Study of a Transformer Thermal System

Similar documents
Extensions to the Finite Element Technique for the Magneto-Thermal Analysis of Aged Oil Cooled-Insulated Power Transformers

Estimation of Current Transformer Insulation Life with an Effect of Environmental Variables

THERMAL BEHAVIOR OF DISTRIBUTION TRANSFORMERS IN SUMMERTIME AND SEVERE LOADING CONDITIONS

Chapter 6: Efficiency and Heating. 9/18/2003 Electromechanical Dynamics 1

Accurate Location of Transformer Hottest Spot by FEM and Thermal Models

Introduction to Heat and Mass Transfer. Week 7

HOTTEST SPOT AND LIFE EVALUATION OF POWER TRANSFORMER DESIGN USING FINITE ELEMENT METHOD

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 18, NO. 4, OCTOBER

Dr. Michael Müller. Thermal Management for LED applications

Experimental study of dynamic thermal behaviour of an 11 kv distribution transformer

Thermal Modeling of Electrical Transformers

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

A dynamic model of electric resistor's warming and its verification by micro-thermocouples

Determining Thermal Life Expectancy Of Power Transformer Under Non Linear Loads Using FEM By ANSYS And MATLAB

TYPE. max. working voltage 250 V 350 V 500 V 750 V. max. overload voltage 500 V 700 V 1000 V 1500 V. basic specifications IEC B

Experiment 1. Measurement of Thermal Conductivity of a Metal (Brass) Bar

Sensors and Actuators Sensors Physics

Application of Artificial Neural Networks in Evaluation and Identification of Electrical Loss in Transformers According to the Energy Consumption

Calculation and Characteristic Research of Temperature Rise for Motor Temperature Field

Double Layer Capacitors. PN: NEX_ series & NED_ series

Lecture 4: Losses and Heat Transfer

TYPE. 250 ppm / 200 ppm /

Technical Notes. Introduction. PCB (printed circuit board) Design. Issue 1 January 2010

Understanding Hot-Wire Anemometry

DUBLIN INSTITUTE OF TECHNOLOGY Kevin Street, Dublin 8.

Study and Characterization of the Limiting Thermal Phenomena in Low-Speed Permanent Magnet Synchronous Generators for Wind Energy

ELEC9712 High Voltage Systems. 1.2 Heat transfer from electrical equipment

Damping resistor design consideration

Thermal Calculation for Linear Regulator

Sensing, Computing, Actuating

O Plus Dry Bushing 69 kv system, 350 kv BIL, 3000 A. Table of contents

Thermal Properties of Power Terminals in High Power IGBT Modules

VALIDATION OF CFD ANALYSIS OF NATURAL CONVECTION CONDITIONS FOR A RESIN DRY-TYPE TRANSFORMER WITH A CABIN.

If there is convective heat transfer from outer surface to fluid maintained at T W.

Energy saving in electromechanical equipment with power coefficient correction. Dimitris Al. Katsaprakakis Aeolian Land S.A.

The Electrodynamics of a Pair of PV Modules with Connected Building Resistance

Metallized polyester film capacitors MKT 470

Jerad P. 10/1/2015. Motor Thermal Limits on Torque Production (Frameless Motor Level)

ME 105 Mechanical Engineering Laboratory Spring Quarter Experiment #2: Temperature Measurements and Transient Conduction and Convection

Heat Sinks and Component Temperature Control

University of Bristol - Explore Bristol Research. Peer reviewed version. Link to published version (if available): /DEMPED.2017.

Analyzing the Effect of Ambient Temperature and Loads Power Factor on Electric Generator Power Rating

Operation of an Electromagnetic Trigger with a Short-circuit Ring

Sensors and Actuators Sensors Physics

Memory Thermal Management 101

Chapter 10: Steady Heat Conduction

FEATURES APPLICATIONS DESCRIPTION QUICK REFERENCE DATA. PILKOR components

Dynamic Behavior of Three phase Inductions Motors as Loads in an Electric Power System with Distributed Generation, a Case of Study.

