Keywords: Superconducting Fault Current Limiter (SFCL), Resistive Type SFCL, MATLAB/SIMULINK. Introductions A rapid growth in the power generation

Similar documents
Railway Research. Study of Superconducting Fault Current Limiter Device in a AC Railway System. 1. Introduction. International Journal of

Simulation study on operating chara. Author(s) Shirai, Y; Taguchi, M; Shiotsu, M; IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY (2003), 13(2): 18

Superconducting Fault Current Limiters

Superconductivity for Electric Systems DOE 2006 Wire Development Workshop

Conductor Requirements for Superconducting Fault Current Limiters

Superconducting Fault Current Limiter in DC Systems with MLI Fed to IM

Analytical and Experimental Studies on the Hybrid Fault Current Limiter Employing Asymmetric Non-Inductive Coil and Fast Switch

2 nd Generation High-Temperature Superconducting Wires for Fault Current Limiter Applications

Development of 2 MVA Class Superconducting Fault Current Limiting Transformer (SFCLT) with YBCO Coated Conductors

KIT-ENERGY CENTRE. KIT The research University in the Helmholtz Association

Fault Current Limiters

Status and outlook on superconducting fault current limiter development in Europe

Grid Issues and Challenges Addressed by High Temperature Superconductor (HTS) Technology

Superconducting Fault Current Limiters

Fault Current Limiter Based on Coated Conductor

Mitigation of Distributed Generation Impact on Protective Devices in a Distribution Network by Superconducting Fault Current Limiter *

TRANSFORMERS. Pascal Tixador. Grenoble INP - Institut Néel / G2Elab. Introduction

EMTP-ATP Modeling of a Resistive Superconducting Fault Current Limiter

Inductance and Current Distribution Analysis of a Prototype HTS Cable

The development of a Roebel cable based 1 MVA HTS transformer

Transient Analysis of a 150 kv Fault Current Limiting High Temperature Superconducting Cable

Design and Application of Superconducting Fault Current Limiter in A Multi-terminal HVDC System

Applications Using SuperPower 2G HTS Conductor

1. Explain the various methods of methods of grounding. In power system, grounding or earthing means connecting frame of electrical equipment (non-cur

RESULTS OF ON-GRID OPERATION OF SUPERCONDUCTOR DYNAMIC SYNCHRONOUS CONDENSER

current limitation and energy redistribution

HiLumi LHC FP7 High Luminosity Large Hadron Collider Design Study. Milestone Report. Cryogenic Scenarios for the Cold Powering System

Short-circuit protection to a fault: Superconducting fault current limiters

Combined HTS Cable and Fault Current Limiter Project in Germany

Feasibility of HTS DC Cables on Board a Ship

Study on recovery performance of high T c superconducting tapes for resistive type superconducting fault current limiter applications

Thermal Stability of Yttrium Based Superconducting Coil for Accelerator Application

Commissioning testing of a 1 MVA Superconducting transformer featuring 2G HTS Roebel cable

Hydra Fault Current Limiting HTS Cable to be Installed in the Consolidated Edison Grid

3D Finite Element Simulations of Strip Lines in a YBCO/Au Fault Current Limiter

EPRI Technology Watch 2010 Superconducting Cables Fault Current Limiters

Status and Progress of a Fault Current Limiting HTS Cable To Be Installed In The Consolidated Edison Grid

High-Performance 2G HTS Wire for an Efficient and Reliable Electricity Supply

Current Lead Optimization for Cryogenic Operation at Intermediate Temperatures. L. Bromberg, P.C. Michael, J.V. Minervini and C.

