DISTANCE RELAY SETTINGS

Similar documents
ALPS. Advanced Line Protection System

Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent Elements in Line Protection Applications

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.

EDSA IEC 909 SHORT CIRCUIT ANALYSIS

Fault Calculation Methods

ECE 526 Distance Element Examples

Reactive Power Solutions

Distance Elements: Linking Theory With Testing

THE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session

Basic Math for Relay Technicians. Hands On Relay School 2015 Presented by Charlene Reyes

Performance Comparison Between Mho Elements and Incremental Quantity-Based Distance Elements

Dynamic simulation of a five-bus system

Lecture (5) Power Factor,threephase circuits, and Per Unit Calculations

Z n. 100 kv. 15 kv. pu := 1. MVA := 1000.kW. Transformer nameplate data: X T_pu := 0.1pu S T := 10MVA. V L := 15kV. V H := 100kV

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis

2/7/2013. Topics. 15-System Model Text: One-Line Diagram. One-Line Diagram

Module 3 : Sequence Components and Fault Analysis

Fault Analysis Power System Representation

NEW DESIGN OF GROUND FAULT PROTECTION

Section 5. TADS Data Reporting Instruction Manual DRAFT Section 5 and Associated Appendices With Proposed Event Type Numbers

Securing Sequence-Current Differential Elements

ELEC Introduction to power and energy systems. The per unit system. Thierry Van Cutsem

SHORT QUESTIONS AND ANSWERS. Year/ Semester/ Class : III/ V/ EEE Academic Year: Subject Code/ Name: EE6501/ Power System Analysis

Final Exam, Second Semester: 2015/2016 Electrical Engineering Department

c Z ... Ln :E UJ UJ ...J. (f) (f) (f) UJ. (f) (f)

Cahier Technique N 11 Guide de réglage de la protection de Distance. Distance Protection (F21) Setting Guide

Fault Locating PRESENTED BY ERIK SCHELLENBERG IDAHO POWER

Selecting the current rating for equipment

Traveling Wave Relays. Fault Location

Identifying the Proper Impedance Plane and Fault Trajectories in Distance Protection Analysis

Electrical Machines-I Prof. D. Kastha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Two Port Networks. Definition of 2-Port Network A two-port network is an electrical network with two separate ports for input and output

The per unit system is based on the formula shown in Equation (1).

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION

ABSTRACT. residential Photovoltaic (PV) systems. The investigation is done on both conventional and

VLSI Physical Design Prof. Indranil Sengupta Department of Computer Science and Engineering Indian Institute of Technology, Kharagpur

Current protection I 2 t long-time protection

Symmetrical Fault Current Calculations Unlv

The Operation of a Generator on Infinite Busbars

Mitigation of Distributed Generation Impact on Protective Devices in a Distribution Network by Superconducting Fault Current Limiter *

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

POWER SWING AND OUT-OF-STEP CONSIDERATIONS ON TRANSMISSION LINES

Analysis of a Relay Operation for an Intercircuit Fault

Regulating Transformers in Sequence Domain

POWER SEMICONDUCTOR BASED ELECTRIC DRIVES

Fault Diagnosis in Distribution Networks with Distributed Generation

OVER CURRENT RELAYS PROTECTIVE COORDINATION IN DISTRIBUTION SYSTEMS IN PRESENCE OF DISTRIBUTED GENERATION

To order, specify : Types Protection functions Current surge Asymmetry and loss of phase. Operating principle

90 MCB range Modular circuit breakers for circuit protection

Tutorial on Shunt Capacitor Banks Design, Application and Protection Considerations

Module 3 : Sequence Components and Fault Analysis

90 MCB MODULAR CIRCUIT BREAKERS FOR CIRCUIT PROTECTION

Transient Behavior of

NTE4514B & NTE4515B Integrated Circuit CMOS, 4 Bit Latch/4 to 16 Line Decoder

SESSION 3. Short Circuit Calculations, Unsymmetrical Faults. Leonard Bohmann, Michigan State University Elham Makram, Clemson University

