NFRC SOLAR HEAT GAIN COEFFICIENT TEST REPORT. Rendered to: CLEAR FOCUS IMAGING

Similar documents
NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: NU VISTA WD, INC. SERIES/MODEL: Malibu 250 T TYPE: Fixed

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: NORTH EAST WINDOWS USA, INC.

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: C.R. LAURENCE CO., INC.

Test Results: Results of the test period on 06/19/16 using the Equivalent CTS Method: Thermal transmittance at test conditions (U s ):

SHANGHAI MYLCH WINDOWS & DOORS THERMAL PERFORMANCE TEST REPORT

THERMAL PERFORMANCE TEST REPORT

Report No: NCTL NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 12/14/15

Report No: NCTL S NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 07/14/15. Test Specimen

ASTM C THERMAL PERFORMANCE TEST REPORT. Rendered to: UNIVERSAL PULTRUSIONS, LLC. PRODUCT: Fiberglass Door Slab

AIR-INS inc. 1320, boul. Lionel-Boulet, Varennes (Quebec) J3X 1P7 Tél. : (450) Fax : (450)

NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 03/31/06

NFRC THERMAL TEST SUMMARY REPORT January 27, 1999 Test Specimen

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: PARAMOUNT WINDOWS CORPORATION. SERIES/MODEL: 4000 TYPE: Fixed

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: UNITED STATES ALUMINUM. SERIES/MODEL: 7400 TYPE: Fixed

SIMULATION TEST REPORT NCTL E0A0

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: INTERNATIONAL ARCHITECTURAL PRODUCTS, INC. DBA: UNITED STATES ALUMINUM

Simulation Report (Revised) Rendered To: Showcase Custom Vinyl Windows 1002 Olde Towne Drive Irving, TX 75061

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: CMI ARCHITECTURAL PRODUCTS, INC.

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: TUBELITE, INC.

PERFORMANCE TEST REPORT. Rendered to: WORLDWIDE DOOR COMPONENTS, INC. PRODUCTS: PVC and Composite Door Jamb Material

THE EFFECTS OF CALORIMETER TILT ON THE INWARD-FLOWING FRACTION OF ABSORBED SOLAR RADIATION IN A VENETIAN BLIND

WINDOW SIMULATION REPORT

Standard Test Method for Measuring the Steady-State Thermal Transmittance of Fenestration Systems Using Hot Box Methods 1

TEST OF MEASURED SOLAR HEAT GAIN VARIATION WITH RESPECT TO TEST SPECIMEN TILT

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: C.R. LAURENCE CO., INC.

THE IMPORTANCE OF INDOOR AND OUTDOOR AIR-FILM COEFFICIENT MEASUREMENT TO SOLAR CALORIMETERY

Winter Night. Thermos 6mm Outdoors # #

PERFORMANCE TEST REPORT. Rendered to: VELUX AMERICA, INC. PRODUCT: SUN TUNNEL Domes TYPES: Acrylic and Polycarbonate

Reflectec Thermal Fabric & Reflectec Fiberboard

National Fenestration Rating Council. Incorporated. NFRC [E0A1] Procedure for Determining Fenestration Product Condensation Resistance Values

TEST METHOD FOR THERMAL TRANSMITTANCE AND AIR INFILTRATION OF GARAGE DOORS

Solar Radiation 230 BTU s per Hr/SF. Performance Glazing Coatings, Layers & Gases

Guide Specifications Section

CAE 331/513 Building Science Fall 2016

Solar Energy Cooking with the Sun

Building Envelope Requirements Overview Page 3-4

UNIT FOUR SOLAR COLLECTORS

A. Solar Walls. B. Prototype I

announcements 4/17/08

ROLLEASE ACMEDA ACOUSTICAL PERFORMANCE TEST REPORT

AR/IA 241 LN 231 Lecture 4: Fundamental of Energy

Chapter Seven. Solar Energy

CAE 463/524 Building Enclosure Design Fall 2012

ISO INTERNATIONAL STANDARD. Thermal performance of windows, doors and shutters Calculation of thermal transmittance Part 1: Simplified method

CONSTRUCTION MATERIALS

ASTM C STEADY-STATE HEAT FLUX MEASUREMENTS AND THERMAL TRANSMISSION PROPERTIES BY MEANS OF THE HEAT FLOW METER APPARATUS

Engineering Specification

Sound Absorption Test Intertek. kraft paper softwall + softblock modular system. m o l o d e s i g n, l t d

