Composition Shift of a Mixed-Gas Joule-Thomson Refrigerator Driven by an Oil-Free Compressor

Similar documents
Cooling Temperatures of Binary Mixed Refrigerants: Vapor-Liquid-Liquid Equilibrium versus Vapor-Liquid Equilibrium

Comparison of Fluid Flow and Heat Transfer for 1D and 2D Models of an In-Line Pulse Tube Refrigerator

Experimental Investigation on a Single-Stage Stirling-Type Pulse Tube Cryocooler Working below 30 K

Modification In Charging Composition In Order To Arrive At Desired Circulation Composition In The Context Of Sorption Compressor Based J-T Cooler

Theoretical and Experimental Research on a Two-Cold-Finger Pulse Tube Cooler

Flight Acceptance Testing of the Two JPL Planck Sorption Coolers

Electric-Mechanical-Acoustic Coupling Characteristics for Pulse Tube Cryocoolers

CM 3230 Thermodynamics, Fall 2016 Lecture 16

Phase Shift Characteristics of Oscillating Flow in Pulse Tube Regenerators

Name: Discussion Section:

A Model for Parametric Analysis of Pulse Tube Losses in Pulse Tube Refrigerators

Mathematical Modelling for Refrigerant Flow in Diabatic Capillary Tube

Applied Thermodynamics for Marine Systems Prof. P. K. Das Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

Thermodynamic Comparison of Two-Stage Pulse Tube Refrigerators for Two Different Configurations

Oscillating Flow Characteristics of a Regenerator under Low Temperature Conditions

Experimental Investigation of Hybrid System Pulse Tube and Active Magnetic Regenerator

Thermodynamics: An Engineering Approach Seventh Edition Yunus A. Cengel, Michael A. Boles McGraw-Hill, Chapter 7 ENTROPY

ENTROPY. Chapter 7. Mehmet Kanoglu. Thermodynamics: An Engineering Approach, 6 th Edition. Yunus A. Cengel, Michael A. Boles.

Name: Discussion Section:

CHAPTER 5 MASS AND ENERGY ANALYSIS OF CONTROL VOLUMES

Basic Models of Simultaneous Heat and Mass Transfer

Clausius Clapeyron Equation

Numerical Simulation of the Effect of Heat Conductivity in a 4 K Regenerator

Thermodynamics: An Engineering Approach Seventh Edition in SI Units Yunus A. Cengel, Michael A. Boles McGraw-Hill, 2011.

Visualization of Secondary Flow in an Inclined Double-Inlet Pulse Tube Refrigerator

Basic Thermodynamics Prof. S. K. Som Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

Accepted Manuscript. Numerical analysis of the two-phase heat transfer in the heat exchanger of a mixed refrigerant Joule Thomson cryocooler

14.5 K Hydrogen Sorption Cooler: Design and Breadboard Tests

Preface Acknowledgments Nomenclature

first law of ThermodyNamics

Chemical Engineering Thermodynamics Spring 2002

The Effects of Friction Factors on Capillary Tube Length

Vapor-hydrate phases equilibrium of (CH 4 +C 2 H 6 ) and (CH 4 +C 2 H 4 ) systems

Les propriétés d'équilibre entre phases et masses volumiques

(Refer Slide Time: 00:00:43 min) Welcome back in the last few lectures we discussed compression refrigeration systems.

Cryocoolers (CryoCoolers.tex)

Glide Effect on Performance

A cryogenic heat exchanger with bypass and throttling and its thermodynamic analysis

TWO-PHASE FLOW FRICTIONAL PRESSURE DROP OF FC-14 IN HORIZONTAL TUBES

Development of a Compressor for a Miniature Pulse Tube Cryocooler of 2.5 W at 65 K

Earlier Topics. Introduction to Cryogenic Engineering An introductory knowledge of Cryogenic Engineering.

