Supply air beam. Contact, Overview, Index. Guideline heating and cooling. Plexus. Professor / Professor Plus. Premum / Premax / Solus.

Size: px
Start display at page:

Download "Supply air beam. Contact, Overview, Index. Guideline heating and cooling. Plexus. Professor / Professor Plus. Premum / Premax / Solus."

Transcription

1 Contact, Overview, Index Guideline heating and cooling Plexus Professor / Professor Plus Premum / / Solus Architect Polaris I & S Plafond Podium Celo Cabinett Capella Carat Fasadium Atrium / Loggia Regula Drypac Lighting TEKNOsim 0.0 Lindab Ventilation. All forms of reproduction without written permission are forbidden. is the registered trademark of Lindab AB. Lindab's products, systems, product and product group designations are protected by intellectual property rights (IPR).

2

3 Use Lindab's supply air beam can be used for cooling, heating and ventilation. Water valves, actuators, Regula Secura, Regula Combi and Regula Connect can all be built into the beam. Installation I-0 is installed into a false ceiling, and can be suspended by hangers or threaded rods. As standard is delivered for a 00 x 00 T false ceiling. can also be delivered with a variety of different Clip-in options, making the beam suitable for other types of false ceilings. Worth noting features the Lindab JetCone, an innovative way of regulating the air volume. The air volume can easily be adjusted without having to worry about pressure and noise issues. The Angled Nozzle system secures a perfect air spread pattern, available in a number of factory preset angles. As a plus feature the Lindab AirGuide system offers readjustable air spread pattern control. The chilled beam is fully integratable with the Lindab ehybrid solution and together they provide an optimal energy efficient solution. Lindabs active chilled beams are Eurovent-certified and tested according to EN-. Key figures Length: Width: Height: Capacity: 0, 0, 00, 000 mm 00 mm (ceiling adaption available) 00 mm 0 W Calculation setup Room temp: C, Water temp: - C, Air temp: C, Nozzle air pressure: 0 Pa, Air flow: l/s/m

4 Optimal functions Despite the product's small external dimensions, the construction makes it possible to achieve a high cooling capacity. is Lindab's highest performing supply air beam designed to meet extra high cooling demands. is based on the induction principle. Ventilation air is released through the nozzles into a dispersal zone, thereby creating a low static pressure. The low pressure causes the warm air from the room to be induced into the ventilation air through the battery. The volume of the warm indoor air is two to seven times that of the ventilation air. The air is cooled as it passes through the battery, which consists of aluminium fins with copper pipes filled with cold, running water. The heat from the room is absorbed through the aluminium fins and then transferred through the copper pipe to the water circuit and goes further to a central cooling unit. can be delivered with an exhaust air valve, on request. Air duct Copper pipes Cooled air Warm indoor air Actuators Air duct Copper pipes Detachable faceplate Picture. is based on the induction principle. JetCone and Angled Nozzles The opening size of the nozzles can be adjusted, by operating the adjustment pins in each corner of the beam. The air distribution can also be adjusted, to achieve different amounts of air on either side of the beam, or to achieve an asymmetrical air pattern along the side of the beam. All thanks to our patent pending JetCone system. The Lindab Angled Nozzles system successfully combines the Jetcone air volume adjustment with a preset air spread pattern. The combination of the Jetcone and the Angled Nozzles systems results in reduced throw lengths and optimized air volume regulation. The design is made to secure the coanda effect and a fan-shaped air pattern. The adherence of the air to the beam already occurs at the JetCone opening. Then, due to the coanda effect, the air follows the side of the beam towards the ceiling. Coanda effect Battery

5 Hygiene Everything is accessible for service The faceplate is simple to lower or remove. The faceplate is kept in place by four cotter pins. If two of the cotter pins, on one of the long sides of the faceplate are removed, the faceplate will open and hang from the other two pins. For complete removal, please see the installation instruction. When the faceplate is lowered or removed, the battery is accessible from below (see picture ). Construction is power is Lindab's high performing supply air beam, giving the highest cooling capacity to be used in rooms with substantial cooling requirements. In terms of appearence looks like Premum and can therefore preferable be used in alternation with Premum beams and thus provide an architecturally uniform appearance in the room. is developed and designed to achieve a high degree of flexibility. The standard with Angled Nozzles and JetCone allows the adjustment of air diffusion, air volume and air pressure. The beam equipped with the plus feature Airguide, makes it possible to easily change the air spread pattern. The water pipes are made of copper. Nevertheless, the water should be oxygen-free to prevent corrosion. Picture. When the faceplate is lowered or removed, the battery are accessible from below. AirGuide system is shown in picture (plus feature).

6 Initial settings Adjustment JetCone is delivered as standard with Lindab s JetCone air volume adjustment system. The JetCone System makes a very flexible product with possibility of adjusting air diffusion, air volume and air pressure. Adjustment is made by setting the four adjustment pins into different positions. The adjustment pins can be set in any of the steps, thereby offering a total of 0 different settings. The adjustment is done without any tools, which makes it very fast and easy to adjust the air pattern, air volume and air pressure. The fast adjustment system gives an opportunity within planning, since the product choice can be made in an early stage and the products can be drawn into the planning of the project even though the planner do not have all the data normally required to select a suitable beam. Presetting Angled Nozzles To achieve a desired air spread pattern the beam is delivered with the Angled Nozzles air distribution system. The Angled Nozzles are a simple yet effective way of creating a divergent air spread pattern without the capacity issues normally related to an air deflector system. The Angled Nozzles can be delivered preset in one of the following standard settings: 0 (default setting) 0 In order to meet special demands, the Angled Nozzles can be delivered in other configurations than the ones mentioned above (picture ). For more information, please contact Lindab. NB! Please note that the Angled Nozzles are manufactured in a fixed position (default 0 ) and cannot be retrofitted or changed. Picture. Different settings for AirGuide (plus feature). JetCones. Adjustment pins 0.. Position. Max open nozzle, 0% air flow. Position 0. Max closed nozzle, 0% air flow.. Nozzles Picture. Lindab s JetCone air volume adjustment system. Example: A number of beams are installed in an open-plan office. A separate office is to be fitted into the room. If the climate is to be optimal, the air volume and air distribution needs to be adjusted on the beam that will be built into the new room (see picture ). If the air has to be directed in a specific direction, it is also possible to adjust an asymmetrical distribution pattern (see picture ). For more information please go to Picture. A separate office is to be fitted into the room. If the climate is to be optimal, the air quantity and air volume need to be adjusted for the beam that will be built into the new room.

7 Data Variants I-0 and I- are installed as an integrated part of a false ceiling, where the beam is fitted on top of a standard T support bar. X-0 is delivered for mounting below a false ceiling, as an integrated part of a ceiling tile system, with concealed T-bar. Lengths: is available in lengths from: I-0, I- and X-0:. m,. m,. m and.0 m. JetCone: The JetCone is standard feature. The factory settings will be done according to desired pressure (Pa) and primary air flow (l/s) and can be changed easily on site. Angled Nozzles: The Angled Nozzles are manufactured in a fixed position and cannot be retrofitted or changed (default is 0 ). Other settings on request. Water connection: The cooling water connections for are made of mm or mm (Optional), copper pipes. Heating pipes are mm. Air connection: is supplied with a Lindab NPU - nipple for Lindab Safe ducts. Design: is supplied as standard with a Slot perforation, with 0% open area. Other perforation patterns are also available. Surface treatment: is manufactured as standard from enamelled sheet metal. Colour The product is available as standard, in signal white RAL 00 or in pure white RAL 0, gloss value 0. Other RAL colours on request. Accessories Delivered separately. Control: Refer to the chapter Regula. Suspension components: threaded rods ( - 0 cm), or MHS hangers ( - 00 cm), for all beam lenghts. Plus features Factory preinstalled. AirGuide: The Lindab AirGuide system offers readjustable air spread pattern control. With a total of eight adjustment points (two points on each of the four deflector), and four different settings at each adjustment point, the AirGuide deflectors have different settings (Picture ). The adjustment is simply done by releasing a retaining clip in one end of the deflector. The deflector can then be adjusted to the desired setting and the retaining clip is refitted. These easy steps are then carried out for all the adjustment points that needs to be changed. The AirGuide will be pres-set (default is 0 - ) in the factory, If not any other setting is wanted and can be changed easily on side. Selection the AirGuide option will incur a capacity reduction of % for cooling and heating compared to the Angled Nozzles system. The AirGuide system is an alternative to the Angled Nozzles. Recommended settings are: 0 - (default, correspondend to 0 Angled Nozzles) 0 - (correspondend to Angled Nozzles) - (no corrosponded Angled Nozzles) 0-0 (special setting) NB! See page for Air patterns Heating: The product can be equipped with an additional water circuit in the battery to provide a heating function. Crosstalk protection: Crosstalk protection is build-in as standard. Integrated valve and actuator: A control valve, with variable Kv value, and an actuator can be pre-installed in the product. Integrated regulation unit: It is possible to have Lindab's room regulator, Regula Combi, pre-installed in the product. The control panel is fully accessible through the faceplate. Please see the Regula chapter. Regula Secura: Lindab's Regula Secura condensation protection can be installed in the product. Regula Connect: The product can be equipped with the Regula Connect connection card. Please see the Regula chapter for further information. Factory settings: Presetting of pressure (Pa), primary air flow (l/s), Angled Nozzles position (default 0 ) or spread pattern (if the AirGuide has been selected as plus feature). Exhaust air valve: can be delivered with build in exhaust.

