EE5250 TERM PROJECT. Report by: Akarsh Sheilendranath

Similar documents
PowerApps Optimal Power Flow Formulation

Optimal Placement and Sizing of Distributed Generators in 33 Bus and 69 Bus Radial Distribution System Using Genetic Algorithm

CHAPTER 2 LOAD FLOW ANALYSIS FOR RADIAL DISTRIBUTION SYSTEM

Simultaneous placement of Distributed Generation and D-Statcom in a radial distribution system using Loss Sensitivity Factor

Performance Improvement of the Radial Distribution System by using Switched Capacitor Banks

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis

Congestion Alleviation using Reactive Power Compensation in Radial Distribution Systems

Optimal Placement & sizing of Distributed Generator (DG)

Optimal Capacitor placement in Distribution Systems with Distributed Generators for Voltage Profile improvement by Particle Swarm Optimization

Chapter 8 VOLTAGE STABILITY

Elevated Neutral to Earth Voltages Due to Harmonics A T&D Update

A PROPOSED STRATEGY FOR CAPACITOR ALLOCATION IN RADIAL DISTRIBUTION FEEDERS

Analytical approaches for Optimal Placement and sizing of Distributed generation in Power System

THE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session

Analytical Study Based Optimal Placement of Energy Storage Devices in Distribution Systems to Support Voltage and Angle Stability

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

PROPOSED STRATEGY FOR CAPACITOR ALLOCATION IN RADIAL DISTRIBUTION FEEDERS

KINGS COLLEGE OF ENGINEERING Punalkulam

K. Valipour 1 E. Dehghan 2 M.H. Shariatkhah 3

EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION

= V I = Bus Admittance Matrix. Chapter 6: Power Flow. Constructing Ybus. Example. Network Solution. Triangular factorization. Let

The AR OPF: an Exact Convex Formulation for the Optimal Power Flow in Radial Distribution Networks

EE 742 Chapter 3: Power System in the Steady State. Y. Baghzouz

Fault Calculation Methods

OPTIMAL CAPACITOR PLACEMENT USING FUZZY LOGIC

Optimal DG allocation and sizing in a Radial Distribution System using Analytical Approach

ELG4125: Power Transmission Lines Steady State Operation

Distributed vs Bulk Power in Distribution Systems Considering Distributed Generation

A Study of the Factors Influencing the Optimal Size and Site of Distributed Generations

Performance analysis and comparison of load flow methods in a practical distribution system

J. Electrical Systems x-x (2010): x-xx. Regular paper

Distribution System s Loss Reduction by Optimal Allocation and Sizing of Distributed Generation via Artificial Bee Colony Algorithm

mywbut.com Lesson 16 Solution of Current in AC Parallel and Seriesparallel

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK

Module 4. Single-phase AC circuits. Version 2 EE IIT, Kharagpur

Mitigation of Distributed Generation Impact on Protective Devices in a Distribution Network by Superconducting Fault Current Limiter *

ELEC4612 Power System Analysis Power Flow Analysis

Voltage Stability Monitoring using a Modified Thevenin Impedance

Simulation of Random Variation of Three-phase Voltage Unbalance Resulting from Load Fluctuation Using Correlated Gaussian Random Variables

CAPACITOR PLACEMENT IN UNBALANCED POWER SYSTEMS

Brief Steady of Power Factor Improvement

Last Comments on Short-Circuit Analysis

Determination of Optimal Location and Sizing of Distributed Generator in Radial Distribution Systems for Different Types of Loads

SHORT QUESTIONS AND ANSWERS. Year/ Semester/ Class : III/ V/ EEE Academic Year: Subject Code/ Name: EE6501/ Power System Analysis

Farzaneh Ostovar, Mahdi Mozaffari Legha

Enhanced Newton Method Based Radial Distribution System Load Flow Analysis with Extrapolation Techniques

STEADY STATE NETWORK EQUIVALENTS FOR LARGE ELECTRICAL POWER SYSTEMS THESIS. Submitted in Partial Fulfillment. of the REQUIREMENTS for the.