Predicting Natural Light in Atria and Adjacent Spaces using Physical Models

Determination of installed thermal resistance into a roof of TRISO-SUPER 12 BOOST R

Standard Guide for Determination of the Thermal Resistance of Low-Density Blanket-Type Mineral Fiber Insulation 1

Determination of thermal transmittance of window (test title)

Glazing selection for solar design

INVESTIGATING GLAZING SYSTEM SIMULATED RESULTS WITH REAL MEASUREMENTS

Development and Validation of Flat-Plate Collector Testing Procedures

REPORT NUMBER: MID-001 ORIGINAL ISSUE DATE: April 22, 2016 REVISED DATE: NA. EVALUATION CENTER Intertek 8431 Murphy Drive Middleton, WI 53562

The energy performance of an airflow window

Tick the box next to those resources for which the Sun is also the source of energy.

Laboratory 1: Calibration of a High-Volume Sampler

EVALUATION OF THERMAL ENVIRONMENT AROUND THE BLIND ON NON-UNIFOM RADIANT FIELDS A CFD SIMULATION OF HEAT TRANSFER DISTRIBUTION NEAR THE BLINDS

Solar Flat Plate Thermal Collector

Radiant Heating Panel Thermal Analysis. Prepared by Tim Fleury Harvard Thermal, Inc. October 7, 2003

Calculating the heat transfer coefficient of frame profiles with internal cavities

Window air permeability measurement, watertightness and resistance to wind load (designation of the test)

LABORATORY MEASUREMENT OF SOUND ABSORPTION OF SONOGLASS SPRAY-ON TREATMENT IN THREE CONFIGURATIONS

Section 1: Overhang. Sizing an Overhang

SOLAR GEOMETRY (AND RADIATION)

FG 623 Window Wall. Optional Features Integrates with standard Kawneer windows

ISO INTERNATIONAL STANDARD

2018 North Carolina Residential Code Prescriptive Tables for Selection of Support Elements for Beams, Girders, and Headers: Example Problems

Here Comes the Sun. Rachel Wagner. Duluth Energy Design Conference 26 February

Collector test according to EN ,2:2002

Standard Test Method for Thermal Conductivity of Refractories 1

Simplified Collector Performance Model

Series tore word. Acknowledgements

METHOD OF IN-SITU MEASUREMENT OF THERMAL INSULATION PERFORMANCE OF BUILDING ELEMENTS USING INFRARED CAMERA

REPORT NUMBER: GZU-001 ORIGINAL ISSUE DATE:

Use of Phase-Change Materials to Enhance the Thermal Performance of Building Insulations

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6956 Revision 1 ARL

5. Thermal Design. Objective: Control heat flow to: Maintain comfortable indoor conditions

ea980r Digital Anemometer User Manual

SAMPLE ASSESSMENT TASKS PHYSICS ATAR YEAR 11

Standard Practices for Air Speed Calibration Testing

ANSI/AHRI Standard (Formerly ARI Standard ) 2006 Standard for Performance Rating of Desuperheater/Water Heaters

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6986/ARL-SA6987 Revision 0 ARL

QIRT th International Conference on Quantitative InfraRed Thermography

EXPERIMENTAL STUDY ON A CASCADED PCM STORAGE RECEIVER FOR PARABOLIC DISH COLLECTOR

PERFORMANCE EVALUATION OF REFLECTIVE COATINGS ON ROOFTOP UNITS

C1.0 HOP IN FUEL STATION BENCHMARKS PARKING SUMMARY TABLE SITE PAVING: NOTES: SITE LOCATION MAP LEGEND DESCRIPTION PROPOSED EXISTING

ARCHITECTURE IN THE DAYLIGHT

Capstone Design: Energy Efficient Windows Triple Pane Window Analysis

NABCEP Entry Level Exam Review Solfest practice test by Sean White

the distance of conduction (the thickness), the greater the heat flow.

The Electrodynamics of a Pair of PV Modules with Connected Building Resistance

THERMAL DYNAMIC BEHAVIOR OF SINGLE COMPONENT: EXPERIMENTAL ANALYSIS AND NUMERICAL MODELING

NUMERICAL SIMULATION OF THE AIR FLOW AROUND THE ARRAYS OF SOLAR COLLECTORS

TEST METHOD FOR STILL- AND FORCED-AIR JUNCTION-TO- AMBIENT THERMAL RESISTANCE MEASUREMENTS OF INTEGRATED CIRCUIT PACKAGES

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6712/ARL-SA6713 Revision 0 ARL

Midterm Review #4 -FR

Effect of Installing a Curved Venetian Blind to the Glass Window on Heat Transmission