8 Dimensioning Cooling capacity air P a. Start by calculating the capacity required for the room, to keep a certain temperature. Lindab s TEKNOsim is an excellent tool for this.. Calculate which cooling capacity, or read in diagram, that is supplied by the ventilation air.. Remaining heat load needs to be cooled by the water circuit in. The formula for calculating the capacity of the air: P a = q ma x c pa x t ra Size comparison by t r = C with: q a = Primary air flow rate P a [W] = q a [l/s] x. t ra [K] and P a [W] = q a [m³/h] x 0. t ra [K] Minimum flow Please note that flows below the recommended minimum flow, can result in unwanted air in the water pipes. Exciding the nominal flows is not recommandable as the capacity gains will only be minimal. Pipe diameter Min flow Nominelt mm 0.0 l/s 0.0 l/s mm 0.00 l/s 0.0 l/s Dimensioning Cooling capacity water P w Follow the instructions below to read off the effect from the diagram.. Calculate t rw.. Product length L minus 0. m, to obtain the active length L act.. Divide the primary air flow rate q a by the active length L act. Enter the result on the lower axis of diagram.. Follow the flow line to the right pressure, and then read off the specific cooling capacity P Lt per active metre.. Calculate the temperature difference in water circuit Δt w and find the capacity correction factor e Δtw in diagram.. Multiply the specific cooling capacity P Lt that was read off by e Δtw, t rw and active length L act. Definitions: P a = Cooling capacity air [W] P w = Cooling capacity water [W] P tot = Cooling capacity total [W] q ma = Air mass flow rate [kg/s] q a = Primary air flow rate [l/s] c pa = Specific heat capacity air [,00 kj/kg K] t r = Room air temperature [ C] t wi = Water inlet temperature [ C] t wo = Water outlet temperature [ C] t ra = Temp. diff., room air and primary air temp. [K] t rw = Temp. diff., room air and mean water temp. [K] t w = Temp. diff. water circuit [K] e tw = Capacity correction for temperature e qw = Capacity correction for water flow P Lt = Specific cooling capacity [W/(m K)] P a [W] Cooling Luftens kyleffekt capacity air 00 P a = q a, t ra t ra [K] Primary air Luftflöde flow rate q a [l/s] Diagram. Cooling capacity air P a as function of the primary air flow rate q a. If the air supply flow is l/s and the temperature difference of the room air and the supply air is t ra = K, then the cooling capacity of the air is W.

9 Example Cooling: What is the cooling capacity of a. m with 0 l/s and pressure of 0 Pa? The room s summer temperature is assumed to be t r =.º C The cooling water temperature in/out of the is /º C. Answer: Temperature difference: t rw = t r (t wi + t wo )/ t rw =. - (+) / = K Active length: L act =. m - 0. m =. m q a / L act = 0 l/s /. m = l/(s m) Read off, from diagram : P Lt = W/(m K). Diagram shows a capacity correction factor e Δtw : t w = t wi - t wr = C - C = K e Δtw = 0. Cooling capacity: P w = W/(m K) 0. K. m = W NB! The capacity diagram applies for the nominal water flow of q wnom = 0.0 l/s. To obtain the right cooling capacity P w for other flows, read off the capacity correction factor e qw from diagram, and then multiply the calculated cooling capacity by this factor as shown in example for heating. Specific Cooling Capacity P Lt [W/(m K)] Pa 0 Pa Pa 0 Pa 0 Pa NB! A reduction at up to % may occure, if the AirGuide has been selected q a / L act [l/(s m)] Diagram. Specific cooling capacity P Lt as a function of primary air flow rate per active metre at nozzle pressures of 0, 0, 0, 0 and Pa.,000,000 Capacity correction e Δtw,0000 0,00 0,00 0,00 0,00 Diagram. Capacity correction e Δtw as a function of t w. Only applies for cooling. t w

10 Dimensioning Capacity correction for water flow e qw Example Heating: What is the heating capacity of a. m with 0 l/s and pressure of 0 Pa? The room winter temperature is assumed to be t r = º C. The hot water temperature in/out of is /º C. Answer: Temperature difference: Δt rw = (t wi + t wo )/ t r Δt rw = (+) / - = 0 K Active length: L act =. m - 0. m =. m q a / L act = 0 l/s /. m = l/(s m) Read off, from diagram : P Lt =.0 W/(m K). Water capacity: P w =.0 0 K. m = W Use the calculated water capacity and calculate the water flow: q w = P w / (c pw x t w ) q w = / (00 x ) = 0. l/s The capacity correction e qw will then be 0. (see diagram ) and the new capacity: P w = x 0. = W. Using the new heating capacity, a new water flow is calculated: q w = / (00 x) = 0.0 l/s Read off the capacity correction e qw at 0. and calculate the capacity: P w = x 0. = W Using the new heating capacity, a new water flow is calculated: q w = / (00 x) = 0.0 l/s Seeing that the flow is near stabile at this point in the calculation, the heating capacity is calculated to be W. Capacity correction e qw Water Flow Rate q w [l/s] Diagram. Capacity correction e qw for water flow for both cooling and heating. Cooling Heating

11 Pressure drop in water circuit, cooling/heating [l/s] Cooling mm mm Lengths [m], ø,,,0, ø,,, Pressure drop [kpa] [l/s] Heating mm Lengths [m] Pressure drop [kpa] Diagram. Pressure drop in water circuit, cooling and heating. Example Cooling:. m, which provides on output of W, mm pipes. t w = K, q w = P w / (c pw t w ) q w = W/(00 Ws/(kg K) K) = 0.0 I/s The pressure drop in the water is read off as. kpa. Example Heating:. m, which provides on output of W, mm pipes. t w = K, q w = P w / (c pw t w ) q w = W/(00 Ws/(kg K) K) = 0.0 I/s The pressure drop in the water is read off as. kpa. Definitions: q w = Water flow rate [l/s] P w = Cooling/heating capacity water [W] c pw = Specific heat capacity water [00 Ws/(kg K)] Δt w = Temperature difference water circuit [K]

12 p t [Pa] 0 L <. m Pos no: 0 L <.0 m L W A db(a) q V [l/s] q V [ m /h] p t [Pa] 0 _> L. m Pos no: 0 L >,0 m Diagram. Sound effect level L WA and JetCone setting for L W A db(a) q V [l/s] q V [ m /h]

13 Dimensioning Pressure drop in air connection Table shows the pressure drop in the connection. After calculating the necessary pressure for the supply air beam, add the connection pressure drop to the selected static pressure in the nozzles. Example : I 0---A-. with 0 l/s and static nozzle pressure of 0 Pa. This provides the necessary total pressure in the duct of 0 Pa + Pa = Pa. Air flow [l/s] Pressure drop [Pa] 0 Table. Air pressure drop in the connection to I-0. Sound data Table. 's internal sound dampening. Noise level L woct For calculation of the noise level Internal sound dampening L Hz JetCone position db Correction C oct (db) Octave band, average frequency (Hz) L. m Hz db Correction C oct (db) Octave band, average frequency (Hz) L >. m Hz db Table a+b. 's noise levels L woct for each octave band in the beam, are calculated by adding the corrections C oct from the table above to the sound power level L wa db(a). The noise levels are calculated using the following formula: L woct = L wa + C oct Weight and water volume Weight, kg/m Water content, cooling, l/m 0. Water content, heating, l/m 0. Copper pipes, quality Pressure class Table. 's weight and water volume. EN - CU-DHP PN

14 Ventilation connections Inlet C Exhaust G A B Top view F E D H E A F B G C D H Figure. For A connection, is delivered with Lindab's standard nipple (NPU-). For B, C, and D connection, Lindab's elbow piece (BU 0 ) is included. Water connections Possible connections, air ( A, B, C, D ) and water (,,,,, ). A:,,,,, B:,,,,, C:,,, D:,,, Figure. Possible connections, water cooling and heating.