ECE 476. Exam #2. Tuesday, November 15, Minutes

OPTIMAL LOCATION AND SIZING OF DISTRIBUTED GENERATOR IN RADIAL DISTRIBUTION SYSTEM USING OPTIMIZATION TECHNIQUE FOR MINIMIZATION OF LOSSES

Incorporation of Asynchronous Generators as PQ Model in Load Flow Analysis for Power Systems with Wind Generation

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION

Optimal Location and Sizing of Distributed Generation Based on Gentic Algorithm

Optimal Compensation of Reactive Power in Transmission Networks using PSO, Cultural and Firefly Algorithms

Optimal Placement of Multi DG Unit in Distribution Systems Using Evolutionary Algorithms

Deregulated Electricity Market for Smart Grid: A Network Economic Approach

Long-term voltage stability : load aspects

THE introduction of competition in the electricity sector

The Power Flow & Optimal Power Flow Problems

POWER SYSTEM STABILITY

Journal of Artificial Intelligence in Electrical Engineering, Vol. 1, No. 2, September 2012

State Estimation and Power Flow Analysis of Power Systems

Optimal Capacitor Placement and Sizing on Radial Distribution System by using Fuzzy Expert System

Estimating Feasible Nodal Power Injections in Distribution Networks

Role of Synchronized Measurements In Operation of Smart Grids

An Improved Method for Determining Voltage Collapse Proximity of Radial Distribution Networks

Assessment of Available Transfer Capability Incorporating Probabilistic Distribution of Load Using Interval Arithmetic Method

Power Flow Analysis of Radial Distribution System using Backward/Forward Sweep Method

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous)

Power System Engineering Prof. Debapriya Das Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Optimal Placement And Sizing Of Dg Using New Power Stability Index

Optimal Power Flow in Distribution Networks

STATE ESTIMATION IN DISTRIBUTION SYSTEMS

A STATIC AND DYNAMIC TECHNIQUE CONTINGENCY RANKING ANALYSIS IN VOLTAGE STABILITY ASSESSMENT

1 Unified Power Flow Controller (UPFC)

Transmission and Distribution of Electrical Power

Chapter 8: Unsymmetrical Faults

Chapter 3 AUTOMATIC VOLTAGE CONTROL

Alectra Utilities List of Station Capacity

Optimal Capacitor Placement in Distribution System with Random Variations in Load

, and ignoring all load currents, determine

Exercise Dr.-Ing. Abdalkarim Awad. Informatik 7 Rechnernetze und Kommunikationssysteme

Locating Distributed Generation. Units in Radial Systems

Harmonic Modeling of Networks

EE 581 Power Systems. Admittance Matrix: Development, Direct and Iterative solutions

A Novel Technique to Improve the Online Calculation Performance of Nonlinear Problems in DC Power Systems

Meta Heuristic Harmony Search Algorithm for Network Reconfiguration and Distributed Generation Allocation

ELECTRIC POWER CIRCUITS BASIC CONCEPTS AND ANALYSIS

Optimal capacitor placement and sizing via artificial bee colony

The Effect of the Harmonics, the Fault Location and the Fault Resistance on the Performance of the Impedance-Type Distance Relay

Optimal Conductor Selection in Radial Distribution System using Plant Growth Simulation Algorithm

CHAPTER 5 STEADY-STATE ANALYSIS OF THREE-PHASE SELF-EXCITED INDUCTION GENERATORS

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 03 Issue: 03 Mar p-issn:

Geometry of power flows and convex-relaxed power flows in distribution networks with high penetration of renewables

ECE 325 Electric Energy System Components 5 Transmission Lines. Instructor: Kai Sun Fall 2015

Grid Issues and Challenges Addressed by High Temperature Superconductor (HTS) Technology

OPTIMAL DG AND CAPACITOR ALLOCATION IN DISTRIBUTION SYSTEMS USING DICA

DHANALAKSHMI SRINIVASAN COLLEGE OF ENGINEERING AND TECHNOLOGY Mamalapuram Chennai QUESTION BANK V SEMESTER. EE6501-Power system Analysis