Visualization the Distribution of Air-Water Mixtures Flow in Two Outlet Distributor

Gas Chromatography (Chapter 2 and 3 in The essence of chromatography)

Steven W. Van Sciver. Helium Cryogenics. Second Edition. 4) Springer

ECHE Questions Centrifugal Pumps

THE FIRST LAW APPLIED TO STEADY FLOW PROCESSES

Ttions, and its relation to states of matter. This chapter covers the

A Numerical Model of Regenerator Based on Lagrange Description

Available online at ScienceDirect. Physics Procedia 67 (2015 ) Superfluid helium heat pipe. P.

Thermoacoustic Expansion Valve: A New Type of Expander to Enhance Performance of Recuperative Cryocooler Systems

Chapter 1 Introduction and Basic Concepts

Investigations on Performance of an Auto-Cascade Absorption Refrigeration System Operating with Mixed Refrigerants

Chapter 12 PROPERTY RELATIONS. Department of Mechanical Engineering

Analysis on heat transfer effect of air-temperature vaporizer in LNG satellite station

Effect of Coiled Capillary Tube Pitch on Vapor Compression Refrigeration System Performance.

Performance Investigation on Electrochemical Compressor with Ammonia

Course: MECH-341 Thermodynamics II Semester: Fall 2006

Lecture 44: Review Thermodynamics I

Thermodynamics I. Properties of Pure Substances

Vacuum techniques (down to 1 K)


Chapter 2: The Physical Properties of Pure Compounds

Optimal operation of simple refrigeration cycles Part II: Selection of controlled variables

Chapter 3 PROPERTIES OF PURE SUBSTANCES. Thermodynamics: An Engineering Approach, 6 th Edition Yunus A. Cengel, Michael A. Boles McGraw-Hill, 2008

Lecture 35: Vapor power systems, Rankine cycle

Vapor-liquid equilibrium

Development of a 4K Pulse-Tube Cold Finger for Space Applications

PowerPoint Presentation by: Associated Technical Authors. Publisher The Goodheart-Willcox Company, Inc. Tinley Park, Illinois

Gas Chromatography (GC)! Environmental Organic Chemistry CEE-PUBH Analysis Topic 5

Modified Brayton Refrigeration Cycles for Liquid Hydrogen in Spallation Neutron Source Moderator

Technische Universität Dresden Lehrstuhl für Kälte- und Kryotechnik Dresden, 01062, Germany

II/IV B.Tech (Regular) DEGREE EXAMINATION. (1X12 = 12 Marks) Answer ONE question from each unit.

Performance analysis of a miniature Joule Thomson cryocooler with and without the distributed J T effect

Russell B. Schweickart and Gary Mills

Key words: heat exchanger, longitudinal conduction, heat in-leak, helium liquefier, helium refrigerator

Chapter 1 INTRODUCTION AND BASIC CONCEPTS

Chapter 3 PROPERTIES OF PURE SUBSTANCES

THERMODYNAMICS (Date of document: 8 th March 2016)

Cryogenic Engineering Prof. M. D. Atrey Department of Mechanical Engineering Indian Institute of Technology, Bombay. Lecture No. #23 Gas Separation

Thermal Effects. IGCSE Physics

ESO201A: Thermodynamics

TOLERANCES AND UNCERTAINTIES IN PERFORMANCE DATA OF REFRIGERANT COMPRESSORS JANUARY 2017

All rights reserved. Armando B. Corripio, PhD, PE Flash Distillation Flash Drum Variables and Specifications... 2

R13. II B. Tech I Semester Regular Examinations, Jan THERMODYNAMICS (Com. to ME, AE, AME) PART- A

UBMCC11 - THERMODYNAMICS. B.E (Marine Engineering) B 16 BASIC CONCEPTS AND FIRST LAW PART- A

Chapter 5. Mass and Energy Analysis of Control Volumes. by Asst. Prof. Dr.Woranee Paengjuntuek and Asst. Prof. Dr.Worarattana Pattaraprakorn

INTRODUCTION AND BASIC CONCEPTS. Chapter 1. Mehmet Kanoglu. Thermodynamics: An Engineering Approach, 6 th Edition. Yunus A. Cengel, Michael A.