15 Connection,, or Figure. Placement of cooling and heating pipes ( mm). NB! When compression couplings are used, support sleeves must be applied. Connection or All copper pipeoutlets / inlets are labled to ensure correct connections. Connection A Connection B Figure. Examples of the most common supply air A and B variants. Go to next page to see overview of various water pipe connections. A B

16 lindab premax Valves & actuators Valve Actuator Figure. Valve with actuator mounted. Figure. Illustration of how the valve and actuator is placed inside the chilled beam, A example,. Dimensions Examples below show I-0 models with A air connection. For external dimensions, see next page. n Connection or Connection or 0 n 0 Connection or Figure. I-0-A with possible water connections.

17 Suspension I-0 (I-) 0 0 A (I- = ) I-0: L = 0, 0, 00, 000 mm; A =,,, mm. I-: L = 0, 0, 00, 000 mm; A =,,, mm. L = Nominal length (order length) Figure. I-0 suspension, dimensions. Suspension components are not supplied as part of the standard package. X-0 0 A X-0: L = 0, 0, 00, 000 mm; A =,,, mm. L = Nominal length (order length) Figure. X-0 suspension, dimensions. Suspension components are not supplied as part of the standard package.

18 Air patterns, The JetCone & Angled Nozzles systems used in guarantees the Coanda effect and a fan-shaped air pattern in all cases. The fan-shaped air pattern ensures air velocities in the living area that are half those obtained with a linear air pattern. The measurements shown below were made with a cooled supply air ( t room air supply air) of C and cooling in the water circuit ( t room air average water temperature) of C ,0m/s 0,m/s 000mm 000mm Air flow l/s/active m Air flow l/s/active m Figure. 00mm 0 00mm 00mm 0 00mm Figure ,0m/s 0,m/s 0,0m/s 0,m/s 000mm 000mm Air flow l/s/active m Air flow l/s/active m 00mm 0 00mm 00mm 0 00mm Figure. Figure. 0,m/s 0,0m/s Figure -. Air velocities between supply air beams at a separation of 00 mm. Standard air pattern profile (nozzles at a 0 angle). Nozzle pressure of 0 Pa.

19 Air patterns, The JetCone & Angled Nozzles systems used in guarantees the Coanda effect and a fan-shaped air pattern in all cases. The fan-shaped air pattern ensures air velocities in the living area that are half those obtained with a linear air pattern. The measurements shown below were made with a cooled supply air ( t room air supply air) of C and cooling in the water circuit ( t room air average water temperature) of C ,0m/s 0,m/s 0,0m/s 0,m/s 000mm 000mm Air flow 0 l/s/active m Air flow l/s/active m 00mm 0 00mm Figure. Figure. 0 00mm 0 00mm Figure -. Air velocities between supply air beams at a separation of 00 mm. Standard air pattern profile (nozzles at a 0 angle). Nozzle pressure of 0 Pa. 0 0,m/s 000mm 0,m/s 000mm Air flow l/s/active m Air flow l/s/active m 00mm 0 00mm 00mm 0 00mm Figure. Figure. Figure -. Air velocities between supply air beams at a separation of 0 mm. Standard air pattern profile (nozzles at a 0 angle). Nozzle pressure of 0 Pa.

20 Air patterns, The JetCone & Angled Nozzles systems used in guarantees the Coanda effect and a fan-shaped air pattern in all cases. The fan-shaped air pattern ensures air velocities in the living area that are half those obtained with a linear air pattern. The measurements shown below were made with a cooled supply air ( t room air supply air) of C and cooling in the water circuit ( t room air average water temperature) of C ,0m/s 0,m/s 000mm 0,0m/s 0,m/s 000mm Air flow l/s/active m Air flow l/s/active m 00mm 0 00mm Figure. Figure. 00mm 0 00mm 0 0 0,0m/s 0,m/s 0,0m/s 0,m/s 000mm 000mm Air flow 0 l/s/active m Air flow l/s/active m 00mm 0 00mm Figure 0. Figure. 00mm 0 00mm Figure -. Air velocities between supply air beams at a separation of 0 mm. Standard air pattern profile (nozzles at a 0 angle). Nozzle pressure of 0 Pa. 0

21 Air patterns, The JetCone & Angled Nozzles systems used in guarantees the Coanda effect and a fan-shaped air pattern in all cases. The fan-shaped air pattern ensures air velocities in the living area that are half those obtained with a linear air pattern. The measurements shown below were made with a cooled supply air ( t room air supply air) of C and cooling in the water circuit ( t room air average water temperature) of C ,m/s 000mm 000mm Air flow l/s/active m Air flow l/s/active m golvnivå floor 00mm 0 00mm Figure. Figure. 00mm 0 00mm 0 0 0,m/s 0,0m/s 0,m/s 000mm 000mm Air flow l/s/active m Air flow l/s/active m golvnivå floor 00mm 0 00mm 00mm 0 00mm Figure. Figure. Figure -. Air velocities between supply air beams at a separation of 0 mm. Standard air pattern profile (nozzles at a 0 angle). Nozzle pressure of 0 Pa.

22 Air patterns, The JetCone & Angled Nozzles systems used in guarantees the Coanda effect and a fan-shaped air pattern in all cases. The fan-shaped air pattern ensures air velocities in the living area that are half those obtained with a linear air pattern. The measurements shown below were made with a cooled supply air ( t room air supply air) of C and cooling in the water circuit ( t room air average water temperature) of C ,0m/s 0,m/s 0,0m/s 0,m/s 000mm 000mm Air flow 0 l/s/active m Air flow l/s/active m 00mm 0 00mm Figure. Figure. 00mm 0 00mm Figure -. Air velocities between supply air beams at a separation of 0 mm. Standard air pattern profile (nozzles at a 0 angle). Nozzle pressure of 0 Pa.

23 Air patterns, The JetCone & Angled Nozzles systems used in guarantees the Coanda effect and a fan-shaped air pattern in all cases. The fan-shaped air pattern ensures air velocities in the living area that are half those obtained with a linear air pattern. The measurements shown below were made with a cooled supply air ( t room air supply air) of C and cooling in the water circuit ( t room air average water temperature) of C. Air velocities on a table. 000 mm 000 mm 0 Vägg wall 00 mm 000 mm 000 mm Vägg wall 00 mm 000 mm 000 mm Figure. Figure mm Vägg wall Figure mm 000 mm 000 mm Figure -0. Air velocities below s supply air beam, where the air flow is l/s per active metre. Standard air pattern profile (nozzles at a 0 angle). Nozzle pressure of 0 Pa.

24 Air patterns, The JetCone & Angled Nozzles systems used in guarantees the Coanda effect and a fan-shaped air pattern in all cases. The fan-shaped air pattern ensures air velocities in the living area that are half those obtained with a linear air pattern. The measurements shown below were made with a cooled supply air ( t room air supply air) of C and cooling in the water circuit ( t room air average water temperature) of C. Air velocities on a table. Air velocities on a shelf. 000 mm 0 0,m/s 000 mm Vägg wall 00 mm 000 mm 000 mm Vägg wall 00 mm 000 mm 000 mm Figure. Figure. Air velocities at wall / throw ,m/s 000 mm Vägg wall 00 mm 000 mm 000 mm Figure. Figure -. Air velocities below s supply air beam, where the air flow is l/s per active metre. Standard air pattern profile (nozzles at a 0 angle). Nozzle pressure of 0 Pa.

25 Air patterns, The JetCone & Angled Nozzles systems used in guarantees the Coanda effect and a fan-shaped air pattern in all cases. The fan-shaped air pattern ensures air velocities in the living area that are half those obtained with a linear air pattern. The measurements shown below were made with a cooled supply air ( t room air supply air) of C and cooling in the water circuit ( t room air average water temperature) of C. Air velocities on a table. Air velocities on a shelf. 000 mm 0 0,m/s 000 mm Vägg wall 00 mm 000 mm 000 mm Vägg wall 00 mm 000 mm 000 mm Figure. Figure. Air velocities at wall / throw. 0,m/s mm golvnivå floor Vägg wall 00 mm 000 mm 000 mm Figure. Figure -. Air velocities below s supply air beam, where the air flow is l/s per active metre. Standard air pattern profile (nozzles at a 0 angle). Nozzle pressure of 0 Pa.

