ELECTRIC FIELD AND VOLTAGE DISTRIBUTIONS ALONG NON-CERAMIC INSULATORS DISSERTATION

Size: px
Start display at page:

Download "ELECTRIC FIELD AND VOLTAGE DISTRIBUTIONS ALONG NON-CERAMIC INSULATORS DISSERTATION"

Transcription

1 ELECTRIC FIELD AND VOLTAGE DISTRIBUTIONS ALONG NON-CERAMIC INSULATORS DISSERTATION Presented in Partial Fulfillment of the Requirements for the Degree Doctor of Philosophy in the Graduate School o f The Ohio State University By Weiguo Que, M.S. * * * * The Ohio State University 2002 Dissertation Committee: Professor Stephen A. Sebo, Adviser Professor Donald G. Kasten Professor Longya Xu Approved by Adviser Department of Electrical Engineering

2 UMI Number: UMI UMI Microform Copyright 2003 by ProQuest Information and Learning Company. All rights reserved. This microform edition is protected against unauthorized copying under Title 17, United States Code. ProQuest Information and Learning Company 300 North Zeeb Road PC Box 1346 Ann Arbor, Ml

3 ABSTRACT High voltage insulators are essential for the reliable performance of electric power systems. All insulators, regardless of their material, are exposed to various electrical, mechanical and environmental stresses. The electrical stresses are the consequences of regular voltages and overvoltages. The mechanical stresses are related to the presence of various loads, e.g., the weight of conductors and hardware, wind load, ice load, etc. The environmental stresses of prime importance are the many forms of precipitation, UV radiation, and pollution. Since an increasing number of non-ceramic insulators are employed by electric utility companies for their new or updated power transmission lines, the analysis of their performance is relevant. The performance of these high voltage non-ceramic insulators is important for both dry and wet conditions. Long-term problems with them are related to the degradation of polymer materials used for the insulator, corona phenomena on the insulator surface, and pollution flashover. Most of these problems are related to the electric field distribution along the insulators. The dissertation research topic is the investigation of electric field and voltage distributions (EFVD) in the vicinity o f non-ceramic insulators. A three-dimensional 11

4 electric field analysis software package, Coulomb, based on the boundary element method, has been obtained and employed for the calculations. Main contributions of the dissertation research to the state of the art are as follows: 1. Principles of the full and simplified models as well as the calculation models of dry and clean non-ceramic high voltage insulators have been developed for the purpose of accurate calculations together with efficient calculation times. The modeling and its procedures are illustrated in detail by practical examples. 2. Models of the high voltage insulators alone are not sufficient. The detailed modeling of several more major components have been found essential. These major components are the power line tower, the three phase conductors, all conductor hardware, and corona rings. The effects of all these components on the EFVD along dry and clean insulators are analyzed and discussed. 3. A simple model with a flat polymer insulating sheet between two electrodes and a water droplet on it has been used to simulate the behavior of a water droplet on the shed and on the sheath region, respectively, of a non-ceramic insulator. Basic studies related to the effects of the changes in water droplet contact angle, size of droplet, shape of droplet, distance between adjacent droplets, and conductivity of water have been described in terms of the electric field strength enhancement, always referred to an appropriate base case. Ill

5 4. Several models of a four-shed non-ceramic insulator exposed to rain or fog conditions have been initiated, following observations during and after aging tests in a high voltage fog chamber. The calculation models of nine examples have been developed. The electric field and voltage distribution along wet insulators have been calculated and analyzed. 5. Selected calculations on dry and clean insulators using Coulomb software package have been verified with an electric field strength meter. The correspondence of calculations and high voltage measurements has been reasonably good. 6. Several research issues applied to various practical insulator design aspects have been investigated and discussed, such as the effect of the distance between the first shed and the end fitting, the shed spacing, the shed profile and the position of the corona ring on the EFVD along polymer insulators. The research described in the dissertation is directly applicable to the field of high voltage insulator design and development. IV

6

7 ACKNOWLEDGMENTS First and foremost, I express my sincere appreciation to Professor Stephen A. Sebo for guiding me through the most important five years in my life at The Ohio State University. I appreciate his invaluable guidance, insightful discussions, patience, and generous support throughout my studies. 1 would also like to thank Professors Donald G. Kasten and Longya Xu for their kindness of participating in my dissertation committee and for all their constructive advice. The generous support of Mr. Craig Armstrong, General Manager, Integrated Engineering Software was invaluable for this research. The use of Coulomb, an excellent software package of his company, Integrated, has made the dissertation research possible, as well as has made the completion time possible within a reasonable time. 1 also wish to thank Dr. Tiebin Zhao (The Ohio Brass Co.), who provided several polymer insulator samples used for this study. In addition, his technical advice and experience were indispensable for this research. 1 sincerely thank Mr. Robert Hill and Mr. David Crutcher (MacLean Power Systems) for their technical support by providing information and important examples related to 765 kv insulators and hardware. VI

8 I am also grateful for the help of Mr. Ozkan Altay, my colleague, for spending his valuable time in order to conduct some of the experiments with me. My deepest love and gratitude go to my wife WANG Yue, who has shared the excitements and difficulties in my life with me. 1 am grateful for her deep love, her joy, invaluable support and encouragement throughout the last five years. 1 also owe special thanks to my parents, for the education and love I received from them, and for their full support over the years. VII

9 VITA March 12, B om -H arbin, Heilongjiang, China B.S.E.E Tsinghua University, Beijing, China M.S.E.E Tsinghua University, Beijing, China Graduate Research Associate, Department of Electrical Engineering, The Ohio State University PUBLICATIONS Research Publications: 1. W. Que, and S. A. Sebo, Typical cases of electric field and voltage distribution calculations along polymer insulators under various wet surface conditions, Proceedings o f the 2002 Conference on Eleetrical Insulation and Dieleetric Phenomena, October 2002, pp W. Que, E. P. Casale and S. A. Sebo, Voltage-current phase angle measurements during aging tests of polymer insulators, Proceedings o f the 2002 Conference on Electrical Insulation and Dielectric Phenomena, October 2002, pp vm

10 3. E. P. Casale, W. Que and S. A. Sebo, Distribution of sait contamination in the course of fog chamber tests of polymer insulators, Proceedings o f the 2002 Conference on Electrical Insulation and Dielectric Phenomena, October 2002, pp W. Que, and S. A. Sebo, Electric field and potential distributions along dry and clean non-ceramic insulators, Proceedings o f the Electrical Insulation Conference and Electrical Manufacturing & Coil Winding Conference, October 2001, pp W. Que, and S. A. Sebo, Electric field and potential distribution along non-ceramic insulators with water droplets, Proceedings o f the Electrical Insulation Conference and Electrical Manufacturing & Coil Winding Conference, October 2001, pp W. Que, and S. A. Sebo, Electric field distribution in air for various energized and grounded electrode configurations, Proceedings o f the 2000 Conference on Electrical Insulation and Dielectric Phenomena, October 2000, pp E. Wang, X. Eiang, Z. G nan, and W. Que, Research on 500 kv phase to phase composite spacer for compact lines, Proceedings o f the 6th International Conference on Properties and Applications o f Dielectric Materials, June 2000, Vol. l,pp S. A. Sebo, C. M. Pawlak, D. Oswiencinski, and W. Que, Effects of humidity correction on the AC sparkover voltage characteristics of rod-rod gaps in air up to 30 /fwhwaafk)» Manufacturing & Coil Winding Conference, October 1999, pp EThcZticfrZ IX

11 9. S. A. Sebo, J. Kahler, S. Hutchins, C. Meyers, D. Oswiencinski, A. Eusebio and W. Que, Effects of the insulating cylinders (guards) in various gaps - the study o f AC breakdown voltages, Proceedings o f the 11th International Symposium on High Voltage Engineering, August 1999, Vol. 3, pp S. A. Sebo, J. Kahler, S. Hutchins, C. Meyers, D. Oswiencinski, A. Eusebio and W. Que, Effects o f the insulating sheets (barriers) in various gaps - the study of AC breakdown voltages and barrior factors, Proceedings o f the 11th International Symposium on High Voltage Engineering, August 1999, Vol. 3, pp C. M. Pawlak, D. Oswiencinski, W. Que and S. A. Sebo, Influence of rod electrode orientation on power frequency AC sparkover voltages of small air gaps, Proceedings o f the 30th Annual North American Power Symposium, October 1998, pp C. M. Pawlak, D. Oswiencinski, W. Que and S. A. Sebo, Humidity correction procedure and their effects on AC sparkover voltage characteristics of small air gaps, Proceedings o f the 30th Annual North American Power Symposium, October 1998, pp FIELDS OF STUDY Major Field: Electrical Engineering Minor Field: Circuits and Electronics Minor Field: Mathematics X

12 TABLE OF CONTENTS Abstract... ii Dedication... v Acknowledgments... vi Vita... viii List of tables... xiv List of figures...xv Chapters: 1. Introduction Overview Necessity for electric field strength distribution study along non-ceramic insulators Methods used for the study Description of existing problem s Obj ectives and main contributions Organization of dissertation Review of literature Structure of non-ceramic insulators Flashover mechanism of non-ceramic insulators Methods used for the electric field and voltage distribution study along insulators Experimental m ethods Numerical electric field analysis methods Software used for study and boundary element m ethod Software used for study Boundary element m ethod Electric field and voltage distribution study along insulators x i

13 EFVD study along insulators under dry and clean conditions EFVD study along insulators under wet and contaminated conditions Fault detection by electric field strength measurements Design considerations for non-ceramic insulators Summary and tasks of the dissertation Fundamental studies Simplification of the non-ceramic insulator model Effects of conductor and ground supporting structure Some basic features o f water droplets on a non-ceramic insulator surface Hydrophobicity of non-ceramic insulators Water droplet corona and dynamic behavior on the surface of nonceramic insulators Flat SIR sheet with a water droplet Sheath region simulation Shed region simulation Effects of water droplet contact angle, size, shape, distance, and conductivity Effect of water droplet contact angle Effect of water droplet size Effect of water droplet shape Effect of the distance between adjacent water droplets Effect of water droplet conductivity Summary Electric field and voltage distributions along non-ceramic insulators under dry and clean conditions Introduction Model of insulator, tower and additional components Modeling of a non-ceramic insulator and corona rings Modeling of line end hardware and conductors Modeling of tower and ground plane Voltage and electric field distributions along a non-ceramic insulator Comparisons between four and six subconductor bundles Effects of the tower configuration and other components Effects of other two phases of the three phase system Effects of tower configuration Effects of conductor bundles Summary Electric field strength and voltage distributions along a non-ceramic insulator under various wet conditions Introduction Hydrophobicity status of non-ceramic insulators x ii

14 5.3. Experiments in the OSU fog chamber Model setup Insulator models under rain conditions Analysis o f enhancement factors and electric field and voltage distributions for an insulator under rain conditions Insulator models under fog conditions Analysis o f enhancement factors and electric field and voltage distributions for an insulator under fog conditions Summary Verification tests for dry insulator Calibration te st Verification test Error analysis Summary Design considerations Model setup Effects of the distance between the first shed and the end fitting Effects of the shed spacing Effects of the shed profile Effects of the position of the corona ring Summary Conclusions and future w ork Conclusions Suggested future work Appendices: A. Brief review of Coulomb Software B. Basic two-shed insulator m odel Bibliography X lll

15 LIST OF TABLES Table... Page 3.1 Criteria for the hydrophobicity classification (HC) [44] The electric field enhancement factors on the surface o f the water droplet with different contact angles ffydrophobicity status of the insulator after 2 and 7 years o f service[54] Electric field enhancement factor (E. F.) for Cases RHC1-RHC6 at different locations Hydrophobicity of polymer insulator in different regions Electric field enhancement factor (E. F.) for Cases FHC1-FHC6 at different locations Insulator readings under various applied voltages A. 1 Sample computation time and related parameters XIV

16 LIST OF FIGURES Figure... Page 2.1 Simplified structure of non-ceramic insulators Insulator tester Simplified geometry and dimensions of the non-ceramic insulator to be modeled Four simplified insulator models and a full insulator model used for calculation Element configuration on the 34.5 kv non-ceramic insulator model Equipotential contours around the five computation models Voltage magnitude along the insulation distance at the surface of the sheath for Cases (d) and (e) Electric field strength magnitude along the insulation distance at the sheath surface for the full insulator, Case (e), and the simplified insulator model, Case (d ) Insulator model with grounded support structure and line conductor Equipotential contours around three computation models XV

17 3.9 Electric field strength magnitude along the insulation distance at the sheath surface of the insulator with and without the conductor and the grounded supporting structure Electric field strength magnitude along the insulation distance at the sheath surface for the full insulator and the simplified insulator model with the conductor and grounded supporting structure Definition of contact angle Typical examples of surfaces with HC from 1 to 6. HC 7 represent the completely wet surface Behavior of 10 ^1 water droplet located on a SIR sheet [50] Three types of water droplets on a vertical suspension insulator Experimental setup for the sheath region simulation Equipotential contours and electric field lines for sheath region simulation Electric field distribution along the SIR sheet surface for sheath region simulation Equipotential contours and electric field lines around a water droplet on the sheath surface Vector components and the magnitude of the electric field strength on the surface of the water droplet on the sheath surface Experimental setup for the shed region simulation Equipotential contours and electric field lines for the shed region simulation XVI

18 3.22 Electric field distribution along the SIR sheet surface for the shed region simulation Equipotential contours and electric field lines around a water droplet on the shed surface Vector components and the magnitude o f the electric field strength on the surface of the water droplet on the shed surface Equipotential contours and electric field lines around a water droplet on the sheath surface with different contact angles Electric field enhancement factor for a water droplet with different contact angles on the sheath region Electric field enhancement factor for a water droplet o f different diameters on the sheath region Electric field enhancement factor for a water droplet o f different diameters on the shed region Water droplet shapes on the sheath and shed region Equipotential contours around a water droplets with different shapes on the sheath and shed region Effect of the distance between water droplets on electric field enhancement on the sheath and shed region Simplified geometry and dimensions o f the 765 kv non-ceramic insulator model with 10 weather sheds at the line and ground end Dimensions and positions of the line and ground end corona rings Element configuration on the insulator and the corona ring surface xvii

19 4.4 Dimensions and element configuration of the yoke plate for four-subconductor bundles Dimensions and element configuration o f the yoke plate for six-subconductor bundles Geometry and dimensions of a 765 kv power line tower with four-subconductor bundles Geometry and dimensions of a 765 kv power line tower with six-subconductor bundles Entire view o f a 765 kv power line tower with four-subconductor bundles Entire view o f a 765 kv power line tower with six-subconductor bundles Calculation path along the sheath surface of the insulator Per cent equipotential contour for a 765 kv tower with four-subconductor Bundles under three phase energization Voltage distribution along the per cent insulation distance at the surface of the insulator sheath with four-subconductor bundles Electric field strength magnitude along the per cent insulation distance at the surface o f the insulator sheath with four-subconductor bundles Electric field strength magnitude along the per cent insulation distance at the surface of the insulator sheath with four-subconductor bundles near the line end Electric field strength magnitude along the per cent insulation distance at the surface of the insulator sheath with four-subconductor bundles near the ground end xviii

20 4.16 Leakage path at the surface o f the insulator sheath and weather sheds Electric field strength magnitude along the leakage path at the surface o f the insulator Per cent equipotential contours for a 765 kv tower with six-subconductor bundles under three phase energization Voltage distribution along the per cent insulation distance at the surface of the insulator sheath with six-subconductor bundles Electric field strength magnitude along the per cent insulation distance at the surface o f the insulator sheath with six-subconductor bundles Electric field strength magnitude along the per cent insulation distance at the surface of the insulator sheath with six-subconductor bundles near the line end Electric field strength magnitude along the per cent insulation distance at the surface of the insulator sheath with six-subconductor bundles near the ground end Voltage distribution along the per cent insulation distance at the surface of the insulator sheath for Cases F and S Electric field strength magnitude along the per cent insulation distance at the surface of the insulation sheath near the line end for Cases F and S Electric field strength magnitude along the per cent insulation distance at the surface of the insulation sheath near the ground end for Cases F and S Equipotential contours for a 765 kv tower with four-subconductor bundles under (a) single phase and (b) three phase energization xix

21 4.27 Voltage distribution along the per cent insulation distance at the surface of the insulator sheath under single and three phase energization Electric field strength magnitude along the per cent insulation distance at the surface of the insulator sheath near the line end under single and three phase energization Electric field strength magnitude along the per cent insulation distance at the surface of the insulator sheath near the ground end under single and three phase energization Equipotential contours for the four-subconductor bundles without and with the 765 kv tower under three phase energization Equipotential contours for the 765 kv tower without and with the four-subconductor bundles The fog chamber in the OSU High Voltage Eaboratory...I l l 5.2 Geometry and dimensions of a four-shed non-ceramic insulator Case RHCl water droplet distribution on the surface o f a non-ceramic insulator and the calculation model used for study Voltage distribution and equipotential contours on the surface of the first shed on a wet non-ceramic insulator with HCl hydrophobicity Case RHC2 water droplet distribution on the surface o f a non-ceramic insulator and the calculation model used for study Voltage distribution and equipotential contours on the surface of the first shed on a wet non-ceramic insulator with HC2 hydrophobicity XX

22 5.7 Case RHC3 water droplet distribution on the surface o f a non-ceramic insulator and the calculation model used for study Voltage distribution and equipotential contours on the surface of the first shed on a wet non-ceramic insulator with HC3 hydrophobicity Case RHC4 water droplet distribution on the surface o f a non-ceramic insulator and the calculation model used for study Voltage distribution and equipotential contours on the surface of the first shed on a wet non-ceramic insulator with HC4 hydrophobicity Case RHC5 water droplet distribution on the surface o f a non-ceramic insulator and the calculation model used for study Voltage distribution and equipotential contours on the surface of the first shed on a wet non-ceramic insulator with HC5 hydrophobicity Case RHC6 water droplet distribution on the surface o f a non-ceramic insulator and the calculation model used for study Voltage distribution and equipotential contours on the surface of the first shed on a wet non-ceramic insulator with HC6 hydrophobicity Equipotential contours for (a) dry Case and (b)-(g) Cases RHC1-RHC Electric field strength magnitude along the insulation distance at the surface of the sheath for Dry Case and Cases R H C l Electric field strength magnitude along the insulation distance at the surface of the sheath for Dry Case and Cases RHC Case FHCl water droplet distribution on the surface o f a non-ceramic insulator and the calculation model xxi

23 5.19 Case FHC2 water droplet distribution on the surface of a non-ceramic insulator and the calculation model Case FHC3 water droplet distribution on the surface of a non-ceramic insulator and the calculation model Equipotential contours for (a) Dry Case, (b) Case FFICI, (c) Case FF1C2, (d) Case FHC Electric field strength magnitude along the insulation distance at the surface of the sheath for Cases FFICI-FFIC Calibration test setup Relationship between the applied voltage and the insulator tester readings (T) Calculation model for the sphere g ap Verification test setup and dimensions o f the grounded supporting structure Electric field distrihution along the insulator measured hy the insulator tester (*) and calculated by the simulation model ( - ) Geometry and dimensions of a four-shed insulator Electric field strength magnitude along the per cent insulation distance at the surface of the insulator sheath with different D Electric field strength magnitude along the per cent insulation distance at the surface o f the insulator sheath with two different shed spacings Two shed profiles with different sheath/shed transition rounding radius xxii

24 7.5 Electric field strength magnitude along the per cent insulation distance at the surface o f the insulation sheath with different sheath/shed rounding radius values Dimensions and positions of the line end corona ring Maximum electric field magnitude at the triple junction point as a function of the corona ring position Electric field strength magnitude along the insulation distance at the surface of the insulator sheath with the corona ring at different locations..148 A.l The screen view of Coulomb software B. 1 Two-shed insulator between two parallel electrodes B.2 Equipotential contours around the shed edge of a two-shed insulator 159 XXlll

25 CHAPTER 1 INTRODUCTION I.l Overview The reliability of the power networks and apparatus is very important for the performance of an electric power system. In recent years, extra high voltage power lines have been widely used to transmit the electric energy from the power stations to the end users. Insulators are among the key devices of the electric power transmission systems. They are used to support, separate or contain conductors at high voltage. The insulators need to withstand not only regular voltages and overvoltages, such as lightning and switching events, but also various environmental stresses such as rain, snow and pollution. Pollution flashover is one of the main problems that endanger the reliability of an electric power system. The presence of contamination on the insulator surface, combined with highly humid and wet conditions such as fog, dew or rain, is particularly responsible for many insulator pollution ftashovers. With higher and higher voltages, the problem of insulator pollution flashover increases and the penalties increase sharply due to direct and 1

26 indirect lost revenue and the damage to the equipment. Therefore, more and more attention must be paid to improve the pollution performance o f insulators. Both porcelain and glass insulators have been used for over a hundred years. Although these materials have heen proven themselves to resist environmental aging, the pollution performance of these insulators is poor due to the hydrophilic surface of porcelain and glass materials. During recent decades, polymer insulators have heen introduced and widely used due to their better pollution performance. Currently, in the United States, polymer insulators represent approximately 60-70% of all new high voltage insulator sales [1]. Insulators made of polymer materials are often called composite or non-ceramic insulators. Non-ceramic insulators offer several advantages over porcelain insulators. They have excellent hydrophobic surface property under wet conditions, high mechanical strength to weight ratio, resistance against vandalism, saving on labor, and reduced maintenance costs [2]. A non-ceramic insulator consists of a core fiberglass rod, two metal end fittings, and polymer weather sheds, which are shaped and spaced over the fiberglass rod to protect the rod and to provide the required leakage distance. One of the parameters strongly affecting the long-term performance of non-ceramic insulators is the hydrophohicity of the weather shed surface. On a hydrophobic surface, water forms water beads, so the conductive contamination dissolved within the water beads is discontinuous. This reduces the leakage current and the prohability of dry band formation, which leads to higher flashover voltage. However, polymer materials have weaker honds than porcelain so they are more susceptible to chemical changes under multiple stresses encountered in service. These 2

27 stresses include the electric stresses due to the operating voltage, corona, arc, and environmental stresses due to contamination, ultraviolet (UV) rays, and heat cycling. Under these stresses, the hydrophohicity on the surface of the polymer weather sheds will be temporarily or permanently lost, which will worsen the pollution performance of nonceramic insulators. The main disadvantages of non-ceramic insulators are: (1) they are subject to chemical changes, (2) they suffer from erosion and tracking, (3) their life expectancy is difficult to evaluate, (4) faulty insulators are difficult to detect [2]. 1.2 Necessity for electric field strength distribution study along non-ceramic insulators The electric field distribution of non-ceramic insulator is different compared to porcelain insulators. Generally the electric field distribution of a non-ceramic long insulator is more nonlinear than that of a porcelain insulator. The reason is that there are no intermediate metal parts for a non-ceramic insulator. The electric field strength on non-ceramic insulators and associate hardware need to be controlled for three reasons: To prevent significant discharge activity on the surface material of nonceramic insulators under both dry and wet conditions which may result in the degradation o f the pollution performance of non-ceramic insulators. To avoid the internal discharge activity inside the fiberglass rod and the sheath rubber material that could result in mecbanical or electrical failure of nonceramic insulators.

28 To prevent corona activity from the metal hardware or the non-ceramic insulator, which may cause radio interference and acoustic emissions. When non-ceramic insulators are installed on a three phase power line, the conductors, the hardware, the tower configuration and the presence of the other two phases of the three phase system can influence the electric field strength in the vicinity of the non-ceramic insulators. Therefore, it is important to study these effects from a practical standpoint. To control the electric field strength in the vicinity of non-ceramic insulators, the end fitting shape of non-ceramic insulators need to be carefully designed. If necessary, a grading ring needs to be added. The pollution flashover mechanism of non-ceramic insulators has been studied and published by various researchers [3, 4, 5]. According to a recent study [6], the pollution flashover voltage of non-ceramic insulators is determined not only by the hydrophohicity but also by the pollution severity. When the contaminated layer of the insulator becomes moist or wet under rain and fog conditions, the contaminated layer becomes conducting. The presence of the water droplets on the surface of a non-ceramic insulator causes electric field enhancement. Intensification of the electric field strength on the non-ceramic insulator surface could trigger the surface discharges, which may ultimately lead to an undesirable surface flashover. The thorough study of the electric field strength enhancement due to water droplets on the surface of non-ceramic insulators under various wet conditions is important for the in-depth understanding of the discharge process and the pollution flashover initiation mechanism on non-ceramic insulators.