APPLICATIONS OF CONTROLLABLE SERIES CAPACITORS FOR DAMPING OF POWER SWINGS *

The N k Problem using AC Power Flows

Modelling and Simulation of TCPAR for Power System Flow Studies

Transcription:

EE5250 TERM PROJECT Analytical Approaches for Optimal Placement of Distributed Generation Sources in Power System Caisheng Wang, student member, IEEE, and M. Hashem Nehrir, senior member, IEEE Report by: Akarsh Sheilendranath

TABLE OF CONTENTS I. INTRODUCTION... 3 II. OPTIMAL PLACEMENT OF DG ON A RADIAL FEEDER... 3 A. Theoretical Analysis... 4 B. Procedure to Find the Optimal Location of DG on a Radial Feeder... 8 C. Case Studies with Time Invariant Loads and DGs... 9 D. Case Study with Time Varying Load and DG... 10 III. OPTIMAL PLACEMENT OF DG IN NETWORKED SYSTEMS... 11 A. Procedure to find the optimal location of a DG on a network... 13 IV. SIMULATION RESULTS AND CONCLUSIONS... 14 A. RADIAL FEEDER WITH TIME INVARIANT LOADS AND DG... 14 1. Uniformly Distributed Loads... 14 2. Centrally Distributed Load... 15 3. Increasingly Distributed Load... 16 B. NETWORKED SYSTEMS... 18 REFERENCES... 19

I. INTRODUCTION Power system deregulation and the shortage of transmission capacities have led to increased interest in distributed generation (DG) sources. To obtain maximum potential benefits of DGs in power systems optimal placement of these DG sources in the power system grid becomes an important factor. Distributed generation (DG) devices can be strategically placed in power systems for grid reinforcement, reducing power losses and on-peak operating costs, improving voltage profiles and load factors, deferring or eliminating for system upgrades, and improving system integrity, reliability, and efficiency. These DG sources are normally placed close to consumption centers and are added mostly at the distribution level. They are relatively small in size (relative to the power capacity of the system in which they are placed) and modular in structure. A common strategy to find the site of DG is to minimize the power loss of the system. Another method for placing DG is to apply rules that are often used in sitting shunt capacitors in distribution systems. For example, a 2/3 rule is to place DG on a radial feeder with uniformly distributed load, which suggests to install DG of approximately 2/3 capacity of the incoming generation at approximately 2/3 of the length of line. This rule is simple and easy to use, but it cannot be applied directly to a feeder with other types of load distribution, or to a networked system. This report examines different analytical approaches for optimal placement of DG with unity power factor in power systems. First, placement of DG in a radial feeder is analyzed and the theoretical optimal site (bus) for adding DG is obtained for different types of loads and DG sources. Then, a method is presented to find the optimal bus for placing DG in a networked system based on bus admittance matrix, generation information and load distribution of the system. In practice, there are more constraints on the availability of DG sources, and we may only have one or a few DGs with limited output available to add. Therefore, in this study the DG size is not considered to be optimized. The procedure to determine the optimal bus for placing DG may also need to take into account other factors, such as economic and geographic considerations. These factors are not taken into account while examining the approaches presented. II. OPTIMAL PLACEMENT OF DG ON A RADIAL FEEDER To simplify the analysis, only overhead transmission lines with uniformly distributed parameters are considered, i.e., R and L per unit length are the same along the feeder while C and G per unit length are neglected. The loads along the feeder are assumed to vary in discrete time duration; for example, the feeder load distributions along the line for time durations Ti and Ti+1 are shown in Fig. 1.