26 Air patterns, The JetCone & Angled Nozzles systems used in guarantees the Coanda effect and a fan-shaped air pattern in all cases. The fan-shaped air pattern ensures air velocities in the living area that are half those obtained with a linear air pattern. The measurements shown below were made with a cooled supply air ( t room air supply air) of C and cooling in the water circuit ( t room air average water temperature) of C. Air velocities on a table. Air velocities on a shelf. 000 mm 0,m/s 000 mm 0 Vägg wall 00 mm 000 mm 000 mm Vägg wall 00 mm 000 mm 000 mm Figure. Figure ,m/s 000 mm wall Vägg Figure. 00 mm 000 mm 000 mm Figure -. Air velocities below s supply air beam, where the air flow is l/s per active metre. Standard air pattern profile (nozzles at a 0 angle). Nozzle pressure of 0 Pa.

27 Air patterns, The JetCone & Angled Nozzles systems used in guarantees the Coanda effect and a fan-shaped air pattern in all cases. The fan-shaped air pattern ensures air velocities in the living area that are half those obtained with a linear air pattern. The measurements shown below were made with a cooled supply air ( t room air supply air) of C and cooling in the water circuit ( t room air average water temperature) of C. Air velocities on a table. Air velocities on a shelf. 000 mm 0,m/s 000 mm 0 wall Vägg 00 mm 000 mm 000 mm Vägg wall 00 mm 000 mm 000 mm Figure 0. Figure ,m/s 000 mm golvnivå floor Vägg wall Figure. 00 mm 000 mm 000 mm Figure 0-. Air velocities below s supply air beam, where the air flow is 0 l/s per active metre. Standard air pattern profile (nozzles at a 0 angle). Nozzle pressure of 0 Pa.

28 Air patterns, The JetCone & Angled Nozzles systems used in guarantees the Coanda effect and a fan-shaped air pattern in all cases. The fan-shaped air pattern ensures air velocities in the living area that are half those obtained with a linear air pattern. The measurements shown below were made with a cooled supply air ( t room air supply air) of C and cooling in the water circuit ( t room air average water temperature) of C. Air velocities on a table. Air velocities on a shelf. 000 mm 0,m/s 000 mm 0 wall wall Vägg 00 mm 000 mm 000 mm Vägg 00 mm 000 mm 000 mm Figure. Figure ,m/s 000 mm wall Vägg Figure. 00 mm 000 mm 000 mm Figure -. Air velocities below s supply air beam, where the air flow is l/s per active metre. Standard air pattern profile (nozzles at a 0 angle). Nozzle pressure of 0 Pa.

29 Air patterns, Throw and air patterns 00 mm under the ceiling l/s / active meter Angled nozzles presetting: l/s / active meter Angled nozzles presetting: 0 Figure. 0 0 Figure. Default Setting Angled Nozzles (or AirGuide). Throw and spreading 00 mm under the ceiling. 000 Throw and spreading 00 mm under the ceiling l/s / active meter Angled nozzles presetting: 0 l/s / active meter AirGuide setting: 0º - 0º 0 Figure. Figure. Figure -. Throw lengths with l/s active meter at 0 Pa t = K t rw 0

30 Control Lindab offers control equipment that is very simple to use. To avoid the heating and cooling being activated at the same time, the system is controlled sequentially (Regula Combi). For the technical data, refer to the chapter Regula. Designations Product/Version: I or X Type: 0, Connection diam. water, [mm]: or Connection diam. air, [mm]: Coupling options: A, B, C, D Coupling options, exhaust: E, F, G, H Water:,,,,, Length, [m]:. m,. m,. m and.0 m Plus features: See page Angled Nozzles: 0 (default),, 0 AirGuide: 0 - Order code Product I-0 A. 0 0 Type: I-0, I- I = Integrated, lay-in X-0 X = i.e. hidden T-bar, edge DS Water connection: mm, mm Air connection: Ø mm Connection type: A, A, A, A, A, A, B, B, B, B, B, B, C, C, C, C, D, D, D, D Product length:. m -. m -. m -.0 m Static nozzle pressure (Pa): Air volume (l/s): Programme text active chilled beam with adjustable airflow, for a given duct pressure. Air distribution must be adjustable between both sides of the beam and longitudinally, by a system like Lindab JetCone. The flow pattern must be fanshaped through the use of angled nozzles. Water and air connections must be flexible and accessible from below. s from Lindab Qty Product: I-0---A-. m 0 Air quantity: l/s Nozzle pressure: 0 Pa Plus features: AirGuide Regula Secura Heating Cooling control valve Cooling actuator Heating control valve Heating actuator Accessories: Regula Combi: 0 Product: I-0---A-.0 m Plus features: AirGuide Regula Combi Regula Secura Cooling control valve Cooling actuator Accessories: Tectite tool: 0

Supply air beam. Contact, Overview, Index. Guideline heating and cooling. Plexus. Professor / Professor Plus. Premum / Premax / Solus.

Supply air beam. Contact, Overview, Index. Guideline heating and cooling. Plexus. Professor / Professor Plus. Premum / Premax / Solus. Contact, Overview, Index Guideline heating and cooling Plexus Professor / Professor Plus Premum / Premax / Architect Polaris I & S Plafond Podium Celo Cabinett Capella Carat Fasadium Atrium / Loggia Regula

More information

Worth noting. Introduction. Key figures. lindab architect. Picture 1. Architect Circum, Luna and Prisma.

Worth noting. Introduction. Key figures. lindab architect. Picture 1. Architect Circum, Luna and Prisma. Contact, Overview, Index Guideline heating and cooling Plexus Professor / Professor Plus Premum / Premax / Solus Architect Polaris I & S Plafond Podium Celo Cabinett Capella Carat Fasadium Atrium / Loggia

More information

Contact, Overview, Index. Guideline heating and cooling. Plexus. Professor. Pilot. Architect. Polaris I & S. Plafond. Podium. Celo. Cabinett.

Contact, Overview, Index. Guideline heating and cooling. Plexus. Professor. Pilot. Architect. Polaris I & S. Plafond. Podium. Celo. Cabinett. & S Contact, Overview, Index Guideline heating and cooling Plexus Professor Pilot Architect & S Plafond Podium Celo Cabinett Capella Carat Fasadium Atrium H & C /Loggia Regula Drypac Lighting TEKNOsim

More information

Use. Worth noting. Key figures. Installation. lindab fasadium

Use. Worth noting. Key figures. Installation. lindab fasadium Contact, Overview, Index Guideline heating and cooling Plexus Professor / Professor Plus Premum / Premax / Solus Architect Polaris I & S Plafond Podium Celo Cabinett Capella Carat Atrium / Loggia Regula

More information

Nozzles. About Lindab. Comfort and Design. Product overview / symbols. Theory. Ceiling diffusers. Ceiling diffusers - visible.

Nozzles. About Lindab. Comfort and Design. Product overview / symbols. Theory. Ceiling diffusers. Ceiling diffusers - visible. Nozzles About Lindab Comfort and Design Product overview / symbols Theory Ceiling diffusers Ceiling diffusers - visible Plenum boxes Wall diffusers Nozzles Ventiduct Grilles Displacement diffusers VAV

More information

Slot diffusers. Slot diffusers, Round duct diffusers. Slot diffusers. Slot diffusers LD-13, LD-14

Slot diffusers. Slot diffusers, Round duct diffusers. Slot diffusers. Slot diffusers LD-13, LD-14 , Round duct diffusers D-, D- Application D- and D- slot diffusers are designed for the supply of air in rooms with floor to ceiling heights of.5 to m for supplying either cold or warm air, in particular

More information

Air distribution systems. Radial outlet RA-N2...

Air distribution systems. Radial outlet RA-N2... Air distribution systems Radial outlet RA-N... DS E 0.01 Radial outlet RA-N Preliminary remark KRANTZ KOMPONENTEN radial outlets RA-N have fixed radial vanes and are available with circular or square face.

More information

Krantz. Radial slot outlet with square blade array RL-Q2... circular blade array RL-R2... Air distribution systems DS 4186 E 09.