29 In addition, users often have some concerns about the aging of non-ceramic insulators. Their preference is to obtain simple diagnostic tools in order to evaluate the state of insulators and to replace the defective insulators in time. Visible problems can be found relatively easily by visual inspection. However, the non-visible defects inside the insulators are also very dangerous. They usually occur between the fiberglass rod and the sheath material covering the rod that might become separated from the rod. The discharges may occur inside and carbonize the rod. The carbonization of the rod not only reduces the insulating length of the insulator but also weakens the rod mechanically. Since the electric field strength in the vicinity of a non-ceramic insulator decreases considerably in front of an internally shorted or defective insulator, the electric field strength measurement method permits the detection of this kind of non-visible defect if the right type of instrument is available [7, 8]. 1.3 Methods used for the study Two kinds of methods have been used to study the electric field strength distribution along non-ceramic insulators. These methods can be classified as experimental methods and numerical analysis methods. For experimental methods, capacitive probes, flux meters, dipole antennas and electro-optical quartz sensors can be used as electric field strength measuring devices to study the electric field strength distribution along non-ceramic insulators under dry or wet conditions. A commercial available insulator tester designed by Positron Power Division can be used for the on-line measurement of the electric field strength distribution along

30 non-ceramic insulators, at some distance from the insulator. For numerical analysis methods, they can be used to calculate the electric field and voltage distribution (EFVD) along non-ceramic insulators. According to Maxwell s equations, all electromagnetic field problems can be expressed by partial differential equations, which are subject to the associated boundary conditions. By using Green s function, the partial differential equations can be transformed into integral equations. There are two different kinds of numerical analysis methods, using either differential equations or integral equations. The former is known as the field approach or domain method, and the second is known as the source distribution technique or boundary method. The domain methods include the finite difference method (FDM) and finite element method (FEM), which apply mainly for domains with hounded boundaries. The boundary method include the charge simulation method (CSM), and the boundary element method (BEM) which apply for domains with open boundaries and have no restrictions in regards the geometry of the domain. Since the research task is related to domains having open boundaries, the boundary element method is adopted for the study in this dissertation. 1.4 Description of existing problems Although the EFVD along the non-ceramic insulators has been widely studied for a long time, the results of these studies cannot be applied directly to the real power line insulators. The limitations of the previous studies are:

31 The analysis of the EFVD along non-ceramic insulators usually assumes single phase energization. However, a real power line means three phase energization, and the presence of the other two phases may have some influence on the EFVD along a non-ceramic insulator. Corona from water droplets has been demonstrated to play an important role in the aging of the non-ceramic insulator [9]. The knowledge of the relationship between the contact angle, size, shape and distribution of water droplets on the non-ceramic insulator surface and the electric field strength enhancement around the surface of water droplets is still rather limited. The flashover usually happens during fog and light rain conditions. Water droplets on the surface of non-ceramic insulators will change the EFVD along the insulators. The relationship between the wet status of the insulator surface and the EHVD along non-ceramic insulators under wet conditions is still not known completely. 1.5 Objectives and main contributions The general objective of this research is to study the electric field and voltage distribution along non-ceramic insulators, first, under dry and clean conditions and then, under various wet conditions. A commercially available software [55] (Coulomb of Integrated Engineering Software) based on the BEM is employed for the modeling and the calculation for the non-ceramic insulators under different surface conditions.

32 The specific objectives and the main contributions of the research can be summarized as follows: 1. Develop the model of a non-ceramic insulator with clean and dry surface. The geometry and dimensions of typical non-ceramic insulators have been used for modeling purposes. To reduce the calculation time for long non-ceramic insulators, several simplified insulator models have been developed in order to decide which geometry can be simplified without significantly impacting on the accuracy of the EFVD calculation results in the vicinity of the nonceramic insulators. Discussion of this contribution is in Section 3.1. Practical examples are discussed in Section Develop the models of two typical 765 kv power line tower with four or six subconductor bundles and non-ceramic insulators under three phase energization to simulate actual conditions. A simplified insulator model has been used for this case. The effects of the presence of the other two phases of the three phase system on the EFVD along the center phase insulators have been investigated. The effects of tower configuration and conductor bundles have also been studied. Practical examples are discussed in Sections 4.2, 4.3, and Develop a simple model of a flat silicon rubber sheet with a discrete water droplet on the upper side. This model has been used to simulate the water droplet on the shed and on the sheath region of a non-ceramic insulator. The relationships between the contact angle, size, shape, distance between adjacent droplets and conductivity of the water and the electric field strength 8

33 enhancement on the surface of water droplets have been studied. Discussions of this contribution are in Sections 3.3, 3.4 and Develop a four-shed insulator model with discrete water droplets only on the top of each shed to simulate the insulator under rain conditions. Discussions can be found in Chapter 5, especially in Sections 5.5 and 5.6. Develop a fourshed insulator model with discrete water droplets on the top of each shed, on the downside of each shed, and on each sheath region of the insulator as well to simulate the insulator under fog conditions. Discussions of this contribution are in Section 5.7 and 5.8. The relationships between the hydrophohicity status of the non-ceramic insulator and the EFVD along the insulator have been analyzed. 5. Verify the calculation results on a dry and clean non-ceramic insulator by using an electric field strength tester. Description of the measurements are in Chapter Study some important items for the non-ceramic insulator design, such as the distance between the first shed and the line end fitting, shed spacing, shed profile and the position of the corona ring. Results are discussed in Chapter Organization of dissertation The rest of this dissertation is organized as follows. In Chapter 2, the structure and the flashover mechanism of non-ceramic insulators are introduced first. Then, several experimental methods and numerical calculation methods used to study the EFVD along 9

34 the non-ceramic insulator are reviewed. A brief description of the BEM method and the Coulomb software [55] are given. The related research works on the EFVD study along insulators are summarized. In Chapter 3, the simplified model of the non-ceramic insulator is determined for the study of the EFVD along the insulator. Some basic features related to the electric field enhancement due to the existence of water droplets are investigated. In Chapter 4, the EFVD along a 765 kv non-ceramic insulator installed on two typical 765 kv power line tower with four or six sub-conductor bundles under dry and clean conditions are studied. The effects of the other two (side) phases of the three phase system, the tower configuration, and the conductor bundles are analyzed. In Chapter 5, the EFVD along a four-shed non-ceramic insulator under various wet surface conditions are studied. The cases analyzed are based on several stages of the hydrophohicity classification (FlC) recommended by the Swedish Transmission Research Institute (STRI). Electric field enhancement factors on the surface of water droplets are calculated. In Chapter 6, the electric field distribution along a non-ceramic insulator is measured with an insulator tester. The axial component of the electric field strength is measured and compared to the calculation results. In Chapter 7, some important items of the non-ceramic insulator design are discussed. In Chapter 8, the conclusions are summarized and future work is suggested. In Appendix A, Coulomb software package is described. In Appendix B, a two-shed insulator model is set up and the equipotential contours around the shed are shown. 10

35 CHAPTER 2 REVIEW OF LITERATURE In this chapter, several issues related to non-ceramic insulator research will be discussed. First, the structure of non-ceramic insulators will be introduced. Second, the flashover mechanism of non-ceramic insulators will be described in detail. There are many differences between the flashover mechanism of ceramic and non-ceramic insulators. The simultaneous existence of contamination layer and water droplets on the surface of weather sheds changes the electric field distribution along non-ceramic insulators and plays an important role during the discharge process. Third, to study the electric field distribution along non-ceramic insulators under various conditions, two kinds of methods can be used. They can be classified as experimental methods and numerical analysis methods. A brief description of each method and an introduction of the software package Coulomb, employed for the calculation in this research will be given. At the end of this chapter, research studies related to the EFVD along nonceramic insulators will also be reviewed. These research studies can be divided into four different groups: 11

36 1. EFVD study along non-ceramic insulators under dry and clean conditions. 2. EFVD study along non-ceramic insulators under wet and contaminated conditions. 3. Fault detection for non-ceramic insulators using the electric field measurement method. 4. Design considerations for non-ceramic insulator from the electric field strength distribution viewpoint. 2.1 Structure of non-ceramic insulators Non-ceramic insulators have three main components, which are shown in Fig The design of each component needs to be optimized to yield satisfactory electrical and mechanical performance over the lifetime of non-ceramic insulators. A V B ^ c ^ D IZZI (ZZI Figure 2.1: Simplified structure o f non-ceramic insulators: A: fiberglass rod; B: polymer sheath; C: polymeric weather sheds; D: metal end fitting. At the center of the insulator is a fiberglass reinforced polymer (FRF) rod. The FRF rod is reinforced with either polyester, vinyl ester or epoxy resin to provide the appropriate mechanical strength [2]. Epoxy resins offer better electrical properties than polyester resins, which are applied in some cases in order to reduce costs. Glass fibers are 12

37 made of alkali-borosilicate glasses (E-glass), which is a low alkali, lime-alumina borosilicate glass. The FRP rod has the dual burden of being the main insulating part and of being the main load-bearing part as well. Brittle fracture is a mechanical failure for the FRP rod of the non-ceramic insulator, which leads to catastrophic breakage under loads as low as 10 to 15 percent of their design strength. The mechanism involved is stress corrosion of the F-glass fibers, and can occur when the rod becomes exposed to acids in the environment. To avoid brittle fracture, chemical resistant alkali-aluminosilicate glass fibers (FCR) should be used, which are able to withstand acid attacks. The metal end fittings are typically forged steel, ductile cast iron, malleable iron or aluminum and are selected for mechanical strength. The end fittings are usually crimped or swaged to the FRP rod. This method has been proven suitable to supply the most dependable and economical solution for attaching the end fittings to the FRP rod [1]. The shape of the end fittings is also an important factor to limit the production of corona discharges. Corona discharges cause polymeric materials to become brittle, and it may even crack, leading to failure of the insulator by exposing the fiberglass rod to the ambient moisture [10]. The polymeric weather sheds and sheath are shaped and spaced over the FRP rod to prevent the rod from damage and to provide the required leakage distance. Therefore, the materials for sheds and sheath are required to have excellent aging resistance under multiple environmental stresses. The possible materials of the weather sheds include epoxy resins, ethylene-propylene diene monomer (FPDM), ethylene-propylene rubber (FPR) and silicone rubber (SiR). 13

38 The long-term performance of most of these materials in clean environments has been successful; however, in polluted environments their long-term performance has been less satisfactory. But SiR is an exception. The reason for the superior pollution performance of SiR is its ability to transfer the hydrophobic characteristic to the pollution layer on the surface at heavily polluted sites. No other polymeric material shows this property. The mechanism for this phenomenon is that the low molecular weight (LMW) compounds in the silicone rubber migrate to the surface of the pollution layer and form a thin film. Due to this coating effect, the pollution layer behaves like a SiR surface and becomes hydrophobic, which causes the water to bead up rather than to form a continuous film. 2.2 Flashover mechanism of non-ceramic insulators A flashover is a disruptive discharge over the surface of a solid insulation in a gas or liquid. The flashover mechanism of ceramic and glass insulators has been studied and well understood. For an EPDM insulator, the surface of weather shed becomes hydrophilic after a short period of exposure to a polluted environment. Thus the flashover mechanism of an EPDM insulator is similar to that of a ceramic insulator due to the hydrophilic surface. The flashover mechanism of a SiR insulator is different compared to a ceramic insulator due to the hydrophohicity transfer behavior to pollution layers. The contamination flashover is a multi-step process [3, 4, 5] for a SiR insulator. The basic steps in the common flashover process are: 14

39 1. Contamination build-up - The wind drives dust and/or other conductive contaminants onto the surface of the insulators. Insulators are usually covered by a uniform pollution layer. 2. Diffusion of LMW chains - Diffusion (it occurs naturally) drives the LMW polymer chains out of the weather shed material. The top of the pollution layer is covered by a thin layer formed by LMW polymer chains, which assure the hydrophohicity of the surface. 3. Wetting of the surface - Dew, fog, and light rain deposit the water droplets on the hydrophobic surface of the insulator. Salt from the pollutant dissolves in the water droplets that become conductive. The residual dry surface pollution is slowly wetted by the droplet migration. This forms a high resistance conductive layer and changes the leakage current from capacitive to resistive. 4. Ohmic heating - The leakage current flows through a high resistive layer on the surface of the insulator. Since the electrolyte has a negative thermal coefficient, the surface resistance will decrease slowly and the leakage current will increase due to ohmic heating. At the same time, drying and loss of moisture increase the surface resistance. The two opposing phenomena reach equilibrium at a lower value of leakage current. 5. Electric field effect on a hydrophobic surface - The continuous wetting increases the droplet density and reduces the distances among the droplets. The applied electric field flattens and elongates the droplets. If the distance is small, the neighboring droplets coalesce and filaments are formed. 15

40 6. Spot discharges - Filaments reduce the distance between the electrodes, increasing the electric field strength between the adjacent filaments. Corona discharges can occur if the electric field strength is sufficiently large. 7. Reduction of hydrophohicity - Water droplets related corona discharges age the polymer material around the droplets and reduce the hydrophohicity by rotation or breaking of the polymer chains. The filaments are joined together due to the reduction of hydrophohicity, which leads to irregular shape formations in the wet region. 8. Dry hand formation - The areas of the surface with the highest power dissipation dry first. As dry hands are insulating areas, the surface discharge activities continue within the dry hand region until the hand grows to a sufficient length to withstand the applied voltage. The resultant discharge activities cause surface erosion. 9. Flashover occurrence - Increase of the length of the filament and formation of wet areas finally short the insulator by a conductive electrolytic path. This conductive water surface provides a path for the arc, which travels on the surface of the electrolyte layer and causes the flashover. 2.3 Methods used for the electric field and voltage distribution study along insulators Experimental methods In order to obtain measurements of the electric field strength distribution along an insulator, several kinds of devices were designed and used in laboratory and field tests. 16

41 Initially capacitive probes, flux meters and dipole antennas were used as the electric field strength measuring devices. They typically had conductive electrodes, connecting cables, and measurement circuits. The metal connection caused considerable distortion of the electric field when the measurement point was above the ground plane. The systems used presently to measure the electric field strength have been designed differently. The signal is transmitted by means of an optical fiber from the probe at high potential to a receiving unit at ground. The optical fiber link may introduce only a small distortion of the electric field distribution. The size of the probe could be made very small in order to avoid the electric field distortion. The Pockets sensor is one o f the probes, which is used for electric field strength measurement. Hidaka [11, 12] published comprehensive reviews related to the Pockets sensor for electric field strength measurement. In his papers, he described the structure of the Pockets sensor in detail. The electric field strength measuring system consists of a coherent light source, an electro-optic material, polarizing plates, optical devices such as a quarter-wave plate for adjusting a phase shift, and a photo-detector. The main advantages of the Pockets sensors are: they directly measure the electric field strength they respond to changes in electric field strength in a wide range of frequencies from dc to GHz the electric field strength distortion by a Pockets sensor is very small. R. Parraud [13] published a comparative study of different electric field strength measurement methods. The sensors used were: ac potential meters 17

42 capacitive spherical sensors with optical data link [14] electro-optical quartz cubic sensors. The results showed that: The method using ac potential meters is not a good choice. Although the measured potentials are within ±10% of the calculated values, the meter shows significant differences compared to the correct results due to the influence of the measuring probe on the potential distribution. The method with capacitive spherical sensors shows a good correlation in the region between the electrodes. However, there is a significant difference near the electrode connected to the ground. The electro-optical method is a good choice. The measurement results of the electric field strength are very close to the calculated results between the two electrodes, except significant differences close to the electrodes, which can be attributed to the distortion of the field by the measuring probe Numerical electric field analysis methods There are several numerical analysis methods that are often used for the calculation o f the electric field strength distribution along insulators. They are: charge simulation method (CSM) boundary element method (BEM) finite element method (FEM) finite difference method (EDM). 18

43 A comprehensive reference book related to numerical electric field analysis methods is authored hy Zhou [15]. The numerical electric field analysis methods can be divided into two categories: the boundary methods and the domain methods. The boundary methods include the CSM and the BEM. The domain methods include the FEM and the EDM. The basic concept of the CSM is to replace the distributed charge of conductors and the polarization charges on the dielectric interfaces by a large number of fictitious discrete charges. The magnitudes of these charges have to he calculated so that their integrated effect satisfies the boundary conditions. The potential due to unknown surface charges can he approximated by three forms of concentrated fictitious charge arrangements - line, ring and point charges [16]. These charges can be placed at appropriate positions, which are usually inside the conductor surfaces. An adequate combination of the three forms of charges can he made to simulate almost any practical electrode system. The CSM method can be used to solve open boundary problems and is easily applied for three-dimensional electric field problems without axial symmetry. A major problem of CSM is the difficult and subjective placement of simulation charges. The other disadvantage is that it is difficult or impossible to calculate the electric field strength near very thin electrodes because the fictitious charges approximating the field must be usually inside the electrodes. The BEM is based on the boundary integral equation and the principle of weighted residuals, where the fundamental solution is chosen as the weighting function. There are two kinds of BEM. One is called indirect BEM, the other is called direct BEM. 19

44 In the indirect BEM, the potential is not solved directly. An equivalent source, which would sustain the field, is found by forcing it to satisfy prescribed boundary conditions under a free space Green function that relates the location and effect of the source to any point on the boundary. Once the source is determined, the potential or derivatives o f the potential can be calculated at any point. The surface charge simulation method (SCSM) is one type of the indirect BEM. In 3-D problems, the surfaces of the electrodes or the interfacial boundaries are discretized by planar triangle elements, curved triangle elements, or any other curved surface. After the boundary is discretized and the approximate function of the charge distribution is chosen, a great number of integral expressions has to be evaluated. Then the values of the surface charges can be solved from matrix equations. Compared to CSM, due to the flexibility of the approximate function of the surface charge, SCSM is more suitable for problems with complex geometry. In the direct BEM, the value of the function such as the potential and its normal derivative along the boundary are assumed to be unknown. The integral equations are discretized along boundaries and interfaces using the Galerkin method. Setting the proper boundary conditions to the given nodes, a set of linear algebraic equations is obtained. The solutions of these equations result in the boundary value of the potential and its normal derivatives. The field strength of most interest on the boundary is computed directly from the matrix equations. The FEM is a numerical method of solving M axwell s equations in the differential form. The basic feature of the FEM is to divide the entire problem space, including the surrounding region, into a number of non-separated, non-overlapping 20

45 subregions, called finite elements. This process is called meshing. These finite elements can take a number of shapes, but generally triangles are used for 2-D analysis and tetrahedra for 3-D analysis. Each element geometry is expressed by polynomials with nodal values as coefficients. The electric potential within each element is a linear interpolation of the potentials at its vertices. By using the weighted residual approach, the partial differential equations are reduced to a sparse, symmetric and positive definite matrix equation. Since the shape and the size of the elements are arbitrary, it is a flexible method that is well suited to problems with complicated geometry. The FEM analysis is effective for small problems that are closed bounded. If the problems are too large, a large number o f finite elements are required, and the calculation becomes intensive. The FDM is an approximate method for solving partial differential equations. It replaces a continuous field problem by a discretized field with finite regular node. This method utilizes a truncated Taylor series expansion in each coordinate direction, and applied at a set of finite discretization points to approximate the partial derivatives of the unknown function. The partial differential equations are transformed into a set of algebraic equations. The FDM is suitable for obtaining an approximate solution within a regular domain. If a region contains different materials and complex shapes, the FEM is better than the EDM. 2.4 Software used for study and boundary element method Software used for study The goal of this research is to analyze the electric field and voltage distribution in the vicinity of non-ceramic insulators in relevant cases by using an appropriate tool, 21

46 which is an electric field analysis software for the solution of three-dimensional (3-D) problems. There are several commercial software packages available for the computation of the electromagnetic fields. Coulomb, ANSYS/Emag, Maxwell 3D and Flux3D are the most popular ones. Coulomb has been designed hy Integrated Engineering Software Company [55]. It combines the efficiency of the BEM with a powerful user interface. It can he used for the calculation of the distribution of the static and the quasi-static electric field. It can he used to calculate the electric field strength and voltage values at any location throughout the entire model domain. The detailed features of Coulomb are described in Appendix A. ANSYS/Emag has been developed by ANSYS, Inc. It can be used for static, transient, and harmonic low frequency and electromagnetic field calculations. It can simulate electrostatics, circuits, and current conduction, as well as charged-particle tracing in both electrostatic and magnetostatic fields. This software is based on the FEM. Maxwell 3D, a 3D structure electromagnetic field simulator, has heen designed by Ansoft Corporation. The Maxwell 3D Field Simulator includes three analysis capabilities: electric fields, magnetostatic, and AC magnetic problems. The Electric Field module accurately solves electric fields and voltage levels in systems with conductors, charges and dielectrics. Electric stress levels, voltage maps, regions of dielectric stress and capacitance can also he evaluated. Flux3D, a fully integrated finite element based CAD package, has heen developed hy Magsoft Corporation. Flux3D solves electromagnetic and thermal problems for 3D geometry. Flux3D can handle static and steady state problems in closed or open boundary domains. 22

47 It has been observed by researchers that the analysis of the electric field distribution by integral methods such as BEM is more convenient than hy differential techniques such as FEM [17]. A BEM-type software (Coulomb) have several advantages over an FEM-type software (ANSYS/Emag): In BEM models, it uses only 2D surface elements on the surface, which are the interfaces of regions with different materials or surfaces with boundary conditions. This can greatly simplify the modeling process. Results are more accurate due to the smoothness of the integral operator. Its analysis of open boundary problems is superior to that of the FEM. The analysis of unbounded structures can he solved hy BEM without any additional effort because the exterior field is calculated the same way as the interior field. For open boundary problems, artificial boundaries, which are far away from the real structure, must he used for FEM. Therefore, Coulomb is particularly appealing for high voltage application models. In the proposed research work. Coulomb is used for the study of the EFVD along the non-ceramic insulators under different surface conditions. In Coulomb software, there are several basic steps to develop the non-ceramic insulator model in order to calculate the electric field and voltage distribution along the insulators: Setting up model units Creating the geometry Assigning physical properties Assigning voltages to boundaries 23

48 Assigning boundary elements to the boundaries Solving the problem and analysis Boundary element method Coulomb is based on the BEM numerical analysis method. In the BEM numerical analysis method [17], the electrode and dielectric boundaries are discretized into several boundary elements and a suitable distribution function is introduced for the equivalent surface charges along the discrete boundary elements. Then the electric field in the region of interest is considered to be caused by the equivalent surface charges along the boundary elements. The equivalent surface charges are determined by solving a system of integral equations, which are obtained by satisfying the following boundary conditions: 1. On the conductor surfaces with known potential, the prescribed values of the potential function, 0, are maintained. 2. On the dielectric-dielectric boundaries, the condition for the normal component of the electric flux density, D, is maintained. Details of the BEM can be found in [15] and [18]. In [19], there is a brief introduction to the BEM. Consider a bounded, linear, isotropic and homogenous dielectric material body, which is embedded in free space. The material medium is bounded by surface S, and characterized by permittivity e. There may exist a finite, impressed volume source, which has volume charge density Pv or a surface source, which has surface charge density <7, in 24