.. from [1] A. Theoretical Analysis First consider a radial feeder without DG. During the time duration Ti, the loads are distributed along the line with the phasor current density Id(x, Ti) as shown in Fig. 1. The phasor feeder current at point is Assuming the impedance per unit length of the line is Z = (R + jx) Ohm/Km, then the incremental power loss and phasor voltage drop at point x are

The total power loss along the feeder within the time duration Ti is The voltage drop between point and the receiving end is and the voltage at point x is

The total voltage drop across the feeder is Now, let us consider a DG is added into the feeder at the location x0, shown in Fig. 1. In general, the load current density Id(x, Ti) will change (normally decrease) as a result of adding DG due to improvements in the voltage profile along the line. This change in the load current density will cause the feeder current to decrease. The feeder current between the source (at x = l) and the location of DG (at x = x0) will also change as a result of the injected current source. However, the change in feeder current due to the change in the load current density is generally much smaller than the change in the feeder current due to the injected current. For the purpose of analysis, the change in the load current density, resulted from the addition of DG, is neglected in the paper. Therefore, the load current density, used in equation (1), is also used for obtaining the feeder current after adding DG. In this case, the feeder current can be written as follows:

The corresponding power loss and voltage drop in the feeder are The average power loss in a given time period T is Where Nt is the number of time durations in the time period T Equation (6) can still be used under this situation to calculate the voltage at point by using Vdrop (x, Ti) obtained from equation (10).

B. Procedure to Find the Optimal Location of DG on a Radial Feeder The goal is to add DG in a location to minimize the total average power loss and assure that the voltages Vx along the feeder are in the acceptable range, 1+/- 0.05 p.u., i.e., The solution x0 of the above equation will give the optimal site for minimizing the power loss, but it cannot guarantee that all the voltages along the feeder are in the acceptable range. If the voltage regulation cannot be satisfied at the same time, the DG can be placed around x0 to satisfy the voltage regulation rule while decreasing the power loss as much as possible or the DG size can be increased. The analytical procedure to determine the optimal point to place DG on a radial feeder is given as follows. 1) Find the distributed load Id(x, Ti) along the feeder. 2) Get the output current of DG, IDG(Ti). 3) Use equations (9) and (11) to calculate Ploss(x0) and find the solution x0 of equation (13). 4) Use equations (6) and (10) to check whether the voltage regulation is satisfied. 5) If all the voltages are in the acceptable range, then the calculated x0 is the optimal spot xop to add DG. 6) If doesn t meet the voltage regulation rule, then move the DG to see whether there is a point around point x0, where all bus voltages are in the acceptable range. 7) If no point on the feeder can satisfy the voltage regulation rule, then increase the size of DG and repeat steps 2) to 7). 8) Sometimes more than one DG may be needed. Under this situation, the feeder can be divided into several segments and steps 1) to 7) can be applied to each segment.

C. Case Studies with Time Invariant Loads and DGs Table I shows the results of analyses, using the foregoing procedure, to find the optimal location for placing DG on radial feeders with three different load distributions: uniformly distributed load, centrally distributed load and uniformly increasing distributed load. In the results given in Table I, it is assumed that the DG supplies all the loads on the feeder in each case, and the distribution system supplies the system losses. It is noted from this table that the DG reduces the system power losses significantly when it is located properly. The 2/3 rule works well when the load is uniformly distributed along the feeder, but it gives inaccurate results if the load configuration is different. For a uniformly distributed load, if the DG supplies 2/3 of the total load (IDG = Ildl 2 / 6), the optimal site is at (x0 = l / 3) according to equation (9). This result is exactly the same as that of the 2/3 rule. However, when the loads are centrally and increasingly distributed and the DG provides 2/3 of the total load, the optimal location for placing DG turns out to be and, respectively, which differ from what the 2/3 rule.

D. Case Study with Time Varying Load and DG The same feeders studied in part C, but with time varying load and DG, are analyzed in this case. The analysis is given for uniformly distributed load only. The analyses for other types of loads follow similarly. Assuming that DG is located at point x0, and then according to equation (9), the effective power loss is is the load current at the very sending end of the feeder. The average power loss in a given time period T is Assuming that all bus voltages along the feeder are in the acceptable range, (16) can be approximated as duration Ti. is the total load along the feeder in the time