Krantz. Radial slot outlet with square blade array RL-Q2... circular blade array RL-R2... Air distribution systems DS 4186 E 09. Krantz Radial slot outlet with square blade array RL-Q2... circular blade array RL-R2... Air distribution systems DS 86 E 09./1 with square and circular blade array Preliminary remark The radial slot outlet

More information

Krantz. RL-C2 radial slot outlet. Air distribution systems

Krantz. RL-C2 radial slot outlet. Air distribution systems RL-C2 radial slot outlet Air distribution systems DS E 04.1 Introduction The RL-C2 radial slot outlet with circular face generates a turbulent mixed flow. It is used for supply and return air distribution

More information

Nozzle diffuser. Dimensions

Nozzle diffuser. Dimensions Nozzle diffuser GTI Dimensions Installation Ød Description GTI is a flexible supply air nozzle that is suitable for ventilation of large areas. The nozzle can be used for both heated and cooled air and

More information

Variable swirl diffusers

Variable swirl diffusers Swirl diffusers, Variable swirl diffuser OD- Application Diffuser is designed for air conditioning of rooms with floor to ceiling highs of to 0 m and high induction requirements. It is suitable for large

More information

Krantz Components. Twist outlet DD-N... for ceiling installation. Air distribution systems

Krantz Components. Twist outlet DD-N... for ceiling installation. Air distribution systems Krantz Components Twist outlet DD-N... for ceiling installation Air distribution systems DS E 0. Twist outlet Preliminary remarks and construction design Preliminary remarks Twist outlets for ceiling installation

More information

FRB. Exposed passive chilled beam for suspended installation

FRB. Exposed passive chilled beam for suspended installation Exposed passive chilled beam for suspended installation QUICK FACTS FRB is a passive chilled beam for comfort cooling especially designed for visible/suspended installation in the room. High cooling capacity,

More information

Grille. Min. - max. dimensions

Grille. Min. - max. dimensions Min. - max. dimensions H L 0 00 75 00 Standard grilles are available with mm pitch within the above min. and max. sizes. Customized sizes available on request. Description is an adjustable single or double

More information

Air distribution systems. Jet nozzle DW-N2... Swivel jet nozzle DW-V2... Twist nozzle DW-V2-...-DR

Air distribution systems. Jet nozzle DW-N2... Swivel jet nozzle DW-V2... Twist nozzle DW-V2-...-DR Air distribution systems Jet nozzle DW-N... Swivel jet nozzle DW-V... Twist nozzle DW-V-...-DR DS E 01. Jet nozzle and twist nozzle Preliminary remarks Jet nozzle DW N Swivel jet nozzle DW V Twist nozzle

More information

HELLA. Linear slot diffuser. Ordering codes. HELLA - Linear diffuser. Linear Diffusers 1 / 18. Example of the ordering code HELLA B-0-0-AN

HELLA. Linear slot diffuser. Ordering codes. HELLA - Linear diffuser. Linear Diffusers 1 / 18. Example of the ordering code HELLA B-0-0-AN Linear Diffusers / 8 HELLA Linear slot diffuser Ordering codes HELLA - Linear diffuser HELLA - Number of slots... Diffuser length L (mm) ) Increment mm... Deflector colour Damper Diffuser construction

More information

PELICAN Ceiling. Square ceiling air diffuser for supply air and extract air QUICK FACTS

PELICAN Ceiling. Square ceiling air diffuser for supply air and extract air QUICK FACTS Square ceiling air diffuser for supply air and extract air QUICK FACTS Flexible distribution pattern, yet the acoustic data remains the same One K-factor regardless of distribution pattern Designed for

More information

PELICAN Ceiling. Square ceiling air diffuser for supply air and extract air

PELICAN Ceiling. Square ceiling air diffuser for supply air and extract air Ceiling Square ceiling air diffuser for supply air and extract air Quick facts Flexible distribution pattern, yet the acoustic data remains the same One K-factor regardless of distribution pattern Designed

More information

Supply air nozzle. Dimensions. DAD-0 With flange for mounting on a wall or duct side.

Supply air nozzle. Dimensions. DAD-0 With flange for mounting on a wall or duct side. A imensions A-0 With flange for mounting on a wall or duct side. Ø ( ) 0 Ø F Ø Nom 0 0 Ø A Ø B Ø E escription A is an adjustable supply air nozzle suitable for ventilation of large areas where long throws

More information

Nozzle diffuser. Dimensions

Nozzle diffuser. Dimensions Dimensions ØU Ød H 0 ØA Description is a circular diffuser with individually adjustable nozzles. The diffuser is suitable for the horizontal supply of cooled air, where great flexibility in the dispersal

More information

Air distribution systems. Linear whirl outlet WL...

Air distribution systems. Linear whirl outlet WL... Air distribution systems Linear whirl outlet WL... DS 0 E 1.013 Preliminary remarks Mode of operation The linear whirl outlet generates turbulent mixing ventilation. It can be installed on or in a wall

More information

Air distribution systems. Adjustable induction outlet IN-V...

Air distribution systems. Adjustable induction outlet IN-V... ir distribution systems djustable induction outlet IN-V... DS E 0. Construction and function Preliminary remarks In addition to its induction outlet with preset discharge direction ), KRNTZ KOMPONENTEN

More information

KSV. Slot diffusers. Ordering code. Description. Linear diffusers 1 / 16

KSV. Slot diffusers. Ordering code. Description. Linear diffusers 1 / 16 Linear diffusers 1 / 1 KSV Slot diffusers Ordering code Number of slots Diffuser Length (mm) KSV - 1... - 19 Description KSV is an air terminal element primarily designated for air supply. It is suitable

More information

Plain diffuser. Dimensions

Plain diffuser. Dimensions Dimensions ØU Ød 22 37 ØD Description is a circular diffuser with unperforated face plate and can be used for both supply and extract air. is suitable for horizontal supply of cooled air where a high impulse

More information

Dimensions. Order code. Materials and finish. lindab ceiling diffusers

Dimensions. Order code. Materials and finish. lindab ceiling diffusers LKP Description LCP is a flush-mounted square diffuser with a circular unperforated face plate for installation in ceiling systems. LCP can be used for both supply and exhaust air. LCP is suitable for

More information

Air distribution systems. Adjustable radial outlet RA-V...

Air distribution systems. Adjustable radial outlet RA-V... Air distribution systems Adjustable radial outlet RA-V... DS E 0.2013 Construction design Preliminary remarks KRANTZ KOMPONENTEN has developed its wellknown, successful radial outlet into an adjustable

More information

Plain diffuser. Dimensions

Plain diffuser. Dimensions Dimensions Ø U Ød B C Ø E Ø A Description is a circular diffuser with an unperforated adjustable face plate and can be used for both supply and extract air. The diffuser can be switched between horizontal

More information

SWIFT Ceiling. Square ceiling air diffuser for supply air QUICK FACTS

SWIFT Ceiling. Square ceiling air diffuser for supply air QUICK FACTS Square ceiling air diffuser for supply air QUICK FACTS Flush design Also available in a version for extract air. Designed for modular suspended ceilings (600 x 600 mm) Quick Access Adapter for systemized

More information

Multi-cone diffuser. Dimensions

Multi-cone diffuser. Dimensions Dimensions Vertical Ød 8 Max. H ØU ØD Horizontal Ød Description is an adjustable circular multi-cone diffuser, which is typically used for supply air. The diffuser can be switched between horizontal and

More information

Circular duct grille

Circular duct grille Dimensions B+0 A+0 A B Description is a rectangular ventilation grille with vertical adjustable bars for direct installation in circular ducts. The grille can be used for both supply and exhaust air. The

More information

Ceiling Diffuser. Type ADLR with circular face. Type ADLR-Q with square face 2/16/EN/8

Ceiling Diffuser. Type ADLR with circular face. Type ADLR-Q with square face 2/16/EN/8 2/16/EN/8 Ceiling Diffuser Type ADLR with circular face Type ADLR-Q with square face TROX GmbH Telephone +49/28 45/2 02-0 Telefax +49/28 45/2 02-2 65 Heinrich-Trox-Platz e-mail trox@trox.de D-47504 Neukirchen-Vluyn

More information

NOP, NOT and NOX. Adaptable, flexible supply air diffusers with ultra low height for free installation. climecon.fi 07.16

NOP, NOT and NOX. Adaptable, flexible supply air diffusers with ultra low height for free installation. climecon.fi 07.16 NOP, NOT and NOX Adaptable, flexible supply air diffusers with ultra low height for free installation 07.16 NOP, NOT and NOX The most outstanding features of the NOP, NOT and NOX supply air diffusers are