A. P. Sakis Meliopoulos and George J. Cokkinides Power System Relaying, Theory and Applications. Chapter 8 2 Generator Protection 2

Series & Parallel Resistors 3/17/2015 1

Chapter 8: Unsymmetrical Faults

ECE 524: Reducing Capacitor Switching Transients

ECE 524: Lecture 15 Reducing Capacitor Switching Transients. jx s C 2 C 1. Define units: MW 1000kW MVA MW MVAr MVA. rad s

Chapter 33 - Electric Fields and Potential. Chapter 34 - Electric Current

QUESTION BANK ENGINEERS ACADEMY. Power Systems Power System Stability 1

EE 451 Power System Stability

Name. Section. Short Answer Questions. 1. (20 Pts) 2. (10 Pts) 3. (5 Pts) 4. (10 Pts) 5. (10 Pts) Regular Questions. 6. (25 Pts) 7.

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA.

Switched-Capacitor Filters

KINGS COLLEGE OF ENGINEERING Punalkulam

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.

Mathcad Examples. Define units: MVA 1000kW MW MVA kw kvar kw. pu Entering Phasors in Polar Notation

I. Impedance of an R-L circuit.

The Influence of Abnormal Data on Relay Protection

Chapter 2 Circuit Elements

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA

Adaptive Distance Relaying Scheme for Power Swing Tripping Prevention

Remote Display Unit. Installers Handbook Copyright 2001 AirSense Technology Ltd. LM Remote Display Unit Installers Handbook Issue 1.

Worked Example for the Calculation of Earthing Current and Electric Shock Hazard Potential Difference in a Rod and Grid Earthing System

4/27 Friday. I have all the old homework if you need to collect them.

ECE 421: Per Unit Examples

Electromagnetic Oscillations and Alternating Current. 1. Electromagnetic oscillations and LC circuit 2. Alternating Current 3.

T-PRO Application in Reactor Protection Using Neutral Differential and Timed Over-Current Back-up Protection

Microprocessor Based Characteristics and adjustments

Computer Science 324 Computer Architecture Mount Holyoke College Fall Topic Notes: Digital Logic

Preventing Voltage Collapse with Protection Systems that Incorporate Optimal Reactive Power Control

Chapter 5 Steady-State Sinusoidal Analysis

The Ordering Code for various standard model Recorders with an AC supply and without any additional options are as follows:

Introduction to Karnaugh Maps

NEW RECLOSER CHARACTERISTIC TO IMPROVE FUSE SAVING IN DISTRIBUTION NETWORKS WITH DISTRIBUTED GENERATION

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

INSTRUCTION MANUAL FOR MM10 Relay

IGEE 402 Power System Analysis. FINAL EXAMINATION - SAMPLE Fall 2004

ECE 476. Exam #2. Tuesday, November 15, Minutes

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

Digital Current Transducer HO-SW series I P N = A. Ref: HO 100-SW; HO 150-SW; HO 200-SW; HO 250-SW

LESSON 20 ALTERNATOR OPERATION OF SYNCHRONOUS MACHINES

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous)

TSTE25 Power Electronics. Lecture 3 Tomas Jonsson ICS/ISY

Research Article A Novel Algorithm for Power Flow Transferring Identification Based on WAMS

What happens when things change. Transient current and voltage relationships in a simple resistive circuit.

max clear Figure 1 below illustrates a stable case. P post (f) (g) (e) A 2 (d) (c)

Homework 1 solutions

Transcription:

DISTANCE RELAY SETTINGS Introduction Commonly used >33kV Determine whether impedance measured is within set characteristic. Non-unit protection (boundaries not defined) During normal operation impedance is combination of line, transformers and load ( >> line impedance) o Determine fault location by impedance measured o Measured impedance < line impedance fault o Example A 132kV Z = 30 ohms B LOAD 100MVA o Load Impedance = V 2 / P = 132000 2 /100x10 6 =174.2Ω o Relay Measures = 30+174 = 204 Ω o Equivalent Circuit A B 30 ohms 174.24 ohms Source o If have fault at B load impedance shorted out and relay measures 30ohm:

A B 30 ohms 174.24 ohms Source o Above is oversimplification (no errors, angle differences) Time Stepped Distance General: Relays have errors as do CTs and VTs allow 5 to 10%. Line impedance calculation errors allow 10%. o total errors 20%. To ensure whole line covered set to 120% but sees past end and could operate for fault on next line. o Solution 1: time delay A B C relay A Reach relay C reach D relay B reach A to grade with B which grades with C similar to overcurrent end up with slowest operation at the source. o Solution 2: set another zone which cant see past end o Set to 80% of line impedance, instantaneous Set to 80%, inst; to 120%, time delayed.

A B C Slowest clearance on any line is time. Zone 3 to provide backup to remote lines, time delayed to grade with. Time Stepped Distance Settings Major requirements: Fault detection: faulted plant is tripped Coordination: only faulted plant is tripped General comment: Impedance generally refers to PPS impedance (covers different fault combinations and earth return via measurement quantities see last week). Settings: So can be set instantaneous (no intentional delay), set as far as possible whilst ensuring doesn t see remote end o = 0.8xZ line...(1) Settings Set to ensure whole line length covered and time delayed to grade with next line protection. Time delay > Remote (say 50msec) + remote CB (say 80msec) + remote trip relay (say 10msec) + local Zone

2 timing errors (say 50msec) + safety margin (say 50 to 100msec). o 300msec is common. So can use 300msec, require no Z2 overlap A B C F Z2 AB Z AB + Z1 BC ignoring errors o 1.1xZ2AB 0.9(Z AB + Z1 BC ) including errors o Z2AB 0.8(Z AB + Z1 BC ) o Z2AB 0.8(Z AB + 0.8xZ BC ) as Z1 BC = 0.8xZBC o Z2AB 0.8(Z AB + 0.8xZ BC ) Also require whole line to be covered: Z2AB 1.2xZ AB o 1.2xZ AB 0.8(Z AB + 0.8xZ BC ) o ZBC 0.625xZAB o if remote line < 62.5% of protected line impedance no Z2 that satisfies both equations 2 and 3 o generally set as long as possible Zone 3 settings Time delay > Remote (say 50msec pickup + 300msec time delay) + remote CB (say 80msec) + remote trip relay (say 10msec) + local Zone 3 timing errors (say 50msec) + safety margin (say 50 to 100msec). o 600msec is common. Assuming wanting to coordinate Z3, and set 600msec, require no Z3 overlap: o Z3 AB Z AB + Z2 BC ignoring errors 1.1xZ3AB 0.9(Z AB + Z2 BC ) with errors

Z3 AB 0.8(Z AB + Z2 BC ) Z3AB 0.8(Z AB + 0.8(Z BC + 0.8xZ CD )) as Z2 AB 0.8(Z AB + 0.8xZ BC ) Z3AB 0.8xZ AB + 0.64xZ BC + 0.512xZCD Assuming wanting to backup line B-C: Z3AB 1.2(Z AB + Z BC ) o 1.2(ZAB + Z BC ) 0.8xZ AB + 0.64xZ BC + 0.512xZCD o 0.4xZAB + 0.56xZ BC 0.512xZCD o ZAB + 1.4xZ BC 1.28xZ CD o Only satisfy if CD much longer than AB or BC. Not generally the case difficult to achieve backup and coordination. If backup preferred Z3TD >> 600msec. Short Line Considerations What if Z BC < 0.625xZ AB ie cant set Z2 to cover line and not overlap next Z2 (on a short line) o Only a problem if short line protected by TSD. Three solutions o Time delay Z2 BC to grade with Z2 AB (ie set 600msec) Slow clearance for remote end faults o Set Z2 BC (300msec) so it doesn t see past Z1 AB and then set Z3 BC to protect 120% of line and to grade with Z2 AB (ie set 600msec) Only worthwhile if 120% reach only just overlaps Z1AB Slow clearance for remote end faults under worse case errors. o Use whole line high speed protection (eg differential, pilot, distance signalling, etc) Expensive as requires comms Short lines often protect by differential as distance doesn t achieve enough fault resistance coverage.