49 the space. From Maxwell s equations, it is known that at every ordinary point in the medium whose physical properties are continuous: xjf = () (2.1) = (2 2) It is convenient to introduce an electric polarization vector P defined by F = D - e,ê = D (2.3) where Eqis the permittivity of vacuum. By invoking Eq. (2.1), Eq. (2.2) can be written as V.^ = ±(V.^ _V.f) = l ( p + P ^ ) (2.4) ^0 ^0 where p ^= S /-P = ^ - p, (2.5) e Pev is called the equivalent volume charge density. At the interface of dielectric materials, the electric flux density is subject to the boundary condition n-{b^-bp) = a^ (2.6) where unit vector n points from medium (2) into medium (1). By using Eq. (2.3) in Eq. (2.6), M. (Æ, - ) = [(T, -». (^ - ^ )] = (a, + (T,, ) (2.7) ^0 ^0 where =-n-{p^ -.^ ) i s the equivalent surface charge density. From Eqs. (2.4) and (2.7), it can he concluded that the effects of a dielectric body in the electric field can he completely accounted for hy the distribution of the equivalent 25

50 volume charges in the dielectric body and the equivalent surface charges on the interface o f adjacent dielectric bodies. Since the electric field strength E is conservative, there exists a scalar potential such that ^ (2.8) Substitution of Eq. (2.8) into Eq. (2.4) yields modified Poisson s equation = (2.9) ^0 Thus, the potential (j) at any point can be calculated by using Green s theorem and solving Poisson s equation. For a continuously distributed surface or volume source in free space, the electric field strength at an observation point has a component in the direction connecting the source point and the observation point. If the potential of an arbitrary reference is set to zero at infinity and the medium in the problem domain is linear and isotropic, then the potential (j) of the observation point r can be determined by Eq. (2.10): 0 ( r ) = r f i i ± A u ( l ) ^ y + ( l) ù k (2.10) J 4ÆEo ^ J 4ÆEo r. where r,, are the radial distances from the point of the source to the observation point; Pv and Os are the impressed volume and surface charge density of the source, respectively; Pe,, and (Jes are the equivalent volume and surface charge density of the source, respectively. Usually the impressed volume and surface charge densities, Pv and Oi, are given in practice. The equivalent volume charge density, p^, in a homogeneous medium can be 2 6

51 obtained from Eq. (2.5). However, the equivalent surface charge density, Oes, must be determined by the specified boundary conditions. The most commonly used boundary conditions are: (1) Interface condition: If (7s is the boundary surface charge density on the dielectric-dielectric boundary, then the boundary condition at any point / on the interface of two dielectrics can be written as G i( ^ ) i- e 2 ( % 2 = ( T, (2.12) an dn where i, 2 is the permittivity o f dielectric 1, 2 respectively. (2) Dirichlet condition: on the surface of a conductor where f(i) is a known function. (3) Neumann condition: ^ 1 3 ) ^,= /( 0 (2 14) dn at the interface of a conductor and a dielectric where/(z) is a known function. By discretizing the boundary into non-separated, non-overlapping subregions, called boundary elements, Eq. (2.10) become: 1 4ke ' = 1 (' ip.7=1 5 jp (2 15) where (f)(p) is the point p on the electrode surface with known potential. 27

52 Tip and rjp are the radial distances from the point on the boundary of the source to the point p. Pesi and Oesj are the equivalent volume and surface charge density at the element, respectively. By solving the system of equations, the unknown values of charge density can be determined. Once the sources are determined, the potential and electric field strength in the problem domain can also be determined. 2.5 Electric field strength and voltage distribution study along insulators EFVD study along insulators under dry and clean conditions Misaki, Tsuboi, Itaka and Hara [20, 21] computed the electric field strength distribution to optimize the insulator design. Using the SCSM method, each curved surface was divided into many curved surface elements. The use o f the curved surface elements made it easy to approximate the insulator contour. The correction of the insulator contour could be performed smoothly for optimum insulator design. A concentric sphere model and a coaxial cylinder model were chosen to examine the accuracy of this method. This method was used to determine the optimum design of epoxy pole spacers in SFg gas insulated cables. Kaana-Nkusi, Alexander and Hackam [22] calculated the voltage and electric field distribution along a post-type insulator shed. The system was modeled with 146 ring charges, with 30 charges modeling each electrode. Several criteria were applied in order 28

53 to evaluate the quality of the calculation results, which included the potential error, the potential discrepancy, the normal electric flux density and the tangential electric field strength discrepancies. The calculation results showed that the maximum values of the electric field strength along the surface increased with higher dielectric permittivity of the insulating material. Decreasing the radius of curvature of the insulator shed increased both the normal and tangential components o f the electric field strength. Gutfleisch, Singer, Forger and Gomollon [23] described a new algorithm based on tbe BEM to calculate tbe electric field strength. The potential formulas of the different types of surface elements, such as rectangular, triangular, cylindrical, spherical, conical, toroidal, were presented in this paper. The accuracy of the results could be checked by computing the potential and electric field strength at the contour points or at test points at given contours. Two application examples were given in their paper. One was a disc insulator of a three-phase GIS, the other one was a transformer. Zhao and Comber [19] studied tbe electric field and potential distribution along non-ceramic insulators. The Coulomb electric field analysis software was used. Tbe insulator, tower and conductors were considered in the calculation model. Results showed that the conductor length has significant shielding effect on the insulators; the maximum electric field strength decreases when the length of the conductor increases; and the tower structure in the vicinity of the insulator and the diameter and the location of the grading ring are important in determining the maximum electric field strength along an insulator. 29

54 2.5.2 EFVD study along insulators under wet and contaminated conditions Hartings [24] introduced several experimental techniques to study the discharge phenomena on the surface of outdoor insulators. He used a two-dimensional ac probe available at Swedish Transmission Research Institute (STRl), which was developed by Homfeldt [25]. Two electro-optic voltmeters were placed inside a sphere (diameter: 50mm), which was divided into four galvanically separated quarters. The electro-optic voltmeters modified the polarization of appropriate light beams, which were converted to voltages. Hartings [26, 27] also conducted a series of experiments to study the ac behavior of hydrophilic and hydrophobic post insulators during rain. The radial and axial components of the electric field strength along an insulator under dry and rain conditions were measured. Under dry and clean conditions, no corona activity was observed at 50 kv. At 85 kv, discharge activity was observed at the HV flange. The effect of corona activity there is to extend the boundary of the HV flange. Under rainy condition, for a hydrophilic insulator, a capacitive electric field distribution was obtained only in the case of moderate rain intensity (0.4 mm/min) and low rain conductivity (50 ps/cm). A resistive electric field distribution may be obtained at and below 85 kv at values of 1.6 mm/min and 50 ps/cm. For a hydrophobic insulator, a capacitive electric field distribution was observed during all the test environmental conditions. At 50 kv, the electric field distribution during rain was similar to that at dry conditions. Hartings [26] also theoretically analyzed the effect of rain on the electric field distribution along non-ceramic insulators. He used a two-dimensional, cylindrically 30

55 symmetrical FEM program to perform the capacitive field calculations. Under dry conditions and in case of corona activity, the measured electric field distribution agreed well with the calculated capacitive distributions if the corona activity is considered in the model. During rain and no corona conditions, the measured electric field distrihution agreed reasonably with the calculated capacitive electric field distrihution if the water layer on the upper surface was included in the model. During rain and corona conditions, it was difficult to calculate the electric field distrihution due to the unknown potential of the corona activity, if it is not located at the electrode. Eklund and Hartings [28] studied the electric field distribution along composite and ceramic insulators during pollution tests using the same probe described in [24]. The probe was placed about 0.2 m away from the insulator to avoid discharge activities. Axial and radial electric field strength components were obtained for porcelain insulators, RTV-coated insulators, and composite insulators. On hydrophilic porcelain insulators, the increase of the axial electric field strength was accompanied by an increase of leakage currents up to several hundred ma. On hydrophobic composite insulators, the axial electric field strength increased as the amount of pollution built up on the insulator surface. Chakravorti and Mukherjee [29] developed an algorithm based on the CSM for calculating the power frequency and impulse electric field distributions around a HV insulator either with uniform or non-uniform surface pollution. The product of the electric resistivity o f the contaminant [Q/m] and the thickness o f the contaminant layer [m] are treated as a single parameter, Ps, which is called surface resistivity. They found that for ps>10" Q, the field is capacitive, while for ps<10^ ^2, it is resistive. For 31

56 intermediate values of ps, the field is capacitive-resistive. The highest electric field strength for the resistive field is nearly twice the corresponding value for the capacitive field and these stresses occur near the tip of the uppermost shed. For non-uniform surface pollution, excessively high dielectric stresses occurred at the junction of two different surface resistivities. Partial pollution of the insulator surface near the electrodes caused higher dielectric stresses than uniform pollution. Also the effect of dry bands was studied. The wider the dry band, the lower are the stresses at the edges of the dry band. The location of a dry band does not have a strong influence on the electric field strength at the edges. Xu and McGrath [30] studied the electric field strength and fherrnal field distribution of a 15 kv silicone rubber insulator under contaminated surface conditions using FEM. A 6-node triangular element, which has three extra or secondary nodes at the center of each side of the triangle, was employed. The contamination of the insulator was treated as an insulator covered uniformly with a conductive layer. The product of the electric conductivity of the contaminant [S/m] and the thickness of the contaminant layer [m] was treated as a single parameter, which was called surface conductivity. The thickness of the contaminant layer was fixed as ICf^ m. The influence of surface conductivity was also investigated. When the surface conductivity was in the range of 10"" to 10"^ S, the potential distribution along the surface of the insulator was primarily determined by the distribution of stray capacitance. When the surface conductivity was between 10"^** to 10"^ S, the electric field was of resistive-capacitive type. When it exceeded 10"* S, the potential distribution was completely resistive. 32

57 Ahmed, Singer and Mukherjee [31] developed a numerical method for the computation of the electric potential and electric field distribution on the surface of polluted insulators. The method was based on the surface charge simulation and discrete charge simulation techniques. The effects of the dry hand and wet pollution were taken into account. In order to produce a capacitive-resistive field, the value of the wet pollution surface conductance should be greater than 0.01 ns and less than 10 ns. Chakravorti and Steinbigler [32] calculated the capacitive-resistive field of HV porcelain and capacitor bushings. The boundary element method was used for electric field strength computations in two axi-symmetric bushing configurations including four dielectrics with transformer oil, porcelain, air, and bakelite tube. Effects of uniform and non-uniform distributions of surface resistivity and volume resistivity of different dielectric media were studied in detail. The dielectric stresses in the critical zone, where the distance between the live central conductor and the grounded metal tank is at a minimum, were calculated. The results showed that the volume resistivity of the dielectric medium had a significant effect on the stresses in the critical zone. The magnitudes and locations of the maximum dielectric stress were also determined. The uniform surface pollution did increase the dielectric stress near the tip of the uppermost shed, but the worst dielectric stress occurred for non-uniform surface pollution. El-Kishky and Gorur [33] used a modified charge simulation method for calculating the electric potential and field distribution along ac HV outdoor insulators. Accurate modeling of a non-ceramic insulator could be achieved with a significant reduction in the number of charges used in this method. They [34] also studied the electric field and energy distribution on wet insulating surfaces. The insulator wet surface 33

58 model is a rectangular strip of 2cmx25cm with different sizes of water droplets from 50 mm^ to 900 mm^. The relationships between the maximum electric field strength and the size, shape, spacing and location of the droplets were studied. As the size of the water droplets increased, the maximum electric field strength was reduced. As the water droplets were spaced further apart, the maximum electric field strength was reduced. The droplets near the HV electrode were subjected to severe electric field intensification. In another paper, El-Kishky and Gorur [35] also presented an approach for electric field strength computation on an insulating surface in the presence of discrete water droplets. The calculation method was based on the charge simulation technique, which was modified to handle long insulator chains. The accuracy of the method was established by internal error checks in the computation. Spherical and ellipsoidal shapes of water droplets were considered. Significant field intensification was observed at the triple junction of the insulator, air, and water droplet. The electric field intensification increased with the decreasing value of water resistivity. The shape of the water droplets was also an important factor that influenced the field intensification Fault detection by electric field strength measurements Many electric power utilities routinely install and replace non-ceramic insulators on overhead transmission lines using live working procedures. An essential requirement for ensuring worker safety is to confirm the electrical and mechanical integrity of nonceramic insulator prior to performing live work. Non-ceramic insulators may have some hidden or internal faults due to the manufacturing process, or due to the joint electric and 34

59 environmental stresses. One critical defect is the puncture or severe degradation of the sheath, since this type of defect allows ingress of moisture into the FRP rod of the insulator that may cause flashover or brittle fracture. Live line maintenance work needs some simple and economical test methods to detect the faults on the insulators. These defects need to he categorized and analyzed in terms of their likelihood to cause catastrophic failure during live work. Vaillancourt, Bellerive, St-Jean and Jean [36] developed a new live line tester as shown in Fig. 2.2 for porcelain suspension insulators. The insulator tester consists of a specially designed electric field strength probe. The probe is transversally mounted on a plastic sled that can he moved along an insulator string by means of a hot stick. The value of the electric field strength measured at the edge of each insulator shed is automatically recorded by a data logging unit. At the same time, an insulator counting circuit automatically keeps track of the probe position along the string. Data interpretation is done later, using a personal computer. A defective insulator appears as a dip on the plot of the electric field strength vs. probe position along the insulator string. Field tests were performed on some insulators of a 315-kV line and four faulty insulators were found by this method. The new device proved to he a very efficient way to test whether there are internal short-circuits of insulators o f long insulator strings. Figure 2.2: Insulator tester [36]. 35

60 Spangenberg and Riquel [37] summarized and evaluated measurement techniques in order to detect internal defects in non-ceramic insulators. The electric field strength measurements were carried out with a probe mounted on a carriage attached to a dielectric rod. The results showed that the presence of an insulator defect results in a potentially significant distortion of the electric field. The limitations o f this method are: The length of the defective place, compared to the total length o f the insulator, needs to be sufficiently long to produce a distortion of the field distribution curve. The measurement must be conducted on dry insulators. The probe must be in close contact with the insulator. Vaillancourt, Carignan and Jean [7] did some modifications to redesign the tester in [36] for its use on composite insulators. Since composite insulators usually have a much smaller diameter than that of porcelain insulators, the new probe size became much smaller. An optical sensor was used. The shed counting circuit was also redesigned to allow the counting of a large number of thin sheds. Laboratory experiments were designed to put various conductive and semi-conductive materials into the sheds of the insulator. The test results showed that this method worked well. During field tests, insulators damaged internally were located successfully by this method. Chen, Li, Liang and Wang [38] used the electric field mapping method to detect conductive internal defects of a 110 kv composite insulator. The tests were taken under dry and clean condition, wet condition, and polluted condition. The test data showed that under dry and clean conditions, tracking defects extending over one or two sheds can be easily detected at the HV end of the insulator. Experiments conducted on polluted and 36

61 wet insulators showed that the electric field distrihution is strongly distorted. The author concluded that in fair weather, at 82% humidity or less, the electric field strength mapping method is efficient for inspection. Gela and Mitchell [39] initiated a research project to analyze the performance of non-ceramic insulators from the live line working viewpoint. The electric field strength calculations were performed for hoth healthy and defective non-ceramic insulators along a longitudinal path ahout 40mm tfom the tips of the weather sheds. The path corresponds to the location of the electric field tester. The theoretically predicted behavior of the electric field profile along the non-ceramic insulator with a defect was confirmed experimentally using the commercially available tester. The presence of a moist contamination layer on the non-ceramic insulator distorted the electric field strength profiles Design considerations for non-ceramic insulators There are various concepts employed in insulator design to limit the leakage current and electric field strength near the surface of the weather shed which are responsible for tracking, erosion and flashover. These include: creating an aerodynamic weather shed profile for natural cleaning of the contaminants hy wind and rain; increasing the leakage path to limit the magnitude of the leakage current; providing a protected leakage path to establish dry bands o f sufficient number. 37

62 One of the most important details of composite insulator design is the design of the triple junction, i.e., the junction of the housing, air and metal end fittings. The electric field strength near this junction must he controlled in such a way that partial discharges at the metal flange are prevented. Sokolija and Kapetanovic [40] discussed three issues related to the non-ceramic insulator design. They studied the electric field strength in the vicinity of three types of the metal end fittings and pointed out that the point with the highest electric field strength on the electrode should be away from the triple junction point. They also mentioned that many insulator designs are created in such a way that the lowest shed is very close to the metal end fitting to enable the discharge activities reaching the shed region. Chakravorti and Steinhigler [17] studied the relationship between the shape of a porcelain post-type insulator and the maximum electric field strength around it with or without pollution. The position of the maximum electric field strength is near the top triple junction region. The parameters studied in their work are the slope angle of the insulator weather shed, the shed radius, the core radius, the axial height, and the electrode radius. Their findings were as follows: The higher slope angle does not yield notable reduction in the maximum electric field strength. Increasing the shed radius from 6 cm to 10 cm significantly lowers the maximum electric field strength. The increase of the core radius has little effect on the maximum electric field strength reduction. The higher the axial height, the lower the maximum electric field strength. 38

63 For a given insulator shape, increasing the electrode radius increases the maximum electric field strength in clean conditions hut reduces the maximum electric field strength in the presence o f surface pollution. Gorur, Cherney and Hackam [41] used fog chamber experiments to evaluate the polymer insulator shed profile designs. Six insulator profiles were evaluated with the same end fitting design and same leakage distance to surface area ratio. These experiments showed that the protected leakage path provided by the weather sheds plays a major role in the tracking and erosion performance of polymer insulators. For values of the electric field strength between 30 and 40 V/mm on the surface of a polymer insulator, tracking and erosion failure can be expected to occur. 2.6 Summary and tasks of the dissertation The literature reviews shows that the EFVD along dry and clean ceramic or nonceramic insulators has been studied extensively by several researchers. The effect of uniform and non-uniform pollution on the surface of the ceramic insulators has also been studied. The analysis of the EFVD along non-ceramic insulators usually assumes single phase energization. However, a real power line means three phase energization. The presence of the other two phases may have some influence on the EFVD along a nonceramic insulator and need to be studied. The performance of non-ceramic insulators under polluted and wet conditions is quite different and more complex than that of the ceramic insulators. There are only a few 39

64 experimental studies related to the EFVD along non-ceramic insulators when there are water droplets on the surface of the insulator weather shed. The relationship between the hydrophobicity status of the non-ceramic insulator under rain and fog conditions and the EFVD along the insulator is still unknown. The design of non-ceramic insulators and corona rings should also be considered to limit the maximum electric field strength near the triple junction area. Based on the literature review, there are six categories of the tasks for this dissertation. The first group of tasks consists of the simplification of the insulator model in order to reduce calculation time with the least influence on the EFVD calculation along the insulators. The second group of tasks consists of the model development for the 765 kv nonceramic insulator, suspension tower, live end hardware, grading rings, and conductors. The study of the EFVD along the 765 kv non-ceramic insulator under dry and clean condition, and the study of the effects of the other two phases (side phase) of the three phase system, conductors, tower configuration are also included. The third group of tasks consists of the model development of a fiat silicon rubber sheet with discrete water droplets on the upper shed and the study of the basic electric field enhancement around the surface o f a water droplet. The fourth group of tasks consists of the development for a four-shed non-ceramic insulator model under various wet surface conditions, the study of the EFVD along a four-shed non-ceramic insulator, and the study of the electric field enhancement on the water droplet surface. 40

65 The fifth group of tasks consists of the experimental study for the electric field distribution measurements along non-ceramic insulators using an insulator tester for the verification o f the calculation results by the experiment results. The sixth group of tasks consists of the design consideration for non-ceramic insulators, such as the distance between the first shed and the electrode, the shed spacing, the position of the corona ring. 41

66 CHAPTERS FUNDAMENTAL STUDIES In Chapter 2, a survey was presented on the study of the EFVD along nonceramic insulators and several issues were pointed out. Recently, various issues ahout the EFVD study along 765 kv non-ceramic insulators and water droplet related corona have received considerable attention. The two primary tasks of this chapter are: 1. Determine which simplification models of non-ceramic insulators can he used to study the EFVD along the insulators without losing much accuracy. 2. Investigate some basic features related to the electric field enhancement factor due to the existence of water droplets on a non-ceramic insulator. For the first task, several simplified models are investigated to determine the best method for modeling non-ceramic insulators and the approximations necessary to get valid results without requiring excessive computation time. For the second task, a flat silicone rubber (SiR) sheet with water droplets is used to examine the electric field enhancement factor due to the existence of water droplets with different contact angle, size, shape, and conductivity. 42

67 3.1 Simplification of the non-ceramic insulator model There are various kinds of non-ceramic insulators. One of the typical 34.5 kv non-ceramic insulators has 12 weather sheds, and its length is about 0.8 m. For comparison purposes, a typical 765 kv non-ceramic insulator has 103 weather sheds, and its length is 4.7 m. To get accurate results, much more elements have to he used for a 765 kv non-ceramic insulator than for a 34.5 kv non-ceramic insulator. When using the boundary element method to calculate the EFVD along non-ceramic insulators, the more elements are used, the more computation time is needed. In order to reduce the calculation time when analyzing long insulators, some simplifications of the non-ceramic insulator model are necessary. A non-ceramic insulator has four main components. They are the fiberglass rod, polymer sheath on the rod, polymer weather sheds, and two metal end fittings. To decide which component of the insulator can he simplified with the least influence on the accuracy of the calculation results on the EFVD along the non-ceramic insulators, a 34.5 kv non-ceramic power line insulator shown hy Fig 3.1 is employed for the study. The detailed geometric dimensions of a 34.5 kv insulator are shown in Fig The insulator is equipped with metal fittings at hoth line and ground ends. The insulator is made of silicone rubber with a relative permittivity of 4.3 and fiberglass reinforced polymer (FRP) rod with a relative permittivity of 7.2. There are 12 weather sheds on the housing. The insulator is surrounded hy air with a relative permittivity of 1.0. The top metal end fitting is taken as the ground electrode and the bottom electrode is connected to 43

68 a steady voltage source of 1 kv for the purpose of calculations. The insulator is positioned vertically, but it is shown in Fig. 3.1 horizontally for convenience. Units: mm Ground end Line end a Figure 3.1: Simplified geometry and dimensions of the non-ceramic insulators to he modeled. A: metal end fitting; B: fiber glass rod; C: polymer material weather sheds; D: polymer material sheath. Four simplified computation models are used for the step hy step comparison process. In addition, a three dimensional full insulator model is set up as a reference to study the effects of the four simplified computation models of the non-ceramic insulator on the EFVD along the insulator. These five calculation models are shown in Fig. 3.2: (a) two electrodes only (b) two electrodes and the fiberglass rod (c) two electrodes, rod and sheath on the rod without weather sheds (d) two electrodes, rod, sheath, two weather sheds at the each end of the insulator (e) the full 34.5 kv insulator. 44

69 I r (a) (c) (e) Figure 3.2: Four simplified insulator models and a full insulator model used for calculation. As an example to show the element configuration, the full insulator model has four-sided elements applied to the surface of boundaries and the interfaces of different media. The element configuration on the surface of the insulator is partially shown in Fig Figure 3.3: Element configuration on the 34.5 kv non-ceramic insulator model. 45

70 The equipotential contours around the five computation models are shown in Fig As a reminder, the bottom electrode is energized, the top electrode is grounded. The energizing voltage is 1000 V. The insulation distance between two electrodes is 46 cm ^ ^ " ""." " _ ^ _ '" ''7 0 6 ' ' 2 95^ ' 75O, :^ / (a) (b) (c) (d) (G) Figure 3.4: Equipotential contours around the five computational models. Each number shown along the perimeters of the four contour plots means centimeters. Case (a), no solid insulating material between the electrodes, shows that about 20% o f the insulation distance sustain about 70% of the applied voltage. The presence o f the fiberglass rod slightly changes the voltage distribution, see Case (b). The 46