More information

VK2 volume flow controller Overview

VK2 volume flow controller Overview New option with sound attenuator Maintenance-free VK2 volume flow controller that operates without an auxiliary power supply, for ventilation and air conditioning systems. Adjustable on site. Outstanding

More information

SWIFTTM. Ceiling. Square ceiling air diffuser for supply air

SWIFTTM. Ceiling. Square ceiling air diffuser for supply air SWIFTTM Ceiling SWIFT Ceiling Square ceiling air diffuser for supply air Quick facts Flush design Also available in a version for extract air. Designed for modular suspended ceilings (600 x 600 mm) Quick

More information

Krantz. Variable twist outlet with guide ring DD-VL... jet straightener DD-VG... Air distribution systems

Krantz. Variable twist outlet with guide ring DD-VL... jet straightener DD-VG... Air distribution systems Krantz Variable twist outlet with guide ring DD-VL... jet straightener DD-VG... Air distribution systems DS E 01.18 Variable twist outlet with guide ring or jet straightener Preliminary remarks The variable

More information

Swirl Diffusers Type DLA 7 and DLA 8

Swirl Diffusers Type DLA 7 and DLA 8 LTG Incorporated Swirl Diffusers Type DLA 7 and DLA 8 LTG Incorporated 1 Corporate Drive, Suite D Spartanburg, SC 93 PO Box 889, Spartanburg, SC 9 USA Tel: 86-599-63 Fax: 86-599-63 e-mail: info@ltg-inc.net

More information

Swirl diffusers, Variable swirl diffusers Swirl diffusers

Swirl diffusers, Variable swirl diffusers Swirl diffusers IMP Klima, Variable swirl diffusers Swirl diffuser OD- Fixed grille For air supply or exhaust Recommended temperature difference between supplied and internal air in the room is between 0 to 0 K Low static

More information

Multi-cone diffuser. Dimensions. Description FKD is an adjustable circular multi-cone diffuser, which is typically used for supply air.

Multi-cone diffuser. Dimensions. Description FKD is an adjustable circular multi-cone diffuser, which is typically used for supply air. Dimensions Vertical Ø N D F G Ø A Ø B C Horizontal Description is an adjustable circular multi-cone diffuser, which is typically used for supply air. The diffuser can be switched between horizontal and

More information

Krantz Components. Variable twist outlet with guide ring DD-VL... jet straightener DD-VG... Air distribution systems

Krantz Components. Variable twist outlet with guide ring DD-VL... jet straightener DD-VG... Air distribution systems Variable twist outlet with guide ring DD-VL... jet straightener DD-VG... Air distribution systems DS E 01. with guide ring or jet straightener Preliminary remarks The variable twist outlet with guide ring

More information

WISE Damper. Active damper for Swegon s WISE System for demand-controlled ventilation QUICK FACTS

WISE Damper. Active damper for Swegon s WISE System for demand-controlled ventilation QUICK FACTS Active damper for Swegon s WISE System for demand-controlled ventilation QUICK FACTS Variable or constant flow regulation or constant pressure regulation Wireless communication via radio Integrated sensor

More information

PELICAN Ceiling HF. Square extract air diffuser QUICK FACTS

PELICAN Ceiling HF. Square extract air diffuser QUICK FACTS Square extract air diffuser QUICK FACTS Perforated air diffuser front face Manages large extract airflows Flush design Designed for modular suspended ceilings Quick Access front face Can be combined with

More information

EUROVENT 8/12 SOUND TEST METHOD FOR DUCTED FAN COIL UNITS. FCP 2008 testing procedures FCP acoustical test method pag. 1

EUROVENT 8/12 SOUND TEST METHOD FOR DUCTED FAN COIL UNITS. FCP 2008 testing procedures FCP acoustical test method pag. 1 EUROVENT 8/12 SOUND TEST METHOD FOR DUCTED FAN COIL UNITS FCP 2008 testing procedures FCP acoustical test method pag. 1 CONTENTS 1 - PURPOSE... 3 2 - NORMATIVE REFERENCES... 3 3 - DEFINITIONS... 3 3.1

More information

CDD/CDR. Circular ceiling diffuser for supply air QUICK FACTS

CDD/CDR. Circular ceiling diffuser for supply air QUICK FACTS Circular ceiling diffuser for supply air QUICK FACTS Spread pattern can be shielded Used with commissioning box ALS Cleanable Adjustable slot Perforated diffuser face = CDD Non-perforated diffuser face

More information

CDD/CDR. Single cone ceiling diffusers for supply air. Quick facts. Quick guide CDD/CDR A I R F L O W - S O U N D L E V E L

CDD/CDR. Single cone ceiling diffusers for supply air. Quick facts. Quick guide CDD/CDR A I R F L O W - S O U N D L E V E L Single cone ceiling diffusers for supply air Quick facts Spread pattern can be shielded Used with commissioning box ALS Cleanable Adjustable slot Perforated diffuser face = CDD Imperforated diffuser face

More information

Linear diffuser. Description

Linear diffuser. Description A C B + D Description is a rectangular linear diffuser in aluminium. is suitable for both supply and exhaust air. is equipped with air guide baffles, making it possible to use for horizontal supply air.

More information

series FLOOR

series FLOOR series FLOOR www.koolair.com Floor Series 3 DSA, DSA-PR, DSA-HV and DF-CP-MT Floor swirl diffusers CONTENTS DSA / DSA-PR / DSA-HV diffusers 4 Models and dimensions 5 DSA Selection tables 6 DSA Selection

More information

Linear ceiling diffuser

Linear ceiling diffuser L-0--01e Linear ceiling diffuser Type LDD / LDDL Contents Realisation Application Safety instructions Contents Realisation Application Safety instructions Dimensions 3 Dimensions Installation Quick selection

More information

Slot diffuser. Type VSD35 2/2.6/B/3. with 35 mm wide slot

Slot diffuser. Type VSD35 2/2.6/B/3. with 35 mm wide slot 2/2.6/B/3 Slot diffuser Type VSD35 with 35 mm wide slot TROX UK Ltd Telephone +44 (0) 1842 754545 Caxton Way Telefax +44 (0) 1842 763051 Thetford e-mail trox@troxuk.co.uk Norfolk IP24 3SQ www.troxuk.co.uk

More information

ALC. ALBATROSS Supply air terminal for large airflows

ALC. ALBATROSS Supply air terminal for large airflows ALBATROSS Supply air terminal for large airflows Quick facts Large airflows Suitable for cooling or heating Manual or motorised adjustment Pressure drop independent of selected spread pattern Can be used

More information

Step Impulse Diffuser Model SIA

Step Impulse Diffuser Model SIA Step Impulse Diffuser Model SIA Ferdinand Schad KG Steigstraße 25-27 D-78600 Kolbingen Phone +49 (0) 74 63-980 - 0 Fax +49 (0) 74 63-980 - 200 info@schako.de www.schako.de Step Impulse Diffuser Model SIA

More information

Displacement Flow Diffusers

Displacement Flow Diffusers T 1.3/1/EN/2 Displacement Flow Diffusers Types QLE QLF for low turbulence air supply TROX GmbH Telephone +9/28 /2 02-0 Telefax +9/28 /26 Heinrich-Trox-Platz e-mail trox@trox.de D0 Neukirchen-Vluyn www.troxtechnik.com

More information

Swirl Diffuser. Type SDW T 2.2/1/B/1. recommended for room heights from approx m

Swirl Diffuser. Type SDW T 2.2/1/B/1. recommended for room heights from approx m T 2.2/1/B/1 Swirl Diffuser Type SDW recommended for room heights from approx. 2.60... 4.00 m TROX UK Ltd Caxton Way Thetford Norfolk IP24 3SQ Telephone +44(0) 1842 54545 Telefax +44(0) 1842 63051 e-mail

More information

THE ENERGY 68,SAVING TDVI. exible Combine Modular 24, 26, 28, 30, 32, 34, 36, 38, 40, 42, 44 HP 60, 62, 64, 66 HP

THE ENERGY 68,SAVING TDVI. exible Combine Modular 24, 26, 28, 30, 32, 34, 36, 38, 40, 42, 44 HP 60, 62, 64, 66 HP I N V E RT E R ion Range exible Combine Modular TDV I TDV I TDV I INVERTER INVERTER INVERTER 14, 16, 18, 20, 22 HP TDV I 24, 26, 28, 30, 32, 34, 36, 38, 40, 42, 44 HP INVERTER INVERTER INVERTER TDV I INVERTER