A B C D short line with high speed protection Need to ensure that the zone 2 of line AB does not see into the zone 2 of line CD. 1.1xZ2 AB 0.9(Z AB + Z BC + Z1 CD ) Z2 AB 0.8(Z AB + Z BC + Z1 CD ) This can be satisfied provided: 1.2xZ AB 0.8(Z AB + Z BC + 0.8xZ CD ) 0.4xZ AB 0.8(Z BC + 0.8xZ CD ) Z AB 2xZ BC + 1.6xZ CD )...(8) In an interconnected system this becomes easier due to throttling (infeeds from other lines cause adjacent lines to appear to have larger impedances). Affects of Power Transformers

Transformers > 33kV generally use high speed protection grade with Z2 OK. o Check Z2 and Z3 don t see through TX to plant protected by slow protections: Z2 Z Line + ZTX 1.1xZ2 0.9(ZLine + Z TX ) with errors Z2 0.8(Z Line + Z TX ) o What TX impedance to use due to tap position effecting impedance (nominal, worse case) o Also consider TXs run in parallel. o If no TX high speed protection or have to set Z2/3 so can see through, grade Z2 and Z3 with these slower protections. Considerations of Load Load appears as an impedance to a distance relay. Line angle 70-80 deg, load impedance +/- 40 deg (ie pf of 0.8). On heavily loaded, long lines load impedance will approach line impedance load encroachment. Worse case is minimum voltage conditions and maximum load on line (Z = V/I). X Load R

Throttling Change in relay measured impedance due to multiple remote infeeds to fault A ZL1 I1 I2 B ZL2 Fault With no infeed Zr = ZL1 + ZL2. With infeed at B: V A = I 1 Z L1 + (I 1 + I 2 )Z L2 V A Z L1 + Z L2 + I 2 Z L2 = I 1 I1 Potentially large increase in measured impedance; o need to allow for this if setting Z3 to give remote backup, ie extend Z3 but then need to be careful with grading if remote infeeds removed/reduced o Can assist with grading between lines (eg short lines look longer). o Need to be careful of parallel paths and effects of ends opening before others. o Can show we can set Z2 AB so doesn t see past Z1BC ZAB (1+ I 2 /I 1 )1.6xZ BC (compared with Z BC 0.625xZ AB or Z AB 1.6xZ BC previously) Settings for Teed Lines

B A C T Throttling at tee point reduces effectiveness of distance. set to 80% of shortest distance to remote ends ignore throttling here as one end could be open. o If external low impedance connection between remote ends may need to pull back Z1. has to protect whole line and thus set to 120% of largest distance to remote ends, plus consider throttling. o Eg Z2 at A = 120% x Z AT + Z tee max where Ztee max is the max of: (1 + ICB/I AB )Z TB For the impedance from T to B (1 + IBC/I AC )Z TC For the impedance from T to C where Ixy is the current from x to y o When checking coordination, assume one end open o Effected by changes to system. o If coordination not possible, use differential or distance signalling.

TUTORIAL WEEK 4 1) For the following power system determine, 2 and 3 reach and time delay settings. A G B C F H I D E Impedances, loads a) Generator 0.1pu, 1200A, 11kV b) Line A-G 0.3pu, 1000A c) Line B-C 0.4pu, 800A d) Line D-E 0.35pu, 800A e) Line F-H 0.2pu, 400A f) I has impedance of 0.5pu Assume I operates instantaneously. Allow 300msec safety margin between relays. 2) Check reaches determined in Question 1 do not result in any load encroachment problems. Assume all lines have a line angle of 70 degrees and relays are mho relays. 3) Consider options for short line F-H.