0 9.0 4 i Specifications for adjustable releases Order No. Rated current n A Overload protection r Restart A, 7 0. 44, 60 7, 80. 00, 0 T (0) VT9 4-6AC00, 4 T (t)., 60 7, 90 4 0,, 60 7, 90. 0, 4, 60 T (0) VT9 46-6AC00 60 400, 4 T (t) 4 4, 480 6 0, 8 7, 60, 4 60, 400. 4, 4 480, 0 T (0) VT9 480-6AC00 800, 7 T (0) 4 6, 60 6 68, 70 9 760, 800 400, 4. 4, 480 0, 7, 6 T (0) VT9 4-6AC00 00 60, 68 T (0) 7 70, 760 9 800, 866 909, 00 4 nstantaneous short circuit protection Siemens V 6 008 /

ETU MP-Motors Direct protection of motors and generators Possibility for protecting lines and transformers The VT9 4..-6AP00 release is intended only for the VT4 7- AA..-0AA0 switching unit. The operation of the release is controlled by a microprocessor. The release is equipped with a thermal memory that can be disabled by turning a switch on the front panel from position T (t) to position T (0). After having disabled the thermal memory, the thermal release remains active. A practical advantage of the release are specially designed tripping characteristics that provide for optimal exploitation of transformers up to. n. t is possible to set a total of 8 characteristics on the release. From these, in mode M there are 4 characteristics for motor protection and another 4 characteristics in mode T V for protecting transformers and lines. The shape of each characteristic can be changed using a selector switch. When one or two phases fail, in the M-characteristic mode, the switch will open with a 4 s delay (so called undercurrent release). Another parameter for adjusting the release is the rated current, which is adjusted in a range of 0.4 to of n and the shortcircuit tripping level, for which it is possible to set the delay at 0 or ms. The reaching of 80% and % of r is indicated by ED diodes on the front panel denoted as > 80% of r and > % of r. On the lower part of the release cover four photocells are mounted for communicating with the VT9 0-6AE00 signalling unit. Specifications for adjustable releases Order No. Rate d current n Overload protection r t r (7. x r) Restar t nstantaneous short circuit protection A A S ka ms 0., 7 (TV ). 44, 60 (TV ) T (0) 0 7, 80 (TV ) VT9 4-6AP00 00, 0 0 (TV 0)., 4 (TV ) 4, 60 8 (TV 8) T (t). 7, 90 (TV ). 0, (TV ) 0., 60 (TV ). 7, 90 (TV ) T (0) 0, (TV ) 6 VT9 46-6AP00 60 4, 60 0 (TV 0) 400, 4 (TV ) 8 4, 480 8 (TV 8) T (t) 4 0, (TV ) 7, 60 (TV ) 4 4 0 8 6. 400, 4 (TV ). 4, 480 (TV ) T (0) 4 0 4 0, (TV ) 6 9 VT9 480-6AP00 800 7, 6 0 (TV 0) 60, 68 (TV ) 9 7, 760 8 (TV 8) T (t) 4 800, 866 (TV ) 909, 00 (TV ) 6.. 400, 4 (TV ) 4, 480 (TV ) T (0) 0 0, (TV ) 9 VT9 4-6AP00 00 7, 6 0 (TV 0) 4 60, 68 (TV ) 7, 760 8 (TV 8) 7 7 T (t) 800, 866 (TV ) 909, 00 (TV ). 9 / Siemens V 6 008

Tripping characteristic ETU MP 000 00 t [s] 000 00 0 min. r max. r t r 0 ms ms i NSO0_0078 TV 000 00 t [s] 000 00 0 min. r max. r t r 0 ms ms i NSO0_0079 M 00 0 0 0. 0. n=60a n = A n=00a n = 60 A n=a n = 800 A n=600a n = 00 A n = A n = 60 A n = 800 A n = 00 A 0. 0. 0. 0 0..0 0 0...0.0 4.0.0..0.0 4.0 0..0 0.0.0 4.0 t r 6.0.0 7.0 9.0 6.0 8.0 9.0 4 0 x n 00 0 0 0. 0. n=60a n = A n=00a n = 60 A n=a n = 800 A n=600a n = 00 A n = A n = 60 A n = 800 A n = 00 A 0. 0. 0. 8..0 0. 0 0 t r 8...0.0 4.0.0..0.0 4.0 6.0 8.0 0.0.0.0 4.0 6.0.0 7.0 9.0 9.0 4 0 x n Siemens V 6 008 /

