SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL

Similar documents
KINGS COLLEGE OF ENGINEERING Punalkulam

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

In the previous chapter, attention was confined

LO 1: Three Phase Circuits

University of Jordan Faculty of Engineering & Technology Electric Power Engineering Department

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION

Fault Analysis Power System Representation

Fault Calculation Methods

EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION

EEE3405 ELECTRICAL ENGINEERING PRINCIPLES 2 - TEST

SHORT QUESTIONS AND ANSWERS. Year/ Semester/ Class : III/ V/ EEE Academic Year: Subject Code/ Name: EE6501/ Power System Analysis

Module 3 : Sequence Components and Fault Analysis

ECE 325 Electric Energy System Components 7- Synchronous Machines. Instructor: Kai Sun Fall 2015

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A

ELEC Introduction to power and energy systems. The per unit system. Thierry Van Cutsem

Introduction to Synchronous. Machines. Kevin Gaughan

Lecture (5) Power Factor,threephase circuits, and Per Unit Calculations

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis

EE Branch GATE Paper 2010

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM

Week No. 6 Chapter Six: Power Factor Improvement

Power System Stability and Control. Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India

Chapter 3 AUTOMATIC VOLTAGE CONTROL

THE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session

RESULTS OF ON-GRID OPERATION OF SUPERCONDUCTOR DYNAMIC SYNCHRONOUS CONDENSER

Analysis of factors affecting station capacitor bank switching transients

1. Explain the various methods of methods of grounding. In power system, grounding or earthing means connecting frame of electrical equipment (non-cur

GENERATOR INTERCONNECTION APPLICATION

Chapter 1W Basic Electromagnetic Concepts

Generation, transmission and distribution, as well as power supplied to industrial and commercial customers uses a 3 phase system.

ROEVER COLLEGE OF ENGINEERING & TECHNOLOGY ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING ELECTRICAL MACHINES I

Power Factor Improvement

Electric Machines I Three Phase Induction Motor. Dr. Firas Obeidat

Chapter 8: Unsymmetrical Faults

Conventional Paper-I-2011 PART-A

Work, Energy and Power

CHAPTER 2 OVERVOLTAGE DUE TO SELF-EXCITATION AND INRUSH CURRENT DUE TO CAPACITOR SWITCHING

TRANSIENT ANALYSIS OF SELF-EXCITED INDUCTION GENERATOR UNDER BALANCED AND UNBALANCED OPERATING CONDITIONS

Brief Steady of Power Factor Improvement

Lesson 17: Synchronous Machines

QUESTION BANK ENGINEERS ACADEMY. Power Systems Power System Stability 1

Basics of Electric Circuits

CHAPTER 2 CAPACITANCE REQUIREMENTS OF SIX-PHASE SELF-EXCITED INDUCTION GENERATORS

UNIT I INTRODUCTION Part A- Two marks questions

ECEN 460 Exam 1 Fall 2018

EE 742 Chapter 3: Power System in the Steady State. Y. Baghzouz

Power and Energy Measurement

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous)

Power and Energy Measurement

We Make Energy Engaging. Improving Your Power Factor

EE2351 POWER SYSTEM ANALYSIS

CHAPTER 5 STEADY-STATE ANALYSIS OF THREE-PHASE SELF-EXCITED INDUCTION GENERATORS

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA.

Cahier Technique N 13 Principe de réduction des courants d enclenchement des transformateurs

ELECTRIC POWER CIRCUITS BASIC CONCEPTS AND ANALYSIS

Generators. What its all about

POWER SEMICONDUCTOR BASED ELECTRIC DRIVES

CHAPTER 3 ANALYSIS OF THREE PHASE AND SINGLE PHASE SELF-EXCITED INDUCTION GENERATORS

Work, Energy and Power

GATE 2010 Electrical Engineering

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA

BASIC PRINCIPLES. Power In Single-Phase AC Circuit

Electrical Machines and Energy Systems: Operating Principles (Part 2) SYED A Rizvi

Behaviour of synchronous machine during a short-circuit (a simple example of electromagnetic transients)

Harmonic Modeling of Networks

Symmetrical Fault Current Calculations Unlv

Synchronous Machines

POWER SYSTEM STABILITY AND CONTROL

F F FAULT CURRENT Prospective. 1. Introduction. 2. Types of fault conditions

Lecture 05 Power in AC circuit

ELG4125: Power Transmission Lines Steady State Operation

VTU E-LEARNING NOTES ON:

Comparative Study of Synchronous Machine, Model 1.0 and Model 1.1 in Transient Stability Studies with and without PSS