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL

5G50.52 Energy Storage with Superconductors

Investigation of the feasibility of a Superconducting self-healing DC Grid on a LNG Carrier

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A

Development of a Simulink Model of a Saturated Cores Superconducting Fault Current Limiter

F F FAULT CURRENT Prospective. 1. Introduction. 2. Types of fault conditions

Progress in Scale-up of 2G HTS Wire at SuperPower Part III

PERFORMANCE ANALYSIS OF SMART GRID WITH SUPER CONDUCTING FAULT CURRENT LIMITER IN A SOLAR AND WIND BASED MICROGRID

High Field HTS SMES Coil

HTS Roadmap for Electric Power Systems October 2015

Cryogenic and Electrical Test Results of a 30 M HTS Power Cable

Analysis on Current Limiting Characteristics of Transformer Type SFCL with Additionally Coupled Circuit

Superconducting cables Development status at Ultera

Transient Behavior of

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

High-temperature superconducting magnet for use in Saturated core FCL

Finite element modeling of a superconducting fault current limiter

Modeling of the Resistive Type Superconducting Fault Current Limiter for Power System Analysis and Optimization

THE NUMERICAL MODEL OF 2G YBCO SUPERCONDUCTING TAPE IN THE WINDINGS OF THE TRANSFORMER

Russian Development Program on HTS Power Cables

Latest Status of High Temperature Superconducting Cable Projects

Transient Stability Assessment of Synchronous Generator in Power System with High-Penetration Photovoltaics (Part 2)

Transient Stability Improvement of a Multi- Machine Power System by Using Superconducting Fault Current Limiters

An Innovative Simple Test Circuit for Single-Phase Short Circuit Making Test of High-Voltage Switching Devices

Modelling and Analysis of Resistive Superconducting Fault Current Limiter.

ENERGY STORAGE SYSTEMS Vol. II Superconducting Inductive Coils - M. Sezai Dincer and M. Timur Aydemir

High Temperature Superconducting Fault Current Limiters as Enabling Technology in Electrical Grids with Increased Distributed Generation Penetration

Transmission Level HTS Fault Current Limiter

KINGS COLLEGE OF ENGINEERING Punalkulam

Design and preliminary results of a prototype HTS SMES device

TRANSMISSION LINES. All aluminum alloy conductor (AAAC) Aluminum conductor alloy reinforced (ACAR)

CHAPTER 2 OVERVOLTAGE DUE TO SELF-EXCITATION AND INRUSH CURRENT DUE TO CAPACITOR SWITCHING

ECE 422/522 Power System Operations & Planning/ Power Systems Analysis II 3 Load Modeling

IEEE (2012) 22 (2). ISSN

Analysis of smart grid with superconducting fault current limiters

COPPER FOR BUSBARS CHAPTER 4: SHORT-CIRCUIT EFFECTS

Protecting a Full-Scale Nb3Sn Magnet with CLIQ, the New Coupling-Loss Induced Quench System

Coil in Coil Components for the High Voltage Superconducting Resistive Current Limiter CULT 110

HTS Magnets for Accelerator Applications

Reliability of Bulk Power Systems (cont d)

A Cryogenic Magnetostrictive Actuator using a Persistent High Temperature Superconducting Magnet, Part 1: Concept and Design

Capacitor Application Issues

Multiphysics Simulations for the design of a Superconducting magnet for proton therapy

Damping resistor design consideration

Fundamentals of Polymeric PTC 0vercurrent Circuit Protection

An Optimised High Current Impulse Source

JOINTS FOR SUPERCONDUCTING MAGNETS

Instruction. Vacuum Circuit Breaker Operator Module. Type 3AH 4.16kV to 38kV. Power Transmission & Distribution

Effect of Discontinuities and Penetrations on the Shielding Efficacy of High Temperature Superconducting Magnetic Shields

Behaviour of synchronous machine during a short-circuit (a simple example of electromagnetic transients)

Power Factor Improvement

Current Leads, Links and Buses

Temperature rise in a model of resistive HTS element of a fault current limiter

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION

MASSACHUSETTS INSTITUTE OF TECHNOLOGY DEPARTMENT OF MECHANICAL ENGINEERING DEPARTMENT OF NUCLEAR ENGINEERING 2.64J/22.68J , : & HTS