ECH 4224L Unit Operations Lab I Thin Film Evaporator. Introduction. Objective

Design of Standing Wave Type Thermoacoustic Prime Mover for 300 Hz Operating Frequency

CHAPTER 4 MATHEMATICAL MODELING AND SIMULATION

System design of 60K Stirling-type co-axial pulse tube coolers for HTS RF filters

Thermal Energy Loss in the Steam Valves and its Effects

Compression and Expansion of Fluids

The University of Saskatchewan Department of Computer Science. Technical Report #

Chapter 3 PROPERTIES OF PURE SUBSTANCES

Thermodynamics INTRODUCTION AND BASIC CONCEPTS. Copyright The McGraw-Hill Companies, Inc. Permission required for reproduction or display.

Upstream LNG Technology Prof. Pavitra Sandilya Department of Cryogenic Engineering Centre Indian Institute of Technology, Kharagpur

University School of Chemical Technology

ME 2202 ENGINEERING THERMODYNAMICS TWO MARKS QUESTIONS AND ANSWERS UNIT I BASIC CONCEPTS AND FIRST LAW

NGL EXTRACTION SPE - BACK TO BASICS. Ed Wichert Sogapro Engineering Ltd. September 27, 2011

Transcription:

Composition Shift of a Mixed-Gas Joule-Thomson Refrigerator Driven by an Oil-Free Compressor M. Gong, Z. Deng, and J. Wu Technical Institute of Physics and Chemistry Chinese Academy of Sciences Beijing 100080, China ABSTRACT A mixed-gas Joule-Thomson refrigerator (MJTR) driven by an oil-free compressor is built to study the mixture composition shift feature due to the differential liquid holdup in the two-phase flow. A typical multicomponent mixed-refrigerant for refrigeration at 120 K is used to measure the difference of the circulating composition from the original charge. A prediction model is proposed to calculate the mixture composition variation due to phase holdup in the two-phase flow. Both the measured and calculated data show that the composition shift is large for those mixtures which reach a low temperature range. The parameters influencing the mixture composition variation were also analyzed. INTRODUCTION Great achievements in the development of mixed-gases Joule-Thomson refrigerators have been achieved in recent years. Commercial products based on this kind of refrigeration have also become available, such as freezers for biomaterials preservation, and small scale cryocoolers for scientific research (Cryotiger). Meanwhile, there are still many problems needing further research. The composition shift is one of the most important problems. 1,2 The change of the mixture compositions leads to variations of the thermodynamic properties of the refrigerant. In turn, this will influence the performance of the refrigerator. It is necessary to conduct research on the composition shift features of MJTRs. There are several possible reasons for the change in the mixture compositions. One important reason is the different solubility in the lubricant oil for components with different boiling points. Another important reason is the differential phase holdup in the two-phase flow at low temperatures. The study of composition shift due to different solubility in lubricant oil is presented in another paper. 3 In this paper, the composition shift caused by liquid holdup in the two-phase region is investigated theoretically and experimentally. A mixed-gases Joule-Thomson refrigeration system driven by an oil-free compressor is built to measure the composition variations. A prediction model is also proposed to calculate the composition shift due to the differential liquid holdup in the two-phase flow. Cryocoolers 14, edited by S.D. Miller and R.G. Ross, Jr. International Cryocooler Conference, Inc., Boulder, CO, 2007 453