71 distribution of the equipotential contours for Case (c), with the sheath on the rod, is very close to Case (e), however, the presence of the weather sheds changes somewhat the equipotential contours. If more accurate results of the voltage distribution are needed near the line and ground end area, the simplified insulator model with two weather sheds at each end of the insulator. Case (d) can be used. Comparing Cases (d) and (e), the voltage distribution in the vicinity of the two weather sheds is very similar to each other. The positions of the equipotential lines for Cases (d) and (e) are very close to each other along the sheath surface of the insulator. To see the comparison more clearly, the voltage distribution for Cases (d) and (e) along the paths (shown as the dashed line in Figs. 3 (d) and (e) ) are shown in Fig Comparing Cases (d) and (e), the maximum difference between the voltages at the same point along the sheath surface of the insulator is only 1.2% of the applied voltage. This indicates that the simplification introduced by Case (d) is acceptable for the calculation o f the voltage distribution of the full insulator. Case (e), along the sheath surface > 800 & 700 ^ 600 > \ Insulator w ith 12 sh ed s for C ase (e) Insulator w ith 4 sheds for C ase (d) Insulation distance (%) Figure 3.5: Voltage magnitude along the insulation distance at the surface of the sheath for Cases (d) and (e). 47

72 The electric field strength magnitudes for Cases (d) and (e) along the paths defined on the surface of the sheath are also calculated for comparison, which is shown in Fig The dips in the electric field strength plot of the insulator modeled with weather sheds are due to the calculation path passing through the weather shed material, which has a relative permittivity of 4.3. The electric field strength in the vicinity of the two weather sheds at each end of the insulator is same for Cases (d) and (e). There is a slight change in the electric field strength distribution near the other 8 weather sheds shown by Case (e). However, the electric field strength outside the weather sheds region still has a good correspondence in Cases (d) and (e). The maximum electric field strength for Case (d) is kvp/mm, and for Case (e) is kvp/mm. They are the same, which means that the electric field distribution of the insulator with the full number of weather sheds can be estimated through the simplified insulator model with a small number of weather sheds (for example, 2) at the each end of the insulator. ^ a ^ â 0.02 Æ % g ^ ^ a Cl W Insulator w ith 12 sheds for C ase (e) Insulator w ith 4 sh ed s for C ase (d) Insulation distance (% Figure 3.6: Electric field strength magnitude along the insulation distance at the sheath surface for the full insulator. Case (e), and the simplified insulator model. Case (d). 48

73 3.2 Effects of conductor and ground supporting structure When a suspension non-ceramic insulator is put in service, the tower window that is at ground potential, and the conductors that are energized will have some effects on the electric field distribution in the vicinity of the insulator. The effects of the grounded supporting structure and the power line conductor on the EFVD near the insulator are studied by adding a 3m long, 1.74 cm diameter single conductor section just below the insulator. The insulator is suspended from the middle of a 1.6 m x 0.4 m grounded supporting structure. The full insulator. Case (e), and the simplified insulator model, Case (d), are both used for the calculation for comparison purpose. The two insulator models with the conductor and the grounded supporting structure are shown in Fig A (a) Full insulator model (b) Simplified insulator model Figure 3.7: Insulator model with grounded supporting structure and line conductor. 49

74 The equipotential contours around the full insulator model and the simplified insulator model together with the conductor and the grounded supporting structure are shown in Fig _ 26 d " " ^ ^ 65[... A 0 n r ' googoo ; 05% / ; ; 1' ; ' _ (a) Full insulator (b) Full insulator (c) Simplified insulator with no conductor with conductor with conductor Figure 3.8 Equipotential contours around three computation models. For the insulator without the conductor and the grounded supporting structure, 20% of the insulation distance sustain about 65% o f the applied voltage. For the insulator with the grounded supporting structure and conductor, it can be seen that now 20% of the 50

75 insulation distance sustain about 47% of the applied voltage. Comparing the voltage distrihution between the full insulator model and the simplified insulator model, both with the conductor and the grounded supporting structure, they are still very similar to each other. The electric field strength distributions along the sheath surface of the insulator, with and without the conductor and the grounded supporting structure, are shown in Fig The maximum value of the electric field strength at the line end of the insulator with the presence of the 3m long conductor section is kvp/mm and at the ground end is kvp/mm at 1000 V energizing voltage. The maximum value of the electric field strength at the line end of the insulator without the conductor is kvp/mm and at the ground end is kvp/mm. It is obvious that the existence of the conductor at the line end and the grounded supporting structure reduces the electric field strength at the line end, but increases the electric field strength near the ground end I h à W) o.oif I g ^ <u W O 'C ^ w I" 1 \ 1 1 Insulator w ith the conductor and grounded supporting structure Insulator w ithout the conductor and grounded supporting structure Insulation distance (% Figure 3.9: Electric field strength magnitude along the insulation distance at the sheath surface of the insulator with and without the conductor and the grounded supporting structure. 51

76 The electric field strength magnitudes along the sheath surface for the full insulator and the simplified insulator, which is with the conductor and the grounded supporting structure, are also calculated for comparison. The results are shown in Fig. 3.10, which again shows the similarity between the two functions t «o 'B yw F u ll insulator w ith the conductor and grounded supporting structure -S im p lified insulator w ith conductor and grounded supporting structure Insulation distance (%) Figure 3.10: Electric field strength magnitude along the insulation distance at the sheath surface for the full insulator and the simplified insulator model with the conductor and grounded supporting structure. The conclusion is drawn that the simplified insulator model with only a small number of weather sheds, which is shown in Fig. 3.2 (d), can be used to calculate the electric field and voltage distribution along the full insulator in service with no significant influence on the accuracy. 52

77 3.3 Some basic features of water droplets on a non-ceramic insulator surface Hydrophobicity of non-ceramic insulators The excellent pollution performance of non-ceramic insulators is due to the good hydrophobic surface property of weather sheds under wet and contaminated conditions. During the service life of an insulator, the combined effects of electric and environmental stresses accelerate the aging of the non-ceramic insulators. Consequently, the hydrophobicity properties of non-ceramic weather sheds will be temporarily or permanently lost. Hydrophobicity describes the wettability of a surface. There are two methods that are usually used to describe the hydrophobicity of a non-ceramic insulator surface. One is called the single drop method and the other is called the hydrophobicity classification method. The classical method, which is usually used in laboratories to characterize the hydrophobicity of a surface, is the single drop method [42]. A single water drop is put on the surface that needs to be examined. A tangent line is drawn on the water drop s surface at the triple point of water/solid/air. The angle formed by this tangent line and the base line of the water drop is called static contact angle, 6. The contact angle 0 is shown in Fig. 3.11, which is used to characterize the hydrophobicity of a surface. Contact angles are measured in degrees. Low is below about 20 and high is 90 or above. Low angles mean wettable surface. The contact angle can be determined by using a goniometer or projecting the water drop onto an angle net. This technique is relatively simple and gives good indication of the surface hydrophobicity status. 53

78 //////////// Figure 3.11: Definition o f contact angle. The second method is called the hydrophobicity classification (FTC) method, which has been developed by the Swedish Transmission Research Institute (STRI). The HC method was introduced by Gubanski and Flartings in [43]. The only equipment needed is a common spray bottle. The spraying shall continue for seconds from a distance of cm. The wetting appearance of a surface sprayed with water is identified with one of seven classes, HCl to HC7. The criteria for the different classes are given in Table 3.1. HC Description 1 Only discrete droplets are formed. 0~8O or larger for the majority of droplets. 2 Only discrete droplets are formed. 50 < 0 < 80 for the majority of droplets. 3 Only discrete droplets are formed. 20 < 0 < 50 for the majority of droplets. Usually they are no longer circular. 4 Both discrete droplets and wetted traces from the water runnels are observed. Completely wetted areas < 2cm^. Together they cover < 90% of the test area. 5 Some completely wetted areas > 2cm^, which cover < 90% of the test area. 6 Wetted areas cover > 90%, i.e. small unwetted areas are still observed. 7 Continuous water film over the whole tested area. Table 3.1: Criteria for the hydrophobicity classification (TIC) [43]. 54

79 Each HC class corresponds to a characteristic wetting pattern, which is described by a reference picture shown in Fig Apart from the different contact angles, the size and shape of the water droplets are also different for different HC classes. i f f s-r... HC* 2 A :# # ÿ'-'-1 Figure 3.12: Typical examples of surfaces with HC from 1 to 6. HC7 represents the completely wet surface [43]. This method is very simple for the practical evaluation o f the hydrophobicity of insulators in service. Since many researchers have used this method to characterize the hydrophobicity of the insulator surface, the wet insulator models with water droplets on their surface in this research work will also be described using this method. 55

80 3.3.2 Water droplet corona and dynamic behavior on the surface of non-ceramic insulators Water droplets increase the electric field strength at the insulator surface because of their high permittivity. Surface corona discharges from water droplets accelerate the aging of the polymer material of the insulator shed and destroy the hydrophobicity locally, causing the water to spread and the adjacent water drops to coalesce. The loss of hydrophobicity leads to the formation of a wet region, introducing a partial short circuit along the surface of the insulator. This reduces the resistance that limits the current and provides a path for an arc [5]. The corona discharge phenomena from water droplets have received considerable attention and are investigated in recent publications. Phillips, Childs and Schneider [9, 44] studied the corona onset level for a water droplet on the sheath region and the shed region of a non-ceramic insulator by small scale experiments. Tbe surface electric field strength was calculated by the potential difference between the electrodes without any water droplets on the sheath region. This electric field strength is referred to as applied E-field. For the sheath region, a single water drop was put at the center of the sheath region of the insulator section. The electric field is increased at the interface between the water drop, air, and insulating material. For water drops with volumes of 10 to 100 il, the applied F-field values for corona onset were found between 0.56 and 0.44 kv/mm for SIR material with 88 contact angle. The applied F-field required for corona onset 56

81 decreased with increasing water drop size from 10 to 80 ll and remained the same between 80 to 100 al. For the shed region, a single water drop was put on the surface of a non-ceramic insulator shed. For water drops with volumes of 65 to 125 il, the measured average corona onset E-field remained between 0.86 and 0.96 kv/mm. Lopes, Jayaram and Chemey [45] studied the partial discharge from water droplets on a silicone rubber insulating surface. They found that the measured average corona onset applied electric field strength values were 5.2 kv,ms/cm and 4.2 kvrms/cm for a single water droplet with volume of 30 and 80 ll, respectively. Considering that the corona takes place when the local electric field strength around the water droplet reaches the critical ionization value in air 20.4 kvrms/cm for the existing ambient conditions, the average field enhancement factors were 3.9 to 4.8 for one droplet with the volume changing from 30 to 80 xl. Discharges between water droplets were carefully studied by Blackmore and Birtwhistle [46]. They found that discharges between water drop electrodes produced the localized loss of the hydrophobicity of tbe polymer material. Tbe combination of the high discharge temperature and the plasma chemistry of the water vapor and air are responsible for tbe loss of bydropbobicity. The rate of hydrophobicity loss was found to be dependent on water droplet conductivity and contact angle. At higher conductivity and lower contact angle, a longer time has been observed until the hydrophobicity of a polymer material was lost. 57

82 The behavior of water droplets on the surface of the hydrophobic insulating surface under low frequency ac electric field was also investigated by several researchers. Keim and Koenig [47, 48] studied the behavior of a single water droplet of different volumes under applied ac electric field stress. They found that the water droplets were oscillating with an up and down movement. Very active drops varied their contact angle up to a difference of 30 degrees. Krivda and Birtwhistle [49] observed that when a 40 il water drop was deposited on the surface under 0.68 kvrms/mm electric field strength, a significant deformation of water drop was viewed, which elongated and contracted in the direction of the electric field. The diameter of the water drop in the voltage peak positions changed from 6.4 mm in the positive half-cycle to 4.3 mm in the negative half-cycle. Yamada, Sugimoto and Higashiyama [50] experimentally studied the resonance phenomena of a single water droplet located on a hydrophobic sheet under ac electric field. Fig shows the time variation of the deformation of a 10 il water droplet located on a SIR sheet and a PGF (a kind of polymer material) sheet during a half cycle (between co(=0 and %) of the AC field. 1 Figure 3.13: Behavior of 10 pi water droplet located on a SIR and a PGF sheet [50]. 58

83 3.4 Flat SIR sheet with a water droplet The presence of water droplets changes the EFVD on the surface of a nonceramic insulator. Different distributions of water droplets on the surface of the nonceramic insulator lead to different electric field and voltage distributions. Before calculating the EFVD along the non-ceramic insulator model with water droplets, some simple cases should be studied as a preliminary step. Assuming a vertical suspension insulator, there are sessile water droplets on the weather sheds, clinging water droplets on the vertical surface of the polymer sheath of the insulator and pendant water droplets under the sheds as shown in Fig The surface of the insulator shed is close to parallel to the equipotential lines. The surface of the sheath is close to perpendicular to the equipotential lines. Sheath region Pendant d ronlet Shed region S essile dronlet C lin g in g droplet Figure 3.14: Three types of water droplets on a vertical suspension insulator. As the first step, two simple models have been set up to study the basic features of the electric field distribution around water droplets. In both models, a fiat hydrophobic silicone rubber sheet with one discrete water droplet between two electrodes is used to study the electric field enhancement in the vicinity of water droplets. One electrode is energized (e.g., 100 Volts), the other one is grounded. The software used assumes a 59

84 remote ground as well. It is equivalent to conducting an experiment in a high voltage laboratory with the floor, ceiling and walls grounded. In order to represent the sheath region, two electrodes are considered together with a single SIR sheet between them, which are shown in Fig In order to represent the shed region, the SiR sheet is positioned parallel between the two electrodes, which are shown in Fig The effects of the contact angle, size, shape and conductivity, of a water droplet on the electric field enhancement are to be studied using these two models Sheath region simulation In order to represent the sheath region of an insulator, two electrodes are assumed together with a single SiR sheet. The size of the SiR sheet is 10 cm x 10 cm and it is 0.5 cm thick. The relative permittivity of the SiR material used in the calculation is 4.3. The two electrodes are positioned at 10 cm distance from each other. The position of the SiR sheet is shown in Fig. 3.15; the SiR sheet is between the two electrodes as a spacer to simulate the sheath region. The energized electrode is on the left side and the grounded electrode is on the right side. The applied voltage is 100 V, which means the average electric field strength is 100/10=10 V/cm. The x, y, z directions are defined as shown in Fig V IT) d Z A T X 10 cm Figure 3.15: Experimental setup for the sheath region simulation. 60

85 A water droplet of hemispherical shape is assumed at the midway of the electrode spacing. The diameter of the water droplet is 4mm and its height is 2 mm. The relative permittivity of the water droplet is 80 and its conductivity is assumed to be zero. For the sheath region simulation, Fig shows the equipotential contours with a single water droplet at the center on the surface. The electric field distribution along the surface of the sheet is also calculated and shown in Fig The electric field strength is intensified at the interface between the water droplet, air, and insulating sheet to 32.9 V/cm. Z tcm t Î ^ LQ ~ O - O TO- -iri ^ _ CO 00 C3 C4 U) O If) Y (cm ) Figure 3.16: Equipotential contours and electric field lines for sheath region simulation. Em (V /cm ) Y (cm ) Figure 3.17: Electric field distribution along the SIR sheet surface for sheath region simulation. 61

86 The enlarged view of the equipotential contours and electric field lines around the water droplet positioned on a SiR sheet simulating the sheath region is shown in Fig Continuous lines represent the equipotential contours; dashed lines are used for the electric field lines. It can be seen from Fig that the presence of the water droplet causes a considerable distortion in the configuration of the equipotential contours and the electric field lines in the vicinity of the water droplet. For the sheath region simulation, the electric field strength is significantly increased at the interface of the water droplet, air, and the insulating sheet. Z (cm ) O.i AS--* : ^ Y (cm ) Figure 3.18: Equipotential contours and electric field lines around a water droplet on the sheath surface. The electric field strength vector changes its magnitude and direction along the surface of the water droplet. To follow its changes, several quantities can be monitored, for example, the x, y, or z components of the electric field strength vector, or the magnitude of the electric field strength vector. The x, y, z, components and the magnitude of the electric field strength on the surface of the water droplet on the sheath region are 6 2

87 shown in Fig (a), (b), (c), (d), respectively. Each point on the surface of the water droplet is described by its three coordinates (x, y, z). In fact, a fourth dimension would be needed to show the distribution of the magnitude of the electric field strength. In order to be able to show the electric field strength distribution on the surface of the water droplets using a 3D graph, the surface point is represented by its (x,y) coordinates only. In other words, all points on the surface of the water droplet are represented by their projection in the (x,y) plane. Then the z dimension can be used to show the magnitudes of the electric field strength vector or its components at any point on the surface of the water droplet. >. a 2 7 % 2 4 S 21 J n 1 8 Ü 6 'S 3 1.1,. i.i,' Y ( c m ) _o X (cm) Ü u n 1 Y ( c m ) " '' X(cm) (a) X com ponent (b) Y com ponent I > a s ^ 3 3 > 3 0 ^ a 1 8 VD ! s 'S o 0 ^ ^ 0. 3 Ü Y ( c m ) _ X ( c m ) 0. 3 (c) Z com ponent (d) T otal electric field strength Figure 3.19: Vector components and the magnitude of the electric field strength on the surface of the water droplet on the sheath surface. 63

88 For a water droplet in the sheath region, the maximum value of the electric field strength, at 100 V applied voltage, is 32.9 V/cm on the surface of the water droplet, at the interface of the water droplet, air and insulating material. The electric field enhancement factor is 3.29, which is defined as the ratio of the maximum electric field strength at the tip of the water droplet and the applied field strength under dry conditions without the water droplet. The y component of the electric field strength vector is the dominant component, as expected Shed region simulation In order to represent the shed region of an insulator, two electrodes are assumed together with a single SiR sheet. The two electrodes are positioned at 10 cm distance from each other. The SiR sheet is in a parallel position between the two electrodes for simulating the weather shed region as shown in Fig The upper electrode is energized and the lower electrode is grounded. The applied voltage is 100 V, which means the average electric field strength is 100/10=10 V/cm. The x, y, z directions are defined as shown in Fig V o Figure 3.20: Experimental setup for the shed region simulation. 64

89 A water droplet of hemispherical shape is assumed at the midway of the electrode spacing. The diameter of the water droplet is 4mm and its height is 2 mm. The relative permittivity of the water is 80 and its conductivity is assumed to be zero. For the shed region simulation, Fig shows the equipotential contours with a single water droplet at the center on the surface. The electric field distribution along the surface of the sheet is also calculated and shown in Fig The electric field strength has been enhanced at the top of the water droplet. The reason for the change of the magnitude of the electric field strength in Fig is a result of the measurement line passing through the water which has a relative permittivity of 80. Z (cm ) : - 41 % I T + IT? ? -/ir'o --- -AA 4 Î T3 4 5 Y (cm ) Figure 3.21: Equipotential contours and electric field lines for shed region simulation. Em (V /cm ) Y (cm ) Figure 3.22: Electric field distribution along the SiR sheet surface for shed region simulation. 65

90 The enlarged view of the equipotential contours and electric field lines around the water droplet positioned on a SiR sheet simulating the shed region is shown in Fig Continuous lines represent the equipotential contours; dashed lines are used for the electric field lines. It can be seen from Fig that the presence of the water droplet causes a considerable distortion in the configuration of the equipotential contours and the electric field lines in the vicinity of the water droplet. For the shed region simulation, the electric field strength is enhanced at the top of the water droplet. Z (cm ) '46.3' rc 0.7 I4 4 A 4 3 ' ^ I I I f- 0.3 ' ' M & ^7. J--', '-ry Y (cm ) Figure 3.23: Equipotential contours and electric field lines around a water droplet on the shed surface. The X, y, z, components and the magnitude of the electric field strength on the surface of the water droplet on the sheath region are shown in Fig (a), (b), (c), (d), respectively. Similarly to the sheath region simulation, all points on the surface of the water droplet are represented by their projection in the (x,y) plane. Then the z dimension can be used to show the magnitudes of the electric field strength vector or its components at any point on the surface of the water droplet. 66

91 .XVf:;.. Y (cm).n i X (cm ) Yk:m) X (cm) (a) X com ponent (b) Y com ponent g > II I Y (cm) -0.2 ' X (c m ) 0.2 s g ) ^ ^2 I : I %20.1 Y (cm ) i X (cm) 0.3 (c) Z com ponent (d) Total electric field strength Figure 3.24: Vector components and the magnitude of the electric field strength on the surface of the water droplet on the shed surface. For a water droplet in the shed region, the maximum value of the electric field strength, at 100 V applied voltage, is 27.6 V/cm on the top of the water droplet. The electric field enhancement factor is The z component of the electric field strength vector is the dominant component, as expected. 67

92 3.5 Effects of water droplet contact angle, size, shape, distance, and conductivity Effect of water droplet contact angle For a water droplet on the sheath region, the highest electric field strength is at the interface between the water droplet, air, and insulating sheet. It is of practical interest to know the electric field enhancement at various contact angles of the water droplet. For a water droplet on the shed region, the highest electric field is at the top of the water droplet, not the junction between the water droplet and insulating sheet. The effect of the contact angle is not significant. So only the water droplet on the sheath region is considered. Under different hydrophobicity stages of the SiR sheet surface, the contact angle of the water droplet varies. Four typical values of the contact angle are considered for comparison purposes, which are 120, 90, 60, and 30 degrees. To avoid the effect on the electric field enhancement due to varying the water droplet size, the contact area between the water droplet and the SiR sheet for these four cases is kept constant. The contact area in this study is defined as a circle with 4mm diameter. The relative permittivity of the water droplet is 80 and its conductivity is assumed to he zero. The enlarged views of the equipotential contours and electric field lines around the water droplet for these four cases are shown in Fig The water droplet is positioned on a SiR sheet simulating the sheath region. Continuous lines represent the equipotential contours; dashed lines are used for the electric field lines. It can he seen from Fig that the water droplet with larger contact angle causes more distortion in

93 I the configuration of the equipotential contours. The maximum values of the electric field strength on the surface of the water droplet with different contact angles are given in Table 3.2. The relationship between the electric field enhancement factor and the contact angle is shown in Fig ,9 0, , , , , , (a) 120 degrees (b) 90 degrees 0,8 0,7 0,6-0,5 0,4 - CD ^ _ T- CSJ 0, (c) 60 degrees (d) 30 degrees Figure 3.25: Equipotential contours and electric field lines around a water droplet on the sheath surface with different contact angles. 69

94 Contact angle, degrees Maximum electric field strength, V/cm 38A ^ 20.1 Table 3.2: The electric field enhancement factors on the surface of the water droplet with different contact angles. IO w C ontact angle o f w ater droplet (degrees) Figure 3.26: The electric field enhancement factor for a water droplet with different contact angles on the sheath region. The results show that the electric field enhancement factor increases as the contact angle increases. The relationship between them is almost linear. Although in reality, the shape of the water droplet on the vertical sheath region may not be spherical, the results can still be used to estimate the electric field enhancement for the water droplet with same advancing contact angle. The reason is described in detail in section Effect of water droplet size The effects of the electric field strength enhancement due to various water droplet sizes are also investigated. The shape of a typical water droplet is hemispherical. The 70

95 diameters of typical water droplets in this study are between 2 to 8 mm. It means that the volume of water droplet is between 2 to 134 il. The electric field enhancement factors are studied for a water droplet with different diameters on the sheath region and on the shed region. The results are shown in Figs and It is clear that the larger the water droplet, the higher the electric field enhancement. For the water droplet on the sheath region, the effect of the size of water droplet on the electric field enhancement is more significant than that on the shed region. ë 4.5 g S i g 3 (U C 2.5 <u W D iam eter o f w ater droplet (m m ) Figure 3.27: The electric field enhancement factor for a water droplet of different diameter on the sheath region. i.. % «Z6 o 2.5 W 1 D iam eter o f w ater droplet (m m ) Figure 3.28: The electric field enhancement factor for a water droplet of different diameter on the shed region. 71

96 3.5.3 Effect of water droplet shape Based on the laboratory observations and studies of several other researchers, the shape of a water droplet is not always hemispherical and it changes under different conditions. To study the shape effects of water droplets, two pictures of the different shapes of water droplets are shown in Fig (a) W ater droplets on the sheath region (b) W ater droplets on the shed region Figure 3.29: Water droplet shape on the sheath and the shed region. The larger the water droplet, the more chance exists that it may change its shape. Two typical shapes of water droplets are considered with the same base width of 8mm on the sheath region. The first water droplet shape shows the water droplet on the sheath region (pointed by an arrow in Fig (a)). The second water droplet shape represents the shape of two water droplets merged together on the shed region (pointed by an arrow in Fig (b)). 72