Thermal Instability and Current-Voltage Scaling in Superconducting Fault Current Limiters

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis

Design and Application of Fault Current Limiter in Iran Power System Utility

Opus: University of Bath Online Publication Store

MODELING AND MODIFICATION FOR DISTRIBUTION TRANSFORMER (250 KVA, 11/0.416 KV) TO REDUCE THE TOTAL LOSSES

Field-Circuit Coupling Applied to Inductive Fault Current Limiters

Transcription:

IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY Performance of a 3.3kV Resistive type Superconducting Fault Current Limiter S.Vasudevamurthy 1, Ashwini.V 2 1 Department of Electrical and Electronics, Associate Professor, Dr. Ambedkar Institute of Technology, India 2 Department of Electrical and Electronics,M.Tech Student, Dr. Ambedkar Institute of Technology, India ashunatya03@gmail.com Abstract In today s technological world, electrical energy is one of the most important forms of energy and is needed directly or indirectly in almost every field. Increase in the demand and consumption of electrical energy leads to increase in the system fault levels, and it crosses the rated capacity of the existing circuit breakers. One solution to this problem is to use a current limiting device in the system. In view of this, it is desirable to introduce a reliable means of limiting the fault currents so that the circuit breakers open at lower fault currents without any damage. One of them is Superconducting Fault Current Limiter.It appears to be the most attractive option for such purposes. Superconducting fault current limiter (SFCL) based on high temperature Resistive type is an enabling technology for the extensive fault current limitation when compared to Conventional circuit breakers. In this paper overview of the SFCL, modeling and simulation Studies of a 3.3kingle phase resistive type SFCL, to predict the performance of the Resistive type Superconducting Fault Current Limiter (SFCL) using MATLAB/SIMULINK is presented. Keywords: Superconducting Fault Current Limiter (SFCL), Resistive Type SFCL, MATLAB/SIMULINK. Introductions A rapid growth in the power generation efforts are in progress to develop HTSFCL based on 2nd generation (2G) YBCO coated conductors results in an increase in the fault levels The principal of the S-FCL is simple.a and it crosses the rated capacity of the existing circuit breakers. Replacement of existing switchgears due to such increasing fault levels imposes high costs for the electric power utilities and their customers. In view of this, it is desirable to introduce a reliable means of superconducting element is inserted in series with a line. During normal operating the system operates without any limitations because the resistance of the superconducting element is essentially zero, and it is possible to minimize limiting the fault currents so that the circuit breakers the inductive impedance. However, during a open at lower fault currents without any damage. A Superconducting fault current limiter device reacts very rapidly, resets itself after a fault, fault when the fault current reaches many times the rated value, the superconducting element reverts rapidly to its normal state (i.e., its and has minimal impact on system performance resistance increases to a defined value). The during normal operation. increased resistance/impedance limits the fault Superconducting fault current limiters (SFCL) appear to be the most attractive option for limiting the fault current. Earlier SFCLs were made with low temperature superconductors (LTS) which were quite expensive and not reliable at higher levels of fault. current to the desired level. Once the fault HTS applications operate at cryogenic temperatures, typically cooled by liquid nitrogen. Refrigeration systems are needed that are reliable, highly efficient and affordable. In recent years there has been a significant progress in the development of efficient cryo-refrigerators acting as recondensers in HTSFCL cryostats. At present worldwide R&D clears, the superconducting coil carries the system s normal current with zero resistance. During a fault when the superconducting element is in normal state, it warms up to a predetermined temperature. Ideally an S-FCL should limit the fault current to a desired level during a fault and recover quickly after the fault has cleared.