1) Thermo couple sensor

Modeling of Transmission Line and Substation for Insulation Coordination Studies

Predicting transformer temperature rise and loss of life in the presence of harmonic load currents

Peltier Application Note

ADMISSION TEST INDUSTRIAL AUTOMATION ENGINEERING

Numerical investigation to study effect of radiation on thermal performance of radiator for onan cooling configuration of transformer

Resistivity and Temperature Coefficients (at 20 C)

CIGRE SC A2 & D1 JOINT COLLOQUIUM 2011, KYOTO JAPAN. Assessment of Overload Capabilities of Power Transformers by Thermal Modelling.

Temperature Measurement

MODELING AND MODIFICATION FOR DISTRIBUTION TRANSFORMER (250 KVA, 11/0.416 KV) TO REDUCE THE TOTAL LOSSES

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

Thermal Management for LED Applications

Analysis of Thermal Behavior of High Frequency Transformers Using Finite Element Method

NATURAL CONVECTION HEAT TRANSFER CHARACTERISTICS OF KUR FUEL ASSEMBLY DURING LOSS OF COOLANT ACCIDENT

Pin Fin Lab Report Example. Names. ME331 Lab

UNISONIC TECHNOLOGIES CO., LTD LM78XX

Critical parameters of

ELECTRICITY UNIT REVIEW

AS COMPETITION PAPER 2007

An Introduction to Insulation Resistance Testing

Linear Control Design for a Plastic Extruder

UNISONIC TECHNOLOGIES CO., LTD

Electromagnetic Oscillations and Alternating Current. 1. Electromagnetic oscillations and LC circuit 2. Alternating Current 3.

CGS ALUMINUM ELECTROLYTIC CAPACITORS

Thermal Management of SMT LED Application Note

Assessing The Thermal Performance of Building Enclosure Materials Using A Medium-Size Hot Box Chamber Summer Meeting Torkan Fazli

Unit Two Worksheet Matter and Energy WS PS U2

O Plus Dry Bushing 25 kv system, 150 kv BIL, 3000 A

Module 1 Units 3,4,5

NEEL Phase Change in Chromium At the Néel Temperature

Thermal Interface Material Performance Measurement

Standard Rectifier Module

ELECTRICAL AND THERMAL DESIGN OF UMBILICAL CABLE

Thermal Characterization of Packaged RFIC, Modeled vs. Measured Junction to Ambient Thermal Resistance

Chapter 2 HEAT CONDUCTION EQUATION

Design of the Forced Water Cooling System for a Claw Pole Transverse Flux Permanent Magnet Synchronous Motor

Design Guidelines for SFT Chipsets Assembly

EVERLIGHT ELECTRONICS CO.,LTD. Technical Data Sheet High Power LED 1W

High-ohmic/high-voltage resistors

Single-phase Transistor Lab Report. Module: EEE 108

MONITORING OF LONG TERM THERMAL STRESSES OF ELECTRICAL EQUIPMENT

Thermal Modeling of Electrical Utility Transformer

Good practice guide containing experimental results and recommendations for the selection, preparation and calibration of the temperature sensors

I, THERMAL ANALYSIS OF BUS-BAR FOR SWITCH BOARD

Encoders. Understanding. November design for industry: Help clean up the ocean. Horizon failure forensics

Electrical Power Cables Part 2 Cable Rating Calculations

Thermal Systems. What and How? Physical Mechanisms and Rate Equations Conservation of Energy Requirement Control Volume Surface Energy Balance

Thermal model of multilayer structure for NDT thermal parameters evaluation

ME 4/549 Lab Assignment 5: Single Block Experiment Spring 2006 due 1 June 2006

Electrical and Magnetic Modelling of a Power Transformer: A Bond Graph Approach

Transient Heat Transfer Experiment. ME 331 Introduction to Heat Transfer. June 1 st, 2017

Name Partner. Thermal Physics. Part I: Heat of Vaporization of Nitrogen. Introduction:

Transcription:

1 Study of a Transformer Thermal System Pedro de Carvalho Peixoto de Sousa Barros Department of Electrical and Computer Engineering (DEEC) - Instituto Superior Técnico (IST) Abstract This project has as goal the study and modulation of a dry single-phase transformer thermal system, with 1kVA of electrical power. During this study is identified and characterized the different zones of the transformer on which the temperature is considered homogeneous. It is presented a lumped model as well as the methodology to determinate its parameters. Tests are made for different load situations, quantifying the model error and giving particular attention to overload and short-circuit situations, being outstanding the importance of using models in order to foresee with precision the maximum temperature of the transformer as well as its overload capacity. I also presented a introductory study of the thermal behavior of the transformer and its modulation when it finds a regimen of forced cooling convection. Index Terms Transformer, thermal model, distributed parameters, lumped parameters. T I. INTODUCTION HE project and the overload capacity of electric machines, namely transformers, are strongly conditioned by its thermal performance. Due to difficulties of modulating the thermal system, exists the conscience that the advantages of materials are not explored integrally in the construction of transformers, so for precaution reasons, are fixed exaggerated safety margins for its operation. Nowadays there are numerical calculation methods capable to deal with complicated geometries and represent on the same time several phenomenas (heat and mass transportation) that if are used carefully and systematically can allow the creation of more numerical models, namely the thermal component of the transformer. In this work, I have done a thermal study of the transformer, in order to be possible to know its dynamics as well as its hottest zone. The knowledge in identifying and studying the hottest zone of the transformer is directly related with the lifetime reduction of electric machines as the material aging depends on the temperature they are subjected to. It is intended to identify several temperature rises in different zones of the transformer, once the simplest models estimate a homogeneous temperature over all the transformer area. In this study I considered a thermal lumped model, as well as the justification and characterization of its parameters, becoming important the realization of several tests to validate the model and determinate the error. A study is made for overload situations as well as short circuit situations in order to analyse its thermal behaviour and to calculate its overload capacity. Finally, I made an introductory study with the objective to verify the thermal behaviour of the transformer when it finds a cooling forced convection and how this regimen can increase the transformer efficiency. II. IDENTIFICATION OF HOMOGENEOUS ZONES A transformer has in its constitution some kind of materials, namely copper, iron and some types of isolation. Each one of these materials have different thermal characteristics, as such, normally it s expected that the temperature in the transformer is not the same on its different points. To become possible to read the temperature in the different regions of the transformer, I used type J thermocouples in a single-phase transformer of 1kVA and nominal voltage of 24/12V as it shows in the Fig.1. Fig. 1. Thermocouples. Nu-Core, A-A winding, B-B winding, BC-BC winding. The transformer has three windings, being the internal winding (the one next to the core) named as winding A. In the

2 external windings, named as winding B and C, the nominal tension is 12V and when connected in series allows a transformation ratio of 1:1. Please note that the thermocouples from T1 to T6 are assembled under the iron core and the T7 and T8 are out of the core window. The thermocouple T9 has been assembled over the upper part of the core in order to be possible to read its temperature. When a test is carried out in the transformer, for instance a short circuit test, it shows that the transformer temperature is not homogeneous, existing zones where the temperature is higher and others where it is lower. In Fig. 2 is showed the temperature rise for a short circuit test where it s possible to verify the non homogeneity in transformer temperature, and conclude that it is lower in the iron core (T9). Temperature ise (ºC) 55 5 45 4 35 3 25 2 T1 T2 T3 T4 T5 T6 T7 T8 T9 Fig. 4. Temperature variation as the readings move away to the external layers of the copper. variation occurs in the isolation material, whereas in the copper and in the iron it stays practically constant. The temperature differences in the previous figures can be explained appealing to Fig. 5, where it is represented the heat flux on the zone in analysis. 15 1 5 5.2 5.4 5.6 5.8 6 Fig. 2. Temperature rise. Short-Circuit test. In the copper windings, the temperature is lower in the winding A, and it gradually rises as we read the temperature in the external windings, reaching its higher reading (for the short circuit test) in the winding B (T4 and T5) and coming back to lower reading in the winding C. As an example, is presented in the Figs. 3 and 4 the temperature inside windings, as well as its variation as the readings move away to the external layers of the copper. Fig. 3. Temperature inside the winding in the central zone of the transformer. Please note that the Fig. 3 and 4 were made with simulation programs that solve the equations for a distributed parameters model. To simplify the simulation, it was only presented the central zone of the transformer, where were assembled the thermocouples from T1 to T6. In Fig. 4, it is possible to verify that the temperature Fig. 5. Total heat flux [W/m 2 ] Due to the large contact surface with the air temperature, the iron core has a very small increase of temperature when compared with the windings, acting as a heat exchanger. This way it explains the fact the temperature is lower near the core. As the reads move away from the core, the temperature of the winding A rises, because the heat as more difficulty to flow due to the various isolation layers. As was already explained, the hottest temperature is verified in winding B, what it would be expected to happen as it is an internal winding having several isolations layers, and therefore making the heat flux difficult through it. In addition, the winding B connected in series with winding C, has more 18 meters of length than winding A. With more copper, for a giving current it will appear more losses, therefore the temperature will be higher. In the external part of winding C, the temperature comes back to lower values, as it is a outside zone of the winding and the heat is easily dissipated to the air around. In thermocouples T7 and T8, that are not assembled underneath the iron core, when analyzing Fig. 2, we verify that T7 as the same temperature of T5, as both are assembled between winding B and C and near the same wire, however, T8 has a substantially lower reading as it is assembled near the exterior, revealing that the temperature is not constant along the wires on the same layer, being higher on the central zone of the winding and getting lower as it moves for the wires near