97 The calculation results are shown in Fig It should be rotated to the left by 90 to see the true position of the distorted water droplet on the vertical sheath. The maximum electric field strength for Case (a) is at the interface of the water droplet, air and insulating material. The electric field enhancement factor is 4.13 for Case (a). Considering that the electric field enhancement factor for the water droplet (8mm diameter) on the sheath with hemispherical shape is 4.41, the effects of the shape difference are not significant. The maximum electric field strength for Case (b) is at the top surface of the water droplet. The electric field enhancement factor is 2.55 for Case (b). Considering that the electric field enhancement factor for the water droplet (4mm diameter) on the sheath with hemispherical shape is 2.76, the effects of the shape difference are not significant. Y (cm ) Z (cm ) -4 6 ; Z (cm ) Y (cm ) (a) T ilted w ater droplet on the sheath (b) M erged w ater droplet on the shed Figure 3.30: Equipotential contours around a water droplet with different shapes on the sheath and shed region. 73

98 3.5.4 Effect of the distance between adjacent water droplets For the water droplets on the sheath region, the effect of the electric field enhancement due to multiple water droplets is also studied with a pair of 8mm diameter, hemispherical shape water droplets. The distance between them has been varies from 2mm to 8 mm. Fig shows the electric field enhancement factor vs. the distance between the two water droplets. ^ I 1) w D istan ce b etw een w ater droplets (m m ) Figure 3.31: Effect of the distance between water droplets on the electric field enhancement for sheath region simulation. It can be seen that the closer the water droplets, the higher the electric field enhancement. When the distance between the two water droplets is 8mm, the electric field enhancement factor is about 4.6, which is very close to the electric field enhancement factor for a single water droplet, 4.4. Therefore, the influence of the other water droplet can be ignored if the distance between the two water droplets is larger than the diameter of the water droplet. 74

99 3.5.5 Effect of water droplet conductivity The conductivity of water droplets also influences the electric field enhancement. If the relative permittivity and the conductivity of the water droplet are both considered, the electric field enhancement factor on the surface of the are modified. A water droplet with hemispherical shape and 4 mm diameter is used to illustrate the effects of the water droplet conductivity. The relative permittivity remains 80. One typical value of the conductivity are considered for comparison purposes, which is 250 is/cm. The electric field enhancement factor changes from 3.29 to 3.55 for the water droplet on the sheath region and from 2.76 to 3.17 for the water droplet on the shed region. Increasing the conductivity from 250 xs/cm to 2500 jas/cm, there is no change on the electric field enhancement factor. 3.6 Summary In this chapter, the first three objectives of the dissertation research have been addressed. The first objective was to find possible simplifications of an insulator model without significantly compromising the accuracy of the calculation results. The simplified insulator model with only a small number of weather shed at each end is proved to be an accurate model to calculate the electric field and voltage distribution along the full insulator in service. 75

100 The second objective, the effects of conductor and ground supporting structure have also been analyzed. The conductor section at the line end reduces the electric field strength at the line end, but increases the electric field near the ground end. The third objective was to study the basic electric field enhancement feature of the water droplet on the sheath and on the shed region. For a water droplet on the sheath region, the maximum electric field strength on the surface of the water droplet is at the junction point of the water droplet, air and insulating material. The larger the contact angle and the size of the water droplet, the higher the electric field enhancement. The closer the water droplets, the higher the electric field enhancement. For a water droplet on the shed region, the maximum electric field strength is on the top of the water droplet. The larger the size, the higher the electric field enhancement. The shape and conductivity of the water droplet have some effects on the electric field enhancement for a water droplet on sheath or shed region. The influence is not significant. 76

101 CHAPTER 4 ELECTRIC FIELD AND VOLTAGE DISTRIBUTION ALONG NON-CERAMIC INSULATORS UNDER DRY AND CLEAN CONDITIONS 4.1 Introduction High electric field strength may cause corona around non-ceramic insulators, which may result in corona cutting, deterioration and aging of polymer materials of nonceramic insulators. Therefore, control of the electric field strength around non-ceramic insulators is an important aspect for the design of non-ceramic insulators and their associate grading devices. Several studies recommend that the maximum electric field strength should not exceed 2.28 kv/mm at any point on the surface of a non-ceramic insulator in order to prevent dry corona on the insulator surface. Also the typical electric field strength threshold value for water droplet triggered corona are in the range of kvrins/mm [51]. This value is the electric field strength on the surface of the insulator under dry condition without any water droplets. Understanding the electric field strength distribution in the vicinity of a nonceramic insulator is very important for the design and development of non-ceramic insulators. One of the most important details o f non-ceramic insulator design is the design o f the triple junction point: sheath, air and metal end fittings [40]. The electric field 77

102 strength near this junction should be limited to a value less than the corona onset electric field strength. When non-ceramic insulators are installed on a power line, the tower geometry, live-end hardware and conductors in the vicinity of the insulators will have some effects on the electric field distribution around the insulators. Depending on the voltage level, the magnitude of the electric field strength on the surface of the insulator may exceed the corona onset values. Grading rings should be used to redistribute the electric field distribution and reduce the maximum value of the electric field strength. Consequently, to consider all these effects, a three-dimensional calculation model must be set up in the Coulomb software in order to evaluate the EFVD near and along a non-ceramic insulator. In the United States, 765 kv non-ceramic insulators are in the design and development stage. The utility companies are now considering using 765 kv non-ceramic insulators to replace ceramic insulators without changing the tower configuration and line-end hardware and using six-subconductor bundles to replace four-subconductor bundles. This chapter describes the research related to the EFVD along the 765 kv nonceramic insulators when they are installed on a 765 kv tower under three phase energization. The effects of the tower configuration and other components to the EFVD are also analyzed. There are two typical of 765 kv tower configurations. One is considered for foursubconductor bundles and the other is considered for six-subconductor bundles. The simplified geometry and major dimensions of the two 765 kv power line towers and conductor bundles are identified in Sections and

103 Since the center phase insulator is inside the tower window and that is the worst case, the EFVD along the center phase non-ceramic insulator is of most interest. Therefore, for the center phase, the non-ceramic insulators, conductor bundles, line and ground end hardware, and corona rings are included in the calculation model. For the other two (i.e., outer) phases, only the conductor bundles are simulated and the other components are ignored. The basic geometry of the 765 kv non-ceramic insulator, grading rings, line and ground end hardware, ground plane and tower configuration are described in detail separately in the following sections. 4.2 Model of insulator, tower and additional components Modeling of a non-ceramic insulator and corona rings It is of practical interest to know the electric field strength distribution for a fullscale insulator during field conditions under three phase energization. A typical 765 kv non-ceramic insulator is used for this study, which is designed for both foursubconductor and six-subconductor bundles. The insulators are fitted with corona rings at both line and ground ends. The detailed geometric dimensions of the 765 kv insulator are shown in Fig The insulator is made of silicon rubber with a relative permittivity of 4.0 and an FRP rod with a relative permittivity of 5.5. There are 51 large and 52 small weather sheds on an actual 765 kv insulator. The insulator is equipped with metal fittings at both line and ground ends. 79

104 Based on the previous study in Chapter 3, the calculation model for this full scale insulator can be simplified with only a small number of weather sheds (for example, 10) at each end of the insulator to calculate the electric field and voltage distribution. The simplified insulator model is shown in Fig <N 1 ^ 1 ' Units: cm ' y v j ç i i v i j r ^9 T ^ 17 < 436 > 470 Figure 4.1: Simplified geometry and dimensions of the 765 kv non-ceramic insulator model with 10 weather sheds at the line end and ground end. In order to reduce the electric field strength in the triple junction region of the insulator, a 17-inch corona ring is applied at the line end of the insulator and a 12-inch corona ring is applied at the ground end. The dimensions and positions of the two corona rings are shown in Fig Units: cm (a) Line end corona ring (b) Ground end corona ring Figure 4.2: Dimensions and positions of the line end and ground end corona rings. 80

105 The insulator model has elements applied to the surface of boundaries and the interfaces of the different media. For the line end corona ring, the number of the elements used is For the ground end corona ring, the number of elements used is 832. The element configurations on the surface of the insulator and the corona ring at the line end and the ground end are shown in Fig I (a) Element configuration at the line end (b) Element configuration at the ground end Figure 4.3: Element configuration on the insulator and the corona ring surface Modeling of line end hardware and conductors When the insulator is installed on a 765 kv tower, yoke plates are needed to attach the subconductor bundle to the insulators. Two types of yoke plates are used in practice for four-subconductor and six-subconductor bundles. The dimensions and element configuration of a four-subconductor bundle V- string yoke plate are shown in Fig The thickness of the yoke plate for foursubconductor bundles is 1.9 cm. The bundle conductors have been modeled as smooth conductors, positioned parallel to the ground. As mentioned in [19], the length of the conductor bundles modeled should at least 8 times the insulator length for accurate results. The length o f each 81

106 conductor considered here is 60m. The subeonduetor diameter for four-suhconductor bundles is 2.96 cm. The number of the elements used for each subeonduetor is 560. m s (a) Dimensions (cm) (b) Element configuration Figure 4.4: Dimensions and element configuration of the yoke plate for foursubeonduetor bundles. The dimensions and element configuration of the six-subeonduetor V-string yoke plate is shown in Fig The thickness of the yoke plate is 2.54 cm. The suheonduetor diameter for the six-subeonduetor bundle is 2.7 cm. <N m m m (a) Dimensions (cm) (b) Element configuration Figure 4.5: Dimensions and element configuration of the yoke plate for six-subeonduetor bundles. 82

107 4.2.3 Modeling of tower and ground plane The simplified geometry and major dimensions of a typical 765 kv power line tower with four-subconductor bundles are shown in Fig The angle between the center phase insulator and the symmetry line of the tower is 50, as marked on Fig Units: cm sen m <N Figure 4.6: Geometry and dimensions of 765 kv power line tower with foursubconductor bundles. The two ground wires are ignored in the calculations. The ground plane is modeled with a 50 m x 50 m large plane with zero potential. The number of the elements used for the tower is 800 and for the ground plane are 100. The simplified geometry and major dimensions of a typical 765 kv power line tower with six-subconductor bundles are shown in Fig The angle between the center phase insulator and the symmetry line of the tower is also 50, as marked on Fig

108 The two ground wires are also ignored in the calculations. The ground plane is modeled with a 50 m x 50 m large plane with zero potential. The number of the elements used for the tower is 600 and for the ground plane, it is 225. Units: cm 1408 Figure 4.7: Geometry and dimensions of a 765 kv power line tower with sixsubconductor bundles. The view of the entire 765 kv power line tower with four-subconductor bundles, the non-ceramic insulator, end fittings, and hardware is shown three-dimensionally in Fig The entire view for the 765 kv power line tower with six-subconductor bundles is shown in Fig The center phase inside the tower window is enlarged for a clearer view; see Figs. 4.8 (b) and 4.9 (b). 84

109 (a) View of the entire tower with four-subconductor bundles. (b) View of the insulators o f the center phase with four-subconductor bundles. Figure 4.8: Entire view o f a 765 kv power line tower with four-subconductor bundles. 85

110 (a) View of the entire tower with six-subconductor bundles. (b) View of the insulators of the center phase with six-subconductor bundles. Figure 4.9: Entire view o f a 765 kv power line tower with six-subconductor bundles. 86

111 4.3 Voltage and electric field distributions along a nonceramic insulator The electric field and voltage distributions along the 765 kv non-ceramic insulator of the center phase have been studied on two typical power line towers with four and six-subconductor bundles. The instantaneous voltages applied to the three phase conductor system for the worst case when there is maximum voltage across the center phase insulator are: Vicft~ - 0.5x Vccntcr " 0.5* kv, Vccntcr^ 765 X V2 / =624.6 kv (i.e., maximum value of the line-to-ground voltage) Vright= - 0.5x Vcenter= 0.5*624.6= kv. There are some basic principles for showing the calculation results: In the following paragraphs, the voltages are expressed either in kvmax or in per cent values, referred to kvmax, which is the actual applied voltage on the center phase insulator. The electric field strength is always expressed in kvmax/mm units. The insulation distances used in the figures are expressed either in cm units or in per cent values, referred to 436 cm as shown in Fig The calculation path on the surface o f the insulator sheath is identified as a straight dashed line as shown in Fig (not along the leakage path). 87

112 Figure 4.10: Calculation path along the sheath surface of the insulator. The resulting per cent equipotential contours inside the tower window for a 765 kv non-ceramic insulator with four-subconductor bundles are shown in Fig Distance units: cm : i W (a) Full view of one of the insulator (Simplified model) (b) Enlarged area around the line end Figure 4.11: Per cent equipotential contours for a 765 kv tower with four-subconductor bundles under three phase energization.

113 It can be seen that the line end equipotential contours are greatly influenced by the line-end hardware and the line-end corona ring and are nearly parallel to the shed surface. The ten weather sheds near the line end sustain about 35% of the applied voltage. The ten weather sheds near the ground end sustain about 12% of the applied voltage. Fig shows the actual voltage distribution in the worst case along the per cent insulation distance at the surface of the insulator sheath with four-subconductor bundles. The non-linear property of the voltage distribution along the non-ceramic insulator is clearly shown I 0 1 o > Insulation distance (%) Figure 4.12: Voltage distribution along the per cent insulation distance at the surface of the insulator sheath with four-subconductor bundles. The electric field strength magnitude along the path defined on the surface of the insulator sheath is shown in Fig The maximum value of the electric field strength at the triple junction point is kvmax/mm. For a clearer view, the electric field strength distribution along the insulation distance near the line-end fitting is shown in Fig The discontinuities in the 89

114 magnitude of the electric field strength in Fig and 4.14 are the result of the calculation path, shown in Fig. 4.10, passing through the shed material, which has a relative permittivity of 4.0. It can be seen that electric field strength is much higher at the junction region between the sheath and the shed than that at the middle part of the sheath region. I > 1.2 -a f g 0.4 « Insulation distance (%) Figure 4.13: Electric field strength magnitude along the per cent insulation distance at the surface of the insulator sheath with four-subconductor bundles. a 1.4 > I I Insulation distance (%) Figure 4.14: Electric field strength magnitude along the per cent insulation distance at the surface of the insulator sheath with four- sub conductor bundles near the line end. 90

115 The electric field strength distribution along the insulation distance near the ground end fitting is also show n in Fig I è "O CD S!.a % ? 0.1 üj Insulation distance (%) Figure 4.15: Electric field strength magnitude along the per cent insulation distance at the surface of the insulator sheath with four sub-conductor bundles near the ground end. It is also of practical interest to know the electric field strength along the leakage path on the surface of the insulator, which is the path along a-b-c-d-e-f-g-h-i in Fig Figure 4.16: Leakage path at the surface of the insulator (a-b-c-d-e-f-g-h-i). 91

116 ' I i The electric field strength distribution along the leakage path on the surface o f the insulator near the line-end fitting is show n in Fig I > I I r, a J ^ 1 ii' I Leakage distance from the line end fittings (cm) 1 1 ; ' / " h Figure 4.17: Electric field strength magnitude along the leakage path at the surface of the insulator. The result shows that the electric field strength on the sheath region is higher than that on the shed region, especially at the junction region between the sheath and the shed. The electric field strength on the top of the shed is very close to the electric field strength on the down side of the shed. The maximum electric field strength on the shed surface is close to the very edge of the shed. It is interesting that the electric field strength near the shed edge (point d, g) suddenly drops. The equipotential lines are close to parallel to the surface of the weather shed. The rounded shed edge presses out the equipotential lines to the side of the shed edge. The electric field strength is only enhanced at the up and down side of the shed edge, but it is much lower at the center of the shed edge. There is a more detailed explanation in Appendix B. 92

117 The resulting per cent equipotential contours inside the tower window for a 765 kv non-ceramic insulator with six-subconductor bundles are shown in Fig b/S Distance units: cm k ". 4b '\^o \ \ \ ' fw / ; % : / i : U i / / &0 1Û (a) Full view of one of the insulators (Simplified model) (b) Enlarged area around the line end Figure 4.18: Per cent equipotential contours for a 765 kv tower with six-subconductor bundles under three phase energization. It can be seen that the ten weather sheds near the line end sustain about 33% of the applied voltage and the ten weather sheds near the ground end sustain about 14% of the applied voltage. Due to the larger size of the six-subconductor bundles, the density of the equipotential lines at the line end is less than that of the four-subconductor bundles. The larger the line end hardware size, the better shielding effect it has to the insulator. Fig shows the actual voltage distribution in the worst case along the per cent insulation distance at the surface o f the insulator sheath with six-subconductor bundles. 93

118 > (11 tj) o > Insulation distance (%) Figure 4.19: Voltage distribution along the per cent insulation distance at the surface of the insulator sheath with six-subconductor bundles. The electric field strength magnitude along the paths defined on the surface of the insulator sheath is shown in Figure The maximum value of the electric field strength at the triple junction point is kvmax/mm.? CD 3 1- I0.8 - # 0 6 V I.a 0.2 QJ S Insulation distance (%) Figure 4.20: Electric field strength magnitude along the per cent insulation distance at the surface of the insulator sheath with six-subconductor bundles. 94

119 For a clearer v iew, the electric field strength distrihutions along the insulation distance near the line and ground end fittings are show n in Figs and s I 0.6 % «o W Insulation distance (%) Figure 4.21: Electric field strength magnitude along the per cent insulation distance at the surface of the insulator sheath with six-subconductor bundles near the line end. I a CD "O S I t? w Insulation distance (%) Figure 4.22: Electric field strength magnitude along the per cent insulation distance at the surface of the insulator sheath with six-suhconductor bundles near the ground end. 95

120 4.4 Comparisons between four and six subconductor bundles In Section 4.3, the EFVD along the same non-ceramic insulators installed on two typical 765 kv towers with four or six subconductor bundle are calculated. It is interesting to compare the EFVD along the insulators for these two cases. To make the analysis easier, the 765 kv tower with four- sub conductor bundles is named as Case F and with six-subconductor bundles as Case S. The actual voltage distributions in the worst case along the per cent insulation distance at the surface of the insulator sheaths for these two cases are shown together in Fig C ase F C ase S I (D I > Insulation distance (%) Figure 4.23: Voltage distribution along the per cent insulation distance at the surface of the insulator sheath for Cases F and S. It can be seen that the voltage distribution along the insulator for Case S is more uniform than that of Case F. Since it is closer to a straight line, the voltage sustained by 10 line-end sheds is 35% for Case F and is 33% for Case S. The voltage sustained by 10 ground-end sheds is 12% for Case F and 14% for Case S. 96

121 The electric field strength magnitudes near the line and ground ends along the paths defined on the surface of the insulator sheaths for these two cases are shown in Figs and 4.25, respectively. 1.6 ^ 1.4 ^ 1^ "O C ase F C ase S I a 0.8 ' 1 1 q &6 u j! «0.2 o 1 Üj Insulation distance (%) Figure 4.24: Electric field strength magnitude along the per cent insulation distance at the surface of the insulator sheath near the line end for Cases F and S. > C ase F C ase S o 100 Insulation distance Figure 4.25: Electric field strength magnitude along the per cent insulation distance at the surface of the insulator sheath near the ground end for Cases F and S. 97

122 It is shown clearly that the electric field strength on the sheath surface of the insulator for Case S is lower than that of Case F at the line end and higher than that of Case F at the ground end. The maximum electric field strength at the triple junction point at the line end is kvmax/mm for Case F and kvmax/mm for Case S. The reason for that is the much larger bundle diameter and line end hardware size for Case S. It has better shielding effects on the line end fittings. The maximum electric field strength at the triple junction point at the ground-end is kvrnax/mm for Case F and kvmax/mm for Case S. It can be seen that the electric field distribution along the insulator for Case S is more uniform than that of Case F. 4.5 Effects of the tower configuration and other components When evaluating the EFVD along a non-ceramic insulator in service, it is not just the non-ceramic insulator alone that is of concern. The tower, line- and ground-end fittings, corona rings and the three phase conductor bundles are also part of tbe geometry. They should also be included in the calculation model. Therefore, the calculation model is very complex and it is very time-consuming to solve it. It is of practical interest to know the effects of these components and whether some of the components can be omitted without a significant impact on the accuracy of the estimates of the EFVD along the non-ceramic insulators. The 765 kv tower with four-subconductor bundles is selected for this study as an example. 98

123 4.5.1 Effects of other two phases of the three phase system Due to the large phase spacing and the grounded tower structure, the inclusion of the other two phase conductors in the calculation model should not significantly effect the EFVD along the center phase insulator. The effects of the other two phases of the three phase system have been investigated for the 765 kv tower with four-subconductor bundles. The center phase conductor is inside the tower window. In order to evaluate the effects of the three phase energization, two cases have been considered. In the first case, only the center phase conductor bundles inside the tower window are included in the calculation model. The instantaneous applied voltage is kv, which is the maximum value of the line-to-ground voltage. In the second case, the other two phase conductor bundles are also included in the calculation model and the instantaneous voltages applied to the three phase conductor system are: Vkft^ kv, Vccntcr^624.6 kv,vrighr kv. The resulting equipotential contours for a 765 kv tower with four-subconductor bundles are shown in Fig It can be seen from Fig that there are slight differences between Cases (a) and (b). For example, the 10 per cent equipotential line is closer to the ground end of the insulator for single phase energization than the three phase energization. The equipotential contours between 95% and 80%, i.e., close to the conductor bundles, are very similar for Case (a) and Case (b). 99

124 Distance units: cm 3300 I , : X ' %» l ' «%, 4 I,,, 85 ' : ' i\ \ (a) Single phase (b) Three phase Figure 4.26: Equipotential contours for a 765 tower with four-subconductor bundles under (a) single phase and (b) three phase energization. The actual voltage distribution in the worst case along the percent insulation distance at the surface of the insulator sheath with four-subconductor bundles for single phase and three phase energization are shown in Fig

125 700 ^ Three phase energization 1 Sin gle phase energization 500 u ^ 400 o > Insulation distance (%) Figure 4.27: Voltage distribution along the per cent insulation distance at the surface of the insulator sheath under single and three phase energization. It can be seen that the voltage distribution at the ground end and the middle part of the insulator is changed by the presence of the other two phases. The voltage distribution at the line end does not change as much as at the middle part of the insulator. The reason is that the line end of the insulator is of course much closer to its conductors, the hardware, and the corona ring there than to the other two phases. The largest difference between the two curves is about 2% of the applied voltage. The electric field strength distributions along the surface of the insulator sheath near the line and ground end fittings are shown in Fig and 4.29, respectively. 101

126 1 g > QJ "O i a % o 0.2 üj 0 Three phase energization Sin gle phase energization Insulation distance (% Figure 4.28: Electric field strength magnitude along the per cent insulation distance at the surface of the insulator sheath near the line end under single and three phase energization. I a CD "O S! I T hree p h ase energization S in gle phase energization ? w Insulation distance (%) Figure 4.29: Electric field strength magnitude along the per cent insulation distance at the surface of the insulator sheath near the ground end under single and three phase energization. 102

127 The maximum electric field strength at the triple junction point is kvinax/mm under single phase energization and kvmax/mm for three phase energization. The effects of the presence of the other two phases of the three phase system on the voltage distribution is very small and can be ignored. The effects of the presence of the other two phases of the three phase system on the electric field is that the electric field strength under three phase energization near the line end is higher than that of single phase energization and is lower near the ground end. The conclusion can be drawn that for a 765 kv tower with four-subconductor bundles, there is no significant difference between the EFVD along a non-ceramic insulator under single phase energization and under three phase energization Effects of tower configuration The effects of the 765 kv tower configuration with four-subconductor bundles have also been studied. In order to evaluate the effects of the tower configuration, two cases have been considered. In the first case, the 765 kv tower is removed from the calculation model shown in Fig The second case is the same calculation model shown in Fig The resulting equipotential contours for the four-subconductor bundles without and with a 765 kv tower under three phase energization are shown in Fig The figure shows that the existence of the 765 tower at zero potential has only a minor effect on the voltage distribution near the line end. Flowever, naturally it influences the voltage 103