Basic Characteristics of SFCL Figure 1.1: Basic characteristics of SFCL Superconducting state is a state where an electrical conductor exhibits zero electrical resistance if the current flow through the material is below a certain threshold (the critical current level ), when operating below certain temperature and external magnetic field (the so called critical temperature, T c and critical field, H c range). If the current exceeds this critical level however, the superconductor will undergo a transition from its superconducting state to a resistive state. This transition is termed as quenching. SFCL s utilize this property of Superconductors losing its property above the critical current. In quenching state, the resistance of SFCL increases linearly and reaches a value, which will remain constant throughout the quenching period. As long as the heat generated (I 2 R loss) during the resistive stage does not damage the superconductor, the superconductor can be brought back to its superconducting state, if sufficient cooling is provided. The quenching of a superconductor and subsequent recovery to a superconducting state corresponds to a variable resistance effect, which is ideal for current limiting applications. Cryogenic cooling shall be provided to dissipate the heat quickly to lower the temperature of the superconductor to within its critical temperature range. SFCL Technology The SFCLs has the ability to reduce fault current levels within the first cycle of fault current level. The first cycle suppression of fault current by SFCL results in an increased transient stability of power system carrying higher power with greater stability. SFCLs are self regulating in the event of fault and are fail safe. SFCL can give an effective fault limitation without any degradation. Typical operation sequence of an SFCL is shown in figure1.2.from figure 1.2; it is observed that the fault condition occurs for a short time period when a nominal current was flowing in the electric system. The fault current can be 10 to 20 times higher than the nominal current. In presence of an SFCL, fault current can be limited very quickly to a level where the circuit breakers can work safely. After that SFCL goes for a recovery operation and comes back to the initial stage where it carries nominal current and voltage. If the required current limiting performance is specified as ratio of the short-circuit current with fault current limiter operation to the short-circuit current without fault current limiter operation, it should be clearly indicated whether this ratio refers to the short-circuit current at the fault location or the short-circuit current flowing through the fault current limiter. In case of fault current limiters which introduce a resistance into the circuit the fault current limiter not only limits the fault current but also shifts its phase which leads to an additional current limiting effect when a limited and an unlimited fault current sum up to a total short-circuit current. The following figure 1.2 depicts the functionality of an SFCL in case of a fault event. Figure 1.2: The functionality of an SFCL in case of fault event Resistive Type SFCL Resistive SFCLs utilize the superconducting material as the main current carrying conductor under normal grid operation. The principle of their operation is shown in the one-line diagram below (Figure 1.3).

The quench process in resistive SFCLs results in heat that must be carried away from the superconducting element by the cryogenic cooling system. Typically, there is a momentary temperature rise in the superconducting element that causes a loss of superconductivity until the cryogenic system can restore the operating temperature. This period of time is known as the recovery time. Figure1.3: Resistive type SFCL with shunt element When the current passes through the superconductor and when a high fault current begins, the superconductor quenches: it becomes a normal conductor and the resistance rises sharply and quickly. This extra resistance in the system reduces the fault current.superconductor quenches under excessive fault current reverting to a normal conductor, inserting resistance. The current level at which the quench occurs is determined by the operating temperature, and the amount and type of superconductor. The rapid increase in resistance produces a voltage across the superconductor and causes the current to transfer to a shunt, which are a combined inductor and resistor. The shunt limits the voltage increase across the superconductor during a quench. In essence, the superconductor acts like a switch with millisecond response that initiates the transition of the load current to the shunt impedance. Ideally, the incipient fault current is limited in less than one cycle. Early resistive SFCL designs experienced issues with hot spots, or nonuniform heating of the superconductor during the quench. This is a potential failure mode that occurs when excessive heat damages the HTS material. Recent advances in procedures for manufacturing HTS materials coupled with some creative equipment designs have reduced the hotspot issue. The grid characteristic of the resistive SFCL after a quench is determined by the shunt element. Thus, because the shunt is typically quite reactive, a resistive SFCL typically introduces significant inductance into the power system during a fault. During the transition period when current is being transferred from the superconductor to the shunt, the voltage across the combined element is typically higher than it is after the current has transitioned into the shunt. The dynamics of this process depend on the two elements and their mutual inductance. Theory of Fault Current Limiter Consider a simple power system model, consisting of a source with voltage, internal impedance Z s, load Z load, and fault impedance Z fault. In steady state, I line = Z s + Z load (1) When a fault occurs in a system, I fault = Z s + Z fault (2) Where, Z fault << Z load Since the supply impedance is much smaller than the load impedance, Equation 2 shows Z s that the short circuiting of the load will substantially increase the current flow. However, if a FCL is placed in series, I fault = Z s +Z FCL + Z fault (3) Equation 3 tells that, with an insertion of a FCL, the fault current will now be a function of not only the source Z s and fault impedance Z fault, but also the impedance of the FCL. Hence, for a given source voltage and increasing Z FCL will decrease the fault current I fault. Modelling And Simulation Results Of A 3.3kv/200A Single Phase Resistive Type Superconducting Fault Current Limiter Figure 1.4: Model of a 3.3KV/200A single phase without SFCL