More information

Swirl diffusers, Variable swirl diffusers

Swirl diffusers, Variable swirl diffusers 0 Variable swirl diffusers SLOT IFFUSERS, ROUN UCT IFFUSERS SWIRL IFFUSERS, VARIABLE SWIRL IFFUSERS CIRCULAR IFFUSERS, SQUARE IFFUSERS VENTILATING GRILLES, VENTILATING VALVES, Variable swirl diffusers

More information

GTH. Rectangular double deflection grille QUICK FACTS

GTH. Rectangular double deflection grille QUICK FACTS Rectangular double deflection grille QUICK FACTS For supply air Adjustable air deflectors Cleanable Installed using mounting frames FHB / FHA or commissioning box TRG Available in alternative colours A

More information

XHDU Cassette type fan-coils for double/four pipe connections 1,98-14 kw HYDRONIC TERMINALS

XHDU Cassette type fan-coils for double/four pipe connections 1,98-14 kw HYDRONIC TERMINALS HYDRONIC TERMINALS XHDU 402 1203 Versions XHDU 2T XHDU-R 2T XHDU 4T XHDE 2T Single coil for double pipe connections Single coil for double pipe connections with heater Double coil for four pipe connections

More information

CNA-CNB. Centrifugal fans

CNA-CNB. Centrifugal fans NA-NB entrifugal fans Product facts Product Single-inlet low-pressure fans with backward-curved blades. Use In industrial ventilation systems for uncontaminated, non-corrosive air, max. 70 º, where a low

More information

Industrial Air Diffuser Type DLD for Heating and Cooling

Industrial Air Diffuser Type DLD for Heating and Cooling LTG Incorporated Industrial Air Diffuser Type DLD for Heating and Cooling LTG Incorporated Corporate Drive, Suite E Spartanburg, SC 20 PO Box 288, Spartanburg, SC 20 USA Tel: 8--0 Fax: 8-- e-mail: info@ltg-inc.net

More information

VRF Technical Data Book

VRF Technical Data Book VRF Technical Data Book DVM S for Euro_ET (R4A, Hz, HP) Model : Premium (Compact / Energy Efficiency) Type Standard Type History Version Modification Date Remark Ver. 1. Release DVM S (R4A, Hz, HP) for

More information

VDN2.. VEN2.. VUN2.. Radiator valves. Building Technologies HVAC Products ACVATIX TM. NF norm, for 2-pipe heating systems

VDN2.. VEN2.. VUN2.. Radiator valves. Building Technologies HVAC Products ACVATIX TM. NF norm, for 2-pipe heating systems 06 EN - Straight valves VDN.. Angle valves VEN.. Reverse angle valves VUN.. ACVATIX TM Radiator valves NF norm, for -pipe heating systems VDN.. VEN.. VUN.. Valve bodies made of brass, mat nickel-plated

More information

VD1 CLC. Small Valves DIN-range with a higher k v -value

VD1 CLC. Small Valves DIN-range with a higher k v -value 0 EN - Small Valves DIN-range with a higher k v -value VD CLC Valve body made of brass, mat nickel-plated DN, DN 0 and DN Internally and externally threaded (Rp / R) conforming to ISO 7- Manual knob /

More information

Circular duct grille. Dimensions. Description. Maintenance The grille should be removed to gain access to the duct.

Circular duct grille. Dimensions. Description. Maintenance The grille should be removed to gain access to the duct. Dimensions B+0 A+0 A B Description RGS is a rectangular ventilation grille with vertical adjustable bars for direct installation in circular ducts. The grille can be used for both supply and exhaust air.

More information

ALUMINIUM CENTRIFUGAL FANS. 4 x M6 x OUTLET x M6 x 20

ALUMINIUM CENTRIFUGAL FANS. 4 x M6 x OUTLET x M6 x 20 DESCRIPTION Dutair LK-series industrial ventilators consist of a robust body made from die-cast aluminium alloy. Impellers are made of extruded aluminium. The asynchronous electric motors are maintenance

More information

ALUMINIUM CENTRIFUGAL FANS x M6 x x M6 x 16

ALUMINIUM CENTRIFUGAL FANS x M6 x x M6 x 16 LK4 DESCRIPTION Dutair LK-series industrial ventilators consist of a robust body made from die-cast aluminium alloy. Impellers are made of extruded aluminium. The asynchronous electric motors are maintenance

More information

CIRCO. Sound-attenuating transfer unit QUICK FACTS

CIRCO. Sound-attenuating transfer unit QUICK FACTS Sound-attenuating transfer unit QUICK FACTS Supplied in pairs For the transfer of air through a wall Fits in a circular cut opening Simple to install Mounting frame integrated into the transfer diffuser

More information

Siv-inn School. Complete air-supply solution for school premises. Ensures excellent air supply Cleanable Reinforced front Ideal for renovation work

Siv-inn School. Complete air-supply solution for school premises. Ensures excellent air supply Cleanable Reinforced front Ideal for renovation work GB0702 11.15 Complete air-supply solution for school premises Ensures excellent air supply Cleanable Reinforced front Ideal for renovation work TROX Trox Norge AS PO Box NO-2712 Brandbu Telefon +47 61

More information

Method of Measuring Machinery Sound Within an Equipment Space

Method of Measuring Machinery Sound Within an Equipment Space ANSI/AHRI Standard 575 (Formerly ARI Standard 575) 2008 Standard for Method of Measuring Machinery Sound Within an Equipment Space Price $15.00 (M) $30.00 (NM) Printed in U.S.A. 8Copyright 1994, by Air-Conditioning

More information

GRC. Circular egg crate grille for transfer/extract air and wall/ceiling mounting QUICK FACTS

GRC. Circular egg crate grille for transfer/extract air and wall/ceiling mounting QUICK FACTS Circular egg crate grille for transfer/extract air and wall/ceiling mounting QUICK FACTS For exhaust air 91% free area Handles large airflows Cleanable Can be used with commissioning box ALS Standard colour

More information

Connections Standard. Description

Connections Standard. Description Section Convectors Description Connections Standard without built-in valve or version with built-in valve Air vent, Drain Fixing Pressure versions, Fittings, Surface finishes, Special versions Heat output

More information

PHOS 25 Downlight LED PROJECTOR

PHOS 25 Downlight LED PROJECTOR PHOS 25 Downlight LED PROJECTOR SPECIFICATIONS Item: PHOS 25 Downlight Body:... Steel / Aluminium Available Colours:....... White / Black / Silver Weight:.. 3.65 kg Ballast:...... External Ballast Included

More information

DCG adjustable core circular diffusers

DCG adjustable core circular diffusers Lievore, Altherr & Molina DCG adjustable core circular diffusers The DCG series diffusers are designed to be used in air-conditioning, ventilation and heating in premises from,6 meters high. They can be

More information

series 50-PR Square perforated face diffusers

series 50-PR Square perforated face diffusers series 50-PR Square perforated face diffusers www.koolair.com Series 50-PR 1 Square perforated face diffusers CONTENTS Square perforated face diffusers 54-FR Description 2 Coding and dimensions 3 Quick

More information

Addendum to ARI Standard , Air Terminals September 2002

Addendum to ARI Standard , Air Terminals September 2002 Addendum to ARI Standard 880-98, Air Terminals September 2002 The September 2002 Addendum to ARI Standard 880-98, Air Terminals, is comprised of only the shaded portions shown, which has been incorporated

More information

PHOS 15 LED PROJECTOR

PHOS 15 LED PROJECTOR PHOS 15 LED PROJECTOR SPECIFICATIONS Item:.. PHOS 15 Body:.... Aluminium Available Colours:... White / Black / Silver Weight:.... 1.9 kg On / Off Switch:..... Not Available Environmental Conditions:.....