III. OPTIMAL PLACEMENT OF DG IN NETWORKED SYSTEMS The theoretical analysis for placing a DG in networked systems is different and more complicated than in a radial feeder. To simplify the analysis, only one DG is considered to be added to the system..from [1] Consider the system shown in Fig. 2 above with a DG added to the system to reinforce it. The system has N buses and loads, and the DG is located at a bus, say bus j. The main external power is injected into bus 1, which is taken as slack bus. The objective is to find the bus to install the DG so that the total system power loss is minimized and the voltage level at each bus is held in the acceptable range, 1+/- 0.05 p.u. Before the DG is added to the system, the bus admittance matrix is Where superscript 0 denotes the original system. Assuming that the DG is located at bus j, the system admittance matrix is changed from to by considering that bus 1 and bus j are connected together. Actually there is no line to connect those buses together, but the imaginary line will help in finding the optimal location to add DG. is one dimension less than except when the DG is located at bus 1. If the DG is at bus 1, matrix will be the same as. To obtain the new matrix when the DG source is connected, we treat the system as connecting bus 1 and j by eliminating bus j in.

The new matrix is The new bus impedance matrix Zbus is (20) Suppose the complex load and the generated power of the original system is A new load vector SL is setup as follows

At the slack bus, SL1 = 0; it is assumed that the real and reactive power consumed by the load are supplied directly by the external generation at that bus. Also at P-V bus, QLi = 0; it is assumed that the load reactive power can be supplied by the external power source at the P-V bus. A. Procedure to find the optimal location of a DG on a network. To find the optimal point to place the DG, we set up an objective function for DG at each bus as follows: The theoretical procedure to find the optimal bus to place DG in a networked system can be summarized as follows. 1) Find the matrix and set up the load vector SL.

2) Compute and the corresponding Zbus for different DG locations. 3) Calculate the equivalent resistances according to equation (24). 4) Use equations (23) and (25) to calculate objective function values for DG at different buses and find the optimal bus m. 5) If all the voltages are in the acceptable range when the DG is located at bus m, then bus m is the optimal site. 6) If some bus voltages do not meet the voltage rule, then move the DG around bus m to satisfy the voltage rule. 7) If there is no bus that can satisfy the voltage regulation rule, try a different size DG and repeat steps 5) and 6). This method can be easily extended to the systems with multiple DG sources. By connecting all the DG buses and slack bus together through imaginary lines, the new matrix and the corresponding objective function can be established. IV. SIMULATION RESULTS AND CONCLUSIONS I carried out some simulations using the Power World Simulator 8.0 TM to verify the results obtained analytically by the author of my main reference journal. The screenshots of the simulations are presented below. It was verified that the simulation results agree well with the theoretical values. A. RADIAL FEEDER WITH TIME INVARIANT LOADS AND DG 1. Uniformly Distributed Loads

a) Results From the simulation it was observed that the power losses were lowest when the DG was located at BUS 6 which is also the optimal location for the DG as suggested by the theoretical analysis presented above. Screenshot of case summary when the DG is located at BUS 6. Losses are observed to be minimum (losses = 0.20 MW) 2. Centrally Distributed Load a) Results Again, from the simulation it was observed that the power losses were lowest when the DG was located at BUS 6 which is also the optimal location for the DG as suggested by the theoretical analysis presented above.

Screenshot of case summary when the DG is located at BUS 6. Losses are observed to be minimum (losses = 0.02 MW) 3. Increasingly Distributed Load

a) Results From the simulation it was observed that the power losses were lowest when the DG was located at BUS 8 (as shown above) which is also the optimal location for the DG as suggested by the theoretical analysis presented. Screenshot of case summary when the DG is located at BUS 8. Losses are observed to be minimum (losses = 0.05 MW)

B. NETWORKED SYSTEMS The simulation screenshot presented below is that of an IEEE 25kV 6-bus system which can be considered as a sub-transmission /distribution system. All the line parameters and bus voltages for this system was obtained from my main reference journal. The simulation results obtained were the same as that obtained from the proposed analytical method. Screenshot of case summary when the DG is located at BUS 3. Losses are observed to be minimum (losses = 0.21 MW)

REFERENCES [1] Analytical Approaches for Optimal Placement of Distributed Generation Sources in Power Systems Caisheng Wang, student member, IEEE, and M. Hashem Nehrir, senior member, IEEE [2] Power System Analysis and Design J. Duncan Glover and M S Sarma