Transcription:

NFRC 201-2004 SOLAR HEAT GAIN COEFFICIENT TEST REPORT Rendered to: CLEAR FOCUS IMAGING SERIES/MODEL: SunSecure BASE WINDOW: 3/16" Clear Single Glazed PRODUCT TYPE: Window Film on the Interior of Clear 3/16" Glass Summary of Results Solar Heat Gain Coefficient (SHGC) - Base Window 0.84 Solar Heat Gain Coefficient (SHGC) - Base with Attachment 0.40 Percent Reduction of Heat Transfer 52% Daylight Opening 36" x 48" (914 mm x 1219 mm) Layer 1 3/16" Clear Glass Attachment SunSecure non-printable, interior-mount, pressure-sensitive film with a 65/35 perforation pattern (35% open) and 0.06 in. (1.5mm) Reference should be made to ATI Report No. for complete test specimen description and data. 2524 E. Jensen Ave Fresno, CA 93706 phone: 559-233-8705 fax: 559-233-8360 www.archtest.com

NFRC 201-2004 SOLAR HEAT GAIN COEFFICIENT TEST REPORT Rendered to: CLEAR FOCUS IMAGING 60 Maxwell Court Santa Rosa, California 95401 Report No: Test Date: 03/26/10 Report Date: 04/14/10 Record Retention Date: 03/26/14 Test Sample Identification: Series/Model: Base Window: SunSecure 3/16" Clear Single Glazed Type: Fixed Overall Size: 37" x 49" (940 mm x 1245 mm) Daylight Opening Size: 36" x 48" (914 mm x 1219 mm) Test Sample Submitted by: Client Test Procedure: Solar heat gain testing in accordance with NFRC 201-2004, Interim Standard Test Method for Measuring the Solar Heat Gain Coefficient of Fenestration Systems Using Calorimetry Hot Box Methods. Test Results Summary: Solar Heat Gain Coefficient (SHGC) - Base Window Solar Heat Gain Coefficient (SHGC) - Base with Attachement Percent Reduction Heat Gain 0.84 0.40 52% 2524 E. Jensen Ave Fresno, CA 93706 phone: 559-233-8705 fax: 559-233-8360 www.archtest.com

Test Sample Description: Page 2 of 7 Glazing Information: Layer 1 Attachement 3/16" Clear Glass SunSecure non-printable, interior-mount, pressure-sensitive film with a 65/35 perforation pattern (35% open) and 0.06 in. (1.5mm) holes 48" Calorimeter Calibration Information 1. 2 3 4 5 6 7 8 9. Moving Pyranometer Last Calibration Flowmeter Last Calibration Thermocouple Last Calibration Surround Panel Conductivity Last Calibration Power Input Last Calibration Fluid Temperature Difference Last Calibration Miscellaneous Power Input Last Calibration Metering Box Last Calibration Calibration Transfer Standard 02/16/10 01/28/10 02/08/10 12/02/09 02/08/10 02/08/10 02/08/10 03/15/10 03/05/10

Page 3 of 7 Solar Heat Gain Coefficient (SHGC) Test Data: 1. Starting Azimuth 119 Degrees 2. Ending Azimuth 130 Degrees 3. Minimum Altitude 44 Degrees 4. Maximum Altitude 36 Degrees 5. Average Barometric Pressure 29.5 Inches of mercury 6. Maximum Wind Velocity 4 MPH 7. Minimum Wind Velocity 1 MPH 8. Average Wind Velocity 3 MPH 9. Average Wind Direction (North equals 360 degrees) 229 Degrees 10. Maximum Exterior Surface Coefficient (Hh-sun) 11. Minimum Exterior Surface Coefficient (Hh-sun) 12. Average Exterior Surface Coefficient (Hh-sun) 13. Average Exterior Air Temperature (t h ) 5.6 Btu/hr ft² F 5.1 Btu/hr ft² F 5.3 Btu/hr ft² F 53.1 F 14. Standardized Weather Conductance (hstii) 15. Thermal Transmittance (Us)* 16. Maximum Solar Irradiation E s 5.10 Btu/hr ft² F 1.030 Btu/hr ft² F 317.7 Btu/hr ft 2 17. Minimum Solar Irradiation E s 304.1 Btu/hr ft 2 18. Average Solar Irradiation E s 311.6 Btu/hr ft 2 19. Inlet Fluid Temperature 65.9 F 20. Outlet Fluid Temperature 67.1 F 21. Test Start Time 08:47 HHMM 22. Test End Time 9:37 HHMM *Simulated by Window 5