More information

Mechanical flow-rate controllers

Mechanical flow-rate controllers L D L D L D Mechanical flow-rate controller MRP-1 (Circular) Description With the circular air flow controllers with automated action, the air flow rate is controlled via an asymmetrical control flap pivoting

More information

AX6 adjustable blades swirl diffusers

AX6 adjustable blades swirl diffusers AX6 adjustable blades swirl diffusers AX6 series swirl diffusers are designed to be applied in air conditioning, ventilation and heating in different premises from 2,6 meters high and temperature differential

More information

Multifunctional Thermostatic Circulation Valve MTCV

Multifunctional Thermostatic Circulation Valve MTCV Multifunctional Thermostatic Circulation Valve MTCV Introduction Fig. 1 Basic version - A Fig. * Self-acting version with automatic disinfection function - B * thermometer is an accessory Fig. 3 Version

More information

2/S12 DIFFUSER FOR HORIZONTAL OR VERTICAL DISCHARGE DHV. v 3.3 (en)

2/S12 DIFFUSER FOR HORIZONTAL OR VERTICAL DISCHARGE DHV. v 3.3 (en) 2/S12 v (en) DIFFUSER FOR HORIZONTAL OR VERTICAL DISCHARGE DHV 6 7 wwwklimaopremahr wwwklimaopremahr TABLE OF CONTENTS Horizontalvertical diffuser 9 Ordering key 1 Selection diagrams 1 DHV Ceiling diffuser

More information

The diagram below. to the by the. outlet into. calculation. Since TRANSMISSION VIA STRUCTURE. Vibration Via Supports Duct Breakout

The diagram below. to the by the. outlet into. calculation. Since TRANSMISSION VIA STRUCTURE. Vibration Via Supports Duct Breakout NOISE CONTROL IN VENTILATING SYSTEMS INTRODUCTION The diagram below shows the various noise sources and transmission paths of plant rooms and ventilation systems. For the ventilation system this can be

More information

PET PETI PET/PETI. Supply air diffuser for ceilings

PET PETI PET/PETI. Supply air diffuser for ceilings Supply air diffuser for ceilings PET PETI The TR connection box is an optional accessory for PET and PETI. Description The square perforated ceiling diffuser is best suitable for cofort ventilation. The

More information

MR medium rating busbar

MR medium rating busbar technical information General features MR is fully compliant with S EN 0-, specifically, the rated current of the Zucchini busbar trunking systems is always rated at the average ambient temperature of

More information

industry hall : highbay luminaire NJ700 LED Project number : sample system Customer : Processed by : Siteco Light Consulting Date : 07/2013

industry hall : highbay luminaire NJ700 LED Project number : sample system Customer : Processed by : Siteco Light Consulting Date : 07/2013 industry hall Customer : Processed by : Siteco Light Consulting Project description: spatial geometry (L*W*H): 54,00m*21,00m*9m reflection values (C*W*F): 70*50*20 maintenance factor: 0,67 user surface

More information

Hudevad P100. Technical datasheet

Hudevad P100. Technical datasheet Technical datasheet Key benefits Available in three depths Highly flexible in use Integrated top grille Harmonious and finished look Kundenedfal Low, streamlined design Ideal in front of glazing to prevent

More information

BNA Series. PLENUM FAN with Backward Wheels

BNA Series. PLENUM FAN with Backward Wheels BNA Series PLENUM FAN with Backward Wheels BNA Series BNA Series Plenum Fans Backward wheels Kruger Plenum Fans are designed for air handling applications where the fan operates unhoused within a plenum.

More information

Sound power level measurement in diffuse field for not movable sources or emitting prominent discrete tones

Sound power level measurement in diffuse field for not movable sources or emitting prominent discrete tones CFA 2018 - Le Havre Sound power level measurement in diffuse field for not movable sources or emitting prominent discrete tones F. Bessaca et P. Cellardb a CETIAT, Domaine Scientifique de la Doua, 25,

More information

2D - STRIP ANCHOR LIFTING SYSTEM

2D - STRIP ANCHOR LIFTING SYSTEM 2D - STRIP ANCHOR LIFTING SYSTEM WWW.TERWA.COM Terwa reserves the right to make changes to the documentation at any time Page 1 OVERVIEW LIFTING CLUTCHES AND TRANSPORT ANCHOR SA-B SA-ST SA-TTU UNIVERSAL

More information

ALUMINIUM CENTRIFUGAL FANS. 4 x M6 x 16

ALUMINIUM CENTRIFUGAL FANS. 4 x M6 x 16 DESCRIPTION Dutair BCT-series aluminium centrifugal fans with open die-cast aluminium impellers and forward curved blades are suitable for material transport and high pressure applications. The asynchronous

More information

ALUMINIUM CENTRIFUGAL FANS M20 4 x M5 x 10 INLET. 4 x M5 x 12

ALUMINIUM CENTRIFUGAL FANS M20 4 x M5 x 10 INLET. 4 x M5 x 12 BCT61 DESCRIPTION Dutair BCT-series aluminium centrifugal fans with open die-cast aluminium impellers and forward curved blades are suitable for material transport and high pressure applications. The asynchronous

More information

AIR HANDLING REFERENCE CATALOGUE PRODUCT SUMMARY COMPANY PROFILE HOW TO CONTACT US.

AIR HANDLING REFERENCE CATALOGUE PRODUCT SUMMARY COMPANY PROFILE HOW TO CONTACT US. AIR HANDLING REFERENCE CATALOGUE PRODUCT SUMMARY COMPANY PROFILE HOW TO CONTACT US www.bradflo.com.au HOME 1 GRILLES & LOUVRES GRILLES & LOUVRES Chapter Description Product Code 1.11 Double deflection

More information

Cooling Water Flow Regulator

Cooling Water Flow Regulator Temperature controlled, indirectly and directly actuated diaphragm valves / seat valves Port size G 3/8 to G DN 0 to DN 0 ontinuous regulation High accuracy No auxiliary energy required Technical data

More information

textile duct texi-jet textile duct high induction diffusion through perforations applications advantages recommandations and limits of use 5.

textile duct texi-jet textile duct high induction diffusion through perforations applications advantages recommandations and limits of use 5. texi-jet Page 1/5 high induction diffusion through perforations The TEXI-JET has been designed for high air velocity diffusion (7 < V < 15 m/s). This diffusion is ensured through rows of perforations designed

More information

DBS315 1-phase SIDE CHANNEL BLOWERS

DBS315 1-phase SIDE CHANNEL BLOWERS DBS15/ 1-phase DESCRIPTION Dutair blowers for pressure and vacuum are compact machines consisting of an electric motor with a built-on pump housing. The rotational speed of the impeller creates a high

More information

E 094 E 103 E 143. Tank top mounting Connection up to G1 Nominal flow rate up to 135 l/min e

E 094 E 103 E 143. Tank top mounting Connection up to G1 Nominal flow rate up to 135 l/min e R e t u r n F i l t e rs E 094 E 103 E 143 Tank top mounting Connection up to G1 Nominal flow rate up to 135 l/min 20.30-5e D e s c r i p t i o n Application In the return line circuits of hydraulic systems.

More information

MAC Aura XB Acoustic Test Report

MAC Aura XB Acoustic Test Report MAC Aura XB Acoustic Test Report 2017. Information subject to change without notice. HARMAN Professional and all affiliated companies disclaim liability for any injury, damage, direct or indirect loss,

More information

series KAT Acoustic air transfer units

series KAT Acoustic air transfer units series Acoustic air transfer units www.koolair.com 1 Acoustic Air Transfer Unit CONTENTS Acoustic Air Transfer Unit 2 Dimensions 3 Technical Data 5 Product Codes 7 2 Acoustic Air Transfer Unit - Description

More information

IBV Series C Carbon Steel Inverted Bucket Vertical Steam Trap

IBV Series C Carbon Steel Inverted Bucket Vertical Steam Trap Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without

More information

IBV Series Z Alloy Steel Inverted Bucket Vertical Steam Trap

IBV Series Z Alloy Steel Inverted Bucket Vertical Steam Trap Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without

More information

42C/V. Fan Coil Unit 42C/V

42C/V. Fan Coil Unit 42C/V 2/V Fan oil Unit 2/V arrier makes the world a better place to live by creating a comfortable, productive and healthy environment regardless of climate. It is our mission is to be customer s first choice

More information

Section 8 Column radiators

Section 8 Column radiators Section s Description Connections Standard without built-in valve -or- Version with built-in valve Air vent, Drain Fixing and mounting Pressure versions, Fittings, Surface finishes, Special versions eat

More information

Turbine Meter TRZ 03 PRODUCT INFORMATION. Reliable Measurement of Gas

Turbine Meter TRZ 03 PRODUCT INFORMATION. Reliable Measurement of Gas Turbine Meter TRZ 0 PRODUCT INFORMATION Reliable Measurement of Gas TURBINE METER TRZ 0 Method of operation, Construction Method of operation The TRZ 0 turbine meter is a flow meter suitable for gas measurement

More information