3 the exterior. Of everything that was observed it is evidenced that the transformer as several zones with different temperatures, indicating clearly that the temperature is not homogeneous. However, it becomes difficult to make the study of the transformer considering all the different temperatures. In order to be possible to establish a lumped model, it will be considered zones with material homogeneity, as well as zones where it can be found heat sources and using the Biot number [14] is possible to establish a criterion where we can say that a specific region of the transformer is assumed as having a homogeneous temperature. According with (1), it can be assumed that the temperature is uniform if the Biot number (N B ) is lower than,1. This means that the thermal resistance for internal conduction is much less than the thermal resistance for convection at the surface of the transformer. where h L N B = (1) k V L = (2) A In (1), h is the heat transmission coefficient for convection, L is the ratio between the volume of the body (V) and the area of its surface (A) and k is the thermal conductivity. Knowing the transformer geometry and the materials properties is possible to calculate the Biot number for the different zones of the transformer. Therefore, for the iron core, I got a Biot Number of 6x1-3, being this value of 1,4x1-3, 1,5x1-3 and 6x1-6 for the windings A, B and C respectively. As the Biot number is lower than,1 we can assume a temperature homogeneity in each one of the considered zones. With experimental tests, it was verified that the windings B and C can be considered as one only zone of homogeneous temperature. Please note that in all zones it was considered the hottest point. III. LUMPED MODEL One of the goals of this work is the determination of a lumped model on which will be possible its use in a simple way with the lowest error. For that, it was considered each of the transformer regions with a current source (that corresponds to the heat generation on that material), a capacitor (to represent the heat accumulation) and a resistor (to represent the temperature variation in the transformer due to the heat flux). Fig. 6 shows the different transformer zones, being θi the variation of temperature of zone i, Ci the thermal capacity of Fig. 6. Lumped model. Nu-Core, A-A winding, BC-BC winding. each region and Pi represents the heat generation sources. The Gi-j conductances represent the resistance to the heat exchange between regions i and j. Once the winding A is an internal winding, it was verified that most of the heat produced in this winding is lost for the core and winding BC and not directly to the air. Due to this fact, the existence of a conductance between winding A and the air is not considered. A. Determination of the model parameters The thermal equations of the presented model are, in the matricial form, represented by (3) d θ C θ = P dt In which C represents the matrix of the thermal capacities, θ the vector of temperature rise for each region of the transformer, G the matrix of thermal conductances and P the vector of the heat source for each zone where it is verified the heat generation. From (3), it is possible to verify that in a steady state regimen we get (4), G θ = P θ = G 1 P θ = P being the matrix of the thermal capacities. To solve (3), it is necessary to determine the model parameters. Vector P is an entrance value, being possible to represent it depending on the transformer load, whereas the θ vector represents the temperature variation for each specific part of the transformer when related to a specific load. This way, there are two variables to be calculated: the matrix of thermal capacities C, and the matrix of thermal resistances (the matrix G is obtained by inverting the matrix ). 1) Thermal capacities calculation Knowing the transformer geometry and its materials, it is possible to characterize with some accuracy the thermal capacity. th p p (3) (4) C = ρ VC = mc (5) So it is possible to write the matrix C as follows:

4 C C = Nu C A 6253,63 = C BC 485,7 69,18 (6) the steady state. Afterwards, was made a simulation with the previously presented model in order to validate it. 6 2) Thermal resistance calculation The calculation of the thermal resistances values is slightly more complicated than the thermal capacities. Once the transformer geometry is complex, it becomes easier to calculate the thermal resistances values with experimental tests. Observing the steady state equation (4) it is shown that heating each different parts of the transformer and measuring the temperature variation in all the other parts, it is possible to calculate the thermal resistances values. To heat each zone of the transformer, it was made a test with direct current, it means that knowing the current value, it is possible to calculate the heat generated in each zone (power losses). This type of test is valid when is intended to heat the windings. Once is not possible to heat only the iron core (it is impossible to heat it without heating also the windings), to verify the iron core heating, it was made an open circuit test where was monitored the total electric power on the transformer and the current in the winding A. Therefore, with the mentioned tests, it becomes possible to calculate the matrix. Then, the thermal resistances matrix is as follows: = Nu A BC,65 =,66,54,66 2,33 1,42,54 1,42 2,19 where the main diagonal line represents all the resistances connected to a specific zone (Nu, A the BC) and outside the diagonal are represented the thermal resistances between each two zones of the transformer. Inverting the matrix it is possible to obtain the thermal conductances matrix G. G r G 2,23 =,49,23 1 = G =,49,82,41 G BC Ar,23,41,78 IV. EXPEIMENTAL ESULTS AND SIMULATIONS A. Steady State operation (7) For this test, the transformer was placed supplying energy to a resistive load at nominal power rated, reading the temperature in various parts of the transformer until it reaches (8) Temperature ise (ºC) 5 4 3 2 1 2 4 6 8 1 Fig. 7. Steady-State test. From Fig. 7, it is verified that the obtained results for the simulation approaches the experimentally values. It is also observed that the transformer shows a maximum variation of temperature, for the operation at nominal power rate, about 58ºC for the copper windings and 28ºC in the iron core. As it would be expected, it is evidenced that the thermal behaviour of the windings is different from the thermal behaviour of the iron core, being its time constants about 36 (1 hour) and 82 seconds (2 hours and 18 minutes), respectively. For this test, it is evidenced that the winding A losses are about 1,4W being 13,9W for the winding BC, noticing that this difference is due to the longer length of the winding BC. Through a test open circuit test (carried out for the model parameters calculation) it was verified that the iron core losses are about 2W. TABLE I MAXIMUM EO Temperature Simulated Experimental Absolute Error elative Error % T Nu 9,5ºC 8,ºC 1,5ºC 18,8 T A 44ºC 41ºC 3ºC 7,3 T BC 44ºC 41ºC 3ºC 7,3 On table I is presented the maximum error for this test, verifying that it occurs during the transient state. It s noticed that the relative error in the core is high during this test, however, it is verified that it occurs at extremely low temperature with a small absolute error. On the other hand, the relative error in windings is lesser, but occurring an increase of the absolute error. After reaching the temperature steady state the error decreases to values lower than 3,5% in the core and 3,8% in the windings. B. Overloads and Short circuits TNu-Simul. TA-Simul. TBC-Simul. TNu TA TBC In this chapter it is intended to study which is the maximum overload capacity of the transformer, doing tests and simulations, in order to assure the normal operation of the