454 J-T AND THROTTLE-CYCLE CRYOCOOLER DEVELOPMENTS Figure 1. Experimental system, the digital numbers from 1 to 8 indicate different sampling points EXPERIMENTAL RIG An experimental system was developed based on a real mixture refrigeration system, where an oil-free compressor was used to compress the mixed-refrigerant. Figure 1 shows the schematic diagram of the experimental system. It consists of two parts: one is the refrigeration system, and the other is the mixture sampling and analyzing system. The mixture refrigeration system consists of a compressor unit and a cryostat. The compressor unit includes a compressor with an aftercooler. The cryostat, enclosed in a metal dewar (illustrated as a dashed rectangle in Figure 1), includes a counter-flow heat exchanger, a throttle valve, and an evaporator. There are eight sampling positions in this system. Sampling point 1 and 2 are fixed at the inlet and outlet of the high pressure passage of the heat exchanger. Point 3 is at the inlet of the evaporator, and point 4 locates the outlet of the evaporator. Points 5 to 7 are fixed evenly at the lowpressure passage of the heat exchanger. The last point, 8, is at the return line before the inlet of the compressor. The temperature of sampling position 8 is near the ambient temperature. During operation, only this point was used to sample the circulating composition, which ensures a gas-phase state sample. That is, the sampling point 8 is used to monitor the composition shift during the cooling down process. When the steady cooling temperature is reached, the cryostat will be cut off by closing the two valves which connect the cryostat and the ambient units (the compressor and after cooler), and the system will be turned off. When the temperature of the cryostat increases to the room temperature, the sampling points from 1 to 8 will be used to measure the local compositions. The local compositions measured at different points can partially indicate the composition distribution in the system during the operating period. A gas chromatography instrument (GC3400, Beifen China) with a Thermal Conductivity Detector (TCD) was used to analyze the mixture composition. An elaborated capillary column is used to ensure that all of the mixture's components can be separated and detected. The signal generated by the detector is sent to the workstation (BF9202, an auxiliary of the GC3400). With the workstation, the chromatogram of the sample can be obtained. The Normalizing Peak Areas Method is used to determine the compositions of the mixture. A reference mixture is used to calibrate the chromatograph. This mixture was prepared with a precise balance (Sartorius BS 4000S). The detail description of the system can be found in the reference by Gong, et al. 2 PREDICTION MODEL The multicomponent mixtures used in MJTRs for low temperature applications are typical non-azeotropic mixtures, where the difference between the bubble and the dew point temperatures can be as large as 100 K, or more. The compositions of the liquid and vapor phases of the two-phase region are quite different. Therefore, the phase holdup caused by the velocity difference in the twophase flow is one of the most important reasons for the composition shift of multicomponent mix-

COMPOSITION SHIFT OF A MIXED-GAS J-T REFRIGERATOR 455 tures. The phase holdup can be described as: 4 where H L is the liquid holdup, V L is the liquid phase volume, V p is the volume of the flow passage, and H G is the vapor holdup. If the liquid and vapor phases have the same velocities, the phase holdup can be expressed as: (3) (1) (2) where U is the facial velocity, Q is the volume flow rate, and the subscripts of L, G and TP indicate liquid phase, vapor phase and the total two-phase flow, respectively. It is obviously that there will be no composition shift if the vapor phase has the same velocity as the liquid phase. The composition shift is caused by the velocity difference of vapor and liquid phases. This part of the holdup liquid can not circulate in the cycle any more. This will finally influence the circulating compositions. The volume and mole of the holdup liquid can be express as: (4) (5) where V is the volume of the holdup liquid, n is the mole quantity of the holdup liquid, n is the density of the local holdup liquid in mol/m 3. Therefore, the composition shift can be expressed as: (6) (7) where z j is the initial composition of j component, z j is the holdup liquid composition, and z j is the circulating composition; R is the relative composition shift. In the model described above, no dead volume in the system is considered. There are a number of liquid holdup prediction models (void fraction models). Here, the Beggs-Brill-Moody model 5 was used to calculate the liquid holdup (void fraction). RESULTS AND ANALYSIS A typical mixture for 120 K refrigeration 6 was used to measure its composition shift feature in the experimental system described above. The measured results of the maximum relative composition shifts are listed in Table 1 at different initial charged amounts. It can be found that for the same initial composition, the larger amount charged, the less the circulating composition will change. That is, for a system with a fixed volume cryostat, the initial charged mixture quantity can influence the composition shift feature; a larger charged amount will lead to a relative small composition Table 1. Composition Shift for a Typical Mixture at Different Charged Amount