7. Transient stability

ELECTRICALMACHINES-I QUESTUION BANK

Technical Concepts - Fault Analysis Methods

Module 3 : Sequence Components and Fault Analysis

CHAPTER 6 STEADY-STATE ANALYSIS OF SINGLE-PHASE SELF-EXCITED INDUCTION GENERATORS

Refresher course on Electrical fundamentals (Basics of A.C. Circuits) by B.M.Vyas

Final Exam, Second Semester: 2015/2016 Electrical Engineering Department

DHANALAKSHMI SRINIVASAN COLLEGE OF ENGINEERING AND TECHNOLOGY Mamalapuram Chennai QUESTION BANK V SEMESTER. EE6501-Power system Analysis

EE 451 Power System Stability

Tutorial on Shunt Capacitor Banks Design, Application and Protection Considerations

MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION

SECOND ENGINEER REG III/2 MARINE ELECTRO-TECHNOLOGY. 1. Understands the physical construction and characteristics of basic components.

Q. 1 Q. 25 carry one mark each.

UNIT- I Phase Sequence:

Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science Electric Machines

Faults on Electrical System. A Research

Control of Wind Turbine Generators. James Cale Guest Lecturer EE 566, Fall Semester 2014 Colorado State University

CHAPTER 5 SIMULATION AND TEST SETUP FOR FAULT ANALYSIS

11. AC Circuit Power Analysis

A GENERALISED OPERATIONAL EQUIVALENT CIRCUIT OF INDUCTION MACHINES FOR TRANSIENT/DYNAMIC STUDIES UNDER DIFFERENT OPERATING CONDITIONS

ECE 421/521 Electric Energy Systems Power Systems Analysis I 2 Basic Principles. Instructor: Kai Sun Fall 2013

Sinusoidal Response of RLC Circuits

ECE 420. Review of Three Phase Circuits. Copyright by Chanan Singh, Panida Jirutitijaroen, and Hangtian Lei, For educational use only-not for sale.

Power System Engineering Prof. Debapriya Das Department of Electrical Engineering Indian Institute of Technology, Kharagpur

EE 3120 Electric Energy Systems Study Guide for Prerequisite Test Wednesday, Jan 18, pm, Room TBA

GATE 2008 Electrical Engineering

IGEE 402 Power System Analysis. FINAL EXAMINATION - SAMPLE Fall 2004

Transcription:

1 SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL Power Systems: Generation, Transmission and Distribution Power Systems: Generation, Transmission and Distribution Power Systems: Generation, Transmission and Distribution ENGINEERS INSTITUTE OF INDIA 017 All Rights Reserved www.sscje.com

C O N T E N T 1. BASICS OF POWER SYSTEM.. 3-10. CABLES. 11-19 3. DIFFERENT TYPESOF POWER STATION.. 0-63 4. TRANSMISSION AND DISTRIBUTION.. 64-80 5. PROTECTION SYSTEM.. 81-95 ENGINEERS INSTITUTE OF INDIA 017 All Rights Reserved www.sscje.com

3 CHAPTER-1 BASICS OF POWER SYSTEM INTRODUCTION A system of n vectors or quantities may be resolved, when n is prime, into n different symmetrical groups or systems, one of which consists of n equal vectors and the remaining (n -1) systems consist of n equispaced vectors which with the first mentioned group of equal vectors forms an equal number of symmetrical n-phase systems... 3-PHASE SYSTEMS Any three coplanar vectors V a, V b and V c can be expressed in terms of three new vectors V 1, V and V 3 with constant coefficients. Each of the original vectors has been replaced by a set of three vectors making a total ofnine vectors. To simplify the calculations two conditions should be satisfied in selecting systems of components to replace 3- phase current and voltage vectors: Fortescue's theorem, the three unbalanced vectors V a, V b and V c can be replaced by a set of three balanced systems of vectors. Therefore, the solution is unique. A balanced system of three vectors is one in which the vectors are equal in magnitude and are equi-spaced. 1. Positive sequence component equal magnitude but displaced by 10 and same phase sequence as the original vectors.. Negative sequence component equal magnitude but displaced by 10 and the phase sequence opposite to the original vectors. 3. Zero sequence component equal magnitude and also are in phase with each other. (A) (B) (C) FigURE: (A) Positive sequence component; (b) Negative sequence component; (c) Zero sequence component ENGINEERS INSTITUTE OF INDIA 017 All Rights Reserved www.sscje.com