5 transformer and avoiding failures. egarding the short circuits, this study becomes important mainly for the project of transformer circuit breakers and its time actuation reaction, which has to be fast enough to avoid major failures. 1) Overloads In Fig. 8 it is presented the experimental and computational result obtained for a test where the transformer operates at nominal power rate, afterwards operating at a temporary overload, increasing the current to a value 1% higher than its nominal current. Afterwards it decreases the current until it reaches 9% of its nominal value. Temperature ise (ºC) 7 6 5 4 3 2 Fig. 8. Overload test. 1 2 3 4 5 6 7 Of course that when it reaches an overload state increasing the 1% the current, the windings verify an increase on losses of 2% and a temperature rise. As it is possible to see in table II, the error of the simulation values, for the hottest point, is about 2% for the windings and 3% for the iron core. TABLE II MAXIMUM EO: HOT-SPOT Absolute Temperature Simulated Experimental Error TNu-Simul. TA-Simul. TBC-Simul. TNu TA TBC elative Error % T Nu 3ºC 31ºC 1ºC 3,1 T A 66,1ºC 67,3ºC 1,2ºC 1,8 T BC 65,1ºC 64,2ºC,9ºC 1,4 To study temporary overloads situations, a model that calculates which is the temperature variation with a small error shows particularly useful, it means, for a given operation state of the transformer, it is possible to calculate with some accuracy the maximum temperature of the hottest point, if it operates under overload, as well as which is the maximum time that the transformer can support overload situations without isolation damages. This model can also be useful for the thermal design of the transformer as knowing the maximum temperature reached it becomes possible to manufacture smaller transformers and this way avoiding the usual over sizing of electric machines. As an example, the laboratory transformer, as it was already referred, at rated power it produces power losses of 2W in the iron core, being 1,4W and 13,9W in the windings A and BC, respectively. Once this transformer has class H isolation, it s possible a maximum temperature variation of 125ºC with an ambient temperature of 4ºC and 15ºC error margin for the hottest point, it means that this point can reach 18ºC. Fig. 9 represents a simulation where initially the transformer operates at rated power, later on increasing 2,5 times the winding losses it produces losses of 26W in the winding A and 34,8W in winding BC. The losses in iron core can be considered constant once these only depend on the supplied voltage value. Temperature ise (ºC) 12 1 8 6 4 2 Fig. 9. Maximum Overload. TNu-Simul. TA-Simul. TBC-Simul. 2 4 6 8 1 12 As it is presented, the model foresees that the winding temperature variation reaches the limit value, which is the 125ºC. Assuming that the windings resistance does not change with the temperature, it is possible to calculate the theoretical current value that flows trough them for the considered situation, and it is verified that the values reaches 6,6 amperes. Once the nominal current of the transformer is 4,16 amperes, a current of 6,6 amperes corresponds to an increase of 58% in the nominal current, reveals that the laboratory transformer is clearly oversized. In the previous simulation, it was presented an extreme situation of overload, on which the transformer finds an operating state during a period of time long enough to reach a steady state. However, it is possible to put the transformer operating with higher values than the ones mentioned previously if the operating time doesn t exceed the period of time necessary to reach its maximum value of 125ºC. The Fig. 1 presents some simulations for different current values. In this simulation, it is assumed as beginning point the temperature variation in steady state, making afterwards a current change multiplying it by 1.58, 1.7, 2 and 2.5. The situation where the nominal current is multiplied by 1.58 was already presented, being the maximum overload situation. As we increase the current value, it is verified that the temperature reaches quickly the maximum value.