128 distribution near the ground end significantly. T he grounded tow er h o d y reduces the electric field strength near the ground end o f the insulator. Distance units: cm h #. : % %..._ " 2 5 '' \ % : : Tr : / V : ^ \ : ! / ' I - V, / : : (a) W ithout tow er (b) W ith tow er Figure 4.30: Equipotential contours for the four-subconductor bundles without and with the 765 kv tower under three phase energization. The results show that the tower hody is an important part of the calculation model. The tower hody cannot be ignored and it has significant influence on the EFVD along the insulator near the ground end. 104

129 4.5.3 Effects of conductor bundles The effects of the four-subconductor bundles to the EFVD along the non-ceramic insulator have also been studied. In order to evaluate the effects of the four-subconductor bundles, two cases have been considered. In the first case, the four-subconductor bundles attached to the line-end hardware are removed from the calculation model shown in Fig The line end hardware and the metal end fitting are energized to kvmax- The second case is the same calculation model as shown in Fig The equipotential contours for the 765 kv tower without and with foursubconductor bundles are shown in Fig Distance units: cm I I I. I % : , '^ t (a) W ithout four-subconductor bu ndles (b) W ith four-subconductor bundles Figure 4.31: Equipotential contours for the 765 kv tower without and with the foursubconductor bundles. 105

130 It can be seen from Fig.4.31 that there are shielding effects of foursubconduetor bundles. If the four-subconduetor bundles are ignored in the calculation model, the EFVD along the insulator is significantly different from the EFVD along the insulator with four-subeonduetor bundles, which means that this is not an acceptable model. 4.6 Summary In this chapter, the voltage and electric field distribution along the non-ceramic insulators have been calculated for two practical cases. One is with four-subconductor bundles and the other one is with six-subconductor bundles. The maximum values of the electric field strength at the triple junction point have been calculated for these two cases. For four-subconductor bundles, the maximum value is kvmax/mm. For sixsubconductor bundles, the maximum value is kvmax/mm. There is only a slight difference between the EFVD along a non-ceramic insulator under single phase energization and under three phase energization. The conductor bundles and the tower body should be included in the calculation model in order to get the accurate results. 106

131 CHAPTER 5 ELECTRIC EIELD STRENGTH AND VOLTAGE DISTRIBUTIONS ALONG A NON-CERAMIC INSULATOR UNDER VARIOUS WET CONDITIONS 5.1 Introduction The excellent pollution performance of non-ceramic insulators is due to the good hydrophobic surface property of weather sheds under wet and contaminated conditions. However, the combined effects of electric and environmental stresses, such as the energizing voltage, corona and arcing, also contamination, ultraviolet rays, heat cycling, etc., can cause the accelerated aging of non-ceramic insulators during the service life of an insulator. Consequently, due to the weak bonds of polymer materials, the hydrophohicity properties of the weather sheds will temporarily or permanently lost during its service life. That might worsen the wet and contamination performance of nonceramic insulators. Under rain and fog conditions, the presence of water droplets intensifies the electric field strength on the surface of a non-ceramic insulator. If the magnitude of the surface electric field strength exceeds a threshold value, kvnns/mm [51], water droplet corona discharges may occur. The discharges usually occur between water 107

132 droplets and destroy the hydrophohicity of the polymer material surface. The high temperature of such discharges also thermally degrades the insulator surface. As a consequence, the surface corona discharges from water droplets accelerate the aging of the polymer material, cause surface damage due to tracking and erosion, and increase the risk of the flashover of the non-ceramic insulator. The pollution flashover phenomena of non-ceramic insulators have heen studied and described by various researchers [52]. The flashover of a clean non-ceramic insulator during rain conditions shows that a discharge bridges the weather sheds and the leakage distance along the surface of the insulators is not used efficiently. The flashover of nonceramic insulators with artificial contamination in clean fog tests shows that the discharges on a fully contaminated insulator follow the leakage path along the surface of the insulator. For partially contaminated insulators, the discharges in the contaminated section follow the leakage path along the surface of the insulator in the contaminated part. However, an arc may also develop and it may bridge the weather sheds along the clean section of the insulator, which is a high resistance region. Therefore, the study of the electric field strength and voltage distribution along non-ceramic insulators is important for the in-depth understanding of the aging process and the pollution flashover initiation mechanism for non-ceramic insulators. 5.2 Hydrophobicity status of non-ceramic insulators As mentioned in Section 3.3.1, many researchers have used the hydrophohicity classification method developed by STRl to characterize the hydrophohicity o f the 108

133 insulator surface. T his m ethod is also adopted in this research w ork to describe the hydrophohicity o f the surface o f non-ceram ic insulators. Research studies show that the pollution performance of non-ceramic insulators is jointly determined hy the surface hydrophohicity status and pollution severity [6]. When non-ceramic insulators are operating in heavy or medium pollution environment for a long time, the change of hydrophobicity and the build-up of a pollution layer directly affect the pollution performance of non-ceramic insulators. To evaluate the performance of non-ceramic insulators in the field, the information of the surface hydrophobicity status need to be investigated. Wang, Liang, and Guan [53] conducted a system investigation aiming at the inspection and evaluation on the hydrophohicity distribution along the surface of nonceramic insulators. They found that in general, the hydrophobicity distribution on the upper surface of the weather sheds always presented hydrophobicity better than that of the lower surface. In many cases, the top surface showed a hydrophohicity of HC 2-4, while the bottom surface hydrophohicity approached HC 5-6. Due to the high electric field strength around the line end fittings, the weather sheds near the line end are always less hydrophobic. The surface of the sheath, especially at the triple junction areas, is also vulnerable to hydrophobicity loss. Obviously, the electric field plays an essential role on the initiation of hydrophobicity loss. Seifert and Besold [54] reported their service experience o f the SiR insulators under tropical climate conditions in Malaysia. The hydrophohicity of the insulators was checked after 2 and 7 years of service by the HC method. They also found that the top sides o f the weather shed showed better hydrophobicity than the other parts of the 109

134 insulator. Four or fiv e sheds near the line end insulator sh ow ed less hydrophobicity due to more pollution in that region. Their investigation results are show n in Table 5.1: Suspension insulator Tension insulator 2 years 7 years 2 years 7 years Shed top side Shed bottom side Sheath region Table 5.1: Hydrophobicity status (HC numbers) of the insulator after 2 and 7years of service [54]. 5.3 Experiments in the OSU fog chamber One of the objectives of this research is to study the EFVD along non-ceramic insulators under various wet conditions and to study the electric field enhancement factors on the surface of water droplets. Appropriate experiments should be done in order to decide the size, shape and number of droplets and their distribution at the various hydrophobicity conditions of non-ceramic insulators. A series of aging experiments on non-ceramic insulators was performed in the fog chamber at The Ohio State University High Voltage Laboratory. The fog chamber was constructed in Fig. 5.1 shows the view of the fog chamber. The fog chamber is transparent and is made of polycarbonate sheets. The dimensions of the chamber are 1.72m wide x 2.44m long x 1.83m high. The volume of the chamber is 9.5m^. The high voltage bushing is mounted on one of the end walls of the 110

135 chamber. A detachable access door is located at the side across from the bushing. Four nozzles are used to generate the fog inside the chamber. Both a water pump and an air compressor are used to apply water and pressurized air simultaneously to the nozzles. A drainage system collects the water and returns it to a container for recycling purpose hy a pump.? 11#'^: - v n -I Figure 5.1: The fog chamber in the OSU High Voltage Laboratory. Two types of non-ceramic insulators were used for the experiments. One type was made of SiR and the other one was made of EPDM. The insulators under the aging tests were suspended vertically inside the chamber with their ground ends upwards. The insulators were subjected to a continuous electric stress and simultaneous but intermittent salt fog using a 6-hour fog on, 6-hour fog off duty cycle. No artificial solid or liquid contaminants were used. The aging test lasted for about one week. Different hydrophobicity status conditions of the polymer surface of the insulator were observed. In order to avoid drying effects, the typical hydrophohicity status o f the insulator surface 111

136 was recorded using a Canon digital camera at the beginning of the fog off period. The calculation models of the insulator under wet conditions are based on these photos. 5.4 Model setup A short insulator with only four sheds is considered for the following calculations in order to reduce calculation time. The simplified geometry and dimensions of the polymer insulator to be modeled are shown in Fig The sheds are numbered 1-4 from the line end to the ground end. The weather sheds are made of silicon rubber with a relative permittivity of 4.3. The relative permittivity of the fiberglass rod is 7.2. The conductivity of the water droplets is assumed to he 250 ps/cm. The number of the elements used for each case is about 12,000. The applied voltage on the line end of the insulator is assumed to be IkVn. G round end U nits: cm 00 Y 1< 9.4 X Line end Figure 5.2: Geometry and dimensions of a four-shed non-ceramic insulator. Three types o f models are used for simulating specific weather conditions. The first one is the base case, which is a dry and clean insulator model. 112

137 The second one is the insulator model under rain conditions. Due to the shielding effects of the weather shed, one assumption is made that there are only water droplets on the top of each weather sheds. The surface of the vertical sheath and the undersides of the sheds remain dry. The third one is the insulator model under fog conditions. There are water droplets not only on the top of each weather sheds but also on the downside of each shed. Some models may also have water droplets on each sheath region of the insulator as well. 5.5 Insulator models under rain conditions Under rain conditions, the water droplets are usually on the top surface of the weather sheds. The surface of the vertical sheath and the undersides of the weather sheds are dry. Six typical cases of non-ceramic insulators under rain conditions with the surface hydrophobicity from HCl to HC6 are studied. They are named as Case RHCl - Case RHC6. For Case RHCl, only a 10 degree segment of the shed surfaces is modeled. This segment is used 36 times to represent the entire circumference of a shed. There are five medium size water droplets and 10 small size water droplets per segment. The shape of all water droplets is hemispherical, with a diameter of 2mm for medium size water droplets and 1mm for small size water droplets. For Case RHC2, only a 10 degree segment of the shed surfaces is modeled. This segment is used 36 times to represent the entire circumference of a shed. There are four 113

138 large size water droplets and one medium size water droplets per segment. The shape of all water droplets is hemispherical, with a diameter of 4mm for large size water droplets and 3mm for medium size water droplets. For Case RHC3, only a 90 degree segment of the shed surfaces is modeled. This segment is used 4 times to represent the entire circumference of a shed. The shape of some water droplets is no longer hemispherical, which have a length of 6mm. For Case RFIC4, only a 36 degree segment of the shed surfaces is modeled. This segment is used 10 times to represent the entire circumference of a shed. There is a water runnel on the surface of the insulator. For Case RHC5, only a 90 degree segment of the shed surfaces is modeled. This segment is used 4 times to represent the entire circumference of a shed. Several water runnels are merged together on the surface o f the insulator. For Case RHC6, only a 90 degree segment of the shed surfaces is modeled. This segment is used 4 times to represent the entire circumference of a shed. Ahout 90% of the surface of the insulator are covered by water film. For the calculations illustrated by Figs. 5.4, 5.6, 5.8, 5.10, 5.12, 5.14 (a) and (b), each point on the surface of the shed is described by the (x, y, z) coordinates of its location. In fact, a fourth dimension is needed to show the voltage distribution. In order to he ahle to show the voltage distribution on the surface of the shed using a 3D-type view, the surface point is represented by its (x, y) coordinates only. The voltage distribution for each case with water droplets on the surface of the shed closest to the line end (1st shed) is shown in the figure. The equipotential contours on the shed projected in the (X, Y) 114

139 plane are also shown in these figures. The numbers indicated in the graph show the voltage in volts. The applied voltage on the line end is assumed to be 1 kvp. (a) C ase R H C l photo. (b) C ase R H C l rain calculation m odel. Figure 5.3: Case RHCl water droplet distribution on the surface of a non-ceramic insulator and the calculation model used for study. V o lta g e (V ) 800, 780. Y (cm ) Y B40 % _ % % 620. ' % - X (cm ) : Y (cm ) (a) C ase R H C l v o lta g e distribution on the top surface o f the first shed. ' i. J 1 ;Y, ' X (cm ) (b) C ase R H C 1 equipotential contours on the top surface o f the first shed. Figure 5.4: V oltage distrihution and equipotential contours on the surface o f the first shed on a w et non-ceram ic insulator with H C l hydrophohicity. 115

140 (a) C ase R H C 2 photo. (b) C ase R H C 2 rain calculation m odel. Figure 5.5: Case RHC2 water droplet distribution on the surface of a non-ceramic insulator and the calculation model used for the study. V o lta g e (V ) Y (cm ) ^ ^ 0 X (cm ) 3 Y (cm ) X (cm ) (a) C ase R H C 2 v o lta g e distribution on the top surface o f the first shed. (b) C ase R H C 2 equipotential contours o n the top surface o f the first shed. Figure 5.6: V oltage distribution and equipotential contours on the surface o f the first shed on a w et non-ceram ic insulator with H C2 hydrophobicity. 116

141 ''I (a) C ase R H C 3 photo. (b) C ase R H C 3 rain calculation m odel. Figure 5.7: Case RFLC3 water droplet distribution on the surface of a non-ceramic insulator and the calculation model used for the study. V o lta g e (V ) Y (cm ) 7 4 0, , 7 0 0, 6 8 0, 6 6 0, 6 4 0, 6 2 0, 6 0 0, 0 \ l 0 - _. - y ^ - % f f > 1 1 X (cm ) i 4 5 Y (cm ) X (cm ) (a) C ase RH C3 v o lta g e distribution on the top surface o f the first shed. (b) C ase R H C 3 equip otential contours on the top surface o f the first shed. Figure 5.8: Case RHC3 voltage distribution and equipotential contours on the surface o f the first shed on a w et non-ceram ic insulator with HC3 hydrophobicity. 117

142 (a) C ase R H C 4 photo. (b) C ase R H C 4 rain calcu lation m odel. Figure 5.9: Case RHC4 water droplet distribution on the surface of a non-ceramic insulator and the calculation model used for the study. V o lta g e (V ) Y (cm ) 5i % X (cm ) 2 3 Y (cm ) X (cm ) (a) C ase R H C 4 v o lta g e distribution on the top surface o f the first shed. (b) C ase R H C 4 equipotential contours o n the top surface o f the first shed. Figure 5.10: V oltage distribution and equipotential contours on the surface o f the first shed on a w et non-ceram ic insulator w ith ffc 4 hydrophobicity. 118

143 T >rst n ~- ) -. :,ü% i ;vsei (a) C ase RH C5 photo. (b) C ase R H C 5 rain calcu lation m odel. Figure 5.11: Case RHC5 water droplet distribution on the surface of a non-ceramic insulator and the calculation model used for the study. V o lta g e (V ) Y (cm ) I ; 1_ ClV'I - X (cm ) Y (cm ) (a) C ase R H C 5 v o lta g e distribution on the top surface o f the first shed. X (cm ) (b) C ase R H C 5 equip otential contours on the top surface o f the first shed. Figure 5.12: Voltage distribution and equipotential contours on the surface of the first shed on a wet non-ceramic insulator with HC5 hydrophobicity. 119

144 a. ' mkmtfmil' * mwe (a) C ase R H C 6 photo. (b) C ase R H C 6 rain calculation m odel. Figure 5.13: Case RHC6 water droplet distribution on the surface of a non-ceramic insulator and the calculation model used for the study. Y (cm ) V o lta g e (V ) % % X (cm ) Y (cm ) X (cm ) (a) C ase R H C 6 v o lta g e distribution on the top surface o f the first shed. (b) C ase R H C 6 equipotential contours o n the top surface o f the first shed. Figure 5.14: Voltage distribution and equipotential contours on the surface of the first shed on a wet non-ceramic insulator with HC6 hydrophobicity. 120

145 5.6 Analysis of enhancement factors and electric field and voltage distributions for an insulator under rain conditions The voltage distributions on the shed closest to the line end (first shed) with water droplets on the top surface are shown in Figs. 5.4, 5.6, 5.8, 5.10, 5.12, 5.14 (a) and (b). The resulting distribution of the voltage is due to the different shape and size of water droplets. From these results, it can be seen that if the diameter of the water droplet is smaller than 2mm, the effect of the water droplet to the voltage distribution can be ignored. That is the reason why many small size water droplets in the photo are not included in the calculation model. The larger the water droplet size, the bigger its effect is on the voltage distribution along the top surface of the shed. The voltage distribution is significantly distorted by the merged water runnels (Case RFfC5). The existence of the merged water runnels increases the voltage difference between the neighboring water droplets and itself. If the electric field strength between them exceeds the threshold value, kvrms/mm, water droplet corona discharges may occur between water droplets, and that may destroy the hydrophobicity o f the shed material. Without water droplets, the highest electric field strength on the top of the first shed is kvp/mm at 1 kvp. For example, the highest electric field strength on the surface of the water droplets on the first shed for Case RCF13 is kvp/mm at 1 kvp. This clearly shows that the presence of the water droplets enhances the electric field strength on the shed by a factor of about

146 The electric field enhancement factors on the surface of water droplets on the shed at various locations of the non-ceramic insulator for Cases RCH1-RCH6 are summarized in Table 5.2. The sheath region is between the first shed and the second shed. D ry C ase (k V /m m ) C ase R H C l E. F. C ase R H C 2 E. F. Case RHC3 E.F. C ase R H C 4 E.F. C ase RHC5 Triple jun ction point & T op o f the first shed U nder the first shed C E.F. C ase R H C 6 E.F. Table 5.2: Electric field enhancement factors (E. F.) for Cases RCH1-RCH6 at various locations. The equipotential contours along a dry and clean non-ceramic insulator are also calculated and then compared to those of wet insulators, such as Cases RHC 1-6, in order to visualize the different overall voltage distributions of the six models. The calculation results are summarized in Fig Each number shown along the perimeters of the seven contour plots means centimeters. The numbers indicated in the graph show the voltage in volts. Fig. 5.15(a) shows the base case, the non-uniform voltage distribution along a dry and clean insulator. Comparison of the density of the equipotential lines in Figs 15 (b)-(g) to those of the base case can be used to study the overall distribution of the electric field for the cases with water droplets. The 200, 400, 600, 800 equipotential lines are drawn with a darker line for the purpose of comparison. 122

147 r CL Ô ' = : ^8 ^ - t o o _ ^400 ' ^_550 Geo ^ 650' 'k?y 15-14' 13 = = 1' , C (a) D ry C ase (b) C ase R C H 1 (c) Case RCH2 1 5 ^ ro' ^"^^ ' : =:-:-::= 9 ' 250 ==:;::::;y '450: :: -'GOO^XÇ : ' ' 2 - % ^ 'I.-' i;' : : -4 r i ; ; ; r ' : '200%: '400-: (e) Case RCH4 (f) Case RCH5 (g) Case RCH6 Figure 5.15: Equipotential contours for (a) dry Case (b)-(g) Cases RHC1-RHC6. 123

148 Fig (b) shows the voltage distribution for Case RHCl. The positions of the 800, 600, 400, 200 equipotential lines are slightly higher than in the dry case. The electric field strength at the triple junction point is lower than in the dry case. As a result of small size water droplets on the top surface of the insulator shed, the overall electric field strength is a little more uniform than in the dry case. O f course, the local electric field strength enhance factor in the vicinity of each water droplet is enhanced to a ratio about 2.4. Fig (c) shows the voltage distribution for Case RHC2. The positions of the 800, 600, 400, 200 equipotential lines are almost the same as in the dry case. The electric field strength at the triple junction point is also almost the same as in the dry case. The local electric field strength enhancement factor in the vicinity of each water droplet is 2.3. Fig (d) shows the voltage distribution for Case RHC3. The positions of the 400, 200 equipotential lines are significant lower than in the dry case. The electric field strength enhancement factor at the triple junction point is 1.2. The local electric field strength enhancement factor in the vicinity o f each water droplet is about 2.1. Fig (e) shows the voltage distribution for Case RHC4. The positions of the 800, 600 equipotential lines are slightly lower than in the dry case. The electric field strength enhancement factor at the triple junction point is 1.4. Due to the existence of the long water runnels on the top surface of the insulator, the local electric field strength enhancement factor in the vicinity of a water runnel is about 3.7, much higher than Cases RHC 1-3. Fig (f) shows the voltage distribution for Case RHC5. The positions of the 800, 600, 400 equipotential lines are significantly lower than in the dry case. Due to the 124

149 existence of the large complete wet areas on the top surface of the insulator, the electric field strength enhancement factor at the triple junction point is 1.8. The local electric field strength enhancement factor in the vicinity of wet areas is about 4, much higher than Cases R H C l-3. Fig (g) shows the voltage distrihution for Case RHC6. The positions of the 800, 600, 400, 200 equipotential lines are significantly lower than in the dry case. Due to the existence of the 90 % complete wet area on the top surface of the insulator, the electric field strength enhancement factor at the triple junction point is 1.7. The local electric field strength enhancement factor in the vicinity of the wet area is about 1.4. The electric field strength magnitude along the sheath surface of the insulator under rain conditions is also calculated. The calculation path (the dashed line shown in Fig (a)) is 4mm away from the surface of the sheath and starts from the point 0.2 mm above the line end metal fitting. To show the results more clearly, the magnitude of the electric field strength in the air along the surface of the sheath for Case (a) - (g) is shown in two figures. Fig shows the result for Case (a)-(d). Fig shows the result for Case (a) and Cases (e)- (g). The horizontal quantity is the insulation distance along the sheath surface, in percent. It is evident from the analysis of the results in Fig that the worse the hydrophobicity of the insulator surface, the more distortion it causes to the EFVD distribution along the insulators. If the hydrophobicity of the insulator surface is between H C l-2, the EFVD along the insulator under rain condition is nearly the same as along the dry and clean insulator. 125

150 ^ oœ D ry case C ase R H C 1 ÜKCRHC2 ÜMCRHC3 S) 0.02 a 2 O Iw O % M '-y Insulation distance (% ) Figure 5.16: Electric field strength magnitude along the insulation distance at the surface of the sheath for Dry Case and Cases RHC h D ry case ÜKCRHC4 ÜKCRHC5 C ase R H C 6 I I w , to o Insulation distance (%) Figure 5.17: Electric field strength magnitude along the insulation distance at the surface of the sheath for Dry Case and Cases RHC

151 5.7 Insulator models under fog conditions Under fog conditions, the water droplets not only stay on the top surface of the weather sheds but also attach to the undersides of the weather sheds. Sometimes, there are some small water droplets on the sheath region of the insulator. On the vertical sheath region, the size of water droplets is much less than on the shed region because a large water droplet cannot cling itself to the sheath surface. Three typical cases of the nonceramic insulator under different wetting conditions in the fog chamber are illustrated by the photographs shown in Figs. 5.18, 5.19, They are named as Case FHCl, Case FFIC2, and Case FFIC3. The number of elements used for each case is about 12,000. The diameter of the water droplets used for the calculations is about 2-5 mm. The wetting conditions of the three cases are summarized in Table 5.3, in terms of the HC stages. C ase F H C l C ase FH C 2 C ase HC3 T op o f the shed H C l H C 2 HC3 U nder the shed H C l HC2 HC3 Sheath region N o water H C l H C l Table 5.3: Hydrophobicity of polymer insulator in different regions. Case FHCl represents a SIR insulator under early wetting status in the fog chamber as shown in Figs (a) and (b). There are small size water droplets on both the top and the underside of the shed. There is no water droplets on the sheath region of the insulator. The model used for the Coulomb software to calculate the electric field and voltage distribution is shown in Fig (c). To reduce the calculation time, only a