A simple single phase 3.3 KV, 200A, 50Hz power system network without High Temperature Superconducting Fault Current limiter (HTS FCL) and creating fault at exactly 0.3 sec has been simulated with Matlab Simulink and the result is shown in below figure. From the result it is analyzed that at exactly 0.3 sec sudden increase in fault current from 200A to 5000A and decrease in output voltage from 4666V to 4165V after creating fault in the electric network. Figure 1.5: Source Current without SFCL Figure 1.8: Model of a 3.3KV/200A single phase with SFCL In the same single phase 3.3KV, 200A, 50Hz power system network High Temperature Superconducting Fault Current limiter (HTS FCL) is connected and creating fault at exactly 0.3 sec has been simulated with Matlab Simulink and the result is shown in below figure. From the result it is analyzed that at exactly 0.3 sec the fault current is reduced from 5000A to 3750A after creating fault in the electrical network. Figure 1.6: Source Voltage without SFCL Figure 1.9: Limited fault current with SFCL Figure 1.10: Voltage across the load with SFCL Figure 1.7: Voltage across the load without SFCL

SFCL Model Phys. Conf. Ser. Vol. 158, pp. 1173 1178, 1997. 5. Hui D et al, Development and test of 10.5 kv/1.5 ka HTS fault current limiter, IEEE Trans. Appl. Supercond., Vol. 16, pp.687 690, 2006. 6. Umer A.Khan, J.K.Seong Feasibility Analysis Of The Positioning Of Superconducting Fault Current Limiters For The Smart Grid Application Using Simulink, IEEE Trans. Appl. Supercond., Vol. 21, No.3, June 2011. Figure 1.11: The Resistive type SFCL model developed in MATLAB simulink. The SFCL works as follows. First, SFCL model calculates the RMS value of the passing current and then compares it with the triggering current value. Second, if a passing current is larger than the triggering current level, SFCL s resistance increases to maximum impedance level in a predefined response time. Finally, when the current level falls below the triggering current level the system waits until the recovery time and then goes into normal state. Conclusion In this paper simple single phase, without and with High Temperature Superconducting Fault Current Limiter (HTSFCL), and creating fault at 0.6sec has been simulated using Matlab simulink. Output results of the simulation is analysed and the results shows that with HTS FCL optimizes the fault current, and comparitively reliable than circuit breakers, where circuit breakers can handle the fault up to some voltage levels. SFCLs can be used for higher level of faults. References 1. Superconducting Fault Current Limiters: Technology Watch 2009. EPRI, Palo Alto, CA: 2009. 1017793. 2. Application of Fault Current Limiters - Department of Business Enterprise & Regulatory Reform, 2007. 3. Bednorz J G and M uller K A, Possible high Tc superconductivity in the Ba La Cu O system Z. Phys. B, Vol. 64, 189 193, 1986. 4. Paul W, Lakner M, Rhyner J, Untern ahrer P, Baumann T,Chen M, Widenhorn L and Gu erig A, Test of 1.2 MVA high-tc superconducting fault current limiter, Inst.