456 J-T AND THROTTLE-CYCLE CRYOCOOLER DEVELOPMENTS shift. This conclusion is easily obtained from Eq. (6). It is obvious that when the amount (n) of the initial charge mixture increases, the composition variation degree (R) will decrease. The local compositions at different sampling points are also presented in Figures 2 and 3 for number A and C (Table 1), respectively. The measurements were conducted as the procedure described above. These measured compositions at different sampling points can partially indicate the composition distribution in the system. From Figures 2 and 3, it can be found that high-boiling components (isobutane and propane in this study) are accumulated at the low temperature section (points 3~6), while the composition of the low-boiling component (nitrogen in this measurement) decreases greatly. Moreover, when the system was shut off, the accumulated liquid of high-boiling components will drop from the top of the cryostat, this will make the composition of the high-boiling components in the eight sampling point larger than the initial charged one. The composition shift degree for those components with middle-boiling temperatures (methane and ethane in this paper) is relatively small compared with the high and low boiling components. The circulating composition variation along with the refrigeration temperature is also measured, and is shown in Figure 4. The calculated result is presented in Figure 5. The calculation was conducted with the model described above. Same mixture composition was used in the calculation, while the circulating mole flow rate is 0.124 mol/s. It can be found that the composition shift trend of both calculated and measured results are similar to each other. The measure data shows a higher composition shift than the calculated results because it is very hard to eliminate the dead volume in the real refrigeration system. Furthermore, accurate prediction of the low temperature two-phase flow is difficult to determine, especially for multicomponent mixtures. A more accurate prediction requires further study. Figure 2. Local composition distributions for Number A measurement Figure 3. Local composition distributions for Number C measurement

COMPOSITION SHIFT OF A MIXED-GAS J-T REFRIGERATOR 457 Figure 4. Measured composition shift along with the refrigeration temperature Figure 5. Calculated results for composition shift along with the refrigeration temperature However, the calculated results show a good trend. This work can provide a good reference if there are no other measurements. CONCLUSION A real mixed-gases Joule-Thomson refrigerator driven by an oil-free compressor was built to study its composition shift features due to liquid holdup in a two-phase flow. A prediction model was also proposed by calculating the liquid holdup with a void fraction model. From this study, it is found that a variation in mixture composition was found to be caused by the liquid holdup in the low temperature two-phase flow. The composition of high-boiling components will decrease due to the liquid accumulation in the low temperature section in the cryostat. The initial charge refrigerant amount will influence the composition shift degree. The increase of the charged amount will decrease the degree of composition shift. The calculated results show a good agreement with measured data in presence of the composition shift trend. ACKNOWLEDGMENT This work is financially supported by the National Natural Sciences Foundation of China under the contract number of 50206024.

458 J-T AND THROTTLE-CYCLE CRYOCOOLER DEVELOPMENTS REFERENCES 1. Quack, H., Mixture Refrigeration, a lecture presented at Beijing International Conference on Cryogenics, Beijing, China, 2000. 2. Gong, M.Q., Wu, J.F., Luo, E.C., Qi, Y.F., Hu, Q.G.., and Zhou, Y., Research on the Change of Mixture Compositions in Mixed-Refrigerant Joule-Thomson Cryocoolers, Adv. in Cryogenic Engineering, Vol. 47B, Amer. Institute of Physics, Melville, NY (2002), pp. 881-887. 3. Gong, M., Zhou, W., and Wu, J., Composition Shifts due to Different Solubility in the Lubricant Oil for Multicomponent Mixtures, Cryocoolers 14, ICC Press, Boulder, CO, 2007, this proceedings. 4. Saleh, J.M., Fluid Flow Handbook, McGraw-Hill (2002), pp. 159-190. 5. Beggs, H.D., and Brill, J.P., A Study of Two-Phase Flow in Inclined Pipes, Trans. AIME (1967), 607. 6. Gong, M.Q., Luo, E.C., Wu, J.F., and Zhou, Y., On the Temperature Distribution in the Counter Flow Heat Exchanger with Multicomponent Non-Azeotropic Mixtures, Cryogenics, Vol. 42 Issue:12 (December 2002), pp. 795-804.