6 Temperature ise (ºC) 12 1 8 6 4 2 t1 t2 1 t3 2 3 4 5 TNu - 1.58*In TBC - 1.58*In TNu - 1.7*In TBC - 1.7*In TNu - 2*In TBC - 2*In TNu - 2.5*In TBC - 2.5*In secondary winding of the transformer, where the current is 3 times higher the nominal current. Temperature ise (ºC) 12 1 8 6 4 TNu TA TBC Fig. 1. Overload Time. For the situations considered in this simulation, it is also verified that it is possible to operate the transformer with a current 7% higher than the nominal value during a period of time about 8 minutes (t3), decreasing this period to 25 minutes if the current is double of its nominal value (t2). If the current reaches 2.5 times the nominal value, the period of time that the transformer can operate overloaded without any isolation damages decreases to 12 minutes (t1). With this simulation, it is also intended to enhance the importance of the thermal behaviour of the iron core, it means, the iron core working as a heat exchanger how it contributes for the windings cooling operating under overload conditions. Observing again Fig. 1, it is verified that for operating states of soft overloads ( near rated values) the iron core constant thermal time has an important role on the global transformer cooling, it means, the heat generated by the transformer is slowly dissipated by the iron core making the temperature of the hottest point to raise also gradually. As the overload becomes more violent (extremely higher than the rated conditions) the heat generated by the windings reaches extremely high values, producing a quickly temperature increase. The heat generated in the windings needs time to spread into the iron core, being then dissipated by this one. As the windings heat increase time is sufficiently lower than the period of time necessary to spread and dissipate the heat trough the core, the cooper temperature will increase quickly that the core temperature. Take for instance the situation where the current is 2.5 times the nominal current. The temperature in the winding BC takes approximately 12 minutes (t1) to reach its maximum value. At that exactly time, it is verified that the iron core temperature practically doesn t change. 2) Short circuits The use of a proper thermal model allow us to calculate efficiently the period of time that the transformer can operate with short circuit, knowing which is the maximum overload protection actuation time. In Fig. 11 is presented a short circuit situation in the 2-1 -.5.5 1 1.5 2 2.5 3 3.5 Time (s) Fig. 11. Short-Circuit. In the figure above it is possible to observe that the iron core does not have time to heat, reason why its behaviour can be disgard, considering just the windings behaviour. To project the overload protections, it is verified that the transformer can remain in operation under short circuit during 2.75 seconds from which can occur failure. Therefore, the protection actuation time must be lower than the previously referred time. C. Forced Convection In the previous chapters, it was presented a study for the transformer thermal behaviour during a natural convection situation. In this chapter it is intended to present an introductory study for a transformer thermal behaviour when it operates under forced cooling convection. As it is presented, the hottest point of the transformer, under nominal conditions, is located inside the copper windings. Cooling under forced convection has as goal the temperature reduction in that point. As already referred, it was observed that the iron core acts as a heat exchanger. Having verified this, a fan was used pointing directly to iron core and this was increasing, efficiently, the heat exchange. To calculate the model parameters, it was proceeded as previously referred, doing tests with direct current in order to heat each winding separately and a open circuit test in order to heat only the core. This way, it was possible to calculate the model parameters when the transformer operates under forced cooling convection, being the thermal resistance matrix given by (9):,23 =,25,21,25 1,82 1,5,21 1,5 1,84 Inverting the matrix is then possible to obtain the thermal conductances matrix. (9)