Page 4 of 7 Solar Heat Gain Coefficient (SHGC) Test Data: (Continued) Temperatures during maximum irradiation Air and heat exchanger temperatures *Note: See Appendix A for locations Air Top Air Center Air Bottom 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 72.8 F 72.2 F 73.6 F 69.0 F 68.6 F 68.4 F 68.9 F 67.8 F 67.9 F 67.7 F 67.7 F 67.8 F 67.8 F 67.7 F 67.6 F 67.9 F 70.9 F 68.0 F 0.0 F 71.4 F 68.7 F 68.6 F 68.0 F 0.0 F 68.0 F 68.0 F 68.7 F 69.1 F

Page 5 of 7 Solar Heat Gain Coefficient (SHGC) Test Data: (Continued) Data at time of maximum irradiation 1. Average inside air temperature 72.9 F 2 Maximum thermal transmittance (Q u-factor) -209.1 Btu/hr 3 Surround panel inside temperature (tsp1) 69.9 F 4 Surround panel outside temperature (tsp2) 79.1 F 5 6 7 8 Heat flow through surround panel (Qsp) Flanking Loss (Qfl) Fluid volumetric flow rate (f) Auxiliary energy (Q aux) 3.6 Btu/hr 2.970 Btu/hr 2.2 Gal/min 43.5 Btu/hr 9 Heat Extracted From System (Qfluid) 1396.3 Btu/hr 10 Heat Across Walls (Qwalls) 11 Heat Flow Through Test Specimen (Qs) 53.5 Btu/hr 1501.8 Btu/hr The specimen was installed into an extruded polystyrene foam panel with an R-value of 17 using silicone caulking. Tracking system azimuth and altitude are read every minute and the calorimeter is moved to a position normal to the sun from chart stored in computer. The calorimeter is located at 2524 East Jensen in Fresno, California near the southwest corner of the lot elevated approximately 15 feet from ground level. The foreground is desert, the background is industrial buildings. The estimated uncertainty of this test 3.11% This was determined using ANSI/NCSL Z540-2-1997 type B evaluation as described in section 4.3 of this specification. For assumptions used for this calculation or for a description of the procedure contact the "Individual-In-Responsible-Charge" that signed this report.

Page 6 of 7 "This test method does not include separate procedures to determine the heat flows due to either air movement or nighttime U-factor effects. As a consequence, the SHGC results obtained do not reflect the overall performance which may be found in field installations due to temperature differences, wind, shading, air leakage effects, and the thermal bridge effects specific to the design and construction of the fenestration system opening." "Since there is a wide variety of fenestration system openings in residential, commercial and industrial buildings, it is not feasible to select a "typical" surround panel construction in which to mount the fenestration test specimen. The selection of a relatively high thermal resistance surround panel places the focus of the test on the thermal performance system alone. Therefore, it should be recognized that the thermal transmittance results obtained from this test method, for ideal laboratory conditions in a highly insulating surround panel, should only be used for fenestration product comparisons or as input to thermal performance analyses which also include thermal, air leakage and thermal bridge effects due to the surrounding building structure. To determine air leakage effects for windows and doors, refer to Test Method ASTM E 283. For thermal transmittance refer to Test Method ASTM C 1199." Ratings included in this report are for submittal to an NFRC-licensed IA for certification purposes and are not meant to be used for labeling purposes. Only those values identified on a valid Certification Authorization Report (CAR) are to be used for labeling purposes. Detailed drawings, representative samples of the test specimen and a copy of this report will be retained by Architectural Testing for a period of four years. This report is the exclusive property of the client so named herein and relates only to the fenestration product tested. This report may not be reproduced, except in full, without the approval of the laboratory. For ARCHITECTURAL TESTING, INC. Tyler Westerling, P.E. Project Engineer Individual-In-Responsible-Charge Leaton Kirk Director - Regional Operations TW:he Attachments (pages): This report is complete only when all attachments listed are included. Appendix-A: Thermocouple (1)

Page 7 of 7 Revision Log Rev. # Date Page(s) Revision(s) 0 04/14/10 All Original Report Issue. Work requested by Judy Bellah of Clear Focus Imaging 1 4/30/2010 Title, 1, 2 Added registered trademark symbol to series/model 1 4/30/2010 Title Corrected typo

Appendix A Thermocouple s

Absorber Plate Thermocouple Layout 4 BL 8 9 10 11 3 12 13 14 15 7 BO 2 5 BM 16 17 18 19 1 20 21 22 23 6 BN