FAULT CALCULATIONS Classified as: 1. shunt faults (short circuits). series faults (open conductor) shunt type of faults involve power conductor or conductors-to-ground or short circuit between conductors. one or two phases opened is called series type of faults. shunt faults are characterized by increase in current and fall in voltage and frequency whereas series faults are characterized by increase in voltage and frequency and fall in current in the faulted phases. shunt type of faults are classified as (i) line-to-ground fault (ii) line-to-line fault; (i) double line-to-ground fault (iv) 3-phase fault The first three unsymmetrical faults. the method of symmetrical components will be utilized to analyses the unbalancing in the system the 3-phase fault is a balanced fault. The series faults are classified (i) one open conductor (ii) two open conductors Voltage of the neutral The potential of the neutral when it is grounded through some impedance or is isolated, will not be at ground potential under unbalanced conditions such as unsymmetrical faults. the potential of the neutral is given as v n = i n z n, where z n is the neutral grounding impedance and i n the neutral current. here negative sign is used as the current flows from the ground to the neutral of the system and potential of the neutral is lower than the ground. for a 3-phase system, 4 n a b c ()()() a1 a a0 a1 a a0 a1 a a0 I I I I I I I I I I I I I a1(1)(1) 3 3a a0 a0 I I I I V 3I Z a a0 n Question: A - 3 T.L. supplies delta connected load line current in R-phase is 100A. Taking the current in R-phases is 100A. Taking the current in R-phase as reference find symmetry components of line current if phase-b is switched off. Assumed line current in Y-phase as 100 180 A. Solution: Given system is delta connected. Load current Flowing in R-phase = I R = 1000 0 Flowing in Y-phase = I Y = 100180º Flowing in R-phase = I B = 0 ENGINEERS INSTITUTE OF INDIA 017 All Rights Reserved www.sscje.com

We know 5 I R 1 1 1 I 0 1 IR 1 1 K K I Y 3 IR 1 K K IB R 1 I R I 1 R K IY K I 1 B 3 100 100 180 1 10 57.74 330 3 Since R1, Y1, B1 is displaced by 110 as for default R.Y.B. phase Y R R I I 40 K I 57.7310 1 1 1 I I 110 K I 57.7390 B R R 1 1 1 As the negative phase sequence is opposite to the original signal IY KI 57.73 150 R A IB K I 57.73 70 B A Severity of faults: Three-phase (3L) faults 5% Double line-to-grounded (LLG) faults 10% Double line (LL) faults 15% Single line-to-ground (LG) faults 70% Calculation of 3-phase Short-Circuit Currents The impedance of the alternator grows from the instant of short circuit to the steady state condition. Which impedance should be considered for evaluating the short-circuit currents, depends upon whether sub transient, transient or steady state short circuit current is required. The p.u. impedance of equipment = IZ V. ENGINEERS INSTITUTE OF INDIA 017 All Rights Reserved www.sscje.com

Where Z is the impedance of the equipment in ohms and I and V are the rated current and voltage respectively. 6 Now I V / Z SC Z p. u. IZ I IV V I I V SC SC If VI is the base or full load volt-amperes and VISC the short-circuit volt-amperes, then Z p. u. Base or full load volt amperes Short circuit volt amperes Base or full load MVA S. C. MVA Z p. u. Selection of Circuit Breakers Two of the circuit breaker ratings which require the computation of SC current are: rated momentary current and rated symmetrical interrupting current. Symmetrical SC current is obtained by using sub transient reactance for synchronous machines. Momentary current (rms) is then calculated by multiplying the s ymmetrical momentary current by a factor of 1.8 to account for the presence of DC off-set current. The current that a circuit breaker can interrupt is inversely proportional to the operating voltage over a certain range, i.e., Amperes at operating voltage = rated voltage Amperes at rated voltage operating voltage Rated interrupting MVA (three-phase) capacity 3 () V line () I line rated rated int errupting current V (line) is in kv and I(line) is in ka Three-phase SC MVA to be interrupted, where SC (MVA) (3-phase) = 3 pre fault line voltage in kv SC CURRENT IN KA. ENGINEERS INSTITUTE OF INDIA 017 All Rights Reserved www.sscje.com