152 degree segment of the shed surface is modeled, and that segment is used 36 times to represent the entire circumference of a shed. m - If. 4 - (a) C ase F H C l w ith H C l top surface. (b) C ase F H C l w ith H C l underside surface and dry sheath. (C) C ase F H C l calculation m odel. Figure 5.18: Case FHCl water droplet distribution on the surface of a non-ceramic insulator and the calculation model. Case FHC2 represents a SIR insulator under advanced wetting status, which are shown in Figs (a) and (b). There are medium size water droplets on top of each shed, on the underside of each shed, and small water droplets on each sheath region of the insulator as well. The model (as cross-section) used for the calculations is shown in Fig. 128

153 5.19 (c). To reduce the calculation time, only a 10 degree segment of the shed surface is modeled. That segment is used then 36 times to represent the entire circumference of a shed. mm (a) C ase FH C 2 w ith H C 2 top surface. (b) C ase FH C 2 w ith ttc 2 underside surface and FtC l sheath surface. (C ) C ase FH C 2 calculation m odel. Figure 5.19: Case FHC2 water droplet distribution on the surface of a non-ceramic insulator and the calculation model. Case FHC3 represents a SIR insulator under more advanced wetting status, which are shown in Figs (a) and (b). There are large water droplets on top of each shed, on the underside of each shed, and small water droplets on each sheath region of the 129

154 insulator. The model (as cross-section) used for the calculations is shown in Fig (c). To reduce the calculation time, only a 10 degree segment of the shed surface is modeled. That segment is used then 36 times to represent the entire circumference of a shed. TP f I S (a) C ase FH C 3 w ith H C 3 top surface. (b) C ase FH C 3 w ith H C 3 underside surface and H C 1 sheath surface. I \îir' (C ) Case FHC3 calculation m odel. Figure 5.20: Case FF1C3 water droplet distribution on the surface of a non-ceramic insulator and the calculation model used for the study. 130

155 5.8 Analysis of enhancement factors and electric field and voltage distribution for an insulator under fog conditions The equipotential contours along a dry and clean non-ceramic insulator are also calculated and then compared to those of the insulators under fog conditions, such as Cases FHC1-FHC3, in order to visualize the different overall voltage distributions of the four models. The calculation results are summarized in Fig Each number shown along the perimeters of the four contour plots means centimeters. The numbers indicated in the graph show the voltage in volts. Fig. 5.21(a) shows the base case, the non-uniform voltage distribution along a dry and clean insulator. Comparison of the density of the equipotential lines in Figs (b)- (d) to those of in the base case can be used to study the overall distribution of the electric field for the cases with water droplets. Fig. 5.21(b) shows the voltage distribution for Case FFICI. The water droplets are on the topside and on the underside of the weather sheds. The electric field strength ( kvp/mm) at the triple junction area is lower than in the dry and clean case (0.028 kvp/mm). So the electric field enhancement factor is /0.028=0.9. Fig. 5.21(c) shows the voltage distribution for Case FFIC2. The water droplets are on the topside and on the underside of the weather sheds. The electric field strength (0.067 kvp/mm) at the surface of the water at the triple junction area is higher than in the dry and clean case (0.028 kvp/mm). So the electric field enhancement factor is 0.067/0.028=

156 Fig. 5.21(d) shows the voltage distribution for Case FHC3. The hydrophobicity on the top and down surface are different compared to Case FHC2. The presence of the water droplets makes the voltage distribution along the entire insulator more uniform m r (a) Dry case (b) Case FHCl (c) Case FHC2 (d) Case FHC3 Figure 5.21: Equipotential contours for (a) Dry case, (b) Case FHCl, (c) Case FHC2, (d) Case FHC3. The electric field enhancement factors on the surface of water droplet or the shed at different locations of the non-ceramic insulator for Cases FHC1-FHC3 are summarized in Table 5.4. D ry C ase (kv /m m ) C ase F H C l E. F. C ase F H C 2 E. F. C ase FH C 3 Triple jun ction point T op o f the first shed U nder the first shed 0TG Sheath region E. F. Table 5.4: Electric field enhancements factor (E. F.) for Cases FHC1-FHC3 at various locations. 132

157 The magnitude of the electric field strength along the sheath surface of the insulator under fog conditions are shown in Fig The calculation path is 4mm away from the surface of the sheath and starts from the point 0.2 mm above the line end metal fitting. The horizontal quantity is the insulation distance along the sheath surface, in percent > : D ry case C ase F H C l C ase F H C 2 Case FHC W Insulation distan ce (%) Figure 5.22: Electric field strength magnitude along the insulation distance at the surface of the sheath for Dry Case and Cases FHC1-FHC3. The electric field distribution along the sheath surface of the insulator is pretty close for Case FFICI and FF1C2. There is a significant difference between Dry Case and Case FHC3. The overall electric field strength is more uniform for Case FHC3 than the Dry Case. 133

158 5.9 Summary A four-shed insulator model has been used for the study to reduce the calculation time. The models developed for the calculations are based on photographs of insulators undergoing aging tests in a fog chamber. Six insulator models under rain conditions with H C l-6 surface conditions and three insulator models under fog conditions with H C l-3 surface conditions have been developed. The electric field and voltage distributions along non-ceramic insulators under various wet conditions have been calculated and analyzed. Electric field and equipotential lines and electric field enhancement factors on the surface of water droplets have also been presented.. 134

159 Chapter 6 VERIFICATION TESTS FOR DRY INSULATOR In order to verify the dry calculation results by experimental results, a series of experiments were conducted in the High Voltage Laboratory of The Ohio State University by using a Positron insulator tester to study the electric field strength distribution along a dry non-ceramic insulator. The insulator tester measures the AC electric field along insulators. The tester has two parallel dielectrically separated plates that sense the electric field strength between them. The probe measures and records the electric field strength along the insulator when the actuator is pushed. The information collected from the reading is stored in the memory and can be downloaded to a PC for graphical display. The insulator tester had to be calibrated before the verification tests. For that purpose, a 34.5 kv SiR insulator was suspended from a grounded supporting structure. A 1 meter long conductor was connected to the line end of the insulator. The vertical component of the electric field strength distribution along the insulator was measured using the insulator tester. The calculation results of the simulation were compared with the measurement results. 135

160 6.1 Calibration test The insulator tester needed to be calibrated before the verification tests. The vertical sphere gap, asymmetrically energized, was used for the calibration tests. The spheres were aligned and positioned vertically. The diameter of each one of the two sphere electrodes is 35.5 cm. The distance between the two spheres was 20 cm. The center of the upper sphere was 200 cm above the ground plane. The Positron insulator tester was put in the middle of the sphere gap. The upper sphere was energized, and the other one was grounded. The high voltage sphere was energized from a 25-kVA 240 V/250kV transformer via a current-limiting resistor and high voltage bus. The high voltage output of the transformer was controlled using a variable ratio autotransformer on the low voltage side of the transformer. A 40000:1 ratio capacitive voltage divider was connected to the high voltage bus for measurement purposes. The calibration test setup is shown in Fig. 6.1, which also shows how to download the data from the insulator tester to the PC. m # V,' -V» -'IK## Figure 6.1 : Calibration test setup. 136

Electric Field and Potential Distributions along Non-Ceramic Insulators with Water Droplets. Integrated Engineering Software - Website Links

Electric Field and Potential Distributions along Non-Ceramic Insulators with Water Droplets. Integrated Engineering Software - Website Links Electric Field and Potential Distributions along Non-Ceramic Insulators with Water Droplets ABSTRACT The electric field and potential distributions along wet non-ceramic insulators are calculated using

More information

CHAPTER 5 ANALYSIS OF ELECTRIC FIELD AND VOLTAGE DISTRIBUTION

CHAPTER 5 ANALYSIS OF ELECTRIC FIELD AND VOLTAGE DISTRIBUTION 96 CHAPTER 5 ANALYSIS OF ELECTRIC FIELD AND VOLTAGE DISTRIBUTION 5.1 INTRODUCTION The electric field distribution of polymeric insulator is different when compared to porcelain and glass insulators. Generally

More information

Electric Field and Potential Distributions along Dry and Clean Non-Ceramic Insulators. Integrated Engineering Software - Website Links

Electric Field and Potential Distributions along Dry and Clean Non-Ceramic Insulators. Integrated Engineering Software - Website Links Electric Field and Potential Distributions along Dry and Clean Non-Ceramic Insulators ABSTRACT The electric field and potential distributions in the vicinity of non-ceramic insulators under dry and clean

More information

Simulation Studies of Composite Insulators used in High Voltage Transmission

Simulation Studies of Composite Insulators used in High Voltage Transmission Simulation Studies of Composite s used in High Voltage Transmission Rohit P R, Rahul P R (June 18, 2018) Department of Electrical & Electronics Engineering, CMR Institute of Technology, Bengaluru rohitpr300796@gmail.com,

More information

Electric Field Analysis and Experimental Evaluation of 400 kv Silicone Composite Insulator

Electric Field Analysis and Experimental Evaluation of 400 kv Silicone Composite Insulator Electric Field Analysis and Experimental Evaluation of 400 kv Silicone Composite Insulator M. Nageswara Rao, N. Sumathi, V. S. N. K. Chaitanya International Science Index, Electronics and Communication

More information

Power System Engineering Prof. Debrapriya Das Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Power System Engineering Prof. Debrapriya Das Department of Electrical Engineering Indian Institute of Technology, Kharagpur Power System Engineering Prof. Debrapriya Das Department of Electrical Engineering Indian Institute of Technology, Kharagpur Lecture - 01 Overhead Line Insulators So, welcome to this another course that

More information

SPECIFICATION SS 51/9 400KV COUPLING CAPACITORS FOR POWER LINE CARRIER SYSTEM

SPECIFICATION SS 51/9 400KV COUPLING CAPACITORS FOR POWER LINE CARRIER SYSTEM INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION January 2017 SPECIFICATION SS 51/9 400KV COUPLING CAPACITORS FOR POWER LINE CARRIER SYSTEM I. SCOPE This

More information

Finite Element Analysis of Disc Insulator Type and Corona Ring Effect on Electric Field Distribution over 230-kV Insulator Strings

Finite Element Analysis of Disc Insulator Type and Corona Ring Effect on Electric Field Distribution over 230-kV Insulator Strings International Journal of Engineering and Technology, 1 (4) (2012) 407-419 Science Publishing Corporation www.sciencepubco.com/index.php/ijet Finite Element Analysis of Disc Insulator Type and Corona Ring

More information

Measurement of wettability for polymer materials using non-contact surface resistivity

Measurement of wettability for polymer materials using non-contact surface resistivity Proc. 26 Electrostatics Joint Conference Measurement of wettability for polymer materials using non-contact surface resistivity tester Toshiyuki Sugimoto, Takuya Aoki Graduate school of Science and Engineering

More information

Measurement and simulation of the voltage distribution and the electric field on a glass insulator string

Measurement and simulation of the voltage distribution and the electric field on a glass insulator string Available online at www.sciencedirect.com Measurement 41 (2008) 471 480 www.elsevier.com/locate/measurement Measurement and simulation of the voltage distribution and the electric field on a glass insulator

More information

HIGH electric field strength ( ) may cause corona on nonceramic

HIGH electric field strength ( ) may cause corona on nonceramic 1070 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 2, APRIL 2007 Practical Cases of Electric Field Distribution Along Dry and Clean Nonceramic Insulators of High-Voltage Power Lines Weiguo Que, Stephen

More information

Estimation of the Electric Field and Potential Distribution on Three Dimension Model of Polymeric Insulator Using Finite Element Method

Estimation of the Electric Field and Potential Distribution on Three Dimension Model of Polymeric Insulator Using Finite Element Method Estimation of the Electric Field and Potential Distribution on Three Dimension Model of Polymeric Insulator Using Finite Element Method Rifai Ahmed Rifai, Ali Hassan Mansour, Mahmoud Abdel Hamid Ahmed

More information

3D modeling of Electrical Field and Electrical Potential in different contamination condition in Polymeric Insulator

3D modeling of Electrical Field and Electrical Potential in different contamination condition in Polymeric Insulator 3D modeling of Electrical Field and Electrical Potential in different contamination condition in Polymeric Insulator A. Majzoobi *, I. A. Joneidi, S. Mohajer, H.Mohseni, A. A. Shayegani High Voltage Lab,

More information

Simulation of the Electric Field on Composite Insulators Using the Finite Elements Method

Simulation of the Electric Field on Composite Insulators Using the Finite Elements Method Simulation of the Electric Field on Composite Insulators Using the Finite Elements Method V.T. KONTARGYRI I.F. GONOS N.C. ILIA I.A. STATHOPULOS High Voltage Laboratory School of Electrical and Computer

More information

NUMERICAL ANALYSES OF ELECTROMAGNETIC FIELDS IN HIGH VOLTAGE BUSHING AND IN ELECTROMAGNETIC FLOW METER

NUMERICAL ANALYSES OF ELECTROMAGNETIC FIELDS IN HIGH VOLTAGE BUSHING AND IN ELECTROMAGNETIC FLOW METER Intensive Programme Renewable Energy Sources May 2011, Železná Ruda-Špičák, University of West Bohemia, Czech Republic NUMERICAL ANALYSES OF ELECTROMAGNETIC FIELDS IN HIGH VOLTAGE BUSHING AND IN ELECTROMAGNETIC

More information

O Plus Dry Bushing 69 kv system, 350 kv BIL, 3000 A. Table of contents

O Plus Dry Bushing 69 kv system, 350 kv BIL, 3000 A. Table of contents Type test report O Plus Dry Bushing 69 kv system, 0 kv BIL, 000 A Table of contents Abstract... 2 2 Certification... 2 Introduction.... Description and ratings....2 Overview of tests.... Applicable standards....4

More information

Flashover Performance of Station Post Insulators under Icing Conditions based on Electric Field Distribution

Flashover Performance of Station Post Insulators under Icing Conditions based on Electric Field Distribution Flashover Performance of Station Post Insulators under Icing Conditions based on Electric Field Distribution V. Jaiswal and M. Farzaneh NSERC / Hydro-Quebec / UQAC Industrial Chair on Atmospheric Icing

More information

Winai Onchantuek, Boonruang Marungsri, Anant Oonsivilai, Thanatchai Kulworawanichpong. WSEAS TRANSACTIONS on POWER SYSTEMS

Winai Onchantuek, Boonruang Marungsri, Anant Oonsivilai, Thanatchai Kulworawanichpong. WSEAS TRANSACTIONS on POWER SYSTEMS Comparison of Electric Field and Potential Distributions on Silicone Rubber Polymer Insulators under Clean and Various Contamination Conditions Using Finite Element Method WINAI ONCHANTUEK, BOONRUANG MARUNGSRI*

More information

The objective of a grounding system are: 1. To provide safety to personnel during normal and fault conditions by limiting step and touch potential.

The objective of a grounding system are: 1. To provide safety to personnel during normal and fault conditions by limiting step and touch potential. GROUNDING SYSTEMS Part 1 Professor Ahdab Elmorshedy 1 Reference: High Voltage Engineering Theory and Practice, Text Book, Marcel Dekker Inc. NY, USA, 2000. Mazen Abdel-Salam, Hussein Anis, Ahdab Elmorshedy,

More information

Degradation of Hydrophobic Properties of Composite Insulators in Simulated Arid Desert Environment

Degradation of Hydrophobic Properties of Composite Insulators in Simulated Arid Desert Environment International Journal of Engineering & Technology IJET-IJENS Vol:10 No:01 64 Degradation of Hydrophobic Properties of Composite Insulators in Simulated Arid Desert Environment Yasin Khan Abstract Electrical

More information

SCIENCE & TECHNOLOGY

SCIENCE & TECHNOLOGY Pertanika J. Sci. & Technol. 25 (S): 189-196 (2017) SCIENCE & TECHNOLOGY Journal homepage: http://www.pertanika.upm.edu.my/ EFVD along Porcelain Insulator using the FEM Kian Tsong Ho*, Mahdi Izadi and

More information

An Introduction to Insulation Resistance Testing

An Introduction to Insulation Resistance Testing An Introduction to Insulation Resistance Testing In a perfect world, electrical insulation would allow no current to flow through it. Unfortunately, a number of factors can over time result in the deterioration

More information

Reliability Enhancement of Line Insulator of a Transmission System using Artificial Neural Network Sumit Mathur #1, G.K. Joshi* 2

Reliability Enhancement of Line Insulator of a Transmission System using Artificial Neural Network Sumit Mathur #1, G.K. Joshi* 2 Reliability Enhancement of Line nsulator of a Transmission System using Artificial Neural Network Sumit Mathur #1, G.K. Joshi* 2 # Research Scholar, Mewar University, Gangrar, Chittorgarh, Rajasthan, ndia

More information

Experimental Study of the Artificial Neural Network Solutions for Insulators Leakage Current Modeling in a Power Network

Experimental Study of the Artificial Neural Network Solutions for Insulators Leakage Current Modeling in a Power Network Experimental Study of the Artificial Neural Network Solutions for Insulators Leakage Current Modeling in a Power Network Ali Bahramiazar Instrumentation Department, W.A. E.P.D Company, Orumieh, Iran Email:

More information

TEST CERTIFICATES OR REPORTS ISSUED BY VEIKI-VNL LTD.

TEST CERTIFICATES OR REPORTS ISSUED BY VEIKI-VNL LTD. Page 2 of 29 TEST CERTIFICATES OR REPORTS ISSUED BY LTD. Type Test Certificate of Complete Type Test This certificate provides the verification of all the rated characteristics of the equipment as assigned

More information

Evaluation of Capacitance in Motor Circuit Analysis Findings. Howard W Penrose, Ph.D., CMRP President, SUCCESS by DESIGN

Evaluation of Capacitance in Motor Circuit Analysis Findings. Howard W Penrose, Ph.D., CMRP President, SUCCESS by DESIGN Evaluation of Capacitance in Motor Circuit Analysis Findings Howard W Penrose, Ph.D., CMRP President, SUCCESS by DESIGN Introduction The question related to the ability of low voltage testing to detect

More information

ELECTRIC FIELD AND VOLTAGE DISTRIBUTION ALONG INSULATORS UNDER POLLUTION CONDITIONS. V T Kontargyri N C Ilia I F Gonos I A Stathopulos

ELECTRIC FIELD AND VOLTAGE DISTRIBUTION ALONG INSULATORS UNDER POLLUTION CONDITIONS. V T Kontargyri N C Ilia I F Gonos I A Stathopulos ELECTRIC FIELD AND VOLTAGE DISTRIBUTION ALONG INSULATORS UNDER POLLUTION CONDITIONS V T Kontargyri N C Ilia I F Gonos I A Stathopulos National Technical University of Athens School of Electrical and Computer

More information

Advanced Technique for Dielectric Analyses

Advanced Technique for Dielectric Analyses Chroma Systems Solutions, Inc. Advanced Technique for Dielectric Analyses 190xx Series Hipot Testers Keywords: Dielectric Analyses, Destructive testing, Threshold Detection, Breakdown, Test Damage. Title:

More information

Electrical, Electronic and Computer Engineering ENEL4HB - High Voltage 2

Electrical, Electronic and Computer Engineering ENEL4HB - High Voltage 2 Electrical, Electronic and Computer Engineering ENEL4HB - High oltage 2 Main Examination October 2016 Instructions Answer all questions, show all working and include all necessary comments (it is your

More information

PUB NLH 185 Island Interconnected System Supply Issues and Power Outages Page 1 of 9

PUB NLH 185 Island Interconnected System Supply Issues and Power Outages Page 1 of 9 PUB NLH 1 Page 1 of 1 Q. Provide Hydro s list of outage cause codes and indicate how troublemen are managed and trained to properly use the codes. Explain the method used to report outage causes. A. Hydro

More information

Finite Element Analysis on Post Type Silicon Rubber Insulator Using MATLAB

Finite Element Analysis on Post Type Silicon Rubber Insulator Using MATLAB Finite Element Analysis on Post Type Silicon Rubber Insulator Using MATLAB ISSN: 3-9939 Finite Element Analysis on Post Type Silicon Rubber Insulator Using MATLAB Vishal Kahar, Ch.v.sivakumar, 3 Dr.Basavaraja.B

More information

Standard Test Methods for Glass-Bonded Mica Used as Electrical Insulation 1

Standard Test Methods for Glass-Bonded Mica Used as Electrical Insulation 1 Designation: D 1039 94 (Reapproved 1999) e1 An American National Standard Standard Test Methods for Glass-Bonded Mica Used as Electrical Insulation 1 This standard is issued under the fixed designation

More information

Performance Evaluation of Polymers for Bumping and Wafer Level Packaging

Performance Evaluation of Polymers for Bumping and Wafer Level Packaging Performance Evaluation of Polymers for Bumping and Wafer Level Packaging John JH Reche 945 E. Verde Lane, Tempe, AZ 85284 jjhreche@wafer-bumping.com 11th Symposium on Wintherthur Museum and Gardens, DE

More information

1. Explain the various methods of methods of grounding. In power system, grounding or earthing means connecting frame of electrical equipment (non-cur

1. Explain the various methods of methods of grounding. In power system, grounding or earthing means connecting frame of electrical equipment (non-cur 1. Explain the various methods of methods of grounding. In power system, grounding or earthing means connecting frame of electrical equipment (non-current carrying part) or some electrical part of the

More information

A Review of the Dynamic Modelling of Pollution Flashover on High Voltage Outdoor Insulators

A Review of the Dynamic Modelling of Pollution Flashover on High Voltage Outdoor Insulators Journal of Physics: Conference Series PAPER OPEN ACCESS A Review of the Dynamic Modelling of Pollution Flashover on High Voltage Outdoor Insulators To cite this article: Ali A. Salem and R. Abd-rahman

More information

Elizabethtown College Department of Physics and Engineering PHY104

Elizabethtown College Department of Physics and Engineering PHY104 Elizabethtown College Department of Physics and Engineering PHY104 Lab #7- Capacitors 1. Introduction The capacitor is one of the essential elements of analog circuitry. It is highly useful for its energy

More information

Evaluation of Critical Components of Non-Ceramic Insulators In-Service: Role of Defective Interfaces

Evaluation of Critical Components of Non-Ceramic Insulators In-Service: Role of Defective Interfaces PSERC Evaluation of Critical Components of Non-Ceramic Insulators In-Service: Role of Defective Interfaces Final Project Report Power Systems Engineering Research Center A National Science Foundation Industry/University

More information

Electro - Principles I

Electro - Principles I Electro - Principles I Capacitance The Capacitor What is it? Page 8-1 The capacitor is a device consisting essentially of two conducting surfaces separated by an insulating material. + Schematic Symbol

More information

A Novel Approach for Increasing the Reliability of Power Transmission Lines in Galloping Conditions

A Novel Approach for Increasing the Reliability of Power Transmission Lines in Galloping Conditions 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http: //www.cigre.org 2014 Grid of the Future Symposium A Novel Approach for Increasing the Reliability of Power Transmission Lines in Galloping

More information

VOLTAGE DISTRIBUTION ACROSS STRING INSULATORS BY SPHERE GAP METHOD

VOLTAGE DISTRIBUTION ACROSS STRING INSULATORS BY SPHERE GAP METHOD VOLTAGE DISTRIBUTION ACROSS STRING INSULATORS BY SPHERE GAP METHOD Prof. Ch.Kavitha Chenna Reddy 1, Dr.S.Sujitha 2 Assistant professor, EEE Department,New Horizon College of Engineering ABSTRACT Insulators

More information

Analysis and Prediction of Electric Field Intensity and Potential Distribution along Insulator Strings by using 3D models

Analysis and Prediction of Electric Field Intensity and Potential Distribution along Insulator Strings by using 3D models Analysis and Prediction of Electric Field Intensity and Potential Distribution along Insulator Strings by using 3D models ALICIA TINNIRELLO, EDUARDO GAGO, LUCAS D ALESSANDRO, MARIANO VALENTINI Computer

More information

Evaluation of the risk of failure due to switching overvoltages of a phase to phase insulation

Evaluation of the risk of failure due to switching overvoltages of a phase to phase insulation Evaluation of the risk of failure due to switching overvoltages of a phase to phase insulation A. Xemard, J. Michaud, A. Guerrier, I. Uglesic, G. Levacic, M. Mesic Abstract-- The upgrade of an overhead

More information

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad - 00 0 Department of Electrical and Electronics Engineering TUTORIAL QUESTION BANK Course Name : HIGH VOLTAGE ENGINEERING Course Code

More information

Real-time Monitoring of Leakage Current on Insulating Cross-arms in Relation to Local Weather Conditions

Real-time Monitoring of Leakage Current on Insulating Cross-arms in Relation to Local Weather Conditions 2013 Electrical Insulation Conference, Ottawa, Ontario, Canada, 2 to 5 June 2013 Real-time Monitoring of Leakage Current on Insulating Cross-arms in Relation to Local Weather Conditions C. Zachariades,

More information

O Plus Dry Bushing 25 kv system, 150 kv BIL, 3000 A

O Plus Dry Bushing 25 kv system, 150 kv BIL, 3000 A TYPE TEST REPORT O Plus Dry Bushing 25 kv system, 150 kv BIL, 3000 A 02 1 Abstract 02 2 Certification 03 3 Introduction 03 3.1 Description and ratings 03 3.2 Overview of tests 03 3.3 Applicable standards

More information

Prof. Dr. Magdi El-Saadawi

Prof. Dr. Magdi El-Saadawi بسم هللا الرحمن الرحيم رب اشرح لى صدرى ويسر لى أمر واحلل عقدة من لسانى يفقهوا قولى صدق هللا العظيم Prof. Dr. Magdi M. El-Saadawi www.saadawi1.net E-mail : saadawi1@gmail.com www.facebook.com/magdi.saadawi

More information

Optimum Corona Ring Design for High Voltage Compact Transmission Lines. Using Gaussian Process Model. Nihal Mohan

Optimum Corona Ring Design for High Voltage Compact Transmission Lines. Using Gaussian Process Model. Nihal Mohan Optimum Corona Ring Design for High Voltage Compact Transmission Lines Using Gaussian Process Model by Nihal Mohan A Thesis Presented in Partial Fulfillment of the Requirements for the Degree Master of

More information

Effect of Humidity on the Flashover Voltage of Insulators at Varying Humidity and Temperature Conditions

Effect of Humidity on the Flashover Voltage of Insulators at Varying Humidity and Temperature Conditions 4299 J. Basic. Appl. Sci. Res., 2(4)4299-4303, 2012 2012, TextRoad Publication ISSN 2090-4304 Journal of Basic and Applied Scientific Research www.textroad.com Effect of Humidity on the Flashover Voltage

More information

Modeling Electric Fields in High Voltage Submersible Changeover Switch

Modeling Electric Fields in High Voltage Submersible Changeover Switch Excerpt from the Proceedings of the COMSOL Conference 2010 Paris Modeling Electric Fields in High Voltage Submersible Changeover Switch K. Follesø, Cand. scient in Experimental Particle Physics from University

More information

Volume # 7 Issue # 8 August 2015 Rs.5/- Volume # 7 Issue # 8 August-September 2015 INTERNATIONAL.