7 1 5,2 = G =,55,28,55,88,44,28,44,83 (1) Comparing the values obtained for matrix G with forced convection (1) and for the matrix G with natural convection (8), it is observed that almost all the values are similar to the exception to the value obtained for the core conductance. This fact was expected, once only cooling the core with forced convection, increases the thermal conductance between the core and the air, G Nu-ar. As the iron core is the only part of the transformer where the forced convection acts, all the other conductance values don t have significant variations. With the intention of comparing the behaviour of the lumped parameters model under forced convection with the real temperature evolution, a test has been made where the transformer, that was initially at ambient temperature, placing it later on operating under nominal conditions until the temperature rises up to the steady state. Fig. 12 presents the experimental results and the results obtained with the simulation. Comparing the results obtained with forced convection with the ones obtained with natural convection, it is verified a global temperature reduction in the transformer giving the indication that the position chosen for the fan has been efficient. Temperature ise (ºC) 45 4 35 3 25 2 15 1 5 1 2 3 4 5 6 Fig. 12. Forced cooling convection. TNu-Simul. TA-Simul. TBC-Simul. TNu TA TBC During this test it is observed that the maximum temperature variation in the windings is about 43ºC and without forced convection the temperature variation increases to 58ºC. egarding the core, it is verified a reduction to 12ºC compared with the 28ºC with natural convection. In general, with forced convection it is verified a reduction of about 15ºC in the transformer temperature. This temperature reduction reveals particularly importance during overload situations, once it makes possible that the transformer operates with overload during more time. For failure situations, as short circuits, the position chosen for the fan can not be the best one, as it just affects the core thermal behaviour. TABLE III MAXIMUM EO: FOCED COOLING CONVECTION Temperature Simulated Experimental Absolute Error elative Error % T Nu 5,8ºC 4,5ºC 1,3ºC 28,8 T A 28,5ºC 25,8ºC 2,7ºC 1,5 T BC 29,1ºC 26,5ºC 2,6ºC 9,8 From table III, where it is possible to read the model error, we can verify an increase of it when comparing with the same test but with natural convection. This error increase is due to the fact that we are not modelling correctly the forced convection, it means, representing the complex phenomena as the convection, which involves mass transportation, just trough a resistance, what could not be sufficient and therefore increasing the error value. V. CONCLUSION This report presented a lumped model for a dry single-phase transformer, considering it with several zones with homogeneous temperature. The model revealed accuracy, with small error when calculating the transformer temperatures. With the considered model, it was possible to foresee the maximum temperature of the hottest point for situations of overload and short circuits. With the presented tests, it was intended to point out the importance of using models of temperature forecast for a transformer in order to be possible to calculate the overload capacities and the protections time actuation. Placing the transformer in a situation of forced cooling convection, an increase of the model error is verified, this way concluding that modelling complex phenomena as convection requires another kind of study. EFEENCES [1] Çengel, Yunus A., Heat Transfer A Practical Approach, International Edition, McGraw-Hill, 1998. [2] Dente, António, Modelo Térmico das Máquinas Eléctricas, Lisboa, Instituto Superior Técnico, 22. [3] Analog Devices, Monolithic Thermocouple Amplifiers with Cold Junction Compensation, ev C, Norwood, Analog Devices, 1999. [4] Lindsay, J. F., Temperature ise of na Oil-Filled Transformer with Varying Load, Vol. PAS-13, Montreal, IEEE Transactions on Power Apparatus, 1984. [5] Glen, Swift, Molinski, Tom S., Lehn, Waldemar, A Fundamental Approach to Transformer Thermal Modeling Part I: Theory and Equivalent Circuit, Vol. 16, No.2, IEEE Transactions on Power Delivery, 21. [6] Tang, W. H., Wu, Q. H., icherdson, Z. J., Equivalent Heat Circuit Based Power Transformer Thermal Model, Vol 149, No. 2, IEE Proc.- Electr. Power Appl, 22. [7] Tang, W. H., Wu, Q. H., icherdson, Z. J., A Simplified Transformer Thermal Model Based on Thermal-Electric Analogy, Vol 19, No. 3, IEEE Transactions on Power Delivery, 24 [8] Alvares, Marcelo Carvalho, Samesima, Milton Itsuo, Delaiba, António Carlos, Análise do Comportamento Térmico de Transformadores Suprindo Cargas não Lineares Utilizando Modelos Térmicos, Uberlândia, Universidade Federal da Uberlândia, 1999.

[9] esende, Maria José, Thermal Ageing of Distribution Transformers Due to Load and Ambient Temperature Variability, Lisboa, Instituto Superior Técnico, 1998. [1] International Standard - Power transformers - Loading Guide for Oil- Immersed Power Transformers (IEC 354:1991). [11] S Data Sheet, Type J/K/N/T Welded Tip Glass Fiber, 26. [12] S Data Sheet, Thermocouples, 25. [13] Susa, Dejan, Dynamic Thermal Modeling of Power Transformers, Helsinki, Helsinki University of Technology, 25. [14] izzoni, Giorgio, Thermal Systems Module 6, Ohio, The Ohio State University, October 25. [15] Montsinger, V. M., Loading Transformers by Temperature, AIEE Trans., Vol. 49, 193. [16] Dakin T. W., Electrical Insulation Deterioration Treated as a Chemical ate Phenomena, AIEE Trans., Vol. 67, 1948. 8