Overcurrent trip unit-etu UP For protecting complicated loads or those not specified in advance The VT9 4..-6AD00 release is intended only for the VT4 7- AA..-0AA0 switching unit. The release is equipped with a thermal memory that can be disabled by turning the restart switch on the front panel from the position T (t) to the position T (0). After the thermal memory has been disabled, the thermal release remains active. A practical advantage of the release is its maximum flexibility for adjusting the tripping characteristics. With its possibility for setting t = constant and t = constant, it is optimal from the selectivity viewpoint for its interaction with fusing devices. The operational state 70% of r is signalled by an ED indicator that flashes green in a. s interval. As the load grows, the blinking frequency of the diode increases. n case of a load larger than % of r this ED will turn red and just before tripping will begin to blink red. On the lower part of the release cover, four photocells are mounted for communicating with the VT9 0-6AE00 signalling unit. Specifications for adjustable releases Order No. Rated current n Short delayed short circuit protection sd =(n x r ) Overload t r (7. x r ) n t sd t Restart nstantaneous protection r short circuit protection A A S A ms ka, 7 0., 0 0. 44, 60 00, 00 on T (0) 7, 80 400, 600. VT9 4-6AD00 00, 0 7 6 800, 00, 4 8, 0., 60 9 00, 00 off T (t) 7, 90 0 400, 600 4 0, 800, 00, 60 0., 0 7, 90 00, 00 on T (0). 0, 400, 600 VT9 46-6AD00 60 4, 60 7 6 800, 00 400, 4 8, 0 4 4, 480 9 00, 00 off T (t) 6 0, 0 400, 600 8 7, 60 800, 00, 4 0., 0 60, 400 00, 00 on T (0). 4, 4 400, 600 VT9 480-6AD00 800 480, 0 7 6 800, 00, 7 8, 0 4 6, 60 9 00, 00 off T (t) 6 68, 70 0 400, 600 9 760, 800 800, 00 400, 4 0., 0. 4, 480 00, 00 on T (0) 0, 400, 600 VT9 4-6AD00 00 7, 6 7 6 800, 00 60, 68 8, 0 7 70, 760 9 00, 00 off T (t) 9 800, 866 0 400, 600 909, 00 800, 00 4 /4 Siemens V 6 008

Tripping characteristics ETU UP 000 00 t [s] 000 00 0 00 0 0 0. 0. n = A n = 60 A n = 800 A n = 00 A n = A n = 60 A n = 800 A min. n = 00 A S t v [ms] ( t = OFF) 0. 0. r max. i = ( ) x r min 00. 0...0.0 0. t r [s] 0...0.0..0..0 4.0.0.0 4.0.0 4.0 r t r sd i = ( ) x r max 6.0.0 7.0 9.0 6.0 8.0 9.0 4 NSO0_0080 0 x n t v i 000 00 t [s] 000 0 00 0 0 0. 0. n = A n = 60 A n = 800 A n = 00 A n = A n = 60 A n = 800 A min. n = 00 A S 0. 0. r t v [ms] ( t = ON) max. sd = ( ) x r min. 0...0.0 NSO0_008 r t r sd t v i sd = ( ) x r max 00 0. t r [s] 0...0..0 4.0.0..0.0.0 4.0.0 4.0 6.0 6.0 8.0 9.0.0 7.0 9.0 4 0 x n Siemens V 6 008 /

Tripping characteristics ETU UP 000 00 t [s] 000 00 0 00 0 0 0. 0. n = A n = 60 A n = 800 A n = 00 A n = A n = 60 A n = 800 A n = 00 A min. S 0. 0. r t v [ms] ( t = OFF) max. sd = ( ) x r min 00. 0...0.0..0.0 NSO0_008 r t r sd t v i sd = ( ) x r max..0..0 4.0.0.0 4.0.0 4.0 6.0.0 7.0 9.0 6.0 8.0 9.0 4 t r[s] 0 x n 000 00 t [s] 000 00 0 00 0 0 0. 0. n = A n = 60 A n = 800 A n = 00 A n = A n = 60 A n = 800 A min. n = 00 A S 0. 0. r t v [ms] ( t = ON) max. sd = ( ) x r min. 0...0.0 NSO0_008 r t r sd t v i sd = ( ) x r max..0.0 00..0..0 4.0.0.0 4.0.0 4.0 6.0.0 7.0 9.0 6.0 8.0 9.0 4 t r [s] 0 x n 7 /6 Siemens V 6 008

VT Molded Case Circuit Breakers up to 600 A 6 Catalog Technical nformation VT Molded Case Circuit Breakers up to 600 A General data 6/ - Overview Standard circuit breakers, releases 6/ - Selection and ordering data 6/ - Accessories Accessories and Components Auxiliary switches and shunt trip units 6/4 - Selection and ordering data Manual/motorized operating mechanisms 6/ - Overview 6/ - Selection and ordering data Mounting accessories 6/6 - Selection and ordering data Further accessories 6/7 - Selection and ordering data VT Molded Case Circuit Breakers up to 600 A Standard circuit breakers, trip units 6/8 - Technical specifications Circuit breakers, switch disconnectors 6/9 - Schematics 6/ - Functions 6/ - Design 6/ - Dimensional drawings Accessories and Components Withdrawable version 6/ - Technical specifications 6/ - Technical specifications Signalling units 6/ - Technical data Auxiliary switches 6/6 - Technical data Shunt releases 6/7 - Technical data Undervoltage releases 6/8 - Technical data Rotary operating mechanism 6/9 - Technical data Mechanical interlocks and mechanical interlocks for parallel switching 6/0 - Technical data Motorized operating mechanism 6/ - Technical data Siemens V 6 008