Volume # 7 Issue # 8 August 2015 Rs.5/- Volume # 7 Issue # 8 August-September 2015 INTERNATIONAL. Rs.5/- Volume # 7 Issue # 8 August 2015 Rs.5/- Volume # 7 Issue # 8 August-September 2015 INTERNATIONAL www.eqmaglive.com www.eqmaglive.com Materials Matter For Reliable Performance And Power Output Of

More information

DEPARTMENT OF ELECTRICAL ENGINEERING DIT UNIVERSITY HIGH VOLTAGE ENGINEERING

DEPARTMENT OF ELECTRICAL ENGINEERING DIT UNIVERSITY HIGH VOLTAGE ENGINEERING UNIT 1: BREAKDOWN IN SOLIDS 1.) Introduction: The solid dielectric materials are used in all kinds of electrical apparatus and devices to insulate current carrying part from another when they operate at

More information

Study on the design of semiconducting anti icing RTV coatings

Study on the design of semiconducting anti icing RTV coatings International Symposium on omputers & Informatics (ISI 015) Study on the design of semiconducting anti icing TV coatings Fang Zhenyu1, a, Wu Peiyun, b 1State Grid Liaoning Electric Power ompany Anshan

More information

Technical Notes. Introduction. PCB (printed circuit board) Design. Issue 1 January 2010

Technical Notes. Introduction. PCB (printed circuit board) Design. Issue 1 January 2010 Technical Notes Introduction Thermal Management for LEDs Poor thermal management can lead to early LED product failure. This Technical Note discusses thermal management techniques and good system design.

More information

Damping resistor design consideration

Damping resistor design consideration http : //www.cigre.org CIGRÉ B4-054 CIGRÉ Winnipeg 2017 Colloquium Study Committees A3, B4 & D1 Winnipeg, Canada September 30 October 6, 201717 Damping resistor design consideration Elassad Yann MS Resistances

More information

OR Explain thermal breakdown in solid dielectrics. How this mechanism is

OR Explain thermal breakdown in solid dielectrics. How this mechanism is Subject : High Voltage Engineering (2090) ITM Universe, Vadodara Electrical Engineering Department Class : Electrical Sem : th Long Questions Sr. No Question Unit No : 0 Explain Charge Simulation method

More information

Outline of College Physics OpenStax Book

Outline of College Physics OpenStax Book Outline of College Physics OpenStax Book Taken from the online version of the book Dec. 27, 2017 18. Electric Charge and Electric Field 18.1. Static Electricity and Charge: Conservation of Charge Define

More information

MATHEMATICAL MODELING OF DISBONDED COATING AND CATHODIC DELAMINATION SYSTEMS KERRY N. ALLAHAR

MATHEMATICAL MODELING OF DISBONDED COATING AND CATHODIC DELAMINATION SYSTEMS KERRY N. ALLAHAR MATHEMATICAL MODELING OF DISBONDED COATING AND CATHODIC DELAMINATION SYSTEMS By KERRY N. ALLAHAR A DISSERTATION PRESENTED TO THE GRADUATE SCHOOL OF THE UNIVERSITY OF FLORIDA IN PARTIAL FULFILLMENT OF THE

More information

Standard Practice for Heat Aging of Plastics Without Load 1

Standard Practice for Heat Aging of Plastics Without Load 1 Designation: D 3045 92 (Reapproved 2003) Standard Practice for Heat Aging of Plastics Without Load 1 This standard is issued under the fixed designation D 3045; the number immediately following the designation

More information

Warsaw University of Technology Electrical Department. Laboratory of Materials Technology KWNiAE

Warsaw University of Technology Electrical Department. Laboratory of Materials Technology KWNiAE Warsaw University of Technology Electrical Department Laboratory of Materials Technology KWNiAE Practice 8 Determining The Resistivity of the Electroinsulating Materials 1. Behavior of the dielectric in

More information

HIGH ENERGY DENSITY CAPACITOR CHARACTERIZATION

HIGH ENERGY DENSITY CAPACITOR CHARACTERIZATION GENERAL ATOMICS ENERGY PRODUCTS Engineering Bulletin HIGH ENERGY DENSITY CAPACITOR CHARACTERIZATION Joel Ennis, Xiao Hui Yang, Fred MacDougall, Ken Seal General Atomics Energy Products General Atomics

More information

TRANSIENTS POWER SYSTEM. Theory and Applications TERUO OHNO AKIH1RO AMETANI NAOTO NAGAOKA YOSHIHIRO BABA. CRC Press. Taylor & Francis Croup

TRANSIENTS POWER SYSTEM. Theory and Applications TERUO OHNO AKIH1RO AMETANI NAOTO NAGAOKA YOSHIHIRO BABA. CRC Press. Taylor & Francis Croup POWER SYSTEM TRANSIENTS Theory and Applications AKIH1RO AMETANI NAOTO NAGAOKA YOSHIHIRO BABA TERUO OHNO CRC Press Taylor & Francis Croup Boca Raton London New York CRC Press is an imprint of the Taylor

More information

EFFECT OF SURFACE CHARGING ON DC FLASHOVER CHARACTERISTICS OF POLYMERIC INSULATORS

EFFECT OF SURFACE CHARGING ON DC FLASHOVER CHARACTERISTICS OF POLYMERIC INSULATORS EFFECT OF SURFACE CHARGING ON DC FLASHOVER CHARACTERISTICS OF POLYMERIC INSULATORS By IMTIAZ RIFANUL HOQUE SHAHID ALAM Diploma Work No. 73/211 Department of Materials and Manufacturing Technology CHALMERS

More information

Analysis of Very Fast Transients in EHV Gas Insulated Substations

Analysis of Very Fast Transients in EHV Gas Insulated Substations Analysis of Very Fast Transients in EHV Gas Insulated Substations A.Raghu Ram, k. Santhosh Kumar raghuram_a@yahoo.com,ksanthosheee@gmail.com Abstract: Gas insulated switchgear (GIS) has been in operation

More information

PREFERRED RELIABILITY PRACTICES. Practice:

PREFERRED RELIABILITY PRACTICES. Practice: PREFERRED RELIABILITY PRACTICES Practice No. PD-ED-1239 Page 1 of 6 October 1995 SPACECRAFT THERMAL CONTROL COATINGS DESIGN AND APPLICATION Practice: Select and apply thermal coatings for control of spacecraft

More information

Suppressor film capacitor Highlight and Application in Series with the main

Suppressor film capacitor Highlight and Application in Series with the main Suppressor film capacitor Highlight and Application in Series with the main April 2007 Paola Bettacchi - Product Manager 1 Film capacitor : main features and performances Process flow charts Self-healing

More information

Thermal Resistance Measurement

Thermal Resistance Measurement Optotherm, Inc. 2591 Wexford-Bayne Rd Suite 304 Sewickley, PA 15143 USA phone +1 (724) 940-7600 fax +1 (724) 940-7611 www.optotherm.com Optotherm Sentris/Micro Application Note Thermal Resistance Measurement

More information

Double Layer Capacitors. PN: NEX_ series & NED_ series

Double Layer Capacitors. PN: NEX_ series & NED_ series Rev B - August 2010 www.niccomp.com Technical support: tpmg@niccomp.com Double Layer Capacitors PN: NEX_ series & NED_ series NEXC SMT Reflow Soldering NEXA / NEXG NEXS / NEXT Low Profile Radial LDD NEXM

More information

The Dielectrical Properties of Photovoltaic Encapsulants: Measurements and Values.

The Dielectrical Properties of Photovoltaic Encapsulants: Measurements and Values. The self-deception is the base of the Emperor s New Clothes story. Sometimes it is difficult to realize that something is not real. It requires that something or someone new comes up to help us to see

More information

Grading capacitors for circuit breakers

Grading capacitors for circuit breakers Grading capacitors for circuit breakers Service experience and failure mechanisms Contribution from Cigré WG A3.18 (M. Runde, A. Bosma, P. Coventry, S. Dick, P. Gramaglia, H. Jahn, N. Koch, E. Kynast,

More information

WCAP-AS5H Aluminum Electrolytic Capacitors

WCAP-AS5H Aluminum Electrolytic Capacitors A Dimensions: [mm] B Recommended hole pattern: [mm] D1 Electrical Properties: Properties Test conditions Value Unit Tol. Capacitance 0.25V; 120Hz C 10 µf ± 20% Rated voltage U R 16 V (DC) max. Leakage

More information

STATIC GAS MONITOR Type SGM/DEW Revision A of 20 aprile 2016

STATIC GAS MONITOR Type SGM/DEW Revision A of 20 aprile 2016 APPLICATIONS Moisture monitoring of air or gas (SF6) Suitable for indoor or outdoor Industrial, medical or aerospace fields HIGHLIGHTS High voltage circuit breakers commonly used for distribution and transmission

More information

EFFECT OF CLIMATIC VARIATIONS ON POLLUTION DEPOSIT ON ELECTRIC INSULATION AND RELATED FAILURE

EFFECT OF CLIMATIC VARIATIONS ON POLLUTION DEPOSIT ON ELECTRIC INSULATION AND RELATED FAILURE EFFECT OF CLIMATIC VARIATIONS ON POLLUTION DEPOSIT ON ELECTRIC INSULATION AND RELATED FAILURE M.REZAEI M.A.SHARIATI M.A.TALEBI F.DANESHVAR N.R.I -Iran N.R.I -Iran N.R.I -Iran H.D.E.C-Iran Marezaei@nri.ac.ir

More information

Physics (

Physics ( Question 2.12: A charge of 8 mc is located at the origin. Calculate the work done in taking a small charge of 2 10 9 C from a point P (0, 0, 3 cm) to a point Q (0, 4 cm, 0), via a point R (0, 6 cm, 9 cm).

More information

Copyright 2014 IEEE. Paper presented at 2014 IEEE conference on electrical insulation and dielectric phenomena, Des Moines, USA, October, 2014.

Copyright 2014 IEEE. Paper presented at 2014 IEEE conference on electrical insulation and dielectric phenomena, Des Moines, USA, October, 2014. Copyright 2014 IEEE Paper presented at 2014 IEEE conference on electrical insulation and dielectric phenomena, Des Moines, USA, 19-22 October, 2014. This material is posted here with the permission of

More information

Electric Field Calculations on Dry-Type Medium Voltage Current Transformers. Sandeep Kumar Lakshmichand Jain

Electric Field Calculations on Dry-Type Medium Voltage Current Transformers. Sandeep Kumar Lakshmichand Jain Electric Field Calculations on Dry-Type Medium Voltage Current Transformers by Sandeep Kumar Lakshmichand Jain A Thesis Presented in Partial Fulfillment of the Requirements for the Degree Master of Science

More information

Extensions to the Finite Element Technique for the Magneto-Thermal Analysis of Aged Oil Cooled-Insulated Power Transformers

Extensions to the Finite Element Technique for the Magneto-Thermal Analysis of Aged Oil Cooled-Insulated Power Transformers Journal of Electromagnetic Analysis and Applications, 2012, 4, 167-176 http://dx.doi.org/10.4236/jemaa.2012.44022 Published Online April 2012 (http://www.scirp.org/journal/jemaa) 167 Extensions to the

More information

REALIZATION OF HUMIDITY STANDARD FACILITY USING TWO-PRESSURE HUMIDITY GENERATOR AND HUMIDITY CHAMBER

REALIZATION OF HUMIDITY STANDARD FACILITY USING TWO-PRESSURE HUMIDITY GENERATOR AND HUMIDITY CHAMBER METROLOGY AND MEASUREMENT SYSTEMS Index 3393, ISSN 86-8229 www.metrology.pg.gda.pl REALIZATION OF HUMIDITY STANDARD FACILITY USING TWO-PRESSURE HUMIDITY GENERATOR AND HUMIDITY CHAMBER Essam El-Din, Mostafa

More information

EFFECT OF ATMOSPHERIC CONDITIONS ON CABLE TERMINATION TO SWITCHGEAR

EFFECT OF ATMOSPHERIC CONDITIONS ON CABLE TERMINATION TO SWITCHGEAR PK ISSN 0022-2941; CODEN JNSMAC Vol. 46, No.1 & 2 (April & October 2006) PP 53-60 EFFECT OF ATMOSPHERIC CONDITIONS ON CABLE TERMINATION TO SWITCHGEAR Abdur Rashid, Asmatullah Khan and S.F Shaukat Department

More information

World Academy of Science, Engineering and Technology

World Academy of Science, Engineering and Technology Effect of Surface Tracking on LLDPE-NR/TiO2 Nanocomposite Conductivity Using PDC Technique M. S. A. Aziz 1, N. A. Muhamad 1,N.A.M.Jamail 12, Q. E. Kamarudin 3 1 Institute of High Voltage & High Current,

More information

Structure-Property Correlation [2] Atomic bonding and material properties

Structure-Property Correlation [2] Atomic bonding and material properties MME 297: Lecture 05 Structure-Property Correlation [2] Atomic bonding and material properties Dr. A. K. M. Bazlur Rashid Professor, Department of MME BUET, Dhaka Topics to discuss today... Review of atomic

More information

General characteristics

General characteristics General characteristics This range of insulators and partition bushings provides for connecting and supporting low- and medium-voltage electrical equipment. - Their purpose is to provide electrical and

More information

THERMAL ANALYSIS AND OPTIMIZATION OF THERMAL PAD THICKNESS FOR TRANSISTOR MOUNTING IN FOR CPU S

THERMAL ANALYSIS AND OPTIMIZATION OF THERMAL PAD THICKNESS FOR TRANSISTOR MOUNTING IN FOR CPU S ISSN Number (online): 2455-4650 THERMAL ANALYSIS AND OPTIMIZATION OF THERMAL PAD THICKNESS FOR TRANSISTOR MOUNTING IN FOR CPU S S. Balakrishnan *, M. Manikandan *Corresponding Author Department of Mechanical

More information

Modeling of Transmission Line and Substation for Insulation Coordination Studies

Modeling of Transmission Line and Substation for Insulation Coordination Studies TRAINING DUBROVNIK, CROATIA - APRIL, 27-29 2009 SIMULATION & ANALYSIS OF POWER SYSTEM TRANSIENTS WITH EMTP-RV Modeling of Transmission Line and Substation for Insulation Coordination Studies Prof. Ivo

More information

EE650R: Reliability Physics of Nanoelectronic Devices Lecture 18: A Broad Introduction to Dielectric Breakdown Date:

EE650R: Reliability Physics of Nanoelectronic Devices Lecture 18: A Broad Introduction to Dielectric Breakdown Date: EE650R: Reliability Physics of Nanoelectronic Devices Lecture 18: A Broad Introduction to Dielectric Breakdown Date: Nov 1, 2006 ClassNotes: Jing Li Review: Sayeef Salahuddin 18.1 Review As discussed before,

More information

EE6701 HIGH VOLTAGE ENGINEERING UNIT II-DIELECTRIC BREAKDOWN PART A

EE6701 HIGH VOLTAGE ENGINEERING UNIT II-DIELECTRIC BREAKDOWN PART A EE6701 HIGH VOLTAGE ENGINEERING UNIT II-DIELECTRIC BREAKDOWN PART A 1. Mention the gases used as the insulating medium in electrical apparatus? Most of the electrical apparatus use air as the insulating

More information

Comparison of Partial Discharge Characteristics for Different Defect Types in SF 6 Gas Insulation System

Comparison of Partial Discharge Characteristics for Different Defect Types in SF 6 Gas Insulation System Comparison of Partial Discharge Characteristics for Different Defect Types in SF 6 Gas Insulation System D.A. Mansour, T. Okusu, K. Nishizawa, H. Kojima, N. Hayakawa, F. Endo and H. Okubo Nagoya University

More information

Test method to assess the suitability of materials and surfaces to avoid problems from static electricity by measurement of capacitance loading

Test method to assess the suitability of materials and surfaces to avoid problems from static electricity by measurement of capacitance loading 1 of 15 JCI 12 October 2001 Test method to assess the suitability of materials and surfaces to avoid problems from static electricity by measurement of capacitance loading 1 Introduction This document

More information

Solid-state physics. Laue diagrams: investigating the lattice structure of monocrystals. LEYBOLD Physics Leaflets P

Solid-state physics. Laue diagrams: investigating the lattice structure of monocrystals. LEYBOLD Physics Leaflets P Solid-state physics Properties of crystals X-ray structural analysis LEYBOLD Physics Leaflets P7.1.2.2 Laue diagrams: investigating the lattice structure of monocrystals Objects of the experiment Evaluating

More information

Mir Md. Maruf Morshed

Mir Md. Maruf Morshed Investigation of External Acoustic Loadings on a Launch Vehicle Fairing During Lift-off Supervisors: Professor Colin H. Hansen Associate Professor Anthony C. Zander School of Mechanical Engineering South

More information

Consider a point P on the line joining the two charges, as shown in the given figure.

Consider a point P on the line joining the two charges, as shown in the given figure. Question 2.1: Two charges 5 10 8 C and 3 10 8 C are located 16 cm apart. At what point(s) on the line joining the two charges is the electric potential zero? Take the potential at infinity to be zero.

More information

CHAPTER 2 ESTIMATION OF BREAKDOWN VOLTAGES IN SMALL INSULATION GAPS AN EMPIRICAL APPROACH

CHAPTER 2 ESTIMATION OF BREAKDOWN VOLTAGES IN SMALL INSULATION GAPS AN EMPIRICAL APPROACH 17 CHAPTER 2 ESTIMATION OF BREAKDOWN VOLTAGES IN SMALL INSULATION GAPS AN EMPIRICAL APPROACH 2.1 INTRODUCTION Insulation materials of different types viz. gaseous, liquid and solid are used to make the

More information

UNIT I - INTRODUCTION SYLLABUS

UNIT I - INTRODUCTION SYLLABUS SEM / YEAR: VII/IV QUESTION BANK SUBJECT : EE670 HIGH VOLTAGE ENGINEERING UNIT I - INTRODUCTION SYLLABUS Causes of over voltages and its effects on power system Lightning, switching surges and temporary

More information

The Basic Capacitor. Water Tower / Capacitor Analogy. "Partnering With Our Clients for Combined Success"

The Basic Capacitor. Water Tower / Capacitor Analogy. Partnering With Our Clients for Combined Success CAPACITOR BASICS I How s Work The Basic A capacitor is an electrical device which serves to store up electrical energy for release at a predetermined time. In its most basic form, it is comprised of three

More information

Aging Assessment of High Voltage Single Component Room Temperature Vulcanized Silicone Rubber (RTV-1) Subjected to Aqueous Salt

Aging Assessment of High Voltage Single Component Room Temperature Vulcanized Silicone Rubber (RTV-1) Subjected to Aqueous Salt University of Denver Digital Commons @ DU Electronic Theses and Dissertations Graduate Studies 1-1-2016 Aging Assessment of High Voltage Single Component Room Temperature Vulcanized Silicone Rubber (RTV-1)

More information

A Novel Optimized Design for Busbar Structures using Finite Element Methods

A Novel Optimized Design for Busbar Structures using Finite Element Methods A Novel Optimized Design for Busbar Structures using Finite Element Methods Xiaojuan Sun 1, Shuhong Wang, Ruilei Gong,3 1 School of Electronic Information Engeering,Xi an Technological University Xi an,71001,china

More information

INSTITUTE OF AERONAUTICAL ENGINERING DUNDIGAL ELECTRICAL AND ELECTRONICS ENGINEERING

INSTITUTE OF AERONAUTICAL ENGINERING DUNDIGAL ELECTRICAL AND ELECTRONICS ENGINEERING INSTITUTE OF AERONAUTICAL ENGINERING DUNDIGAL ELECTRICAL AND ELECTRONICS ENGINEERING Course code : 067(07-08) Course title : High voltage engineering Course structure Lectures Tutorials Practical credits

More information

Fatima Michael College of Engineering & Technology

Fatima Michael College of Engineering & Technology ANNA UNIVERSITY AFFILIATED COLLEGES BE EEE SEMESTER VI EE2353 - HIGH VOLTAGE ENGINEERING UNIT IOVER VOLTAGES IN ELECTRICAL POWER SYSTEMS 1. What is surge arrester? 2. Name the sources of switching surges.

More information

Performance analysis of 1200 kv ceramic disc insulator string under normal and faulted conditions

Performance analysis of 1200 kv ceramic disc insulator string under normal and faulted conditions Available online at www.sciencedirect.com ScienceDirect Energy Procedia 75 (5 ) 4 9 The 7 th International Conference on Applied Energy ICAE5 Performance analysis of kv ceramic disc insulator string under

More information

WIESON TECHNOLOGIES CO., LTD.

WIESON TECHNOLOGIES CO., LTD. TABLE OF CONTENT 1. Scope.... 2 2. Reference Documents. 2 3. Material and Components.... 2 4. Design and Construction.... 2 5. Rating.. 2 6. Performance and Test Descriptions. 2 7. Test Requirements and

More information

THE EFFECT OF REVERSAL ON CAPACITOR LIFE

THE EFFECT OF REVERSAL ON CAPACITOR LIFE GENERAL ATOMICS ENERGY PRODUCTS Engineering Bulletin 96-004 THE EFFECT OF REVERSAL ON CAPACITOR LIFE November 2003 2003 Sorrento Electronics, Inc. Capacitor Engineering Department General Atomics Energy

More information