If voltage and current are in per unit values on a three-phase basis 7 SC MVA(3) phase V () I MVA perfault SC Base Rated MVA interrupting capacity of a circuit breaker is to be more than (or equal to) the SC MVA required to be interrupted. A three-phase fault though rare is generally the one which gives the highest SC MVA and a circuit breaker must be capable of interrupting it. A three-phase (3L) fault being the most severe must be used to calculate the rupturing capacity of circuit breakers. Methods for Power Factor Improvement The following devices and equipment are used for Power Factor Improvement. 1. Static Capacitor. Synchronous Condenser 3. Phase Advancer 1. Static Capacitor We know that most of the industries and power system loads are inductive that take lagging current which decrease the system power factor. For Power factor improvement purpose, Static capacitors are connected in parallel with those devices which work on low power factor. These static capacitors provide leading current which neutralize (totally or approximately) the lagging inductive component of load current (i.e. leading component neutralize or eliminate the lagging component of load current) thus power factor of the load circuit is improved. These capacitors are installed in Vicinity of large inductive load e.g Induction motors and transformers etc, and improve the load circuit power factor to improve the system or devices efficiency. Suppose, here is a single phase inductive load which is taking lagging current (I) and the load power factor is cosθ as shown in fig-1. ENGINEERS INSTITUTE OF INDIA 017 All Rights Reserved www.sscje.com

In fig-, a Capacitor (C) has been connected in parallel with load. Now a current (Ic) is flowing through Capacitor which lead 90 from the supply voltage ( Note that Capacitor provides leading Current i.e., In a pure capacitive circuit, Current leading 90 from the supply Voltage, in other words, Voltage are 90 lagging from Current). The load current is (I). The Vectors combination of (I) and (Ic) i s (I ) which is lagging from voltage at θ as shown in fig 3. 8 It can be seen from fig 3 that angle of θ < θ1 i.e. angle of θ is less than from angle of θ. Therefore Cosθ is less than from Cosθ1 (Cosθ> Cosθ1). Hence the load power factor is improved by capacitor. Also note that after the power factor improvement, the circuit current would be less than from the low power factor circuit current. Also, before and after the power factor improvement, the active component of current would be same in that circuit because capacitor eliminates only the re-active component of current. Also, the Active power (in Watts) would be same after and before power factor improvement. Advantages: Capacitor bank offers several advantages over other methods of power factor improvement. Losses are low in static capacitors There is no moving part, therefore need low maintenance It can work in normal conditions (i.e. ordinary atmospheric conditions) Do not require a foundation for installation They are lightweight so it is can be easy to installed Disadvantages: The age of static capacitor bank is less (8 10 years) With changing load, we have to ON or OFF the capacitor bank, which causes switching surges on the system If the rated voltage increases, then it causes damage it Once the capacitors spoiled, then repairing is costly. Synchronous Condenser ENGINEERS INSTITUTE OF INDIA 017 All Rights Reserved www.sscje.com

When a Synchronous motor operates at No-Load and over-exited then it s called a synchronous Condenser. Whenever a Synchronous motor is over-exited then it provides leading current and works like a capacitor. 9 When a synchronous condenser is connected across supply voltage (in parallel) then it draws leading current and partially eliminates the re-active component and this way, power factor is improved. Generally, synchronous condenser is used to improve the power factor in large industries. Advantages: Long life (almost 5 years) High Reliability Step-less adjustment of power factor. No generation of harmonics of maintenance The faults can be removed easily It s not affected by harmonics. Require Low maintenance (only periodic bearing greasing is necessary) Disadvantages: It is expensive (maintenance cost is also high) and therefore mostly used by large power users. An auxiliary device has to be used for this operation because synchronous motor has no self starting torque It produces noise 3. Phase Advancer Phase advancer is a simple AC exciter which is connected on the main shaft of the motor and operates with the motor s rotor circuit for power factor improvement. Phase advancer is used to improve the power factor of induction motor in industries. As the stator windings of induction motor takes lagging current 90 out of phase with Voltage, therefore the power factor of induction motor is low. If the exciting ampere-turns are excited by external AC ENGINEERS INSTITUTE OF INDIA 017 All Rights Reserved www.sscje.com

source, then there would be no effect of exciting current on stator windings. Therefore the power factor of induction motor will be improved. This process is done by Phase advancer. 10 Advantages: Lagging kvar (Reactive component of Power or reactive power) drawn by the motor is sufficiently reduced because the exciting ampere turns are supplied at slip frequency (fs). The phase advancer can be easily used where the use of synchronous motors is Unacceptable Disadvantage: Using Phase advancer is not economical for motors below 00 H.P. (about 150kW) Power Factor Improvement in single phase and three phase star & delta connections Power factor improvement in three phase system by connecting a capacitor bank in (1). Delta connection (). Star Connection) ENGINEERS INSTITUTE OF INDIA 017 All Rights Reserved www.sscje.com